Loading...
Report (37) -FE'S 2v 1"7--00(25 I L115- CIL/ 7o DN-60602:A1 FireWarden-100-2(E) Rev 3 NOTIFIER® Intelligent Addressable FACP by Honeywell Addressable Fire Alarm Control Panel General The Notifier FireWarden-100-2 Rev 3(NFW2-100) with Version 5.0 firmware is a combination FACP(Fire Alarm Control Panel) and DACT(Digital Alarm Communicator/Transmitter)all on one circuit board.This compact intelligent addressable control panel has an extensive list of powerful features. The SLC(Signaling Line Circuit)of the FireWarden-100-2 Rev 3 operates using a Rapid Group Polling communication protocol technology that polls multiple devices simultaneously for a quicker device response time.This patented technology allows a fully-loaded panel with up to 198 devices to report an incident and activate the notification circuits in under 10 seconds. With this improved polling,devices can be wired on standard twisted, unshielded wire up to a distance of 10,000 feet. The's quick-remove chassis protects the electronics during con- struction. The backbox can be installed allowing field wiring to be pulled. When construction is completed, the electronics can be quickly installed with just two bolts. New features for Rev 3 with Version 5.0 firmware include removable terminal blocks, improved transient protection, addi- tional secondary ANN-BUS,and increased power for the reset- table and remote sync outputs. Available accessories include ANN-BUS devices as well as ACS LED, graphic and LCD annunciators, and reverse polarity/city box transmitter. The integral DACT transmits system status(alarms,superviso- ries, troubles, AC loss, etc.) to a Central Station via the public • Remote site or local USB port upload/download, using PS- switched telephone network. It also allows remote and local pro- Tools. gramming of the control panel using the PS-Tools Upload/Down- • Four (4) Style Y (Class B) NAC circuits, which can be con- load utility. In addition,the control panel may be programmed or verted to four (4) Style Z (Class A) circuits with optional interrogated off-site via the public switched telephone network. ZNAC-92 converter module. (Up to 6.0 amps total NAC Any personal computer with Windows@ XP or greater, a com- power when using optional XRM-24B.) patible modem, and PS-Tools—the Upload/Download software • Selectable strobe synchronization for System Sensor,Whee- kit—may serve as a Service Terminal.This allows download of lock,and Gentex devices. the entire program or upload of the entire program, history file, • Remote Acknowledge, Silence, Reset and Drill via address- walktest data, current status and system voltages. The panel able monitor modules or FDU-80, N-ANN-80 or Legacy ACS can also be programmed through the FACP's keypad or via a Annunciators. standard PS-2 computer keyboard, which can be plugged directly into the printed circuit board.This permits easy typing of • ANN BUS for connection to following optional modules(cannot address labels and other programming information. be used if ACS annunciators are used): Version 5.0 firmware supports the following: Primary and Sec –N-ANN-80(-W)Remote LCD Annunciator ondary ANN-bus devices,NP-Al 00,USB port,NAC circuit diag- –N-ANN-I/O LED Driver nostics,a new report has been added to the walk-test that lists –N-ANN-S/PG Printer Module untested devices, new device types added: audio telephone –N-ANN-RLY Relay Module type code for NFV-25/50ZST,Photo Supervisory and auto-reset- –N-ANN-LED Annunciator Module table Drill(non-latching). –N-ANN-RLED Annunciator Module alarms only The FireWatch Series internet monitoring modules IPDACT-2 –ROME Relay Option Module Enclosure and IPDACT-2UD permit monitoring of alarm signals over the Internet saving the monthly cost of two dedicated business tele • ACS&Terminal-mode Annunciators: phone lines. Although not required, the secondary telephone –ACS Annunciators:Up to 32 Legacy ACM Series annuncia- line may be retained providing backup communication over the tors (ACM-16AT or ACM-32 series). Cannot be used if public switched telephone line. ANN-BUS devices are used. NOTE: Unless otherwise specified, the term `FireWarden-100-2" –Terminal-mode Annunciators: Up to 32 Legacy FDU-80 is used in this document to refer to both the FireWarden-100-2 and annunciators. the FireWarden-100-2E FACPs(Fire Alarm Control Panels). Like- • EIA-232 printer/PC interface(variable baud rate)on main cir- wise, "NFW2-100"refers to NFW2-100E as well. cuit board,for use with optional UL-listed printer PRN-6. • Integral 80-character LCD display with backlighting. Features • Real-time clock/calendar with automatic daylight savings H • Listed to UL standard 864,9th edition. control. • On-board DACT. • Detector sensitivity test capability(NFPA 72 compliant). DN-60602:A1•12/07/2010—Page 1 of 6 • History file with 1,000-event capacity. • Ground Fault(yellow) • Maintenance alert warns when smoke detector dust accumu- KEYPAD CONTROLS lation is excessive. • Automatic device type-code verification. • Acknowledge/Step • One person audible or silent walk test with walk-test log and • Alarm Silence printout. • Drill • Point trouble identification. • System Reset(lamp test) • Waterflow(nonsilenceable)selection per monitor point. • 16-key alpha-numeric pad(similar to telephone keypad) • System alarm verification selection per detector point. • 4 cursor keys • PAS(Positive Alarm Sequence)and presignal delay per point • Enter (NFPA 72 compliant). NOTE:Only detectors may participate in PAS. Product Line Information SLC LOOP: NFW2-100: FireWarden-100-2 Rev 3 198-point addressable • SLC can be configured for NFPA Style 4,6,or 7 operation. Fire Alarm Control Panel,one SLC loop. Includes 80-character • SLC supports up to 198 addressable devices per loop (99 LCD display, single printed circuit board mounted on chassis, detectors and 99 monitor,control,or relay modules). and cabinet. 120 VAC operation. • SLC loop maximum length 10,000 ft.(3,000 m.). NFW2-100R:Same as NFW2-100,except in a red backbox. See installation manual for wire tables. NFW2-100E:Same as NFW2-100,except with 240 VAC opera- NOTIFICATION APPLIANCE CIRCUITS(NACS): tion. 4XTM Reverse Polarity Transmitter Module: Provides super- • Four onboard NACs with additional NAC capability using out- vised output for local energy municipal box transmitter, alarm, put control modules (NC-100). The four Class B NACs can and trouble. be converted to four Class A NACs with optional ZNAC-92 converter module. ZNAC-92: Optional converter module which converts four (4) • Silence Inhibit and Auto Silence timer options. Style Y (Class B) NAC circuits to four(4) Style Z(Class A) cir- cuits. • Continuous, March Time, Temporal or California code for PS Tools: Programming software for Windowse-based PC main circuit board NACs with two-stage capability. computer(cable not included),available on www.firelite.com. • Selectable strobe synchronization per NAC. • 2.5 amps maximum per each NAC circuit. DP-9692B:Optional dress panel for FireWarden-100-2 Rev 3. NOTE:Maximum 24VDC system power output is shared among TR-CE-B:Optional trim Ring for semi flush mounting. all NAC circuits and 24VDC special-application auxiliary power BB-26: Battery backbox, holds up to two 26 AH batteries and outputs. Total available output is 3.0 amps. Using the optional CHG-75. XRM-24B transformer increases 24VDC output to 6.0 amps. NFS-LBB:Battery box,houses two 55 AH batteries. PROGRAMMING AND SOFTWARE: CHG-75: Battery charger for lead-acid batteries with a rating of • Autoprogram(learn mode)reduces installation time. 25 to 75 AH. • Custom English labels (per point) may be manually entered CHG-120: Remote battery charging system for lead-acid batter- or selected from an internal library file. ies with a rating of 55 to 120 AH. Requires additional NFS-LBB • Three Form-C relay outputs(two programmable). for mounting. • 99 software zones. NOTE: CHG-120 or CHG-75 required for batteries larger than Continuous fire protection during online programming at the 18AH. • front panel. BAT Series:Batteries,see data sheet DN-6933. • Program Check automatically catches common errors not XRM-24B(E): Optional transformer. Increases system power linked to any zone or input point. output to 6.0 amps. Use XRM-24BE with FireWarden-100-2E • OFFLINE PROGRAMMING: Create the entire program in Rev 3. your office using a Windows®-based software package PRT/PK-CABLE: Cable printer/personal computer interface (NFW2-100 requires PS-Tools Programming software, avail- cable;required for printer or for local upload/download program- able on www.magni-fire.com).Upload/download system pro- ming and updating panel firmware. gramming locally to the NFW2-100 Rev 3 in less than one PRN-6: UL listed compatible event printer. Uses tractor-fed minute. paper. • USB upload/download programming with standard Male-A to IPDACT2/2UD, IPDACT Internet Monitoring Module: Mounts Male-B cable. in bottom of enclosure with optional mounting kit(PN IPBRKT). Connects to primary and secondary DACT telephone output User Interface ports for internet communications over customer provided ether- net internet connection. Requires compatible Teldat LED INDICATORS VisorALARM Central Station Receiver.Can use DHCP or static • AC Power(green) IP.(See data sheet DN-60408 for more information.) • Fire Alarm(red) IPBRKT:Mounting kit for IPDACT-2/2UD in common enclosure. • Supervisory(yellow) IPSPLT:Y-adaptor option allows connection of both panel dialer • Alarm Silenced(yellow) outputs to one IPDACT-2/2UD cable input. • System Trouble(yellow) COMPATIBLE ANNUNCIATORS • Maintenance/Presignal(yellow) N-ANN-80(-W): LCD Annunciator is a remote LCD annunciator • Disabled(yellow) that mimics the information displayed on the FACP LCD display. • Battery Fault(yellow) Recommended wire type is un-shielded. (Basic model is black; order-W version for white;see DN-7114.) Page 2 of 6—DN-60602:A1•12/07/2010 N-ANN-LED:Annunciator Module provides three LEDs for each Appliance Circuit option requires external 24 VDC to power noti- zone: Alarm, Trouble and Supervisory. Ships with red or black fication appliances. enclosure(see DN-60242). relay moduletwo 00 N-ANN-RLED:Provides alarm(red)indicators for up to 30 input se slof Form Cessable con acts, which operatenasning a DPDTisolated swtch. zones or addressable points.(See DN-60242). Mounts directly to a 4.0" (10.16 cm.) box, surface mount using N-ANN-RLY: Relay Module, which can be mounted inside the the SMB500. cabinet, provides 10 programmable Form-C relays. (See DN- NOT BG12LX: Addressable manual pull station with interface 7107.) module mounted inside. ROME-B: Relay Option Module Enclosure (order ROME-B for N100-ISO: Fault Isolator Module.This module isolates the SLC black or ROME for red). Provides one N-ANN-RLY Relay Mod- loop from short circuit conditions(required for Style 6 or 7 oper- ule already installed. The ROME Series provides mounting ation). space for one additional Relay Module or one addressable Multi- SMB500:Used to mount all modules except the NMM-100P. module. (See Installation Sheet PN 53530.) N-ANN-S/PG: Serial/Parallel Printer Gateway module provides NMM-100-10: Ten-input monitor module. Mount one or two a connection for a serial or parallel printer.(See DN-7103.) a BB-XP n ainet(optional).Mount up to six modules onn a N-ANN-I/O: LED Driver Module provides connections to a user a CHS-6 chassis in BB-25. supplied graphic annunciator.(See DN-7105.) NZM-100-6: Six-zone interface module for compatible conven- tional B-XP ACM-8R:Relay module provides 8 Form-C 5.0 amp relays. cabinet(optional)t Mount po-wire deectors. ount to six modules on aone or twouCHS-6 in ahassis ACM Annunciator Series: LED-type fire annunciators capable in a BB-25. of providing up to 99 software zones of annunciation.Available NOTE:For more information on Compatible Addressable Devices in increments of 16 or 32 points to meet a variety of applications. for use with the Fire Warden-100-2 Rev 3, see the following data LDM Graphic Series: Lamp Driver Module series for use with sheets(document numbers):N100-ISO(DN.-6994),NP-100 series custom graphic annunciators. (DN-6995),NI-100(DN-6996),NH-100 series (DN-6997),ND-100 FDU-80(Liquid Crystal Display)point annunciator:80 char- series (DN-7006), NP-A100 (DN-6998), NMM-100/NMM-100P/ NDM-100/NZM-100 (DN , NC-100/NC-100R acter, backlit LCD-type fire annunciators capable of displaying NOT-BG12LX (DN-7001),6999)NMM-100-10 (DN-6990), and NZM- English-language text. 100-6(DN-60150). NOTE:For more information on Compatible Annunciators for use with the Fire Warden-100-2 Rev 3, see the following data sheets Wiring Requirements (document numbers)ACM-8R(DN-3558),ACS/ACM Series(DN- 0524),LDM Series(DN-0551),FDU-80(DN-6820). While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical COMPATIBLE ADDRESSABLE DEVICES interference.Wire size should be no smaller than 18 AWG(0.78 All feature a polling LED and rotary switches for addressing. mm2) and no larger than 12 AWG (3.1 mm2). The wire size NI-100:Addressable low-profile ionization smoke detector, depends on the length of the SLC circuit. Refer to the panel NP-100:Addressable low-profile photoelectric smoke detector. manual for wiring details. NP-100T:Addressable low-profile photoelectric smoke detector with thermal sensor. NP-100R: Addressable remote test capable detector for use with DNR(W)duct smoke detector housings. NH-100:Fast-response,low-profile heat detector. NH-100R: Fast-response,low-profile heat detector with rate-of- rise option. NH-100H: Fixed high-temperature detector that activates at 190F/88C. NP-A100:Addressable low-profile multi-sensor detector. DNR: Innovair Flex low-flow non-relay duct-detector housing. Order NP-100R separately. DNRW: Innovair Flex low-flow non-relay duct-detector housing, with NEMA-4 rating. Watertight.(Order NP-100R separately.) NMM-100: Addressable Monitor Module for one zone of nor- mally-open dry-contact initiating devices. Mounts in standard 4.0"(10.16 cm.)box.Includes plastic cover plate and end-of-line resistor.Module may be configured for either a Style B(Class B) or Style D(Class A)IDC. NDM-100: Dual Monitor Module. Same as NMM-100 except it provides two Style B(Class B)only IDCs. NMM-100P: Miniature version of NMM-100. Excludes LED and Style D option.Connects with wire pigtails.May mount in device backbox. NZM-100: Similar to NMM-100, but may monitor up to 20 con- ventional two-wire detectors. Requires resettable 24 VDC power.Consult factory for compatible smoke detectors. NC-100: Addressable Control Module for one Style Y/Z (Class B/A) zone of supervised polarized Notification Appliances. Mounts directly to a 4.0" (10.16 cm.) electrical box. Notification DN-60602:A1•12/07/2010—Page 3 of 6 FireWarden-100-2 Rev 3 - 4 Fire Alarm Control/ fl ANN-BUS Communicator or ANN-BUS DEVICES EIA-485 N-ANN-80,N-ANN-LED, in ACS mode t? N-ANN-S/PG,N-ANN-I/O (two wires) _ o SMOKE DETECTORS _ NP-100,NP-100T, 24 VDC NI-100,NP-A100 I I? .1 I Optional Ci MEI nM f a REVERSE :v o: POLARITY/ HEAT DETECTORS My n= CITY BOX NH-100,NH-100R,NH-100H my n: OUTPUT 'Ea CI m (4XTM) ' � — ma CI= ANNUNCIATORS / 1 / 1 1 ♦ / ' _ -� II 1• ACS/ACM,LDM 8 FORM-C,5-AMP RELAYS DUCT DETECTORS NOTE:System can use (optional,order ACM-8R) ND-100,ND-100R,DNR either ANN-BUS devices OR ACS-mode annunciators. Quo ono They cannot be used • simultaneously. NACs(Notification 0 Appliance Circuits) 1 0,f 0. BELLS,SIGNALS,STROBES MONITOR/CONTROL NMM-100,NZM-100, NDM-100,N100-ISO, - EIA-232 NC-100,NC-100R INTERFACE (PIM-24)built into the motherboard Ie ► iiiii 11111 / /—� u O O O ADDRES ABLE MULTI-MODULE PRINTER NZM-100-6,NMM-100-10 NOTE:System can use either the printer OR the FDU-80. They t?_E1(6) cannot be used simultaneously. —�'- EIA-485 24 VDC INTERFACE ,, ii (four wires) MINI-MONITOR ► . NMM-100P • FI • RE FDU-80 LI Up to 6,000 ft.(1825.8 m) o between each FDU-80 in '; the EIA-485 loop,and between PULL STATION a each FDU-80 and the FACP. NOT-BG12LX e Page 4 of 6—DN-60602:A1•12/07/2010 SYSTEM SPECIFICATIONS System Capacity (42.29 cm.)wide x 5.20" (13.34 cm.)deep.Trim Ring(TR-CE- • Intelligent Signalling Line Circuits 1 B):22.00"(55.88 cm.)high x 19.65"(49.91 cm.)wide. • Addressable device capacity 198 • Programmable software zones 99 Shipping Specifications • ACS Annunciators 32 Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00" (50.80 cm.) • ANN-bus devices 16 high x 22.5"(57.15 cm.)wide x 8.5"(21.59 cm.)deep. Electrical Specifications Temperature and Humidity Ranges AC Power: FireWarden-100-2 Rev 3: 120 VAC, 60 Hz, 3.0 This system meets NFPA requirements for operation at 0(non- amps. — FireWarden-100-2 Rev 3(E):240 VAC,5 0 Hz, 1.5 amps. 49 den n 120°F 32an°C at a re(90°F 3 humidity. However,±2%RH Wire size:minimum 14 AWG(2.00 mm2)with 600 V insulation. licondensing) at 32°C ±2°C (90°F±3°F). the useful e electronic compo- Battery charger capacity:7 AH-18 AH batteries.Up to two 18 rents may be of the adversem's lyy affendbycted by extrematteries and e temperature ranges Ah batteries can be housed in the FACP cabinet. Larger batter- and humidity. Therefore,it is recommended that this system and ies require an external battery charger such as the CHG-75 or its peripherals be installed in an environment with a normal room CHG-120,and a separate battery cabinet such as the BB-26 or temperature of 15—27°C/60—80°F. NFS-LBB. Communication Loop:Supervised and power-limited. NFPA Standards Notification Appliance Circuits: Each terminal block provides The FireWarden-100-2 Rev 3 complies with the following NFPA connections for two Style Y(Class B) for a total of four Style Y 72 Fire Alarm Systems requirements: (Class B)or with an optional ZNAC-92 module converts to four Style Z(Class A) NACs. Maximum signaling current per circuit: —LOCAL (Automatic, Manual, Waterflow and Sprinkler 2.5 amps. End-of-Line Resistor:4.7K ohm, 1/2 watt(P/N 71252 Supervisory). UL listed)for Style Y(Class B)NAC. Refer to panel documenta- —AUXILIARY (Automatic, Manual and Waterflow) (requires tion and Notifier Device Compatibility Document for listed com- 4XTM). patible devices. —REMOTE STATION (Automatic, Manual, Waterflow and Two Programmable Relays and One Fixed Trouble Relay: Sprinkler Supervisory)(Where a DACT is not accepted,the Contact rating:2.0 amps @ 30 VDC(resistive),0.5 amps CO 30 alarm,trouble and supervisory relays may be connected to VAC(resistive).Form-C relays. UL 864 listed transmitters. For reverse polarity signaling of Special Application Non-resettable Power (24 VDC Nomi- alarm and trouble,4XTM is required.) nal):Jumper selectable(JP4)for conversion to resettable power —PROPRIETARY (Automatic, Manual,Waterflow and Sprin- output. Up to 1.0 amp total DC current available from each out- kler Supervisory). put.Power-limited. —CENTRAL STATION (Automatic, Manual, Waterflow and Special Application Resettable Power (24 VDC nominal): Sprinkler Supervisory). Jumper selectable(JP6)for conversion to non-resettable power. —OT,PSDN(Other Technologies, Packet-switched Data Net- Up to 1.0 amp total DC current available. Refer to the Notifier work) Device Compatibility Document for listed compatible devices. Remote Sync Output: Remote power supply synchronization Agency Listings and Approvals output. Nominal special application power: 24 VDC. Maximum The listings and approvals below apply to the basic FireWarden- current:300 mA. End-of-Line Resistor:4.7K ohm.Output linked 100-2 Rev 3 control panel. In some cases,certain modules may to NAC 1 control.Supervised and power-limited. not be listed by certain approval agencies, or listing may be in Telephone Interface: Unless used with Teldat VISORALARM, process.Consult factory for latest listing status. requires dedicated business telephone number with a minimum • UL Listed:S635 of 5 volts DC (off-hook voltage). Obtain dedicated phone line directly from your local phone company. Do not use shared • FM approved phone lines or PBX(digital)type phone line extensions. • CSFM:7165-0028:0235 • MEA: 120-06-E,Volume 2 Cabinet Specifications For ULC-listed version,see DN-60600. Door: 19.26"(48.92 cm.)high x 16.82"(42.73 cm.)wide x 0.12" (.30 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" NOTIFIER® is a registered trademark of Honeywell International Inc. Wheelock®is a registered trademark of and ExcederTM is a trademark of Cooper Notification. ©2010 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. '�O 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. CERTF 1 E We cannot cover all specific applications or anticipate all requirements.. UICIM IIID a ALUMINIUMAll specifications are subject to change without notice. 1111,.QUALITY SYSTEMS ��� For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. Made in the U.S.A. www.notifier.com Page 6 of 6—DN-60602:A1•12/07/2010 DBD From Tyco Security Products HSPA Universal Wireless .. Commercial Fire Alarm Communicator CSC 3G4O1OCF ' ''' 484, Odle h; • U `` P '3 .,t, ., ,, ,,,- j 9 3 c', n 4®-,,,_ ,,,...,:r. ,:,..B.L.i. �," � m `IV " M ' ',',,,; .:'',0•:;'4,c.'::;7, 3G technology from DSC! Pa The 3G4010CF connects the alarm protected premises within not more ''' va `a � control panel to the Cellular network than 24 hours of the failure. and reports alarm signals directly to "_ ' a monitoringstation receiver How it Works p �xf.4144 (Sur-Gard System I-IP/II/III/IV/5).The f • o The 3G4010CF can be used as � � � 3G4010CF uses the Cellular network either a Sole Communicator or as a II * to ensure low-cost, high-speed and Backup Communicator.When being ®•'�a. ,h , reliable alarm communications and is „ �{ n compatible with control panels that used as a Sole Communicator the ! ';' $` communicate using the Contact ID or 3G4010CF will replace the phone r• fe e ® line connection on the panel and „ � SIA(300 baud)format. as soon as it detects that an alarm The 3G4010CF is compliant needs to be transmitted it will send , tib a, I with the latest requirements for the alarm across the Cellular network '''''''"''.'./ �* , � o: Communications Methods as per immediately.When being used as a � i ,, s i �•r` UL864 and NFPA72 2010 and backup the communicator assesses ; q �' 2013 Editions. It can be used in the connection to the PSTN phone x• 4; e ,, . `,,, Amo It Fire Monitoring applications as a line, and only in the event of a phone r 7: View, a cat -status single communications technology, line failure will it send all alarm traffic , in which case anyfailure of the across the Cellular network to the �� s - communications path shall be monitoring station. q Ito rr t ,u annunciated at the supervising station k,...,:' ;-„:4-...1;-,..;.., within 5 minutes(NFPA72 2010)or In instances where the control panel ie� ; ��s does not support Contact ID or = 1 hour(NFPA72 2013)of the failure, SIA(300 baud), ' '� .' 1 kt�• 4 ' ° �' or it can be used as part of a multiplethe 3G4010CF has « s' communications technologies(for inputs pre-set to transmit fire alarm, i "� fire supervisory or system trouble. �@ e e er example in conjunction with a DACT). . "r 7 When used as a back-up provision Alarm signals are transmitted directly shall be made to monitor the integrity without the need of a clearinghouse • of each communication path and to the IP linecard of the monitoring • �� . irst.‘00.” ",,. failure of any communications station receiver(Sur-Gard®System • t fix" path shall be annunciated at the 1-1P/II/III/IV/5). 41ksupervising station and at the communications Contact your DSC distributor. www.dsc.com 11-888-888-7838 MOO From Tyco Security Products Activating & Initializing the Unit Rate Plan Activating and initializing the 304010CF can be done using Cost-effective rate plans have been negotiated and are the automated telephone activation system(VRU), mobile available through authorized master resellers. Contact your interface or web-user interface provided by monitoring station or visit www.connect24.com to find a C24 Communications. No special tools are required. master reseller.When used as a sole communicator,the 3G4010CF requires use of the 4MB(NFPA72 2010)or Mobile Site for Easy Installation and 500kB(NFPA72 2013)rate plans to support the supervision Comprehensive Maintenance requirements. C24 Communications mobile site(m.connect24.com) Specifications makes the installation a simple process and offers intuitive trouble-shooting features, cutting down on time and cost Dimensions 11-1/2"x 10"x 3" allocated to maintenance. (290 mm x 254 mm x 75 mm) Input Voltage 120 VAC Current Draw 200 mA(standby) —.44* 400 mA(transmitting) InE Operating Environment 32°to 120° F(0°to 49°C) •ww. - Weight 12.8 lbs(5.8 kg) ERN Optional Acessories 6 m OF MOO 3escnp o i .; UL Listing GS TNT 15 ft e' .,on antroa fmre � ) f - The 304010CF is UL listed under File S4019, Listing guide GS-25ANT 25 ft extension antenna UOXX,as a sole or backup communicator for Commercial Fire (internal/external use) monitoring installations.When used as a sole communicator GS760ANT 5,.0ft i on under NFPA72 2010 guidelines the 304010CF will send I'tk3�.� 1 Ante • #.' � its heartbeat once every 97 seconds ensuring that three heartbeats will be received at the supervising station within the 300 second window.When used as a sole communicator under NFPA72 2013 guidelines the 3G4010CF will send its heartbeat once every 5 minutes to monitor connectivity with the supervising station within the 1 hour window.When used as a backup communicator the 304010CF will monitor the other communication method(DACT)and send a daily test transmission to the supervising station. CSFM Listing The 304010CF has been approved by the California State Fire Marshal(CSFM)pursuant to Section 13144.1 of the California Health and Safety Code. Ordering Information: 3G4010CF-USA Universal Wireless Commercial Fire Alarm Communicator (U.S. Model/SIM Card Included) 0 ii communications For product information www.dsc.com Product specifications sod availability subject to change without notice.Certain product nooses mentioned herein may be trade names and/or registered trademarks of other companies. -201,7v,o Security Products dn-7114:c•Al-65 N-ANN-80 eeNOTIFIER® 80 Character LCD Serial Annunciatorby HoneywellAnnunciators General The N-ANN-80 annunciator is a compact, backlit, 80-character LCD fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC Power, Alarm,Trouble, Supervisory, and Alarm Silenced condi- tions. TheNANN 80 and the FACP commnicate over a twowire serial interfacemployinghe ANN BScommunication forma. Connectdeices are powered, via twoadditional wires, by eiththest FACPor a remote UL listed, filtered poweppyAN80 is black;for white order N ANN 80 W.ThA80pas English-languagetext of system point infacldevice type, zone, independent point aaservisory status, as well as any custom aaagaed into the control panel. It includes con-trlete control of critical system functions. (Atsunauthorized operation of the control swithA -80s may be connected to the ANN-BUS of aAP. nal programming is required,which saves time drisstmmissioning. The N ANN 80 is compatible thACPs with an ANN BUS,such as the NFW 50. Troubl Features Supervisory • Listed to UL Standard 864,9th Edition. Alarm Silenced • Backlit 80 character LCD display(20 characters x 4 lines). • Mimics all display information from the host panel. Specifications • Control switches for System Acknowledge, Signal Silence, Operating voltage range: 18 VDC to 28 VDC. Drill,and Reset. Current consumption @ 24 VDC nominal(filtered and non- • Control switches can be independently enabled or disabled resettable):40 mA maximum. at the FACP. Ambient temperature:32°F to 120°F(0°C to 49°C). • Keyswitch enables/disables control switches and mechani Cally locks annunciator enclosure • Relative humidity: 93%±2% RH(noncondensing)at 32°C Keyswitch can be enabled or disabled at the FACP. t 2°C(90°F±3°F). • Enclosure supervised for tamper. 5.375" (13.65 cm.) high x 6.875" (17.46 cm.)wide x 1.375" (3.49 cm.)deep. • • System status LEDs for AC Power, Alarm, Trouble, Supervi For use indoors in a dry location. sory,and Alarm Silence. Local sounder can be enabled or disabled at the FACP. All connections are power-limited and supervised. • • N ANN 80 connects to the ANN BUS terminal on the FACP Agency Listings and Approvals and requires minimal panel programming. • Displays device type identifiers, individual point alarm, trou The listings and approvals below apply to the N ANN 80. In ble,supervisory,zone,and custom alpha labels. some cases, certain modules may not be listed by certain • Time and date display field. approval agencies,or listing may be in process.Consult factory • Surface mount directly to wall or to single, double, or 4" for latest listing status. square electrical box. • UL:S635 • Semi-flush mount to single, double, or 4" square electrical • FM approved box.Use ANN-SB8OKIT for angled view mounting. • CSFM:7120 0028:240 • Can be remotely located up to 6,000 feet(1,800 m)from the • MEA:442-06-E Vol.2 panel. • Backlight turns off during AC loss to conserve battery power The ANN-BUS but will turn back on if an alarm condition occurs. • May be powered by 24 VDC from the host FACP or by remote POWERING THE DEVICES ON THE ANN-BUS FROM power supply(requires 24 VDC). AUXILIARY POWER SUPPLY • Up to eight N-ANN-80s can be connected on the ANN-BUS. Controls and Indicators • AC Power The ANN BUS can be powered by an auxiliary power supply when the maximum number of ANN-BUS devices exceeds the ANN-BUS power requirements. See the FACP manual for more information. • Alarm dn-7114:c•5/22/09—Page 1 of 2 ANN-BUS DEVICE ADDRESSING After calculating the total worst case current draw,the following Each ANN-BUS device requires a unique address(ID Number) table specifies the maximum distance the modules can be in order to communicate with the FACP.A maximum of 8 devices located from the FACP on a single wire run.The table ensures can be connected to the FACP ANN-BUS communication circuit. 6.0 volts of line drop maximum.In general,the wire length is lim See the FACP manual for more information. ited by resistance, but for heavier wire gauges, capacitance is the limiting factor. WIRE REQUIREMENTS:COMMUNICATIONS CIRCUIT These cases are marked in the chart with an asterisk(*). Maxi- The N-ANN-80 connects to the FACP ANN-BUS communica- mum length can never be more than 6,000 feet (1,800 m), tions circuit.To determine the type of wire and the maximum wir- regardless of gauge used. See table below. ing distance that can be used with FACP ANN-BUS accessory WIRE REQUIREMENTS:POWER CIRCUIT modules,it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus.The total worst • 14 to 18 AWG (0.75-2.08 mm2)wire for 24 VDC power cir- case current draw is calculated by adding the individual worst cult is acceptable. case currents for each module. • All connections are power-limited and supervised. NOTE: For total worst case current draw on a single ANN-BUS • A maximum of eight N-ANN-80 modules may be connected refer to appropriate FACP manual. to this circuit. Communication Pair Wiring Distance: FACP to Last ANN-BUS Module Total Worst Case 22 Gauge 18 Gauge 16 Gauge 14 Gauge Current Draw(amps) 0.100 1,852 ft. 4,688 ft. *6,000 ft. *6,000 ft. 0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft. 0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft. 0.400 463 ft. 1,172 ft. 1,866 ft. 2,953 ft. 0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft. 0.600 309 ft. 781 ft. 1,244 ft. 1,969 ft. 0.700 265 ft. 670 ft. 1,066 ft. 1,687 ft. 0.800 231 ft. 586 ft. 933 ft. 1,476 ft. 0.900 206 ft. 521 ft. 829 ft. 1,312 ft. 1.000(max.) 185 ft. 469 ft. 746 ft. 1,181 ft. WIRING CONFIGURATION ORDERING OPTIONS: The following figure illustrates the wiring between the FACP and a a E w .u ° I<e °: • r • .x ANN-BUS devices. N-ANN-80-W:White,80 character LCD Annunciator. ANN-BUS and power ANN-SB80KIT B: Black surface mount backbox with angled wiring are supervised wedge. and power-limited. ANN-SB8OKIT W: White surface mount backbox with angled si ® o n a wedge. TBI rI�I 4 3 2 1 ANN-BUS Device NFW-50 TB3 a '10'4 c• 1 2 3 4 5 6 7 8 FACP Wiring to ANN-BUS Device ©2009 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. �:x�����. We try to keep our product information up-to-date and accurate. C E R T F 1 E D We cannot cover all specific applications or anticipate all requirements. ENEINEBINfi 6 UMW= All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2—dn-7114:c•5/22/09 Monitor Modules DN-6999:C N MM-100(A), NMM-100P(A), NOTIFIER° N ZM-100(A), and NDM-100(A) for FireWarden Series Panels by Honeywell Intelligent Addressable Devices General Four different monitor modules are available for Notifier's Fire- Warden Series intelligent control panels for a variety of appli- cations. Monitor modules supervise a circuit of dry-contact , No input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors(NZM-100(A)). NMM-100(A)is a standard-sized module(typically mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices. NMM-100P(A) is a miniature monitor module a mere 1.3" (3.302 cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D that supervises a Style B (Class B) circuit of dry-contact input devices. Its compact design allows the NMM-100P(A) to be mounted in a single-gang box behind the device it monitors. % , 1-2 NZM-100(A) is a standard-sized module that monitors and supervises compatible two-wire,24 volt,smoke detectors on a Style D(Class A) or Style B(Class B)circuit. NDM-100(A) is a standard-sized dual monitor module that NMM-100(A)(Type H) monitors and supervises two independent two-wire Style B (Class B) dry-contact initiating device circuits (IDCs) at two separate,consecutive addresses in intelligent,two-wire systems. NMM-100(A) OPERATION Each NMM-100(A) uses one of the available module N MM-100(A) Monitor Module addresses on an SLC loop. It responds to regular polls from Built-in type identification automatically identifies this device the control panel and reports its type and the status(open/nor- • Bs a monitorpmodule to the control panel. mal/short)of its Initiating Device Circuit(IDC).A flashing LED aindicates that the module is in communication with the control • Powered directly by two-wire SLC loop.No additional power panel. The LED latches steady on alarm (subject to current required. limitations on the loop). • High noise(EMF/RFI)immunity. SEMS screws with clamping plates for ease of wiring. NMM-100(A) SPECIFICATIONS • Direct Decade entry of address: 01 —99 on FireWarden- Nominal operating voltage: 15 to 32 VDC. • 100-2,01 —50 on FireWarden-50. Maximum current draw:5.0 mA(LED on). • LED flashes during normal operation and latches on steady Average operating current: 350 pA (LED flashing), 1 corn- to indicate alarm. munication every 5 seconds,47k EOL. The NMM-100(A) Monitor Module is intended for use in intelli- Maximum IDC wiring resistance:40 ohms. gent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It pro EOL resistance:47K ohms. vides either a two-wire or four-wire fault-tolerant Initiating Temperature range:32°F to 120°F(0°C to 49°C). Device Circuit (IDC) for normally-open-contact fire alarm and Humidity range: 10%to 93%noncondensing. supervisory devices. The module has a panel-controlled LED indicator. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4° (10.16 cm) square x NMM-100(A)APPLICATIONS 2.125"(5.398 cm)deep box. Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally- open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B(Class B)or Style D(Class A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. DN-6999:C•10/06/2010—Page 1 of 4 Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x • Built-in type identification automatically identifies this device 0.65"(1.651 cm)deep. as a monitor module to the panel. Wire length:6"(15.24 cm)minimum. • Powered directly by two-wire SLC loop.No additional power required. NZM-100(A) Interface Module • High noise(EMF/RFI)immunity. • Supports compatible two-wire smoke detectors. • Tinned,stripped leads for ease of wiring. • Supervises IDC wiring and connection of external power • Direct Decade entry of address: 01 — 99 on FireWarden- source. 100-2,01 —50 on FireWarden-50. • High noise(EMF/RFI)immunity. • SEMS screws with clamping plates for ease of wiring. 3 1415 0 1 ADDRESS 0 1 • Direct Decade entry of address:, 01 — 99 on FireWarden- s 13 , 2 ^ 2 100-2,01 —50 on FireWarden-50. 3 12 11 1// LOOP 1 3 • LED flashes during normal operation. 10 I 5 4 • LED latches steady to indicate alarm on command from 9 6 7 6 9 8 7 6 5 control panel. TENS ONES The NZM-100(A)Interface Module is intended for use in intelli- gent, addressable systems, where the individual address of n each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- 3 wire conventional smoke detectors.It transmits the status(nor- O W W s U mal,open,or alarm)of one full zone of conventional detectors m back to the control panel. All two wire detectors being moni LU - is° tored must be UL compatible with the module. NZM-100(A) APPLICATIONS Use the NZM-100(A) to monitor a zone of two-wire smoke I detectors. The monitored circuit may be wired as an NFPA The NMM-100P(A) Mini Monitor Module can be installed in a Style B(Class B)or Style D(Class A) Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor (provided) terminates the single-gang junction directly behind the monitored unit. Its end of the Style B or D (class B or A) circuit (maximum IDC small size and light weight allow it to be installed without rigid loop resistance is 25 ohms). Install ELR across terminals 8 mounting.The NMM-100P(A)is intended for use in intelligent, and 9 for Style D application. two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiat- NZM-100(A)OPERATION ing device circuit for normally-open-contact fire alarm and Each NZM-100(A) uses one of the available module security devices. NMM-100P(A) addresses on an SLC loop. It responds to regular polls from NMM-100P(A)APPLICATIONS the control panel and reports its type and the status(open/nor- mal/short)of its Initiating Device Circuit(IDC). A flashing LED Use to monitor a single device or a zone of four-wire smoke indicates that the module is in communication with the control detectors,manual fire alarm pull stations,waterflow devices,or panel. The LED latches steady on alarm (subject to current other normally-open dry-contact devices. May also be used to limitations on the loop). monitor normally-open supervisory devices with special super- visory indication at the control panel. Monitored circuit/device NZM-100(A)SPECIFICATIONS is wired as an NFPA Style B(Class B)Initiating Device Circuit. Nominal operating voltage: 15 to 32 VDC. A 47K ohm End-of-Line Resistor(provided)terminates the cir- cuit. Maximum current draw:5.1 mA(LED on). NMM-100P(A)OPERATION Maximum IDC wiring resistance:25 ohms. Each NMM 100P(A) uses one of the available module Average operating current: 300 pA, 1 communication and 1 addresses on an SLC loop. It responds to regular polls from LED flash every 5 seconds,3.9k eol. the control panel and reports its type and the status(open/nor- EOL resistance:3.9K ohms. mal/short)of its Initiating Device Circuit(IDC). External supply voltage (between Terminals T3 and T4): NMM-100P(A) SPECIFICATIONS DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms maximum.Current:90 mA per module maximum. Nominal operating voltage: 15 to 32 VDC. Average operating current: 350 pA, 1 communication every Temperature range:32°F to 120°F(0°C to 49°C). 5 seconds, 47k EOL; 600 pA Max. (Communicating, IDC Humidity range: 10%to 93%noncondensing. Shorted). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x Maximum IDC wiring resistance:40 ohms. 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x Maximum IDC Voltage: 11 Volts. 2.125'(5.398 cm)deep box. Maximum IDC Current:400 pA. EOL resistance:47K ohms. Temperature range:32°F to 120°F(0°C to 49°C). Humidity range: 10%to 93%noncondensing. Page 2 of 4—DN-6999:C•10/06/2010 NDM-100(A) Dual Monitor Module • MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100); 227-03-E Vol.3(NDM-100) The NDM-100(A) Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent two Product Line Information wire initiating device circuits(IDCs)at two separate,consecutive addresses. It is capable of monitoring normally open contact fire NOTE:"A"suffix indicates ULC-listed model. alarm and supervisory devices.The module has a single panel NMM-100(A): Monitor module. controlled LED. NOTE: The NDM-100(A)provides two Style B(Class B)IDC cir- NMM-100P(A):Monitor module,miniature. cults ONLY. Style D(Class A)IDC circuits are NOT supported in NZM-100(A):Monitor module,two-wire detectors. any application. NDM-100(A): Monitor module,dual,two independent Class B NDM-100(A)SPECIFICATIONS circuits. Normal operating voltage range: 15 to 32 VDC. SMB500:Optional surface-mount backbox. Maximum current draw:6.4 mA(LED on). NOTE: See installation instructions and refer to the SLC Wiring Average operating current:750 pA(LED flashing). Manual,PN 52304. Maximum IDC wiring resistance: 1,500 ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current:240 pA EOL resistance:47K ohms. Maximum SLC Wiring resistance:40 Ohms. Temperature range:32°to 120°F(0°to 49°C). Humidity range: 10%to 93%(non-condensing). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 2.125"(5.398 cm)deep. NDM-100(A) AUTOMATIC ADDRESSING The NDM-100(A) automatically assigns itself to two address- - able points, starting with the original address. For example, if the NDM-100(A) is set to address "26", then it will automati- cally assign itself to addresses"26"and"27". NOTE: "Ones"addresses on the NOM-100(A)are 0,2, 4, 6, or 8 only. Terminals 6 and 7 use the first address,and terminals 8 and 9 use the second address. QCAUTION: Avoid duplicating addresses on the system. Installation NMM-100(A), NZM-100(A), and NDM-100(A) modules mount directly to a standard 4" (10.16 cm)square,2.125"(5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installa- tion instructions are provided with each module. All wiring must conform to applicable local codes,ordinances,and regu- lations. These modules are intended for power-limited wiring only. The NMM-100P(A) module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordi- nances,and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. • UL:S635 • ULC:S635 • FM Approved • CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM- _ 100);7300-0028:0237(NDM-100) DN-6999:C•10/06/2010—Page 3 of 4 Notifier®and FireWarden®are registered trademarks and FireWatch',"is a trademark of Honeywell International Inc. ©2010 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. E R T F 1 E We cannot cover all specific applications or anticipate all requirements. ** 6YIIMENNI i IMMU CIRINC All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 4 of 4—DN-6999:C•10/06/2010 dn-60383:A2 NC-100R(A) N OTI F I E R® Relay Module for e y FireWarden Series Panels by Honeywell Addressable General The NC-100R(A) Addressable Relay Module provides NOTI- FIER's FireWarden Series intelligent control panels with two isolated sets of Form-C dry-contact outputs for activating a variety of auxiliary devices,such as fans, dampers,door hold40P % 1110 - ers,control equipment, etc.Addressability allows the dry con- tact to be activated, either manually or through panel programming,on a select basis. Features • Built-in type identification automatically identifies these devices to the control panel. • Internal circuitry and relay powered directly by two-wire SLC loop. ; • Integral LED "blinks" green each time a communication is received from the control panel and turns on in steady when • activated. % 40111 • High noise immunity(EMF/RFI). • Wide viewing angle of LED. • SEMS screws with clamping plates for wiring ease. NC-100R(A) • Direct Decade entry of address: 01 —99 with the FireWar- - den-100-2(C)and 01 —50 with the FireWarden-50(C). Applications The NC-100R(A)may be programmed to operate dry contacts Specifications for door holders,Air Handling Unit shutdown,etc.,and to reset Normal operating voltage: 15 to 32 VDC. four-wire smoke detector power. Maximum SLC current draw: 6.5 mA(LED). Construction Average operating current: 230 pA direct poll(CLIP mode), • The face plate is made of off-white heat-resistant plastic. 255 pA group poll with LED flashing. • Controls include two rotary switches for direct-dial entry of EOL resistance: not used. address setting. Temperature range: 32°F to 120°F(0°C to 49°C). • The NC-100R(A) provides two Form-C dry contacts that Humidity range: 10%to 93%non-condensing. switch together. Dimensions: 4.5" (11.43 cm) high x 4' (10.16 cm) wide x Operation 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125"(5.398 mm)deep box. Each NC-100R(A)uses one of the addresses on a SLC loop. It responds to regular polls from the control panel and reports its Relay Contact Ratings type and status. The LED blinks with each poll received. On command,it activates its internal relay. Load Description Application Maximum Current Rotary switches set a unique address for each module. The Voltage Rating address may be set before or after mounting. The built-in Resistive Non-Coded 30 VDC 3.0 A TYPE CODE(not settable)will identify the module to the con- trol panel. Resistive Coded 30 VDC 2.0 A Resistive Non-Coded 110 VDC 0.9 A Resistive Non-Coded 125 VAC 0.9 A Inductive(L/R=5ms) Coded 30 VDC 0.5 A Inductive(L/R=2ms) Coded 30 VDC 1.0 A Inductive(PF=0.35) Non-Coded 125 VAC 0.5 A dn-60383:A2.06/17/10—Page 1 of 2 Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. • UL/ULC Listed:S635. • CSFM approved:file 7300-0028:230. • FM approved. • MEA approved:file 72-01-E,Vol.2. Product Line Information NC-100R: Intelligent addressable relay module. NC-100RA:Intelligent addressable relay module,ULC listed model. SMB500:Optional surface-mount backbox. NOTE: For installation instructions, see document 156-2593-001 and refer to the SLC Wiring Manual,document 52304. NOTIFIER®is a registered trademark of Honeywell International Inc. ©2010 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot CERT�F�EO cover all specific applications or anticipate all requirements. Emma IIM i MANIf1LL71IN6 All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2—dn-60383:A.2•06/17/10 DN-7001:D•Al-380 NOT-BG 12LX NOT 1 F 1 E R® Addressable Manual Pull Station by Honeywell Intelligent/Addressable Devices General The Notifier NOT-BG12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station �n that includes an addressable interface for FireWarden series intelligent control panels,and the NSP-25 panel. Because the z. NOT-BG12LX is addressable,the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. 1 Features • Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. • Handle latches in down position and the word"ACTIVATED" appears to clearly indicate the station has been operated. E • Captive screw terminals wire-ready for easy connection to SLC loop(accepts up to 12 AWG/3.25 mm2 wire). • Can be surface mounted (with SB-10 or SB-I/O) or semi " ' flush mounted. Semi-flush mount to a standard single- gang,double-gang,or 4"(10.16 cm)square electrical box. • Smooth dual-action design. The NOT-BG12LX • Meets ADAAG controls and operating mechanisms guide- Addressable Manual Pull Station lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. • Highly visible. The BG12TR is usually needed for semi-flush mounting with 4" Attractive shape and textured finish. (10.16 cm)or double gang boxes(not with single gang boxes). •• Key reset. Operation • Includes Braille text on station handle. • Optional trim ring(BG12TR). Pushing in,then pulling down on the handle causes it to latch in the down/activated position.Once latched,the word"ACTT- • Meets UL 38, Standard for Manually Actuated Signaling VATED" (in bright yellow) appears at the top of the handle, Boxes. while a portion of the handle protrudes from the bottom of the station.To reset the station, simply unlock the station with the Construction key and pull the door open.This action resets the handle;clos- Shell, door, and handle are molded of durable polycarbonate ing the door automatically resets the switch. material with a textured finish. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual Specifications switch.Two rotary decimalswitches allow address settings (1 —99 on NFW2-100/NFW2-100C, 1 —50 for NFW-50/NFW- • Shipping Weight:9.6 oz.(272.15 g) 50C). • Normal operating voltage:24 VDC. • Maximum SLC loop voltage:28.0 VDC. Architectural/Engineering • Maximum SLC standby current:375 IA. Specifications • Maximum SLC alarm current:5 mA. Manual Fire Alarm Stations shall be non-coded, with a key- • Temperature Range:32°F to 120°F(0°C to 49°C) operated reset lock in order that they may be tested, and so • Relative Humidity: 10%to 93%(noncondensing) designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key.An operated sta- • For use indoors in a dry location tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of Installation red-colored polycarbonate material with clearly visible operat- The NOT-BG12LX will mount semi-flush into a single gang, ing instructions provided on the cover. The word FIRE shall double-gang,or standard 4"(10.16 cm)square electrical outlet appear on the front of the stations in white letters, 1.00 inches box, or will surface mount to the model SB-10 or SB-I/O sur- (2.54 cm) or larger. Stations shall be suitable for surface face backbox. If the NOT-BG12LX is being semi flush mounting on matching backbox SB-10 or SB-I/O;or semi-flush mounted, then the optional trim ring (BG12TR) may be used. mounting on a standard single gang, double gang, or 4"(10.16 cm) square electrical box, and shall be installed DN-7001:D•4/13/2012—Page 1 of 2 within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel,send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. Product Line Information NOT BG12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian applications.) SB-10:Surface backbox;metal. SB-UO:Surface backbox;plastic. BG12TR:Optional trim ring. 17021:Keys,set of two. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess.Consult factory for latest listing status. • UUULC Listed: S692 (listed for Canadian and non-Cana- dian applications). • MEA:67-02-E Vol. IV. • CSFM:7150-0028:0199. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. NOTIFIER®is a registered trademark of Honeywell International Inc. ©2012 by Honeywell International Inc.All rights reserved.Unauthorized use of this document is strictly prohibited. ISO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. C E R T F 1 E D We cannot cover all specific applications or anticipate all requirements. UMIMEMIMi&mamma All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2—DN-7001:D•4/13/2012 DN-6995:C•Al-320 NP-100(A) Series8N OT I F 1 E R® Addressable Photoelectric Detectors for the FireWarden Series by Honeywell Addressable General The NP-100(A), NP-100T(A) and NP-100R(A) addressable, low-profile plug-in photoelectric detectors use a state-of-the- art photoelectric sensing chamber with communications to €' provide open area protection and are used exclusively with NOTIFIER's FireWarden Series(FireWarden-100-2 and Fire- Warden-50) and Spartan (NSP-25) Addressable Fire Alarm Control Panels (FACPs). The NP-100T(A)adds thermal sen- sors that will alarm at a fixed temperature of 135°F (57°C). Since these detectors are addressable, they will help emer- gency personnel quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage.Two LEDs on each sensor light to provide a local,visible sensor indication.Remote LED annunciator capa- bility is available as an optional accessory, PN RA100Z(A). The NP-100R(A)is a remote test capable detector for use with NP-100(A) in B210LP(A) Base DNR(A)/DNRW duct smoke detector housings. Features Applications SLC loop Use photoelectric detectors in life-safety applications to pro- • Two-wire loop connection. vide a broad range of fire-sensing capability,especially where • Unit uses base for wiring. smoldering fires are anticipated. Ionization detectors are often better than photoelectric detectors at sensing fast, flaming Addressing fires. • Addressable by device. • Rotary,decimal addressing:01 –99 with FireWarden-100-2 Construction and NSP-25,and 01 –50 with FireWarden-50. These detectors are constructed of off-white fire resistant plas- Architecture tic. NP-100(A) series plug-in, low-profile smoke detectors are • Unique single-source, dual-chamber design to respond designed to commercial standards and offer an attractive quickly and dependably to a broad range of fires. appearance. • Sleek,low-profile design. • Integral communications and built-in type identification. Installation • Built-in tamper-resistant feature. NP-100(A)series plug-in detectors use a detachable mounting • Removable cover and insect-resistant screen for simple base to simplify installation,service and maintenance. field cleaning. Mount base(all base types)on an electrical backbox which is Operation at least 1.5"(3.81 cm)deep. For a chart of compatible junction boxes,see DN-60054. • Withstands air velocities up to 4,000 feet-per-minute(20 m/ sec.)without triggering a false alarm. NOTE:Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring `T-taps" or • Factory preset at 1.5% nominal sensitivity for panel alarm branches are permitted for Style 4(Class B) wiring. NP-100R(A) threshold level. mounts in a DNR(A)/DNRW duct detector housing. • Visible LED"blinks"when the unit is addressed (communi- cating with the fire panel)and latches on in alarm. Operation Mechanicals Each NP-100(A) series detector uses one of 99 possible • Sealed against back pressure. addresses on the FireWarden-100-2 and NSP-25,or one of 50 • Direct surface mounting or electrical box mounting. possible addresses on the FireWarden-50 Signaling Line Cir- • Mounts to: single gang box, 3.5" (8.89 cm) or 4.0" (10.16 cuit (SLC). It responds to regular polls from the system and cm)octagonal box,or 4.0" (10.16 cm)square electrical box reports its type and status. (using a plaster ring—included). The addressable photoelectric sensor in the NP-100(A)series Other system features has a unique unipolar chamberthat responds quickly and uni- formly to a broad range of smoke conditions. It can withstand • Fully coated circuit boards and superior RF/transient pro- wind gusts up to 4,000 feet-per-minute (20 m/sec.) without _ lection. sending an alarm level signal. Because of its unipolar cham- • 94-VO plastic flammability rating. ber, the NP-100(A) series is approximately two times more • Low standby current. responsive than most photoelectric sensors. This makes it a more stable detector. _ Options • Remote LED output connection, PN RA100Z(A). DN-6995:C•12/07/2011—Page 1 of 2 Detector Sensitivity Test NP-100RA:Same as NP-100R with ULC Listing for use with a DNRA duct detector housing; B210LPA base included. Each detector can have its sensitivity tested (required per NFPA 72,Chapter 14 on Inspection, Testing and Maintenance) INTELLIGENT BASES when installed/connected to a FireWarden-100-2 or FireWar- NOTE:"A"suffix indicates ULC Listed model. den-50 addressable fire alarm control panel.The results of the sensitivity test can be printed off the FireWarden-100-2 or Fire- NOTE:For details about intelligent bases and their mounting,see Warden-50 for record keeping. DN-60054. B210LP(A): Plug-in detector base (included); standard U.S. Specification flanged low-profile mounting base. Voltage range: 15—32 VDC(peak). B210LPBP: Bulk pack of B210LP;package contains 10. Standby current:300 pA 24 VDC. B501(A):Standard European flangeless mounting base. LED current:6.5 mA @ 24 VDC(latched"ON"). B501 BP: Bulk pack of B501;package contains 10. Air velocity:4,000 ff./min.(20 m/sec.)maximum. B200SR(A): Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Size:2.1"(5.33 cm)high;base determines diameter. Replaces B501 BH series bases in retrofit applications. —B210LP(A):6.1"(15.5 cm)diameter. B224RB(A): Plug-in System Sensor relay base. Screw termi- -B501(A):4.1"(10.4 cm)diameter. nals:up to 14 AWG(2.0 mm2).Relay type:Form-C. Rating:2.0 —B200SR(A):6.875"(17.46 cm)diameter. A © 30 VDC resistive; 0.3 A © 110 VDC inductive; 1.0 A —B224RB(A):6.2'(15.748 cm)diameter. 30 VDC inductive. Weight:3.6 oz.(102 g). B224BI(A): Plug-in System Sensor isolator detector base. Maximum 25 devices between isolator bases(see DN-6994). Operating temperature range: for NP-100(A):0°C to 49°C ACCESSORIES (32°F to 120°F); for NP-100T(A):0°C to 38°C(32°F to 100°F). NP-100R(A):installed in a DNR(A)/DNRW-20°C to 70°C(-4°F F110: Retrofit flange to convert B210LP(A) to match the to 158°F). B710LP(A) profile, or to convert older high-profile bases to Temperature:0°C—49°C(32°F—120°F). low profile. Relative humidity: 10%—93%,non-condensing. F110BP:Bulk pack of F110;package contains 15. F210: Replacement flange for B210LP(A)base. Listings RA100Z(A): Remote LED annunciator.3—32 VDC. Mounts to Listings and approvals below apply to the NP-100(A), NP- a U.S. single-gang electrical box. For use with B501(A) and 100T(A), and NP-100R(A) detectors. In some cases, certain B210LP(A)bases only. modules may not be listed by certain approval agencies, or SMB600:Surface mounting kit listing may be in process. Consult factory for latest listing sta M02-04-0O:Test magnet. tus. • UL Listed:S1115. M02-09-00:Test magnet with telescoping handle. • ULC Listed:S911. XR2B: Detector removal tool. Allows installation and/or CSFM:7272 0028:0231. removal of detector heads from bases in high ceiling applica- • tions. • MEA:243-02-E Vol.2. XP-4: Extension pole for XR2B. Comes in three 5-foot(1.524 • Maryland State Fire Marshal:permit 2173. m)sections. • FM approved. T55-127-010: Detector removal tool without pole. Product Line Information BCK-200B:Black detector covers for use with NP-100(A)only; box of 10. NOTE:"A"suffix indicates ULC Listed model. WCK-200B: White detector covers for use with NP-100(A) ' ��� ' ��!`r � only;box of 10. NP-100A:Sames as NP-100 with ULC Listing; B210LPA base included. NP-100T: Same as NP-100 but with thermal element; B210LP base included. NP-100TA: Same as NP-100T with ULC Listing; B210LPA base included. NP-100R: Remote test capable addressable photoelectric NOTIFIER® and FireWarden® are registered trademarks of Honeywell detector for use with a DNRA/DNRW duct detector housing; International reserved. Unauthorized use of this document is strictly B210LP base included. prohibited. This document is not intended to be used for installation purposes. ISO 9001 We try to keep our product information up-to-date and accurate. .� CERT 1 F 1 E D We cannot cover all specific applications or anticipate all requirements. inimmumm BICINEMINi 6 MMUMCi1NN6 All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2—DN-6995:C•12/07/2011 DN-6997:D•Al-320 NH-100(A) Series NOTIFIER® Intelligent Addressable Thermal Detectors for FireWarden Series by Honeywell Addressable General The NOTIFIER NH-100(A) Series thermal detectors are addressable sensors that use a state-of-the-art thermistor sensing circuit for fast response.These sensors provide open- area protection and are intended for use with FireWarden t,Nk k,=, Series (FireWarden-100-2 and FireWarden-50) and Spartan (NSP-25)addressable Fire Alarm Control Panels(FACPs). The NH-100(A) and NH-100R(A) sensors provide fixed tem- perature alarm detection at 135°F (57°C). The NH-100R(A) sensor also responds to rate-of-rise conditions of greater than 15°F(8.3°C)per minute.The NH-100H(A)is a fixed high-tem- perature detector that activates at 190°F (88°C). These ther- mal detectors provide addressable property protection in a variety of applications. NH-100(A) in B210LP(A) Base Two LEDs on each sensor light to provide a local,visible sen- sor indication. Remote LED annunciator capability is available using an optional accessory,the RA100Z. • Low standby current. • 94-5V plastic flammability rating. Features Options: SLC loop: • Remote LED output connection to optional RA100Z remote • Two-wire SLC loop connection. LED annunciator. • Unit uses base for wiring. • Flanged surface mounting kit. Addressing: Installation • Addressable by device. NH-100(A) Series plug-in intelligent thermal detectors use a • Rotary, decimal addressing: 01 —99 with FireWarden-100- detachable base to simplify installation, service and mainte- 2,NSP-25,01 —50 with FireWarden-50. nance. Installation instructions are shipped with each detector. Architecture: Mount base (all base types)on an electrical backbox which is • Sleek,low-profile,stylish design. at least 1.5"(3.81 cm)deep. For a chart of compatible junction • State-of-the-art thermistor technology for fast response. boxes,see DN-60054. • Integral communications and built-in device-type identifica- NOTE:Because of the inherent supervision provided by the SLC tion. loop, end-of-line resistors are not required. Wiring `T-taps" or • Built-in tamper resistant feature. branches are permitted for Style 4(Class"B")wiring only. • Built-in functional test switch activated by external magnet. Applications Operation: Factory preset at 135°F(57°C)for the NH-100(A) and NH- Use thermal detectors for protection of property. • 100R(A); 190°F(88°C)for the NH-100H(A). Rate-of-rise triggers at 15°F(8.3°C) per minute for the NH- Construction • 100R(A). These detectors are constructed of off-white fire-resistant • 360°-field viewing angle of the visual alarm indicators (two plastic. The NH-100(A) Series plug-in intelligent thermal bicolor LEDs). LEDs blink red in Normal condition and turn detectors are designed to commercial standards and offer an on steady red in Alarm. attractive appearance. • Visible LEDs"blink"every time the unit is addressed. Mechanicals: Operation • Sealed against back pressure. Each NH-100(A)Series detector uses one of 99(FireWarden- 100-2, NSP-25)or 50(FireWarden-50) possible addresses on • SEMS screws for wiring of the separate base. a control panel SLC loop. It responds to regular polls from the • Designed for direct-surface or electrical-box mounting. control panel and reports its type and the status.If it receives a • Plugs into separate base for ease of installation and main- test command from the panel(or a local magnet test),it stimu- tenance. lates its electronics and reports an alarm. It blinks its LEDs • Separate base allows interchange of photoelectric, ioniza- polled and turns the LEDs on when commanded by the tion and thermal sensors. panel.The NH-100(A)Series offers features and performance that represent the latest in thermal detector technology. Other system features: • Remote test feature from the panel. • Walk test with address display. DN-6997:D•5/17/13—Page 1 of 2 Spefications INTELLIGENT BASES Size:2.1"(5.3 cm)high; base determines diameter. NOTE:"A"suffix indicates ULC Listed model. —8210LP(A):6.1"(15.5 cm)diameter. NOTE:For details about intelligent bases and their mounting,see DN-60054. —B501(A):4.1'(10.4 cm)diameter. B210LP(A): Plug-in detector base (included); standard U.S. —B200SR(A):6.875°(17.46 cm)diameter. flanged low-profile mounting base. —B224RB(A):6.2"(15.748 cm)diameter. B210LPBP:Bulk pack of B210LP;package contains 10. Shipping weight:4.8 oz.(137 g). B501(A):Standard European flangeless mounting base. Installation temperature: B501 BP: Bulk pack of B501;package contains 10. —NH-100(A), NH-100R(A):—4°F to 100°F(-20°C to 38°C). —NH 100H(A):—4°F to 150°F(-20°C to 66°C). B200SR(A): Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Humidity range: 10% to 93% relative humidity (noncon- Replaces B501 BH series bases in retrofit applications. densing). B224RB(A): Plug-in System Sensor relay base. Screw termi- Voltage range: 15 to 32 VDC peak. nals:up to 14 AWG(2.0 mm2).Relay type:Form-C.Rating:2.0 Standby current: 300 pA CP 24 VDC (one communication A © 30 VDC resistive; 0.3 A © 110 VDC inductive; 1.0 A every five seconds with LED blink enabled). 30 VDC inductive. LED current:6.5 mA©24 VDC. B224BI(A): Plug-in System Sensor isolator detector base. Mounting: B210LP(A) flanged base, included. See "Product Maximum 25 devices between isolator bases(see DN-6994). Line Information: Intelligent Bases"if using a different base. ACCESSORIES Fixed-temperature setpoint: 135°F (57°C) for the NH-100 F110: Retrofit flange to convert B210LP(A) to match the and NH-100R(A)(A); 190°F(88°C)for the NH-100H(A). B710LP(A) profile, or to convert older high-profile bases to Rate-of-rise detection:responds to greater than 15°F(8.3°C) low profile. per minute. F110BP:Bulk pack of F110;package contains 15. F210: Replacement flange for B210LP(A)base. Listings and Approvals RA100Z(A): Remote LED annunciator.3—32 VDC. Mounts to Listings and approvals below apply to the NH-100(A) Series a U.S. single-gang electrical box. For use with B501(A) and detectors. In some cases, certain modules may not be listed B210LP(A)bases only. by certain approval agencies, or listing may be in process. SMB600:Surface mounting kit Consult factory for latest listing status. UL Listed:S747. M02-04-00:Test magnet. •• ULC Listed:S747. M02-09-00:Test magnet with telescoping handle. • CSFM:7270-0028:0234. XR2B: Detector removal tool. Allows installation and/or • MEA:387-02-E Vol. II. removal of detector heads from bases in high ceiling applica- tions. • FM approved. XP-4: Extension pole for XR2B. Comes in three 5-foot(1.524 m)sections. Product Line Information T55-127-010: Detector removal tool without pole. NOTE:"A"suffix indicates ULC Listed model. NH-100: Intelligent thermal sensor; 135° F (57° C); B210LP base included. NH-100A: Same as NH-100 but with ULC Listing; B210LPA base included. NH-100R: Same as NH-100 with rate-of-rise feature; B210LP base included. NH-100RA:Same as NH-100R but with ULC Listing;B210LPA base included. NH-100H: Intelligent fixed high-temperature thermal detector; 190°F(88°C); B210LP base included. NH-100HA:Same as NH-100H but with ULC Listing;B210LPA base included. NOTIFIER® and FireWarden® are registered trademarks of Honeywell International Inc. ©2013. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. ISO 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. ENNINEBIIS 8 MMIU ACIUMN6 All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S.A. For more information,contact Notifier.Phone:(203)484-7161,FAX:(203)484-7118. www.notifier.com Page 2 of 2—DN-6997:D•5/17/13 SYSTEM �$ SENSOR® Indoor Selectable- Output Strobes and Horn Strobes for A Ceiling Applications System Sensor L-Series audible visible notification i a ; products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features The System Sensor L-Series offers the most versatile and • Plug-in design with minimal intrusion into the back box easy-to-use line of horns,strobes,and horn strobes in the industry with lower current draws and modern aesthetics.With white and red • Tamper-resistant construction plastic housings,wall and ceiling mounting options,System Sensor • Automatic selection of 12 or 24-volt operation L-Series can meet virtually any application requirement. at 15 and 30 candela The entire L-Series product line of ceiling-mount strobes and horn • Field-selectable candela settings on ceiling units: 15,30,75,95, 115, 150,and 177 strobes include a variety of features that increase their application versatility while simplifying installation.All devices feature a plug-in • Horn rated at 88+dBA at 16 volts design with minimal intrusion into the back box,making installations • Rotary switch for horn tone and two volume selections fast and foolproof while virtually eliminating costly and time- • Universal mounting plate for ceiling units consuming ground faults. • Mounting plate shorting spring feature checks wiring continuity To further simplify installation,the L-Series utilizes a universal before device installation mounting plate so installers can mount them to a wide array of back • Electrically Compatible with legacy SpectrAlert and SpectrAlert boxes.With an onboard shorting spring,installers can test wiring Advance devices continuity before the device is installed. • Compatible with MDL3 sync module Installers can also easily adapt devices to a suit a wide range of • Listed for ceiling mounting only application requirements using field-selectable candela settings, automatic selection of 12-or 24-volt operation,and a rotary switch for horn tones with two volume selections. Agency Listings SIGNALING ® c ) USTED APPROVED ISI S5512 FM approved except 7125-1653:0504 S4011 for ALERT models 7135-1653:0503 3057383 L-Series Specifications Architect/Engineer Specifications General L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 x 4 x 1'/cinch back box,4-inch octagon back box,or double- gang back box.Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box.A universal mounting plate shall be used for mounting ceiling and wall products.The notification appliance circuit wiring shall terminate at the universal mounting plate.Also,L-Series products,when used with the Sync•Circuit° Module accessory,shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts.When used with the Sync•Circuit Module,12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts;24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts.Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field-selectable candela settings including 15,30,75,95,115,150,and 177. Strobe The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service.The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service.The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,flashing at 1 Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal(continuous)pattern.These options are set by a multiple position switch.The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service.The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three.Also,while operating the strobes,the module shall silence the horns on horn strobe models over a single pair of wires.The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box.The module shall also control two Style Y(class B)circuits or one Style Z(class A)circuit.The module shall synchronize multiple zones.Daisy chaining two or more synchronization modules together will synchronize all the zones they control.The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1 Operating Voltage Rangel 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Operating Voltage Range(MDL3) 8.5 to 17.5V(12 V nominal)or 16.5 to 33 V(24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions(including lens) 6.8"diameter x 2.5"high(173 mm diameter x 64 mm high) Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9"diameter x 3.4"high(175 mm diameter x 86 mm high) (SBBCRL,SBBCWL) Notes: 1.Full Wave Rectified(FWR)voltage is a non-regulated,time-varying power source that is used on some power supply and panel outputs. 2.P,S,PC,and SC products will operate at 12 V nominal only for 15 and 30 cd. AVDS86800 UL Current Draw Data UL Max.Strobe Current Draw(mA RMS) 8-17.5 Volts 16-33 Volts Candela DC DC FWR 15 87 41 60 30 153 63 86 75 N/A 111 142 95 N/A 134 164 115 N/A 158 191 150 N/A 189 228 177 N/A 226 264 UL Max.Current Draw(mA RMS),2-Wire Horn Strobe 8-17.5 Volts 16-33 Volts DC Input 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 103 167 71 90 143 165 187 217 254 Temporal Low 96 165 54 71 137 161 185 211 249 Non-Temporal High 106 173 71 90 141 165 187 230 273 Non-Temportal Low 95 166 54 71 124 161 170 216 258 3.1KTemporal High 111 164 69 94 147 163 184 229 257 3.1K Temporal Low 103 163 54 88 143 155 185 212 252 3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271 3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259 16-33 Volts FWR Input 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 107 135 179 198 223 254 286 Temporal Low 78 101 151 172 199 229 262 Non-Temporal High 107 135 179 198 223 254 286 Non-Temportal Low 78 101 151 172 199 229 262 3.1K Temporal High 108 135 179 200 225 255 289 3.1K Temporal Low 79 101 150 171 196 229 260 3.1K Non-Temporal High 108 135 179 200 225 255 289 3.1K Non-Temporal Low 79 101 150 171 196 229 260 Horn Strobe Tones and Sound Output Data Horn and Horn Strobe Output(dBA) 8-17.5 16-33 Volts Volts Switch Position Sound Pattern dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 AVDS86800 • L-Series Dimensions _ 2.47 -- 1 .37 -7-1 0 6.92 r_2.50 1 0 6.83 1 A I —8 0 0 0 8 --__ 1 0( 11'1 C r :;11.:}.' 008 _ 0 } Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box 1 i, ]�41;_x! ® X6`1® / 0; J Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box L-Series Ordering Information Model Description Model Description Ceiling Horn Strobes Ceiling Strobes '?::."• ';.', ';'•:•....•'-••' g ate.•. SCRL Strobe,Red PC2WL 2-Wire,Horn Strobe,White SCWL Strobe,White SCWL-CLR-ALERT Strobe,White,ALERT Accessories TRC-2 Universal Ceiling Trim Ring Red TRC-2W Universal Ceiling Trim Ring White SBBCRL Ceiling Surface Mount Back Box,Red SBBCWL Ceiling Surface Mount Back Box,White SYSTEM ©2017 System Sensor. 3825 Ohio Avenue•St.Charles,IL 60174 Product specifications subject to change without notice.Visit systemsensor corn �� SENSOR® Phone:800-SENSOR2•Fax:630-377-6495 or current product information.inctodtgthelatestVersionofthisdatasheet. AVDS86801•03/17 GENTEX CORPORATION Fire Alarm Bell G B Applications The GB Series provide durable and dependable operation SERIES required for life safety alarm systems. Alarm bells are low current, high decibel notification appliances for use in fire and burglary systems or other signaling applications. The GB Series is available in 24VDC or 120VAC. The GB Series is available in 6"or 10" housing and listed for indoor and outdoor applications. Bells must be used with the GBBB box for outdoor use. n� The GB Series is UL 464 listed and the units are warranted for 3 years from the date of purchase. GB10 GB6 Standard Features Product Listings • Available in 24VDC or 120VAC SIGNALING ''-- w • Available in 6"or 10"housing UU • Four wire 24VDC or 120VAC operation � :. • High dbA output LISTED 1t • Mounts to a standard 4"square electrical box • ANSI/UL 464 • ANSI/UL listed for outdoor use when used with the GBBB back box • CSFM:7135-0569:139 • MEA:#285-91-E • 18 AWG wire leads • Available in red metal finish Product Compliance • NFPA72 • Meets ANSI/UL 464 requirements • Quality Management System is certified to:ISO 9001:2008 111MIMIWIAF-7117171- ITI4TIFTil7TIMMIIII WWI MEMBER Voltage urrent = a 11111;011r4i411111 Draw 10 feet B10-24 904-1279-002 24VDC 10" 100mA 96 B6-120 904-1280-002 120VAC 6" 46mA 95 B10-120 904-1281-002 120VAC 10" 46mA 98 Notes GBBB back box dimensions:4.25"(10.7950 cm) square x 1.5"(3.81 cm) deep GBBB part number:901-0242-000 Operating Temperature for GB Series: Indoor Applications: 32°F to 120°F(0°C to 48.89°C) Outdoor Applications: -31°F to 150°F(-35°C to 65.56°C) Dimensions Mounting 10" DIA. GONG ,....-------"% 4"SQUARE OUTLET BOX '^r� �\ GBBB Box .- •-- 1 ('' \ I "� i' lr~) ,I '� J 6" DIA GONG, * �_� Jis 1 -J..� 1 .0 ) ADAPTOR G PLATE 7401) STRIKER HEX-BOLT GONG Wiring Diagrams D.C. BELLS (OBSERVE POLARITY) � w RED IN _� RED(OUT) 1 OF BASE FROM CONTROL PANEL .'16111TO NEXT BELL OR OR END-OF-LINE PRECEDING BELL �ill100.41111 RESISTOR BLACK INr BLACK(OUT) 'MN II1Pr 5-2WW A.C. BELLS RED IN Adini RED(OUT) FROM CONTROL PANEL OR •,1' PRECEDING BELL � ' BLACK IN BLACK(OUT) III III Architect & Engineering Specifications The audible signal shall be Gentex GB Series or approved equal and shall be listed by Underwriters Laboratories, Inc.per ANSI/UL 464.The notification appliance shall also be listed with the California State Fire Marshal (CSFM)and the Bureau of Standards and Appeals(NYC). The notification appliance shall produce a peak sound output of 95dBA or greater as measured in an anechoic chamber. The appliance shall be polarized to allow for electrical supervision of the system wiring.The unit will mount to a double gang box or double workbox without the use of an adapter plate. The GB unit must be used with the GBBB outdoor box for outdoor applications to meet UL listing requirements. 20 units per carton 44 pounds per carton GB6 50 pounds per carton GB10 Important Notice: 551-0042-03 G E N T E X These materials have been prepared by Centex Corporation Centex')for informational purposes only,are necessarily summary,and are not purported to serve as legal advice and should not be used as such.Gen- - tax makes no representations and warranties,express or implied, t these materials are complete and ac CORPORATION curate,up-to-date,or in compliance with all relevant local,state andfederal laws,regulations and rules.The materials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of Fire Protection Products Group•www. entex.com laws,regulations and rules and the application of such laws,regulations and rules to particular fact paaerns. g Each person's activities can differently affect the obligations that exist under applicable laws,regulations or 10985 Chicago Drive •Zeeland, Michigan 49464 rules.Therefore,these materials should be used only for informational purposes and should not be used as a substitute tsr seeking professional legal advice.Centex will not be responsible for any action or failure to 616.392.7195• 1.800.436.8391 •616.392.4219 Fax act in reliance upon the information contained in this material. Gentex Corporation reserves the right to make charges to the product data sheet at their discretion. "9, (J SIGNALING FADLISTED ACE-11 FIRE ALARM DOCUMENTS The FAD is the perfect fit to meet the demanding code requirements today. SAE's number one goal is to manufacture code compliant solutions and this product allows you to do just that. NFPA 72 2007 section 6.2.2.1 states, "A record of installed software and firmware version numbers shall be maintained at the location of the fire alarm control unit." This durable 16 gauge steel enclosure with a solid piano hinge and key lock will keep all of your code required documents in one safe place. With a 4GB USB flash drive it stores your fire alarm software safe and secure eliminating the occurrences of the soft- ware not being on site when technicians arrive to service the system.Along with your fire alarm soft- Standard Features: ware you can store your test & inspection docu- ments, service records, manuals &AS built drawings • Installed with a 4 gig digital flash drive for the system. Using a standard USB B connector it with USB B connector allows you to plug in with any standard SB printer • 2 Key ring hooks to hold system keys cable to upload or download information. • Business card holder for key contacts • Overall Dimensions are 12" x 13"tall and 21/4 deep The FDB is designed to hold critical manuals and • 16 gauge steel box and cover for security documents with a durable steel retainer. It has • Durable powercoat baked on finish designated hooks to organize key rings and hold other colors available important business cards for easy access and • Standard%"cat 30 key lock other lock as- reference. Inside the cover it has a organized note semblies available table that allows for documentation for passwords • Solid stainless steel piano hinge and other critical system information. • Permanently screened white ink 1" high "Fire Alarm Documents" • Legend sheet for passwords and system information BOK � n ISO 9 Space Age Electronics, Inc. FRE cilli!! R 1 RED www.lsae.com NEPA ANY 800.486.1723 Toll Free MEMBER Made In U.S.A. 508 485 0966 Local 508.485.4740 Fax Space Age Electronics, Inc. 2009 No Excuses, Just Solutions! ED0549 LT10559 Rev.D 1/2 PACE AGE ELECTRONICS, INC. - Specifications: The fire alarm documents box (FAD) shall be UL Listed, constructed of 18 gauge cold rolled steel. It shall have a red powder coat epoxy finish. The cover shall be permanently screened with 1" high lettering "FIRE ALARM DOCUMENTS " with white indelible ink. The access door shall be locked with a 3/4" barrel lock and the hinge shall be a solid width 12" stainless steel piano hinge. The enclosure will supply 4 mounting holes. Inside the enclosure will accommodate standard 8 1/2 x 11 manuals and loose document records that will be protected within the enclosure.A legend sheet will be permanently attached to the door for system required documentation, key contacts and system information. The FAD will have securely mounted inside a minimum of 4 Gigabyte digital flash memory drive with a standard USB B connector for uploading and downloading information. The drive shall not be accessible without tools to any person whom gains access to the records. The enclosure shall also provide 2 key ring holders with a location to mount standard business type cards for key contact personnel. go . 7. USB Storage Interface Requires Standard USB-B Connector a vont,rdm.a,r�M E�elm,m Properly Information Minimum Required Documentation(SIG-FUN) Key Ring ow�6 a: � Name Address gawM °WM.name.awu o Wants.system actgon Hooks occw.ncv mc wM VP. ,.arca own o EMa.a a Alt lc* cedIN6UUo"and Approvals mrq.n Eramenoaa n<.rwn mal°e.Kn.ne armal.�lpnem ,5.,system Inslellalicn Contrector ow o rKlae.° AI,Lown N e�em,ee 0.IL N°Mein aeoae...,INa a. e°.°a«oraw mNFFnm..rde rdN°I.rxn. Enclosed Or It Location nr.m.°ra.awerann Saneo wA o ErcMw a Alt Location Preted nen* E,al"ama. l'.ea.' Business °—— nw" re publahed. a"" ...on and maintenance,aanotan Phone o Enclosed OT Alt Location Card Holder RS Au homy is gJurstl tion E a aM.rcNwm .a,.<�aa,wnaNNntrdN System vmrm ttb he Installed and operating papeM Voltage aonappliance mut, with Itespprooed Gena 01°grae. , l el n, vwA o Erc.aw a MLeulbn NFFAn.erda cNed Wen Operations end,. CampMw Ward Hryrmn a.uetlry0.nd.8.3 vwn o End...P'At muton POS.name 10• — 9169E record of CO .n ono accordance v7.5 6 end i.e.2 apervra-on�— o o rcox° LrcAon 11 Copy Melte spocilk software r oxlA o Enc..Or...on Ml®W EqullmneM Informationo"e.nm la+e+x°9«nt Laeuon v ercla.a emiand maa a.a.a .ve ooire. accordance n n.<.ord.nwSection le , ,•:,,, nose. owno a...bon cru.n accord..Mb 77 1 � roes own o Enclave a Al Location end record Dam. r—,— J sp,aapv eatrma,Inc. 56 clrrxun saw %Amp MA msec eo¢.ee,rz, vwxtve cont LT10aH Ray.t Legend sheet for storing system information including contacts,sign-off,maintenance & test information,and alternate locations of additional records. Ordering Information: Part# Description SSU00685 Fire Alarm Storage Cabinet RED BOX Space Age Electronics, Inc. SS000686 Custom screening with your Logo www.lsae.com 800.486.1723 Toll Free Check out our Infinity line eFAD single gang 2 Gig digital storage 508.485.0966 Local solutions(IAMEFAD) 508.485.4740 Fax This document is subject to change without notice,see doc#ED0479 for legal disclaimer No Excuses, Just Solutions! ED0549 LT10559 Rev.D 2/2