Loading...
Report (44) Sel,c\d,Vtit • TSE Submittal c-r7201/ED Prepared For: Date:May 7, 2019 ,1\ �, y Protemp a Attn: Jeff Guyer. Job Name: OFf t CE lmmunolugy Trane U.S. Inc. is pleased to provide the enclosed submittal for your review',and approval. Product Summary Qty Product 3 Packaged Rooftop, Cooling/Heating Units The attached information describes the equipment we propose to furnish for this protect,and is submitted for your approval. Product performanee and submittal data is valid for a period of 6 months from the date of submittal generation. If six months or more has elapsed between submittal generation and equipment release,the product Kyle Wolf-Trane U.S. Inc performance and submittal data will need to be verified. It is the Phone: (503) 620-8031 customer's responsibility to obtain such verification. Cell: (503) 828-6788 Kyle.Wolf@Trane.com SUBMITTAL NOTES: 1) Adapter curbs not required to fit on existing downflow curbing. Please confirm in field, 2) Original factory performance configurations not available. Please confirm',performance requirements. 3) Please confirm voltages&accessories at the time of order, J.•IJOBS1124176874131Immunolugy Submittal-01.doc Table Of Contents ProductSummary........ ......... ........................... .... Packaged Rooftop, Cooling/Heating Units (Items Al -A3) Tag Data 3 • Product Data............... Performance Data....... ,..,.. 3 3 Mechanical Specifications 6 Unit Dimensions Fan Curve Weight, Clearance&Rigging Diagram......................... ' 16 19 Accessory...... , Immunolugy Tag Data-Packaged Rooftop, Cooling/Heating Units(Qty:3) y 7,2019 Item Tag(s) Qty Description Model Number Al RTU-2 1 40 Ton Packaged Commercial Rooftop YCD480BEH A2 RTU-3 1 35 Ton Packaged Commercial Rooftop YCD420BEH A3 RTU-1 1 30 Ton Packaged Commercial Rooftop YCD360BEH Product Data-Packaged Rooftop, Cooling/Heating Units All Units DX Cooling, natural gas heat Downflow supply and upflow return 208 Volt 60 Hertz 3 Phase High gas heat capacity 100% Power exhaust 2" MERV 8 High efficiency, throwaway filters 0-100% Economizer, dry bulb control with low leak OA damper VAV(DTC)with supply VFD w/bypass Thru-the-base electrical provision Trane communication interface Hinged service access doors Standard efficiency unit Item: Al Qty: 1 Tag(s): RTU-2 40 ton 60 Hertz 15 hp supply motor Item: A2 Qty: 1 Tag(s): RTU-3 35 ton 60 Hertz 15 hp supply motor Item:A3 Qty: 1 Tag(s): RTU-1 30 ton 60 Hertz 10 hp supply motor Performance Data - Packaged Rooftop, Cooling/Heating Units Tags RTU-2 RTU-3 RTU-1 Supply airflow(cfm 17600 14000 13000 Elevation (ft) 0.00 0.00 0.00 Cooling entering DB (F) 80.00 80.00 80.00 Cooling entering WB (F) 67.00 67.00 67.00 Ent air relative humidity(%) 51.08 51.08 51.08 Ambient DB (F) 95.00 95.00 95.00 Cooling leaving unit DB(F) 62.51 61.23 62.34 Cooling leaving unit WB (F) 59.27 58.70 59.26 Cooling leaving coil DB(F) 59.73 58.80 60.12 Cooling leaving coil WB (F) 58.22 57.78 58.43 Gross total capacity(MBh) 483.01 407.06 352.58 Gross sensible capacity(MBh) 384.50 324.80 282.13 Gross latenPca capacity(MBh) ,439.09 -373.75 324 5 P 98.51 82.26 70, Net total capacity(MBh) 97 Net sensible capacity(MBh) 340.58 291.49 254.52 Net sensible heat ratio(%) 77.56 77.99 78,32 Input htg capacity(MBh) 800.00 600.00 600.00 Output htg capacity(MBh) 640.00 480.00 480.00 Heating EAT (F) 70.00 70.00 70.00 Heating LAT(F) 104.00 102.00 104,50 Heating delta T(F) 34.00 32.00 34.50 ESP(in H2O) 1.250 1.250 1.250 Total static pressure (in H2O) 2.456 2,385 2.140 FLD=Furnished by Trane U.S. Inc./Installed by Equipment Submittal Page 3 of 23 Others " " Irnn"wplusx � Ta�s ^ � May�zmn _ _ RTU-2 RTU-3 RTU-1 Actual Supply Motor BF-IP(hp) 14.046 11.451 ~ 0426 Supply Motor Power(kW)(rpm) 663 �- 709 Indoor motor power(N�> 12.87 976 8.09 _ Ou�uurmu�rpower�VV> '4.O8 3. ] 3.37 Compressor power(kW) 33.17 27.78 '�54 ` System power(kW) 50.72 -40.77 3599 - EER��AHR| (EER) 0.3 10.3 1-~� 3 |EER��AHF0 (EER) 11.8 `�� 12.61��O K8inhnumc�ouhampu�ty(/0 -238'57 --- - �1A210 172.33 Maximum overcurrenprotection (A) 300.00 2250020000 Minimum disconnect switch size (A) 247.00 20400 183DO Compressor RLA(A) 50.50 506U . � 50.50Compm (A)000r2RLA83.90O � 58�uU 50.50 uomp�moor3RLA�V .O.8O - O.UO 080 Supply fan FLA(A) 42.40 42.4U ^~50 Condenser fan FLA(A) '7.OO 7�08 � 7O0 Condenserfancount4.00 3.00 3@0 (Each) ' ` Exhau/�tonFLA�A) 54O - ' ~ Exhaust fan count(Each) 2.00 4.10 4�1O 2.00 2�O Boo�oho�orFLA�U 0.00 0.00 O' U ' Crankcase he�orFLA(/) 0'00 VUO " 'Unit est opemhngweight(|b) 555.0 5225.0' O��5134.0 Fan m��hs�(M8h) 43.92 33.31 Discharge duct- 63 Hz(dB) 00 �~'"' 87 87� Discharge125Hz(dB> 93 » - 87 86 Discharge duct-250 Hz(dB) 85 8484 ,Discharge.Dioohargoduct' 5O0Hz(dB) 84 86 - 86 'Discharge duct 1 kHz(dB) 77 80 78| D�ohargad��-:�kHz(dB> 76 - ^ 76 75 Discharge duct-4 ��z(�B) 70 72 71 Discharge da�'8kHz(dB) 66 a8 66 Outdoor-03Hz(dB) 104 10O -108 Outdoor- 125 Hz(dB) 97 96 96 Outdoor'25OHz(dB) 96 97 97 Outdoor-500 Hz(dB) 97 96 96 Outdoor- 1 kHz(dB) - 95 93 -03 Outdoor'2kHz(dB) 93 89 89' Outdoor-4 kHz(dB) 88 90 90 Ou�oor'8kHz(d8) 79 ` ' 83 83 ��mdu��k��hau�'O3HzNB) 94 94 94 Return duct 94 � 93 Return ducm/low exhaus -25OHz(dB) 87 84 84 Return duct w/low exhaust'5OUHz(dB) 85 84 ` O4 | ` ^ Return duct*y/ovv exhaust- 1 kHz(dB) ' 86 85 85 Rotumdu/�m/low exhau�� 2 kHz(dB) ' 85 ' 84 84 Return duct m/low exhaust'4kHz(d8) 84 84 84 _ Return duct W/low exhaust 8 kHz(dB) 82 81 81 Return duct m/med. exhaust'03Hz(dB) 93 92 92 Return duct m/med. exhaust' 125Hz(dB) 93 91 81 I Return duct wymed. exhaust'25OHz(dB) 88 8O 88 Returndu��w� exhaust 500Hz(dB) 86 85 med. - 85 Return duct wI med. exhaust- I kHz(dB) 86 86 86 Return duct wI med. exhaust 2 kHz(dB) 85 86 86 Return duct w/med. exhaust-4kHz(dB) 85 85 85 Return duct WI med. exhaust 8 kHz(dB) 85 84 84 Ro�mdu��w/high exhu�g'83Hz(dB) 91 '80 89 FLD=Furnished by Trane U.S.Inc./Instalfed by Equipment Otherspage*pfzo r • _Immunolugy Tags Mav 7— 2019 RTU-2 RTU-3 RTU-1 Return duct w/high exhaust- 125 Hz(dBl 91 -88 88 _Return duct w/high exhaust-250 Hz(dB) 89 87 87 Return duct w/high exhaust-500 Hz(dB) 86 85 85 -Return duct w/high exhaust- 1 kHz(dB) 86 86 86 Return duct w/high exhaust-2 kHz(dB) 87 87 87 _Return duct w/high exhaust 4 kHz(dB) 86 86 86 Return duct w/high exhaust-8 kHz(dB) 86 85 85 .HFCF-410A refrigerant charge-circuit 1 (Ib) ,19.4 33.3 29,3 HFCF-410A refrigerant charge-circuit 2(Ib) 37.0 EDB in HGRH (F) 73.00 73.00 73.00 EWB in HGRH (F) 64.00 64.00 64.00 Ambient in HGRH (F) 75.00 75.00 75.00 Reheat setpoint (F) 70.00 70.00 70.00 FLD=Famished by Trane U.S.Inc./Installed by Equipment Submittal Others Page 5 of 23 Y Immunolugy May 7, Mechanical Specifications-Packaged Rooftop, Cooling/Heating Units las Item: Al -A3 Qty: 3 Tag(s): RTU-2, RTU-3, RTU-1 General R-410A The units shall be downfiow, horizontal, or mixed airflow. The operating range shall be between 115°F and 0°F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with AHRI testing procedures.All units shall be factory assembled,internally wired, fully charged with R-410A refrigerant and 100% run tested to check cooling operation, fan and blower rotation and control sequence before leaving the factory. Wiring internal to the unit shall be numbered for simplified identification. Units shall be cULus listed. Compressors R410A The 3-D Scroll shall provide a completely enclosed compressor chamber with optimized scroll profiles which leads to increased efficiency. The 3-D Scroll shall include a direct-drive, 3600 rpm, suction gas cooled hermetic motor. The compressor shall include a centrifugal oil pump, scroll tips seals, internal heat shield that lowers the heat transfer from discharge and suction gas, oil level sight glass and oil charge valve. Some compressor models shall also provide a dip tube that allows for oil draining, in addition to a low leakage internal discharge check valve to help prevent refrigerant migration. Each compressor shall have a crankcase heater installed, properly sized to minimize the amount of liquid refrigerant present in the oil sump during off cycles. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Cabinet surface shall be tested 672 hours in salt spray in compliance with ASTM B117. All components shall be mounted in a weather resistant steel cabinet with a painted exterior.Where top cover seams exist, they shall be double hemmed and gasket sealed to prevent water leakage. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have handles and shall be removable while providing a water and air tight seal.Control box access shall be hinged.The indoor air section shall be completely insulated with fire resistant, permanent, odorless, foil faced glass fiber material. The base of the unit shall have provisions for crane lifting. Hinged Service Access Filter access panel and supply fan access panel shall be hinged for ease of unit service. Phase and Voltage Monitor Standard on all Voyager Commercial units. Shall protects 3-phase equipment from phase loss, phase reversal, and low voltage.Any fault condition shall send the unit into an auto stop condition.cULus approved. Refrigerant Circuits Each refrigerant circuit shall have independent thermostatic expansion devices,service pressure ports and refrigerant line filter driers factory-installed as standard.An area shall be provided for replacement suction line driers. Outdoor Fans The outdoor fan shall be direct-drive statically and dynamically balanced,draw through in the vertical discharge position. The fan motors shall be permanently lubricated and have built-in thermal overload protection. Evaporator and Condenser Coils- R410A Condenser coils shall have all Aluminum Microchannel coils. Evaporator coils shall be internally finned Copper tubes mechanically bonded to high performance Aluminum plate fins.All coils shall be leak tested at the factory to ensure pressure integrity.The evaporator coil is pressure tested to 450 psig and the condenser coil at 650 psig.All dual circuit evaporator coils shall be of intermingled configuration. Sloped condensate drain pans are standard. High/Low 2 Stage Gas Heat The heating section shall have a drum and tube heat exchanger(s)design with primary and secondary surfaces of corrosion resistant aluminized steel or optional stainless steel.A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system. In order to provide reliable operation, a regulated gas valve shall be used that requires blower operation to initiate gas flow. On an initial call for heat, the combustion blower shall purge the heat exchanger(s)45 seconds before ignition.After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat, Two stage gas heat units shall be suitable for use with natural gas or propane(field installed kit). Gas heat units comply with California requirements for low NOx emissions. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Others Page 6 of 23 • Immunology May 7.2019 Indoor Fan, 60 Hz Supply Motor Unit will have belt driven,forward curve, centrifugal fans with fixed motor sheaves. The supply fan motors will be circuit breaker protected. All 60 Hz supply fan motors meet the Energy Independence and Security Act of 2009(EISA). Bypass control Provides full nominal airflow in the event of drive failure. Variable Frequency Drive Unit shall include factory-installed and tested variable frequency drive[s](VFD)to provide motor speed modulation. The VFD shall receive a 0-10VDC speed signal from the unit controller. The drive will respond to the signal by accelerating or decelerating to maintain the controlling set point(duct static, space pressure, etc). VFD shall also include the following features: 1. Designed, constructed, and tested in accordance with NEMA ICS, NFPA, and IEC standards and housed in a plastic IP20 enclosure. 2. DC link reactors on both the positive and negative rails of the DC bus equal to 3% impedance to minimize power line harmonics. 3. Full rated output current continuously- 110% of rated current for 60 seconds and 160% of rated current for up to 0.5 second while starting. 4. Isolation between the Drive's power circuitry and control circuitry to ensure operator safety and to protect connected electronic control equipment from damage caused by voltage spikes, current surges, and ground loop currents. 5. Audible noise reduction through automatic adjustment of the carrier frequency and frequency avoidance. 6. Rated at 40C with a standard operating range of-10 to 50C (14 to 124F)ambient temperatures and 0 to 95% relative humidity 7. Self-diagnostics and motor protections such as: cULus listed overload, phase loss, and internal thermal overload. 8. Off/Stop and Auto/Start selector switches to start and stop the AC Drive and determine the speed reference. a. On units with bypass, an AC Drive/Off/Bypass hand selector switch shall be provided in the unit control box b. In DRIVE mode speed reference shall be provided by a 0-10 VDC analog input 9. A keypad interface which shall be programmable by language and feature multiple lines for easy reading 10. Controlled and/or accessible points such as AC Drive Start/Stop, speed reference, and fault diagnostics. 11. Meter points such as motor power in HP, motor power in kW, motor kW-hr, motor current,motor voltage,hours run, DC link voltage, thermal load on motor, Thermal load on AC Drive and Heatsink temperature. 12. Troubleshooting features such as: a. AC Drive memory storage of the last 10 faults and related operational data b. Four simultaneous displays: frequency or speed, run time, output amps and output power c. Keypad which shall display: Reference Signal Value,Output Frequency in Hz or percent,Output Amps, Motor HP, Motor kW, kW 13. Coated circuit boards for protection against corrosive environments 14. Field readable BACnet points to allow for communication of stauts, setpoints and diagnostics to the BAS. 100% Power Exhaust Fan Power exhaust shall be available on all units and shall be factory installed. It shall assist the barometric relief damper in maintaining building pressurization. FLU=Furnished by Trane U.S.Inc.I Installed by Equipment Submittal Others Page 7 of 23 • tmmunotugy Mav 7,2019 2"High Efficiency Filters -MERV 8 2"High Efficiency MERV 8 filters will be standard. Economizer with Ultra Low Leak Dampers and Dry Bulb Control An economizer will be factory installed. The assembly includes: 0-100 percent fully modulating low leak dampers, minimum position setting, preset linkage, wiring harness and dry bulb control. Controls Unit shall be completely factory wired with necessary controls and terminal block for power wiring. Units shall provide an external location for mounting fused disconnect device_ ReliaTel controls shall be provided for all 24 volt control functions. The resident control algorithms shall make all heating, cooling and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures.The control algorithm maintains accurate temperature control, minimizes drift from set point and provides better building comfort. ReliaTel controls shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection. Unit Interrupt Rating (Standard Short Circuit Current Rating-SCCR) A 5,000 Amp rating shall be applied to the unit enclosure using a non-fused circuit breaker for disconnect switch purposes. Fan motors,compressors, and electric heat circuits shall be provided with protective devices that will provide the unit rated level of fault protection.The unit shall be marked with approved cULus markings and will adhere to cULus regulations. Through-The-Base Electrical Provision An electrical service entrance shall be provided which allows access to route all high and low voltage electrical wiring inside the curb, through the bottom of the outdoor section of the unit and into the control box area. Trane Communication Interface(TCI) Shall be provided to interface with the Trane Integrated Comfort System and shall be available field or factory-installed. The TCI shall allow control and monitoring of the rooftop unit via a twowire communication link. Certified AHRI Performance Packaged Rooftop units cooling, heating capacities and efficiencies are rated within the scope of the Air-Conditioning, Heating & Refrigeration Institute(AHRI) Certification Program and display the AHRI Certified®mark as a visual confirmation of conformance to the certification sections of AHRI Standard 340-360(I-P)and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial Warm Air Furnaces.The applications in this catalog specifically excluded from the AHRI certification program are: -Ventilation modes -Heat Recovery PLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Others Page 8 of 23 immunoiugy Ma Unit Dimensions-Packaged Rooftop,Cooling/Heating Units ?"2019 Item: Al Qty: 1 Tag(s): RTU-2 ./' letir NOTES: / 1.SEE ROOFCURB DRAWING FOR DETAILS J ON FIELD DUCT FITUP ANDCONNECTIONS '`� 2.SEE DETAIL HOOD DRAWING FOR HORIZONTAL/ ti' , DOWNFLOW UNITS FOR ADDITIONAL DIMENSION ''"` AND LOCATION: 3.THRU-THE-BASE ELECTRICAL IS NOT STANDARD :32 Sir ON ALL UNITS. SEE NOTE 2 M1 .. .: 3 ti4 • :1/477'''' r:::r''''''''''',,,‘'' '`. •:',499116' 11‘ ` ;... 7,,,,,,t,,,,it:::::::;k5,--,:'*'i!;1, 77« 5 5,"96" \,� 93 20 �1' 1 • PVC HIPC ....._�. / ''k..;, 232 318" GAS INLET ..s� ,,... ) / ., �r 46 15`]6-" ,. �•-. eUSTOMER. . ,4 90 P16- CONNECT€ON JOINT-` '' ` 4 �T .f' 711'0 311.1&« ,." —539/16"- -. ;',,,,r 54 I7$" m,.i I 7:1,'6" __. .... ' 1 I f I @ I ,, -,„:jr.....-,1/4,-:.4i ,, „f.....„,.6._ , SEE NOTE 2— t 9 € I I 1 1 , tteliDiVi I I 1 € I _ 1 7513/16" { RFT.-(N I I 7P`5l16" SUPPLY I 1 I t I 1 I I ' € I I € if ' /y` I I 1 I PLAN VIEW DOWNFLOW SUPPLY AND UPFLOW RETURN CONFIGURATION DIMENSIONAL DRAWING FLD=Furnished by Trane U.S.Inc.I Installed by Equipment Submittal Others Page 9 of 23 1 i } ImmunotugyMaY 7,2019 Unit Dimensions-Packaged Rooftop, Cooling/Heating Units Item:Al Qty: 1 Tag(s): RTU-2 • I I I II I t I 1 t t 1 t t 11 1 1 \ I \ / 1 I 1 1 \ i \ i I I I 1 7. — — — _ act1/W i I I I./ I/ I E I d I I1 I ( \. / \ / I 1 I ' \ / \ / I 1 I I N-------- 3 s'a L__ _� I ./ _ i e \ j 2 516.. I CONNECTION / € —THREE PLACES (THRU-BASE- 7 jj 1/2"NPS ELECTRICAL)—/ (.... CONNECTION (THRU-BASE- ELECTRICAL) I"- .'----- - 216 9/16 ........_ ...._...,....._.._ ....: ,: 2 518` NOTES: 1 THRU-THE`.-BASE ELECTRICAL IS NOT STANDARD ON ALL UNITS. 2..VERIFY ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION, THRU-THE-BASE ELECTRICAL PROVISION PLAN VIEW ._.._.- FLO=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 10 of 23 Others tmmurtalugy Unit Dimensions-Packaged Rooftop, Cooling I Heating Units May 7,2019 Item:Al Qty: 1 Tag(s): RTU-2 • • • ELECTRICAL/GENERAL DATA UNIT -� Model(Tonnage) YCD480(40..0) Operating voltage range: 187-229 Primary voltage: 208 Hertz: 60 Phase: 3 EER/IEER: 10.3 EER/11.8 EER HEATING-PERFORMANCE COMPRESSOR• Heat Highber 2 Heating Input(Btulh): 800,000 Tons13/20 First Stage(Btu/h): 600,000 Compressor Rated Coad Amps 50.5/83.9 Heating Output(Blu/h): 648,000 Lod<ed Rotor Amps" 315/485 • First Stage(Btu/h): 486,000 •• No Burners: 2 No.Stages/Turn Down Rate: 2 ELECTRIC HEATER Gas Supply Pressure(in w.0) Electric Heater kw N/A Natural or LP: 2.5/14,0 Electric Heater Full Load Amps NIA Gas Connection Pipe Size: 1" • • INDOOR MOTOR SUPPLY FAN OUTDOOR MOTOR Horsepower 15.0 Number 4 Motor speed(rpm) 1,760 Horsepower 1.1 Indoor motor lull load amps 40.7 Phase1 Outdoor motor full load amps 7,0 EXHAUST MOTOR FILTERS (7) Number 2 Horsepower 1.5 Type • Throwaway Phase 3 Furnished Yes Exhaust motor full bad amps 5.4 Number 17 Recommended size 16"x20"x2" REFRIGERANT TYPE (6) Type R-410A Factory Charge(Circuit#1) 194 lb Factory Charge(Clrcult#2) 37.0 lb • Cooling MCA=(1.25 x Load 1)+Load 2+Load 4 • • Cooling MOP=(2.25 x Load 1)+Load 2+Load 4 _ Notes: 1.LOAD 1=Current of the largest motor(Compressor or Fan Motor);LOAD 2=Sum of the currents of all remaining rotors LOAD 3=FLA(Full Load Amps)of the electric heater;LOAD 4=Any other load rated at 1 amp or more. 2.For Electric Heat MCA,MOP,RDE values,calculate for both cooling and heating modes. 3..If selected Max Over Cur is less than the Min Cir Amp,then select the lowest maximum fuse size which is equal to or larger than the Min Cir Amp,provided tho selected fuse size does not exceed 800 amps. 4.The use of Liquid Propane(LP)requires unit modification,Contact a Trane salesman for Information. • 5.Compressor KW at AHRI rating conditions of 80/67-95 6.Refrigerant charge is an approx.value.For a more precise value,see unit nameplate and service instructions. 7.Filter dimension are actual.Norminal filter size 16"x20" FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 11 of 23 Others x 1 immunology Unit Dimensions-Packaged Rooftop, Cooling/Heating Units May 7,219 item: A2, A3 Qty: 2 Tag(s): RTU-3, RTU-1 -,' kms -' NOTES: 1 SEE ROOFCURB DRAWING FOR DETAILS '' '^ ON FIELD DUCT FITUP AND CONNECTIONS ''� 1f 2.SEE DETAIL HOOD DRAWING FOR HORIZONTAL/ DOWNFLOW UNITS FOR ADDITIONAL DIMENSION 2681y43" AND LOCATION. 3.THRU-THE-BASE ELECTRICAL IS NOT STANDARD \ ON ALL UNITS.. h ' SEE NOTE 2-•-.,, "">� : � 31;4, r. � i I ^, i 7071E ,44 is• h``•..I '"s. _ -�s. 63 i:06- x PVCP6'E._._t 48' ' E�`"s,t ., . i / K' i GAS INLET 207112" i 4,11 ,`'40 3d1$" `,, / ,.'' i M CUSTOMER 7. i ,!" w' " ✓'' CONNECTION POINT—' , A1'" '"'✓ ti,, -616/16" 96141 ". � , 71/'96" = ' � ...__,.,.--23 4/2" _ a-_� a 7",18" • SEE NOTE 2 I I i �. 7513/16" f RETURN 7015(16" SUPPLY 1 1 I yI I I 1 i 1 I r ct . : v., — i I r xI 1 .O. ._......�: _s ' PLAN VIEW DOWNFLOW SUPPLY AND UPFLOW RETURN CONFIGURATION DIMENSIONAL DRAWING FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Others Page 12 of 23 i 1 k lmmunolugy Ma 7,2019 Unit Dimensions-Packaged Rooftop,Cooling/Heating Units Item:A2, A3 Qty: 2 Tag(s): RTU-3, RTU-1 r----1 r I 1 o 1 1 I � I 1 ) s. 1 / I I ES intr I I / I ( .\\\ 1 I 1 I I l I I I II I I v ✓ I, I �� 33/4- I I L_--„_--__---__ — l I L J ' ti 25/9' '0 Y`'- THREE PLACES 1/2 NPS 2 1/2”NPS CONNECTION I (THRU-BASE-ELECTRICAL) CONNECTION(THRU-BASE- � ... ELECTRICAL) ''-- 1---__— ..._.. ........: •%111/16° ..:....__ ,,- 2 5,31 NOTES: 1.THRU-THE-BASE ELECTRICAL IS NOT STANDARD ON ALL UNITS. 2.VERIFY ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION_ 'Aida* Allit THRU-THE-BASE ELECTRICAL PROVISION PLAN VIEW PLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 13 of 23 Others 1 • ImmunOlu9m Unit Dimensions-Packaged Rooftop,Cooling I Heating Units May 7,2019 Item: A2 Qty: 1 Tag(s):RTU-3 ELECTRICAL/GENERAL DATA • UNIT Model(Tonnage) YCD420(35:0) Operating voltage range: 187-229 Primary voltage; 208 Hertz: 60 Phase: 3 EER/IEER: 10.3 EER/12.6 EER HEA'T'ING*PERFORMANCE COMPRESSOR Heat: High Heating Input(Btu/hg Number Tons ns13 First Stage(Btu/h)r 426,000 '; 13.0/15.0 Compressor Rated L Heating Output(Bluth): 486,000 Lead Amps 50.5/56.0 First Stage(Btu/h): 344,500 Locked Rotor Amps 315A/351.0 No Burners: 2 No Stages/Tum Down Rate: 1 ELECTRIC HEATER Gas Supply Pressure(in w.c.) Electric Heater kw i N/A Natural or LP: 2.5/14.0 Electric Heater Full Load Amps N/A Gas Connection Pipe Size: 1" INDOOR MOTOR SUPPLY FAN OUTDOOR MOTOR Horsepower 15.0 Number Motor speed(rpm) 1,760 ! 3 Indoor motor full load amps 40.7 Horsepower 1.1 Phase 1 Outdoor motor full load amps 7.0 EXHAUST MOTOR FILTERS (7) Number Horsepower 2 0.0 Type Throwaway Phase 3 Furnished Yes Exhaust motor full load amps 4.1 Number 18 Recommended size 16"x20"x2" REFRIGERANT TYPE (s) Type R-410A Factory Charge(Circuit#1) 33.3 lb Factory Charge(Circuit#2) Not Available Cooling MCA=(1.25 x Load 1)+Load 2+Load 4 Cooling MOP=(2.25 x Load 1)+Load 2+Load 4 Notes: 1.LOAD 1.Current of the largest motor(Compressor or Fan Motor):LOAD 2=Sum of the currents of all remaining motors LOAD 3-I"LA(Futi LeadArnps)of hie electric heater;LOAD 4.Any other load rated at 1 amp or more. 2.For Floors Heat MCA MOPROE vaiu<xs Oalr„titate for both cooling and hearing modes. 3.If Wanton Max Duos Cur is less hen the Min Cls Amp,then select the lowest maximum fuse size which is equal tom larger than the fin C,r Amp,prcwi7ed the seloctet1 fust size does not exceed 800 amps. -4 The use of Liquid Propane(LP)requires unit modification.Contact a Trane salesman for information, 5.Compressor KW at AHRI rating conditions of 80/87-95 6.Refrigerant charge is an approx.value.For a more precise value,see unit nameplate and service Instructions. 7.Filter dimension are actual.Normlnal filter sea l6"x20" FLD=Furnished by Trane U.S inc.llrtstalled by Equipment Submittal Others Page 14 of 23 Immunes€ugy Unit Dimensions-Packaged Rooftop,Cooling/Heating Units May 7,>201g Item:A3 Qty: 1 Tag(s): RTU-1 ELECTRICAL/GENERAL DATA 1 • UNIT ®.._ Model(Tonnage) YCD360(30.0) Operating voltage range: 187-229 Primary voltage: 208 Hertz: 60 Phase: 3 EER/IEER: 10.3 EER/12.0 EER • HEATING-PERFORMANCE COMPRESSOR Heat: High Number Heating Input(Btulh): 600,000 1 First Stage(Btu/h): 425,000 Tons - 103 .51 Heating Output(Btu/h): 488,000 Compressor Rated Wad Amps 50.51550.5 0.5 First Stage(Btu/h): 344,500 Locked Rotor Amps 315.0/315:0 No Burners: 2 No,Stages/Tum Down Rate: 2 ELECTRIC HEATER Gas Supply Pressure(in w.c.) Electric Heater kw N/A Natural or LP: 2.5/14.0 Electric Heater Full Load Amps N/A ( Gas Connection Pipe Size: 1" r I INDOOR MOTOR SUPPLY FAN OUTDOOR MOTOR Horsepower 10.0 Number 1 Motor speed(rpm) 1.760 3 Indoor motor full load amps 29.0 Horsepower 1.1 Phase 1 Outdoor motor full load amps 7.0 EXHAUST MOTOR FILTERS (7) ! Number 2 Type Throwawa Horsepower 1,0 Furnished Yes y Phase 3 Number 16 Exhaust motor full load amps 4,1 Recommended size 165(20.'02" # REFRIGERANT TYPE (6) Type R-410A Factory Charge(Circuit#1) 29.3 lb Factory Charge(Circuit#2) Not Available • • Cooling MCA=(125 x Load 1)I Load 2+Load 4 Cooling MOP=(2.25 x Load 1)+Load 2+Load 4 9 Notes: 1.LOAD 1=Current of the largest motor(Compressor or Fan Motor);LOAD 2=Sum of the currents of at remaining inrrlor9 LOAD 3=FLA(Full Load Amps)of the electric heater,LOAD 4=Any other load rated at 1 amp or more. 2,For Electric Heat MCA,MOP,RDE values,calculate for both cooling and heating modes. 3.If selected Max Over Cur is less than the Min Cir Amp,then select the lowest maximum fuse size which is equal to or larger than the Min Cir Amp,provided the selected luse size does not exceed 800 amps, 4.The use of Liquid Propane(LP)requires unit modification.Contact a Trane salesmen for information. 5 Compressor KW at AHRI rating conditions of 80/67-95 6.Refrigerant charge Is an approx.value.For a more precise value,see unit nameplate and service instructions. 7.Filter dimension are actual.Norminal filter aloe 16"x20" FLD=Furnished by Trane U.S.1nc,1Installed by Equipment Submittal Page 15 of 23 Others , immunolugy May 7.2019 Fan Curve-Packaged Rooftop, Cooling/Heating Units Item: Al Qty: 1 Tag(s): RTU-2 V48 .,.. - 1 ulittakuom 50 --',._ 40airvkirme inattioln 1 qmaiNagoRessw2.46rEIM 1 1.- 41,0111)4MMO qtramfOletimseRwt.N.Talm 45 _ , . Ast4v0.3J4 atvem i, ampTermara- v‘or. I ic=> c--...1 -T- ---4.° . ic ..-.. Crl, , 5 A., I I e 1 C.> _ --• 0 :.,,, , 05 °- -...-- .1.. ..,..- 1,. L. — — , ,, — — 0 5:0:1 10M0 15:03 2:C00 MX 3D10 3510 AnioN(dni) 63± 173-t 211-t. 5a-it 1 14-k 24-k 414± 8 1,4-t Dsch3w cIrt: 99 93 85 84 77 70 ES atcta mat 104 97 93 97 93 “,, 79 Fttun cid loNetast: 94 94 87 E6 E6 66 64 62 iEtt.m dzt m3i.matast: 93 93 1,.; E6 ffi E5 ffi 85 REkm dct hcji adust: 91 91 ,It., 86 E6 87 ffi E6 , FLD=Furnished by Trane U.S.Inc /Installed by Equipment Submittal Page 16 of 23 Others , Irnmunalugy May 7„2019 Fan Curve-Packaged Rooftop,Cooling/Heating Units Item:A2 Qty: 1 Tag(s): RTU-3 1.42 1 1 1 tkettlait4:0"; 50 -t- 4 cUraiVrt(W itONDGill I Ctitritro!**Retate 235v1-20 . ...., 4.-4,91,544raik 45 : , , .• .•awitfseRwr 1,46ttgy I ' Altilkariatril 5/749 —4.0 35 Ckwilirtunqr q __ ... i I— ),71W '-, i e r....." , 30 = 25 ., ' ' st,w, co 1-1.0 W,AC f i _ , 4 0 510 1010 157) 2)2Q) 25S0:1 Airflow(cfril 63-t 123-t 23:Hz 52Q-t 1 kl-t 2 id-t 41ft 8 - .., ElscrErcj act: 87 87 84- EB 8) 76 72 a3 Oictxr sard 1(3 93 97 % 93 .1: 9) 83 Rstun act I:WE:411g: X. 93 84 84 83 84 84 81 bun d.ct rrEdnatast: T 91 E6 E6 88 66 65 84 Rstun cid hg.1 edast: :: a 87 85 66 87 83 E6 .,„,..s.„.. , ...,,,,,,,,a, .C.,, ,s,...,„,-,,• ",,V ;.-I'' 5., -....,,- FW=Furnished by Trane U.S.Inc.it Installed by Equipment Submittal Page 17 of 23 Others _ ........._ _ , lmill unolugy May 7,2019 Fan Curve-Packaged Rooftop, Cooling/Heating Units Item:A3 Qty: 1 Tag(s): RTU-1 • 45 • AthetWINcYft10 thw-�.0 rus�mt c) ,- s35 a X25 moi, -gip ,. X1.5 X1.0 05 m I P O 0 510 1= Sl 19330 DX MO Maw(chir- 63 k 1 3-tz 1 k* 21-17 4k- 8 � 87 % 84 E6 93 75 71 83 F�und.ttlaved-a 94 93 .. 84 ffi 84 81 81 ttund.d rrsciunetast: I M 91 86 E6 f3 85 86 84 Fttt.md,d lig,eda.st: I s .* 87 85 E6 El 85 86 FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 18 of 23 Others immuno[ugy Mdiv 7,2019 Weight,Clearance & Rigging Diagram - Packaged Rooftop, Cooling/Heating Units Item: Al Qty: 1 Tag(s): RTU-2 • .4\ // 1111%1SA'' ..NN,,,,,,. • ail 4 IA 1Ji 46" DI E 'F CLEARANCE NOTES: 1.HORIZONTAL AND DOWNFLOW UNITS, ALL SIZES: 2:-CONDENSER COIL IS LOCATED AT THE END AND SIDE OF THE UNIT. t 3 CLEARANCES ON MULTIPLE UNIT w INSTALLATIONS ARE DISTANCES BETWEEN UNITS, I'7 4.ECONO/EXHAUST END MULTIPLE UNITS144". C B .. ..�. A 5<CONDENSER COIL END/SIDE 192" TO 96" 48" 6 SERVICE SIDE ACCESS 96" y ESTIMATED OPERATING WEIGHT OPERATION WEIGHT: 5955.0 lb --- - - _......... CENTER OF GRAVITY OPTIONAL COMPONENTS EIIEMMINIIII=111N. POWER EXHAUST =155.p lb BARD.RELIEF VA E=ZZUI .. IIIIIIII CORNER LOADING PERCENTS ECONOMIZER 290.p1B I THR1.I.BASVELECTRICAL '643 lb DISC SWITCH , EM En B 1 C_..._ 0Milla MANUAL DAMPERS VPD '115.9 lb " Mal 17% 18% IF% 155! 16% ULTRA LOW LEAK EXH. ULTRA LOWLEAKECON 1111111 COIL HAIL.GUARD '`NIA MOD..HOT GAS REHEAT WA WEIGHT NOTES: 1.THE WEIGHT SHOWN REPRESENTS THE TYPICAL UNIT OPERATING WEIGHT FOR THE CONFIGURATION SELECTED. ESTIMATED AT +1-10%OF THE NAMEPLATE WEIGHT 2.THE ACTUAL WEIGHT IS STAMPED ON THE UNIT NAMEPLATE. FLO=Furnished by Trane U,S:Ind./Installed by Equipment Submittal Page 19 of 23 Others • ' v 3mmunoiugy fvtay 7,2019 , poki,s„, ,ii. Weight,Clearance& Rigging Diagram - Packaged Rooftop, Cooling/Heating Units )::,,.,'''''''''',‘i , 1 Item:A2 Qty: 1 Tag(s): RTU-3 • • �P 1---/".;,,,,,,,,,„,, -1-,:,,,-,:v‘, ----t.s,1/4 ,-,..7). 0110. , Pm �R 1 a i " "`�,� I 48" O E F CLEARANCE NOTES: 1.HORIZONTALAND DOWNFLOW UNITS, ALL SIZES. 2,CONDENSER COIL IS LOCATED AT THE END AND SIDE OF THE UNIT.' 3.CLEARANCES ON MULTIPLE UNIT a INSTALLATIONS ARE DISTANCES BETWEEN t UNITS. at. 4.ECONO/EXHAUST END MULTIPLE UNITS 144". ? C: - 13 A (I 5.CONDENSER COIL END/SIDE 192" . TE48" 6.SERVICE SIDE ACCESS 96" E L____ ___________________J ESTIMATED OPERATING WEIGHT OPExRATI6)N WEIGHT, 5225.0 W ... .. _ - CENTER OF GRAVITY OPTIONAL COMPONENTS K 42" Y 46' POWER EXHAUST ' . _... /.._.. I'1450 Ib BARD.RELIEF 'N£A. SERVICE VALVES NIA. CORNER.LOADING PERCENTS. .:ECONOMIZER. 1'2Bj_0 IPj_.., THRU-EASE ELECTRICAL "6.0.1b....... DISC.SWITCH NIA. 20% 20% '16°+s 17%' I441r, 19% tPLTRALOWLEAfGEXI-I: `.NIA ULTRA LOW SWITCH N/A VFD 'BS:OE1 l A B C 0 E F MANUAL DAMPERS NA GPI LOW LEAKECON 'N/A COIL HAIL GUARD NIA ....... MOD,HOT GAS REHEAT N/A .._ ...._. MEI WEIGHT NOTES: 1.THE WEIGHT SHOWN REPRESENTS THE TYPICAL UNIT OPERATING WEIGHT FOR THE CONFIGURATION SE.ECTFI) ESTIMATED AT +/-10%OF THE NAMEPLATE WEIGHT. 2.THE ACTUAL WEIGHT IS STAMPED ON THE UNIT NAMEPLATE FLO=Furnished by Trane U.S.Inc.I installed by Equipment Submittal Page 20 of 23 Others Immunalugy Y 7,2019 Weight,Clearance& Rigging Diagram-Packaged Rooftop, Cooling/Heating Units Item:A3 Qty: 1 Tag(s):RTU-1 14'i" ''''''' ,. - - l'- w '..NAA.•,: :7 1100 O It '`''s,� _ _ _ _ I "--Ll ri II iiI I �—_ Irs 48" 1 i 0 72" F 1 CLEARANCE NOTES: -4-. ; �� t 1-HORIZONTAL AND DOWNFLOW UNITS, ALL SIZES, ,` 2.CONDENSER COIL IS LOCATED AT THE - 1 END AND SIDE OF THE UNIT 3,CLEARANCES ON MULTIPLE UNIT --1 .2,6,,L'' ; ''"-' i INSTALLATIONS ARE DISTANCES BETWEEN I UNITS, X I 4 ECONO/EXHAUST END MULTIPLE -, I UNITS 144". t C i.. . 6 A 5..CONDENSER COIL ENDISIDE 192" TO 96" 49" I 6.SERVICE SIDE ACCESS 96' - ,Y ESTIMATED OPERATING WEIGHT OPERATION WEIGHT. 5134.0 lb - _ "— — CENTER OF:GRAVITY OPTIONAL COMPONENTS 1 X 143" 1 Y 194" POWER EXHAUST T165.6 lb BAIlc RELIEF NIA SERVICE VALVES NIA CORNER LOADING PERCENTS VCON+:3MIZER -..26i1.0It) ... THRID-BASE EI.ECTflicAL. to Io ' DISC.SWITCH 'PA - r t 1As. B C Q E F MAN{JAL OAM.'ERS -N I GFS WITH DISCON,SWITCH 'NIA I VFD X85 0 lb 21 �1G% '18% 17% 14' 15% ULTRA LOW LEAK EXH. 14.A ULTRA LOW LEAK ECON ! N/A V COIL HAM GUARO. N;A. _ R MOD.HOT GAS REHEAT N/A WEIGHT NOTES i _...... ___ 1 THE WEIGHT SHOWN REPRESENTS THE TYPICAL UNIT OPERATING WEIGHT FOR THE CONFIGURATION SELECTED, ESTIMATED AT +/-10%OF THE NAMEPLATE WEIGHT. 2.THE ACTUAL WEIGHT IS STAMPED ON THE UNIT NAMEPLATE. '.. FLD=Furnished by Trane U.S.Ina/installed by Equipment Submittal Page 21 of 23 Others Immunolugy May.7 Accessory-Packaged Rooftop,Cooling/Heating Units `2019 Item: Al -A3 Qty: 3 Tag(s): RTU-2, RTU-3,RTU-1 yi—'EN6OF UNIT' I POWER 14 "'^ . EXHAUSTI HOOD�---..,�� Why.'' 3 .,/ j I 3 i t SII ----57 s,4 FRESH AIR AND POWER EXHAUST HOODS FOR DOWNFLOW* RW UNIT DETAIL. FLD=Furnished by Trane U.S.Inc./Installed by Equipment Submittal Page 22 of 23 Others A ` Immunolugy May 7,2019 Accessory-Packaged Rooftop, Cooling/Heating Units Item: Al Qty: 1 Tag(s): RTU-2 f EXHAUST ,' < .....,,..„ ginHOOD � '`� , ,, ,,..„,,,, man an . ,4 ., `l / / may/ , , ,,, EXHAUST I"'--34 1t1G».—..,. - —4Q'€12°•-- / HOOD --- / // ,. j ' 13 SPIE'--` I.r' FRESH AIR HOOD-- TOP VIEW ISOMETRIC VIEW DIMENSIONAL DRAWING PARTIAL DRAWING 3217P"—« r i t..-23718"—t'q EXHAUST HOOD--N. Pr 1; 4 Ort" 12 t9e — t` f FRESH AIR HOOD ---1 BACK VIEW SIDE VIEW DIMENSIONAL DRAWING DIMENSIONAL DRAWING 40-50 TON FRESH AIR AND POWER EXHAUST HOODS HORIZONTAL OONF9GURATION DIMENSIONAL DRAWING FL13=Furnished by Trane U.S,Inc./installed by Equipment Submittal Page 23 of 23 Others