Loading...
Energy Study PE Tigard Library Energy Study _ __.---- .„--------- - _ _ _ ._._ .,.. __,------ __-- „„------- January 14,2003 Analysis By: ENGINEERS, INC G CONSULTING Suite 300 PAE C.., • ”. Avenue, 808 SpWortTlahnldra, Orego_n _,9,7204 _ (503)226-2"1 - SponsoredRAiBy: ELECTRIC GENE-- Rd. - PORTLAND - r Bowles Ferry POR 0 sW Upper 97224 1628 Portland, OR 603-1651 (503) Manning - - Attn: Richard Tigard Library Energy Study 1/14/2003 Table of Contents 1.0 Executive Summary 2 1.1 Introduction 2 1.2 Objectives of the Analysis 2 1.4 Summary of Findings 2 Table 1.1 Energy Savings and Payback 4 Figure 1.1 Energy Use of Baseline Building 5 Figure 1.2 Energy Use of Suggested Building 6 2.0 General Project Information 7 2.1 Overview 7 2.2 Operating Schedule and Electrical Costs 8 3.0 Energy Analysis Methodology 9 3.1 Methodology 9 4.0 Energy Efficiency Measures Evaluation 12 EEM 1: High Performance Glazing 12 EEM 2: Increased Wall Insulation 13 EEM 3: Increased Roof Insulation 14 EEM 4: Natural Ventilation 15 EEM 5: High Efficiency Boilers 16 EEM 6: CO2 Sensors 17 EEM 7: Daylighting 18 EEM 8: Point of Use Domestic Water Heating 19 EEM 9: Evaporative Air Cooled Water Chiller 20 EEM 10: Underfloor Ventilation System 21 Combined Building 22 5.0 Tables of Energy Saving and Cost for all EEMs 24 Appendices Appendix 1: Energy Cost Schedules Appendix 2: EEM Cost Estimates Appendix 3: PowerDOE Printouts Appendix 4: File Comparisons Appendix 5: Baseline Input File PAE Consulting Engineers,Inc. Page 1 Tigard Library Energy Study 1/14/2003 1.0 Executive Summary 1.1 Introduction This report summarizes the results of the Tigard Library energy study. The report is sponsored by Portland General Electric through its Earth Advantage program. The Tigard Library is a new 47,000 square foot building. It is located in Tigard, Oregon, and includes library spaces, office spaces, a community meeting wing, and a two-story tall lobby. 1.2 Objectives of the Analysis The objective of this analysis is to evaluate the economic value of ten energy efficiency measures (EEMs) proposed for the Tigard Library. In addition to reducing the new building's overall environmental impact, implementing the optimum combination of energy efficiency measures will reduce the building's exposure to the increasingly volatile electricity and gas markets. 1.3 Energy Efficiency Measures The following EEMs were analyzed: EEM 1: High Performance Glazing EEM 2: Increased Wall Insulation EEM 3: Increased Roof Insulation EEM 4: Natural Ventilation EEM 5: High Efficiency Boilers EEM 6: CO2 Sensors EEM 7: Daylighting EEM 8: Point of Use Domestic Water Heating EEM 9: Evaporative Air Cooled Water Chiller EEM 10: Underfloor Ventilation System 1.4 Summary of Findings Based on the findings of the energy study, each EEM was recommended or not recommended: EEM 1: High Performance Glazing Recommended EEM 2: Increased Wall Insulation Recommended EEM 3: Increased Roof Insulation Not Recommended EEM 4: Natural Ventilation Recommended EEM 5: High Efficiency Boilers Recommended EEM 6: CO2 Sensors Recommended EEM 7: Daylighting Recommended EEM 8: Point of Use Water Heating Recommended EEM 9: Evaporative Air Cooled Water Chiller Not Recommended EEM 10: Underfloor Ventilation System Recommended PAE Consulting Engineers,Inc. Page 2 Tigard Library Energy Study 1/14/2003 EEMs 1, 2, 4, 5, 6, 7, 8, and 10 have been combined as the "Suggested Building." The suggested building will save 133,934 kWh and 57 Therms annually. Considering current electricity and gas rates, the suggested building saves $17,696 in operating costs over a baseline system every year. The incremental first cost of the Suggested Building is $65,805 over the baseline system. This results in a 3.7 year simple payback. PAE Consulting Engineers,Inc. Page 3 II II I I II I I I I I I I I I I I I I I I I I I I I I I I I I Tigard Library Energy Study 1/14/2003 Table 1.1 : Energy Savings and Payback . ANNUAL CONSUMPTION ANNUAL SAVINGS ELECTRIC NAT GAS ELECTRIC NAT GAS %Better than Total Energy Energy TOTAL CUST. Oregon Energy Incremental Usage Savings SAVINGS PAYBACK Recommendations Code Cost kWh KW,pk THERM (MMbtu) TOTAL($) kWh KW,pk THERM (MMbtu) ($) (YR) %Saved($) Baseline - 786,839 320 18,915 4,576 $72,290 - - - - - - - . - EEM 1:High Performance Glazing Yes 4.40% $12,273 768,480 307 17,528 4,375 $69,893 18,359 13 1,387 201 $2,397 5.1 3% EEM 2:Increased Wall Insulation Yes 2.04% ($4,355) 788,667 318 17,919 4,483 $71,626 -1,828 2 996 93 $664 -6.6 1% EEM 3:Increased Roof Insulation No 0.57% $8,578 784,870 319 18,723 4,550 $71,998 1,969 1 192 26 $292 29.4 0% EEM 4:Natural Ventilation Yes 1.82% ($10,350) 767,962 299 18,724 4,493 $70,740 18,877 21 191 84 $1,550 -6.7 2% EEM 5:High Efficiency Boilers Yes 14.31% $11,000 786,838 320 12,365 3,921 $67,085 1 0 6,550 655 $5,205 2.1 7% EEM 6:CO2 Sensors Yes 4.40% $3,000 783,127 329 17,026 4,375 $70,538 3,712 -9 1,889 202 $1,752 1.7 2% EEM 7:Daylighting Yes 3.85% $27,600 728,702 295 19,136 4,400 $68,144 58,137 25 -221 176 $4,146 6.7 6% EEM 8:Point of Use Domestic Water Heating Yes 0.35% ($863) 797,620 321 18,385 4,560 $72,674 -10,781 -1 530 16 -$384 None -1% EEM 9:Evaporative Air Cooled Water Chiller No 4.35% $178,388 723,573 305 19,085 4,377 $68,003 63,266 15 -170 199 $4,287 41.6 6% EEM 10:Underfloor Ventilation System Yes 4.05% $27,500 740,854 306 18,631 4,391 $68,905 45,985 14 284 185 $3,385 8.1 5% Combined Building 32.20% $65,805 652,905 263 8,750 3,103 $54,594 133,934 57 10,165 1,474 $17,696 3.7 24% 'Building Square Footage 46,710 I Baseline EUI 97,973 66,427 btu/sq ft Total Building Energy 4,576 3,103 MMBtu Energy Saved 0 1,474 MMBtu %Reduction NA 32.20% PAE Consulting Engineers,Inc. 1 1 1 I I 1 1 1 I I I I 1 I I I I I I I 1 1 1 1 1 I I I 1 I 1 1 Tigard Library Energy Study 1/14/2003 Figure 1 .1 Energy Use of Baseline Building Fans 8% Hot Water 1 % Pumps Lights 0% 17% _ r Lights Space Cooling ■ Misc Equip 15% ❑ Space Heating Equip�� Misc Eq p ❑ Space Cooling 18% II Pumps ‘11•r .01 • Fans ■ Hot Water Space Heating 41 % PAE Consulting Engineers, Inc. i i i I I I I I I I I I I I I I I I I I I 1 I I I I I I I I I I Tigard Library Energy Study 1/14/2003 Figure 1 .2 Energy Use of Suggested Building Lights 14% M Lights Savings �� �����€f, � ,€ • Misc Equip 32% ❑ Space Heating Misc Equip 19 /o o ❑ Space Cooling Hot Watery ■ Pumps 1 % ' 111 Fans ■ Hot Water Fans Pumps Space Heating • Savings 50/0 0% 19% Space Cooling 10% PAE Consulting Engineers, Inc. 1/14/2003 Energy Study Tigard Library 2.0 Genera Information General Project _ 2.1 O verv ie w — pur)ose of Study U d y - Thepurposeof t his study is to evaluate the possible energy savings from 10 potential energy er g Y conservation measures for Tigard Library. _ Baseline Building Description _ The baseline building is modeled to match the architectural building plans with respect to — dimensions,orientations, and room designations and layouts. The model's schedules are basedon the OregonEnergyCode suggested schedules forasimplifedTraae-Off approach and modified — to match the actual useof the Tigard Library. _ A rendered image of the building ing as designed in the he mo del can be seen in.-21r e 2.1. Figure2.1 Rendered Imageof Tigard Library _.-- .„--- ,---- - .,--- _---: ----- _ _ - _ - , ---- - ., — __,---- ) „.-- .... _,------- ,,,--- __-- _ - ,---- — _ Page 7 Inc. PAE Consulting Engineers, Tigard Library Energy Study 1/14/2003 2.2 Operating Schedule and Electrical Costs Electricity Rates are described by Portland General Electric Company Schedule 38 Standard Offer Service. The schedule can be found in Appendix 1 and is summarized as follows: Monthly Rate: Energy On Peak Charge: $0.07859/kWh Off Peak Charge: $0.06486/kWh Demand No Demand Charge On Peak Charge is Monday-Friday 7 a.m. to 8 p.m. Off Peak Charge is Monday-Friday 8 p.m. to 7 a.m.; and all day Saturday and Sunday _ Natural Gas Rates are described by NW Natural Schedule 3, Commercial, Institutional &Industrial Service. The schedule can be found in Appendix 1 and is summarized as follows: Monthly Rate: Customer Charge: $7/month Energy $0.79457/Therm Demand No demand charge Effective Cost of Gas per kWh: 1 therm gas= 29.31 kWh 1 kWh gas =$0.0271 Occupancy Occupancy schedules were based on the Oregon State Energy Code suggested schedules for a Simple Trade-Off approach and were modified to match Tigard Library's actual schedules. PAE Consulting Engineers,Inc. Page 8 Tigard Library Energy Study 1/14/2003 3.0 Energy Analysis Methodology 3.1 Methodology The energy analysis for the Tigard Library was performed using standard engineering calculation procedures and the PowerDOE energy analysis programs. The baseline building has been modeled by using PowerDOE inputs that closely approximate those of the actual building. The floor plans of the building serve as the foundation of the model, with individual spaces and areas divided into "zones." The exterior of the building, or envelope, is added to the perimeter zones, complete with windows, geographical orientation (North, south, etc.), glass type, external shading, construction type, insulation values and interior space finish. Internal heat loads are modeled by adding people, lights, and equipment to each zone. Occupancy schedules model the movement of people in and out of the zones. Lighting schedules model the time of use of lighting in each zone. Space temperatures to be maintained for each zone in heating and cooling modes were also input. Water and airside HVAC equipment was modeled to match the suggested systems for the building. After the above inputs were entered, the PowerDOE simulation was run using hourly Portland, Oregon weather data. The predicted energy use and costs generated by the baseline model are a function of the building construction, HVAC systems,weather files, and local utility rates. The building's energy use was calibrated to match typical energy use of similar buildings in the Pacific Northwest region. The baseline-building model was used as a basis for comparing the EEMs. The baseline model was modified with each separate energy efficiency measure to determine the effect of that measure individually. Individual EEMs showing a desirable payback were combined to determine which combination of measures would provide the most cost-effective and energy efficient design. The combination of EEMs showing the most desirable payback, were modeled simultaneously and became the Suggested Building. Although every attempt has been made to model the actual building conditions that will exist when construction is complete and while PowerDOE is generally accepted as the most accurate energy simulation program available, the predicted energy consumption should not be interpreted as an absolute prediction of the actual usage. Actual conditions may differ from the original assumptions due to unpredictable variables such as changes in occupancy schedules, equipment selection and installation, building construction and operation, and weather variations from year to year. PAE Consulting Engineers,Inc. Page 9 Tigard Library Energy Study 1/14/2003 Baseline Model: The Oregon State Energy Code and the building's architectural specifications determined the baseline thermal characteristics. The baseline building thermal characteristics are as follows: Baseline Building Envelope Description: Library Wing Exterior Walls: Exterior walls are modeled as layered walls with thermal mass. The layers are 4"Face Brick, an air layer,batt insulation, and 5/8" gyp board. The overall wall U-value is 0.13 BTU/HR-FT2-°F. Community Wing Exterior Walls: Exterior walls are modeled as layered walls with thermal mass. The layers are 8" CMU blocks, Rigid Insulation, and 5/8"gyp board. The overall wall U-value is 0.13 BTU/HR-FT2-°F. Roof: The roof is modeled as a layered surface with thermal mass. The layers are a horizontal air film,built-up roofing, rigid insulation, and an interior air layer. The overall roof U-value is 0.05 BTU/HR-FT2-°F. Slab-on-Grade: The slab-on-grade is modeled as a layered surface with thermal mass. The layers are a 12" soil layer,poured concrete, an isulating layer, and carpet. The overall slab U-value is 0.075 BTU/HR-FT2-°F. _ Baseline Glazing: Glass was chosen to meet the Oregon State Energy Code. The overall U-value was chosen to be 0.57 BTU/HR-FT2-°F; the overall shading coefficient was chosen to be 0.54. The visible transmittance of the glass was modeled as 0.57. Infiltration: Inflitration was calculated at 0.1 cfm/square foot exterior wall. The calculated cfm infiltration was entered into PowerDOE as an air-changes per hour value. PAE Consulting Engineers,Inc. Page 10 Tigard Library Energy Study 1/14/2003 Baseline Building Equipment Description: HVAC HVAC System 1: Lower Floor: PVAV unit serving the lower floor of the Library Wing HVAC System 2: Upper Floor: PVAV unit serving the upper floor of the Library Wing HVAC System 3: Community Wing: PVAV unit serving the Community Meeting Wing. HVAC System 4: Lobby: Package Single Zone system serving the Lobby. All HVAC systems are served with hot water from two 80% efficient gas fired boilers and have DX-cooling set to meet the Oregon Energy Code minimums for efficiency. Lighting Light power densities were used for the baseline model were based on light densities listed in the Schematic Design package. Lighting schedules were implemented to turn lights off when rooms are not in use. - Lighting: General Library Zones 1.2 W/ft2 Reading/Program Zones 1.7 W/ft2 Community Meeting Wing 1.2 W/ft2 Miscellaneous Equipment Equipment: General Library Zones 0.5 W/ft2 Library Office Areas 1.5 W/ft2 Computer Areas 200 W/computer terminal Community Meeting Wing 1.0 W/ft2 Utility Rooms Based on expected room load PAE Consulting Engineers,Inc. Page 11 Tigard Library Energy Study 1/14/2003 4.0 Energy Efficiency Measures Evaluation EEM 1: High Performance Glazing This EEM proposes to improve the building's glazing to a Viracon VE1-2M or equivalent glass. VE1-2M glass has a shading coefficient of 0.44 and a center of glass u-value of 0.29. Modeling Strategy This EEM was modeled using PowerDOE energy analysis software. The properties of all glazing were modified to match the improved u-value and shading coefficient of the proposed glazing. Baseline Assumptions: PowerDOE Conductance Value: 0.60 Shading Coefficient: 0.57 EEM Assumptions: PowerDOE Conductance Value: 0.44 Shading Coefficient: 0.43 Annual Savings: Electricity: 18,359 kWh Demand: 13 kW Natural Gas: 1,387 Therms Dollars: $2,397 Capital Cost: $12,273 Simple Payback: 5.1 years Note: Though the model currently shows a glazing percentage of 35%, the architect has indicated that the final design will be at or below 30% glazing to meet Oregon Energy Code requirements. PAE Consulting Engineers,Inc. Page 12 Tigard Library Energy Study 1/14/2003 EEM 2: Increased Wall Insulation This EEM proposes to increase the insulation of all walls in the new Library. The Community Wing walls were modeled with 2" of polyisocyanurate rigid insulation behind the CMU blocks. The framed walls of the Library Wing were modeled with R-19 insulation and 24" on-center metal stud placement. Modeling Strategy This EEM was modeled using PowerDOE energy analysis software. The model was run with additional insulation added to the layered wall constructions to obtain u-values that matched the hand calculated u-values of the upgraded walls. Baseline Assumptions: Community Meeting Wing Wall U-Value: 0.13 BTU/HR-FT2-T Library Wall U-Value: 0.13 BTU/HR-FT2-°F EEM Assumptions: Community Meeting Wing Wall U-Value: 0.05 BTU/HR-FT2-°F Library Wall U-Value: 0.093 BTU/HR-FT2-.F Annual Savings: Electricity: -1,828 kWh Demand: 2 kW Natural Gas: 996 Therms Dollars: $664 Capital Cost: ($4,355) Simple Payback: -6.6 years PAE Consulting Engineers,Inc. Page 13 Tigard Library Energy Study 1/14/2003 EEM 3: Increased Roof Insulation This EEM proposes to increase the insulation of the new Library's roof. One additional inch of polyisocyanurate was modeled. The proposed roof would have 4-inches of insulation. Modeling Strategy This EEM was modeled using PowerDOE energy analysis software. The layered roof construction was modified to match the modified roof's u-value to the u-value of a wall with 4- inches of polyisocyanurate insulation. Baseline Assumptions: Roof U-Value: 0.05 BTU/HR-FT2-°F EEM Assumptions: Roof U-Value: 0.033 BTU/HR-FT2-°F Annual Savings: Electricity: 1,969 kWh Demand: 1 kW Natural Gas: 192 Therms Dollars: $8,578 Capital Cost: $292 Simple Payback: 29.4 years PAE Consulting Engineers,Inc. Page 14 — Tigard Library Energy Study 1/14/2003 EEM 4: Natural Ventilation — This EEM proposes to naturally ventilate the two-story Lobby. To cool the Lobby, about 100 square feet of manually operable windows will be added at the bottom and an additional 100 square feet top of the Lobby to allow the stack effect to draw adequate air into the space. The Modeling Strategy — This EEM was modeled using PowerDOE energy analysis software. The natural ventilation of the lobby was not directly modeled, but the savings of the system were calculated by replacing the Lobby's rooftop air conditioning unit with a unit heater. The Lobby's temperature was ...., allowed to float, and the cost of air conditioning the Lobby was effectively removed from the model. Baseline Assumptions: Full Air Conditioning in the Lobby Lobby System Type: Package Single Zone Cooling SetPoint: 75°F — Heating SetPoint: 55°F EEM Assumptions: Heat-only in Lobby — Lobby System Type: Unit Heater Cooling SetPoint: NA Heating SetPoint: 55°F Annual Savings: Electricity: 18,877 kWh Demand: 21 kW — Natural Gas: 191 Therms Dollars: $1,550 _ Capital Cost: ($10,350) Simple Payback: -6.7 years MEM IMININ PAE Consulting Engineers,Inc. Page 15 — Tigard Library Energy Study 1/14/2003 EEM 5: High Efficiency Boilers — This EEM proposes to replace the baseline boilers with High Efficiency condensing boilers. Condensing boilers have an efficiency of 92% at full load and this efficiency can increase to up — to 98% at lower part loads. Condensing boilers require a lower heating water temperature — setpoint to operate efficiently. — Modeling Strategy This EEM was modeled using PowerDOE energy analysis software. The boiler Heat-Input-Ratio — was changed to match the efficiency of the condensing boilers. The part-load performance curve of a typical condensing boiler was assigned to the model's two boilers. The heating water setpoint was reduced to 140°F. Baseline Assumptions: Boiler HIR= 1.25 Hot Water Loop Setpoint= 180 °F — Default Boiler Curve Used EEM Assumptions: Boiler HIR= 1.087 Hot Water Loop Setpoint= 140 °F — Condensing Default Boiler Curve Used Annual Savings: — Electricity: 1 kWh _ Demand: 0 kW Natural Gas: 6,550 Therms — Dollars: $5,205 — Capital Cost: $11,000 Simple Payback: 2.1 years — PAE Consulting Engineers,Inc. Page 16 — Tigard Library Energy Study 1/14/2003 EEM 6: CO2 Sensors — This EEM proposes to implement CO2 sensors in the Community Wing of the new Library. CO2 _ sensors will modulate the air handler's outside air damper to only bring in as much outside air as is required for the current occupancy. Modeling Strategy - This EEM was modeled using PowerDOE energy analysis software. The occupancy schedule of the Community Wing was considered, in addition to the minimum requirement of outside air per person in the Community Wing. An outside air damper position schedule was created that matched the outside air supply flow rate to the occupancy of the Community Wing. Twenty cfm of outside air is thus supplied to every person who is actually occupying the wing. In contrast, the — baseline model provides at least 20 cfm of outside air for the estimated maximum occupancy at all hours during which the air handler is in operation. The min-flow-schedule of the Community Wing was reduced to allow lower air flows that the default of the design outside-air cfm. In both models, the air handler is allowed to increase the outside air flow rate if economizer operation warrants. Baseline Assumptions: 4250 cfm of outside air is supplied from 10 a.m. to 10 p.m. EEM Assumptions: — 20 cfin of outside air is provided for every person occupying the Community Wing. _ Annual Savings: _ Electricity: 3,712 kWh Demand: -9 kW _ Natural Gas: 1,889 Therms Dollars: $1,752 Capital Cost: $3,000 Simple Payback: 1.7 years i PAE Consulting Engineers,Inc. Page 17 Tigard Library Energy Study 1/14/2003 EEM 7: Daylighting This EEM proposes to implement daylighting controls in the upper floor and lower perimeter zones of the Library Wing. The Lobby was also modeled with daylighting controls. Photocell sensors will determine how much natural light is available and will dim the artificial lights accordingly. Modeling Strategy This EEM was modeled using PowerDOE energy analysis software. Daylight sensors were added to the open library spaces of the upper floor and perimeter zones of the lower Library Wing. The Lobby was also modeled with daylight sensors. The ballasts were modeled to dim to a minimum of 30% depending on natural light levels. Baseline Assumptions: No daylighting EEM Assumptions: Daylighting in Upper Floor open areas of Library Wing Daylighting in perimeter zones of lower Library Wing Daylighting in Lobby Annual Savings: Electricity: 58,137 kWh Demand: 25 kW Natural Gas: -221 Therms Dollars: $4,146 Capital Cost: $27,600 Simple Payback: 6.7 years PAE Consulting Engineers,Inc. Page 18 Tigard Library Energy Study 1/14/2003 EEM 8: Point of Use Domestic Water Heating This EEM proposes to replace the two baseline gas water heaters with instant electric water heaters at each point of use. Modeling Strategy This EEM was modeled using PowerDOE energy analysis software. The water heater type was changed to electric and the domestic water pump was added to a new electricity meter, Electricity Meter 2. The new meter was not added to the electric utility schedule and thus the energy cost of the domestic water pump was discounted. The efficiency of the modeled electric water heater was set to 100%, to match the efficiency of instant electric water heaters. Baseline Assumptions: Gas Water Heater Heat Input Ratio= 1.37 EEM Assumptions: Electric Water Heater Efficiency= 100% Domestic Water Pump energy discounted Annual Savings: Electricity: -10,781 kWh Demand: -1 kW Natural Gas: 530 Therms Dollars: -$384 Capital Cost: ($863) Simple Payback: None years PAE Consulting Engineers,Inc. Page 19 — Tigard Library Energy Study 1/14/2003 EEM 9: Evaporative Air Cooled Water Chiller — This EEM proposes to install two high efficiency air-cooled water chillers in lieu of the baseline DX-cooling system. — Modeling Strategy This EEM was modeled using PowerDOE energy analysis software. A chilled water loop and all — associated pumps was added to the model. Two high efficiency Trane RTAA chillers were attached to the new chilled water loop. The air handling units were changed to VAV units with — chiller-water coils. Baseline Assumptions: — DX-Cooling in all units Unit Types: PVAV — No chiller No chilled water — — EEM Assumptions: All units use chiller-water cooling coil — Unity types: VAV — Chiller EIR: 0.328 Chilled Water Setpoint=44°F Annual Savings: — Electricity: 63,266 kWh Demand: 15 kW — Natural Gas: -170 Therms Dollars: $4,287 — Capital Cost: $178,388 Simple Payback: 41.6 years — PAE Consulting Engineers,Inc. Page 20 - Tigard Library Energy Study 1/14/2003 EEM 10: Underfloor Ventilation System — This EEM proposes to serve the upper Library Wing from the lower floor through a displacement ventilation system. The system will supply 63°F air to the upper Library floor and return the air through a plenum return. Both the baseline and EEM are ducted supply systems. Modeling Strategy — This EEM was modeled using PowerDOE energy analysis software. The temperature of supply air for HVAC System 2 was increased to 63°F. The entire light load and 25% of the equipment — load of the upper floor was assigned to the plenum, to simulate the effects of displacement _, ventilation. Reassigning the light and equipment loads to the plenum increased the return air temperature and allows for longer economizer operation. Baseline Assumptions: -" HVAC System 2: Upper Floor: Packaged rooftop, hydronic heat, DX-Cooling Supply Air Temp=55°F — % of Light to Plenum=20% — EEM Assumptions: HVAC System 2: Upper Floor: — Packaged rooftop, hydronic heat, DX-Cooling Supply Air Temp=63°F % of Light to Plenum= 100% — % of Equipment to Plenum=25% — Annual Savings: Electricity: 45,985 kWh Demand: 14 kW — Natural Gas: 284 Therms Dollars: $3,385 — Capital Cost: $27,500 — Simple Payback: 8.1 years PAE Consulting Engineers,Inc. Page 21 — Tigard Library Energy Study 1/14/2003 Combined Building — The suggested building incorporates EEMs 1, 2, 4, 5, 6, 7, 8 ,and 10. Modeling Strategy — This EEM was modeled using PowerDOE energy analysis software. The inputs from the accepted EEMs were combined into one model and run to see the interactive effects of each — EEM on the others. — Baseline Assumptions: PowerDOE Conductance Value: 0.60 — Shading Coefficient: 0.57 Community Meeting Wing Wall U-Value: 0.13 BTU/HR-FT2-°F — Library Wall U-Value: 0.13 BTU/HR-FT2-°F Full Air Conditioning in the Lobby — Lobby System Type: Package Single Zone Cooling SetPoint: 75°F — Heating SetPoint: 55°F — Boiler HIR= 1.25 — Hot Water Loop Setpoint= 180 °F Default Boiler Curve Used 4250 cfm of outside air is supplied from 10 a.m. to 10 p.m. — _ No daylighting Gas Water Heater Heat Input Ratio = 1.37 HVAC System 2: Upper Floor: — Packaged rooftop, hydronic heat, DX-Cooling — Supply Air Temp= 55°F % of Light to Plenum=20% — PAE Consulting Engineers,Inc. Page 22 Tigard Library Energy Study 1/14/2003 EEM Assumptions: PowerDOE Conductance Value: 0.43 Shading Coefficient: 0.44 Community Meeting Wing Wall U-Value: 0.05 BTU/HR-FT2-°F Library Wall U-Value: 0.093 BTU/HR-FT2-°F Heat-only in Lobby Lobby System Type: Unit Heater Cooling SetPoint: NA Heating SetPoint: 55°F Boiler HIR= 1.087 Hot Water Loop Setpoint= 140 °F Condensing Default Boiler Curve Used 20 cfm of outside air is provided for every person occupying the Community Wing. Daylighting in Upper Floor open areas of Library Wing Daylighting in perimeter zones of lower Library Wing Daylighting in Lobby Electric Water Heater Efficiency= 100% Domestic Water Pump energy discounted HVAC System 2: Upper Floor: Packaged rooftop, hydronic heat, DX-Cooling Supply Air Temp =63°F % of Light to Plenum = 100% % of Equipment to Plenum=25% Annual Savings: Electricity: 133,934 kWh Demand: 57 kW Natural Gas: 10,165 Therms Dollars: $17,696 Capital Cost: $65,805 Simple Payback: 3.7 years PAE Consulting Engineers,Inc. Page 23 a 1114 • 101 amMOI Appendix 1 : Energy Cost schedules WWI .w OAR I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I Tigard Library Energy Study 1/14/2003 Table 1.1: Energy Savings and Payback ANNUAL CONSUMPTION ANNUAL SAVINGS ELECTRIC NAT GAS ELECTRIC NAT GAS %Better than Total Energy Energy TOTAL CUST. Oregon Energy Incremental Usage Savings SAVINGS PAYBACK Recommendations Code Cost kWh KW,pk THERM (MMbtu) TOTAL($) kWh KW,pk THERM (MMbtu) ($) (YR) %Saved($) Baseline - _ 786,839 320 18,915 4,576 $72,290 - - - - - - - EEM 1:High Performance Glazing Yes 4.40% $12,273 768,480 307 17,528 4,375 $69,893 18,359 13 1,387 201 $2,397 5.1 3% EEM 2:Increased Wall Insulation Yes 2.04% ($4,355) 788,667 318 17,919 4,483 $71,626 -1,828 2 996 93 $664 -6.6 1% EEM 3:Increased Roof Insulation No 0.57% $8,578 784,870 319 18,723 4,550 $71,998 1,969 1 192 26 $292 29.4 0% EEM 4:Natural Ventilation Yes 1.82% ($10,350) 767,962 299 18,724 4,493 $70,740 18,877 21 191 84 $1,550 -6.7 2% EEM 5:High Efficiency Boilers Yes 14.31% $11,000 786,838 320 12,365 3,921 $67,085 1 0 6,550 655 $5,205 2.1 7% EEM 6:CO2 Sensors Yes 4.40% $3,000 783,127 329 17,026 4,375 $70,538 3,712 -9 1,889 202 $1,752 1.7 2% EEM 7:Daylighting Yes 3.85% $27,600 728,702 295 19,136 4,400 $68,144 58,137 25 -221 176 $4,146 6.7 6% EEM 8:Point of Use Domestic Water Heating Yes 0.35% ($863) 797,620 321 18,385 4,560 $72,674 -10,781 -1 530 16 -$384 None -1% EEM 9:Evaporative Air Cooled Water Chiller No 4.35% $178,388 723,573 305 19,085 4,377 $68,003 63,266 15 -170 199 $4,287 41.6 6% EEM 10:Underfloor Ventilation System Yes 4.05% $27,500 740,854 306 18,631 4,391 $68,905 , 45,985 14 284 185 $3,385 8.1 5% Combined Building 32.20% $65,805 652,905 263 8,750 3,103 $54,594 133,934 57 10,165 1,474 $17,696 3.7 24% 'Building Square Footage 46,710 I Baseline EUI 97,973 66,427 btu/sq ft Total Building Energy 4,576 3,103 MMBtu Energy Saved 0 1,474 MMBtu %Reduction NA 32.20% PAE Consulting Engineers,Inc. Portland General Electric Company P.U.C. Oregon No. E-17 Original Sheet No. 38-1 SCHEDULE 38 STANDARD OFFER SERVICE (COST OF SERVICE) OPTIONAL TIME-OF-DAY LARGE NONRESIDENTIAL (NO NEW SERVICE) AVAILABLE In all territory served by the Company. APPLICABLE This schedule is applicable to Large Nonresidential Consumers served under Schedules 37 and 38 as of September 30, 2001. Consumers served on this schedule that subsequently select service under another rate schedule are not eligible to return to this schedule. CHARACTER OF SERVICE Sixty-hertz alternating current of such phase and voltage as the Company may have available. MONTHLY RATE The sum of the following charges per Point of Delivery:* Basic Charge Single Phase Service $20.00 - Three Phase Service $25.00 Transmission and Related Services Charge 0.221 0 per kWh Distribution Charge 3.490 0 per kWh Energy Charge** On-Peak Period 4.148 0 per kWh Off-Peak Period 2.775 0 per kWh * See Schedule 100 for applicable adjustments. ** On-Peak Period is Monday-Friday, 7 a.m.to 8 p.m. Off-Peak Period is Monday-Friday,8 p.m. to 7 a.m.; and all day Saturday and Sunday. Advice No. 00-14A Issued September 14, 2001 Effective for service Pamela Grace Lesh, Vice President on and after October 1, 2001 f- . Portland General Electric Company P.U.C. Oregon No. E-17 Original Sheet No. 38-3 SCHEDULE 38(Concluded) ADJUSTMENTS Service under this schedule is subject to adjustments approved by the Commission. — Adjustments include those summarized in Schedule 100. SPECIAL CONDITIONS Electricity delivered to the Consumer under this schedule may not be resold by the — Consumer. If the Company's transformers are used exclusively for service to the Consumer, the Company may, at its option, permit installation of metering equipment on the primary — voltage side of the transformers; in such case, billing will be based on meter registration less a deduction of 1-1/2 percent to compensate for transformer losses. — This schedule is not available to Consumers who meet all or a portion of their Electricity — requirements from sources other than the Company. TERM Service under this schedule shall not be for less than a one-year term. RULES AND REGULATIONS Service and rates under this schedule are subject to all applicable General Rules and — Regulations contained in the Tariff of which this schedule is a part:' 4' Advice No. 00.14A Issued September 14, 2001 Effective for service Pamela Grace Lesh,Vice President on and after October 1, 2001 — 0. 11 Appendix 2•• EEM Cost Estimates t t 1 t 1 1 1 f 1 I I 1 I I I 1 I I I I I I I I I 1 1 1 1 1 1 1 Tigard Library Energy Study 1/14/2003 EEM Cost Estimate Date: EEM: EEM 1: High Performance Glazing By: MPB Job: Tigard Library Job No. 7692 Estimate Source: Culver Glass Company Last Modified: Unit , Price/Unit Quantity Total Cost References/Notes Material&Labor Costs Solarban 60 Clear Glass $46.25 10,672 $493,580 Culver Glass Company Oregon Energy Code Compliant Glass $45.25 -10,672 ($482,908) Culver Glass Company Material Costs Subtotal $10,6.72 Taxes and Fees Contractor's Fee 15% $1,601 Contingency 0% $0 Business &Operating Tax 0.0% $0 State Sales Tax 0% $0 Taxes and Fees Subtotal $1,601 Total Cost I I I $12,273 Material Costs plus Taxes and Fees PAE Consulting Engineers, Inc. 1 e 1 1 1 1 1 1 I ! I I I I I I I I I I I I I I I I I I I I I I Tigard Library Energy Study 1/14/2003 EEM Cost Estimate Date: EEM: EEM 2: Increased Wall Insulation By: MPB Job: Tigard Library Job No. 7692 Estimate Source: 2003 RS Means Building Construction Cost Data Last Modified: Unit Price/Unit Quantity Total Cost References/Notes Material & Labor Costs Library Wing Walls Area: 11,400 sq ft Baseline 3-1/2"Thick R-11, 15"Wide Batt Insulation $0.52 -11,400 ($5,928) per sq. ft. wall area, includes O&P 16" O.C. Studs $25.50 -950 ($24,225) per sl.f.wall, includes O&P EEM 6"Thick, R-19, 23"Wide Batt Insulation $0.66 11,400 $7,524 per sq. ft. wall area, includes O&P 24"O.C. Studs $18.25 950 $17,338 per sl.f. wall, includes O&P Community Wing Wall Area: 6,527 sq. ft. Baseline 3/4"thick isocyanurate rigid insulation $0.83 -6,523 ($5,414) per sq. ft. wall area, includes O&P 2"thick isocyanurate rigid insulation $1.06 6,527 $6,919 per sq. ft. wall area, includes O&P Material Costs Subtotal _ -$3,787 Taxes and Fees Contractor's Fee 15% -$568 Contingency 0% $0 Business&Operating Tax 0.0% $0 State Sales Tax 0% $0 Taxes and Fees Subtotal -$568 Total Cost -$4,355 Material Costs plus Taxes and Fees PAE Consulting Engineers, Inc. 1 1 1 1 I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I 1 I 1 1 Tigard Library Energy Study 1/14/2003 EEM Cost Estimate Date: EEM: EEM 3: Increased Roof Insulation By: MPB Job: Tigard Library Job No. 7692 Estimate Source: 2003 RS Means Building Construction Cost Data Last Modified: Unit Price/Unit Quantity Total Cost References/Notes Material&Labor Costs Baseline 2.5" polyisocyanurate $0.91 -26,639 ($24,241) per sq. ft. roof area, includes O&P EEM 3.5" polyisocyanurate $1.19 26,639 $31,700 per sq. ft. roof area, includes O&P Material Costs Subtotal $7,459 Taxes and Fees Contractor's Fee 15% $1,119 Contingency 0% $0 Business&Operating Tax 0.0% $0 State Sales Tax 0% $0 Taxes and Fees Subtotal $1,119 Total Cost I I I $8,578 Material Costs plus Taxes and Fees PAE Consulting Engineers, Inc. I 1 I I 1 I I I I I I I I I I I I I I I I I I I I I I I ► I I Tigard Library Energy Study 1/14/2003 EEM Cost Estimate Date: EEM: EEM 4: Natural Ventilation By: MPB Job: Tigard Library Job No. 7692 Estimate Source: PAE Consulting Engineers, Inc. Last Modified: Unit Price/Unit Quantity Total Cost References/Notes Material & Labor Costs Lobby Air Conditioning $2.25 -4,000 ($9,000) Price/cfm Material Costs Subtotal -$9,000 Taxes and Fees Contractor's Fee 15% -$1,350 Contingency 0% $0 Business&Operating Tax 0.0% $0 State Sales Tax 0% $0 Taxes and Fees Subtotal -$1,350 Total Cost I -$10,350 (Material Costs plus Taxes and Fees PAE Consulting Engineers, Inc. I I 1 1 I I I I I I I I I I I I I I I I I I I I I I I I I I I I Tigard Library Energy Study 1/14/2003 EEM Cost Estimate Date: EEM: EEM 5: High Efficiency Boilers By: MPB Job: Tigard Library Job No. 7692 Estimate Source: Vender Quote Last Modified: Unit Price/Unit Quantity Total Cost References/Notes Material& Labor Costs Condensing Boilers $15,500 2 $31,000 Marelhurst Boiler Quote Baseline Boilers $10,000 -2 ($20,000) Marelhurst Boiler Quote Material Costs Subtotal $11,000 Taxes and Fees Contractor's Fee 0% $0 Contingency 0% $0 Business&Operating Tax 0.0% $0 State Sales Tax 0% $0 Taxes and Fees Subtotal $0 Total Cost I $11,000 (Material Costs plus Taxes and Fees PAE Consulting Engineers, Inc. i i i t I t i t t t t t i t t i t I t t t t t t t t t t it Tigard Library Energy Study 1/14/2003 EEM Cost Estimate Date: EEM: EEM 6: CO2 Sensors By: MPB Job: Tigard Library Job No. 7692 Estimate Source: PAE Consulting Engineers, Inc. Last Modified: Unit Price/Unit Quantity Total Cost References/Notes Material& Labor Costs CO2 Sensors $1,500 2 $3,000 Material Costs Subtotal $3,000 Taxes and Fees Contractor's Fee 0% $0 Contingency 0% $0 Business&Operating Tax 0.0% $0 State Sales Tax 0% $0 Taxes and Fees Subtotal $0 Total Cost I I I $3,000 (Material Costs plus Taxes and Fees PAE Consulting Engineers, Inc. 1 1 1 1 1 I 1 1 II I I I I I I I I I I I I I I I I 1 1 I I 1 Tigard Library Energy Study 1/14/2003 EEM Cost Estimate Date: EEM: EEM 7: Daylighting By: MPB Job: Tigard Library Job No. 7692 Estimate Source: Pacific Light Works Last Modified: Unit Price/Unit Quantity Total Cost References/Notes Material& Labor Costs Photocell Sensors $500 6 $3,000 Dimming Ballasts $100 210 $21,000 Material Costs Subtotal $24,000 Taxes and Fees Contractor's Fee 15% $3,600 Contingency 0% $0 Business &Operating Tax 0.0% $0 State Sales Tax 0% $0 Taxes and Fees Subtotal $3,600 Total Cost I I I $27,600 Material Costs plus Taxes and Fees PAE Consulting Engineers, Inc. 1 1 1 1 1 1 1 I I I 1 I I I 1 I I I I 1 1 I 1 I I 1 1 1 1 1 1 1 Tigard Library Energy Study 1/14/2003 EEM Cost Estimate Date: EEM: EEM 8: Point of Use Domestic Water Heating By: MPB Job: Tigard Library Job No. 7692 Estimate Source: 2003 RS Means- Plumbing Last Modified: Unit Price/Unit Quantity Total Cost References/Notes Material & Labor Costs Gas Water Heater $1,850 -2 ($3,700) Pump $200 -1 ($200) Piping $2,200 -1 ($2,200) Gas pipe $750 -1 ($750) Flue $500 -1 ($500) Electric Point of Use 2.5 Gallons $400 12 $4,800 Mans p 296 Electrical Connection $150 12 $1,800 Material Costs Subtotal -$750 Taxes and Fees Contractor's Fee 15% -$113 Contingency 0% $0 Business&Operating Tax 0.0% $0 State Sales Tax 0% $0 Taxes and Fees Subtotal -$113 Total Cost I I I -$863 (Material Costs plus Taxes and Fees PAE Consulting Engineers, Inc. 1 1 1 1 1 1 1 I 1 I I I I I I I I I I I I I I I I I I I I I I I Tigard Library Energy Study 1/14/2003 EEM Cost Estimate Date: EEM: EEM 9: Evaporative Air Cooled Water Chiller By: MPB Job: Tigard Library Job No. 7692 Estimate Source: PAE Consulting Engineers, Inc. Last Modified: Unit Price/Unit Quantity Total Cost References/Notes Material& Labor Costs 160 ton Air Cooled Water Chiller $112,000 1 $112,000 Primary Chilled Water Pumps $10,000 2 $20,000 Punderground preinsulated chilled water piping $100 200 $20,000 Chilled Water Piping $55 720 $39,600 AHU Chilled water valve sets $2,400 3 $7,200 Expansion Tank $1,200 1 $1,200 Air Separator $600 1 $600 Chemical Treatment System $1,200 1 $1,200 Deduct for removal of DX System ($0.50) 46,825 ($23,413) $0.5/cfm Material Costs Subtotal $178,388 Taxes and Fees Contractor's Fee 0% $0 Contingency 0% $0 Business &Operating Tax 0.0% $0 State Sales Tax 0% $0 Taxes and Fees Subtotal $0 Total Cost I I $178,388 Material Costs plus Taxes and Fees PAE Consulting Engineers, Inc. i i I 1 I I I I I I I I I I I I I I I I I I I I I I I Tigard Library Energy Study 1/14/2003 EEM Cost Estimate Date: EEM: EEM 10: Underfloor Ventilation System By: MPB Job: Tigard Library Job No. 7692 Estimate Source: Last Modified: Unit Price/Unit Quantity Total Cost References/Notes Material& Labor Costs Baseline Terminal Units, LP Ductwork, Diffusers, Grilles $3,000 -25 ($75,000) Price per zone Ductwork $5.50 -24,000 ($132,000) $5.5/Ib sheetmetal EEM Terminal Units, LP Ductwork, Diffusers, Grilles $3,500 25 $87,500 Ductwork $7 21,000 $147,000 Material Costs Subtotal $27,500 Taxes and Fees Contractor's Fee 0% $0 Contingency 0% $0 Business & Operating Tax 0.0% $0 State Sales Tax 0% $0 Taxes and Fees Subtotal $0 Total Cost J I $27,500 Material Costs plus Taxes and Fees PAE Consulting Engineers, Inc. Appendix 3 : PowerDOE Printouts 11 1 1 I I I 1 I I I I I I I I I I I I I I I I I I I I I I I I File: C:\Documents and Settings\Administrator\Desktop\FINAL TIGARD VALUES.TXT 1/14/2003, 5:25:04PM BASELINE REPORT- BEPS Building Energy Performance WEATHER FILE- Portland OR WYEC2 TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL • EM1 ELECTRICITY MBTU 771.8 0.0 846.7 0.0 669.4 0.0 14.3 383.3 0.0 0.0 0.0 0.0 2685.5 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1831.7 0.0 0.0 6.9 0.0 0.0 0.0 52.9 0.0 1891.5 MBTU 771.8 0.0 846.7 1831.7 669.4 0.0 21.2 383.3 0.0 0.0 52.9 0.0 4576.9 TOTAL SITE ENERGY 4576.94 MBTU 98.0 KBTU/SQFT-YR GROSS-AREA 98.0 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 9947.86 MBTU 213.1 KBTU/SQFT-YR GROSS-AREA 213.1 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 0.1 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.0 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Portland OR WYEC2 METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED UTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? PGE SCHEDULE 38 ELECTRICITY EM1 786839. KWH 57177. 0.0727 YES NW NATURAL SCHEDULE 3 NATURAL-GAS FM1 18915. THERM 15113. 0.7990 YES 72290. ENERGY COST/GROSS BLDG AREA: 1.55 ENERGY COST/NET BLDG AREA: 1.55❑ Page: 1 File: C:\Documents and Settings\Administrator\Desktop\FINAL TIGARD VALUES.TXT 1/14/2003, 5:25:04PM EEM1 REPORT- BEPS Building Energy Performance WEATHER FILE- Portland OR WYEC2 TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL EM1 ELECTRICITY MBTU 771.8 0.0 846.7 0.0 626.7 0.0 13.4 364.3 0.0 0.0 0.0 0.0 2622.8 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1693.0 0.0 0.0 6.9 0.0 0.0 0.0 52.9 0.0 1752.8 MBTU 771.8 0.0 846.7 1693.0 626.7 0.0 20.2 364.3 0.0 0.0 52.9 0.0 4375.6 TOTAL SITE ENERGY 4375.60 MBTU 93.7 KBTU/SQFT-YR GROSS-AREA 93.7 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 9621.20 MBTU 206.1 KBTU/SQFT-YR GROSS-AREA 206.1 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 0.1 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.0 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Portland OR WYEC2 METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED UTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? PGE SCHEDULE 38 ELECTRICITY EM1 768480. KWH 55882. 0.0727 YES NW NATURAL SCHEDULE 3 NATURAL-GAS FM1 17528. THERM 14011. 0.7994 YES 69893. ENERGY COST/GROSS BLDG AREA: 1.50 ENERGY COST/NET BLDG AREA: 1.50❑ - - - - - Page: 2 I 1 1 1 1 1 1 1 1 1 I I 1 1 1 I 1 1 1 1 I 1 File, C:\Documents and Settings\Administrator\Desktop\FINAL TIGARD VALUES.TXT 1/14/2003, 5:25:04PM IEM2 REPORT- REPS Building Energy Performance WEATHER FILE- Portland OR WYEC2 TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL 6.141 ELECTRICITY MBTU 771.8 0.0 846.7 0.0 678.8 0.0 14.0 380.5 0.0 0.0 0.0 0.0 2691.7 ?M1 NATURAL-GAS MBTU 0.0 0.0 0.0 1732.1 0.0 0.0 6.9 0.0 0.0 0.0 52.9 0.0 1791.9 MBTU 771.8 0.0 846.7 1732.1 678.8 0.0 20.8 380.5 0.0 0.0 52.9 0.0 4483.6 TOTAL SITE ENERGY 4483.64 MBTU 96.0 KBTU/SQFT-YR GROSS-AREA 96.0 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 9867.04 MBTU 211.3 KBTU/SQFT-YR GROSS-AREA 211.3 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 0.1 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.0 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Portland OR WYEC2 METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED JTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? ?GE SCHEDULE 38 ELECTRICITY EMI 788667. KWH 57304. 0.0727 YES 1W NATURAL SCHEDULE 3 NATURAL-GAS FM1 17919. THERM 14322. 0.7993 YES 71626. ENERGY COST/GROSS BLDG AREA: 1.53 ENERGY COST/NET BLDG AREA: 1.53❑ - - - -- ---- Page: 3 File: C:\Documents and Settings\Administrator\Desktop\FINAL TIGARD VALUES.TXT 1/14/2003, 5:25:04PM EEM3 REPORT- BEPS Building Energy Performance WEATHER FILE- Portland OR WYEC2 TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL EM1 ELECTRICITY MBTU 771.8 0.0 846.7 0.0 662.8 0.0 14.2 383.2 0.0 0.0 0.0 0.0 2678.7 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1812.5 0.0 0.0 6.9 0.0 0.0 0.0 52.9 0.0 1872.3 MBTU 771.8 0.0 846.7 1812.5 662.8 0.0 21.1 383.2 0.0 0.0 52.9 0.0 4551.0 TOTAL SITE ENERGY 4551.01 MBTU 97.5 KBTU/SQFT-YR GROSS-AREA 97.5 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 9908.49 MBTU 212.2 KBTU/SQFT-YR GROSS-AREA 212.2 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 0.1 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.0 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Portland OR WYEC2 METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED UTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? PGE SCHEDULE 38 ELECTRICITY EM1 784870. KWH 57038. 0.0727 YES NW NATURAL SCHEDULE 3 NATURAL-GAS FM1 18723. THERM 14961. 0.7991 YES 71998. ENERGY COST/GROSS BLDG AREA: 1.54 ENERGY COST/NET BLDG AREA: 1.54❑ Page: 4 1 I I I I I I I I I 1 1 1 1 1 1 1 I 1 1 1 1 1 1 1 1 1 1 1 1 1 ?ile: C:\Documents and Settings\Administrator\Desktop\FINAL TIGARD VALUES.TXT 1/14/2003, 5:25:04PM 3EM4 2EPORT- BEPS Building Energy Performance WEATHER FILE- Portland OR WYEC2 TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL Ni ELECTRICITY MBTU 771.8 0.0 846.7 0.0 646.7 0.0 13.6 342.2 0.0 0.0 0.0 0.0 2621.0 ?M1 NATURAL-GAS MBTU 0.0 0.0 0.0 1812.9 0.0 0.0 6.6 0.0 0.0 0.0 52.9 0.0 1872.4 MBTU 771.8 0.0 846.7 1812.9 646.7 0.0 20.2 342.2 0.0 0.0 52.9 0.0 4493.4 TOTAL SITE ENERGY 4493.39 MBTU 96.2 KBTU/SQFT-YR GROSS-AREA 96.2 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 9735.45 MBTU 208.5 KBTU/SQFT-YR GROSS-AREA 208.5 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 0.1 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.0 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. 2EPORT- ES-D Energy Cost Summary WEATHER FILE- Portland OR WYEC2 METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED TTILITY-RATE RESOURCE METERS UNITS/YR (5) ($/UNIT) ALL YEAR? GE SCHEDULE 38 ELECTRICITY EM1 767962. KWH 55779. 0.0726 YES 44,1 NATURAL SCHEDULE 3 NATURAL-GAS FM1 18724. THERM 14961. 0.7991 YES 70740. ENERGY COST/GROSS BLDG AREA: 1.52 ENERGY COST/NET BLDG AREA: 1.520 - - - - Page: 5 File: C:\Documents and Settings\Administrator\Desktop\FINAL TIGARD VALUES.TXT 1/14/2003, 5:25:04PM EEM5 REPORT- REPS Building Energy Performance WEATHER FILE- Portland OR WYEC2 TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL EM1 ELECTRICITY MBTU 771.8 0.0 846.7 0.0 669.4 0.0 14.3 383.3 0.0 0.0 0.0 0.0 2685.5 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1176.7 0.0 0.0 6.9 0.0 0.0 0.0 52.9 0.0 1236.5 MBTU 771.8 0.0 846.7 1176.7 669.4 0.0 21.2 383.3 0.0 0.0 52.9 0.0 3921.9 TOTAL SITE ENERGY 3921.92 MBTU 84.0 KBTU/SQFT-YR GROSS-AREA 84.0 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 9292.84 MBTU 199.0 KBTU/SQFT-YR GROSS-AREA 199.0 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 0.1 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.0 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Portland OR WYEC2 METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED UTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? PGE SCHEDULE 38 ELECTRICITY EM1 786838. KWH 57177. 0.0727 YES NW NATURAL SCHEDULE 3 NATURAL-GAS FM1 12365. THERM 9909. 0.8014 YES 67085. ENERGY COST/GROSS BLDG AREA: 1.44 ENERGY COST/NET BLDG AREA: 1.440 ------- - -- - - -- -- --- Page: 6 1 1 1 1 1 1 1 1 1 1 l I I I I I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 File: C:\Documents and Settings\Administrator\Desktop\FINAL TIGARD VALUES.TXT 1/14/2003, 5:25:04PM EEM6 REPORT- BEPS Building Energy Performance WEATHER FILE- Portland OR WYEC2 TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL EM1 ELECTRICITY MBTU 771.8 0.0 846.7 0.0 689.8 0.0 14.2 350.3 0.0 0.0 0.0 0.0 2672.8 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1642.8 0.0 0.0 6.9 0.0 0.0 0.0 52.9 0.0 1702.6 MBTU 771.8 0.0 846.7 1642.8 689.8 0.0 21.1 350.3 0.0 0.0 52.9 0.0 4375.4 TOTAL SITE ENERGY 4375.41 MBTU 93.7 KBTU/SQFT-YR GROSS-AREA 93.7 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 9720.99 MBTU 208.2 KBTU/SQFT-YR GROSS-AREA 208.2 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 0.0 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.0 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Portland OR WYEC2 METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED 7TILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? PGE SCHEDULE 38 ELECTRICITY EM1 783127. KWH 56925. 0.0727 YES VW NATURAL SCHEDULE 3 NATURAL-GAS FM1 17026. THERM 13612. 0.7995 YES 70538. ENERGY COST/GROSS BLDG AREA: 1.51 ENERGY COST/NET BLDG AREA: 1.51❑ Page: 7 File: C:\Documents and Settings\Administrator\Desktop\FINAL TIGARD VALUES.TXT 1/14/2003, 5:25:04PM 3EM7 REPORT- BEPS Building Energy Performance WEATHER FILE- Portland OR WYEC2 TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL 3M1 ELECTRICITY MBTU 627.7 0.0 846.7 0.0 635.3 0.0 13.9 363.5 0.0 0.0 0.0 0.0 2487.0 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1853.8 0.0 0.0 6.9 0.0 0.0 0.0 52.9 0.0 1913.6 MBTU 627.7 0.0 846.7 1853.8 635.3 0.0 20.8 363.5 0.0 0.0 52.9 0.0 4400.6 TOTAL SITE ENERGY 4400.62 MBTU 94.2 KBTU/SQFT-YR GROSS-AREA 94.2 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 9374.71 MBTU 200.8 KBTU/SQFT-YR GROSS-AREA 200.8 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 0.1 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.0 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Portland OR WYEC2 METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED TTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? ?GE SCHEDULE 38 ELECTRICITY EM1 728702. KWH 52855. 0.0725 YES JW NATURAL SCHEDULE 3 NATURAL-GAS FM1 19136. THERM 15289. 0.7990 YES 68144. ENERGY COST/GROSS BLDG AREA: 1.46 ENERGY COST/NET BLDG AREA: 1.46❑ Page: 8 I 1 1 1 1 1 1 1 I I 1 1 I 1 1 1 1 1 1 I I I I I I I I I I I I I I I I I I i I 1 I 1 I I I I I I I I I I I I I I I I I I I I File: C:\Documents and Settings\Administrator\Desktop\FINAL TIGARD VALUES.TXT 1/14/2003, 5:25:04PM 6EM9 REPORT- BEPS Building Energy Performance WEATHER FILE- Portland OR WYEC2 TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL 3M1 ELECTRICITY MBTU 771.8 0.0 846.7 0.0 442.1 0.0 78.5 330.5 0.0 0.0 0.0 0.0 2469.5 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1848.7 0.0 0.0 6.9 0.0 0.0 0.0 52.9 0.0 1908.5 MBTU 771.8 0.0 846.7 1848.7 442.1 0.0 85.4 330.5 0.0 0.0 52.9 0.0 4378.0 TOTAL SITE ENERGY 4378.02 MBTU 93.8 KBTU/SQFT-YR GROSS-AREA 93.8 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 9317.09 MBTU 199.5 KBTU/SQFT-YR GROSS-AREA 199.5 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 0.1 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.0 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Portland OR WYEC2 METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED JTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? ?GE SCHEDULE 38 ELECTRICITY EM1 723573. KWH 52755. 0.0729 YES 8W NATURAL SCHEDULE 3 NATURAL-GAS FM1 19085. THERM 15248. 0.7990 YES 68003. ENERGY COST/GROSS BLDG AREA: 1.46 ENERGY COST/NET BLDG AREA: 1.46❑ ----- - ---- -- - --- - -- -- Page: 9 File: C:\Documents and Settings\Administrator\Desktop\FINAL TIGARD VALUES.TXT 1/14/2003, 5:25:04PM EEM10 REPORT- BEPS Building Energy Performance WEATHER FILE- Portland OR WYEC2 TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL EM1 ELECTRICITY MBTU 771.8 0.0 848.6 0.0 565.4 0.0 12.9 329.8 0.0 0.0 0.0 0.0 2528.5 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 1803.3 0.0 0.0 6.9 0.0 0.0 0.0 - 52.9 0.0 1863.1 MBTU 771.8 0.0 848.6 1803.3 565.4 0.0 19.8 329.8 0.0 0.0 52.9 0.0 4391.6 TOTAL SITE ENERGY 4391.59 MBTU 94.1 KBTU/SQFT-YR GROSS-AREA 94.1 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 9448.63 MBTU 202.4 KBTU/SQFT-YR GROSS-AREA 202.4 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE _ 0.2 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.0 NOTE: ENERGY IS APPORTIONED HOURLY TO ALL END-USE CATEGORIES. REPORT- ES-D Energy Cost Summary WEATHER FILE- Portland OR WYEC2 METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED UTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? PGE SCHEDULE 38 ELECTRICITY EM1 740854. KWH 54018. 0.0729 YES VW NATURAL SCHEDULE 3 NATURAL-GAS FM1 18631. THERM 14887. 0.7991 YES 68905. ENERGY COST/GROSS BLDG AREA: 1.48 ENERGY COST/NET BLDG AREA: 1.48❑ - -- ---- ---- ------ - - - - Page: 10 I 1 1 1 I I I I I I I I I I I I 1 I I I I I I I I I I I I I I I 1 1 1 1 1 1 I 1 I 1 I f I 1 I I I I I 1 I I I I I I I I I I I I File: C:\Documents and Settings\Administrator\Desktop\FINAL TIGARD VALUES.TXT 1/14/2003, 5:25:04PM COMBINED REPORT- BEPS Building Energy Performance WEATHER FILE- Portland OR WYEC2 TASK MISC SPACE SPACE HEAT PUMPS VENT REFRIG HT PUMP DOMEST EXT LIGHTS LIGHTS EQUIP HEATING COOLING REJECT & AUX FANS DISPLAY SUPPLEM HOT WTR USAGE TOTAL EM1 ELECTRICITY MBTU 626.5 0.0 848.6 0.0 455.7 0.0 11.9 248.9 0.0 0.0 36.8 0.0 2228.3 Elec ELECTRICITY MBTU 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 FM1 NATURAL-GAS MBTU 0.0 0.0 0.0 868.5 0.0 0.0 6.6 0.0 0.0 0.0 0.0 0.0 875.0 MBTU 626.5 0.0 848.6 868.5 455.7 0.0 18.5 248.9 0.0 0.0 36.8 0.0 3103.4 TOTAL SITE ENERGY 3103.39 MBTU 66.5 KBTU/SQFT-YR GROSS-AREA 66.5 KBTU/SQFT-YR NET-AREA TOTAL SOURCE ENERGY 7560.09 MBTU 161.9 KBTU/SQFT-YR GROSS-AREA 161.9 KBTU/SQFT-YR NET-AREA PERCENT OF HOURS ANY SYSTEM ZONE OUTSIDE OF THROTTLING RANGE = 32.2 PERCENT OF HOURS ANY PLANT LOAD NOT SATISFIED = 0.0 REPORT- ES-D Energy Cost Summary WEATHER FILE- Portland OR WYEC2 METERED TOTAL VIRTUAL ENERGY CHARGE RATE RATE USED UTILITY-RATE RESOURCE METERS UNITS/YR ($) ($/UNIT) ALL YEAR? PGE SCHEDULE 38 ELECTRICITY EM1 Elec 652905. KWH 47557. 0.0728 YES NW NATURAL SCHEDULE 3 NATURAL-GAS FM1 8750. THERM 7037. 0.8042 YES 54594. ENERGY COST/GROSS BLDG AREA: 1.17 ENERGY COST/NET BLDG AREA: 1.17 Page: 11 i Appendix 4: File Comparisons AMR rig MOM nal 1 I I I I I 1 1 1 I I I I I I I ► 1 I I I I I I I I I ► I I ► ► File: C:\Documents and Settings\Administrator\Desktop\eeml 1/14/2003, 6:30:28PM Comparing: C:\POWERDOE\PROJECTS\Final Tigard\7692EEM1\7692EEM1.INP To: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 197 <! SHADING-COEF = 0.43 198 <1 GLASS-CONDUCT = 0.44 199 <! VIS-TRANS = 0.6 !a SHADING-COEF = 0.57 !a GLASS-CONDUCT = 0.602 !> VIS-TRANS = 0.57 • - ------ Page: 1 File: C:\Documents and Settings\Administrator\Desktop\combined 1/14/2003, 6:32:42PM Comparing: C:\POWERDOE\PROJECTS\Final Tigard\combined\combined.INP To: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 101 <! CONDUCTIVITY = 0.145 105 <! CONDUCTIVITY = 0.0119 106 <! .. 107 <! "Surf Air Film Vert (AL01)" = MATERIAL 108 <! LIBRARY-ENTRY "Surf Air Film Vert (AL01)" 109 <! .. 110 <! "Moving Air Layer" = MATERIAL 111 <! LIBRARY-ENTRY "Surf Air Film Vert (AL01)" 112 <! RESISTANCE = 0.17 113 <! . 114 <! "MinWool Batt R19 (IN03)" = MATERIAL 115 <! LIBRARY-ENTRY "MinWool Batt R19 (IN03)" Is CONDUCTIVITY = 0.0325 119 <I MATERIAL = ( "Moving Air Layer", "Face Brick 4in (BK05)", 120 <! "MinWool Batt R19 (IN03)", "GypBd 5/8in (GP02)", 121 <! "Surf Air Film Vert (AL01)" ) 122 - <I THICKNESS = ( &D, 0.52, 0.2 ) I> MATERIAL = ( "Face Brick 4in (BK05)", "Air Lay <3/4in Vert (AL11)", !> "MinWool Batt R11 (IN02)", "GypBd 5/8in (GP02)" ) 210 <! SHADING-COEF = 0.43 211 <! GLASS-CONDUCT = 0.44 212 <! VIS-TRANS = 0.6 I> SHADING-COEF = 0.57 Is GLASS-CONDUCT = 0.602 Is VIS-TRANS = 0.57 485 <! "CO2 MIN OA WEEKDAY DSCHD" = DAY-SCHEDULE-PD 486 <! TYPE = FRACTION 487 <! VALUES = ( 0, &D, &D, &D, 80, 80, &D, &D, &D, 0.12, 80, &D, &D, 488 <! &D, &D, &D, &D, &D, &D, 80, 80, &D, 0 ) 489 <! .. 490 <! "CO2 MIN OA SAT DSCHD" = DAY-SCHEDULE-PD 491 <! TYPE = FRACTION 492 <! VALUES = ( 0, &D, 80, &D, &D, &D, &D, &D, &D, 0.12, &D, &D, &D, 493 <! &D, &D, 0.342, &D, &D, 0.12, 0 ) 494 <! .. 495 <! "CO2 MIN OA SUN DSCHD" = DAY-SCHEDULE-PD 496 <! TYPE = FRACTION 497 <1 VALUES = ( 0, &D, &D, 80, &D, &D, &D, &D, &D, 0.12, 80, &D, &D, 498 <! 80, &D, 0.12, 80, &D, 0.12, 0 ) 499 <! .. 500 <I "CO2 MIN OA MEETING DSCHD" = DAY-SCHEDULE-PD 501 <I TYPE = FRACTION 502 <! VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, 0.12, &D, &D, &D, 503 <! &D, &D, 80, 80, 0.19, 0.342, 80, 80, 0.19, 0 ) 504 <! .. 598 <! "CO2 OA WSCHD" = WEEK-SCHEDULE-PD 599 <! TYPE = FRACTION 600 <! DAY-SCHEDULES = ( "CO2 MIN OA WEEKDAY DSCHD", 601 <! "CO2 MIN OA MEETING DSCHD", 80, "CO2 MIN OA MEETING DSCHD", &D, 602 <! "CO2 MIN OA SAT DSCHD", "CO2 MIN OA SUN DSCHD" ) 603 <! .. 693 <! "CO2 SENSOR SCHEDULE" = SCHEDULE-PD 694 <! TYPE = FRACTION 695 <! MONTH = ( 12 ) 696 <! DAY = ( 31 ) 697 <! WEEK-SCHEDULES = ( "CO2 OA WSCHD" ) 698 <! .. 1459 <! LIGHTING-TYPE = ( REC-FLUOR-RV ) 1461 <! LIGHT-TO-SPACE = 0 1466 <I LIGHT-TO-RETURN = 1 1491 <! DAYLIGHTING = YES Is DAYLIGHTING = NO 1558 <! DAYLIGHTING = YES Is DAYLIGHTING = NO Page: 1 1 I 1 1 I I 1 1 I I I I I I I l I I I I I I I I I I I I I I I I I I 1 I 1 I 1 I I I I I 1 I I I I I ► ► I I I I I I I I I File: C:\Documents and Settings\Administrator\Desktop\combined 1/14/2003, 6:32:42PM 1613 <! DAYLIGHTING = YES I> DAYLIGHTING = NO 1814 e! DAYLIGHTING = YES !> DAYLIGHTING = NO 1883 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 1936 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 2333 e! DAYLIGHTING = YES !> DAYLIGHTING = NO 2649 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 2804 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 2911 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 3617 c! EQUIPMENT-W/AREA = ( 1.13 ) 3618 <! DAYLIGHTING = YES !> EQUIPMENT-W/AREA = ( 1.5 ) !> DAYLIGHTING = NO 3666 <! EQUIPMENT-W/AREA = ( 1.13 ) 3667 e! DAYLIGHTING = YES !> EQUIPMENT-W/AREA = ( 1.5 ) !> DAYLIGHTING = NO 3707 <! EQUIPMENT-W/AREA = ( 0.38 ) 3732 <! EQUIPMENT-W/AREA = ( 1.13 ) 3733 <! DAYLIGHTING = YES I> EQUIPMENT-W/AREA = ( 1.5 ) !> DAYLIGHTING = NO 3780 <! EQUIPMENT-W/AREA = ( 15 ) !> EQUIPMENT-W/AREA = ( 20 ) 3804 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0.5 ) 3840 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0.5 ) 3884 <! EQUIPMENT-W/AREA = ( 1.13 ) !> EQUIPMENT-W/AREA = ( 1.5 ) 3910 <! EQUIPMENT-W/AREA = ( 1.13 ) 3911 <! DAYLIGHTING = YES I> EQUIPMENT-W/AREA = ( 1.5 ) !> DAYLIGHTING = NO 3969 <! EQUIPMENT-W/AREA = ( 0.38 ) 3970 <! DAYLIGHTING = YES !> EQUIPMENT-W/AREA = ( 0.5 ) !> DAYLIGHTING = NO 4028 <! EQUIPMENT-W/AREA = ( 0.38 ) 4029 <! DAYLIGHTING = YES !> EQUIPMENT-W/AREA = ( 0.5 ) !> DAYLIGHTING = NO 4109 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0.5 ) 4135 <! DAYLIGHTING = YES I> DAYLIGHTING = NO 4168 <! EQUIPMENT-W/AREA = ( 7.5 ) 4169 <! DAYLIGHTING = YES !> EQUIPMENT-W/AREA = ( 10 ) !> DAYLIGHTING = NO 4228 <! EQUIPMENT-W/AREA = ( 1.13 ) 4229 <! DAYLIGHTING = YES !> EQUIPMENT-W/AREA = ( 1.5 ) I> DAYLIGHTING = NO 4263 <! EQUIPMENT-W/AREA = ( 7.5 ) 4264 <! DAYLIGHTING = YES !> EQUIPMENT-W/AREA = ( 10 ) Is DAYLIGHTING = NO 4301 <! EQUIPMENT-W/AREA = ( 0.38 ) 4338 <! EQUIPMENT-W/AREA = ( 0.38 ) 4367 <! EQUIPMENT-W/AREA= ( 0.38 ) Page: 2 File: C:\Documents and Settings\Administrator\Desktop\combined 1/14/2003, 6:32:42PM 4385 <I EQUIPMENT-W/AREA = ( 0.38 ) 4386 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 4452 <! EQUIPMENT-W/AREA = ( 0.38 ) 4463 <! EQUIPMENT-W/AREA = ( 0.38 ) 4485 c! EQUIPMENT-W/AREA = ( 0.38 ) 4500 <! EQUIPMENT-W/AREA = ( 1.13 ) !s EQUIPMENT-W/AREA = ( 1.5 ) 4519 e! EQUIPMENT-W/AREA = ( 1.13 ) 4520 <! DAYLIGHTING = YES !> EQUIPMENT-W/AREA = ( 1.5 ) !> DAYLIGHTING = NO 4591 <! EQUIPMENT-W/AREA = ( 0.38 ) 4602 <! EQUIPMENT-W/AREA = ( 0.38 ) 4631 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 4649 c! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 4667 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 4685 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 4703 <! EQUIPMENT-W/AREA = ( 5 ) Is EQUIPMENT-W/AREA = ( 0 ) 4726 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 4745 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 4768 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 4787 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 4810 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 4829 <! EQUIPMENT-W/AREA = ( 0.13 ) is EQUIPMENT-W/AREA = ( 0 ) 4848 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 4904 <I EQUIPMENT-W/AREA = ( 2.5 ) !> EQUIPMENT-W/AREA = ( 0 ) 4922 <! EQUIPMENT-W/AREA = ( 0.38 ) !s EQUIPMENT-W/AREA = ( 0 ) 4946 <! EQUIPMENT-W/AREA = ( 2.5 ) !> EQUIPMENT-W/AREA = ( 0 ) 4985 <! EQUIPMENT-W/AREA = ( 0.13 ) is EQUIPMENT-W/AREA = ( 0 ) 5013 e! EQUIPMENT-W/AREA = ( 0.13 ) is EQUIPMENT-W/AREA = ( 0 ) 5031 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 5050 <! EQUIPMENT-W/AREA = ( 0.13 ) !s EQUIPMENT-W/AREA = ( 0 ) 5097 <! EQUIPMENT-W/AREA = ( 0.13 ) !s EQUIPMENT-W/AREA = ( 0 ) 5109 c! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 5127 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 5142 <I 'EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 5159 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 5187 <! EQUIPMENT-W/AREA = ( 0.13 ) Is EQUIPMENT-W/AREA = ( 0 ) 5199 <I EQUIPMENT-W/AREA = ( 0.13 ) is EQUIPMENT-W/AREA = ( 0 ) 5222 <! "Condensing Boiler PartLoadCurve" = CURVE-FIT 5223 <! TYPE = QUADRATIC - --- - -- --- -- Page: 3 I I I I i I I l 1 1 I l l l l l l 1 i l l I 1 I I I I I I I 1 I 1 1 1 1 1 1 I 1 1 I I I I 1 I I I 1 1 1 1 1 I File: C:\Documents and Settings\Administrator\Desktop\combined 1/14/2003, 6:32:42PM 5224 <! INPUT-TYPE = DATA 5225 <! INDEPENDENT = ( 1, 0.5, 0.25 ) 5226 c! DEPENDENT = ( 1, 0.48, 0.23 ) 5227 <! .. 5243 <! "Electric Meter 2" = ELEC-METER 5244 <! TYPE = UTILITY 5245 <! .. 5278 <! ELEC-METER = "Electric Meter 2" 5308 <! HEAT-SETPT-T = 140 5325 <! HEAT-INPUT-RATIO = 1.087 5326 <! HIR-FPLR _ "Condensing Boiler PartLoadCurve" 5327 <! AQUASTAT-SETPT-T = 140 !s LOCATION = ZONE 5349 <! TYPE = ELEC I> TYPE = GAS 5729 <! MIN-SUPPLY-T = 63 5730 <! COOL-SET-T = 63 5982 <1 MIN-AIR-SCH = "CO2 SENSOR SCHEDULE" 5986 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 5993 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 5999 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 6005 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 6011 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 6017 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 6024 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 6031 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 6038 <I MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 6080 <! TYPE = UHT 6081 <! HEAT-SOURCE = FURNACE I> TYPE = PSZ !s COOL-SIZING-RATI = 1.5 !> ECONO-LOCKOUT = NO !> CONTROL-ZONE _ "25 LOBBY ZONE" • Page: 4 File: C:\Documents and Settings\Administrator\Desktop\eeml 1/14/2003, 6:30:28PM Comparing: C:\POWERDOE\PROJECTS\Final Tigard\7692EEM1\7692EEM1.INP To: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 197 <! SHADING-COEF = 0.43 198 <! GLASS-CONDUCT = 0.44 199 <! VIS-TRANS = 0.6 !> SHADING-COEF = 0.57 !> GLASS-CONDUCT = 0.602 !> VIS-TRANS = 0.57 Page: 1 i l l l l l l I I I I I I I I I I I I I 1 I I 1 1 1 1 1 1 I I ► 1 ► ► 1 ► 1 1 I I 1 1 I I I 1 I 1 I I I 1 ► 1 I 1 I 1 ! 1 File: C:\Documents and Settings\Administrator\Desktop\eem9 1/14/2003, 6:32:06PM Comparing: C:\POWERDOE\PROJECTS\Final Tigard\7692EEM9\7692EEM9.INP To: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 5221 e! "CH-1 PUMP" = PUMP 5222 <! .. 5223 <! "CH-2 PUMP" = PUMP 5224 <! .. 5225 <! "CHILLED WATER LOOP PUMP" = PUMP 5226 <! .. 5248 <! "CHILLED WATER LOOP" = CIRCULATION-LOOP 5249 TYPE = CHW 5250 <! LOOP-PUMP = "CHILLED WATER LOOP PUMP" 5251 <! . 5258 <! "Chiller 1" = CHILLER 5259 <! TYPE = ELEC-HERM-REC 5260 <! ELEC-INPUT-RATIO = 0.328 5261 <! CHW-LOOP = "CHILLED WATER LOOP" 5262 <! CHW-PUMP = "CH-1 PUMP" 5263 <! CONDENSER-TYPE = AIR-COOLED 5264 <! AIR-COND-KW = 0 5265 <! .. 5266 <! "Chiller 2" = CHILLER 5267 <! TYPE = ELEC-HERM-REC 5268 <! ELEC-INPUT-RATIO = 0.328 5269 <! CHW-LOOP = "CHILLED WATER LOOP" 5270 <! CHW-PUMP = "CH-2 PUMP" 5271 <! CONDENSER-TYPE = AIR-COOLED 5272 <! AIR-COND-KW = 0 5273 <! .. 5394 <! SET-DEFAULT FOR SYSTEM 5395 <! TYPE = VAVS 5396 <! HEAT-SOURCE = HOT-WATER 5397 <! CHW-LOOP = "CHILLED WATER LOOP" 5398 <! CHW-VALVE-TYPE = TWO-WAY 5399 <! RETURN-AIR-PATH = DUCT 5400 <! MAX-SUPPLY-T = 95 5401 <! HEAT-SET-T = 55 5402 <! MIN-SUPPLY-T = 58 5403 <! COOL-SET-T = 53 5404 <! COOL-CONTROL = WARMEST 5405 <! ECONO-LOW-LIMIT = 40 5406 <! MIN-AIR-SCH = "OA SCHD" 5407 <1 FAN-SCHEDULE = "FAN SCHD" 5408 <! FAN-CONTROL = SPEED 5409 <! SUPPLY-STATIC = 5.5 5410 <! RETURN-STATIC = 2 5411 <! NIGHT-CYCLE-CTRL = CYCLE-ON-ANY 5412 <! REHEAT-DELTA-T = 40 5413 <! HW-LOOP = "HOT WATER" 5414 <! COOLING-EIR = 0.37 5415 <! .. !> 5429 <1 TYPE = VAVS I. TYPE = PVAVS 5704 <! TYPE = VAVS !> TYPE = PVAVS 5954 <! TYPE = VAVS !s TYPE = PVAVS Page: 1 File: C:\Documents and Settings\Administrator\Desktop\eem7 1/14/2003, 6:31:52PM Comparing: C:\POWERDOE\PROJECTS\Final Tigard\7692EEM7\7692EEM7.INP To: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1443 <I DAYLIGHTING = YES !> DAYLIGHTING = NO 1510 <I DAYLIGHTING = YES !s DAYLIGHTING = NO 1565 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 1766 <I DAYLIGHTING = YES !> DAYLIGHTING = NO 1835 <I DAYLIGHTING = YES !> DAYLIGHTING = NO 1888 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 2285 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 2601 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 2756 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 2863 <! DAYLIGHTING = YES DAYLIGHTING = NO 3570 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 3619 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 3684 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 3862 <! DAYLIGHTING = YES != DAYLIGHTING = NO 3921 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 3980 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 4086 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 4120 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 4180 <! DAYLIGHTING = YES I> DAYLIGHTING = NO 4215 <! DAYLIGHTING = YES !> DAYLIGHTING = NO 4333 =! DAYLIGHTING = YES I> DAYLIGHTING = NO 4464 <! DAYLIGHTING = YES !> DAYLIGHTING = NO -- — Page: 1 I I I 1 1 1 I I I I 1 1 1 1 1 1 1 I I I I 1 1 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I File: C:\Documents and Settings\Administrator\Desktop\eem6 1/14/2003, 6:31:38PM Comparing: C:\POWERDOE\PROJECTS\Final Tigard\7692EEM6\7692EEM6.INP To: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 472 <! "CO2 MIN OA WEEKDAY DSCHD" = DAY-SCHEDULE-PD 473 e! TYPE = FRACTION 474 s! VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, 0.12, &D, &D, &D, 475 <! &D, &D, &D, &D, &D, &D, &D, &D, &D, 0 ) 476 <! .. . 477 <! "CO2 MIN OA SAT DSCHD" = DAY-SCHEDULE-PD 478 <! TYPE = FRACTION 479 <! VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, 0.12, &D, &D, &D, 480 <! &D, &D, 0.342, &D, &D, 0.12, 0 ) 481 <! .. 482 <! "CO2 MIN OA SUN DSCHD" = DAY-SCHEDULE-PD 483 e! TYPE = FRACTION 484 e! VALUES _ ( 0, &D, &D, &D, &D, &D, &D, &D, &D, 0.12, &D, &D, &D, 485 <! &D, &D, 0.12, &D, &D, 0.12, 0 ) 486 <! .. 487 <! "CO2 MIN OA MEETING DSCHD" = DAY-SCHEDULE-PD 488 <! TYPE = FRACTION 489 <! VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, 0.12, &D, &D, &D, 490 <! &D, &D, &D, &D, 0.19,0.342, &D, &D, 0.19, 0 ) 491 <! .. 585 <! "CO2 OA WSCHD" = WEEK-SCHEDULE-PD 586 <! TYPE = FRACTION 587 <! DAY-SCHEDULES = ( "CO2 MIN OA WEEKDAY DSCHD", 588 <! "CO2 MIN OA MEETING DSCHD", &D, "CO2 MIN OA MEETING DSCHD", &D, 589 <! "CO2 MIN OA SAT DSCHD", "CO2 MIN OA SUN DSCHD" ) 590 <! .. 680 <! "CO2 SENSOR SCHEDULE" = SCHEDULE-PD 681 <! TYPE = FRACTION 682 <! MONTH = ( 12 ) 683 c! DAY = ( 31 ) 684 <! WEEK-SCHEDULES = ( "CO2 OA WSCHD" ) 685 <! .. 5941 <! MIN-AIR-SCH = "CO2 SENSOR SCHEDULE" 5945 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 5952 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 5958 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 5964 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 5970 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 5976 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 5983 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 5990 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 5997 <! MIN-FLOW-SCH = "COMMUNITY OCC SCHD" 6175 <! ------- - - Page: 1 File: C:\Documents and Settings\Administrator\Desktop\eem5 1/14/2003, 6:31:26PM Comparing: C:\POWERDOE\PROJECTS\Final Tigard\7692EEM5\7692EEM5.INP To: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 5164 <! "Condensing Boiler PartLoadCurve" = CURVE-FIT 5165 <! TYPE = QUADRATIC 5166 e! INPUT-TYPE = DATA 5167 <I INDEPENDENT = ( 1, 0.5, 0.25 ) 5168 <1 DEPENDENT = ( 1, 0.48, 0.23 ) 5169 =1 .. 5246 <! HEAT-SETPT-T = 140 5263 =1 HEAT-INPUT-RATIO = 1.087 5264 <! HIR-FPLR = "Condensing Boiler PartLoadCurve" 5265 <! AQUASTAT-SETPT-T = 140 !> LOCATION = ZONE — — ----- — --- Page: 1 i i i i i I I I I I 1 1 1 I I I I I I I I 1 I I I I I I I 1 1 1 II 1 I I I I 1 I 1 I 1 1 I I I I I I I I I 1 1 I 1 I 1 I 1 1 1 1 File: C:\Documents and Settings\Administrator\Desktop\eem4 1/14/2003, 6:31:10PM Comparing: C:\POWERDOE\PROJECTS\Final Tigard\7692EEM4\7692EEM4.INP To: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 293 <! "LOBBY COOLING DSCHD" = DAY-SCHEDULE-PD 294 <! TYPE = TEMPERATURE 295 <! VALUES = ( 999, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 296 <! &D, &D, &D, &D, &D, &D, &D, &D, &D, &D ) 297 <! .. 507 <! "LOBBY COOLING WSCHD" = WEEK-SCHEDULE-PD 508 <! TYPE = TEMPERATURE 509 <! DAY-SCHEDULES = ( "LOBBY COOLING DSCHD", &D, &D, &D, &D, 510 <! "LOBBY COOLING DSCHD", "LOBBY COOLING DSCHD" ) 511 <! .. 628 <! "LOBBY COOLING SCHD" = SCHEDULE-PD 629 <! TYPE = TEMPERATURE 630 <! MONTH = ( 12 ) 631 <! DAY = ( 31 ) , 632 <! WEEK-SCHEDULES = ( "LOBBY COOLING WSCHD" ) 633 <! .. 6013 <! TYPE = UHT 6014 <! HEAT-SOURCE = FURNACE I> TYPE = PSZ I> COOL-SIZING-RATI = 1.5 I> ECONO-LOCKOUT = NO !> CONTROL-ZONE _ "25 LOBBY ZONE" 6021 <! COOL-TEMP-SCH = "LOBBY COOLING SCHD" 6023 <! Page: 1 File: C:\Documents and Settings\Administrator\Desktop\eem3 1/14/2003, 6:30:56PM Comparing: C:\POWERDOE\PROJECTS\Final Tigard\7692EEM3\7692EEM3.INP To: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 52 <! CONDUCTIVITY = 0.0118 !> CONDUCTIVITY = 0.0255 128 <! THICKNESS = ( &D, 0.031, 0.333 ) I> THICKNESS = ( &D, 0.031, 0.45 ) 146 <! THICKNESS = ( &D, 0.031, 0.333 ) !> THICKNESS = ( &D, 0.031, 0.45 ) ..— _ — --- Page: 1 I I I I 1 1 I l I l I I I I I I I I 1 I I 1 1 1 1 1 I I 1 J 1 1 1 I 1 1 1 1 I I I 1 I I I I I 1 1 I I 1 1 1 I 1 I I 1 1 1 I 1 1 File: C:\Documents and Settings\Administrator\Desktop\eem2 1/14/2003, 6:30:44PM Comparing: C:\POWERDOE\PROJECTS\Final Tigard\7692EEM2\7692EEM2.INP To: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 101 <! CONDUCTIVITY = 0.145 105 <! CONDUCTIVITY = 0.0119 106 <! .. 107 <I "Surf Air Film Vert (AL01)" = MATERIAL 108 <! LIBRARY-ENTRY "Surf Air Film Vert (AL01)" 109 <! .. 110 <! "Moving Air Layer" = MATERIAL 111 <1 LIBRARY-ENTRY "Surf Air Film Vert (AL01)" 112 <! RESISTANCE = 0.17 113 <! .. 114 c! "MinWool Batt R19 (IN03)" = MATERIAL 115 <! LIBRARY-ENTRY "MinWool Batt R19 (IN03)" !> CONDUCTIVITY = 0.0325 119 <! MATERIAL = ( "Moving Air Layer", "Face Brick 4in (BK05)", 120 <! "MinWool Batt R19 (IN03)", "GypBd 5/8in (GP02)", 121 <! "Surf Air Film Vert (AL01)" ) 122 <! THICKNESS = ( &D, 0.52, 0.2 ) !> MATERIAL = ( "Face Brick 4in (BK05)", "Air Lay <3/4in Vert (AL11)", !> "MinWool Batt R11 (IN02)", "GypBd 5/8in (GP02)" ) — — - — Page: 1 File: C:\Documents and Settings\Administrator\Desktop\eem10 1/14/2003, 6:32:28PM Comparing: C:\POWERDOE\PROJECTS\Final Tigard\7692EM10\7692EM10.INP To: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1414 <I LIGHTING-TYPE = ( REC-FLUOR-RV ) 1416 <I LIGHT-TO-SPACE = 0 1421 <! LIGHT-TO-RETURN = 1 3572 <! EQUIPMENT-W/AREA = ( 1.13 ) !> EQUIPMENT-W/AREA = ( 1.5 ) 3621 <! EQUIPMENT-W/AREA = ( 1.13 ) !> EQUIPMENT-W/AREA = ( 1.5 ) 3662 <! EQUIPMENT-W/AREA = ( 0.38 ) 3687 <! EQUIPMENT-W/AREA = ( 1.13 ) !> EQUIPMENT-W/AREA = ( 1.5 ) 3735 <! EQUIPMENT-W/AREA = ( 15 ) !> EQUIPMENT-W/AREA = ( 20 ) 3759 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0.5 ) 3795 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0.5 ) 3839 <I EQUIPMENT-W/AREA = ( 1.13 ) !> EQUIPMENT-W/AREA = ( 1.5 ) 3865 <! EQUIPMENT-W/AREA = ( 1.13 ) !> EQUIPMENT-W/AREA = ( 1.5 ) 3924 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0.5 ) 3983 <! EQUIPMENT-W/AREA = ( 0.38 ) - !> EQUIPMENT-W/AREA = ( 0.5 ) 4064 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0.5 ) 4123 <! EQUIPMENT-W/AREA = ( 7.5 ) !> EQUIPMENT-W/AREA = ( 10 ) 4183 <! EQUIPMENT-W/AREA = ( 1.13 ) !> EQUIPMENT-W/AREA = ( 1.5 ) 4218 <! EQUIPMENT-W/AREA = ( 7.5 ) I> EQUIPMENT-W/AREA = ( 10 ) 4256 <! EQUIPMENT-W/AREA = ( 0.38 ) 4293 <! EQUIPMENT-W/AREA = ( 0.38 ) 4322 <! EQUIPMENT-W/AREA = ( 0.38 ) 4340 <! EQUIPMENT-W/AREA = ( 0.38 ) 4407 <I EQUIPMENT-W/AREA = ( 0.38 ) 4418 <! EQUIPMENT-W/AREA = ( 0.38 ) 4440 <! EQUIPMENT-W/AREA = ( 0.38 ) 4455 <! EQUIPMENT-W/AREA = ( 1.13 ) !> EQUIPMENT-W/AREA = ( 1.5 ) 4474 <! EQUIPMENT-W/AREA = ( 1.13 ) !> EQUIPMENT-W/AREA = ( 1.5 ) 4546 <! EQUIPMENT-W/AREA = ( 0.38 ) 4557 <! EQUIPMENT-W/AREA = ( 0.38 ) 4586 <! EQUIPMENT-W/AREA = ( 0.38 ) F> EQUIPMENT-W/AREA = ( 0 ) 4604 <I EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 4622 <! EQUIPMENT-W/AREA = ( 0.13 ) I> EQUIPMENT-W/AREA = ( 0 ) 4640 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 4658 <! EQUIPMENT-W/AREA = ( 5 ) I> EQUIPMENT-W/AREA = ( 0 ) 4681 <! EQUIPMENT-W/AREA = ( 0.13 ) I> EQUIPMENT-W/AREA = ( 0 ) 4700 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 4723 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 4742 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 4765 <! EQUIPMENT-W/AREA = ( 0.13 ) - -- Page: 1 I r 1 1 1 1 1 1 1 1 1 1 I 1 1I I II I I I r I I I I I I I I I I I I I I I I I I I File: C:\Documents and Settings\Administrator\Desktop\eem10 1/14/2003, 6:32:28PM I> EQUIPMENT-W/AREA = ( 0 ) 4784 e! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 4803 c! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 4859 <! EQUIPMENT-W/AREA = ( 2.5 ) !> EQUIPMENT-W/AREA = ( 0 ) 4877 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 4901 <I EQUIPMENT-W/AREA = ( 2.5 ) !> EQUIPMENT-W/AREA = ( 0 ) 4940 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 4968 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 4986 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 5005 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 5052 <! EQUIPMENT-W/AREA = ( 0.13 ) I> EQUIPMENT-W/AREA = ( 0 ) 5064 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 5082 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 5097 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 5114 <! EQUIPMENT-W/AREA = ( 0.38 ) !> EQUIPMENT-W/AREA = ( 0 ) 5142 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 5154 <! EQUIPMENT-W/AREA = ( 0.13 ) !> EQUIPMENT-W/AREA = ( 0 ) 6134 <! VARIABLE-TYPE = "HVAC System 2: UPPER FLOOR" 6135 <! VARIABLE-LIST = ( 17, 39, 4 ) !> VARIABLE-TYPE _ "HVAC System 3: COMMUNITY WING" I> VARIABLE-LIST = ( 17, 39 ) ------ — - --- - - Page: 2 • • Appendix 5 : Baseline In ut File • p MON IMO WINN .114 MOO BMW • WINN C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM - 1 INPUT .. 2 3 -- 4 $ 5 $ Abort, Diagnostics 6 $ ▪ 7 8 9 10 11 $ 12 $ Global Parameters 13 $ - 14 15 16 — 17 $ 18 $ Title, Run Periods, Design Days, Holidays 19 $ - 20 21 22 "Run Period 1" = RUN-PERIOD-PD 23 24 25 26 27 28 $ 29 $ Site and Building Data - 30 $ 31 32 "Default SITE-PARAMETERS" = SITE-PARAMETERS -- 33 34 35 "Default BUILD-PARAMETERS" = BUILD-PARAMETERS - 36 37 38 ▪ 39 40 $ 41 $ Materials / Layers / Constructions 42 $ 43 44 "Surf Air Film Horiz (AL03)" = MATERIAL 45 LIBRARY-ENTRY "Surf Air Film Horiz (AL03)" - 46 47 "Blt-Up Roof 3/8in (BRO1)" = MATERIAL 48 LIBRARY-ENTRY "Bit-Up Roof 3/8in (BRO1)" -- 49 50 "Polystyrene 4in (IN37)" = MATERIAL 51 LIBRARY-ENTRY "Polystyrene 4in (IN37)" 52 CONDUCTIVITY = 0.0255 53 54 "Interior Air Film" = MATERIAL 55 LIBRARY-ENTRY "Surf Air Film Vert (AL01)" - 56 RESISTANCE = 0.68 57 58 "Face Brick 4in (BK05)" = MATERIAL "" 59 LIBRARY-ENTRY "Face Brick 4in (BK05)" 60 DENSITY = 110 61 - 62 "Air Lay <3/4in Vert (AL11)" = MATERIAL 63 LIBRARY-ENTRY "Air Lay <3/4in Vert (AL11)" 64 _, 65 "MinWool Batt Rll (IN02)" = MATERIAL 66 LIBRARY-ENTRY "MinWool Batt R11 (IN02)" 67 CONDUCTIVITY = 0.058 68 69 "GypBd 5/8in (GP02)" = MATERIAL 70 LIBRARY-ENTRY "GypBd 5/8in (GP02)" 71 72 "Wood 4in (HF-B9)" = MATERIAL 73 LIBRARY-ENTRY "Wood 4in (HF-B9)" 74 ▪ 75 "GypBd 1/2in (GPO1) 2" = MATERIAL 76 LIBRARY-ENTRY "GypBd 1/2in (GPO1)" 77 - 78 "Carpet & Fiber Pad (CP01)" = MATERIAL 79 LIBRARY-ENTRY "Carpet & Fiber Pad (CP01)" 80 ▪ 81 "Conc LW 801b Bin (CC26)" = MATERIAL 82 LIBRARY-ENTRY "Conc LW 801b 8in (CC26)" 83 84 "Soil 12in" = MATERIAL +.. 85 LIBRARY-ENTRY "Soil 12in" 86 CONDUCTIVITY = 0.25 87 ▪ 88 "Slab-on-Grade Insulation" = MATERIAL 89 TYPE = RESISTANCE 90 RESISTANCE = 3 ▪ 91 92 "AcousTile (HF-E5)" = MATERIAL Page: 1 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 93 LIBRARY-ENTRY "AcousTile (HF-E5)" 94 95 "Unconditioned Floor Insulation" = MATERIAL 96 TYPE = RESISTANCE e 97 RESISTANCE = 8.6 98 99 "CMU MW 8in ConcFill (CB32)" = MATERIAL _ 100 LIBRARY-ENTRY "CMU MW 8in ConcFill (CB32)" 101 102 "Insul Bd 2in (HF-B3)" = MATERIAL 103 LIBRARY-ENTRY "Insul Bd 2in (HF-B3)" 104 CONDUCTIVITY = 0.0325 105 106 107 "Exterior Wall Layer" = LAYERS 108 MATERIAL = ( "Face Brick 4in (BK05)", "Air Lay <3/4in Vert (AL11)", 109 "MinWool Batt R11 (IN02)", "GypBd 5/8in (GP02)" ) 110 111 "Slab-on-Grade Layer" = LAYERS 112 MATERIAL = ( "Soil 12in", "Conc LW 801b Bin (CC26)", �.. 113 "Slab-on-Grade Insulation", "Carpet & Fiber Pad (CPO1)" ) 114 THICKNESS = ( &D, 0.75 ) 115 116 "INTERIOR WALL LAYERS" = LAYERS 117 MATERIAL = ( "GypBd 1/2in (GP01)", "Wood 4in (HF-B9)", 118 "GypBd 1/2in (GPO1)" ) 119 Mom 120 "Floor Layers" = LAYERS 121 MATERIAL = ( "Carpet & Fiber Pad (CPO1)", 122 "Conc LW 801b Bin (CC26)" ) .� 123 124 "Roof Layers" = LAYERS 125 MATERIAL = ( "Surf Air Film Horiz (AL03)", 126 "Blt-Up Roof 3/8in (BRO1)", "Polystyrene 4in (IN37)", 127 "Interior Air Film" ) 128 THICKNESS = ( &D, 0.031, 0.45 ) e.. 129 130 "Accoustic Ceiling Tile Layer" = LAYERS 131 MATERIAL = ( "AcousTile (HF-E5)" ) 132 .. 133 "Exposed Floor Layers" = LAYERS 134 MATERIAL = ( "Carpet & Fiber Pad (CPO1)", 135 "Unconditioned Floor Insulation", "Conc LW 801b 8in (CC26)" ) �- 136 137 "COMMUNITY ROOM EX WALL LAYERS" = LAYERS 138 MATERIAL. = ( "CMU MW 8in ConcFill (CB32)", "Insul Bd 2in (HF-B3)", 139 "GypBd 5/8in (GP02)" ) 140 THICKNESS = ( &D, 0.16667 ) 141 142 "COMMUNITY WING ROOF LAYERS" = LAYERS 143 MATERIAL = ( "Surf Air Film Horiz (AL03)", 144 "Blt-Up Roof 3/8in (BRO1)", "Polystyrene 4in (IN37)", 145 "Interior Air Film" ) 146 THICKNESS = ( &D, 0.031, 0.45 ) 147 . 148 149 "Exterior Wall Construction" = CONSTRUCTION 150 TYPE = LAYERS 151 LAYERS = "Exterior Wall Layer" 152 153 "Interior Wall Construction" = CONSTRUCTION 154 TYPE = LAYERS 155 LAYERS = "INTERIOR WALL LAYERS" 156 157 "Slab-on-Grade Construction" = CONSTRUCTION _ 158 TYPE = LAYERS 159 LAYERS = "Slab-on-Grade Layer" 160 161 "Floor Construction" = CONSTRUCTION 162 TYPE = LAYERS 163 LAYERS = "Floor Layers" 164 . 165 "Roof Construction" = CONSTRUCTION 166 TYPE = LAYERS 167 LAYERS = "Roof Layers" 168 169 "Accoustic Ceiling Tile Construct" = CONSTRUCTION 170 TYPE = LAYERS 171 LAYERS = "Accoustic Ceiling Tile Layer" 172 173 "Exposed Floor Construction" = CONSTRUCTION 174 TYPE = LAYERS 175 LAYERS = "Exposed Floor Layers" 176 177 "AIR WALL" = CONSTRUCTION 178 TYPE = U-VALUE 179 U-VALUE = 1 180 .. 181 "COMMUNITY WING WALLS CNS" = CONSTRUCTION 182 TYPE = LAYERS 183 LAYERS = "COMMUNITY ROOM EX WALL LAYERS" 184 .. Page: 2-- File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 185 "COMMUNITY WING ROOF CNS" = CONSTRUCTION 186 TYPE = LAYERS 187 LAYERS = "COMMUNITY WING ROOF LAYERS" 188 189 190 191 $ 192 $ Glass Types 193 $ - 194 195 SET-DEFAULT FOR GLASS-TYPE 196 TYPE = SHADING-COEF 197 SHADING-COEF = 0.57 - 198 GLASS-CONDUCT = 0.602 199 VIS-TRANS = 0.57 200 — 201 202 "N-E Glazing" = GLASS-TYPE 203 TYPE = SHADING-COEF — 204 205 "S-W Glazing" = GLASS-TYPE 206 TYPE = SHADING-COEF - 207 208 "Skylight Glazing" = GLASS-TYPE 209 TYPE = SHADING-COEF 210 SHADING-COEF = 0.57 211 GLASS-CONDUCT = 1.23 212 213 - 214 215 $ 216 $ Window Layers - 217 $ 218 219 - 220 221 $ 222 $ Lamps / Luminaries / Lighting Systems - 223 $ 224 225 226 - 227 228 229 $ 230 $ Day Schedules 231 $ 232 - 233 "LIBRARY WEEKDAY OCC DSCHD" = DAY-SCHEDULE-PD 234 TYPE = FRACTION 235 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, 0.2, 0.9, &D, 0.5, - 236 &D, 0.9, &D, &D, &D, &D, &D, 0.7, 0.2, 0 ) 237 238 "LIBRARY SAT OCC DCHD" = DAY-SCHEDULE-PD - 239 TYPE = FRACTION 240 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, 0.2, 0.9, &D, 0.5, 241 &D, 0.9, &D, &D, 0.7, 0.2, 0 ) _ 242 .. 243 "LIBRARY SUN OCC DSCHD" = DAY-SCHEDULE-PD 244 TYPE = FRACTION 245 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 0.2, — 246 0.9, &D, &D, &D, 0.7, 0.2, 0 ) 247 248 "LIBRARY WEEKDAY LIGHT DSCHD" = DAY-SCHEDULE-PD — 249 TYPE = FRACTION 250 VALUES = ( 0.05, &D, &D, &D, &D, &D, &D, &D, &D, 0.9, &D, &D, &D, 251 &D, &D, &D, &D, &D, &D, &D, &D, 0.9, 0.05 ) 252 253 "LIBRARY SAT LIGHT DSCHD" = DAY-SCHEDULE-PD 254 TYPE = FRACTION 255 VALUES = ( 0.05, &D, &D, &D, &D, &D, &D, &D, &D, 0.9, &D, &D, &D, 256 &D, &D, &D, &D, &D, 0.05 ) 257 258 "LIBRARY SUNDAY LIGHT DSCHD" = DAY-SCHEDULE-PD ▪ 259 TYPE = FRACTION 260 VALUES = ( 0.05, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 0.9, 261 &D, &D, &D, &D, &D, 0.05 ) ▪ 262 263 "LIBRARY WEEKDAY RECEPT DSCHD" = DAY-SCHEDULE-PD 264 TYPE = FRACTION �. 265 VALUES = ( 0.2, &D, &D, &D, &D, &D, &D, &D, &D, 0.5, 0.6, &D, &D, 266 &D, &D, &D, &D, &D, &D, &D, &D, 0.5, 0.2 ) 267 ▪ 268 "LIBRARY SAT RECEPT DCHSD" = DAY-SCHEDULE-PD 269 TYPE = FRACTION 270 VALUES = ( 0.2, &D, &D, &D, &D, &D, &D, &D, &D, 0.5, 0.6, &D, &D, 271 &D, &D, &D, &D, 0.5, 0.2 ) 272 .. 273 "LIBRARY SUN RECEP DSCHD" = DAY-SCHEDULE-PD 274 TYPE = FRACTION ▪ 275 VALUES = ( 0.2, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 0.5, 276 0.6, &D, &D, &D, 0.5, 0.2 ) Page: 3 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 277 �. 278 "LIBRARY WEEKDAY COOLING DSCHD" = DAY-SCHEDULE-PD 279 TYPE = TEMPERATURE 280 VALUES = ( 99, &D, &D, &D, &D, &D, &D, 85, 75, 75, &D, &D, &D, 281 &D, &D, &D, &D, &D, &D, &D, &D, &D, 99 ) 282 283 "LIBRARY SAT COOLING DSCHD" = DAY-SCHEDULE-PD 284 TYPE = TEMPERATURE 285 VALUES = ( 99, &D, &D, ED, &D, &D, &D, &D, 85, 75, &D, &D, &D, 286 &D, &D, &D, &D, &D, 99 ) 287 288 "LIBRARY SUN COOLING DSCHD" = DAY-SCHEDULE-PD 289 TYPE = TEMPERATURE 290 VALUES = ( 99, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 85, 75, 291 &D, &D, &D, &D, ED, 99 ) 292 293 "LIBRARY WEEKDAY HEATING DSCHD" = DAY-SCHEDULE-PD 294 TYPE = TEMPERATURE 295 VALUES = ( 65, &D, &D, &D, &D, &D, &D, &D, 68.5, 70, 70, &D, &D, 296 &D, &D, &D, &D, &D, &D, &D, &D, 70, 65 ) 297 .. 298 "LIBRARY SAT HEATING DSCHD" = DAY-SCHEDULE-PD 299 TYPE = TEMPERATURE _ 300 VALUES = ( 65, &D, &D, &D, &D, &D, &D, &D, 68.5, 70, &D, &D, &D, 301 &D, &D, &D, &D, &D, 65 ) 302 303 "LIBRARY SUN HEATING DSCHD" = DAY-SCHEDULE-PD 304 TYPE = TEMPERATURE 305 VALUES = ( 65, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 68.5, 70, 306 &D, ED, &D, &D, &D, 65 ) 307 308 "LIBRARY SAT OA DSCHD" = DAY-SCHEDULE-PD 309 TYPE = FRAC/DESIGN 310 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, -999, 311 &D, &D, &D, &D, &D, &D, 0 ) 312 .. 313 "LIBRARY SUN OA DSCHD" = DAY-SCHEDULE-PD 314 TYPE = FRAC/DESIGN 315 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, -999, 316 &D, &D, &D, &D, &D, &D, 0 ) 317 318 "COMMUNITY WEEKDAY OCC DSCHD" = DAY-SCHEDULE-PD 319 TYPE = FRACTION 320 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, 0.2, &D, &D, &D, 321 &D, &D, &D, &D, &D, &D, &D, ED, &D, 0 ) 322 323 "COMMUNITY SAT OCC DCHD" = DAY-SCHEDULE-PD 324 TYPE = FRACTION 325 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, 0.2, &D, &D, &D, 326 &D, &D, 0.9, &D, &D, 0.2, 0 ) 327 328 "COMMUNITY SUN OCC DSCHD" = DAY-SCHEDULE-PD 329 TYPE = FRACTION 330 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 0.2, 331 &D, &D, &D, &D, &D, &D, 0 ) 332 333 "COMMUNITY WEEKDAY LIGHT DSCHD" = DAY-SCHEDULE-PD 334 TYPE = FRACTION 335 VALUES = ( 0.05, &D, &D, &D, ED, &D, &D, &D, &D, 0.9, &D, &D, &D, 336 &D, &D, &D, &D, &D, &D, &D, &D, 0.9, 0.05 ) 337 .. 338 "COMMUNITY SAT LIGHT DSCHD" = DAY-SCHEDULE-PD 339 TYPE = FRACTION 340 VALUES = ( 0.05, &D, ED, &D, &D, &D, &D, &D, &D, 0.9, &D, &D, &D, 341 &D, ED, &D, ED, ED, 0.05 ) 342 343 "COMMUNITY SUNDAY LIGHT DSCHD" = DAY-SCHEDULE-PD 344 TYPE = FRACTION _ 345 VALUES = ( 0.05, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, ED, 0.9, 346 ED, &D, &D, &D, &D, 0.05 ) 347 348 "COMMUNITY WEEKDAY RECEPT DSCHD" = DAY-SCHEDULE-PD 349 TYPE = FRACTION 350 VALUES = ( 0.2, &D, &D, &D, &D, &D, &D, &D, &D, 0.5, 0.6, &D, &D, 351 &D, &D, &D, &D, &D, &D, &D, &D, 0.5, 0.2 ) 352 353 "COMMUNITY SAT RECEPT DCHSD" = DAY-SCHEDULE-PD 354 TYPE = FRACTION 355 VALUES = ( 0.2, &D, &D, &D, &D, &D, &D, &D, &D, 0.5, 0.6, &D, &D, 356 &D, &D, &D, &D, 0.5, 0.2 ) 357 .. 358 "COMMUNITY SUN RECEP DSCHD" = DAY-SCHEDULE-PD 359 TYPE = FRACTION 360 VALUES = ( 0.2, &D, ED, &D, &D, &D, &D, &D, &D, ED, &D, &D, 0.5, 361 0.6, &D, &D, &D, 0.5, 0.2 ) 362 363 "COMMUNITY WEEKDAY COOLING DSCHD" = DAY-SCHEDULE-PD 364 TYPE = TEMPERATURE 365 VALUES = ( 99, &D, &D, &D, &D, &D, &D, 85, 75, 75, &D, &D, &D, 366 &D, &D, &D, &D, &D, &D, &D, &D, &D, 99 ) 367 .. 368 "COMMUNITY SAT COOLING DSCHD" = DAY-SCHEDULE-PD Page: 4"' Zile: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM - 369 TYPE = TEMPERATURE 370 VALUES = ( 99, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 85, 75, 371 &D, &D, &D, &D, &D, &D, 99 ) ▪ 372 373 "COMMUNITY SUN COOLING DSCHD" = DAY-SCHEDULE-PD 374 TYPE = TEMPERATURE - 375 VALUES = ( 99 ) 376 377 "COMMUNITY WEEKDAY HEATING DSCHD" = DAY-SCHEDULE-PD 378 TYPE = TEMPERATURE 379 VALUES = ( 65, &D, &D, &D, &D, &D, &D, &D, 68.5, 70, 70, &D, &D, 380 &D, &D, &D, &D, &D, &D, &D, &D, 70, 65 ) _ 381 .. 382 "COMMUNITY SAT HEATING DSCHD" = DAY-SCHEDULE-PD 383 TYPE = TEMPERATURE 384 VALUES = ( 65, &D, &D, &D, &D, &D, &D, &D, &D, &D, 68.5, 70, 70, -" 385 &D, &D, &D, &D, &D, &D, 65 ) 386 387 "COMMUNITY SUN HEATING DSCHD" = DAY-SCHEDULE-PD - 388 TYPE = TEMPERATURE 389 VALUES = ( 65 ) 390 .- 391 "COMMUNITY SAT OA DSCHD" = DAY-SCHEDULE-PD 392 TYPE = FRAC/DESIGN 393 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, -999, 394 &D, &D, &D, &D, &D, &D, 0 ) 395 396 "COMMUNITY SUN OA DSCHD" = DAY-SCHEDULE-PD 397 TYPE = FRAC/DESIGN ▪ 398 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, -999, 399 &D, &D, &D, &D, &D, &D, 0 ) 400 - 401 "PAE OA DSCHD" = DAY-SCHEDULE-PD 402 TYPE = FRAC/DESIGN 403 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, &D, -999, &D, &D, - 404 &D, &D, &D, &D, &D, &D, &D, &D, &D, 0 ) 405 406 "ALWAYS ON DSCHD" = DAY-SCHEDULE-PD 407 TYPE = ON/OFF 408 VALUES = ( 1 ) 409 410 "PAE FAN DSCHD" = DAY-SCHEDULE-PD MM. 411 TYPE = ON/OFF/FLAG 412 VALUES = ( 0, &D, &D, 0, &D, 0, &D, &D, &D, &D, 1, &D, &D, &D, 413 &D, &D, &D, &D, &D, &D, &D, &D, 0 ) ▪ 414 415 "PAE SAT FAN DSCHD" = DAY-SCHEDULE-PD 416 TYPE = ON/OFF/FLAG ▪ 417 VALUES = ( 0, &D, &D, 0, &D, &D, &D, 0, &D, 1, &D, &D, 1, &D, &D, 418 &D, &D, &D, &D, 0, &D, &D, 0 ) 419 - 420 "PAE FAN SUN FAN DCSHD" = DAY-SCHEDULE-PD 421 TYPE = ON/OFF/FLAG 422 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 1, &D, 423 &D, &D, &D, &D, 0 ) 424 425 "FAN OFF DSCHD" = DAY-SCHEDULE-PD 426 TYPE = ON/OFF/FLAG - 427 VALUES = ( 0, &D, &D, 0, &D, &D, &D, &D, 0, &D, &D, &D, &D, &D, 428 &D, &D, &D, &D, &D, &D, &D, &D, 0 ) 429 .. "• 430 "OEC SCHD-A WEEKDAY INFILTR DSCHD" = DAY-SCHEDULE-PD 431 TYPE = FRACTION 432 VALUES = ( 1, &D, &D, &D, &D, &D, &D, 0.85, &D, &D, &D, &D, &D, - 433 &D, &D, &D, &D, &D, &D, &D, &D, 1 ) 434 435 "OEC SCHD-A SAT INFILTR DSCHD" = DAY-SCHEDULE-PD 436 TYPE = FRACTION 437 VALUES = ( 1, &D, &D, &D, &D, &D, &D, &D, &D, 0.85, &D, &D, &D, 438 &D, &D, &D, &D, &D, 1 ) _ 439 440 "OEC SCHD-A SUN INFILTR DSCHD" = DAY-SCHEDULE-PD 441 TYPE = FRACTION 442 VALUES = ( 1, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, &D, 0.85, "'" 443 &D, &D, &D, &D, &D, 1 ) 444 445 "COMMUNITY MEETING OCC DSCHD" = DAY-SCHEDULE-PD 446 TYPE = FRACTION 447 VALUES = ( 0, &D, &D, &D, &D, &D, &D, &D, &D, 0.2, &D, &D, &D, 448 &D, &D, &D, &D, 0.5, 0.9, &D, &D, 0.5, 0 ) �. 449 450 "LOADS DSCHD" = DAY-SCHEDULE-PD 451 TYPE = FRACTION 452 VALUES = ( 1 ) 453 454 "SCHEDULE 38 WDSCHD" = DAY-SCHEDULE-PD 455 TYPE = FLAG 456 VALUES = ( 0, &D, &D, &D, &D, &D, &D, 1, &D, &D, &D, &D, &D, &D, 457 &D, &D, &D, &D, &D, &D, 0 ) 458 .. ▪ 459 "SCHEDULE 38 WENDSCHD" = DAY-SCHEDULE-PD 460 TYPE = FLAG Page: 5 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 461 VALUES = ( 0 ) 462 463 "SCHD38 DSCHD" = DAY-SCHEDULE-PD 464 TYPE = FRACTION 465 VALUES = ( 0.06486, &D, &D, &D, &D, &D, &D, 0.07859, &D, &D, &D, 466 &D, &D, &D, &D, &D, &D, &D, &D, &D, 0.06486 ) 467 468 "SCHD38 WENDSCHD" = DAY-SCHEDULE-PD 469 TYPE = FRACTION 470 VALUES = ( 0.06486 ) 471 .. 472 473 $ 474 $ Week Schedules 475 $ 476 477 "LIBRARY OCCUPANCY WSCHD" = WEEK-SCHEDULE-PD 478 TYPE = FRACTION 479 DAY-SCHEDULES = ( "LIBRARY WEEKDAY OCC DSCHD", &D, &D, &D, &D, 480 "LIBRARY SAT DCC DCHD", "LIBRARY SUN OCC DSCHD" ) 481 482 "LIBRARY LIGHTING WSCHD" = WEEK-SCHEDULE-PD 483 TYPE = FRACTION 484 DAY-SCHEDULES = ( "LIBRARY WEEKDAY LIGHT DSCHD", &D, &D, &D, &D, 485 "LIBRARY SAT LIGHT DSCHD", "LIBRARY SUNDAY LIGHT DSCHD" ) 486 487 "LIBRARY RECEPTACLE WSCHD" = WEEK-SCHEDULE-PD 488 TYPE = FRACTION 489 DAY-SCHEDULES = ( "LIBRARY WEEKDAY RECEPT DSCHD", &D, &D, &D, &D, 490 "LIBRARY SAT RECEPT DCHSD", "LIBRARY SUN RECEP DSCHD" ) 491 492 "LIBRARY INFILTRATION WSCHD" = WEEK-SCHEDULE-PD 493 TYPE = FRACTION 494 DAY-SCHEDULES = ( "OEC SCHD-A WEEKDAY INFILTR DSCHD", &D, &D, &D, &D, 495 "OEC SCHD-A SAT INFILTR DSCHD", "OEC SCHD-A SUN INFILTR DSCHD" ) 496 .. 497 "LIBRARY COOLING WSCHD" = WEEK-SCHEDULE-PD 498 TYPE = TEMPERATURE 499 DAY-SCHEDULES = ( "LIBRARY WEEKDAY COOLING DSCHD", &D, &D, &D, &D, 500 "LIBRARY SAT COOLING DSCHD", "LIBRARY SUN COOLING DSCHD" ) 501 502 "LIBRARY HEATING DSCHD" = WEEK-SCHEDULE-PD 503 TYPE = TEMPERATURE 504 DAY-SCHEDULES = ( "LIBRARY WEEKDAY HEATING DSCHD", &D, &D, &D, &D, 505 "LIBRARY SAT HEATING DSCHD", "LIBRARY SUN HEATING DSCHD" ) 506 .. 507 "COMMUNITY OCC WSCHD" = WEEK-SCHEDULE-PD 508 TYPE = FRACTION 509 DAY-SCHEDULES = ( "COMMUNITY WEEKDAY OCC DSCHD", 510 "COMMUNITY MEETING OCC DSCHD", &D, "COMMUNITY MEETING OCC DSCHD", 511 &D, "COMMUNITY SAT OCC DCHD", "COMMUNITY SUN OCC DSCHD" ) 512 .. _ 513 "COMMUNITY LIGHTING WSCHD" = WEEK-SCHEDULE-PD 514 TYPE = FRACTION 515 DAY-SCHEDULES = ( "COMMUNITY WEEKDAY LIGHT DSCHD", &D, &D, &D, &D, 516 "COMMUNITY SAT LIGHT DSCHD", "COMMUNITY SUNDAY LIGHT DSCHD" ) 517 518 ""COMMUNITY RECEP WSCHD" = WEEK-SCHEDULE-PD 519 TYPE = FRACTION 520 DAY-SCHEDULES = ( "COMMUNITY WEEKDAY RECEPT DSCHD", &D, &D, &D, &D, 521 "COMMUNITY SAT RECEPT DCHSD", "COMMUNITY SUN RECEP DSCHD" ) 522 .. 523 "COMMUNITY INFILTRATION WSCHD" = WEEK-SCHEDULE-PD 524 TYPE = FRACTION 525 DAY-SCHEDULES = ( "OEC SCHD-A WEEKDAY INFILTR DSCHD", &D, &D, &D, &D, 526 "OEC SCHD-A SAT INFILTR DSCHD", "OEC SCHD-A SUN INFILTR DSCHD" ) 527 528 "COMMUNITY COOLING WSCHD" = WEEK-SCHEDULE-PD _ 529 TYPE = TEMPERATURE 530 DAY-SCHEDULES = ( "COMMUNITY WEEKDAY COOLING DSCHD", &D, &D, &D, &D, 531 "COMMUNITY SAT COOLING DSCHD", "COMMUNITY SUN COOLING DSCHD" ) 532 . 533 "COMMUNITY HEATING DSCHD" = WEEK-SCHEDULE-PD 534 TYPE = TEMPERATURE 535 DAY-SCHEDULES = ( "COMMUNITY WEEKDAY HEATING DSCHD", &D, &D, &D, &D, 536 "COMMUNITY SAT HEATING DSCHD", "COMMUNITY SUN HEATING DSCHD" ) 537 538 "PAE OA WSCHD" = WEEK-SCHEDULE-PD �. 539 TYPE = FRAC/DESIGN 540 DAY-SCHEDULES = ( "PAE OA DSCHD", &D, &D, &D, &D, 541 "LIBRARY SAT OA DSCHD", "LIBRARY SUN OA DSCHD" ) 542 543 "ALWAYS ON WSCHD" = WEEK-SCHEDULE-PD 544 TYPE = ON/OFF 545 DAY-SCHEDULES = ( "ALWAYS ON DSCHD", &D, &D, &D, &D, "ALWAYS ON DSCHD" ) 546 547 "PAE FAN WSCHD" = WEEK-SCHEDULE-PD 548 TYPE = ON/OFF/FLAG — 549 DAY-SCHEDULES = ( "PAE FAN DSCHD", &D, &D, &D, &D, "PAE SAT FAN DSCHD", 550 "PAE FAN SUN FAN DCSHD" ) 551 .. — 552 "FAN OFF WSCHD" = WEEK-SCHEDULE-PD Page: 6"- c'ile: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM - 553 TYPE = ON/OFF/FLAG 554 DAY-SCHEDULES = ( "FAN OFF DSCHD", &D, &D, &D, &D, "FAN OFF DSCHD" ) 555 —' 556 "LOADS WSCHD" =WEEK-SCHEDULE-PD 557 TYPE = FRACTION 558 DAY-SCHEDULES = ( "LOADS DSCHD", &D, &D, &D, &D, "LOADS DSCHD" ) - 559 560 "SCHEDULE 38 WSCHD" = WEEK-SCHEDULE-PD 561 TYPE = FLAG ▪ 562 DAY-SCHEDULES = ( "SCHEDULE 38 WDSCHD", &D, &D, &D, &D, 563 "SCHEDULE 38 WENDSCHD" ) 564 565 566 $ 567 $ Annual Schedules 568 $ - 569 570 "OA SCHD" = SCHEDULE-PD 571 TYPE = FRAC/DESIGN - 572 MONTH = ( 12 ) 573 DAY = ( 31 ) 574 WEEK-SCHEDULES = ( "PAE OA WSCHD" ) r. 575 576 "ALWAYS ON SCHD" = SCHEDULE-PD 577 TYPE = ON/OFF 578 MONTH = ( 12 ) 579 DAY = ( 31 ) 580 WEEK-SCHEDULES = ( "ALWAYS ON WSCHD" ) 581 582 "FAN SCHD" = SCHEDULE-PD 583 TYPE = ON/OFF/FLAG 584 MONTH = ( 12 ) 585 DAY = ( 31 ) 586 WEEK-SCHEDULES = ( "PAE FAN WSCHD" ) 587 - 588 "OCCUPANCY SCHD" = SCHEDULE-PD 589 TYPE = FRACTION 590 MONTH = ( 12 ) — 591 DAY = ( 31 ) 592 WEEK-SCHEDULES = ( "LIBRARY OCCUPANCY WSCHD" ) 593 594 "LIGHTING SCHD" = SCHEDULE-PD 595 TYPE = FRACTION 596 MONTH = ( 12 ) 597 DAY = ( 31 ) 598 WEEK-SCHEDULES = ( "LIBRARY LIGHTING WSCHD" ) 599 600 "RECEPTACLE SCHD" = SCHEDULE-PD 601 TYPE = FRACTION 602 MONTH = ( 12 ) 603 DAY = ( 31 ) — 604 WEEK-SCHEDULES = ( "LIBRARY RECEPTACLE WSCHD" ) 605 606 "INFILTRATION SCHD" = SCHEDULE-PD 607 TYPE = FRACTION 608 MONTH = ( 12 ) 609 DAY = ( 31 ) 610 WEEK-SCHEDULES = ( "LIBRARY INFILTRATION WSCHD" ) 611 612 "COOLING SCHD" = SCHEDULE-PD 613 TYPE = TEMPERATURE " 614 MONTH = ( 12 ) 615 DAY = ( 31 ) 616 WEEK-SCHEDULES = ( "LIBRARY COOLING WSCHD" ) 617 618 "HEATING SCHD" = SCHEDULE-PD 619 TYPE = TEMPERATURE ▪ 620 MONTH = ( 12 ) 621 DAY = ( 31 ) 622 WEEK-SCHEDULES = ( "LIBRARY HEATING DSCHD" ) 623 624 "COMMUNITY OCC SCHD" = SCHEDULE-PD 625 TYPE = FRACTION 626 MONTH = ( 12 ) ▪ 627 DAY = ( 31 ) 628 WEEK-SCHEDULES = ( "COMMUNITY OCC WSCHD" ) 629 ▪ 630 "COMMUNITY LIGHTING SCHD" = SCHEDULE-PD 631 TYPE = FRACTION 632 MONTH = ( 12 ) 633 DAY = ( 31 ) 634 WEEK-SCHEDULES = ( "COMMUNITY LIGHTING WSCHD" ) 635 ▪ 636 "COMMUNITY RECEP SCHD" = SCHEDULE-PD 637 TYPE = FRACTION 638 MONTH = ( 12 ) 639 DAY = ( 31 ) 640 WEEK-SCHEDULES = ( "COMMUNITY RECEP WSCHD" ) 641 642 "LOADS SCHD" = SCHEDULE-PD 643 TYPE = FRACTION 644 MONTH = ( 12 ) S Page: 7 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 645 DAY = ( 31 ) 646 WEEK-SCHEDULES = ( "LOADS WSCHD" ) 647 648 "PGE SCHEDULE 38 SCHD" = SCHEDULE-PD 649 TYPE = FLAG 650 MONTH = ( 12 ) 651 DAY = ( 31 ) 652 WEEK-SCHEDULES = ( "SCHEDULE 38 WSCHD" ) 653 654 655 656 $ 657 $ Polygons 658 $ 659 660 "Polygon 1" POLYGON 661 VI = ( 15, 0 ) 662 V2 = ( 15, -15 ) 663 V3 = ( 60, -15 ) 664 V4 = ( 60, 0 ) 665 666 "Polygon 2" = POLYGON 667 V1 = ( 0, 0 ) 668 V2 = ( 15, 0 ) 669 V3 = ( 15, 31 ) 670 V4 = ( 0, 31 ) 671 672 "Polygon 3" = POLYGON 673 Vl = ( 0, 0 ) 674 V2 = ( 33, 0 ) 675 V3 = ( 33, 33 ) 676 V4 = ( 27, 33 ) 677 V5 = ( 27, 58 ) 678 V6 = ( 0, 58 ) 679 680 "Polygon 4" = POLYGON 681 V1 = ( 0, 0 ) 682 V2 = ( 41, 0 ) 683 V3 = ( 41, 7 ) 684 V4 = ( 21, 7 ) 685 V5 = ( 21, 33 ) 686 V6 = ( 0, 33 ) 687 688 "Polygon 5" = POLYGON 689 VI = ( 0, 0 ) 690 V2 = ( 6, 0 ) 691 V3 = ( 6, 10 ) 692 V4 = ( 6, 32 ) 693 V5 = ( 3, 32 ) .� 694 V6 = ( 0, 32 ) 695 696 "Polygon 6" = POLYGON 697 VI = ( 0, 0 ) 698 V2 = ( 0, 15 ) 699 V3 = ( -15, 15 ) 700 V4 = ( -15, 32 ) 701 V5 = ( -35, 27 ) 702 V6 = ( -45, 24.4 ) 703 V7 = ( -39, 0 ) 704 V8 = ( -35.5, -13 ) 705 V9 = ( 0, -4 ) 706 707 "Polygon 7" = POLYGON 708 V1 = ( -24, 39 ) 709 V2 = ( -34.5, 79.75 ) 710 V3 = ( -45, 65 ) 711 V4 = ( -38, 35.75 ) 712 .. _ 713 "Polygon 8" = POLYGON 714 VI = ( -66.5, 27 ) 715 V2 = ( -38, 35.75 ) 716 V3 = ( -45, 65 ) 717 V4 = ( -80, 65 ) 718 719 "Polygon 9" = POLYGON 720 V1 = ( -84.5, 22.75 ) 721 V2 = ( -66.5, 27 ) 722 V3 = ( -80, 65 ) 723 V4 = ( -100.5, 79.75 ) 724 725 "Polygon 10" = POLYGON 726 V1 = ( 0, 0 ) 727 V2 = ( 0, 10 ) 728 V3 = ( 3, 10 ) 729 V4 = ( 3, 26 ) 730 V5 = ( -7, 26 ) 731 V6 = ( -7, 0 ) 732 733 "Polygon 11" = POLYGON 734 V1 = ( 0, 0 ) 735 V2 = ( 0, -27 ) 736 V3 = ( 18, -27 ) Page: 8 file: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 737 V4 = ( 18, -16 ) 738 V5 = ( 13, -16 ) 739 V6 = ( 13, 0 ) -•• 740 741 "Polygon 12" = POLYGON 742 V1 = ( 1, -1 ) - 743 V2 = ( 1, 32 ) 744 V3 = ( -42, 32 ) 745 V4 = ( -42, 25 ) 746 V5 = ( -8, 25 ) 747 V6 = ( -8, -1 ) 748 749 "Polygon 13" = POLYGON 750 V1 = ( 0, 0 ) 751 V2 = ( 90, 0 ) 752 V3 = ( 90, 32 ) "" 753 V4 = ( 60, 32 ) 754 V5 = ( 60, 64 ) 755 V6 = ( 30, 64 ) - 756 V7 = ( 30, 32 ) 757 V8 = ( 0, 32 ) 758 .... 759 "Polygon 14" = POLYGON 760 V1 = ( 0, 0 ) 761 V2 = ( 15, 0 1 762 V3 = ( 15, 32 ) 763 V4 = ( 0, 32 ) 764 765 "Polygon 15" = POLYGON ▪ 766 V1 = ( 15, 0 ) 767 V2 = ( 30, 0 ) 768 V3 = ( 30, 32 ) - 769 V4 = ( 15, 32 ) 770 771 "Polygon 1 - Mirror" = POLYGON - 772 V1 = ( 0, 0 ) 773 V2 = ( 0, 93 ) 774 V3 = ( -15, 93 ) - 775 V4 = ( -15, 15 ) 776 777 "Polygon 2 - Mirror" = POLYGON 778 V1 = ( 0, 0 ) - 779 V2 = ( 46, 0 ) 780 V3 = ( 31, 15 ) 781 V4 = ( 0, 15 ) - 782 783 "Polygon 3 - Mirror" = POLYGON 784 V1 = ( 0, 0 ) - 785 V2 = ( 58, 0 ) 786 V3 = ( 58, 27 ) 787 V4 = ( 33, 27 ) - 788 V5 = ( 33, 33 ) 789 V6 = ( 0, 33 ) 790 791 "Polygon 4 - Mirror" = POLYGON 792 V1 = ( 0, 0 ) 793 V2 = ( 33, 0 ) 794 V3 = ( 33, 21 ) 795 V4 = ( 7, 21 ) 796 V5 = ( 7, 41 ) 797 V6 = ( 0, 41 ) - 798 799 "Polygon 5 - Mirror" = POLYGON 800 V1 = ( 0, 0 ) - 801 V2 = ( 32, 0 ) 802 V3 = ( 32, 6 1 803 V4 = ( 10, 6 ) - 804 V5 = ( 10, 37 ) 805 V6 = ( 0, 37 ) 806 807 "Polygon 7 - Mirror" = POLYGON - 808 V1 = ( 0, 0 ) 809 V2 = ( 0, -15 ) 810 V3 = ( 50, -15 ) .... 811 V4 = ( 65, 0 ) 812 813 "Polygon 8 - Mirror" = POLYGON 814 V1 = ( 0, 0 ) 815 V2 = ( 15, 15 ) 816 V3 = ( 15, 35 ) - 817 V4 = ( 0, 50 ) 818 819 "Polygon 9 - Mirror" = POLYGON - 820 V1 = ( 0, 0 ) 821 V2 = ( 65, 0 ) 822 V3 = ( 50, 15 ) 823 V4 = ( 0, 15 ) mon 824 825 "Polygon 10 - Mirror" = POLYGON 826 V1 = ( 0, 0 ) - 827 V2 = ( 0, -7 ) 828 V3 = ( 26, -7 ) Page: 9 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 829 V4 = ( 26, 3 ) 830 V5 = ( 10, 3 ) 831 V6 = ( 10, 0 ) 832 833 "Polygon 11 - Mirror" = POLYGON 834 V1 = ( 0, 0 ) 835 V2 = ( 0, 13 ) 836 V3 = ( -16, 13 ) 837 V4 = ( -16, 18 ) 838 V5 = ( -27, 18 ) 839 V6 = ( -27, 0 ) 840 841 "Polygon 12 - Mirror" = POLYGON 842 V1 = ( 0, 1 ) 843 V2 = ( 0, -10 ) 844 V3 = ( 25, -10 ) 845 V4 = ( 25, -42 ) 846 V5 = ( 32, -42 ) 847 V6 = ( 32, -22 ) 848 V7 = ( 52, -22 ) 849 V8 = ( 52, 1 ) 850 .. 851 "Polygon 13 - Mirror" = POLYGON 852 V1 = ( 0, 0 ) 853 V2 = ( 32, 0 ) 854 V3 = ( 32, 30 ) 855 V4 = ( 64, 30 ) 856 V5 = ( 64, 60 ) 857 V6 = ( 32, 60 ) 858 V7 = ( 32, 90 ) 859 V8 = ( 0, 90 ) 860 861 "Polygon 14 - Mirror" = POLYGON 862 V1 = ( 0, 0 ) 863 V2 = ( 64, 0 ) 864 V3 = ( 64, 15 ) 865 V4 = ( 15, 15 ) 866 867 "Polygon 15 - Mirror" = POLYGON 868 V1 = ( 0, 0 ) 869 V2 = ( 15, 15 ) 870 V3 = ( 15, 30 ) 871 V4 = ( 0, 30 ) 872 .. 873 "Mirror Poly 1" = POLYGON 874 V1 = ( -1, 1 ) 875 V2 = ( -1, -9 ) 876 V3 = ( 25, -9 ) 877 V4 = ( 25, -42 ) 878 V5 = ( 32, -42 ) 879 V6 = ( 32, -22 ) 880 V7 = ( 52, -22 ) 881 V8 = ( 52, 1 ) 882 . 883 "Mirror Poly 2" = POLYGON 884 V1 = ( -1, 1 ) 885 V2 = ( -1, -8 ) 886 V3 = ( 25, -8 ) 887 V4 = ( 25, -42 ) . , 888 V5 = ( 32, -42 ) 889 V6 = ( 32, -22 ) 890 V7 = ( 52, -22 ) 891 V8 = ( 52, 1 ) 892 893 "Polygon 33" = POLYGON 894 V1 = ( 0, 0 ) 895 V2 = ( 32, 0 ) 896 V3 = ( 32, 7 ) 897 898 "Polygon 34" = POLYGON 899 V1 = ( 0, 0 ) 900 V2 = ( 32, 0 ) - 901 V3 = ( 0, 7 ) 902 903 "Polygon 35" = POLYGON 904 V1 = ( 0, 0 ) 905 V2 = ( 58, 0 ) 906 V3 = ( 58, 39 ) 907 V4 = ( 10, 39 ) 908 V5 = ( 10, 22 ) 909 V6 = ( 0, 22 ) 910 - 911 "Polygon 35 - Mirror" = POLYGON 912 V1 = ( 0, 0 ) 913 V2 = ( 22, 0 ) .-. 914 V3 = ( 22, 10 ) 915 V4 = ( 39, 10 ) 916 V5 = ( 39, 58 ) 917 V6 = ( 0, 58 ) 918 .. 919 "Mirror Poly 3" = POLYGON 920 Vl = ( 0, 0 ) Page: 10- dile: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM ▪ 921 V2 = ( -5, 1.5 ) 922 V3 = ( -17, -50 ) 923 V4 = ( -4, 0 ) 924 V5 = ( -13, -35.5 ) 925 V6 = ( 0, -39 ) 926 V7 = ( 24.4, -45 ) 927 V8 = ( 27, -35 ) 928 V9 = ( 32, -15 ) 929 V10 = ( 15, -15 ) 930 V11 = ( 15, 0 ) 931 932 "Mirror Poly 4" = POLYGON 933 V1 = ( 0, 0 ) 934 V2 = ( 0, -15 ) 935 V3 = ( 30, -15 ) 936 V4 = ( 42, 0 ) 937 938 "Mirror Poly 5" = POLYGON 939 V1 = ( 0, 0 ) 940 V2 = ( 60, 0 ) 941 V3 = ( 40, 15 ) 942 V4 = ( 0, 15 ) .� 943 944 "Polygon 39" = POLYGON 945 V1 = ( -100.5, 79.75 ) 946 V2 = ( -80, 65 ) 947 V3 = ( -45, 65 ) 948 V4 = ( -34.5, 79.75 ) 949 - 950 "Polygon 39 - Mirror" = POLYGON 951 V1 = ( 0, 0 ) 952 V2 = ( 0, 66 ) - 953 V3 = ( -15, 55 ) 954 V4 = ( -15, 20 ) 955 956 "Mirror Poly 6" = POLYGON 957 V1 = ( 0, 0 ) 958 V2 = ( 40, 0 ) - 959 V3 = ( 30, 36 ) 960 V4 = ( 0, 36 ) 961 962 "Mirror Poly 7" = POLYGON 963 V1 = ( 0, 0 ) 964 V2 = ( 40, 0 ) 965 V3 = ( 30, 33 ) ▪ 966 V4 = ( 0, 33 ) 967 968 "Polygon 43" = POLYGON ▪ 969 V1 = ( -68, 0 ) 970 V2 = ( -53.5, 0 ) 971 V3 = ( -55.5, 18 ) - 972 V4 = ( -70, 13.75 ) 973 974 "Polygon 43 - Mirror" = POLYGON 975 VI = ( 0, -70 ) 976 V2 = ( 15, -75 ) 977 V3 = ( 19, -60 ) 978 V4 = ( 0, -55 ) 979 980 "Polygon 45" = POLYGON 981 V1 = ( -53.5, 0 ) 982 V2 = ( -24, 0 ) 983 V3 = ( -30, 24.4 ) 984 V4 = ( -55.5, 18 ) - 985 986 "Mirror Poly 8" = POLYGON 987 Vl = ( 0, 2 ) ▪ 988 V2 = ( 0, 66 ) 989 V3 = ( -15, 55 ) 990 V4 = ( -15, 20 ) 991 992 "Polygon 47" = POLYGON 993 V1 = ( 0, 15 ) 994 V2 = ( 15, 15 ) 995 V3 = ( 15, 37 ) 996 V4 = ( 0, 32 ) 997 ▪ 998 "Polygon 48" = POLYGON 999 V1 = ( 0, 48 ) 1000 V2 = ( 0, 32 ) r•1001 V3 = ( 15, 37 ) 1002 V4 = ( 15, 30 ) 1003 V5 = ( 35, 30 ) ▪ 1004 V6 = ( 35, 48 ) 1005 1006 "Polygon 48 - Mirror" = POLYGON _1007 V1 = ( 48, 0 ) 1008 V2 = ( 48, 35 ) 1009 V3 = ( 30, 35 ) 1010 V4 = ( 30, 15 ) ▪ 1011 V5 = ( 37, 15 ) 1012 V6 = ( 32, 0 ) Page: 11 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 1013 r. 1014 "Mirror Poly 9" = POLYGON 1015 V1 = ( 0, 0 ) 1016 V2 = ( 31, 0 ) 1017 V3 = ( 31, 15 ) 1018 V4 = ( 0, 15 ) 1019 _ 1020 "Mirror Poly 10" = POLYGON 1021 V1 = ( 0, 15 ) 1022 V2 = ( 0, 93 ) 1023 V3 = ( -15, 93 ) 1024 V4 = ( -15, 15 ) 1025 1026 "Mirror Poly 11 POLYGON 1027 V1 = ( 0, 15 ) 1028 V2 = ( 0, 61 ) 1029 V3 = ( -15, 61 ) 1030 V4 = ( -15, 15 ) 1031 1032 "Mirror Poly 12" = POLYGON 1033 V1 = ( 0, 0 ) 1034 V2 = ( 10, 0 ) 1035 V3 = ( 10, 3 ) 1036 V4 = ( 10, 6 ) 1037 VS = ( 10, 37 ) 1038 V6 = ( 0, 37 ) 1039 1040 "Mirror Poly 13" = POLYGON 1041 V1 = ( 0, 0 ) 1042 V2 = ( 32, 0 ) 1043 V3 = ( 32, 3 ) 1044 V4 = ( 32, 6 ) 1045 V5 = ( 10, 6 ) 1046 V6 = ( 0, 6 ) 1047 1048 "Polygon 55" = POLYGON 1049 V1 = ( 0, 0 ) 1050 V2 = ( 35, 0 ) 1051 V3 = ( 21, 32 ) 1052 V4 = ( 0, 32 ) 1053 1054 "Mirror Poly 14" = POLYGON 1055 V1 = ( 0, 0 ) 1056 V2 = ( 40, 0 ) 1057 V3 = ( 30, 32 ) 1058 V4 = ( 0, 32 ) 1059 1060 "Mirror Poly 15" = POLYGON 1061 V1 = ( 0, 0 ) 1062 V2 = ( 40, 0 ) 1063 V3 = ( 30, 30 ) 1064 V4 = ( 0, 30 ) 1065 1066 "Mirror Poly 16" = POLYGON 1067 V1 = ( 0, 2 ) 1068 V2 = ( 0, 66 ) 1069 V3 = ( -17, 55 ) 1070 V4 = ( -15, 20 ) 1071 1072 "Mirror Poly 17" = POLYGON 1073 V1 = ( 0, 2 ) 1074 V2 = ( 0, 65 ) 1075 V3 = ( -17, 54 ) 1076 V4 = ( -15, 20 ) 1077 1078 "Mirror Poly 18" = POLYGON 1079 V1 = ( 0, 2 ) 1080 V2 = ( 0, 64 ) 1081 V3 = ( -17, 54 ) 1082 V4 = ( -15, 20 ) 1083 1084 "Mirror Poly 19" = POLYGON 1085 V1 = ( 0, 0 ) 1086 V2 = ( 40, 0 ) 1087 V3 = ( 30, 31 ) 1088 V4 = ( 0, 31 ) 1089 1090 "Mirror Poly 20" = POLYGON 1091 V1 = ( 0, 0 ) 1092 V2 = ( 0, -15 ) 1093 V3 = ( 30, -15 ) 1094 V4 = ( 42.5, 0 ) 1095 1096 "Mirror Poly 21" = POLYGON 1097 V1 = ( 0, 2 ) 1098 V2 = ( 0, 64 ) 1099 V3 = ( -16, 53 ) 1100 V4 = ( -15, 20 ) 1101 1102 "Polygon 47 - Mirror" = POLYGON 1103 V1 = ( 15, 0 ) 1104 V2 = ( 32, 0 ) Page: 12'- cile: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM - 1105 V3 = ( 37, 15 ) 1106 V4 = ( 15, 15 ) 1107 1108 "Polygon 6 - Mirror" = POLYGON 1109 V1 = ( 0, 0 ) 1110 V2 = ( -4, 0 ) -- 1111 V3 = ( -13, -35.5 ) 1112 V4 = ( 0, -39 ) 1113 V5 = ( 24.4, -45 ) - 1114 V6 = ( 27, -35 ) 1115 V7 = ( 32, -15 ) 1116 V8 = ( 15, -15 ) _ 1117 V9 = ( 15, 0 ) 1118 1119 "Polygon 45 - Mirror" = POLYGON 1120 V1 = ( 0, -55 ) 1121 V2 = ( 19, -60 ) 1122 V3 = ( 25.5, -30 ) 1123 V4 = ( 0, -24 ) 1124 1125 "Mirror Poly 22" = POLYGON 1126 V1 = ( 0, 2 ) -•. 1127 V2 = ( 0, 64 ) 1128 V3 = ( -16.5, 53 ) 1129 V4 = ( -15, 20 ) 1130 1131 "Polygon 55 - Mirror" = POLYGON 1132 V1 = ( 0, 0 ) 1133 V2 = ( 32, 0 ) 1134 V3 = ( 32, 21 ) 1135 V4 = ( 0, 35 ) 1136 --' 1137 "Mirror Poly 23" = POLYGON 1138 V1 = ( 0, 15 ) 1139 V2 = ( 15, 15 ) - 1140 V3 = ( 15, 30 ) 1141 V4 = ( 0, 30 ) 1142 1143 "Mirror Poly 24" = POLYGON 1144 V1 = ( 0, 0 ) 1145 V2 = ( 64, 0 ) 1146 V3 = ( 64, 15 ) 1147 V4 = ( 0, 15 ) 1148 1149 "Mirror Poly 25" = POLYGON 1150 V1 = ( -1, 1 ) 1151 V2 = ( -1, -8 ) 1152 V3 = ( 25, -8 ) "" 1153 V4 = ( 25, -42 ) 1154 V5 = ( 32, -42 ) 1155 V6 = ( 32, -8 ) - 1156 V7 = ( 52, -8 ) 1157 V8 = ( 52, 1 ) 1158 - 1159 "Mirror Poly 26" = POLYGON 1160 V1 = ( -1, 1 ) 1161 V2 = ( -1, -8 ) _ 1162 V3 = ( 25, -8 ) 1163 V4 = ( 25, -42 ) 1164 V5 = ( 32, -42 ) 1165 V6 = ( 32, -12 ) -- 1166 V7 = ( 52, -12 ) 1167 V8 = ( 52, 1 ) 1168 - 1169 "Polygon 73" = POLYGON 1170 V1 = ( 0, 0 ) 1171 V2 = ( 45, 0 ) ▪ 1172 V3 = ( 31, 32 ) 1173 V4 = ( 0, 32 ) 1174 1175 "Mirror Poly 27" = POLYGON 1176 V1 = ( 0, 15 ) 1177 V2 = ( 30, 15 ) 1178 V3 = ( 30, 30 ) m" 1179 V4 = ( 0, 30 ) 1180 1181 "Mirror Poly 28" = POLYGON - 1182 V1 = ( 0, 15 ) 1183 V2 = ( 32, 15 ) 1184 V3 = ( 32, 30 ) ▪ 1185 V4 = ( 0, 30 ) 1186 1187 "Polygon 73 - Mirror" = POLYGON ▪ 1188 V1 = ( 0, 0 ) 1189 V2 = ( 32, 0 ) 1190 V3 = ( 32, 31 ) 1191 V4 = ( 0, 45 ) 1192 1193 "Mirror Poly 29" = POLYGON 1194 V1 = ( 0, 0 ) 1195 V2 = ( 32, 0 ) 1196 V3 = ( 32, 15 ) m. Page: 13 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 1197 V4 = ( 0, 15 ) 1198 1199 "Polygon 78" = POLYGON 1200 Vl = ( 0, 0 ) 1201 V2 = ( 90, 0 ) 1202 V3 = ( 90, 32.5 ) 1203 V4 = ( 0, 32.5 ) 1204 1205 "Polygon 79" = POLYGON 1206 V1 = ( 0, 0 ) 1207 V2 = ( 30, 0 ) OMNI 1208 V3 = ( 30, 17 ) 1209 V4 = ( 0, 17 ) 1210 1211 "Polygon 80" = POLYGON 1212 Vl = ( 0, 0 ) 1213 V2 = ( 30, 0 ) 1214 V3 = ( 30, 15.5 ) 1215 V4 = ( 0, 15.5 ) 1216 .. 1217 "Polygon 81" = POLYGON 1218 Vl = ( 0, 0 ) 1219 V2 = ( 15, 0 ) 1220 V3 = ( 0, 4 ) 1221 1222 "Polygon 82" = POLYGON 1223 V1 = ( 0, 0 ) MINN 1224 V2 = ( 15, 0 ) 1225 V3 = ( 15, 4 ) 1226 . 1227 "Mirror Poly 30" = POLYGON 1228 V1 = ( 0, 0 ) 1229 V2 = ( 32, 0 ) 1230 V3 = ( 32, 21 ) 1231 V4 = ( 0, 36 ) 1232 _ 1233 "Mirror Poly 31" = POLYGON 1234 V1 = ( 0, 0 ) 1235 V2 = ( 32, 0 ) 1236 V3 = ( 32, 31 ) 1237 V4 = ( 0, 46 ) 1238 1239 "Mirror Poly 32" = POLYGON 1240 V1 = ( 0, 15 ) 1241 V2 = ( 0, 60 ) 1242 V3 = ( -15, 60 ) .� 1243 V4 = ( -15, 15 ) 1244 1245 "Polygon 86" = POLYGON 1246 V1 = ( -20, 27 ) 1247 V2 = ( -24, 39 ) 1248 V3 = ( -33, 37 ) _ 1249 V4 = ( -30, 24.4 ) 1250 1251 "Mirror Poly 33" = POLYGON 1252 V1 = ( 39, -24 ) 1253 V2 = ( 35.75, -38 ) 1254 V3 = ( 65, -45 ) 1255 V4 = ( 79.75, -34.5 ) 1256 1257 "Mirror Poly 34" = POLYGON 1258 V1 = ( 79.75, -100.5 ) 1259 V2 = ( 79.75, -34.5 ) 1260 V3 = ( 65, -45 ) 1261 V4 = ( 65, -80 ) 1262 1263 "Mirror Poly 35" = POLYGON 1264 Vl = ( 22.75, -84.5 ) 1265 V2 = ( 79.75, -100.5 ) 1266 V3 = ( 65, -80 ) 1267 V4 = ( 27, -66.5 ) 1268 1269 "Mirror Poly 36" = POLYGON 1270 V1 = ( 27, -66.5 ) 1271 V2 = ( 65, -80 ) 1272 V3 = ( 65, -45 ) 1273 V4 = ( 35.75, -38 ) 1274 1275 "Mirror Poly 37" = POLYGON 1276 V1 = ( 0, -70 ) 1277 V2 = ( 13.75, -70 ) _ 1278 V3 = ( 18, -55.5 ) 1279 V4 = ( 0, -55 ) 1280 1281 "Mirror Poly 38" = POLYGON 1282 V1 = ( 0, -69 ) 1283 V2 = ( 13.75, -70 ) 1284 V3 = ( 18, -55.5 ) 1285 V4 = ( 0, -55 ) 1286 1287 "Mirror Poly 39" = POLYGON 1288 V1 = ( 0, -68 ) Page: 14-- File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 1289 V2 = ( 13.75, -70 ) 1290 V3 = ( 18, -55.5 ) 1291 V4 = ( 0, -55 ) 1292 1293 "Mirror Poly 40" = POLYGON 1294 V1 = ( 0, -55 ) 1295 V2 = ( 18, -55.5 ) 1296 V3 = ( 24.4, -30 ) 1297 V4 = ( 0, -24 ) - 1298 1299 "Mirror Poly 41" = POLYGON 1300 V1 = ( 0, -53.5 ) 1301 V2 = ( 18, -55.5 ) 1302 V3 = ( 24.4, -30 ) 1303 V4 = ( 0, -24 ) 1304 -- 1305 "Mirror Poly 42" = POLYGON 1306 V1 = ( 0, -68 ) 1307 V2 = ( 13.75, -70 ) 1308 V3 = ( 18, -55.5 ) 1309 V4 = ( 0, -53.5 ) 1310 .. ▪ 1311 "Polygon 97" = POLYGON 1312 V1 = ( -81.5, 10.75 ) 1313 V2 = ( -70, 13.75 ) - 1314 V3 = ( -63.5, 15.25 ) 1315 V4 = ( -66.5, 27 ) 1316 V5 = ( -84.5, 22.75 ) 1317 1318 "Polygon 98" = POLYGON 1319 V1 = ( -63.5, 15.25 ) 1320 V2 = ( -55.5, 18 ) - 1321 V3 = ( -30, 24.4 ) 1322 V4 = ( -33, 37 ) 1323 V5 = ( -38, 35.75 ) - 1324 V6 = ( -66.5, 27 ) 1325 1326 "Polygon 98 - Mirror" = POLYGON — 1327 V1 = ( 15.25, -63.5 ) 1328 V2 = ( 27, -66.5 ) 1329 V3 = ( 35.75, -38 ) ▪ 1330 V4 = ( 37, -33 ) 1331 V5 = ( 24.4, -30 ) 1332 V6 = ( 18, -55.5 ) 1333 1334 "Polygon 97 - Mirror" = POLYGON 1335 V1 = ( 10.75, -81.5 ) 1336 V2 = ( 22.75, -84.5 ) - 1337 V3 = ( 27, -66.5 ) 1338 V4 = ( 15.25, -63.5 ) 1339 V5 = ( 13.75, -70 ) - 1340 1341 "Polygon 86 - Mirror" = POLYGON 1342 V1 = ( 27, -20 ) - 1343 V2 = ( 24.4, -30 ) 1344 V3 = ( 37, -33 ) 1345 V4 = ( 39, -24 ) 1346 1347 "Mirror Poly 43" = POLYGON 1348 V1 = ( -1, 1 ) 1349 V2 = ( -1, -8 ) - 1350 V3 = ( 25, -8 ) 1351 V4 = ( 25, -42 ) 1352 V5 = ( 32, -42 ) - 1353 V6 = ( 32, 1 ) 1354 1355 ▪ 1356 1357 $ 1358 $ Wall Parameters ▪ 1359 $ 1360 1361 1362 1363 $ 1364 $ Fixed and Building Shades 1365 $ —' 1366 1367 1368 "Bldg Shade 1" = BUILDING-SHADE ▪ 1369 X = 58 1370 Y = -9.5 1371 Z = 15 ▪ 1372 HEIGHT = 70 1373 WIDTH = 32 1374 1375 "Bldg Shade 2" = BUILDING-SHADE 1376 X = 58 1377 Y = -41.5 1378 Z = 15 _ 1379 HEIGHT = 70 1380 WIDTH = 32 Page: 15 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 1381 AZIMUTH = 90 1382 1383 "Bldg Shade 3" = BUILDING-SHADE 1384 X = 26 1385 Y = -9.5 1386 Z = 15 1387 HEIGHT = 70 1388 WIDTH = 32 1389 AZIMUTH = -90 1390 1391 1392 1393 $ 1394 $ Misc Cost Related Objects .� 1395 $ 1396 1397 1398 1399 "Default BASELINE" = BASELINE 1400 .. 1401 1402 1403 $ ********************************************************* 1404 $ ** ** 1405 $ ** Floors / Spaces / Walls / Windows / Doors ** 1406 $ ** ** 1407 $ ********************************************************* 1408 1409 SET-DEFAULT FOR SPACE 1410 PEOPLE-SCHEDULE = "OCCUPANCY SCHD" 1411 LIGHTING-SCHEDUL = ( "LIGHTING SCHD" ) 1412 EQUIP-SCHEDULE = ( "RECEPTACLE SCHD" ) 1413 INF-SCHEDULE _ "INFILTRATION SCHD" Nom 1414 INF-METHOD = AIR-CHANGE 1415 LIGHTING-W/AREA = ( 1.2 ) 1416 EQUIPMENT-W/AREA = ( 0.5 ) 1417 LIGHT-REF-POINT1 = ( &D, &D, 6 ) 1418 LIGHT-REF-POINT2 = ( &D, &D, 6 ) 1419 AREA/PERSON = 200 1420 .. �- 1421 1422 SET-DEFAULT FOR EXTERIOR-WALL 1423 SHADING-SURFACE = YES 1424 1425 1426 SET-DEFAULT FOR UNDERGROUND-WALL 1427 1428 1429 1430 "Floor 1" = FLOOR 1431 SHAPE = BOX 1432 FLOOR-HEIGHT = 14 1433 WIDTH = 100 1434 DEPTH = 100 1435 SPACE-HEIGHT = 12 1436 .. 1437 "1 ENTRY HALLWAY" = SPACE 1438 X = 15 1439 SHAPE = BOX 1440 WIDTH = 61 1441 DEPTH = 15 1442 AIR-CHANGES/HR = 0.4 1443 DAYLIGHTING = NO 1444 LIGHT-REF-POINT1 = ( 30, 10 ) 1445 .. _ 1446 "Exterior Wall 38" = EXTERIOR-WALL 1447 CONSTRUCTION = "Exterior Wall Construction" 1448 LOCATION = SPACE-V1 1449 1450 "Window 5" = WINDOW 1451 GLASS-TYPE = "S-W Glazing" 1452 X = 11 1453 Y = 2 1454 HEIGHT = 12 1455 WIDTH = 10 1456 1457 "Window 6" = WINDOW 1458 GLASS-TYPE _ "S-W Glazing" 1459 X = 41 1460 Y = 2 1461 HEIGHT = 12 1462 WIDTH = 10 1463 1464 "Interior Wall 1" = INTERIOR-WALL 1465 CONSTRUCTION = "Slab-on-Grade Construction" 1466 INT-WALL-TYPE = ADIABATIC 1467 LOCATION = BOTTOM 1468 .. 1469 "Interior Wall 61" = INTERIOR-WALL 1470 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 1471 INT-WALL-TYPE = ADIABATIC �. 1472 LOCATION = TOP Page: 16� File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM ▪ 1473 1474 "Interior Wall 108" = INTERIOR-WALL 1475 NEXT-TO - "25 LOBBY" ▪ 1476 CONSTRUCTION = "Interior Wall Construction" 1477 LOCATION = SPACE-V4 1478 " 1479 "Interior Wall 109" INTERIOR-WALL 1480 NEXT-TO = "14 ELEV MACH/JAN" 1481 CONSTRUCTION "Interior Wall Construction" 1482 X = 20 1483 WIDTH 20 1484 LOCATION = SPACE-V3 1485 1486 "Interior Wall 110" = INTERIOR-WALL 1487 NEXT-TO = "2 CIRC DESK SOUTH PERIM" 1488 CONSTRUCTION = "AIR WALL" • 1489 LOCATION = SPACE-V2 1490 1491 "Interior Wall 111" INTERIOR-WALL ". 1492 NEXT-TO - "19 INFO DESK HALLWAY" 1493 CONSTRUCTION = "AIR WALL" 1494 WIDTH = 41 . 1495 LOCATION SPACE-V3 1496 1497 "Undrgrnd Wall 1" = UNDERGROUND-WALL . 1498 CONSTRUCTION "Slab-on-Grade Construction" 1499 HEIGHT = 1 1500 LOCATION = SPACE-V1 1501 1502 "2 CIRC DESK SOUTH PERIM" - SPACE 1503 X - 76 1504 SHAPE = BOX ▪ 1505 WIDTH 36 1506 DEPTH = 15 1507 AIR-CHANGES/HR = 0.4 • 1508 LIGHTING-W/AREA = ( 1.2 ) 1509 EQUIPMENT-W/AREA = ( 2 ) 1510 DAYLIGHTING - NO = 1511 LIGHT-REF-POINT1 = ( 18, 10 ) 1512 1513 "Exterior Wall 39" = EXTERIOR-WALL 1514 CONSTRUCTION " "Exterior Wall Construction" 1515 LOCATION SPACE-V1 1516 1517 "Window 7" = WINDOW ▪ 1518 GLASS-TYPE "S-W Glazing" 1519 X = 10 1520 Y 2 ▪ 1521 HEIGHT = 12 1522 WIDTH = 10 1523 1524 "Interior Wall 2" = INTERIOR-WALL 1525 CONSTRUCTION - "Slab-on-Grade Construction" 1526 INT-WALL-TYPE = ADIABATIC 1527 LOCATION = BOTTOM 1528 1529 "Interior Wall 62" - INTERIOR-WALL . 1530 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 1531 INT-WALL-TYPE = ADIABATIC 1532 LOCATION = TOP 1533 1534 "Interior Wall 112" = INTERIOR-WALL 1535 NEXT-TO = "19 INFO DESK HALLWAY" 1536 CONSTRUCTION = "RIR WALL" • 1537 X = 17 1538 WIDTH = 17 1539 LOCATION = SPACE-V3 . 1540 1541 "Interior Wall 113" = INTERIOR-WALL 1542 NEXT-TO = "19 INFO DESK HALLWAY' . 1543 CONSTRUCTION - "AIR WALL" 1544 WIDTH = 19 1545 LOCATION = SPACE-V3 1546 ▪ 1547 "Interior Wall 114" - INTERIOR-WALL 1548 NEXT-TO = "3 CIRC WORKROOM SOUTH PERIM" 1549 CONSTRUCTION = "Interior Wall Construction" 4 1550 LOCATION = SPACE-V2 1551 1552 "Undrgrnd Wall 2" = UNDERGROUND-WALL . 1553 CONSTRUCTION = "Slab-on-Grade Construction" 1554 HEIGHT = 1 1555 LOCATION = SPACE-V1 . 1556 1557 "3 CIRC WORKROOM SOUTH PERIM" = SPACE 1558 X = 112 1559 SHAPE = BOX 1560 WIDTH = 59 1561 DEPTH = 15 1562 AIR-CHANGES/HR = 0.4 ' 1563 LIGHTING-W/AREA = ( 1.2 ) 1564 EQUIPMENT-W/AREA = ( 2 ) • Page: 17 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 1565 DAYLIGHTING = NO 1566 LIGHT-REF-POINT1 = ( 30, 10 ) 1567 . 1568 "Exterior Wall 40" = EXTERIOR-WALL 1569 CONSTRUCTION = "Exterior Wall Construction" 1570 LOCATION = SPACE-V1 1571 .. 1572 "Window 8" = WINDOW 1573 GLASS-TYPE = "S-W Glazing" 1574 X = 10 1575 Y = 2 1576 HEIGHT = 12 1577 WIDTH = 10 1578 1579 "Window 9" = WINDOW 1580 GLASS-TYPE = "S-W Glazing" 1581 X = 36 1582 Y = 2 1583 HEIGHT = 12 1584 WIDTH = 10 1585 1586 "Interior Wall 3" = INTERIOR-WALL 1587 CONSTRUCTION = "Slab-on-Grade Construction" 1588 INT-WALL-TYPE = ADIABATIC 1589 LOCATION = BOTTOM 1590 1591 "Interior Wall 63" = INTERIOR-WALL 1592 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 1593 INT-WALL-TYPE = ADIABATIC 1594 LOCATION = TOP 1595 .. 1596 "Interior Wall 115" = INTERIOR-WALL 1597 NEXT-TO = "21 CIRC WORKROOM INTERIOR" 1598 CONSTRUCTION = "AIR WALL" 1599 LOCATION = SPACE-V3 1600 .. 1601 "Interior Wall 116" = INTERIOR-WALL 1602 NEXT-TO = "4 ELEC" 1603 CONSTRUCTION = "Interior Wall Construction" 1604 LOCATION = SPACE-V2 1605 1606 "Undrgrnd Wall 3" = UNDERGROUND-WALL 1607 CONSTRUCTION = "Slab-on-Grade Construction" 1608 HEIGHT = 1 1609 LOCATION = SPACE-V1 1610 .. 1611 "4 ELEC" = SPACE 1612 X = 171 1613 SHAPE = BOX 1614 WIDTH = 13 1615 DEPTH = 14 1616 AIR-CHANGES/HR = 0.89 1617 NUMBER-OF-PEOPLE = 0 1618 LIGHTING-W/AREA = ( 0.8 ) 1619 EQUIPMENT-W/AREA = ( 10 ) 1620 .. 1621 "Exterior Wall 41" = EXTERIOR-WALL 1622 CONSTRUCTION = "Exterior Wall Construction" 1623 LOCATION = SPACE-V1 1624 .. 1625 "Exterior Wall 42" = EXTERIOR-WALL 1626 CONSTRUCTION = "Exterior Wall Construction" 1627 LOCATION = SPACE-V2 1628 1629 "Interior Wall 4" = INTERIOR-WALL 1630 CONSTRUCTION = "Slab-on-Grade Construction" 1631 INT-WALL-TYPE = ADIABATIC 1632 LOCATION = BOTTOM 1633 1634 "Interior Wall 64" = INTERIOR-WALL 1635 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 1636 INT-WALL-TYPE = ADIABATIC 1637 LOCATION = TOP 1638 1639 "Undrgrnd Wall 4" = UNDERGROUND-WALL 1640 CONSTRUCTION = "Slab-on-Grade Construction" 1641 HEIGHT = 1 1642 LOCATION = SPACE-V1 1643 1644 "Undrgrnd Wall 24" = UNDERGROUND-WALL 1645 CONSTRUCTION = "Slab-on-Grade Construction" • 1646 HEIGHT = 1 1647 LOCATION = SPACE-V2 1648 1649 "5 DONATIONS" = SPACE 1650 X = 192 1651 Y = 14 1652 SHAPE = BOX 1653 WIDTH = 21 1654 DEPTH = 13 1655 AIR-CHANGES/HR = 0.75 • 1656 LIGHTING-W/AREA = ( 1.2 ) Page: 18 ' tile: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 1657 AREA/PERSON = 600 1658 1659 "Exterior Wall 44" = EXTERIOR-WALL --- 1660 CONSTRUCTION = "Exterior Wall Construction" 1661 LOCATION SPACE-V1 1662 ▪ 1663 "Exterior Wall 45" - EXTERIOR-WALL 1664 CONSTRUCTION = "Exterior Wall Construction" 1665 LOCATION = SPACE-V2 — 1666 1667 "Interior Wall 5" = INTERIOR-WALL 1668 CONSTRUCTION = "Slab-on-Grade Construction" - 1669 INT-WALL-TYPE = ADIABATIC 1670 LOCATION = BOTTOM 1671 1672 "Interior Wall 65" = INTERIOR-WALL — 1673 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 1674 INT-WALL-TYPE = ADIABATIC 1675 LOCATION = TOP — 1676 1677 "Undrgrnd Wall 5" = UNDERGROUND-WALL 1678 CONSTRUCTION = "Slab-on-Grade Construction" — 1679 HEIGHT = 1 1680 LOCATION = SPACE-V1 1681 1682 "Undrgrnd Wall 25" = UNDERGROUND-WALL 1683 CONSTRUCTION = "Slab-on-Grade Construction" 1684 HEIGHT = 1 1685 LOCATION = SPACE-V2 - 1686 1687 "6 MAIL/LOAD" = SPACE 1688 X = 192 1689 Y 27 1690 SHAPE = BOX 1691 WIDTH = 21 -- 1692 DEPTH = 20 1693 AIR-CHANGES/HR = 0.29 1694 LIGHTING-W/AREA = ( 1.2 ) — 1695 EQUIPMENT-W/AREA = ( 3 ) 1696 1697 "Exterior Wall 46" - EXTERIOR-WALL - 1698 CONSTRUCTION = "Exterior Wall Construction" 1699 LOCATION = SPACE-V2 1700 1701 "Interior Wall 6" - INTERIOR-WALL ▪ 1702 CONSTRUCTION = "Slab-on-Grade Construction" 1703 INT-WALL-TYPE = ADIABATIC 1704 LOCATION BOTTOM -- 1705 1706 "Interior Wall 66" = INTERIOR-WALL 1707 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 1708 INT-WALL-TYPE = ADIABATIC 1709 LOCATION = TOP 1710 1711 "Undrgrnd Wall 6" = UNDERGROUND-WALL 1712 CONSTRUCTION = "Slab-on-Grade Construction" 1713 HEIGHT = 1 1714 LOCATION = SPACE-V2 1715 1716 "7 TECH SERV. EAST PERIM" = SPACE 1717 X = 188 -- 1718 Y 47 1719 SHAPE = BOX 1720 WIDTH = 25 -- 1721 DEPTH = 32 1722 AIR-CHANGES/HR = 0,24 1723 LIGHTING-W/AREA ( 1.2 .. 1724 EQUIPMENT-W/AREA = ( 3 I 1725 1726 "Exterior Wall 47" = EXTERIOR-WALL .. 1727 CONSTRUCTION - "Exterior Wall Construction" 1728 LOCATION = SPACE-V2 1729 1730 "Window 22" = WINDOW ▪ 1731 GLASS-TYPE = "N-E Glazing" 1732 HEIGHT = 10 1733 WIDTH = 10 "." 1734 .. 1735 "Window 23" = WINDOW 1736 GLASS-TYPE = "N-E Glazing" ▪ 1737 X = 22 1738 1 3 1739 HEIGHT = 6 ▪ 1740 WIDTH = 10 1741 1742 "Interior Wall 7" = INTERIOR-WALL 1743 CONSTRUCTION = "Slab-on-Grade Construction" 1744 INT-WALL-TYPE = ADIABATIC 1745 LOCATION = BOTTOM 1746 1747 "Interior Wall 67" - INTERIOR-WALL 1748 CONSTRUCTION = "Accoustic Ceiling Tile Construct" Page: 19 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 1749 INT-WALL-TYPE = ADIABATIC 1750 LOCATION = TOP 1751 .. 1752 "Undrgrnd Wall 7" = UNDERGROUND-WALL ""' 1753 CONSTRUCTION = "Slab-on-Grade Construction" 1754 HEIGHT = 1 1755 LOCATION = SPACE-V2 1756 .. 1757 "8 TECH SERV. NORTH PERIM" = SPACE. 1758 X = 188 1759 Y = 79 1760 SHAPE = BOX 1761 WIDTH = 25 _ 1762 DEPTH = 15 1763 AIR-CHANGES/BR = 0.64 1764 LIGHTING-W/AREA = ( 1.2 ) 1765 EQUIPMENT-W/AREA = ( 3 ) - ... 1766 DAYLIGHTING = NO 1767 LIGHT-REF-POINT1 = ( 12, 5 ) 1768 .. 1769 "Exterior Wall 48" = EXTERIOR-WALL 1770 CONSTRUCTION = "Exterior Wall Construction" 1771 LOCATION = SPACE-V2 1772 . 1773 "Window 24" = WINDOW 1774 GLASS-TYPE = "N-E Glazing" 1775 Y = 3 1776 HEIGHT = 6 1777 WIDTH = 10 1778 1779 "Window 25" = WINDOW 1780 GLASS-TYPE = "N-E Glazing" 1781 X = 10 1782 HEIGHT = 9 1783 WIDTH = 5 1784 .. 1 1785 "Exterior Wall 49" = EXTERIOR-WALL 1786 CONSTRUCTION = "Exterior Wall Construction" 1787 LOCATION = SPACE-V3 1788 1789 "Window 29" = WINDOW 1790 GLASS-TYPE = "N-E Glazing" 1791 HEIGHT = 9 1792 WIDTH = 7 1793 .. 1794 "Window 30" = WINDOW 1795 GLASS-TYPE _ "N-E Glazing" 1796 X = 7 1797 Y = 3 1798 HEIGHT = 6 1799 WIDTH = 18 1800 .. 1801 "Interior Wall 8" = INTERIOR-WALL 1802 CONSTRUCTION = "Slab-on-Grade Construction" 1803 INT-WALL-TYPE = ADIABATIC 1804 LOCATION = BOTTOM 1805 .. 1806 "Interior Wall 68" = INTERIOR-WALL 1807 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 1808 INT-WALL-TYPE = ADIABATIC 1809 LOCATION = TOP 1810 .. '.. 1811 "Interior Wall 117" = INTERIOR-WALL 1812 NEXT-TO = "65 STAFF ROOM" 1813 CONSTRUCTION = "Interior Wall Construction" 1814 LOCATION = SPACE-V4 1815 . 1816 "Undrgrnd Wall 8" = UNDERGROUND-WALL ..- 1817 CONSTRUCTION = "Slab-on-Grade Construction" 1818 HEIGHT = 1 1819 LOCATION = SPACE-V2 1820 .. 1821 "Undrgrnd Wall 29" = UNDERGROUND-WALL 1822 CONSTRUCTION = "Slab-on-Grade Construction" 1823 HEIGHT = 1 1824 LOCATION = SPACE-V3 1825 .. 1826 "9 VOL COORD." = SPACE 1827 X = 151 1828 Y = 79 1829 SHAPE = BOX 1830 WIDTH = 11 1831 DEPTH = 15 1832 AIR-CHANGES/HR = 0.4 1833 LIGHTING-W/AREA = ( 1.2 ) 1834 EQUIPMENT-W/AREA = ( 1.5 ) 1835 DAYLIGHTING = NO "'1836 LIGHT-REF-POINT1 = ( 5, 5 ) 1837 .. 1838 "Exterior Wall 50" = EXTERIOR-WALL 1839 CONSTRUCTION = "Exterior Wall Construction" 1840 LOCATION = SPACE-V3 Page: 20— File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 1841 1842 "Window 34" = WINDOW 1843 GLASS-TYPE = "N-E Glazing" - 1844 Y 3 1845 HEIGHT = 6 1846 WIDTH 6 - 1847 1848 "Window 35" = WINDOW 1849 GLASS-TYPE "N-E Glazing" 1850 X = 6 1851 HEIGHT = 9 1852 WIDTH = 5 - 1853 1854 "Interior Wall 9" = INTERIOR-WALL 1855 CONSTRUCTION = "Slab-on-Grade Construction" 1856 INT-WALL-TYPE = ADIABATIC 1857 LOCATION = BOTTOM 1858 1859 "Interior Wall 69" = INTERIOR-WALL — 1860 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 1861 INT-WALL-TYPE = ADIABATIC 1862 LOCATION = TOP - 1863 1864 "Interior Wall 120" = INTERIOR-WALL 1065 NEXT-TO = "23 WC" - 1866 CONSTRUCTION = "Interior Wall Construction" 1867 LOCATION = SPACE-V1 1868 1869 "Interior Wall 121" = INTERIOR-WALL 1870 NEXT-TO = "lOSEATING NORTH PERIM" 1871 CONSTRUCTION = "Interior Wall Construction" 1872 LOCATION = SPACE-V4 1873 1874 "Undrgrnd Wall 10" = UNDERGROUND-WALL 1875 CONSTRUCTION "Slab-on-Grade Construction" - 1876 HEIGHT = 1 1877 LOCATION = SPACE-V3 1878 - 1879 "10SEATING NORTH PERIM" = SPACE 1880 X = 103 1881 Y 79 - 1882 SHAPE ,= BOX 1883 WIDTH = 48 1884 DEPTH = 15 1885 AIR-CHANGES/HR = 0.4 1886 LIGHTING-W/AREA = ( 1.7 ) 1887 EQUIPMENT-W/AREA ( 1.5 ) 1888 DAYLIGHTING = NO 1889 LIGHT-REF-POINT1 = ( 24, 5 ) 1890 AREA/PERSON = 100 1891 -- 1892 "Exterior Wall 51" - EXTERIOR-WALL 1893 CONSTRUCTION = "Exterior Wall Construction" 1894 LOCATION = SPACE-V3 -- 1895 1896 "Window 36" = WINDOW 1897 GLASS-TYPE = "N-E Glazing" 1898 HEIGHT = 9 1899 WIDTH = 5 1900 1901 "Window 37" - WINDOW mm' 1902 GLASS-TYPE = "N-E Glazing" 1903 X = 5 1904 Y 3 -- 1905 HEIGHT = 6 1906 WIDTH = 20 1907 1908 "Window 38" = WINDOW 1909 GLASS-TYPE = "N-E Glazing" 1910 X = 25 1911 HEIGHT = 9 1912 WIDTH = 10 1913 1914 "Window 39" = WINDOW 1915 GLASS-TYPE = "N-E Glazing" 1916 X - 35 1917 Y = 3 1918 HEIGHT = 6 1919 WIDTH = 13 1920 1921 "Interior Wall 10" - INTERIOR-WALL 1922 CONSTRUCTION = "Slab-on-Grade Construction" 1923 INT-WALL-TYPE = ADIABATIC 1924 LOCATION = BOTTOM 1925 1926 "Interior Wall 70" = INTERIOR-WALL 1927 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 1928 INT-WALL-TYPE = ADIABATIC 1929 LOCATION = TOP _ 1930 1931 "Interior Wall 122" = INTERIOR-WALL 1932 NEXT-TO = "16 NEW BOOKS + AV" Page: 21 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 1933 CONSTRUCTION = "AIR WALL" 1934 LOCATION = SPACE-V1 1935 1936 "Interior Wall 123" INTERIOR-WALL 1937 NEXT-TO = "10A OPAC SELF CHECK NORTH PERIM" 1938 CONSTRUCTION = "AIR WALL" 1939 LOCATION = SPACE-V4 1940 1941 "Undrgrnd Wall 11" = UNDERGROUND-WALL 1942 CONSTRUCTION = "Slab-on-Grade Construction" 1943 HEIGHT = 1 1944 LOCATION = SPACE-V3 1945 1946 "11 SHELVES" = SPACE 1947 Y = 94 1948 SHAPE = POLYGON 1949 AIR-CHANGES/HR = 0.13 1950 POLYGON = "Polygon 1" 1951 1952 "Exterior Wall ill" = EXTERIOR-WALL 1953 CONSTRUCTION = "Exterior Wall Construction" 1954 LOCATION = SPACE-V1 1955 1956 "Window 79" = WINDOW 1957 GLASS-TYPE = "S-W Glazing" 1958 X = 2.5 1959 Y = 3 1960 HEIGHT = 6 1961 WIDTH = 10 1962 .. 1963 "Interior Wall 11" = INTERIOR-WALL 1964 CONSTRUCTION = "Slab-on-Grade Construction" 1965 INT-WALL-TYPE = ADIABATIC 1966 LOCATION = BOTTOM 1967 1968 "Interior Wall 71" = INTERIOR-WALL ,EM 1969 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 1970 INT-WALL-TYPE = ADIABATIC 1971 LOCATION = TOP 1972 .. 1973 "Undrgrnd Wall 16" = UNDERGROUND-WALL 1974 CONSTRUCTION = "Slab-on-Grade Construction" 1975 HEIGHT = 1 1976 LOCATION = SPACE-V1 1977 1978 "12 SHELVES WEST PERIM" = SPACE 1979 Y = 48 1980 SHAPE = POLYGON 1981 AIR-CHANGES/HR = 0.59 MINN 1982 POLYGON = "Polygon 2" 1983 1984 "Exterior Wall 53" = EXTERIOR-WALL 1985 CONSTRUCTION = "Exterior Wall Construction" 1986 LOCATION = SPACE-V4 1987 1988 "Window 80" = WINDOW 1989 GLASS-TYPE = "S-W Glazing" 1990 HEIGHT = 14 1991 WIDTH = 10 1992 1993 "Exterior Wall 112" = EXTERIOR-WALL 1994 CONSTRUCTION = "Exterior Wall Construction" 1995 LOCATION = SPACE-V3 1996 1997 "Window 47" = WINDOW 1998 GLASS-TYPE _ "N-E Glazing" 1999 X = 10 2000 HEIGHT = 14 2001 WIDTH = 5 2002 2003 "Interior Wall 12" = INTERIOR-WALL 2004 CONSTRUCTION = "Slab-on-Grade Construction" 2005 INT-WALL-TYPE = ADIABATIC 2006 LOCATION = BOTTOM 2007 .. 2008 "Interior Wall 72" = INTERIOR-WALL 2009 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2010 INT-WALL-TYPE = ADIABATIC 2011 LOCATION = TOP 2012 2013 "Undrgrnd Wall 17" = UNDERGROUND-WALL 2014 CONSTRUCTION = "Slab-on-Grade Construction" 2015 HEIGHT = 1 2016 LOCATION = SPACE-V3 2017 2018 "Undrgrnd Wall 32" = UNDERGROUND-WALL 2019 CONSTRUCTION = "Slab-on-Grade Construction" 2020 HEIGHT = 1 2021 LOCATION = SPACE-V4 2022 .. 2023 "13 YOUTH SERVICE" = SPACE 2024 SHAPE = POLYGON Page: 22� C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM - 2025 AIR-CHANGES/HR - 0.19 2026 EQUIPMENT-W/AREA - ( 1.5 ) 2027 AREA/PERSON = 100 —2028 POLYGON - "Polygon 48" 2029 2030 "Exterior Wall 54" = EXTERIOR-WALL ...2031 CONSTRUCTION = "Exterior Wall Construction" 2032 LOCATION - SPACE-V1 2033 2034 "Window 81" = WINDOW 2035 GLASS-TYPE "S-W Glazing" 2036 X = 6 2037 HEIGHT = 14 2038 WIDTH = 10 2039 2040 "Interior Wall 13" = INTERIOR-WALL 2041 CONSTRUCTION - "Slab-on-Grade Construction" 2042 INT-WALL-TYPE = ADIABATIC 2043 LOCATION = BOTTOM —2044 2045 "Interior Wall 73" = INTERIOR-WALL 2046 CONSTRUCTION = "Accoustic Ceiling Tile Construct" —.2047 INT-WALL-TYPE = ADIABATIC 2048 LOCATION = TOP 2049 2050 "Undrgrnd Wall 18" = UNDERGROUND-WALL 2051 CONSTRUCTION = "Slab-on-Grade Construction" 2052 HEIGHT = 1 2053 LOCATION = SPACE-V1 - 2054 2055 "14 ELEV MACH/JAN" - SPACE 2056 X - 15 - 2057 Y 15 2058 SHAPE = BOX 2059 WIDTH 20 -.2060 DEPTH - 15 2061 NUMBER-OF-PEOPLE = 0 2062 LIGHTING-W/AREA = ( 0.8 ) -.2063 EQUIPMENT-W/AREA = ( 10 ) 2064 AREA/PERSON 600 2065 2066 "Interior Wall 14" = INTERIOR-WALL 2067 CONSTRUCTION - "Slab-on-Grade Construction" 2068 INT-WALL-TYPE = ADIABATIC 2069 LOCATION - BOTTOM ""..2070 2071 "Interior Wall 74" = INTERIOR-WALL 2072 CONSTRUCTION = "Accoustic Ceiling Tile Construct" —2073 INT-WALL-TYPE - ADIABATIC 2074 LOCATION =. TOP 2075 - 2076 "15 CHILDREN'S AREA/SHELVES" = SPACE 2077 X = 15 2078 Y 48 2079 SHAPE = BOX 2080 WIDTH = 78 2081 DEPTH = 31 2082 -.2083 "Interior Wall 15" = INTERIOR-WALL 2084 CONSTRUCTION = "Slab-on-Grade Construction" 2085 INT-WALL-TYPE = ADIABATIC --2086 LOCATION = BOTTOM 2087 2088 "Interior Wall 75" = INTERIOR-WALL —2089 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2090 INT-WALL-TYPE - ADIABATIC 2091 LOCATION TOP ..2092 2093 "16 NEW BOOKS + AV" = SPACE 2094 X - 93 2095 Y 40 2096 SHAPE POLYGON 2097 POLYGON - "Polygon 35" 2098 -..2099 "Interior Wall 16" = INTERIOR-WALL 2100 CONSTRUCTION - "Slab-on-Grade Construction" 2101 INT-WALL-TYPE = ADIABATIC •-•2102 LOCATION = BOTTOM 2103 2104 "Interior Wall 76" = INTERIOR-WALL ..2105 CONSTRUCTION "Accoustic Ceiling Tile Construct" 2106 INT-WALL-TYPE = ADIABATIC 2107 HEIGHT - 12 2108 LOCATION = TOP 2109 2110 "17 FAMILY W.C." = SPACE 2111 X = 35 .."2112 Y 42 2113 SHAPE = BOX 2114 WIDTH = 15 2115 DEPTH = 6 2116 NUMBER-OF-PEOPLE = 0 Page: 23 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 2117 LIGHTING-W/AREA = ( 0.8 ) 2118 EQUIPMENT-W/AREA = ( 0 ) 2119 .. 2120 "Interior Wall 17" = INTERIOR-WALL 2121 CONSTRUCTION = "Slab-on-Grade Construction" 2122 INT-WALL-TYPE = ADIABATIC 2123 LOCATION = BOTTOM 2124 2125 "Interior Wall 77" = INTERIOR-WALL 2126 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2127 INT-WALL-TYPE = ADIABATIC 2128 LOCATION = TOP 2129 2130 "18 IDF CLOSET" = SPACE 2131 X = 50 2132 Y = 42 2133 SHAPE = BOX 2134 WIDTH = 10 2135 DEPTH = 6 2136 NUMBER-OF-PEOPLE = 0 2137 LIGHTING-W/AREA = ( 0.8 ) 2138 EQUIPMENT-W/AREA = ( 20 ) 2139 .. 2140 "Interior Wall 18" = INTERIOR-WALL 2141 CONSTRUCTION = "Slab-on-Grade Construction" 2142 INT-WALL-TYPE = ADIABATIC 2143 LOCATION = BOTTOM 2144 2145 "Interior Wall 78" = INTERIOR-WALL 2146 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2147 INT-WALL-TYPE = ADIABATIC 2148 LOCATION = TOP 2149 .. .� 2150 "19 INFO DESK HALLWAY" = SPACE 2151 X = 93 2152 Y = 15 2153 AZIMUTH = -90 2154 SHAPE = POLYGON 2155 LIGHTING-W/AREA = ( 1.2 ) 2156 EQUIPMENT-W/AREA = ( 1 ) 2157 POLYGON = "Polygon 3" 2158 2159 "Interior Wall 19" = INTERIOR-WALL 2160 CONSTRUCTION = "Slab-on-Grade Construction" 2161 INT-WALL-TYPE = ADIABATIC 2162 LOCATION = BOTTOM 2163 2164 "Interior Wall 79" = INTERIOR-WALL 2165 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2166 INT-WALL-TYPE = ADIABATIC 2167 LOCATION = TOP 2168 2169 "20 CIRC DESK" = SPACE 2170 X = 93 2171 Y = 15 2172 SHAPE = BOX 2173 WIDTH = 19 2174 DEPTH = 25 2175 LIGHTING-W/AREA = ( 1.2 ) 2176 EQUIPMENT-W/AREA = ( 1.5 ) 2177 2178 "Interior Wall 20" = INTERIOR-WALL 2179 CONSTRUCTION = "Slab-on-Grade Construction" 2180 INT-WALL-TYPE = ADIABATIC 2181 LOCATION = BOTTOM 2182 2183 "Interior Wall 80" = INTERIOR-WALL 2184 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2185 INT-WALL-TYPE = ADIABATIC 2186 LOCATION = TOP 2187 2188 "21 CIRC WORKROOM INTERIOR" = SPACE 2189 X = 112 2190 Y = 15 2191 SHAPE = BOX 2192 WIDTH = 59 2193 DEPTH = 25 2194 LIGHTING-W/AREA = ( 1.2 ) 2195 EQUIPMENT-W/AREA = ( 1.5 ) 2196 2197 "Interior Wall 21" = INTERIOR-WALL 2198 CONSTRUCTION = "Slab-on-Grade Construction" 2199 INT-WALL-TYPE = ADIABATIC 2200 LOCATION = BOTTOM 2201 .. — 2202 "Interior Wall 81" = INTERIOR-WALL 2203 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2204 INT-WALL-TYPE = ADIABATIC ^- 2205 2205 LOCATION = TOP 2206 2207 "22 STAFF ENTRY HALLWAY" = SPACE — 2208 X = 192 Page: 24— C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 2209 Y 47 2210 AZIMUTH = 180 2211 SHAPE = POLYGON 2212 AIR-CHANGES/HR = 0.06 2213 EQUIPMENT-WAREA ( 0 ) 2214 POLYGON = "Polygon 4" -"" 2215 2216 "Exterior Wall 43" EXTERIOR-WALL 2217 CONSTRUCTION = "Exterior Wall Construction" ==.2218 X = 9 2219 WIDTH = 9 2220 AZIMUTH = 0 —. 2221 LOCATION = SPACE-V6 2222 2223 "Interior Wall 22" = INTERIOR-WALL 2224 CONSTRUCTION = "Slab-on-Grade Construction" 2225 INT-WALL-TYPE = ADIABATIC - 2226 LOCATION = BOTTOM 2227 —" 2228 "Interior Wall 82" INTERIOR-WALL 2229 CONSTRUCTION "Accoustic Ceiling Tile Construct" 2230 INT-WALL-TYPE ADIABATIC "" 2231 LOCATION TOP 2232 2233 "Undrgrnd Wall 26" = UNDERGROUND-WALL —. 2234 CONSTRUCTION = "Slab-on-Grade Construction" 2235 X = 9 2236 HEIGHT = 1 -. 2237 WIDTH - 9 2238 LOCATION = SPACE-VS 2239 2240 "23 WC" - SPACE 2241 X = 151 2242 47 2243 SHAPE = BOX -"" 2244 WIDTH 31 2245 DEPTH = 32 2246 NUMBER-OF-PEOPLE - 0 "" 2247 LIGHTING-W/AREA = ( 0.8 ) 2248 EQUIPMENT-W/AREA = ( 0 ) 2249 -. 2250 "Interior Wall 23" INTERIOR-WALL 2251 CONSTRUCTION = "Slab-on-Grade Construction" 2252 INT-WALL-TYPE = ADIABATIC - 2253 LOCATION = BOTTOM 2254 2255 "Interior Wall 83" = INTERIOR-WALL 2256 CONSTRUCTION "Accoustic Ceiling Tile Construct" -** 2257 INT-WALL-TYPE == ADIABATIC • 2258 LOCATION = TOP 2259 -"• 2260 "24 HALLWAY" = SPACE 2261 X = 188 2262 Y = 79 == 2263 AZIMUTH = 180 2264 SHAPE POLYGON 2265 POLYGON - "Polygon 5" -. 2266 2267 "Interior Wall 24" = INTERIOR-WALL 2268 CONSTRUCTION "Slab-on-Grade Construction" 2269 INT-WALL-TYPE = ADIABATIC 2270 LOCATION BOTTOM 'A 2271 2272 "Interior Wall 84" - INTERIOR-WALL -- 2273 CONSTRUCTION "Accoustic Ceiling Tile Construct" • 2274 INT-WALL-TYPE == ADIABATIC 2275 LOCATION TOP " 2276 • 2277 "25 LOBBY" - SPACE 2278 X 15 == 2279 0 2280 HEIGHT 28 2281 SHAPE ,= POLYGON ▪ 2282 AIR-CHANGES/HR 0.39 2283 LIGHTING-W/AREA = ( 1 ) 2284 EQUIPMENT-WAREA = ( 1 ) 2285 DAYLIGHTING = NO ▪ 2286 LIGHT-REF-POINT1 ( -20, 5 ) 2287 LIGHT-REF-POINT2 ( -25, 20 2288 ZONE-FRACTION1 = 0.5 "" 2289 ZONE-FRACTION2 0.5 2290 AREA/PERSON - 14 2291 POLYGON "Polygon 6" — 2292 2293 "Exterior Wall 113" - EXTERIOR-WALL 2294 CONSTRUCTION "Exterior Wall Construction" .. 2295 LOCATION SPACE-V4 2296 2297 "Window 48" = WINDOW ..2298 GLASS-TYPE = "N-E Glazing" 2299 HEIGHT = 25.5 • 2300 WIDTH = 20.6 Page: 25 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 2301 2302 "Exterior Wall 114" = EXTERIOR-WALL 2303 CONSTRUCTION = "Exterior Wall Construction" 2304 LOCATION SPACE-V7 2305 2306 "Window 74" = WINDOW 2307 GLASS-TYPE = "S-W Glazing" 2308 HEIGHT = 25.5 2309 WIDTH = 13.46 2310 .. 2311 "Exterior Wall 115" = EXTERIOR-WALL 2312 CONSTRUCTION = "Exterior Wall Construction" 2313 LOCATION = SPACE-V8 2314 .. 2315 "Window 75" = WINDOW 2316 GLASS-TYPE _ "S-W Glazing" 2317 HEIGHT = 25.5 2318 WIDTH = 36.62 2319 OVERHANG-A = -8 2320 OVERHANG-B = -16 2321 OVERHANG-W = 20 2322 OVERHANG-D = 6 2323 .r 2324 "Exterior Wall 116" = EXTERIOR-WALL 2325 CONSTRUCTION = "Exterior Wall Construction" 2326 LOCATION =SPACE-V9 2327 2328 "Window 78" = WINDOW 2329 GLASS-TYPE = "N-E Glazing" 2330 HEIGHT = 25.5 2331 WIDTH = 4 2332 2333 "Exterior Wall 154" = EXTERIOR-WALL 2334 CONSTRUCTION = "Exterior Wall Construction" 2335 Z = 14 2336 HEIGHT = 14 2337 LOCATION = SPACE-V6 2338 . 2339 "Window 73" = WINDOW 2340 GLASS-TYPE _ "S-W Glazing" 2341 HEIGHT = 11.5 2342 WIDTH = 25.13 2343 2344 "Interior Wall 91" = INTERIOR-WALL 2345 CONSTRUCTION = "Slab-on-Grade Construction" 2346 INT-WALL-TYPE = ADIABATIC 2347 LOCATION = BOTTOM 2348 2349 "Undrgrnd Wall 19" = UNDERGROUND-WALL 2350 CONSTRUCTION = "Slab-on-Grade Construction" 2351 HEIGHT = 1 2352 LOCATION = SPACE-V7 i= 2353 2354 "Undrgrnd Wall 27" = UNDERGROUND-WALL 2355 CONSTRUCTION = "Slab-on-Grade Construction" 2356 HEIGHT = 1 2357 LOCATION = SPACE-V8 2358 2359 "Undrgrnd Wall 28" = UNDERGROUND-WALL 2360 CONSTRUCTION = "Slab-on-Grade Construction" 2361 HEIGHT = 1 2362 LOCATION = SPACE-V9 2363 2364"Undrgrnd Wall 33" =UNDERGROUND-WALL 2365 CONSTRUCTION = "Slab-on-Grade Construction" 2366 HEIGHT = 1 2367 LOCATION = SPACE-V4 2368 2369 "26 COMMUNITY ROOM EAST PERIM" = SPACE 2370 HEIGHT = 28 2371 SHAPE = POLYGON ==2372 AIR-CHANGES/HR = 0.5 2373 LIGHTING-W/AREA = ( 1.2 ) 2374 EQUIPMENT-W/AREA = ( 1 ) 2375 AREA/PERSON = 20 2376 POLYGON = "Polygon 7" 2377 2378 "Exterior Wall 59" = EXTERIOR-WALL 2379 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 2380 HEIGHT = 26 2381 LOCATION = SPACE-V1 2382 2383 "Window 50" = WINDOW 2384 GLASS-TYPE _ "N-E Glazing" 2385 X = 32.08 2386 HEIGHT = 22.5 2387 WIDTH = 10 2388 2389 "Interior Wall. 26" = INTERIOR-WALL 2390 CONSTRUCTION = "Slab-on-Grade Construction" 2391 INT-WALL-TYPE = ADIABATIC 2392 LOCATION = BOTTOM Page: 26 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INR 1/14/2003, 3:29:54PM 2393 2394 "Undrgrnd Wall 21" = UNDERGROUND-WALL 2395 CONSTRUCTION = "Slab-on-Grade Construction" 2396 HEIGHT - 1 2397 LOCATION SPACE-V1 2398 -- 2399 "27 COMMUNITY ROOM CENTER" = SPACE 2400 HEIGHT = 28 2401 SHAPE - POLYGON -- 2402 LIGHTING-W/AREA = ( 1.2 ) 2403 EQUIPMENT-W/AREA ( 1 ) 2404 AREA/PERSON = 20 2405 POLYGON "Polygon 8" 2406 2407 "Interior Wall 27" = INTERIOR-WALL 2408 CONSTRUCTION "Slab-on-Grade Construction" m"-^ 2409 INT-WALL-TYPE - ADIABATIC 2410 LOCATION = BOTTOM 2411 -- 2412 "28 COMMUNITY ROOM WEST PERIM" = SPACE 2413 HEIGHT = 28 2414 SHAPE .= POLYGON -- 2415 AIR-CHANGES/HR = 0.42 2416 LIGHTING-W/AREA = ( 1.2 ) 2417 EQUIPMENT-W/AREA ( 1 ) _ 2418 AREA/PERSON = 20 2419 POLYGON - "Polygon 9" 2420 2421 "Exterior Wall 61" = EXTERIOR-WALL 2422 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 2423 HEIGHT = 26 2424 LOCATION = SPACE-V4 -- 2425 2426 "Window 71" = WINDOW 2427 GLASS-TYPE = "S-W Glazing" -- 2428 HEIGHT = 20 2429 WIDTH = 5 2430 -- 2431 "Interior Wall 28" = INTERIOR-WALL 2432 CONSTRUCTION = "Slab-on-Grade Construction" 2433 INT-WALL-TYPE = ADIABATIC 2434 LOCATION = BOTTOM 2435 2436 "Undrgrnd Wall 23" = UNDERGROUND-WALL 2437 CONSTRUCTION = "Slab-on-Grade Construction" —. 2438 HEIGHT = 1 2439 LOCATION = SPACE-V4 2440 -- 2441 "29 COMMUNITY ROOM NORTH PERIM" = SPACE 2442 HEIGHT = 28 2443 SHAPE = POLYGON - 2444 AIR-CHANGES/HR - 0.53 2445 LIGHTING-W/AREA = ( 1.2 ) 2446 EQUIPMENT-W/AREA = ( 1 ) 2447 AREA/PERSON - 20 2448 POLYGON "Polygon 39" 2449 2450 "Exterior Wall 120" = EXTERIOR-WALL 2451 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 2452 HEIGHT = 26 2453 LOCATION = SPACE-V4 2454 2455 "Window 49" = WINDOW 2456 GLASS-TYPE = "N-E Glazing" -- 2457 HEIGHT - 22.5 2458 WIDTH = 10 2459 — 2460 "Window 51" = WINDOW 2461 GLASS-TYPE = "N-E Glazing" 2462 X = 61 2463 HEIGHT = 20 2464 WIDTH = 5 .2465 2466 "Interior Wall 29" = INTERIOR-WALL ▪ 2467 CONSTRUCTION = "Slab-on-Grade Construction" 2468 INT-WALL-TYPE = ADIABATIC 2469 LOCATION = BOTTOM -" 2470 2471 "Undrgrnd Wall 22" - UNDERGROUND-WALL 2472 CONSTRUCTION = "Slab-on-Grade Construction" 2473 HEIGHT = 1 2474 LOCATION = SPACE-V4 2475 2476 "30 COMMUNITY ROOM STORAGE" - SPACE 2477 HEIGHT = 26 2478 SHAPE =. POLYGON - 2479 AIR-CHANGES/HR = 0.42 2480 AREA/PERSON = 600 2481 POLYGON = "Polygon 98" 2482 - 2483 "Exterior Wall 152" = EXTERIOR-WALL 2484 CONSTRUCTION = "COMMUNITY WING WALLS CNS" Page: 27 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 2485 Z = 14 2486 HEIGHT = 12 2487 LOCATION = SPACE-V1 2488 2489 "Exterior Wall 153" = EXTERIOR-WALL 2490 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 2491 Z = 14 2492 HEIGHT = 12 2493 LOCATION = SPACE-V2 2494 2495 "Interior Wall 30" = INTERIOR-WALL 2496 CONSTRUCTION = "Slab-on-Grade Construction" 2497 INT-WALL-TYPE = ADIABATIC 2498 LOCATION = BOTTOM 2499 2500 "31 COMMUNITY ROOM VESTIBULE" = SPACE 2501 HEIGHT = 28 2502 SHAPE = POLYGON 2503 AIR-CHANGES/HR = 0.73 2504 NUMBER-OF-PEOPLE = 0 2505 POLYGON = "Polygon 97" 2506 2507 "Exterior Wall 62" = EXTERIOR-WALL 2508 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 2509 HEIGHT = 26 2510 LOCATION = SPACE-V1 a 2511 2512 "Exterior Wall 64" = EXTERIOR-WALL 2513 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 2514 HEIGHT = 26 2515 LOCATION = SPACE-V5 2516 2517 "Exterior Wall 151" = EXTERIOR-WALL 2518 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 2519 Z = 14 2520 HEIGHT = 12 2521 WIDTH = 7 2522 LOCATION = SPACE-V2 2523 .. 2524 "Interior Wall 31" = INTERIOR-WALL 2525 CONSTRUCTION = "Slab-on-Grade Construction" 2526 INT-WALL-TYPE = ADIABATIC 2527 LOCATION = BOTTOM 2528 .. 2529 "Undrgrnd Wall 34" = UNDERGROUND-WALL 2530 CONSTRUCTION = "Slab-on-Grade Construction" 2531 HEIGHT = 1 2532 LOCATION = SPACE-V1 2533 2534 "Undrgrnd Wall 35" = UNDERGROUND-WALL 2535 CONSTRUCTION = "Slab-on-Grade Construction" 2536 HEIGHT = 1 2537 LOCATION = SPACE-V5 2538 2539 "34 COMMUNITY ROOM VESTIBULE" = SPACE 2540 HEIGHT = 28 2541 SHAPE = POLYGON 2542 AIR-CHANGES/HR = 0.61 2543 NUMBER-OF-PEOPLE = 0 2544 POLYGON = "Polygon 86" 2545 2546 "Exterior Wall 121" = EXTERIOR-WALL 2547 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 2548 HEIGHT = 26 2549 LOCATION = SPACE-V1 2550 2551 "Interior Wall 34" = INTERIOR-WALL 2552 CONSTRUCTION = "Slab-on-Grade Construction" 2553 INT-WALL-TYPE = ADIABATIC 2554 LOCATION = BOTTOM 2555 2556 "Undrgrnd Wall 20" = UNDERGROUND-WALL 2557 CONSTRUCTION = "Slab-on-Grade Construction" 2558 HEIGHT = 1 2559 LOCATION = SPACE-V1 2560 2561 "35 PANTRY" = SPACE 2562 SHAPE = POLYGON 2563 AIR-CHANGES/HR = 0.73 2564 NUMBER-OF-PEOPLE = 0 2565 LIGHTING-W/AREA = ( 0.8 ) 2566 AREA/PERSON = 600 2567 POLYGON = "Polygon 43" 2568 2569 "Exterior Wall 118" = EXTERIOR-WALL 2570 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 2571 LOCATION = SPACE-V1 2572 .. 2573 "Exterior Wall 119" = EXTERIOR-WALL 2574 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 2575 LOCATION = SPACE-V4 2576 .. Page: 28— File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 2577 "Interior Wall 35" = INTERIOR-WALL 2578 CONSTRUCTION = "Slab-on-Grade Construction" 2579 INT-WALL-TYPE = ADIABATIC ▪ 2580 LOCATION = BOTTOM 2581 2582 "Undrgrnd Wall 36" = UNDERGROUND-WALL - 2583 CONSTRUCTION = "Slab-on-Grade Construction" 2584 HEIGHT = 1 2585 LOCATION = SPACE-V1 —. 2586 2587 "Undrgrnd Wall 37" = UNDERGROUND-WALL 2588 CONSTRUCTION = "Slab-on-Grade Construction" 2589 HEIGHT = 1 2590 LOCATION = SPACE-V4 2591 . .... 2592 "10A OPAC SELF CHECK NORTH PERIM" = SPACE 2• 593 X = 93 2594 Y = 79 2595 SHAPE = BOX 2596 WIDTH = 10 2597 DEPTH = 15 2598 AIR-CHANGES/HR = 0.4 • 2599 NUMBER-OF-PEOPLE = 8 2600 EQUIPMENT-W/AREA = ( 10 ) 2601 DAYLIGHTING = NO - 2602 LIGHT-REF-POINT1 = ( 5, 5 ) 2603 2604 "Exterior Wall 104" = EXTERIOR-WALL 2605 CONSTRUCTION = "Exterior Wall Construction" 2606 LOCATION = SPACE-V3 2607 2608 "Window 40" = WINDOW — 2• 609 GLASS-TYPE = "N-E Glazing" 2610 Y = 3 2611 HEIGHT = 6 - 2612 WIDTH = 7 2613 2614 "Window 41" = WINDOW — 2615 GLASS-TYPE = "N-E Glazing" 2616 X = 7 2617 HEIGHT = 9 - 2618 WIDTH = 3 2619 2620 "Interior Wall 85" = INTERIOR-WALL 2621 CONSTRUCTION = "Slab-on-Grade Construction" 2622 INT-WALL-TYPE = ADIABATIC 2623 LOCATION = BOTTOM 2624 '.r 2625 "Interior Wall 86" = INTERIOR-WALL 2626 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2627 INT-WALL-TYPE = ADIABATIC - 2628 LOCATION = TOP 2629 2630 "Interior Wall 124" = INTERIOR-WALL ✓ 2631 NEXT-TO = "16A OPAC/SELF CHECK INTERIOR" 2632 CONSTRUCTION = "AIR WALL" 2633 LOCATION = SPACE-V1 2634 2635 "Interior Wall 125" = INTERIOR-WALL 2636 NEXT-TO = "64 SHEVES NORTH PERIM" 2637 CONSTRUCTION = "Interior Wall Construction" 2• 638 LOCATION = SPACE-V4 2639 2640 "Undrgrnd Wall 12" = UNDERGROUND-WALL '— 2641 CONSTRUCTION = "Slab-on-Grade Construction" 2642 HEIGHT = 1 2643 LOCATION = SPACE-V3 .. 2644 2645 "16A OPAC/SELF CHECK INTERIOR" = SPACE 2646 X = 93 .� 2647 Y = 62 2648 SHAPE = BOX 2649 WIDTH = 10 2650 DEPTH = 17 2651 NUMBER-OF-PEOPLE = 16 2652 EQUIPMENT-W/AREA = ( 10 ) 2653 2654 "Interior Wall 87" = INTERIOR-WALL 2655 CONSTRUCTION = "Slab-on-Grade Construction" 2656 INT-WALL-TYPE = ADIABATIC •••' 2657 LOCATION = BOTTOM 2658 2659 "Interior Wall 88" = INTERIOR-WALL 2660 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2661 INT-WALL-TYPE = ADIABATIC 2662 LOCATION = TOP .„ 2663 2664 "63 RESTROOMS" = SPACE 2665 SHAPE = POLYGON 2666 AIR-CHANGES/HR = 0.3 2667 NUMBER-OF-PEOPLE = 0 2668 LIGHTING-W/AREA = ( 0.8 ) Page: 29 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 2669 EQUIPMENT-W/AREA = ( 0 ) 2670 POLYGON = "Polygon 45" 2671 2672 "Exterior Wall 117" = EXTERIOR-WALL 2673 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 2674 LOCATION = SPACE-V1 2675 2676 "Interior Wall 94" = INTERIOR-WALL 2677 CONSTRUCTION = "Slab-on-Grade Construction" 2678 INT-WALL-TYPE = ADIABATIC 2679. LOCATION = BOTTOM 2680 2681 "Undrgrnd Wall 38" = UNDERGROUND-WALL 2682 CONSTRUCTION = "Slab-on-Grade Construction" 2683 HEIGHT = 1 2684 LOCATION = SPACE-V1 2685 2686 "62 COFFEE" = SPACE 2687 SHAPE = POLYGON 2688 EQUIPMENT-W/AREA = ( 5 ) 2689 AREA/PERSON = 400 2690 POLYGON = "Polygon 47" 2691 2692 "Interior Wall 89" = INTERIOR-WALL 2693 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2694 INT-WALL-TYPE = ADIABATIC 2695 LOCATION = TOP 2696 2697 "Interior Wall 90" = INTERIOR-WALL 2698 CONSTRUCTION = "Slab-on-Grade Construction" 2699 INT-WALL-TYPE = ADIABATIC 2700 LOCATION - = BOTTOM 2701 .. 2702 "64 SHEVES NORTH PERIM" = SPACE 2703 X = 60 2704 Y = 79 2705 SHAPE = BOX 2706 WIDTH = 33 2707 DEPTH = 15 2708 AIR-CHANGES/HR = 0.4 2709 2710 "Exterior Wall 106" = EXTERIOR-WALL 2711 CONSTRUCTION = "Exterior Wall Construction" — 2712 LOCATION = SPACE-V3 2713 2714 "Window 42" = WINDOW 2715 GLASS-TYPE _ "N-E Glazing" 2716 HEIGHT = 9 2717 WIDTH = 7 2718 2719 "Window 43" = WINDOW 2720 GLASS-TYPE = "N-E Glazing" 2721 X = 7 2722 Y = 3 2723 HEIGHT = 6 2724 WIDTH = 20 2725 2726 "Window 44" = WINDOW 2727 GLASS-TYPE = "N-E Glazing" 2728 X = 27 2729 HEIGHT = 9 2730 WIDTH = 5 2731 2732 "Interior Wall 101" = INTERIOR-WALL 2733 CONSTRUCTION = "Slab-on-Grade Construction" 2734 INT-WALL-TYPE = ADIABATIC 2735 LOCATION = BOTTOM 2736 2737 "Interior Wall 102" = INTERIOR-WALL 2738 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2739 INT-WALL-TYPE = ADIABATIC 2740 LOCATION = TOP 2741 2742 "Undrgrnd Wall 13" = UNDERGROUND-WALL 2743 CONSTRUCTION = "Slab-on-Grade Construction" 2744 HEIGHT = 1 2745 LOCATION = SPACE-V3 2746 .. ..- 2747 "65 STAFF ROOM" = SPACE 2748 X = 162 2749 Y = 79 2750 SHAPE = BOX 2751 WIDTH = 26 2752 DEPTH = 15 2753 AIR-CHANGES/HR = 0.4 2754 LIGHTING-W/AREA = ( 1.2 ) 2755 EQUIPMENT-W/AREA = ( 1.5 ) 2756 DAYLIGHTING = NO 2757 LIGHT-REF-POINT1 = ( 13, 5 ) 2758 .. 2759 "Exterior Wall 105" = EXTERIOR-WALL 2760 CONSTRUCTION = "Exterior Wall Construction" Page: 30— File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 2761 LOCATION = SPACE-V3 2762 2763 "Window 31" = WINDOW ▪ 2764 GLASS-TYPE _ "N-E Glazing" 2765 Y = 3 2766 HEIGHT = 6 - 2767 WIDTH = 2 2768 2769 "Window 32" = WINDOW — 2770 GLASS-TYPE _ "N-E Glazing" 2771 X = 2 2772 HEIGHT = 9 - 2773 WIDTH = 10 2774 2775 "Window 33" = WINDOW 2776 GLASS-TYPE _ "N-E Glazing" 2777 X = 12 2778 Y = 3 2779 HEIGHT = 6 — 2780 WIDTH = 14 2781 2782 "Interior Wall 99" = INTERIOR-WALL r' 2783 CONSTRUCTION = "Slab-on-Grade Construction" 2784 INT-WALL-TYPE = ADIABATIC 2785 LOCATION = BOTTOM 2786 _ 2787 "Interior Wall 100" = INTERIOR-WALL 2788 CONSTRUCTION = "Accoustic Ceiling Tile Construct" ▪ 2789 INT-WALL-TYPE = ADIABATIC 2790 LOCATION = TOP 2791 _ 2792 "Interior Wall 118" = INTERIOR-WALL 2793 NEXT-TO = "23 WC" 2794 CONSTRUCTION = "Interior Wall Construction" 2795 LOCATION = SPACE-V1 2796 2797 "Interior Wall 119" = INTERIOR-WALL 2798 NEXT-TO = "9 VOL COORD." — 2799 CONSTRUCTION = "Interior Wall Construction" 2800 LOCATION = SPACE-V4 2801 "Undrgrnd Wall 9" = UNDERGROUND-WALL 2803 CONSTRUCTION = "Slab-on-Grade Construction" 2804 HEIGHT = 1 2805 LOCATION = SPACE-V3 2806 2807 "66 PROG ROOM STOR." = SPACE 2808 X = 15 "� 2809 Y = 94 2810 SHAPE = BOX 2811 WIDTH = 10 - 2812 DEPTH = 32 2813 AIR-CHANGES/HR = 0.78 2814 LIGHTING-W/AREA = ( 0.8 ) .� 2815 AREA/PERSON = 600 2816 2817 "Exterior Wall 109" = EXTERIOR-WALL - 2818 CONSTRUCTION = "Exterior Wall Construction" 2819 LOCATION = SPACE-V3 2820 2821 "Window 46" = WINDOW 2822 GLASS-TYPE = "N-E Glazing" 2823 X = 5 2824 HEIGHT = 14 - 2825 WIDTH = 5 2826 2827 "Exterior Wall 110" = EXTERIOR-WALL - 2828 CONSTRUCTION = "Exterior Wall Construction" 2829 LOCATION = SPACE-V4 2830 2831 "Window 72" = WINDOW 2832 GLASS-TYPE = "S-W Glazing" 2833 HEIGHT = 14 2834 WIDTH = 5 2835 2836 "Interior Wall 97" = INTERIOR-WALL _ 2837 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2838 INT-WALL-TYPE = ADIABATIC 2839 LOCATION = TOP 2840 ▪ 2841 "Interior Wall 96" = INTERIOR-WALL 2842 CONSTRUCTION = "Slab-on-Grade Construction" 2843 INT-WALL-TYPE = ADIABATIC - 2844 LOCATION = BOTTOM 2845 2846 "Undrgrnd Wall 15" = UNDERGROUND-WALL �. 2847 CONSTRUCTION = "Slab-on-Grade Construction" 2848 HEIGHT = 1 2849 LOCATION = SPACE-V3 2850 2851 "Undrgrnd Wall 31" = UNDERGROUND-WALL 2852 CONSTRUCTION = "Slab-on-Grade Construction" Page: 31 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 2853 HEIGHT = 1 2854 LOCATION = SPACE-V4 2855 2856 "67 PROG ROOM" = SPACE 2857 X = 25 2858 Y = 94 2859 SHAPE = POLYGON 2860 AIR-CHANGES/HR = 0.37 2861 LIGHTING-W/AREA = ( 1.7 ) 2862 EQUIPMENT-W/AREA = ( 1.5 ) 2863 DAYLIGHTING = NO w 2864 LIGHT-REF-P0INT1 = ( 13, 15 ) 2865 AREA/PERSON = 100 2866 POLYGON = "Polygon 55" 2867 2868 "Exterior Wall 107" = EXTERIOR-WALL 2869 CONSTRUCTION = "Exterior Wall Construction" 2870 LOCATION = SPACE-V2 2871 2872 "Window 26" = WINDOW w 2873 GLASS-TYPE = "N-E Glazing" 2874 HEIGHT = 12 2875 WIDTH = 10 2876 2877 "Window 27" = WINDOW 2878 GLASS-TYPE = "N-E Glazing" 2879 X = 10 2880 Y = 3 2881 HEIGHT = 9 2882 WIDTH = 18 2883 2884 "Window 28" = WINDOW 2885 GLASS-TYPE = "N-E Glazing" 2886 X = 28 2887 HEIGHT = 12 2888 WIDTH = 6.5 2889 .. 2890 "Exterior Wall 108" = EXTERIOR-WALL 2891 CONSTRUCTION = "Exterior Wall Construction" 2892 LOCATION = SPACE-V3 2893 2894 "Window 45" = WINDOW 2895 GLASS-TYPE = "N-E Glazing" 2896 HEIGHT = 14 2897 WIDTH = 15 2898 .. 2899 "Interior Wall 95" = INTERIOR-WALL 2900 CONSTRUCTION = "Slab-on-Grade Construction" 2901 INT-WALL-TYPE = ADIABATIC 2902 LOCATION = BOTTOM 2903 2904 "Interior Wall 96" = INTERIOR-WALL 2905 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 2906 INT-WALL-TYPE = ADIABATIC 2907 LOCATION = TOP 2908 .. 2909 "Interior Wall 126" = INTERIOR-WALL 2910 NEXT-TO = "11 SHELVES" 2911 CONSTRUCTION = "Interior Wall Construction" 2912 LOCATION = SPACE-V1 2913 2914 "Interior Wall 127" = INTERIOR-WALL �. 2915 NEXT-TO = "66 PROG ROOM STOR." 2916 CONSTRUCTION = "Interior Wall Construction" 2917 LOCATION = SPACE-V4 2918 2919 "Undrgrnd Wall 14" = UNDERGROUND-WALL 2920 CONSTRUCTION = "Slab-on-Grade Construction" 2921 HEIGHT = 1 2922 LOCATION = SPACE-V2 2923 2924 "Undrgrnd.Wall 30" = UNDERGROUND-WALL 2925 CONSTRUCTION = "Slab-on-Grade Construction" 2926 HEIGHT = 1 2927 LOCATION = SPACE-V3 �- 2928 2929 "1 ENTRY HALLWAY PLENUM" = SPACE 2930 X = 15 ... 2931 HEIGHT = 2 2932 SHAPE = BOX 2933 WIDTH = 61 _ 2934 DEPTH = 15 2935 ZONE-TYPE = PLENUM 2936 LIGHTING-W/AREA = ( 0 ) 2937 EQUIPMENT-W/AREA = ( 0 ) 2938 2939 "Exterior Wall 38 PLENUM" = EXTERIOR-WALL 2940 CONSTRUCTION = "Exterior Wall Construction" 2941 LOCATION = SPACE-V1 2942 .. 2943 "2 CIRC DESK SOUTH PERIM PLENUM" = SPACE 2944 X = 76 Page: 32— File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 2945 HEIGHT = 2 2946 SHAPE = BOX 2947 WIDTH = 36 '—' 2948 DEPTH = 15 2949 ZONE-TYPE = PLENUM 2950 LIGHTING-W/AREA = ( 0 ) 2951 EQUIPMENT-W/AREA = ( 0 ) 2952 2953 "Exterior Wall 39 PLENUM" = EXTERIOR-WALL - 2954 CONSTRUCTION = "Exterior Wall Construction" 2955 LOCATION = SPACE-V1 2956 2957 "3 CIRC WORKROOM SOUTH PERIM PLEN" = SPACE 2958 X = 112 2959 HEIGHT = 2 2960 SHAPE = BOX — 2• 961 WIDTH = 59 2962 DEPTH = 15 2963 ZONE-TYPE = PLENUM — 2964 LIGHTING-W/AREA = ( 0 ) 2965 EQUIPMENT-W/AREA = ( 0 ) 2966 .. 2967 "Exterior Wall 40 PLENUM" = EXTERIOR-WALL 2968 CONSTRUCTION = "Exterior Wall Construction" 2969 LOCATION = SPACE-V1 - 2970 2971 "4 ELEC PLENUM" = SPACE 2972 X = 171 2973 HEIGHT = 2 2974 SHAPE = BOX 2975 WIDTH = 13 2976 DEPTH = 14 - 2977 ZONE-TYPE = PLENUM 2978 LIGHTING-W/AREA = ( 0 ) 2979 EQUIPMENT-W/AREA = ( 0 ) 2980 2981 "Exterior Wall 41 PLENUM" = EXTERIOR-WALL 2982 CONSTRUCTION = "Exterior Wall Construction" - 2983 LOCATION = SPACE-V1 2984 2985 "Exterior Wall 42 PLENUM" = EXTERIOR-WALL 2986 CONSTRUCTION = "Exterior Wall Construction" 2987 LOCATION = SPACE-V2 2988 2989 "5 DONATIONS PLENUM" = SPACE 2• 990 X = 192 2991 Y = 14 2992 HEIGHT = 2 '""' 2993 SHAPE = BOX 2994 WIDTH = 21 2995 DEPTH = 13 2996 ZONE-TYPE = PLENUM 2997 LIGHTING-W/AREA = ( 0 ) 2998 EQUIPMENT-W/AREA = ( 0 ) ▪ 2999 3000 "Exterior Wall 44 PLENUM" = EXTERIOR-WALL 3001 CONSTRUCTION = "Exterior Wall Construction" 3002 LOCATION = SPACE-V1 3003 3004 "Exterior Wall 45 PLENUM" = EXTERIOR-WALL 3005 CONSTRUCTION = "Exterior Wall Construction" 3006 LOCATION = SPACE-V2 3007 3008 "6 MAIL/LOAD PLENUM" = SPACE - 3009 X = 192 3010 Y = 27 3011 HEIGHT = 2 — 3012 SHAPE = BOX 3013 WIDTH = 21 3014 DEPTH = 20 3015 ZONE-TYPE = PLENUM 3016 LIGHTING-W/AREA = ( 0 ) 3017 EQUIPMENT-W/AREA = ( 0 ) 3018 3• 019 "Exterior Wall 46 PLENUM" = EXTERIOR-WALL 3020 CONSTRUCTION = "Exterior Wall Construction" 3021 LOCATION = SPACE-V2 ▪ 3022 3023 "7 TECH SERV. EAST PERIM PLENUM" = SPACE 3024 X = 188 ▪ 3025 Y = 47 3026 HEIGHT = 2 3027 SHAPE = BOX — 3028 WIDTH = 25 3029 DEPTH = 32 3030 ZONE-TYPE = PLENUM �. 3031 LIGHTING-W/AREA = ( 0 ) 3032 EQUIPMENT-W/AREA = ( 0 ) 3033 3034 "Exterior Wall 47 PLENUM" = EXTERIOR-WALL 3• 035 CONSTRUCTION = "Exterior Wall Construction" 3036 LOCATION = SPACE-V2 Page: 33 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 3037 3038 "8 TECH SERV. NORTH PERIM PLENUM" = SPACE 3039 X = 188 3040 Y = 79 3041 HEIGHT = 2 3042 SHAPE = BOX 3043 WIDTH = 25 3044 DEPTH = 15 3045 ZONE-TYPE = PLENUM 3046 LIGHTING-W/AREA = ( 0 ) 3047 EQUIPMENT-W/AREA = ( 0 ) 3048 3049 "Exterior Wall 48 PLENUM" = EXTERIOR-WALL 3050 CONSTRUCTION = "Exterior Wall Construction" 3051 LOCATION = SPACE-V2 3052 3053 "Exterior Wall 49 PLENUM" = EXTERIOR-WALL �- 3054 CONSTRUCTION = "Exterior Wall Construction" 3055 LOCATION = SPACE-V3 3056 3057 "9 VOL COORD. PLENUM" = SPACE 3058 X = 151 3059 Y = 79 3060 HEIGHT = 2 3061 SHAPE = BOX 3062 WIDTH = 11 3063 DEPTH = 15 3064 ZONE-TYPE = PLENUM 3065 LIGHTING-W/AREA = ( 0 ) 3066 EQUIPMENT-W/AREA = ( 0 ) 3067 .. 3068 "Exterior Wall 50 PLENUM" = EXTERIOR-WALL 3069 CONSTRUCTION = "Exterior Wall Construction" 3070 LOCATION = SPACE-V3 3071 3072 "10SEATING NORTH PERIM PLENUM" = SPACE 3073 X = 103 3074 Y = 79 3075 HEIGHT = 2 _ 3076 SHAPE = BOX 3077 WIDTH = 48 3078 DEPTH = 15 3079 ZONE-TYPE = PLENUM 3080 LIGHTING-W/AREA = ( 0 ) 3081 EQUIPMENT-W/AREA = ( 0 ) 3082 .. 3083 "Exterior Wall 51 PLENUM" = EXTERIOR-WALL 3084 CONSTRUCTION = "Exterior Wall Construction" 3085 LOCATION = SPACE-V3 3086 3087 "11 SHELVES PLENUM" = SPACE 3088 Y = 94 3089 HEIGHT = 2 3090 SHAPE = POLYGON 3091 ZONE-TYPE = PLENUM 3092 LIGHTING-W/AREA = ( 0 ) 3093 EQUIPMENT-W/AREA = ( 0 ) 3094 POLYGON = "Polygon 1" 3095 .. 3096 "Exterior Wall 111 PLENUM" = EXTERIOR-WALL 3097 CONSTRUCTION = "Exterior Wall Construction" 3098 LOCATION = SPACE-V1 3099 3100 "12 SHELVES WEST PERIM PLENUM" = SPACE 3101 Y = 48 3102 HEIGHT = 2 3103 SHAPE = POLYGON 3104 ZONE-TYPE = PLENUM _ 3105 LIGHTING-W/AREA = ( 0 ) 3106 EQUIPMENT-W/AREA = ( 0 ) 3107 POLYGON = "Polygon 2" 3108 .. 3109 "Exterior Wall 53 PLENUM" = EXTERIOR-WALL 3110 CONSTRUCTION = "Exterior Wall Construction" 3111 LOCATION = SPACE-V4 3112 3113 "Exterior Wall 112 PLENUM" = EXTERIOR-WALL 3114 CONSTRUCTION = "Exterior Wall Construction" 3115 LOCATION = SPACE-V3 3116 3117 "13 YOUTH SERVICE PLENUM" = SPACE 3118 HEIGHT = 2 3119 SHAPE = POLYGON 3120 ZONE-TYPE = PLENUM _ 3121 AIR-CHANGES/HR = 0.19 3122 LIGHTING-W/AREA = ( 0 ) 3123 EQUIPMENT-W/AREA = ( 0 ) 3124 POLYGON = "Polygon 48" 3125 .. 3126 "Exterior Wall 54 PLENUM" = EXTERIOR-WALL 3127 CONSTRUCTION = "Exterior Wall Construction" 3128 LOCATION = SPACE-V1 Page: 34� e'ile: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM - 3129 3130 "14 ELEV MACH/JAN PLENUM" = SPACE 3131 X = 15 - 3132 Y = 15 3133 HEIGHT = 2 3134 SHAPE = BOX - 3135 WIDTH = 20 3136 DEPTH = 15 3137 ZONE-TYPE = PLENUM - 3138 LIGHTING-W/AREA = ( 0 ) 3139 EQUIPMENT-W/AREA = ( 0 ) 3140 3141 "16 NEW BOOKS + AV PLENUM" = SPACE 3142 X = 93 3143 Y = 40 _ 3144 HEIGHT = 2 3145 SHAPE = POLYGON 3146 ZONE-TYPE = PLENUM 3147 LIGHTING-W/AREA = ( 0 ) 3148 EQUIPMENT-W/AREA = ( 0 ) 3149 POLYGON = "Polygon 35" 3150 —. 3151 "17 FAMILY W.C. PLENUM" = SPACE 3152 X = 35 3153 Y = 42 - 3154 HEIGHT = 2 3155 SHAPE = BOX 3156 WIDTH = 15 _ 3157 DEPTH = 6 3158 ZONE-TYPE = PLENUM 3159 LIGHTING-W/AREA = ( 0 ) 3160 EQUIPMENT-W/AREA = ( 0 ) - 3161 3162 "18 IDF CLOSET PLENUM" = SPACE 3163 X = 50 3164 Y = 42 3165 HEIGHT = 2 3166 SHAPE = BOX - 3167 WIDTH = 10 3168 DEPTH = 6 3169 ZONE-TYPE = PLENUM 3170 LIGHTING-W/AREA = ( 0 ) 3171 EQUIPMENT-W/AREA = ( 0 ) 3172 3173 "19 INFO DESK HALLWAY PLENUM" = SPACE -3174 X = 93 3175 Y = 15 3176 AZIMUTH = -90 ..""3177 HEIGHT = 2 3178 SHAPE = POLYGON 3179 ZONE-TYPE = PLENUM —.3180 LIGHTING-W/AREA = ( 0 ) 3181 EQUIPMENT-W/AREA = ( 0 ) 3182 POLYGON = "Polygon 3" - 3183 3184 "20 CIRC DESK PLENUM" = SPACE 3185 X = 93 3186 Y = 15 3187 HEIGHT = 2 3188 SHAPE = BOX 3189 WIDTH = 19 —.3190 DEPTH = 25 3191 ZONE-TYPE = PLENUM 3192 LIGHTING-W/AREA = ( 0 ) "�3193 EQUIPMENT-W/AREA = ( 0 ) 3194 3195 "21 CIRC WORKROOM INTERIOR PLENUM" = SPACE .� 3196 X = 112 3197 Y = 15 3198 HEIGHT = 2 3199 SHAPE = BOX 3200 WIDTH = 59 3201 DEPTH = 25 3202 ZONE-TYPE = PLENUM 3203 LIGHTING-W/AREA = ( 0 ) 3204 EQUIPMENT-W/AREA = ( 0 ) 3205 —.3206 "22 STAFF ENTRY HALLWAY PLENUM" = SPACE 3207 X = 192 3208 Y = 47 ▪ 3209 AZIMUTH = 180 3210 HEIGHT = 2 3211 SHAPE = POLYGON ▪ 3212 ZONE-TYPE = PLENUM 3213 LIGHTING-W/AREA = ( 0 ) 3214 EQUIPMENT-W/AREA = ( 0 ) 3215 POLYGON = "Polygon 4" 3216 3217 "Exterior Wall 43 PLENUM" = EXTERIOR-WALL 3218 CONSTRUCTION = "Exterior Wall Construction" `3219 X = 9 3220 WIDTH = 9 ... Page: 35 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 3221 AZIMUTH = 0 3222 LOCATION = SPACE-V6 3223 3224 "23 WC PLENUM" = SPACE _ 3225 X = 151 3226 Y = 47 3227 HEIGHT = 2 3228 SHAPE = BOX 3229 WIDTH = 31 3230 DEPTH = 32 3231 ZONE-TYPE = PLENUM 3232 LIGHTING-W/AREA = ( 0 ) 3233 EQUIPMENT-W/AREA = ( 0 ) 3234 3235 "24 HALLWAY PLENUM" = SPACE 3236 X = 188 3237 Y = 79 3238 AZIMUTH = 180 3239 HEIGHT = 2 3240 SHAPE = POLYGON _ 3241 ZONE-TYPE = PLENUM 3242 LIGHTING-W/AREA = ( 0 ) 3243 EQUIPMENT-W/AREA = ( 0 ) 3244 POLYGON = "Polygon 5" 3245 3246 "25 LOBBY PLENUM" = SPACE 3247 X = 15 3248 Y = 0 3249 Z = 26 3250 HEIGHT = 2 3251 SHAPE = POLYGON 3252 ZONE-TYPE = PLENUM 3253 LIGHTING-W/AREA = ( 0 ) 3254 EQUIPMENT-W/AREA = ( 0 ) 3255 POLYGON = "Polygon 6" 3256 3257 "Exterior Wall 123 PLENUM" = EXTERIOR-WALL 3258 CONSTRUCTION = "Roof Construction" 3259 LOCATION = TOP 3260 3261 "26 COMMUNITY ROOM EAST PERIM PLE" = SPACE 3262 Z = 24 3263 HEIGHT = 2 3264 SHAPE = POLYGON 3265 ZONE-TYPE = PLENUM 3266 LIGHTING-W/AREA = ( 0 ) 3267 EQUIPMENT-W/AREA = ( 0 ) 3268 POLYGON = "Polygon 7" 3269 _ 3270 "Exterior Wall 2 PLENUM" = EXTERIOR-WALL 3271 CONSTRUCTION = "COMMUNITY WING ROOF CNS" 3272 Z = 4 3273 LOCATION = TOP 3274 3275 "Exterior Wall 59 PLENUM" = EXTERIOR-WALL 3276 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 3277 Z = 2 3278 LOCATION = SPACE-V1 3279 3280 "27 COMMUNITY ROOM CENTER PLENUM" = SPACE 3281 Z = 24 3282 HEIGHT = 2 3283 SHAPE = POLYGON 3284 ZONE-TYPE = PLENUM 3285 LIGHTING-W/AREA = ( 0 ) _ 3286 EQUIPMENT-W/AREA = ( 0 ) 3287 POLYGON = "Polygon 8" 3288 3289 "Exterior Wall 3 PLENUM" = EXTERIOR-WALL 3290 CONSTRUCTION = "COMMUNITY WING ROOF CNS" 3291 Z = 4 3292 LOCATION = TOP 3293 3294 "28 COMMUNITY ROOM WEST PERIM PLE" = SPACE 3295 Z = 24 3296 HEIGHT = 2 3297 SHAPE = POLYGON 3298 ZONE-TYPE = PLENUM 3299 LIGHTING-W/AREA = ( 0 ) 3300 EQUIPMENT-W/AREA = ( 0 ) 3301 POLYGON = "Polygon 9" 3302 3303 "Exterior Wall 4 PLENUM" = EXTERIOR-WALL 3304 CONSTRUCTION = "COMMUNITY WING ROOF CNS" 3305 Z = 4 3306 LOCATION = TOP 3307 3308 "Exterior Wall 61 PLENUM" =EXTERIOR-WALL ..� 3309 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 3310 Z = 2 3311 LOCATION = SPACE-V4 3312 .. Page: 36 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 3313 "29 COMMUNITY ROOM NORTH PERIM PL" = SPACE 3314 Z = 24 _ 3315 HEIGHT = 2 3316 SHAPE = POLYGON 3317 ZONE-TYPE = PLENUM 3318 LIGHTING-W/AREA = ( 0 ) ▪ 3319 EQUIPMENT-W/AREA = ( 0 ) 3320 POLYGON = "Polygon 39" 3321 - 3322 "Exterior Wall 5 PLENUM" = EXTERIOR-WALL 3323 CONSTRUCTION ="COMMUNITY WING ROOF CNS" 3324 Z = 4 - 3325 LOCATION = TOP 3326 3327 "Exterior Wall 120 PLENUM" = EXTERIOR-WALL 3328 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 3329 Z = 2 3330 LOCATION = SPACE-V4 3331 ▪ 3332 "30 COMMUNITY ROOM STORAGE PLENUM" = SPACE 3333 Z = 24 3334 HEIGHT = 2 -- 3335 SHAPE = POLYGON 3336 ZONE-TYPE = PLENUM 3337 LIGHTING-W/AREA = ( 0 ) - 3338 EQUIPMENT-W/AREA = ( 0 ) 3339 POLYGON = "Polygon 98" 3340 - 3341 "Exterior Wall 7 PLENUM" = EXTERIOR-WALL 3342 CONSTRUCTION = "COMMUNITY WING ROOF CNS" 3343 Z = 4 _ 3344 LOCATION = TOP 3345 3346 "Exterior Wall 153 PLENUM" = EXTERIOR-WALL 3347 CONSTRUCTION = "COMMUNITY WING WALLS CNS" - 3348 Z = 2 3349 LOCATION = SPACE-V2 3350 - 3351 "Exterior Wall 247" = EXTERIOR-WALL 3352 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 3353 Z = 2 ▪ 3354 HEIGHT = 2 3355 LOCATION = SPACE-V1 3356 3357 "31 COMMUNITY ROOM VESTIBULE PLEN" = SPACE 3358 Z = 24 3359 HEIGHT = 2 3360 SHAPE = POLYGON - 3361 ZONE-TYPE = PLENUM 3362 LIGHTING-W/AREA = ( 0 ) 3363 EQUIPMENT-W/AREA = ( 0 ) ▪ 3364 POLYGON = "Polygon 97" 3365 3366 "Exterior Wall 6 PLENUM" = EXTERIOR-WALL •� 3367 CONSTRUCTION = "COMMUNITY WING ROOF CNS" 3368 Z = 4 3369 LOCATION = TOP __ 3370 3371 "Exterior Wall 62 PLENUM" = EXTERIOR-WALL 3372 CONSTRUCTION = "COMMUNITY WING WALLS CNS" _ 3373 Z = 2 3374 LOCATION = SPACE-V1 3375 3376 "Exterior Wall 64 PLENUM" = EXTERIOR-WALL - 3377 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 3378 Z = 2 3379 LOCATION = SPACE-V5 ▪ 3380 3381 "Exterior Wall 151 PLENUM" = EXTERIOR-WALL 3382 CONSTRUCTION = "COMMUNITY WING WALLS CNS" ▪ 3383 Z = 2 3384 HEIGHT = 2 3385 WIDTH = 7 3386 LOCATION = SPACE-V2 3387 3388 "34 COMMUNITY ROOM VESTIBULE PLEN" = SPACE 3389 Z = 24 - 3390 HEIGHT = 2 3391 SHAPE = POLYGON 3392 ZONE-TYPE = PLENUM — 3393 LIGHTING-W/AREA = ( 0 ) 3394 EQUIPMENT-W/AREA = ( 0 ) 3395 POLYGON = "Polygon 86" ▪ 3396 3397 "Exterior Wall 11 PLENUM" = EXTERIOR-WALL 3398 CONSTRUCTION = "COMMUNITY WING ROOF CNS" .. 3399 Z = 4 3400 LOCATION = TOP 3401 3402 "Exterior Wall 121 PLENUM" = EXTERIOR-WALL 3403 CONSTRUCTION = "Exterior Wall Construction" 3404 Z = 2 Page: 37 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 3405 LOCATION = SPACE-V1 �. 3406 3407 "35 PANTRY PLENUM" = SPACE 3408 Z = 12 3409 HEIGHT = 2 3410 SHAPE = POLYGON 3411 ZONE-TYPE = PLENUM 3412 LIGHTING-W/AREA = ( 0 ) 3413 EQUIPMENT-W/AREA = ( 0 ) 3414 POLYGON = "Polygon 43" 3415 3416 "Exterior Wall 8 PLENUM" = EXTERIOR-WALL 3417 CONSTRUCTION = "COMMUNITY WING ROOF CNS" 3418 LOCATION = TOP 3419 3420 "Exterior Wall 118 PLENUM" = EXTERIOR-WALL 3421 CONSTRUCTION = "Exterior Wall Construction" 3422 LOCATION = SPACE-V1 3423 3424 "Exterior Wall 119 PLENUM" = EXTERIOR-WALL 3425 CONSTRUCTION = "Exterior Wall Construction" 3426 LOCATION = SPACE-V4 3427 3428 "l0A OPAC SELF CHECK NORTH PLENUM" = SPACE 3429 X = 93 3430 Y = 79 3431 HEIGHT = 2 3432 SHAPE = BOX 3433 WIDTH = 10 3434 DEPTH = 15 3435 ZONE-TYPE = PLENUM 3436 LIGHTING-W/AREA = ( 0 ) 3437 EQUIPMENT-W/AREA = ( 0 ) 3438 3439 "Exterior Wall 104 PLENUM" = EXTERIOR-WALL 3440 CONSTRUCTION = "Exterior Wall Construction" 3441 LOCATION = SPACE-V3 3442 3443 "16A OPAC/SELF CHECK INTERIOR PLE" = SPACE 3444 X = 93 3445 Y = 62 3446 HEIGHT = 2 3447 SHAPE = BOX 3448 WIDTH = 10 3449 DEPTH = 17 3450 ZONE-TYPE = PLENUM 3451 LIGHTING-W/AREA = ( 0 ) 3452 EQUIPMENT-W/AREA = ( 0 ) 3453 3454 "63 RESTROOMS PLENUM" = SPACE 3455 SHAPE = POLYGON 3456 ZONE-TYPE = PLENUM 3457 LIGHTING-W/AREA = ( 0 ) 3458 EQUIPMENT-W/AREA = ( 0 ) 3459 POLYGON = "Polygon 45" 3460 3461 "Exterior Wall 117 PLENUM" = EXTERIOR-WALL 3462 CONSTRUCTION = "COMMUNITY WING WALLS CNS" 3463 LOCATION = SPACE-V1 3464 3465 "Exterior Wall 122 PLENUM" = EXTERIOR-WALL 3466 CONSTRUCTION = "COMMUNITY WING ROOF CNS" 3467 LOCATION = TOP 3468 3469 "62 COFFEE PLENUM" = SPACE 3470 HEIGHT = 2 3471 SHAPE = POLYGON 3472 ZONE-TYPE = PLENUM 3473 LIGHTING-W/AREA = ( 0 ) 3474 EQUIPMENT-W/AREA = ( 0 ) 3475 POLYGON = "Polygon 47" 3476 3477 "64 SHEVES NORTH PERIM PLENUM" = SPACE 3478 X = 60 3479 Y = 79 3480 HEIGHT = 2 3481 SHAPE = BOX 3482 WIDTH = 33 3483 DEPTH = 15 3484 ZONE-TYPE = PLENUM 3485 LIGHTING-W/AREA = ( 0 ) 3486 EQUIPMENT-W/AREA = ( 0 ) 3487 3488 "Exterior Wall 106 PLENUM" = EXTERIOR-WALL 3489 CONSTRUCTION = "Exterior Wall Construction" 3490 LOCATION = SPACE-V3 3491 3492 "65 STAFF ROOM PLENUM" = SPACE 3493 X = 162 3494 Y = 79 3495 HEIGHT = 2 3496 SHAPE = BOX Page: 38"— File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM - 3497 WIDTH = 26 3498 DEPTH = 15 3499 ZONE-TYPE = PLENUM - 3500 LIGHTING-W/AREA = ( 0 ) 3501 EQUIPMENT-W/AREA = ( 0 ) 3502 — 3503 "Exterior Wall 105 PLENUM" = EXTERIOR-WALL 3504 CONSTRUCTION = "Exterior Wall Construction" 3505 LOCATION = SPACE-V3 -� 3506 3507 "66 PROG ROOM STOR. PLENUM" = SPACE 3508 X = 15 .. 3509 Y = 94 3510 HEIGHT = 2 3511 SHAPE = BOX _ 3512 WIDTH = 10 3513 DEPTH = 32 3514 ZONE-TYPE = PLENUM 3515 LIGHTING-W/AREA = ( 0 ) ▪ 3516 EQUIPMENT-W/AREA = ( 0 ) 3517 3518 "Exterior Wall 109 PLENUM" = EXTERIOR-WALL -� 3519 CONSTRUCTION = "Exterior Wall Construction" 3520 LOCATION = SPACE-V3 3521 - 3522 "Exterior Wall 110 PLENUM" = EXTERIOR-WALL 3523 CONSTRUCTION = "Exterior Wall Construction" 3524 LOCATION = SPACE-V4 3525 3526 "67 PROG ROOM PLENUM" = SPACE 3527 X = 25 3528 Y = 94 - 3529 HEIGHT = 2 3530 SHAPE = POLYGON 3531 ZONE-TYPE = PLENUM - 3532 LIGHTING-W/AREA = ( 0 ) 3533 EQUIPMENT-W/AREA = ( 0 ) 3534 POLYGON = "Polygon 55" ▪ 3535 3536 "Exterior Wall 107 PLENUM" = EXTERIOR-WALL 3537 CONSTRUCTION = "Exterior Wall Construction" ▪ 3538 LOCATION = SPACE-V2 3539 3540 "Exterior Wall 108 PLENUM" = EXTERIOR-WALL 3541 CONSTRUCTION = "Exterior Wall Construction" 3542 LOCATION = SPACE-V3 3543 3544 "15 CHILDREN'S AREA/SHELVS PLENUM" = SPACE - 3545 X = 15 3546 Y = 48 3547 SHAPE = BOX — 3548 WIDTH = 78 3549 DEPTH = 31 3550 ZONE-TYPE = PLENUM ▪ 3551 LIGHTING-W/AREA = ( 0 ) 3552 EQUIPMENT-W/AREA = ( 0 ) 3553 3554 "Floor 2" = FLOOR 3555 Z = 14 3556 SHAPE = BOX 3557 FLOOR-HEIGHT = 12 _ 3558 WIDTH = 100 3559 DEPTH = 100 3560 SPACE-HEIGHT = 12 - 3561 3562 "36 OREGON HISTORY" = SPACE 3563 X = 30 — 3564 SHAPE = BOX 3565 WIDTH = 30 3566 DEPTH = 15 ▪ 3567 AIR-CHANGES/HR = 0.4 3568 LIGHTING-W/AREA = ( 1.7 ) 3569 EQUIPMENT-W/AREA = ( 1.5 ) 3570 DAYLIGHTING = NO 3571 LIGHT-REF-POINT1 = ( 15, 10 ) 3572 AREA/PERSON = 100 3573 3574 "Exterior Wall 68" = EXTERIOR-WALL 3575 CONSTRUCTION = "Exterior Wall Construction" 3576 LOCATION = SPACE-V1 ""' 3577 3578 "Window 10" = WINDOW 3579 GLASS-TYPE = "S-W Glazing" ▪ 3580 X = 5 3581 Y = 3 3582 HEIGHT = 6 ... 3583 WIDTH = 20 3584 .. 3585 "Interior Wall 36" = INTERIOR-WALL 3586 CONSTRUCTION = "Floor Construction" 3587 INT-WALL-TYPE = ADIABATIC 3588 LOCATION = BOTTOM — Page: 39 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 3589 .. fon 3590 "Interior Wall 128" = INTERIOR-WALL 3591 NEXT-TO = "37 YOUNG ADULTS" 3592 CONSTRUCTION = "Interior Wall Construction" 3593 LOCATION = SPACE-V2 3594 3595 "Interior Wall 129" = INTERIOR-WALL 3596 NEXT-TO = "49 STAIRWELL" 3597 CONSTRUCTION = "Interior Wall Construction" 3598 LOCATION = SPACE-V3 3599 3600 "Interior Wall 130" = INTERIOR-WALL 3601 NEXT-TO = "68 QUIET STUDY" 3602 CONSTRUCTION = "Interior Wall Construction" 3603 LOCATION = SPACE-V4 3604 3605 "Interior Wall 144" = INTERIOR-WALL �- 3606 NEXT-TO = "36 OREGON HISTORY PLENUM" 3607 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 3608 LOCATION = TOP 3609 3610 "37 YOUNG ADULTS" = SPACE 3611 X = 60 3612 SHAPE = BOX 3613 WIDTH = 30 3614 DEPTH = 15 3615 AIR-CHANGES/HR = 0.4 .� 3616 NUMBER-OF-PEOPLE = 16 3617 LIGHTING-W/AREA = ( 1.7 ) 3618 EQUIPMENT-W/AREA = ( 1.5 ) 3619 DAYLIGHTING = NO 3620 LIGHT-REF-POINT1 = ( 15, 10 ) 3621 .. 3622 "Exterior Wall 69" = EXTERIOR-WALL 3623 CONSTRUCTION = "Exterior Wall Construction" 3624 LOCATION = SPACE-V1 3625 3626 "Window 11" = WINDOW 3627 GLASS-TYPE = "S-W Glazing" 3628 X = 5 3629 Y = 3 3630 HEIGHT = 6 3631 WIDTH = 20 3632 3633 "Interior Wall 37" = INTERIOR-WALL 3634 CONSTRUCTION = "Floor Construction" 3635 INT-WALL-TYPE = ADIABATIC 3636 LOCATION = BOTTOM 3637 .. 3638 "Interior Wall 131" = INTERIOR-WALL 3639 NEXT-TO = "38 SHELVES SOUTH PERIMETER" 3640 CONSTRUCTION = "Interior Wall Construction" 3641 LOCATION = SPACE-V2 3642 3643 "Interior Wall 132" = INTERIOR-WALL _ 3644 NEXT-TO = "51 REFERENCE DESK/OPACS" 3645 CONSTRUCTION = "Interior Wall Construction" 3646 LOCATION" = SPACE-V3 3647 .. 3648 "Interior Wall 145" = INTERIOR-WALL 3649 NEXT-TO = "37 YOUNG ADULTS PLENUM" 3650 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 3651 LOCATION = TOP 3652 3653 "38 SHELVES SOUTH PERIMETER" = SPACE 3654 X = 90 3655 SHAPE = BOX 3656 WIDTH = 39 _ 3657 DEPTH = 15 3658 AIR-CHANGES/HR = 0.4 3659 3660 "Exterior Wall 70" = EXTERIOR-WALL 3661 CONSTRUCTION = "Exterior Wall Construction" 3662 LOCATION = SPACE-V1 3663 3664 "Window 12" = WINDOW 3665 GLASS-TYPE = "S-W Glazing" 3666 X = 9.5 3667 Y = 3 3668 HEIGHT = 6 3669 WIDTH = 20 3670 3671 "Interior Wall 38" = INTERIOR-WALL 3672 CONSTRUCTION = "Floor Construction" _ 3673 INT-WALL-TYPE = ADIABATIC 3674 LOCATION = BOTTOM 3675 .. 3676 "39 QUITE STUDY" = SPACE 3677 X = 129 3678 SHAPE = BOX 3679 WIDTH = 21 3680 DEPTH = 15 Page: 40� File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 3681 AIR-CHANGES/HR = 0.4 3682 LIGHTING-W/AREA = ( 1.7 ) 3683 EQUIPMENT-W/AREA = ( 1.5 ) 3684 DAYLIGHTING = NO 3685 LIGHT-REF-POINT1 = ( 10, 10 ) 3686 AREA/PERSON = 100 3687 3688 "Exterior Wall 71" = EXTERIOR-WALL 3689 CONSTRUCTION = "Exterior Wall Construction" -r 3690 LOCATION = SPACE-V1 3691 3692 "Window 13" = WINDOW 3693 GLASS-TYPE = "S-W Glazing" 3694 X = 0.5 3695 Y = 3 3696 HEIGHT = 6 3697 WIDTH = 20 3698 3699 "Interior Wall 39" = INTERIOR-WALL 3700 CONSTRUCTION = "Floor Construction" 3701 INT-WALL-TYPE = ADIABATIC 3702 LOCATION = BOTTOM 3703 3704 "Interior Wall 133" = INTERIOR-WALL 3705 NEXT-TO = "41 TRAINING ROOM" .— 3706 CONSTRUCTION = "Interior Wall Construction" 3707 LOCATION = SPACE-V2 3708 3709 "Interior Wall 134" = INTERIOR-WALL 3710 NEXT-TO = "52 ELEC. INFO" 3711 CONSTRUCTION = "Interior Wall Construction" 3712 LOCATION = SPACE-V3 - 3713 3714 "Interior Wall 135" = INTERIOR-WALL 3715 NEXT-TO = "38 SHELVES SOUTH PERIMETER" - 3716 CONSTRUCTION = "Interior Wall Construction" 3717 LOCATION = SPACE-V4 3718 —. 3719 "Interior Wall 146" = INTERIOR-WALL 3720 NEXT-TO = "39 QUITE STUDY PLENUM" 3721 CONSTRUCTION = "Accoustic Ceiling Tile Construct" .� 3722 LOCATION = TOP 3723 3724 "40 DATA/MECH" = SPACE 3725 X = 170 3726 SHAPE = BOX 3727 WIDTH = 14 3728 DEPTH = 25 ▪ 3729 AIR-CHANGES/HR = 0.48 3730 LIGHTING-W/AREA = ( 0.8 ) 3731 EQUIPMENT-W/AREA = ( 20 ) ▪ 3732 AREA/PERSON = 600 3733 3734 "Exterior Wall 72" = EXTERIOR-WALL ▪ 3735 CONSTRUCTION = "Exterior Wall Construction" 3736 LOCATION = SPACE-V1 3737 ▪ 3738 "Exterior Wall 124" = EXTERIOR-WALL 3739 CONSTRUCTION = "Exterior Wall Construction" 3740 WIDTH = 14 3741 LOCATION = SPACE-V2 3742 3743 "Interior Wall 40" = INTERIOR-WALL 3744 CONSTRUCTION = "Floor Construction" -- 3745 INT-WALL-TYPE = ADIABATIC 3746 LOCATION = BOTTOM 3747 ▪ 3748 "41 TRAINING ROOM" = SPACE 3749 X = 150 3750 SHAPE = BOX ▪ 3751 WIDTH = 20 3752 DEPTH = 40 3753 AIR-CHANGES/HR = 0.65 3754 LIGHTING-W/AREA = ( 1.2 ) 3755 EQUIPMENT-W/AREA = ( 0.5 ) 3756 AREA/PERSON = 100 3757 mm 3758 "Exterior Wall 73" = EXTERIOR-WALL 3759 CONSTRUCTION = "Exterior Wall Construction" 3760 LOCATION = SPACE-V1 '" 3761 3762 "Interior Wall 41" = INTERIOR-WALL 3763 CONSTRUCTION = "Floor Construction" 3764 INT-WALL-TYPE = ADIABATIC 3765 LOCATION = BOTTOM 3766 3767 "42 SHAFT" = SPACE 3768 X = 170 3769 Y = 25 3770 SHAPE = BOX 3771 WIDTH = 14 3772 DEPTH = 15 Page: 41 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 3773 ZONE-TYPE = UNCONDITIONED 3774 NUMBER-OF-PEOPLE = 0 3775 LIGHTING-W/AREA = ( 0 ) 3776 EQUIPMENT-W/AREA = ( 0 ) 3777 3778 "Exterior Wall 185" EXTERIOR-WALL 3779 CONSTRUCTION = "Roof Construction" 3780 Z = 14 3781 LOCATION = TOP 3782 3783 "43 REF. WORKROOM" = SPACE 3784 X = 193 3785 Y = 14 3786 SHAPE = BOX 3787 WIDTH = 20 3788 DEPTH = 53 3789 AIR-CHANGES/HR = 0.41 3790 LIGHTING-W/AREA = ( 1.2 ) 3791 EQUIPMENT-W/AREA = ( 0.5 ) 3792 AREA/PERSON = 100 3793 3794 "Exterior Wall 75" = EXTERIOR-WALL 3795 CONSTRUCTION = "Exterior Wall Construction" _ 3796 LOCATION = SPACE-V1 3797 3798 "Window 14" = WINDOW 3799 GLASS-TYPE = "S-W Glazing" 3800 X = 13.5 3801 Y = 3 3802 HEIGHT = 6 3803 WIDTH = 6.5 3804 3805 "Exterior Wall 76" = EXTERIOR-WALL 3806 CONSTRUCTION = "Exterior Wall Construction" 3807 LOCATION = SPACE-V2 3808 3809 "Window 15" = WINDOW 3810 GLASS-TYPE _ "N-E Glazing" 3811 Y = 3 _ 3812 HEIGHT = 6 3813 WIDTH = 6.5 3814 3815 "Window 16" = WINDOW 3816 GLASS-TYPE = "N-E Glazing" 3817 X = 32 3818 Y = 3 3819 HEIGHT = 6 3820 WIDTH = 16 3821 .. 3822 "Interior Wall 43" = INTERIOR-WALL 3823 CONSTRUCTION = "Floor Construction" 3824. INT-WALL-TYPE = ADIABATIC 3825 LOCATION = BOTTOM 3826 3827 "44 OFFICE" = SPACE 3828 X = 198 3829 Y = 67 3830 SHAPE = BOX 3831 WIDTH = 15 ""' 3832 DEPTH = 11 3833 AIR-CHANGES/HR = 0.4 3834 LIGHTING-W/AREA = ( 1.2 ) 3835 EQUIPMENT-W/AREA = ( 1.5 ) 3836 3837 "Exterior Wall 78" = EXTERIOR-WALL 3838 CONSTRUCTION = "Exterior Wall Construction" 3839 LOCATION = SPACE-V2 3840 3841 "Window 17" = WINDOW 3842 GLASS-TYPE _ "N-E Glazing" 3843 X = 2 3844 Y = 3 3845 HEIGHT = 6 3846 WIDTH = 9 3847 .. 3848 "Interior Wall 44" = INTERIOR-WALL 3849 CONSTRUCTION = "Floor Construction" 3850 INT-WALL-TYPE =ADIABATIC 3851 LOCATION = BOTTOM 3852 3853 "45 ADMIN" = SPACE 3854 X = 193 3855 Y = 78 3856 SHAPE = BOX 3857 WIDTH = 20 3858 DEPTH = 16 3859 AIR-CHANGES/HR = 0.68 3860 LIGHTING-W/AREA = ( 1.2 ) 3861 EQUIPMENT-W/AREA = ( 1.5 ) 3862 DAYLIGHTING = NO 3863 LIGHT-REF-POINT1 = ( 5, 5 ) 3864 .. Page: 42— File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 3865 "Exterior Wall 79" = EXTERIOR-WALL 3866 CONSTRUCTION = "Exterior Wall Construction 3867 LOCATION = SPACE-V2 3868 3869 "Window 18" = WINDOW 3870 GLASS-TYPE = "N-E Glazing" 3871 Y = 3 3872 HEIGHT = 6 3873 WIDTH = 16 3874 3875 "Exterior Wall 80" = EXTERIOR-WALL 3876 CONSTRUCTION = "Exterior Wall Construction" 3877 LOCATION = SPACE-V3 3878 3879 "Window 52" = WINDOW - 3880 GLASS-TYPE = "N-E Glazing" 3881 HEIGHT = 12 3882 WIDTH = 7 3883 3884 "Window 53" = WINDOW 3885 GLASS-TYPE = "N-E Glazing" 3886 X = 7 -- 3887 Y = 3 3888 HEIGHT = 6 3889 WIDTH = 13 — 3890 3891 "Interior Wall 45" = INTERIOR-WALL 3892 CONSTRUCTION = "Floor Construction" ▪ 3893 INT-WALL-TYPE = ADIABATIC 3894 LOCATION = BOTTOM 3895 - 3896 "Interior Wall 136" = INTERIOR-WALL 3897 NEXT-TO = "44 OFFICE" 3898 CONSTRUCTION = "Interior Wall Construction" 3899 LOCATION = SPACE-V1 3900 3901 "Interior Wall 137" = INTERIOR-WALL 3902 NEXT-TO = "55 HALLWAY" — 3903 CONSTRUCTION = "Interior Wall Construction" 3904 LOCATION = SPACE-V4 3905 — 3906 "Interior Wall 147" = INTERIOR-WALL 3907 NEXT-TO = "45 ADMIN PLENUM" 3908 CONSTRUCTION = "Accoustic Ceiling Tile Construct" ▪ 3909 LOCATION = TOP 3910 3911 "46 CONF" = SPACE 3912 X = 150 3913 Y = 79 3914 SHAPE = BOX 3915 WIDTH = 30 3916 DEPTH = 15 3917 AIR-CHANGES/HR = 0.4 3918 NUMBER-OF-PEOPLE = 18 3919 LIGHTING-W/AREA = ( 1.2 ) 3920 EQUIPMENT-W/AREA = ( 0.5 ) 3921 DAYLIGHTING = NO ✓ 3922 LIGHT-REF-POINT1 = ( 15, 5 ) 3923 3924 "Exterior Wall 81" = EXTERIOR-WALL 3925 CONSTRUCTION = "Exterior Wall Construction" 3926 LOCATION = SPACE-V3 3927 3928 "Window 56" = WINDOW 3929 GLASS-TYPE = "N-E Glazing" 3930 HEIGHT = 12 3931 WIDTH = 4 ▪ 3932 . 3933 "Window 57" = WINDOW 3934 GLASS-TYPE = "N-E Glazing" ▪ 3935 X = 4 3936 Y = 3 3937 HEIGHT = 6 �. 3938 WIDTH = 20 3939 3940 "Window 58" = WINDOW 3941 GLASS-TYPE = "N-E Glazing" 3942 X = 24 3943 HEIGHT = 12 3944 WIDTH = 6 ▪ 3945 3946 "Interior Wall 46" = INTERIOR-WALL 3947 CONSTRUCTION = "Floor Construction" ▪ 3948 INT-WALL-TYPE = ADIABATIC 3949 LOCATION = BOTTOM 3950 — 3951 "Interior Wall 138" = INTERIOR-WALL 3952 NEXT-TO = "53 HALLWAY/JAN/STAFF WC" 3953 CONSTRUCTION = "Interior Wall Construction" ▪ 3954 LOCATION = SPACE-V1 3955 .. 3956 "Interior Wall 139" = INTERIOR-WALL Page: 43 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 3957 NEXT-TO = "55 HALLWAY" 3958 CONSTRUCTION = "Interior Wall Construction" 3959 LOCATION = SPACE-V2 3960 .. 3961 "Interior Wall 140" = INTERIOR-WALL 3962 NEXT-TO = "47 READING PERIM" 3963 CONSTRUCTION = "Interior Wall Construction" 3964 LOCATION = SPACE-V4 3965 3966 "Interior Wall 148" = INTERIOR-WALL 3967 NEXT-TO = "46 CONF PLENUM" 3968 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 3969 LOCATION = TOP 3970 .. 3971 "47 READING PERIM" = SPACE 3972 X = 60 3973 Y = 79 3974 SHAPE = BOX 3975 WIDTH = 90 3976 DEPTH = 15 3977 AIR-CHANGES/HR = 0.4 3978 LIGHTING-W/AREA = ( 1.7 ) 3979 EQUIPMENT-W/AREA = ( 0.5 ) 3980 DAYLIGHTING = NO 3981 LIGHT-REF-POINT1 = ( 45, 5 ) 3982 AREA/PERSON = 100 3983 3984 "Exterior Wall 82" = EXTERIOR-WALL 3985 CONSTRUCTION = "Exterior Wall Construction" 3986 LOCATION = SPACE-V3 3987 3988 "Window 59" = WINDOW 3989 GLASS-TYPE = "N-E Glazing" 3990 HEIGHT = 12 3991 WIDTH = 4 3992 _ 3993 "Window 60" = WINDOW 3994 GLASS-TYPE = "N-E Glazing" 3995 X = 4 3996 Y = 3 3997 HEIGHT = 6 3998 WIDTH = 20 3999 4000 "Window 61" = WINDOW 4001 GLASS-TYPE = "N-E Glazing" 4002 X = 24 4003 HEIGHT = 12 4004 WIDTH = 10 4005 4006 "Window 62" = WINDOW 4007 GLASS-TYPE = "N-E Glazing" 4008 X = 34 4009 Y = 3 4010 HEIGHT = 6 4011 WIDTH = 20 4012 4013 "Window 63" = WINDOW 4014 GLASS-TYPE = "N-E Glazing" 4015 X = 54 4016 HEIGHT = 12 4017 WIDTH = 10 4018 4019 "Window 64" = WINDOW 4020 GLASS-TYPE _ "N-E Glazing" 4021 X = 64 4022 Y = 3 4023 HEIGHT = 6 4024 WIDTH = 20 4025 4026 "Window 65" = WINDOW 4027 GLASS-TYPE _ "N-E Glazing" 4028 X = 84 4029 HEIGHT = 12 4030 WIDTH = 5 4031 .. 4032 "Interior Wall 47" = INTERIOR-WALL 4033 CONSTRUCTION = "Floor Construction" 4034 INT-WALL-TYPE = ADIABATIC 4035 LOCATION = BOTTOM 4036 4037 "Interior Wall 141" = INTERIOR-WALL _ 4038 NEXT-TO = "57 NON-FICTION" 4039 CONSTRUCTION = "AIR WALL" 4040 LOCATION = SPACE-V1 4041 4042 "Interior Wall 142" = INTERIOR-WALL 4043 NEXT-TO = "48 SITTING ROOM" 4044 CONSTRUCTION = "Interior Wall Construction" 4045 LOCATION = SPACE-V4 4046 .. 4047 "Interior Wall 149" = INTERIOR-WALL 4048 NEXT-TO = "47 READING PERIM PLENUM" Page: 44-- •••01 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 4049 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 4050 LOCATION = TOP - 4051 4052 "48 SITTING ROOM" = SPACE 4053 X = 15 4054 Y = 79 4055 SHAPE = BOX 4056 WIDTH = 45 4057 DEPTH = 15 ▪ 4058 AIR-CHANGES/HR = 0.13 4059 LIGHTING-W/AREA = ( 1.7 ) 4060 EQUIPMENT-W/AREA = ( 0.5 ) - 4061 4062 "Exterior Wall 84" = EXTERIOR-WALL 4063 CONSTRUCTION = "Exterior Wall Construction" — 4064 LOCATION = SPACE-V4 4065 4066 "Window 83" = WINDOW 4067 GLASS-TYPE = "S-W Glazing" 4068 X = 2.5 4069 Y = 3 4070 HEIGHT = 6 4071 WIDTH = 10 4072 4073 "Interior Wall 48" = INTERIOR-WALL — 4074 CONSTRUCTION = "Floor Construction" 4075 INT-WALL-TYPE = ADIABATIC 4076 LOCATION = BOTTOM 4077 4078 "49 STAIRWELL" = SPACE 4079 X = 30 4080 Y = 15 4081 SHAPE = BOX 4082 WIDTH = 30 4083 DEPTH = 32 4084 AIR-CHANGES/HR = 0.2 4085 EQUIPMENT-W/AREA = ( 0 ) 4086 DAYLIGHTING = NO mm 4087 LIGHT-REF-POINT1 = ( 15, 16 ) 4088 4089 "Exterior Wall 90" = EXTERIOR-WALL — 4090 CONSTRUCTION = "Exterior Wall Construction" 4091 Y = 17 4092 Z = 14 ▪ 4093 HEIGHT = 9 4094 LOCATION = SPACE-V1 4095 4096 "Window 1" = WINDOW 4097 GLASS-TYPE = "S-W Glazing" 4098 HEIGHT = 5 4099 WIDTH = 30 4100 4101 "Interior Wall 49" = INTERIOR-WALL 4102 CONSTRUCTION = "Floor Construction" 4103 INT-WALL-TYPE = ADIABATIC 4104 LOCATION = BOTTOM 4105 ▪ 4106 "Interior Wall 163" = INTERIOR-WALL 4107 NEXT-TO = "60 FICTION SOUTH INTERIOR" 4108 CONSTRUCTION = "AIR WALL" 4109 LOCATION = SPACE-V4 4110 4111 "50 ELECTRONIC INFO" = SPACE 4112 X = 30 4113 Y = 47 4114 SHAPE = BOX 4115 WIDTH = 30 m" 4116 DEPTH = 32 4117 AIR-CHANGES/HR = 0.33 4118 NUMBER-OF-PEOPLE = 36 '"" 4119 EQUIPMENT-W/AREA = ( 10 ) 4120 DAYLIGHTING = NO 4121 LIGHT-REF-POINT1 = ( 15, 16 ) ▪ 4122 4123 "Exterior Wall 95" = EXTERIOR-WALL 4124 CONSTRUCTION = "Exterior Wall Construction" 4125 Z = 14 4126 HEIGHT = 12 4127 LOCATION = SPACE-V3 4128 4129 "Window 69" = WINDOW 4130 GLASS-TYPE = "N-E Glazing" 4131 HEIGHT = 9 ▪ 4132 WIDTH = 30 4133 4134 "Exterior Wall 143" = EXTERIOR-WALL """ 4135 CONSTRUCTION = "Exterior Wall Construction" 4136 Z = 19 4137 LOCATION = SPACE-V4 — 4138 POLYGON = "Polygon 34" 4139 4140 "Window 77" = WINDOW Page: 45 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 4141 GLASS-TYPE = "S-W Glazing" 4142 HEIGHT = 4 4143 WIDTH = 12 4144 4145 "Exterior Wall 144" = EXTERIOR-WALL 4146 CONSTRUCTION = "Exterior Wall Construction" 4147 Z = 14 4148 HEIGHT = 5 4149 LOCATION = SPACE-V4 4150 4151 "Window 76" = WINDOW 4152 GLASS-TYPE = "S-W Glazing" 4153 HEIGHT = 5 4154 WIDTH = 12 4155 4156 "Interior Wall 50" = INTERIOR-WALL 4157 CONSTRUCTION = "Floor Construction" 4158 INT-WALL-TYPE = ADIABATIC 4159 LOCATION = BOTTOM 4160 .. 4161 "Interior Wall 151" = INTERIOR-WALL 4162 NEXT-TO = "49 STAIRWELL" 4163 CONSTRUCTION = "AIR WALL" 4164 LOCATION = SPACE-Vi 4165 4166 "Interior Wall 152" = INTERIOR-WALL 4167 NEXT-TO = "49 STAIRWELL" 4168 CONSTRUCTION = "AIR WALL" 4169 LOCATION = SPACE-V2 4170 4171 "51 REFERENCE DESK/OPACS" = SPACE 4172 X = 60 4173 Y = 15 4174 SHAPE = BOX 4175 WIDTH = 30 4176 DEPTH = 32 4177 AIR-CHANGES/HR = 0.14 4178 LIGHTING-W/AREA = ( 1.2 ) 4179 EQUIPMENT-W/AREA = ( 1.5 ) 4180 DAYLIGHTING = NO 4181 LIGHT-REF-POINT1 = ( 15, 16 ) 4182 AREA/PERSON = 100 4183 .. 4184 "Exterior Wall 91" = EXTERIOR-WALL 4185 CONSTRUCTION = "Exterior Wall Construction" 4186 Y = 17 4187 Z = 14 4188 HEIGHT = 9 4189 LOCATION = SPACE-V1 4190 4191 "Window 2" = WINDOW 4192 GLASS-TYPE = "S-W Glazing" 4193 HEIGHT = 5 4194 WIDTH = 30 4195 .. 4196 "Interior Wall 51" = INTERIOR-WALL 4197 CONSTRUCTION = "Floor Construction" 4198 INT-WALL-TYPE = ADIABATIC 4199 LOCATION = BOTTOM 4200 4201 "Interior Wall 162" = INTERIOR-WALL 4202 NEXT-TO = "49 STAIRWELL" 4203 CONSTRUCTION = "AIR WALL" 4204 LOCATION = SPACE-V4 4205 .. 4206 "52 ELEC. INFO" = SPACE 4207 X = 120 4208 Y = 15 4209 SHAPE = BOX 4210 WIDTH = 30 4211 DEPTH = 32 4212 AIR-CHANGES/HR = 0.2 4213 NUMBER-OF-PEOPLE = 32 4214 EQUIPMENT-W/AREA = ( 10 ) 4215 DAYLIGHTING = NO �. 4216 LIGHT-REF-POINT1 = ( 15, 16 ) 4217 4218 "Exterior Wall 93" = EXTERIOR-WALL 4219 CONSTRUCTION = "Exterior Wall Construction" 4220 Y = 17 4221 Z = 14 4222 HEIGHT = 9 4223 LOCATION = SPACE-V1 4224 4225 "Window 4" = WINDOW 4226 GLASS-TYPE = "S-W Glazing" 4227 HEIGHT = 5 4228 WIDTH = 30 4229 .. 4230 "Interior Wall 52" = INTERIOR-WALL 4231 CONSTRUCTION = "Floor Construction" 4232 INT-WALL-TYPE = ADIABATIC Page: 4Er e'ile: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 4233 LOCATION = BOTTOM 4234 4235 "Interior Wall 160" = INTERIOR-WALL — 4236 NEXT-TO = "41 TRAINING ROOM" 4237 CONSTRUCTION = "Interior Wall Construction" 4238 LOCATION = SPACE-V2 ▪ 4239 4240 "Interior Wall 161" = INTERIOR-WALL 4241 NEXT-TO = "38 SHELVES SOUTH PERIMETER" - 4242 CONSTRUCTION = "Interior Wall Construction" 4243 WIDTH = 9 4244 LOCATION = SPACE-V1 —. 4245 4246 "53 HALLWAY/JAN/STAFF WC" = SPACE 4247 X = 150 _ 4248 Y = 47 4249 SHAPE = BOX 4250 WIDTH = 30 4251 DEPTH = 20 - 4252 4253 "Interior Wall 53" = INTERIOR-WALL 4254 CONSTRUCTION = "Floor Construction" --4255 INT-WALL-TYPE = ADIABATIC 4256 LOCATION = BOTTOM 4257 - 4258 "Interior Wall 158" = INTERIOR-WALL 4259 NEXT-TO = "57 NON-FICTION" 4260 CONSTRUCTION = "Interior Wall Construction" 4261 LOCATION = SPACE-V4 4262 4263 "54 WC" = SPACE 4264 X = 150 - 4265 Y = 67 4266 SHAPE = BOX 4267 WIDTH = 30 —•4268 DEPTH = 12 4269 NUMBER-OF-PEOPLE = 0 4270 LIGHTING-W/AREA = ( 0.8 ) —.4271 EQUIPMENT-W/AREA = ( 0 ) 4272 4273 "Interior Wall 54" = INTERIOR-WALL - 4274 CONSTRUCTION = "Floor Construction" 4275 INT-WALL-TYPE = ADIABATIC 4276 LOCATION = BOTTOM 4277 4278 "Interior Wall 159" = INTERIOR-WALL 4279 NEXT-TO = "57 NON-FICTION" 4280 CONSTRUCTION = "Interior Wall Construction" - 4281 LOCATION = SPACE-V4 4282 4283 "55 HALLWAY" = SPACE - 4284 X = 180 4285 Y = 94 4286 SHAPE = POLYGON —4287 AIR-CHANGES/HR = 0.19 4288 POLYGON = "Polygon 11" 4289 ...4290 "Exterior Wall 89" = EXTERIOR-WALL 4291 CONSTRUCTION = "Exterior Wall Construction" 4292 LOCATION = SPACE-V6 --4294 4293 4294 "Window 54" = WINDOW 4295 GLASS-TYPE _ "N-E Glazing" 4296 Y = 3 —'4297 HEIGHT = 6 4298 WIDTH = 7 4299 ▪ 4300 "Window 55" = WINDOW 4301 GLASS-TYPE = "N-E Glazing" 4302 X = 7 ▪ 9303 HEIGHT = 12 4304 WIDTH = 6 4305 _4306 "Interior Wall 55" = INTERIOR-WALL 4307 CONSTRUCTION = "Floor Construction" 4308 INT-WALL-TYPE = ADIABATIC 4309 LOCATION = BOTTOM ▪ 4310 4311 "56 HALLWAY" = SPACE 4312 X = 192 ▪ 4313 Y = 15 4314 SHAPE = POLYGON 4315 AIR-CHANGES/HR = 0.1 ▪ 4316 POLYGON = "Polygon 12" 4317 4318 "Exterior Wall 132" = EXTERIOR-WALL - 4319 CONSTRUCTION = "Exterior Wall Construction" 4320 LOCATION = SPACE-V6 4321 .. _4322 "Interior Wall 107" = INTERIOR-WALL 4323 CONSTRUCTION = "Floor Construction" 4324 INT-WALL-TYPE = ADIABATIC Page: 47 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 4325 LOCATION = BOTTOM 4326 . 4327 "57 NON-FICTION" = SPACE 4328 X = 150 .- 4329 Y = 79 4330 AZIMUTH = 180 4331 SHAPE = POLYGON 4332 AIR-CHANGES/HR = 0.21 4333 DAYLIGHTING = NO 4334 LIGHT-REF-POINT1 = ( 45, 15 ) 4335 LIGHT-REF-POINT2 = ( 45, 45 ) 4336 ZONE-FRACTION1 = 0.5 4337 ZONE-FRACTION2 = 0.5 4338 POLYGON = "Polygon 13" 4339 4340 "Exterior Wall 92" = EXTERIOR-WALL 4341 CONSTRUCTION = "Exterior Wall Construction" 4342 Z = 14 4343 HEIGHT = 12 4344 LOCATION = SPACE-V1 4345 4346 "Window 68" = WINDOW 4347 GLASS-TYPE = "N-E Glazing" 4348 HEIGHT = 9 4349 WIDTH = 90 4350 4351 "Exterior Wall 94" = EXTERIOR-WALL 4352 CONSTRUCTION = "Exterior Wall Construction" 4353 Y = 47 4354 Z = 14 4355 HEIGHT = 9 4356 LOCATION = SPACE-V5 4357 4358 "Window 3" = WINDOW 4359 GLASS-TYPE = "S-W Glazing" 4360 HEIGHT = 5 4361 WIDTH = 30 4362 4363 "Interior Wall 57" = INTERIOR-WALL _ 4364 CONSTRUCTION = "Floor Construction" 4365 INT-WALL-TYPE = ADIABATIC 4366 LOCATION = BOTTOM 4367 .. — 4368 "Interior Wall 153" = INTERIOR-WALL 4369 NEXT-TO = "51 REFERENCE DESK/OPACS" 4370 CONSTRUCTION = "AIR WALL" — 4371 LOCATION = SPACE-V3 4372 4373 "Interior Wall 154" INTERIOR-WALL 4374 NEXT-TO = "51 REFERENCE DESK/OPACS" 4375 CONSTRUCTION = "AIR WALL" 4376 LOCATION = SPACE-V4 4377 4378 "Interior Wall 155" = INTERIOR-WALL 4379 NEXT-TO = "38 SHELVES SOUTH PERIMETER" 4380 CONSTRUCTION = "AIR WALL" — 4381 LOCATION = SPACE-V5 4382 4383 "Interior Wall 156" = INTERIOR-WALL 4384 NEXT-TO = "52 ELEC. INFO" 4385 CONSTRUCTION = "AIR WALL" 4386 LOCATION = SPACE-V6 4387 4388 "Interior Wall 157" = INTERIOR-WALL 4389 NEXT-TO = "52 ELEC. INFO" — 4390 CONSTRUCTION = "AIR WALL" 4391 LOCATION = SPACE-V7 4392 4393 "58 FICTION NORTH INTERIOR" = SPACE 4394 X = 15 4395 Y = 47 4396 SHAPE = BOX — 4397 WIDTH = 15 4398 DEPTH = 32 4399 .. — 4400 "Interior Wall 58" = INTERIOR-WALL 4401 CONSTRUCTION = "Floor Construction" 4402 INT-WALL-TYPE = ADIABATIC 4403 LOCATION = BOTTOM 4404 4405 "59 FICTION SOUTH PERIMETER" = SPACE — 4406 Y = 15 4407 SHAPE = POLYGON 4408 AIR-CHANGES/HR = 0.19 4409 POLYGON = "Polygon 14" — 4410 4411 "Exterior Wall 85" = EXTERIOR-WALL 4412 CONSTRUCTION = "Exterior Wall Construction" 4413 WIDTH = 15 4414 LOCATION = SPACE-V4 4415 .. — 4416 "Window 84" = WINDOW Page: 48— File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 4417 GLASS-TYPE _ "S-W Glazing" 4418 X = 5 _4419 HEIGHT = 12 4420 WIDTH = 10 4421 4422 "Interior Wall 59" = INTERIOR-WALL 4423 CONSTRUCTION = "Floor Construction" 4424 INT-WALL-TYPE = ADIABATIC 4425 LOCATION =BOTTOM - 4426 4427 "60 FICTION SOUTH INTERIOR" = SPACE 4428 Y = 15 4429 SHAPE = POLYGON 4430 POLYGON = "Polygon 15" 4431 4432 "Interior Wall 60" = INTERIOR-WALL 4433 CONSTRUCTION = "Floor Construction" 4434 INT-WALL-TYPE = ADIABATIC 4435 LOCATION = BOTTOM 4436 4437 "68 QUIET STUDY" = SPACE 4438 X = 15 - 4439 SHAPE = BOX 4440 WIDTH = 15 4441 DEPTH = 15 —4442 AIR-CHANGES/HR = 0.4 4443 LIGHTING-W/AREA = ( 1.7 ) 4444 EQUIPMENT-W/AREA = ( 1.5 ) 4445 AREA/PERSON = 100 4446 4447 "Exterior Wall 130" = EXTERIOR-WALL 4448 CONSTRUCTION = "Exterior Wall Construction" 4449 LOCATION = SPACE-V1 4450 4451 "Interior Wall 104" = INTERIOR-WALL 4452 CONSTRUCTION = "Floor Construction" 4453 INT-WALL-TYPE = ADIABATIC 4454 LOCATION = BOTTOM 4455 4456 "69 HOUGHTON RM" = SPACE 4457 X = 15 - 9958 Y = 94 4459 SHAPE = POLYGON 4460 AIR-CHANGES/HR = 0.48 - 4461 NUMBER-OF-PEOPLE = 24 4462 LIGHTING-W/AREA = ( 1.7 ) 4463 EQUIPMENT-W/AREA = ( 1.5 ) 4464 DAYLIGHTING = NO 4465 LIGHT-REF-POINT1 = ( 18, 15 ) 4466 POLYGON = "Polygon 73" 4467 ▪ 4468 "Exterior Wall 125" = EXTERIOR-WALL 4469 CONSTRUCTION = "Exterior Wall Construction" 4470 LOCATION = SPACE-V2 m=4471 4472 "Window 19" = WINDOW 4473 GLASS-TYPE _ "N-E Glazing" ▪ 4979 HEIGHT = 12 4475 WIDTH = 10 4476 • 4477 "Window 20" = WINDOW 4478 GLASS-TYPE _ "N-E Glazing" 4479 X = 10 _4480 Y = 3 4481 HEIGHT = 9 4482 WIDTH = 18 4483 ▪ 4484 "Window 21" = WINDOW 4485 GLASS-TYPE _ "N-E Glazing" 4486 X = 28 —4487 HEIGHT = 12 4488 WIDTH - 6.5 4489 ▪4490 "Exterior Wall 126" = EXTERIOR-WALL 4491 CONSTRUCTION = "Exterior Wall Construction" 4492 LOCATION = SPACE-V3 4493 . 4494 "Window 66" = WINDOW 4495 GLASS-TYPE = "N-E Glazing" 4496 HEIGHT = 12 4497 WIDTH = 15 4498 4499 "Window 67" = WINDOW ▪4500 GLASS-TYPE _ "N-E Glazing" 4501 X = 26 4502 HEIGHT = 12 • 4503 WIDTH = 5 4504 4505 "Exterior Wall 127" = EXTERIOR-WALL . 4506 CONSTRUCTION = "Exterior Wall Construction" 4507 LOCATION = SPACE-V4 4508 • Page: 49 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 4509 "Window 70" = WINDOW 4510 GLASS-TYPE = "S-W Glazing" 4511 HEIGHT = 12 _ 4512 WIDTH = 5 4513 .. 4514 "Interior Wall 103" = INTERIOR-WALL 4515 CONSTRUCTION = "Floor Construction" 4516 INT-WALL-TYPE = ADIABATIC 4517 LOCATION =BOTTOM 4518 .. 4519 "Interior Wall 143" = INTERIOR-WALL 4520 NEXT-TO = "48 SITTING ROOM" 4521 CONSTRUCTION = "Interior Wall Construction" 4522 LOCATION = SPACE-V1 4523 .. 4524 "Interior Wall 150" = INTERIOR-WALL 4525 NEXT-TO = "69 HOUGHTON RM PLENUM" 4526 CONSTRUCTION = "Accoustic Ceiling Tile Construct" 4527 LOCATION = TOP 4528 .. `.. 4529 "70 HALLWAY" = SPACE 4530 X = 180 4531 Y = 47 4532 SHAPE = BOX 4533 WIDTH = 13 4534 DEPTH = 20 9535 .. 4536 "Interior Wall 105" = INTERIOR-WALL 4537 CONSTRUCTION = "Floor Construction" 4538 INT-WALL-TYPE = ADIABATIC 4539 LOCATION = BOTTOM 4540 4541 "71 FICTION NORTH PERIMETER" = SPACE 4542 Y = 47 4543 SHAPE = POLYGON 4544 AIR-CHANGES/HR = 0.59 4545 POLYGON = "Polygon 14" 4546 .. 4547 "Exterior Wall 129" = EXTERIOR-WALL 4548 CONSTRUCTION = "Exterior Wall Construction" 4549 LOCATION = SPACE-V3 4550 .. 4551 "Exterior Wall 136" = EXTERIOR-WALL 4552 CONSTRUCTION = "Exterior Wall Construction" 4553 LOCATION = SPACE-V4 9559 .. 4555 "Window 82" = WINDOW 4556 GLASS-TYPE = "S-W Glazing" _ 4557 HEIGHT = 12 4558 WIDTH = 10 4559 .. 4560 "Interior Wall 106" = INTERIOR-WALL 4561 CONSTRUCTION = "Floor Construction" 4562 INT-WALL-TYPE = ADIABATIC 4563 LOCATION = BOTTOM 4569 . 4565 "36 OREGON HISTORY PLENUM" = SPACE 4566 X = 30 4567 HEIGHT = 2 4568 SHAPE = BOX 4569 WIDTH = 30 4570 DEPTH = 15 4571 ZONE-TYPE = PLENUM 4572 LIGHTING-W/AREA = ( 0 ) 4573 EQUIPMENT-W/AREA = ( 0 ) ` 4574 .. 4575 "Exterior Wall 12 PLENUM" = EXTERIOR-WALL 4576 CONSTRUCTION = "Roof Construction" — 4577 LOCATION = TOP 4578 .. 4579 "Exterior Wall 68 PLENUM" = EXTERIOR-WALL 4580 CONSTRUCTION = "Exterior Wall Construction" 4581 LOCATION = SPACE-V1 4582 . 4583 "37 YOUNG ADULTS PLENUM" = SPACE 4584 X = 60 4585 HEIGHT = 2 4586 SHAPE = BOX r 4587 WIDTH. = 30 4588 DEPTH = 15 4589 ZONE-TYPE = PLENUM 4590 LIGHTING-W/AREA = ( 0 ) 4591 EQUIPMENT-W/AREA = ( 0 ) 4592 . 4593 "Exterior Wall 13 PLENUM" = EXTERIOR-WALL 4594 CONSTRUCTION = "Roof Construction" 4595 LOCATION = TOP 4596 4597 "Exterior Wall 69 PLENUM" = EXTERIOR-WALL 4598 CONSTRUCTION = "Exterior Wall Construction" 4599 LOCATION = SPACE-V1 4600 .. Page: 50- File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 4601 "38 SHELVES SOUTH PERIMETER PLENU" = SPACE 4602 X = 90 4603 HEIGHT = 2 4604 SHAPE = BOX 4605 WIDTH = 39 4606 DEPTH = 15 4607 ZONE-TYPE = PLENUM 4608 LIGHTING-W/AREA = ( 0 ) 4609 EQUIPMENT-W/AREA = ( 0 ) 4610 4611 "Exterior Wall 14 PLENUM" = EXTERIOR-WALL 4612 CONSTRUCTION = "Roof Construction" "" 4613 LOCATION = TOP 4614 4615 "Exterior Wall 70 PLENUM" = EXTERIOR-WALL —. 4616 CONSTRUCTION = "Exterior Wall Construction" 4617 LOCATION SPACE-V1 4618 4619 "39 QUITE STUDY PLENUM" = SPACE 4620 X = 129 4621 HEIGHT = 2 4622 SHAPE = BOX 4623 WIDTH = 21 4624 DEPTH = 15 4625 ZONE-TYPE = PLENUM - 4626 LIGHTING-W/AREA = ( 0 ) 4627 EQUIPMENT-W/AREA = ( 0 ) 4628 4629 "Exterior Wall 15 PLENUM" = EXTERIOR-WALL 4630 CONSTRUCTION - "Roof Construction" 4631 LOCATION = TOP —4632 4633 "Exterior Wall 71 PLENUM" = EXTERIOR-WALL 4634 CONSTRUCTION = "Exterior Wall Construction" 4635 LOCATION = SPACE-V1 4636 4637 "40 DATA/MECH PLENUM" = SPACE 4638 X = 170 —. 4639 HEIGHT = 2 4640 SHAPE = BOX 4641 WIDTH - 14 ▪ 4642 DEPTH = 25 4643 ZONE-TYPE = PLENUM 4644 LIGHTING-W/AREA = ( 0 ) - 4645 EQUIPMENT-W/AREA = ( 0 ) 4646 4647 "Exterior Wall 16 PLENUM" - EXTERIOR-WALL m. 4648 CONSTRUCTION = "Roof Construction" 4649 LOCATION = TOP 4650 4651 "Exterior Wall 72 PLENUM" - EXTERIOR-WALL 4652 CONSTRUCTION - "Exterior Wall Construction" 4653 LOCATION = SPACE-V1 4654 ▪ 4655 "Exterior Wall 124 PLENUM" = EXTERIOR-WALL 4656 CONSTRUCTION = "Exterior Wall Construction" 4657 WIDTH = 14 ..4658 LOCATION = SPACE-V2 4659 4660 "41 TRAINING ROOM PLENUM" = SPACE - 4661 X = 150 4662 HEIGHT = 2 4663 SHAPE = BOX -. 4664 WIDTH = 20 4665 DEPTH = 40 4666 ZONE-TYPE = PLENUM 4667 LIGHTING-W/AREA = ( 0 ) 4668 EQUIPMENT-W/AREA = ( 0 ) 4669 4670 "Exterior Wall 17 PLENUM" = EXTERIOR-WALL ▪ 4671 CONSTRUCTION = "Roof Construction" 4672 LOCATION = TOP 4673 .• ▪ 4674 "Exterior Wall 73 PLENUM" = EXTERIOR-WALL 4675 CONSTRUCTION = "Exterior Wall Construction" 4676 LOCATION = SPACE-VI -. 4677 4678 "43 REF. WORKROOM PLENUM" - SPACE 4679 X - 193 ▪ 4680 Y = 14 4681 HEIGHT = 2 4682 SHAPE = BOX 4683 WIDTH = 20 - 4684 DEPTH = 53 4685 ZONE-TYPE = PLENUM 4686 LIGHTING-W/AREA ( 0 ) ▪ 4687 EQUIPMENT-W/AREA = ( 0 ) 4688 4689 "Exterior Wall 20 PLENUM" = EXTERIOR-WALL - 4690 CONSTRUCTION = "Roof Construction" 4691 LOCATION = TOP 4692 Page: 51 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 4693 "Exterior Wall 75 PLENUM" = EXTERIOR-WALL 4694 CONSTRUCTION = "Exterior Wall Construction" 4695 LOCATION = SPACE-V1 4696 .. 4697 "Exterior Wall 76 PLENUM" = EXTERIOR-WALL 4698 CONSTRUCTION = "Exterior Wall Construction" 4699 LOCATION = SPACE-V2 4700 •. 4701 "44 OFFICE PLENUM" = SPACE 4702 X = 198 4703 Y = 67 4704 HEIGHT = 2 4705 SHAPE = BOX 4706 WIDTH = 15 4707 DEPTH = 11 4708 ZONE-TYPE = PLENUM 4709 LIGHTING-W/AREA = ( 0 ) 4710 EQUIPMENT-W/AREA = ( 0 ) 4711 .. 4712 "Exterior Wall 21 PLENUM" = EXTERIOR-WALL 4713 CONSTRUCTION = "Roof Construction" 4714 LOCATION = TOP 4715 .. 4716 "Exterior Wall 78 PLENUM" = EXTERIOR-WALL 4717 CONSTRUCTION = "Exterior Wall Construction" 4718 LOCATION = SPACE-V2 9719 .. 4720 "45 ADMIN PLENUM" = SPACE 4721 X = 193 4722 Y = 78 4723 HEIGHT = 2 4724 SHAPE = BOX 4725 WIDTH = 20 4726 DEPTH = 16 4727 ZONE-TYPE = PLENUM 4728 LIGHTING-W/AREA = ( 0 ) 4729 EQUIPMENT-W/AREA = ( 0 ) 4730 .. 4731 "Exterior Wall 22 PLENUM" = EXTERIOR-WALL 4732 CONSTRUCTION = "Roof Construction" 4733 LOCATION = TOP 4734 .. 4735 "Exterior Wall 79 PLENUM" = EXTERIOR-WALL 4736 CONSTRUCTION = "Exterior Wall Construction" 4737 LOCATION = SPACE-V2 4738 4739 "Exterior Wall 80 PLENUM" = EXTERIOR-WALL 4740 CONSTRUCTION = "Exterior Wall Construction" 4741 LOCATION = SPACE-V3 4742 .. 4743 "46 CONE PLENUM" = SPACE 4744 X = 150 4745 Y = 79 4746 HEIGHT = 2 4747 SHAPE = BOX 4748 WIDTH = 30 4749 DEPTH = 15 4750 ZONE-TYPE = PLENUM 4751 LIGHTING-W/AREA = ( 0 ) 4752 EQUIPMENT-W/AREA = ( 0 ) 4753 .. 4754 "Exterior Wall 23 PLENUM" = EXTERIOR-WALL 4755 CONSTRUCTION = "Roof Construction" 4756 LOCATION = TOP 4757 .. 4758 "Exterior Wall 81 PLENUM" = EXTERIOR-WALL 4759 CONSTRUCTION = "Exterior Wall Construction" 4760 LOCATION = SPACE-V3 — 4761 .. 4762 "47 READING PERIM PLENUM" = SPACE 4763 X = 60 4764 Y = 79 4765 HEIGHT = 2 4766 SHAPE = BOX 4767 WIDTH = 90 4768 DEPTH = 15 4769 ZONE-TYPE = PLENUM 4770 LIGHTING-W/AREA = ( 0 ) w 4771 EQUIPMENT-W/AREA = ( 0 ) 4772 4773 "Exterior Wall 24 PLENUM" = EXTERIOR-WALL 4774 CONSTRUCTION = "Roof Construction" 4775 LOCATION = TOP 4776 .. 4777 "Exterior Wall 82 PLENUM" = EXTERIOR-WALL 4778 CONSTRUCTION = "Exterior Wall Construction" 4779 LOCATION = SPACE-V3 4780 .. 4781 "48 SITTING ROOM PLENUM" = SPACE 4782 X = 15 e 4783 Y = 79 4784 HEIGHT = 2 Page: 52— File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 4785 SHAPE = BOX 4786 WIDTH = 45 4787 DEPTH = 15 4788 ZONE-TYPE = PLENUM 4789 LIGHTING-W/AREA ( 0 ) 4790 EQUIPMENT-W/AREA = ( 0 ) - 4791 4792 "Exterior Wall 25 PLENUM" = EXTERIOR-WALL 4793 CONSTRUCTION = "Roof Construction" - 4794 LOCATION - TOP 4795 .. 4796 "Exterior Wall 84 PLENUM" = EXTERIOR-WALL - 4797 CONSTRUCTION = "Exterior Wall Construction" 4798 LOCATION = SPACE-V4 4799 — 4800 "49 STAIRWELL PLENUM" - SPACE 4801 X 30 4802 1 15 4803 HEIGHT = 2 4804 SHAPE = BOX 4805 WIDTH = 30 4806 DEPTH = 32 - 4807 ZONE-TYPE = PLENUM 4808 LIGHTING-W/AREA = ( 0 ) 4809 EQUIPMENT-W/AREA = ( 0 ) —• 4810 4811 "Exterior Wall 26 PLENUM" - EXTERIOR-WALL 4812 CONSTRUCTION = "Roof Construction" .. 4813 Y 17 4814 Z 11 4815 HEIGHT = 15.5 4816 TILT = -14.9 4817 LOCATION - TOP 4818 4819 "Exterior Wall 140 PLENUM" = EXTERIOR-WALL 4820 CONSTRUCTION = "Roof Construction" 4821 HEIGHT - 17 4822 LOCATION = TOP - 4823 4824 "Exterior Wall 149 PLENUM" = EXTERIOR-WALL 4825 CONSTRUCTION = "Exterior Wall Construction" ▪ 4826 1 2 4827 HEIGHT = 5 4828 WIDTH = 15 .. 4829 LOCATION SPACE-V4 4830 4831 "Exterior Wall 150 PLENUM" = EXTERIOR-WALL 4832 CONSTRUCTION = "Exterior Wall Construction" 4833 Z 7 4834 LOCATION = SPACE-V4 4835 POLYGON = "Polygon 82" ▪ 4836 4837 "50 ELECTRONIC INFO PLENUM" = SPACE 4838 X = 30 "". 4839 Y 47 4840 HEIGHT = 2 4841 SHAPE = BOX ▪ 4842 WIDTH = 30 4843 DEPTH = 32 4844 ZONE-TYPE = PLENUM -. 4845 LIGHTING-W/AREA = ( 0 ) 4846 EQUIPMENT-W/AREA = ( 0 ) 4847 4848 "Exterior Wall 27 PLENUM" - EXTERIOR-WALL 4849 CONSTRUCTION = "Roof Construction" 4850 Z 7 4851 HEIGHT = 32.5 — 4852 TILT = 12.3 4853 LOCATION = TOP 4854 4855 "51 REFERENCE DESK/OPACS PLENUM" = SPACE 4856 X = 60 4857 Y 15 ▪ 4858 HEIGHT = 2 4859 SHAPE = BOX 4860 WIDTH = 30 4861 DEPTH = 32 4862 ZONE-TYPE = PLENUM 4863 LIGHTING-W/AREA = ( 0 ) 4864 EQUIPMENT-W/AREA = ( 0 ) ▪ 4865 4866 "Exterior Wall 28 PLENUM" = EXTERIOR-WALL 4867 CONSTRUCTION = "Roof Construction" 4868 Y 17 4869 Z 11 4870 HEIGHT = 15.5 ▪ 4871 TILT = -14.9 4872 LOCATION = TOP 4973 4874 "Exterior Wall 139 PLENUM" = EXTERIOR-WALL 4075 CONSTRUCTION = "Roof Construction" 4876 HEIGHT = 17 Page: 53 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 4877 LOCATION = TOP 4878 .. 4879 "52 ELEC. INFO PLENUM" = SPACE 4880 X = 120 4881 Y = 15 4882 HEIGHT = 2 4883 SHAPE = BOX 4884 WIDTH = 30 4885 DEPTH = 32 4886 ZONE-TYPE = PLENUM 4887 LIGHTING-W/AREA = ( 0 ) 4888 EQUIPMENT-W/AREA = ( 0 ) 4889 .. 4890 "Exterior Wall 29 PLENUM" = EXTERIOR-WALL MEM 4891 CONSTRUCTION = "Roof Construction" 4892 Y = 17 4893 Z = 11 4894 HEIGHT = 15.5 4895 TILT = -14.9 4896 LOCATION = TOP 4897 .. 4898 "Exterior Wall 138 PLENUM" = EXTERIOR-WALL 4899 CONSTRUCTION = "Roof Construction" 4900 HEIGHT = 17 4901 LOCATION = TOP 4902 .. 4903 "Exterior Wall 147 PLENUM" = EXTERIOR-WALL 4904 CONSTRUCTION = "Exterior Wall Construction" 4905 Y = 17 4906 Z = 2 "M 4907 HEIGHT = 5 4908 WIDTH = 15 4909 LOCATION = SPACE-V2 '� 4910 .. 4911 "Exterior Wall 148 PLENUM" = EXTERIOR-WALL 4912 CONSTRUCTION = "Exterior Wall Construction" ... 4913 Y = 17 4914 Z = 7 4915 LOCATION = SPACE-V2 4916 POLYGON = "Polygon 81" 4917 . 4918 "53 HALLWAY/JAN/STAFF WC PLENUM" = SPACE 4919 X = 150 4920 Y = 47 4921 HEIGHT = 2 4922 SHAPE = BOX 4923 WIDTH = 30 4924 DEPTH = 20 4925 ZONE-TYPE = PLENUM 4926 LIGHTING-W/AREA = ( 0 ) 4927 EQUIPMENT-W/AREA = ( 0 ) 4928 .. 4929 "Exterior Wall 30 PLENUM" = EXTERIOR-WALL 4930 CONSTRUCTION = "Roof Construction" 4931 LOCATION = TOP 9932 .. 4933 "54 WC PLENUM" = SPACE 4934 X = 150 4935 Y = 67 ft- 4936 HEIGHT = 2 4937 SHAPE = BOX 4938 WIDTH = 30 4939 DEPTH = 12 4940 ZONE-TYPE = PLENUM 4941 LIGHTING-W/AREA = ( 0 ) .+ 4942 EQUIPMENT-W/AREA = ( 0 ) 4943 .. 4944 "Exterior Wall 31 PLENUM" = EXTERIOR-WALL _ 4945 CONSTRUCTION = "Roof Construction" 4946 LOCATION = TOP 4947 4948 "55 HALLWAY PLENUM" = SPACE - 4949 X = 180 4950 Y = 94 _ 4951 HEIGHT = 2 4952 SHAPE = POLYGON 4953 ZONE-TYPE = PLENUM 4954 LIGHTING-W/AREA = ( 0 ) 4955 EQUIPMENT-W/AREA = ( 0 ) 4956 POLYGON = "Polygon 11" 4957 .. 4958 "Exterior Wall 32 PLENUM" = EXTERIOR-WALL 4959 CONSTRUCTION = "Roof Construction" 4960 LOCATION = TOP 4961 .. 4962 "Exterior Wall 89 PLENUM" = EXTERIOR-WALL 4963 CONSTRUCTION = "Exterior Wall Construction" 4964 LOCATION = SPACE-V6 4965 . 4966 "56 HALLWAY PLENUM" = SPACE 4967 X = 192 4968 Y = 15 Page: 54- File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 4969 HEIGHT = 2 4970 SHAPE = POLYGON 4971 ZONE-TYPE = PLENUM 4972 LIGHTING-W/AREA = ( 0 ) 4973 EQUIPMENT-W/AREA = ( 0 ) 4974 POLYGON = "Polygon 12" 4975 4976 "Exterior Wall 33 PLENUM" = EXTERIOR-WALL 4977 CONSTRUCTION = "Roof Construction" -m" 4978 LOCATION = TOP 4979 4980 "Exterior Wall 132 PLENUM" = EXTERIOR-WALL === 4981 CONSTRUCTION = "Exterior Wall Construction" 4982 LOCATION SPACE-V6 4983 — 4984 "57 NON-FICTION PLENUM" = SPACE 4985 X = 150 4986 Y 79 - 4987 AZIMUTH = 180 4988 HEIGHT - 2 4989 SHAPE = POLYGON 4990 ZONE-TYPE = PLENUM - 4991 LIGHTING-W/AREA = ( 0 ) 4992 EQUIPMENT-W/AREA = ( 0 ) 4993 POLYGON = "Polygon 13" 4994 4995 "Exterior Wall 34 PLENUM" - EXTERIOR-WALL 4996 CONSTRUCTION = "Roof Construction" —= 4997 Z 14 4998 TILT = -12.3 4999 LOCATION - TOP 5000 POLYGON = "Polygon 78" 5001 5002 "Exterior Wall 141 PLENUM" = EXTERIOR-WALL 5003 CONSTRUCTION = "Roof Construction" 5004 X = 30 5005 Y 32 5006 1 7 - 5007 TILT = 14.9 5008 LOCATION = TOP 5009 POLYGON = "Polygon 80" ▪ 5010 5011 "Exterior Wall 142 PLENUM" = EXTERIOR-WALL 5012 CONSTRUCTION - "Roof Construction" ▪ 5013 X = 30 5014 1 47 5015 LOCATION = TOP 5016 POLYGON = "Polygon 79" 5017 5018 "Exterior Wall 145 PLENUM" = EXTERIOR-WALL 5019 CONSTRUCTION = "Exterior Wall Construction" ▪ 5020 1 2 5021 HEIGHT = 5 5022 LOCATION = SPACE-V8 — 5023 5024 "Exterior Wall 146 PLENUM" = EXTERIOR-WALL 5025 CONSTRUCTION = "Exterior Wall Construction" .. 5026 1 7 5027 LOCATION = SPACE-V8 5028 POLYGON = "Polygon 33" - 5029 5030 "58 FICTION NORTH INTERIOR PLENUM" = SPACE 5031 X = 15 5032 Y 47 5033 HEIGHT = 2 5034 SHAPE - BOX 5035 WIDTH = 15 "m 5036 DEPTH = 32 5037 ZONE-TYPE = PLENUM 5038 LIGHTING-W/AREA = ( 0 ) .= 5039 EQUIPMENT-W/AREA = ( 0 ) 5040 5041 "Exterior Wall 35 PLENUM" = EXTERIOR-WALL .. 5042 CONSTRUCTION = "Roof Construction" 5043 LOCATION = TOP 5044 ▪ 5045 "59 FICTION SOUTH PERIMETER PLENU" = SPACE 5046 Y 15 5047 HEIGHT = 2 5048 SHAPE = POLYGON 5049 ZONE-TYPE = PLENUM 5050 LIGHTING-W/AREA = ( 0 ) 5051 EQUIPMENT-W/AREA = ( 0 ) ▪ 5052 POLYGON = "Polygon 14" 5053 5054 "Exterior Wall 36 PLENUM" = EXTERIOR-WALL = 5055 CONSTRUCTION = "Roof Construction" 5056 LOCATION = TOP 5057 . 5058 "Exterior Wall 85 PLENUM" - EXTERIOR-WALL 5059 CONSTRUCTION = "Exterior Wall Construction" 5060 WIDTH = 15 • Page: 55 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 5061 LOCATION = SPACE-V4 5062 .. 5063 "60 FICTION SOUTH INTERIOR PLENUM" = SPACE _ 5064 Y = 15 5065 HEIGHT = 2 5066 SHAPE = POLYGON 5067 ZONE-TYPE = PLENUM 5068 LIGHTING-W/AREA = ( 0 ) 5069 EQUIPMENT-W/AREA = ( 0 ) 5070 POLYGON = "Polygon 15" 5071 .. 5072 "Exterior Wall 37 PLENUM" = EXTERIOR-WALL 5073 CONSTRUCTION = "Roof Construction" 5074 LOCATION = TOP 5075 .. 5076 "68 QUIET STUDY PLENUM" = SPACE 5077 X = 15 5078 HEIGHT = 2 5079 SHAPE = BOX 5080 WIDTH = 15 5081 DEPTH = 15 5082 ZONE-TYPE = PLENUM 5083 LIGHTING-W/AREA = ( 0 ) 5084 EQUIPMENT-W/AREA = ( 0 ) 5085 .. 5086 "Exterior Wall 130 PLENUM" = EXTERIOR-WALL 5087 CONSTRUCTION = "Exterior Wall Construction" 5088 LOCATION = SPACE-V1 5089 .. 5090 "Exterior Wall 133 PLENUM" = EXTERIOR-WALL 5091 CONSTRUCTION = "Roof Construction" 5092 LOCATION = TOP 5093 . 5094 "69 HOUGHTON RM PLENUM" = SPACE 5095 X = 15 5096 Y = 94 5097 HEIGHT = 2 5098 SHAPE = POLYGON 5099 ZONE-TYPE = PLENUM 5100 LIGHTING-W/AREA = ( 0 ) 5101 EQUIPMENT-W/AREA = ( 0 ) 5102 POLYGON = "Polygon 73" 5103 .. 5104 "Exterior Wall 125 PLENUM" = EXTERIOR-WALL 5105 CONSTRUCTION = "Exterior Wall Construction" 5106 LOCATION = SPACE-V2 5107 .. 5108 "Exterior Wall 126 PLENUM" = EXTERIOR-WALL 5109 CONSTRUCTION = "Exterior Wall Construction" ..- 5110 5110 LOCATION = SPACE-V3 5111 .. 5112 "Exterior Wall 127 PLENUM" = EXTERIOR-WALL 5113 CONSTRUCTION = "Exterior Wall Construction" 5114 LOCATION = SPACE-V4 5115 .. 5116 "Exterior Wall 134 PLENUM" = EXTERIOR-WALL 5117 CONSTRUCTION = "Roof Construction" 5118 LOCATION = TOP 5119 .. 5120 "70 HALLWAY PLENUM" = SPACE 5121 X = 180 5122 Y = 47 5123 HEIGHT = 2 5124 SHAPE = BOX 5125 WIDTH = 13 5126 DEPTH = 20 5127 ZONE-TYPE = PLENUM 5128 LIGHTING-W/AREA = ( 0 ) — 5129 EQUIPMENT-W/AREA = ( 0 ) 5130 .. 5131 "Exterior Wall 135 PLENUM" = EXTERIOR-WALL 5132 CONSTRUCTION = "Roof Construction" 5133 LOCATION = TOP 5134 .. 5135 "71 FICTION NORTH PERIMETER PLENU" = SPACE 5136 Y = 47 5137 HEIGHT = 2 _ 5138 SHAPE = POLYGON 5139 ZONE-TYPE = PLENUM 5140 LIGHTING-W/AREA = ( 0 ) 5141 EQUIPMENT-W/AREA = ( 0 ) 5142 POLYGON = "Polygon 14" 5143 .. 5144 "Exterior Wall 129 PLENUM" = EXTERIOR-WALL 5145 CONSTRUCTION = "Exterior Wall Construction" 5146 LOCATION = SPACE-V3 5147 .. 5148 "Exterior Wall 136 PLENUM" = EXTERIOR-WALL 5149 CONSTRUCTION = "Exterior Wall Construction" 5150 LOCATION = SPACE-V4 5151 - .. 5152 "Exterior Wall 137 PLENUM" = EXTERIOR-WALL Page: 56- File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 5153 CONSTRUCTION = "Roof Construction" 5154 LOCATION TOP 5155 5156 5157 _ 5158 $ ********************************************************* 5159 $ ** ** 5160 $ ** Performance Curves ** 5161 $ ** ** --= 5162 $ ********************************************************* 5163 5164 5165 5166 $ ********************************************************* 5167 $ ** ** 5168 $ ** Electric & Fuel Meters ** 5169 $ ** ** 5170 $ ********************************************************* 5171 5172 $ 5173 $ Electric Meters 5174 $ - 5175 5176 "EMI." ELEC-METER 5177 LIBRARY-ENTRY "EMI" - 5178 5179 5180 -r 5181 $ 5182 $ Fuel Meters 5183 $ 5184 5185 "FM1" = FUEL-METER 5186 LIBRARY-ENTRY "FM1" 5187 5188 5189 5190 $ -- 5191 $ Master Meters 5192 $ 5193 — 5194 "Default MASTER-METERS" = MASTER-METERS 5195 MSTR-ELEC-METER "EMI." 5196 MSTR-FUEL-METER = "FM1" — 5197 5198 5199 ▪ 5200 $ ********************************************************* 5201 $ ** ** 5202 $ ** HVAC Circulation Loops / Plant Equipment ** 5203 $ ** ** ▪ 5204 $ ********************************************************* 5205 5206 $ — 5207 $ Pumps 5208 $ 5209 — 5210 "DOMESTIC HOT WATER PUMP" = PUMP 5211 5212 "BOILER 1 CIRC PUMP" = PUMP 5213 LIBRARY-ENTRY "DEFAULT-HW-PUMP" 5214 5215 "BOILER 2 CIRC PUMP" = PUMP 5216 LIBRARY-ENTRY "DEFAULT-HW-PUMP" 5217 5218 "PRIMARY HOT WATER PUMP" = PUMP 5219 CAP-CTRL = VAR-SPEED-PUMP - 5220 5221 5222 5223 $ 5224 $ Circulation Loops 5225 $ 5226 5227 SET-DEFAULT FOR CIRCULATION-LOOP 5228 TYPE = HW ▪ 5229 LOOP-OPERATION = DEMAND 5230 5231 _ 5232 "Domestic Hot Water" = CIRCULATION-LOOP 5233 TYPE DHW 5234 LOOP-PUMP = "DOMESTIC HOT WATER PUMP" 5235 PROCESS-FLOW = 0.36 ▪ 5236 PROCESS-SCH = "OCCUPANCY SCHD" 5237 5238 "HOT WATER" = CIRCULATION-LOOP ▪ 5239 TYPE HW 5240 LOOP-PUMP = "PRIMARY HOT WATER PUMP" 5241 ., 5242 5243 5244 $ �_— Page: 57 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 5245 $ Chillers 5246 $ 5247 5248 5249 5250 $ 5251 $ Boilers 5252 $ 5253 5254 SET-DEFAULT FOR BOILER .... 5255 TYPE = HW-BOILER 5256 LOCATION = ZONE 5257 .� 5258 5259 "Boiler 1" = BOILER 5260 TYPE = HW-BOILER 5261 ZONE-NAME = "40 DATA/MECH ZONE" 5262 HW-LOOP = "HOT WATER" 5263 HW-PUMP = "BOILER 1 CIRC PUMP" 5264 5265 "Boiler 2" = BOILER 5266 TYPE = HW-BOILER 5267 ZONE-NAME = "40 DATA/MECH ZONE" .... 5268 HW-LOOP = "HOT WATER" 5269 HW-PUMP = "BOILER 2 CIRC PUMP" 5270 5271 5272 5273 $ 5274 $ Domestic Water Heaters 5275 $ 5276 5277 "D.H.W. Heater 1" = DW-HEATER 5278 TYPE = GAS 5279 DHW-LOOP = "Domestic Hot Water" 5280 5281 5282 5283 $ 5284 $ Heat Rejection 5285 $ 5286 5287 5288 5289 $ 5290 $ Tower Free Cooling 5291 $ 5292 5293 5294 5295 $ 5296 $ Electric Generators 5297 $ 5298 5299 5300 5301 $ 5302 $ Thermal Storage 5303 $ 5304 5305 5306 5307 $ 5308 $ Heat Exchangers 5309 $ 5310 5311 5312 5313 $ 5314 $ Ground Loop Heat Exchangers 5315 $ 5316 5317 5318 5319 $ ********************************************************* 5320 $ ** ** 5321 $ ** Steam & Chilled Water Meters ** 5322 $ ** ** 5323 $ ********************************************************* 5324 5325 $ 5326 $ Steam Meters 5327 $ 5328 5329 5330 5331 $ 5332 $ Chilled Water Meters 5333 $ 5334 5335 5336 Page: 58- File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM ▪ 5337 $ ********************************************************* 5338 $ ** ** 5339 $ ** HVAC Systems / Zones ** 5340 $ ** ** 5341 $ ********************************************************* ▪ 5342 5343 SET-DEFAULT FOR SYSTEM 5344 TYPE = PSZ 5345 MIN-AIR-SCH = "OA SCHD" - 5346 FAN-SCHEDULE = "FAN SCHD" 5347 5348 SET-DEFAULT FOR SYSTEM - 5349 TYPE = PVAVS 5350 HEAT-SOURCE = HOT-WATER 5351 RETURN-AIR-PATH = DUCT -- 5352 MAX-SUPPLY-T = 95 5353 HEAT-SET-T = 55 5354 MIN-SUPPLY-T = 58 5355 COOL-SET-T = 53 5356 COOL-CONTROL = WARMEST 5357 ECONO-LOW-LIMIT = 40 5358 MIN-AIR-SCH = "OA SCHD" - 5359 FAN-SCHEDULE = "FAN SCHD" 5360 FAN-CONTROL = SPEED 5361 SUPPLY-STATIC = 5.5 '' 5362 RETURN-STATIC = 2 5363 NIGHT-CYCLE-CTRL = CYCLE-ON-ANY 5364 REHEAT-DELTA-T = 40 - 5365 HW-LOOP = "HOT WATER" 5366 COOLING-EIR = 0.37 5367 - 5368 5369 SET-DEFAULT FOR ZONE 5370 TYPE = CONDITIONED 5371 OA-FLOW/PER = 15 5372 DESIGN-HEAT-T = 70 5373 HEAT-TEMP-SCH = "HEATING SCHD" 5374 DESIGN-COOL-T = 75 ▪ 5375 COOL-TEMP-SCH = "COOLING SCHD" 5376 THROTTLING-RANGE = 4 5377 SIZING-OPTION = ADJUST-LOADS ▪ 5378 HW-VALVE-TYPE = TWO-WAY 5379 5380 ▪ 5381 "HVAC System 1: LOWER FLOOR" = SYSTEM 5382 TYPE = PVAVS 5383 5384 "1 ENTRY HALLWAY ZONE" = ZONE 5385 TYPE = CONDITIONED 5386 OA-FLOW/PER = 0 5387 OUTSIDE-AIR-FLOW = 50 _ 5388 SPACE = "1 ENTRY HALLWAY" 5389 5390 "5 DONATIONS ZONE" = ZONE ▪ 5391 TYPE = CONDITIONED 5392 OA-FLOW/PER = 20 5393 SPACE = "5 DONATIONS" ▪ 5394 .. 5395 "6 MAIL/LOAD ZONE" = ZONE 5396 TYPE = CONDITIONED 5397 OA-FLOW/PER = 20 5398 SPACE = "6 MAIL/LOAD" 5399 5400 "7 TECH SERV EAST PERIM ZONE" = ZONE 5401 TYPE = CONDITIONED 5402 OA-FLOW/PER = 20 5403 SPACE _ "7 TECH SERV. EAST PERIM" 5404 5405 "8 TECH SERV. NORTH PERIM ZONE" = ZONE 5406 TYPE = CONDITIONED ▪ 5407 OA-FLOW/PER = 20 5408 SPACE = "8 TECH SERV. NORTH PERIM" 5409 ▪ 5410 "9 VOL COORD. ZONE" = ZONE 5411 TYPE = CONDITIONED 5412 OA-FLOW/PER = 20 ▪ 5413 SPACE = "9 VOL COORD." 5414 5415 "10 SEATING NORTH PERIM ZONE" = ZONE 5416 TYPE = CONDITIONED 5417 SPACE = "10SEATING NORTH PERIM" 5418 5419 "11 SHELVES ZONE" = ZONE ▪ 5420 TYPE = CONDITIONED 5421 SPACE _ "11 SHELVES" 5422 — 5423 "12 SHELVES WEST PERIM ZONE" = ZONE 5424 TYPE = CONDITIONED 5425 SPACE = "12 SHELVES WEST PERIM" ▪ 5426 5427 "13 YOUTH SERVICE ZONE" = ZONE 5428 TYPE = CONDITIONED Page: 59 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 5429 SPACE = "13 YOUTH SERVICE" 5430 5431 "14 ELEV MACH/JAN ZONE" = ZONE 5432 TYPE = CONDITIONED 5433 OA-FLOW/PER = 0 5434 EXHAUST-FLOW = 400 5435 SPACE _ "14 ELEV MACH/JAN" 5436 5437 "15 CHILDREN'S AREA ZONE" = ZONE 5438 TYPE = CONDITIONED 5439 SPACE - = "15 CHILDREN'S AREA/SHELVES" 5440 5441 "16 NEW BOOKS+AV ZONE" = ZONE 5442 TYPE = CONDITIONED 5443 SPACE = "16 NEW BOOKS + AV" 5444 5445 "17 FAMILY WC ZONE" = ZONE 5446 TYPE = CONDITIONED 5447 OA-FLOW/PER = 0 5448 OUTSIDE-AIR-FLOW = 50 5449 EXHAUST-FLOW = 50 5450 SPACE = "17 FAMILY W.C." 5451 5452 "18 IDF CLOSET ZONE" = ZONE 5453 TYPE = CONDITIONED 5454 OA-FLOW/PER = 0 5455 SPACE = "18 IDF CLOSET" 5456 5457 "19 INFO DESK HALLWAY ZONE" = ZONE 5458 TYPE = CONDITIONED 5459 SPACE = "19 INFO DESK HALLWAY" 5460 5461 "20 CIRC DESK ZONE" = ZONE 5462 TYPE = CONDITIONED 5463 SPACE = "20 CIRC DESK" 5464 _ 5465 "21 CIRC WORKROOM ZONE" = ZONE 5466 TYPE = CONDITIONED 5467 OA-FLOW/PER = 20 5468 SPACE = "21 CIRC WORKROOM INTERIOR" 5469 5470 "22 STAFF ENTRY HALLWAY ZONE" = ZONE 5471 TYPE = CONDITIONED 5472 OA-FLOW/PER = 0 5473 OUTSIDE-AIR-FLOW = 50 5474 SPACE _ "22 STAFF ENTRY HALLWAY" 5475 5476 "23 WC ZONE" = ZONE 5477 TYPE = CONDITIONED 5478 OA-FLOW/PER = 50 5479 EXHAUST-FLOW = 350 5480 SPACE _ "23 WC" _ 5481 5482 "24 HALLWAY ZONE" = ZONE 5483 TYPE = CONDITIONED 5484 OA-FLOW/PER = 0 5485 OUTSIDE-AIR-FLOW = 10 5486 SPACE _ "24 HALLWAY" 5487 5488 "10A OPAC SELF CHECK ZONE" = ZONE 5489 TYPE = CONDITIONED 5490 SPACE = "10A OPAC SELF CHECK NORTH PERIM" �. 5491 5492 "16A OPAC SELF CHECK ZONE" = ZONE 5493 TYPE = CONDITIONED 5494 SPACE = "16A OPAC/SELF CHECK INTERIOR" 5495 5496 "62 COFFEE ZONE" = ZONE _ 5497 TYPE = CONDITIONED 5498 SPACE = "62 COFFEE" 5499 5500 "64 SHELVES NORTH ZONE" = ZONE 5501 TYPE = CONDITIONED 5502 SPACE = "64 SHEVES NORTH PERIM" 5503 �- 5504 "65 STAFF ROOM ZONE" = ZONE 5505 TYPE = CONDITIONED 5506 OA-FLOW/PER = 20 5507 SPACE _ "65 STAFF ROOM" 5508 5509 "66 PROG ROOM STOR ZONE" = ZONE 5510 TYPE = CONDITIONED 5511 OA-FLOW/PER = 0 5512 SPACE = "66 PROG ROOM STOR." 5513 5514 "67 PROG ROOM ZONE" = ZONE 5515 TYPE = CONDITIONED 5516 SPACE = "67 PROG ROOM" 5517 .. 5518 "2 CIRC DESK SOUTH ZONE" = ZONE 5519 TYPE = CONDITIONED -- 5520 SPACE = "2 CIRC DESK SOUTH PERIM" Page: 60— File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 5521 5522 "3 CIRC DESK WORKROOM ZONE" = ZONE - 5523 TYPE = CONDITIONED 5524 OA-FLOW/PER = 20 5525 SPACE = "3 CIRC WORKROOM SOUTH PERIM" 5526 5527 "4 ELEC ZONE" = ZONE 5528 TYPE = CONDITIONED 5529 OA-FLOW/PER = 0 - 5530 SPACE = "4 ELEC" 5531 5532 "1 ENTRY HALLWAY PLENUM ZONE" = ZONE — 5533 TYPE = PLENUM 5534 SPACE = "1 ENTRY HALLWAY PLENUM" 5535 - 5536 "5 DONATIONS PLENUM ZONE" = ZONE 5537 TYPE = PLENUM 5538 SPACE _ "5 DONATIONS PLENUM" - 5539 5540 "6 MAIL/LOAD PLENUM ZONE" = ZONE 5541 TYPE = PLENUM 5542 SPACE = "6 MAIL/LOAD PLENUM" 5543 5544 "7 TECH SERV EAST PERIM PLENUM ZO" = ZONE 5545 TYPE = PLENUM — 5546 SPACE = "7 TECH SERV. EAST PERIM PLENUM" 5547 5548 "8 TECH SERV. NORTH PLENUM ZONE" = ZONE - 5549 TYPE = PLENUM 5550 SPACE _ "8 TECH SERV. NORTH PERIM PLENUM" 5551 - 5552 "9 VOL COORD. PLENUM ZONE" = ZONE 5553 TYPE = PLENUM 5554 SPACE _ "9 VOL COORD. PLENUM" 5555 5556 "10 SEATING NORTH PERIM PLENUM ZO" = ZONE 5557 TYPE = PLENUM 5558 SPACE _ "10SEATING NORTH PERIM PLENUM" 5559 5560 "11 SHELVES PLENUM ZONE" = ZONE 5561 TYPE = PLENUM '" 5562 SPACE = "11 SHELVES PLENUM" 5563 5564 "12 SHELVES WEST PERIM PLENUM ZON" = ZONE ▪ 5565 TYPE = PLENUM 5566 SPACE = "12 SHELVES WEST PERIM PLENUM" 5567 ▪ 5568 "13 YOUTH SERVICE PLENUM ZONE" = ZONE 5569 TYPE = PLENUM 5570 SPACE = "13 YOUTH SERVICE PLENUM" 5571 5572 "14 ELEV MACH/JAN PLENUM ZONE" = ZONE 5573 TYPE = PLENUM 5574 SPACE = "14 ELEV MACH/JAN PLENUM" ▪ 5575 5576 "15 CHILDREN'S AREA PLENUM ZONE" = ZONE 5577 TYPE = PLENUM — 5578 SPACE = "15 CHILDREN'S AREA/SHELVS PLENUM" 5579 5580 "16 NEW BOOKS+AV PLENUM ZONE" = ZONE .•. 5581 TYPE = PLENUM 5582 SPACE = "16 NEW BOOKS + AV PLENUM" 5583 5584 "17 FAMILY WC PLENUM ZONE" = ZONE 5585 TYPE = PLENUM 5586 SPACE = "17 FAMILY W.C. PLENUM" -ft5587 5588 "18 IDF CLOSET PLENUM ZONE" = ZONE 5589 TYPE = PLENUM 5590 SPACE = "18 IDF CLOSET PLENUM" ▪ 5591 5592 "19 INFO DESK HALLWAY PLENUM ZONE" = ZONE 5593 TYPE = PLENUM 5594 SPACE = "19 INFO DESK HALLWAY PLENUM" 5595 5596 "20 CIRC DESK PLENUM ZONE" = ZONE — 5597 TYPE = PLENUM 5598 SPACE = "20 CIRC DESK PLENUM" 5599 5600 "21 CIRC WORKROOM PLENUM ZONE" = ZONE 5601 TYPE = PLENUM 5602 SPACE = "21 CIRC WORKROOM INTERIOR PLENUM" 5603 ▪ 5604 "22 STAFF ENTRY HALLWAY PLENUM ZO" = ZONE 5605 TYPE = PLENUM 5606 SPACE = "22 STAFF ENTRY HALLWAY PLENUM" • 5607 5608 "23 WC PLENUM ZONE" = ZONE 5609 TYPE = PLENUM ▪ 5610 SPACE = "23 WC PLENUM" 5611 „ 5612 "24 HALLWAY PLENUM ZONE" = ZONE Page: 61 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 5613 TYPE = PLENUM 5614 SPACE = "24 HALLWAY PLENUM" 5615 5616 "10A OPAC SELF CHECK PLENUM ZONE" = ZONE 5617 TYPE = PLENUM 5618 SPACE = "10A OPAC SELF CHECK NORTH PLENUM" 5619 . 5620 "16A OPAC SELF CHECK PLENUM ZONE" = ZONE 5621 TYPE = PLENUM 5622 SPACE = "16A OPAC/SELF CHECK INTERIOR PLE" 5623 5624 "62 COFFEE PLENUM ZONE" = ZONE 5625 TYPE = PLENUM 5626 SPACE _ "62 COFFEE PLENUM" 5627 5628 "64 SHELVES NORTH PLENUM ZONE" = ZONE 5629 TYPE = PLENUM 5630 SPACE = "64 SHEVES NORTH PERIM PLENUM" 5631 5632 "65 STAFF ROOM PLENUM ZONE" = ZONE 5633 TYPE = PLENUM 5634 SPACE = "65 STAFF ROOM PLENUM" 5635 5636 "66 PROG ROOM STOR PLENUM ZONE" = ZONE 5637 TYPE = PLENUM 5638 SPACE = "66 PROG ROOM STOR. PLENUM" 5639 5640 "67 PROG ROOM PLENUM ZONE" = ZONE 5641 TYPE = PLENUM 5642 SPACE = "67 PROG ROOM PLENUM" — 5643 5644 "2 CIRC DESK SOUTH PLENUM ZONE" = ZONE 5645 TYPE = PLENUM 5646 SPACE = "2 CIRC DESK SOUTH PERIM PLENUM" 5647 5648 "3 CIRC DESK WORKROOM PLENUM ZONE" = ZONE 5649 TYPE = PLENUM 5650 SPACE = "3 CIRC WORKROOM SOUTH PERIM PLEN" 5651 5652 "4 ELEC PLENUM ZONE" = ZONE 5653 TYPE = PLENUM 5654 SPACE = "4 ELEC PLENUM" 5655 .. — 5656 "HVAC System 2: UPPER FLOOR" = SYSTEM 5657 TYPE = PVAVS 5658 .� 5659 "36 OREGON HISTORY ZONE" = ZONE 5660 TYPE = CONDITIONED 5661 SPACE = "36 OREGON HISTORY" 5662 5663 "37 YOUNG ADULTS ZONE" = ZONE 5664 TYPE = CONDITIONED 5665 SPACE = "37 YOUNG ADULTS" 5666 5667 "38 SHELVES SOUTH ZONE" = ZONE 5668 TYPE = CONDITIONED — 5669 SPACE = "38 SHELVES SOUTH PERIMETER" 5670 5671 "39 QUITE STUDY ZONE" = ZONE 5672 TYPE = CONDITIONED 5673 SPACE = "39 QUITE STUDY" 5674 .. — 5675 "40 DATA/MECH ZONE" = ZONE 5676 TYPE = CONDITIONED 5677 OA-FLOW/PER = 0 ` 5678 SPACE = "40 DATA/MECH" 5679 5680 "41 TRAINING ROOM ZONE" = ZONE 5681 TYPE = CONDITIONED — 5682 OA-FLOW/PER = 20 5683 SPACE _ "41 TRAINING ROOM" 5684 .. — 5685 "42 SHAFT ZONE" = ZONE 5686 TYPE = UNCONDITIONED 5687 SPACE = "42 SHAFT" .. 5688 5689 "43 REF. WORKROOM ZONE" = ZONE 5690 TYPE = CONDITIONED 5691 OA-FLOW/PER = 20 5692 SPACE = "43 REF. WORKROOM" 5693 5694 "44 OFFICE ZONE" = ZONE 5695 TYPE = CONDITIONED 5696 OA-FLOW/PER = 20 5697 SPACE = "44 OFFICE" 5698 5699 "45 ADMEN ZONE" = ZONE 5700 TYPE = CONDITIONED 5701 OA-FLOW/PER = 20 5702 SPACE = "45 ADMIN" 5703 . 5704 "46 CONF ZONE" = ZONE Page: 62— File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 5705 TYPE = CONDITIONED 5706 OA-FLOW/PER = 20 — 5707 SPACE = "46 CONF" 5708 5709 "47 READING PERIM ZONE" = ZONE — 5710 TYPE = CONDITIONED 5711 SPACE _ "47 READING PERIM" 5712 5713 "48 SITTING ROOM ZONE" = ZONE 5714 TYPE = CONDITIONED 5715 SPACE _ "48 SITTING ROOM" 5716 . - 5717 "49 STAIRWELL ZONE" = ZONE 5718 TYPE = CONDITIONED 5719 OA-FLOW/PER = 0 -m* 5720 OUTSIDE-AIR-FLOW = 50 5721 SPACE = "49 STAIRWELL" 5722 ▪ 5723 "50 ELECTRONIC INFO ZONE" = ZONE 5724 TYPE = CONDITIONED 5725 SPACE = "50 ELECTRONIC INFO" 5726 5727 "51 REFERENCE DESK/OPACS ZONE" = ZONE 5728 TYPE = CONDITIONED 5729 SPACE = "51 REFERENCE DESK/OPACS" 5730 5731 "52 ELEC. INFO ZONE" = ZONE 5732 TYPE = CONDITIONED - 5733 SPACE = "52 ELEC. INFO" 5734 5735 "53 HALLWAY/JAN/STAFF WC ZONE" = ZONE - 5736 TYPE = CONDITIONED 5737 OA-FLOW/PER = 0 5738 OUTSIDE-AIR-FLOW = 80 ▪ 5739 EXHAUST-FLOW = 100 5740 SPACE = "53 HALLWAY/JAN/STAFF WC" 5741 5742 "54 WC ZONE" = ZONE 5743 TYPE = CONDITIONED 5744 OA-FLOW/PER = 50 5745 EXHAUST-FLOW = 350 ▪ 5746 SPACE = "54 WC" 5747 5748 "55 HALLWAY ZONE" = ZONE ▪ 5749 TYPE = CONDITIONED 5750 OA-FLOW/PER = 0 5751 OUTSIDE-AIR-FLOW = 20 ▪ 5752 SPACE = "55 HALLWAY" 5753 5754 "56 HALLWAY ZONE" = ZONE ▪ 5755 TYPE = CONDITIONED 5756 OA-FLOW/PER = 0 5757 OUTSIDE-AIR-FLOW = 25 5758 SPACE = "56 HALLWAY" 5759 5760 "57 NON-FICTION ZONE" = ZONE 5761 TYPE = CONDITIONED ▪ 5762 SPACE = "57 NON-FICTION" 5763 5764 "58 FICTION NORTH INTERIOR ZONE" = ZONE ▪ 5765 TYPE = CONDITIONED 5766 SPACE _ "58 FICTION NORTH INTERIOR" 5767 - 5768 "59 FICTION SOUTH PERIM ZONE" = ZONE 5769 TYPE = CONDITIONED 5770 SPACE _ "59 FICTION SOUTH PERIMETER" 5771 5772 "60 FICTION SOUTH INTERIOR ZONE" = ZONE 5773 TYPE = CONDITIONED 5774 SPACE _ "60 FICTION SOUTH INTERIOR" — 5775 5776 "68 QUITE STUDY ZONE" = ZONE 5777 TYPE = CONDITIONED m" 5778 SPACE _ "68 QUIET STUDY" 5779 5780 "69 HOUGHTON RM ZONE" = ZONE ▪ 5781 TYPE = CONDITIONED 5782 SPACE _ "69 HOUGHTON RM" 5783 r 5784 "70 HALLWAY ZONE" = ZONE 5785 TYPE = CONDITIONED 5786 OA-FLOW/PER = 0 5787 OUTSIDE-AIR-FLOW = 15 5788 SPACE = "70 HALLWAY" 5789 5790 "71 FICTION NORTH PERIM ZONE" = ZONE — 5791 TYPE - = CONDITIONED 5792 SPACE = "71 FICTION NORTH PERIMETER" 5793 5794 "36 OREGON HISTORY PLENUM ZONE" = ZONE 5795 TYPE = PLENUM 5796 SPACE = "36 OREGON HISTORY PLENUM" Page: 63 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 5797 5798 "37 YOUNG ADULTS PLENUM ZONE" = ZONE 5799 TYPE = PLENUM 5800 SPACE = "37 YOUNG ADULTS PLENUM" 5801 5802 "38 SHELVES SOUTH PLENUM ZONE" = ZONE 5803 TYPE = PLENUM 5804 SPACE = "38 SHELVES SOUTH PERIMETER PLENU" 5805 5806 "39 QUITE STUDY PLENUM ZONE" = ZONE 5807 TYPE = PLENUM 5808 SPACE = "39 QUITE STUDY PLENUM" 5809 .. 5810 "40 DATA/MECH PLENUM ZONE" = ZONE 5811 TYPE = PLENUM 5812 SPACE = "40 DATA/MECH PLENUM" 5813 5814 "41 TRAINING ROOM PLENUM ZONE" = ZONE 5815 TYPE = PLENUM 5816 SPACE = "41 TRAINING ROOM PLENUM" 5817 5818 "43 REF. WORKROOM PLENUM ZONE" = ZONE 5819 TYPE = PLENUM 5820 SPACE = "43 REF. WORKROOM PLENUM" ... 5821 5822 "44 OFFICE PLENUM ZONE" = ZONE 5823 TYPE = PLENUM 5824 SPACE = "44 OFFICE PLENUM" 5825 5826 "45 ADMIN PLENUM ZONE" = ZONE 5827 TYPE = PLENUM 5828 SPACE = "45 ADMIN PLENUM" 5829 5830 "46 CONF PLENUM ZONE" = ZONE 5831 TYPE = PLENUM 5832 SPACE = "46 CONF PLENUM" 5833 5834 "47 READING PERIM PLENUM ZONE" = ZONE 5835 TYPE = PLENUM 5836 SPACE = "47 READING PERIM PLENUM" 5837 5838 "48 SITTING ROOM PLENUM ZONE" = ZONE 5839 TYPE = PLENUM 5840 SPACE = "48 SITTING ROOM PLENUM" 5841 5842 "49 STAIRWELL PLENUM ZONE" = ZONE 5843 TYPE = PLENUM 5844 SPACE = "49 STAIRWELL PLENUM" 5845 .. 5846 "50 ELECTRONIC INFO PLENUM ZONE" = ZONE 5847 TYPE = PLENUM 5848 SPACE = "50 ELECTRONIC INFO PLENUM" 5849 5850 "51 REFERENCE DESK/OPACS PLENUM Z" = ZONE 5851 TYPE = PLENUM 5852 SPACE _ "51 REFERENCE DESK/OPACS PLENUM" 5853 5854 "52 ELEC. INFO PLENUM ZONE" = ZONE 5855 TYPE = PLENUM 5856 SPACE _ "52 ELEC. INFO PLENUM" 5857 .. 5858 "53 HALLWAY/JAN/STAFF WC PLENUM Z" = ZONE 5859 TYPE = PLENUM 5860 SPACE = "53 HALLWAY/JAN/STAFF WC PLENUM" 5861 .. 5862 "54 WC PLENUM ZONE" = ZONE 5863 TYPE = PLENUM 5864 SPACE = "54 WC PLENUM" 5865 5866 "55 HALLWAY PLENUM ZONE" = ZONE 5867 TYPE = PLENUM 5868 SPACE = "55 HALLWAY PLENUM" 5869 5870 "56 HALLWAY PLENUM ZONE" = ZONE 5871 TYPE = PLENUM 5872 SPACE = "56 HALLWAY PLENUM" 5873 5874 "57 NON-FICTION PLENUM ZONE" = ZONE �. 5875 TYPE = PLENUM 5876 SPACE = "57 NON-FICTION PLENUM" 5877 5878 "58 FICTION NORTH INT PLENUM ZONE" = ZONE 5879 TYPE = PLENUM 5880 SPACE = "58 FICTION NORTH INTERIOR PLENUM" 5881 5882 "59 FICTION SOUTH PERIM PLENUM ZO" = ZONE 5883 TYPE = PLENUM 5884 SPACE = "59 FICTION SOUTH PERIMETER PLENU" 5885 5886 "60 FICTION SOUTH INT PLENUM ZONE" = ZONE 5887 TYPE = PLENUM 5888 SPACE _ "60 FICTION SOUTH INTERIOR PLENUM" Page: 64— File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 5889 5890 "68 QUITE STUDY PLENUM ZONE" = ZONE 5891 TYPE = PLENUM 5892 SPACE _ "68 QUIET STUDY PLENUM" 5893 5894 "69 HOUGHTON RM PLENUM ZONE" = ZONE 5895 TYPE = PLENUM 5896 SPACE = "69 HOUGHTON RM PLENUM" 5897 5898 "70 HALLWAY PLENUM ZONE" = ZONE 5899 TYPE = PLENUM 5900 SPACE _ "70 HALLWAY PLENUM" X5901 5902 "71 FICTION NORTH PERIM PLENUM ZO" = ZONE 5903 TYPE = PLENUM - 5904 SPACE = "71 FICTION NORTH PERIMETER PLENU" 5905 5906 "HVAC System 3: COMMUNITY WING" = SYSTEM 5907 TYPE = PVAVS 5908 HEAT-SIZING-RATI = 1.5 5909 5910 "26 COMMUNITY ROOM EAST PERIM ZON" = ZONE - 5911 TYPE = CONDITIONED 5912 MAX-HEAT-RATE _ -90000 5913 OA-FLOW/PER = 20 ▪ 5914 SPACE = "26 COMMUNITY ROOM EAST PERIM" 5915 5916 "27 COMMUNITY ROOM CENTER ZONE" = ZONE ▪ 5917 TYPE = CONDITIONED 5918 OA-FLOW/PER = 20 5919 SPACE = "27 COMMUNITY ROOM CENTER" 5920 5921 "28 COMMUNITY ROOM WEST PERIM ZON" = ZONE 5922 TYPE = CONDITIONED 5923 OA-FLOW/PER = 20 5929 SPACE = "28 COMMUNITY ROOM WEST PERIM" 5925 5926 "29 COMMUNITY ROOM NORTH PERIM ZO" = ZONE ▪ 5927 TYPE = CONDITIONED 5928 OA-FLOW/PER = 20 5929 SPACE = "29 COMMUNITY ROOM NORTH PERIM" —5930 5931 "30 COMMUNITY ROOM STORAGE ZONE" = ZONE 5932 TYPE = CONDITIONED ..5933 OA-FLOW/PER = 0 5934 SPACE _ "30 COMMUNITY ROOM STORAGE" 5935 5936 "31 COMMUNITY ROOM VESTIBULE ZONE" = ZONE 5937 TYPE = CONDITIONED 5938 OA-FLOW/PER = 0 5939 OUTSIDE-AIR-FLOW = 10 ▪ 5940 SPACE = "31 COMMUNITY ROOM VESTIBULE" 5941 5942 "34 COMMUNITY ROOM VESTIBULE ZONE" = ZONE ▪ 5943 TYPE = CONDITIONED 5944 OA-FLOW/PER = 0 5945 OUTSIDE-AIR-FLOW = 10 ▪ 5946 SPACE = "34 COMMUNITY ROOM VESTIBULE" 5947 5948 "35 PANTRY ZONE" = ZONE „�5999 TYPE = CONDITIONED 5950 OA-FLOW/PER = 0 5951 EXHAUST-FLOW = 350 _5952 SPACE = "35 PANTRY" 5953 5954 "63 RESTROOMS ZONE" = ZONE 5955 TYPE = CONDITIONED ▪ 5956 OA-FLOW/PER = 0 5957 EXHAUST-FLOW = 680 5958 SPACE _ "63 RESTROOMS" —5959 5960 "26 COMMUNITY ROOM EAST PLENUM ZO" = ZONE 5961 TYPE = PLENUM ▪ 5962 SPACE = "26 COMMUNITY ROOM EAST PERIM PLE" 5963 5964 "27 COMM ROOM CENTER PLENUM ZONE" = ZONE 5965 TYPE = PLENUM 5966 SPACE _ "27 COMMUNITY ROOM CENTER PLENUM" 5967 5968 "28 COMM ROOM WEST PERIM ZON" = ZONE 5969 TYPE = PLENUM 5970 SPACE = "28 COMMUNITY ROOM WEST PERIM PLE" 5971 ▪ 5972 "29 COMM ROOM NORTH PERIM ZO" = ZONE 5973 TYPE = PLENUM 5974 SPACE = "29 COMMUNITY ROOM NORTH PERIM PL" ▪ 5975 5976 "30 COMM ROOM STORAGE PLENUM ZONE" = ZONE 5977 TYPE = PLENUM ▪ 5978 SPACE = "30 COMMUNITY ROOM STORAGE PLENUM" 5979 5980 "31 COMM ROOM VESTIBULE PLENUM ZO" = ZONE Page: 65 File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 5981 TYPE = PLENUM 5982 SPACE = "31 COMMUNITY ROOM VESTIBULE PLEN" 5983 5984 "34 COMM ROOM VESTIBULE PLENUM ZO" = ZONE .�. 5985 TYPE = PLENUM 5986 SPACE = "34 COMMUNITY ROOM VESTIBULE PLEN" 5987 5988 "35 PANTRY PLENUM ZONE" = ZONE 5989 TYPE = PLENUM 5990 SPACE = "35 PANTRY PLENUM" 5991 .. 5992 "63 RESTROOMS PLENUM ZONE" = ZONE 5993 TYPE = PLENUM 5994 SPACE = "63 RESTROOMS PLENUM" 5995 5996 "HVAC System 4: LOBBY" = SYSTEM 5997 TYPE = PSZ 5998 HEAT-SIZING-RATI = 1.5 5999 COOL-SIZING-RATI = 1.5 6000 ECONO-LOCKOUT = NO .� 6001 SUPPLY-STATIC = 3 6002 CONTROL-ZONE = "25 LOBBY ZONE" 6003 6004 "25 LOBBY ZONE" = ZONE 6005 TYPE = CONDITIONED 6006 SPACE _ "25 LOBBY" 6007 6008 "25 LOBBY PLENUM ZONE" = ZONE 6009 TYPE = PLENUM 6010 SPACE = "25 LOBBY PLENUM" 6011 6012 6013 6014 $ ********************************************************* 6015 $ ** ** 6016 $ ** Metering & Misc HVAC ** 6017 $ ** ** 6018 $ ********************************************************* 6019 6020 $ 6021 $ Equipment Controls 6022 $ 6023 6024 6025 6026 $ 6027 $ Load Management 6028 $ 6029 6030 6031 6032 $ ********************************************************* 6033 $ ** ** 6034 $ ** Utility Rates ** 6035 $ ** ** 6036 $ ********************************************************* 6037 6038 $ 6039 $ Ratchets 6040 $ 6041 6042 6043 6044 $ 6045 $ Block Charges 6046 $ 6047 6048 "ON PEAK CHARGE" = BLOCK-CHARGE 6049 BLOCK-SCH = "PGE SCHEDULE 38 SCHD" 6050 SCH-FLAG = 1 6051 BLOCKS-1 = ( le+008 ) 6052 COSTS-1 = ( 0.07859 ) 6053 6054 "OFF PEAK CHARGE" = BLOCK-CHARGE 6055 BLOCK-SCH = "PGE SCHEDULE 38 SCHD" 6056 SCH-FLAG = 0 6057 BLOCKS-1 = ( le+008 ) 6058 COSTS-1 = ( 0.06486 ) 6059 6060 6061 6062 $ 6063 $ Utility Rates 6064 $ 6065 6066 "PGE SCHEDULE 38" = UTILITY-RATE 6067 TYPE = ELECTRICITY 6068 MONTH-CHGS = ( 25 ) 6069 BLOCK-CHARGES = ( "ON PEAK CHARGE", "OFF PEAK CHARGE" ) 6070 .. 6071 "NW NATURAL SCHEDULE 3" = UTILITY-RATE 6072 TYPE = NATURAL-GAS Page: 66-' File: C:\POWERDOE\PROJECTS\Final Tigard\7692\7692.INP 1/14/2003, 3:29:54PM 6073 MONTH-CHGS = ( 7 ) 6074 ENERGY-CHG = 0.79457 6075 6076 6077 ▪ 6078 $ ********************************************************* 6079 $ ** ** 6080 $ ** Output Reporting ** 6081 $ ** ** 6082 $ ********************************************************* 6083 6084 $ ▪ 6085 $ Loads Non-Hourly Reporting 6086 $ 6087 6088 LOADS-REPORT 6089 6090 r. 6091 6092 $ 6093 $ Systems Non-Hourly Reporting ▪ 6094 $ 6095 6096 SYSTEMS-REPORT 6097 6098 6099 6100 $ ▪ 6101 $ Plant Non-Hourly Reporting 6102 $ 6103 - 6104 PLANT-REPORT 6105 6106 ... 6107 6108 $ 6109 $ Economics Non-Hourly Reporting 6110 $ 6111 6112 ECONOMICS-REPORT 6113 ▪ 6114 6115 6116 $ ▪ 6117 $ Hourly Reporting 6118 $ 6119 ▪ 6120 "Report Block 1" = REPORT-BLOCK 6121 VARIABLE-TYPE = "HVAC System 3: COMMUNITY WING" 6122 VARIABLE-LIST = ( 17, 39 ) ▪ 6123 6124 "Report Block 2" = REPORT-BLOCK 6125 VARIABLE-TYPE = GLOBAL 6126 VARIABLE-LIST = ( 4 ) 6127 .. 6128 6129 "Hourly Report 1" = HOURLY-REPORT "m6130 REPORT-SCHEDULE = "ALWAYS ON SCHD" 6131 REPORT-BLOCK = ( "Report Block 1" ) 6132 ▪ 6133 6134 6135 $ 6136 $ THE END 6137 $ 6138 6139 END .. 6140 COMPUTE .. 6141 STOP .. S Page: 67