Report Fs) o\c\ oco u_ 5 SvJ tet) ct • RFCEIVED JUN -3 2019 CITY OF f IGPRD BUILDING DIVISION PROJECT: PAPE MATERIAL HANDLING 6955 SW SANDBERG TIGARD OR 97223 FIRE ALARM SYSTEM EQUIPMENT SPECIFICATIONS, PLANS, BATTERY CALCS FIRE ALARM CONTRACTOR: ACTION TECHNOLOGY SYSTEMS LLC 835 SE 17TH AVENUE PORTLAND OREGON 97214 (503) 231-1992 CCB#157630 FACE OP 1111 POTTER AFC-50 Features AFC-5 0 The Symbol of Protection Fire Alarm Control Panel ysEMs<F • 50 addresses available on this analog addressable system • Additional system capacity achieved via multi-point SLC modules P,o • 99 software zones a rHE�y • NFPA 72 Compliant Smoke Sensitivity Test Built-In ©bra i,'w°�'IIIAli r, • System Operates as Class A or Class B for SLC,P-Link and NACs �� � 11111111,114 iQFC-SO • 5 Amp Power Supply,Expandable to 310 amps ui II 11 • 2 NACS,Regulated,Rated at 3 Amps each,expandable to 188 11111111111 f 1"gh1'uli I'' II • 2 Input/output(I/O)Circuits for system flexibility rated at 1 Amp i111011 lil "lilN each l 11 t III l 1 III • Strobe Synchronization and System Wide Sync for Gentexe, , �Ii GN lYw ,,IM it p. AMSECO®,Cooper Wheelock®and System Sensor®strobes '1 '1 V�II Ivry r 0il1 1 • Dedicated Alarm,Supervisory and Trouble Relays II1 II ii° • 4,000 Event History Buffer 1 • Optional two line DACT with UD-1000 that can report General,Zone or Point Information I h 111111 • Built in IP Communicator • Ethernet Port for Programming and Network Connectivity • E-Mail System Status,Reports and Event Information NYC Fire Dept. • Product includes 5 year warranty. Certificate ofApproval }' 6256 l._ I LISTED 7165-0328:0509 S735 Description Technical Specifications The AFC-50 is an analog/addressable fire alarm system with a total system capacity of 50 addresses.Additional capacity on the system is achieved Dimensions 16"W x 17"H x 3 1/s"D using multi-point SLC modules.The control panel utilizes the exclusive 3.0 Amps @ 120 VAC 50/60 HZ Potter protocol that includes a complete line of sensors and modules. AC Mains 2.0 Amps @ 240 VAC 50/60 HZ Each SLC may be comprised of any combination of smoke sensor,heat detectors or modules and allows for a total of 50 ohms of impedance and Enclosure 16 gauge cold rolled steel with removable may use any wire compliant with the National Electrical Code(NEC). locked door with Lexan viewing window The AFC-50 has a 5 Amp power supply with two Notification Appliance Standby Current-130 mA Circuits(NACs)and two Input/Output(U0)circuits.The NACs are rated at Alarm Current-200 mA • 3 Amps each and the VOs are rated at 1 Amp each.Each output is regulated 5 Amps power for NACs,I/O,and P-Link • and power limited.In addition,each output is uniquely programmable and Battery 3 Amps per NAC,regulated • may be configured for steady signal, strobe synchronization, constant 1 Amp per I/O circuit,regulated • Battery Charger range 8-55 Ah power, door holder power, or releasing. The strobe synchronization • Battery Charger voltage 27.3 VDC includes Gentex,AMSECO, System Sensor and Cooper/Wheelock and • P-Link maximum current of 1 Amp with the exclusive Quadrasync each output may have a unique brand and all strobes will flash together. Temperature and 32°to 120°(0°C to 49°C)with a maximum Humidity Range humidity of 93%non-condensing. The NACs may be expanded using the PSN-1000 series intelligent power supplies.Each PSN-1000 adds another 10 Amps of power,2 additional input circuits and the AFC-50 will support up to 31 power supplies.The system will synchronize the strobes system wide.in addition,the PSN- 1000E has space to allow the installation of up to six expansion cards. The cards mount on a stacker bracket that allows access to all circuit connections. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830133-REV B • 01/18 PAGE 1 OF 4 IR 4111 ETIs Ilii POTTER AFC-50 0°0IIII® The Symbol of Protection Fire Alarm Control Panel SLC Loop Accessories The control panel may be connected with up to 50 addressable devices or modules in any combination.The SLC is not restricted by any special wire requirements and may be wired with any wire that complies with the NEC. SLC Loop Devices Device Description PAD100-PD Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot. PAD 100-PHD Combination Analog Photo Electric Smoke/Heat Detector—a smoke detector with a listed obscuration of 1.02 to 3.83 percent obscuration and a fixed temperature 135°Fahrenheit heat detector. PAD100-HD Analog Fixed(135d-185dF)or Rate-of-Rise Heat Detector(software selectable) PADI00-DUCTR Addressable Duct Smoke Detector with Form C Relay.Addressable Duct Smoke Detector with Form C relay rated at l0a @ 250/120VAC or 8amps at 30VDC. PAD100-DUCT Addressable Duct Smoke Detector. PAD 100-6B 6"round base that is mounted to an electrical box and wired for connection of one of the above sensors. PAD100-4B 4"round base that may be mounted to an electrical box and wired for connection to the above sensors. PAD100-IB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop. PAD100-RB Addressable Relay Base that contains one relay controlled by the SLC.Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125VAC. PAD100-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local,group and all call. PAD100-CD Addressable CO gas detector. PAD100-DD Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure. Modules Device Description PAD100-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure. PAD100-PSSA Single Action Addressable Pull Station. PAD 100-PSDA Dual Action Addressable Pull Station. PAD100-SIM Single Input Module is a standard contact module with an LED that mounts into a 4"square electrical box. PAD100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode. PAD 100-TRTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel.Each relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC.Also provides two contact inputs. PAD100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel. PAD 100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system. PAD100-IM Isolater Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop. PAD100-RM Relay Module that provides one form C relay controlled by the control panel.Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC. PAD100-LED Module provides a single addressable LED that is controlled by the control panel. PAD100-SM Speaker Module provides switching for two audio channels. PAD 100-LEDK Addressable LED and key switch that mounts in a single gang box. PAD100-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised.For use with the PAD100-DUCTR only. PAD100-OROI One Relay One Input Module provides one form C relay and one input.The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830133-REV B • 01/18 PAGE 2 OF 4 P POTTE][� AFC-5 0 The Symbol of Protection Fire Alarm Control Panel SLC Features RA-6075R—2 x 16 LCD annunciator with a key pad in a locked The Potter protocol is a digital protocol with a proven design for metal enclosure. reliability and noise immunity.The system does not require special RA-6500R(F)—4 x 40 LCD annunciator with a key pad in a locked cable or conductors for connection of the Signaling Line Circuit metal enclosure.Flush mount version available. as long as the cable is compliant with NFPA 70 and NFPA 72. LED-16(F)—16 LED annunciator with common indicators in a The system allows for Class A or Class B installations as well as locked metal enclosure.Flush mount version available. "T-Taps",with a max wiring distance of 10,000 Ft. PSN-1000(E)—10 amp,remote intelligent power supply with 6 NACs,2 I/0s and a P-Link repeater.This panel is listed in Sensor Features conjunction with the AFC-50 as releasing circuits. The sensors through the fire alarm control panel provide a real CA-6075—Class A convertor that converts the SLC,NACs and time status as to the condition of the system.The smoke detector P-Link connection sensitivity,heat detector temperature level and drift compensation UD-1000—UL listed,Dual line telephone alarm communicator are all programmable options.The system also allows for a day/night DRV-50—LED driver expander,used to connect up to 50 LEDs in a mode where the panel automatically adjusts the sensitivity depending graphic display on the time of day.To assist in the reduction of false alarms,the FCB-1000—Fire communication bridge,provides remote mounting smoke detectors also have a maintenance warning that sends a trouble of the Ethernet connection signal when a detector is dirty to the point that it can no longer maintain the programmed sensitivity. FIB-1000—Fiber interface module,used to extend P-Link to multi- mode fiber(2 required) User Interface RLY-5—Relay module,provides 5 form C relay contacts rated at 3.0 amps 24VDC/125AC The fire alarm control panel has a 2 x 16 LCD display to provide information to the system status.The keypad has navigation keys SPG-1000—Serial parallel gateway,allows for the connection to a to allow manipulation of the Menu on board the panel.The panel is serial or parallel printer shipped standard with the following LEDs: The FIB-1000,FCB-1000 and the SPG-1000 may be installed in the stacker bracket or ordered with the optional rack mount enclosure. • AC Power-Green MC-1000 Multi-Connect allows up to sixty-three AFC series panels • Alarm-Red to share a single reporting technology. • Earth Fault-Amber AE-2—Two card expansion cabinet • Supervisory-Amber AE-8—Eight card expansion cabinet • Silenced-Amber AE-14—Fourteen card expansion cabinet • Trouble-Amber Ethernet/I.P. Connection • Pre-Release-Amber The AFC-50 is shipped standard with an Ethernet connection. • Release-Red This connection is the programming port and may be connected to a building Wide Area Network(WAN)or Local Area Network The common buttons include a Silence,Reset,Acknowledge,and Drill.All of the buttons are accessible once the locked door is (LAN).Once connected to the Internet,the panel may be selectively programmed to e-mail alarm conditions,trouble conditions, opened. supervisory conditions,test,Event History and detector status.An e-mail may be sent to the panel and the panel will e-mail the event P-Link history,detector status,configuration file or server status to an The AFC-50 has a proprietary communication protocol that authorized E-mail account.In addition,reminders may be set to send communicates through a RS-485 connection to field devices.Up an e-mail for service,testing or other conditions. to 32 devices may be connected to a single P-Link connection.The In addition,the Ethernet connection is UL listed as an IP P-Link includes the communication terminals and regulated 24 VDC communicator.The IP communicator is listed to report to the UL connection for the field devices.The field devices may be any of the listed Sur-Gard III IP receiver.The IP communicator replaces the following: traditional less reliable alarm communicator transmitter that utilized PAD100-SLCE-Analog/Addressable loop expansion module telephone lines.The IP communicator is an active method of SLCE-127-Nohmi addressable loop expansion module for retrofit connection and communication to the monitoring station. applications. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830133-REV B • 01/18 PAGE 3 OF 4 11 POTTER AFC-50 The Symbol of Protection Fire Alarm Control Panel Dimensions 0 0 t TOP DEPTH=3.75" DOOR= 16.07 BACKBOX=15.77' DEPTH=3.84" 0 • • p0 • • 9 ( 0 0 ° ° 0 o o G m 1 LEFT SIDE RIGHT SIDE • BOTTOM OWG N593.1 Ordering Information Model Description Stock No. AFC-50 Fire Alarm Control Panel 3992752 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830133-REVB • 01/18 PAGE4OF4 . , PO 1 1 _6075 The Symbol of Protection LCD ANNUNCIATOR INSTALLATION 11 1 , I,L I �IIC qI II"IgE Iyq hlgl I,II 11 4ttju 1kl� l,gti11111 ,l lgtII: "IIIIw,llll11111 h �i tt Ir!Ys,-- 1aII qIl rq,fl � I, ,w dXal ' Features 1119,�au l Its N 1 I +,, Iu1.40 II IIII 11." 'q1�I1 111 N l uIIII IIIu 1 w IY,'^"1i 1, StandbyCurrent 20 mA ru IV it" V1 �wa IIIVIIErypN V"9 Ip III 1 1,1 ryu �1t (I0 1 uu% "JIl 11 1 M It - 1 X11, +1 Alarm Current 25 mA �gd1, « q �ull "q 111I1i111,gIi IIID Ili ''t 0 0 0 0 „ 1 '4,'144111„R1744` Operating Temperature 0°C-49°C(32 F-120 F) 10/0-93/o f,i1r rll �ll ptil 911111 1 I,III44441[ eta l 11911 �it) , IIII x a 11 1 r "I1111111111. )" +k u„1 @ 30°C(86°F)non-condensing I;" gull 1 HE �1i r( Ii119u�1 114','1t X71 humidity 91111 Iu Iu 1 Ih111111 j 1 131'01014111$11141141111111111II I1 iu" I 1 u Maximum Wire Length 6500 FT wl P IIr ' unl�I III 1 +Iltt " 11111IXI 1I � � O 1 u1u III 1 � I , ,,,111.1;,1111 Maximum Annunciators 31 In N91u1 1,11144,, 42;11 41h1:41041 NI tI .. 11,1 1n df„p15V,V0,9 11I111 a 11II1111H ��y�� Y In a 1 `�' Dimensions(WxHxD) 8”x 6-1/4"x 1-5/8"(Cabinet) -.lit/u9I111 IVN,II ME 111 uI "1 9 q ulurylll1II r 111 4 1al l Hl1I,I11�1 4I � y, 9II�„Iplluluulllnral n�111, � ,,111;,,,N,u Wire Gauge 14 AWG-22 AWG { 1 1"SII 1 1 11 ,` pn„IN„Iu11V1IR1111 1„„u 111111 II1,0,;---1.14,,,,I.,,,,,, 1 '111r , Display 2 lines x 16 characters .11 11�11Vi Now 11,1,11-mo- 111 s t --�w. u NV Ww 1„�umilu''rt pOTT'„''„x Product includes 5 year warranty 1,1y 111 41) tai.9;)LISTED S2930 7165-0328:0195 Description Installation The RA-6075 is a LCD remote annunciator for the PFC-6075 and The RA-6075 is connected to the PFC-6075 using a four wire RS-485 PFC-6030 addressable fire control panel.The RA-6075 communicates connection.The connection is power limited and supervised.Up to using a RS-485 connection to the main panel providing common thirty-one(31)RA-6075 LCD annunciators can be connected using indication of Alarms,Supervisory,Trouble and other system status and Class B or Class A wiring.Class A wiring requires an optional Class A control functions. Expander. The RA-6075 features a 32 character, 16x2 LCD display with LED's for Power,Alarm,Supervisory,Trouble,and Silenced conditions. pugill9lu'I',;11'14141- "111111 C II II a ”'I'11i,n' X11 ,„fir 1I,VIV111 Illy1111111111u11t..-mz 1u u1,.. 11,1111111 nuu1 I L11 1111181 10111 IIIIr,111P N1111I1,�,1I110111 � 1111 „i,„ It can be mounted on a single gang electrical box or a four square = electrical box.The annunciator is enclosed in a sheet metal enclosure Install in accordance with compatible fire alarm panel. and has a Potter lock securing the keypad. Figure 1:RA-6075 Class B Wiring Example Figure 2:RA-6075 Class A Wiring Example To the next annunciator CA-6075 NN ',; m O O R O Connection O m ,1'M a +P-LINAK -..B 1 IMINIC7IIPanel rr1 M + O O O O O a Remote + + �- '�- Panel . Connection © Annunciator Connection "• Remote P-LIN< BAnnunciator :LIi I U+ a a 'Loi1 O i NNN Remote O 41 O Annunciator \ O Annunciator Potter Electric Signal Company,LLC•St.Louis,MO•Cust Service:866-956-1211•Tech Support:866-240-1870•Canada:888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5406077-REV B-1 PAGE 1 OF 2 9/11 POTTE]CZ p) RA-6075 The Symbol of Protection LCD ANNUNCIATOR INSTALLATION Address Settings The RA-6075 address is set by dip switch SI located on the back of the RA-6075.The address must be set in the range of 1 to 31 to be recognized by the control panel. Figure 3:RA-6075 Class A(back panel view) 4 \ 3' \ 0 \ — 0 0 7 -;;;;6C;`- r 1 � / 0 4/ �rr \ I A Ew.-J 9 W® } El' / O 0/ Dip Switch Settings Refer to the table below for dip switch settings per Annunciator Address. Annunciator Dip Switch Settings Annunciator Dip Switch Settings Address SW-1 SW-2 SW-3 SW-4 SW-5 Address SW-1 SW-2 SW-3 SW-4 SW-5 1 On Off Off Off Off 17 On Off Off Off On 2 Off On Off Off Off 18 Off On Off Off On 3 On On Off Off Off 19 On On Off Off On 4 Off Off On Off Off 20 Off Off On Off On 5 On Off On Off Off 21 On Off On Off On 6 Off On On Off Off 22 Off On On Off On 7 On On On Off Off 23 On On On Off On 8 Off Off Off On Off 24 Off Off Off On On 9 On Off Off On Off 25 On Off Off On On 10 Off On Off On Off 26 Off On Off On On 11 On On Off On Off 27 On On Off On On 12 Off Off On On Off 28 Off Off On On On 13 On Off On On Off 29 On Off On On On 14 Off On On On Off 30 Off On On On On 15 On On On On Off 31 On On On On On 16 Off Off Off Off On PRINTED IN USA MFG.#5406077-REV B-1 PAGE 2 OF 2 9/11 . , P POTTER UD-1000 The Symbol of Protection Digital Alarm Communicator Features , _. „Ills y5E>,�a<F • Allows for communication to Monitoring Station 1 . -.w11 "'L '41 I1 :�4I;I<I '''�„ A . W T " 4! �, III • . • Communicates using SIA-DCS or Ademco Contact ID ProtocolsjvnI "-• i aL rHe�`¢ vviT • For use with 6000 series and P series Addressable Panels .-. ilk '11•' 411 x: A 4tl„� r • Status LEDs indicate operation of DACT card v g • Installs with ease behind main panel LCD display via User Interface II k •,,10•111114v„11,1/1„,,-iyllll lull ” ) P Y �1�� mIl t 3�°1„1 • INIt40,11- 11 �Il�lli� bracket : k, 1 1+ t IIII • r1 III 41 • Device address is set by dipswitches located on DACT card v � Il.VI 1 I 111 It,- �I 1 1 * 141-4,..7.,' 'NI ,r4 it1 1 ,,e,d1II„1 VIII I ITR. • Installation materials including 4 pin connector and screw are supplied ” , .v.v4711,11111R„,„,ril "Il��llill r1r111I1I IIIv:11411174,0/,' vv with DACT card M 1i jp V111 I1 l�il 11I1H1II1 . • UUKL Listed with Smoke Control 11 1 1 � :r� Nl„� I �lllll ( „`� ,III'. I i c w"1 1 „N 44 41 II n, 1 1I1 ililh 1V rw a •__ ••( "•.•__ u. Gr IlNk iT"41,1L } �a".1[[ 'te'. .a 4f/A 4) , APPROVED LISTED F- S735 7165-0328:0195 Description Technical Specifications The UD-1000 Digital Alarm Communicator Transmitter (DACT) Operating Voltage 22.0-24.0V provides for up to two (2) phone lines for communication to a monitoring station. The UD-1000 communicates using the SIA- Standby Current 16mA DCS or Ademco Contact ID protocols. When enabled, the DACT Alarm Current 23mA automatically monitors each phone line or voltage and has the Max UD-1000s per panel 1 ability to seize the line and connect with a remote receiver.Once the communication is complete,the DACT will hang up. Dimensions 4"W*6"H* 1-5/8"D The DACT is provided with an RJ-I I jack for each phone line and a Operating Tempuratures 0°C-49°C(32°F-120°F) RJ-11 to RJ-33 cord.In order for the DACT to work properly,it must 10%-93%@ 30°C(86°F) be installed on aplain old telephone service(POTS)line or equivalent Operating Humidity Range p q (non-condensing) deemed by the authority having jurisdiction. The DACT must be Mounting Options In FACP Behind keypad installed before any other equipment to ensure it can seize the phone line. Shipping Weight 0.47 lbs Phone lines are high voltage and should be run in a separate conduit from other circuits.The wire conductors connecting the DACT to the phone system should be 26 AWG or larger. Potter Electric Signal Company,LLC • St. Louis,MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com 8830048-REV B • 12/18 PAGE 1 OF 2 Pte ' U D-1000 The Symbol of Protection Digital Alarm Communicator , UD-1000 DACT Installation on UD-1000 DACT Installation on PFC-6030/6075R PFC-6800/6200 Fig 1 Fig 2 0 11111111V57.; it ► CI.g I E. � El a o ^ ill pl.a ,,0 ERZZ:"fe:7 SEE? . ' ='(=1 a D. a =Ds l. i_. Irl 1 Lip_E ct '') lla I IILT .— .— \ i t c.' �' �,�"'FI�1=L�?..su.s::ie�.- �:�-.. AI 9: I�\�,,�a � .: I c – nI,I � � - Tut �,� ra:71.....:,_rimini__________________" �Screw UD-1000 DARI_� ❑ RIr.1Rar�1 Slidezinguidesundermainboard. � r'�pp� fct ARO• . DWG N593-32A �+' 01711,11 0,\Wv —gt; rill c ..0 E" 16 m P Connector 5— DD.,o00c on PFC-6075 1® ❑ —_-----'I main board jR p wai I0 n v Q_ ..:1®�. Q P Connector LAI®�G��CJ ' on PFC-6800 — NOTICE _L �I��_,,. -; main board p A Install in accordanceI 0E5 �'� with compatible fire alarm control panel tNI a. :_C installation manual _I. I-■ y-�_, aI �_ --.-=.-----:-.===- i lir_,... -------__... Installation The UD-1000 DACT is connected to the control panel using the provided four-wire cable connection(P/N 5210514)between P4 and UD-1000 P1.The connection is power limited and supervised. 1. Power system down. 2. Slide the UD-1000 into the carduides located under the User Interface bracket. acket. 3. Secure the UD-1000 to the User Interface bracket using the provided#6-32x3/815 screw 4. Install the provided four-wire conductor jumper between UD-1000 P1 and P4. Potter Electric Signal Company,LLC • St. Louis,MO • Tech Support: 866-956-1211 /Customer Service: 866-572-3005 • www.pottersignal.com ISO 90131:20081 DESIGNING,MANUFACTURING, CERTIFIED &DISTRIBUTING QUALITY SYSTEMS 8830048-REV B • 12/18 PAGE 2 OF 2 11111 POTTER PAD1 00-PD The Symbol of Protection Photoelectric Smoke Sensor Features p55EMs<Fo • Low profile,less than 2 inches with the base \ .40.0 •�rHE Jyp • Wide selectable sensitivity range of 1.0 to 3.7%/foot • Sensor communicates sensitivity to control panel11111 CA • UL listed smoke calibration and sensitivity • Optional locking tab to prevent unwanted removal ,y` • Simple DIP switch address setting,no programming tool required • LED alarm indicator Plpil yillti • Product includes a 5 year warranty • UUKL Listed for Smoke Control .i. APPROVED LISTED Description Technical Specifications The Photoelectric Smoke Sensor is a listed Analog Addressable smoke Operating Voltage 24 VDC sensor compatible with fire alarm control panels that utilize the Potter Addressable Device(PAD)protocol.The PAD100-PD is a low profile Detector Current Draw 300µA smoke sensor with a wide sensitivity range.The sensor and base(not Alarm indicator 1 LED included)are made of a durable plastic in an off-white color to blend Alarm set-point range 1.0 to 3.7%/ft 3.6-12%/m in with the ceiling. Installation temperature The PAD100-PD has a sensitivity range of 1.0 to 3.7%per foot and range 32 to 120°F/ 0 to 49°C is UL.The PAD 100-PD features drift compensation and has built in dirty detector warning as well as. The PAD 100-PD and the control Operating relative 0%to 93%(Non-condensing) panel communicate over a proven and robust digital communication humidity range path and the system analyzes the information at the particular device. Start-up time Max. 1 sec. The total polling speed is less than five(5)seconds,well under the UL Maximum number of requirements. addresses per loop 127 The sensor is compatible with any of the PAD series sensor bases and Maximum number of simply twists on. The PAD100-PD is addressed using DIP switches lighted indicators in 30 in the rear of the sensor and can be easily programmed in the field alarm per loop. without special tools. Color Eggshell White Setting the Address Weight(without base) 101g(3.56oz) Each addressable device on the SLC loop must have a unique address Dimensions(without Height: 1.35 in(34mm) from 1 to 127 to function properly. The address is set using DIP base) Diameter:3.93 in(100 mm) switches. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to SLC or device.Verify the following: I. Power to the device is removed 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830108-REVD • 12/18 PAGE 1 OF 2 • . . • . , 111 .p POTTER PAD1•00-PD The Symbol of Protection Photoelectric Smoke Sensor • • Air Velocity Ratings The PAD 100-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute. The system has a maximum of 30 LEDs that can be turned on simultaneously.If the system already has 30 LEDs on,the PAD100-PD will operate even though the LED may not illuminate. • Operation The PAD100-PD is an analog addressable sensor that uses one address on the Signaling Line Circuit(SLC)of a compatible fire alarm control panel. The unit communicates with the control panel as it is polled.The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is in an active status.The polling LED can be turned off if desired for less conspicuous operation. The PAD100-PD with the PAD100-4DB or PAD100-6DB has a low profile of less than two(2)inches to blend into the surrounding environment.The sensor includes an insect screen to prevent foreign objects from reaching the chamber and the can be cleaned to restore operation of a dirty detector. Sensor Sensitivity The PAD100-PD and the compatible control panel work in tandem to keep the sensitivity consistent.As the sensor is installed over time,the sensor compensates for the dirt in the unit until it is out of range.At that time,the panel will indicate a dirty sensor.The sensor will then have to be cleaned or replaced. The PAD100-PD can be programmed to provide a maintenance alert prior to reaching the dirty sensor level which will allow for intervention prior to the sensor going into trouble. This allows for sensor replacement or cleaning prior to a nuisance trouble occurs. NOTE:As required by NFPA,do not install the sensors until all construction is complete and the work area has been thoroughly cleaned.If the sensors have been installed in a construction environment,they should be cleaned or replaced before the system is placed into service. Spacing The PAD100-PD is UL listed with a recommended maximum spacing of 30 feet.Refer to NFPA 72 for specific information regarding detector spacing, placement and special applications. Compatible Bases All bases will mount on a single gang,double gang,octagon,4"square or mud ring electrical box. Device Description Stock No. PAD100-4DB 4"Standard Base 3992731 PAD100-6DB 6"Standard Base • 3992732 PAD100-IB 6"base with an isolator module included. 3992730 PAD100-RB 6"base with one Form-C relay contact. 2A @ 30VDC,0.5A a 125VAC 3992728 PAD100-SB 6"base with sounder module included.Sound pattern is provided from external source. 3992729 PAD100-SPKB 6"base with speaker included 3992762 Ordering Information Model Description Stock No. PAD100-PD Photoelectric Smoke Sensor 3992733 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830108-REVD • 12/18 PAGE2OF2 P POTTER PAD100-4DB/6DB The Symbol of Protection 4"/6"Addressable Detector Base Features 55EM8ZF0 • Terminals Marked with Polarity to assist with installation 'ono��" 47 • Duplicate terminals for in and out SLC wiring "' "INA�P y rHE'1 • Terminals accept 22 to 12 AWG wire sizes illq • Installs on single gang,double gang,octagon or 4"square box • Locking tab prevents unauthorized detector removal • Product includes 5 year warranty ' J 1 ,. cul x UI0INpiVIIW0 piu @0111 g1 aw.aP'';u /4; (1) tuu hum APPROVED LISTED Application Technical Specifications The Potter PAD100-6DB and PAD100-4DB detector bases are used Mounting Options Single gang, double gang, octagon, and 4" to install Potter's addressable smoke and heat detectors.The PAD100- square box 6DB will mount on a single gang,double gang,octagon or 4"square Terminals Screw-Clamp Type electrical box. Wire Guage 22 to 12 AWG Diameter:6.3 in(166 mm) Description Dimensions Height 0.72 in(18 mm) The PAD100-6DB and PAD100-4DB are low-profile, surface mount Shipping Weight 87g(3.07 oz) bases used with Potter's addressable detectors.The base uses screw- clamp terminals that accept wire ranging from 22 to 14 AWG.When Material Durable Plastic installed on recessed electrical boxes the PAD 100-6DB is wide enough to completely cover the back box and the immediate surrounding area. The base is equipped with a locking tab to deter unauthorized removal of the attached detector. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PRINTED IN USA 8830107—REV C • 12/18 PAGE 1 OF 2 1 pj�OTT PAD100-4DB/6DB The Symbol of Protection 4 /6„Addressable Detector Base Locking Feature Wiring Diagram The MD100-6DB and PAD100-4DB include a locking feature that Fig.3 prevents removal of the detector without using a tool. 1.To eliminate this feature,break off the locking tab(refer to Figure 1),and then install the detector. oat j� Fig.1 s+- s+ To FACP First Detector Base Last Detector Base Loop(SLC) ir `4 ,. IeP .—V' I_ / 1, te- ? `” 11W1 v// Break off tab(gray arcking featurentue. disable locking fOrdering Information . Model Description Stock No. 2.To remove the detector from the base when the locking feature has PAD 100-6DB 6"Sensor Base 3992732 been enabled, insert a small screw driver into the slot on the base to push the plastic tab while simultaneously turning the detector head PAD100-4DB 4"Sensor Base 3992731 counter-clockwise. Fig.2 Insert small screwdriver lk1 into slot to remove o° Ti detector from base. /+ firti . 17 1 CI Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com PRINTED IN USA 8830107-REV C • 12/18 PAGE 2 OF 2 PAD100-PSSA/PSDA �0 Addressable Pull Station The Symbol of Protection Single/Dual Action Features •,5sEMs,Fo • Single or Dual Action versions • • Durable die-cast construction �`�THE\ • Reset key matches the fire alarm control panels m .. • Compatible with IPA Series panels 1 in ' L 1 QM • SLC Class A,Class X&Class B ��L ' R tilt f41► • Product includes a 5 year warranty �, • UUKL Listed for Smoke Control `�, 1 ill N' 8$ 1 11PULL DOW 11 1 ILloll,II illsii rorrER ®FOTTER ® UL APPROVED 1" '.1 Description Technical Specifications cations The PAD100-PSSA (Single Action) is activated by simply pulling Operating Voltage 24.0 VDC the white "T" bar handle down. The PAD100-PSDA (Dual Action) is activated by lifting the front cover and then pulling the white"T" Max SLC Standby Current 200uA bar handle down.Once activated,the"T"bar cannot be reset without Max SLC Alarm Current 200uA opening the front cover.Opening the front cover will also activate the 32°F-120°F(0°-49°C) pull station.To reset the PAD100-PS Series,use the Potter WS-93 key Environmental Limitations Indoor Only to unlock and open the front cover. Once the cover is open,push the "T"bar back into the normal position and re-secure the front cover. Dimensions 4.75"H x 3.25"W x 1.75"D Relative Humidity Range 0-93%(non-condensing) Application MountingOptions Single gang box or The PAD100-PSSA/PSDA is compatible with Potter's IPA and AFC/ p Potter P32-BB/DBB ARC series addressable fire alarm control panels. It is a non-coded APS-SA-1.22 lbs. addressable pull station available in either a single or dual action Shipping Weight model and installs on a single gang box or surface mounts using the APS-DA-1.46 lbs. P32-BB or P32-DBB(deep)back box. Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830097-REV D • 12/18 PAGE 1 OF 2 PAD100-PSSA/PSDA Addressable Pull Station The Symbol of Protection Single/Dual Action Setting the Address The PAD100-PS Series uses one SLC address assigned to the device.The address is set using the DIP switch located on the back of the PAD100-PS device. Pull Station Front View Fig 1 e„„,., — 0 I ARM o 7.1.111.010 R, � / '@ o--- c..,/, li:woom.- .- .--- / !ic–ill__ 1,111 IrniLlorks. ImMiii Ll owmhO ( y1,16IIPULL ©P o Porgy �� PAD 100-PSDA PAD100-PSSA Pull Station Back View and Wiring Fig 2 O 0 (5P ABI drillW Pli II 1 I. I FACTORY WIRED CONTACTS FROM FACP OR / PREVIOUS DEVICE TO NEXT DEVICE I Ordering Information Model Description Stock No. PAD100-PSSA Addressable Pull Station,Single Action 3992721 PAD100-PSDA Addressable Pull Station,Dual Action 3992720 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830097-REV D • 12/18 PAGE 2 OF 2 POTTY Few) PAD100-MIM The Symbol of Protection Micro Input Module Features _x Sssma, 1 2 4 a ]l = 94 P , O• • One Class B contact monitoring input . 4000 • Small size allows mounting in most electrical boxes .+,46 ai i nt"'*°"a. ��NE�`'P• • SLC Class A,Class X&Class B • 6"Pigtail wiring connections Q FaN NONNth • Product includes a 5 year warranty 'X°y • INKL Listed for Smoke Control ©(�o1 SER N PAD 100-MIM (SLC Module) _ ,...J-SLG+ 117-1 1 t 4//; Uce L APPROVED Description The PAD100-MIM is used to monitor the status of an initiating Technical Specifications device(s)that contain a normally open set of dry contacts.The module is enclosed in a plastic case to protect against inadvertent shorts and Operating Voltage 24.0V ground faults. The case can be mounted using a single screw. The Max SLC Standby PAD100-MIM has a status indicator LED to indicate communication Current 200µA and alarm condition.In normal condition,the LED flashes when the Max SLC Alarm device is being polled by the control panel.When the input is activated, Current 200µA the LED will flash at a fast rate. IDC Input Circuit Wiring Class B Application Max Wiring Resistance 100 n The micro input module(PAD100-MIM)is compatible with Potter's of IDC IPA and AFC/ARC series addressable fire alarm control panels. Max Wiring Generally the PAD100-MIM is used to monitor pull stations and Capacitance of IDC 1µF other devices where the module is installed in an electrical box or EOL Resistor 5.1K S2 enclosure behind the device being monitored. Operating Temperature 32 to 120°F(0 to 49°C) Range OpeRange Humidity 0 to 93%(non-condensing) R g Max no.of Module Per Loop 127 units Dimensions 1.75"(44.5mm)L x 1.36" (34.5mm)Wx.43"(11mm)D Mounting Options 2-1/2"(64mm)deep single-gang box Shipping Weight 0.3 lbs Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830079-REV D • 12/18 PAGE 1 OF 2 • j OTT PADI00-MIM The Symbol of Protection Micro Input Module Setting the Address Each addressable SLC device must be assigned an address.The address is set using the DIP switch located on the front of the PAD100-MIM.Before connecting a device to the SLC loop,take the following precautions to prevent potential damage to the panel or device: 1. Power to the device is removed. 2. Field wiring is correctly installed. 3. Field wiring has no open or short circuits. Wiring Diagram Fig 1 0 lid POTTER PAD100-MIM f \0 0 ®4 FROM FACP OR PREVIOUS TO NORMALLY OPEN DEVICE AND TO NEXT DEVICE _ - -- MONITORED DEVICE 5.1K OHM REQUIRED Part#3005013 Ordering Information Model Description Stock No. PAD 100-MIM Micro Input Module 3992700 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com 8830079-REVD • 12/18 PAGE 2 OF 2 te. .. 1,0111111,1114,1.11.,,, ,,r".„-•111,,I, !-11111111 .��'--- --,;-. ,rr---V- I�. aI I.I!�I 1.I I- ° -1 °.. ::"1,"',1:111111111,:':H....-. 11II 1 1pII IlIIIII^411:1„,-; ,111:411[111'''"'---,==„L"--- 1h11 IIIf▪-._ I:, ..,„..1,,„4:1.11:::.11:•:,::::'..,.1.,v1.'I,Ia: - �, x. „ _ - ; bil r I 1ItlIl 1 .1,. 1 uIIIll I IIIIIuilI haa — 11111111 1 ,q11111111111111111111,111111111111II1 1 II 1 u 1 , 111111111 1111II IIIII IIIIII"I1Ir_ .... . .r 1 'u6uIIid1III IIII _-a11111111111111 y IVl lfI _ vIIiIryiyl �lii 11 s IIIl9, v71,i1 1 11r,,,,111 - IIIX111111 IIIII11111111,1 11 � .rII ;° ,..,111111k1,11,",;.'5:"'' M 1Iv1 ',;,Z11:11,1101,",,,,, 1Id 1'r.v i'',1111111111.,'" 1II 101 �+ 1 ‘-..-`'tI� VIII 1 , �1'u - v .,11110IIIIII1 � ,. r 1 IIu1il[.....,. IIp1oI1 -. .M TheCOt°e`1MUNICA1}1var•d The CellComSLCF offers cellular fire I-_LY SUPCPtVI FI.. EASY U1,) ,'o, '< communication on any fire control panel via �11r�lU f ll�'°.� i 9t VMI C 'L( P ',_,-_. Contact ID Captures or Zone Inputs. Meets Provides a fully supervised alarm Older,dial-up panels have new life with the NFPA72Standard for Single Communication communication path for burglary control addition of cellular communication. Earn Technology, panels over the CDMA network providing customerloyaltybyextendingthelifeoftheir higher speeds, existing panels, enabling them tof increase -- K S WITH MOST PANEL ,00„.J, -: CTI t4 OPTIONS the ROl on theilrss. em investment and build Tlf the existing panel supports Contact ID, CellComSL communicators can be attached satisfaction with the purchase decision. then it's a candidate for upgrading with the to the existing panel in a variety of ways.It ;BUILD C ;,Ir I YAt..T Y CellComSLCF can capture Contact ID messages from the Avoid the possibility of customers seeking ,r-1F1„D i"I _.. �. I y , fµl=s dialer,or connect the four input zones from mobile intrusion alarm features from a The Model 400 USB Flash Module allows outputs on the panel; or it can sense the competitor by enabling those features you to easily field update firmware for output of the bell of an existing alarm and on their existing panel with a minimal panels that would otherwise require the communicate the appropriate message to additionalcost.Theyarelesslikelytoswitch use of a computer and a Model 399 the Central Station. systemsandcanceltheircontract.Whenthe Programming Harness. :{ h1F time does come to replace the panel, they I aNNIININ1ImI1 .*,,,,,, III `i- "6 Each of the CellComSL models provide four are more likely to rely on you. 3 _ zones for connection to burglary control R $o I panel outputs. Zone 4 is intended for Iv, connection to the control panel bell output. 1111,11,11,111 ,110,111.1 1 '' I",": IFICATICN"- Dimensions: 5.5"W x 3.75"H x 1" 0 California State Fire Marshal(CSFM) Color: Red ANSI/UL 864 Fire Protective Signaling Systems Open-Collector Outputs: 2 Zones: 4 Cellular Primary Power(CellComSLCF): 12-24VDC FCC Part 15:MIVCNN0301 Current Draw: Alarm 210 mA Standby 210 mA J 2 c — v — o ac.-. 5 o` cp 'c o _f - = r ® r 1111111�NIi1I11pV1Wl `u ® fru. .._. 111 p 1 1I�1^old _ ur y N r -0111111,1111111��II"1 :,tt:'3v11 °' muuur m:; 41�I IIGy� � rN°� � "� � f 1�1I Ila� _'� �> w+r...."".° '� 'n1f➢VI f V u, li', t le -____11+5''''''',,'''',.'., _ Poi vVl7� a aTat IN � � rl I 1 IIII h� 11 s . '+c, p�II141g619 vu d 4 _ 1..r ..# •811111111 k..11 a 1111111 1''IV�'I]Irti IIIA 1 r 11 1�r-w��✓IVuhil'11�1. �ull 1 w s lNli "u �I$� r v _`2 I I{i��1 Flo a�1 nershi BOU eva d'nal ur 800. Ft 4282 rig 1j Com ,IIIIIII11',"1 :11 X111°I a7. ...n tri ICtf?11 I �° �� I � uu' o- � - p �1 nVl IIV NR u1W 1 a'� 1 I '. 1 VIII y.IR, 1. a 19111111�I VI:41'I u — r7•)ritn[6r[i[ t lilt, 1 w ,.M �a„��a„"-... - �"� �r,r,,.�.0 �wx �„I Il llu� �m � r ur f Iud0 1 - 111111111'1J 1I111lrIIvII r';11111 0r 1 µ /,-3-"" " 1 x` 64 1 P :i.', �1 SI 111 � o IIi a h1111 4" 1 v"a 1i�10 I ��� n r� 1II a'. .011.1 a � a Ill, ll'_I I :--'r 1 .. rt hI I V I I =-a,y .;,,,,,7 W 11 II 1 1 1 � inn H' ,d"LII 11 11,V IIN s 1 ru drn. 3 °I 9Ci7i'7 u# Idlp 11101,11 1 41i 111 41. 1 f. y 11G �M 111111,01:4- 0.., ,Nea"",. dldr d 11 .yVlu � 1 III IIr,LI�l