Report (123) SSU'O C:AZ , Q (\(\ RECEIVED SEP 19 2018 CITY ® �V��t�� BUILDING OFFICE COPY n/nt® n tet TEG /t# E S Making a Daily Difference Product Data Submittal Booklet Durham Education Center Fire Alarm System Project #: 302-FN-H0293 Submittal Date: August 28, 2018 Project Manager: Gene Durnin Electronic Security Project Engineer: Bryan Duffel Fire Alarm & Life Safety Building Automation 503-228-8522 I www.conver2int.com EQUIPMENT LIST Head End Equipment item Part# Manufacturer Description 1 5496 Silent Knight 6 Amp Intelligent Booster Power Supply 2 5860 Silent Knight Remote Annunciator, Red 3 5820XL-EVS Silent Knight Emergency Voice System & Fire Alarm Control Panel 4 SS000685 Space Age Fire Alarm Documents 5 TG-7FS TelGuard Cellular Communicator Field Devices item Part# Manufacturer Description 6 MR-101/MR-201 Edwards Mutli-Voltage Control Relays 7 SK-HEAT Silent Knight Intelligent Heat Detector, Fixed Temp 8 SK-ISO Silent Knight Intelligent Isolation Module 9 SK-MONITOR Silent Knight Intelligent Single Input Module 10 SK-MONITOR-2 Silent Knight Intelligent Dual Input Module 11 SK-PHOTO Silent Knight Intelligent Photoelectric Smoke Detector 12 SK-PULL-SA Silent Knight Intelligent Manual Pull Station, Single Action 13 SK-RELAY Silent Knight Intelligent Control Relay Notification Devices Rem Part# Manufacturer Description 14 SPCW System Sensor Indoor Ceiling Speaker, White 15 SW System Sensor Wall Strobe, Standard cd, White 16 SCW System Sensor Ceiling Strobe, Standard cd, White 17 SPW System Sensor Indoor Wall Speaker, White Battery information is subject to availability at time of installation and not presented here. Sampling tube lengths for duct detectors to be coordinated with mechanical vendor. H Z Lu Lu Z w Lu FIRE SYSTEM ACCESSORY 410 SILENT 5496 Intelligent KNIGHT Power Module by Honeywell A dynamic combination of power and intelligence for your notification expansion needs. The Model 5496 Intelligent Power Module by Silent Knight is the most-powerful and cost-effective power supply available today. It delivers 6 amps of notification appliance circuit power and built-in synchronization for appliances from System Sensor®, Gentex®, Faraday,AMSECO and Wheelock®—what you need to drive power-hungry components like ADA notification appliances. The 5496's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies. For the most sophisticated and cost-effective notification power supply available, you need Model 5496. Call Silent Knight today for more information at 1-800-328-0103. Model 5496 • 3 amps per output circuit Intelligent Power Module • Ground fault detector The model 5496 is a 6 amp notification • Communicates to the FACP via 4- power expander that provides its own wire SBUS (wire runs up to 6000 ft) AC power connection, battery charging • AC loss delay option shuts off power circuit, and backup battery for use with to non-essential high-current fire and security controls such as the accessories like magnetic door IntelliKnight Model 5808 Fire Control holders /Communicator. The 5496 is the cost- • Lightweight design adds to ease of <<� effective solution for powering installation and reduces shipping notification appliances required by the costs Americans with Disabilities Act(ADA). The 5496 has built-in ANSI cadence • UL 864,1481 & 1971 listed • ANSI Cadence pattern output pattern, which can upgrade older control panels that lack cadence capability built-in capability. The Output circuits can be Specifications programmed as Notification Appliance AC Input 120 VAC at 2.7 A SH.Evr Circuits, or as Auxiliary Power �� ����� A��� "�6H7 (configurable for, constant, resettable, Output: 24 VDC at 6 amps or door holder power). Current: Model 5496 Intelligent Features Standby 40 mA Power Module • UL Listed for 6 amps of notification Alarm 160 mA Ambient Temp.: 32°to 120° F power Notification/Aux. 0°to 49°C • Power supply's advanced switch Power circuits: 4 mode design reduces damaging Dimensions: 12.25"W x 16" H x heat and manages power up to 50% Output 3" D(30.88 cm W configuration: 2 Class A(Style Z) x 40.64 cm H x more efficiently than other systems 4 Class B(Style Y) 7.62 D cm) • Built-in synchronization for (1 Class A& appliances from AMSECO, Gentex®, 2 Class B) Approvals: UL Faraday, System Sensor®, andAmps per CSFM Wheelock® output circuit: 3.0(6.0 amps total) MEA 429-92-E vol.XIV • 24 VDC filtered output voltage Notification • Four power-limited notification circuit output: 20.4 to 27.3 VDC Compatible FACPs outputs; 2 Class A or 4 Class B, or 1 @ 3.0 amps each, • Class A and 2 Class B 4.7k EOL resistor IntelliKnight 5700 • NACs are programmable as required on each • IntelliKnight 5808 Notification Appliance Circuits, or as Class B circuit IntelliKnight 5820XL auxiliary power to be used as Battery charging constant, resettable, or door holder capacity: 35.0 AH power FIRE SYSTEM ACCESSORY Firepower 5496 Distributed Power Module Engineering Specifications The contractor shall supply a power module compatible with the Silent Knight FACP. The power module must have 6.0 amps of output power. The power module shall connect to the main FACP via an RS 485 system bus (SBUS). The Outputs shall be programmable as Notification Appliance Circuits, or as Auxiliary Power (configurable for, constant, resettable, or door holder power). The power module shall have four separate outputs. The power module RS 485 bus shall be optically isolated providing ground loop isolation and transient protection. 4 Outputs Programmable as Notification Appliance Circuits, or as Auxiliary Power Output 1 . i SBUS Communication To a Compatible Output 2 -` I Silent Knight FACP 011/1 Output 3 . Output 4 A, Auxiliary Power Can Be Programmed To Be Constant, Resettable, or Door Holder Power SILENT-41%lith This document is not intended to be used for installation purposes.We try MADE IN AMERICA KNIGHT to keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are FORM#350387 Rev D subject to change without notice. For more information, contact ©2010 Honeywell International Inc. by Honeywell Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone:(800)328-0103, Fax: (203)484-7118.www.silentknight.com INTELLIKNIGHT ACCESSORY 10 SILENT 5860 Remote Annunciator KNIGHT by Honeywell Bring the power to control an IntelliKnight fire alarm control panel to every area within your facility Now you can operate and program your IntelliKnight system from up to twelve locations throughout your facility. The 5860 remote annunciator provides the same advanced, easy-to-use interface found on the IntelliKnight panel's built-in annunciator. The 80-character display and ergonomically designed keypad allow for simple and error-free system operation.All operations—including reset, silence, detector status checking, fire drill, and programming—are identical. Access to the system is through a firefighter's key or an access code. For security, a special installation code is needed for programming functions. The 5860 connects to the IntelliKnight panel via the RS-485 system bus. Wire runs can be up to 6000 feet from the panel. For more information about the IntelliKnight system, or to locate your nearest source, please call 1-800-328-0103. Description • Available in red or light gray Features include an 80-character • Support for simultaneous use of backlit LCD providing easy-to- multiple 5860s understand system messages. The • RS-485 interface to panel annunciator is ergonomically • Operation and appearance is w designed with over-sized buttons identical to 5860 built-in �M ... for the most frequently used annunciator - • features, like Reset and Silence. • On-board piezo sounder audibly indicates alarms, troubles, and • In addition to status messages � a. supervisories m ����". displayed on the LCD, there are • Five statusLEDs for alarm, five LEDs for alarm, supervisory, supervisory, trouble, silence and trouble, silence, and AC power AC power conditions status. • Wiring lengths up to 6000 ft. from 5860 The annunciator is available in gray the FACP (depending on wire Environmental to match virtually any decor and gauge and number of devices on Operating Temperature: 320 F– SBUS) 120°F (0°C–49°C) red for applications where the • UL listed, complies with NFPA 7210% 0 annunciator must stand out. The p Humidity: – 93/o non- annunciator enclosure can be • CSFM approved condensing surface or flush mounted. A trim Electrical Specifications Compatibility ring kit is available for surface Operating Voltage: 24 VDC The 5860 is compatible with the mounting. Standby Current: 20 mA max following FACP's: Features Alarm Current: 25 mA • 5820XL Addressable Fire Control • 80-character backlit LCD display Wiring Distance: 6,000 max. from Panel (4 lines with 20 characters on each line FACP (depending on wire gauge 5820XL-EVS Fire Control Panel and number of devices on the with Emergency Voice System • Tactile and audible feedback SBUS) • 5808 Addressable Fire Control • Accepts user codes or fire Panel fighter's key Mechanical Specifications • Larger keypad buttons for system Physical 9.1" W x 7.4" H x 1.5" D • 5700 Addressable Fire Control reset and silence (23.1 W x 18.8 H x 3.8 D cm) Panel • Install up to twelve 5860s per Shipping Weight: 2.8 lbs (1.3 kg) 5820XL/EVS or 5808 system Color • Install up to eight 5860s per 5700 PN 5860R: Red ©2014 Honeywell5022I4 nternational Inc system 5860: Gray INTELLIKNIGHT ACCESSORY • 5860 Remote Annunciator Engineering Specifications The main control must have a built-in annunciator and must support up to 12 remote annunciators. Remote annunciators shall have the same control and display layout so as to match the appearance of the built-in annunciator. Remote annunciators shall be available in two colors, red or light gray. Remote annunciators shall have identical functionality and operation as the built-in annunciator.All annunciators must have an 80-character LCD display and must feature five LEDs for: General Alarm, Supervisory, System Trouble, System Silence, and System Power. All controls and programming keys are silicone mechanical type with tactile and audible feedback. Keys have a travel of .040 inches. No membrane style buttons will be permissible. The annunciator must be able to silence and reset alarms through the use of a code entered on the annunciator keypad or by using a firefighter's key. The annunciator must have two levels of user codes that will limit the operating system programming to authorized individuals. The control panel must allow all annunciators to accommodate multiple user input simultaneously. Wire Runs Up to 6000 Feet From FACP - ' 111o -H644t. Y Q+T44: 444 C3. SBUS 1 •44 i z� `.5860 5860 1118 5860 IIIIa • Up to 12 5860s Per IFP-100/ECS or IFP-1000/ECS System •Up to Eight 5860s Per 5700 System Compatible IntelliKnight FACP Listings Ordering Information NFPA 72; UL Listed; 5860R Remote Annunicator four line LCD CSFM 7170-0559: 135; annunciator with 20 characters per line. MEA 429-92-E Vol. IX; Red FM Approved 5860 Remote Annunciator four line LCD annunciator with 20 characters per line. Gray Accessories 5860TR Red Trim Ring for surface mounting 5860TG Gray Trim Ring for surface mounting SILENT This document is not intended to be used for installation purposes.We try to *********** itikKNIGHT keep our product information up-to-date and accurate.We cannot cover all ******* k*** specific applications or anticipate all requirements.All specifications are *** *** subject to change without notice. For more information,contact Silent Knight by Honeywell 12 Clintonville Road, Northford, CT 06472-1610. Phone: (800)328-0103, Fax: (203)484-7118. For Technical Support, Please call 800-446-6444. www.silentknight.com Assembled in America INTELLIKNIGHT FIRE ALARM CONTROL PANEL WITH EMERGENCY VOICE SYSTEM SILENT IntelliKnight® Model 5820XL-EVS 4110 KNIGHT Addressable Fire Alarm Control Panel with Emergency Voice System by Honeywell The IntelliKnight System is the easy way to make the most of fire alarm technolo . IntelliKnight 5820XL-EVS offers an Emergency Voice System integrated with the fire alarm functions of the control panel. The 5820XL-EVS offers built-in digital communication, distributed intelligent power, a modular design and an expanded, easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the 5820XL-EVS system, or to locate your nearest source, please call 800-328-0103. Description 5820XL-EVS is an intelligent addressable fire alarm control panel combined with an Emergency Voice System (EVS). When the EVS features are enabled, they are integrated with • the fire alarm and voice evacuation functions of the control panel. The 5820XL-EVS panel and accessories provide features to meet the requirements for Mass Notification „I OW III MI Systems as described in UL 2572. ,- �� NM MO / �IINN � The basic 5820XL-EVS system can be expanded by adding memowNo am me my modules such as 5860 remote annunciator, 5815XL signalling line circuit expander, 5824 serial/parallel printer interface module (for printing system reports), and 5895XL intelligent power module. 5820XL-EVS supports SD or SK devices. — "• ` Features • Built in support for 99 SK detectors and 99 SK modules, Model 5820XL-EVS expandable to 396 SK detectors and 396 SK modules using • Programmable date setting for Daylight System Sensor protocol Saving Time • Built-in support for 127 SD devices, expandable to 508 SD • Two built-in Form C programmable relays devices using the SD protocol rated at 2.5 amps at 27.4 VDC • Support of up to four EVS-50W, EVS-100W or EVS-125W • 6 amp power supply and maximum charging amplifiers for a maximum of 500 watts capacity of 35 amp hours (An additional • Each amplifier has four built-in speaker circuits expandable cabinet enclosure is required for batteries in to eight excess of 18 amp hours) • 15 Recordable one minute messages that can be mapped to • Improvements in SKSS software deliver five eight EVS buttons times faster uploads/downloads • Can select EVS message as priority over fire • 16 built-in speaker group switches • Support of up to four EVS-RCU's. The EVS-RCU meets the expandable to 32 requirements for a LOC • Built-in RS-232 and USB interface for • Six FlexputTM I/O circuits programming via PC • Central station reporting by point or by zone Compatibility • Built-in synchronization for appliances from AMSECO®, Gentex®, Faraday, System Sensor, and Wheelock® The 5820XL-EVS is compatible with the • Supports Class B (Style 4) and Class A(Style 6) configu- following EVS components: ration for SLC, SBUS, and Flexput circuits • EVS-50W - 50 watt amplifier • 13 pre-programmed output cadences (including ANSI-3.41) • EVS-125W - 125 watt amplifier and 4 programmable outputs • EVS-100W - 50/100 watt amplifier • Built-in annunciator with 80-character LCD display • EVS-100WBU - External backup amplifier • RS-485 bus provides communication to system accessories • EVS-INT5OW- 50 watt internal amplifier • UL listed for Continuous or ANSI 520Hz speaker tones that • EVS-SW24 - 24 switch expander meet NFPA 72 Low Frequency Signal Requirements for • EVS-VCM - Voice control module Sleeping Areas when used with the EVS-INT5OW or EVS- • EVS-RCU - Supervised remote control unit 100W amplifiers and compatible speakers. P/N 351562 Rev G ©2016 Honeywell International Inc. INTELLIKNIGHT FIRE ALARM CONTROL PANEL WITH EMERGENCY VOICE SYSTEM ''` '" 1 I ► lit I I. SK Minlmon SK.Duol Input Module Smoke Detector I ' k n e aA ♦ fAv, ti'1 I 1 1 t 2-Wire Notification Monitor Relay Isolator 1010Aace Module Module Module Module EVS-RCU EVS-125W SBUS 5820X1-EVS Module SK RADA ?k Addressable I, i 1 l 1 I PWIStStatialin,, an — SLC .+M `.,. ,,: .40" #'r"' d'' loop 0000 I _ _ SKPhotoSK Ion SK-Heat CO Smoke Sounder Relay Isolator S 2 :• Det Base Base Base mo-oec as mss SBUS I MIIIM o� arc . 4,___„„g I \ 5860 5824 NemMehnun�ater 5 .Paralls P I_ ll .iece M1Etd ue r 5895X1 Pwskfetlu: NotificatioNAuxP� L000 lICnoI swtoFmd Pull — 0,- 0- 0- 0 sets SSIro�es,.1„.04,./.. snake Delectars sass llors Command input on Monaco I -- VCM or RVM Systom MAMA M rasa Relay s^nae 5880 %654 or 58654 nwd-pie L=artcsL rer LED.Ann4nc-0101 EVS 5580 mvmM0040 ;58054 A0mm) or input Physical Meets the requirements for NFPA 72 Local Protective Flush Mount Dimensions: Signaling Systems& Emergency Communication Systems. 20.25"W x 26.75"H x 2.5"—3"D Other Listings: (51.4 W x 68 H x 6.4-7.6 D cm) CSFM; OSHPD (CA) OSP-0065-10 Overall Dimensions: 20"W x 26.5"H x 4.6"D Compatible Devices (50.75 W x 67.3 H x 11.8 D cm) See the specification sheets listed below for a complete Color: Red listing of the SD and SK devices. Environmental 53624 SD Devices Data Sheet Operating Temperature: 32°F— 120°F (0°C—49°C) 53623 SK Devices Data Sheet Humidity: 10%—93% non-condensing Ordering Information Electrical 5820XL-EVS FACP with Emergency Voice System Primary AC: 120 VAC @ 60 Hz, 2.5A EVS Accessories Total Accessory Load: 6A @ 27.4 VC power-limited EVS-50W 50 Watt Amplifier Standby Current: 275 mA EVS-125W 125 Watt Amplifier Alarm Current: 440 mA EVS-100W 50/100 Watt Amplifier Battery Charging Capacity: 7 to 35 AH EVS-100WBU External Backup Amplifier Battery Size: 18 AH max. allowed in control panel cabinet. EVS-INT5OW 50 Watt Internal Amplifier Larger capacity batteries can be housed in RBB accessory EVS-CE4 4 Circuit Audio Expander cabinet EVS-SW24 24 Switch Expander Six Conductor Wiring: Two voice bus&four SBUS EVS-VCM Voice Control Module Listings VIP-TR Panel Trim Ring to flush mount NFPA 13, NFPA 15, NFPA16, NFPA 72: Central station; SK-SCK Seismic Compliance Kit remote Signaling; Local Protective Signaling Systems; EVS-RCU Supervised Remote Command Unit Auxiliary Protected Premises Unit; &Water Deluge releasing service. Suitable for automatic, manual, waterflow, sprinkler- supervisory (DACT non-coded)signaling services. - UL 864 and UL 2572 SILENTN till This document is not intended to be used for installation purposes.We try to keep our product information up-to- KNIGHT date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information, contact Silent Knight 12 Clintonville Road, Northford,CT 06472 Phone: (203)484-7161, Fax: (203)484-7118. For Technical Support, by Honeywell Please call 800-446-6444.www.silentknight.com. SN SIGNALING ((eie LISTED ACE-11 FIRE ALARM DOCUMENTS The FAD is the perfect fit to meet the demanding code requirements today. SAE's number one goal is FIRE ALARM DOCUMENTS to manufacture code compliant solutions and this Records / Programs Software product allows you to do just that. NFPA 72 2007 section 6.2.2.1 states, "A record of installed software and firmware version numbers shall be maintained at the location of the fire alarm control unit." This durable 16au a steel enclosure with a solid 9 9 piano hinge and key lock will keep all of your code required documents in one safe place. With a 4GB USB flash drive it stores your fire alarm software safe and secure eliminating the occurrences of the soft- ware not being on site when technicians arrive to service the system. Along with your fire alarm soft- Standard Features: ware you can store your test & inspection docu- ments, service records, manuals &AS built drawings • Installed with a 4 gig digital flash drive for the system. Using a standard USB B connector it with USB B connector allows you to plug in with any standard SB printer • 2 Key ring hooks to hold system keys cable to upload or download information. • Business card holder for key contacts • Overall Dimensions are 12" x 13" tall and 2 '/4 deep The FDB is designed to hold critical manuals and • 16 gauge steel box and cover for security documents with a durable steel retainer. It has • Durable powercoat baked on finish designated hooks to organize key rings and hold other colors available important business cards for easy access and • Standard%"cat 30 key lock other lock as- reference. Inside the cover it has a organized note semblies available table that allows for documentation for passwords • Solid stainless steel piano hinge and other critical system information. • Permanently screened white ink 1" high "Fire Alarm Documents" • Legend sheet for passwords and system information BOX ISO 9001Space Age Electronics, Inc. FIRE° WINll- REGISTERED www.lsae.corn NFPA COMPANY 800.486.1723 Toll Free MEMBER Made In U.S.A. 508.485.0966 Local 508.485.4740 Fax Space Age Electronics, Inc. 2009 ED0549 LT10559 Rev.D 1/2 No Excuses, Just Solutions! 4 SPACE AGE ELECTRONICS, INC. Specifications: The fire alarm documents box (FAD) shall be UL Listed, constructed of 18 gauge cold rolled steel. It shall have a red powder coat epoxy finish. The cover shall be permanently screened with 1" high lettering "FIRE ALARM DOCUMENTS " with white indelible ink. The access door shall be locked with a 3/4" barrel lock and the hinge shall be a solid width 12" stainless steel piano hinge. The enclosure will supply 4 mounting holes. Inside the enclosure will accommodate standard 8 1/2 x 11 manuals and loose document records that will be protected within the enclosure. A legend sheet will be permanently attached to the door for system required documentation, key contacts and system information. The FAD will have securely mounted inside a minimum of 4 Gigabyte digital flash memory drive with a standard USB B connector for uploading and downloading information. The drive shall not be accessible without tools to any person whom gains access to the records. The enclosure shall also provide 2 key ring holders with a location to mount standard business type cards for key contact personnel. s II USB Storage Interface _— Requires Standard USB-B Connector Fv.epacemem forms order am En5215(gty 10) .1030x Property Information Minimum Required fh talion(SIGFUN) Key Ring (Reference 22 2013 d. app—, �ap Hooks R,. Or AR :\ a Certifications d Approvals pmn .n0,.-e .�mn2w wanm.m X61 Sy t t 11 t C l C n �, sled* all NFPA standardsmed h.,.i ..g .p•.t n. ..�nnr.ae.nw.... u Cie p= Business Signed p"'"p ,° ': Mona D WA D Enclosed Or All Location Card Holder 65 Authorty Hav ng Jursd onErl Of All dl imed pivna.ra�au, _0,q_ v� wln eppaed ea W.a +ad wihv 11,22,121ed rex.elnaprJm stowN/A Enclosed Or AI Locelion ,, * Conpled,e�da�npRbowill e2 N/A Endo.Or A.Location • pTale er. —— ,, of Me Leann 6 Equipment Information �� 113.1 c a A22....2. WA on panvnntan n.�.d.o.am Scion 2s se enol .p.rnen d ID NOR 14 ROW.rec.rata..and 0 maintenance in Mu.,2 Senal N/A-1 Enc..Or AIL Locall2n Access coda. SW. Dale i ~ J s Ag2 Checks.Road Stm Mn01.4 200,26,223 v LT10644 Rev 1 pare Age Incrt. 'n9. wxv.see.¢m Legend sheet for storing system information including contacts,sign-off, maintenance & test information,and alternate locations f \ of additional records. Ordering Information: Part# Description SSU00685 Fire Alarm Storage Cabinet RED Space Age Electronics, Inc. SSU00686 Custom screening with your Logo www.isae.com 800.486.1723 Toll Free Check out our Infinity line eFAD single gang 2 Gig digital storage 508.485.0966 Local solutions (IAMEFAD) 508.485.4740 Fax This document is subject to change without notice,see doc#ED0479 for legal disclaimer No Excuses, Just Solutions! ED0549 LT10559 Rev.D 2/2 C c N C '` f `a � 0 CD �," �' +N.+ `a- U �' �-+ N U 'ik?.44e"a,HIIM .s :? x Q w OC n N Ccac o > o x o o c o w i O ii co D — u: i (D i u- i on C a ,o4,''''",'nx ,e �,.: �� Li _CD O slit ,. i Af • a./". n' xss M-, . n v » ;,\ C l wa (% ' NU -a .O 011 u- NNcNCLL) 4„ 73 5 ro co U z N + UU a6,U O ONO C \N C O "N �L LL 7 a)1WQQ (n N >, Q r6 U L U 0t3 O L1- Nyr � '6 Ow vi To 0 >, N — NC V +Na r ` sF # Ay .. > Q O U) 6) w O +. C ' N .- OC $ , r 'Ai„ «Q> tpC aaU N ateU . N COO � " N4 c ' ` o0W +3 ” U N N O .2 .ar6 >” 'o vQ N No a � � � � v Q ,y, HV) Q w ° Q O C "LZ � � O3 . . �- � Ca � wi tA 3 3 5 � v n 0 � 40_, OU .` > '2 � , � ro„-,- c2 O N O o . r „ro Q c 9 oLI! U H � }' O .0 ro . 6 — o ;6 LE _ 7 (6 . NCL QEj ,,,,„„,,,,,„,,,,,-E),-, SV O 4V 6 U U N - u) 6U3O 6 t6 CiL 6 - t : . w ' Fce C O 0 �ONr6 S3 O Q2 c +c, O a =3) O E) N .- ra 4k C w' 0 O0v CM Pi— E � 7 OE N O2 �O -LN� hT UN ( 4 i , ) a, a( IN N ' ro : t 1Z O 0 O O C cn a f . •c O 'I'. O > aiO > 'c o t , w ' r at Ua z U aot9xa N a i � U i, a) a:, ra E m E U U N I— Q 5 a. ” :' ; " � fe �' T w , ,Y"aYf ( µ %: 7' MNt �ro 6j, ,.1',',.`,,,,k, t v '` , s d v t ,,:,,,o,,,,,,,,,,,,,,..o,,,4,,,,,-',"'„:40 tr fi,riirr-p h -t ,,,,,,„41- 1 i b s Mt w*V q° t ' X3%9"S v- , e. 4(4(,,, -4,rat`',tLy ' '- --4. '' r o,. W H #M<� ,,N 54° T'' � .-*$, r , 4!:,,A4',., 4 nw ;^G 4.4114 1 ' ',P '.'' Kro,,, ,.`�'F rim, ,6,3 6 t f�, Sreur • ,rrt /� I. Y O' (4 o r {')OO , v v 3 Q m v? ',/ 'D 0 c N 0 C sv O t.l S'p Z5 ,_.�. K i y n /�// N iv Q S N.. COQ- • , moi//// o� m _ 3449. rQ• z �� D o C a • 0 0: o v m , a o x -I-1 v o 5. D v o �_ o N ' P 0 W O (D CS '"� Ut u// < `-�. vii O .-+ * o • Nv fa. Q N- n ,D j --n ED' _ o - CO Qvb %(D ccr o fD O . x 3 0N /' x . ' / C7^ N (n < C 7oCTi � C N O � 11 0 > 0v t3 '- , Q Q OK 0 0y1iv �3a N K K (4 N • , • „ O i %�%'/✓/ m,<r "d'i�i .S. . www*v.✓ s • 0 c H c 0- 1— fio:) o a ° r m 2 D o 3 '� nm • fir X 0 n lDcc, O rt � @Jill Z o n o v n o n '_* >< 0 Cu O Ort v C • m CD �+ of Cn N g a a ii o m 2 o �� m 2 O D m �' p m V N "�6 m` N �. C rt to p O• O < N 3. O OO 10 Q C rr 0 o_ 3 0 0 v (4 W rt a N o W-7,,--- ,< N 0 N A3 Ni .�. 10 p <. s4 m D `< Q _ m n w n N (D (D C o) - 0 " 3 1y rt_ O O < rt v o a 3 r- cu n� v � D 0 D O0 rt sL - f« / r. m o� o m v ° o n Cu w C� 0 0 - a l.JJ c m _ (DD 0 8_rY5.. Cn S714E- T 7 Vf y 0. N ,,,• W rt 3 0 PY, g • K rt N O O1 3 y r /i D o s a� 3 CO 0 o �3A III III \ C O < c v -"0 0 N n Cu (r) ° v a (0 A fp 71 m > 3 . Q n v I•-r 0 --1 o " 3 LI 110111)kv vw f r= 3 = Q >(O C. � N r ° 3 (D � Ono.:, ymm K O_ > ^: g'mm `, . (D -% 0 F. ild- 1 6d /VB-' Z in ci O a �. ..�,. ...:..Hv�++.a-....,r.�c�e....r•'�;.i.-.„�lECtWq'W4�.,'e.�e'.M^^m':.. ... .a..n•..-3AM."'�-�.�e!.�+.c._... v...:;a.f,v...i..yn_:, n.�..�:..� -. FIELD DEVICES Power Supplies and Accessories ST Life Safety & Communications "RELAY ON" LED LED VIEWING HOLE 'SNAP (3141=. APART" :.. Multi -Voltage SEAMSMR 101/C, MR 201/C Control Relays : MR-100 & MR-200 Series MR-104/T LED VIEWING HOLES \\. > MR-101/T \o \\ MR-104/C,MR-204/C Overview Standard Features The MR-Series Multi-Voltage Control Relays offer SPDT or DPDT • Each relay position may be energized from one of four input 10 Amp contacts which may be operated by one of four input voltages control voltages.A single relay may be energized from a voltage • Each relay position contains a red LED which illuminates when source of 24 Vdc, 24 Vac, 115 Vac or 230 Vac by wiring to ap the coil is energized.This provides a timesaving convenience propriate input terminals. when checking an installed system; no metering is required. Each relay position contains a red light emitting diode(LED)which • Single, dual or triple relay modules may be"snapped apart" indicates the relay coil is energized. Relays may be"snapped from a standard four-position master apart"from a standard four-module assembly and used independ- ently. • SPDT or DPDT relays available These devices are ideal for applications where local contacts are • Available in dustproof metal enclosures with LED viewing port required for system status, remote contacts for control of electri- • Track mounting hardware to facilitate installation in standard cal loads and general purpose switching.They are suitable for cabinets use with HVAC Temperature Control, Fire Alarm, Security, Energy Management, and Lighting Control Systems. • UL recognized relays rated at 10 million mechanical operations • ULI listed as control unit accessory Page 1 of 2 270062 issue 1.1 • ....,,,,,,,,,AS ", Installation Wiring (TYPICAL FOR ONE MODULE POSITION) SPDT Contacts A UTC Fire&Security Company 10 AMPS @ DPDT Contacts ' 115 V.A.C. 10 AMP @ 115 V.A.C. Detection&alarm since 1872 7I I I\ I U.S. I• NC C NO • I• • T 888-378-2329 NO C NC NO C NC F 866-503-3996 0 0 0 0 0 0 Canada ENERGIZED"\... Chubb-Edwards INDICATOR T 519 376 2430 F5193767258 I I I I Southeast Asia I I I I T:+65 6391 9300 F:+65 6391 9306 Input 1• 0 24 t15 230 • Input • 0 24 n5 230 •I India Control I I I I I Control I I I I I T:+91 80 4344 2000 Voltage Voltage F:+91 80 4344 2050 24 VDC OV 24V . 24 VDC OV 24V... Australia 24 VAC C C X 24 VAC C C ♦ T+61 3 92391200 115 VAC N 115 VAC N F+61 3 9239 1299 230 VAC H •. H 230 VAC H . H Europe TERMINAL STRIP CONNECTIONS TERMINAL STRIP CONNECTIONS T+32 2 725 11 20 MR-101 (MR-104) MR-201 (MR-204) F+32 2 721 86 13 Latin America Specifications T 305 593 4301 F 305 593 4300 Power Requirements utcfireandsecurity.com MR-101 Position 15 mA @ 24 Vac,24 Vdc, 115 Vac,230 Vac MR-201 Position 35 mA @ 24 Vac,24 Vdc, 115 Vac,230 Vac ©2010 UTC Fire&Security. Relays All rights reserved. MR-101 UL Recognized SPDT MR-201 UL Recognized SPDT Enclosure 18 ga.CRS,plated with 1/2 in conduit knockouts(top and bottom) Contact Rating 10 Amps @ 115 Vac Ambient Temperature -58°F to 185°F(-50°C to 85°C) Approvals UL Listed control unit accessory Dimensions MR-101/Tand MR-201/T 3.0 H x 2.125 W x 1.5 D in(76 H x 54 W x 38 D mm) MR-104/T and MR-204/T 3.OHx8.5Wx1.5Din(76Hx216Wx38Dmm) MR 101/C and MR- 6.125 H x 3.25 W x 2.5 D in(156mm H x 83mm W x 64 D mm) 201/C- _- MR 104/C and MR- -6,125 H x 9.5 W x 2.5 D in(156 H x 241 Wx64Dmm) 204/C Ordering Information Model Description MR-101/T Single SPDT relay with LED and track mounting hardware MR-101/Cm Single SPDT relay with LED mounted in metal enclosure MR-104/T Four-position SPDT relay with LEDs and track mounting hardware MR-104/C Four-position SPDT relay with LEDs mounted in metal enclosure MR-201/T Single DPDT relay with LED and track mounting hardware MR-201/CSingle DPDT relay with LED mounted in metal enclosure MR-204/T Four-position DPDT realy with LEDs and track mounting hardware MR-204/C Four-position DPDT relay with LEDs mounted in metal enclosure Page 2 of 2 270062 Issue 1.1 INTELLIKNIGHT ACCESSORY 44 SILENT `� SK-Heat, SK-Heat-HT KNIGHT and SK-Heat-ROR by Honeywell Addressable Thermal Heat and Rate-of-Rise Detectors The SK-Heat, SK-Heat-HT, and SK-Heat-ROR are plug in thermal detectors, with integral communication, that provide features that surpass conventional detectors. These thermal detectors are for use with Silent Knight IntelliKnight series Fire Alarm Control Panels (FACPs). IntelliKnight heat detectors are an essential component in virtually any IntelliKnight installation. The IntelliKnight panel recognizes each detector by its specific address, so precious seconds are not wasted in determining location of an alarm. Description visibility SK-Heat, SK-Heat-HT and SK- • Detector transmits signal to ,„ Heat-ROR are intelligent sensors indicate maintenance is required <<� that utilize a state-of-the art • Plug-in mounting provides ease -, thermistor sensing circuit for fast of installation response. Sensitivity is • Optional remote LED annunciator continuously monitored and (System Sensor® PN RA100Z) reported to the FACP. Point ID capability allows each detector's • Tamper-proof feature available on address to be set with rotary mounting bases address switches, providing exact • Rotary address switches for fast SK-Heat (base included) detector locations for selective installation SK-Heat-HT: High temperature heat maintenance when chamber • UL Listed sensor 135°F - 190°F (57°C - 88°C) contamination reaches unacceptable levels. Specifications SK-Heat-ROR: Rate-of-rise SK-Heat is a fixed temperature Physical detection 15°F/min (8.3°C/min) sensor that uses a thermistor Height: 2.0" (51 mm) Compatibility sensing circuit to produce 135°F Diameter: 6.1" (155 mm) installed (57°C) fixed temperature alarm. in B210LP base The SK-Heat-HT and SK-Heat- Shipping Weight: 4.8 oz (137 g) ROR are compatible with the SK-Heat-HT is a variable high following IntelliKnight FACP's: temperature detector that provides Electrical high temperature detection at Operating Voltage: 5820XL 135°F - 190°F. (57°C - 88°C) 15 to 32 Volts DC Peak 5808 SK-Heat-ROR is a rate-of-rise Standby Current: 5700 temperature sensor with 135°F 300pA @ 24 VDC The SK-Heat is compatible with the (57°C) fixed temperature alarm. LED Current: 6.5 mA@ 24 VDC following IntelliKnight FACP's: Features Environmental 5820XL 5808 • Reliable analog communications Operating Temperature 5700 for trouble-free operation SK-Heat & SK-Heat-ROR: 5600 (Rev 2.0 or higher) -4°— 100°F (-20°C— 38°C) • Age resistant polymer housing The SK-Heat, SK-Heat-HT and SK- • Innovative thermistor sensing SK-Heat-HT: -4°— 150°F Heat-ROR are compatible with the circuit (-20°C— 66°C) following detector bases: • Superior EMI resistance for Humidity: 10% — 93% B210LP 6" base (included) reliability noncondensing B501 2 wire base • Variety of mounting options to Thermal Ratings 822481 Isolator base meet any application SK-Heat: Fixed temperature alarm B224RB Relay base B200SR Sounder base • Dual LED indicators for 360° 135°F (57°C) INTELLIKNIGHT ACCESSORY • Model SK-Heat, SK-Heat-HT, SK-Heat ROR Addressable Thermal and Rate-of-Rise Thermal Detectors Engineering Specifications The contractor shall furnish and install where indicated on the plans, Intelligent Thermal Sensor Silent Knight Model SK-Heat, SK-Heat-HT or SK-Heat-ROR. The base included shall be B210LP. The Heat detector shall have a flashing status LED for visual supervision. When the detector is activated, the flashing LED will latch on steady at full brilliance. The detector may be reset by actuating the control panel reset switch. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field removable when not required.Voltage and RF/transient suppression techniques shall be employed to minimize false alarm potential. SLC IN OUT nbt XI gi j Compatible FACP Ca VII CZ.2 RA100Z(Optional) IIIIIIIIIIIIIIMRIMM 1 J 7--iiiN ��J `f% ' .• ;1111111111111P" \milli rte— �,,0 „del, ‘66-----/ I, Class A Optional Wiring / Wiring SK-Series Detector Mounting Bases Accessories M02-09-00-Test Magnet with Telescoping Handle. RA100Z-Remote LED Annunciator. XP-4-Extension Pole for XR2B. Extends from 5—15 ft. RMK400-Recessed Mounting Kit. Provides low profile for use with T55-127-000 Detector Removal Head. 8501. XR2B-Detector Removal Tool.A removal and re-placement tool BCK-200B Black Detector Kit. For SK-series detectors. for SK plug-in detectors. Includes the T55-127-000. *Unless otherwise noted,specifications apply to all SK thermal M02-04-01 -Replacement Test Magnet. detectors. SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA NOftkeep our product information up-to-date and accurate.We cannot cover all KNIGHT specific applications or anticipate all requirements.All specifications are subject FORM#350120 Rev. D1 to change without notice. For more information,contact Silent Knight 12 ©2013 Honeywell International Inc. by Honeywell Clintonville Road Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. For Technical Support call 800-446-6444. www.silentknight.com INTELLIKNIGHT ACCESSORY SILENT SK-ISO KNIGHT 00 Intelligent Fault Isolator Module by Honeywell The SK-ISO Isolator Module enable part of a communication loop to continue operating when a short circuit occurs on it. If a short occurs between any two isolators, then both isolators immediately switch to an open circuit state and isolate the device between them. For more information about the IntelliKnight system, or to locate you nearest source, please call 800-328-0103. Description The SK-ISO is an addressable line isolator module for use with Silent Knight IntelliKnight series fire alarm control panels (FACPs). rss The SK-ISO acts as an automatic switch that opens when O the line voltage on the signaling line circuipt (SLC) loop drops below four volts. Isolator modules should be spaced between groups of sensors or modules in a looptp o protect the rest of the loop. If a short occurs between any two isolators, then both isolators immediately switch to an � y open circuit state and isolate the devices between them. The remaining units on the SLC loop continue to fully operate. No more than 25 devices are recommended for TM' each group. Features SK-ISO • Panel controlled status LED that flashes green in normal state and is solid red in alarm Compatibility The SK-ISO is compatible with the following • Isolates short circuits on an SLC loop IntelliKnight Systems: 5700 • Protects the modules on the SLC loop so other devices 5808 continue to operate 5820XL 5820XL-EVS • Standard 4 inch electrical box mounting SK-FFT • SEMS screws for easy wiring • UL Listed Installation The SK-ISO mounts directly into a 4" square electrical box. The box must have a minimum depth of 2-1/8".A surface mount electrical box (System Sensor® PN SMB500) is available from Silent Knight. INTELLIKNIGHT ACCESSORY Model SK-ISO Intelligent Isolator Module SK-ISO Isolator Module SK-ISO Isolator Module din 0 J (-) Isolated Devices 1(-) 2(+) 2(+) 3(-) • —1(-) f--1(-) 31) 4(+) • —2(+) _I_2(+) 4(+) . ( 11; 4Ip pip r I ark l / Isolated + E91 Groups of Devices are Separated by SK-ISO Isolator Modules. Devices IN – [ Any Combination of Compatible Listed Devices May Be SLC + Mixed Within a Group. 1(-) OUT ..n_ 2(+) jab _1(-) A Pair of SK-ISO Isolator Modules Will Disconnect a 2(+) Compatible FACP Group of Devices if a Short Circuit Occurs on the Signaling Line Circuit Within that Group. SK-ISO Isolator Module SK-ISO Isolator Module 0 10(1 din CID 1(-) Isolated Devices 2(+) 2(+) 4(+) s. _2( +) —2(+) 4(+) • a 1 Wiring SK-ISO Modules Specifications Fault Detection Delay: 250 ms min. Physical Fault Detection Threshold: 4V Height: 4.5" (11.4 cm) Line Restoration Threshold: 7V Width: 4" (10.2 cm) Environmental Depth: 0.25" (0.6 cm) Operating Temperature: 32°F— 120°F (0°C —49°C) Shipping Weight: 6.3 oz (196 g) Humidity: 10% —93% non-condensing Electrical Accessories Operating Voltage: 15 — 32 VDC SMB500 4" Square Surface Mount Electrical Box Standby Current: 450 IIA max (not isolating; relay closed) Isolation Current: 5 mA max SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA KNIGHT to keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All FORM#350134 Rev D specifications are subject to change without notice. For more information, ©2013 Honeywell International Inc. by Honeywell contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. For Technical Support, Please call 800-446-6444. www.silentknight.com INTELLIKNIGHT ACCESSORY SILENT SK-Monitor KNIGHT by Honeywell Intelligent Monitor Module The SK-Monitor module provides an interface to contact devices, such as security contacts, waterflow switches, or pull stations. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Monitor is an addressable monitor module for use with Silent Knight IntelliKnight series fire alarm control panels (FACPs). The SK-Monitor is intended for use in intelligent, two-wire systems, where individual address of each module is selected using the built-in rotary switches. The SK Monitor supports Class A supervised or Class B \ ` supervised wiring to the load device. Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions. Features • Single contact monitor • Support for Class A and Class B wiring • Fully supervised • Panel controlled status LED that flashes green in normal state and is solid red in alarm • Attractive ivory cover plate SK-Monitor • Rotary address switches for fast installation • SEMS screws for easy wiring Specifications • UL Listed Physical Installation Height: 4.5" (11.4 cm) The SK-Monitor mounts directly into a 4" square electrical Width: 4" (10.2 cm) box. The box must have a minimum depth of 2-1/8". A Depth: 1.25" (3 cm) surface mount electrical box (System Sensor® PN Shipping Weight: 6.3 oz (196 g) SMB500) is available from Silent Knight. Electrical Compatibility Operating Voltage: 15 — 32 VDC The SK-Monitor is compatible with the following Current Draw (LED on): 5.0 mA max IntelliKnight FACP's: Operating Current (LED flashing): 375 pA 5700 5808 5820XL INTELLIKNIGHT ACCESSORY Model SK-Monitor Intelligent Monitor Module TO NEXT - . r---" FROM RAVEL OR DE9 ICE t € �,� 4 PREMOUS DEVICE. Licauroe ANY NUMBER CF LLUBTEDCONTACT MI MODULEMk $� CLOSURE:DEVICES MAY EE USED.DO NOT AIX, , . .�- ^ kX CONNECT MOOLLESTO LETIED C€ MIELE FRE ALARM INTIATNO,SLPEF IECRY,CO ed t Ck ib Q I CONTROL PANELS ONLY EECLRlTYDE4ICESONTHESAME MODULE k I ' n ` _ N ' / I . 47X En LT T9k'vR1AL LINE CRCU r(9L€ RESISTOR — I S2 WIC MAX ELR-4M I,. MR TWISTED PAIR A 19 FEIC'OMENDE0 999 NrFLkTWO DEVICE CRCJrr(IOC)-NFPA STYLE e POMEFI UIIITED:4EDIA MAX.O 11 VDC WAX INSTALL CONTACT CLOSURE DEVICES PER ALL WRING MOWN I9 SLFERVIEED AM]POWER MIMED YANL ACTIJFER'9INBTALLATK7N NBTRUCTICN9. 2-Wire Initiating Circuit Configuration, NFPA Style B TO NEXT FROM PANEL OR DEVICE 4e.IIIII.w IMP ii.Al. +I.IE.41, s'1111.Ir O.A 411. ` PREVIOUS DEVICE MONITOR !` #ANY NUMBER OF UL LIB t ED CONTACT MODULE T T Fl.CLOSURE DEVICES MAY BE USED.DO NOT MIX CONNECT MODULES TO LISTED COMPATIBLE RRE ALARM INTIATINO,SUPERVISORY,OR O Cb • # NOTIFIER CONTROL PANELS ONLY SECURITY DEVICES ON THE SAME MODULE t • i 0 ii 0 r----Th LINE GIR,CU TJALSA A. 82 VDC MAC: EOL RESISTOR IS me a aw I SHIELDED-TWISTED PAIR INTERNAL AT — — I IS RECOMENDED TERMINALS 9&9 I L1 INSTALL CONTACT CLOSURE DEVICES PER ALLWIRING SHOWN IS SUPERVISED AND POWER LIMITED MANUFACTURER'S INSTALLATION INSTRUCTIONS, 4-Wire Initiating Circuit Configuration, NFPA Style D Standby Current: Environmental 400 pA max @ 24 VDC (one communication every 5 sec Operating Temperature: 32°F— 120°F (0°C—49°C) with 47K EOL) Humidity: 10%—93% non-condensing 550 pA max @ 24 VDC (one communication every 5 sec with EOL<1K) 5.5 mA(with LED latched on) 4,. Ordering Information SK-Monitor Monitoring Module LED Current: 5.5 mA(with LED latched on)End-of-Line Resistance: 47K 12 Accessories Initiating Device Circuit Wiring Resistance: 1,500 S2 max SMB500 4" Square Surface Mount Electrical SLC Loop Resistance: 40 S2 max. Box SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA 1011 KNIGHT keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are FORM#350131 Rev C subject to change without notice. For more information,contact Silent Knight ©2012 Honeywell International Inc. by Honeywell 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY tSILENT SK-Monitor-2 ill I KNIGHT by Honeywell Intelligent Dual Monitor Module The SK-Monitor-2 module is capable of monitoring two separate Class B circuits simultaneously, making it ideal for waterflow tamper switch and flow switch monitoring. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Monitor-2 is an addressable monitor module with two initiating circuits for use with Silent Knight IntelliKnight series fire alarm R \ control panels (FACPs). The SK-Monitor-2 acts as an interface to contact devices, such as waterflow switches and pull stations. sir The SK-Monitor-2 supports Class B supervised wiring to the load device. Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions. SK-Monitor-2 Installation Features SK-Monitor-2 mounts directly into a 4" • Monitor two circuits, with unique addresses, square electrical box. The box must have simultaneously a minimum depth of 2-1/8". A surface • Support for Class B wiring mount electrical box (System Sensor® • Fully supervised part number SMB500) is available from • Panel controlled status LED that flashes green Silent Knight. in normal state and is solid red in alarm Compatibility • Attractive ivory cover plate The SK-Monitor-2 is compatible with the • Rotary address switches for fast installation following IntelliKnight FACP's: • SEMS screws for easy wiring 5700 • UL Listed 5808 5820XL INTELLIKNIGHT ACCESSORY • Model SK-Monitor-2 Intelligent Dual Monitor Module To Next Device + 4 n n = 0 O o Ta €T. till At T7 i inn.; . • e• • BOOP ••II... ••.••�� a O a O 0. Compatible FACP U U Two Initiating Device Circuits NFPA Style B Power Limited 230 pA Max @ 12 VDC Max Fl n _ SLC 7OUT IN4. i o oICI /i ,,OUT, Ys.' a Ii r Te 14\Vit + ;,Te.,•. •.,.. ma (� ,MI s:6t� OF O ma0 O 791 U U Wiring SK-Monitor-2 Modules Specifications End-of-Line Resistance: 47K 0 Physical Max IDC wiring resistance: 1,50052 Height: 4.5" H x 4"W x 1.25" D SLC Line Loop Resistance: 4052 max. Shipping Weight: 6.3 oz (196 g) Environmental Electrical Operating Temperature: 32°F— 120°F (0°C—49°C) Operating Voltage: 15—32 VDC Humidity: 10%—93% non-condensing Current Draw(LED on): 6.4 mA max Accessories Operating Current(LED flashing): 750 pA SMB500 4" Square Surface Mount Electrical Box This document is not intended to be used for installation purposes.We try MADE IN AMERICA SILENTNI it to keep our product information up-to-date and accurate.We cannot cover KNIGH all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent FORM#350124 Rev B Knight 12 Clintonville Road, Northford,CT 06472-1610 ©2009 Honeywell International Inc. by Honeywell Phone:(800)328-0103, Fax: (203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY SK-Photo and SK-Photo-T Intelligent Photoelectric Smoke Sensors The SK-Photo is a photoelectric smoke detector and the SK-Photo-T is a photoelectric smoke detector with thermal. These plug in smoke detectors, with integral communication, provide features that surpass conventional detectors and are for use with Silent Knight IntelliKnight Fire Alarm Control Panels (FACPs). For more information about the IntelliKnight system, or to locate your nearest source, please call 800-328-0103 or in Connecticut, call (203) 484-7161. Description • Plug-in mounting provides ease of SK-Photo and SK-Photo-T are plug-in installation type smoke sensors that combine a • Tamper-proof feature available on photoelectric sensing chamber with mounting bases addressable analog communications. • Listed for use in duct applications Point ID capability allows each detector's address to be set with rotary • Rotary address switches for fast installation address switches, providing exact , detector locations for selective • UL Listed maintenance when chamber • contamination reaches unacceptable FM Approved levels. Specifications SK-Photo and SK-Photo-T have a Physical unique optical sensing chamber that is Height: 2.0" (5.0 cm) engineered to sense smoke produced Diameter: 4.1" (10.4 cm) by a wide range of combustion sources. In the SK-Photo-T, dual Shipping Weight: 5.2 oz. (147 g) SK-Photo (Base included) electronic thermistors add 135°F (57°C) Electrical Compatibility thermal technology to maximize Operating Voltage: 15-32 VDC detection. Standby Current: The SK-Photo and SK-Photo-T are compatible with the following Features 300 pA @ 24 VDC Maximum IntelliKnight FACPs: • Sleek, low-profile design Alarm Current: 6.5 mA @ 24 VDC max 5700 • Base included (with LED on) 5808 Environmental 5820XL • Reliable analog communications for Operating Temperature trouble-free operation p g p SK Photo and SK Photo T are SK-Photo: 32°— 120°F (0°C—49°C) compatible with the following detector • Age resistant polymer housing SK-Photo-T: 32°— 100°F (0°C—38°C) bases: • Dual electronic thermistor design on Humidity: 10%—93% non condensing B210LP (included) 6" base the SK-Photo-T B501 2 wire base • Superior EMI resistance for reliability Other Ratings B501 BHT-2 Temporal base SK-Photo-T Thermal: Fixed B224RB Relay base • Simple field cleaning for code temperature set point 135°F (57°C) B224B1 Isolator base compliance Velocity: 0—4000 fpm (0—20 m/sec) B501 BH-2 Sounder base • Variety of mounting options to meet SK-Photo Insect Screen Hole Size: any application 0.016" (0.41 mm) nominal • Dual LED indicators for 360°visibility SILENT • Detector transmits signal to indicate KNIGHT maintenance is required • Optional remote LED annunciator 'Honeywei (System Sensor® PN RA100Z) INTELLIKNIGHT ACCESSORY Model SK-Photo and SK-Photo-T Intelligent Photoelectric Smoke i 4:11 Sensors : . t ( Engineering Specifications The contractor shall furnish and install where indicated on the plans, Intelligent photoelectric smoke sensors Silent Knight SK-Photo or SK-Photo-T with thermal. The combination detector head, and twist-lock base, shall be UL listed and compatible with Silent Knight's IntelliKnight fire control panels. The base shall permit direct interchange with SK-Photo or SK-Photo-T. Base shall be the appropriate twist-lock base part number B210LP (included). The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SK-Photo shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. C M Kate t, I olioriot..1\ i ! Ifr+> , c141114401 \\\:,„, ,/ 7 / 1 if �aim 014110.� �•• t 011 �!' l://1 s s M Waring K4e0-10.5 D4 or talowvting c f SILENTNI ICN IG HT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA keep our dWe specific applicationsproductinformation or anticipateup-to-all requirements.ateand Allaccurate.specificationscannotcover are subject FORM#350118 Rev A, to change without notice. For more information,contact Silent Knight 12 ©2009 Honeywell International Inc. by Honeywed Clintonville Road, Northford,CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY • SILENT SK-Pull-SA and SK-Pull-DA 1101 KNIGHT Intelligent Pull Stations by Honeywell The SK-Pull-SA and SK-Pull-DA are a single action or dual action addressable fire alarm pull station for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SK-Pull-DA and SK-Pull-SA provide a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Pull-SA is a single action pull station requiring only one motion to activate the station. The SK-Pull-DA is a dual action pull station requiring two motions to active the station. Both pull stations are designed to work with Silent KnightI PULL DOWN Ir Intelliknight series fire alarm control panels (FACPs). Features • Installer can open station without causing an alarm condition SILENT {T; \ ) 64f^P:ttryal • Dual-color LED is visible through handle of station blinks a green to indicate normal operation and remains steady red in an alarm condition SK-Pull-SA • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP locks FI • Meets the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls and operating mechanisms ( PUSH IN guidelines (Section 4.1.3[13]) *PULL • Meets ADA requirement for 5 lbs maximum pull force to active • Shell, door, and handle molded from durable LEXAN® �SK;, • Reliable analog communications for trouble-free operation • Braille text on station handle SK-Pull-DA • Handle latches in down position and the word Activated Compatibility appears, clearly indicating the station has been pulled The SK-Pull-SA and SK-Pull-DA are compatible • Rotary address switches for fast installation with the following IntelliKnight FACP's: 5600 • UL Listed, including UL 38, Standard of Manually Actuated 5700 Signaling System 5808 5820XL INTELLIKNIGHT ACCESSORY Model SK-Pull-DA and SK-Pull-SA Intelligent Pull Stations Engineering Specifications The contractor shall furnish and install where indicated on the plans,Addressable Pull Stations, Silent Knight model SK-Pull-SA single action pull station or SK-Pull-DA, dual action pull station. SK-Pull-DA or SK-Pull-SA meet the ADAAG controls and operating mechanisms guidelines, and the ADA requirements for a 5 lb. maximum pull force to activate the pull station. t Class A !N 1,1 — SLC t OUT ' Class B Compatible FACP 11 1 3 . t 1 r ���=e p's IL . . . 1 1 I 1 1 t. N P i I' Class A Wiring: ------- Class B Wiring: Wiring SK-Pull-SA&SK-Pull-DA Pull Stations Specifications Electrical Physical Operating Voltage: 15-32 VDC Height: 5.5" (14 cm) Average Operating Current (LED flashing): 300 pA Width: 4" (10.2 cm) Wire Gauge: Up to 12 AWG (3.1 mm2) Depth: 5.4 oz. (3.7 cm) Environmental Housing Material: LEXAN polycarbonate resin Operating Temperature 32°— 120°F (0°C—49°C) Bi-Colored LED: Humidity: 10%—93% non-condensing Blinking Green: Normal Steady Red:Alarm Accessories Switch: Single pole, single throw(SPST) normally open (N/O) BG-TR Optional trim ring. switch which closes upon activation of the pull station SB-I/O Surface backbox SILENTN ith This document is not intended to be used for installation purposes. We try MADE IN AMERICA to keep our product information up-to-date and accurate.We cannot cover KNIGHT all specific applications or anticipate all requirements.All specifications are FORM#350135 Rev B subject to change without notice. For more information, contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 ©2012 Honeywell International Inc. by Honeywell Phone: (800)328-0103, Fax: (203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY SK-Relay Intelligent Relay Module The SK-Relay Module is intended for use in intelligent, two-wire systems where the individual address of each module is selected using the built in rotary switches. For more information about the Intelliknight system, or to locate you nearest source, please call 800-328-0103 or in Connecticut, call (203) 484-7161. Description The SK-Relay is an addressable relay module for use with Silent Knight IntelliKnight series fire alarm control panels (FACPs). \\ The SK-Relay allows a Silent Knight FACP to switch discrete contacts by code command. The relay contains two isolated sets of Form C contacts, which operate as a DPDT switch. No supervision is provided for the notification appliance circuit. The SK-Relay contacts can be used for virtually any normally .r open or normally closed application. Each SK-Relay is programmed with a unique signaling line circuit (SLC) loop address. When an event occurs that controls the SK-Relay, the SK-Relay relay is triggered by the FACP. Installation The SK-Relay mounts directly into a 4" square Features electrical box. The box must have a minimum • Two sets of Form C contacts depth of 2-1/8".A surface mount electrical box • Rotary address switches for fast installation (System Sensor® PN SMB500) is available • Contacts are rated for a variety of amps (see Specifications) from Silent Knight • Panel controlled status LED that flashes green in normal state and is solid red in alarm Compatibility The SK-Relay is compatible with the following • Relay programming is completely flexible—can be mapped to IntelliKnight FACP's: zone conditions 5700 5808 • Polling LED visible through the cover plate 5820XL • Attractive ivory cover plate SILEN • SEMS screws for easy wiring T • UL Listed KNIGHT by Honeywell INTELLIKNIGHT ACCESSORY Model SK-Relay iiX To Next Device i If Any Wiring to Terminals 3=9 is Not Power + 4 Limited,the CB500 Barrier is Required.The CB50O Includes a Non-Power Limited Label, (-"l f-1 Which Must Be Placed Over the Power Limited [ Jo o , , Terminal information on the Name Plate Label, Relay Common 2 ** 0.. 0 IIIII, Normally Closed 2 rf t, 44 1 IV- Normally Open 2 ' `r ,'• 2 14,1, Relay Common 1 a t,* From Compatible FACP .i + or Previous Device Normally Closed 1 s . . 4 Module Does Not Supervise "' zzt 6 Normally Open t Controlled Circuits ) 19 U U E Wiring theSK-Relay Module Specifications End-of-Line Resistance: not used Physical Standby Current: 300 pA max @ 24 VDC (one Height: 4.65" communication every 5 sec with LED enabled) Width: 4.25" LED Current: 5.5 mA(with LED latched on) Depth: 1.1" SLC Loop Resistance: 4052 max. Shipping Weight: 6.3 oz (196 g) Relay Contact Ratings 3.0A @ 30 VDC resistive Electrical Operating Voltage: 15—32 VDC 0.9A @ 110 VDC resistive Current Draw: 6.5 mA max (LED on) 0.9A @ 125 VAC resistive Operating Current: 0.5A @ 125 VAC inductive (PF = .35) 230 pA(LED flashing)direct poll 0.7A @ 75 VAC inductive (PF = .35) 255 pA(LED flashing)group poll SILENTThis document is not intended to be used for installation purposes.We try to MADE IN AMERICA keep our product information up-to-date and accurate.We cannot cover all NI KNIGHT" specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent Knight FORM#350127 Rev A by Honeywell 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, ©2009 Honeywell International Inc. Fax:(203)484-7118. www.silentknight.com • NOTIFICATION DEVICES • SYSTFAI4A1 SENsoR , F Indoor Selectable- + ,A ` Output Speaker �•i ` `.:.• Strobes and Dual "{,.i`:'P. .•i { _ • ,si,Pi i••#R:i� ♦lis Mls tis l� � ��yx� i.{ ,Pa•{iii {+• �� P Voltage Evacuation ` " •.bilii {� ata s • i {i� •+i Speakers for Ceiling Applications SpectrAlert Advance selectable-output speaker strobes and dual-voltage evacuation speakers can reduce ground SPECT faults and enable faster installation. f r oro S . 'S e Features The SpectrAlert Advance Series of speakers and speaker • Plug-in design and protective cover reduce ground faults strobes reduce costly ground faults using a plug-in design and universal mounting plate that allow the installer to pre-wire mounting • Universal mounting plate with an onboard shorting spring tests plates,dress the wires,and confirm wiring continuity before plugging wiring continuity before installation in the speakers. In addition,a protective plastic cover prevents • No extension ring required nicked wires by covering exposed speaker components. • Field selectable candela settings: Standard: 15, 15/75,30, 75,95, 110, 115 These devices also enable faster installations by providing instant High: 135, 150, 177, 185 feedback to ensure that wiring is properly connected,rotary switches to select voltage and power settings,and 11 field-selectable candela • Automatic selection of 12-or 24-volt operation at 15 and settings for both wall and ceiling speaker strobes. 15/75 candela • Rotary switch simplifies field selection of speaker voltage(25 The low total harmonic distortion of the SP speaker offers high fidelity and 70.7 Vrms)and power settings(1/4,1/2, 1 and 2 watts) sound output while the SPV speaker offers high volume sound output • SP speakers offer high fidelity sound output for use in high ambient noise applications. • SPV speakers offer high volume sound output SpectrAlert Advance makes installation easy • Compatible with System Sensor synchronization protocol •Attach a universal mounting plate to a 4 x 4 x 21/8 inch back box. • Electrical compatibility with existing SpectrAlert products Flush mount applications do not require an extension ring. •Connect the notification appliance circuit or speaker wiring to the • Tamper-resistant construction terminals on the mounting plate. • Listed for ceiling or wall mounting •Attach the speaker or speaker strobe to the mounting plate by inserting the product tabs into the mounting plate grooves.Hinge the device into position to lock the product pins into the mounting plate terminals.The device will temporarily hold in place with a catch until it is secured with a captured mounting screw. Agency Listings SIGNALING u� ��� ® MEA Nall .„nc,„„ approved 54048 7320-1653:201 10-08-E SpectrAlert Advance Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications t mak;, „ General SpectrAlert Advance speaker and speaker strobes shall mount to a 4 x 4 x 21/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate.Also, SpectrAlert Advance speaker strobes,when used with the Sync•CircuitTM Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32°F and 120°F from a regulated DC,or full-wave rectified, unfiltered power supply.Speaker strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110, 115, 135, 150, 177, 185. Speaker The speaker shall be a System Sensor SpectrAlert Advance model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service.The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F.The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor SpectrAlert Advance model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems.The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch,and shall have a frequency range of 400 to 4,000 Hz.The speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical Specifications,,.„ Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Dimensions,Ceiling-Mount Diameter Depth SPC Speaker 6.8 in, 173 mm 2.8 in,71 mm SPCV Speaker 6.8 in, 173 mm 2.9 in,74 mm With Surface Mount Back Box 6.9 in, 175 mm 3.4 in,86 mm SPSC Speaker Strobe 6.8 in, 173 mm 2.8 in,71 mm SPSCV Speaker Strobe 6.8 in, 173 mm 2.9 in,74 mm With Surface Mount Back Box 6.9 in, 175 mm 5.325 in, 135 mm Electrical/Operating Specifications \�\ Nominal Voltage(speakers) 25 Volts or 70.7 Volts (nominal) Maximum Supervisory Voltage(speakers) 50 VDC Strobe-Flash Rate 1 flash per second Nominal Voltage(strobes) Regulated 12 V DC/FWR or regulated 24 DC/FWR Operating Voltage Range(includes fire 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) alarm panels with built in sync) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33 V(24 V nominal) Frequency Range 400 to 4,000 Hz Power 1/4,1/2, 1,2 watts UL Current Draw Data it.Max.Strobe Cunent Draw(rnA RMS • 8 to 17.5 Volts 16 to 33 Volts Candela DC FWR DC FWR Standard 15 123 128 66 71 Candela Range 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High 135 NA NA 228 207 Candela Range 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 Sound Output UL Reverberant(dBA @ 10 ft.) 2W 1W 1/2W ¼W Ceiling-Mount SPC Series 86 83 80 77 Ceiling-Mount SPCV Series 90 87 84 81 Ceiling-Mount SPSC Series 85 82 79 76 Ceiling-Mount SPSCV Series 89 86 83 80 Dimensions 6.81 " r.971-1.96=- 6.81 " - [97-i--1.841- ooStVilliiiieSt% Atal'AMAgAlga 86TaViA46°?404'0000A IN. eltsisvocsszoo.ssA ill. :,,,quilitititichai.iciter 1 1 „III i010:400110i0e..08:0:0100080.10,00":730t, . Iiiill ____: c.o. . 00 00°00:.°78' SiggeeelloggiVoctc? -,- '°809fecfeecl @go° 000.:40.77//////// 0 000°800o:0g 0.0 0000.0 0 00 0 0.0000%. \c:Flicactagg° \048.000A00 0.0.00000 ,c'edie700::: 0 0 Ceiling-Mount SPV Speaker Ceiling-Mount SP Speaker 2.83" 6.81" - 1.60'1 1.84 c?Iffiff:0°144°Z°030eiZ•01 .0700§ta : oh _ , ' kik I iiiP ...0.0 III[15 :.. :Jail , __. 0, vs:35;k° scoop ( lI 014,17A051); () Ceiling-Mount SPS Speaker Strobe Surface Mounting iii, � '\ °°°°° �m .,____ ()/, moo()°00000000i° moo '°o°o°oo°o°e??,, r°° _ , Illi °o &:; pI: .,.,1 10- 1 +-ri---- 4,L � / ,, 0 , � n�i�i / °0000aao Ceiling-Mount Speaker with SBBCR/SBBCW Surface Mount Back Box Skirt Ordering Information for SpectrAlert®Advance Speakers and Speaker Strobes Ceiling Mount ..: '-' White Red Description SPCW SPCR Speaker only SPCWV SPCRV Speaker only, High dB SPSCW SPSCR Speaker Strobe,Standard cd SPSCW-P Plain Speaker Strobe,Standard cd SPSCWH SPSCRH Speaker Strobe,High cd SPSCWH-P — Plain Speaker Strobe, High cd SPSCWV SPSCRV Speaker Strobe,Standard cd,High dB SPSCWV-P — Plain Speaker Strobe, High Volume,Clear Lens,White SPSCWVH SPSCRVH Speaker Strobe, High cd,High dB SPSCW-CLR-ALERT — Speaker Strobe, Standard cd,Clear Lens Accessories White Red Description RFPW RFP 7 in x 9.5 in Retrofit Plate SBBCW SBBCR Surface Mount Back Box TRCW TRC Ceiling Mount Trim Ring Notes: All-P models have a plain housing(no"FIRE"marking on cover) "Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings. "High cd"refers to strobes that include 135,150, 177,and 185 candela settings. 3825 Ohio Avenue•St.Charles, IL 60174 ©2o,ssystemsenser /•� Phone:800-SENSOR2• Fax:630-377-6495 Product specifications subject to change without ntice.visit systemsensorcom �`/ for current product IntoreJili'including the latest version st this data sheet. W Ww.systemsenSOLCom AVDS1 t tot•2/t 5 1 W"41 ---'\\ i _ : ...V SENSO '' ' ........ Selectable-Output Horns, Strobes, and ;� 11 Horn Strobes ( SpectrAlert'Advance selectable-output horns,strobes, ., and horn strobes are rich with features guaranteed to cut installation times and maximize profits. SPECT"v' - it Features The SpectrAlert Advance series offers the most versatile and •Plug-in design with minimal intrusion into the back box easy-to-use line of horns,strobes,and horn strobes in the industry. With white and red plastic housings,wall and ceiling mounting •Tamper-resistant construction options,and plain and FIRE-printed devices,SpectrAlert Advance can •Automatic selection of 12-or 24-volt operation at 15 and 15/75 meet virtually any application requirement. candela •Field-selectable candela settings on wall and ceiling units:15,15/75, Like the entire SpectrAlert Advance product line,horns,strobes, 30,75,95,110,115,135,150,177,and 185 and horn strobes include a variety of features that increase their •Horn rated at 88+dBA at 16 volts application versatility while simplifying installation.All devices •Rotary switch for horn tone and three volume selections feature plug-in designs with minimal intrusion into the back box,which make installations fast and foolproof while virtually •Universal mounting plate for wall and ceiling units eliminating costly and time-consuming ground faults.Furthermore, •Mounting plate shorting spring checks wiring continuity before a universal mounting plate with an onboard shorting spring tests device installation wiring continuity before the device is installed,protecting devices •Electrically compatible with existing SpectrAlert products from damage. •Compatible with MDL sync module In addition,field-selectable candela settings,automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with three volume selections enables installers to easily adapt devices to suit a wide range of application requirements. Agency Listings SIGNALING O u) ® MEA Niko approved 77,2255-11:5533 125-1653:186(indoor strobes) LISTED APPROVED PP 7125 1653 188(horn strobes, 54011(chimes,horn strobes,horns) 3023572 MEA452-05-E chime strobes) 55512(strobes) 7135-1653:189(horns,chimes) • SpectrAlert Advance Specifications tct/EngineerSpecifications General SpectrAlert Advance horns,strobes,and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box,4-inch octagon back box,or double-gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,SpectrAlert Advance products,when used with the Sync•Circuit""Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module,12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts.Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.Strobes and horn strobes shall have field-selectable candela settings including 15,15/75,30, 75,95,110,115,135,150,177,and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service.The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three-pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.On four-wire products,the strobe shall be powered independently of the sounder.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 4"/16 x 411/26 x 21/4-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z (class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR' Operating Voltage Rangel 8 to 17.5 V(12 V nominal)or 16 to 33 V(24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions(including lens) 6.8"diameter x 2.5"high(173 mm diameter x 64 mm high) Wall-Mount Dimensions(including lens) 5.6"L x 4.7"W x 2.5"D(142 mm L x 119 mm W x 64 mm D) Horn Dimensions 5.6"L x 4.7"W x 1.3"D(142 mm Lx 119 mm W x 33 mm D) Wall-Mount Back Box Skirt Dimensions(BBS-2,BBSW-2) 5.9"L x 5.0"W x 2.2"D(151 mm L x 128 mm W x 56 mm D) Ceiling-Mount Back Box Skirt Dimensions(BBSC-2,BBSCW-2) 7.1"diameter x 2.2"high(180 mm diameter x 57 mm high) Wall-Mount Trim Ring Dimensions(sold as a 5 pack)(TR-HS,TRW-HS) 5.7"L x 4.8"W x 0.35"D(145 mm L x 122 mm W x 9 mm D) Ceiling-Mount Trim Ring Dimencinnc(cold •• : -. -. ••"•'••i- • -I "••i n n•iameter x 9 mm high) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source if Id is used on some-power supply and panel outputs. 2.P,5,PC,and SC products will operate at 12 V nominal only for 15 and 15/75 cd. A05-0395-007 UL Current Draw Data : � "• � \\ �, ,,... �� tn.max.Horn„ ..."i 1 i -a .` ..�...,. � a 8-1".5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Carssela FWR DC FWR Sound Pattern d8 DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela Range 15/75 142 148 77 81 Temporal Medium 44 49 58 69 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non-temporal High 57 56 69 75 95 NA NA 181 176 Non-temporal Medium 42 50 60 69 110 NA NA 202 195 Non-temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 Nigh 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela Range 150 NA NA 246 220 Coded Low 40 46 52 50 177 NA NA 281 251 185 NA NA 286 258 teerre 1 Horn Stro rdCa Candela Range(15-115 cd). \. a. < 8 7,"Volts 16_.33 Volts DClnput 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non Temporal Low 132 154 80 90 105 161 184 202 211 UL Max.Current Draw(mA RMS), ' ,igh Gan 16-33 Volts 16-33 Volts DClnput 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non Temporal Low 214 229 256 262 Horn Tones and Sound Output Data Horn and3 299 Output u 8-17.5 16-33 24-Volt Nominal Switch Volts Volts Reverberant Anechoic Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non-Temporal High 82 82 88 88 93 92 100 100 5 Non-Temporal Medium 78 78 85 85 90 90 98 98 6 Non Temporal Low 75 75 81 81 88 84 96 92 7t Coded High 82 82 88 88 93 92 101 101 8t Coded Medium 78 78 85 85 90 90 97 98 9t Coded Low 75 75 81 81 88 85 96 92 tSettings 7,8,and 9 are not available on 2-wire horn strobe. A05-0395-007 SpectrAlert Advance Dimensions � 4.T' 2.5� r)h Dia. "D‘.' 15'7 . *4- 111 1 .` Wad-mount horn strobes Ceiling-mount horn strobes 7.1" 1�2. 5"~I r2.23+1 /—� Dia. I C I PPQQD qc 5.98"• c u u oho r Wall back box skirt Ceiling back box skirt SpectrAlert Advance Ordering Information Model Des �� � {� Model Description �� � , N Wall Horn Strobes Ceding Strobes P2R*t 2-Wire Horn Strobe,Standard cd',Red SCR Strobe,Standard cd,Red P2RH* 2-Wire Horn Strobe,High cd,Red SCRH Strobe,High cd,Red P2W* 2-Wire Horn Strobe,Standard cd,White SCW* Strobe,Standard cd,White P2WH* 2-Wire Horn Strobe,High cd,White SCWH Strobe,High cd,White P4R* 4-Wire Horn Strobe,Standard cd,Red Horns P4RH 4-Wire Horn Strobe,High cd,Red HR Horn,Red P4W 4-Wire Horn Strobe,Standard cd,White HW Horn,White Wall Strobes Accessories SR*f Strobe,Standard cd,Red BBS-2 Back Box Skirt,Wall,Red SRH*t Strobe,High cd,Red BBSW-2 Back Box Skirt,Wall,White SW* Strobe,Standard cd,White BBSC-2 Back Box Skirt,Ceiling,Red SWH* Strobe,High cd,White BBSCW-2 Back Box Skirt,Ceiling,White Ceiling Horn Strobes TR-HS Trim Ring,Wall,Red PC2R* 2-Wire Horn Strobe,Standard cd,Red TRW-HS Trim Ring,Wall White PC2RH 2-Wire Horn Strobe,High cd,Red TRC-HS Trim Ring,Ceiling,Red PC2W*t 2-Wire Horn Strobe,Standard cd,White TRCW-HS Trim Ring,Ceiling,White PC2WH* 2-Wire Horn Strobe,High cd,White PC4R 4-Wire Horn Strobe,Standard cd,Red PC4RH 4-Wire Horn Strobe,High cd,Red PC4W 4-Wire Horn Strobe,Standard cd,White Notes: *Add"-P"to model number for plain housing(no"FIRE"marking on cover),e.g.,P2R-P. t Add"-SP"to model number for"FUEGO"marking on cover,e.g.,P2R-SP. #"Standard cd"refers to strobes that include 15,15/75,30,75,95,110,and 115 candela settings."High cd"refers to strobes that include 135,150,177,and 185 candela settings. SYSTEM ®2009 System Sensor. 111 �. / 3825 Ohio Avenue•St.Charles,IL 60174 Produtt specfications subject to change without notice Visit systemsensoccom for Phone:800-SENSOR2•Fax:630-377-6495 current product information,inducing the latest version of this data sheet. A05-0395-007.4/09•#2132 • -Th -'' .." SEN5:1- -,-., Indoor Selectable- Output Speaker Strobes and Dual Voltage Evacuation I Speakers for Wall Applications , The SpectrAlert°Advance selectable output speaker strobes and dual-voltage evacuation speakers can reduce SPECT'IA - rt ground faults and enable faster installation. ' e r `s e ng Features The SpectrAlert Advance Series of speakers and speaker Plug-in design and protective cover reduce ground faults strobes reduce costly ground faults using a plug-in design and • universal mounting plate that allow the installer to pre-wire mounting • Universal mounting plate with an onboard shorting spring tests plates,dress the wires,and confirm wiring continuity before plugging wiring continuity before installation in the speakers. In addition,a protective plastic cover prevents • No extension ring required nicked wires by covering exposed speaker components. • Field selectable candela settings: Standard: 15, 15/75,30,75,95, 110, 115 These devices also enable faster installations by providing instant High: 135, 150, 177, 185 feedback to ensure that wiring is properly connected,rotary switches to select voltage and power settings,and 11 field-selectable candela • Automatic selection of 12-or 24-volt operation at 15 settings for both wall and ceiling speaker strobes. and 15/75 candela • Rotary switch simplifies field selection of speaker voltage The low total harmonic distortion of the SP speaker offers high fidelity (25 and 70.7 Vrms)and power settings(1/4,1/2, 1 and 2 watts) sound output while the SPV speaker offers high volume sound output • SP speakers offer high fidelity sound output for use in high ambient noise applications. • SPV speakers offer high volume sound output SpectrAlert Advance makes installation easy • Compatible with System Sensor synchronization protocol •Attach a universal mounting plate to a 4 x 4 x 21i8 inch back box. • Electrical compatibility with existing SpectrAlert products Flush mount applications do not require an extension ring. •Connect the notification appliance circuit or speaker wiring to the • Tamper-resistant construction terminals on the mounting plate. • Listed for ceiling or wall mounting •Attach the speaker or speaker strobe to the mounting plate by inserting the product tabs into the mounting plate grooves.Hinge the device into position to lock the product pins into the mounting plate terminals.The device will temporarily hold in place with a catch until it is secured with a captured mounting screw. Agency Listings SIGNALING " ® _ LISTED iiiii ® approved 54048 7320-1653:201 10-O8L SpectrAlert Advance Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General SpectrAlert Advance speaker and speaker strobes shall mount to a 4 x 4 x 21/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate.Also, SpectrAlert Advance speaker strobes,when used with the Sync•CircuitTM Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32°F and 120°F from a regulated DC,or full-wave rectified, unfiltered power supply.Speaker strobes shall have field-selectable candela settings including 15, 15/75,30,75,95, 110, 115, 135, 150, 177, 185. Speaker The speaker shall be a System Sensor SpectrAlert Advance model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service.The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F.The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor SpectrAlert Advance model listed to UL1480 and UL 1971 and be approved for fire protective signaling systems.The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch,and shall have a frequency range of 400 to 4,000 Hz.The speaker shall have power taps that are selected by rotary switch.The strobe shall comply with the NFPA 72 requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1 Hz.The module shall mount to a 411/16 x 411/16 x 21/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. . . � . Physical Specifications at � � � Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non- condensing Dimensions,Wall-Mount Length Width Depth SP Speaker 6 in, 152 mm 5 in, 127 mm 2.8 in,71 mm SPV Speaker 6 in, 152 mm 5 in, 127 mm 2.9 in,74 mm With Surface Mount Back Box 6 in, 152 mm 5.1 in, 130 mm 3.4 in,86 mm SPS Speaker/Strobe 6 in, 152 mm 5.1 in, 127 mm 4.7 in, 119 mm (including lens and speaker) With Surface Mount Back Box 6 in, 152 mm 5.1 in, 130 mm 5.325 in, 135 mm Electrical/Operating Specifications .....„�,.. '� � .,.. Nominal Voltage(speakers) 25 Volts or 70.7 Volts (nominal) Maximum Supervisory Voltage(speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage(strobes) Regulated 12 VDC/ FWR or regulated 24 DC/FWR Operating Voltage Range(includes fire 8 to 17.5 V(12 V alarm panels with built in sync) nominal)or 16 to 33V (24 V nominal) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V(12 V nominal)or 16.5 to 33V(24 V nominal) Frequency Range 400 to 4000 Hz Power 1/4,1/2, 1,2 watts UL Current Draw Data Ill..Max.Strobe.Current Draw( ACM ".e 8 to 125 Volts 16 to 33 Volts Candela DC FWR DC FWR Standard 15 123 128 66 71 Candela Range 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High 135 NA NA 228 207 Candela Range 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 Sound Output UL Reverberant(dBA @ 10 ft.) 2W 1W 172W 1 W Wall-Mount SP Series 86 83 80 77 Wall-Mount SPV Series 90 87 84 81 Wall-Mount SPS Series 85 82 79 76 Wall-Mount SPSV Series 89 86 83 80 Dimensions 5.00"" .97----1.84- 5.00"" 2.83" 1 i.1_-.-_- -. --., ,,. ,r =...,.=...,.l,, ,ii__--i_--_ 1 ■�I. ®5.98 591I1P1 IJ o Wall-Mount SP Speaker Wall-Mount SPS Speaker Strobe I Surface Mounting '- R t st--7 Ili 1 rA i'r Llii , .-- ■� - 1 0 _Lit (ii !I , i 01 Ail .'1,-,1,-, ,-1(,(-:.4c,4 1,1 11111..„ ,i, *'..'''__'.7: .7,r----..... Wail-Mount Speaker Strobe with SBBSPR Surface Mount Back Ordering Information for SpectrAlert®Advance Speakers and Speaker Strobes Wall Mount White Red Description SPW SPR Speaker only SPWV SPRV Speaker only,High dB SPSW SPSR Speaker Strobe,Standard cd SPSW-P SPSR-P Plain Speaker Strobe,Standard cd SPSW-ALERT — Speaker Strobe,Standard cd,Amber Lens SPSW-CLR-ALERT — Speaker Strobe,Standard cd,Clear Lens SPSWH SPSRH Speaker Strobe, High cd SPSWH-P — Plain Speaker Strobe, High cd SPSWV SPSRV Speaker Strobe,Standard cd, High dB SPSWV-P SPSRV-P Plain Speaker Strobe,Standard cd, High dB Accessories White Red Description RFPW RFP 7 in x 9.5 in Retrofit Plate SBBSPW SBBSPR Surface Mount Back Box for Speakers and Speaker Strobes TRW TR Wall Mount Trim Ring Notes: All-P models have a plain housing(no"FIRE"marking on the cover) "Standard cd"refers to strobes that include 15,15/75,30,75,95, 110,and 115 candela settings. "High cd"refers to strobes that include 135, 150, 177,and 185 candela settings. *� SYSTEM 3825 Ohio Avenue•St. Charles, IL 60174 ©2015syslemsensor. Phone:800-SENSOR2•Fax: 630-377-6495 pr. Visit systemsensoccom for current product Information,IncWding the latest version o°thls data shoe°. www.systemsensor.com Avos,1602•2115