Report 06,/ FCFIVEI) 2,II S 7 O _1 )1)18 Available Fault Current 10,000 Panel 24B CITY OF TIGA ' D !V1SJO AMPS 200 Main Lug Flush Mount Voltage 480/277 Phase 3 Wire 4 BRKR Connected Calculated Load Per Phase Connected BRKR Description D A P escription �^^ Amps ID A B C ID Amps c. A p 40 3 12.5T RTU 3 34 1 108.01 2 59.205 1 Xmer-PnI 228 90 3 " " 3 34 3 112.03 4 78.03 2 " " 3 34 5 113.17 6 79.17 5 " " III If7 0.00 8 9 0.00 10 11 0.00 12 13 0.00 14 15 0.00 16 17 " 0.00 18 19 0.00 20 21 0.00 22 23 0.00 24 25 0.00 26 27 0.00 28 29 0.00 30 31 0.00 32 33 0.00 34 35 0.00 36 37 0,00 38 39 0.00 40 41 0.00 42 Per Phase Ar 108.01 112.03 113.17 Max phase A 113.17 Code NEC Referance A B C 1 Lighting-SW-sign 215-2(A)(1) 74.01 0.00 0.00 2 Receptacle 0.00 78.03 0.00 3 HVAC/Heating 34.00 34.00 34.00 4 Kitchen Equipment 220-56 0.00 0.00 0.00 Qty of Kitchen Equipment on feeder 0 5 Equipment 0.00 0.00 79.17 Demand Factor 100% 6 Motor-largest 0.00 0.00 0.00 7 Motor 0.00 0.00 0.00 Available Fault Current 10,000 Panel 22B AMPS 200 Main Lug Flush Mount Voltage 208/120 Phase 3 Wire 4 BRKR Connected Calculated Load Per Phase Connected BRKR Description Description A P Amps ID A B C ID Amps A p 20 1 R-210,211,212 2 15 1 27.50 2 10 1 Lights 20 1 20 1 R-203,209 2 7.5 3 19.50 4 12 2 R-Autoclave-228 20 1 20 1 R-213,214,215 2 10.5 5 13.50 6 3 2 R-228 20 1 20 1 R-216,217 2 10.5 7 16.50 8 6 2 R-UC Freezer-217 20 1 20 1 R-227 2 3 9 3.00 10 NA 20 1 20 1 R-231 2 4.5 11 12.00 12 7.5 2 R-232,234 20 1 20 1 R-218,219 2 9 13 21.00 14 12 2 R-Autoclave-227 20 1 20 1 R-231 2 7.5 15 13.50 16 6 2 R-239,240,235,236 20 1 20 1 R-Washer-240 2 10 17 13.00 18 3 2 R-Counter-221 20 1 20 1 R-Autoclave-227 2 12 19 24.00 20 12 2 R-Autoclave-227 20 1 30 2 E-Water Heater235 5 16.28 21 22 28 22 6 2 R-UC Freezer-223 20 1 " " 5 16.28 23 22.28 24 6 2 R-UC Refer-203 20 1 20 1 R-207,226 2 9 25 13.50 26 4.5 2 R-230 20 1 30 2 E-Dryer-240 5 17 27 23.00 28 6 2 R-Copy/Prn-204 20 1 " " 5 17 29 23.00 30 6 2 R-Copy/Prn-205 20 1 30 1 R-Refer-221 2 10 31 22.00 32 12 2 R-Micro-221 20 1 20 1 Lights 1 11.26 33 14.08 34 NA 20 1 20 1 R-IH-221 2 8 35 20.50 36 10 1 Lights 20 1 20 1 R-205,223 2 6 37 12.00 38 6 2 R-204 20 1 20 1 R-DW-221 2 8 39 84.55 40 76.55 2 Sub-feed-Pnl G 80 2 20 1 R-234 2 6 41 78.25 42 72.25 2 " " Per Phase Ar 136.50 179.91 182.53 Max phase AI 182.53 I Code NEC Referance A B C 1 Lighting-SW-sign 215-2(A)(1) 12.50 14.08 12.50 2 Receptacle 124.00 132.55 136.75 3 HVAC/Heating 0.00 0.00 0.00 4 Kitchen Equipment 220-56 0.00 0.00 0.00 Qty of Kitchen Equipment on feeder 0 5 Equipment 0.00 33.28 33.28 Demand Factor 100% 6 Motor-largest 0.00 0.00 0.00 7 Motor 0.00 0.00 0.00 Available Fault Current 10,000 Panel 22G AMPS 100 Main Lug Flush Mount Voltage Phase 3 Wire 4 BRKR Connected Calculated Load Per Phase Connected BRKR Description Descri A P ption Amps ID A B ID Amps .. A P 20 1 Lg-OP-Lts-4L-15K 1 3.54 1 7.55 2 2.5 1 Sm-OP-Lts-3L-10K 20 1 20 2 2Ton Nsplit RTU 3 17.5 3 35.00 4 17.5 3 2Ton split RTU 20 2 3 17.5 5 35.00 6 17.5 3 " " II II 20 1 R-Chair 2 10 7 4 20.00 8 10 2 R-Chair 20 1 20 1 R-Microscope(3) 2 9 9 15.00 10 6 2 R-Microscope(2) 20 1 20 1 R-4duplex 2 6 11 12.00 12 6 2 R-4duplex 20 1 20 1 AutoClave 2 16 13 19.00 14 3 2 R-204 20 1 20 1 Sterile-Lts 1 1 15 5.25 16 4 2 Router 20 1 17 0.00 18 Space 20 1 NA 19 0.00 20 NA NA 21 0.00 22 NA NA 23 0.00 24 NA NA 25 0.00 26 NA NA 27 0.00 28 NA NA 29 0.00 30 NA NA 31 0.00 32 NA NA 33 0.00 34 NA NA 35 0.00 36 NA NA 37 0.00 38 NA NA 39 0.00 40 NA NA 41 0.0042 NA Per Phase Ar 76.55 72.25 ` Max phase A 76.55 Code NEC Referance A B 1 Lighting-SW-sign 215-2(A)(1) 7.55 1.25 2 Receptacle 39.00 19.00 3 HVAC/Heating 0.00 35.00 4 Kitchen Equipment 220-56 0.00 0.00 Qty of Kitchen Equipment on feeder 0 5 Equipment 0.00 0.00 Demand Factor 100% 6 Motor-largest 0.00 0.00 7 Motor 0.00 0.00