Specifications (78) - ver \\A T -k,Q1\ NAC EOL VOLTAGE CALCULATION , CAPITOL ELECTRIC CO., INC. AUG 27 2018 (503) 255-9488 Office (503) 255-1966 Fax CITY( TIGARD KT: NG ITT '7fON Job Name: TIGARD STORAGE Job Address: 11123 SW 68TH PARKWAY TIGARD, OR 97223 Job Number: Conductor Wire Gauge 14 Prepared By: Shane Tercek Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/2/2018 Cable Length In Feet (source to end of line) 30 Total Circuit Current 0.168 Nominal System Voltage 20.4 Panel Description: SK 6700 Minimum Device Voltage 16 Panel No.: NAC 1.0 Output No.: 1 Point To Point Method EOLv 20.37 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock Load Centering Method EOLv 20.38 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) llifi, AZOWI-6 AMriveAttrix X24, 4y , 1 EXTERIOR FLOW H/S ASWP-2475W-FR W/P H/S-H 75 Cd 0.168 30 20.37 2 20.37 3 20.37 4 20.37 5 20.37 6 20.37 7 20.37 8 20.37 9 20.37 10 20.37 11 20.37 12 20.37 13 20.37 14 20.37 15 20.37 16 20.37 17 20.37 18 20.37 19 20.37 20 20.37 TS FACP, NAC B.1 EOLv Calc NAC, 2 CKT (20.4V Nominal).xls OUTPUT 1 . , FACP BATTERY CALCULATIONS CAPITOL ELECTRIC CO, INC' (503)255-9488 Office, (503) 255-1966 Fax JOB NAME: TIGARD STORAGE JOB ADDRESS: 11123 SW 68TH PARKWAY TIGARD, OR 97223 DATE: 8/2/2018 PANEL DESCRIPTION:SK 6700 FACP BY: Shane Tercek DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE DESCRIPTION QUANTITY CURRENT CURRENT CURRENT CURRENT FACPINTERNAL COMPONENTS Silent Knight Model 6700 FACP 1 0165000 0165000 0.310000 0.310000 6855 Remote LCD Annunciator 1 0.020000 0.020000 0.025000 0.025000 5860 Remote Annunciator 0.020000 0.00000 0o25000 0.000000 5496 Addressable Power Module 0010000 0.00000 0.010000 0000008 INITIATING DEVICES 0.000000 0.000000 SK-Photo Photo Smoke Detector 31 0.000300 0.009300 0.006500 0.201500 SK-Pull-DA Manual Station, Double Action 1 0.000375 0.000375 0o00375 0o00375 SK-Heat-ROR Heat Det(135 Deg FT/ROR) 6 0.000300 0.00180 0.006500 0.039000 Spm,Riser Flow Switch"ws*-Minimon 6 0.000375 0.802250 0.080375 0.002250 Spklr Riser Valve Switch w/SK-Minimon 8 0.000375 0.003000 0u00375 0.003000 Spklr Vault Valve Switch w/SK-Minimon 2 8.000375 0o00750 0o00375 0.000750 SK-Minimon 6 0.000375 0.002250 0.000375 0.002250 OUTPUT DEVICES JN�����'�W� SK-Relay Relay Module 0.000255 0.000000 0088255 0.080800 SK-Relay Relay Module(Elev Recall) 6 0.000255 0001530 0.000255 0.001530 SK-Relay Relay Module(Elev Shunt Trip) 2 0.000255 0000510 0.000255 0.000510 SK-Relay Relay Module(FSD Control) 1 0.000255 0.000255 8000255 0.000255 SK-Relay Relay Module(HVAC Shutdown) 4 0o00255 0.001020 0.000255 0001020 0.000000 0.000000 0.080000 0.000000 UONumber 1 0.000 Wheelock ASWP-2475W-FW Outside H/S (H) 1 0.168 0.188 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 I/O 1 Alarm Total 0.168 |/ONumber z 111,P° 0.000 SPARE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 I/O 2 Alarm Total 0.000 TS FACP, NAC B.1 Batt Calc SK 6700 (20.4V Nominal).xls 8700Batt Calc FACP BATTERY CALCULATIONS STANDBY TOTAL CURRENT: 0.208 STANDBY HOURS: 24 STANDBY AMP HOURS: 4.99296 ALARM TOTAL CURRENT: 0.755 ALARM MINUTES: 5 ALARM AMP HOURS: 0.0630 TOTAL CALCULATED AMP HOURS 5.056 NAC TOTAL CURRENT: 0.168 APPLIED SAFETY FACTOR 1.20 MINIMUM AMP HOURS REQURED 6.067 SELECTED BATTERY SIZE 12 EACH 12 VOLT, 7 AMP HOUR BATTERIES TS FACP, NAC B.1 Batt Calc SK 6700 (20.4V Nominal).xls 6700 Batt Calc -11 Honeywell SILENT KNLIGHT 6700 Addressable Fire Alarm Control Panel The 6700 is an addressable fire alarm control panel(FACP) that can be configured to achieve an overall point capacity of up to 100 points.It has one built-in signaling line circuit (SLC),which can support 50 System Sensor"(SK)sensors and 50 SK modules or 50 Hochiki®(SD)devices per loop. A common communications and annunciation link allows up to 17 panels to be connected via copper or fiber optic cable.A designated panel is configured as the communicator for all panels in the link for convenient single-point communications.It also has a built-in,dual- line POTs and IP communicator and optional cellular side-cars. 6700 The 6700 system can be enhanced by adding modules such as the It supports a variety of devices,including the 6860 remote annunciator which also has four programmable function 6860,5860,and 6855 remote annunciators, buttons to help automate tasks and reduce time spent at the panel. 5824 serial parallel printer interface module(for printing system reports),the 5496 NAC expander, SWIFT®wireless compatibility provides options for wireless 5895XL power module,and SK or SD devices. detection through a Class A mesh network. It is ideal for hard- to-wire locations,buildings where new wiring is not allowed,or to provide an easy install fire system for new construction projects. SWIFT devices can be combined with other hard-wired 6700 compatible devices.SWIFT is only compatible with System Sensor (SK)devices.It is not compatible with Hochiki(SD)devices. The 6700 also has Form C trouble relay,and two programmable Form C relays,along with powerful features such as drift compensation,pre- trouble maintenance alert,a built-in sensor test to comply with NFPA 72 calibration testing requirements,and calibration trouble alert. FEATURES & BENEFITS • Capable of providing • Convenient • 6860 annunciator with • Programmable date • 125 software zones up to 100 points to field-upgradeable a 4 x 40 large display, setting for automatic and 125 output satisfy smaller firmware and 4 programmable and convenient groups for flexible installation needs • Integrated dual path function buttons. Daylight Saving Time design options • Connect up to 17 IP and POTs Free-up time spent at changes panels on one site with communications and the panel.Program • Built-in dual phone them for simple or convenient single- optional cellular line and digital alarm point access using the side-cars for reliable complex tasks. communicator/ SK-NIC Network backup • Built-in USB interface transmitter(DACT)for Interface Card. for convenient and additional Connected panels can quick programming communication have mixed compatible options FACP models. 6700 Product Information SIGNAL LINE CIRCUIT(SLC) non-coded)signaling services. The 6700 SLC loops support multiple • ns¢cgtse mi .; IS • UL Listed:S2766 '0" trInntnni device types,maintenance alerts,and a • CSFM 7165-0559:050 built-in sensor test to comply with NFPAZ. • • FDNY COA#6250 72 calibration testing requirements. U OOO a 000 • Seismic(CA)(pending) INDICATOR LIGHTS ® 000 Q,C a�, F-1 000 0 • General Alarm(Red): Flashes if in ORDERING INFORMATION alarm;solid when alarm is silenced 6700:Addressable Fire Alarm 6700 KEYPAD Control Panel.(Red cabinet) • Supervisory(Yellow):Flashes if a supervisory condition exists;solid PROGRAMMING COMPATIBLE ANNUNCIATORS when supervisory is silenced The 6700 system offers several options 6860:4x40 LCD remote fire • System Trouble(Yellow):Flashes to simplify and speed-up programming. annunciator(4 lines and up to if a trouble condition exists; JumpStart"autoprogramming 160 characters)per system;four solid when trouble is silenced minimizes programming required to programmable buttons • S stem Silenced(Yellow): start a new system.The built-in keypad, y or the 6860,5860 or 6855 remote 5860:4x20 LCD remote fire On when an alarm,trouble or annunciator.5860 is gray;5860R is red supervisory condition has been annunciators give you on-site access silenced but not yet cleared to current system programming.You 6855:4x20 LCD remote fire can also program the system using annunciator • System Power(Green):Flashes the Honeywell Fire Software Suite 5865-3 or 5865-4:LED annunciators for AC failure;solid when (HESS),which is Windows®based. can display up to 30 LEDs(15 red and power systems are normal 15 yellow).The 5865-4 has key switches SOFTWARE TOOLS for silence and reset,and a system USER INTERFACE SKST:Silent Knight Selection Tool trouble LED. The 6700 built-in 4 x 20 annunciator provides the installer or design architect g 5880:The 5880 LED/10 module with 80 character LCD display with a Windows"softwaresystem and large easy-to-use tactile has 40 programmable LED outputs configuration tool to create a detailed and eight supervised dry contact touchpad can be used for system Bill of Material(BOM)and battery inputs which are useful for custom operation,programming and calculations. applications.You can use up to eight maintenance.It has five LEDs for HFSS:Honeywell Fire Software Suite 5880 modules on one control panel for alarm,supervisory,system trouble, provides communication and panel maximum flexibility.Its compact size system silenced and system power. programming,detector status,event allows mounting inside the annunciator, System operations include silencing history and additional data. Requires a or in an accessory cabinet. alarms and troubles,resetting alarms Windows-based computer. and the display of alarm troubles and memory.The system's non-volatile ADDITIONAL INFORMATION event history buffer stores 1,000 Twisted unshielded pair wire is events for viewing from the built- recommended.The 6700 also has in or remote annunciator.System 13 preset notification cadence operations can be initiated with a patterns(including ANSI 3.41). mechanical firefighter's key or a AGENCY LISTINGS AND APPROVALS valid 4-to 7-digit operator's code. NFPA 13, NFPA 15,NFPA 16,NFPA 70, NFPA 72:Central station;remote Signaling; Local Protective Signaling Systems;Auxiliary Protected Premises Unit;Water Deluge releasing service. Suitable for automatic,manual, waterflow,sprinkler supervisory(DACT 6700 COMPATIBLE DEVICES AND B200S-LF:Low-frequency intelligent smoke detector ACCESSORIES sounder base WSK-PHOTO-T:Wireless Multi-criteria See the data sheets listed below for a B224RB: Relay base photoelectric smoke detector with thermal complete listing of the SK,SD or SWIFT B224B1: Isolator base detection(135°F fixed temperture)and devices. B510W 4"base 53623:SK Devices Data Sheet SD COMPATIBLE ADDRESSABLE WSK-H EAT:Wireless Heat,(135°F fixed 53624:SD Devices Data Sheet DEVICES temperture)and B510W 4"base 350614,350616&350618:SWIFT SD505-6AB:Addressable 6"base WSK-HEAT-ROR:Wireless heat,ROR wireless devices SD505-61B:Addressable 6"short circuit (135°F fixed temperture)and B510W 4" For a complete and current listing of isolator base base compatible devices and accessories go to SD505-6RB:Addressable 6"relay base WSK-MONITOR:Wireless monitor module www.silentknight.com SD505-6SB:Addressable 6"sounder base WSK-RELAY:Wireless relay module Important:You cannot mix SK and SD SD500-AIM:Addressable input module W-USB:SWIFT Tools USB transceiver used devices in the same fire alarm system. (switch input) for communication with SWIFT devices SD500-ANM:Addressable notification SK COMPATIBLE ADDRESSABLE module SBUS ACCESSORIES DEVICES SD500-ARM:Addressable relay module 5496:A 6 amp notification power expander SK-ACCLIMATE:Multi criteria photoelectric smoke detector with thermal SD505-DTS-K:Remote test switch and with four power-limited notification 135°F fixed temperture LED indicator for the SD505-DUCTR appliance circuit outputs. SK-BEAM:Reflected beam smoke detector SD505-DUCT:Addressable Duct Smoke 5883:Relay interface.Provides 10 Form C without test feature Detector. relays. SK-BEAM-T:Reflected beam smoke SD505-DUCTR:Addressable Duct 5824:Serial/Parallel printer interface detector with test feature Detector housing with relay base. module for printer connection. SK-CONTROL:Supervised control module SD505-H EAT:Absolute temperature 5895XL:Power supply with six Flexput° heat detector.Trip point range from circuits,and two Form C relays.Max.16 per SK-CONTROL-6:Six circuit supervised 135°F-150°F(0°C-37°C). system. control module SK-DUCT:Photoelectric duct smoke SD500-LIM:Addressable Line isolator 5815RMK:Remote mounting kit. module Dimensions 10 3/8"W x 10-3/16"H x 3"D detector with extended air speed range SD500-MIM:Addressable Mini input SK-FIRE-CO:Four criteria fire and carbon monitor module(switch input) COMMUNICATION OPTIONS monoxide detector SD505-PHOTO:Photoelectric smoke CELL-CAB-SK:Cellular communicator, SK-HEAT:Fixed thermal detector(135°F) detector metal enclosure with lock/key* SK-HEAT-ROR:Fixed rate of rise detector SD500-PS/-PSDA:Addressable Single or CELL-MOD:Cellular communicator,plastic (135°F) dualaction pull station enclosure* SK-HEAT-HT:Fixed high temperature SD500-SDM:Addressable smoke detector *Sole path,powered by panel. thermal detector(190°F) module IPGSM-4G:Dual path fire alarm SK-ISO:Fault isolator module communicator,cellular and/or IP(primary SK-MINIMON:Mini monitor module AUDIBLE/VISIBLE DEVICES or backup,selectable) SK-MONITOR:Monitor module These AV devices are all 2-wire.Color:"R" SK-IP-2:Remote reporting via the Internet. SK-MONITOR-2:Dual input monitor indicates red;"W"denotes white.For a Requires a VisorAlarm®receiver at the module complete listing of Silent Knight AV devices central station SK-MON-10:10 input monitor module go to www.silentknight.com. SK-PHOTO:Photoelectric smoke detector CHSRL/CHSWL:Wall chime/strobe MISC.ACCESSORIES SK-PHOTO-T:Photoelectric smoke CHSCRL/CHSCWL:Ceiling chime/strobe SK-NIC:Network Interface Card.Provides a detector with thermal(135°F fixed CHRL/CHWL:Wall chime common communications link for the 6700 temperture) HRL/HWL:Wall horn SK-NIC-KIT:Installation Accessory Kit SK-PHOTOR:Photoelectric detector with P2RL/P2WL:Wall horri/strobe SK-FML:Fiber Optic Multi Mode, remote test capability PC2RL/PC2WL:Ceiling horn/strobe transmitter and receiver SK-FSL:Fiber-Optic Single Mode SK-PULL-SA:Addressable single action SRL/SWL:Wall strobe pull station RBB:Remote battery box accessory cabinet SCRL/SCWL:Ceiling strobe for batteries that are too large to fit in the SK-PULL-DA:Addressable dual action pull SPSCRL/SPSCWL:Ceiling speaker/strobe FACP cabinet.Dimensions:16"W x 10"H x station SPSRL/SPSWL:Wall speaker/strobe 6"D(406mm W x 254mm H x 152mm D). SK-RELAY:Addressable relay module SK-RELAY-6:Addressable Six relay control SPRL/SPWL:Wall speaker SK-SCK:Seismic Compliance Kit used to module SPCRL/SPCWL:Ceiling speaker securely fasten batteries to the fire panel. SK-RELAYMON-2:Addressable Dual relay/ SWIFT WIRELESS DEVICES monitor module SK-ZONE:Addressable zone interface SWIFT is only compatible with module System Sensor(SK)devices.It is not SK-ZONE-6:Six zone interface module compatible with Hochiki(SD)devices. B210LP:6"mounting base WSK-WG I:Wireless Gateway B501:4"Flangeless mounting base WSK-PHOTO:Wireless Photoelectric B200S:Intelligent sounder base 6700 Technical Specifications PHYSICAL NOTIFICATION APPLIANCE CIRCUITS(NACs) For a complete listing of all Overall Dimensions:12.71"W x 15.12"H x 3.33"D Two programmable circuits which can be compliance approvals and Weight:15 lbs. programmed individually as: certifications,please visit www.sitentknight.com. Color:Red NACs:2.5A®27.4VDC per circuit,power-limited (with a panel maximum current of 2.5A) Microsoft,Windows,and ENVIRONMENTAL Auxiliary Power Circuits:2.5A®27.4VDC per the Windows Logo are 0 120°F (0°C circuit,power-limited registered trademarks Operating Temperature:32°F to 120 F (0 C to or trademarks of 49°C) Microsoft Corporation. Humidity:0 to 93°/o relative humidity(non- Supports Class B(Style 4)and Class A(Style 6 or 7) condensing) configuration for the SLC Silent Knight,Honeywell° and SWIFT`are registered ELECTRICAL trademarks of Honeywell WIRING:See the product manual for wiring details International,Inc. 6700 Primary AC:120 VAC @ 60 Hz,1.5A Total Accessory Load:2.5A @ 27.4 VDC power-limited This document is not Standbyintended to be used for Current:165mA installation purposes.We Alarm Current:310mA try to keep our product Battery Charging Capacity:7 to 35AH information up-to date and accurate.We Battery Size:7AH max.allowed in control panel cannot coverallspecific cabinet.Larger capacity batteries can be housed in applications or anticipate RBB accessory cabinet.. all requirements.All specifications are subject to change without notice. For Technical Support, call 800-446-6444. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472 3516071A111/17 Honeywell 800-328-0103 ©2017 Honeywell International Inc. � � eywell ®SILENT* KNIGHT 6860 Remote Annunciator The 6860 remote annunciator can be used to view system status indicators for Honeywell Silent Knight fire alarm control panels(FACPs)from anywhere within the system.It provides a convenient way to view system a ;' status indicators. The 6860 comes in a locked,key controlled cabinet-combining security with easy access.It does not require a code or firefighter's key to silence or Al Al Ala reset a panel,and also has convenient separate scroll buttons for alarm, VI supervisory and trouble conditions.The remote annunciator communicates with the main fire alarm control panel through an RS-485 , connection. „ t. The 6860 has a large 160 character,4 x 40 display and four programmable • buttons.These features provide more options for set-up and operation x�eQ I °`� "`"° when compared to similar remote annunciators. 6860 The 6860 can be surface or flush mounted.The RA-100TR trim ring can be used for surface mounts. COMPATIBILITY The 6860 is compatible with the following Honeywell Silent Knight FACPs: • 6820:Addressable fire alarm control panel with up to 1,110 addressable points • 6820EVS:Addressable fire alarm control panel with an emergency voice system,up to 1,110 addressable points • 6808:Addressable fire alarm control panel with up to 198 addressable points • 6700:Addressable fire alarm control panel with up to 100 addressable points FEATURES & BENEFITS • Four line LCD display • Easily view current • Five status LEDs make • System access • Four programmable with 40 characters per status by alarms, it easier to monitor through a user code or function keys for for line;160 characters supervisories,or and respond to status firefighter's key improved efficiencies provides ample space troubles changes.They include: and time-savings; • Support for for communicating Alarm,Supervisory, frees-up time spent at • On-board piezo simultaneous use of operating messages sounder audibly Silence and AC Power multiple 6860s the panel • Larger keypad buttons indicates alarms, indicators. • Can be flush or • Comfortable tactical makes it easier to troubles,and • Accommodates wiring feel and clear audible surface mounted.Trim maneuver for system supervisories lengths up to 6000 ft. ring available for confirmation supports reset and silencing . Uses the RS 485 from the control panel surface mounting. accurate • Initiate and end fire SBUS to interface with for added design and programming and drills with a single key the panel install flexibility easy operation press 6860 Technical Specifications Review Events For a complete listing of all Individually by Alarms, compliance approvals and Supervisories,or Troubles 160 Character Display certifications,please visit www.silentknight.com. LED_Status ind ors Microsoft,Windows,and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Large Buttons for System Silence,Reset, e <�h Event Acknowledge, Silent Knight and and Fire Drill Honeywell'are registered trademarks of Honeywell International,Inc. O nen 9 n n This document is not moon ;� ®I�l� intended to be used for [] o , Ergonomic installation purposes.We Designed Keypad try to keep our product (Hidden when door is closed) information up-to date and accurate.We cannot cover all specific applications or anticipate Numeric Keypad all requirements.All (Hidden when door is closed) specifications are subject Four Programmable to change without notice. Function Keys For Technical Support, 6860 FEATURES call 800 446 6444. PHYSICAL ORDERING INFORMATION Flush Mount 6860:Remote Annunciator.Four line(4x40)LCD Outside wall:12.25"W x 11.5"H x 7/8"D(31.1W x annunciator.Red 29.2H x 2.2D cm) Inside wall:9-3/8"W x 8-3/8"H x 2"D(23.8W x ACCESSORIES 21.3H x 5.1D cm) RA-100TR:Red surface mount trim ring Surface Mount:(Including Trim Ring)12.25"W x 11.5"H x 3"D(31.1W x 29.2H x 2.2D cm) AGENCY LISTINGS AND APPROVALS UL listed ENVIRONMENTAL CSFM#7165-0559:0500 Operating Temperature:32°F to 120°F (0°C to NFPA 72 49°C) FM approved Humidity:0 to 93%relative humidity(non- FDNY COA approved condensing) ELECTRICAL Operating Voltage:24VDC Standby Current:25mA Alarm Current:50mA For more information Learn more about Silent Knight's 6860 and other products available by visiting www.SilentKnight.com Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472-1610 Honeywell 800.328.0103 3516121A111/17 ®SII ENT www.honeywell.com ©2017 Honeywell International Inc. KNIGHT SK-Control 11 Intelligent Notification Module am% Rao The SK-Control gives you the flexibility to add notification circuits wherever they are needed on an IntelliKnight FACP signaling line circuit (SLC) loop. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103 or in Connecticut, call (203) 484-7161. Description The SK-Control is an addressable notification module for use with Silent Knight IntelliKnight series fire alarm control panels (FACPs). The SK-Control provides supervised monitoring of wiring to load devices that require an external power supply to operate, such as bells, horns, and strobes. It is capable of Class B (Styles Y) and Class A(Style Z) supervision. Upon command from the FACP, the SK-Control will disconnect the supervision and connect the external power supply across the load device. The disconnection of the SK-COntrO1 supervision provides a positive indication to the panel that the Installation control relay actually turned on. The external power supply is The SK-Control mounts directly into a 4" square always relay isolated from the SLC loop, so that a trouble electrical box. The box must have a minimum condition on the power supply will never interfere with the depth of 2-1/8". A surface mount electrical box rest of the system. (System Sensor® PN SMB500) is available from Features Silent Knight. • Flexible solution for adding notification circuits where needed Compatibility • Support for Class B (style Y) or Class A(style Z) wiring The Control is compatible with the following IntelliKnight FACP's: • Panel controlled status LED that flashes green in normal 5700 state and is solid red in alarm 5808 5820XL • Polling LED visible through the cover plate • Attractive ivory cover plate • Rotary address switches for fast installation • SEMS screws for easy wiring • UL Listed SILENT MIGHT h,ltonewiell - . - . .- - Model SK-Control 1 i (!, NOTFICATIONAPPUANCE CIRCUIT NFPA STYLE Y =A FrmPr,9 - t .b •ZMIII IM tf3An7r,AAr i 1 I '1 V - ilMS Y uYt 4 d i m r F arill =a t t s..? ... , o ar T}I TO NTR4X.t1i7Ct.E 'CA E1+rS F-t FEIN(CAE Rtl+x+s etta rea r,'w tAcy cyan IVOTIFICATtOM APPLIANCE CIIRCUIT NFPA STYLE Z Frail.Piro j......a....) , G G 4 ____j_., ie limo TO NEXTOYARCL WW1 j of EIMA-t!E PHEW CM U$"aNM IS t4t011iWU/Ott itS C.,4,2tisT Specifications Standby Current Physical 400 pA max @ 24 VDC (one communication every 5 Height: 4.5" (11.4 cm) sec with 47K EOL) Width: 4" (10.2 cm) 550 pA max @ 24 VDC (one communication every 5 Depth: 1.3" (3.2 cm) sec with EOL <1K) Shipping Weight: 6.3 oz(196 g) LED Current: 5.5 mA(with LED latched on) Environmental SLC Loop Resistance: 40 0 max. Operating Temperature: 32°F— 120°F (0°C—49°C) Accessories Humidity: 10%—93% non-condensing SMB500 Electrical Operating Voltage: 15—32 VDC Current Draw: 6.5 mA max (LED on) Operating Current: 375 pA average (LED flashing) Drain on External Power Supply: 1.7 mA max (using internal EOL relay) End-of-Line Resistance: 47K n SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA leKNIGHT keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are subject FORM#350125 Rev A r to change without notice. For more information, contact Silent Knight ©2009 Honeywell International Inc. by Honeywell 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. www.silentknight.com SK-DUCT Detect smoke in air handling systems and air handling equipment with Silent Knight's addressable duct smoke detector a ligair 1 The SK-Duct Intelligent Non-Relay air duct smoke detector is used with SK- Photo (included)for detecting smoke and products of combustion present in air moving through an HVAC air handling system. When smoke is detected in a duct, the unit communicates the condition to the IntelliKnight control panel. The panel, in turn, depending on programming and wiring, turns off fans, blowers, and other devices. Now there's even more power and flexibility available to the IntelliKnight family of products! Description The Model SK-Duct Air Duct Smoke Detector utilizes photoelectric technology for the detection of smoke. It provides early detection of smoke and products of combustion present in air moving through HVAC ducts in Commercial and Industrial applications. The SK-Duct is in a heavy duty gray steel back box with a clear cover. It features a pivoting housing that fits both square and rectangular footprints capable of mounting to a round or rectangular duct. It installs quickly and easily. SK-DUCT The unit senses smoke in the most challenging conditions, Specifications operating in airflow speeds of 100 to 4000 feet per minute, temperatures of-4°F to 158°F, and a humidity range of 0 to 95 Physical percent (non-condensing). (Rectangular): 14.38 in (37 cm) Length; 5in (12.7 cm) Width; 2.5 in (6..6 cm) Depth (Square): 7.75 in (19.7cm) Length; Features 9 in (22.9cm) Width ; 2.5 in (6.35cm) Depth • Versatile mounting options: square or rectangular Weight: 1.61b (0.73kg) configuration Environmental • New Cover tamper signal Operating Temperature: -4°F— 158°F • LED alarm indication and communication on sensor head (-20°C— 70°C) • Detects and limits the spread of smoke • Rugged steel back box with clear plastic cover Humidity: 0% — 95% (non-condensing) • Easy to clean Air Velocity • Large terminal connection screws 100 to 4000 ft/min (0.5—20.3 m/sec.) • Transparent cover for convenient visual inspection Electrical • Patented sampling tube installs from front or back of the Please see detector head installation manual detector with no tools required for electrical specifications. • Available space within housing to accommodate mounting of relay module • UL listed SILENT E:11KNIGHT by Honeywell . . - . •- - Model SK-DUCT Air Duct Smoke Detector lrrli #144 Engineering Specifications The air duct smoke detector shall be a SK-Duct non-relay photoelectric duct smoke detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4000 ft/min (0.5 m/sec to 20.32 m/sec). The unit shall be capable of providing a trouble signal in the event that the sensor cover is removed or improperly installed. It shall be capable of local testing via magnetic switch or remote testing using the RTS151KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12-18AWG wiring. Ordering Information SK-Duct Intelligent non-relay duct smoke detector SK-Photo Addressable Photo Detector(included with SK-Duct) SK-Relay Addressable Relay Module, must be added if relay function is required, (fits in housing) Accessoriest DST1 Metal Sampling Tube Duct Width up to 1' DST1.5 Metal Sampling Tube Duct Widths 1'-2' DST3 Metal Sampling Tube Duct Widths 2'—4' DST5 Metal Sampling Tube Duct Widths 4'—8' DST10 Metal Sampling Tube Duct Widths 8'—12' DH4000E-1 Weatherproof Enclosure ETX Metal Exhaust Tube Duct width 1' RA100Z Remote LED Annunciator DCOIL Duct accessory coil, required on DNR if a remote test station is used RTS151 Magnetic Remote Test station RTS151KEY Key-Activated Remote Test station M02-04-00 Test Magnet P48-21-00 Replacement End Cap for Metal Sampling Tube APA151 Remote annunciator with piezo alarm Important Notes: •The use of either RTS151 or RTS151KEY requires the installation of an accessory coil, DCOIL, sold separately. Please refer to the SK-Duct installation instructions for more information •The RTS151/RTS151 KEY test coil circuit requires an external 24VDC power supply which must be UL listed 0 SILENT KNIGHT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA LT�7- keep our product information up-to-date and accurate.We cannot cover all i�l LGH l specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information, contact Silent Knight FORM#350122 Rev A 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, ©2009 Honeywell International Inc. by Honeywell Fax: (203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY � SK-Heat, SK-Heat-HT and '" / �� �� ►SK-Heat-ROR '-'.- f Addressable thermal heat and rate-of-rise detectors '' The SK-Heat, SK-Heat-HT, and SK-Heat-ROR are plug in thermal detectors, B • ' with integral communication, that provide features that surpass conventional detectors. These thermal detectors are for use with Silent Knight IntelliKnight series Fire Alarm Control Panels (FACPs). IntelliKnight heat detectors are an essential component in virtually any IntelliKnight installation. The IntelliKnight panel recognizes each detector by its specific address, so precious seconds are not wasted in determining location of an alarm. Description •Two module mounting in the IDP-ACB SK-Heat, SK-Heat-HT and SK- cabinet Heat-ROR are intelligent sensors • Up to two unused modules can be ,_," that utilize a state-of-the art disabled • thermistor sensing circuit for fast • Rotary address switches for fast response. Sensitivity is installation continuously monitored and 111111 reported to the FACP. Point ID • Mounting hardware included capability allows each detector's • UL Listed address to be set with rotary address switches, providing exact SK-Heat (base included) Specifications detector locations for selective Physical detection 15°F/min (8.3°C/min) maintenance when chamber Height: 2.0" (51 mm) contamination reaches Compatibility unacce table levels. Diameter: 6.1" (155 mm)installed in p B210LP base The SK-Ion is compatible with the SK-Heat is a fixed temperature Shipping Weight: 4.8 oz (137 g) following IntelliKnight FACP's: thermal detector that uses a Electrical 5700 thermistor sensing circuit to Operating Voltage: 15 to 32 Volts 5808 produce 135°F (57°C) fixed thermal DC Peak 5820XL detection. Standby Current: 300pA @ 24 The SK-Heat, SK-Heat-HT and SK- SK-Heat-HT is a high temperature VDC Heat-ROR are compatible with the detector that provides fixed following detector bases: temperature alarm at 190°F. LED Current: 6.5 mA@ 24 VDC SK-Heat-ROR is a fixed B210LP (included) 6" base temperature and rate-of-rise Environmental B501 2 wire base thermal detector that uses a Operating Temperature B224B1 Isolator base thermistor sensing circuit to SK-Heat & SK-Heat-ROR: -4°— B224RB Relay base produce 135°F (57°C) thermal 100°F (20°C— 38°C) B501 BH-2 Sounder base protection. SK-Heat-HT: -4°— 150°F 8501 BHT-2 Temporal base Features (20°C—66°C) • Converts a conventional two-wire Humidity: 10% — 93% loop to an SLC loop noncondensing • Six zone inputs Thermal Ratings • Fully supervised SK-Heat: Fixed temperature • Support for Class B and Class A setpoint 135°F (57°C) wiring SK-Heat-HT: High temperature heat SILENT • Removable 12 to 18 AWG plug in terminal blocks 190°F(88°C) co KNIGHT • Individual LED for each relay contact SK-Heat-ROR: Rate-of-rise by Honeywell INTELLIKNIGHT ACCESSORY Model SK-Heat, SK-Heat-HT, SK-Heat ROR Addressable Thermal and Rate-of-Rise Thermal Detectors Engineering Specifications The contractor shall furnish and install where indicated on the plans, Intelligent Thermal Sensor Silent Knight Model SK-Heat, SK-Heat-HT or SK-Heat-ROR. The base included shall be B210LP. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady at full brilliance. The detector may be reset by actuating the control panel reset switch. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field removable when not required.Voltage and RF/transient suppression techniques shall be employed to minimize false alarm potential. eI IN our Compatible F M P :La.. .. z AAIODF(+ phonal) E 'r E di III r PI 7 kil (-0.--IN CICI-- E Oh_ t A g...,1 ipak i' 4.10\ flap; [ -67111111II i. i'ill 3CC \ ��ft \411\ tom{ Ir .n., ,..A, r+. . .. .– —. . p «9Tt!'.7 ,im, ,1:r/-T,T f,,—.. ..� , >.4.,n . I .,.s., ..`,,.....�,s.<,�.�.,,.a.�,.�m,,,ti Wiring$I6-Se t46 attector Nowlin Sam Accessories M02-09-00-Test Magnet with Telescoping Handle. RA100Z-Remote LED Annunciator. XP-4-Extension Pole for XR2B. Extends from 5—15 ft. RMK400-Recessed Mounting Kit. Provides low profile for use with T55-127-000-Detector Removal Head. B501. BCK-200B-Black Detector Kit. For SK-series detectors. XR2B-Detector Removal Tool.A removal and re-placement tool for SK plug-in detectors. Includes the T55-127-000. *Unless otherwise noted, specifications apply to all SK thermal detectors. M02-04-01 -Replacement Test Magnet. IL E This document is not intended to be used for installation purposes.We try to MADE IN AMERICA NI keep our product information up-to-date and accurate.We cannot cover all * KNIGHT j specific applications or anticipate all requirements.All specifications are FORM#350119 Rev.A subject to change without notice. For more information, contact Silent Knight ©2009 Honeywell International Inc. � � 12 Clintonville Road Northford,CT 06472-1610 Phone: (800)328-0103, by ElonFax: (203)484-7118.www.silentknight.com . - •- SILENT SK-ISO KNIGHT Intelligent Fault Isolator Module by Honeywell The SK-ISO Isolator Module enable part of a communication loop to continue operating when a short circuit occurs on it. If a short occurs between any two isolators, then both isolators immediately switch to an open circuit state and isolate the device between them. For more information about the IntelliKnight system, or to locate you nearest source, please call 800-328-0103. Description The SK-ISO is an addressable line isolator module for use with Silent Knight IntelliKnight series fire alarm controln �,. panels (FACPs). } The SK-ISO acts as an automatic switch that opens when ' c3Frolnswr t the line voltage on the signaling line circuit (SLC) loop t Q drops below four volts. Isolator modules should be spaced between groups of sensors or modules in a loop to the rest of the loop. If a short occurs between any two isolators, then both isolators immediately switch to an open circuit state and isolate the devices between them. The remaining units on the SLC loop continue to fully operate. No more than 25 devices are recommended for x., each group. Features SK-iso • Panel controlled status LED that flashes green in normal state and is solid red in alarm Compatibility The SK-ISO is compatible with the following • Isolates short circuits on an SLC loop IntelliKnight Systems: 5700 • Protects the modules on the SLC loop so other devices 5808 continue to operate 5820XL 5820XL-EVS • Standard 4 inch electrical box mounting SK-FFT • SEMS screws for easy wiring • UL Listed Installation The SK-ISO mounts directly into a 4" square electrical box. The box must have a minimum depth of 2-1/8". A surface mount electrical box (System Sensor® PN SMB500) is available from Silent Knight. - I- - Model SK-ISO Intelligent Isolator Module SK-ISO Isolator Module SK-ISO Isolator Module • o * 1 1(-) Isolated Devices 2(+) 2(+) 3(-) —1(-) —1(-) 3(-) 4(+) • —2(+) —2(+) 4(+) • 0 Isolated + ! Groups of Devices are Separated by SK-ISO Isolator Modules. Devices IN - jur Any Combination of Compatible Listed Devices May Be SLCet-. Mixed Within a Group. !1(-) OUT + l��ia 2(+) - —1(-) A Pair of SK-ISO Isolator Modules Will Disconnect a 2(+) Compatible FACP Group of Devices if a Short Circuit Occurs on the Signaling Line Circuit Within that Group. SK-ISO Isolator Module SK-ISO Isolator Module i s Iv " p tv1" 1(-) Isolated Devices 1(-) 2(+) 2(+) 3 O —1(-) —1(-) 3(-) , 4(+) • —2(+) —2(+) 4(+) • rip alp • 1 , Wiring SK-ISO Modules Specifications Fault Detection Delay: 250 ms min. Physical Fault Detection Threshold: 4V Height: 4.5" (11.4 cm) Line Restoration Threshold: 7V Width: 4" (10.2 cm) Environmental Depth: 0.25" (0.6 cm) Operating Temperature: 32°F— 120°F (0°C—49°C) Shipping Weight: 6.3 oz (196 g) Humidity: 10% — 93% non-condensing Electrical Accessories Operating Voltage: 15—32 VDC SMB500 4" Square Surface Mount Electrical Box Standby Current: 450 pA max (not isolating; relay closed) Isolation Current: 5 mA max This document is not intended to be used for installation purposes.We try MADE IN AMERICA SILENT, to keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All FORM#350134 Rev D a specifications are subject to change without notice. For more information, ©2013 Honeywell International Inc. by Honeywell contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. For Technical Support, Please call 800-446-6444. www.silentknight.com , - • .- 10 SILENT SK-Minimon KNIGHT by Honeywell Intelligent Mini Monitor Module The SK-Minimon addressable mini monitor modules for use with Silent Knight IntelliKnight fire alarm control panels (FACP). The SK-Minimon is designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm initiation devices. For more information about the IntelliKnight system, or to locate your nearest source, please call 800-328-0103. Description # , The SK-Minimon is an addressable . It monitor modules for use with the IntelliKnight fire alarm control panels (FACPs). The SK-Minimon acts as an interface to contact devices, such as waterflow switches and pull stations. � The SK-Minimon supports Class B ` supervised wiring to the load device. Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions The SK-Minimon can be mounted in a single gang junction box directly behind the monitored device. Its small size and light weight allow it to be installed SK-Minimon without rigid mounting requirements. Specifications Humidity:° Electrical 10/o — 93/o non-condensing Features Operating Voltage: 15—32 VDC • Single contact monitor SLC Standbyand Alarm Current: • SK-Minimon support for Class B Compatibility (Style B) contact monitor wiring 350 pA The SK-Minimon is compatible with • Small and lightweight size allows End-of-Line Resistance: 47K Q the following IntelliKnight Systems: for flexible mounting options Initiating Device Circuit Wiring 5820XL • Rotary address switches for fast Resistance: 1,50052 max 5820XL-EVS installation SLC Loop Resistance: 40Q max. 5808 • UL listed 5700 Wire Length: 6" min. 5600 (Rev 2.0 or higher) Listings Physical SK-FFT UL Dimensions: CSFM 2.75" Wx1.3' Hx0.5" D FM Weight: 1.2 oz (37 g) Environmental Operating Temperature: 32°F — 120°F (0°C —49°C) P/N 350133 Rev F ©2015 Honeywell International Inc - SK-Minimon Intelligent Monitor Module Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable monitor modules Silent Knight SK-Minimon. The modules shall be UL listed and compatible with Silent Knight's IntelliKnight FACPs. The SK-Minimon shall be installed inside a single gang junction box directly behind the monitored unit. IN — SLC OUT ] r'f?] 1415 0 1 ADDRESS 0 1 2 Compatible FACP �� 1� '14 /4 1 3 98 7 6 LOOP 9 876 TENS ONES - + + - W to C 9 jr_in Other Devices Wiring the SK-Minimon SILENT This document is not intended to be used for installation purposes.We try to keep our product information 10 KNIGHT up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information, contact Silent Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. by Honeywell For Technical Support, Please Call 800-446-6444. www.silentknight.com I - •-- 410 SILENT SK-Monitor KNIGHT by Honeywell Intelligent Monitor Module The SK-Monitor module provides an interface to contact devices, such as security contacts, waterflow switches, or pull stations. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103. Description The SK-Monitor is an addressable monitor module for use with Silent Knight IntelliKnight series fire alarm control panels (FACPs). The SK-Monitor is intended for use in x , intelligent, two-wire systems, where individual address of ��' each module is selected using the built-in rotary switches The SK-Monitor supports Class A supervised or Class B �• supervised wiring to the load device. Conventional 4-wire r: „• smoke detectors can be monitored for alarm and trouble • ' conditions. `~w Features • Single contact monitor q • Support for Class A and Class B wiring • Fully supervised • Panel controlled status LED that flashes green in Jff;� s normal state and is solid red in alarm • Attractive ivory cover plate SK-Monitor • Rotary address switches for fast installation • SEMS screws for easy wiring Specifications • UL Listed Physical Installation Height: 4.5" (11.4 cm) The SK-Monitor mounts directly into a 4" square electrical Width: 4" (10.2 cm) box. The box must have a minimum depth of 2-1/8". A Depth: 1.25" (3 cm) surface mount electrical box (System Sensor® PN Shipping Weight: 6.3 oz (196 g) SMB500) is available from Silent Knight. Electrical Compatibility Operating Voltage: 15 — 32 VDC The SK-Monitor is compatible with the following Current Draw (LED on): 5.0 mA max IntelliKnight FACP's: Operating Current (LED flashing): 375 pA 5700 5808 5820XL 5820XL-EVS - . - • .- - Model SK-Monitor Intelligent Monitor Module DEY "C RIM PANEL OR i : c: X# PREVIOUSDEVICE M[)NNITGH ANY NUMBER OF I.L.LISTED CONRCT r-y MODULE t- CLCISLRE DEVICES PAYEE USED.CO NOT MX CCI MIECT MOOIJLESTO LISTED COMPATIBLE FRE ALARM INITIATING,SLFERVIECRY,DR op ib j PANELS F# B OILYSECLELI TY DEVICES ONTIE SAY8C E OLLE I i TO RESISTOR E1AA71i t I - -inn ♦—rj. NITKFITNEICEVICECJIT0DO)-NFPASTYLE9 ' PUNIER UMTED:4SBIIA MIX.0 11 WDC MAX tYi�tTALLC:[TNW T CLOSURE DEVICES PER ALLWR1NI3 MOAN IS BLPERNt�AMD POWER LASTED MANLIRIOTUFBYS INSTJILLATKSN NBTFLJCrIOMS. 2-Wire Initiating Circuit Configuration, NFPA Style B TO NEXT C ((-)+ " FROM PANEL OR DEVICE .i s AP.4111P— a a►i iii, 0 +r s i a l s . PREVIOUS DEVICE MONITOR ' , ANY NUMBER OF LIL LISTED CONTACT MODULE CI CLOSURE DEVICES MAY BE USED.DO NOT MIX ,, ! CONNECT MODULES TO LISTED CONWATIBLE FIRE ALARM INTIATING,SUPERVISORY,OR `O 00 0 NOTIFER CONTROL PANELS ONLY SECURITY DEVICES ON THE SAME MODULE ( • + 1 n kI�— .�J►(4 ••I I 1 EOL RESISTOR IS I Ms o , INTERNAL ATII lk 0I♦ Am TERMINALS 8 SO u u INSTALL CONTACT CLOSURE DEVICES PER ALL WIRING SHOWN IS SUPERVISED AND POWER UNITED MAMJFACTUFTER'8 INSTALLATION INSTRUCTIONS. 4-Wire Initiating Circuit Configuration, NFPA Style D Standby Current: Environmental 400 pA max @ 24 VDC (one communication every 5 Operating Temperature: 32°F— 120°F (0°C—49°C) sec with 47K EOL) Humidity: 10% — 93% non-condensing 550 pA max @ 24 VDC (one communication every 5 sec with EOL <1K) Ordering Information 5.5 mA(with LED latched on) SK-Monitor Monitoring Module LED Current: 5.5 mA(with LED latched on)End-of-Line Resistance: 47K Q Accessories Initiating Device Circuit Wiring Resistance: 1,500 c max SMB500 4" Square Surface Mount Electrical SLC Loop Resistance: 40 Q max. Box SILENT This document is not intended to be used for installation purposes.We try to Assembled in USA 110 keep our product information up-to-date and accurate.We cannot cover all KNIGHT specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information, contact Silent Knight 12 FORM#350131 Rev E by Honeywell Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203) ©2013 Honeywell International Inc. 484-7118. For Technical Support, Please call 8200-446-6444. www.silentknight.com - , •-• j: '' SK-Photo k and SK-Photo-T 11 • N ."' ' Intelligent Photoelectric Smoke Sensors The SK-Photo is a photoelectric smoke detector and the SK-Photo-T is a photoelectric smoke detector with thermal. These plug in smoke detectors, with integral communication, provide features that surpass conventional detectors and are for use with Silent Knight IntelliKnight Fire Alarm Control Panels (FACPs). For more information about the IntelliKnight system, or to locate your nearest source, please call 800-328-0103 or in Connecticut, call (203) 484-7161. Description • Plug-in mounting provides ease of installation ,',` SK-Photo and SK-Photo-T are plug-in , Tamper-proof feature available on �� type smoke sensors that combine a , photoelectric sensing chamber with mounting bases addressable analog communications. • Listed for use in duct applications / ,t .. Point ID capability allows each detector's address to be set with rotary • Rotary address switches for fast address switches, providing exact installation detector locations for selective • UL Listed ' maintenance when chamber • contamination reaches unacceptable FM Approved levels. Specifications SK-Photo and SK-Photo-T have a Physical unique optical sensing chamber that is engineered to sense smoke produced Height: 2.0" (5.0 cm) by a wide range of combustion Diameter: 4.1" (10.4 cm) sources. In the SK-Photo-T, dual Shipping Weight: 5.2 oz. (147 g) SK-Photo (Base included) electronic thermistors add 135°F (57°C) Electrical thermal technology to maximize Operating Voltage: 15-32 VDC Compatibility detection. Standby Current: The SK-Photo and SK-Photo-T are compatible with the following Features 300 pA @ 24 VDC Maximum IntelliKnight FACPs: • Sleek, low-profile design Alarm Current: 6.5 mA @ 24 VDC max 5700 • Base included (with LED on) 5808 • Reliable analog communications for Environmental 5820XL trouble-free operation Operating Temperature SK-Photo and SK-Photo-T are SK-Photo: 32°— 120°F (0°C—49°C) compatible with the following detector • Age resistant polymer housing SK-Photo-T: 32°— 100°F (0°C—38°C) bases: • Dual electronic thermistor design on Humidity: 10%—93% non-condensing B210LP (included)6" base the SK-Photo-T B501 2 wire base Other Ratings B501 BHT-2 Temporal base • Superior EMI resistance for reliability SK-Photo-T Thermal: Fixed B224RB Relay base • Simple field cleaning for code temperature set point 135°F (57°C) B224B1 Isolator base compliance Velocity: 0—4000 fpm (0—20 m/sec) B501 BH-2 Sounder base • Variety of mounting options to meet SK-Photo Insect Screen Hole Size: any application 0.016" (0.41 mm) nominal • Dual LED indicators for 360°visibility '.rILENT • Detector transmits signal to indicate KNIGHT maintenance is required • Optional remote LED annunciator by Honerivell (System Sensor° PN RA100Z) - . - . .-• Model SK-Photo and SK-Photo-T Intelligent Photoelectric Smoke : ,i Sensors Engineering Specifications The contractor shall furnish and install where indicated on the plans, Intelligent photoelectric smoke sensors Silent Knight SK-Photo or SK-Photo-T with thermal. The combination detector head, and twist-lock base, shall be UL listed and compatible with Silent Knight's IntelliKnight fire control panels. The base shall permit direct interchange with SK-Photo or SK-Photo-T. Base shall be the appropriate twist-lock base part number B210LP (included). The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SK-Photo shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. $LC I suers k '4 p##dh4e'ACF I. 1.,. R41 G17 Z(ti ph caa!) ml I = 1I ,IiP ,Chs 1 M.....441. r 1 3 PP , 4 j E r i t [ auxgp4tana111sA I Wiring$1 -Senn.s Ot4eztor Motar4Ing Sawa c c SILENTNI KNIG1IT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA keep oodeWa specificour applicationsprductinformatior anticipatenup-to-all reatequirements.andaccuratAll.specificationse cnnotcover are suallbject FORM#350118 Rev A, to change without notice. For more information,contact Silent Knight 12 ©2009 Honeywell International Inc. Its Hones Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. www.silentknight.com . - •- SK-Pull-SA and u ►SK-Pull-DA Intelligent Pull Stations a The SK-Pull-SA and SK-Pull-DA are a single action or dual action • addressable fire alarm pull station for use with Silent Knight's IntelliKnight SAP i fire control panel. Extremely easy to operate, the SK-Pull-DA/SA provides a fast and practical means of manually initiating a fire alarm signal. The 01.* IntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103 or in Connecticut, call (203) 484-7161. Description The SK-Pull-SA is a single action pull station requiring onlyr ri( one motion to activate the station. The SK-Pull-DA is a dual action pull station requiring two motions to active the station. Both pull stations are designed to work with Silent Knight IPULL 0040 Intelliknight series fire alarm control panels (FACPs). Features • Installer can open station without causing an alarm condition • Dual-color LED is visible through handle of station blinks green to indicate normal operation and remains steady red in an alarm condition SK-Pull-SA • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP locks • Meets the Americans with Disabilities Act Accessibility PUSH IN II Guidelines (ADAAG) controls and operating mechanisms rJLL6O'N•J+. guidelines (Section 4.1.3[13]) • Meets ADA requirement for 5 lbs maximum pull force to active • Shell, door, and handle molded from durable LEXAN® R • Reliable analog communications for trouble-free operation SK-Pull-DA • Braille text on station handle Comp • Handle latches in down position and the word Activated The am yam and SK-Beam-T are compatible appears, clearly indicating the station has been pulled with the following IntelliKnight FACP's: • Rotary address switches for fast installation 5700 5808 • UL Listed, including UL 38, Standard of Manually Actuated 5820XL Signaling System litSILENT KNIGHT by Honeywell ■ •.� Model SK-Pull-Da and SK-Pull-SA r�. rr Engineering Specifications The contractor shall furnish and install where indicated on the plans, Addressable Pull Stations, Silent Knight model SK-Pull-SA single action pull station or SK-Pull-DA, dual action pull station. SK-Pull-DA or SK-Pull-SA meet the ADAAG controls and operating mechanisms guidelines, and the ADA requirements for a 5 lb. maximum pull force to activate the pull station. QuiA1 ; r a Clans Et Co upatitar FACP r` „ 11 . 11 II II1 1111,1t aNSSIO AISA Wiring .... _ `•, Mitac op ON: _. lj Wiring SK Pu!l=S>ti 4 SK-Put-OA Put Stations Specifications Electrical Physical Operating Voltage: 15-32 VDC Height: 5.5” (14 cm) Average Operating Current (LED flashing): 300 pA Width: 4" (10.2 cm) Wire Gauge: Up to 12 AWG (3.1 mm2) Depth: 5.4 oz. (3.7 cm) Environmental Housing Material: LEXAN polycarbonate resin Operating Temperature 32°— 120°F (0°C—49°C) Bi-Colored LED: Humidity: 10%—93% non-condensing Blinking Green: Normal Steady Red:Alarm Accessories Switch: Single pole, single throw(SPST) normally open (N/O) BG-TR Optional trim ring. switch which closes upon activation of the pull station SB-I/O Surface backbox This document is not intended to be used for installation purposes.We try to MADE IN AMERICA SILENT keep our product information up-to-date and accurate.We cannot cover all KNIGHT specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information, contact Silent Knight FORM#350135 Rev A 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, ©2009 Honeywell International Inc. by Honeywell Fax: (203)484-7118. www.silentknight.com - •- SILENT SK-Relay 4101 KNIGHT Intelligent Relay Module by Honeywell The SK-Relay Module is intended for use in intelligent, two-wire systems where the individual address of each module is selected using the built in rotary switches. For more information about the IntelliKnight system, or to locate you nearest source, please call 800-328-0103. Description The SK-Relay is an addressable relay module for use with Silent Knight IntelliKnight series fire alarm control panels y st (FACPs). The SK-Relay allows a Silent Knight FACP to switch '„ discrete contacts by code command. The relay contains two isolated sets of Form C contacts, which operate as a DPDT switch. No supervision is provided for the notification appliance circuit. ate The SK-Relay contacts can be used for virtually any normally open or normally closed application. Each SK- SK-Relay Relay is programmed with a unique signaling line circuit (SLC) loop address. When an event occurs that controls the Installation SK-Relay, the relay is triggered by the FACP. The SK-Relay mounts directly into a 4" square Features electrical box. The box must have a minimum • Two sets of Form C contacts depth of 2-1/8". A surface mount electrical box • Rotary address switches for fast installation (System Sensor® PN SMB500) is available from Silent Knight • Contacts are rated for a variety of amps (see Specifications) Compatibility • Panel controlled status LED that flashes green in normal The SK-Relay is compatible with the following state and is solid red in alarm IntelliKnight FACP's: 5820XL • Relay programming is completely flexible—can be mapped 5820XL-EVS to zone conditions 5808 5700 • Polling LED visible through the cover plate 5600 (Rev 2.0 or higher) • Attractive ivory cover plate • SEMS screws for easy wiring • UL Listed - . - . •- - Model SK-Relay Intelligent Relay Module To Next Device — 4 If Any Wiring to Terminals 3—9 is Not Power + i Limited,the CB500 Barrier is Required.The CB500 Includes a Non-Power Limited Label, n n Which Must Be Placed Over the Power Limited 0 ° O Terminal Information on the Name Plate Label.CZ ......)] Relay Common 2 t • . 0 ■ Normally Closed 2IY • 3���1:b I I Is i Normally Open 2 't :' • 2 — From Compatible FACP Relay Common 1 10 • ; 7,18,' a � ' or Previous Device Normally Closed 1 .iso 5 V, � ' + —74 .. m...Z� Module Does Not Supervise 1.---.474— c ° O O Normally Open 1 Q Controlled Circuits • • U U Wiring the SK-Relay Module Specifications End-of-Line Resistance: not used Physical Standby Current: 300 pA max @ 24 VDC (one Height: 4.65" communication every 5 sec with LED enabled) Width: 4.25" LED Current: 5.5 mA(with LED latched on) Depth: 1.1" SLC Loop Resistance: 4052, max. Shipping Weight: 6.3 oz (196 g) Relay Contact Ratings Electrical 3.0A @ 30 VDC resistive Operating Voltage: 15— 32 VDC 0.9A @ 110 VDC resistive Current Draw: 6.5 mA max (LED on) 0.9A @ 125 VAC resistive Operating Current: 0.5A @ 125 VAC inductive (PF = .35) 230 pA(LED flashing) direct poll 0.7A @ 75 VAC inductive (PF = .35) 255 pA(LED flashing) group poll SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA 4f�j KNIGHT to keep our product information up-to-date and accurate.We cannot cover all specific applications or anticipate all requirements.All specifications are FORM#350127 Rev D subject to change without notice. For more information,contact Silent ©2013 Honeywell International Inc. by Honeywell Knight 12 Clintonville Road, Northford, CT 06472-1610 Phone: (800)328-0103, Fax: (203)484-7118. For Technical Support, Please Call 800-446-6444. www.silentknight.com ' ) genesis® ge'nests 2V7.OAh NP7-121 ,o n p E q - m 1"--. SEALED xrcxaxcFau '� rte, �IP4;(` „...: ENEHSYS m F4.xePa1YM111 N P 7- 12 xwErecxixn Y,.,.u.nr..•• NP7- 12FR Sealed Rechargeable Specifications .< Lead-Acid Battery •NOMINAL VOLTAGE: 12V •CHARGE RETENTION(shelf life) 12V, 7.0Ah at 68°F(20°C): •NOMINAL CAPACITY: 1 month 97°,t 20 hr.rate of 0.35A to 10.5V 7.0Ah 3 months 91% 10 hr.rate of 0.65A to 10.5V 6.5Ah 6 months 85% Terminal 5 hr.rate of 1.19A to 10.2V 5.95Ah 1 hr.rate of 4.20A to 9.60V 4.2Ah •LIFE EXPECTANCY: .185±.004 STANDBY USE 3 to 5 years •WEIGHT(approx.): 6.17 pounds CYCLE USE (approx.): .060 .020 (2.80 kgs.) 100%depth of discharge 250 cycles l' 50%depth of discharge 550 cycles 4 MIME ,. > •ENERGY DENSITY(20 hr.rate): 30%depth of discharge 1200 cycles o $ I illn — 1.49 WH/cubic inch(91.0 WH/liter) •SEALED CONSTRUCTION: 4 INCH = MM •SPECIFIC ENERGY(20 hr.rate): Can be operated in any position _ .250 6.35 13.6 WH/pound(30 WH/kg) without leakage. .185 4,70 4 .124 3.15 •INTERNAL RESISTANCE OF CHARGED •STANDARD TERMINAL: .098 2.49 BATTERY: Quick Disconnect.187 .031 ±.004 30 milliohms(approx.) or Optional.250 .060 1.52 .031 0.79 •MAXIMUM DISCHARGE CURRENT •HOUSING MATERIAL: ABS Resin .020 0.51 WITH STANDARD TERMINALS: .004 0.10 40 amperes •OPTIONAL: Container and cover made from •MAXIMUM SHORT-DURATION Flame Retardant ABS DISCHARGE CURRENT: (UL94-VO/L.O.1.>28%) Dimensions 210 amperes •OPERATING TEMPERATURE RANGE: ��1Z CHARGE 5°F to 122°F �f �J (-15°C 50°C) 656 I °40- 0 0- DISCHARGE -4°F to 144 0°F (2 56±ooa) (-20°C to 60°C) t t ) 15:± a- (595±0.04) o c II 1i P N -4 I H H DIMENSIONS:MM(INCHES) el" , UL listing pending-File No MH16464 En_er TM iS0 r 9000 TM Power/Full Solutions Publication No: US-NP7-12-02•July 2005 DISCHARGE CHARACTERISTIC TEMPERATURE EFFECTS IN RELATION CURVES AT 25°C (77°F) TO BATTERY CAPACITY Battery Battery Battery NP Temperature 25C(77°F) 13.0- 6.5-a.33__■ - .' -■ ■,IIMI n 12D . . . urW�46 • �� � \. Q za- so-aa � o �."RI`` 1 = 100¢ o9c P — — 1 - _41111��41IN►1 °A 110- 5.53.67 , d ..11',111M 01)_00C. C. LL • /T7(7-0.2 — t0.0- 5.0-3.33 --� ilium 1111 C7 9.0- -a.5-3.01.1111.2c/ A 11111111111 I2 80- 4.0-2.87 maim U A 1.111111.12D ,, r Pl 0 1 2 a s e 10 26 ao at z a s e 10 za -20 -10 0 10 20 30 40 50 (°C) I mm .(. h -24 14 32 50 68 86 104 122 (°F) Discharge Time Temperature SELF DISCHARGE CHARACTERISTICS OPEN CIRCUIT VOLTAGE VS REMAINING CAPACITY (,) (v) AT 25°C(77°F) ,_ 100 `1 a 14.0 co I- at 75 13.0 c� z G50 72.0 cc .... 20°C(60°F) a '— oc 40'C(104°F) 30'C(86'F) o 25 11.0 0 I 3 B 9 12 15 18 10.0 0 20 40 60 8I0 100 , STORAGE TIME(MONTHS) REMAINING CAPACITY(%) CYCLE SERVICE LIFE IN RELATION FLOAT SERVICE LIFE TO DEPTH OF DISCHARGE "' TESTING CONDITIONS:DISCHARGE CURRENT:0.17C AMP.(FN.1.7V/CELL) m j CHARGING CURRENT:0.09C AMP. -1 TESTING CONDITIONS:FLOATING VOLTAGE 2.25 TO 2.30V/CELL CHARGING VOLUME:125%OF DISCHARGED CAPACITY R AMBIENT TEMPERATURE:20'C TO 22°C(64°F TO 72°F) a (AH%) AMBIENT TEMPERATURE:20°C TO 25°C(68°F TO 771) a (AN%) 3- 120 120 100 1100 ••80 0 a 60 100"/D.O.D. 50%D.O.D. 30%DEPTH OF DISCHARGE z 20 wr. a 40 CC 0 1 2 3 4 5 5.5 ' a a 20 ' LIFE(YEARS) 0 200 400 600 800 1000 1200 1400 NUMBER OF CYCLES When the battery will be used by current in excess of 3C,consult with EnerSys prior to use. CHARGING METHODS(At 20°C) Cycle use: Maximum charging current 1.75A Charging voltage 14.4 to 15.0V CAUTION •Avoid short circuit Standby use: Float charging voltage 13.50 to 13.80V •Do not charge in a sealed container. EnerSys EnerSys EMEA Represented by: Ener P.O. Box 14145 Brussels, Belgium Reading, PA 19612-4145 Tel:+32(0)2 247 94 47 USA EnerSys Asia . Paoomo-Fuo solutions Tel.:+1-610-208-1991 Guandong, China +1-800-538-3627 Tel:+86 755 689 9220 Printed in U.S.A. www.enersys.com ©2005 EnerSys.All rights reserved. Trademarks are the property of EnerSys and its affiliates unless otherwise noted.