Report RECEIVED Matt 5863 Lakeview Blvd,#100 MAY 3 2018 Lake Oswego, OR 97035 ANA" CITY OF TIGARD (503)627-0100 CORPORATION BUILDING DIVISION FIRE ALARM TABLE OF CONTENTS Durham Square — Buildings 1 & 2 SW Durham Rd. Tigard, OR 97223 Drawing Notifier— NFW-50 Fire Alarm Control Panel DSC — 3G4010CF Cellular Communicator Notifier— NMM-100P Addressable Input Module Notifier — NOT-BG12LX Addressable Manual Pull Station Notifier— NP-100 Photoelectric Smoke Detector Gentex — GB6-24 and GBBB 24 Volt DC Water Flow Bell with Weatherproof Back Box = r - GMk:M I � PRT/PK-CABLE: Cable printer/personal computer interface DNR: InnovairFlex low-flow non-relay duct-detector housing. cable. (Order NP-100R separately.) PRN-6: UL listed compatible event printer. Uses tractor-fed DNRW: InnovairFlex low-flow non-relay duct-detector housing, paper. with NEMA-4 rating. Watertight.(Order NP-100R separately.) IPDACT, IPDACT-2/2UD Internet Monitoring Module: NMM-100: Addressable Monitor Module for one zone of nor- Mounts in bottom of enclosure with optional mounting kit(PN mally-open dry-contact initiating devices. Mounts in standard IPBRKT). Connects to primary and secondary DACT tele- 4.0" (10.16 cm.)box. Includes plastic cover plate and end-of- phone output ports for internet communications over customer line resistor. Module may be configured for either a Style B provided ethernet internet connection. Requires compatible (Class B)or Style D(Class A)IDC. Teldat Visoralarm Central Station Receiver. Can use DHCP or NDM-100: Dual Monitor Module.Same as NMM-100 except it static IP.(See data sheet do-60408 for more information.) provides two Style B(Class B)only IDCs. IPBRKT:Mounting kit for IPDACT-2/2UD in common enclosure. NMM-100P: Miniature version of NMM-100. Excludes LED IPSPLT: Y-adaptor option allows connection of both panel and Style D option.Connects with wire pigtails. May mount in dialer outputs to one IPDACT-2/2UD cable input. device backbox. AC-TRMBLK:AC Terminal Block mounts to a metal bracket,in NZM-100A:Similar to NMM-100A. Addressable Monitor Mod- turn, mounts to the FACP chassis. Use AC-TRMBLK when ule for one zone of conventional two-wire detectors. Requires wire nuts are not allowed for AC connections to the trans- resettable 24 VDC power. Refer to the Device Compatibility former. Document for listed compatible devices and quantity limita- OPTIONAL MODULES tion. 4XTM Reverse Polarity Transmitter Module: Provides a NZM-100-6: Six-zone interface module. Mount one or two mod- supervised output for local energy municipal box transmitter, modules inC a -6BBhaXP cabinet BB-2(optional). Mount up to six alarm and trouble. Includes a disable switch and disable trou- ble LED. NMM-100-10: Ten-input monitor module. Mount one or two ANN-SEC: Optional secondary ANN BUS interface module. modules in a BB-2 cabinet(optional).Mount up to six modules Note:Used only with firmware 3.0 or higher. on a CHS-6 chassis in a BB 25 cabinet. NC-100:Addressable Control Module for one Style Y/Z(Class COMPATIBLE ANNUNCIATORS B/A) zone of supervised polarized Notification Appliances. N-ANN-80(-W):Remote LCD annunciator mimics the informa- Mounts directly to a 4.0"(10.16 cm.)electrical box.Notification tion displayed on the FACP LCD display. Recommended wire Appliance Circuit option requires external 24 VDC to power type is un-shielded. (Basic model is black; order-W for white; notification appliances. see DN-7114.) NC-100R: Addressable relay module containing two isolated N-ANN-UO: LED Driver Module provides connections to a sets of Form-C contacts, which operate as a DPDT switch. user supplied graphic annunciator.(See DN-7105.) Mounts directly to a 4.0"(10.16 cm.)box,surface mount using N-ANN-LED: Annunciator Module provides three LEDs for the SMB500. each zone: Alarm, Trouble, and Supervisory. Ships with red NOT BG12LX: Addressable manual pull station with interface enclosure.(See DN-60242.) module mounted inside. N-ANN-RLED: Provides alarm (red) indicators for up to 30 N100-ISO:Fault Isolator Module. input zones or addressable points. (See DN-60242.) SMB500:Used to mount all modules except the NMM-100P. N-ANN-RLY: Relay Module provides 10 programmable Form- NOTE:For more information on Compatible Addressable Devices C relays. Can be mounted inside the cabinet. (See DN-7107.) for use with the FireWarden-50, see the following data sheets N-ANN-S/PG: Serial/Parallel Printer Gateway module pro- (document numbers):N100-ISO (DN-6994), NP-100 series (DN- vides a connection for a serial or parallel printer. (See DN- 6995), N1-100 (DN-6996), NH-100/NH-100R (DN-6997), DNR/ 7103.) InnovairFlex(DN-60424, DN-60429), NP-A100(DN-6998), NMM- 100/NMM-100P/NDM-100/NZM-100 (DN-6999), NC-100 (DN- ADDRESSABLE DEVICES 7000), NC-100R(DN-60383),NMM-100-10(DN-6990), and NOT- BG 12LX(DN-7001). All feature a polling LED and rotary switches for addressing. NI-100:Addressable low-profile ionization smoke detector. ADDRESSABLE DEVICE ACCESSORIES NP-100:Addressable low profile photoelectric smoke detector. End-of-Line Resistor Assembly (R-47K and R-3.9K): The 47k ohm assembly supervises the NMM-100-10, NDM-100, NP-100T:Addressable low-profile photoelectric smoke detec- NMM-100P, and NC-100 module circuits. The 3.9k ohm tor with thermal sensor. assembly supervises the NZM-100-6 module circuit. These NP-100R: Remote test capable addressable photoelectric resistors are included with each module. smoke detector for use with DNR(W)duct detector housing. Power Supervision Relay: Supervises the power to 4-wire NH-100:Fast response,low profile heat detector. smoke detectors and notification appliances. NH-100R: Fast-response, low-profile heat detector with rate- Wiring Requirements of-rise option. NH-100H: Fast-response, low-profile heat detector that acti While shielded wire is not required, it is recommended that all vales at 190°F/88°C. SLC wiring be twisted-pair to minimize the effects of electrical interference.Refer to the panel manual for wiring details. NP-A100:Addressable low-profile multi-sensor detector. DN-7102:E•02/22/2011—Page 3 of 4 ' a SYSTEM SPECIFICATIONS System Capacity (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the • Intelligent Signalling Line Circuits 1 50 useful life of the system's standby batteries and the electronic Addressable devlin capacitycomponents may be adversely affected by extreme tempera- • ture ranges and humidity. Therefore, it is recommended that • Programmable software zones 20 this system and its peripherals be installed in an environment • Annunciators 8 with a normal room temperature of 15—27°C/60—80°F. Electrical Specifications NFPA Standards AC Power: FireWarden-50: 120 VAC, 60 Hz, 3.0 A. FireWar- The FireWarden-50 complies with the following NFPA 72 Fire den-50E:240 VAC,50 Hz, 1.5 A.Wire size:minimum 14 AWG Alarm Systems requirements: (2.00 mm2) with 600 V insulation. Nonpower-limited, super- —LOCAL (Automatic, Manual, Waterflow and Sprinkler vised. Supervisory). Battery: Two 12 V 18 AH lead-acid batteries.Battery Charger —AUXILIARY(Automatic,Manual and Waterflow) (requires Capacity: 7-18 AH (FireWarden-50 cabinet holds maximum of 4XTM). two 18 AH batteries.) —REMOTE STATION (Automatic, Manual and Waterflow) Communication Loop: Supervised and power-limited. (Where a DACT is not accepted, the alarm, trouble and Notification Appliance Circuits: Terminal Block provides supervisory relays may be connected to UL 864 listed trouble, connections for two NACs,Style Y(Class B)or Style Z(Class For equiree polarity signaling of alarm and 4XT A). Special Application power. Power-limited, supervised cir- cuitry. trouble,4XTM is required.) Maximum signaling current per circuit: 2.5 A. End-of- —PROPRIETARY(Automatic,Manual and Waterflow). Line Resistor:4.7k ohm,1/2 watt(P/N 71252 UL listed)for Style —CENTRAL STATION (Automatic, Manual and Waterflow, Y(Class B)NAC. Refer to the NOTIFIER Device Compatibility and Sprinkler Supervised). Document for listed compatible devices. —OT, PSDN (Other Technologies, Packet-switched Data Two Programmable Relays and One Fixed Trouble Relay: Network) Contact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive). Form-C relays,nonpower-limited,nonsupervised. Agency Listings and Approvals The listings and approvals below apply to the basic FireWar- Cabinet Specifications den-50 control panel.In some cases,certain modules may not Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x be listed by certain approval agencies,or listing may be in pro- 0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x cess.Consult factory for latest listing status. 16.65° (42.29 cm.)wide x 5.25" (13.34 cm.)deep. Trim Ring • UL:S635 (TR-CE/B):22.00"(55.88 cm.)high x 19.65"(49.91 cm.)wide. • FM approved Shipping Specifications • CSFM:7165-0028:239 • MEA:442-06-E Vol.2 Weight:26.9 lbs.(12.20 kg.)Dimensions:20.00"(50.80 cm.) NOTE:See DN-60446 for ULC-listed model. high x 22.5"(57.15 cm.)wide x 8.5"(21.59 cm.)deep. Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 — 49°C/32 — 120°F and at a relative humidity 93% ± 2% RH NOTIFIER®, FireWarden®, and System Sensor® are registered trademarks of Honeywell International Inc. Microsoft®and Windows®are registered trademarks of the Microsoft Corporation. ©2011 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannotcover all specific applications or anticipate all requirements. CERTIFIED P pp UIUMHIM 8 NMM DATIMM All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 4 of 4—DN-7102:E•02/22/2011 DSC From Tyco Security Products Activating & Initializing the Unit Rate Plan Activating and initializing the 3G4010CF can be done using Cost-effective rate plans have been negotiated and are the automated telephone activation system(VRU), mobile available through authorized master resellers.Contact your interface or web-user interface provided by monitoring station or visit www.connect24.com to find a C24 Communications. No special tools are required. master reseller.When used as a sole communicator,the 3G4010CF requires use of the 4MB(NFPA72 2010)or Mobile Site for Easy Installation and 500kB(NFPA72 2013)rate plans to support the supervision Comprehensive Maintenance requirements. C24 Communications mobile site(m.connect24.com) Specifications makes the installation a simple process and offers intuitive trouble-shooting features, cutting down on time and cost Dimensions 11-1/2"x 10"x 3" allocated to maintenance. (290 mm x 254 mm x 75 mm) Input Voltage 120 VAC Current Draw 200 mA(standby) ,g, -°.v,. 400 mA(transmitting) ^-1--- Operating Environment 32°to 120°F(0°to 49°C) z Weight 12.8 lbs(5.8 kg) < m Optional Acessories > th Model Description UL Listing GS-15ANT 15 ft extension antenna(internal use) The 304010CF is UL listed under File S4019, Listing guide GS-25ANT 25 ft extension antenna UOXX, as a sole or backup communicator for Commercial Fire (internaVexternal use) monitoring installations.When used as a sole communicator GS-50ANT 50 ft extension antenna under NFPA72 2010 guidelines the 304010CF will send (intemaVexternal use) its heartbeat once every 97 seconds ensuring that three heartbeats will be received at the supervising station within the 300 second window.When used as a sole communicator under NFPA72 2013 guidelines the 3G4010CF will send its heartbeat once every 5 minutes to monitor connectivity with the supervising station within the 1 hour window.When used as a backup communicator the 3G4010CF will monitor the other communication method(DACT)and send a daily test • transmission to the supervising station. CSFM Listing The 3G4010CF has been approved by the California State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health and Safety Code. Ordering Information: 3G4010CF-USA Universal Wireless Commercial Fire Alarm Communicator (U.S. Model/SIM Card Included) 8 0 a communications For product information www.dsc.com poth 1 imps mci d harem 11 L,1 P 90n m0 r,-nor I J 1 I i 1 of P1rIe;coIIPe1lzs '�=:201 o Tyca Secun!y FuidH;U' Dimensions: 1.3" (3.302 cm) high x 2.75"(6.985 cm) wide x 0.65'(1.651 cm)deep. • Built-in type identification automatically identifies this device as a monitor module to the panel. Wire length:6"(15.24 cm)minimum. • Powered directly by two-wire SLC loop.No additional power required. NZM-100(A) Interface Module • High noise(EMF/RFI)immunity. • Supports compatible two-wire smoke detectors. • Tinned,stripped leads for ease of wiring. • Supervises IDC wiring and connection of external power • Direct Decade entry of address: 01 — 99 on FireWarden- source. 100-2,01 —50 on FireWarden-50. • High noise(EMF/RFI)immunity. 53 • SEMS screws with clamping plates for ease of wiring. 3 1415 0 1 ADDRESS 0 1 • Direct Decade entry of address:, 01 —99 on FireWarden- 13 , 2 2 100-2,01—50 on FireWarden-50. 3 12 4°1 4 LOOP �� 3 • LED flashes during normal operation. �I 4 • LED latches steady to indicate alarm on command from 10 9 6 5 I I g 6 5 control panel. 8 7 g 7 TENS ONES The NZM-100(A)Interface Module is intended for use in intelli- n n ri ri gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- wk 1- ire conventional smoke detectors.It transmits the status(nor- o W p Y mal,open,or alarm)of one full zone of conventional detectors - OJ 1 back to the control panel. All two-wire detectors being moni- m tored must be UL compatible with the module. NZM-100(A) APPLICATIONS Use the NZM-100(A) to monitor a zone of two-wire smoke I I I I detectors. The monitored circuit may be wired as an NFPA Style B(Class B)or Style D(Class A)Initiating Device Circuit. The NMM-100P(A) Mini Monitor Module can be installed in a A 3.9 K ohm End-of-Line Resistor (provided) terminates the single-gang junction directly behind the monitored unit. Its end of the Style B or D (class B or A) circuit(maximum IDC small size and light weight allow it to be installed without rigid loop resistance is 25 ohms). Install ELR across terminals 8 mounting.The NMM-100P(A)is intended for use in intelligent, and 9 for Style D application. two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiat- NZM-100(A)OPERATION ing device circuit for normally-open-contact fire alarm and Each NZM-100(A) uses one of the available module security devices. NMM-100P(A) addresses on an SLC loop. It responds to regular polls from NMM-100P(A)APPLICATIONS the control panel and reports its type and the status(open/nor- mal/short)of its Initiating Device Circuit(IDC).A flashing LED Use to monitor a single device or a zone of four-wire smoke indicates that the module is in communication with the control detectors,manual fire alarm pull stations,waterflow devices,or panel. The LED latches steady on alarm (subject to current other normally-open dry-contact devices. May also be used to limitations on the loop). monitor normally-open supervisory devices with special super- visory indication at the control panel. Monitored circuit/device NZM-100(A)SPECIFICATIONS is wired as an NFPA Style B(Class B)Initiating Device Circuit. Nominal operating voltage: 15 to 32 VDC. A 47K ohm End-of-Line Resistor(provided)terminates the cir- cuit. Maximum current draw:5.1 mA(LED on). NMM-100P(A)OPERATION Maximum IDC wiring resistance:25 ohms. Each NMM 100P(A) uses one of the available module Average operating current: 300 pA, 1 communication and 1 addresses on an SLC loop. It responds to regular polls from LED flash every 5 seconds,3.9k eol. the control panel and reports its type and the status(open/nor- EOL resistance:3.9K ohms. mal/short)of its Initiating Device Circuit(IDC). External supply voltage (between Terminals T3 and T4): NMM-100P(A) SPECIFICATIONS DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms maximum.Current:90 mA per module maximum. Nominal operating voltage: 15 to 32 VDC. Temperature range:32°F to 120°F(0°C to 49°C). Average operating current: 350 pA, 1 communication every 5 seconds, 47k EOL; 600 pA Max. (Communicating, IDC Humidity range: 10%to 93%noncondensing. Shorted). Dimensions: 4.5' (11.43 cm) high x 4" (10.16 cm) wide x Maximum IDC wiring resistance:40 ohms. 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125"(5.398 cm)deep box. Maximum IDC Voltage: 11 Volts. Maximum IDC Current:400 pA. EOL resistance:47K ohms. Temperature range:32°F to 120°F(0°C to 49°C). Humidity range: 10%to 93%noncondensing. Page 2 of 4—DN-6999:C•10/06/2010 j NDM-100(A) Dual Monitor Module • MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100); The NDM-100(A) Dual Monitor Module is intended for use in 227-03-E Vol.3(NDM-100) intelligent, two-wire systems. It provides two independent two- wire initiating device circuits(IDCs)at two separate,consecutive Product Line Information addresses.It is capable of monitoring normally open contact fire NOTE:'A"suffix indicates ULC-listed model. alarm and supervisory devices.The module has a single panel- controlled LED. NMM-100(A):Monitor module. NOTE: The NDM-100(A)provides two Style B(C/ass B)IDC cir- NMM-100P(A):Monitor module,miniature. cuits ONLY. Style D(Class A)/DC circuits are NOT supported in NZM-100(A):Monitor module,two-wire detectors. any application. NDM-100(A):Monitor module, dual,two independent Class B NDM-100(A)SPECIFICATIONS circuits. Normal operating voltage range: 15 to 32 VDC. SMB500:Optional surface-mount backbox. Maximum current draw:6.4 mA(LED on). NOTE: See installation instructions and refer to the SLC Wiring Average operating current:750 pA(LED flashing). Manual,PN 52304. Maximum'IDC wiring resistance: 1,500 ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current:240 pA EOL resistance:47K ohms. Maximum SLC Wiring resistance:40 Ohms. Temperature range:32°to 120°F(0°to 49°C). Humidity range: 10%to 93%(non-condensing). Dimensions: 4.5" (11.43 cm) high x 4' (10.16 cm) wide x 2.125"(5.398 cm)deep. NDM-100(A) AUTOMATIC ADDRESSING The NDM-100(A) automatically assigns itself to two address- able points, starting with the original address. For example, if the NDM-100(A) is set to address "26", then it will automati- cally assign itself to addresses"26"and"27". NOTE: Ones"addresses on the NDM-100(A)are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address,and terminals 8 and 9 use the second address. QCAUTION: Avoid duplicating addresses on the system. Installation NMM-100(A), NZM-100(A), and NDM-100(A) modules mount directly to a standard 4"(10.16 cm)square,2.125'(5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installa- tion instructions are provided with each module. All wiring must conform to applicable local codes,ordinances,and regu- lations. These modules are intended for power-limited wiring only. The NMM-100P(A) module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordi- nances,and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. • UL:S635 • ULC:S635 • FM Approved • CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM- 100);7300-0028:0237(NDM-100) DN-6999:C•10/06/2010—Page 3 of 4 Notifier®and FireWarden®are registered trademarks and FireWatchim is a trademark of Honeywell International Inc. ©2010 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. C E R T I F I E D We cannot cover all specific applications or anticipate all requirements. ENEIMBINI IMNLIPATIUry6 All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 4 of 4—DN-6999:C•10/06/2010 within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel,send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. Product Line Information NOT BG12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian applications.) SB-10:Surface backbox;metal. SB-I/O:Surface backbox;plastic. BG12TR:Optional trim ring. 17021:Keys,set of two. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess.Consult factory for latest listing status. • UL/ULC Listed: S692(listed for Canadian and non-Cana- dian applications). • MEA:67-02-E Vol.IV. • CSFM:7150-0028:0199. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. NOTIFIER®is a registered trademark of Honeywell International Inc. ©2012 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. C E R T F 1 E D We cannot cover all specific applications or anticipate all requirements. MI N,d IMIAf1IMMINI All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2—DN-7001:D•4/13/2012 Detector Sensitivity Test NP-100RA:Same as NP-100R with ULC Listing for use with a DNRA duct detector housing;B210LPA base included. Each detector can have its sensitivity tested (required per NFPA 72,Chapter 14 on Inspection, Testing and Maintenance) INTELLIGENT BASES when installed/connected to a FireWarden-100-2 or FireWar- NOTE:A°suffix indicates ULC Listed model. den-50 addressable fire alarm control panel.The results of the sensitivity test can be printed off the FireWarden-100-2 or Fire- NOTE:For details about intelligent bases and their mounting,see Warden-50 for record keeping. DN-60054. B210LP(A): Plug-in detector base (included); standard U.S. Specification flanged low-profile mounting base. Voltage range: 15-32 VDC(peak). B210LPBP:Bulk pack of B210LP;package contains 10. Standby current:300 pA 0 24 VDC. B501(A):Standard European flangeless mounting base. LED current:6.5 mA©24 VDC(latched"ON"). B501BP: Bulk pack of B501;package contains 10. Air velocity:4,000 ft./min.(20 m/sec.)maximum. B200SR(A): Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Size:2.1"(5.33 cm)high;base determines diameter. Replaces 8501 BH series bases in retrofit applications. -B210LP(A):6.1"(15.5 cm)diameter. B224RB(A): Plug-in System Sensor relay base. Screw termi- -B501(A):4.1"(10.4 cm)diameter. nals:up to 14 AWG(2.0 mm2).Relay type:Form-C.Rating:2.0 -B200SR(A):6.875"(17.46 cm)diameter. A © 30 VDC resistive; 0.3 A © 110 VDC inductive; 1.0 A -B224RB(A):6.2"(15.748 cm)diameter. 30 VDC inductive. Weight:3.6 oz.(102 g). B224B1(A): Plug-in System Sensor isolator detector base. Maximum 25 devices between isolator bases(see DN-6994). Operating temperature range: for NP-100(A):0°C to 49°C ACCESSORIES (32°F to 120°F);for NP-100T(A):0°C to 38°C(32°F to 100°F). NP-100R(A):installed in a DNR(A)/DNRW-20°C to 70°C(-4°F F110: Retrofit flange to convert B210LP(A) to match the to 158°F). B710LP(A) profile, or to convert older high-profile bases to Temperature:0°C-49°C(32°F-120°F). low profile. Relative humidity: 10%-93%,non-condensing. F110BP:Bulk pack of F110;package contains 15. F210:Replacement flange for B210LP(A)base. Listings RA100Z(A):Remote LED annunciator.3-32 VDC.Mounts to Listings and approvals below apply to the NP-100(A), NP- a U.S. single-gang electrical box. For use with B501(A) and 100T(A), and NP-100R(A) detectors. In some cases, certain B210LP(A)bases only. modules may not be listed by certain approval agencies, or SMB600:Surface mounting kit listing may be in process. Consult factory for latest listing sta M02-04-00:Test magnet. tus. • UL Listed:S1115. M02-09-00:Test magnet with telescoping handle. • ULC Listed:S911. XR2B: Detector removal tool. Allows installation and/or CSFM:7272 0028:0231. removal of detector heads from bases in high ceiling applica- • tions. • MEA:243-02-E Vol.2. XP-4: Extension pole for XR2B. Comes in three 5-foot(1.524 • Maryland State Fire Marshal:permit 2173. m)sections. • FM approved. T55-127-010:Detector removal tool without pole. Product Line Information BCK-200B:Black detector covers for use with NP-100(A)only; box of 10. NOTE:"A"suffix indicates ULC Listed model. WCK-200B: White detector covers for use with NP-100(A) NP-100: Adressable photoelectric detector; B210LP base only;box of 10. included. NP-100A:Sames as NP-100 with ULC Listing;B210LPA base included. NP-100T: Same as NP-100 but with thermal element; B210LP base included. NP-100TA: Same as NP-100T with ULC Listing; B210LPA base included. NP-100R: Remote test capable addressable photoelectric NOTIFIER® and FireWarden® are registered trademarks of Honeywell detector for use with a DNRA/DNRW duct detector housing; International Inc. B21 OLP base included. ®2011. All rights reserved. Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. • :;:;:;:� C E R T I F I E D We cannot cover all specific applications or anticipate all requirements. �IMi 3MAINACTINNI All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2-DN-6995:C•12/07/2011