Loading...
Report (57) f-,5020/i- GeniCf Simplex ®Ceyv sw ur�w�cd 3a) p TrueAlarm Analog Sensing UL, ULC Listed; FM, CSFM, TrueAlarm Analog Sensors — Photoelectric, and NYC, MEA Approved* Ionization, and Heat; Compatible Bases and Accessories Features TrueAlarm®analog sensing provides digital transmission of analog sensor values via MAPNET ll or IDNetTM,two-wire communications** Fire alarm control panel provides: I i f f��; SII • Individual sensitivity selection for each sensor • Sensitivity monitoring that satisfies NFPA 72 sensitivity testing requirements • Peak value logging allowing accurate analysis for 4098-9714 TrueAlarm Photoelectric Sensor Mounted in Base sensitivity selection • Automatic,once per minute individual sensor Descri•tion calibration check that verifies sensor integrity Automatic environmental compensation Digital Communication of Analog Sensing. • TrueAlarm analog sensors provide an analog • Display of sensitivity directly in percent per foot measurement that is digitally communicated to the host • Multi-stage alarm operation control panel using Simplex addressable communications. Ability to display and print detailed sensor At the control panel,the data is analyzed and an average • value is determined and stored.An alarm or other information in plain English language abnormal condition is determined by comparing the Photoelectric smoke sensors: sensor's present value against its average value and time. • Seven levels of sensitivity from 0.2%to 3.7% Intelligent Data Evaluation. Monitoring each sensor's Heat sensors: average value provides a continuously shifting reference point. This software filtering process compensates for • Fixed temperature sensing environmental factors(dust,dirt, etc.)and component • Rate-of-rise temperature sensing aging,providing an accurate reference for evaluating new Utility temperature sensing activity. With this filtering,there is a significant reduction • in the probability of false or nuisance alarms caused by Ionization smoke sensors*: shifts in sensitivity,either up or down. • Three levels of sensitivity; 0.5%,0.9%and 1.3% Control Panel Selection. Peak activity per sensor is For use with Simplex: stored to assist in evaluating specific locations. The alarm set point for each TrueAlarm sensor is determined at the • 4010,4020,4100, and 4120 Series control panels host control panel,selectable as more or less sensitive as • Universal Trans onders and 2120 TrueAlarm CDTs the individual application requires. equipped for MAPNET II operation Timed/Multi-Stage Selection. Sensor alarm set points Magnetic test feature can be programmed for timed automatic sensitivity selection(such as more sensitive at night, less sensitive Functional and architecturally styled chamber during day). Control panel programming can also provide enclosure: multi-stage operation per sensor. For example,a 0.2% • Louvered design enhances smoke capture by directing level may cause a warning to prompt investigation while a flow to chamber 2.5%level may initiate an alarm. • Entrance areas are minimally visible when ceiling Sensor Alarm and Trouble LED Indication. Each mounted sensor base's LED pulses to indicate communications with the panel. If the control panel determines that a Optional accessories include remote LED alarm indicator and output relays sensor is in alarm,or that it is dirty or has some other type of trouble,the details are annunciated at the control panel UL listed to Standard 268 and that sensor base's LED will be turned on steadily. During a system alarm,the control panel will control the * These products have been approved by the California State Fire Marshal(CSFM) LEDs such that an LED indicating a trouble will return to pursuant to Section 13144.1 of the California Health and Safety Code.See CSFM Listings 7272-0026:218,7271-0026:231,7270-0026:216,and 7300-0026:217 for pulsing to help identify the alarmed sensors. allowable values and/or conditions concerning material presented in this document.It is subject to re-examination,revision,and possible cancellation.Accepted for use-Cityof New York Department of Buildings-MEA35-93E.ULC models are designated by a"C" "TrueAlarm analog sensors and MAPNET II and IDNet communications am protected by one or suffix.4098-9717 was not ULC listed as of document revision date.Additional listingsmore of the following U.S.Patents:5,155,468;5,173,683;5,543,777;5,400,014;5,552,765; may be applicable,contact Simplex for the latest status. 5,552,763;4,796,025; DES.377,460. ©2000 Simplex Time Recorder Co.All rights reserved. S4098-0019-7 4/00 ' TrueAlarm Sensor Bases and Accessories . Sensor Base Features TrueAlarm sensor bases contain integral addressable Base mounted address selection: electronics that constantly monitor the status of the detachable photoelectric, ionization,or heat sensors. Each • Address remains with its programmed location sensor's output is digitized and transmitted to the system • Accessible from front(dipswitch under sensor) fire alarm control panel every four seconds. Automatic identification provides default sensitivity Since TrueAlarm sensors use the same base,different when substituting sensor types sensor types can be easily interchanged to meet specific Integral red LED for power-on(pulsing),or alarm or location requirements. This feature also allows intentional trouble(steady on) sensor substitution during building construction. When Locking anti-tamper design conditions are temporarily dusty, instead of covering the smoke sensors(causing them to be disabled),heat sensors Magnetically operated functional test may be installed without reprogramming the control Mounts on standard outlet box panel. Although the control panel will indicate an incorrect sensor type,the heat sensor will operate at a Sensor Bases default sensitivity providing heat detection for building protection at that location. 4098-9792, Standard sensor base 4098-9789,Sensor base with wired connections for: Mountin• Reference • 2098-9808 Remote LED alarm indicator or 4098-9822 relay(unsupervised) Electrical Box Requirements:(boxes are by others) 4098-9791,Sensor base with supervised relay driver Without relay:4"octagonal or 4"square, 1 1/2"deep; output(not compatible with 2120 CDT): single gang,2"deep • Relay operation is programmable and can be manually With relay:4"octagonal or 4"square, 1 1/2"deep, operated from control panel with 1 1/2"extension ring • Use with remote mount 2098-9737 relay 4"(102 mm)Square Box 4"(102 mm)Octagonal Box • Also includes wired connections for remote LED Surface mount reference alarm indicator or 4098-9822 relay - prnialMarairl 2098-9737, Remote or local mount supervised relay: • DPDT contacts for resistive/suppressed loads,power 1 1/2"(38 mm) minimum box depth limited rating of 3 A @ 28 VDC;non-power limited Flush mount reference,mount even with final rating of 3 A @ 120 VAC(requires external 24 VDC surface,or with up to 1/4"(6.4 mm)maximum recess coil power) 2098-9737 Relay(mounts in 4098-9822 Relay(mounts 4098-9822, LED Annunciation Relay: base electrical box or remotely) in base electrical box) • Activates when base LED is on steady, indicating _ local alarm or trouble 11111111 • liresistive/suppressed-Toads,power limited rating of 2 A @28 VDC; limitednonpow rating of 1/2 A @ 120 VAC,(requires external 24 VDC coil power) Relay Size: 2 1/2"X 1 1/2"X 1"(3.75 cubic inches) 4098-9832,Adapter plate: (64 mm X 38 mm X 25.4 mm) • Required for surface or semi-flush mounting to NOTE:Review total wire count,wire size,and accessories 4" square electrical box and for surface mounting to being wired to determine required box volume. 4"octagonal box • Can be used for cosmetic retrofitting to existing 6 3/8" F- 6 3/8"(162 mm) -1 diameter base product / � 4098-9832 Adapter Plate,required 2098-9808, Remote red LED Alarm 1/4" for mounting to surface mounted Indicator: (6.4 mm) boxes and 4"square flush box • Mounts on single gang box ALARM 4 7/8"(124 mm) .� (shown in illustration to right) � ( 415/16"mI mm) \ 0 /J !i Simplex TrueAlarm Bases 4098-9789,-9791,&-9792 i Simplex Time Recorder Co. 2 S4098-0019-7 4/00 TrueAlarm Sensors 4098-9714 Photoelectric Sensor PlTrueAlarm photoelectric sensors use a stable,pulsed infrared LED light source and a silicon photodiode Sealed against rear air flow entry receiver to provide consistent and accurate low power Interchangeable mounting smoke sensing. Seven levels of sensitivity are available for each individual sensor,ranging from 0.2%to 3.7%per EMI/RFI shielded electronics foot of smoke obscuration. Sensitivity is selected and Heat sensors: monitored at the fire alarm control panel. • Selectable rate compensated,fixed temperature The sensor head design provides 360°smoke entry for sensing with or without rate-of-rise operation optimum response to smoke from any direction.A built-in Listed to UL Standard 521 for 60 ft(18.3 m)spacing screen keeps insects from entering the smoke chamber. • for 135° F(57.2°C)alarm, and 40 ft(12.2 m)spacing Due to its photoelectric operation,air velocity is not for 155° F(68°C)alarm normally a factor,except for impact on area smoke flow. 1,1 4 7/8"(124 mm) ►I Smoke Sensors: • Photoelectric or ionization technology sensing • 360°smoke entry for optimum response O‘-----LED status indicator 2 1/8" (54 mm) 1 • : I I 11I PreaieffarA irtegs effi III I I LJ TrueAlarm heat sensors are self-restoring and provide rate ` compensated,fixed temperature sensing,selectable with or without rate-of-rise temperature sensing.Due to its 4098-9714 Photoelectric Sensor with Base small thermal mass,the sensor accurately and quickly measures the local temperature for analysis at the fire 4098-9717 Ionization Sensor alarm control panel. TrueAlarm Ionization sensors use a single radioactive Rate-of-rise temperature detection is selectable at the source with an outer sampling ionization chamber and an control panel for either 15°F(8.3°C)or 20°F(11.1°C) inner reference ionization chamber to provide stable _ per minute. Fixed temperature sensing is independent of operation under fluctuations in environmental conditions rate-of-rise sensing and programmable to operate at such as temperature and humidity. Smoke and invisible 135° F(57.2°C)or 155° F(68°C). In a slow developing combustion gases can freely penetrate the outer chamber. fire,the temperature may not increase rapidly enough to With both chambers ionized by a small radioactive source operate the rate-of-rise feature. However,an alarm will be [Am 241 (Americium)],a very small current flows in the initiated when the temperature reaches its rated fixed circuit. The presence of particles of combustion will cause temperature setting. a change in the voltage ratio between chambers. This TrueAlarm heat sensors can be programmed as a utility difference is measured by the electronics in the sensor device to monitor for temperature extremes in the range base and digitally transmitted back to the control panel for from 32° F to 155°F(0°C to 68° C).This feature can processing. provide freeze warnings or alert to HVAC system Three levels of sensitivity are available for each problems. (Refer to specific panels for availability.) ionization sensor: 0.5,0.9,and 1.3%per foot of smoke obscuration 4 7i6"024 mm} 1-* 4 7/8"(124 mm) O‘-----LED status indicator 0`* -LED status indicator 2 3/8" MMIIIMINIF (60 mm) 2 1/8 (54 mm) 1.1111111•111/ ILI me....— .I m_ Ili Vir111 °u \111 4098-9733 Heat Sensor with Base 4098-9717 Ionization Sensor with Base WARNING: In most fires, hazardous levels of smoke Sensor locations should be determined only after careful and toxic gas can build up before a heat detection consideration of the physical layout and contents of the device would initiate an alarm. In cases where Life area to be protected. Refer to NFPA 72,the National Fire Safety is a factor, the use of smoke detection is highly Alarm Code.On smooth ceilings, smoke sensors spacing recommended. g P g of 30 ft(9.1 m)may be used as a guide. For detailed application information,refer to 4098 Detectors, Sensors, and Bases Application Manual(574-709). Simplex Time Recorder Co. 3 S4098-0019-7 4/00 • ' TrueAlarm Analo• Sensin• Product Selection Chart TrueAlarm Sensor Bases Model Description Compatibility Mounting Requirements 4098-9792 Standard Sensor Base, no options Sensors 4098-9714,-9733, &-9717 4"octagonal or 4"square box, 1 1/2"min. depth; or single gang box,2"min.depth Sensor Base with connections for • Sensors 4098-9714, -9733, &-9717 4098-9789 Remote LED Alarm Indicator or • 2098-9808 remote LED alarm 4"octagonal or 4"square box Unsupervised Relay indicator or 4098-9822 relay 9 q Sensor Base with connections for • Sensors 4098-9714, -9733, &-9717 Note: Box depth requirements depend on Supervised Remote Relay and • 2098-9737 remote relaytotal wire count and wire size, refer to 4098-9791 connections for Remote Alarm • accessories list below for reference. 2098-9808 remote alarm indicator or Indicator or Unsupervised Relay 4098-9822 relay(unsupervised) TrueAlarm Sensors Model Description Compatibility Mounting Requirements 4098-9714 Photoelectric Smoke Sensor 4098-9717 Ionization Smoke Sensor Bases 4098-9792,4098 9789, Refer to base requirements and 4098-9791 4098-9733 Heat Sensor TrueAlarm Sensor/Base Accessories Model Description Compatibility Mounting Requirements Remote Mounting requires 4"octagonal or 2098-9737 Supervised Relay,mounts remote For use with 4098-9791 base 4"square box, 1 1/2"minimum depth or in base electrical box Base Mounting requires 4"octagonal box, 2 1/8"deep with 1 1/2"extension ring 2098-9808 Remote Red LED Alarm Indicator Single gang box, 1 1/2"minimum depth on single gang stainless steel plate Relay,tracks base LED status Bases 4098-9789 and 4098-9791 4098-9822 (unsupervised,mounts only in base 4"octagonal box,2 1/8"deep with 1 1/2" electrical box) extension ring Required for surface or semi-flush mounted 4098-9832 Adapter Plate Bases 4098-9792, -9789,&-9791 4"square box and for surface mounted 4"octagonal box Refer to Simplex publication 4098 Detectors, Sensors, and Bases Application Manual(574-709)for additional information. General Operating Specifications Communications and Sensor Supervisory Power MAPNET II or IDNet, auto-select,24-40 VDC w/data,400µA typical, 1 address per base Communications Connections Screw terminals for in/out wiring, 18 to 14 AWG Remote LED Alarm Indicator Current 1 mA typical, no impact to alarm current Remote LED Alarm Indicator and Relay Connections Color coded wire leads, 18 AWG UL Listed Temperature Range , 32°to 100° F(0°to 38°C) Operating Temperature with 4098-9717 or 4098-9733 32°to 122° F(0°to 50°C) Range,with Each Base with 4098-9714 15°to 122° F(-9°to 50°C) Humidity Range 10 to 95% RH 4098-9714, Photoelectric Sensor 0-2000 fUmin(0-610 m/min) Air Velocity Range 4098-9717, Ionization Sensor 0-200 ft/min(0-61 m/min) Altitude Up to 8000 ft(2.4 km) Housing Color Frost White 4098-9791 Base With Supervised Remote Relay 2098-9737(see page 2 for contact ratings) Externally Supplied Relay Coil Voltage 18-32 VDC(nominal 24 VDC) Supervisory Current 270 PA,from 24 VDC supply Alarm Current with 2098-9737 Relay 28 mA,from 24 VDC supply 4098-9822 Unsupervised Relay,Requirements for Bases 4098-9789 and 4098-9791 (see page 2 for contact ratings) Externally Supplied Relay Coil Voltage 18-32 VDC(nominal 24 VDC) Supervisory Current Supplied from communications Alarm Current 13 mA from separate 24 VDC supply - Simplex,the Simplex logo,TrueAlarm,MAPNET II,and IDNet are either trademarks or registered trademarks of Simplex Time Recorder Co.in the U.S.and or other countries.NI PA 72 is a registered trademark of the National lire Protection Association(NPPA). S 019-7 /00 ®Simplex Massachusetts 0 01441-0001 USA Westminster, USA visit us on the world wide web at www.simpiexnet.com All specifications and other information shown were current as of printing and are subject to change without notice. Wheelock ExcederTM Series COOPER Notification ED T" Strobe, Horn Strobe, and Horn Notification Appliances ;' FIRE ,Il �� Ceiling - - - - - Wall Description: The Wheelock®ExcederTM Series of notification appliances feature a sleek modern design that will please building owners with reduced - Save up to 48% in current draw* total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes,voltage test - Up to 9 models now in 1 appliance points, 12/24 VDC operation,universal mounting base and multiple mounting options for both new and retrofit construction. -Save up to 1 4% cost of installation** The Wheelock®ExcederTM Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit.All strobe models feature an industry first of 8 candela settings on a single Sleek Modern Aesthetics appliance.Models with an audible feature 3 sound settings(90,95, 99 dB).All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. tipj Finger Slide Switches Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock® ExcederTM Series of wall and ceiling notification LVoltage Test Points appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting 12Multiple Voltages base can be pre-wired to allow full testing of circuit wiring before VDC the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt,dust,paint 3 Audible Settings and damage to the contacts. The Contact Cover also acts as a 90,95, 99 dB shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while 8 Candela Settings*** it is on the UMB. When the Contact Cover is removed the circuit Wall- 15/1575/30/75/95/110/135/185 will show an open until the appliance is installed.The UMB allows -15/30/60/75/95/115/150/177 for consistent installation and easy replacement of appliances if *** required. Wall models provide an optional locking screw for extra Universal Mounting Base secure installation, while the ceiling models provide a captivated Ceiling and Wall Mounts to 5 Backbox Types screw to prevent the screw from falling during installation. 61 Environmentally Friendly Low Current Draw Compatibility and Requirements -Synchronize using the Wheelock'Sync Modules or panels with built-in Wheelock'Patented Sync Protocol -Compatible with UL"Regulated Voltage"using filtered VDC or unfiltered VRMS input voltage -Strobes produce 1 flash per second over the"Regulated Voltage"range "Compared to competitive models ***Patented **Compared to previous models . NOTE:All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING - OR APPLYING THIS PRODUCT. VISIT WWW.000PERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: General Notes: •Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range'. •All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. •Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 120°F(0°C to 49°C)and maximum humidity of 93%(±2%)UL 464(85%UL 1971). •Series Exceder horns are under UL Standard 464 for audible signal appliances(Indoor use only). Low Current Draw = Fewer Power Supplies Strobe Ratings per UL Standard 1971 UL Max Current* 24 VDC/24 FWR 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140 5TC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110 Horn Strobe Ratings per UL 1971 &Anechoic at 24VDC UL Max Current*at Anechoic 99 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159 HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125 UL Max CtJrent*at Anechoic 95 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153 HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 ,-,/ 0.230 0.272 0.122 ,FF UL Max Current*at Anechoic 90 dBA 24VDC 12 VDC - Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148 HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120 Horn Ratings per UL Anechoic Model Regulated Voltage 99 dB 95 dB 90 dB s; Range VDC HN 16-33.0 0.064 0.044 0.022 HNC 16-33.0 0.084 0.044 0.022 / HN 8.0-17.5 0.047 0.026 0.017 HNC 8.0-17.5 0.047 0.026 0.017 *UL max current rating is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units). For strobes the UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions. Specification & Ordering Information Sync w/ Model Strobe DSM or 12/24 VDC* Mounting Candela Wheelock Power Options Supplies Horn Strobes HSR 15/1575/30/75/95/110/135/185 X X x UMB** o N HSW 15/1575/30/75/95/110/135/185 X X - UMB** 07,0 HSRC 15/30/60/75/95/115/150/177 X X u UMB** o V HSWC 15/30/60/75/95/115/150/177 X X UMB** Ty as -0 Strobes - O cu E STR •>- 15/1575/30/75/95/110/135/185 X X o UMB*" v STW15/1575/30/75/95/110/135/185 X X M UMB** E STRC 15/30/60/75/95/115/150/177 X X UMB** --> STWC p 15/30/60/75/95/115/150/177 X X v UMB** N Horn °i 03 O HNR - X X N UMB** HNW X X c' UMB** V no w HNRC c0 X X °i UMB** HNWC ' X X UMB** *12 VDC models feature 15&15/75 settings **UMB=Universal Mounting Base r MI Model Legend 4; : '��—r. ; HN = Horn A =Agent Lettering ST = Strobe (Strobes only) ' -•.. .,. HS = Horn Strobe AL=Alert Lettering ` Ill C = Ceiling Mount (Strobes only) W = White N =No Lettering ��� "� R = Red (Strobes only) -, / , A / N - ...- ' � Example 1: STRC=Strobe,Red,Ceiling Mount r / is •.r Example 2: HSR=Horn Strobe,Red,Wall Mount Example 3: HSW=Horn Strobe,White,Wall Mount I Example 4:STW-AL=Strobe,White,Wall Mount,Alert Lettering Example. Example: HSWC tlfilL... 1 H .. .' tip,, ''N. i.: 0 0 4 *UMB Contact Cover Voltage test points for quick 8 candela settings Common base for wall and ceiling with 5 troubleshooting and easy spot mounting options checking (wall models only) NOTE: Due to continuous development of our products,specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc.,dba Cooper Notification standard terms and conditions. Architects and Engineers Specifications The notification appliances shall be WheelockExceder— Series HS Audible Strobe appliances, Series ST Visual Strobe appliances .and Series HN Audible appliances or approved equals.The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired)for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B.All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel(FACP)with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The Series shall be of low current design. Where Multi-Candela appliances are specified,the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g.ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three(3)field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel(FACP). The mounting base shall be the same base among all horn, strobe, horn strobe,wall and ceiling models. All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24"H x 4.58"W x 2.19"D. Series HN wall shall measure 5.24" H x 4.58" W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68"x 2.63" D. Series HNC ceiling shall have a diameter of 6.68"x 1.50" D. When synchronization is required,the appliance shall be compatible with Wheelock°'s DSM Sync Modules,Wheelock'Power Supplies or other manufacturer's panels with built-in Wheelock®Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate,the strobe shall revert to a non-synchronized flash-rate and still maintain(1) flash per second over its Regulated Voltage Range.The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock° synchronization protocol. Wall Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM Ceiling Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM Member WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Exceder- Spec Sheet 6/11 NJ Location 273 Branchport Ave. Long Branch,NJ 07740 P:800-631-2148 F:732-222-8707 www.coopernotification.com Cooper Notification is Wheelock' ',;I]Di Pi SAFEPATHW WAVES, 1 * COOPER Notification COOPER Notification Series CH Chimes and Chime Strobes 1 ,i-it.:41,-,i,,,:: 4; , ' _,,,,,!,,4::: FIRE , - t � SERIES CH70 _ CHIME STROBE SERIES CH70 SERIES CH90 SERIES CH90 CHIME STROBE CHIME CHIME Description Features The Wheelock Series CH Chimes and Chime Strobes • Approvals include: UL Standard 1971, UL Standard 464, minimize alarm system power supply requirements and New York City (MEA), and California State Fire Marshal wiring costs with a low current draw and a patented chime (CSFM) and Chicago(BFP) See approvals by model in mounting plate for fast, easy installation. Each model has Specifications and Ordering Information a built-in level adjustment feature and an aesthetic two (2) ADA/NFPA/UFC/ANSI compliant screw grille cover. • These unique solid-state chime appliances provide field Complies with OSHA 29 Part 1910.165 selectable single-stroke or vibrating operation with Anechoic • Wall mount models are available with Field sound levels adjustable up to 83 dB and tone adjustable from Selectable Candela Settings of 15/30/75/110cd or 800 to 1200 Hz. 135/185cd (Multi-Candela models)or 1575cd(single Strobe options for wall mount models include 1575cd or candela model) Wheelock patented MCW multi-candela strobe with field • Ceiling mount models are available with field selectable selectable candela settings of 15/30/75/110cd or the high candela settings of 15/30/75/95cd or intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models are available in Wheelock patented 115/177cd (Multi candela models) MCC multi-candela ceiling strobe with field selectable • Low current draw with temperature compensation to intensities of 15/30/75/95cd or the high intensity MCCH strobe reduce power consumption and wiring costs with field selectable 115/177cd. • Strobes produce 1 flash per second over the regulated The strobe portion of all Series CH Chime Strobes may be voltage range synchronized when used in conjunction with the Wheelock • 24 VDC with wide UL"Regulated Voltage" using filtered SM,DSM Sync Modules,Wheelock Power Supplies or other DC or unfiltered VRMS input voltage manufacturers panels incorporating the Wheelock Patented Sync Protocol. Wheelock's synchronized strobes offer an • Synchronize using the Wheelock Sync Modules or panels easy way to comply with ADA recommendations concerning with built-in Wheelock Patented Sync Protocol photosensitive epilepsy as well as meeting the requirements • Adjustable Volume and Tone Control of NFPA 72 and UFC. • Single Stroke or Vibrating Operation The Series CH Chime Strobes are UL Listed for indoor, wall or ceiling mount applications under Standard 1971 • Fast Installation with IN/OUT screw terminals using#12 to for Signaling Devices for the Hearing-Impaired and under #18 AWG wires Standard 464 for Private Mode Audible Signal Appliances. They are available in two attractive package styles for flush mounting to standard electrical boxes or convenient surface mounting.All models include IN/OUT wiring terminations that accept two#12 to#18 AWG wires at each terminal. Inputs are polarized for compatibility with industry standard reverse polarity supervision. aiii>,,,. ilabl :w- M EA APPROVED S5391 151-92-E 7125-0785:151 7135-0785:109(Chime Only) • NOTE:All CAUTIONS and WARNINGS are identified by the symbol A.All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.000PERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range". Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F(0°C to 49°C)and maximum humidity of 93%(±2%). • Series NH horns are listed under UL Standard 464 for audible signal appliances(Indoor use only). • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range". Table 1:Average RMS Current CH70 Strobe current-Wall Mount CH90 Strobe current-Ceiling Mount CH70/ Chime CH90 241575W 24MCW 24MCWH 24MCC 24MCCH Chimes current • • 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd • 24 vdc 0.022 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270 • UL max* 0.022 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420 Table 2: Chime dBA ratings * RMS current ratings are per UL average RMS dBA @ 10 ft method. UL max current rating is the maximum RMS reverberant current within the listed voltage range(16-33v for 24v Peak dBA @ units). For strobes the UL max current is usually at CH70/CH90 10 ft. anechoic the minimum listed voltage (16v for 24v units). For sound level Min Max audibles the max current is usually at the maximum 83 52 58 listed voltage(33v for 24v units). For unfiltered FWR ratings, see installation instructions. Application 1. The chimes are factory set in single stroke(SS)mode. They can be changed to vibrating(VIB)mode with jumper on PC Board.SINGLE STROKE OPERATION: The minimum Input pulse duration must be at least 160 ms"on"time and 160 ms"off'time. The chime will only operate once each time it is pulsed.This mode is recommended for coded systems.VIBRATING OPERATION:Continuous input voltage applied to the chime will activate the chime at one-second intervals. 2. The volume and tone controls have been adjusted at the factory to insure maximum dBA output.However,once the mode is selected,the installer may want to fine-tune the signal to better suit the application. 3. Anechoic dBA is measured in an anechoic chamber with peak meter response.Reverberant dBA is rated per UL Standard 464. 4. Chime inrush current is 0.100 amps maximum with filtered DC input(0.140 amps with VRMS input voltage)with a time duration of 100 milliseconds. Wiring Diagrams# . SERIES CH CHIME & STROBE OPERATE INDEPEN- SERIES CH CHIME STROBES SYNCHRONIZED W/ DANTLY(NON-SYNC OR SYNC) MULTIPLE DSM MODULES =Ram DSM #10 _'RETEDINGO +P +CSO HOOTS APPLIANC.E,C APPLIANCEO Syno0 SYNC NJEI,LE,_ - -C OR EOLRO Strobe NAC Cir,2)}I1 C}i_C CH.a POYIER SrTPPLIL F❑ 1-' V Note: Figure OR SACS] DSM #20 shows intercon- POECE 5 nc0 FRECEDINuO + — 1 — — —— — +11ITE,..,, �❑ strobe NAC Ci ' CH CI ,�L rection to strobe APPLIANCE,❑ RE.RO _ SYNC MXIJLE,O ii 1 r— - — R° co through sync POWER SUPPLYO DSM #30 module. Chime ; ; ; ; P❑ SYnci cH_Q CH Q portion requires 2 +o-1,r• +Elm Strobe NAC CSS separate conduc- STROBE❑ CHIME: DSM Interconnecting wiring shown. Maximum of tors to FACP. (OPTIONAL).. twenty (20)D SERIES CH CHIME STROBE APPLIANCES SERIES CH CHIME STROBE APPLIANCES & RSS SYNCHRONIZED WITH DSM MODULE SINGLE STROBES SYNCHRONIZED WITH PS-12/24-8CP "CLASS A" and PS-12/24-8MP DSM Series PS-12/24-OMPC �..z < ® 45 .e4r• I OUTPUTS EC2H ell --4� -r/19v9.m. 4-CLASS;_ Au <ORO 8 a 1 g c❑ PC 2-CLASSO „A„O 1 4 • •94,a • -N A►FuMsa AN4a.i9 ..�.. � r..4.. < ® r+ rµr CH eries PS-12/24-SP J For wiring information on the PS-24-8MC Power Supply, please refer to Data Sheet#8900. Specifications and Ordering Information Strobe Sync Model Model Agency Approvals Order Wall Ceiling w/SM, DSM Strobe 24 Mounting Model Number Color Color Code Mount Mount or Candela VDC RED White Options PS-24-8MC UL MEA CSFM BFP CH70-24MCW-FR 9018 X X 15/30/75/110 X X - L,O,P,Q,R,U,Y X X X X CH70-24MCW-FW 9019 X - X 15/30/75/110 X - X L,O,P,Q,R,U,Y X X X X CH70-24MCWH-FR 9083 X - X 135/185 X X - L,O,P,Q,R,U,Y X X X * CH70-24MCWH-FW 9084 X - X 135/185 X - X L,O,P,Q,R,U,Y X X X * CH70-241575W-FR 7830 X - X 15(75 on Axis) X X - L,O,P,Q,R,U,Y X X X X --> CH90-24MCC-FW 3168 - X X 15/30/75/95 X - X Q,U,V X X X * CH90-24MCC-FR 3167 - X X 15/30/75/95 X X - Q,U,V X X X * CH90-24MCCH-FW 3110 - X X 115/177 X - X Q,U,V X X X * CH70-24-R 7825 X X - - X X - L,O,P,Q,R,U,Y X X X X CH70-24-W 7827 X X - - X - X L,O,P,Q,R,U,Y X X X X CH90-24-W 7826 X X - - X - X Q,U,V X X X X - ICH90-24-R 7828 X X - - X X - Q,U,V X X X X Models are available in either Red or White.Call Customer Service for Order Code&Delivery. *PENDING NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc.standard terms and conditions. • Architects and Engineers Specifications The chime appliances shall be Wheelock Series CH Chimes and the chime strobe appliances shall be Wheelock Series CH Chime -Strobes or approved equals. The chime shall be UL Listed under Standard 464 for Audible Signal Appliances and chimes equipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing-Impaired. In addition,the strobes shall be certified to meet the requirements of FCC Part 15, Class B and shall incorporate low temperature compensation to ensure the lowest possible current consumption. All chimes shall use solid state components and shall provide field selectable single stroke or vibrating operation with volume control and tone control.All models shall have a peak Anechoic sound output of 83 dB at 10 feet and an adjustable frequency range of 800 to 1200 Hz.All inputs shall employ terminals that accept#12 to#18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1)flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The strobe shall be of low current design. Where Multi-Candela Chime Strobes are specified, the strobe intensity shall have a minimum of four(4) field selectable settings and shall be rated per UL Standard 1971 at: 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount.The selector switch for selecting the candela shall be tamper resistant and not accessible from the front of the appliance.The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 listing with 75 candela on-axis is required (e.g.ADA compliance). When synchronization is required, the strobe portion of the appliance shall be compatible with Wheelock SM, DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built-in Wheelock Patented Sync Protocol.The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed),the strobe shall revert to a non-synchronized flash rate. The chime and the chime strobe appliances shall be designed for indoor surface or flush mounting.The chime and chime strobe shall incorporate a chime mounting plate with a grille cover which is secured with two screws for a level, aesthetic finish and shall mount to standard electrical hardware requiring no additional trimplate or adapter. All chime and chime strobe appliances shall be backward compatible. IMAM Member WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S0710 CH 10/07 NJ Location FL Location VA Location 273 Branchport Ave. 7565 Commerce Ct. P:877-459-7726 Long Branch,NJ 07740 Sarasota,FL 34243 F:703-294-6560 P:800-631-2148 P:941-487-2300 F:732-222-8707 F:941-487-2389 www.coopernotification.com 0111 Cooper Notification is Wheelock®(MEDC) SAFEPATH WAVE COOPERNotification