Report (34) +P5401 r-ad 0,-. -- 1Cr065 st-' GterrN c/)-•- x ✓' tlIC 0 r, ( Worldwide www.tyco-fire.com Fire Protection Contacts Products Series TY-FRB, 5.6 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General NOTICE The TYCO Series TY-FRB Sprinklers 7,3 Description described herein must be installed and maintained in compliance with this doc The TYCO Series TY-FRB,5.6 K-factor, ument, as well as with the applicable Upright(TY313) and Pendent Y323 r' - R ) standards of the National Fire Protec- Sprinklers described in this data sheet tion Association,in addition to the Stan- are quick response,standard coverage, dards of any other authorities having decorative 3 mm glass bulb-type spray jurisdiction.Failure to do so may impair sprinklers designed for use in light or the performance of these devices. \ ordinary hazard,commercial occupan- cies such as banks, hotels, and shop- The owner is responsible for maintain ^ in malls. in their fire ping g protection system and „ The recessed version of the Series TY- devices in proper operating condition. The installing contractor or sprinkler FRB Pendent Sprinkler,where applica- manufacturer should be contacted with ble, is intended for use in areas with a any questions. finished ceiling.This recessed pendent sprinkler uses one of the following: • A two-piece Style 15 Recessed Sprinkler k Escutcheon with recessed adjust- Identification !---,1 x + ment up to 5/8 inch (15,9 mm)from , the flush pendent position. Number (SIN) • A two-piece Style 20 Recessed s Escutcheon with recessed adjust- TY313 Upright 5.6K, 1/2-NPT ment up to 1/2 inch (12,7 mm) from TY323 Pendent 5.6K, 1/2"NPT the flush pendent position. The adjustment provided by the Technical Recessed Escutcheon reduces the Temperature Rating accuracy to which the fixed pipe drops Data 135°F(57°C) to the sprinklers must be cut. 155°F(68°C) Intermediate level versions of Series Approvals 175°F(79°C) TY-FRB Sprinklers are described in UL and C-UL Listed 200°F(93°C) Technical Data Sheet TFP357. Sprin- FM, LPCB,and VdS Approved 286°F(141°C) kler guards and shields are described CE Certified Finishes in Technical Data Sheet TFP780. Sprinklers with Polyester Finish are UL Sprinkler:Refer to Table A and C-UL Listed as Corrosion-Resis- Recessed Escutcheon:White Coated, tant Sprinklers. Chrome Plated,or Brass Plated Maximum Working Pressure Physical Characteristics 175 psi (12.1 bar) Frame Bronze 250 psi(17.2 bar)* Button Brass/Copper `The maximum working pressure of 250 psi Sealing Assembly Stainless IMPORTANT (17.2 bar)only applies to the listing by Un- Steel w/TEFLON Always refer to Technical Data derwriters Laboratories,Inc.(UL). Bulb Glass Sheet TFP700 for the "INSTALLER Discharge Coefficient Compression Screw Bronze WARNING"that provides cautions K=5.6 GPM/psi1/2(80,6 LPM/bar1I2) Deflector Bronze with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 FEBRUARY 2014 TFP172 TFP172 Page 2 of 4 Components: *Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2" 7/16"(11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 6* _...... RICTLE —\ ----- / 5 Icf (11,11 mm) AA I t6" MI ioI c NOMINAL 2° 4 V MAKE IN (50yr CA ,8 mm) I I� 2 r ;, 2" \O CV 1-3/8" N.) A. f (50,8 mm) (34,9 mm) WRENCH ��� 3 4 J—_ ' FLATS 1/2"NPT** DEFLECTOR* 2-7/8"(73,0 mm)DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT(TY313)AND PENDENT(TY323)SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE G, Operation Installation The glass bulb contains a fluid which The TYCO Series TY-FRB,5.6 K-factor, WRENCH RECESS expands when exposed to heat.When Upright(TY313)and Pendent(TY323) (USE ONLY the rated temperature is reached, the Sprinklers must be installed in accor- END"A") fluid expands sufficiently to shatter the dance with this section. "017 glass bulb, allowing the sprinkler to General Instructions FIGURE 2 activate and water to flow. Do not install any bulb-type sprinkler if W-TYPE 6 the bulb is cracked or there is a loss SPRINKLER WRENCH Design of liquid from the bulb.With the sprin- kler held horizontally, a small air bub- Criteria ble should be present. The diameter WRENCH of the air bubble is approximately 1/16 RECESS The TYCO Series TY-FRB,5.6 K-factor, inch(1,6 mm)for the 135°F(57°C)and Upright(TY313) and Pendent(TY323) 3/32 inch(2,4 mm)for the 286°F(141°C) Or.' Sprinklers are intended for fire protec- temperature ratings. tion systems designed in accordance A leak tight 1/2 inch NPT sprinkler joint with the standard installation rules rec should be obtained by applying a min- d by the applicable Listing or imum to maximum torque of 7 to 14 Approval agency(such as, UL Listing ft.-lbs. (9,5 to 19,0 Nm). Higher levels 4 is based on the requirements of NFPA of torque can distort the sprinkler Inlet �r, 13, and FM Approval is based on the with consequent leakage or impairment PUSH WRENCH requirements of FM's Loss Prevention of the sprinkler. INTO ENSURE Data Sheets).Only the Style 15 or Style ENGAGEMENT 20 Recessed Escutcheon is to be used Do not attempt to compensate for WITH SPRINKLER for recessed pendent installations. insufficient adjustment in the Escutch- eon Plate by under-or over tightening WRENCHING AREA the sprinkler. Re-adjust the position of FIGURE 3 the sprinkler fitting to suit. W-TYPE 7 RECESSED SPRINKLER WRENCH Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1.Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. TFP172 Page 3 of 4 Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 2-7/8"DIA. 6 Sprinkler Wrench(Figure 2).With ref- (73,0 mm) erence to Figure 1,apply the W-Type 6 Sprinkler Wrench to the wrench flats. 2-1/4"DIA. Torque sprinklers 7 to 14 ft. lbs. (9,5 to FACE OF (57,2 mm) 19,0 Nm). SPRINKLER FITTING 5/8"(15,9 mm) Recessed Pendent Sprinklers The Series TY-FRB Recessed Pendent —� 1 FLUSH Sprinklers must be installed in accor (9,5±7,9 mm)3/8±5/16" �7� II i dance with the following instructions. Step A.After installing the Style 15 or } Style 20 Mounting Plate over the sprin- kler threads, and with pipe-thread SURFACE (3,2 mm) sealant applied to the pipe threads, CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) hand-tighten the sprinkler into the sprinkler fitting. TY-FRB PLATE 3/4"(19,1 mm) Step B.Tighten the sprinkler into the FIGURE 4 sprinkler fitting using only the W-Type SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) 7 Recessed Sprinkler Wrench (Figure WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 3).With reference to Figure 1,apply the RECESSED ESCUTCHEON W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque sprinklers 7 to 14 ft. lbs. (9,5 to 19,0 2 7/8"DIA. - Nm). (73,0 mm) FACE OF Step C.After ceiling installation and fin- SPRINKLER 2-1/4"DIA. ishing,slide on the Style 15 or Style 20 FITTING (57,2 mm) Closure over the Series TY-FRB Sprin- kler and push the Closure over the 5/16mm)" Mounting Plate until its flange comes in 1/2"(12,7 mm) (7,9±6,4 contact with the ceiling. FLUSH Care and t / �' + MOUNTING �i 1/8" J Maintenance SURFACE (3,2 mm) The TYCO Series TY-FRB,5.6 K-factor, Upright(TY313) and Pendent(TY323) CLOSURE SERIES MOUNTING 1-3/8"(34,9 mm) Sprinklers must be maintained and ser- TY-FRB PLATE viced in accordance with this section. 7/8"(22,2 mm) FIGURE 5 Before closing a fire protection system SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY(TY323) main control valve for maintenance WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 work on the fire protection system RECESSED ESCUTCHEON that it controls, obtain permission to shut down the affected fire protection Modified sprinklers must be replaced. standards of any other authorities hav- systems from the proper authorities Sprinklers that have been exposed to ing jurisdiction. Contact the installing and notify all personnel who may be corrosive products of combustion, but contractor or sprinkler manufacturer affected by this action. have not operated,should be replaced regarding any Absence of the outer piece of an if they cannot be completely cleaned g gp questions. escutcheon, which is used to cover by wiping the sprinkler with a cloth or Automatic sprinkler systems are rec- a clearance hole, can delay sprinkler by brushing it with a soft bristle brush. and maintained to be inspected, tested, Inspec- operation in a fire situation. and maintained by a qualified Care must be exercised to avoid dam- tion Service in accordance with local The owner must assure that the sprin- age to the sprinklers before,during,and requirements and/or national codes. after installation. Sprinklers damaged klers are not used for hanging any objects and that the sprinklers are only by dropping, striking, wrench twist/ slippage, or the like, must be replaced. cleaned by means of gently dusting with a feather duster; otherwise, non- Also, replace any sprinkler that has a operation in the event of a fire or inad cracked bulb or that has lost liquid from vertent operation may result. its bulb. (Ref. Installation Section.) Sprinklers which are found to be leak- The owner is responsible for the ing or exhibiting visible signs of corro- inspection,testing,and maintenance of their fire protection system and devices sion must be replaced. sprinklers must never be in compliance with this document, as Automaticainted, coated, or other-e well as with the applicable standards ad, plated,after leavingotetheo factory. of the National Fire Protection Associa- wisey tion (e.g., NFPA 25), in addition to the i TFP172 Page 4 of 4 P/N* 77 - XXX - X - XXX ' I I SPRINKLER TEMPERATURE FINISH RATINGS SIN 1 NATURAL BRASS 135 135°F(57°C) PURE WHITE(RAL9010)`* 155 155°F(68°C) 370 5.6K UPRIGHT(1/2"NPT) TY313 3 POLYESTER 4 SIGNAL WHITE(RAL9003) 175 175°F(79°C) 371 5.6K PENDENT(1/2"NPT) TY323 POLYESTER *Use suffix"I"for ISO 7-1 connection; 9 CHROME PLATED 200 200°F(93°C) for example,77-370-4-175-1 **Eastern Hemisphere sales only 286 286°F(141°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for avail- www.tyco-fire.com. ability.When placing an order,indicate the full product name and Part Num- ber(P/N). Sprinkler Assemblies with NPT Thread Connections Specify:Series TY-FRB Upright or Pen- dent(specify) Sprinkler, SIN (specify), K=5.6,Quick Response,(specify)tem- perature rating, (specify) finish, P/N (specify,refer to Table A). Recessed Escutcheon Specify:Style 15 Recessed Escutcheon with(specify*)finish,P/N(specify*) Specify: Style 20 Recessed Escutch- eon with(specify*)finish,P/N(specify*) *Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 1 1400 Pennbro k Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. /to ire Protection Products TEFLON is trademark of The DuPont Corporation.