Loading...
Report (90) • �psao� S- oc>�-� � ‘caao nLl 1'4i A LC • • SEP 1 72018 • • MATERIAL SUBMITTAL • • , • • • • • , • CYPRESS SEMICONDUCTOR j 10220 SOUTH WEST GREENBURG ROAD � 3 LINCOLN, SUITE 417, LAB • TIGARD, OREGON 97223 • • • � CLEAN AGENT FIRE SUPPRESSION • WITH CONVENTIONAL i DETECTION AND CONTROLS • • • • � SYSTEM DESIGNED AND i INSTALLED BY SPECIAL HAZARD � FIRE PROTECTION CONTRACTOR: • SUPRESSION SYSTEMS, INC. • SPECIAL HAZARD FIRE PROTECTION � 3077 20TH STREET EAST, SUITE B • FIFE, WA 98424-1798 • k (253) 926-3300 FAX (253) 926-3306 • • Ps • TABLE OF CONTENTS • ❖ PROJECT CALCULATIONS BATTERY CALCULATIONS • y VOLTAGE DROP CALCULATIONS CLEAN AGENT CALCULATIONS • • ❖ DETECTION AND CONTROLS CONTROL PANEL • CONTROL ACCESSORIES • > DETECTION • ➢ AUDIO VISUAL • ❖ CLEAN AGENT • ➢ AGENT • ➢ CYLINDER • ➢ ACCESSORIES . ➢ NOZZLES ➢ PIPE AND FITTINGS • SIGNS • • • •• • il4 • • 0 0 • • • • • • r • • • • • • System Power Requirements°Pulse • AP-542D/542R Fire Alarm Control Panel • Protected Premises: 1861 -CYPRESS SEMICONDUCTOR Date: 9/10/2018 Address: 10220 SOUTH WEST GREENBURG ROAD, 3 LINCOLN SUITE 417 LAB • City: TIGARD State: OREGON Zip: 97223 • Prepared By: JUSTIN CARTER Phone: 253-926-3300 • Address: 3077 20TH STREET EAST, SUITE B Email: Justin@Suppression.com City: FIFE State: WASHINGTON Zip: 98424 •• • AC Branch Current Requirements 3.66 AMPS @ 120 VAC • Current required by source to power the fire • alarm system. • Primary Standby Load 0.12 Amps • Current load on the primary power supply during non-alarm conditions. • • Primary Alarm Load 1.36 Amps • Current load on the primary power supply during alarm conditions. • Secondary Load Requirements 3.93 Amp Hours • Total Secondary Load from the calculation table below. • • Current Draw I I Time(hours) I Total (AH) Seconday Standby Load Required Standby Time • 0.122 A x 24 hours 2.94 • Secondary Alarm Load x Required Alarm Time(hours) • 1.356 A 0.250 hours 0.34 Total Secondary Load 3.28 • Derating factor x 1.2 • Secondary Load Requirements 3.93 AH • • Battery Selection 7 Amp Hours Select batteries from the list below. • 7 AH CUSTOM BATTERY(12 volt) • IE Two {v Four(two 12VDC sets in parallel) • • • • • Page 1 of 2 • • • • • Battery Distribution Chart • Shows amp-hour distribution of your selections. • • Secondary Alarm Load oSpare Battery Capacity • 6% ❑Secondary Standby Load • Secondary Alarm Load 41 • SecondaryCir • Standby Load • 50% • vievirievw • • • Comments • 1. Batteries will fit in the FACP cabinet. • 2. Selected battery size meets secondary load requirements. 3. The selected batteries(7AH)are within the charger range of this power supply(7-26AH). • Spare Battery Capacity 3.07 Battery Selection(AR)-Secondary Load Requirements(AH) • Secondary Standby Load 3.53 Secondary Standby Load(AH)*Derating Factor • Secondary Alarm Load 0.41 Secondary Alarm Load(AH)*Derating Factor • • • • • • • • • • • 0 • • • • • • • Page 2 of 2 • • • • • • • • Pulse System Current Draw -AP-542D/542R • Current Draw Primary Non-Alarm-Cl Primary Alarm-C2 Cl0.122 A • .�... C2 1.356 A 0.00 0.72 1.44 2.16 2.88 0.00 1.40 2.80 4.20 5.60 7.00 • C3 0.122 A Power Used(Amps) Power Used(Amps) C4 1.356 A 110 ,N. -Al. C2-P . Al. C3-S- . .. N. -Al. • Device Qty Draw Non-Alarm Qty Draw Alarm Qty Draw Standby Main Circuit Board 1 x 0.12200 0.12200 1 x 0.18500 0.18500 1 x 0.12200 0.12200 • 73327-HF Electric Actuator 1 x 0.00000 0.00000 1 x 0.57000 0.57000 1 x 0.00000 0.00000 GENTEX BLUE STROBE AND H/S 1 x 0.00000 0.00000 1 x 0.40100 0.40100 1 x 0.00000 0.00000 • B11OLP 2 x 0.00012 0.00024 2 x 0.10000 0.20000 2 x 0.00012 0.00024 • 2151 2 x 0.00009 0.00017 2 x 0.00000 0.00000 2 x 0.00009 0.00017 NBG-12LR 1 x 0.00000 0.00000 1 x 0.00000 0.00000 1 x 0.00000 0.00000 • Total Nan 0.122 Total Alarm Load: 1.356 Total Standby 0.122 Alarm Load] Load: • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 040 • 00000 . 40 • • • • • • • • • • • • x► • • • • • • • • • • • • • • • This calculator provided voltage drop calculations in three formats(Point to Point, End of Line,and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name 1861-CYPRESS SEMICONDUCTOR CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date 9/11/20181 Circuit Number OUTPUT 1 Totals Voltage Totals Voltage Totals Voltage Area Covered HORN STROBE(2ND ALARM) Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 24' 0.271 50 0.13 0.271 50 0.133 0.271 50 0.066 Minimum Device Voltage 16 End of Line Voltage 23.87 End of Line Voltage 23.87 End of Line Voltage 23.93 Total Circuit Current 0.271 Wire Ohm's Percent Drop 0.55% Percent Drop 0.55% Percent Drop 0.28% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st device 50 16 4.89 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit 16 4.89 18=7.77 16=4.89 14=3.07 12=1.981 10=1-241 Enter current in amps. Distance 18-14 Awg=Solid Conductors 12-10 Awg=Stranded Conductors .150= 150 ma from Voltage Notes: 1 Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires(Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.271 50 23.87 0.133 0.55% the manufactures listed minimum operating voltage(IE: rated operating voltage 20-32 VDC). END 1 23.87 0.133 0.55% 1 ( 1 END 23.87 0.133 0.55% Device Manufacturer GENTEX Device Manufacturer END 23.87 0.133 0.55% Current I Current END 23.87 0.133 0.55% COMMANDE3ERIES @Rated @Rated END 23.87 0.133 0.55% Model# Candela Voltage Model# Candela Voltage END23.87 0.133 0.55% STROBES 15 0.105 END 23.87 0.133 0.55% 30 0.13 END 23.87 0.133 0.55% 60 0.203 END 23.87 0.133 0.55% 75 : 0.243 END 23.87 0.133 0.55% 110 0.310 END 23.87 0.133 0.55% HORN/STROBE 75 ' 0.271 END 23.87 0.133 0.55% END 23.87 0.133 0.55% HF-ACTUATOR N/A 0.570 END 23.87 0.133 0.55% END 23.87 0.133 0.55% 6"BELL N/A 0.054 END 23.87 0.133 0.55% END _ 23.87 0.133 0.55% END 23.87 0.133 0.55% 1 END 23.87 0.133 0.55% Totals 0.271 1 50 End of Line Voltage 23.87 This calculator provided voltage drop calculations in three formats(Point to Point, End of Line,and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction I Point to Point Method End of Line Method Load Centering Method Project Name 1861 -CYPRESS SEMICONDUCTOR CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date 9/11/2018 Circuit Number OUTPUT 2 Totals Voltage Totals Voltage Totals Voltage Area Covered SOLENOID Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 24 0.570 50 0.28 0.570 50 0.279 0.570 50 0.139 Minimum Device Voltage 16 End of Line Voltage 23.72 End of Line Voltage 23.72 End of Line Voltage 23.86 Total Circuit Current 0.570 Wire Ohm's Percent Drop 1.16% Percent Drop 1.16% Percent Drop 0.58% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st device , 0 16 4.89 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit , 16_"r,maa4.89 I 18=7.77 16=4.891 14=3.071 12=1.981 10=1.241 Enter current in amps. Distance 18-14 Aw =Solid Conductors 12-10 Awg=Stranded Conductors .150= 150 ma from Voltage Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires(Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.570 50 23.72 0.279 1.16% the manufactures listed minimum operating voltage(IE: rated operating voltage 20-32 VDC). END 23.72 - 0.279 1.16% END 23.72 0.279 1.16% Device Manufacturer CENTEX Device Manufacturer END 23.72 0.279 1.16% Current 1 Current END 23.72 0.279 1.16% ate MMANDE 3''SERIES @Rated @Rated END 23.72 0.279 1.16% Model# Candela Volta a Model# Candela Voltage END 23.72 0.279 1.16% STROBES 15 0.105 END ' 23.72 0.279 1.16% . 30 0.13' END 23.72 0.279 1.16% 60 0.203 END 23.72 0.279 1.16% 75 0.243 END 23.72 0.279 1.16% 110 0.310 END 23.72 0.279 1.16% HORN/STROBE 75 0.271 END 23.72 0.279 1.16% END 23.72 0.279 1.16% HF-ACTUATORN/A 0.570 END 23.72 0.279 1.16% END 23.72 0.279 1.16% 6"BELL N/A 0.054 END 23.72 0.279 1.16% END 23.72 0.279 1.16% END 23.72 0.279 1.16% J-1 _, - END 23.72 0.279 1.16% Totals 0.570 50 End of Line Voltage 23.72 1 • 411 • • • • • • • 411, 00 • • • • • • • 41 • • • • • • • • • • • • • • • • • • 41110 • 11041/ • • • • • • • • • • ► • • • • . • • • • • • • , • , • • • . • . • . • a • • • . • • i •► This calculator provided voltage drop calculations in three formats(Point to Point, End of Line,and Load Centering). Make sure that you know what method is accepted by,and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name 1861 -CYPRESS SEMICONDUCTOR CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date 9/11/2018 Circuit Number OUTPUT 3 Totals Voltage Totals Voltage Totals Voltage Area Covered DISCHARGE STRODE Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 24 0.130 50 0.06 0.130 50 0.064 0.130 50 0.032 Minimum Device Voltage 16 End of Line Voltage 23.94 End of Line Voltage 23.94 End of Line Voltage 23.97 Total Circuit Current 0.130 Wire Ohm's Percent Drop 0.26% Percent Drop 0.26% Percent Drop 0.13% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st device :50 16 4.89 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit 16 4.89 18=7.77 16=4.89 14=3.07 12=1.98 10=1.24 Enter current in amps. Distance 18-14 Awgi=Solid Conductors 12-10 Awg=Stranded Conductors .150= 150 ma from Voltage Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires(Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.130 50 23.94 0.064 0.26% the manufactures listed minimum operating voltage(IE: rated operating voltage 20-32 VDC). END 23.94 0.064 ' 0.26% END 23.94 0.064 0.26% Device Manufacturer GENTEX Device Manufacturer END 23.94 0.064 0.26% Current Current END 23.94 0.064 ' 0.26% COMMANDE 3 SERIES @Rated @Rated END 23.94 0.064 0.26% Model# Candela Voltage Model# Candela Voltage END 23.94 0.064 0.26% STROBES 15 0.105 END 23.94 0.064 - 0.26% 30 0.13 END 23.94 0.064 0.26% 60 0.203' END 23.94 0.064 0.26% 75 0.243 END 1 23.94 0.064 0.26% 110 0.310 END 23.94 0.064 0.26% HORN/STROBE 75 0.271 END 23.94 0.064 0.26% END 23.94 0.064 0.26% HF-ACTUATOR N/A 0.570 1 END 23.94 0.064 0.26% END 23.94 0.064 0.26% 5'BELL N/A 0.054'' END 23.94 0.064 0.26% END 23.94 0.064 0.26% END .r 23.94 0.064 0.26% END 23.94 0.064 0.26% Totals 0.130 50 End of Line Voltage 23.94 This calculator provided voltage drop calculations in three formats(Point to Point, End of Line,and Load Centering). Make sure that you know what method is accepted by,and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name 1861 -CYPRESS SEMICONDUCTOR CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS 1 Date 9/11/2018 Circuit Number OUTPUT 4 Totals Voltage Totals Voltage Totals Voltage Area Covered BELL(1ST ALARM) Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 24 0.054 50 0.03 0.054 50 0.026 0.054 50 0.013 Minimum Device Voltage 16 End of Line Voltage 23.97 End of Line Voltage 23.97 End of Line Voltage 23.99 Total Circuit Current 0.054 Wire Ohm's Percent Drop 0.11% Percent Drop 0.11% Percent Drop 0.06% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st device 50 16 4.89 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit 16 4.89 I 18=7.771 16=4.891 14=3.071 12=1.981 10=1.241 Enter current in amps. Distance 18-14 Awg=Solid Conductors 12-10 Awg=Stranded Conductors .150= 150 ma from Voltage Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires(Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.054 50 23.97 0.026 0.11% the manufactures listed minimum operating voltage(IE: rated operating voltage 20-32 VDC). END °''• 23.97 0.026 0.11% I I I I END y�.<< 23.97 0.026 0.11% Device Manufacturer GENTEX Device Manufacturer END 23.97 0.026 0.11% , Current I Current END 23.97 0.026 0.11% COMIV1ANDE3'SERIES @Rated @Rated END 23.97 0.026 0.11% Model# Candela Voltage Model# Candela Voltage END 23.97 0.026 0.11% STROBES 15 0.105 END 23.97 0.026 0.11% 30 0.13 END 23.97 0.026 0.11% 60 0.203 END - 23.97 0.026 0.11% 75 0.243 END 23.97 0.026 0.11% 110 0.310 END 23.97 0.026 0.11% HORN/STROBE 75 0.271 END 23.97 ' 0.026 0.11% END 23.97 0.026 0.11% HF-ACTUATORN/A 0.570 END 23.97 0.026 0.11% END23.97 0.026 0.11% 6"BELL N/A 0.054 END 23.97 0.026 0.11% END 23.97 0.026 0.11% END 23.97 0.026 0.11% END I 23.97 0.026 0.11% Totals 0.054 50 End of Line Voltage 23.97 • • • • • • • • 0/ 0011411040111 • • • • • • • • • 400001, 411011 • • • • 0011100410 • • ANSUL • INERGEN DESIGNER Version 2.1.2 • • Data file name: S:\Job Files-Server\Curr rent\000 DESIGN RESOURCES\DESIGN PROGRAM FILES\ANSUL\Ansul Inergen Designer\Projects\1861\18I IIIv Job: 1861 • Customer: CYPRESS SEMICONDUCTOR Hazard Area Information S • Area: LAB Design concentration 38.5% at 60° Fahrenheit • Estimated maximum concentration 42.1% at maximum hazard temperature 80° Fahrenheit • Net volume of enclosure 2456.5 cubic feet i Minimum INERGEN required 1218.4 cubic feet Approximate INERGEN supplied 1317. cubic feet Flooding factor .496 cubic feet of INERGEN per cubic feet of enclosure volume • Maximum allowable wall strength 5.0 lbs./sq.ft. Area consists of one volume Volume 1: Length 17 ft Width 17 ft Height 8.5 ft • 1 nozzles. Nozzle identifiers: 301 Agent Storage Conditions • Number of cylinders: 3 each containing 439 cubic feet of INERGEN. Ak Total agent 1317 cubic feet Engineering units (ft, cu ft, psia) are specified • Calculation based on 70 degree Fahrenheit pre-discharge Pipeline Temperature • Calculation based on fixed nozzle and pipe sizes • Pipe Data Input • Sec Sec Nominal Length Elev 90's Side Thru Union/ Noz Eql Start End Pipe Size (ft) (ft) Tee Tee Cplg Dia (ft) IP • 1 2 1/2 - 40 T 0.01 0.00 0 0 0 0 38.00 • 2 3 1 - 80 T 1.00 0.00 0 1 0 0 0.00 3 4 1 - 80 T 1.00 0.00 0 1 0 0 2 cyl 0.00 • 4 5 1 - 80 T 2.00 1.00 1 1 0 0 3 cyl 0.00 • 5 6 1 - 80 T 0.00 0.00 0 0 0 0 Orifice • 6 7 1 - 40 T 11.60 2.90 1 0 0 0 0.00 • 7 301 1 - 40 T 1.00 -1.00 1 0 0 0 0.453 0.00 r • S S 1 (End of Data Input File Printout) • • • • • ANSUL • INERGEN DESIGNER • UL listed EX4510, FMRC Approved(J.I.)2Y0A9.AF,ULC listed CEx1151 Version 2.1.2 • Data file name: S:\Job Files-Server\Curr rent\000 DESIGN RESOURCES\DESIGN PROGRAM FILES\ANSUL\Ansul Inergen Designer\Projects\1861\1111 Job Number 1861 for CYPRESS SEMICONDUCTOR • • Agent Storage Conditions S Storage pressure is 2175 psia at 70 degrees Fahrenheit. 439 cubic feet of INERGEN stored in each of 3 cylinders. Total agent in storage is 1317 cubic feet. • Time to discharge 1185 cubic feet (90% of INERGEN) is 59.7 seconds • Maximum pressure downstream of manifold orifice is 1607 psia i Concentrations i 95% Maximum Minimum Requested Time Cu Ft Concentration Concentration Concentration Area Volume (sec) INERGEN at Max. Temp. at Min. Temp. at Min Temp. LAB 2456.5 56 1317.0 42.1% at 80°F 40.9% at 60°F 38.5% at 60°F • Sea level equivalent oxygen: 12.2% at 80°F 0 Free Vent Calculation • Peak Maximum Wall Minimum Free • Area Rate Strength Vent Area • LAB 3178.2 cfm 5.0 lbs./sq.ft. 122 sq. in. • • Pressure Drop Results S • Sec Sec Nominal Length Equiv Elev Tee/ Start Term Flow • Start End Pipe Size (ft) Length(ft) (ft) Mfld psia psia (cfm) . 1 2 1/2 40 T 0.0 38.0 0.0 MFLD 1033 988 576.9 • 2 3 1 80 T 1.0 5.8 0.0 MFLD 988 989 576.9 3 4 1 80 T 1.0 5.8 0.0 MFLD 989 984 1153.8 • S 4 5 1 80 T 2.0 9.2 1.0 MFLD 984 972 1730.8 5 6 ORIFICE .422 INCHES DRILL NO. 27/64 972 701 1730.8 • 6 7 1 40 T 11.6 14.2 2.9 701 749 1730.8 S 7 301 1 40 T 1.0 3.6 -1.0 749 746 1730.8 Calculation based on 70 degree Fahrenheit pre-discharge Pipeline Temperature • ID 1 (Continued) • r • • ANSUL • INERGEN DESIGNER UL listed EX4510, FMRC Approved(J.I.)2Y0A9.AF,ULC listed CEx1151 • Version 2.1.2 • Data file name: S:\Job Files-Server\Curr • rent\000 DESIGN RESOURCES\DESIGN PROGRAM FILES\ANSUL\Ansul Inergen Designer\Projects\1861\181 • Job Number: 1861 • • Pipe and Fittings • Sec Sec Nominal Length Side Thru Unions/ EqI • Start End Pipe Size (ft) 90's Tee Tee Cplgs (ft) • • 1 2 1/2 40 T 0.0 0 0 0 0 Cyl Valve 38 ft 2 3 1 80 T 1.0 0 1 0 0 3 4 1 80 T 1.0 0 1 0 0 • • 4 5 1 80T 2.0 1 1 0 0 5 6 1 80 T 0 0 0 0 Man. Orifice IPI 6 7 1 40T 11.6 1 0 0 0 • • 7 301 1 40T 1.0 1 0 0 0 • Nozzle Performance Summary • Nozzle Nominal Drill Drill Quantity (cu ft) Area • Number Pipe Size Number Diameter Discharged Name • • 301 1 40 T 29/64 0.453 1317.0 LAB • •Messages/Errors • ANSUL 150 bar INERGEN DESIGNER Version number 2.1.2 • Calculation based on fixed nozzle and pipe sizes. • Calculation done on 9/6/18 at 2:01:15 PM illipe schedule selected for pipe sizes downstream of the manifold orifice is based on the maximum •ipe pressure for Grade A-53B, A-106B Seamless. To determine if other grades are acceptable, erify that the maximum pipe pressures for other grades are equal to or greater than the maximum nticipated downstream pressure. • Calculation by SUPPRESSION SYSTEMS INC. • NINA M REEVES 3077 20TH STREET EAST, SUITE B • FIFE WA 98424 USA • Telephone: 253-926-3300 • Fax: 253-926-3306 • • 2 End of Printout • • • • DATA SHEET AutoPulse 111 • AUTOPUISE 542R/E 'Agent Control Panel 1I = 5 • • Description The AUTOPULSE 542R is a six-zone Agent Releasing Control i � • Panel for single and dual hazard agent releasing applications. • The AUTOPULSE 542R provides reliable fire detection,signaling and protection for commercial, industrial and institutional 88 • buildings requiring agent-based releasing.The AUTOPULSE 542R is compatible with System Sensor's i3 detectors which are • conventional smoke detectors that can transmit a maintenance trouble signal to the panel indicating the need for cleaning and 411/ a supervisory'freeze'signal when the ambient temperature 111/ falls below the detector rating of approximately 45°F(7°C). In addition,the control panel is compatible with conventional input • devices such as two-wire smoke detectors,four-wire smoke detectors, pull stations,waterflow devices,tamper switches 007701 • and other normally-open contact devices. Refer to Device is System Sensor i3 series detector compatible Compatibility Document for a complete listing of compatible • devices. • Four programmable Style Y(Class B)output circuits—(special application power) • Four outputs are programmable as NACs (Notification Appliance Circuits)or releasing circuits.Three programmable Form-C • Strobe synchronization • relays (factory programmed for Alarm,Trouble and Supervisory) —System Sensor and 24 VDC special application resettable and non-resettable —Wheelock • power outputs are also included on the main circuit board.The AUTOPULSE 542R supervises all wiring,AC voltage, battery —Gentex • charger and battery level. —Faraday • Activation of a compatible smoke detector or any normally- j —Amseco open fire alarm initiating device will activate audible and is Three programmable Form-C relays • visual signaling devices, illuminate an indicator, display alarm ■ Latching option for relays information on the panel's LCD,sound the piezo sounder at the • panel,activate the panel alarm relay and operate an optional is Pre-discharge relay option . module used to notify a remote station or initiate an auxiliary ■ 7.0 amps total 24 VDC output current control function. j • Resettable and non-resettable output power • The AUTOPULSE 542R(E) releasing panel offers the same ■ guilt-in Programmer features as the AUTOPULSE 542R but allows connection to • 220/240 VAC. Unless otherwise specified,the information in this • Short circuit RAC supervision data sheet applies to both the 110/120 VAC and 220/240 VAC• is ANN-BUS for connection to optional devices(up to eight total versions of the panels. of any of the following): • —ANN-80 Remote LCD Annunciator Features —ANN-I/O LED Driver III ■ Designed for agent releasing standards NFPA 12, 12A, 12B —ANN-S/PG Printer Module • and 2001 —ANN-RLY Relay Module • ■ Disable/Enable control per input zone and output zone —ANN-LED Annunciator Module ■ Extensive transient protection ■ 80-character LCD display(backlit) is Dual hazard operation ■ Real-time clock/calendar with daylight savings time control • • Manual release/Abort combination zone ■ History log with 256 event storage • ■ Adjustable pre-discharge,discharge and waterflow delay timers • Piezo sounder for alarm,trouble and supervisory • 24 volt operation me., ■ Cross-zone(double interlock)capability Is Low AC voltage sense • ■ Six programmable Style B(Class B) IDCs (Initiating Device Circuit) • • One Stanton Street ( rvlarinette,WI 54143-2542,USA ( +1-•715.735.7411 ) www.ansu€.cam `I • 2018 Johnson Controls.All rights reserved.At specifications and other informalicon shown were Johnson �)'` • current as of document revision date and are subject to change without notice. ) Form No.T-2010233-02 Controls F. Features (Continued) CONTROL BUTTONS 0 • ■ ACKNOWLEDGE a Outputs programmable for: -Releasing Circuits • ALARM SILENCE a NACs programmable for: a SYSTEM RESET(lamp test) 0 -Silence Inhibit a DRILL • -Auto-Silence AC Power-TB -Strobe Synchronization a AUTOPULSE 542R: 120 VAC,50/60 Hz,2.3 amps • -Selective Silence (horn-strobe mute) ■ AUTOPULSE 542R(E):240 VAC,50 Hz, 1.15 amps • -Temporal or Steady Signal a Wire size: minimum#14 AWG (2.0 mm2)with 600V insulation -Silenceable or Non-Silenceable ■ Supervised, nonpower-limited • -Release Stage Sounder • -Stage Silenceable Option Battery(sealed lead acid only)-J12: a Maximum Charging Circuit-Normal Flat Charge:27.6 VDC • -Cross Zone Pre-discharge @ 1.4 amp Supervised, nonpower-limited -Cross Zone Discharge • ■ Maximum Charger Capacity:26 Amp Hour battery a Automatic battery charger with charger supervision (two 18 Amp Hour batteries can be housed in the panel • a Optional Dress Panel DP-51050(red) cabinet. Larger batteries require separate battery box such as a Optional Trim Ring TR-CE (red)for semi-flush cabinet the BB-26 or BB-55). • mounting a Minimum Battery Size:7 Amp Hour • a Optional CAC 5X Class A Converter Module for Outputs and Initiating Device Circuits-TB4 and TB6 III 3 ■ Alarm Zones 1 -5 on TB4 a Optional 4XTM-F Municipal Box Transmitter Module • a Alarm Zone 6 on TB6 a Optional Digital Alarm Communicators(411,411UD, 411UDAC) ■ Supervised and power-limited circuitry • PROGRAMMING AND SOFTWARE: a Style B (Class B) or Style Z(Class A)with optional converter II module a Custom English labels(per point) may be manually entered or . selected from an internal library file a Normal Operating Voltage: Nominal 20 VDC a Programmable Abort operation ■ Alarm Current: 15 mA minimum • a Three programmable Form-C relay outputs a Short Circuit Current:40 mA maximum • a Eleven pre-programmed templates and one user-defined a Maximum Loop Resistance: 100 ohms(700 ohms for linear template heat detection) • a Continuous fire protection during online programming at the ■ End-of-Line Resistor:4.7K ohms, 1/2 watt • front panel ■ Standby Current:4 mA a Program Check automatically catches common errors not • linked to any zone or input point Notification Appliance and Releasing Circuit(s)-TB5 and TB7 a Selectable timer options for Discharge 1 and 2, and a Four output circuits • Pre-discharge 1 and 2 a Style Y(Class B) or Style Z(Class A)with optional converter • module USER INTERFACE: • Integral 80-character LCD display with backlighting a Special application power ■ Real-time clock/calendar with automatic daylight savings a Supervised and power-limited circuitry • adjustments a Normal Operating Voltage: Nominal 24 VDC • a ANN-Bus for connection to remote annunciators a Maximum Signaling Current:7.0 amps(3.0 amps maximum . a Audible or silent walk test capabilities per NAC) ■ Piezo sounder for alarm,trouble,and supervisory ■ End-of-Line Resistor:4.7K ohms, 1/2 wattID a Maximum Wiring Voltage Drop:2 VDC • Controls and indicators Refer to the Device Compatibility Document for compatible LED INDICATORS listed devices. • a FIRE ALARM (red) • a SUPERVISORY(yellow) • a TROUBLE (yellow) a AC POWER (green) • a ALARM SILENCED(yellow) • a DISCHARGED(red) . a PRE-DISCHARGE (red indicator) • a ABORT(yellow indicator) • • , • Controls and Indicators (Continued) PRN-6: Printer. • Form-C Relays—Programmable—TB8 ANN-I/O: LED Driver Module provides connections to a user- 11 ■ Relay 1 (factory default programmed as Alarm Relay) supplied graphic annunciator. ■ Relay 2 (factory default programmed as fail-safe Trouble DP-51050: Dress panel (red) is available as an option.The dress • Relay) panel restricts access to the system wiring while allowing access • ■ Relay 3(factory default programmed as Supervisory Relay) to the membrane switch panel. • Relay Contact Ratings: DP-51050LED: Dress panel is available as an option.The dress . panel restricts access to the system wiring while allowing access 2 amps @ 30 VDC (resistive) to the membrane switch panel. It also allows the installation of • —0.5 amps @ 30 VAC(resistive) an optional ANN-LED annunciator module. • Auxiliary Trouble Input—J6 TR-CE:Trim-ring (red) is available as an option.The trim-ring The Auxiliary Trouble Input is an open collector circuit which I allows semi-flush mounting of the cabinet. • can be used to monitor external devices for trouble conditions. BB-26: Battery box, holds up to two 26 Amp Hour batteries and It can be connected to the trouble bus of a peripheral, such as a • power supply,which is compatible with open collector circuits. CHG-75. • Special Application Resettable Power—TB9 BAT Series Batteries • ■ Operating Voltage: Nominal 24 VDC System Specifications • ■ Maximum Available Current: 500 mA—appropriate for SYSTEM CAPACITY powering 4-wire smoke detectors (see Note) • w Power-limited circuitry e Annunciators:8 • ELECTRICAL SPECIFICATIONS Special Application Resettable or Nonresettable Power—TB9• ■ AUTOPULSE 542R (PEPS-7 Power Supply): 120 VAC,50/60 Hz, r Operating Voltage: Nominal 24 VDC 2.3 amps • r Maximum Available Current: 500 mA(see Note) ■ AUTOPULSE 542R(E) (FLPS-7 Power Supply):240 VAC, 50 HZ, 1.15 amps • e Power-limited circuitry is Wire Size: Minimum 14 AWG (2.0 mm2)with 600 V insulation, • ■ Jumper selectable by JP31 for resettable or nonresettable supervised, nonpower-limited power• CABINET SPECIFICATIONS Note:Total current for resettable power, nonresettable power Door: 19.26 in. (489 mm) high x 16.82 in. (427 mm)wide x • and output circuits must not exceed 7.0 amps. 0.72 in. (18 mm) deep • Backbox: 19.00 in. (483 mm) high x 16.65 in. (423 mm)wide x Product Line Information 5.25 in. (133 mm) deep • AUTOPULSE 542R:Six zone,24 volt Agent Release Control Trim Ring(TR-CE):22.00 in.(559 mm)high x 19.65 in.(499 mm)wide i • Panel (includes backbox, power supply,technical manual, and SHIPPING DIMENSIONS a frame&post operating instruction sheet)for single and dual • hazard clean agent applications. — Height: 20.00 in. (508 mm) AUTOPULSE 542R(E): Same as above but allows connection to ® Width: 22.50 in. (572 mm) • 220/240 VAC. — Depth: 8.50 in.(216 mm) • CAC-5X:Class A Converter Module can be used to convert the TEMPERATURE AND HUMIDITY RANGES • Style B (Class B) Initiating Device Circuits to Style D (Class A) This system meets NFPA requirements for operation at and Style Y(Class B) Output Circuits to Style Z(Class A). 32°F to 120°F(0°C to 49°C) and at a relative humidity • Note:Two Class A Converter modules are required to convert all 93%±2% RH (non-condensing) at 90°F±3°F(32°C±2°C). • four Output Circuits and six Initiating Device Circuits. However,the useful life of the system's standby batteries and the electronic components may be adversely affected by 4XTM-F:Transmitter Module provides a supervised output for extreme temperature ranges and humidity.Therefore,it is • local energy municipal box transmitter and alarm and trouble recommended that this system and its peripherals be installed • reverse polarity. It includes a disable switch and disable trouble in an environment with a normal room temperature of LED. J 60°F to 80°F(15to 27°C). • ANN-80: LCD Annunciator is a remote LCD annunciator that NFPA STANDARDS mimics the information displayed on the panel LCD display. Recommended wire type is un-shielded. — NFPA 12 CO2 Extinguishing Systems(High Pressure Only) • ANN-LED:Annunciator Module mounts in the DP-51050LED — NFPA 12A Halon 1301 Extinguising Systems Dress Panel and provides three LEDs for each zone:Alarm, — NFPA 72 National Fire Alarm Code for Local Fire Alarm • Trouble and Supervisory. Systems and Remote Station Fire Alarm Systems(requires an • ANN-RLY: Relay Module,which can be mounted inside the i optional Remote Station Output Module) cabinet,provides 10 programmable Form-C relays. — NFPA 2001 Clean Agent Fire Extinguishing Systems • ANN-S/PG: Serial/Parallel Printer Gateway module provides a • connection for a serial or parallel printer. 1111 • 6p Listings and Approvals Ordering Information • The listings and approvals below apply to the basic Part No. Description • AUTOPULSE 542R and AUTOPULSE 542R(E)control panels. In some cases,certain modules may not be listed by certain 433607 AUTOPULSE 542R Agent Releasing Control Panel, • approval agencies,or listing may be in process.Consult factory 120 VAC for latest listing status. 433608 AUTOPULSE 542R(E)Agent Releasing Control • ■ UL: S4935 Panel,220/240 VAC • ■ FM:Approved • ■ CSFM:7165-0595:118 Note:The converted metric values in this document are provided for dimensional reference only and do not reflect an actual measurement. ■ MEA:333-07-E AUTOPULSE and the product names listed in this material are marks and/or • registered marks.Unauthorized use is strictly prohibited. 4 . • • • • • • • • • • • . ••• • . • • • •• • • • • • • • • 4110 • * • 1 • <0 • • t r9i ) • • N. • r . , • 1 • • • ................ .____........_• ...._ . ._.Seated 1. e_....ad_.-Acid Batteries F±i • , V E % ,.. , 4-4. / , , • /R GEL e ' tC*4) • t --, • r `‘ • • • • • • ogi g • • r , • „00'40:j • • • • • ' -- • L isi • ,,,,,t.,7;,,,,,,, ,.it.;----7:--',,!;;,- - ,,,, 3011 — l'I''W *1 , • , ,,....,,.. , . • 't ,.: -,- ' -- .--,01-. ,,,,p7.,.. .- _ , . , • - ,, . „„.. , . • -:•:.,:-\\VYTFP • . .. ... . .„. .. , ._. • 0 '1. ;‘,.• ,,,-....... ' * •-• ....,. • • UPS Acid Batteries • • • • turesBenefits... ....___.__,,, _ ,, • Our Universal line of AGM and GEL batteries are defined as Non Hazardous& Non-Spillable by DOT (Department • of Transportation), IATA (International Airline Transport Association),and ICAO (International Civil Aviation i Organization). • • IP • • 0Outstanding performance,withstanding high current 4 Battery Terminal • output and deep cycling. t 0 �NIVE Excellent resistance to vibration,shock,chemicals 8121III 8 12,,,, ,,'!..Y„,w?,n� and heat ' ,aANegative Electrode iii• IP Lower self-discharge. . 0 Exceptional leak resistance even in an upside-down ---'4 AGM Separator • position. • ate � -':!,:;,ft" 0 Reliable power for critical applications. '[ • DOT 60 classified for easy transportation. ��i' . • UL recognized. Positive Electrode . • ABS Case • • EL Battery ^Design •AGM & GEL batteries are lead-acid and of the same battery chemistry (lead dioxide,sponge-lead and sulfuric acid electrolyte) but the electrolyte is stabilized differently. • I • • • ',"'•' . ,_tip. t� • Nine _ . • S a The electrolyte is suspended in fiberglass mat The electrolyte is suspended in silica-based • separators which act as absorbent sponges. gel as a thick pasty material. 11111 Art I Sealed Lead- • Acid Batteries wWW.upgi.com • i • • Sealed Lead-Acid/AGM • Nom Capacity Dimensions Weight Case Skid • __ _.,_ .,.___________ _______ _____„„__-_-_._.T . __._ _., _..___ _Length - Wsf�h Height _., __,._ ____ ______. UPG No. Model No. Terminal Volt 20 hr.rate iii, mon in, mm mm lbs.+1,5% Qty Qty 40559 08445 F2_ 4 4.50 1.86% T47_. 2.06 52 3.82_ _97 1,10 20 1920 • X5798 UB490 `.....:. F2 4_ _._. ... 9.00 4 2 I fl2 1.74 44 3.91 99 2.10'.._ 5 500 48561 ........ UB6 l fl.......... 2.011,650 2.20 56 0.53....... 20 2240411 .. 0573 I 06613 :: F I 6_ 1.30 3.82 97 0.96 24 2,22 56 -.. 0 64 -.. 60 3780.. [)5645 16326_..-_ H b_ 3.20 257_---65 1.28 33 4.00 102I 10 30 1920__-- _.- _40681 .--- ..086321. Ft 6 3.2.0 5.7.6 140 1.33__- 32__ 2,37_. 58____1,40 20___,-_ 960-____x__ • (75732 1 8634....... FI _6. _3.40 ....... 5.25 133 1.32 33 2.57 65.....1.10 20 1700....._...... 05.733 _._ U_E645 FI_... 6 4.50_.-.._.:. 276..._,70 ...1.85 47 4.17 1.061.83 20 I7OC1 ... ... 40565 UB645WL WL 6 4.50 2.75 __.69 1.86 47.__ 394..-.. 100 _._202 10 1200._-- 411 05697 U.B6SOS Lantern .,_ 52.... ._6.. 5;00 2.63 .._ 67 2..63 67 4.50 1 14 2 02 ......, 20 1000 05897 . ... ...F1... 6 5.00 _..._.. 2.63....._67 2 > UBbSOF.La.ncu-0......... 63 67. 4.00 E0"_ ......2.02 ........ 20........ 1000 ...........- 411 X5734,__._... 08670,.__.... .......:... FI_.. 6 7.00 : : 594-_._.150 1.34 34 3.94 1002,43 10 _: 1000 05735 U8685 F1.-_ 6 8.50 3.82_.._97 2.19 56_ 460 117 ....310 -__ I0 800 41105.736 05778 U86120 F I ' F2 6 12.00 5.94 :151 1.94 49..•. 3-.82 .. 97 4.06_...... 10 650 40575 086130 TOY Fl... 6 13.00 4.25 .,.,.108 2.82 72.., 5.44 138 5.04 .,.... I Q ....,. SO 05737 UB6120 TOY P2 6 12.00 4.25 108 2.78 71 5.47 139 4.19 10 50 411 40.560 0136 120 F2 45969 U136200062flfl0(Grp 27 Case} 14 6 6 42.00 200 00 6.42 163 3.48 88 6A1 ;:: 163 :::13 20 2 12.00 305 60 141 q 6 168 9 25 235 58.20 1 42 45966 ..... UB-GC2(Golf Cart) L5 _ 6 20000 ... 10.26 260 7.12 180. 967...,.. 245 ..62.30 1 50 • 45791 0.81208 _,. WL; 12. 0...80 3.78 96 0:98 25.., 244.,..., 62 0.75 30 1000 015738 ... UB1213 Fl 12. 1.30. 3.82 ..-971:69 43 2.28 58 L21 20 2000 • 02798 081220-T ST 12 2.00 5.91 150 0.79 20 3.50 89 . 1.54 20 1200 05734 81222 F I 12 2.20 7 00 178 1.38 35 2.50 63 2,20 20 ._. .1400 N/A UB1223A ---- PC 12 2.30 7.17 182 0.93----24 240 61__--1 46 10 05760 05740 UB1229TF1 12 2.90 306----78---.2,19 56 4.00 02 2.12 10 500 UB 1234_- F I: !2 3,40 5.25 133 2.63 67 2.44 .. 320 10 960 800 . 05741 f 05777 UB 1250 Fl f F2 12 5.00 3.54 90 2.76 70 4.21 107 3,09 10 850 40800 .._..__ 081270___ . 1 7.0000 5.94151 2, 65 3.94.._.. 100.._...450__.._. 8 :._.._ 369 .._.: _... _.. 56 40760 _. 0131272 F 1.... 12. 7.20 5.94 151 2.56._....65 3.94 100 4.90 ..... 8........... 50.1.___ • D5743105779 0131280 � Fl /F2 12. 800 593 151_-_2.5665 3.94 1044.96 8 544 40749?40748 UB12901 UB 1296F2. F1 12 9.00 5.94 151 2.56 65 3.94 100 5.10 8 .504 05719 UBI2100-5 F2 12 10.00 5.94 151 2.56 65 4.61 117 728 8 504 410 021744 f 5775 UB 12120 F 1 12 12 12 00 5 94 151 3 88 99 4 00 102 8.38 4 336 4065$ ___ _ 0812150 Tab wlhole 12 ____15,80_____-_594 151 3.89 99 3.95 1-08 9.60 4 244 • 40672 0812.150...... [35745'40648 081218OF2 12 T4'-F2 12 ._15 00..._.._... 5 94...... 151 3.89 99 3.95 ._. 100 9.60 18_00 713_ 181 391 76 6.57 167 I 1 90_ ...._.. 4 4 244 ............... 240 40696 UB 12220 T4 12 22 00 7 13 181 3.01 76.., 6 57.... 167 ...13 01 2 240 . D5747 06122.0.... 13_. 12 13 12 26,00 6.50 165 6.86 174. 4,94 125 ...18 08 ..... 2 16$.. 40596 UB i 2226.©T. 26.00. ......... 6.50 165 ...4.94 125 6.86 174 174.....21.00.... 2 ..........1.50. _._..-...._. ._ • 05722 ..U812350(Group U1). LI 12. 35.00 . .,_._. 768 195 :5,.16 131 7.13.:.._ 181. 2145 I 128 45976 L1.812350..Groip UI). 12 12. 35.40 .._.._ 7.68 .195 ..5.46 131_. 6.14 156.......23.15 1 __.. 128 . _.. .... 45977 0812500 1.2... 12 50.00 7.72 196 6.50 165 7.17 ..,. 182 31.97 I 100 U812550• Z1......................12 55.00 9 02 229 5 43 138 9.13 232 38.58 1 84 40740 ,,. UB 12550 (4 ON LEFT) Zl : 12 55.00 9.02 229 5A3 138 9.13 232 38.58 I 84 • 45980 UB12550 GI up22N'1 14 12 55,00 902 .-,'2_29 543 138 8.27.._._ 2103858 I 84 45821 0812750ijGr©up 24) ZI 12 75.00 10.24 260 6.61 168 9.13 232 50,71 I 60 35822 0812750{Group 24)._ E4-__ 12.- 75.00 10.24. 260 6.61 168. 8.27 210 50.71 _ I 66- • 458263B129fl0:{Group 27.? ZI' 12 90.00 1205_..-306 6.61 168 913 232 5680 ._ 1 52 ._.._ 45823 {11312900{Group 2Tj.._ 14.... !2 90.00 12 05._ 306 6...61 168 8.27 210 56 80 ... 1 52 • 45.978 UE121000(Group..27) Zi.... 12 10000 -__, 1205._..-306 .6-61 138 9.13 232 ` 5890_.._.. I 52 05751 061'21!Ofl{Grp r1 301i� FL I_ 12 1 10 00 12 9. 3,28 , 6.77 172 9.29 236 67.21 € 97 45981 UB 121 100{'Gr-oup 301.41 16 12 110,00 12 91 3286.77 172 8,58 218 67.24 1 47 45824 081)1100(Gr Dula 30H) L3 12 110.00 12 91 328 6.77 172 9.29 236 67.24 1 47 40994 ...-... UB121350 16 12. 135.00 13.39 340 6.81 173 1 1 22 285 87.08 _.. I 40 - - 45965 UB-4D AGM L4 12 200.00 __2075 527 8.lI 206 965 _ 245 ('2346 1 24 • 45964 UB-8D AGM L4 12 250.00 20.47 _520 10.55 268 9.65 169 _160.94 I 18 • L •venture Power Marine Absorbent Glass Mat (AGM) • Noris Capacity LeDimensions Width Height Weight Case Ski• Length UPG No, Model No. Terminal Volt 20 hr.rate In v mm m nn m min lbs. r5% Qty oty • _,. 40600 SSfl+.Group 224 1F1, Man,lo Pot 12 55.00 9.02 229 SA3 13,8,, 10.22 259 39.00 ___ 84 40601 UBI:. Group 241 _-- Manna a_Pos 2 7500. 1024 260 6.61 168 IQ16---258 __5450__ t 66 4111 40602 0812980 eup 2/). Marine Post 12 088 12.05 306 6.61 168 10.16 258 64,0'._..._ 1 _..._ 52 40663 08121 100{ .,308) Marine Post ?, 0.08 13 00 330 6.91 175 10.37 263 ..5' I 46 • Flame Retardant . led Lead-Acid/Absorbent Glass j •t • Nom Capacity Dimension. Weight Case Skid Length Ydldt Height IP UPG No Model No. Terminal olt 20 hr.rate „- mm ie, n min lbs., ° Qty _Qty _ 45565 UB1254FR._-._ F2 ._.._ 12 5.00 3.54 90 ..6 .__.70 4.21 107 3.09 10 600. • 45566 081270FR F.2.. L2 7.0.0 5.94 __I 45567 0912.120FR --- F2. 2-56 64- 3.94.__ -_ 496 ..__ $ 360 00 594 51 3,88 98_ 400_- 182 .-_838 336__._____ 45568 . UB1218QFR T4 L2 18.4 7 t81 3.01 76 6.57__ 167 11.90 4 480 • 40995__. U812260FRT3 12 26.00 54 166 6.89 -_.175 4.92 125_..-_1808 2 120 -_ ©58$0 +1B123.50FR__-- _ --_ LI 12 3590 -$._--495_.-516_.__131_ __7:13_____181___ .315---__-2 __---J28__----__ • 05881 11612>SOFR ZI__ 1.2 55 0 9.0 229 5,43 138 9.13 232 38.58 .__ 1 8`I. 05882 t161275OFR ll l2 - _00_-_ ___10.24 __ 0 6.61 J_b$ 913._.232 5071 L 60 45983 ...-_ 0812750FR 14._ l2 7500 10.24 260 6.61 1.6.8 831.-.. 211 __50,71 --_- 1 .... 60.... • ©.5883 US 12900FR Z 1' 90.00 12.05. 306 ..;- 16.8. 9 13_.. 232 :_59 52 : L .._.. 52 L? 884 UB121 I OOFFt_.. 21... 2 110.00 12.91 328 6.7 .172 9.29.._. 236 67 24....... 1.......... 47 • Sealed_ Lead-Acid 411 Nom Capacity Dimensions Weight Case Skid . Ler- WIUh iie(iht UPG Na Model N* Terminal Volt 20 hr rate n mar, m nm n nen QtY Qty 40703 .. UB-G (GoIfC_aic)Gel L5 6 80.00 .._ 1026 260 7.12 184 967 245 6320 I 200 • J?5470. L1 ):1 1.1 L2 32,00 7,69_-_195 _ 5,19 132 7,00__ 178 _23 10 1 128 05871B-22NFCEL ZL12 5500 902.__..229 5.38 137 9.13.-- 232 3858 84 05872 03-21 G.E. l 42 75.09_____. 1025--- 260 663 168 9.25 235 __5010 l 60 • 05873 U8-27 GEL Z i 12 90.00 12.05 306 . 6-61 168 9.13 232 59.52 1 05' UB-30H GEL FL2 12 1.0000 ..-... 12.91 .__.32$ 6,77 172 929_.. 236 57,24 1 52 • 01 UB-4D GEL L4 12 180.00 20.87 530 8.11 206 9.61 244 132,28 1 1 40702 UB-80 GEL L4 12 23000 20.47 520 10.55 268 9.65 245 171.96 1 16 • • Performance Characteristics • 0 0 Discharge Current vs Time Curve 25`t(77'n Cycle Life vs Depth of Discharge • 111mMiil0• 1,mNL, 10mEiI11sNim.i 111l\\ 1mLI111119M .• 20 ..... „..•,. . ..,;...... @erTartu9re • imellsLgssmili0 A 200 • Cycle Nnn'n,ei' rz -60 ;:'.. ,, 1=1.1111.11111111EMenntaingalk NEIN • IIIIIIIIIIIMIIMIIMIIMMERMIIBMNIMMENCIOABRIMMIE ,'22 Aniummmiumweammemitewsle Open Circuit Voltage vs Residual Capacity • o :1 nummiiniammainniginikanichynni. an ' IM1111111111111111111111111EIMMORM1111111111110111 „,.. '-5 11111 11 ' '' IMMEMEMIllatillantelif 1,,''''' 7.00 . . 14.0 A. • i > • .-'- ,,,,, 11-11- 12.0 ;..‘: • 30 50 100 200 500 , 2 3 5 1D 15 20 30 50 100 200 5.75.15- + - ' -6. II 5 > . . 11.0 f'Z' 41 Mscharge Current 3 • 3 : • - 20 40 IO 00 a ' a., a a • Residual Capacityl,',4) • • Discharge Characteristics Shelf-Life & Storage Temperature • Niii _ INIMLIMI- s 12 C,•-f.:, 4 . , .-. i;re..;:.1i,LE • ----*".4411--'44111 —44 -44 ,,• 80 III -5 1 _..__ - hill h.. 0 411 '4414140 RI ft.n.niftzuy,:ef _ 7 i .00C 0.MC ,-. , 5 60 ID d) • :,-' V! 04 (104T) 86'F) (68'F) I,:tCleries,each 1 2 3 5 IC: 20 30 60 2 3 5 I 0 20 ,t" : C. --r" I • , M „, Min. Hr. 0 '.' Discharge Time0 2 4 6 8 10 12 14 16 18 20 IP Standing Ptrrind(Months) • 4111 • Discharge Current vs Final Discharge Voltage Effect of Temperature on Capacity • 120 : i 1 ° Final Discharge >, 100 4 1 ,t, • Discharge Current(A) ",...,, . Voltage(Vicell) m 00 ! ,,c,-w ! - . : 11 . i i • 0,01C>C A too m .0 . . 0.2>CA a0,01C 1.75 • , • , 1.0,,,, : : : -?:,, :4' ,' ' L, ! ..--1----t---±— i 0.5>CA o0 2C 1,70 ,..,f, m 0 .2. , 1 i 1 1 1 • 2.0>CA a.0.5C 1,60 CA a2.0C 1.30 c, ;C To 20-10 20 - 100 r; .4 14 32 F,0 88 85 Ambient Temperature 10 • • ----------------------------------------------------------"--------------------"------•"""-""----------------- 0 0 For assistance,please contact a UPG sales professional at 866.892,1122 or by email ' .iqr '''' ‘.,.,\ U PG • at sales@upecom. \':',. --y STAY POWERED' • • • • • Terminal Configurations • • F Series(Fasten Tabs) P Series(Plastic Connector) P2 44.0 mm . on 1.73 in Ivra18e I. It w II T h I.9 7 6.50 mm 1.75 mm 6.00 mm 5.00 mm 0.80 mm Jr Fl 0.26 in 0.19 in 0.24 in 0.20 in 0.03 in - -!22.5 mm I L I h2 7.80 mm 6.35 mm 7.80 mm 6.00 mm 0.80 mm 10.89 in 0.31 in 0.25 in 0.31 in 0.24 in 0.03 in -✓ -I • 14.5 mm 0.57 in • m,. ._,._._, .. ........ ............ ... ......., 5555..8 mm I Marinearirte Combo PosE Flag ierminai(FL1) 301.z1 in Flag Terminal(Ft.2j 250 mm0.98 in 7.92 mm 28.0 mm I..._- 0.49 in • I I.10 in 82.03 mm ,D.99 in 0.31 in "9598 m CO• , lip TIA r , 116 I.gm • 2.00 mm I 0.59IS•9 mmIMM e mo°.iii v.m:. •in 6' 5.60 mmI I 0.08 in _le'^ 0.22 in I 8-337 • 10.0mm { €- rxs mm 36.2 mm 0.39 in L Ig 0.99 is 1.43 in 2.o0 mm} Fa 12.3 mm 0.08 in 0.48 in • !_ 10.2 mm 57.0 mm 059 nm 0.40 in 2.21 in �� I_ < E.E 1 10.0 nm ' 0.79 In 12.0 mm -.kV* ' o `` / �-'� 0.47T. e.!a'm„� �\- / �, 45 mm -_ c.n m T • o.9sm- x220 mm 54.9 mm • 087 n ..165mm 5 555 5555_.. 5 555..2.16 in 1�.....__. 1.83 in 5555_ ... ... 5555. 5555 5,,555. I Series(Internal Thread) Z Series(2 Pest Terminal) S Series • H j . St . I I X 1' M.11,-14.347' 9.00 mm i I. o is 6.00 mm 15.0 mm 3.00 IT 22.1 15.0 mm 021 in 059 0.12 in 1a 9.52 mm 160 m 4.00 mm "I nl ph 0.59'n • m n 037 in 1063 n 0.16m ))) a NI H _900 mm 600 mm1150 400 mm I` ONm 059 016 in ZI 17.0 mm 8.00 m121.5 mm 9.00 mm -j 0.00 in rn 952 mm I70 4.00 mm 067 in 0.32 n 10.85 in 0.35 in • �� I' 0.37 n 10.67 0.16 in ��I919.0 mm ;I-' ' 1600 mm',160 1.06 in 0.75 in !ONn 063 0.16n 9.52 mm'116.0 mm 4.00 mm j__'_ • I' 0.77m 0.63 in 0.16 in �- f �- 1 30.. ..19.0 mm 2.00 mm �.// 0.39_in__ 0.75 in 0.08 in__ 5555.-_� 3:13r-LA? mm 1500 mm1 • In 0.37 in ''�,0.75 in 0.16 in -- 1 L Series(L Type Terminal) T Series (Tab Terminal) • Tynenspe` ion L A N h _ 17.5 mm 7.00 mm 17.0 mm 7.00 mm 8.50 mm Y n i w `� Li 10.69 7.0in .0.28 in 0.69 in r 0.28 in 0.31 in � L W h 1769 in 9.00 mm 17.0 mm 9.00 mm 6.50 mm 11.0 mm 2.00 mm 125 mm 6.00 mm j 6.00 mm • �; _ I: 0.69 in 0.35 in 0.69 in 0.35 in 0.26 in 0 'T3 0.55 in 6.09 in i OA9 m :0.24 in :0.24 in -/ 25.5 mm 7.00 mm 22.0 mm 10.5 mm 8.50 mm 12.0 mm 3.00 mm 1 12.5 mm 1 5.00 mm 5.50mm I 6 5 in 0.78 in _0.87 in 0.41 in 0.31 in -1,-H-- T4 0.47 in 0.12 in O.49 in 1 0.20 in 0.22 in 26.5 mm 0.00 min 245 mm 120 mm 9.00 mm I ' __ _ U 1.04 in 0.32 n 097 047 in 035 in • I_ 26.5 mm 8.50 mm 24.0 min 100 mm 8.00 mm I; 104 in 034n 0.95 in 039 in 032n • Battery Care ............ • • To properly charge your deep cycle AGM/GEL battery: Active users:Charge daily. • Occasional users: Charge your battery before any outing,after active use or every 90 days if no use. • OOnly use with a specified charger. Only use appropriate charger to charge AGM vs GEL batteries as charging 11 • rates differ. • 0 Never use an automotive or wet type charger on a AGM/GEL battery. • OTop charge your battery frequently and/or leave on a charger/maintainer. Battery_ Storage • • 0 Batteries should always be stored fully charged in a cool and dry place to maintain maximum service life. • 0 Depending on storage temperature,batteries hold their charge for 3 to 9 months until recharge is necessary, Above 30°C (86°F),recharge at 9 months. Above 40°C (104`'F),recharge at 3 months.Do not store above 40t (104T). • 0 If a battery is stored for 9 months or longer without being charged,its service life may be shortened. • 0 Never store batteries in a sealed environment or incorporate into a sealed structure/enclosure without adequate ventilation. • • • Usage Precautions • SLA batteries if used under recommended conditions generate no sulfuric acid gasses. However,because they contain lead and • sulfuric acid,which are both toxic,proper care and handling is important in order to avoid accidental fires,damage to property, • bodily injuries or even death. *Improper charging and poor maintenance may cause battery to °Use of.SLA batteries in the upside down position is not recommended. • emit hydrogen gas. Therefore,do not use battery near a spark, fuse flame and/or equipment that emits sparks. • °Do not use organic solvent,cleaning agents,paint,'thinner,petroleum products to °Never mix the SLA batteries together with other types of batteries, clean battery surface.These products can lead to battery container/cover cracking, 4111 such as dry cells and nickel-cadmium batteries. °Keep the battery terminals from contact with wire,metal cabinets,metal °SLA batteries may not be compatible with certain equipment. Any uncertainty • tools.such as screw drivers,spanners,torque wrenches unless they are about the specifications of the battery should be brought to our attention. properly insulated. Do not wear any watches,personal jewelry. • hair pins or any other metallic objects when servicing the batteries. °observe circuit polarities. Do not make or break live circuits, °Short circuiting the terminals of the battery can cause burns,injuries: • °As appropriate,use an insulating blanket to cover exposed portions of the battery damage to the storage battery,or trigger explosions. system when performing extended maintenance that could result in personal or • °Do not direct solder to terminal. This may lead to electrolyte leakage. equipment contact with the energized conductors, Primary Power Applications StandbyPower Applications • Consumer Electronics Motorcycles 0 Access Control Devices • 0 Electric Vehicles 0 Photography 0 Automotive&Cable Electronics • Engine Starters '" Powersports 0 Emergency Lighting i Golf Cart 0 Portable Tools 0 Security Hunting 0 Solar 0 Telecommunications Equipment • 0 Lawn &Garden 0 Toys& Hobbies 0 UPS Systems • Marine 0 Trucking C Medical Mobility 0 Other Portable Equipment • Medical Equipment • Specialized Applications • If your needs are specialized,we are able to custom manufacture batteries and chargers to meet your particular specifications. • Tell us what you need and let us handle the rest. • • Environmental Care • Improper disposal of batteries can lead to contamination of soil and ground water. At UPG,we work with authorized recyclers • to pick up your"spent"fused batteries and we ensure that these batteries are properly disposed of by EPA licensed smelters. • Adventure Power®Chargers & Maintainers • enture Power &Maintainers;f • :4)id Maintaining sealed -acid batteries in boats,motorcycles,A :Snowmobiles other ture Power Charger& Maintainers • ', conveniently and charge whilestorage wl;X ter . in to disconnect ,, ' .: �, t 9„/ f • UPS o. Description Charges and/or Maintains T 84036 12V IA Charger&Maintainer 12 V 2.9 Ah - 12V 7.2 Ah Batteries • 84037.... 12V 2A Charger&Maintainer 12V 8 Ah- 1 1 Ah Batteries 8€038 12V-4A Charger&Maintainer 1 2V 12�Ah batteries and Up • Adv,s':wre.Pow4:r is a registere+i uaderrark.�.i UPG. • • a �n=..«.ee._.__..,...es__a.....n x..a<..,..,n.,.,.n.,,.....>a -. „--e..a.a=_._ss——— ___,,.,ex.,._...._kn_.._»._.n...,....,_....._.._.....,>n.. .——. ..., • 463.832.1122 488 S. Royal Lane T 866.892.1122 • �; 4,;r; Coapell,Texas 75019 F 469.892.1123 ,. ., • sales@upgi.com • 0 • I • • ANSUL. System Components 41, UI EX-4510 2-1-12 Page 1-3.4 • REV. 3 r - (Th) (7 r • . Sy-stanw— ..i.., ge ../ Valve Electric Actuation • 0 • Description ,,,,,,,1 1/4--18 • Electrical actuation of an agent cylinder and/or selector valves is accomplished by an HF electric actuator interfaced • %through an AUTOPULSE Control System.This actuator can To 0 be used in hazardous environments where the ambient tern- ‘-...... 0 perature range is between 0°E to 130°F(-18°C to 54°C). 1.00,444..................00 --..........--- A • The HF electric actuator meets the requirements of N.E.C. Class I, Div. 1, Groups B, C, D and Class U, Div. 1, Groups IP E, F. G. A maximum of two HF electric actuators can be 40 used on a single AUTOPULSE release circuit. When utiliz- ing only one HF electric actuator,an in-line resistor, Part No. 1110 73506,is required in the supervised release circuit. 411/ The actuator specifications are: Nominal Rated Voltage _.,,,..--'" 1110111■0° • Voltage Minimum Maximum • t- 12 VDC @ 0.57 amps 12.0 VDC 14,0 VDC 2 1 41N ;5.?cm),..„. "C'J,34 O In auxiliary or override applications, a manual-local override valve actuator or a manual cable pull actuator can be • installed on top of the HF electric actuator by removing the • safety cap. A reset tool Is required to reset the actuator after operation. . ' Thread 0 The actuator contains a standard 1/2 in. threaded female Component Material Size/Type i Approvals straight connector for electrical conduit hookup. I • r HF Electric Body: 1/2 in. UL(EX-4510): • 1 1 Shipping Assembly i Actuator I Brass Straight I Listed for use I Part No. Description I Plunger: Fetilaie 1 with FM 0 Stainless > 73327 HF electric actuator Steel I Approved systems , 75433 HF Reset Tool 41 • Description 1 i'4-18 ONEF The Booster Actuator, Part No. I 0• 2 50> 428949, is used when electric actua- 1 • / ----ca, --- . -- lion is required on the selector valve I • or the CV-98 cylinder valve. The t- _ .— 1— I -_-....,,...._.,.......--e-_ • actuator mounts directly to the corn- 11111111=111.1111.110.11111MMI----- ponent and then a HF electric actua- 1 • tor mounts to the top of the booster 1 i 1 • actuator. 3 25 I 1 The Booster Actuator requires reset- L _......1i • ting after actuation. A Reset Tool, ....._---- $ • Part No. 429847is available for this _o use. _ - .._ • / C1W.,7 O 1 118-18 1.11NIEF 1 • tqco Copyright 2012 Tyco Foe Poctorts LP Fire Protection One Stanton Street +1-715-735-7411 All rights reserved. 0 Products Marinette,WI 54143-2542 voivw,anstil.corn Form No.F-95025-03 • • • • +11 ANSUL i Bulletin No. 2015187 • November 20,2015 • Page UL EX-4510 • Technical Information • Thread Suggested • Part Size J Electrical List Price • Number Description Material Type Rating Approvals (USD)* • 441870 INERGENe HF Electric Switch—Stainless 1/2 in. — 24 V, 0.4 A UL Listed $105.00 • 7 Actuator Placement Steel/Plastic/Gold 14 NPSM (EX-4510) Indicator Switch Contacts Assemk FM Approved • Y Housing—Plastic 2.010 • 441871 Halocart on Electrical Switch—Stainless 1/2 in, — 24 V,0.4 A UL Listed Actuator Placement Steel/Plastic/Gold 14 NPSM (EX-4510) • Indicator Switch Contacts Assembly FM Approved • = Housing—Plastic • • b� notice,Always refer to the latest price ties the ANSUL Distributor Portal prior to ordering, • �`Note;Prices are subject to ch Placement indicator Switch Switch Wiring Diagram • 0 • SENSOR SWITCH • AND CONNECTOR ASSEMBLY ',4 x ' Nousteo TO CONTROL PANEL INPUT CIRCUIT • - ,. / PROGRAMME.L7 FOR SUPERVISORY CONNECTOREtN.RESISTO=R SPECIFIC TO • RETAINER COvEFt � _, (1/4( . AUrAPULS£SIRE CONTROL.PANEL (OO NOT REMOVE) Jlb '4'1,4:: ' 3 r OR C ) • j COVER *. • \\*, \ .,,-.:::.- . 1 I • it .„.,. .,,,,,,... ...,,t4„ , .14 _, ....,, , „„ ,. _ , 10 , , , , • SCREW11110041 ' • (COVER) INTEGRAL BOLT • SCREW,.TWO PLACES • (CONNECTOR RETAINER • COVER) • • • • • VICO One Stanton Street Marinette Alt WI $la61 Telephone Nc tar +1-800-862-6785(r+1-715-735-7415 • Fire�Protection;�r�r�r�cxs . SuStomer Services... .Press 2 T€rrhni€.a(Settts ,.., ..,Press 4 es Ens t com Training Services .........Press 6 Duality Assurance ........,.,Press 8 • • • • • • Detection and Control Components • • , • ` ' _: �P u Ise Abort Switch • \.. r (IQ-318, IQ-636X-2, 542R, 542D) • • Features • • Stackable, screw-terminal,contact blocks ABORT SWITCH (PARALLEL) • • Compatible with AUTOPULSE control units ____ EOL RESISTOR • • Surface-mount assemblies listed by Underwriters r___ I Laboratories, Inc. ( •� (+) • • Components mounted on stainless steel switch plate P. 1 1H I I CONTROL UNIT I I ABORT CIRCUIT • Applicationsq (..)TERMINALS OR L----1 003735 ADDRESSABLE ► N .ABORT I MONITOR MODULE • The Abort Switch is used to momentarily interrupt the release SWITCH L-_— circuit signal when the control unit is in the alarm condition. " SEE CONTROL UNIT MANUAL FOR SPECIFIC WIRING REQUIREMENTS. • As long as the abort pushbutton is held in, the fire suppres- • sion system will not release. (Note:When the control unit is Ordering Information programmed for IRI compliance, the abort will not be effec- Shipping • tive after pre-discharge.) When the pushbutton is released, Weight the release circuit is activated (unless the control unit has Part No. Description lb (kg) • been reset to the non-alarm condition). 76494 Abort Switch, Surface-Mount 1.0 (0.45) • Description > 76495 Abort Switch, Flush-Mount 1.0 (0.45) • The Abort Switch assembly consists of a momentary- 436983 Extra Contact Block, NC 0.25 (0.11) • contact pushbutton switch, normally-open contact block, 436982 Extra Contact Block, NO 0.25 (0.11) normally-closed contact block, and stainless steel switch • plate with silk-screened label. Surface-mount assemblies include a single-gang weather-proof box with three 1/2 in. • I.P.S. threaded conduit outlets and gasket. • The stackable, screw-terminal contact blocks are rated for 28 VDC @ 1.1 amp make/break or 6 amp continuous carry. • Listings and Approvals • The switch is UL listed (S3623)when installed in the surface- • mount box (with gasket) that is provided with the surface- • mount assembly. • MOUNTING DIMENSIONS • SURFACE-MOUNT FLUSH-MOUNT p. . 73/8 INmm —� �-- 3 IN. ) '' �_(67/6 m) r • ( ) (76 mm • N /• _ FIRE SUPPRESSION • SYSTEM ABORT • 0 4 5/8 IN (117 mm) M um • PUSH AND HOLD J 007362 • 0 • , . • • 3-15 • TYCO FIRE PROTECTION PRODUCTS ONE STANTON STREET Copyright©2011 Tyco Fire Protection Products All rights reserved. MARINETTE,WI 54143-2542 715-735-7411 Form No.T-2007130-3 • • • • • Detection and Control Components • • A : ©Pu1se Key Maintenance Switch • \,. (I0-318, IQ-636X-2, 542R, 542D) r 41 Features TYPICAL WIRING DIAGRAM • • Stackable,screw-terminal,contact blocks CONTROL UNIT RELEASE • KEY-OPERATED CIRCUIT TERMINALS ORR ► • Compatible with AUTOPULSE control units 24 VDC LOCK-OUT SWITCH ADDRESSABLE RELEASE CONTROL r-———— • Surface-mount assemblies listed by Underwriters ACTUATOR41 i MODULE" Laboratories, Inc. LPNM I r, (+) • Components mounted on stainless steel switch plate N O I „ •• I O Applications I • pp I POLARITY IS The Key Maintenance Switch is used to interrupt the release I n �� ” i SHOWN M circuit signal to the fire suppression system. It is key-operat- I———— _ J 24 VDC POWER _CONDITION ed to allow authorized personnel to deactivate the release SOURCE • 007360 circuit during service or maintenance. An indicator lamp, 24VOC 5 located on the switch plate, will light when the switch is in the INDICATOR LAMP "lock-out" mode to serve as a reminder that the release cir- " SEE CONTROL UNIT MANUAL FOR SPECIFIC WIRING REQUIREMENTS. • cult has been disconnected. Description Ordering Information • The Key Maintenance Switch assembly consists of a key- Shipping • operated switch, 24 VDC indicator lamp, normally-open con- Weight • tact block, normally-closed contact block, and stainless steel Part No. Description lb (kg) switch plate with silk-screened label. Surface-mount assem- 76498 Maintenance Switch,Surface-Mount 2.0 (0.9) 5 blies include a double-gang weather-proof box and gasket. ---> 76499 Maintenance Switch, Flush-Mount 2.0 (0.9) • The stackable, screw-terminal contact blocks are rated for 28 436983 Extra Contact Block, N.C. 0.25 (0.11) • VDC @ 1.1 amp make/break or 6 amp continuous carry. 436982 Extra Contact Block, N.O. 0.25 (0.11) Listings and Approvals 436088 Spare Key 0.25 (0.11) • The switch is UL listed when installed in the surface-mount 0 box (with gasket) that is provided with the surface-mount • assembly. • MOUNTING DIMENSIONS • SURFACE-MOUNT FLUSH-MOUNT ► 4 11/16 I N. 3 IN. 2 5/81N • ► * (119 mm) r ...---(76 mm) w- ~—(67 mm)—i • • • I. NORMAL DISCONNECT 171.-1 • Ii 0) 45/81N. I =1 • J (117 mm) ■ �_ 41 FIRE SUPPRESSION SYSTEM DISCONNECT • 0 0 ✓ \ • 007361 • • 3-16 • TYCO FIRE PROTECTION PRODUCTS Copyright CO 2011 Tyco Fire Protection Products • ONE STANTON STREET All rights reserved. MARINETTE,WI 54143-2542 715-735-7411 Form No.T-2007129-3 • • • • • Detection and Control Components • • • AutP.ulse NBG-12LR Dual-Action Agent Release Station • ` I (IQ-318, IQ-636X-2, 542R, 542D) • • General ..o • The NBG-12LR is an Agent Release Station designed for use with AUTOPULSE Fire Suppression Control Panels. ..x • • Features • • Non-coded,dual-action operation • Made with durable polycarbonate • • Optional surface backbox 1 LDo N j • • Dual-action release only PUSH IN • Applications P_ �► • v ,„ The NBG-12LR is ideal for areas such as clean rooms and �� . • computer rooms where a chemical agent is used to extinguish a fire. , ‘�� • • Wiring TO MANUAL • RELEASE►CRCUTOR 4 (+) 2 1h s .) ADDRESSABLE >k ��' � 4. 1 • I MONITOR (—) r ►MODULE 4 , , � ooaozl • 'REFER TO CONTROL PANEL MANUAL FOR LISTED ELR 008019 • Dimensions, Backboxes • 41/8 IN. Listings and Approvals • 1- (105 mm) UL S692 i • FM Approved 1110 California State Fire Marshall (CSFM). . . . 7150-0028:199 0 Ordering Information • 1 3/8 IN �j �� O (35 mm) Shipping • DEEP SB-1 05 1/2 IN. Weight ► (140 mm) • Part No. Description lb (kg) 0 0 > 435471 NBG-12LR Dual-Action Agent 2 (0.91) • o Release Station • 418990 SB-10 Surface BackBox 0.5 (0.23) for NBG-12LR • • 008020 • • • • • • 3-13.1 TYCO FIRE PROTECTION PRODUCTS Copyright©2011 Tyco Fire Protection Products • ONE STANTON STREET All rights reserved. MARINETTE,WI 54143-2542 715-735-7411 Form No.T-2008057-3 • • • • Detection and Control Components • • / - • "41. u se II • 2151 Photoelectric Smoke Detector (542R/542D) • • Features Technical Information • • Unique optical sensing chamber Stand-by Current. 85 microamps • • Built-in signal processing Sensitivity. 3 0%nominal • • 3.0%nominal sensitivity Weight: 0 5 lb(277 g) • • Removable cover for field cleaning Size: 1 7 in. high x 4.0 in.diameter (84mmx102mm) • • Visible LED"blinks"in standby • Sealed against dirt, insects, and back pressure Construction: Flame retardant white thermo plastic • • Field metering of detector sensitivity Temperature: 32°F to 120°F(0°C to 49°C) • • Built-in magnetic test switch Humidity Range. 10-93%RH (non-condensing) • Low standby current Maximum Air Velocity: 3000 ft per minute • • Built-in tamper-resistant feature (15 m per second) • • Designed for direct surface or electrical box mounting • • 360°Field viewing angle of the visual alarm LEDs 2151 PHOTOELECTRIC SMOKE DETECTOR WITH BASE • • Insect-resistant screening • • Easy plug-in of the head to base • SEMS screws for easy wiring \ n o I�� • • Air velocity up to 3000 feet per minute (914 meters perLL • minute) • Applications • Photoelectric detectors are recommended in areas where slow smoldering fires are likely to ignite. In areas where small • combustion particles are usually present from fork-lift trucks, • cooking stoves, etc., they are less likely than ionization detectors to produce false alarms. The detectors are used in , • combination with an AUTOPULSE Control System and an • (( fire suppression system for automatic detection, alarm, equipment control, and fire suppression system release • capabilities. Description • 007353 • The 2151 photoelectric smoke detector contains a unique optical sensing chamber designed to sense the presence of • smoke particles produced by a wide range of combustion B110LP OPTIONAL NFPA CLASS"A"WIRING sources and meet the performance criteria designed by UL • 268. An integrated circuit incorporates signal processing to reduce false alarms and sample/hold circuitry to provide easy • field metering of sensitivity. • The 2151 photoelectric detector incorporates the light scatter 2 (-)® 2 c->® • principle within its sensing chamber and solid-state circuitry 0 , s 0 s allowing it to react to either smoldering or flaming fires. (-0 4 c+> 4 • The high impedance circuitry of the detector allows a single (-00 \ (+)!4/ • loop to power multiple detectors with very low power con sumption.Two externally-mounted LED indicators are provid- (+) • ed which will blink as long as the detector is powered and will (+ 007350 light steadily when the detector is in alarm. 411/ • • 3-55 • 0 • • • Technical Information (Continued) • Current Current Base Loop Limit Contact Standby Draw on • Model Type Resistor Type Voltage Alarm • B110LP 2-Wire No -- 12-24 VDC 10-100 mA` B401 2-Wire No -- 12-24 VDC 10-100 mA* • B401 B 2-Wire No —— 8.5-35 VDC 10-100 mA* • B401 BR-750 2-Wire Yes -- 17-32 VDC 10-39 mA B402B 2/4 Wire Yes Form NC 17-32 VDC 14-39 mA • 'Limited by control unit • Detector Base/Control Unit Compatibility • Detector AUTOPULSE AUTOPULSE • Base 542R, IQ-318, IQ-636X-2 (Part No.) 542D FZM-1 • B110LP(430025) Yes Yes • B401 (423026) Yes Yes • B401 B(417996) Yes Yes B401 BR-750(78997) No No III B402B(79011) 4-wire only 4-wire only • B110LP BASE WIRING DIAGRAM Listings and Approvals* • (-) UL S911 • EOL California State Fire Marshal(CSFM) 7271-1209:159 �� 0,3 RESTS OR Factory Mutual(FM) Approved • 2 (—) 2 H3 II MEA 205-94-E • ►i,1 Q1 (+) (+) ' Listings and Approvals are under SYSTEM SENSOR • (+)is + 'ii Ordering Information • (+) (+) Shipping • 007351 Weight Part No. Description lb (kg) • Mounting Guidelines > 430023 2151, Photoelectric Detector 1 (0.4) • The detector bases are designed for surface mounting. The430025 B110LP Standard Base 0.5 (0.2) detector head can be inserted or removed from the base 430026 B401 4 in. Dia Base 0.5 (0.2) • without disrupting the wiring connections. ► All detector bases can be mounted to a 3 1/2 in. (89 mm) 428138 F110 Trim Ring, Low Profile 0.5 (0.2) ► octagon, 4 in. (102 mm)octagon, or a 4 in. (102 mm) square 417675 M02-04 Test Magnet 0.5 (0.2) • outlet box. 417699 EOL, Power Supervision Relay 1 (0.4) • • • • • • • • • • • TYCO FIRE PROTECTION PRODUCTS Copyright©2011 Tyco Fire Protection Products • ONE STANTON STREET All rights reserved. MARINETTE,WI 54143-2542 715-735-7411 Form No.T-2007122-3 • • • • • • GES3 / GEC3 Colored Lens Series • Selectable Candela Signals • 24 VDC Colored Lens Strobe and Horn/Strobe • 24 units per carton,28 pounds per carton • • Applications • The Commander3 Series Colored Lens Signals are wall mount,low profile strobes .x • or horn/strobes that offer dependable audible and visual alarms for warning and „,,,.,,.,,,,..1 - emergency notification. Applications include emergency communication,severe '-` • weather,emergency response and many more. IE • The GB Colored Lens Series are 24VDC units available in lens colors of amber,blue, • green and red. The Series offers tamperproof field selectable candela options of 15, 30,60,75,and 110 candela. The GEC3 horn/strobe offers a continuous or synchable ' v • temporal 3 in 2400Hz,mechanical and chime as well as a whoop tone.All tones are r€ • easy for the professional to change in the field by the use of switches. The Commander3 Colored Lens Series is shipped with a standard 4”mounting plateti i f ` • which incorporates the popular Super-Slide feature that allows the installer to easily t l` ' ; • test for supervision. The product also features a locking mechanism that secures the -! signal to the bracket without showing any screws. The GE3 Colored Lens Series also "a • features the patented Checkmate"instant voltage verification feature which allows • the installer to check the voltage drop draw and match it against the blueprint. • The Commander3 Colored Lens Series are ANSI/UL1638,ANSI/UL464,CAN/ULC S525 and/or CAN/ULC S526 listed.The Series is also compliant with the rated candela per • the polar dispersion requirements of ANSI/UL 1971. Therefore,the ANSI/UL 1971 • polar plot is equal to the candela listed on the product,no derating was required. Product Listings The GE3 Colored Lens Series is warranted for three years from date of purchase. • SIGNALING - • Standard Features 'C lis ,' x� • Nominal voltage 24 VDC LISTED - Field selectable candela options of 15,30,60,75,and 110 • a Unit Dimensions:5'(12.7 cm)high x 4,5"(11.43 cm)wide x 2.5"(6.35 cm)deep ANSii`t1i.464 and ANSI/UL 1638 Listed • x Lens colors available:amber,blue,green and redCAN/ULC S525 and/or CAN/ULC S526 Listed • Super-Slide'Bracket Ease of Supervision Testing 9 CSFM:7135-0569:135(Horn/Strobes) • - Checkmate-Instant Voltage Verification 7135-0569:136(Strobes) • x Prewire entire system,install mounting bracket,then install signals • Input terminals accept 12 to 18 AWG Patents • . Switch selection for high or low dBA 7,375,617 May 20,2008 • • Switch for 2400 Hz,mechanical,chime and whoop tones Switch for continuous or temporal 3(not available on whoop tone) • - Synchronize strobe and/or horn with Gentex AVSM Control Module Product Compliance • - Silence audible while visual appliance will remain flashing = NEPA 72 Tamperproof re-entrant grill • IBC/IFC/IRC • m Surface mount with the GS8(Gentex Surface Mount Box) s Quality Management System is certified to: m Faceplate available in red or off-white ISO 9001:2008 • m Wall mount • Note:ANSI/UL 1971 is not applicable to emergency communications devices,but • readings were obtained using the measurement • procedure specified under ANSI/UL 1971. l s" •'� //,ice..,.: , •a � .,r.. .;�. " ��`.�.F ,� . .;,.; ,?�. ';.,.. ,✓,�a.,..��.., . .. �,,., ..'�:,y. • • • GES3 Colored Lens Strobe,Selectable Candela Low Profile • • Model Part Number Lens Color Voltage(VDC) Candela _ • GESA24PWR i 904-1335-002 1 Amber i 24 1 15,30,60,75,110 GESA24PWW 1 9041336-002 1 Amber 1 24 1 15,30,60,75,110 0 GESB24PWR 1 904-1337-002 1 Blue 24 i 17 30 60 75,110 • GESB24PWW 1 904-1338-002 1 Blue 24 1 15,30,60 75,110 GESG24PWR 1 904-1339-002 ' Green 24 115,30 60 75 110 • ' GESG24PWW i 904-1340-002 1Green 24 315,30, s_30,60,75,110 • GESR24PWR 1 904-1341-002 1 Red 24 1 15 30,60,75,110 GESR24PWW i 904-1342-002 - Red 24 1 15,30,60,75,110 • GEC3 Colored Lens Horn/Strobe,Selectable Candela Low Profile • • Reverberant Anechoic Room Model Part Number Lens Color Voltage(VDC) Candela dBA at 10ft. dBA at 10ft. 5 GECA24PWR i 904-1327-002 1....... Amber 24... 15 30,60,75,110 1 62-82 dBA 100 dBA GECA24PWW 1 904-1328-002 1 Amber 1 24 1 15,30,60,75,110 1 62-82 dBA 1 100 dBA • GECB24PWR ; 904-1329-002 ', Blue 24 1 15 30,60,75,110 1 62-82 dBA 1 100 dBA . GECB24PWW 1 90 -1330-002 • 1330 002Blue 24 15,30,60,75,110 1 62-82 dBA 100 dBA GECG24PWR 1 904-1331-002 1 Green 1 24 _._ 15,30,60,75,110 i 62-82 dBA 1 100 dBA GECG24PWW _ 904-1332-002 i Green i 24 �15,30,60,75,110 i 62-82 dBA 100 dBA • GECR24PWR 1 904-1333-002 Red 24 1 15,30,60,75,110E 62-82 dBA 1 100 dBA 1 • GECR24PWW 1 904-1334-002 i Red 24 115,30,60,75,110 1 62-82 dBA 1 100 dBA • R=Red Faceplate,W=White Faceplate • Al units are available in plain(no lettering. Plain units are not returnable • Lens colors:A=Amber R=Red B=Blue G=Green ALERT and AGENT bezels available Au order • GE3 Colored Lens Series Strobe Current Ratings • Amber Lens Blue/Green/Red Lens • Current Ratings Current Ratings . Candela 15 cd i 30 cd i 60 cd i 75 cd 1 110 cd 15 cd 1 30 cd 60 cd 75 cd 110 cd UL Max 1 47 mA 1 64 mA i 113 mA i 145 mA ? 178 mA 105 mA 1 130mA j 203mA 1 243mA J, 310mA • • GE3 Colored Lens Series Horn Decibel(dBA)and Current Ratings(mA) 5 Horn Decibel Horn Current . Levels(dBA) Ratings(mA) UL MAX 5 Minimum . Minimum Regulated SPL at 10ft. SPL at 10ft. 24 VDC 411 per per Operating ANSI/UL 464 ANSI/UL 464 Current • Horn Mode (HIGH) (LOW) (HIGH) Temp 3 2400Hz 1 78 dBA l 71 dBA* 28 mA • Temp 3 Mechanical 1 76 dBA 1 70 dBA" 25 mA Temp 3 Chime 1 70 dB * 15 mA • Continuous 2400Hz 1 81 dBA 1 74 dBA. 28 mA 5 Continuous,Mechanical i 80 dBA 1 72 dBA*_, ,_ W 25 mA Continuous Chime 1 70 dBA" 66 dBA" 15 mA • Whoop 1 8'dBA 1 69 dBA* 56 mA • ""Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound • level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application(not applicable when using the chime tone. The chime • tone is always private mode). • GEC3/GES3 -Colored Lens Series • • 0 . • • • • 1 f A • e 1,--- ,„,,,,,,,FI [ \ _______ __.v 7_7\ 1,......._ mil • At.-- I1 0 • 111liab .1 11( .;-&- __---- =0?°,1 ) • WI 12.7 cm M111111* • I [1I ■ In �., 1111111I I_ S II • • JII• 1.4 114cm �1 111( 6.35 cm )I • Gentex Super-Slide® Mounting Bracket • 1 UL Listed Allows the installer to prewire the system,test for system Control Signal Signal • supervision,remove the signal head until occupancy,switch out Panel s+ s+ s- ri+ H- s+ s+ S- H+ H_ • Gentex signals without changing mounting brackets and has Signal Circuit Supervised IS, 6� S 0 0 . ." B S • locking edge connector for snap-in-place installation. \ 0 E NDOFLINE RESISTOR O • Gentex Checkmate° Instant Voltage • Verification • It is often necessary to confirm the voltage drop along a line of devices.The access holes are provided in the back of the terminal U • block to allow the voltage to be measured directly without III O • removing the device.Typically this would be clone at the end of the ` 0 line to confirm design criteria.Most measurements will be taken . 0 ( • using the 5+and S-locations although access is provided to other `v • locations.Notice:Core should be taken to not short the test probes. +",� ` 114:11IOC\ [I • �� —• SCJ s+ Notes {• �. s+ az Operating temperature:32°to 120°F CO'to 49°C) --- 11 CJS g_ E • The GES3/GEC3 Colored Lens Series is not listed for outdoor use ♦ 11 H+ 1..i� i9� • For nominal and peak current across ANSI/UL regulated voltage j ,.•1 .I. II_ — rane for filtered DC power and unfiltered(FWR[Full Wave ray �r • g ��JO Buil Rectified])power,see installation manual • • The sound output for the temporal 3 tone is rated lower since '\. - the time the horn is off is averaged into the sound output rating. CD C23 Cpc? • While the horn is producing a tone in the temporal 3 mode,its sound pressure is the same as the continuous mode. 01D O DO NOT P,INT • o • This appliance is not recommended for use on coded or pulsing ^ ^ J// • signaling circuits I-- — '—�7-1 • • • • • • • • GES3 / GEC3 Colored Lens Series Sec • • Architect & Engineering Specifications • The audible andior visible signal shall be Gentex GES3,GEC3 Colored Lens Series or approved equal and shall be listed by Underwriters • Laboratories(ANSI/UL)per ANSI/UL 1638 and/or ANSI/UL 464 and CAN/ULC S526 and/or CAN/ULCS525 and shall have compliance with the polar dispersion requirements of ANSI/UL 1971.The notification appliance(GEC3 Colored Lens Series)shall produce a peak sound output • of 100 dBA or greater as measured in an anechoic chamber and shall also have the capability to silence the audible signal while leaving • the visible signal energized with the use of a single pair of power wires. Additionally,the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized. The unit shall be capable of being installed so that any • unauthorized attempt to change the candela setting will result in a trouble signal at the fire alarm control panel. The audible/visible and • visible signaling appliance shall also maintain a minimum flash rate of 1 Hz or up to 2 Hz regardless of power input voltage. The appliance shall have an operating current of 47 mA or less at 24 VDC for the 15 Cd strobe circuit with an amber lens. The appliance shall be polarized • to allow for electrical supervision of the system wiring. The unit shall be provided with a mounting bracket with terminals with barriers for • input/output wiring and be able to mount to a single gang or double gang box or double workbox without the use of an adapter plate. The GE3 Colored Lens Series shall be mounted on the wall. The unit shall have an input voltage range of 16-33 volts with either direct current 0 of full wave rectified power for 24 volt models. The appliance shall be capable of testing supervision without disconnecting wires,verify • voltage at the unit without removing unit and be capable of mounting to a surface back box. • • • 0 • • • • • • • tire Protection ProducteOrotipl 10985 ChicagoPthie Zeeland,M.149464 551-0045-Dit ' • • • • • • • • gentex.carn Gone 6 8°"36.8391 Fax 616392-4219 . tmpnrtatit Notice:These have been prepared by Gentestorpon("Centex}for informationat purposes only,are necessarily vas legal advice and should not be used as suth.Centex makes no representations and wartanties,express Of implied,that these matenab are compieteand ascutate,upttomkge,or io complisincewith at relevant locale state and federal g ons and rules materials do not address at legal considerations as there is inevitable uncerta€nt(regarding interkiretaNce of Nws4egufattonsand rules and the application rif such taws regutatians and hies to particular fact patterns,Each person's activities can differently affect the obligations that exist under appticable laws,regulationsor rules, • Therefore,them materials used only for infommtional purposes and should not be used assubstitute for seeking professional fecal advice. foranyaction "- orfailure oact inreliance formation containedi teriat Gentex Corporation reserves the.right..to'makechangestothepraductdatas et dip. • • • • • SYSTEM . • SENSOR • • • SSM/SSV Series aid ; - • Alarm Bells • • • System Sensor's SSM and SSV series alarm bells are40 low current,high decibel notification appliances for • use in fire and burglary systems or other signaling Vim; applications. • • • • Features Reliable Performance.The SSM and SSV series provide loud • Approved for indoor and outdoor use resonant tones.The SSM series operates on 24VDC and are motor• driven,while the SSV series operates on 120VAC utilizing a vibrating •Low current draw • mechanism. •High dB output • •Available in six-inch,eight-inch,and ten-inch sizes Simplified Installation.For indoor use,the SSM and SSV series • mount to a standard four-inch square electrical box.For outdoor •AC and DC models applications,weatherproof back box,model number WBB,is used. • •DC models polarized for use with supervision circuitry • •Mount directly to standard four-inch square electrical box indoors The SSM and SSV series come pre-wired,to reduce installation time. The SSM series incorporates a polarized electrical design for use with •SSM and SSV series come pre-wired supervision circuitry. • • • • • • • • • Agency Listings • UL 0 MEA • LISTED ® APP® approved • 54011 00549 3005255 7135-1653:0217 331-91-4 • • • • • • SSM/SSV Specifications • Architectural/EngineeringSpel fir r /y ' • Model shall be a SSM or SSV Series alarm bell.Bells shall have underdome strikers and operating mechanisms.Gongs on said bells shall be no smaller than • nominal 6"/8%10"(specify size)with an operating voltage of 24VDC or 120VAC(specify by part number).Bells shall be suitable for surface or semi-flush mounting.Outdoor surface mounted installations shall be weatherproof(using optional WBB weatherproof electrical box).Otherwise bells shall mount to • a standard 4-square electrical box having a maximum projection of 211".Bells shall be located as shown on the drawings or as determined by the Authority Having Jurisdiction.Bells shall be listed for indoor/outdoor use by Underwriters Laboratories and the California State Fire Marshal,and approved by Factory • Mutual and MEA. Physi : • Operating Temperature Range —31°F to 140°F • Operating Voltage SSM series:24 VDC SSV series:120 VAC • Termination Provided with 2 sets of leads for in/out wiring Service Use Fire Alarm,General Signaling,Burglar Alarm • Warranty 3 years Electrical Specifications Model Gong Diameter Nominal Voltage Operating Voltage Maximum Current Sound Output(dBA) 411 (inches) Limit • SSM24-6 6 Regulated 24VDC 16 to 33VDC DC-31.1 mA/FWR-53.5mA 82 • SSM24-8 8 Regulated 24VDC 16 to 33VDC DC-31.1 mA/FWR-53.SmA 80 SSM24-10 10 Regulated 24VDC 16 to 33VDC DC-31.1 mA/FWR-53.5mA 81 • SSV120-6 6 Regulated 120VAC 96 to 132VAC 53mA 85 • SSV120-8 8 Regulated 120VAC 96 to 132VAC 53mA 82 SSV120-10 10 Regulated 120VAC 96 to 132VAC 53mA 82 *Sound output measured at Underwriter Laboratories,as specified in UL464 • • • • • •i • • Ordering Information • Model o el N p ICan Dest4tiori SSM24-6 SSM24-6A Bell,6",24VDC,Polarized,82dBA SSM24-8 SSM24-8A Bell,8",24VDC,Polarized,80dBA 4111 SSM24-10 SSM24-10A Bell,10",24VDC,Polarized,81 dBA SSV120-6 SSV120-6A Bell,6",120VAC,85dBA • SSV120-8 SSV120-8A Bell,8",120VAC,82dBA • SSV120-10 SSV120-10A Bell,10",120VAC,82dBA WBB Weatherproof back box for SSM and SSV series,when installed outdoors • • • • • • • SYSTEM ©2011 System Sensor 3825 Ohio Avenue•St.Charles,IL 60174 Prnauttspecfications sobjea to mange without notiee�sit rystemsensorcom for '!\P Phone:800-SENSOR2•Fax:630-377-6495 oJrrent product information,induding the latest version of this data sheet. A05-0260-010.08/11•#2870 •• • • • •• • Additional equipment includes—Control panels,releasing devices, 41 waNTAL I1ipACT remote manual pull stations,corner pulleys,door closures,pres- INERGEN agent is a mixture of three naturally occurring gases:nitro- sure trips,bells and alarms,and pneumatic switches.All or some are gen,argon,and carbon dioxide.As INERGEN agent is derived from required when designing a total system. • gases present in the earth's atmosphere,it exhibits no ozone depleting INERGEN Agent—INERGEN agent is a mixture of three inerting potential,does not contribute to global warming,nor does it contribute (oxygen diluting)gases:52%nitrogen,40%argon,and 8%carbon • unique chemical species with extended atmospheric lifetimes.Because dioxide.INERGEN gas extinguishes fire by lowering the oxygen content INERGEN agent is composed of atmospheric gases,it does not pose below the level that supports combustion.When INERGEN agent is • the problems of toxicity associated with the chemically derived Halon discharged into a room,it introduces the proper mixture of gases that alternative agents. still allow a person to breathe in a reduced oxygen atmosphere. It • actually enhances the body's ability to assimilate oxygen.The normal atmosphere in a room contains 21%oxygen and less than 1%carbon dioxide.If the oxygen content is reduced below 15%,most ordinary 1111 ON combustibles will cease to burn.INERGEN agent will reduce the oxygen content to approximately 12.5%while increasing the carbon • The INERGEN Fire Suppression System,manufactured by Tyco,is an dioxide content to about 3%.The increase in the carbon dioxide content • engineered clean-agent system utilizing a fixed nozzle agent distribu- tionincreases a person's respiration rate and the body's ability to absorb network.The system is designed and installed in accordance with oxygen.Simply stated,the human body is stimulated by the carbon • the National Fire Protection Association(NFPA)Standard 2001,"Clean Agent Fire Extinguishing Systems."When properly designed,the dioxide to breathe more deeply and rapidly to compensate for the lower oxygen content of the atmosphere. INERGEN system will suppress surface burning fire in Class A,B,and Cylinders—The cylinders are constructed,tested,and marked in III C hazards by lowering the oxygen content below the level that supports accordance with applicable Dept.of Transportation(DOT)and the U.S. combustion.• Bureau of Explosives specifications.As a minimum,the cylinders must INERGEN agent has also been tested by Factory Mutual(FM)for meet the requirements of DOT 3AA2300 or 3AA2015+. 411 inerting capabilities.Those tests have shown that INERGEN agent,at Cylinder Assembly—The cylinder assembly is of steel construction design concentrations between 40%and 50%,has successfully inerted with a red standard finish.Four sizes are available to meet specific • mixtures of propane/air,and methane/air. needs. Each is equipped with a pressure seat-type valve equipped with 41 The system can be actuated by detection and control equipment for gauge.The valve is constructed of forged brass and is attached to the automatic system operation along with providing local and remote cylinder providing a leak tight seal.The valve also includes a safety • manual operation as needed.Accessories are used to provide alarms, pressure relief device which provides relief at 2900-3300 psi ventilation control,door closures,or other auxiliary shutdown or (200-228 bar)per CGA test method.Cylinder charging pressure is functions. 2175 psi at 70°F(150 bar at 21 °C).The cylinders are shipped with • a maintenance record card and shipping cap attached.The cap is When INERGEN agent is discharged into a room,it introduces the attached to the threaded collar on the neck of each cylinder to protect • proper mixture of gases that will allow a person to breathe in a reduced the valve while in transit.The cylinder serial number and date of manu- oxygen atmosphere. facture are stamped near the neck of each cylinder. • A system installation and maintenance manual is available containing Electric Actuator—Electric actuation of an agent cylinder is accom- • information on system components and procedures concerning design, plished by an electric actuator interfaced through an AUTOPULSE operation,inspection,maintenance,and recharge. Control System.This actuator can be used in hazardous environments where the ambient temperature range is between 32°F and 130°F • The system is installed and serviced by authorized distributors that are (0°C and 54°C). In auxiliary or override applications,a manual lever trained by the manufacturer. actuator can be installed on top of the actuator. • Basic Use—The INERGEN system is particularly useful for suppressing Manual or Pneumatic Actuators—Manual pneumatic actuators are fires in hazards where an electrically non-conductive medium is essen- available for lever actuation on the cylinder valve.Manual actuation is tial or desirable;where clean-up of other agents presents a problem;or accomplished by pulling the hand lever on the actuator. • where the hazard is normally occupied and requires a non-toxic agent. Selector Valves—Selector valves are used to direct the flow of • The following are typical hazards protected by INERGEN systems: INERGEN agent into a single hazard of a multiple hazard system. a Computer rooms Detection System—The AUTOPULSE Control System is used where • a Subfloors an automatic electronic control system is required to actuate the aaTape storage INERGEN system.This control system is used to control a single fixed • fire suppression or alarm system based on inputs received from fire ® Telecommunication/Switchgear detection devices.The detection circuits can be configured using cross, • a Museums counting,independent or priority-zone(counting)concepts.The control aLibraries system has been tested to the applicable FCC Rules and Regulations for Class A Computing devices. a Normally occupied or unoccupied electronic areas where equipment Nozzles—Nozzles are designeddischarge of INERGEN• to direct the is either very sensitive or irreplaceable agent using the stored pressure from the cylinders.Nozzles are avail- Composition and Materials—The basic system consists of extinguish- able in either 360°or 180°discharge patterns.The system design • ing agent stored in high strength alloy steel cylinders.Various types of specifies the nozzle and orifice size to be used for proper flow rate and actuators,either manual or automatic,are available for release of the distribution pattern.The nozzle selection depends on the hazard and • agent into the hazard area.The agent is distributed and discharged into location to be protected. the hazard area through a network of piping and nozzles.Each nozzle • is drilled with a fixed orifice designed to deliver a uniform discharge to the protected area.On large hazards,where three or more cylinders are • required,a threaded or welded pipe manifold assembly is employed. The cylinder(s)is connected to the distribution piping or the manifold by • means of a flexible discharge bend and check valve assembly. M • AVAILABILITY AND COST • Pressure Reducer—The pressure reducer is required in the distribution piping to restrict the flow of INERGEN agent,thus reducing the agent Availability—INERGEN Systems are sold and serviced through a pressure down stream of the reducer.The pressure reducer contains network of independent distributors located in most states and many a stainless steel orifice plate which is drilled to the specific size hole foreign countries. • required based on the hydraulic calculation.The orifice plate provides Cost—Cost varies with type of system specified,size,and design. readily visible orifice identification.The pressure reducer is available in nine sizes: 1/2 in.,3/4 in., 1 in., 1 1/4 in., 1 1/2 in.,2 in.,2 1/2 in.,3 in., and 4 in.NPT. 'MAINTENANCE iANCE • Maintenance is a vital step in the performance of a fire suppression PRODUCT DESCRIPTION system.As such,it must be performed by an authorized ANSUL distrib • - utor in accordance with NFPA 2001 and the manufacturer's design, Pipe and Fittings—The system manifold must be constructed of installation,recharge,and maintenance manual.When replacing compo411 - Schedule 80 or 160 piping and 2000 or 3000 psi iron fittings,threaded nents on the ANSUL system,use only ANSUL approved parts. or welded.The distribution piping down stream from the orifice union must be constructed of a minimum of Schedule 40 piping with class 300 malleable iron threaded fittings or welded steel fittings.All piping must be black iron of the following type and grade:ASTM A-53 seamless or electric resistance welded,grade A or B,or ASTM A-106 grade A,B, • or C.Do not use ASTM A-120,ASTM A-53 type F or ordinary cast iron pipe or fittings. Limitations—The INERGEN system must be designed and installed within the guidelines of the manufacturer's design,installation,operation, • inspection,recharge,and maintenance manual.The ambient temper- ature limitations are 32°F to 130°F(0°C to 54°C).All AUTOPULSE 0 Control Systems are designed for indoor applications and for tempera- ture ranges between 32°F and 120°F(0°C and 49°C). • • TECHNICAL DATA Applicable Standards:The INERGEN system complies with NFPA Standard 2001,Standard for Clean Agent Fire Extinguishing Systems, 411 and EPA Program SNAP,Significant New Alternate Policy. • The INERGEN System is listed by Underwriters Laboratories, Inc.(UL) and Underwriters Laboratories of Canada(ULC),and is approved by • Factory Mutual(FM). INERGEN Agent is listed by Underwriters Laboratories, Inc.(UL)and • Underwriters Laboratories of Canada(ULC),and is approved by Factory Mutual(FM). • INSTALLATIONS • All system components and accessories must be installed by personnel trained by the manufacturer.All installations must be performed accord- ing to the guidelines stated in the manufacturer's design,installation, • operation,inspection,recharge,and maintenance manual. • •' • • • • • • • • • • Vico • ` i o Copyright©2011 Tyco Fire Protection Products • Fire Protection One Stanton Street +1-715-735-7411 All rights reserved Products Marinette,WI 54143-2542 www.ansul.com Form No.F-9312-11 • • 0 • System Components S ANSUL® U.S.C.G. APPROVAL NO. 162.162/1/0 REV. 4 • A Tyco International Company UL EX-4510 7-14-14 Page 1-5a s = �LJL� , o • Cleanngen`\ Systems 150-Bar CV-98 Valve/Cylinder Shipping Assembly 9 • I Description Component Material Specification • The cylinder is factory filled with INERGEN agent. A single Cylinders • cylinder may be used or multiple cylinders can be mani DOT Specification Steel 3AA2300 folded together to obtain the required quantity of agent for Meets TC3AM176 • total flooding. The cylinder valve can be actuated automat- or TC3AAM176 • ically, pneumatically, and/or manually with approved valve ► UN Specification Steel ISO 9809-1 actuation components. All valves are equipped with an Valve Brass 111) anti-recoil feature. The cylinders are shipped with a maintenance record card Safety Relief Valve Brass and protective shipping cap attached to the threaded neck Valve/Cylinder UL Listed (EX-4510) • of each cylinder. This cap entirely encloses and protects Assembly • the valve while in shipment. Shipping Cap Steel The friction loss through the valve (equivalent length) and 0 flexible discharge bend is equal to 38 ft (11.6 m) of 1/2 in. • Sch. 40 pipe. O Shipping Nominal Cylinder Actual INERGEN Approximate • Assembly SizeAgent Quantity Weight Dimension A Dimension B Part No. ft3 (m3) ft3 (m3) lb (kg) in. (mm) in. (mm) 411 Shipping Assemblies-Red Enamel Paint 0 ' 426147 200 (DOT/TC) (5.7) 205 (5.8) 128 (58) 52.7 (1339) 8.5 (216) 426148 250(DOT/TC) (7.1) 266 (7.5) 169 (77) 57.7 (1466) 9.3 (235) • 426149* 350(DOT/TC) (9.9) 355 (10.1) 217 (98) 60.0 (1516) 10.7 (272) O 426620* 350 (DOT/TC) (9.9) 355 (10.1) 217 (98) 60.5 (1537) 10.5 (268) 441665 350(UN) (9.9) 355 (10.1) 217 (98) 60.5 (1537) 10.5 (268) 1 428646* 435 (DOT/TC) (12.3) 439 (12.4) 260 (118) 66.0 (1676) 11.0 (279) • ,> 426150* 435 (DOT/TC) (12.3) 439 (12.4) 260 (118) 67.0 (1702) 11.0 (279) 441661 435 (UN) (12.3) 439 (12.4) 260 (118) 67.0 (1702) 11.0 (279) ► *These containers are special order:minimum order quantities apply,please call for delivery time. w . �-0CYLINDER � SHIPPING CAP PRESSURE - • GAUGE ,/VALVE SHIPPING CAP • ORD TAG �''`"VALVE rog-` PRESSURE • . v -�- GAUGE SAFETY RELIEF 9 FILL PORT LET y 1 i VALVE ■ HEIGHT TO OUTLET IG �� --) I CENTER A II O / \ \ \r B AO / \ 002252 • 00225, • • • • • System Components U.S.C.G.APPROVAL NO. 162.162/1/0 REV.0 • UL EX-4510 7-14-14 Page 1-5b • CV-98 INERGEN Valve • ► The valve requires no internal maintenance. The valve • is sealed closed and must not be disassembled. If there is • ever a malfunction of the CV-98 valve, the complete valve ► must be returned to Tyco Fire Protection Products. • Note: Use Flexible Discharge Bend(Part No, 427082)when • attaching valve to supply pipe or manifold. • • • • • M • • • • • • • • • • • • • • • • • • • • • • • • • Vico One Stanton Street +1-715-735-7411 Copyright©2014 Tyco Fire Products LP. Vico All rights reserved. Marinette,WI 54143-2542 www.ansul.com Form No.F-98086-04 • • • • • • System Components • :1 ANSUL, U.S.C.G.APPROVAL NO. 162.162/1/0 REV.3 • ATyco(nternat;mnalcompany UL EX-4510 4-16-12 Page 1-41 • In ," • clean agent systems Pressure Switch — 3PDT • • Description • The pressure switch is operated by the INERGEN agent Shipping Assembly • pressure when the system is discharged. The pressure switch can be used to open or close electrical circuits to Part No. Description • . shut down equipment(single or 3-phase) or turn on lights or ► 437900 Pressure switch—3PDT • alarms. The housing is constructed of 16 ga. steel, painted -7 red, and is rated IP65 for dust and water ingress. The 3/8 ,.� • in. NPT brass pressure inlet is used to connect the pres- sure switch to the suppression system. Minimum operating pressure is 50 psi (3.5 bar). • • Component Material Thread Size/Type Electrical Rating Approvals • Pressure Switch Switch: Nickel-plated Brass Conduit Inlets: 10A, 250 VAC UL Listed 411, —3PDT Housing/Cover: G.R. 16 ga steel 3/4 in. and 1/2 in. 15A, 125 VAC (EX-4510) Plunger: Stainless Steel Pressure Inlet: 3/4 HP, 250 VAC • Pressure Port: C37700 Brass 3/8 in. NPT Female 1-, 2-, and 3-phase • •� • 6.0 IN 1 g (152 mm) 4.45 IN. ' • (113 mm) • — � 4 � 0 0 • 01. � g ti • ` 4.51 IN. 411 4.45 IN. �:..:' . O6 (115 mm) - -;11 { r" i (113 mm) 2.751N. ,, (70 mm) --C •ill09 a l o ELECTRICAL 1 0 0 • SCHEMATIC dam.. 9 008978 3.831N. r . 5.251N. r • (97 mm) 1 (133 mm) 008979 1 • ► • a • a • • • i• two One Stanton Street +1-715-735-7411 Copyright©2012 Tyco Fire Products LP. All rights reserved. Marinette,WI 54143 2542 www.ansul.com Form No.F-2012058 0 • • • :l. ANSUL. System Components U.S.C.G.APPROVAL NO. 162.162/1/0 REV. 2 A Tyco International Company UL EX-4510 4-16-12 Page 1-6 ! Iner@r 0 clean agent,\ systems Flexible Discharge Bend 0 Description • The valve Flexible Discharge Bend (Part No. 427082) is a • 5/8 in. (16 mm) I.D. extra-heavy flexible hose which con- Shipping Assembly nects the valve discharge outlet to the fixed piping or head- Part No. Description • er manifold. The discharge bend has a special female 427082 Flexible discharge bend • thread for connecting to the valve outlet and a male 1/2 in. 437919 Gasket • NPT thread for connecting to the fixed piping or manifold. The discharge bend will withstand a pressure of 9000 psi 42430 Gasket(for previous adaptor i, (620.5 bar). Its flexible connection allows for easy align- ► design) ment of multiple cylinder banks to fixed piping. Each bend • has a built-in check valve that prevents loss of agent should II the system discharge while any cylinder is removed. The equivalent length of the valve and hose is equal to 38 ft • (11.6 m) of 1/2 in. Sch. 40 pipe. • • Thread Size/Type Component Material Valve End Manifold End Approvals 0 ► 5/8 in. Flexible SAE 100 R2 Special to 1/2 in. NPT Male UL Listed (EX-4510) 0 Discharge Bend Hose Type AT mate with (5 CV-98 Valve • 0 18 7/8 IN. (479 mm) • FEMALE ADAPTOR ► (SWIVEL,BRASS) 112 IN.NPT • MALE COUPLING CHECK WASHER41 SWAGE ON \ , 7 ini!n//i,9, //r',."a \`�.-.-.-vs-- --,s vi ivy/ VALVE END-� IIIIIIf'',/ • :1 ANSUL System Components U.S.C.G.APPROVAL NO. 162.162/1/0 REV.2 ATyco International Company UL EX-4510 4-16-12 Page 1-19 In 0 a Clean Agent )Systems Stainless Steel Actuation Hose • Description •- The Stainless Steel Actuation Hose is used to connect the • actuation line compression tees between each agent tank. The hose has the same thread, 7/16-20, as the compres- sion tees. The actuation hose allows flexibility between the • rigid actuation piping and the tank valve. 24 IN. (610 mm) • Shipping Assembly 1 Part No. Description %` 110 • > 31809 16 in. (406 mm) Stainless Steel Hose 32335 20 in. (508 mm) Stainless 71fi-20 7/16-20 • Steel Hose 32336 24 in. (609 mm) Stainless Steel Hose 000433 • Component Material Thread Size Approvals • ► Stainless Steel Stainless Steel Female 7/16-20 UL Listed (EX-4510) • Hose (Both ends) • Additional actuation fittings are available: Part No. Description 31810 Male Elbow(7/16-20 x 1/4 in. NPT) 31811 Male Tee (7/16-20 x 7/16-20 x 1/4 in. NPT) • 32338 Male Straight Connector(7/16-20 x 1/4 in. NPT) 418359 Flared Tee (7/16—20 x 7/16—20 x 1/8 in. NPT) 73236 Pilot Valve Actuation Adaptor 32334 Male Elbow(7/16—20 Flare x 1/8 in. NPT) • • • • • • • • • • • A tyCO One Stanton Street +1-715-735-7411 Copyright©2012 Tyco Fire Products LP. Al!rights reserved. Marinette,WI 54143 2542 www.ansul.com Form No.F-98111-02 • • • • :1 ANSUL System Components • U.S.C.G.APPROVAL NO. 162.162/1/0 REV.3 41111 A Tyco International Company UL EX-4510 4-16-12 Page 1-18 mAccaClean B Pilot Valve Actuation Adaptor • • Description 0 The Pilot Valve Actuation Adaptor and fittings are used in ID large INERGEN systems requiring more than one pilot Shipping Assembly • cylinder.This is required in systems where, because of the Part No. Description size of the union orifice, low manifold pressure can be pro- 73236 Pilot valve actuator adaptor 40 duced which is not high enough to adequately operate the > 32334 Male elbow • remaining cylinders on the manifold. > 418359 Flared tee To overcome this, additional pilot cylinders, pneumatically • operated through the pilot actuation port, are required. 40 Refer to system design to determine if additional pilot cylin Component Material Approvals ders are required in the system. Pilot valve Brass UL Listed (EX-4510) • actuator adaptor Note: Systems comprising three or more cylinders must Male elbow Brass UL Listed (EX-4510) use a minimum of two pilot cylinders. • Flared tee Brass UL Listed (EX-4510) • • S 1/4 IN.CHECK VALVE ► �,u_ (PART NO.25627) � ITO MARINE . ACTUATION IIIIIIII.'44m.m. STATION�1,/q'STRAIGHT ADAPTOR ���v • ► 41 la (PART NO.32338) 1110 ► , COR ELBOW PART NO.31810) ow. imhvV, � ? 410 iti. 16 IN.STAINLESS fa) ---(��`� ' Ilri STEEL HOSE ,• i. �� TEE(PART NO.418359) (PART NO.31809)(TYP.) ��'� (TYP.) • ADAPTOR (PART NO. 41 ► 73236)(TYP.) MALE ELBOW(PART ► NO.32334)(TYP.) 5 0036'36 . . . . • 0 .. • Vice One Stanton Street +1-715-735-7411 Copyright 2012 Tyco Fire Products LP. All rights reserved. Marinette,WI 54143 2542 www.ansul.com Form No.F-98099-03 • . • • • • :1 ANSUL� System Components U.S.C.G.APPROVAL NO. 162.162/1/0 REV.3 • A Tyco International Company UL EX-4510 4-16-12 Page 1-34 • • Iflec n[ syste�l Pressure Reducer/Union • • Description • The pressure reducer/union is required to restrict the flow • of INERGEN agent thus reducing the agent pressure down C stream of the union. The 3000 psi (206.9 bar) NSCWP B ~I • union contains a stainless steel orifice plate which is drilled f el to the specific size hole required based on the flow calcula- tion.* The orifice plate provides readily visible orifice identi- 111 f ' -0. I% • fication. The orifice union is available in six sizes: • 1/2 in., 3/4 in., 1 in., 1 1/4 in., 1 1/2 in., and 2 in. NPT. -1111 0 ' — \ I' A All pressure reducer/unions must be installed in the piping s • with the orifice identification tab on the pressure inlet side DIRECTION t N till. NN0of the system. The 1 1/4 in., 1 1/2 in. and 2 in. orifice OF FLOW S.l unions must be installed per the direction of the flow arrow 1111 stamped on the body. VISIBLE ORIFICE P Y IDENTIFICATION 002197 • • Shipping Assembly A B C . Part No. Description in. (mm) in. (mm) in. (mm) 416677 1/2 in. NPT pressure reducer/union 2.06 (52) 1.18 (29) 1.95 (49) • 416678 3/4 in. NPT pressure reducer/union 2.38 (61) 1.50 (38) 2.38 (61) • > 416679 1 in. NPT pressure reducer/union 2.63 (67) 1.78 (45) 2.77 (70) 416680 1 1/4 in. NPT pressure reducer/union 2.94 (75) 2.04 (52) 3.31 (84) • 416681 1 1/2 in. NPT pressure reducer/union 3.31 (84) 2.31 (59) 3.70 (94) 1110 416682 2 in. NPT pressure reducer/union 3.56 (90) 2.85 (72) 4.39 (112) • • Component Material Thread Size Approvals ► Pressure Reducer/Union Body: Forged Steel 1/2, 3/4, 1, 1 1/4, 1 1/2, 2 in. NPT UL Listed (EX-4510) • Orifice Plate: Stainless Steel le • *Orifice diameter must be specified when placing order. IlkNote:Refer to"Nozzle/Pressure Reducer Range Chart"in Design Section for detailed orifice range information. • • 0 • • • • • I, 5 Vico One Stanton Street +1-715-735-7411 Copyright 2012 Tyco Fire Products LP. All rights reserved. Marinette,WI 54143 2542 www.ansul.com Form No.F-98112-03 • • • • • :l ANSUL System Components U.S.C.G.APPROVAL NO. 162.162/1/0 REV.3 A Tyo nre,aro a Company UL EX-4510 4-16-12 Page 1-38 0 LflAe!2S1 360° Discharge Nozzle •• Description 4111 Discharge nozzles are designed to direct the discharge of Shipping Assembly • INERGEN agent using the stored pressure from the cylin- Part No. Description 0 ders. Ten sizes of nozzles are available.The system design specifies the orifice size to be used for proper flow rate and 417908 1/4 in. NPT nozzle III distribution pattern*. The nozzle selection depends on the 417723 3/8 in. NPT nozzle • hazard and location to be protected. Standard nozzles are 417362 1/2 in. NPT nozzle constructed of brass. 417363 3/4 in. NPT nozzle • Note: 2, 2 1/2 and 3 in. nozzles are not recommended in -- - 417364 1 in. NPT nozzle areas that are subject to damage by high velocity dis- 417365 1 1/4 in. NPT nozzle charges. 417366 1 1/2 in. NPT nozzle • 426155 2 in. NPT nozzle • 426156 2 1/2 in. NPT nozzle • 426137 3 in. NPT nozzle B • II Component Material Thread Size Approvals • Nozzle Body: 1/4, 3/8, 1/2, UL Listed Brass 3/4, 1, 1 1/4, (EX-4510) / 0 1 1/2, 2, 2 1/2, 0 rib 3 NPT 0 % Lir 0 002199 A r 0 • ► 'Orifice diameter must be specified when ordering nozzle. 5 Note:Refer to"Nozzle/Pressure Reducer Range Chart"in Design Section for • detailed orifice range information. A B C Size in. (mm) in (mm) in. (mm) Hex • ► 1/4 in. 5/8 (16) 1 9/16 (40) 21/32 (17) 5/8 IP 3/8 in. 3/4 (19) 1 5/8 (41) 23/32 (18) 3/4 • 1/2 in. 15/16 (24) 1 31/32 (50) 27/32 (21) 15/16 3/4 in. 1 1/8 (29) 2 5/32 (55) 7/8 (22) 1 1/8 • 1 in. 1 13/32 (36) 2 9/16 (65) 1 (25) 1 7/16 1 1/4 in. 1 3/4 (44) 2 3/4 (70) 1 1/16 (27) 1 3/4 • 1 1/2 in. 2 (51) 2 31/32 (75) 1 1/16 (27) 2 ID 2 in. 2 3/8 (60) 3 (76) 1 (25) 2 3/8 2 1/2 in. 3 (76) 3 1/2 (89) 1 (25) 3 • ► 3 in. 3 1/2 (89) 4 1/8 (105) 1 1/4 (32) 3 1/2 • • Vico One Stanton Street +1-715-735-7411 Copyright 2012 Tyco Fire Products LP. All rights reserved. Marinette,WI 54143-2542 www.ansul.com Form No.F-98114-03 • • • • • • - System Components • a ANSUL U.S.C.G.APPROVAL NO. 162.162/1/0 REV. 2 O A7ycolntematlonalCompany UL EX-4510 4-16-12 Page 1-45a • 4110 �Iner@ Agent� sLms Cylinder Bracketing . • • Description • The cylinder bracketing is designed to rigidly support the coating. Uprights and back frame assemblies can be bolted • installed INERGEN agent cylinders.The bracketing compo- or welded together, which ever makes the installation more nents are constructed of heavy structural steel. Bracket convenient. 5 assemblies are available in modules for two to six cylinders and can also be connected together for any combination Component Material Approvals over six. Bracketing can be assembled to support single . Bracketing Steel UL Listed (EX-4510) • row, double row or back-to-back rows of cylinders. Bracketing components are painted with a red enamel 4, • Shipping Assembly 0 Part No. Description • 45120 200 ft3(5.7 m3) cylinder strap(single cylinder) • 45244 200 ft3 (5.7 m3)cylinder channel with nuts and bolts(single cylinder) 45121 250 ft3 (7.1 m3)cylinder strap (single cylinder) • 45261 250 ft3(7.1 m3)cylinder channel with nuts and bolts(single cylinder) • 45122 350 ft3(9.9 m3)cylinder strap(single cylinder) 45245 350 ft3(9.9 m3) cylinder channel with nuts and bolts (single cylinder) • 427704 435 ft3(12.3 m3)cylinder strap with padding (single cylinder) • 427705 435 ft3 (12.3 m3)cylinder channel with nuts, bolts, saddle, and padding (single cylinder) • 79638 Back frame assembly(2 cylinder) > 79639 Back frame assembly(3 cylinder) • 79640 Back frame assembly(4 cylinder) • 79641 Back frame assembly(5 cylinder) 79642 Back frame assembly(6 cylinder) > 73257 Upright for 200, 250, 350, and 435 ft3 cylinders(used either for right side, left side or center(center upright • required when connecting seven or more cylinders in a row)) . --- 73553 Single row or back-to-back row bracket foot(left side) > 73554 Single row or back-to-back row bracket foot(right side) • 73555 Double row bracket foot(left side) • 73556 Double row bracket foot(right side) 418508 Center upright foot • 79413 Connector(required to hook together back frames for seven or more cylinders) • 73250 10.5 in. (267 mm)carriage bolt with lockwasher and nut(for single row 200 ft3(5.7 m3)cylinders) 73251 11 in (279 mm) carriage bolt with lockwasher and nut(for single row 250 ft3(7.1 m3) cylinders) • 73252 12.5 in. (318 mm)carriage bolt with lockwasher and nut(for single row 350 ft3(9.9 m3) and 425 ft3 • (12.0 m3)cylinders) > 418502 13 in. (330 mm)carriage bolt with lockwasher and nut(for single row 435 ft3 (12.3 m3)cylinders) • 73253 21 in. (533 mm)carriage bolt with lockwasher and nut(for double row 200 ft3 (5.7 m3) cylinders) • 73254 22 in. (559 mm)carriage bolt with lockwasher and nut(for double row 250 ft3(7.1 m3)cylinders) 73255 26 in. (660 mm)carriage bolt with lockwasher and nut(for double row 350 ft3 (9.9 m3)and 425 ft3 Ili (12.0 m3)cylinders) • 418503 27 in. (686 mm)carriage bolt with lockwasher and nut(for double row 435 ft3(12.3 m3)cylinders) • • • 4111• • • • System Components U.S.C.G.APPROVAL NO. 162.162/1/0 REV.2 • UL EX-4510 4-16-12 Page 1-45b • • Shipping Assembly • Part No. Description • 73091 Cylinder clamp(2 cylinders) • > 73092 Cylinder clamp(3 cylinders) 71683 Weigh rail support—single row • 71682 Weigh rail support—double row , 71684 Weigh rail support—back-to-back rows • 423027 Weigh rail support back-to-back double row • • Multi-Cylinder Single Cylinder • • 9 /UPRIGHT • • II ;-:1.- I• %:I ,,- JL " ' `1 • `IJ .• 4 4 I i� .. t > I t I .3\ t tl I I • ' I I 1 I BACK FRAME` J� t 11 II II� 1p% • f ii i i I I �1�r CYLINDER CLAMP` I II II s�•j • I II I .lioil;40 CARRIAGE BOLT • i _ ,I WITH NUT AND 1 /` I LOCKWASHER i1 II • II 1 II ith, lici,-- lik RIGHT / CLAMP • I I L,,, /BRACKET FOOT • I f CHANNEL I 1\�-�f ' • -- • '�-- • �t 1 • ,LEFT BRACKET FOOT 004386 • *Note:Two sets of cylinder clamps and back frame assemblies are required to secure cylinders. • • • • • Vic© One Stanton Street +1-715-735-7411 Copyright,t)2012 Tyco Fire Products LP. . All rights reserved. Marinette,WI 54143 2542 www.ansul.com Form No.F-98116-02 • • .a, •si5r x , _,..A.. -- — L , .itt ,4, •-„ ... * , , '.- - .» 1 f � .fi y ,' ` y'-ry•'�R+ § fz�- IWC .„ -9. , , L......) 0 (2 ,. , ON iiii ic ` i' ' , -,,, • *,. \ r ,,,.,. ITS I, • .• ... t 0.. "Cl .4,,, \ or C litli C i ... ea Iiii s, ATAL ,k ,.,- - , , \ -,,, \ - ",,,,, ..., 0 , t . •...t !ATM;' - \l, TeN '4, , ''',, 0 ... i 1 .f 115 : iio 6:1-- ' ---vr---vor—mti = _ ` " 0 ez C 0 rt 0 LI k t.,,,`,4,4.!',.<. ' x 1 If it, ..Z:ll in •••:, lk. ' 1 ' . 41( i • -i I., \:::: , . It .fl t • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 111/ III pipe standard - -- 0 ill Wheatland Tube is known as a leader in the standard '\ • A53 cw and ERW pipe industry. We've been producing tube and pipe F, for more than 75 years and our reputation for qualityfp - and durability is unmatched. We're the only full line b producer of continuous welded and electric �, ' resistance weld 1/4"to 12" pipe, and we set the P standards worldwide for hot dip galvanized products. • We produce from 1/ 4"to 12" nominal sizes and stock 1/8"to 12" pipe sizes in a variety of ASTM standards so we can meet all of your requirements. • UL Listed; FM Approved : NSF61 • Suitable for Welding,Threading, • • Wheatland offers over 350 different combinations of Grooving and Bending finish, end treatments and lengths on our standard • Produced to ASTM A53A 53M, Federal pipe. We're strategically located and carry a large Specification WW P404 and ASME B3o.l0M • inventory so we can ship quickly to satisfy your • delivery schedules. Hydrostatic Testing We're the only CW producer in the North America. Hydrostatic test pressures for plain end pipe are indicated below. +� Standard Extra Strong • • Hot-Dipped Galvanized NPS Weight-PSI Weight-PSI 1/2 through 1 1500 1500 Our standard process is to galvanize to the ASTM A53 1 1/4 1 1/2 2000 2000 40 requirements. 2 through 3 2500 2500 40 3 1/2 4 2800 2800ISO Surface and End Finishes Tensile Requirements • Surface Finishes: black, passivate, galvanized, S uncoated, pickled and oiled, pickled, bare and Tensile Strength, min. 48,000 psi soluble oil. Yield Strength, min. 30,000 psi Elongation in 2" Refer to A 53 table x 4.1, latest S • End Finishes: plain ends, roll groove, cut groove, revisions ASTM A53/A 53M • threaded and coupled, and threads only(one or both ends). Bending Test- L • ess than NPS 2" • Choose From a Full Line of Standard Pipe Degree Diameter of Bend of Mandrel 111 ASTM A53 is used for mechanical and low pressure Standard 90° 12 x outside pipe diameter41 applications and in ordinary uses in steam, water, gas Close Coiling 90° 8 x outside pipe diameter41 and air lines. It can be formed and welded. Our products include: Flattening Test- NPS 2 'h"and Greater • A53 rt S i As a test for quality of the weld, position the weld at , 41 • Type F Grade A 90°from the direction of force and flatten until the • Black, Passivate, Bare, Pickled and Oiled, OD is 3/a of the original outside diameter. No cracks and Hot dipped Galvanized shall occur along the inside or outside surface of the 41 • Sizes; 1/2" 4" weld. • • Standard and Extra Heavy S • MIC Shield Coatings Compatible with CPVC • • 0 • • • • Dimensions and Weight Chart - ASTM A 53 Type • • STANDARD (SCHEDULE 40) BLACK PLAIN END Nominal Size 0,D,. Inches Nominal Wall Weight/Lb, Ft. • 2" 2.375 .154 3.66 • 2-1/2" 2.875 .203 5.80 • 3" 3.500 .216 7.58 4" 4.500 .237 10,88 • 5" 5.563 .258 14.63 • 6" 6.625 .280 18.99 • 8" 8.625 .322 28.58 10" 10.750 .365 40.52 • 12" 12.750 .375 49.61 • A53 Electric-Resistance WeldTensile Requirements • Type E, Grade B • Black and hot-dipped galvanized Tensile Strength, min. 60, 000 psi • Nominal Sizes: Schedule 40 2" - 12" Yield Strength, min. 35,000 psi • • UL Listed; FM Approved . • Suitable for welding, threading and grooving Bending Test (Cold) • Produced to ASTM A 53/53M, Federal Specification • WW-P404 and ASME B36,10M. For NPS 2 and under • Degree of Bend 90° Hydrostatic Testing and Diameter of Mandrel 12 x outside pipe diameter • Nondestructive Electric Testing • Flattening Test Hydrostatic inspection test pressures for plain-end 1110 pipe are listed in Table X 2.2 of the A53/A 53M As a test for ductility of the weld for pipe 2-1/2" NPS • specification. Test pressures shall be maintained for a and larger, position the weld at 0°and alternately at • minimum of five seconds. 90°to the direction of force and flatten until the OD is 2/3 of the original outside diameter. No cracks shall • Nondestructive electric testing of the weld seam is occur along the inside or outside surface of the weld. • required on each length of ERW pipe NPS 2 and larger. All of our facilities have quality systems in • place. At a minimum, they're registered to • ISO 9001:2008 Quality Management Systems. • i , • • U • f { • • 40 • • • • Dimensions and Weight Chart - ASTM 3 TyF II" BLACK PLAIN END • Nominal OD Sch. 40 Sch. 80 Size Inches Wall Inches Weight Lb./Ft. Wall Inches Weight Lb./Ft. 1/2" 0.84 0.109 0.85 0.147 1.09 • 3/4" 1.05 0.113 1.13 0.154 1.48 • 1" 1.315 0.133 1.68 0.179 2.17 • 1-1/4" 1.66 0.14 2.27 0.191 3 1-1/2" 1.9 0.145 2.72 0.2 3.63 2" 2.375 0.154 3.66 0.218 5.03 • 2-1/2" 2,875 0.203 5.8 0.276 7.67 • 3" 3.5 0.216 7.58 0.3 10.26 3-1/2" 4 0.226 9.12 0.318 12.52 4" 4.5 0.237 10.8 0.337 15 • • I Standard Pipe Schedule 40 - ASTM A53 Grades A and B M Outside Diameter Inside Diameter Wall Thickness Nominal Weight(Mass) per unit Length • NPS DN Threads& Threads& • Designator Designator (Inches) (mm) (Inches) (mm) (Inches) (mm) Plain End Plain End Couplings Couplings gra (Ib/ft) (kg/m) (Ib/ff) (kg/m • 1/8" 6 0.405 10.3 0.269 6.8 0.068 1.73 0.24 0.37 0.25 0.37 • 1/4" 8 0.540 13.7 0.364 9.2 0.088 2.24 0.43 0.63 0.43 0.63 • 3/8" 10 0.675 17.1 0.493 12.5 0.091 2.31 0.57 0.84 0.57 0.84 • 1/2' 15 0.840 21.3 0.622 15.8 0.109 2.77 0.85 1.27 0.86 1.27 ISO 3/4" 20 1.050 26.7 0.824 20.9 0.113 2.87 1.13 1.69 1.14 1.69 • 1" 25 1.315 33.4 1.049 26.6 0.133 3.38 1.68 2.50 1.69 2.50 • 1-1/4" 32 1.660 42.2 1.380 35.1 0.140 3.56 2.27 3.39 2.28 3.40 • 1-1/2" 40 1.900 48.3 1.610 40.9 0.145 3.68 2.72 4.05 2.74 4.04 • • 2" 50 2.375 60.3 2.067 52.5 0.154 3.91 3.66 5.44 3.68 5.46 • 2-1/2" 65 2.875 73.0 2.469 62.7 0.203 5.16 5.80 8.63 5.85 8.67 3" 80 3.500 88.9 3.068 77.9 0.216 5.49 7.58 11.29 7.68 11.35 • 3-1/2" 90 4.000 101.6 3.548 90.1 0.226 5.74 9.12 13.57 9.27 13.71 • 4" 100 4.500 114.3 4.026 102.3 0.237 6.02 10.8 16.07 10.92 16.23 . 5" 125 5.563 141.3 5.047 158.2 0.258 6.55 14.63 21.77 14.90 22.07 • 6" 150 6.625 168.3 6.065 154.1 0.280 7.11 18.99 28.26 19.34 28.58 • 8" 200 8.625 219.1 7.981 202.7 0.322 8.18 28.58 42.55 29.35 43.73 is 10" 250 10.750 273.0 10.020 254.5 0.365 9.27 40.52 60.29 41.49 63.36 • L 12' 300 12.750 323.8 12.000 304.8 0.375 9.52 49.61 73.78 51.28 76.21 • • 0 • • • • • Extra Heavy Pipe Schedule 80 - ASTM A53• Type • Outside Diameter Inside Diameter Wall Thickness Nominal Weight(Mass) per unit Length • NPS DN • Designator Designator Plain End Plain End Threads& Threads& (Inches) (mm) (Inches) (mm) (Inches) (mm) (lb/ff) (kg/m) Couplings Couplings • (lb/ft) (kg/m • 1/8" 6 0.405 10.3 0.215 5.5 0.095 2.41 0.31 0.47 0.32 0.46 • 1/4' 8 0.540 13.7 0.302 7.7 0.119 3.02 0.54 0.80 0.54 0.80 • • 3/8" 10 0.675 17.1 0.423 10.7 0.126 3.20 0.74 1.10 0.74 1.10 • 1/2'' 15 0.840 21.3 0.549 13.9 0.147 3.73 1.09 1.62 1.09 1.62 • 3/4" 20 1.050 26.7 0.742 18.8 0.154 3.91 1.48 2.20 1.48 2.21 • • 1" 25 1:315 33.4 0.957 24.3 0.179 4.55 2.17 3.24 2.19 3.25 . • 1-1/4" 32 1.660 42.2 1.278 32.5 0.191 4.85 3.00 4.47 3.03 4.49 • • 1-1/2'' 40 1.900 48.3 1.500 38.1 0.200 5.08 3.63 5.41 3.65 5.39 • 2" 50 2.375 60.3 1.939 49.3 0.218 5.54 5.03 7.48 5.08 7.55 • 2-1/2" 65 2.875 73.0 2.323 59.0 0.276 7.01 7.67 11.41 7.75 11.52 • • 3" 80 3.500 88.9 2.900 73.7 0.300 7.62 10.26 15.27 10.35 15.39 • 3-1/2" 90 4.000 101.6 3.364 85.4 0.318 8:08 12.52 18.63 12.67 18.82 410 4" 100 4.500 114.3 3.826 97.2 0.337 8.56 15.00 22.32 15.20 22.60 • • • Permissible Variations - ASTM A53 Gradesand E • • Permissible Variations for ASTM A53 Grades A and B Pipe • 0.D. Over Under • NPS 1/8 to 1-1/2 1/64" 1/64" DN 6 to 40 (0.4mm) (0.4mm) • Outside Diameter NPS 2 and up DN 50 and up 1% 1% • • Wall Thickness at Any Point 12.50% • • Weight 10% 10% • Mechanical Properties • Grade A:Yield 30,000 (205 Mpa) psi minimum Tensile:48,000 psi (330 Mpa) minimum • Grade B:Yield 35,000 (240 Mpa) psi minimum Tensile: 60,000 psi (415 Mpa) minimum 0 • • PICTORIAL TABLE OF CONTE " II • Forged Steel • 4,-,:,',',:I' oo � • • • v! FORGED STEEL FITTINGS — CLASS 2000 THREADED • •• Fig. 2101 Fig. 2102 Fig. 2103 Fig. 2104 90°Elbow 45°Elbow Tee Cross • Size Range:'/4"thru 4" Size Range:1/4"thru 3" Size Range:'/4"thru 4" Size Range: 1/4"thru 3" A Page 91 Page 91 ,, ,r v,,,, ,,.�, . Page 92>.. Page 92.., °�, • FORGED STEEL FITTINGS — CLASS 3000 THREADED 4 , k. Fig. 2111 Fig. 2112 Fig.2114 IF Fig. 2115 Fig. 2113 90°Elbow 45°Elbow Tee Cross 90°Street Elbow •• Size Range:1/8''thru 4" Size Range:1/(4''thru 4" Size Range:'/e°thru 4" Size Range:1/8"thru 4" Size Range: 1/8"thru 2" I Page 93 Page 93 Page 93 Page 94 Page 94 • f ,'Nrv,. .��..,��.��..••: ,.,.r: ,�roa,>,. .:°..:. \ • 0 • '' 0 Fig. 2116 Fig. 2117 Fig.2119 Fig. 2118 k Fig. 2120 Lateral 1 Coupling Half Coupling Reducing Coupling Pipe Cap • Size Range:'/2"thru 2" 1 Size Range:1/8"thru 4" Size Range:'/8"thru 4" "Size Range:'/4"x'/8"thru 4"x 1'/2 a Size Range:1/8"thru 4" Page 94 I Page 95 Page 95 Page 96 Page 96 • , ,,, „.„ FORGED STEEL FITTINGS — CLASS 6000THREADED •• • , , ,,,. „. , ,, , „„ , ..„, , ‘ ,,,, „ , • 1 .....,:,....,,,,..„, .„ ,,, • ,„ , :„. • , t ,, , ...,.... 90°Elbow 45°Elbow Tee 34 Fig. 2135 Fig. 2133 Fig.2131 Fig.2132 Fig. 21 • ICross 90°Street Elbow 1 Size Range:1/8"thru 4" " Size Range:1/8"thru 4" Size Range:1/8'thru 4" Size Range:'/8 thru 4" Size Range: 1/8"thru 11/2" • Page 97 Page 97 Page 97 Page 98 Page 98 qua0 -=:."''',. .., •'::'',' r r Fig. • 2136 Fig. 2137 Fig.2141 Fig. 2138 Fig. 2143 • Lateral Coupling Half Coupling Reducing Coupling y Pipe Cap * Size Range:1/2"thru 11/2" > Size Range:'/8"thru 4" Size Range:1/8"thru 4" I Size Range:1/4"x'/8"thru 4"x 2" Size Range:1/8"thru 4' ;, • Page 98 I Page 99 Page 99 , Page 100 Page 100 • • 12 ^ ttw.anvilint .com' PF-11.13 • .,,,,...... \� /%ANVIL • • , . PICTORIAL TABLE OF CONTENTS 11 • • Forged teel (Continued) • • GED STEEL I TINGS FORGED STEEL FITTINGS • CLASS 3000 SOCKET WELD CLASS 6000 SOCKET WELD I • • Fig. 2150 Fig. 2151 Fig. 2152 Fig.2170 a Fig. 2171 Fig. 2172 90°Elbow 45°Elbow Tee 90°Elbow 45°Elbow Tee Size Range:'/e'thru 4 Size Range:1/e thru 4" Size Range:1/8"thru 4" Size Range:'/2"thru 4" Size Range:'/2"thru 4" Size Range:'/2"thru 4"• Page 101 Page 101 Page 102 Page 106 I Page 106 Page 107 r • Fig. 2153 Fig. 2158 Fig.2154 i Fig. 2173 Fig. 2178 Fig.2174 • Cross z Lateral 1, Coupling , Cross Lateral Coupling Size Range:'/s"thru 4" Size Range: 1/2"thru 2" Size Range:'/s"thru 4" Size Range:1/2"thru 2" Size Range: 1/2"thru 11/2" Size Range:1/2"thru 4" iii , Page 102 Page 103 Page 103 Page 107 Page 107 Q Page 108 • / '''''' ,, ' 2 1 '''' iiV'','" ' : 1 :kAlpi. .,, . i' 'o, l• - ',,,;,,,..,, 1 : v#0-, \ y • 1 Fig. 2155 '::::. Fig. 2156 Fig. 2157 Fig. 2175 Fig. 2176 Fig. 2177 • i Half Coupling Reducing Coupling Pipe Cap Half Coupling Reducing Coupling Pipe Cap Size Range:'/s"thru 4" Size Range: Size Range:'/s"thru 4" Size Range:'/2"thru 4" Size Range: Size Range:'/2"thru 4" • Page 104 1/4'x'/s thru 4'x 2" Page 105 Page 108 i 1/2"x'/4 thru 4"x 2" Page 109 • Page 104 i Page 109 • • FORGED STEEL FITTINGS — HIGH PRESSURE PLUGS & BUSHINGS • • Fig.2122 Fig. 2142 Fig. 2121 Fig. 2139 Fig. 2140 • Square Head Plug Hex Head Plug Round Head Plug Hex Head Bushing Flush Bushing Size Range. /8 thru 4" Size Range:'/s"thru 4" Size Range. /13 thru 4 Size Range. /4 x'/e"thru 4"x 1'/2" Size Range. /4 x'/e"thru 2"x'/4' 0 • Page 110 Page 110 Page 110 Page 111 Page 111 III • • • • • • • • • o • ( )41M/IL: wwa�ntl.co 13 PF-11.13 • • Eli PICTORIAL TABLE OF CONTENTS II • Forged Steel (Continued) — Anvilets • • FORGED STEEL FITTINGS FORGED STEEL UNIONS • SOCKET WELD REDUCER INSERTS „,,,,,„...„.„„_,,,,,,..„.„:„,,,,,_______1. • . .. Class 3000 Class 3000 y Class 6000 .,. \\\\ • For use with Sch.40&80 Pipe For use with Sch.160 Pipe ., r Size Range:l/2 x1/4”thru 3"x 21/2 Size Range:3/4"x 1/4'thru 2"x11/4" Y Page 112 Page 113 • • Fig. 2125 Fig.2126 • UNIVERSAL ELB L T Threaded Union Socket Weld Union Size Range:'/4"thru 3" Size Range:1/d'thru 3" •.•. • .,.....•' , I ;',it,, Page 114 Page 114 Class 6000 • „ .,... Fig.2127.ti<.,. dig. 4yH • Threaded Union Socket Weld Union r. Class 3000&6000–Buttweld,Threaded& Socket-Weld Size Range:'/4"thru 2" Size Range:'/4"thru 2" • Class 3000 Threaded&SocketWeld/Standard&XS/XH Buttweld Page 115 Page 115 I.1 Size Range:1/z°thru 2" ,d, daa.a,..a.�.. .,, .A..••L�.:e ,�, .,,, • Class 6000 Threaded&SocketWeld • Size R '/Z thru UNIVERSAL FORGED STEEL ANVILETS { ange Page 122 • Buttweld .... T.-,,,--: • LATERAL ANVILET Standard Extra Strong i XXS,Sch.160 • Size Range:1/4"thru 24 Size Range:1/6"thru 24' Size Range:1/2'thru 4 "" Page 117 Page 117 Page 118 • 1. Class 3000 Buttweld&Threaded Class 3000 Standard/XS Butt Weld Threaded Size Range:'/z"thru 2" �Ar • Class 3000 Threaded/Standard k. Size Range:112"thru 2" • Page 123 . 4: „ Class 3000 Class 6000 I FLAT E Size Range:'/4"thru 4' Size Range:1/2"thru 2" III Page 119 Page 119 Class 3000 Threaded, Buttweld &Socket-Weld • Size Range:'/4"thru 3" Socket-Weld Page 124 t • • • Class 3000 Class 6000 • Size Range:118"thru 4" Size Range:1/2"thru 2" Page 120 Page 120 • • • • • • �NVIL • PF-11.13 • 1111 i allif FORGED STEEL FITTINGS . 1M , • � r ', x�r`'4`��� ..may .<� tea: � . .,,„. ,., , ter; 3 ��. --,,,,.... \\ Iia €..,, �,.; `€ \ . g . .:, p ',:s4A,,'•",....;,,. 1,:ft.t. ,,,N:4„,, ','':::S.,'''S.'z'',Pk ' a ii• • '4 .--,,,:'-'1,13.Y1,14''''' i',','"'''' "-- '-,.,' .!,;-:1'..cii-f- -11-4 '----v-- • / • • Materials Dimensions • The steel for Anvil Forged Carbon Steel Fittings consists of forging, bars, seamless pipe ASME B16.11,unless otherwise noted or tubes which conform to the requirements for melting process,chemical composition • and mechanical properties of ASTM A105. Threads • ANSI/ASME B1.20.1 NPT Threads Design Basis • ASME B16.11 -Forged fittings,socket-weld and threaded • • • Forged Steel Fittings Reducing Fittings • In accordance with ASME standard B16.11 - "Forged Fittings, Reducing elbows,tees and crosses are available in both threaded Socket Welding and Threaded"this table shows the schedule of and socket-welding. • pipe corresponding to each class of fitting for rating purposes. On reducing tees and crosses give the size of the largest run • opening; then give the opposite opening. Ona tee give the PRESSURE RATINGS branch size last.On a cross give the largest side out41, let third and Schedule the opposite opening last. • Class I N.P.T. S.W. suarim • 2000 80 — imeNvio, 711:11,,,9c, _,, Branch ` - Outtllet 3000 160 80 : '� • 6000 XXS/XXH 160 thx3/ax1�/a �411 1Yx/4X1/4x1/2 TEE CROSS IPASME B16.11 provides that the maximum allowable pressure of III a fitting be computed in accordance with the applicable piping ...-v 19 code or regulation for straight seamless pipe or for material of side l Branch Outlet • equivalent composition and mechanical properties to the fitting. 32 K Any corrosion or mechanical allowances and any reduction in �, - �`< • allowable stress due to temperature or other service conditions 36 B x 19 x 32 mm 36 38 x 19 x 32 x 13 mm • must be applied to the pipe and fitting alike. TEE CROSS • • Standards and Specifications Dimensions Material Thread Pressure Rating • FOR I STEEL THEADtD'tin"INGS 411 Class 2000,3000,6000 ASME 816,11• ASTM A105,ASTM Al 82,ASTM A350 ASMEB1.20.1+ ASME B16.11• • •an American National standard(ANSI), +ASME 81.20.1 was ANSI B2.1 90 anviiintl. om �� ANVIL I L PF-11.13 411 • FORGED STEEL FITTINGS 1 • • Forged SteelFittings 0 • Class 2000 Threaded • .12 • FIGURE 2101 Size A H Unit Weight • 90° Elbows NPS " ON in mm in mm lbs kg • /48 0.81 21 0.88 22 0.18 0.08 • V • • "! % 10 0.97 25 1.00 25 0.28 0.13 • 1/2 15 1.12 28 1.31 33 0.55 0.25 • 3/420 1.31 33 1.50 38 0.72 0.33 .t • ELL- ?...In 25 1.50 38 1.81 46 1.22 0.55 y • • 11/4 32 1.75 44 2.19 56 1.65 0.75 F • EA- 1'/2 40 2.00 51 2.44 62 2.12 0.96 ,. SI w. • T2 50 2.38 60 2.97 75 3.78 1.71 ° H III- __ • i 21/2 65 3.00 76 3.62 92 6.50 2.95 c • 3 80 3.38 86 4.31 109 11.10 5.03 �" • a • 4 100 4.19 106 5.75 146 22.30 10.11 I • • FIGURE 2102 Size C H Unit Weight i ' 45° Elbows g • NPS ON in mm in mm lbs kg • 1/4 8 0.69 17 0.88 22 0.16 0.07 • • % 10 0.75 19 1.00 25 0.25 0.11 _sis • '/2 15 0.88 22 1.31 33 0.48 0.22 • 3/4 20 1.00 25 1.50 38 0.57 0.26 • 1 25 1.12 28 1.81 46 0.88 0.40 g • cL' • 11/4 32 1.31 33 2.19 56 1.32 0.60 -g- . m • /Rt 1 Y2 40 1.38 35 2.44 62 1.62 0.73 •• \` 2 50 1.69 43 2.97 75 2.83 1.28 • 212 65 2.06 52 3.62 92 7.70 3.49 • 3 80 2.50 64 4.31 109 12.00 5.44 • • • (0)ANVIL www.anvilintl.com 91 • PF-6.13 • • IIM FORGED STEEL FITTINGS • Forged tee Fittings • Class 2000 Threaded • • FIGURE 2103 Size A H Unit Weight • Tees • NPS ON in mm in mm lbs kg 1/4 8 0.81 21 0.88 22 0.25 0.11 • % 10 0.97 25 1.00 25 0.37 0.17 • t • '/2 15 1.12 28 1.31 33 0.62 0.28 • 3/4 20 1.31 33 1.50 38 0.43 0.20 • 1 25 1.50 38 1.81 46 1.33 0.60 • 11/4 32 1.75 44 2.19 56 2.10 0.95 • • 11/2 40 2.00 51 2.44 62 2.80 1.27 • 2 50 2.38 60 2.97 75 4.50 2.04 • H ' 1 • 2'/2 65 3.00 76 3.62 92 9.10 4.13 IEA-- 1 • 3 80 3.38 86 4.31 109 13.50 6.12 • 4 100 4.19 106 5.75 146 32.00 14.51 • • FIGURE 2104 Size A H Unit Weight • Crosses • NPS ON in mm In mm ibs ! kg 1/4 8 0.81 21 0.88 22 0.50 0.23 • • % 10 0.97 25 1.00 25 0.40 0.18 • /2 15 1.12 28 1.31 33 0.85 0.39 • '` 3/a 20 1.31 33 1.50 38 1.10 0.50 • • 1 25 1.50 38 1.81 46 1.70 0.77 • 11/4 32 1.75 44 2.19 56 2.40 1.09 • i 11/2 40 2.00 51 2.44 62 3.20 1.45 • 2 50 2.38 60 2.97 75 5.20 2.36 • 21/2 65 3.00 76 3.62 92 16.50 7.48 • i-.- A 3 80 3.38 86 4.31 109 20.00 9.07 • • • 92 w .anviiintl.com (0/4n"- • ww PF-6.13 • • • FORGED STEEL FITTINGS • • • Forged Steel Fittings • Class 3000 Threaded l' • 7-t,--* z • FIGURE 2111 Size A H Unit Weight 90° Elbows • NPS ON in mm in mm lbs kg • lA 3c 6 0.81 21 0.88 22 0.23 0.10 2- - • 1/i 8 0.97 25 1.00 25 0.35 0.16 2 % 10 1.12 28 1.31 33 0.66 0.30 411 . ' A- 1 y2 15 1.31 33 1.50 38 0.93 0.42 % 20 1.50 38 1.81 46 1.48 0.67 • ',' t 111 1 25 1.75 44 2.19 56 2.30 1.04 at • ,,,,, '-'s,,‘",„4"' _y_ 1 i 11/4 32 2.00 51 2.44 62 2.68 1.22 --- .Tra • ,,,,,t,:kk4, !i'Y•' 11/2 40 2.38 60 2.97 75 5.30 2.40E"- cr) 2 50 2.50 64 3.31 84 5.85 2.65 • .........„,.... , .... 21/2 65 3.25 83 4.00 102 10.00 4.54 • 3 80 3.75 95 4.75 121 17.20 7.80 4 100 4.50 114 6.00 152 29.30 13.29 IS • c,,. 2 8 • FIGURE 2112 Size C H ,R.P.3. Unit Weight • 45Elbows NPS ON in mm in mm : lbs kg • % 6 0.69 17 0.88 22 0.18 0.08 8.4, • 3/4 8 0.75 19 1.00 25 0.25 0.11 ..,,,..N . • 10 0.88 22 1.31 33 0.53 0.24 • .,.,, ,,/ , 1/2 15 1.00 25 1.50 38 0.78 0.35 • t. % 20 1.12 28 1.81 46 1.20 0.54 , 125 1.31 33 2.19 56 1.90 0.86 • .. „ . A 1, 32 1.38 35 2.44 62 2.30 1.04 .0 • ,• •=:. 11/2 40 1.69 43 2.97 75 4.16 1.89 e' ,•;c 2 50 1.72 44 3.31 84 5.12 2.32 • 21/2 65 2.06 52 4.00 102 7.70 3.49 • 3 80 2.50 64 4.75 121 12.00 5.44 4 100 3.12 79 6.00 152 19.70 8.93 i • • FIGURE 2114 Size A H Unit Weight • Tees NPS ON in mm in mm lbs kg • 1/8 6 0.81 21 0.88 22 0.31 0.14 U • ,,,,......,•,„, 1/4 8 0.97 25 1.00 25 0.42 0.19 '?.. 0... % 10 1.12 28 1.31 33 0.93 0.42 = • k kk. % 15 1.31 33 1.50 38 1.20 0.54 0 i • ,,k.:',•,-4. :-•,..,,,.", ...='.;: 1 • - ,,,.,:,',i1'.' T i , % 20 1.50 38 1.81 46 1.84 0.83 52,'1 1 25 1.75 44 2.19 56 3.05 1.38 • `: ' e'Vt.A:''': . 0:, ,e' yi __.1 11/4 32 2.00 51 2.44 62 3.62 1.64 • ';,, ''.' - fr+,-*T 1 - 1% 40 2.38 60 2.97 75 6.65 3.02 \ =,';', .'*z..,',< ' '' " • 1-4 -1 ii..,it4'. • , 2 50 2.50 64 3.31 84 7.15 3.24 • 21/2 65 3.25 83 4.00 102 13.70 6.21 • 3 80 3.75 95 4.75 121 21.00 9.52 4 100 4.50 114 6.00 152 38.00 17.23 0 • • ((C))ANVI L vinlvw.anvilirttl.com 93 • ..,......r.._ PF-11.13 • • 1111 FORGED STEEL FITTINGS Id • Forged Steel Fittings • Class 3000 Threaded • • FIGURE 2115 Size A H Unit Weight • Crosses • NPS LW in mm in mm Is kg 1/8 6 0.81 21 0.88 22 - - • 1/4 8 0.97 25 1.00 25 - - • 3/a 10 1.12 28 1.31 33 - - • 1/2 15 1.31 33 1.50 38 1.40 0.63 • 3/4 20 1.50 38 1.81 46 2.10 0.95 ;31,3I -r 1 25 1.75 44 2.19 56 3.50 1.59 • '-,, ` ---Q4-( -- 1-I 11/4 32 2.00 51 2.44 62 4.30 1.95 • 1'/z 40 2.38 60 2.97 75 8.20 3.72 • a 1'- A 2 50 2.50 64 3.31 84 8.40 3.81 . 21/2 65 3.25 83 4.00 102 17.10 7.76 • 3 80 3.75 95 4.75 121 20.00 9.07 . 4 100 4.50 114 6.00 152 32.00 14.51 • FIGURE 2113 Size A G H Unit Weight 90° Street Elbows • NPS LW in mm in mm ! in mm lbs kg 1/8 6 0.75 19 1.00 25 0.75 19 - - • 1/4 8 0.88 22 1.25 32 1.00 25 0.23 0.10 40 \% G H % 10 1.00 25 1.50 38 1.25 32 0.38 0.17 • e , -1.7`.1 t.,' \f.,,,Ii,, 1 iI���l�� - 1/215 1.12 28 1.62 41 1.50 38 0.53 0.24 • Z, r rllf(IfI A 3/4 20 1.38 35 1.88 48 1.75 44 0.88 0.40 4", • 1 i I 1 25 1.75 44 2.25 57 2.00 51 1.40 0.63 1'1-1'1 1'/a 32 2.00 51 2.62 66 2.44 62 2.40 1.09 • 11/2 40 2.12 54 2.81 71 2.75 70 2.90 1.32 0 2 50 2.50 64 3.31 84 3.31 84 5.00 2.27 411/ • FIGURE 2116 Size B K L Unit Weight • Laterals NPS LW in mm T in ' mm in mm lbs. kg • /z 15 1.56 39.62 2.56 65.02 3.56 90.42 1.75 0.79 • �� 3/4 20 1.84 46.74 3.00 76.20 4.13 104.90 2.75 1.24 x • Yx i 1 25 2.22 56.39 3.50 88.90 4.81 122.17 4.63 2.10 1'/4 32 2.50 63.50 3.94 100.08 5.38 136.65 5.50 2.48 • • '' [< L ,I 1'/z 40 3.03 79.96 4.75 120.65 6.44 163.58 10.81 4.91 . 2 50 3.34 84.84 5.00 127.00 6.63 168.40 11.50 5.23 • • • 94 www.anvilint1.com <<©>»i NVIL PF-11.13 • • • I FORGED STEEL. FITTINGS I • • Forged Steel itti • Class 3000 Threaded a • m • FIGURE 2117 Size 0 W Unit Weight • Couplings NPS ON in mm in mm lbs kg • /e 6 0.6216 1.25 32 0.14 0.06 • v, 8 0.75 19 1.38 35 0.10 0.05 • 3/e 10 0.88 22 1.50 38 0.13 0.06 • 1/2 15 1.12 28 1.88 48 0.28 0.13 a, • 3/4 20 1.38 35 2.00 51 0.44 0.20 g u- • 1 25 1.75 44 2.38 60 1.08 0.49 • -_____,,,,,_....3 11/4 32 2.25 57 2.62 67 1.68 0.76 :i'' • ---- +--- ID 11 40 2.50 64 3.12 79 2.17 0.98 c, 250 3.00 76 3.38 86 3.20 1.45 • I` W 'I 2%z 65 3.62 92 3.62 92 4.70 2.13 • me • 3 80 4.25 108 4.25 108 6.80 3.08 .0 tbtt .0 • 4 100 5.50 140 4.75 121 12.30 5.58 • • FIGURE 2119 Size 0 W/2 Unit Weight • Half Couplings } NPS £1N in mmin mm lbs kg Q' • '/8 6 0.62 16 0.63 16 0.05 0.02 • '/a 8 0.75 19 0.69 18 0.04 0.02 • 3/8 10 0.88 22 0.75 19 0.06 0.03 • /z 15 1.12 28 0.94 24 0.12 0.05 8' I • 0 3/a 20 1.38 35 1.00 26 0.21 0.10 • 1 25 1.75 44 1.19 30 0.43 0.20 S a • - I 11/4 32 2.25 57 1.31 34 0.76 0.34 com • -- - p 11 40 2.50 64 1.56 40 1.14 0.52 "5' • i 2 50 3.00 76 1.69 43 1.50 0.68 • 1-4-W/2->i 2% 65 3.62 92 1.81 46 2.40 1.09 • 3 80 4.25 108 2.13 54 3.25 1.47 • 4 100 5.50 140 2.38 61 6.25 2.83 • • • (( )AimyIL www.anvilintl.corn 95 • or,e�A PF-6.13 • • I FORGED STEEL FITTINGS • Forged Steel Fittings • Class 3000 Threaded • • FIGURE 2118Size D W Unit Weight • Reducing Couplings NPS ON NPS ON in mm in mm lbs kg • 1/4 8 1/2 6 0.75 19 1.38 35 0.10 0.05 • � ' % 10 '/8 6 0.88 22 1.50 38 0.15 0.07 • • '/2 15 1/8 6 1.12 28 1.88 48 0.35 0.16 41 3/4 20 '/8 6 1.38 35 2.00 51 0.52 0.24 • 1 25 1/8 6 1.75 44 2.38 60 1.10 0.50 • 11/4 32 1/4 8 2.25 57 2.62 67 2.08 0.94 • *;' • _111111111I I II II I III IIIII ID 1'/2 40 1/4 8 2.50 64 3.12 79 2.93 1.33 • I II I I �IOIIIIII 2 50 1/4 8 3.00 76 3.38 86 4.40 2.00 • W 'I- 1 212 65 % 20 3.62 92 3.62 92 7.50 3.40 • • 3 80 3/a 20 4.25 108 4.25 108 11.00 4.99 • 4 100 1'/2 40 5.50 140 4.75 121 20.50 9.30 • • FIGURE 2120Size D P Unit Weight • Pipe Caps . NPS ON in mm in mm lbs V Y 6 0.62 16 0.75 19 0.07 0.03 • 1/4 8 0.75 19 1.00 25 0.08 0.04 0 3/e 10 0.88 22 1.00 25 0.11 0.05 • 1/2 15 1.12 28 1.25 32 0.23 0.10 • • % 20 1.38 35 1.44 37 0.40 0.18 0 1 25 1.75 44 1.62 41 0.79 0.36 • 11/4 32 2.25 57 1.75 44 1.21 0.55 • T p 1' 40 2.50 64 1.75 44 1.75 0.79 • I",-,] I 2 50 3.00 76 1.88 48 2.46 1.12 • f P-H 2'/2 65 3.62 92 2.38 60 4.37 1.98 • 3 80 4.25 108 2.56 65 6.50 2.95 410 4 100 5.50 140 2.69 68 11.30 5.12 • • • 96 www.anvilintl.com (0)4 Fi I_ • PF-6.13 • • • I FORGED STEEL FITTINGS I • • • Forged Steel Unions • Manufactured to MSS standard practice SP83 Class 3000 Threaded & Socket-Weld (Class 6000 by method ofMSSSP83) • l • , Q . . . E o �s • A . !Li A , 7 D • f B B • Threaded Socket-Weld • FIGURE 2125:Threaded Union • Size A B C* D E F Unit Weight • NPS ON in mm , in mm , in mm in mm in mm in mm lbs kg 1/4 8 111/6 43 131/64 38 53/x4 21 2%2 20 7/s 11 0.555 14 0.30 0.14 0.575 15 • % 10 127/32 47 1''/6 43 1 25 31/32 25 7/6 11 0.690 18 0.50 0.23 • 1/2 15 2 51 115/,6 49 13/16 30 13/32 28 7/,6 11 0.855 22 0.70 0.32 0.875 22 • 3/4 20 25/16 59 2% 60 115/32 37 15/32 29 9/6 14 1.065 27 1.20 0.54 1.085 28 • 1 25 27/16 62 22%2 71 125/32 45 1% 35 9/s 14 1.330 34 1.70 0.77 1.350 34 11/4 32 27/6 73 32%4 85 2%2 686 14%4 43 9/6 14 1.675 43 2.50 1.13 1.695 43 • 1915 49 11/2 40 3 76 32%4 85 235/x4 65 1% 48 9/s 14 . 3.30 1.50 1.935 49 • 2 50 31/2 89 42%4 112 3'/6 78 2'/6 52 11/6 17 2.406 61 5.30 2.40 2.426 62 • 212 65 41/4 108 515/x4 133 39/1s 90 2% 60 7/ 22 2.906 74 8.60 3.90 2.931 74 • 3 80 47/16 113 65/32 156 4%2 109 27/16 62 1 25 3.535 90 12.70 5.76 • 3.560 90 • FIGURE 2126: Socket-Weld Union • Size A B C* 0 E F Unit Weight NPS ON in mm in mm in mm in mm in mm in mm lbs k9 • 1/4 8 111/s 43 131/64 38 5%4 21 2%2 20 '/,6 11 0.555 14 0.30 0.14 0.575 15 • 3/e 10 127/32 47 111/6 43 1 25 31/32 25 7/6 11 0.690 18 0.710 18 0.50 0.23 • 1/2 15 2 51 115/s 49 13/6 30 1%2 28 7/6 11 0.855 22 0.875 22 0.70 0.32 • 3/4 20 25/16 59 2% 60 115/32 37 15/32 29 9/1s 14 1.065 27 1.20 0.54 1.085 28 • 1 25 27/16 62 22%2 71 125/32 45 1% 35 9/s 14 1.330 34 1.70 0.77 1.350 34 • 11/4 32 2'/e 73 323/x4 85 27/32 686 145/64 43 9/s 14 1.675 43 2.50 1.13 1.695 43 • 112 40 3 76 32%4 85 23%4 65 17/e 48 9/6 14 1.915 49 3.30 1.50 1.935 49 • 2 50 31/2 89 427/x4 112 31/6 78 21/6 52 11/6 17 2.406 61 5.30 2.40 2.426 62 • 21/2 65 41/4 108 515/x4 133 39/1s 90 2% 60 7/e 22 2.906 74 8.60 3.90 2.931 74 • 3 80 47/s 113 65/x2 156 4%2 109 27/6 62 1 25 3.535 90 12.70 5.76 3.560 90 5 ."c"dimension measures across octagon corners or across the diameter as applicable.The 21/2'NPS(65 ON)and 3"NPS(80 DN)-3000 and 2'NPS(50 DN)-6000 sizes have octagonal male and female ends the other sizes are round. • 114 www.anvilint1.com �0/�IVVIL PF-11.13 • • • FORGED STEEL FITTINGS • ' Forged Steel Unions • Class 6000 Threaded & Socket-Weld t > 2 41 E SE III L • I IC A lip- A ri %______ ; . . •- - =1 1, Irj D o l • i Manufactured to MSS standard practice SP83 1"-C I 1-F F -I (Class 6000 by method of MSS SP83) ill B - B ' Threaded Socket-Weld °gn ah FIGURE 2127:Threaded Union 1MP" 41. Size A B C" D E F Unit Weight • NPS " ON in mm in '+ mm in.', mm in mm in mm in mm lbs kg 1/4 8 12%2 47 111/6 43 1 25 31/32 25 7/6 11 0.575 15 0.60 0.27 L-'' • act • 0.60 18 3/a 10 2 51 115/s 49 13/16 30 13/32 28 '/16 11 0.790 18 0.80 0.36 0.a. 40 a 1/2 15 25A6 59 2% 60 115/32 37 15/32 29 9/6 14 0.0.87855 2222 1.40 0.63 5 3/4 20 27/16 62 225/32 71 12%32 45 1% 35 %6 14 11:(0,85 28 2.00 0.91 ` 1 25 2% 73 32%4 85 2%2 686 145/64 43 9/6 14 1.350 34 3.10 1.41 E. 11/4 32 3 76 323/32 94 235/x4 65 1%6 48 9/s 14 11.695 43 5.90 2.68 11/2 40 311 89 42%4 112 31A6 78 21/6 52 11/16 17 11.835 49 6.60 2.99 0 2 50 41/8 105 513/44 133 39/6 90 2% 60 '/e 22 '.44€2) 6162 a10.50 4.76 3' 2 ' 41• FIGURE 2128: Socket-Weld Union 01) Size A B C° D E F Unit Weight a 1110 NPS ON in mm in mm in mm in mm in mm in mm lbs kg I /4 8 12712 47 111/6 43 1 25 31/32 25 %6 11 0.575 115 0.60 0.27 8 0 0. 0 18 3/s 10 2 51 115/6 49 13/6 30 1%2 28 'A6 11 0.790 18 0.80 0.36 0 U' 40 0.855 22 /z 15 25/16 59 23/6 60 115/32 37 15/32 29 9/s 14 0.875 22 1.40 0.63 3/4 20 27/16 62 225/32 71 12%2 45 1% 35 9/16 14 11.085 28 2.00 0.91 1' ip m 1 25 2% 73 323/64 85 2712 686 145/64 43 9/6 14 11.350 34 3.10 1.41 • 11/4 32 3 76 323/32 94 23%4 65 1% 48 9/s 14 1.675 43 5.90 2.68 • 11% 40 311 89 423¼ 112 31/16 78 21/e 52 71/6 17 1.915 49 6.60 2.99 • 1.935 49 • 2 50 41% 105 515/x4 133 39/6 90 2% 60 %I 22 2.426 62 10.50 4.76 0 "'C"dimension measures across octagon corners or across the diameter as applicable.The 277'NPS(65 DN)and 3'NPS(80 DN)-3000 and 2"NPS(50 DN)-6000 sizes have octagonal male and female • ends,the other sizes are round. • (�(©��ANVIL www.anvilintl.com 115 PF-6.1 3 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ''''''" -WA' r,;',/:)- ' :‘ i 'llr III 0 N % 4 9.:::,, ,El//' 7...-..4I ROOM PROTECTED BY CLEAN AGENT EXTINGUISHING SYSTEM DO NOT ENTER AREA DURING OR AFTER DISCHARGE _,....,_,,...._„,........„ KEEP DOOR CLOSED AT ALL TIMES SUPPRESSION SYSTEMS INC. (253) 926-3300 :.,,,,,',,,'„,--0 '4 , k . G/' ,,, 0" 15.1 r uh CLEAN AGENT EXTINGUISHING SYSTEM DISCHARGE ALARM ALARM 1 - BELL PREDISCHARGE - HORN /1.''P ''''," , �:4; .. -T-4f% hep. . gjii -f4 i/,:. /' T.'9 / ��� / ,,��% %.i''. /.te j j/ b y %jam .,''':!,,'°,,,,I. %'. fir ,,.