Plans ,, 5,k 0/6 , 0002. l 32 5` 5c f cd6s4 ri4 tqcii , , ,.,. Fire Protection Worldwide Contacts www•tyco-fire.com Products SEP 2 9 ?015 Series TY-FRB — 2.8, � 5 6 and 8 0 K-Fa• ctor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General when exposed to corrosive atmo- spheres. Although corrosion-resistant Description coated sprinklers have passed the standard corrosion tests of the appli- The TYCO Series TY-FRB, 2.8, 4.2, cable approval agencies,the testing is ° 5.6,and 8.0 K-factor,Upright,Pendent, not representative of all possible cor- and Recessed Pendent Sprinklers rosive atmospheres. Consequently, described in this data sheet are quick it is recommended that the end user be consulted with respect to the suit- response, standard coverage, deco- rative 3 mm glass bulb-type spray ability of these coatings for any given sprinklers designed for use in light or corrosive environment. The effects of 1 3. , j - .1- ordinary hazard,commercial occupan- ambient temperature,concentration of ,; cies such as banks, hotels,and shop- chemicals, and gas/chemical velocity, ~" it,01 X ping malls. should be considered, as a minimum, z ":k along with the corrosive nature of the •`"" The recessed version of the Series chemical to which the sprinklers will be TY-FRB Pendent Sprinkler, where exposed. applicable,is intended for use in areas with a finished ceiling. This recessed An intermediate level of the Series pendent sprinkler uses one of the TY-FRB Pendent Sprinklers is detailed following: in Technical Data Sheet TFP356, and • A two-piece Style 10(1/2 inch NP Sprinkler Guards are detailed in Tech- or Style 40(3/4 inch NPT)Recessed nical Data Sheet TFP780. " Escutcheon with 1/2 inch (12,7 mm) NOTICE of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment The Series TY-FRB, 2.8, 4.2, 5.6, from the flush pendent position,or a and 8.0 K-factor, Upright, Pendent, • A two-piece Style 20 2 inch NP and Recessed Pendent Sprinklers 1/ $ ( T) described herein must be installed v" or Style 30(3/4 inch NPT)Recessed and maintained in compliance with Escutcheon with 1/4 inch (6,4 mm) this document and with thea lica- of recessed adjustment or up to 1/2 ble standards of the National Fire Pro- inch (12,7 mm) of total adjustment from the flush pendent position. tection Association, in addition to the standards of any authorities having The adjustment provided by the jurisdiction.Failure to do so may impair Recessed Escutcheon reduces the the performance of these devices. Sprinkler accuracy to which the fixed pipe drops The owner is responsible for maintain- to the sprinklers must be cut. ing their fire protection system and Identification Corrosion-resistant coatings, where devices in proper operating condition. Number (SIN) applicable,are utilized to extend the life The installing contractor or sprinkler of copper alloy sprinklers beyond that manufacturer should be contacted with which would otherwise be obtained any questions. TY1131 -Upright 2.8K,1/2-NPT TY1231 -Pendent 2.8K, 1/2"NPT City of Tigard I TY2131 -Upright 4.2K,1/2"NPT TY2231 -Pendent 4.2K,1/2"NPT • IMPORTANT An,. •Ve. Plans TY3131 -Upright 5.6K,1/2"NPT Always refer to Technical Data - 1 _ ��''r TY3231 -Pendent 5.6K,1/2-NPT Sheet TFP700 for the `INSTALLER Date . (k TY4131 -Upright 8.0K,3/4"NPT WARNING"that provides cautions "~------ TY4231 -Pendent 8.0K,3/4"NPT with respect to handling and instal- � l j_,_„` t"T' TY4831 -Upright 8.0K,1/2"NPT lation of sprinkler systems and com- jCs l l G-� ponents. Improper handling and TY4931 -Pendent 8.0K,1/2-NPT installation can permanently damage a sprinkler system or its compo- OFFICE COPY nents and cause the sprinkler to fail COPY 11 to operate in a fire situation or cause ft to operate prematurely. Page 1 of 10 NOVEMBER 2015 TFP171 TFP171 Page 2 of 10 *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - gutton 4 Bulb 6 Assembly ScrewSrlector* Deflector. special request. PLATE SEATING 7 - Bushing 7 1 ire--l"rfl"Prr-rit.--- ;n-cil 7/16" I ati,A.,... 3 1 (11,1 mm) I . NOMINAL 2-1/4" �� �` 1 2 - MAKE IN (57,2 mm) 111S-10 I I 2-3/16" 4 ( ) 1 9/16" �. 5 55,6mm illi III (39,7 mm) I �� 1/2"NPT** - WRENCH STYLE 10 or 20 Ir 2-7/8"(73,0 mm)DIA. - FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 1 QUICK RESPONSE SERIES TY-F2$K FACTOR/21N)AHNP PENDENT(TY1231)SPRINKLERS *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression_ Button Assembly Screw is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 4 Bulb6 Serlector* Deflector. special request. PLATE SEATING SURFACE 1 J P ___ ,fff 3 7/,6" _ 17--------- --. ilt 2, 2 i (NOMINAL 2 3/16" ��- r MAKE IN (55,6 mm) 4 0 r�r 2-3/16" Ili1-1/2" 4if I � j (55,6 mm) i (38,1 mm) ice-5 __ III • _ 1 ---• lir 6* 1/\ 1 NPT** I WRENCH • STYLE 10 or 20 L..._2-7/8"(73,0 mm)DIA. - FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 2 QUICK RESPONSE SERIES TY-FRB K FUPRIGHT (T Y21 1)AHNP PENDENT(TY2231)SPRINKLERS *Temperature rating ** Pipe thread connections per 1 - Frame 3 - Sealing 5 - Compression2 - gutton Assembly Screw is indicated on ISO 7-1 can be provided on ESCUTCHEON 4 Bulb 6 Deflector* Deflector. special request. PLATE SEATING SURFACE 1 r _____ __ 7/16" ��'\��1':�� fl (NOMINAL111 II , ik 2 ,.... ______. 1 / ME 2-3/16" 100 - MAKE IN (55,6 mm) 1 4 2-3/16" 101-1/2" (55,6 mm) i (38,1 mm) jam-5 A_ 1/2"NPT** f WRENCH STYLE 10 or 20 2-7/8"(73,0 mm)DIA. FLATS RECESSED UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 3 QUICK RESPONSE SERIES TY-FRB K RI GHT(T Y3 INCAND H NPPENDENT(TY3231)SPRINKLERS TFP171 Page 3 of 10 *Temperature rating ** Pipe thread connections per is indicated on ISO 7-1 can be provided on ESCUTCHEON 2 - Frame 3 AssemblySealing 5 Compression Deflector. special request. PLATE SEATING 2 Button Screw 4 Bulb 6 Deflector* ____ ___________i SURFACE -,-Y 0 1 (121, mm) i `�. , y� 3 NOMINAL • f� y t MAKE-IN , 2-5/16" m� ��- 2 iii i I (58,7 mm) j 2-1/4" 1 (57,2 mm) I 1-9/16" 1� - IF (39,7 mm) I 3/4"NPT** WRENCH STYLE 30 or 40 ..-- �� FLATS RECESSED 2-7/8"(73,0 mm)DIA. UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION FIGURE 4 QU/CK RESPONSE SERIES TY-FRB UPRIGHT(TY4131)AND PENDENT(TY4231)SPRINKLERS 8.0 K-FACTOR,3/4 INCH NPT CEILING PLATE 1 - Frame 5 - Compression SEATING SURFACE 2 - Button Screw ��"�- -'�'�,i t , 1 3 - Sealing 6 - Deflector* 7/16" SE' y 3 4 Bulb Assembly (11,1 mm) � - 2-1/4" 4 OF till 1° NOMINAL (57,2 mm) 7/1 4 2 MAKE-IN r r -1 2-3/16" *Temperature rating is II01-9/16" I 4 indicated on Deflector. (55,6 mm) i (39,7 mm) . f --�5 ** Pipe thread connections _., W ,,` * per ISO 7-1 can be 1/2"NPT** WRENCH 6 provided on special UPRIGHT FLATS request. PENDENT CROSS SECTION FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT(TY4831)AND PENDENT(TY4931)SPRINKLERS 8.0 K-FACTOR, 1/2 INCH NPT L' WRENCH RECESS WRENCH RECESS (END"A"USED FOR fill' ..01/".". 1/2"NPT MODELS) WRENCH RECESS ` (END"B"USED FOR , 3/4"NPT MODELS) PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER FIGURE 6 WRENCHING AREA W-TYPE 6 SPRINKLER FIGURE 7 WRENCH W--TYPE 7 RECESSED SPRINKLER WRENCH TFP171 Page 4 of 10 Do not attempt to compensate for Design insufficient adjustment in the Escutch Technicaleon Plate by under-or over-tightening Data Criteria the sprinkler.Re-adjust the position of the sprinkler fitting to suit. Approvals The TYCO Series TY-FRB, 2.8, 4.2, UL and C-UL Listed 5.6,and 8.0 K-factor,Upright,Pendent, Series TY-FRB Upright and Pendent FM,LPCB,and NYC Approved and Recessed Pendent Sprinklers are Sprinklers Refer to Table A and B for complete intended for fire protection systems The Series TY-FRB Pendent and approval information including corrosion- designed in accordance with the stan- Upright Sprinklers must be installed resistant status. dard installation rules recognized by inst uctordance with the following Maximum Working Pressure the applicable Listing or App ons. agency(such as, UL Listing is based Step 1.Install Pendent sprinklers in the Refer to Table C. on the requirements of NFPA 13, and Discharge Coefficient FM Approval is based on the require- pendent position. Install upright sprin- klers in the upright position. K=2.8 gpm/psis(40,3 Ipm/bars) ments of FM's Loss Prevention Data K=4.2 gom/psis(60.5 Ipm/bard) Sheets). Only the Style 10, 20, 30, or Step 2. With pipe-thread sealant K=5.6 gpm/psis(80,6 Ipm/bars) 40 Recessed Escutcheon,as applica- applied to the pipe threads, hand- K=8.0 gpm/psis(115,2 Ipm/barye) ble,is to be used for recessed pendent tighten the sprinkler into the sprinkler installations. Temperature Rating Refer to Table A and B. Installation Step 3.Tighten the sprinkler into the sprinkler fitting using only the W-Type Finishes6 Sprinkler Wrench(Figure 6).With ref- Sprinkler:Refer to Table D. The TYCO Series TY-FRB,2.8,4.2,5.6, erence to Figures 1 through 5, apply and 8.0 K-factor,Upright,Pendent,and the W-Type 6 Sprinkler Wrench to the Recessed Escutcheon:Signal or Pure Recessed Pendent Sprinklers must sprinkler wrench flats. White,Jet Black,Chrome Plated,or p be installed in accordance with this Series TY-FRB Recessed Pendent Natural Brass section. Physical CharacteristicsSprinklers Bronze General Instructions The Series TY-FRB Recessed Pendent Frame Brass/Copper Do not install any bulb-type sprinkler S rinklers must be installed in accor- Setton Beating Assembly..Beryllium Nickel w/TEFLON if the bulb is crackedtthere is a loss dance with the following instructions. Bulb Glass of liquid from the bulb.With the sprin- dance with the following instructions. Compression Screw Bronze kler held horizontally,a small air bubble Step A.After installing the Style 10,20, Deflector Copper/Bronze Bushing(K=2.8) Bronze should be present.The diameter of the 30, or 40 Mounting Plate, as applica- air air bubble is approximately 1/16 inch ble,over the sprinkler threads and with Operation (1,6 mm)for the 135°F(57°C)and 3/32 pipe-thread sealant applied to the pipe inch(2,4 mm)for the 286°F(141°C)tem- threads,hand-tighten the sprinkler into The glass bulb contains a fluid that perature ratings. the sprinkler fitting. expands when exposed to heat.When A leak-tight 1/2 inch NPT sprinkler Step B.Tighten the sprinkler into the the rated temperature is reached, the joint should be obtained by applying a sprinkler fitting using only the W-Type fluid expands sufficiently to shatter the minimum to maximum torque of 7 to 7 Recessed Sprinkler Wrench (Figure glass bulb, allowing the sprinkler to 14 ft.-lbs.(9,5 to 19,0 Nm).A leak tight 7). With reference to Figures 1 to 4, activate and water to flow. 3/4 inch NPT sprinkler joint should be apply the W-Type 7 Recessed Sprinkler obtained with a torque of 10 to 20 ft.- Wrench to the sprinkler wrench flats. lbs. (13,4 to 26,8 Nm). Higher levels of Step C. After ceiling installation and torque can distort the sprinkler Inlet finishing,slide on the Style 10,20, 30, with consequent leakage or impairment or 40 Closure over the Series TY-FRB of the sprinkler. Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. TFP171 Page 5 of 10 SPRINKLER FINISH(See Note 5) K TYPE TEMPERATURE BULB LIQUID NATURAL I CHROME FACTOR COLOR I POLYESTER*** BRASS PLATED 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY1231) and 175°F(79°C) Yellow UPRIGHT 1,2,3,4 (TY1131) 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange 2.8 RECESSED 1/2"NPT PENDENT 155°F(68°C) Red (TY1231)* 175°F(79°C) Yellow Figure 8 200°F(93°C) Green 135°F(57°C) Orange 1,2,4 RECESSED PENDENT 155°F(68°C) Red (TY1231)** 175°F(79°C) Yellow Figure 9 200°F(93°C) Green 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY2231) and 175°F(79°C) Yellow UPRIGHT (TY2131) 200°F(93°C) Green 286°F(141°C) Blue - 135°F(57°C) Orange 4.2 RECESSED 1/2"NPT PENDENT 155°F(68°C) Red (TY2231)* 1,2 Figure 10 175°F(79°C) Yellow 200°F(93°C) Green RECESSED 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY2231)** 175°F(79°C) Yellow Figure 11 200°F(93°C) Green NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the City of New York under MEA 354-01-E. 5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. *Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. **Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. ***Frame and Deflector only. N/A:Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K-FACTOR SPRINKLERS TFP171 Page 6 of 10 SPRINKLER FINISH(See Note 8) BULB LIQUID NATURAL I CHROME I POLYESTER*** LEAD K TYPE TEMPERATURE COLOR BRASS PLATED COATED FACTOR 135°F(57°C) Orange PENDENT (TY3231) 155°F(68°C) Red and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,3,5 UPRIGHT P00°F(93°C) Green (TY3131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 5.6 PENDENT175°F 1,2,4,5 N/A 1/2"NPT (TY3231)* 175°F(79°C) Figure 12 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT175°F 1,2,3,4,5 N/A (TY3231)** 175°F(79°C) Figure 13 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT 155°F(68°C) Red (TY4231) and 175°F(79°C) Yellow 1,2,3,4,5,6,7 1,2,5 UPRIGHT 200°F(93°C) Green (TY4131) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red 8.0 PENDENT 175°F(79°C) Yellow 1,2,5 N/A 3/4"NPT (TY4231)* Green Figure 14 200°F(93°C) 286°F(141°C) Blue 135°F(57°C) Orange RECESSED 155°F(68°C) Red PENDENT175°F 1,2,3,5 N/A (TY4231)** 175°F(79°C) Figure 15 200°F(93°C) Green 286°F(141°C) Blue 135°F(57°C) Orange PENDENT (TY4931) 155°F(68°C) Red8,0 1/2"NPT and 175°F(79°C) Yellow 1,2,4,5,6 1,2,5 UPRIGHT 200°F(93°C) Green (TY4831) 286°F(141°C) Blue NOTES: 1. Listed by Underwriters Laboratories,Inc.,(UL)as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories,Inc.,for use in Canada(C-UL)as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation(FM)as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board(LPCB Ref.No.007k/04)as Quick Response Sprinklers.However,LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354-01-E. 6. VdS Approved(For details,contact Tyco Fire Suppression&Building Products,Enschede,Netherlands,Tel.31-53-428-4444/Fax 31-53-428-3377.) 7. Approved by the Loss Prevention Certification Board(LPCB Ref.No.094a/06)as Quick Response Sprinklers. 8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed,the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where Lead-Coated Sprinklers are noted to be FM Approved,the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers. •Installed with Style 10(1/2"NPT)or Style 40(3/4"NPT)3/4"Total Adjustment Recessed Escutcheon,as applicable. *'Installed with Style 20(1/2"NPT)or Style 30(3/4"NPT)1/2"Total Adjustment Recessed Escutcheon,as applicable. ***Frame and Deflector only. N/A:Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K-FACTOR SPRINKLERS TFP171 Page 7 of 10 K . FACTOR TYPE NATURAL CHROME LEAD BRASS PLATED POLYESTER PENDENT(TY1231) COATED and 2.8 UPRIGHT(TY1131) 1/2"NPT 175 PSI(12,1 BAR) RECESSED N/A PENDENT(TY1231) PENDENT(TY2231) and 4.2 UPRIGHT(TY2131) 1/2"NPT 175 PSI(12,1 BAR) RECESSED N/A PENDENT(TY2231) PENDENT(TY3231) and 5.6 UPRIGHT(TY3131) 250 PSI(17,2 BAR) 1/2"NPT OR 175 PSI(12,1 BAR) RECESSED (SEE NOTE 1) PENDENT(TY3231) PENDENT(TY4231) and 175 PSI 3/48.$NPT 0 UPRIGHT(TY4131) (12,1 BAR) 175 PSI(12,1 BAR) RECESSED PENDENT(TY4231) N/A g p PENDENT(TY4931) BAR) 175 PSI 1/2" 175 (12,1PSI NPT UPRIGHT(TY4831) (12,1 BAR) NOTES: 1. The maximum working pressure of 250 psi(17,2 bar)only applies to the Listing by Underwriters Laboratories Inc.(UL);the Listing by Under- writers Laboratories,Inc.for use in Canada(C-UL);and,the Approval by the City of New York. TABLE C MAXIMUM WORKING PRESSURE Care and have not operated,should be replaced Care must be exercised to avoid if they cannot be completely cleaned damage to the sprinklers -before, Maintenance by wiping the sprinkler with a cloth or during, and after installation. S by brushing it with a soft bristle brush. klers ams ed bydropping, Sprin- klers TYCO Series TY-FRB must be Care must be exercised to avoid wrench twist/slippage, striking,or the ,mt maintained and serviced in accordance damage to the sprinklers before, be replaced. Al , rrelace any sprin- with this section. during, and after installation. Sprin- kler that has a cracked bulb or that has klers damaged by dropping, striking, lost liquid from its bulb. (Ref. Installa- Before closing a fire protection system wrench twist/slippage,or the like,must main control valve for maintenance tion Section). be replaced. Also, replace any sprin- Initial and frequent visual inspections of work on the fire protection system kler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa- random samples are recommended for that it controls, obtain permission to systems from the proper authoritiesY The corrosion-resistant sprinklers to verify shut down the affected fire protection tion Section.) and notify all personnel who may be the integrity of the corrosion-resistant affected by this action. owner is responsible for the material of construction. Thereafter, inspection,testing,and maintenance of annual inspections per NFPA 25 should Absence of the outer piece of an their fire protection system and devices suffice. in compliance with this document, as Inspections of corrosion-resistant escutcheon, which is used to cover a clearance hole, can delay sprinkler well as with the applicable standards Asso- operation in a fire situation. of the National Fire Protection Asso- sprinklers are recommended at close ciation (e.g., NFPA 25), in addition to range, instead of from the floor level Sprinklers which are found to be the standards of any other authorities sprin- leaking or exhibiting visible signs ofper NFPA. Inspection at close range 9 havingjurisdiction.Contact the install- can bettercondition determine the the exactm integ- corrosion must be replaced. ing cntractor or sprinkler manufac- rity ofhe oand the corrosion-resistant ant material,Automatic sprinklers must never be turer regarding any questions. rity the corrosion-resistant painted, plated, coated, or other- which can be affected by the corrosive wise altered after leaving the factory. Automatic sprinkler systems are rec- conditions present. Modified sprinklers must be replaced. ommaintained to be inspected,qualified tested, Sprinklers that have been exposed to and Service in ba with local corrosive products of combustion,but tion Service s accordanceowith local requirements and/or national codes. TFP171 Page 8 of 10 2-7/8"DIA. 2-7/8"DIA. (73,0 mm) 1/2"(12,7 mm) (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" 5/8±1/4" 1/4"(6,4 mm) (12,7±3,2 mm) 2 1/4"DIA. 1/4"(6,4 mm) (15,9±6,4 mm) 2-1/4"DIA. -1/4 m IA (57,2 mm) / FACE OF MOUNTING / FACE OF MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8 1/8" (3,2 mm) (3,2 mm) G 7,. • 1 _lat__ till MOUNTING Viiiir SURFACE IP MOUNTING . �,I,�� SURFACE iireti�� 1 5/16"(33,3 mm) TY-FRB SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(27,0 mm) CLOSURE 13/16"(20,6 mm) TY-FRB FIGURE 9 FIGURE 8 SERIES TY-FRF RECESSED PENDENT SERIES TY-FRB3/4RECESSEDO PTAL AD DENT ADJUSTMENT WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT WITH TWO-PIECE E10 RECESSED ESCUTCHEONSTYLE 20 RECESSED ESCUTCHEON 2.8 K-FACTOR, 1/2 INCH NPT 2.8 K FACTOR, 1/2 INCH NPT 2-7/8"DIA. . 2-7/8"DIA. (73,0 mm) 1/2"(12,7 mm) (73,0 mm) 3/4"(19,1 mm) 1/2±1/8" 5/8±1/4" 12,7±3,2 mm) 2-1/4"DIA. 2_1/4"DIA. —� 1/4"(6,4 mm) (1559/8±±614/4n 159±64 mm) 1/4"(6,4 mm) / FACE OF (57,2 mm) MOUNTING FACE OF (57'2 mm) MOUNTING PLATE PLATE SPRINKLER SPRINKLER FITTING FITTING 1/8 1/8" / (3,2 mm) I (3,2 mm) a �P �� �TX111j '_ i / ,12 MOUNTING ' f SURFACE . MOUNTING -- SURFACE SERIES 1-1/4"(31,8 mm) 1-1/4"(31,8 mm) CLOSURE CLOSURE SERIES TY-FRB 1"(25,4 mm) TY-FRB 3/4"(19,1 mm) FIGURE 11 FIGURE 10 SERIES TY-FRB RECESSED PENDENT SERIES C 3/4 RECESSED PENDENTAJUST WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT WITH TWO-PIECE TL10CESSINCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON STYLE K RECESSED ESCUTCHEON 4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT TFP171 Page 9 of 10 2-7/8"DIA. 5/8±1/4" (73,0 mm) 0 mm 2 7/8"DIA. 3/4"(19,1 mm) (73, (15,9±6,4 mm) 2_1/4"DIA. 1/4"(6,4 mm) 1/211/8" ) 1/2"(12,7 mm) (12,713,2 mm) 2-1/4"DIA. 1/4"(6,4 mm) FACE OF (57,2 mm) h SPRINKLER MOUNTING / FACE OF (57,2 mm) MOUNTING FITTING PLATE SPRINKLER / FITTING PLATE 1/8" ' (3,2 mm) / 7--; 1/8" (3,2 mm) / i0I. _/,ir MOUNTING ,t' J MOUNTING SURFACE _ ��;_. SURFACE A__,_ CLOSURE SERIES 1-1/4"(31,8 mm) SERIES 1-1/4" 31,8 mm TY-FRB 3/4"(19,1 mm) CLOSURE TY-FRB ( ) FIGURE 12 1"(25,4 mm) SERIES TY-FRB RECESSED PENDENT FIGURE 13 WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT SERIES TY-FRBE1/ INC TOTAL PENDENT STYLE 10 RECESSED ESCUTCHEON WITH TWO-PIECE 2 CE C /NCH TOTAL ADJUSTMENT 5.6 K-FACTOR, 1/2 INCH NPT STYLE 20 RECESSED ESCUTCHEON 5.6 K-FACTOR, 1/2 INCH NPT 2-7/8"DIA. _ 5/811/4" (73,0 mm) 3/4"(19,1 mm) 2-7/8"DIA. (15,9±6,4 mm) 2-1/4"DIA. 1/4"(6,4 mm) 1/2±1/8" (73,0 mm) 1/2"(12,7 mm) / (57,2 mm) (12,7±3,2 mm) �_2-1/4"DIA. 1/4"(6,4 mm) FACE OF MOUNTING / (57,2 mm) SPRINKLER FACE OF PLATE SPRINKLER MOUNTING FITTING PLATE / 1/8" FITTING (3,2 mm) / I 1/8" �''>r;I I - 1/8" (3,2 , 7 4-L---7 TririlL/ \ -/721-7 ��� 1 } U VI MOUNTING � } MOUNTING f SURFACE \. SURFACE CLOSURE SERIES 1-5/16"(33,3 mm) CLOSURE SERIES 1-5/16"(33,3 mm) TY-FRB 13/16"(20,6 mm) TY-FRB FIGURE 14 1-1/16"(27,0 mm) SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB FIGURE 15 WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO-PIECE 1/2 INTOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K-FACTOR,3/4 INCH NPT 8.0 K-FACTOR,3/4 INCH NPT TFP171 Page 10 of 10 P/N 57 - XXX- X- XXX SPRINKLER TE RATINGS RE SIN FINISH 330 2.8K UPRIGHT(1/2"NPT) TY1131 1 NATURAL BRASS 135 135°F(57°C) 331 2.8K PENDENT(1/2"NPT) TY1231 3 PURE WHITE 155 155°F(68°C) (RAL9010)1 340 4.2K UPRIGHT(1/2"NPT) TY2131 4 SIGNAL WHITE 175 175°F(79°C) (RAL9003) 341 4.2K PENDENT(1/2"NPT) TY2231 5 JET BLACK 200 200°F(93°C) POLYESTER(RAL9005)2 370 5.6K UPRIGHT(1/2"NPT) TY3131 7 LEAD COATED 286 286°F(141°C) 371 5.6K PENDENT(1/2"NPT) TY3231 9 CHROME PLATED 390 8.0K UPRIGHT(3/4"NPT) TY4131 NOTES: 1. Eastern Hemisphere sales only. and 8.0K 391 8.0K PENDENT(3/4"NPT) TY4231 2. Available in only 2.8K, °C) and 200°F(93°C);requires lead titimeto mmanufacture. 360 8.0K UPRIGHT(1/2"NPT) TY4831* 361 8.0K PENDENT(1/2"NPT) TY4931` TABLE D SERIES TY-F PAPENDENT AND RT NUMBER SELPRTION IGHT SPRINKLERS Limited Ordering Warranty Procedure For warranty terms and conditions,visit Contact your local distributor for www.tyco-fire.com. availability. When placing an order, indicate the full product name and Part Number(P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB (Specify SIN), (specify K-factor), (specify Pendent or Upright)Sprinkler(specify)temperature rating, (specify)finish or coating, P/N (specify from Table D) Recessed Escutcheon Specify: Style (10, 20, 30, or 40) Recessed Escutcheon with (specify`) finish,P/N(specify*) Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 *Refer to Technical Data Sheet TFP770 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1415-362-0700 Copyright©2015 Tyco Fire Products,LP. All rights reserved. 'NCO TEFLON is trademark of The DuPont Corporation. Fire Protection Products FireLock® V27, K5.6 Models V2709,V2710 ✓ota 4 0.11 0.11 Standard Spray Horizontal and Recessed Horizontal Sidewall Technical Specifications: Standard and Quick Response Models:V2709, V2710 Style: Horizontal Sidewall or Recessed Horizontal Sidewall '—""" � Nominal Orifice Size: W/13 mm K Factor:5.6 Imp./8.1 S.I.1 Nominal Thread Size: W/15 mm V2709/V2710 V2709/V2710 Standard Horizontal Recessed Horizontal Max.Working Pressure: Sidewall Sidewall • 175 psi/1200 kPa (FM) • 250 psi/1725 kPa (UL) Approvals/Listings: Factory Hydrostatic Test: 100% @ 500 psi/3450 kPa e` LDus F^+ LPCBI C 31 Min.Operating Pressure: See Victaulic Publication 10.01 for more details. • 7 psi/48 kPa Temperature Rating:See chart on page 3 Product Description: For K-Factor when pressure is measured in Bar,multiply S.I.units by 10.0. These Model V27, standard spray horizontal sidewall sprinklers are designed for up to ordinary Hazard per NFPA 13, and can be used for standard or recessed installations. The design provides a crescent-shaped water discharge pattern for installation along a wall or under a beam or ceiling. It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, 11 reducing assembly effort. This sprinkler is available in various temperature ratings(see chart on page 3) and finishes to meet many design requirements. The 11// recessed pendent should be utilized with a Model V27 recessed escutcheon which provides up to 3/4719 mm of adjustments. � � NI - r Coverage I '' For coverage area and sprinkler placement, refer to NFPA 13 or applicable standard. Exaggerated for clarity Job/Owner Engineer System No. Spec Section Location _•-_ Paragraph Contractor __■- Approved Submitted By 111111111111111111111111111111111111 Date Date victaulic.com I Sprinklers I FireLock®I K5.6, V27 I Publication 40.11 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. 1 ictcauI c' victaulic.com I Sprinklers I FireLock®I K5.6,V27 I Publication 40.11 Material Specifications: Accessories Horizontal Deflector:Commercial bronze per Installation Wrench: UNS C2200O ❑ Open End:V27 Bulb:Glass with glycerin solution ❑ Recessed:V27-2 Bulb Nominal Diameter: ❑ Standard: 5.0 mm Sprinkler Finishes: ❑✓ Quick Response:3.0 mm El Plain Brass Load Screw: Low Silicon bronze per UNS C65100 ❑ Chrome plated Pip Cap: Low Silicon bronze per UNS C65100 ❑✓ White painted3 Spring: Beryllium nickel ❑ Flat black painted3 Seal:Teflon2 tape ❑ Custom painted3 Frame: Die cast brass 65-30 ❑ Proprietary Nickel/Teflon2 coating3 Lodgement Spring:Stainless steel per UNS S3020O VC-2504 155,200,286 SR Only: ❑ Wax3 For cabinets and other accessories refer to separate sheet. NOTE:Weather resistant recessed escutcheon available upon request. 2 Teflon is a registered trademark of Dupont Co. UL Listed for corrosion resistance. 4 UL Listed and FM Approved for corrosion resistance. 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. \iCtdl IliGP victaulic.com 2 v victau�com I Sprinklers I FireLock®I K5.6, V27 I Publication 40.11 Approvals/Listings: APPROVALS/LISTINGS Orifice Size inches) V2709 V2709 Recessed icz V2710 V2710 Recessed V2710 Recessed Orifice Size mm �,_ Nominal K Factor Imperial ®®-_® Nominal K Factor 5.1.5 alnnlinl IMMEMMINIMININNIMMAMMIIIIMINILIMIIIIIINIMBEIMIIIMMENLAMM "" Standard Standard Quick Quick Quick Deflector Type Horizontal Recessed Recessed Horizontal Horizontal Recessed Sidewall Horizontal Horizontal Sidewall* Sidewall Sidewall(up to Sidewall(up to �----- IT adjustment) 3A"adjustment) 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C 175°F/79°C 155°F/68°C 155°F/68°C 135°F/57°C 135°F/57°C 200°F/93°C 175°F/79°C 175°F/79°C 155°F/68°C i5S°F/68°C 286°F/141°C 200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C 360°F/182°C 286°F/141°C 200°F/93°C 200°F/93°C 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C 175°F/79°C 155°F/68°C 155°F/68°C 135°F/57°C 200°F/93°C 175°F/79°C 175°F/79°C 155°F/68°C 286°F/141°C 200°F/93°C 200°F/93°C 175°F/79°C 360°F/182°C 286°F/141°C 200°F/93°C 135°F/57°C NYC/MEA 6#62-99-E 175°F/79°C 135°F/57°C 155°F/68°C 135°F/57°C 155°F/68°C 135°F/57°C 200°F/93°C 175°F/79°C 175°F/79°C 155°F/68°C 155°F/68°C 286°F/141°C 200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C 360°F/182°C 286°F/141°C 200°F/93°C 200°F/93°C 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C CSFM 6#7690-0531:112 175°F/79°C 155°F/68°C 135°F/57°C 135°F/57°C 200°F/93°C 155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C 155°F/68°C 286°F/141°C 200°F/93°C 200°F/93°C 175°F/79°C 175°F/79°C 360°F/182°C 286°F/141°C 200°F/93°C 200°F/93°C 135°F/57°C LPCB 6104b/01 155°F/68°C 135°F/57°C 6104b/02 175°F/79°C 155°F/68°C 200°F/93°C None 175°F/79°C None None 286°F/141°C 200°F/93°C 360°F/182°C 286°F/141°C 135°F/57°C 155°F/68°C 135°F/57°C 135°F/57°C VNIIPO 175°F/79°C 155°F/68°C 155°F/68°C 135°F/57°C 175°F/79°C 200°F/93°C 175°F/79°C 155°F/68°C 286°F/141°C 200°F/93°C 200°F/93°C 175°F/79°C 360°F/182°C 1.11 286°F/141°C 200°F/93°C ZSTBS 155°F/68°C None1111 None None 5 For K Factor when pressure is measured in Bar,multiply S.I.units by 10.0 6 Light Hazard ONLY Note:Listings and Approvals as of printing.All are approved open. 40.11 2545 Rev.,1 Updated 07/2014 ©2014 Victaulic Company.All rights reserved. victau_IIS 3 ✓ctaulic J victaum I Sprinklers I FireLock®I K5.6,V27 I Publication 40.11 Dimensions: 3"/89 mm 21/4"/57 mm -r— ,fl1I ,e, —,-3, _i___ j Itmm / a-1 Smmy— Q� 1_ 32 mm I ili l.— Standard HSW—V2709,V2710 11/167 17 mm 11/16" 11/16"/ 26mm 43mm 30mm 56 mm (�/ Finished Ceiling y�Iy�jj����II Finished Ceiling 4 12"/102-305mm 4-12/1Pe02-NFPA5 mm 'A Per NFPA 1� J� 2'/51 mm 23/8"/60 mm ----- �,� 2"/51 mm 23/8"/60 mm 215/16"/ iC��, Min Hole Max.Hale '...=--�'1 Y Min.Hole Max.Hole 75 mm ■� AFinished Surfac- I Typical Wall Finished Surface I Typical Wall +i �1 MAXIMUM RECESS MAXIMUM EXTENSION 1"Adjustment Recessed—V2709,V2710(drawing not to scale) 15/16"/ 24 mm 7/16" 5/16' 23/16"/ iii 9/16"/18 mm 37 mm 37 mm �ySb mme/ 'p �,{��I ►�� Finished Ceiling Finished Ceilbg 4-12'/102-305 mm q-12"/102-305 mm I� Per NFPA Per NFPA ■—- ■ No �I 2"/51 mm 23/8'/60 mm �i 2751 mm 23/8760 mm 215/16'/ C�", Min Hole Max Hole IG 1^, Min ole 75 mm . Finished Surface fI�I Finished Surface I�I -.4 4--Typical Wall �} 1« Typical Wall MAXIMUM RECESS MAXIMUM EXTENSION 3,4"Adjustment Recessed—V2709,V2710(drawing not to scale) 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. ✓ctaulid vlCtaU 2m victaulic.com I Sprinklers.l FireLock®I K5.6, V27 I Publication 40.11 Distribution Patterns: Models V2709,V2710 K5.6 Standard Horizontal Sidewall and Recessed Horizontal Sidewall Distribution Patterns-Trajectory t a 3.O m � 1, f ♦ w.� .. t 10' P f 8 ... .. ._ _. �y� , � � 2.4m t •. I ---.- ......,.. �' ._ ._....,..F. 7psi �..�... 6 ..,,_ _.®... .._. } ► i X44 0 48 kPa .. 4 1 r ` ♦' 15 psi �..�,.g E „ h 1 4 ` .. .. ♦ 103 kPa 1.2m 2 1 # 1 r �; s i ♦ 30 psi .�._,.... ..... w ...n..;,... 0,6 m t k f .4.4*. .... 207 kPa .. • t tt 2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26' 0,6m 1,2m 1,8m 2.4m 3.Om 3.7m 4.3m 4.9m 5.5m 6.1 m 6.7m 7.3m 7.9m Models V2709,V2710 K5.6 Standard and Recessed Horizontal Sidewall Distribution Patterns-Plan View 2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26' 28' 0.6m 1.2m 1.8m 2.4m 3.Om 3.7m 4.3m 4.9m 5.5m 6.1 m 6.7m 73m 7.9m 8.5m 0' COOI • ♦ 6 t ♦ 7psi �..�... 1.8 m ._.__ __4 --- t.. 48 kPa , 8' 2.4 m •�'' 15 psi �---- 103 kPa 3.0m i �„�.. ir., _• 30 psi !N 207 kPa 14' •��• 4.9 m --.� x . . _. NOTES: A.Data shown is approximate and can vary due to differences in installation. B.These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers.They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation.Refer to the appropriate NFPA National Fire Code or the Authority Having Jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements.Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings,Approvals and Warranties. 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. ✓ataulie victaulic.com 5 f victaulic.com I Sprinklers I FireLock'I K5.6,V27 I Publication 40.11 Available Wrenches: Ratings: All glass bulbs are rated for temperatures from -67°F V27_2 V27 (-55°C)to those shown in the table below. Recessed Open End Temperature-°F/°C No escutcheon / Maximum With escutcheon i Sprinkler Victaulic Nominal Ambient Glass Temperature Part Temperature Temperature Bulb Classification Identification Rating Allowed Color Ordinary A 135°F/57°C 100°F/38°C Orange Ordinary C 155°F/68°C 100°F/38°C Red Intermediate E 175°F/79°C 150°F/65°C Yellow Intermediate F 200°F/93°C 150°F/65°C Green High 1 286°F/141°C 225°F/107°C Blue Extra High 7 K 360°F/182°C 300°F/149°C Purple - M Open - No Bulb 7 Standard response only. 4t • Always read and understand installation,care,and maintenance instructions,supplied with each box of sprin- klers,before proceeding with installation of any sprinklers. • Always wear safety glasses and foot protection. • Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. • Installation rules,especially those governing obstruction,must be strictly followed. • Painting,plating,or any re-coating of sprinklers(other than that supplied by Victaulic)is not allowed. Failure to follow these instructions could result in serious personal injury and/or property damage. 43 The owner is responsible for maintaining the fire protection system and devices in proper operating condition.For minimum maintenance and inspection requirements,refer to the current National Fire Protection Association pam- phlet that describes care and maintenance of sprinkler systems.In addition,the authority having jurisdiction may have additional maintenance,testing,and inspection requirements that must be followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product,contact Victaulic World Headquarters:P.O.Box 31,Easton,Pennsylvania 18044-0031 USA,Telephone: 9 001-610-559-3300. Note Reference Installation Installation sand(Maintenance Sheet for1the prrodlctaulic uct you areinstalling.ock This installation sheet to be installed inll accco dance with manufactured cur current Vy Victaulic ictaulic installation/assemblyr to Victaulic s 'ons.All instructions.products is included with each shipment of Victaulic products for complete installation and assembly Victaulic Qu pmeneservesthe t porige and changeht to wtngetproducts specifications,designs and standard data,and is available in PDF format on our website at victaulic.com. Trademarks Warrnty Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic is a registered trademark of Victaulic Company. 40.11 2545 Rev.J Updated 07/2014 ©2014 Victaulic Company.All rights reserved. NiCtaUliC victaulic.com 6 FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS 40.47 V27, K4.9 c4Lus Residential Pendent and Recessed Pendent SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS V2740 QUICK RESPONSE This Model V27 residential sprinkler is designed to meet the requirements of NFPA 13, 13D and 13R for residential use in a variety of room sizes,depending upon available operating pressure and room configuration.The design incorporates state-of-the-art,heat responsive, frangible glass bulb design(quick response)for prompt,precise operation. Tig", The die cast frame is more streamlined and attractive than traditional sand cast frames. It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort.This sprinkler is available in various finishes to meet many design requirements. PENDENT (V2740) SPRINKLER OPERATION: The operating mechanism is a frangible glass bulb which contains a heat responsive liquid.During a fire,the ambient temperature rises causing the liquid in the bulb to expand.When the ambient temperature reaches the rated temperature of the sprinkler,the bulb shatters.As a result,the waterway is cleared of all sealing parts and water is discharged towards the deflector.The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire. COVERAGE: Residential spray coverage up to 20 feet x 20 feet/6.1 m x 6.1m room sizes per NFPA. TECHNICAL SPECIFICATIONS: Model:V2740 Style:Pendent and Recessed Pendent ACCESSOR Nominal Orifice Size:%e"/12 mm InstallationWSrench: • W K-Factor:4.9 Imp./7.1 S.I.^for room sizes upto • Recessed:n End:V27 2076.1 m V27-1 Sprinkler Finishes: .��� Nominal Thread Size:W NPT/15mm Max.Working Pressure: 175 psi/1200kPa •• Plain brass Ui 100% Chrome painted**plated \� / Factory Hydrostatic Test: 500 psi/ • White �/® I 4000110 3450kPa • Custom painted** JMin.Operating Pressure:7psi/48kPa For escutcheons,cabinets and other accessories Temperature Rating:See chart on page 3 p g refer to separate sheet. Atit _rill` MATERIAL SPECIFICATIONS A For K-Factor when pressure is measured in Pendent Deflector.Bronze per UNS C51000 Bar,multiply S.I.units by 10.0. Bulb:Glass with glycerin solution *Teflon is a registered trademark of Bulb Nominal Diameter: Dupont Co. i • Quick Response:3.0 mm **UL Listed for corrosion resistance in all Load Screw:Bronze per UNS C65100 configurations. Pip Cap:Bronze per UNS C65100 NOTE:Weather resistant recessed escutcheon �� �� Seal:Teflon*tape available upon request. VO = Frame:Die cast brass 65-30 Exaggerated for clarity JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Location Date Para Approved Date www.victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV_E \ACtaUhe 40.47 1 F 40.47 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE Approved Temperature Ratings APPROVALS/LISTINGS Orifice Nominal Yp Deflector T e °F/C T Model Size K-Factor Response Inches Imperial cUWs mm S•I•n i i,.... _ ._._ _155,us 175 V2740 X12 I 49 Quick 1 Pendent 68,79 c 12 I 71 ...:. . .. .... .....,...,_ .. .s>.,....,,_-.....�.:......,...,.,...». .,....__.� _.i.....� �.., 155 175 1 Recessed Pendent 58 17 V2740 7,1:226 7,9 Quick i Up to 1/2"Adjustment 79 155,175 i Recessed Pendent �� V2740 4.9 i Quick Up to 3"Adjustment# 16558,17795 7.1 *Listings and approval as of printing. A For K-Factor when pressure is measured in Bar,multiply S.I.units by 10.0. *For 12'x 12'to 20'x 20'rooms #For 12'x 12'to 18'x 18'rooms RATINGS All glass bulbs are rated for temperatures from—67°F/-55°C to those shown in table below. Temperature—°F/°C Victaulic Sprinkler Temperature Part Nominal Temperature Maximum Ambient Rating Temperature Allowed Glass Bulb Color_® Identification - -" , Classification -- "' 155 100 ! Red �� Ordinary 1168 I 38 .. .._ 175 150 Yellow ------>" Intermediate I E 79 I 65 ORDERING INFORMATION Please specify the following when ordering: Sprinkler Model Number' •-w Style Temperature Rating K-Factor ,. _. Thread Size Quantity Sprinkler Finish Escutcheon Finish Wrench Model Number ✓ctaulid www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV_E 40.47_2 5 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS �/0■A�{7 V27, K4.9 `F Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE WARNING • Always read and understand installation,care,and maintenance instructions,supplied with each box of sprinklers,before proceeding with installation of any sprinklers. c• •• Always wear safety glasses and foot protection. 1 • Depressurize and drain the piping system before attempting to 1,p- install,remove,or adjust any Victaulic piping products. • Installation rules,especially those governing obstruction,must be strictly followed. • Painting,plating,or any re-coating of sprinklers(other than that 0 Ii supplied by Victaulic)is not allowed. ii Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition.For minimum maintenance and inspection requirements,refer to the current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler ID systems. In addition,the authority having jurisdiction may have addi- tional maintenance,testing,and inspection requirements that must be followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product,contact Victaulic World Headquarters:P.O.Box 31,Easton,Pennsylvania 18044-0031 USA,Telephone:001-610-559-3300. AVAILABLE WRENCHES Sprinkler Type Open End -... Recessed V2740 Pendent V27 ( V27-2 V2740 Recessed Pendent iI — I V27-2 www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY 6 2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REVE iCtaU�iC° 40.47 3 y 40.47 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE DIMENSIONS Standard Pendent—V2740 1..S Frl60 mm1%/ I 41 mm 30 mm Maximum Recess—lh"Adjustment Recessed—V2740(drawing not to scale) 23/60 mm ` Max.Hole 2"/51 mm Min Hole 7aJ/.lu.� —,.,, /—A, Typ�ingTile 30mm �L//I.r jl.IZLII/� Typical Ceiling Tile 17 mm i I` 1 Ne 110) 30 mm . Finihed Surface . Finished Surface y 43 mm 1 MAXIMUM RECESS 2"/""/ 75 mm MAXIMUM EXTENSION Maximum Recess—3/4"Adjustment Recessed—V2740(drawing not to scale) 234"/60 mm _ Max.Hole 2"/51 mm Min.Hole —, 1 1'/�y �ui dr. :111 /app 1 e"/ 1 37 m��i(/�II,r��f111 �I1 ��// A Typical Ceiling Tile 24 mm 8 / MEI trill— / Typical Ceiling Tile y 18 mm � i �/lf/t/ t VT 24 mm Finished Surface yy{6^/ Finished Surface43 mma MAXIMUM RECESS 2'31e/ 75 mm MAXIMUM EXTENSION www.victaulic.com viCtaulid VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV_E 40.47_4 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS V27, K4.9 ssed 40.47 Residential Pendent and RecePendent V2740 QUICK RESPONSE ROOM SIZE Victaulic V2740,4.9 K-Factor Pendent Sprinkler For Ceiling types refer to NFPA 13, 13R or 130 2013 Editions Max. Ordinary Temp Intermediate Temp Coverage Rating Aver�'� 15 Rng°C Rating Deflector to Installation 175`F/79"C Minimum Ceding Type Flaw° Pressure" Flow," Pressure" Spacing Ft.z Ft. GPM PSI m z m L/min GPM -bar bar L/min bar Ft. 12X12 I 13 i7.0 m 3.7 X 3.7 € 49.27.0 9, I 14 X 14 ._�.-._... ....._ 70 0.48 _49.2 � 048 13 I 13 1.. F 4.3X4.3 + q92 ; , 70 i ,#.... 0.48 49.2 i 0.48 —� 16 X 16 g 13 "recessed 4.9X49 492 .4 13 7..4 i a Escutcheon(c) non-recessed 2.0 w-.- I 048 t 49.2 0.48 s 1 Aa to 4 inch or non-recessed 2.4 18X18 x 17 12 17 ° perNFPA13,13R. 5.5X5.5 ` 12 I or13D 643 083 I 643 i 083 20X20 16.7 ) 20 i 16.7 a.._..F_M ._. _ 6.1X6.1 E 75J ._��. 1.15 75.7 1.15 (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)For NFPA 13 residential applications,the greater of 0.1gpm/ft2 over the design area of the flow in accordance with the criteria in the table must be used. (c) For 20 x 20 Coverage Area-%"Maximum Recess www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY®2013 . REV E �CtaUIic, VICTAULIC COMPANY.ALL RIGHTS RESERVED 40.47 5 t 40.47 FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE Model V2740 NOMINAL WETTING PATTERNS K4.9 residential pendent and recessed pendent(3/a") 13 GPM/49.2LPM-16'x16'/4.9x4.9m coverage area �' 5 - s 1 ...- r . ism 1 k'. # ..+.... k. B 6.. 4 ] and o.6m 1 —, r 4',1 am 24m 19m 13m Gam ., r_,,,,. $, 2 12m 03m t OFfiOOM --.._...,..-—�...,..—.,_.... .._:......., Obm Model V2740 1(4.9 residential pendent an 5.5m coverage are d recessed pendent(3k") 17 GPM/64.3 LPM-18'x 18'/5.5 x a 24m.w ....._».. ,.,.. :, T+ $,•' 3 21m,t 6 — .... 1.2m, t }—..y .1 24m i4m 1 Sm 11m d6m I 03m L 2 �1Rm 1� CLOr ROOM. — . _.. ._....._ ... .. aX (161..4_ ,._ See notes on next page. xiCtBUliC. www.victaulic.com REV_E VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.47_6 FIRE PROTECTION P /�RODUCTS—AUTOMATIC SPRINKLERS 0.A 7 V27, K4.9 `'F `f Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE NOMINAL WETTING PATTERNS Model V2740 1(4.9 residential pendent and recessed pendent 04") 20 GPM/75.7 LPM—20'x 2076.1 x 6.1 m coverage area 8' 51 12m ,, ,._,.. 9 itl 30m 14 4 lam 6 14' 0 6 y 24m m .2m Om 03m1 1 12m lam ¢ _ OF'ROOM • NOTES: 1 Data shown is approximate and can vary due to differences in installation. 2 These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock automatic sprinklers.They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation.Refer to the appropriate NFPA National Fire Code or the authority having jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements.Failure to follow these guidelines could adversely affect the perfor- mance of the sprinkler and will void all Listings,Approvals and Warranties. 3 All patterns are symmetrical to the centerline of the waterway. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2013 VICTAULIC COMPANY.ALL RIGHTS REV E RESERVED. ictaulic° 40.47 7 40.47 FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS V27, K4.9 Residential Pendent and Recessed Pendent V2740 QUICK RESPONSE WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com �CtaU�iC* 40.47 4525 REV E UPDATED 04/2013 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2013 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.47 0 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS V27, K5.6 40. 10 UL FM ® LPCB I.,' Standard Spray; Upright, Pendent and Recessed Pendent SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE These Model V27 standard spray sprinklers are designed to produce a hemispherical spray : �� ~ A y pattern for standard commercial applications.They are available with either standard or quick response bulbs.The design incorporates P. state-of-the-art,heat responsive,frangible glass bulb design(standard or quick response)for prompt,precise operation. (1/2703 AND (V27O7 AND The die cast frame is more streamlined and attractive than traditional sand cast UPRIGHT PENDENT RECESSED frames.It is cast with a hex-shaped wrench boss to allow easy tightening from many 2029_ V2708) PENDENT angles,reducing assembly effort.This sprinkler is available in various temperature (1/2707 AND V2708) ratings(see chart on page 2)and finishes to meet many design requirements. The recessed pendent should be utilized with a Model V27 recessed escutcheon which provides up to 9 /19mm of adjustments. SPRINKLER OPERATION The operating mechanism is a frangible glass bulb which contains a heat responsive liquid.During a fire,the ambient temperature rises causing the liquid in the bulb to expand.When the ambient tem- perature reaches the rated temperature of the sprinkler,the bulb shatters.As a result,the waterway is cleared of all sealing parts and water is discharged towards the deflector.The deflector is designed to distribute the water in a pattern that is most effective in controlling the fire. COVERAGE For coverage area and sprinkler placement,refer to NFPA 13 standards. TECHNICAL SPECIFICATIONS Models/S.I.N.:V2703,V2704,V2707,V2708 Style:Pendent,Upright or Recessed Pendent ACCESSORIES (fr)e5 Nominal Orifice Size: 'fj3 mm K-Factor:5.61mp./8.1 S.I.^ Installation Wrench: Nominal Thread Size:W NPT/15mm • Open End:V27 Max.Working Pressure: • Recessed:V27-2 175 psi/1200kPa FM Global Finishes: 250 psi/1725kPa UL • Plain brass Factory Hydrostatic Test: • Chrome plated 100% 500psi/3450kPa • • White painted** U Min.Operating Pressure:7psi/48kPa • Black painted** ' Temperature Rating:See charts on page 2&3. • Custom painted** • Proprietary nickel Teflon*coating** MATERIAL SPECIFICATIONS • For 155,200,and 286°F Standard Response Response Only,wax coated** Upright Deflector:Bronze per UNS C22000 Pendent Deflector:Bronze per UNS C51000 For cabinets and other accessories refer to i Bulb:Glass with glycerin solution. Bulb Nominal Diameter: separate sheet. cp Standard:5.O mm NOTE:Weather resistant recessed escutcheons Quick Response:3.Omm available upon request. Load Screw:Bronze per UNS C65100 ^ For K-Factor when pressure is measured in Pip Cap:Bronze per UNS C65100 Bar,multiply S.I.units by 10.0. Spring:Beryllium nickel * Teflon is a registered trademark of Dupont Co. Exaggerated for clarity Seal:Teflon*tape **UL Listed for corrosion resistance in all Frame:Die cast brass 65-30 Lodgement Spring:Stainless steel per UNS configurations. S30200 JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Location Sppr SectdPara Date Approved Date www.victaulic.corn VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2012ED. REV I ✓ctaulic° VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.10_1 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.10 V27, K5.6 Standard Spray;Upright, Pendent and Recessed Pendent STANDARDMODELS/S.I.N.V2703 AND V2707 RESPONSE MODELS/S.I.N.V2704 AND V27O8 QUICK RES RESPONSE Model V2708 '-07 V2707 V2704 V2708 APPROVALS/LISTINGS v2703 v27o7 1/2" F• r� I 13 .. .t 'Orifice Size finches) ,� iu ,.. r1 .,._3 =• 13 _ ,... 113 _ 13 k 6 13 56 56 T On Size-Anil : ; 56 ,�. z�w � 56 . . 5.6 _ s _ 81 Nominal:. K Factor Imperial ..., .,,.,, ,.°,. ".... 81 8;1 _ � .. ... Quick . 5. I 1 I Qwck Quick , ._ _81 Standard )_ � Nominal K Factor S I � 3�_` Standard F Standard �_-:.._...— � �---� �— Recessed 1 1 Response< ....,.... ,_w"-- -- — I Recessed I I Pendent —- E Upnght Pendent / Deflector ! Upright Pendent ( Pendent __- 1 - Type ... .-�°-� F up to 3/a i up to3 I-'Adjustment ..:a. Model Approved Temperature Ratings F`IC by Agency 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C $ 135°F/57°C 4 135°F/57°C 4 I 155°F/68°C 155°F/68°C I 155°F/68°C I 155°F/68°C : 155°F/68°C 155°F/68°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C i 175°F/79°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C , 200 F/93°C 200°F/93 C UL 286°F/141°C 286°F/141°C 286°F/141°C 286°F/141°C 4 286 F/141°C 360°F/182°C 360 F/182°C i 135 F/57°C 135°F/57°C I 135°F/57°C 135 F/57°C t I 135°F/57°C 135°F/57°C 155°F/68°C I 155°F/68°C 155°F/68°C 155°F/68°C I 155°F/68°C 1 155°F/68°C 175°F/79°C 175°F/79°C 175°F/79°C 4 175°F/79°C I 175°F/79°C 175°F/79°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C ULC r 200°F/93°C £ 286°F/141°C 200°F/93°C 286°F/141°C 286°F/141°C v 286 F/141°C 286°F/141 C ; I 360 F/182°C 360 F/182°C I 135°F/57°C ° 57°C 135°F/57°C 135°F/57°C 135°F/57°C I 135°F/57°C 135°F/57°C I 155°F/68°C € 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C k 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 200°F/93°C I 200°F/93°C 200°F/93°C 200°F/93°C I 200°F/93°C I FM# 286°F/141°C 200°F/93°C 286°F/141°C 286°F/141°C 286°F/141 C I 360°F/182°C } 360°F/182°C F/57°C E I =„w w,. 135°F/57°C ( 1 135°F/57 C 135° 135 F/57°C i a 135°F/57 C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 175°F/79°C 175°F/79°C I 175°F/79°C ' ` 175°F/79°C I 175°F/79°C 175°F/79 C 200°F/93°C y NYC/MEA#62.99-E ” 200°F/93 C 200°F/93°C 200°F/93°C I 200°F/93°C 1 200°F/93°C 286°F/141°C 286 F/141°C s 286°F/141°C I 286 F/141 C I 286°F/141 C ° 1 360 F/182°C 360 F/182 C ,uv..., __M._ 35'Ff 135°F/57°C , 135°F/57°C i 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C t 155°F/68°C 155°F/68°C ! 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 175T/79°C 17S°F/79°C i 175°F/79°C I 175°F/79°C i 175*F/79°C 175°F/79°C 175°F/9°C 200°F/93°C € 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C CSFM:#7690.0531:112 286°F/141°C E 286°F/141°C 286°F/141°C s I 1 286°F/141°C 286 F/141 C r 360°F/182°C 360F/182°C—._.,..., t__..., 135°F/57°C r 135°F/57°C I 1 s 1 155°F/68°C 135°F/57°C `I 155°F/68°C ' 135°F/57°C 1 s 175°F/79°C None None ;. 3 175°F/79°C 175°F/79°C 175°F/79°C ! ` I 200°F/93°C I LPCB 3 200°F/93°C 200°F/93°C 200°F/93°C 286 F/141°C 286°F/141°C s 360°F/182°C 135°F/ 1135°F/57°C 135°F/57°C 135°F/57°C i 135.F/57.c y 1350F/57.c 135°F/57°C ' r 155°F/68°C 155°F/68°C 155°F/68°C 135°F/58°C I 175°F/79°C 155°F/68°C 175°F/79°C 175°F/79°C { 175°F/79°C 175°F/79°C 175°F/79°C i 200°F/93°C 175°F/79°C 200°F/93°C VNIIPO 200°F/93°C 200°F/93°C 200°F/93°C t. 286°F/141°C I 286°F/141°C 200°F/93°C 286°F/141°C I 286°F/141 C ° I 360°F/182 C 360 F/182°C ,._..�,.._.. "..... ..........__.. I 1. ¢ _m K-ZSTZ I K-ZSTX ZSTZ ZSTX 155°F/68°C 155°F/68 C None 1 , 155°F/68°C I 155°F/68°C None 200°F/93°C b 200°F/93 C CCC 200°F/93°C 200°F/93°C 1 k 1 I _m,a .v.wm_ww #Listings and Approvals as of printing.All are approved open,except for areas designated'No'. in Bar,multipy 5 FK Factor when with pressure1/2 adjustment es c tcheon only I quilck re10.0 sponse 8 FM App ✓ctaulad IS A E www.victRcom REV_I VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ao.io_2 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS V27, K5.6 40.10 Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE RATINGS All glass bulbs are rated for temperatures from-67°F/-55°C to those shown in table below. Temperature-°F/°C Sprinkler Temperature Victaulic Clasempen Identification RatingPart Nominal Temperature Maximum Ambient Temperature Allowed Glass Bulb Color Ordinary y A 135 € 100 ." I 57 __. r 38 ! Orange Ordinary' m C I 155 100 68 t 38 Red Intermediate E i 175 150 79 Yellow ... 65 Intermediate F 200 150 High ,_k.n 93 65 Green J 286 £....._..... 225— 141 I 107 I Blue Extra High* K 360 ; 300 u 182 ti ... - ,- _.., — Purple # t v M Open #Standard response only. a No Bulb All are approved open,except for areas designated"No'. —150/65 if wax coated. ORDERING INFORMATION Please specify the following when ordering: Sprinkler Model Number Style Temperature Rating _ n ,_. K-Factor �.u.v _, Thread Size Quantity Sprinkler Finish Escutcheon Finish "'"" " Wrench Model Number www.victaulic.corrl VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY. RESERVED. REV ( �CtaUIiC° 0 2012 VICTAULIC COMPANY.ALL RIGHTS 40.10_3 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.10 V27, K5.6 Standard Spray; Upright, Pendent and Recessed Pendent STANDARDMODELS/S.I.N.V2703 AND V2707 RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE WARNING • Always read and understand installation,care,and maintenance instructions,supplied with each box of sprinklers,before proceeding 4 with installation of any sprinklers. • Always wear safety glasses and foot protection. • Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. • Installation rules,especially those governing obstruction,must be strictly followed. • Painting,plating,or any re-coating of sprinklers(other than that sup- () plied by Victaulic)is not allowed. Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition.For minimum maintenance and inspection requirements,refer to the current National Fire Protection Association document NFPA 25 that describes care andmaintena0 nce may of sprinkler systems.In addition,the authority having jurisdiction have additional maintenance,testing,and inspection requirements that must be followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product,contact Victaulic World Headquarters:P.O.Box 31,Easton,Pennsylvania 18044-0031 USA,Telephone:001-610-559-3300. Standard Upright—V2703,V2704 Standard Pendent—V2707,V2708 1 x/ DIMENSIONS 31 mm 111111 23/4^/ 1�/a/60 mm 41mm1 "/ Iiiiil 2W/ 1�'�I41 mm 60 mm `m�r Limmt III 1"/ 25 mm L___- 1/2"Adjustment Recessed—V2707,V2708(drawing not to scale) 2Max.0 mm Maz.Hole 2"/51 mm Mm.Hole '���tr.:al 30 m 'Re/ -yyOjangelic Typical I/l/LI�/.�Yti$�ti/�iLfI1/� 17m _J�//�ll: =ll� t tom^/ -� 1 30•m PSe/ �:�� Finished Surface Mi 43 mm — — MAXIMUM RECESS 21W/ 75 mm MAXIMUM EXTENSION VICt� www.v V CTA LIC IS Gom REV_I VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2012 VICTAULIC COMPANY.ALL RIGHTS RESERV 40.10_4 • FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS V27, K5.6 40.10 Standard Spray; Upright, Pendent and Recessed Pendent MODELS/S.I.N.V2703 AND V2707 STANDARD RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE DIMENSIONS 3/4"Adjustment Recessed—V2707,V2708(drawing not to scale) 2W/60 mm Max.Hole 2751 mm Min.Hole 24 mm '15.% aro llF i1-� 18 mm �� rn ///yyy ® - �Z F - Typical Ceiling The ro. I /� 1 / Finished Surface " %/ `�!� �.� 24 mm MAXIMUM RECESS --- Tile/ 75 mm MAXIMUM EXTENSION AVAILABLE WRENCHES Spunkier Type V27-2 Recessed V2707,V2708 Pendent V27 Open End F yes yes V2707,V2708 Recessed Pendent 1 yes V2703,V2704 Uprighti yes yes DISTRIBUTION PATTERNS Models/S.I.N.V2707,V2708 K5.6 standard pendent and recessed pendent distribution patterns—trajectory DI 10,FI, •.4%, i i I ` e 1 I k • %y i•♦♦ i I ...., i • s i ♦ s• € I 7 t , i 2' 0.6m _, _. ' K w i ♦ 1 `F ♦ I 4 ♦♦ L I ( i • `.... ...�.. ♦i.. .. „ 6' 8' �,..,.. .,�_f.,1. 0.6m 1.2m 1.8m 2.4m 70 3 .Om 3.77 3 m 7psi 1=M1•1•11=1•••• 4.3m 48 kPa IS psi 103 kPa 30 psi ....... 207 kPa See notes on next page. www.victaulic.corn VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANYALL RIGHTS RESERVED. REV I �Cta ulic° ©2012 VICTAULIC COMPANY. 40.10_5 FIRE PROTECTION PRODUCTS- 40.10 AUTOMATIC SPRINKLERS .. V27, K5.6 Standard Spray;Upright,Pendent and Recessed Pendent STANDARDMODELS/S.I.N.V2703 AND V2707 RESPONSE MODELS/S.I.N.V2704 AND V2708 QUICK RESPONSE DISTRIBUTION PATTERNS ModeIs/S.I.N.V2703,V2704 K5.6 standard upright distribution patterns—trajectory 10' t 2.4m r k I P �:' t ;. _ y a _.. .ami .. f k ••{ �1 +�•� i s 6 }r._.. . ..., I t.;• , ,' ••• i i I, 1.Sm kt E 2' ji 4 I S • .--x_ 14' 2' . .._...�4 6' 8' 10 12' 3.7m4.3m49m 2.4m 3.0m 1.2m 1.8m 0.6m ��� �� 30 psi "-- „�... 15 psi 7 psi 103 kPa 207 kPa 48 kPa NOTES: 1 Data shown is approximate and can vary due to differences in installation. for 2 These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns guidancpe inthese lavoidinglobst obstructions to sprisprinklers. should not be used as minimum isprinkler spacing al Fire Code or the rity avinurisdiction for installation. Refer information appropriatee onegarding obstrruc ion ,spacing m t tons and area h g j of coverage requirements.Failure to follow theseApprovals uidoevianduWarrantiesly affect the perfor- mance of the sprinkler and will void all Listings, pp als 3 All patterns are symmetrical to the centerline of the waterway. Refer to the Warranty section of the current Price List or contact Victaulic for details. WARRANTY This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be NOTE installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com �Ct_all�rC' 40.10 2544IS REGI UPDATED 04/R012 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.10 o FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS V36, K5.6 40.64 UL FM g Dry Type Standard Spray, Light Hazard LISTED Horizontal Sidewall and Recessed Horizontal Sidewall sr —400 T V3609 STANDARD RESPONSE V3610 QUICK RESPONSE ,;� I�_ ' FLUSH HORIZONTAL SIDEWALL DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL f *E. - il EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL The V36 dry Sprinkler is used in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary horizontal pipe nipples. The Model V36 Dry Type Horizontal Sidewall Sprinkler utilizes a frangible glass bulb.At the bulb's rated temperature,the sprinkler opens releasing the bulb seat assembly,causing the inner tube assembly to move,allowing the spring assembly to pivot alongside the inner tube.At this time,water flows through the sprinkler and is distributed by the deflector,in an approved discharge pattern. The heart of the Model V36 sprinkler's proven actuating assembly is a hermetically sealed frangible glass bulb that contains a precisely measured amount of fluid.When heat is absorbed,the liquid within the bulb expands increasing the internal pressure.At the prescribed temperature the internal pressure within the bulb exceeds the strength of the glass causing the glass to shatter.This results in water discharge which is distributed in an approved pattern. COVERAGE: For coverage area and sprinkler placement,refer to NFPA 13 standards. JOB OWNER CONTRACTOR System No. ENGINEER Submitted By Location Spec Sect Para Date Approved Date www.victaulic.corrm VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.m 2009D. REV I \ICtauliic° VICTAULIC COMPANY.ALL RIGHTS RESERVE 40.64_1 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.64 ® FM C V36} K5.6 LISPED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and . ,,It 1. Recessed Horizontal Sidewall 1+ ;, V3609 STANDARD RESPONSE V3610 QUICK RESPONSE ' DRY RECESSED DRY SLEEVE&SKIRT FLUSH HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL TECHNICAL SPECIFICATIONS: I HN I i no ter--- ifiira//Yy�E_ wl E11i-----m7el trr✓mviY�f07/�/�Y�S/�YyiY�/yIliAM III I Exaggerated for clarity Models:V3610 and Vwall ACCESSORIES Installation Wrench:Model V36 Open End and Style:HorizontalSidewall and Recessed Recessed Wrenches fit all V36 Series frames. Horizontal Sidewall Finishes: Nominal Orifice Size:'h'y13mm Plain• Orifice Insert:Stainless steel per UNS S30300 • Chromebrass plated A K-Factor:5.6 Imp./8,1 S.I.A • Whe a ° Nominal Thread Size:1"NPT/33.7 mm • n i Flat black papated° Max.Working Pressure:175 psi/1200 kPa • Custom painted d Factory Hydrostatic Test:100%@ 500 psi/ • Wax° 3450kPa ••• Proprietary Nickel Teflon*Coated° Mem Operating Rating:Pressure:cart on pagePa For cabinets and other accessories refer to Temperature See chart on 3. separate sheet. MATERIAL SPECIFICATIONS A For K-Factor when pressure is measured in Deflector:Brass per UNS C22000 or Stainless Bar,multiply S.I.units by 10.0. Steel per NS S30400 " Teflon is a° UL Listed forgcoro cored rdemark of rosion inn allll con-Co. Bulb:Glasss with glycerin solution • Standard:5.0mm figurations. • Quick Response:3.0mm NOTES: Split Spacer:Stainless steel per UNS S30300 1.Weather resistant escutcheon available upon Load Screw:Brass per UNS C36000 request. Pip Cap:Stainless steel per UNS S30300 2.Only the Plain Brass and Nickel Teflon Spring Seal Assembly:Teflon*coated Beryllium finishes are FM approved. nickel alloy and Stainless steel per UNS S30300 Frame:Die cast brass Outer Tube:Galvanized steel pipe Inner Tube:Stainless steel per UNS S30400 Escutcheon:1010-1018 mild steel and Stainless Steel Torsion Spring:Stainless Steel Wire ✓ctaulid www.victaulic.comISA EREV_I VICTAULIC ISA REGISTERED TRADEMARK of VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.64_2 FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS V36, K5.6 40.64 0 FM g e Dry Type Standard Spray, Light Hazard LISTED Horizontal Sidewall and Recessed Horizontal Sidewall V3609 STANDARD RESPONSE ` V3610 QUICK RESPONSE '.1r; ' k I FLUSH HORIZONTAL SIDEWALL DRY RECESSED HORIZONTAL SIDEWALL DRYSLEEVE&SKIRT HORIZONTAL SIDEWALL %- *ItE,„ EXTENDED HORIZONTAL SIDEWALLPLAIN APPROVALS/LISTINGS HORIZONTAL SIDEWALL Orifice Nominal Approved Temperature Ratings Model Size K-Factor Response Deflector Type Inches Imperial Standard Fi°C# mm S.L^ or Quick V3610 i 56 ry' UL`.:. C-UL* FM 13 g 1 Quick Horizontal Sidewall 1135,155,200,286 135,155,200,2861 135,155,200,286 I 5Z 68 93,141 57 68,93,141_ V36i0 � f 56 � � -----a� '_ 57,68 93,141 13 5.1 Quick ,Recessed Horizontal 1135 155,200:286,135,155,200 286 135,155,200 V3609. 1 ry ( 5 6 _ Sidewall 57,68,93,141 57,68 93,141 57,68,93 Standard F Horizontal Sidewall 135,155,200,286 i 135,155,200,286,135,155,200,286 11 , 57 68,93, w - 141 p 57.68 93 141 E 57 68,93,141 V3609' 'l 5.6 " t Recessed Horizontal?135,155,200,286;135,155,200,286, 135,155,200 13 8.1 s Standard Sidewall f Listings and approval i 57,68,93,141 , 57,68,93,141 57,68,93 as of printing. A For K Factor when pressure is measured in Bar,multiply S.I.units by 10. *Light Hazard Only-Listed for light hazard only with deflector from 4"-12"below the ceiling. **Approved for V3609 and V3610 up to 48"length. RATINGS All glass bulbs are rated for temperatures from-67°F/-55°C to those shown in table below. IIIIIIIIMMIZONEEMENE Sprinkler Temperature Nominal Temperature Maximum Ambient Classification Rating Temperature Allowed Glass Bulb Color Ordinary 135/155 100 57/68 38 i Orange/Red Intermediate 200 15� "" 93 65 s Green High 286 p 225 Blue 141 107 p www.victaulic.Com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. RESERVED. REV I ®2009 VICTAULIC COMPANY.ALL RIGHTS �CtaUlie 40.64_3 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.64 ® FM C V36' K5.6 LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall and l,' I Recessed Horizontal Sidewall 4 �� V3609 STANDARD RESPONSE DRY SLEEVE&SKIRT V3610 QUICK RESPONSE FLUSH DRY RECESSED HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL • EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL ORDERING INFORMATION Please specify the following when ordering: Sprinkler Model Number Style ..._. ...n_ ____.. Temperature Rating KFactor _—. — ..... Quantity ,___ M..._.,_.. Sprinkler Finish """ ...,m—" Escutcheon Style "A Dimension—Distance from face of fitting to the finished ceiling line regardless of escutcheon used. AVAILABLE WRENCHES Model V36 Open End and Recessed Wrenches fit all V36 Series frames. 'Eel.. V'Ct® IS A E www.victRcom REV_I VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.64_4 FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS V36, K5.6 40.64 t <> co Dry Type Standard Spray, Light Hazard Horizontal Sidewall and LISTED Recessed Horizontal Sidewall V3609 STANDARD RESPONSE V3610 QUICK RESPONSE i . ' 1 �° + z- FLUSH L�2 HORIZONTAL SIDEWALL DRY RECESSED HORIZONTAL SIDEWALL DRY SLEEVE&SKIRT 0•I .NiL SI, WA L itillE,i4 _ _ EXTENDED HORIZONTAL HORIZONTALI S DEWgLL SIDEWALL • Always read and understand installation,care,and maintenance instructions,supplied with each box of sprinklers,before proceeding with installation of any sprinklers. c • Always wear safety glasses and foot protection. • Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. lk • Installation rules,especially those governing obstruction,must be strictly followed. 0 • Painting,plating,or any re-coating of sprinklers(other than that sup- plied by Victaulic)is not allowed. Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition.For minimum maintenance and inspection requirements,refer to the current National Fire Protection 9 Association pamphlet that describes care and maintenance of sprinkler systems.In addition,the authority having jurisdiction may have addi- tional maintenance,testing,and inspection requirements that must be followed. If you need additional copies of this publication,or if you have any questions about the safe installation of this product,contact Victaulic World Headquarters:P.O.Box 31,Easton,Pennsylvania 18044-0031 USA,Telephone:001-610-559-3300. www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV I auli V'Ct_ C ® 40.64_5 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.64 UL FM C LUTED V36, K5.6 Dry Type Standard Spray,Light Hazard Ia k-.4' ...r Horizontal Horizontal Sidewall and " Recessed Horizontal Sidewall s, V3609 STANDARD RESPONSE DRY RECESSED DRY SLEEVE&SKIRT V3610 QUICK RESPONSE FLUSH HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL , ' le - .es-4 .. . ,.-- - , ,,„,, . HORIZONTAL SIDEWALL PLAIN EXTENDED HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL er,which exends into er from a piping system, NOTE:The to account of a ceilinglthi thickness off the freezers.See IMPORTANTt mustINSTALLATION DIMENSIONSmust take In INFORMATION later in this document. u. A •—•'•—•—•—• V (Min.1'W) ' � Twa Piece EscNcheon _ rT ]„�A t _.� 1'"PT "LI—I-�1 4. �_� 3'/' [..—..)-1—• ��' I ��I —II!w� Dm • [--(..J 1%'Min.Dia. J _utlrs 3'Dla. ale wrier size tlolelnWall [:—.-J 1`h'Mln.Dla_ / Ta with sa Hole in Wall sprinkler thread size Tee IMPORT NT INlet TA / See IMPORTANT INSTALLATION 4x'Max. as sprinkler thread size Z'h See IMPORTANT INSTALLATION INFORMATION later in this document. INFORMATION Inter in this document ,. ,' Flush Sleeve (Mni.1W) -- 1'NPT I - i==1101 �I Tee with same outlet size ties 25/e"ewl as sprinkler thread size See IMPORTANT INSTALLATION INFORMATION later in this document. Plain Bartel (Ming (MM,Y.9 l•NPT Wall Cup ,14'MIn.DIa. Collar \ Hole in Wall ` I <L.f 1 �lyligtr Do I r{ Ilk=�1111111111DIa. r\V� I •NrI isl.l ---. Hole In Wall Tee snh IMPORTANT etsi Two Piece F 2.Min Dia prinlderfiread size \ Escutcheon Tee wMisar^e outlet size ILA'Min See IMPORTANT a sprinklerthreadST 2W Max. INSTALLATION ize See IMPORTANT INSTALLATION INFORMATION later In 4'MIn. INFORMATION later in this document. N. this document ^p SW Max. (MIn1V0 Recessed Extended DEFLECTO CONFIGURAT ONS / 05 MM SHOWN ABOVE. V1Ct� Www.victIS A R com REV_I VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVE . 40.64_6 FIRE PROTECTION PRODUCTS-AUTOMATIC SPRINKLERS V36, K5.6 40.64 UL FM CO Dry Type Standard Spray, Light Hazard LISTED Horizontal Sidewall and Recessed Horizontal Sidewall V3609 STANDARD RESPONSE I V3610 QUICK RESPONSE FLUSH DRY RECESSEDSL HORIZONTAL SIDEWALL HORIZONTAL SIDEWALLDEWALL HORI SIDEWALL Ar` AT 1011E, EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS MODELS V3610,V3609 HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS-TRAJECTORY 1114- t 2.4m •`� T• I • a 1 • *i 2' AP I i t • t t •I s P. £ L ` a ' .. 0.6 m 1.2 m 1.8 m 2.4 m 3.0 m 3.7 4.3 m 4.9 m 5.5 m 6.1 m 6.7 m 7.3 m 7.9 m 7siP —•• 15 psi �� 30 psi 48103 kPa 207 kPa MODELS V3610,V3609 HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL DISTRIBUTION PATTERNS-PLAN VIEW 2' 4 6' 8' 10' 12 14' 16' 18' 20' 22' 24' 26' 28' 06m 1.2m 1.8m 24m 30m 37m 4.3m 4.9m Sym 61m 6.7m 73m 7.9m 85m 4 . I 1 �_ 1.2m ♦F • 6' € 1.8mw. „..-.. �; ♦I €N € 2.4m € ►•_ ..._ • 10' € �i••f 3.0m ,; I ., . .- •oo .40 i •0- 14' € i • 7si —••—•• 15 psi �� 30 psi 48103 kPa 20kPa See notes on last page. www.victaulic.coru VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANYVICTAULIC COMPANY.ALL RIGHTS RESERVED .®2009 VICTA . REV 1 xiCtaulie 40.64_7 I FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.64 ® FM C 0 V36, K5.6 LISTED Dry Type Standard Spray, Light Hazard Horizontal Sidewall andI Recessed Horizontal Sidewall { '` V3609 STANDARD RESPONSE V3610 QUICK RESPONSE DRY RECESSED DRY SLEEVE&SKIRT HORIZONTAL SIDEWALL FLUSH HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL IMPORTANT INSTALLATION INFORMATION For detailed installation instructions,see publication 1-40. No. 1 Victaulic Model V36 Series Dry sprinklers should be installed in accordance with NFPA 13.These sprinklers are to be installed using a pipe wrench applied to the outer tube. When this is not possible,the proper sprinkler wrench may be used with extreme care for lengths up to approximately 18".Excessive force may distort the frame thus destroying the unit. No.2 Dry sprinklers MUST be installed only into the outlet of a cast or malleable iron tee. No.3 DO NOT install dry sprinklers into any couplings or threaded elbows.In addition,DO NOT install dry sprinklers into any fitting that interferes with thread penetration.NOTE:The end seal of the dry sprinkler MUST NOT bottom out in the fitting. NOTE:The"A"dimension of a dry sprinkler,which extends into a �� freezer from a wet piping system,must take into account the wall or End seal ,�� HEATED SPACE _ ceiling thickness of the freezer.The minimum length of the dry sprinkler J�/" should not be less than the lengths specified in the following table,plus ��i �i the thickness of the freezer's wall or ceiling("A"_"C"+"V). Refer to the drawing for a representation of the"A"dimension.DO NOT 'C°Exposed Minimum Barrel type of fescutcheis sepcted.S ace the attempt to modify dry sprinklers,since they are manufactured to this Length(Refer to Table) Diameteofhole is selected.Space must be sealed to prevent condensation from see Ne specific"A°dimension. forming,per NFPA requirements. The following table is used when the ambient temperature is maintained between 40°F/4°C and 60°F/16°C around the wet piping system. EXPOSED BARREL AMBIENT TEMPERATURE(°F/°C) ot 1 I Insulation Exposed Minimum Barrel Length Ambient Temperature inches/mm .0. Exposed to Discharge End of Sprinkler 40°F/4"C 50"F/10°C 60'F/16°C °F/°C 40 0 0 0 Wall or Ceiling of Freezer ; 30 0 0 i 0 0 ., 0 0 1 v _ ( 0 20 I 4 I 0 102 I 0 i 0 .w,,., ,....� Ir i �/ COLD SPACE 10I 8 -12 � 203 r 25 0 _... ., ,.. 12 � .�_.I .®. 3 1.. Exaggerated for Clariry -18 I 305 ( 76 L0.__.w.,- ..,..._..._....".. 35.6 ' 4 1 TYPICAL SLEEVE AND SKIRT CONFIGURATION FOR EXAMPLE ONLY -10 I 14 102 25 -20 6 3 14 s 152 I 76 356 -29 S _..u..., .T.. _ -30 i 16 I 84 102 _34 406 203 i -40 18 i 8 -40 1 457 I . 203 102 _50 508 20 254 L 6 I 152 -46 ¢ 6 -60 20 10 51 ' 508 254 152 NOTE:Exposed minimum barrel lengths are inclusive up to 30-mph/48-kph wind velocities ✓ctaulid www.victauliC.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.©2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. REV_I 40.64_8 FIRE PROTECTION PRODUCTS—AUTOMATIC SPRINKLERS 40.64 V36, K5.6 ® FM c Dry Type Standard Spray, Light Hazard LISTED Horizontal Sidewall and Recessed Horizontal Sidewall V3609 STANDARD RESPONSE i '! thA 1. V3610 QUICK RESPONSE i4. ' ` � FLUSH DRY RECESSED &SKIRT HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL DRYSLEEVE HORIZONTAL SIDEWALL 110:1E . L EXTENDED PLAIN HORIZONTAL SIDEWALL HORIZONTAL SIDEWALL NOTES 1 Data shown is approximate and can vary due to differences in installation. 2 These graphs illustrate approximate trajectories,floor-wetting,and wall-wetting patterns for these specific Victaulic FireLock automatic sprinklers.They are provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprin- kler spacing rules for installation.Refer to the appropriate NFPA National Fire Code and the Authority Having Jurisdiction for specific information regarding obstructions,spacing limitations and area of coverage requirements.Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings,Approvals and Warranties. 3 All patterns are symmetrical to the centerline of the waterway. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. US&WORLD HEADQUARTERS CANADA P.O.Box 31 CENTRAL AND SOUTH AMERICA 905-884-7444 Easton,PA 18044-0031 USA 905-884-9774(fax) 1-610-559-3600 viccanada�victaulic.com 1-610-559-3608(fax) 4901 Kesslersville Road vital@victaulic.com Easton,PA 18040 USA 1-800-PICK-VIC(1-800-742-5842) EUROPE ASIA PACIFIC 1-610-559-3300 32-9-381-15-00 86-21-54253300 1-610-250-8817(fax) 32-9-380-44-38(fax) 86-21-54253671 (fax) pickvic@victaulic.com viceuro@victaulic.be vicap@victaulic.com www.victaulic.com UNITED KINGDOM MIDDLE EAST 44(0)1438310690 971-4-883-88-70 44(0)1438310699(fax) 971-4-883-88-60(fax) viceuro@victaulic.be UPDATED 12/2009 40.64 3127 REV I VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 40.64 iCta'IUliGJ' Bulletin 016 Rev.E Model DH56 HSW c -—--—-—1---nIIS 4O Model DH56 HSW Recessed Model DH56 HSW Concealed a) Quick Response, IIIMININIM ililliMINILIIIIIIIIIIII Extended Coverage Dry Sprinklers m For coverages up to 28 feet wide and 10 feet long'). 250 psi (17,2 bar) rated. _ Features: �, ,,„ - ' 1. Coverage for long and narrow spaces such as hall- ways, corridors, decks and rooms up to 28 feet wide and 10 feet long.(' 2. Deflector to ceiling dimensions are: DH56 HSW 4"(102mm)min.to 12"(305mm)max. 3. Minimum spacing between sprinklers 13 feet(4m).(1 4. Polyester Coated Corrosion Resistant Sprinklers(cULus) Vi 5. UL Listed for extended coverage, light hazard appli- iiiiiii/(1i cations. '° 6. 5.6 K Factor. 7. Sprinkler is approved for 250 psi(17,2 bar)applications. 8. Quick response performance. t' 9. 1/2" (13mm)adjustment of escutcheon and cover. Viii. , 10.Concealed cover plate can prevent the sprinkler from being used for unintended purposes. No exposed DH56 HSW FP Recessed thermal element with the concealed version. 11.Push-on/thread-off sturdy convenient escutcheon for recessed and cover for concealed. 12.Factory assembled sprinkler&cup, shipped complete with bulb protector for concealed and FP recessed ver- sions. 13.Sprinkler&cup assembly and escutcheon or cover are separately packaged. 14.Cover finishes available in standard white paint, spe- cial bronze, black paint or flat white paint. DH56 HSW Concealed with SWC coverplate (1)See Fig. 7. Approval Organizations a fire the rising ambient temperature melts the solder and 1. Listed by Underwriters Laboratories Inc. and the cover plate is ejected away by springs exposing the UL certified for Canada(cULus) 3mm frangible glass bulb. The use of a 3mm bulb allows 2. NYC MEA 258-93-E quick response which enables the sprinkler to apply water to a fire sooner than standard response sprinklers of the Products Description same temperature rating. The Model DH56 are quick response extended coverage Model DH56 dry sprinklers are intended for use in dry sidewall dry sprinklers for use in light hazard applications. and preaction systems to protect areas subjected to freez- The Model DH56 dry sprinkler with SWC cover plate is a ing temperatures and unheated portions inside buildings. concealed sprinkler that uses Reliable's push on/thread off See Fig. 1 for guidelines on using dry sprinklers in wet sidewall cover.This sprinkler has the cup factory mounted systems. and is shipped with a bulb protector that protects the 3mm Environments wherein dry sprinklers are employed can frangible glass bulb during shipping and post installation be corrosive. For this reason, Model DH56 dry sprinklers finishing operations. The DH56 can be combined in the have a special wax fillet placed in the gap between the field with the FP or F2 Escutcheon to make a recessed cup that supports the bulb and the wrenching boss. This dry sprinkler. The SWC cover plate, FP and F2 recessed wax will not interfere with the operation of the sprinkler,and escutcheons have 1/2" adjustment. The SWC cover plate it prevents contaminants from entering the internal portion is attached with 135 & 165 degree solder. In the event of of the drop nipple. The wax must not be removed. The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application DH56 HSW Concealed with SWC Cover Plate The Model DH56 is a horizontal sidewall dry sprinkler To install the DH56 HSW dry sprinkler with the SWC intended for installation in light hazard occupancies in ac- coverplate as a concealed sprinkler, cut a 21/8" diam- cordance with NFPA 13. These sprinklers are designed to eter hole into the wall as shown in Fig. 6. Temporari- provide fire protection in long and narrow spaces such as ly remove the plastic protective cap, and then use the hallways, corridors, decks and rooms up to 28 feet (8,5m) Model XLO2 wrench (see Fig. 2) to tighten the sprinkler wide and 10 feet(3m)long. They are rated for 250 psi(17,2 until it is secured in the sprinkler fitting. Note:The Model bar) and can be mounted between 4 and 12 inches (102 XLO2 wrench has a notch in it to accommodate the de- and 305mm)down from the ceiling. flector top. This wrench can only be inserted one way. Care must be taken not to damage the deflector during General Installation Instructions tightening.Apply a Teflon**based sealant to the sprinkler Model DH56 dry sprinklers must be installed only in Stan threads before installing in the sprinkler. Wrench only on dard (ANSI B 16.3 class 150 and ANSI B 16.4 class 125) the square boss. DO NOT WRENCH ON ANY OTHER pipe tees in the horizontal position,even at branch line ends. PART OF THE SPRINKLER. It is recommended that the They should not be installed into elbows or pipe couplings located on drop nipples to the sprinklers. For these and sprinkler be protected during plastering and painting op- erations by reinstalling the plastic protective cap. Instal- other fittings including CPVC, the dry sprinkler should be installed into a fitting to allow protrusion into the fitting in ac- lation is completed by removing the protective cap and inserting the coverplate. coverplate assemblies provide cordance with the diagrams. The "A"dimension of the dry sprinkler, which extends into a freezing zone from wet pipe 1/2" (13mm) of adjustment. Final adjustment is made by systems, should be selected to provide,as a minimum, the turning the coverplate clockwise until the skirt flange makes full contact with the wall surface. Cover removal specified lengths in inches shown in Fig. 1. Ca ,tion requires turning in the counter-clockwise direction. Do not install Model DH56 HSW Dry sprinklers into CPVC Concealed coverplate assemblies are listed only for adapter fittings or tees that have an internal obstruction. use with specific sprinklers. The use of any other con- This will damage the sprinkler and/or the fitting. Refer to cealed wall sprinkler or the use of the SWC coverplate Fig. 8 on any sprinkler with which it is not specifically listed will void all guarantees, warranties, listings and approvals. DH56 HSW Note: DH56 and DH56 Recessed Sprinklers have or- To install the DH56 HSW dry sprinkler cut a 21/8"diameter ange bulb protectors to minimize bulb damage during hole in the wall as shown in Fig. 4. Use the Model G3 instal- shipping, handling, and installation. REMOVE THIS PRO lation wrench (see Fig. 3) to tighten the sprinkler until it is TECTION AT THE TIME THE SPRINKLER SYSTEM IS secured in the sprinkler fitting. Apply a Teflon* based seal- PLACED IN SERVICE FOR FIRE PROTECTION. Remov- ant to the sprinkler threads before installing in the sprinkler. al of the protectors before this time may leave the bulb vulnerable to damage. RASCO wrenches are designed Wrench only on the square boss. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER. Installation is corn- pletedto install sprinklers when covers are in place. REMOVE by removing the orange glass bulb-protector and as PROTECTORS BY UNDOING THE CLASP BY HAND. DO sembling the slip-on escutcheon to the sprinkler's can. NOT USE TOOLS TO REMOVE THE PROTECTORS. DH56 HSW Recessed with FP Escutcheon To install the DH56 HSW dry sprinkler with the FP Escutch- eon as a recessed sprinkler cut a 25/8" diameter hole in the wall as shown in Fig.5. Temporarily remove the plastic pro- tective cap, and then use the Model XLO2 wrench(see Fig. 2) to tighten the sprinkler until it is secured in the sprinkler fitting. Note: The Model XLO2 wrench has a notch in it to accommodate the deflector top. This wrench can only be inserted one way. Care must be taken not to damage the deflector during tightening. Apply a Teflon** based seal- ant to the sprinkler threads before installing in the sprinkler. Wrench only on the square boss. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER. It is recommended that the sprinkler be protected during plastering and paint- ing operations by reinstalling the plastic protective cap. In- stallation is completed by removing the protective cap and inserting the push-on escutcheon. Turn clockwise to adjust the escutcheon against the wall. "DuPont Registered Trademark 2. RECOMMENDED MINIMUM EXPOSED BARRAMBIENT EA KLER TEMPERATURE IN THE PROTECTED AREA (STANDARD DH56 HSW DRY NP EXPOSED BARREL AMIENr AMBBNr TEVPERATURE TDIPERATURE OF PROTECTED 47F/4C 160F/10'C 167E/TBC 0AREA*AT THE 18CHAROE ENO mom MINIMUM BARREL am** OF THE SPRAACLER (FM.E OF TEE TO TOP OF Ca*40) IN.M) N.(MM) IN.M 40'F(4C) 0 0 0 30F(-1'C) 0 0 0 20F(-7'C) 4(101) 0 0 L. CLEARANCE 10F(-17C) 8(203) 1 ( HOLE OF(-TBC) 12(306) 3(76)(75) O IMOLA EXPOSED -10F(-23C) 14(356) 4(101) 1 (25.1) DAR TH EL ..: :::5::::: : ESCUTCHEON-20F(-2rC) 14(356) 6(152) 3(75) \:.:.:..:.:.:......................\ -30F(-340) 4(101) :;:;:::;::5:::::::::'::°:0':::°:\ 16(406) 8( ) \:::::::::::::::: ::::::::'i::i\ -47F(-4OC) 18(457) 8(203) 4(101) ORATED AREA) \::: 5 ::•:•:•o-:•o-.i::::.•�:.\ 20(608) 10(264) \::::::::':':::::::::::::::::::::: -60'F(-ICC) 6(152) \::`•:::i:::::i:::::=::: °::--_ -60F(-61'C) 20(608) 10(264) 6(152) - •THE PROTECTED AREA REFERS TO THE AREA BELOW THE CEILING. ( 1\■ III i --_----------- ------- 1 1_'• DIA THE AMBIENT TEMPERATURE IS THE TELIPERAIURE AT THE mscHARRE I III ENI)OF TILE SPRINKLER. FOR PROTECTED AREA 1E PERATURF,S THAT OCCUR 8ET*1 THE VALUES i :ji i i[yi;i;ii; E;iii / LISTED.USE THE NFxT COOLER 11JRE. \:::;::: ::: ::::::: **THE WIN.REQUIRED BARREI.LENGTH B NOT TFIE SAME AS'NE'A DIMENSION. \::iiii::i: i:iili:i::i: \ NOTE EXPOSED MINIMUM BARREL LFNanIS ARE ILLCLU ATE UP TO 30MPHE \.;... \ (PROTECTED AREA) WINO VELDCIRFS IN THE PROTECTED AREA \i................................. INSTAL 1 INCH NPT THREADED \;;;;;;;,;;,;,;,;,; :T.,..•....,._\ END b OF DRY PENDENT SIDESIDE R WNL POFFRA B 18.3(CLASS 160) TEE MSG PPEER ANSI cAsT K16.. THREADED 126)ONLY. INSULATED COOLS FRS OORR EAERIOR FRAMING CAUSES CEDDE AT») T E EXPOSED DRY TAPEspssfus,CONSIDER THE EXPOSED EQUIVALENT. DRSIAATDRG SEAL.TLE CLEARANCE SPACETO ® AROUND SPRINKIP LEAKAGEAREAAND AIR INTD FEQiNATIN PROTECTED Hicw Doom*OPERATDIL CAUSE TURF IR Os.SEE IELOW FDR RECOMMENDED SPRINKLER (STANDARD DH56 HSWDRY SPRINKLEARRANGEMENTS S � SHOWN) mom EXPOSED WDLTNUN ARREL �E RA1OSE LENGTH 1 ABOVE) MEE ABOVE) . FACE DRY SPRINKLER INSIDE FACEM CAI FADE 1..'..::::.:::::'::::: :::::::::::1 iiii IN COLD AREA ii OEATED AREA) 1..;.;..:;,..•..•.i:.,.,.,...L CLEATED AREA) 1 1:::::::::::::::::::::::::::::::::► E1IIIIIIIIIP�1 1�� ill s: io.---'-IIIIIIIIII �II�''� LM iliilili�ll�� X11-;' li�llllil1��'� ;,:;: ::::: :::•:•:1 SEAL %1;:;:;::: ::::::: :::::::::::: :• O'ROTECTED AREA) S::::: :::::::::::::::t lk ::::::::::::::: ::: :::� RA(�0 ) INSULATED� OR Fig. 1 3. Technical Data: Maintenance K Factor Temperature Sprinkler Model DH56 Quick Response Dry Sprinklers should be Thread Rating Maximumt Identification inspected quarterly and the sprinkler system maintained in US Metric Size Sprinkler SWC Temperature Number accordance with NFPA 25. Do not remove the factory ap- Cover (SIN) plied thermally sensitive wax fillet between the bulb support- 155°F 135°F 100°F ing cup and the wrenching boss. Do not replace this wax with (68°C) (57°C) (38°C) a substitute substance. An alternate substance may interfere 5.6 80 1 175°F 165°F 150°F RA1664 with proper operation of the sprinkler. Do not clean sprinklers (79°C) (74°C) (66°C) with soap and water, ammonia or any other cleaning fluids. 200°F 165°F 150°F Remove dust by using a soft brush or gentle vacuuming. Re- (93°C) (74°C) (66°C) move any sprinkler which has been painted(other than factory applied)or damaged in any way. A stock of spare sprinklers Coverage Area should be maintained to allow quick replacement of dam- Maximum Coverage aged or operated sprinklers. Prior to installation, sprinklers Area Width x Length Flow Rate Pressure should be maintained in their original cartons and packaging ft x ft(m x m) gpm(L/min) Psi(bar) until used to minimize the potential for damage to sprinklers 28 x 8(8,5 x 2,4) 23(87,1) 16 9(1 2) that would cause improper operation or non operation. 28 x 10(8,5 x 3) 28(106) 25(1,7) Model DH56 Quick Response Approval Type: Extended Coverage Horizontal • Quick Response, Extended Coverage. Sidewall Dry Sprinkler Specification • Approved for installation in accordance with NFPA 13 Sprinklers shall be a [quick response—cULus Listed] ex- for light hazard occupancies. tended coverage horizontal sidewall sprinkler for light hazard occupancies. Sprinklers to be of bronze frame construction Step 1 - with a special deflector capable of providing a discharge over .,. a coverage area of 28 ft. (8,5m)wide, and 10 ft. (3m) long horizontal throw.Water seal assembly shall consist of a Teflon- . � ' coated Belleville spring washer. Installation shall permit sprin- kler deflectors to be positioned 4" (102mm)to 12" (305mm) Step 2 below the ceiling. Sprinklers shall have a nominal K-factor - of 5.6(80), and 1" NPT thread. Sprinkler temperature rating shall be [155°F(68°C)] and [200°F(93°C)]. Rated working ....r :" pressure shall be 250 psi (17.2 bar). Standard finish: [whit T e][ chrome][bronze][Special finish—specify]. Quick response extended coverage horizontal sidewall dry sprinklers shall be Step 3 Reliable Model DH56,SIN RA1664(Bulletin 016). For recessed EC horizontal sidewall sprinklers: Replace "horizontal sidewall"with"recessed horizontal sidewall." Add: '� " `" . :4 (1)Recessed escutcheon assembly shall be a two-piece es- adjcutcheon ustment.of push on Standard and thshallreadbe off designchrome,white with Yz" and(13mmbrass.) finish E Quick response recessed horizontal sidewall sprinklers shall Fig.2-XLO2 Wrench be Reliable Model DH56,SIN RA1664(Bulletin 016). For concealed EC horizontal sidewall sprinklers: Replace "horizontal sidewall" with "concealed horizontal sidewall." Add: Cover plate assembly shall consist of a brass cover al plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push-on and thread-off design allowing a 1/2" (13mm) cover plate adjust- ment. Cover plate temperature rating shall be 135°F(57°C) for 155°F (68°C) dry sprinkler and 165°F (74°C) for 200°F (93°C) dry sprinkler. A bulb protector shall be provided and factory installed inside the sprinkler cup to protect the glass bulb from damage, which could occur during construction Ag.3-G3 Wrench before the cover plate is installed.Standard cover plate finish: [white] [Custom Color— specify]. Quick response extended coverage concealed horizontal sidewall dry sprinklers shall be Reliable Model DH56,SIN RA1664(Bulletin 016). 4. DH56 HSW DRY SPRINKLER 1 1/2. [38.10mm] I- Total Adjustment I`I` ------- _ _ r Ceiling LA t 1 1/4" [31.75mm] i- - ---I 4" [101.60mm] Min. Escutcheon Adjustment 12' [304.80mm] Max. i 1/4" [6.35mm] System Tee i --,..I Escutcheon Adjustment 1" NPT 1 $ I i-N 1 15/16" —r II a F-� [53.18mm] l II 1 I I ---- I11/ ' `IIII IIII I _—_— IW II II —+-� p�� 3" Dia. � IIIIiI IIII I `;�`\ / I I -� — •� [76.20mm] I ---...t..------,__I 1 - 2 1/8" Dia. 1 [53.98mm] — I Hole in Wall I..�I 1/4" [6.35mm] Protrusion Sprinkler Can— A" Dimension Nominal Position Adjustment Range + 1/4" [+6.35mm] of Escutcheon ofelWS4 - 1 1/4 [-31.75mm] Available "A" Dim. is 2" to 48" (51 mm to 1219mm)in 1/4" (6mm) increments Note: The Sprinkler Can protrudes /"when escutcheon is in nominal position. Escutcheon adjustment provides + 1/4" (+6mm) to -11/4" (-32mm) "A" dimension adjustment range. Fig. 4 DH56 HSW RECESSED DRY SPRINKLER Ceiling ] II-------- 1 1/4M Escutcheon [31.75mm] 11 4" [101.6mm]Min. Cup i 31 12" [304.Smm]Max.* System Tee 1111Kagg 0 1" NPT - _414 -VII I ail�1.'4 3 7/32" Dia. ;`:k , J!\IL i I'111_, r- 1 2 5/8" Dia. [66.68mm] i c Nominal Position Hole in Wall of Escutcheon 2 9/32" Dia. [57.94mm] 1/4" [6.35] Escutcheon Adjustment "A" Dimension 1/2" [12.7mm] Adjustment Range Escutcheon Adjustment 01 28 ±1/4* ±6.35mm 1/4" [6.35) [ ] Escutcheon Adjustment Available "A" Dim. is 3-1/2" to 48" (89mm to 1219mm)in 1/4" (6mm) increments Note: Do not install the Model DH56 Dry EC Horizontal Recessed Sidewall Sprinkler in walls which have positive pressure in their side space. Fig. 5 5. DH56 HS i CO CEALED DRY SPRI KLER —11 tt 3 Lain tt f•Apf - b�• III � (feta m m«„ tt I �� . . 1111111111111 - -- -�--- ------ I ta" tine w.euw, 11 - a;/Id („,e20;Ing oferoofA ofibeFMp IN mama A MWeems 040 afNd l/wY[lg y/ r Available "A" Dim. is 3-1/2" to 48" (89mm to 1219mm) in 1/4" (6mm) increments Fig. 6 I \ N1,3' [4m] Minimum Spacing 28' [8.5m] Maximum Spacing I \\ l NN\ MODEL DH56 DRY SPRINKLER \ WALL Fpi1 [100mm] min.From Ceiling 12"[305mm] max.From Ceiling 28' [8.5mJ 016FG04A 10' 1:.3-m] Fig. 7 6. *CAUTION* DONOT INSTALL MODEL F3, TEESEL THATQR OR HAVE ANDEL DH56 HSW DRY INTERNAL OBSTRUCTION SPRINKLERS THISWILLTO CP CPVC ADAPTERITTIINGS OR DAMAGE THE SPRINKLER AND/OR THE FITTING. UN ADAPTER FITTINGSRETROFIITTINGSWITH PROCESS INTERNAL RELIABLE'S OLDER MODELALSO G3 DRYCOMMONLY FOUND DURING T SPRINKLERS. NO INTERNAL INTERNAL OBSTRUCTION OBSTRUCTION FEMALErtir A 0N .41 Il4 $ FEMALE . 10 THREAD �� THREAD INCORRECT CORRECT CPVC ADAPTER CPVC ADAPTER FITTING OR TEE FITTING OR TEE RELIABLE MANUFACTURES A FULL-LINE OF MODEL F3-PL. MODEL F3QR-PL. AND MODEL DH56 HSW-PL DRY SPRINKLERS THAT HAVE A SHORTER INLET FOR THESE APPLICATIONS. Will I LONGER SHORTER �� INLET INLET T,,____ MALE MALE Rimm.......... PIPEmiiii.......m.. PIPE THREAD THREADVII I I MODEL F3-PL, STANDARD MODEL F3QR-PL OR MODEL F3, MODEL DH56 HSW-PL MODEL F3QR OR DRY SPRINKLER MODEL DH56 HSW DRY SPRINKLER BE SURE TO ORDER THE CORRECT SPRINKLERS FOR YOUR APPLICATION 016fgO8 Fig.8 7. Ordering Information Specify: Installation Wrench Model XLO2 Sprinkler Wrench (Recessed &Concealed) 1. Sprinkler Type(select one): Model G3 Sprinkler Wrench (a)Model DH56 Dry EC HSW Note: A leak tight 1" NPT sprinkler joint can be obtained (b)Model DH56 Dry Recessed EC HSW/FP with a torque of 20-30 ft-lbs (27.1 - 40.7 N-m). Do not (c)Model DH56 Dry Concealed EC HSW tighten sprinklers over maximum recommended torque. 2. Sprinkler Temperature Rating. It may cause leakage or impairment of the sprinklers. 3. Sprinkler Finish. 4. Cover Plate/Escutcheon Finish. Escutcheon Data: 5. Length: "A"Dimension(face of tee to face of ceiling or FP cup/escutcheon assembly- 1/2"(13mm)adjustment wall) in 1/4" (6mm) increments. Note: Finishes (1) 1. The "A" dimension is based on a nominally gauged 3.11 Standard Finishes of pipe thread "make-up" of 0.600" (15mm) per ANSI Escutcheon Cover Plate B2.1 [71/2 threads approximately], whiro P/Chrome//yBronze nzee> roWhite/Chrome White 2. All platings and paintings are decorative and intend- (1) Other colors and finishes are available. Consult factory for details. ed for interior use. (2)cULus Listed as Corrosion Resistant Sprinkler in UL Listing Category White. standard Black or Sprinklers, Cat Automatic and Open. Note:Paint or any other coatings applied over the factory finish will void Quick Response Sprinklers. all approvals and warranties. The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Productsmanufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and se . -.by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by The Reliable Automatic Sprinkler Co.,Inc. nau Relt (800)431-1588 Recycled (800)848-6051 Sales Offices Paper Sales Fax MONNIMIngimiiiimini (914)829 2042 Corporate Offices Revision lines indicate updated or new data. www.reliablesprinkler.com Internet Address EG.Printed in U.S.A 05/10 P/N 9999970308 • FlameGuard® PEARS CPVC FIRE SPRINKLER PRODUCTS FG-2-0312 Complete System of Pipe, Fittings & Solvent Cement Corrosion Resistant • Superior Flow • Ease of Installation `<,.A t==` Spears® flameGuard® CPVC Fire Sprinkler Products provide a cost effective alternative to metal systems with advantages of high corrosion resistance, improved system hydraulics, ease of installation and quick t f � .t0 a} assembly with readily available tools. CPVC Fire Sprinkler Systems are . , i ,i...4,�u ^ based on proven ewe run sneman ra© uers products that have been in continuous service for over 40years. Spears®FlameGuard® ' products are approved by UL®, FM® milt. j m Global, LPCB and Certified by NSF Wia:41P . yip International for potable water use. Check local codes for restrictions and limitations. Corrosion Resistant CPVC Material Does Not sy In staltionf rLonLower Costs Sustain Biological Growth FlameGuard® emiinstallations significantly Unlike metal systems, productsreducepiping virtually rust,scale or pit and do not sustain bioloial growth a cause eliminating prefabrication. Systems can be fully installed d of Microbiologically Influenced Corrosion(MIC)which can on site using solvent cement joining methods. destroy metal fire sprinkler systems from the inside out. UL®Listed for U.S. and Canada in NFPA 13, 13R& 13D Systems Superior Flow Characteristics for Lower FlameGuard® CPVC Fire Sprinkler Products are UL® Friction Losses listed for U.S. and Canada applications for Light Hazard The smooth-wall interior surfaces of FlameGuard® CPVC occupancies as defined in NFPA 13,Residential occupancies systems result in reduced friction loss over metal systems. up to and including 4-stories as defined in NFPA 13R, The design flow characteristics remain constant throughout and Residential occupancies for one and two family the life of the product because there is no interior corrosion dwellings and manufactured homes as defined in NFPA in the system due to microbiological activity. 13D.Consult Spears®FlameGuard®CPVC Fire Sprinkler Pressure Rated to 175 psi(1200kpa) @ 150°F Products Installation Instructions and NFPA Standards for (65°C) additional applications including air plenum,system risers, oncealed, exposed, underground, combustable attic, FlameGuard®CPVC Products are produced in combinations ce basement and low pressure dry piping installations. of Schedule 40 and Schedule 80 Fitting configurations con- garage, forming to ASTM F 438 or F 439 standards and FlameGuard® Full Limited Lifetime Warranty SDR 13.5 CPVC Fire Sprinkler Pipe conforming to ASTM F FlameGuard® CPVC Fire Sprinkler Products carry a 442 standards. UL® Rated working pressure is 175 psi limited lifetime warranty against defects in material or (1200kpa)@ 150°F(65°C)(LPCB rated to 120°F)(49°C). workmanship.Consult Spears®warranty for additional details. CERTp PROGRESSIVE PRODUCTS FROM °" iii:c/4 SPEARS®INNOVATION& .. LPCB o U KAS TECHNOLOGY IA 007 Visit our web site: www.spearsmfg.com Spears® FlameGuard®. . . The Leader in Innovative CPVC Fire Sprinkler System Products Pioneer in Molded-in Metal Insert Head Adapters Spears® pioneered the development of the FlameGuard® molded-in-place 0 b metal thread insert for connection of sprinkler heads to CPVC fire sprinkler systems, plus Metal FIPT threaded female adapters for metal-to-plastic transitions. Developed the Special Reinforced (SR) Head Adapters aim_ Spears® FlameGuard® continuous improvement program developed the technology to produce a superior patented plastic threaded fitting - the ,,,,‘11111T Special Reinforced(SR)Design.This unique design incorporates a patented thermoplastic compression process that equalizes stresses generated by tapered thread joint make-up. All CPVC plastic body and threads provide a more uniform construction and improved corrosion resistance. Now, the Revolutionary TorqueSafeTM Gasket Sealed Head Adapter •Requires NO Thread Sealants •Eliminates Stress •Prevents Over Tightening •Provides Easy Frame Alignment Spears® revolutionary design features a special molded-in-place Brass Thread Insert fitted with an elastomer gasket seal at the base of the threads. The gasket seal allows a modified thread design that eliminates radial stress and associated problems typical with tapered thread joint make up. The insert is designed to rotat sprinkler frame alignment without over tightening. Patent Pending. e for easy Full Assortment of Specialty Products & Fitting Configurations Spears® FlameGuard®provides the specialty fittings needed in today's fire sprinkler systems. adjustable drop nipple for fine-tuning to finished ceiling height,and ringed head adapter for ease o during installation. Plus, Spears®FlameGuard®line offers a full assortment sprinkler fitting y s• Like the configurations including Tees, Elbows, Flanges, Couplings, Caps, Maleof CPVC fire of locating Adapters and Unions, sizes 3/4" through 3"; with new 3/4" and 1" Repair Couplings. tersGr000ved Coupling Complete Size Range of CPVC Pipe 11111111 in Spears®FlameGuard® meGuto3"ard®CPVC Fire Sprinkler Pipestandard is available sizes . Conforms to ASTM F 442 SDR 13.5 CPVC pipe. Spears® Solvent Cements & Thread Sealant FlameGuard®products should be installed using Spears® FS-5 One-Step Solvent Cement. For threaded joints, use Spears® BLUE 75'Thread Sealant that has been tested for compatibility with Fla ® CPVC Fire Sprinkler Products. Spears®TorqueSafeTM Gasket Sealed meGalant. Consult sprinkler head manufacturer prior to use. Adapter requires no sealant. Installation Training Available - Contact Spears® Technical Services or FlameGuarde Products must be installed in accordance with Spears®CPVC Fire Sprinkler Piping Products Installation Infstruu tDetalio al Fire Protection Association Standards 13, 13R, 13D,and in accordance with local codes.Code requirements and field conditions may differ. It is the responsibility of the installing contractor to insure that the product is suitable to meet these requirements. EsSPEARS® MANUFACTURING COMPANY CORPORATE OFFICE °* 15853 Olden St., Sylmar, CA 91342•PO Box 9203,Sylmar, CA 91392 W. 1 (818)364-1611 •www.spearsmfg.com ©Copyright 2012 Spears®Manufacturing Company. All Rights Reserved.Printed in the United States of America 03/12. FG-2-0312 lifb ( lanearplpe"team 'fbll( rest BOO lie®•'18613 www,p Mending Test tCoid3 • I Scope For NPS 2°and under Covers black and hot-dipped galvanized furnace butt-weided pegree of Bend p M1. eter of ndrel for mechanical and pressure applications (continuous welded)Grade A pipe. Pipe is intended Standard f10' 12 x outside pipe . andf is acceptable diameter I for ordinary uses In steam,water,gas and air lines. Pipe Close Coiling90• 8 x outside pipe diameter Is suitable for welding,threading,grooving and bending. I Flattening Test As a test for quality of the weld for pipe 2W'NPS and larger, Hct:"Cippsd tOeiVanized The average weight of zinc coating shall be not less than posOD Isn the the original outside diafrom the meter. Nocracl�nshallrx ur alongi • 1.8 oz.per sq.ft.of surface(inside and outside). •, When galvanized pipe Is bent or otherwise fabricated the inside or outside surface of the weld. to a degree which causes zinc coating to stretch or compress Frequency of Tests beyond the omit of elasticity, ticity,some flaking bf the coating Tensile teats are required on each lot of 25 tons or fraction thereof may ocof pipe NPS 1W and smaller and from each lot of 50 tons or fraction Hydrostaticsthereof of pipe NPS 2 and larger. pTasting Hydrostatic lest pressures for plain-end pipe are For NPS 2W and larger,a flattening testis also required on each lot of 50 tons. indicated bei Weight Extra Strong W NPS Std.Wthrough 3" 850 psi Dimensions and Weights rcatron are in 11through? 700 The dimensions and weights furnished under this specif �' through 1000 Psi 1300 Sipagreement with the standardized dimensions and weights specified in ' ASME 838.10. • End Finish Black PlLlin End Plain End: Permissible MI 1W and smaller.unless otherwise specified on order, Soh.40 Soh. Variat ions ®W0lgtht end finish shall be at the option of the manufacturer. in Wall Nominal 00 Weight yWeig t. Size Inches Wap �•�• Thickness ; .405 .068 .24 •085 .81 NPS 2'and larger,STD and X5 weights:ends beveled '/; 540 OSB 43 .118 `� with a root face of'%al f/n Minimum wall thick- °/. .675 _091 .57 .126 .74 •. to angle of 30', K°,-0' point shall +/_ .840 109 .85 .147 1.09 . ossa at any "/' 1.060 .113 1.13 .154 1.4e Threaded:To ANSI Standard B 1.20.1 not be more than • 1" 1.815 .133 1.89 .178 2.17 Couplings To ASTM Standard A 885 12 b%under nominal i'1+' 1.900 .140 2.27 .19100 a� . 1.900 .145 268Soo wall thickness 12""" 2.375 .154 3.68 218 5.03 l g/," 2.875 .203 5.80 276.300 17.87 Chemical Requirements 7.87 specified. s" 3500 .216 7.58 Composition,max.% e+OPhosuhortts Permissible Variations In Outside Diameter n oar nese ._.�-- .30 1.20 05 04' NPS 1'k"and under: a.018" �MolvttdsriBLll NPS 2"and over: a 1% Tamar Chromium a .40 .40 .40 .15 .08 *The combination of these five elements permissible Variations Weight Per Foot shall not exceed 1.00%. Pipe shall not vary more than*10%from the standard specified. Tensile Requirements Product Marking Tensile Strength,min. 48,000 psi Each length of pipe'A"NPS and larger is continuously stenciled to Yield Strength,min. 30,000 psi show the manufacturer,the grade of pipe(ASTM A53),the kind of pipe Elongation in 2' Refer to A53 Table X4.1 (F for continuous weld,A for Grade A),the size,XS for extra strong, and length. assume liability or responsibility for any loss,damage or Injury whatsoever resulting from the use of this information. In all rases,the customer Legal Notice:This brochure is intended for general information only.Pioneer makes no warranty or representation.expressed or implied,of any kind with respect to the information iscontained herein and shalltoa no event is therefore requested to use this information at Its can risk and rasponsibpfty. . Nevartacri North American Pipe&Steel www.napsteel.com N�4P$teel FIRE SPRINKLER PIPE � ! ._. _ _ North American Pipe & Steel has been a trusted source for steel piping products since 1981. With strong ties to mills in the U.S. and abroad, we are certain to supply "What you need when you need it". Our fire sprinkler line of pipe is another example of our commitment to meeting the needs of our increasing customer base. NAP SuperFlow and NAP Schedule 10 Pipe is: l ' manufactured to ASTM A135,A795 and A53A. UL listed and FM approved for fire sprinkler applications including roll grooved, plain end and welded joints. fully traceable. NAP SuperFlowAPPIOWE 1 1/4 1.660 .� .:.. ,� ` �° � 1 494 1.400 61300 3.70/0.26 � a0.4 �.. MIME 2.375 2.185 2 320 37 300 Wit::,* `* �� - 3.58/0.30 3" 3.280 3.500 3 320 _�.. ��. � �.��� '�" 19 300 1.27/0.09 NAP Schedule 10 1-1/4" 1.660 1.442 1 400 61 300 —. 2" EM111111 2.157 2 320 " 2-1 ;:; � . 300 , ,. is oafs; ® 3.500 . - •* k. . 3260 3.280 19 � .,, . . 300 — � ' z a �� ata * . � 8.: “.,-4,4*„„- s ' s x NAP Super Row Pipe and NAP Schedule 10 Pipe are manufactured by MS Pipe Co.,LTD, South Korea Surrey,BC Longview,WA Auburn,WA Nampa, ID 11933 Tannery Road,V3V 3X1 7 International Way,98632 3136 B Street NW,98001 21147 Delta Drive,83687 1-800-665-7473 1-877-735-0275 1-877-735-0275 1-877-735-0275 d FittingsIronThreade Ductile ii.- f_ '4 > "^a fix.. I*. ''"+.,,� _ ,. ' 4 - i k' Ductile Iron Threaded Fittings 4 r1. . _ _ ,_______ r �ti »t F € I, , ., e • branded fittings are UL Listed and FM Approved at 500 psi • Rated to 300 psi WSP • Ductile iron castings conform to ASTM A536 a Ul. US • Fitting dimensions conform to ASME B 16.3 LISTED • Bushings and plugs conform to ASME B16.14 44:111: • All fittings are 100% air tested APPROVED • NPT threads on all fittings conform to ASME B 1.20.1 • Independent lab verification that fittings meet applicable chemical &mechanical properties • Manufacturing facilities are ISO 9001:2008 and ISO 14001 • ProPakTM Packaging -..ir' fro:0Am, lilt*:' YOtfillarillsel),30430101;r0res4Atatifto fr.., 1,31110, _ .,, ,W -20 to 100 500 "" — fi�� rb_s.*'�!i."eik' ni,S't tjf y$:4,2.' '{li•A b f Y:�.Z" -.t 200 «.,'rditt:5�'Vf ..rY.z�.« .v-�-^�r'�rgK�t as ar' 480 o t-A- .,r ;, ' **'''f'''''.7,1*:.;" +-"4 .. ' a a.$`4.e 4t' w. 300 = — .,�.*:•.A �. :,,,....���.�� .�;A,� ` 440 ' +` aye-. � .' ' x:�`,r^9 i..[�` _3t.e ''�, +c t-4' 1. .. 400 3 _ .. 400 Itll ' 500 �:.�� ,- + . 360 F 600 . . s n 4°rlt 3W dt � 00. ,, i.0 320 4 ,t 11ar "-- , 3:is 4 i. M :'4 rt c 8 .N r SCI ProPakrilf System �.y(, 1 Ductile Iron Threaded Fittings - Class 300 UL/FM c 0 us 4111> APPROVED LISTED Fig. 35E 3 90°Elbow it Al ' ..'" 1/2 35E 3004 1.13 100 200 0.2^ 5 kat A 1 35E 3010 1.50 40 glillt /2 , .. *. 80 _ 0 s 18 1.1 ' 1-1/2 35E 3014 1.94 ( .,'"' at Wi � 35E 3024 2.70 ri Fig. 35RE3—90°Reducing Elbow :W'';717 '". rt.,::: "MA77 7''-',,,`'*''' - 0 ti:.''',,/,'N„yisitaTi i ,,,,.,,,,- , :-11;7 t. 80�. 35RE3006004 1.20 10 0.3 ♦ i .":4—v. lt*,.....,,-,:mx--,...„„',.,..,,,,'1.,':,,,pt.,e;7,..,,,'„,.„ft.4.5.,,,,,,4„,,z,31-,,„, .,.„,, : ,,,,,, ,„1„,.., 164,1.38 1.45 50 100 0.4 1 x 3/4 35RE3010006 may A '•"` . r t ,. „ � 3 35 70 0 6 A I A 1-1/4 x 3/4 35RE3012006 1.63 ^ , ' g * 4; :. ,7-§,' tom. 6 1 75 30 0 0 0 6 1-1/2 x 1/2 35RE3014004OMNI 30 6 ' a , yes• . �p 1-1/2 x 1 35RE3014010 1.65 1.80 20 400 8 k a 97 . 18 36 �,. 1 0 2 x 1/2 35RE3020004 1.60 wfr_a or:, 0,1235RE3020010 1 73 2 02 162 . 2x1 0,k � �: 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 , t p ,14J . -,:*4-1,4.0.,,c,,,::'•.: ,: . 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 Fig. 35F 3 45°Elbow • .: tk trri , pt 1 . '' a . '' 44: ' . e - ; 1/2 35F 3004 0.88 150 300 0.2 41/0 �i 0 5 _1&,' •� 1 35F 3010 1 13 40 80 / -:',• 1-1/2 35F3014 144 20 40 10 '! 2-1/2 35F 3024 1.95 Fig. 35T 3 Tee . `, tLiu.; • . ,t,11rt, 14 \���` 1/2 35T3004 113 80 160 11101 \���II i lA ,:".„„1„,i/2„...,,,,,, 41,„,..1::,43, 0,4,,, ._�" a 1 1 50 25 w �0 .�� �I ', 35T 3010 . . . .. ---—-WILI- r'21:',-.!;To ot 35T 3014 1 94 r 10 ' moi;—, 1-1/2 ,�� �... 2-1/2 35T 3024 2.70 201 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com ( . E �. , Ductile Iron Threaded Fittings - Class 300 UL/FM c0us ® Fig. 35RT3-Reducing Tee LISTED APPROVED 411 411i. 4 i \%.i C + 3/4 x 1/2 35RT3006004 1.20 1.20 1.22 60 120 0.4 _1 -- 1 x 1/2 x 1 35R13010004010 1;50 1;36 1 50 30 60 0.6 'P'‘.-...."-•....,..,& ,.,1 3K a -r,R ~!' fi" ..fir 'f ..z. afi£r� ,a. :1 ds,*.d«a-� .°,"'�`> •x'`4`" , D c B, `� 1 x 3/4 x 3/4 35RT3010006006 1.38 1.31 1.45 35 70 0.6 . ki7:'x+a 10 ,:- ; i',)', iiii -,, n p�x jx'M '7. 3.; ',1. l y r :: /{U 1-1/4 x 1/2 35RT3012004 1.34 1.34 1.53 20 40 0.8 ',?,P1/4M-144,4A:,. ',..4', ,c`.,. :i is 'f57 G r s"l 4, T.. ,a'-$ RNg, 1-1/4x3/4 35RT3012006 1.45 1.45 1.62 15 30 0.9 1-1/4x 1 35RT3012010 1.58 1.58 1.67 15 X30 1.0� a 1-1/4 x 1 x 3/4 35RT3012010006 1.45 1.38 1.63 20 40 0.8 1-1/4 x 1 x 1-1/4 35RT3012010012 1.75 1.69 1.75 15 30 1.0 �.s 1 Affe .,.'' n ..r# ..r" * . ,a y�pAI. ' '...!';'_i'..!!:>,:7 MAI;.. 1-1/2 x 1/2 x 1-1/4 35RT3014004012 1.81 b 1.56 1.88 24 48 1.1 �q1 1-1/2 x 3/4 y} 35RT3014006 1.52 1.52 1.75 16 32 1.1 - - Z S +R _ x A,- .., i Y? �i. C at9s. i:,5- epi il't ':�..:", ' Pd',v, ,j,f^. W.>.m. 1-1/2 x 3/4 x 1-1/2 35RT3014006014 1.94 1.75 1.94 18 36 1.2 1-1/2 x 1 x 1/2 3 35RT3014010004 1.44 1.25 1.69 20 40 0.8 �- ,,.,..# - � -,. orb 1 1/2 x 1 x 1 35RT301401001>0 1.65 1.50 1.80 16 32 1.0 1-1/2 x 1 x 1-1/2 35R-13014010014 1.94 1.80 1.94 12 24 1.3 .. 1-1/2 x 1-1/4 x 1/2 35RT3014012004 1.41 1.34 1.66 16 32 0.9 . --•.ate= ,2" 5 .> ;.!;; a.F.t a r, ,:iz '„- !.' 7� r'" „.l n R _,,,�r- 1 1/2 x 1-1/4 x 1 35RT3014012010 " 1.65 1.58 1.80 16 32 X1.11 1-1/2 x 1-1/4 x 1-1/2 35RT3014012014 1.94 1.88 1.94 14 28 1.4 2 x 3/4 35R13020006 1.60 1.60 1.97 10 20 1.6 l :.tea . 'r '.f Y"st4f w a> f iii.'iLl 1.k",.;.,..:. ` 2 x 1 x 2 35RT3020010020ya2.25 2.02 2.25{ 8 16 1.9 Nh Jj :(1M. ::,;Sicm.rdirl 2 ��.S ` ,i�' W, ' . « �'..-. YJ," ,. v. 2 x 1-1/4 x 2 35R13020012020 2.25 2.10 2.25 8 16 2.0 2 x 1-1/2 x 1/2 35RT3020014004 1.49 1.41 1.88 ,�1,0 20 1.3 2 x 1-1/2 x 1 35RT3020014010 1.73 1.65 2.02 8 16 1.5 „2 x11 J T 2 x 1-1/2 x 1-1/2 35RT3020014014 2.02 1.94 2.16 8 16 1.8 Fig. 35BT3-Bull Head TeeI y{� � lire ��#�lumller�� � r �.- � .���, 11N!� � _. 4 n. in • . : ..-Inner Master, "; 11111), lig/' ��.. 3/4 x 1 358T3006010 1 45 1.45 :I.. 7 30 60 0.6 IC�11-- ,. ix 1,4/ *.%r At: it l .-1 M: '' :1:10,":, - 148, :: 0 9 1 x 1-1/2 35BT3010014 1.80 1.80 1.65 15 30 _ 1.0 a 1-1/4 x 1-1/2 35BT3012014 1.88 1.88 i 1.82 15 30 1.3 :,?c *C'ittar 17 T_ ..� art 1-1/2 x 1-1/4 x 2 358T3014012020 2.16 2.10 2.02 10 20 1.8 202 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • wwwsmithcooper.com Ductile Iron Threaded Fittings- Class 300 UL/FM c (DO us 410> APPROVED Fig. 35CP3 -Straight Coupling with Ribs LISTED 0 A 1/2 35CP3004138 200 400 0.1 ` °- 4 lit,, r. 6. * ap,`„ ..r r 1 ' 'q',.... ,a �, % 1 35CP3010 1.75 60 120 0.4 D 1-1/2 35CP3014 2.19 25 50 0.7 � 2-1/235CP30243.009 18 2.2 1 Fig. 35RC3 -Hex Reducing Coupling �..ap Y9 h x k i;:::!,'''''..‘.2'..;: i. :1 :.1...?...;';'..ttii:71i.! j,N; - _ B A 1 x 1/2 35RC3010004 1,69 80 160 0.3 w a:x. t.�,, .. ;;\ 1-1/4x3/4 35RC3012006 2.06 40 80n 0 6 rtiliiAte:'' ;'e ,;., ,. i k Fig. 35HB3 -Hex Bushing � ice'{ £ ` t F i t a tx "B B ' 1 x 1/2 35HB3010004 1.06 1.40 180 360 0.2 Nii i\�J a� 1 i IIS 1.sa 1 i , �A 1-1/4 x 1 35HB3012010 1.19 1.80 90 180 0.2 • I 44 Is I 1I i7i q`ht ° ° �.ti o:sWS:- 5 kr , ''. a M �1 1/2 x 1-1/4 35HB3014012 1.25 1.95 75 150 0.3 2 x 1-1/4 35HB3020012 1.38 40 80 0.6 WiFta it , '. � F :, 'h , • • y y ik Fig. 35SP3 -Square Head Plug x , t . _1 f1 [ , Y q -T�% 1/2 35SP3004 0.94 600 1200 0.07 i Iii A �; e all- ' 1 I p1 1 35SP3010 1.25 200 400 0.1 1-1/2 35SP3014 1.44 80 160 0.4 Z a x k' Cj.�s 4 ..,;a ;r P' V :! t 'F` ` Fig. 35U 3-Union with Brass Seat 1 35U 3010 2.19 20 40 1.0 �. '� '^'�� .k .r�,,.�r a,�.... .x a. n ...,W�tti. r..�a ..,... .� ",,,i-''',7',7,.:tazs..,. A ',... ' - 1-1/2 35U 3014 2.62 10 20 1.7 / / : 203 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com 1 Ductile Iron Threaded Fittings - Class 300 UL/FM C (1411 US APFig. 3. ...5X 3—Cross LISTED PROVED _ � T `--!� s ; r A .., per".""-4, 4 - lir lige.. ,��i 1 35X 3010 _ 1.50 -. 20 40 ,,,, .r ` 42 r " ', . s ,,,,,,,...,9,,, ,,,,,,..4,04„.„..• U 1/2 I 1' 35X 361;i- 1.94 ���, .x•_, r �. .: a •„ � � U C T£ B I---) Fig. 35RX3—Reducing Cross � � F �, � 4 A . � ,` , I I -- 1-1/4 x 1 35RX3012010 1.67 •1 58 - I- -1-- ''-'-''.2';','; -.= 15 30 1 2 2 x 1 2. ? • .,< ��, I 1 1 I IA 35RX3020010 2.02 1 73 8 16 2.0 11111 Fig. 35C 3-...Cap � �. 1/2 0046 € „„....„.„........„.................,...„........._:... .......„,„.,.....••- it 1 6. ,.,.............. 11114, ,4 0.8716 300 pp 35C 3010 _ 1.16 i ,:ter0 ` 110 220 0.2 1-1/2 35C 3014 1.33 50 •100 , 0.5 21/2 35C3024x . . ,t 1.70 18 36 fil,. . 1.6 :; r Fig. 35BC3—Beam Clamp • AI-- � �/ 3/8 35BC3003 0.75 100 �� 11G .. 200 0 3 titit 204 SMITH-COOPER INTERNATIONAL® • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • wwwsmithcooper.com FireLock® Fittings 4tauiic 10.03 Material Specifications: ' Fitting: Ductile iron conforming to ASTM A-536,grade 65-45-12. 0 t Fitting Coating: ❑ Orange enamel ❑ Red enamel in Europe, Middle East,Africa, and India ❑ Optional: Hot dipped galvanized Approvals/Listings: COUS . > LPCB Vds CSP usreo Product Description: FireLock®products comprise a unique system specifically designed for fire protection services. FireLock full-flow elbows and tees feature CAD- developed, hydrodynamic design, affording a shorter center-to-end dimension than standard fittings. A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. FireLock fittings are designed for use exclusively with Victaulic couplings that have been Listed or Approved for Fire Protection Services. Use of other couplings or flange adapters may result in bolt pad interference. Refer to the appropriate listing agency or approval body for pressure ratings. Pressure ratings vary by agency. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By I Date Date victaulic.com I FireLock® Fittings I Publication 10.03 10.03 1539 Rev M Updated 12/2014 ©2014 Victaulic Company.All rights reserved. 1 �CtauliG' victaulic.com I FireLock®Fittings I Publication 10.03 Dimensions: I.ct0E1 c 10 CtoE 1 toE toE t 1,=, e ki-... L tp 0 l P---.IL NO.001 NO.003 NO.002 No.006 No.001 No.003 90°Elbow 45°Elbow Straight Tee2 No.006 p Actual Cap Nominal Outside Approx. Approx. Approx. Size Diameter C to E Weight Weight Approx. ght Each C to E Each Weight Weight inches inches Lbs. C to E Each C to E Each inchesinches Lbs. inches Lbs. inches Lbs. mm mm mm kg mm 1�A 1.660 kg mm kg mm 32 42.4 - - - kg 32 1.900 - - - _ 0.82 0.3 - 21 0.1 - 40 48.3 - - - - - - 21 0.4 2 2.375 2.75 1.7 2.00 - 21 0.2 50 60.3 70 0.8 1.8 70 2.4 22 2 1/2 51 0.8 0.6 65 .8 05 76 3.00 3.1 2.25 2.2 3.00 31.61 0.88 10.0 76.15 3.000 3.00761.4 57 1.0 76 1.6 221S 330 2.25 2.4 3.00 22 0.5 76.1 76 1.5 57 3.8 3 3.500 3.38 1.1 76.2 1.7 - - 3 1.2 88.90 86 1.8 230 3.1 3.38 5.3 108 mm 4.250 4.00 5.764 1.4 86 2.4 22 0.5 108.0 102 2.6 3.00 5.1 4.00 7.5 4 4.500 76 2.3 102 3.4 - - 140 4.5001143 4.00 6.7 3.00 5.6 4.00 5 5.563 3.0 76 8.7 25 1.1.4 125 5.561413 4.88 12.6 3.25 83 102 15.73. 25 124 5.7 83 4.88 1.00 4.1 139.7 mm 5.500 4.88 12.4 3.25 3.8 124 7.1 25 1.9 139.7 124.0 8.2 248 15.4 5.6 159 mm 6.250 5.50 12.6 82.6 3.7 124.0 6.9 - - 158.8 140 3.50 9.2 5.50 17.9 6 6.625 550 18389 4.2 140 8.0 - - 150 1683 140 8.3 3.50 11.7 5.50 22.7 1,00 5.9 165.1 mm 6.500 5.43 17.6 5'3 140 10.3 25 2.7 165.1 139.7 7.9 88.9 5.2 39.5.5 22.0 8 8.625 6.81 88.9 5.2 139.7 9.9 - - 200 219.1 173 25.5 4.25 20.4 6.94 11.6 108 9.3 176 38.7 1.13 12.7 29 5.8 10.03 1539 Rev M Updated 12/2014 0 2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulic victaulic.com I FireLock®Fittings I Publication 10.03 Flow Data: Frictional Resistance Actual Equivalent Feet/meters of Straight Pipet Nominal Outside No.002 Size Diameter Elbows Straight Tee inches inches No.001 No.003 mm mm 90°Elbow 45°Elbow Branch Run 11/a 1.660 - - - - 32 42.4 - - - 1 ih 1.900 - - - - 40 483 - - - 2 2.375 3.5 1.8 8'5 1.15 50 60.3 1.1 05 2.6 21 2.875 4.3 2.2 10.8 4.3 1 3 3.000 4.5 2.3 65 73.0 1.3 0.7 33 4.5 76.1 mm 76.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.0 80 88.9 15 0.8 4.0 1.5 4.250 6.4 3.2 153 6.4 108mm 108.0 2.0 0.9 4.7 2.0 4 4500 6.8 3.4 16.0 6.8 100 1143 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 2.68.5 125 141.3 2.6 1.3 6.4 5.500 83 4.1 20.6 8.3 139.7mm 139.7 2.5 13 63 2.5 159mm 6.250 9.4 4.9 25.0 9.6 158.8 2.9 15 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 150 168.3 3.0 15 7.6 3.0 6500 9.8 4.9 24.5 9.8 165.1 mm 165.1 3.0 15 7.5 3.0 8 8.625 13.0 5.0 33.0 13.0 200 219.1 4.0 1.5 10.1 4.0 1 The flow data listed is based upon the pressure drop of Schedule 40 pipe. General Notes: NOTE:When assembling FireLock EZ couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009N/009H couplings, use FireLock No.006 end caps containing the "EZ" marking on the inside face or No. 60 end caps containing the"QV EZ" marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V/009H couplings. Note Insterlation This the product youla a in talling.Handbooks are included with each shipment o1 Victaulic r to be installed stalled inll be accordance fwith ccu current Victaulic installation/ay Victaulic or to Victaulic ssembly'ons.All instructions. products products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Trademarks Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic®is a registered trademark of Victaulic Company. 10.03 1539 Rev M Updated 12/2014 ®2014 Victaulic Company.All rights reserved. \iCtaUlid victaulic.com 3 Victaulic® FirelockTM Rigid Coupling Style 009N °taU'ie • 10.64 Patented 1.0 CERTIFICATION/LISTINGS c®u FM LPCBJ VdS ume C104-1a/36 2.0 PRODUCT DESCRIPTION • The FireLock EZTM Style 009N Installation-ReadyTM Rigid Coupling is for use in the fire protection market. • The coupling's unique design eliminates loose parts, promotes consistent installation and provides substantial gains in productivity. • IMPORTANT: FireLock EZTM Style 009N couplings are recommended for use ONLY on fire protection systems. 3.0 MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A 536, Grade 65-45-12. Ductile iron conforming to ASTM A 395, Grade 65-45-15, is available upon special request. Housing Coating: (specify choice) ❑ Orange enamel (North America, Asia Pacific) ❑ Red enamel (Europe) ❑ Hot dipped galvanized Gasket: (specify choice') ❑ Grade "E" EPDM (Type A) FireLock EZ products have been Listed by Underwriters Laboratories Inc., Underwriters Laboratories of Canada Limited, and Approved by Factory Mutual Research for wet and dry(oil free air)sprinkler services within the rated working pressure. 1 Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. Bolts/Nuts: Zinc electroplated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A 449 and physical requirements of ASTM A 183. System No. I Location Spec Section Paragraph Submitted By Date Approved Date victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. 1 ✓ctaulie victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 4.0 LISTINGS/APPROVAL 2 The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Vds LPCB Nominal Size cULus FM Sch.5 Sch. 10 Sch.40 Sch.5 Sch.10 Sch.40 psi psi inches psi psi psikPa kpsi pPa kPa kPa kPa si psi mm kPa kPa kPaa 11/4 232 365 365 175 363 363 363 363 32 1600 2517 2517 1205 2502 2502 2500 2500 11/2 232 365 365 175 363 363 363 363 40 1600 2517 2517 1205 2502 2502 2500 2500 2 363 365 365 175 363 363 363 363 50 2502 2517 2517 1205 2502 2502 2500 2500 21/2365 365 365 175 363 363 363 363 65 2517 2517 1205 2502 2502 2500 2500 3363a 363 363 76.1 mm N/A 2517 3 N/A N/A 2502 4 N/A 2500 2500 3N/A 365 365 175 363 363 363 363 80 2517 2517 1205 2502 2502 2500 2500 4365 365 365 175 363 363 363 363 100 2517 2517 1205 2502 2502 2500 2500 N/A 175 363 363 N/A N/A 108.0 mm N/A N/A 1205 2502 2502 5 290 365 N/A 363 363 232 N/A 125 N/A 2000 2517 2502 2502 1600 3634 N/A N/A N/A 133.0 mm N/A N/A N/A N/A 2502 4 290 5363 2502 4 4 232 139.7 mm N/A 2 00 s N/A N/A N/A 1600 N/A 3634 N/A N/A N/A 159.0 mm N/A N/A N/A N/A 2502 4 290 6 N/A N/A 3634 N/A N/A N/A 165.1 mm N/A 2000 6 2502 4 6 290 365 N/A 363 363 232 N/A 150 N/A 2000 2517 2502 2502 1600 3634 N/A N/A N/A 216.0 mm N/A N/A N/A N/A 2502 4 N/A 365 363 363 232 N/A 8 N/A 2502 2502 1600 200 2000 2517 2 Listed/Approved for wet and dry pipe systems(>—40°F/-40°C)for continuous use in freezing conditions,use of Style 005H Coupling with Silicone Gasket is recommended. lubrication is required. Please see the Victaulic Installation Manual 1-009N/009H for details concerning when supplemental 3 cULus listed for DIN 2458 2.6 mm pipe wall. 4 FM approved for BS 1387 Medium 3.6 mm pipe wall. 5 cULus listed for EN 10220 4.0 mm pipe wall. 6 cULus listed for EN 10255 4.5 mm pipe wall. • • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. 2 ✓ctaulid victaulic.com 4victaulic.1LIST.comINI CouplingsGS/APPROVAL I FireLock I Rigid I Style 009N I Publication 10.64 Speciality Pipe Pipe Size Pressure Rating Pipe Size Pressure Rating Pipe Size Pressure Rating cULus FM cULus FM inches psi psi inchespsi cUsFM kPa kPa psi inches psi psi kPa kPa kPa kPa BLT 1/a-2 300 365 EZT 1�/a 2 300 365 MT 1/,-2 300 365 2068 2517 2068 2517 DF 1/a-4 300 365 2068 2517 2068 2517 FF 1 Y,-q 300 365 MLT 1�/,-2 N/A 365 2068 2517 2517 DT 11/4-2 300 365 FLF 1'/a-4 N/A 365 2068 2517 2517 ST 114-2 N/A 365 EF 11/4-q 175 175 2517 1206 1206 FLT 1'/a-2 N/A 365 STF 1�/a 4 N/A 365 2517 2517 EL 7 y,_2 300 365 FLTL 1�h 2 365 2068 2517 N/A 2517 TF 2�/a 4 N/A 365 2517 ET40 11/4-2 300 365 GL 1/a-2 300 365 2068 2517 2068 2517 WLS 1'/a-2 300 365 300 365 2068 2517 EZF 3-4 2068 2517 MF 1,/a-4 300 365 2068 2517 WST 1�/a-2 N/A 365 2517 XL 1/a-2 300 365 NOTES 2068 2517 • BLT=BLT steel pipe manufactured by Allied Tube&Conduit Corp. • DF=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • DT=DYNA-FLOW steel pipe manufactured by Allied Tube&Conduit Corp. • EF=EDDY FLOW steel pipe manufactured by Bull Moose Tube Co. • EL=EDDYLITE steel pipe manufactured by Bull Moose Tube Co. • ET40=Eddythread 40 steel pipe manufactured by Bull Moose Tube Co. • EZF=EZ-Flow steel pipe manufactured by Northwest Pipe Co. • EZT=EZ-Thread steel pipe manufactured by Youngstown Tube Co. • FF=Fire-Po steel pipe manufactured by Youngstown Tube Co. • FLF=Fire-Line Flow steel pipe manufactured by Western International Forest Products Inc. • FLT=Fire-Line Threadable steel pipe manufactured by Western International Forest Products Inc. • FLTL=Fire-Line Threadable Light steel pipe manufactured by Western International Forest Products Inc. • GL=GL steel pipe manufactured by Wheatland Tube Co. • MF=Mega-Flow steel pipe manufactured by Wheatland Tube Co. • MT=Mega-Thread steel pipe manufactured by Wheatland Tube Co. • MLT=MLT steel pipe manufactured by Wheatland Tube Co • ST=STD wall pipe in accordance with ASTM A53. • STF=Steady Flow steel pipe manufactured by AMS Tube Corp. • TF=Tex-Flow steel pipe manufactured by Tex-Tube Co. • WLS=WLS steel pipe manufactured by Wheatland Tube Co. • WST=WST steel pipe manufactured by Wheatland Tube Company. • XL=XL steel pipe manufactured by Allied Tube&Conduit Corp. • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 ✓ctaulic victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • • 5.0 DIMENSIONS Style 009NY c0 .u, ////�Y�� r-Z 4r ////01u1 J till 1111 :1 J \:1 IrI �� �� r� .Jr Style 009N Pre-Assembled Style 009N Joint Assembled (Push On Condition) Dimensions Pre-assembled Approx. Actual Maximum Maximum Allow. (Push On Condition) Joint Assembled Weight Nominal Outside Working End Pipe End Bolt/Nut 9 Y Z Each Size Diameter Pressure 7 Load' Separations Size X Y X inches inches psi lbs. inches inches inches inches inm ches inches inches lbs. mm mm kPa N mm No. mm mm kg 11/4 1.660 365 790 0.10 3/8 x 2 3.13 5.00 2.75 5.00 2.00 1.4 32 42.4 2517 3514 2.54 2 M10 x 2 79 127 70 127 51 0.6 11 1.900 365 1035 0.10 Ws x 2 3.38 5.13 3.00 5.13 2.00 1.5 40 48.3 2517 4604 2.54 2 M10 x 2 86 130 76 130 51 0.7 2 2.375 365 1616 0.12 3/s x21/2 4.00 5.63 3.50 5.63 2.00 1.9 50 60.3 2517 7193 3.05 2 M10 x 21/2 102 143 89 143 51 0.9 21/2 2.875 365 2370 0.12 %x 21h 4.50 6.13 4.00 6.13 2.00 2.1 65 73.0 2517 10542 3.05 2 M10 x 21h 114 156 102 156 51 1.0 76.1 mm 3.000 365 2580 0.12 2 3/s x 2'h 4.63 6.00 4.13 6.13 2.00 2.1 76.1 2517 11476 3.05 M10 x21/2 118 152 105 156 51 1.0 3 3.500 365 3512 0.12 3/s x 21 5.13 6.75 4.63 6.75 2.00 23 80 88.9 2517 15622 3.05 2 M10 x 21h 130 171 117 171 51 4 4500 365 5805 0.172 3/s x 21/2 6.00 7.88 5.63 7.50 2.13 2.9 100 114.3 2517 25822 4.32 M10 x 21/2 152 200 143 191 54 1.3 4.250 365 5175 0.17 3/8 x 2'h 5.63 7.38 538 738 2.13 3.1 108.0mm 108.0 2517 23020 4.32 2 M10x21h 152 1.87 137 187 54 1.4 5 5.563 365 8870 0.17 1/2 x 3 7.25 925 6.75 9.13 2.25 5.0 125 141.3 2000 39456 432 2 M12 x3 184 235 171 232 57 2.3 5.250 365 7897 0.17 'h x 3 6.63 9.00 638 9.00 2.25 4.8 133.0 mm 133.0 2517 35106 4.32 2 M12 x 3 168 229 162 229 57 2.2 139.7 mm 5500 365 8667 0.17 2 1/2 x 3 6.88 925 6.75 9.13 2.25 4.9 139.7 2517 38529 432 M12 x3 175 235 171 232 57 2.2 6.250 365 11192 0.17 1h x 31/4 7.88 10.00 7.38 9.88 2.25 5.6 159.0 mm 159.0 2517 49753 4.32 2 M12 x 3'/a 200 254 187 251 57 2.5 6.500 365 12105 0.17 'h x 3'/a 8.00 1025 7.75 10.13 225 6.0 165.1 mm 57 2.7 165.1 2517 53813 4.32 2 M72 x 3'/a 203 260 197 257 6 6.625 365 12582 0.17 1h x 31/4 838 1038 72.88 10.1325 25 5 2 6.0 150 168.3 2000 44469 4.32 2 M12 x3% 213 264 2.7 8.500 365 20712 0.17 %x 4 10.63 1325 1025 10.13 2.63 11.4 216.0 mm 216.0 2517 55968 4.32 2 M16 x 4 270 337 260 257 67 5.2 8 8.625 365 21326 0.17 5/8 x 4 10.88 1338 1025 13.13 250 11.4 200 219.1 1620 94863 4.32 2 M16 x 4 276 340 260 333 64 52 7 Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.See the Listings/Approvals section of this publication for ratings on other pipe. 8 The allowable pipe separation dimension shown is for system layout purposes only.FireLock EZTM'couplings are considered rigid connections and will not accommodate expansion or contraction of the piping system. 9 Number of bolts required equals number of housing segments. NOTES • When assembling FireLock EZT1 couplings onto end caps,take additional care to make certain the end cap is fully seated against the gasket end stop.For FireLock EZT""Style 009N couplings,use FireLock No.006 end caps containing the"EZ"marking on the inside face or No.60 end caps containing the"QV EZ"marking on the inside face.Non-Victaulic end cap products shall not be used with Style 009N couplings.IMPORTANT:Gaskets intended for the Style 009 or Style 009V couplings cannot be used with the Style 009N coupling.There is no interchanging of gaskets or housings between coupling styles. • Use Of Flushseal Gaskets For Dry Pipe Systems FireLock EZTM couplings are supplied with FireLock EZTM Grade"E"Type A gaskets.These gaskets include an integral pipe stop,that once installed provides the similar benefits as a FlushSeal gasket for dry pipe systems.It should be noted that standard Victaulic Flush-SealT"'gaskets are not compatible and cannot be used with the FireLock EZTM couplings. • • 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. ✓ctaulad victaulic.com 4 victaulic.com I Couplings I FireLock I Rigid I Style 009N I Publication 10.64 • • 6.0 REFERENCE MATERIALS Publication 05.01:Seal Selection Guide 1-009N/009H:Installation Instructions FireLock EZTC Rigid Coupling User Responsibility for Product Selection and Suitability Each user bears final responsibility for making a determination as to the suitabilityof Note p hall Thibes nduct e manufactwith d by VictaulicVictaulic or to Vti lla i in assembly instr All products Victaulic standardsproducts specifications,as well as Victaulic performance,Nith industry tomaintenance, Victaulic installed intheaccordance changeh current instaa designs an instructions. ns. safety,and warning instructions.Nothing in this or any other document,nor anyverbal equipment without the right andwithout productcurrispecifications,oblgos. designs and standard recommendation,advice,or opinion from any Victaulic employee,shall be deemed to without notice without incurring obligations. alter,vary,supersede,or waive any provision of Victaulic Company's standard conditions Installation Reference should always be made to the l-009N/I-009H Firelock EZ Rigid Coupling of sale,installation guide,or this disclaimer. Intellectual Property Rights Installation Instructions for the product you are installing.Handbooks are included with No statement contained herein concerning a possible or suggested use of any material, each shipment of Victaulic products,providing complete installation and assembly data, product,service,or design is intended,or should be constructed,to grant any license and are available in PDF format on our website at www.victaulic.com. under any patent or other intellectual property right of Victaulic or any of its subsidiaries Warranty or affiliates covering such use or design,or as a recommendation for the use of such Refer to the Warranty section of the current Price List or contact Victaulic for details. material,product,service,or design in the infringement of any patentor other intellectual Trademarks property ion- eady.are traemarks or or patent applications rfor articles t"Patented" Pending"Patent refer methods of use intheUnto ited States and/or aother rergistered trademarks of Victaul ceCompany,land/ornstallatits offiliated entitiesa in the U.S.and/ countries. or other countries. 10.64 7072 Rev G Updated 10/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com ✓ctaulic 5 06.08 CARBON STEEL PIPE GROOVED COUPLINGS CQ FM elLPCB 0, Reducing Coupling LISTED 104-1a/05 SEE VICTAULIC PUBLICATION 10.01 DETAILS STYLE 750 The Style 750 Reducing Coupling permits direct reduction on the piping run.Designed11111 104r4 to replace two couplings and a reducing fitting,the Style 750 features a special reducing gasket for pressure responsive sealing.A steel washer which prevents telescoping of the smaller pipe inside the larger pipe during vertical systems assembly is available upon request. irli 0 elle 111 MATERIAL SPECIFICATIONS Housing:Ductile iron conforming to ASTM A-536,grade 65-45-12.Ductile iron conforming to ASTM A-395,grade 65-45-15,is available upon special request. Housing Coating:Orange enamel • Optional:Hot dipped galvanized and others Gasket:(Specify choice*): • Grade"E"EPDM(All other sizes) EPDM(Green color code).Temperature range—30°F to+230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services.UL classified in accordance with ANSI/NSF 61 for cold+86°F/+30°C and hot+180°F/+82°C potable water service.NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade"T"nitrile Nitrile(Orange color code).Temperature range—20°F to+180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range.Not recommended for hot water services over+150°F/+66°C or for hot dry air over+140°F/+60°C. * Services listed are General Service Recommendations only.It should be noted that there are services for which these gaskets are not recommended.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. • Optional:Assembly Washer:Galvanized,carbon steel Bolts/Nuts:Heat-treated plated carbon steel,trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. CONTRACTOR ENGINEER JOB/OWNER Spec Sect Para System No. Submitted By Date Approved Location Date ✓ctaulic www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 06.06_1 REV J * CARBON STEEL PIPE-GROOVED COUPLINGS 06.08 Reducing Coupling a STYLE 750 DIMENSIONS Max.Work Allow.Pipe Size Pressure* Max.End Load* End Se t Bolt/Nut@ P Deflect.Fr.Cit No-Size Approx. Dimensions-Inches/mm Wgt.Each Nominal Size psi Lbs. Per Pipe Inches/mm kPa N Inches/mm Cmm/ni x I Y I 2 1 350 Deg. mmlm : Inches Z Lbs. 50 x 500 0-0.07 kg 2225 0-1.8 0°-57' i 0120 3.38 528 1.88 25 .2410 17 , 2 3/8 x 22 7 11/2 1000 w vt 85 134 48 I 1 2 350 0-007 2%z 2410 4450 0-18 0 -57 0170 2-3/8x2 i 3385.28 1.882.0 2 500 .... .... .. . t 85 134 65 x 1 2215 0-007 t s 48 ; ,.w11 ,,,...,. 50 3450 9850 0-1 8 0 -47 1 4 2-3/8 x 2 i 4 00 5 93 1 88 761 mm x .,,_. ,,.,...,...�.. .. 48 3 1 2 350 1550 0-0.07 ._.. „_. ... x..... �. ._... ,., 102 151 j 1 1 4 50 2410 6900 0°-4T 0.16 438 z T I 3 0 18 14 1 2-' x23/4 6.63 ; 188 I 4.6 2 350 111 168 48 80 X 50 1550 0-007 ; 21 2410 6900 0 18 0 -39' 110.3 1 2-174x 4 75 2 3/a 713 1 88 4 9 2 5 500 3250 , 121 181 I 48• 1.,m 2 2 0-0.07 c ° ,.»..m.,,.......� �.:..w. ,... 65 3450 tI 14460 0-18 0 -39' ��3 2-Yzx234 ' 45 713 T 788 t 4.3 88.9mm x 76.1mm 350 2475 t 0-007 ._....{...............� .._,...._.._121,. w..... 181, r 48 i 2.0 2410 11010 t 0-18 0° 39' 01,3 2-1x23/4 1 475 7.13 1 188 42. 4 2 350 „ . . . - �,. _ , _........H.. ..m_ 121 181 48 x 1550 0-013 @ 1 .25 _1 8.90 )..,. 1.1 100 50 t 2410 6900 0-3.2 1 1 -19' j 028 [ 2-5/8 x 3%4 6.25 8.90 I 225 ' g,1 2!z 25 350 2275 0-013 _J. . 0.28 ., ..w159 L.. 226 i 57 0 3.7 10125 1 -19' 625 65 2410 0-32 2-5/8x3%a ` 8.90 225 8.6 3 500 4810 0-013 . 1 159 57 3.9 226 ,...,•... .,..„.�.. 80 3450 21400 € 0-32_ 1 19' i 0.28 2 5/8 x 3 Ya ( ..600 E 8.90 t 225 6.7 114,3 mm x 76.1 mm I 350 i 2475 I 0-0.13 -_._ , € _152 226 257 3.0 1._ 2410 11014 ( 32 1 19' . 058 2-5/8x3Ya € 625 890 25 ., 3.1 5 x f 159 226 4 350 5565 ( O •.. 0- 125 100 l 2410 013 1 _3 1 02212-3k x .x718 10.70 24765 3.2 4%a k 213 112 6 x 4 350 1 5565 r 0 013 1,, 182254 6 7 150 272 100 2410 ! 24765 I 0-32 0 52 t 0 3/4x4%4 1 853 t ,.1190 575 17657 18 5 24100 t�...k. 8500 �.',.. .._... .K.. °.., `15 ... .., . 1 1 302 7 6 2 { Ii 125 • 0 0.13 37825 0 32 1 0 52 0 8 2-3/ax4%4 831 11.90 1 2.25 12.9 1651 mm X 4 .. - y..13 . 02115 9 350 5565 0-0.13 .1:, • 30290 57 100 2410 1 24765 0-3.2 1 0 55 16 2-3kx4%a 863 1 225 ',. 152 '. 8 6 I +..�...... .._.....,,..�... ...,m._,. _..¢..,� 219 �_. �. . 200 x 350 12060 0-0.13 t � 0.13 t 302 57 � .w..6.9 150 1 2410 53645 0-3.2 ' 0 -38' 2-7/8 x 5 10.81 14 88 , 2.50 t 224 i li, 2191 mm x 350 # 11610 „.,..,,., ,.....,.�.,..,.. ` 165.1 mm s 0 0.13 1 75 2410 # 51645 I 0 3.2 0" 38 ' 0.13 t 2-7/8 x S 10 75 378 10.2 �^ 1488 250 i 23 10 11 378 8 3502 9 273 1,. ., I 64 I 10.5 .. 273 x 2191 20450 0 0.13 2410 90970 t 0-3.2 1 0° 25' ' 0'9 2-1 x 5 1312 I 1726 p 262 1 314 I Style 750 Reducing couplings should not be used with end caps(#60)in systems where a vacuum may be developed.Contact Vic aulic for details.38 1 67 1 142 *Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe.Maximum working pressure rating based on larger pipe size. Maximum End Load rating based on smaller pipe size.WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe.Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by:50%for 944-31/2720-90 mm;25%for 47100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. WARNING:Depressurize and drain the piping system before attempting to install,remove,or adjust any Victaulic piping products. Y r-Zi Y 4-2-, � � I- N/ i r,i 111 1 alno �_ 1`_.,f www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.© RESERVED. 2012 VICTAULIC COMPANY.ALL RIGHTS 06.08 2 jetaulie REV 1 • CARBON STEEL PIPE-GROOVED COUPLINGS 06.08 Reducing Coupling STYLE 750 FLOW DATA HEAD LOSS The head loss across Style 750 Reducing coupling is very small and is essentially the same as for standard short body reducing pipe fittings. Equivalent lengths of standard weight steel pipe are shown in the tables.All data is based on water flowing at ambient temperature. FLOW REDUCING FLOW EXPANDING Equiv.Pipe Equiv.Pipe Size Length Size Length Nominal NominalSize Sm.Dia. Size Sm.Dia. Inches/mm Feet/m Inches/mm Feet/m 1 ,` 2 27 50 25 i 2 x 1 5.9 25 x 50 0.8 1 20, ...,._ ' „_ 2 .rw'9 40 I 0.6 X 40 50 06., I 2 ....... 2 1.9 _.,._ 2 x 21/2 1/2 65 x 50 0:6 .,.0 50 w a. 65 .�. 03 ...,.I 76.1 mm x 2 1.9 50 06 761mm 03 3 x 2 3 3.5 5.5 3 1.1 80 50 1.7 ,... 65 1.2 100 0.9 _.„_.w 3.8 21/23 25 88.9mm X 76.1 mm 1.2 65 x 80 I 0.8 4......... ,. 2._ 6.0. 4._,3. 0 100 x 50 1.8 100 I 0.9 2,5 _I.-..m6.0. .__ 2.5 18 76.imm x 88.9mm 08 3 6.0 114.3mm1 3.0 80 18 09 „_ ., 6.0 3 x 4 r 2.5 5 1143mm' x 761mm gp 100 8 18 �. .: w_. . _ 45 1. 3 3 125 x 100 09 100 x 125 1.0 v....r.l 6 4 6.0 6 i 46 150 x 100 1.8 150 14 _. _ _. 4.6 5 45 1651 mm 125 1 1.4 .4 ..,__. .... .,, .. . . _ _.._,....._,. 4 6.0 5X 165.1 mm X 100 1. 8 125 150 0:7 .. 8 6 7.36 x g 6.0 x 200 150 22 150 200 12 7.3 54 1651 mm x 2191 mm 7 65 219.1 mm X 165,1 mms 2.23 i .. 10 8 8.7 8 10 1. 6.3 273 x 2191 s 2.65x 2191 273 192 www.victaulic.com �CtaUliid VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2012 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 06.0$_3 REV J CARBON STEEL PIPE-GROOVED COUPLINGS 06.08 Reducing Coupling STYLE 750 INSTALLATION Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product you are instating.Handbooks are included with each shipment of Victaulic products for complete installation and assembly data,and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. For complete contact information,visit www.victaulic.com 06.08 1536 REV J UPDATED 08/2012 VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.0 2012 VICTAULIC COMPANY ALL RIGHTS RESERVED. 06.08 ✓ctaul�� Victaulic® Flexible Coupling ✓ctaulid Style 75 06.05 - - NA• • Victaulic RX roll sets must be used when grooving light-wall/thin-wall stainless steel pipe for use with Victaulic Couplings. • Failure to use Victaulic RX roll sets when grooving I" ! stainless steelpipe may cause joint light-wall/thin-wall failure,resulting in serious personal injury and/or Exaggerated for clarity property damage. Approvals/Listings ® NOTICE •FM PCB0Victaulic RX grooving rolls must be ordered See Victaulic publication 10.01 for details separately.They are identified by a silver color and See Victaulic publication 02.06 for portable water approvals if applicable. the desi:nation RX on the front of the roll sets. Product Description Style 75 is available where moderate pressures are expected or weight considerations are a factor. Up to 50% lighter in weight than the Style 77,the Style 75 coupling is recommended for service up to 500 psi/3450 kPa depending on size. Housings are cast in two identical pieces in all sizes. Hot-dip galvanized and special coatings are available for all sizes. The Victaulic standard flexible coupling offering for grade "EHP" or "T" gaskets is the Style 177 installation-ready flexible coupling. For all available sizes,the Style 177 is the standard flexible coupling Victaulic supplies in North America for piping systems using Grade "EHP" or"T" gaskets. Contact Victaulic for further details. Performance data presented in this document is based on use with standard wall,carbon steel pipe. For use with stainless steel pipe, please referencepublication 17.09 for pressure ratings and end loads.When used on light wall stainless steel pipe,the Victaulic RX roll set must be used to roll groove the pipe. For further information regarding roll grooving stainless steel, refer topublication 17.01. Job/Owner Engineer .-- Spec Section System No. Paragraph Location __..... Approved Contractor Date Submitted By 111111111111111111111111111 Date victaulic.com I Couplings I Flexible I Style 75 I Publication 06.05 06.05 1470 Rev 0 Updated 09/2014 ©2014 Victaulic Company.All rights reserved. \iCtaUlid 1 victaulic.com I Couplings I Flexible I Style 75 I Publication 06.05 Material Specifications Housing: Bolts/Nuts: Ductile iron conforming to ASTM A-536,grade 65-45-12. Heat-treated plated carbon steel,trackhead meeting the Ductile iron conforming to ASTM A-395,grade 65-45-15, physical and chemical requirements of ASTM A-449 and is available upon special request. physical requirements of ASTM A-183 Housing Coating:(specify choice) ❑ Standard: Orange enamel. ❑ Optional: Hot dipped galvanized and others. Gasket: (specify choice') NOTE:Additional gasket styles are available.Contact Victaulic for details. ❑ Grade"E"EPDM EPDM (Green stripe color code). Temperature range—30°F to+230°F/-34°C to+110°C. May be specified for cold and hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. UL Classified in accordance with ANSI/NSF 61 for cold +73°F/+23°C and hot+180°F/+82°C potable water service and ANSI/NSF 372. NOT COMPATIBLE FOR PETROLEUM SERVICES. ❑ Grade"T"Nitrile Nitrile(Orange stripe color code). Temperature range 20°F to+180°F/29°C to+82°C. May be specified for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range. Not compatible for hot water services over +150°F/+66°C or for hot dry air over+140°F/+60°C. 1 Services listed are General Service Guidelines only.It should be noted that there are services for which these gaskets are not compatible.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service guidelines and for a listing of services which are not compatible. 06.05 1470 Rev 0 Updated 09/2014 0 2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓otaulic victaulic.com I Couplings I Flexible I Style 75 I Publication 06.05 Dimensions Style 75 I '�1 ,:I I 1_ Ci!411 � Ir11 Actual Maximum Maximum Allow. Dimensions Approx. Nominal Outside Working End Pipe End Deflection from Weight Size Diameter Pressure 2 Load 2 Separation3 Centerline3 Bolt/Nut4 X Y Z Each Pipe inches inches psi lbs. inches Per Cplg. inches/ft. inches inches inches lbs. mm mm kPa N mm Degrees mm/m (No.)size inches mm mm mm kg 1 1.315 500 680 0-0.062°-43, 0.57 2-34 x 2 2.38 4.27 1.77 1.3 25 33.4 3450 3025 0-1.6 48 61 108 45 0.6 1'/a 1.660 500 1080 0-0.06 ° 0.45 2-3/a x 2 2.68 4.61 1.77 1.4 2-10' 68 117 45 0.6 32 42.2 3450 4805 0-1.6 38 1 1h 1.900 500 1420 0-0.061.-56' 0.40 2-3/a x 2 2.91 4.82 1.77 1.5 40 48.3 3450 6320 0-1.6 33 74 122 45 0.6 2 2.375 500 2215 0-0.061°-31' 0.32 2-3/a x 2 3.43 133 8748 0.8 522 1.88 1.7 50 60.3 3450 9860 0-1.6 26 2'/z 2.875 500 3245 0-0.0610-15' 0.26 2-3/s x 2 3.88 5.68 1.88 1.9 65 73.0 3450 14440 0-1.6 22 98 144 48 0.9 3.000 500 3535 0-0.061°_12, 0.26 2-3/a x 2 4.00 5.90 1.88 1.9 76.1 mm 76.1 3450 15730 0-1.6 22 102 150 48 0.9 3 3.500 500 4800 0-0.061,-2' 0.22 2-'/z x 2 3/a 4.50 7.00 1.88 2.9 80 88.9 3450 21360 0-1.6 114 178 48 1.3 3' 4.000 500 6300 0-0.0600-54' 0.6 2_'/:x 2 3/a 5.00 7.50 1.88 2.9 90 101.6 3450 28035 0-1.6 127 191 48 1.3 4 4.500 500 7950 0-0.1310_36' 0.34 2-1/e x 2 3k 147 20034 2.13 4.1 544 1.9 100 114.3 3450 35380 0-32 28 4250 450 6380 0-0.131°�1, 0.35 2-12 x 70 5.55 7.79 2.13 3.7 108.0 mm 108.0 3100 28395 0-3.2 29 141 198 54 1.7 41/2 5.000 450 8820 0-0.130.25 6.13 9.43 2.13 5.5 1,-26' 120 127.0 3100 39250 0-3.2 21 2-5/e x 3'/a 156 240 54 2.5 5 5.563 450 10935 0-0.130.27 2-3/s x 3 1/a 6.88 10.07 2.13 5.8 1.-18' 175 256 54 2.6 125 1413 3100 48660 0-32 23 5250 450 9735 0-0.131°-21' 0.28 2-16 x 82.5 6.55 9.37 2.13 6.0 133.0 mm 133 0 3100 43325 0-3.2 24 166 238 54 2.7 5.500 450 10665 0-0.13 1°-18' 028 2_s/a x 3'/a 6.80 9.59 2.13 6.3 139.7 mm 139.7 3100 47460 0-3.2 24 173 244 54 2.9 6.000 450 12735 0-0.131°-12' 0,8 2-5/e x 3'/a 7.38 10.48 1.88 6.2 152.4 mm 152.4 3100 56670 0-32 187 266 48 2.8 6 6.625 450 15525 0-0.131.-5' 0.23 2-3/s x 3'/a 8.00 11.07 2.13 7.0 150 1683 3100 69085 0-3.2 18 203 281 54 3.2 6.250 450 13800 0-0.13 1° 9, 0.24 2_16 x 82.5 7.63 10.49 2.13 6.8 159.0 mm 159.0 3100 61405 0-3.2 20 194 266 54 3.1 8 8.625 450 26280 0-0.1300_50, 0.18 14 3k x 4,/a 10.34 13.97 2.13 12.4 200 219.1 3100 116945 0-32263 355 59 5.6 2 Working Pressure and End Load are total,from all internal and external loads,based on standard weight(ANSI)steel pipe,standard roll or cut grooved in accordance with Victaulic specifications.Contact Victaulic for performance on other pipe. 3 Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled.These figures are maximums;for design and installation purposes these figures should be reduced by: 50%for 3-3 1/"/20-90 mm;25%for 4"/100 mm and larger. 4 Number of bolts required equals number of housing segments. General Notes Metric thread size bolts are available(color coded gold)for all coupling sizes upon request.Contact Victaulic for details. WARNING:FOR ONE TIME FIELD TEST ONLY,the Maximum Joint Working Pressure may be increased to 11/2 times the figures shown. 06.05 1470 Rev 0 Updated 09/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 3 jctaulic victaulic.com I Couplings I Flexible I Style 75 I Publication 06.05 Installation Reference should always be made to the I-100 Victaulic Field Installation Handbook for Note the product you are installing.Handbooks are included with each shipment of Victaulic This inprstallectd in accordancehall e withithec by Victaulic Victaulicc or to Calla ion assembly inst.Allt products products for complete installation and assembly data,and are available in PDF format to be installed in current installation/assembly instructions. on our website at taula. Victaulic reserves the right to change product specifications,designs and standard Warranty equipment without notice and without incurring obligations. Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic®is a registered trademark of Victaulic Company. 06.05 1470 Rev 0 Updated 09/2014 C 2014 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctaulic 1 , tA MAYTY ® SIDEWINDER® FOR WOOD -Horizontal Application Product Features Application No pre-drilling required. Not less than 2"nominal width (1-1/2")up to 3-112"pipe;not less than •Quick to install using the Sammy . 3"(2-1/2")nominal width 4"S,5"pipe Nut Driver with an 18V cordless „•,�,,, * H Floor Joist _ drill/driver. # Minimum 2-112"from bottom for J branch lines.Minimum 3"from bot- tom for main lines.Exception:This •Saves time from traditional W ' methods. requirement shall not apply to 2"or W thicker nailing strips resting on top of steel beams. ' •Reduces installation costs. .. .., Cl) _ . '. •Made in the U.S.A. : ; i i T. Composite I Truss ' ConsulCrus;ma jI Ct s for ecomr^eid d.nSt0Va6on poin[. '?ret:n I r;may Re r,tpnred for Model S d,'G 25 4',",Too ava=ble o'pay,11 atoh a video demonsha6on of W i t"�,,;I wWww.ilwbuildex.com W Screw Ultimate UL Test Box • Cas° Rod Part Model Cl) Approvals Size Number Descriptions Pullout(lbs) Load(lbs) Qty Qty HORIZONTAL MOUNT 114 x 2 1725(Fir) 25 125 114 8019957 SWG 200 v 125 114 x 2 1725(Fir) 1050 25 :741 I SWG 20 e — w 318 8021957 a .T � ^ I'v 4 ` ' , ,y r '5 1500 25 125 2 3/8":••• 18* 802illti2925 SWG 25-380 318 x 2 112 2249(Fir) #14 SW Red _ 'lltv °v r :. n. *4'4Nut Driver LuLu Part#8114910 *May require pre-drilling;consult joist manufacturer. Z SAMMYS SWIVEL HEAD' FOR WOOD - Swivel Application C Product Features V Application • % ,ro,,,o„ ••Eliminates distortion of threaded rod. womcarm °P" •Accommodates up to 3 1/2"x 12 pitch roof. •• ••Allows 17°deflection from vertical. Cl) t ,u„a„-+ •Saves time from traditional methods. W „" •Reduces installation costs. MAX •Made in the U.S.A. 0 �� Cl) NAterGER �� h Rod Part Screw Ultimate UL Test Load FM Test Min Box Case W Approvals Model Descri tions Pullout(lbs) (lbs) Load(Ibs) Thickness Qty Qty V Size Number P '` — SWIVEL MOUNT 1050 1475 25 125 V� #14 Black `4'� 318" 8139957 SH-GST 20 ,41/4,,x 2 1257(Fir) , 7 v 47 ; , 51:0 ,. =Nut Driver — E3a * << fif� .., �� Part#8113910 =e. x' 1903 Dim Lumber 1500 25 125 v�, 318'* 8269957 SH-GSTICST 20 5116 x 1-3/4" 1406 @ 45 off vertical 850 @ 45 Dim.Lumber J * 44®V 1 x� 1x54 Pxr. q" 'a k $ b4ve4cI • „ 5 ' `� � v— jril" CSlU tfi4..„.n,,,,,,,x 34 48, fTv, . ri€ T .° r 1 m ,, ., wo, , .i May require pre dolling;consult joist manufacturer. #14 SH Orange a Nut Driver Part#8273910 Q 5 To find a distributor near you.call 800-BUILDEX SA3t0, A ; IFO� . ` , ,A SAMMYS® FOR WOOD - Vertical Application Application Product Features Not less than 2"nominal width Wood Flooring (tom trz)♦ •No pre-drilling required. •Quick to install using the Sammy Not less than Nut Driver with an 18V cordless 3"nominal t I thickness(2-1/2") drill/driver. (depth or side Wood Joist J f vertical member) sissicimmumw- •Saves time from traditional methods. Double Sheetrock ;� Fc vertr3� Ceiling irstai in cnt r suer Face_ •Reduces installation costs. lr mum eroee�rert into Lase "% -' •Made in the U.S.A. as 'f- rnaleraI for NFPA iJoompl ance. ' Composite/Truss Cons'I'r„ .ill rd. [or i � rt ammecu i nn.a laror lanf. ;r S. i r 1:9m,'o y _r,ytuieo for 027 <. 27 3" Tao! r s-N2 oo page I 1..:. 7 Watch a video demonsbadon at ;' wwvaiwbuildexcom lotimabs) LoUaLd Tsbts) LoFMad T(elbsst) BQotYx Case Approvals Riozed Number Model Descriptions PuUll VERTICAL MOUNT 1/4" 8002957 GST 100 1/4 x 1" 210 (7/16"OSB) 670 (3/4 Ply) 25 125 ...W 3v /� - 49#7 ` a a 1/4 8004957 GST300 1/4� ;A e -, 25 r snx �- 2060 (Fir) 25 125 4.„Q.-1,!:?, 3/8" 8008957 GST 20 1/4 x 2" 1760 (Fir) 5 " '*"�'� 850 25 125 1475 Q 3/8 8009925 GST 25-380 3/8 x 2-1/2" 2113 (Fir) 1500 #14 Black Ln r25 125 ata 7r� c a " - AAA ° r Nut Driver 4, 3/8" 8069925 GST 30-SS 1/4 x 3 1 Part#8113910 � �' J 1 2060 (Fir) 25 125 1/2 8013925 GST2"x. 1/4 x 2 1760(Fir) ' e2i� itgt� - 25 125 —. 1/2" 8015925 GST 3 1/4 x 3" 2275 (Fir) 12 25 12' 5 #14 SW Red Nut Driver Part#8114910 \,..9 auuE na u.s.a y oHS SPECIAL NUT DRIVER SYSTEM:The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time.When the face of the driver comes into contact with the material you are installing into,continue drilling until nut driver spins free.Installation is then complete.Warranty requires the use of the appropriate nut driver for installations. For the most up to date information,visit www.itwbuildex.com 4 • Z47/30 00 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 514 CPVC - COPPER #905 #906 STEEL OFFSET HANGER 40.0Ili .� 31 1 A - - r _.=_________ ..... SIZE-SYSTEM PIPE: 3/4"thru 2" 4, O MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. LISTING/APPROVAL- Hanger/Restrainer COOS 203-EX 4231,EX 2551 M1111 I■� PATENT-No.6,648,278. �� FUNCTION- Support horizontal piping: CPVC,Copper or Steel. Provides listed vertical/horizontal restraint and prevents upward movement of pipe from pendent sprinkler discharge. Hanger/ %�✓ Stabilize vertical piping. �— Stabilize INSTALLATION- Per these instructions Restrainer ''��� �� including NFPA 13, 13R,13D and CPVC manufacturers instructions. Install on horizontal or vertical mounting surface. �= Snap over pipe then squeeze strap back allowing pipe to slide freely. When #905 threads are exposed in wood,install#906 backing nut. QV FASTENERS-UL Listed per NFPA 13 WOOD- CPVC pipe-#905 screw-no pre-drill. Copper and Steel pipe-#14 SMS or 1/4"xl 1/2"lag screw- no pre-drill. Thru 5/8"gypsum board- 1/4"x 2"lag screw. STEEL-min. 18 GA.-CPVC,Copper and Steel pipe- 1/4"or#14 Tek Screw. • o • p CONCRETE:Required minimum load each fastener= 5(wt) 2 501bs. 4 0 FEATURES * 1 1/2"Offset-loose fit allows pipe to slide. *Common center-line for 3/4" and 1". .' . *Offset edge eliminates abrasion.*AFCON#905 screw included-5/16"hex head. IllgaXv ORDERING-Part#and pipe size. AFCON#906 backing nut sold separately. Specific AFCONproducts are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. OT t against nBe advisedot mnufacturedlorsold by AFCON.AFCON shallNOT be ableeuunder any circumstancess whatsoever for anydirectfailure or Indirect,incidental or consequential roducts when used in combination damages of any kind,including but not systems limited to loss of business or profit,when non-AFCONproducts have been,or are used. ,F.,CAP 11/13 .11d7g0§.§) P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 515 CPVC DOUBLE OFFSET HANGER Hanger/Restrainer REINK 0 Io SIZE-SYSTEM PIPE:3/4"and 1" MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. LISTING/APPROVAL- .„,(2.203-EX 4231 PATENT-No.6,702,236 FUNCTION-Support horizontal CPVC pipe. Provides listed vertical/horizontal restraint and prevents / Hanger/Restrainer upward movement of pipe from pendent sprinkler discharge. INSTALLATION- Per these instructions including13R, NPFA 13, 13D and CPVC manufacturers ins Install on horizontal or vertical instructions. FASTENERS-UL Listed per NFPA 1mounting surface. #904 screw in wood-no pre-drill. FEATURES *Double 1 1/2"offset *Common center-line for 3/4"and 1". *Offset edge eliminates abrasion. *Required AFCON#904 screw included-3/8"hex head. ORDERING-Part#and pipe size. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCONproducts have been,or are used. 11/13 . 7./ 71g'00 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 510 CPVC - COPPER - STEEL HANGER Fastener m. SIZE Q. 3/4 2.125 1 2.312 41 , 1 1/4 3.170 1 1/2 3.400 2 4.010 ® 2 1/2 4.320 3 5.320 SIZE-SYSTEM PIPE:3/4"thru 3" MATERIAL-Carbon Steel. FINISH-Mil.Galvanized. LISTING/APPROVAL- ° a"203-EX 4231,EX 2551 LISTE FUNCTION-Support horizontal piping: CPVC,Copper or Steel. Size 3/4"-2"Prevents upward movement of pipe from pendent sprinkler discharge. Stabilize vertical piping. INSTALLATION- Per these instructions including NFPA 13, 13R, 13D and CPVC manufacturers instructions. Install on horizontal or vertical mounting surface. FASTENERS- UL Listed per NFPA 13 in WOOD: 3/4"-3"CPVC pipe-#905 screw-no pre-drill. 3/4"-3"Steel and Copper pipe-#14 x 1 1/2"SMS or Restraint 1/4"x11/2"lag bolt-no pre-drill. in STEEL-min. 18 GA. 3/4"-3"CPVC,Copper and Steel pipe-1/4"or#14 Tek Screw. FEATURES i *Offset edge eliminates abrasion. pipe installation. i *Retainer dimples secure hanger to i e during Hanger Stabilize *Required AFCON#905 screw included-5/16"hex head. -� ORDERING-Part#and pipe size. / I � ALSO1111 BE USED TO REPLACE-#500 Pipe Strap CAN #520 Tin Strap n a Specific AFCONare exclusively designed ONLY other listed brace, assembly Beadvised the followingwarranty con will apply.DISCLAIMER AFCON NOT warrant against the failuref its products when useed incombinatiowith other products,partsorsystems - not manufactured or sld by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCON products have been,or are used. '^ '. - • 7ffi00� P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 300 RING HANGER ,I 1 thru 4 Inch pipe 1/2&3/4 Inch pipe LISTED FOR STEEL/CPVC 5 thru 8 inch pipe NFPA 13 UL PIPE ROD 1 WT. 5 W7+250 TEST LOAD 1 3/8 30.75 403.75 750 11/4 3/8 43.95 469.75 750 11/2 3/8 54.15 520.75 750 SIZE-ROD-3/8"or 1/2" SIZE-SYSTEM PIPE- 1/2"thru 8" 2 3/876.95 2 1/2 3/8 118.35 841 841 634.75 750 ,75 850 MATERIAL-Carbon Steel,Mil.Galvanized to G-90 spec. 3 3/8 162,30 1061,50 1050 LISTING/APPROVAL- 4 3/8 246.00 1480.00 1500 C �L Uf 5 1/2 349.45 1996.75 2000 IIVi 203-EX 2551 1"-8" 6 1/2 476,35 2631,75 2650 FM•Approval guide-1"-8" 8 1/2 711.00 3805,00 4050 OSHPD OPA-0601 See Website. CONFORMS WITH:Federal Specification WW-H-171E,Type 10. Manufacturers Standardization Society ANSI/MSS-SP-58 Type 10. MAXIMUM TEMPERATURE-650°F. FUNCTION-Pipe hanger component of an AFCON hanger. To support steel,CPVC or copper pipe. INSTALLATION-Per NFPA 13, 13R, 13D,these instructions and the CPVC or copper pipe manufacturers instructions. PIPE B pp p p r1 8793 2.5259 FEATURES- TT 11/4 2.1382 2.7650 * Sized and listed exclusively for use with#310 Surge Restrainer. 11.2 2.2673 2.9'49 * Band edge is offset for EASY pipe insertion. A a 2 26946 3.25'6 * Custom fit swivel nut for better retention in ring. 2 3/2 3.7945 4.311 3 3.]845 4.4317 ORDERING-Part#,pipe size. 4 4.3582 4.9992 \i. 6 6.0668 6.8180 8 7,5768 8.3290 � M 11/09 • .. 7: 71g 00 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 077 ATTACHMENT FITTING LOCKING 17/32" 17/32" ,4414r: O, e dig -- e 47, e 0 ikt I 0_ 077D DUCTILE BASE PLATE 077S STEEL BASE PLATE SIZE-BRACE PIPE: 1"and 1 1/4"Sch.40 MATERIAL-Carbon Steel,Ductile Iron or S.S.(Type 304). FINISH-Plain or E.G. LISTING/APPROVAL- °0'"203A-EX2625 FM FM Approved-1950 OSHPD See Website. u FUNCTION-Structure attachment fittingof an AFCON swaybrace assembly. �® os Max. Horizontal Load Y cyano Sway brace assemblies are intended to be installed in accordance with Size 1-1 1/4 I 2015 NFPA 13 and the manufacturer's installation instructions. INSTALLATION-Per these instructions including NFPA 13 or FM 2-8. Load rating-see chart. ASSEMBLY Combine with proper AFCON components-see disclaimer below. Insert brace pipe thru fitting near pivot bolt. FM Max.Horizontal Load Tighten set bolt until head contacts bracket. FEATURES 30-44° 45-59°60-74°75-90° *Swivel allows attachment at any angle. *Visual inspection,verifies proper installation. Size 1-1 1/4 630 870 1620 1810 *Larger fastener hole available.-Consult factory. ORDERING-Part#,size-brace pipe and finish. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used m combination with other products,parts or systems not manufactured or sold by AFCON AFCON shall NOT be liable under any circumstances whatsoever for any d rect or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCON products have been,or are used. 9/14 .. f/ 70100 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 411 SWAY BRACE FITTING Part#077-, p 1 7Part#078 SIZE-SYSTEM PIPE:Nominal Pipe Size ���\♦ i Sch.40 Steel 1"- 12" � I `.t / Sch. 10 Steel 1 1/4"- 12" Sch.7 Steel 2"-6" MATERIAL-Carbon Steel or S.S.(Type 304) FINISH-Plain or E.G. PATENT-No.7,140,579 LISTING/APPROVAL ®Listed Max.Horizontal Load 1"-10" 2765 c®us 203A-EX 2625 q© FM Approved-1950 12" 3740 UST Ell FUNCTION-Longitudinal fitting of an AFCON sway brace assembly. Sway brace assemblies are intended to be installed in accordance with NFPA 13 and the manufacturer's installation instructions. ©certired Max.ASD Horizontal Load INSTALLATION- Per these instructions SZesm Sch. 30°-44" 45°-59° 60°-74° 75°-90° including NFPA 13 or FM 2-8 1"-1 1/2" 10-40 420 510 570 Load rating-see chart. 2"-3" 7-40 860 1030 1150 ASSEMBLY-See drawing. 4" 7-ao 860 1030 1150 Combine with proper AFCON components-see disclaimer below. s" 7-a0 2220 1150 3040 Align brace member parallel to face of 411 fastener flanges. 8" 10-40 1340 1620 1810 Tighten 1/2"bolts until fastener flanges connect. FEATURES * Patented-design eliminates bending of fastener flanges during installation. * Patented-design prevents over tightening on system pipe. * Improved assembly-fastener flanges connect for superior strength. * Visual inspection-proper installation when 411 fastener flanges connect. ORDERING-Part#,size-system pipe and finish. Specific AFCONproducts are exclusively designed to be compatible ONLY with other AFCONproducts including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used in combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCON products have been,or are used. 5/14 • .. 23/g 00 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 078 ATTACHMENT FITTING LOCKING ® Part#077 ', 9/16 Dia tqb 0 1 1 "‘ \ r Part#078 III ( 1 Part#410/411- SIZE-BRACE PIPE: 1"and 1 1/4"Sch.40 MATERIAL-Carbon Steel or S.S.(Type 304). FINISH-Plain or E.G. °`<j LISTING/APPROVAL- Da's 203A-EX 2625 <> FM Approved-1950 OSHPD See Website. MED FUNCTION-Structure attachment fitting of an AFCON sway brace assembly. Common transition component with 411 sway brace fitting-see drawing Sway brace assemblies are intended to be installed in accordance with NFPA 13 and the manufacturer's installation instructions. INSTALLATION- Per these instructions including NFPA 13 or FM 2-8. 41 Max. Horizontal Load Load rating-see chart. 30°-44° 45°-59° 60°-89° 90° DO NOT BEND-If angle required use part 070,075,076 or 077. 1008 1425 1745 2015 ASSEMBLY Combine with proper AFCON components-see disclaimer below. Insert brace pipe thru fitting near pivot bolt. Tighten set bolt until head contacts bracket. © Max. Horizontal Load FEATURES 30°-44° 450-59° 60°-74° 750-90° *Visual inspection,verifies proper installation. 430 620 760 940 *Bolt hole fits 410/411 sway brace fitting. ORDERING-Part#,size-brace pipe and fmish. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners,resulting in a listed sway brace,restrainer or hanger assembly. Be advised the following warranty restriction will apply.DISCLAIMER-AFCON will NOT warrant against the failure of its products when used m combination with other products,parts or systems not manufactured or sold by AFCON.AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect,incidental or consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCON products have been,or are used. i 4 4/14 �00: 0 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 400 RISER CLAMP IRON PIPE A PIPE s le— "" "" C--�+� SIZE A B C STOCK MAX.REC. = SIZE LOAD LBS. 1 1/2" 10 3/8" 3/8" 1 1/2" 3/16"x1 1/4" 255 ool i tit tat 2" 10 3/4" 3/8" 2" 3/16"x1 1/4" 255 o m 2 1/2" 11" 3/8" 2 1/8" 1/4"x1 1/4" 390 1s1 tlli 3" 12" 3/8" 3 1/4"x1 1/4" 530 i \ 3 1/2" 13" 1/2" 3 5/16" 1/4"x1 1/4" 670 B B 4" 13 1/2" 1/2" 3 3/8" 1/4"x1 1/4" 810 5" 141/2" 1/2" 4" 1/4"x11/2" 1160 6" 15 1/8" 1/2" 4 1/2" 1/4"x2" 1570 8" 18 1/2" 5/8" 5 13/16" 3/8x2" 2500 NOTE:MAXIMUM TEMPERATURE:650°F hi SIZE- 1/2 thru 20 inch pipe. 40 MATERIAL-Carbon Steel. `` FINISH-Plaigl .,H.D.G.and S.S. LISTING/APPROVAL- EX 2551 11/2"-8"pipe. OSHPD OPA-0601 See Website. 16i, I) CONFORMS WITH: Federal Specification WW-H-171E,type 8,3/4 thru 20 inch,and .��` Manufacturers Standardization Society SP-69,type 8. FUNCTION-Used for supporting vertical piping. ORDERING-Part#,pipe size and finish. t CAD 1/08 IPS CARBON STEEL PIPE-FIRE PROTECTION PRODUCTS10..96 ® Riser pp 00 FM FireLock® Zone Control Module SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS SERIES 747M Designed for NFPA 13 commercial requirements,the Victaulic Series 747M Zone Control Riser Module features a cast body,and is compact and easy to install in zoned wet sprinkler systems. The integrated module body consists of a shut off valve,test and drain valve combination and different orifice sizes(K factors),a UL Listed and FM Approved Flow Switch,and a Pressure Gauge.The Series 747M FireLock Zone Control Riser Module is available in sizes from 1 rV4 through 6'/32mm-150mm with grooved ends on the main pipe for installation in the horizontal or vertical up-flow positions with UL Listed,FM Approved Victaulic grooved couplings.11/4-2"modules have an NPT drain port.21/z-6'modules have a grooved drain port. The Series 747M FireLock Zone Control Riser Module is FM Approved and UL and ULC Listed STYLE 747M for working pressures up to 365psi/2517kPa.An optional pressure relief valve kit is available PATENT PENDING for all sizes.The Pressure Relief Valve is FM Approved and UL and ULC Listed for working pressures up to 175psi/1200kPa. r Aprx.Weight DIMENSIONS Dimensions Inches/mm Each Module Body Sae ,, .. ,ie us B i ar' iaMete Grain- , .. itv. s f15.2 Rff "NIP1 r/a i1.660 1 § 11.45 7.20 577 • 3.50 10.05 7.48 2.54 i 69 '. 32 42.2 33.4 $ 290.8 182.9 146.5 88.9 255 3 190.0 • 64.5 D r JLAP I C 1 t/z _ 1 ' 1145'$" 7 32 i 5.77 3.50 i ta 10 05; 7.48 2.54 15.5 1.900 7.0 _.. � F 483 33.4 290.8E 185.9 , 146.5 88 9 i 255 3 ; 190.0 64 5 40 ® 2 2 375 4 1 z 11.45 £ 7.55 I 5.77 3.50 I 10.05 I 7.48 § 2.54 i 19.9 .._., f- " �//� 50 603 334 t 290.8 191.8 ' 146.5 88.9 i 255.3 190.0 I 64.5 9.0 ... 2Yz 2875 1 Ya 12.00 8.41 6.18 4.25 9.76 r 11.87 4.25 t 22.7 G 65 73.0 42 305 214 157 108 248 302; 108 i 103 E � 23.2 5 4,. 3 3.500 p 1'/. f 12.00 ¢ 9.42 i 6.18 4 25 i 9.76 r 11 87 r 4.251 10.6 A 80 I' 889 t 42 i 305 . 239 157 3 108 . 248 r 302 108 1 A-2"/32-50 mm Nominal Sizes 4 i 4500i 12.00 990 , 725 1 5.00 1015 12.62 ; 421 30.3 2 8 100 1143 1 60 9 305 ` 252 184 t, 127 258 321 107 1...__,,. } ...._' 2I 6.00 1015 1 13.62 4.24 ` 36.7 6 i I 2 r 1305 1276 , 8.3111 I 154 258 i 346 107.7 16.7 150 � 1683 1 60 f B Orifices R "` ?� �1 Nominal Size 1inchesIl il D 1.25 ....111110.1.1133311....111111.111111' 11' �� I 1.5 � 1111111.11111111.11.111111111 l L; �: II 2 = K5.6 K6.9 K8.0 K11.2 25 ( i 3 K5.6K6.9K8.0K11.2 E4 K5.6K6.9K8.0K11.2K14.0K16.8 11 6 K5.6 K6.9 K8.0 K11.2 K14.0 K16.8 A 21/2-6"/65.0-150 mm Nominal Sizes Nominal Size Drain Type Drain Size (Valves shown above in the"test"position. inches Shown with optional Pressure Relief Valve Kit _ -- -- Hose Clamp NPT 1 '""""`""'" 1.25 d.._ .. 1.5NWT 2 25 NPT. n- 1 # Grooved 1 Yd 7 4 Grooved 3 Pressure Relief Valve Illii----,,,,,,,,,... Hose Clamp Grooved__ a _ . .. Grooved 6 e Drain Tubing ` Close Nippl Elbow Barbed Fitting Optional Pressure Relief Valve Kit Detail CONTRACTOR ENGINEER JOB/OWNER Spec Sect Para System No. Submitted By Date Approved Location Date \iCtaulid www.Victaulic.com VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. 10,96_1 REV_I • FIRE PROTECTION PRODUCTS—DEVICES 10.96 FireLock® Zone Control Riser Module SERIES 747M MATERIAL SPECIFICATIONS Module Body:Cast from ductile iron conforming to ASTM A-536,grade 65-45-12 with integral Victaulic grooved ends.Finish:orange enamel. Shut-off and Test/Drain Valve:Chrome plated brass ball,S 37700 brass clapper,416SS or 410SS shafts,Delrin orifice,virgin Teflon*,enhanced Teflon and EPDM rubber seals. *Teflon is a registered trademark of Dupont Coupling:Any UL Listed,FM Approved Victaulic IPS-sized coupling may also be used.Note: Couplings not included with product. Waterflow Detector:System Sensor Model WFD/WFDTH vane type waterflow detector with sealed retard,visual switch activation,and mechanical delay adjustment.Cover includes tamper resistant security screws and tool.Note:ULC models WFDA/WFDTHA include cover tamper switch. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. WARNING • This product must be installed by an experienced,trained installer, in accordance with the instructions provided with each valve.These instructions contain important information. Failure to follow these instructions may result in serious personal injury, property damage,or valve leakage. If you need additional copies of this product literature or the valve installation instructions,or if you have any questions about the safe installation and use of this device,contact Victaulic Company,P.O. Box 31,Easton,PA 18044-0031 USA,Telephone:001-610-559-3300. For complete contact information,visit www.victaulic.com 10.96 3089 REV I UPDATED 7/2010 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2010 VICTAULIC COMPANY.ALL RIGHTS RESERVED. ICtaUIfCr 10.96 FireLock® Check Valves ✓�taulic Series 717 & 717H 1o.os Grooved ends allow fast, easy installation with just two Victaulic couplings or the valve may be mounted l ' to flanged (ANSI CL.150)equipment using either to Victaulic Style 741 Vic-Flange®or Style 744 FireLock flange adapters on either end. Series 717 Series 717 (21/2—3'/65—80 mm) (4—127100—300 mm) , Series 717H High Pressure Check Valve (2—3750—80 mm) Approvals/Listings: cam FM vds LPCB) t� ILTED See Victaulic Publication 10.01 for more details. The FireLock Series 717 Check Valve and Series 717H High Pressure Check Valves are CAD designed for hydrodynamic efficiency and available in 2750 mm—3780 mm (Series 717H)and 2 1/2765 mm—127300 mm (Series 717)sizes. Series 717H valves are cULus Listed and FM Approved for service up to 365 psi/2517 kPa. See chart below for approved services for the Series 717 valves. In both valve designs,the single-disc mechanism incorporates a spring-assisted feature for nonslamming operation.This spring-assisted,single-disc design achieves a leak-free seal with as little as 5ft/1.5m of head. Series 717 and 717H FireLock Check Valves can be installed either vertically(flow upwards only)or horizontally.A cast flow arrow indicator is provided to assist with proper valve orientation. Both valves include upstream and downstream pressure taps. Each valve is factory-tested to the rated working pressure. For systems requiring a Riser Check option, refer to publication 10.09. Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date Check Valve I Firelock®I Series 717&717H I Publication 10.08 ✓ctaul�d victaulic.com 1 • Check Valve I Firelock®I Series 717&717H I Publication 10.08 Material Specifications: Spring:All sizes Type 302/403 Stainless Steel Housing: Shaft Plug: Ductile iron conforming to ASTM A-536,grade • Series 717H (2—3750—80 mm): Type 416 Stainless 65-45-12. Ductile iron conforming to ASTM A-395, Steel grade 65-45-15, is available upon special request. • Series 717(2 '/z—12"/65—300 mm): Carbon steel Body Coating: zinc plated Series 717H Body: Black Paint Pipe Plug: Series 717H Endface: Electroless Nickel • Series 717H (2—3750—80 mm): carbon steel zinc Series 717(2 'h—3"): PPS Coating Series 717(4— 12"): Black Paint plated Body Seat: • Series 717(4— 127100—300 mm): Carbon steel zinc plated Series 717H—Nitrile 0-ring installed into an electroless nickel plated endface Series 717(2 1—3"): PPS Coated ductile iron Series 717(4—12"): Electroless Nickel plated Disc Seal or Coating: (specify choice') ❑ Grade "T" nitrile(Series 717H Only) Nitrile(Orange color code).Temperature range—20°F to +180°F/-29°C to+82°C. Recommended for petroleum products,air with oil vapors,vegetable and mineral oils within the specified temperature range;except hot,dry air over+140°F/+60°C and water over+150°F/+66°C. NOT RECOMMENDED FOR HOT WATER SERVICES. ❑ Grade "E" EPDM (Series 717 Only) EPDM(green color code).Temperature range-30°F to +230°F/-34°C to+110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids,oil-free air and many chemical services. NOT RECOMMENDED FOR PETROLUEM SERVICES. ' Services listed are General Service Recommendations only.It should be noted that there are services for which these gaskets are not recommended.Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Discs: • Series 717H (2—3750—80 mm): CF8M Cast Stainless Steel • Series 717(2 1/2—3"):Aluminum bronze with elastomer seal • Series 717(4— 127100—300 mm): Elastomer encapsulated disc with electroless nickel plated seat Shaft: • Series 717H (2—3750-80 mm): Brass • Series 717(2 ' —3"): Type 416 Stainless Steel • Series 717(4—127100—300 mm) Type 316 Stainless Steel victaulic.com 2 ✓ctaulic Check Valve I Fireloca I Series 717&717H I Publication 10.08 Approval/Listing: Approval/Listing Service Pressures Series 717H Size cULus FM LPCB Vds 2"/50 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 2'h"/65 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 76.1 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 3"/80 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa 4"/100 mm n/a n/a n/a n/a 5"/125 mm n/a n/a n/a n/a 139.7 mm n/a n/a n/a n/a 6"/150 mm n/a n/a n/a n/a 165.1 mm n/a n/a n/a n/a 8"/200 mm n/a n/a n/a n/a 10"/250 mm n/a n/a n/a n/a 12"/300 mm n/a n/a n/a n/a Approval/Listing Service Pressures Series 717 Size cULus FM LPCB Vds 2"/50 mm n/a n/a n/a n/a 21/2"/65 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa n/a 76.1 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa up to 16bar/232 psi 3"/80 mm up to 250 psi/1725 kPa n/a up to 365 psi/2517 kPa up to 16bar/232 psi 4"/100 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 5"/125 mm up to 365 psi/2517 kPa up to 365 p si/2517 kPa up to 365 psi/2517 kPa n/a 139.7 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 6"/150 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 16bar/232 psi 165.1 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 365 psi/2517 kPa n/a 8"/200 mm up to 365 psi/2517 kPa up to 365 psi/2517 kPa up to 348 psi/2400 kPa up to 16bar/232 psi 10"/250 mm up to 250 psi/1725 kPa up to 250 psi/1725 kPa up to 1725 kPa/250 psi n/a 12"/300 mm up to 250 psi/1725 kPa up to 250 psi/1725 kPa up to 1725 kPa/250 psi n/a victaulic.com 3 ✓ctaulid --7'mm''"'mm'm.m.".......l"ll.."l.11llIl.IlI1III1IIII...IlIllllIllllIlllIlllllll. Check Valve I Firelock®I Series 717&717H I Publication 10.08 Dimensions-Series 717: A r._� A 0 u ' :IAD-i OJP 1,----- C�A...., r____B �� D E II�K-►I C� I B -►I J Imo- O K �i� i 0 iiai 011 c g W NPT Upstream Drain m %2"NPT Downstream Drain ©Y"NPT Upstream Drain 2"NPT(Drain Optional) ®'�z"NPT Downstream Drain Typical 2 1-3765-80 mm Typical 4-8"/100-200 mm Typical 10-12"/250-300 mm Actual Dimensions Nominal Outside E to E Approx. Size Diameter A BCDEJK P R Each inches inches inches inches inches inches inches inches inches inches inches lbs. mm mm mm mm mm mm mm mm mm mm mm kg 21/2 2.875 3.88 4.26 337 65 73.0 99 108 91 - - - - - - 3.6 76.1 mm 3.000 3.88 4.26 3.57 1.6 108 91 - - - - 3.6 3 3300 4.25 5.06 4.17 1.6 80 88.9 108 129 106 - - - - - - 2.0 4 4.500 9.63 6.00 3.88 2.75 2.0 100 114.3 245 152 99 3 50 51 114 89 3.35 20.0 70 89 51 114 89 85 9.1 5 5.563 10.50 6.80 4.50 125 141.3 267 173 114 - 4 7 55 1495.88 4.08104 101 123 10655 149 104 101 123 1392mm 5.500 10.50 6.80 4.50 139.7 267 173 114 - 106 55 1495.88 1044.08 101 27.03 6 6.625 11.50 106 55 149 104 101 12.3 8.00 5.00 430 2.38 6.67 4.73 150 168.3 292 203 127 - 3.89 38.0 114 61 169 120 99 17.2 165.1 mm 6.500 11.50 8.00 5.00 _ 4.50 2.38 165.1 292 203 127 114 6.67 4.7393.89 38.0 8 8.625 14.00 9.88 61 169 120 99 17.2 200 219.1.626.06 5.05 5.65 2.15 8.85 5.65 5.75 64.0 356 251 154 128 144 10 10.750 17.00 12.00 7.09 55 225 144 146 29.0 250 273.0 432 305 180 151 170 55 10.92 671 170 55 277 171 - 100.0 12 12.750 19.50 14.00 8.0645.4 300 323.9 495 356 6.91 7.64 2.51 12.81 7.73 205 176 194 64 925 - 140.0 _ 196 63.5 Dimensions-Series 717H: A •--B w� gill1111 E ®° r D R J Typical 2750 mm-3"/80 mm Dimensions Nominal E to E Approx. Size A B C D E K P Weight R Each inches inches inches inches inches inches inches inches inches inches mm mm mm mm mm mm mm lbs. 2 8.66 mm mm mm kg 6.46 3.23 1.48 3.02 2.80 50 219.8 164.1 82.1 37.5 76.7 71.0 - - 4.25 1.9 21/2 9.37 6.94 3.31 108.0 49 65 238.0 1763 84.1 2 8-� 3.38 - 4.38 13.8 6.3 42.2 86.4 85.9 76.1 mm 9.37 6.94 3.31 1.66 1113 6.3 238.0 176.3 84.13.40 338 4.38 13.8 42.2 86.4 85.9 3 9.62 7.44 353 1.911113 6.3 80 244.3 189.0 89.7 3.65 338 2010 48.5 92.7 85.9 - 117.6- 9.1 �Ctaulic° victaulic.com 4 Check Valve I Fire'oda I Series 717&717H I Publication 10.08 Flow Characteristics The charts below express the flow of water at 60°F/16°C through valve. S717H/717HR i , € I , i F� F ti � € I I I I �F Iti o }. _ L� _ L _ # 4. dI..u. . I I i € • E D. ° € ... s I € i i 1 ; I i i . %. € 1 ; z.' 10 100 woo Flow-GPM S717H/717HR 10000 ,% 7y4 ;.71,37----1-1r.7-ti ` l' IY11. .,q tF«p i 1j R « ' I b< F , Y .. € ._� I s t E� FF M € : F F R € 12 I € € F l m a ro $', F F y^ 10.00,; € I I I 'e €:€" a § k" F e $r '•• '1"1-11-, ,. 4 ; J P. w I it 1 ,II € I'$ 100 1000 . . .,I .106OU _ 1ooboo 10 Flow Rate-Litres/min. �CtaUlie victaulic.com 5 Check Valve I Firelock I Series 717&717H I Publication 10.08 Flow Characteristics The charts below express the flow of water at 60°F/16°C through valve. S717/717R 10 r .-�F .. i ...11e� b` .. � - s ,... ' F ('. € '�,� b c F I I 0- f - o 1� '''Ir 8 ., a�F 1 . .. I . , € �; i ( €IFS a ,F F $ yo ,,vJ I 1 , 1 S P Ii �0 i I h�e ^ I i £k,k 1 1 _•.* ) r `I` Li-" I i it I I i 1. I 0.1 _ ._ „.., _ , ___._"x. .. III E ;_... , '. 1,,z 10 1001000 10000 100000 Flow-GPM S717/717R 10 - y ly /S /! l r 3 pp 10 100 1000 10000 100000 Flow-GPM Installation Note Reference should always be made to the 1-100 Victaulic Field Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are included with each shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic and FireLock are registered trademarks of Victaulic Company. 10.08 1479 Rev.R Updated 05/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 6 ictaulkc FireLock® Buterfly Valve ✓ctaulid Style 705 with Weatherproof Actuator 10.81 Material Specifications: Body: Ductile iron conforming to ASTM A-536, grade 65-45-12 End Face, 2—6"/50— 150 mm: Ductile iron conforming to ASTM A-536,grade 65-45-12 Seal Retainer, 8— 12"/200—300 mm: Ductile iron conforming to ASTM A-536,grade 65-45-12 Approvals/Listings: Coating: Black alkyd enamel c 4� us Fnn vds ILPCB Disc: Ductile iron conforming to ASTM A-536,grade LISTED #G410001 104j/04 65-45-12,with electroless nickel coating conforming to See Victaulic Publication 10.01 for more details. ASTM B-733 Seat: Product Description: 0 Grade "E" EPDM The Series 705 Butterfly Valve features a weatherproof actuator housing Approved for indoor or outdoor use, a Stems:416 stainless steel conforming to ASTM A-582 ductile iron body and disc with EPDM seats. Designed for fire protection services only.Victaulic FireLock Stem Seal Cartridge: C36000 brass Series 705 Butterfly Valve is cULus Listed, LPCB Listed, FM and VdS Approved for 300 psi/2068 kPa service. Bearings: Stainless Steel with TFE lining Contact Victaulic for details of agency approvals. Stem Seals: EPDM Stem Retaining Ring: Carbon steel Actuator: ❑ 2—8750—200mm: Brass or bronze traveling nut on a steel lead screw, in a ductile iron housing 0 10—127250—300mm: Steel worm and cast iron quadrant gear, in a cast iron housing Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. 1 ictaulid victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Approvals and Listings: 11111 Series 705 Butterfly Valve IIIIIIIIIIIIIIIMIIIMEIMM 2"/50 mm up to 300psi/2068kPa �- n/a up to 300psi/2068kpa up to 300psi/2068kPa MEM up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 76.1 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 3"/80 mm up to 300psi/2068kPa up to 300psi/2068kpa up to 300psi/2068kPa up to 300psi/2068kPa 4"/100 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa IMIZZEI up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 139.7 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 6"/150 mm up to 300psi/2068kpa up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa MEM up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kpa 8"/200mm up to 300psi/2068kPa up to 300psi/2068kpa up to 300psi/2068kPa up to 300psi/2068kPa 10"/250 mm up to 300psi/2068kPa up to 300psi/2068kPa up to 300psi/2068kPa 12"/300mm up to 300psi/2068kpa up to 300psi/2068kPa ■■ up to 300psi/2068kPa 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 2 ✓ctaulie victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Dimensions: AVleb*: ifirc7"'0 1 -•r OH -r 1 i-it ...._ J' BIN F j~ �,I G E- A D NOTE:OPTIONAL W/15MM TAP AVAILABLE. CONTACT VICTAULIC FOR DETAILS. Dimensions Actual Nominal Outside E to E B D E F G DIA H Size Diameter A inches inches inches inches inches inches inches inches inches i hes inches mm mm mm mm mm mm mm mm mm4.22 mm4.50 mm 4.00 2.12 2 2.375 4.25 2.28 6.41 - - 107.2 114.3 53.8 60.3 603 108.0 57.9 162.8 101.6 4.22 4.50. 3. 21 2.875 3.77 2.28 7.54 4.00 107.21 1.777 73 73.0 95.8 57.9 191.5 101.4.00 4.22 4.50 1.77 76.1 mm 76.1 3.775. 2.287. 1915 101.6 1072 114.3 45.0 76.1 95.8 57.9 4.50 4.22 4.50 1.77 3 3.500 3.77 253 7.79 4.50 107.2. 1.50 1.77 88.9 88.9 95.8 64.3 197.9 5.50 4.22 4.50 2.20 108 mm 108.0 17. 2.883. 23. _ - 139.7 107.2 1143 55.9 108.0 117.6 73.2 223.8 5.50 422 4.50 220 4 4.500 4.63 2.88 8.81 - - 107.2 114.3 55.9 114.3 114.3 117.6 732 223.8 139.79 7. 6.4. 5. 5250 5.88 335 10.88 166.66.566.191 160.0 2.5865.5 133 mm 133.0 149.4 85.1 276.4630 2.58 6.56 6.19 139.7 mm 139.7 5.88 85.135 10.886. _ - 166.6 1572 160.0 65.6 139.7 149.4 85.1 276.4 656 6.19 630 2.58 5 5.563 5.88 3.35 10.88 _ 166.6 157.2 160.0 653 141.3 141.3 149.4 85.1 276.4 0.41 752 6.19 630 2.58 159 mm 159.0 5.889 3.847. 289.111.38 10.4 191.0 157.2 160.0 65.5 159.0 149.4 97.5 289.1 6500 5.88 3.84 11.38 _ 0.41 752 6.19 630 2.58 165.1 mm 165.1 149.4 97.5 289.1 10.4 191.0 1572 160.0 65.5 6 6.625 5.88 3.84 11.38 _ 0.41 752 6.19 630 1.90 1683 168.3 149.4 97.5 289.1 10.4 191.0 1572 160.0 483 8 8.625 5.33 5.07 1353 0.80 1.47 10.00 6.19 8.10 2.33 219.1 219.1 135.4 128.8 343.6 203 37.3 254.0 1572 205.7 592 10 10.750 6.40 6.37 15.64 1.41 1.81 1225 8.10 9.00 273 273.0 162.6 161.8 397.3 35.8 46.0 311.2 205.7 228.6 12 12.750 650 736 16.64 230 2.80 1425 8.10 9.00 _ 323.9 323.9 165.1 186.9 422.7 58.4 71.1 362.0 205.7 228.6 10.81 5662 Rev F Updated 11/2014 C 2014 Victaulic Company.All rights reserved. \iCtdLlliC: victaulic.com 3 victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Performance: The chart expresses the frictional resistance of Victaulic Series 705 Butterfly Valve in equivalent feet/ meters of straight pipe. Nominal Outside Size Diameter Equivalent mm mm Feet/m inches inches 2 of pipe 2375 6 50 60.3 1.8 NM 2.875 73.0 MIMI MEM 76.1 mm 3.000 76.1 3 3.500 MIN 80 88.9 4 4.50114.3 . 100 114.3 108 mm 108 mm MEM Mall 5500 139.7 mom IIEIIII 6 .150 Mill 6.500 165.1 MOM 8 200 1 1 0 ®■ 250 273.035 12 12.750 300 323.9 MEM 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 4 ✓ctaulic • victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Performance: Cy values for flow of water at+60°F/+16°C through a fully open valve are shown in the table below. For additional details,contact Victaulic. Formulas for K values Formulas for Cy values Where: Where: AP=Q2/K„2 K AR=Q2/Cv2 Flow Factor Flow Coefficient C Q=K5 x SAP Q(Flow) m'/hr Q=Cv x VAP Q(Flow) Ea AP(Pressure) bar AP(Pressure Drop) psi Valve Size Full Open Valve Size Full Open Actual Actual Nominal Outside Nominal OutsideSize Diameter Flow Coefficient Size Diameter Flow Coefficient 1(,,CV inches inches inches inches mm mm mm mm 2 2.375 147 2 2.375 170 50 60.3 50 60.3 2 r� 2.875 225 21/22.875 260 65 73.0 65 73.0 3.000 225 3.000 260 76.1 mm 76.1 3.50 76.1 mm 76.1 3 76.1 380 3 3.500 440 80 88.9 80 88.9 4 4500 710 4 4.5003 .500 820 100 1143 100 114.3 108mm 108mm 820 108mm 108mm 710 5 5.563 1040 5 5.563 1200 125 1413 125 141.3 133mm 133mm 1200 133 mm 133 mm 1040 5.500 139.7 mm 1040 5.500 1200 139.7 mm 139.7 139.7 6 6.625 1560 6 6.625 1800 150 1683 150 168.3 159 mm 159 mm 1800 159 mm 159 mm 1560 6.500 1560 6.500 1800 165.1 mm 165.1 165.1 mm 165.1 8 8.625 2940 8 8.625 3400 200 219.1 200 219.1 10 10.750 5020 10 10.750 5800 250 273.0 250 273.0 12 12.750 7790 12 12.750 9000 300 323.9 300 323.9 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. ‘iiCt3UliCr victaulic.com 5 victaulic.com I Butterfly Valve I Series 705 I Publication 10.81 Switch and Wiring: 1DNULLTON BAEDOX • CONDUIT 'I/ 1. The supervisory switch contains two single pole, double throw, pre-wired switches. l:_r.�14'NPT ;`C7iii1,410';'‘fiii. ONNER0R52. Switches are rated: r WIRE NM 10 amps @ 125 or 250 VAC/60 Hz 0.50 amps @ 125 VDC FIRE ALARM TO END-OF-LINE RESISTOR 0.25 amps®250 VDC CONTROL PANEL OR NEXT INDICATOR SUPERVISORY CIRCUIT 3. Switches supervise the valve in the "OPEN" position. SACH C10A TACT AT D 5. One switch has two#18 insulated wires per terminal, UA AT,25 AND 5124 OSA AT 125 VDC, which permit complete supervision of leads (refer 025AT250VDC i= MO MEMN RELL 4 Ell =Ito diagrams and notes below).The second switch VOLTAGE SOURCE NORN has one#18 insulated wire per terminal. This double WW1 l:llazds Per terminal Switch 2:1 lead Per terminal circuit provides flexibility to operate two electrical devices at separate locations,such as an indicating light and an audible alarm, in the area that the valve NOTE:The above diagram shows a connection between is installed. the common terminal (yellow—S1 and yellow-with- orange stripe—S2)and the normally closed terminal 6. A#14 insulated ground lead (green) is provided. (blue—S1 and blue-with-orange stripe—S2). In this Switch#1 =S1 example,the indicator light and alarm will stay on until the valve is fully open. When the valve is fully open, the For connection to the supervisory circuit of a UL indicator light and alarm will go out. Cap off any unused Listed alarm control panel wires(e.g. brown with orange stripe). Switch#2=S2 Only S1 (two leads per terminal) may be connected to Auxiliary switch that may be connected to auxiliary the fire alarm control panel. devices, per the authority having jurisdiction The connection of the alarm switch wiring shall be in accordance with NFPA 72 and the auxiliary switch per Normally Closed: (2) Blue S1 NFPA 70(NEC). Common: (2)Yellow Normally Closed: Blue with Orange Stripe S2 Normally Open: Brown with Orange Stripe Common: Yellow with Orange Stripe Installation Note Reference should always be made to the I-100 Victaulic Field Installation Handbook for This product shall be manufactured by Victaulic or to Victaulic specifications.All products the product you are installing.Handbooks are Included with each shipment of Victaulic to be installed in accordance with current Victaulic installation/assembly instructions. products for complete installation and assembly data,and are available in PDF format Victaulic reserves the right to change product specifications,designs and standard on our website at www.victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulice is a registered trademark of Victaulic Company. 10.81 5662 Rev F Updated 11/2014 ©2014 Victaulic Company.All rights reserved. victaulic.com 6 iataulic FireLock NXTM Dry Valve jctaulic° Series 768 30.80 Patent Pending Certifications/Listings: c®us FM LPCB //!! \32 Vds P 104f/01 0832 MEA:248-98-E See Victaulic Publication 10.01 for more details. Product Description: The patent-pending Victaulic Series 768 FireLock NXT Dry Valve is a low differential, latched clapper valve that uses a unique direct acting diaphragm to separate system water supplies from dry-pipe sprinkler systems. 1 see page 12 for European trim Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. 1 iCtauliC" victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Features: The low differential, unique latch and actuator design of the valve allows the valve to be reset without opening the valve. The low differential design is not subject to water columns. The valve allows the water to operate a water • i motor alarm and/or electric pressure alarms, which Clapper / tip Latch continue until the flow of water stops. With the optional �^`km s accelerator,the valve can be configured to respond tip , � faster for use in larger systems, or where faster response 110 times are required. '• ; /4": Diaphragm Thevalveisratedto300\ l s`��"•`:- e0m; Assembly psi/2065 kPa water working 1`�Vii;-Ii- n�� pressure and is factory tested hydrostatically to 600 psi/ _�,0_� 4135 kPa for sizes 1 %2—8'740—200 mm. VdS trim * f Clapper Seal g approved to 16 BAR (see page 12). '�� configurations are � seat Required air pressure for all trim variations is 13 psi/ 90 kPa. The Series 768 is available grooved x grooved. Exaggerated for clarity Standard grooved dimensions conform to ANSI/AWWA Note:Valve is shown in the"set"position C606. The Victaulic Series 768 FireLock NXT Dry Valve is made of high-strength, low-weight ductile iron, and it offers easy access to all internal parts. All internal parts are replaceable. Maintenance and service can be performed without removing the valve from its installed position. The rubber clapper seal is replaced easily without removing the clapper from the valve. The valve is painted inside and out to increase corrosion resistance. The body is tapped for main drain and all available trim configurations. Installation Options The Victaulic Series 768 FireLock NXT Dry Valve is available bare, or in the following configurations: Pre-trimmed The pre-trimmed valve comes completely assembled with all necessary trim components. Vic-Quick Riser The Vic-Quick Riser comes completely pre-trimmed and includes a shut off valve(uses a Series 705W FireLock Butterfly valve—request publication 10.18;for 1 i and 2740 and 50 mm sizes, the Vic-Quick Riser comes with a Series 728 Ball Valve—request publication 10.17)for system shut off, pre-set pressure switches, and a drain kit for ease of installation. For complete Vic-Quick Riser information request publication 30.20. Series 745 FireLock Fire-Pac (Available in North America only) The Fire-Pac is a completely pre-assembled fire protection valve that provides maximum service in a minimal enclosed space. The unit includes a water supply shutoff valve,the sprinkler system fire protection valve, alarm line pressure switches, air supervisory pressure switches, supervisory pump switches, and digital pressure gauges that are easily viewed through a window in the cabinet door. For complete Fire-Pac information request publication 30.23. Optional accessories ship separately. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 2 ✓ataulic victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Dimensions: The 4 Inch/114.3 Mm UI Listed,FM Approved Configuration Is Shown Below 1 Y2-2748.3-60.3 mm Configurations Contain V/19 mm Drain Valves. 2'/2-3"/73.0-88.9 mm Configurations Contain 1 1/4"/31 mm Drain Valves. 4-8"/114.3-219.1 mm Configurations Contain 2"/50 mm Drain Valves. ii 3rs I J-S G TTS -I -.I:-II.I! - rr-T I .k__.--_IL.'_ it,. r-,I 7,1 I J!��`aL+-1, F ri.rIn�.I I II r E � 11" II I� lil II, �_'q1� I D *Dl LL-%' LL J� � �� 7 is InJPL. 1 1 .7 I' III.��,�'�� ® / _I ITI �. \ fir- I 1 1 _.O IItrigia,pr 1.1101 l 'j: 1 I *Bl rI Q,1 •��� I I I I '"i"••� + _ :*.r. cal - Ikrt n -, i 11[ ._� 1�� 1 A B �� Cr- milli, b - ,i *A1 � lit rO �• • Iwo O ,. . .n-l._ rr-T 91 6161 �I �_m --, -1101111(91=-4- i1 I�.1, i to y j :4- 4-yJ IME"lil IP wili I`El � H -.1. `l--- K C "El-0 Full Open Approx. Weight Dimensions Each Actual - Without With Nominal Outside Size Diameter A Al B Bl C D Dl E ElF G H J K Trim Trim inches inches inches inches inches inches inches inches inches inches inches inches inches inches inches inches lbs. lbs. mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm kg kg 1 Yz 1.900 9.00 16.35 27.25 39.50 13.75 16.00 _ 5.25 8.50 9.50 21.25 3.04 9.17 6.98 16.7 43.0 40 483 228.60 415.29 692 1003 349 406 133 215 241 539 7721 232.91 177.29 7.6 19.5 2 2375 9.00 13.37 2725 39.50 13.75 16.00 _ 5.25 8.50 950 21.25 3.04 9.17 6.98 17.0 43.0 50 60.3 228.60 339.60 692 1003 349 406 133 215 241 539 77.21 232.91 177.29 7.7 19.5 2 Yz 2.875 12.61 16.50 .2565 73.0 320.29 419.10 32.25819 1123 1342 3.50 1406 6.00 1444 133 228 234 5.25 9.00 9.257.50 25 95 99.06 266.0 176.02 18.7 29.5 76.1 mm 3.000 12.61 16.50 3225 44.25 13.50 16.00 17.50 525 9.00 9.25 21.25 3.90 10.50 6.93 41.0 65.0 76.1 32029 419.10 819 1123 342 406 444 133 228 234 539 99.06 266.70 176.02 18.7 29.5 3 3.500 12.61 16.50 32.25 44.25 13.50 16.00 17.50 5.25 9.00 9.25 21.25 3.90 10.50 6.93 41.0 65.0 80 88.9 320.29 419.10 819 1123 342 406 444 133 228 234 539 99.06 266.70 176.02 18.7 29.5 4 4500 15.03 19.83 3350 45.50 15.00 15.75 2050 5.25 9.00 10.75 21.00 625 9.62 8.46 59.0 95.0 100 114.3 381.76 503.68 850 1155 381 400 520 133 228 273 533 158.75 244.34 214.88 26.7 43.0 165.1 mm 6.500 16.00 22.00 34.00 46.00 15.50 17.00 22.00 5.25 8.50 11.50 20.50 6.20 9.62 8.84 80.0 116.0 165.1 406.40 558.80 863 1168 393 431 558 133 215 292 520 157.48 244.34 224.53 36.2 52.6 6 6.625 16.00 22.05 34.00 46.00 15.50 17.00 22.00 5.25 850 11.50 2050 620 9.62 8.84 80.0 116.0 150 168.3 406.40 560.07 863 1168 393 431 558 133 215 292 520 157.48 24434 224.53 36.2 52.6 8 8.625 17.50 23.00 3350 45.50 16.75 20.00 2525 6.25 8.75 12.75 18.50 6.05 9.40 1021 122.0 158.0 200 219.1 444.50 584.20 850 1155 425 508 641 158 222 323 469 153.67 238.76 259.33 55.3 71.6 NOTES: The"A"dimension coupling is not shown in order to clarify dimensional callouts. Components shown as dotted lines denote optional equipment. *Measurements denoted with an asterisk take optional equipment into account. Optional drain connection kit is shown for reference and takeout dimensions. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. �Ct9U�iCr victaulic.com victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Performance: Hydraulic Friction Loss The chart below expresses the flow of water at 65°F/18°C through a full open valve. 6.0 5.0 j -1 i±: #._ I i---- J 3.0 11_ 1--i € F y � _ t ii [ ' j F '01 " ® 4 I , 1 w t. Ia 03 , w. _. # . E ; 1s E , 0.2 i_ ., ,_..._ , , a i ij 1 I s I I I 0.1 z 10 20 30 40 60 80 100 200 300 400 600 1,000 2,000 4,000 6,000 10,000 20,000 800 3,000 8,000 FLOW RATE—GPM Frictional Resistance The chart below expresses the frictional resistance of Victaulic Series 768 FireLock NXT. Dry Valve in equivalent feet of straight pipe. Actual Equivalent Nominal Outside Length of Size Diameter Pipe inches inches feet mm mm meters 1 Y2 1.900 3.00 40 48.3 0.914 2 2.375 9.00 50 60.3 2.743 21 2.875 8.00 65 73.0 2.438 76.1 mm 3.000 8.00 76.1 2.439 3 3.500 17.00 80 88.9 5.182 ' 4 4.500 21.00 100 114.3 6.401 165.1 mm 6.500 22.00 165.1 6.706 6 6.625 22.00 150 1683 6.706 • 8 8.625 50.00 200 219.1 15.240 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 4 ✓ataulic victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 C„Values: Operation: C„values for flow of water at+60°F/+16°C through a fully The Series 768 Dry Valve contains a clapper,which has open valve are shown in the table below. a replaceable rubber seal. The clapper makes contact with the valve's seat ring,which has access Formulas for Cv values Where: holes leading into an intermediate chamber in the valve. AP=Q2/cvs Flow Coefficient C, The diaphragm contacts the latch, and the latch holds JM' Q(Flow) GPM the clapper closed. o=cvx DP(Pressure Drop) psi In the closed position,the valve diaphragm is maintained in the extended position by the water supply pressure from upstream of the water supply control valve.The diaphragm latch holds the clapper in the closed position. The Series 776 Low Pressure Actuator(LPA) maintains Valve Size Full Open the water,and the system's air pressure controls the Actual LPA. Required air pressure is 13 psi/90 kPa.The design Nominal Outside of the 776 actuator does not require the traditional air Size Diameter Flow Coefficient cushion of 10—20 psi/69—138 kPa. Excess air inches inches cpressure above 13 psi/90 kPa will cause a delay in valve mm mm operation. 11/2 1.900 60 40 48.3 52.0 Once the system's air pressure reduces to the trip point, 2 2375 110 the LPA opens and allows the water supply pressure in 50 603 95.0 the diaphragm to release(i.e.an open sprinkler).This 21f2 2.875 180 65 73.0 156.0 release allows the latch to move to its open position, 76.1 mm 3.000 180 permitting the clapper to pivot freely,thus allowing water 76.1 156.0 into the system. 3 80 3.5008.173 0 Water enters the intermediate chamber of the valve ---> a 4.500 350 through the holes in the seat ring.The water flows from 100 1143 302.8 the intermediate chamber to the alarm line,which 165.1 mm 6.500 1000 activates the system's alarms.The alarms continue to 165.1 865.0 sound until the flow of water stops. 6 6.625 1000 150 1683 865.0 When the flow of water stops,the spring-assisted valve 8 8.625 1500 clapper returns to the closed position.The valve acts as 200 219.1 1499.1 an alarm check valve until the system is back in service as a dry system,according to the proper procedure. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 5 ViCtaUlie victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Material Specifications: Body: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Clapper:Aluminum bronze UNS-C95500 Latch:Aluminum bronze UNS-C95500 Shaft:Stainless 17-4 Clapper Seal: Peroxide cured EPDM, ASTM D2000 Bushings/Seat 0-rings: Nitrile Springs:Stainless Steel (300 Series) Diaphragm: Peroxide cured EPDM with fabric reinforcement Bill of Materials 1 Valve Body 12 Cover Plate 2 Clapper 13 Cover Plate Gasket 3 Clapper Seal 14 Cover Plate Bolts* 4 Seal Ring 15 Latch 5 Seal Washer 16 Latch Spring 6 Seal Retaining Ring 17 Latch Spring Bushing and 0-ring(Qty.2) 7 Seal Assembly Bolt 18 Diaphragm 8 Bolt Seal 19 Diaphragm Cover 9 Clapper Spring 20 Diaphragm Cover Cap Screws(Qty.8) 10 Clapper Shaft 21 Latch Shaft 11 Clapper Shaft Bushing and 0-ring(Qty.2) N * .. „) S ci—p -, '-- toe- o z, m • 1 . 'l k 0 / /-..J L �� / ,01 .--/ _ `. 0 A (;2'.1i$. 0 . O *NOTE:The 11/2-inch/48.3-mm and 2-inch/60.3-mm valve sizes contain washers under the heads of the cover plate bolts. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 6 ✓ctaiulic' victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Trim Package Details: • Air Compressor(See page 8 for more on the Victaulic Series 7C7 Compressor Package) Trim Packages: NOTE: See page 11 for details of trim and page 12 for • Air Maintenance Trim Assembly details of European trim. • Alarm Panels 1 Galvanized components. • Drain Connection Kit 2 Series 776 Low-Pressure Actuator—The Series 776 Low-Pressure Actuator is pneumatically actuated and requires only 13 psi/90 kPa minimum air Air Supply Requirements: pressure, regardless of the system supply pressure. The required air pressure for Series 768 FireLock NXT This actuator allows the system to operate with a low Dry Valves is 13 psi/90 kPa minimum, regardless of the air or gas pressure of 7 psi/48 kPa. system supply water pressure.Air pressures should be 3 All Required Pipe and Fittings. kept below 18 psi/124 kPa, unless a Series 746-LPA 4 All Standard Trim Accessories. Dry Accelerator is installed.Systems with air pressures higher than 18 psi/124 kPa may require the addition of a 5 All Required Gauges Series 746-LPA Dry Accelerator. Optional Trim Package: If multiple Series 768 FireLock NXT Dry Valves are 1 Black Trim for Foam Systems—If the valve is installed with a common air supply, isolate the systems intended for use in a foam system, black trim must with a spring-loaded, soft-seated ball check valve to be ordered, per NFPA requirements.Specify this ensure air integrity for each system. Good practice is requirement on the order. to include a ball valve for isolation and service of each individual system. The engineer/system designer is responsible for sizing Optional Accessories: the compressor so that the entire system is charged to • Series 746-LPA Dry Accelerator—The Series the required air pressure within 30 minutes. DO NOT 746-LPA Dry Accelerator is required when the oversize the compressor to provide more airflow. An Series 768 Dry Valve is installed in large systems to oversized compressor will slow down or possibly prevent improve response time. Request submittal 30.64. valve operation. • Series 760 Water Motor Alarm—The Series 760 If the compressor fills the system too fast, it may be Water Motor Alarm is a mechanical device that necessary to restrict the air supply. Restricting the air sounds when a sustained flow of water occurs(such supply will ensure that air being exhausted from an open as with an open sprinkler). Request submittal 30.32. sprinkler or manual release valve is not replaced by the air supply system as fast as it is being exhausted. • Series 75B Supplemental Alarm Device—The Series 75B Supplemental Alarm Device is designed to provide a continuous alarm for systems equipped with a mechanical device. Request submittal 30.33. • Series 75D Water Column Kit—The Series 75D Water Column Kit is designed to minimize residual water in the riser from collecting above the clapper. Request submittal 30.34. • Alarm Pressure Switch—Alarm Pressure Switches are designed to activate electrical alarms and control panels when a sustained flow of water occurs(such as with an open sprinkler). • Air Supervisory Pressure Switch—Air Pressure Supervisory Switches are used to monitor low system air pressure and are factory pre-set. • Air Supply System—The air supply system contains all components for establishing and maintaining air in the system.The compressor, low-pressure alarms, ball valves,and required trim are included in the air supply system. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 7 ictaulic victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Compressor Sizing: COMPRESSOR REQUIREMENTS 1z11_11 ... 11_11_1_111 _m... 20 psi/138 kPa 113 psi/90 kPa __., , 10 _ __u... _...1 i 1 LL 8 e uI I s I 6 1_111,1111 11_, .,w.�. }� 1111,„... _.___....... 4 aE 1 .._.._.,i .._..._....... 1111£ 0 �I 1 K I f. a ; a . _._ .. Ce i y ..- 1111. i i I 2 3/I . , +___1111. _..._.e....�,.. ... ,. i.._. 40 1 ..,...�._..,,..�.. 1111_ _. 8 0 " 0 0 0 o w u, m SYSTEM CAPACITY(in gallons) Base or Riser-Mounted Compressors: Shop Air or Tank-Mounted Air Compressors: For base or riser-mounted compressors,the recom- In the event a compressor becomes inoperative, a mended air pressure of 13 psi/90 kPa is the "on" or properly sized tank-mounted air compressor provides "low" pressure setting for the compressor. The "off" the greatest protection for systems. or"high" pressure setting should be 18 psi/124 kPa. Victaulic offers the Series 7C7 Compressor package When shop air or a tank-mounted air compressor is used,the Series 757 Regulated AMTA must be installed. for FireLock NXT devices which is riser-mounted and pre-set for the FireLock NXT pressure requirements as The Series 757 Regulated AMTA provides proper air stated above. For information on the Series 7C7 regulation from the air reservoir to the sprinkler system. package, consult publication 30.22. The Series 7C7 For tank-mounted air compressors,the recommended Compressor package is only available in North America. air pressure of 13 psi/90 kPa should be used as the set point for the air regulator. The "on" pressure of the When a base or riser mounted air compressor supplies air to a Series 768 FireLock NXT Dry Valve, it is not compressor should be at least 5 psi/34 kPa above the necessary to install the Victaulic Series 757 Regulated set point of the air regulator. Air Maintenance Trim Assembly(AMTA). In this case, the airline of the compressor connects to the trim at the fitting where the Series 757 Regulated AMTA is normally installed (refer to the applicable trim drawing). If the compressor is not equipped with a pressure switch,the Series 757P Air Maintenance Trim Assembly with Pressure Switch should be installed. For information on the Series 757 Regulated Air Maintenance Trim Assembly, see publication 30.35. For information on the Series 757P Air Maintenance Trim Assembly, see publication 30.36. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 8 ✓ctaulic victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Series 757 Regulated Air Maintenance Trim Assembly: • Victaulic recommends a maximum of two Series 768 FireLock NXT Dry Valves per Series 757 Regulated AMTA Bill of Materials 1 '/8"/3.2 mm Restrictor ii 2 Slow FII Ball Valve(Normally Open) 3 Air Regulator 4 Strainer(100 Mesh) - '' .. 5 Spring-Loaded,Soft-Seated it, i. Ball Check Valve 0 _, 0 6 Fast Fill Ball Valve(Normally Closed) ii is✓ © Exaggerated for clarity Series 757P Air Maintenance Trim Assembly With Pressure Switch: • Victaulic recommends a maximum of two Series 768 FireLock NXT Dry Valves per Series 757P AMTA with Pressure Switch N, r j . ., 0 Bill of Materials 0 I i S1of Item Qty. Description j 1 1 Restrictor('h-inch NPT) Y # j • 02 1 Strainer('h-inch NPT) ;; 3 1 Swing Check(h-inch NPT) 4 1 Slow-Fill Ball Valve 9 �i (Normally Open) �j, 5 1 Spring-Loaded,Soft-Seated t l.r 0 Check Valve 6 1 Pressure Switch 7 2 Compression Fitting,Straight ' 0 (1/4-inch NPT x1/4-inchTube) s �► (07 0 8 1 Copper Tubing('/4-inch OD) e� ��. 9 11 Close Nipple ® ;IV. ('h-inch NPTx 1.13) ric. 10 1 Nipple('h-inch NPTx 4.00) 0 Ill 1 900 Female Elbow('h-inch NPT) 12 4 Female Tee(h-inch NPT) 13 3 Union('h-inch NPT) , 14 2 Reducing Bushing "� Ch-inch NPT x'/a-inch NPT) 04$-'' :`• �� 15 1 Fast-Fill Ball Valve �ci © 4r, (Normally Closed) © 11f i,-, 16 1 Pressure Switch Isolation Ball m ;?!' Valve(Normally Open- i i 14_ Lockable) FROM ® �0„ COMPRESSOR y, TO SYSTEM Exaggerated for clarity 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. �Ct:aUliC victaulic.com 9 victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Compressor Requirements: Remote System Test Valve Requirements Compressor Requirements and Settings for Series 768 The remote system test valve(inspector's test connection) FireLock NXT Dry Valves Installed with Series 746-LPA should contain a UL Listed and/or FM Approved valve Dry Accelerators (normally closed),which can be opened to simulate the Set the air regulator of the Series 757 Regulated AMTA operation of a sprinkler. to 13 psi/90 kPa. The remote system test valve(inspector's test connection) THE SERIES 757P AIR MAINTENANCE TRIM should be located at the most hydraulically ASSEMBLY WITH PRESSURE SWITCH MUST NOT BE demanding location in the release system. USED ON A SERIES 768 FIRELOCK NXT DRY VALVE NOTE: Multiple restrictions on the remote system test INSTALLED WITH A SERIES 746-LPA DRY ACCELERATOR. When a Series 768 FireLock NXT Dry Valve is installed valve(inspector's test connection) may slow the air decay rate and cause the system to respond slower than required. with a Series 746 LPA Dry Accelerator, the Series 757 The remote system test valve(inspector's test connection) Regulated AMTA must be used. NOTE: The use of an air should terminate with an orifice equal to the regulator with a base or risermounted compressor could smallest orifice in the releasing system. cause short cycling, resulting in premature wear of the The remote system test valve(inspector's test connection) compressor. is used to ensure that water reaches the most remote In the event a compressor becomes inoperative,a part of the system within 60 seconds. properly sized tank-mounted air compressor provides the greatest protection for systems installed with a Series 746-LPA Dry Accelerator. In this situation,air can be supplied continuously to the sprinkler system for an extended time period. NOTE: The Series 757 Regulated AMTA must be used with a tank-mounted air compressor or shop air system that continually supplies air to a Series 768 FireLock NXT Dry Valve installed with a Series 746-LPA Dry Accelerator. The air regulator of the Series 757 Regulated AMTA is a relief-type design.Any pressure in the system that is above the set point of the air regulator will be released. Therefore, charging the air regulator above the set point could cause premature operation of a valve installed with a Series 746-LPA Dry Accelerator. NOTE:The series 746-LPA should not be used above 30 psi. If higher pressures are required,the series 746 should be used. Settings for Air Supervisory Pressure Switches and Alarm Pressure Switches Air supervisory pressure switches are required for dry systems and must be set according to the following instructions. NOTE: Switches for Vic-Quick Risers are pre-set at the factory. Wire the air supervisory pressure switches to activate a low-pressure alarm signal. NOTE: In addition,the local authority having jurisdiction may require a high-pressure alarm. Contact the local authority having jurisdiction for this requirement. Set the air supervisory pressure switches to activate at 2—4 psi/14—28 kPa below the minimum air pressure required, but not lower than 10 psi/69 kPa. Wire the alarm pressure switch to activate a water flow alarm. Set the alarm pressure switch to activate on a pressure rise of 4—8 psi/28—55 kPa. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 10 ✓ctaulic" victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Exploded View Drawing— Trim Components (c 414 us <>Trim) lSTED Series 768 FireLock NXT Dry Valve (Optional Accessories Also Shown) Bill of Materials 01 1 Series 768 FireLock NXT Dry Valve Ile 2 FireLock Rigid Coupling(Optional/ Sold Separately-Comes StandardVI ✓ I when VQR Assembly is Ordered) From System IV i 3 Water Supply Main Control Valve Air Feed (OptionaVSold Separately Comes y� i / � t! I ID' Standard when VQR Assembly is Ordered) I L / 4 Drain Swing Check Valve m 5 Drip Cup with Cap , 1 ') 6 Alarm Pressure Switch(Optional/Sold :. 7, Separately-Comes Standard when VQR Assembly is Ordered) e ® V L tie" 7 Series 729 Drip Check Valve m -- -- 0 8 Diaphragm-Charge-Line Ball Valve tl� (Normally Open) i �1 9 3-in-1 Strainer/ChecWRestrictor i���� i CD z. ey Assembly • `� r 10 Series 760 Water Motor Alarm i '�I i 24 rte'•'` © I 1��-,--.,, ® � � �� i' I ,3� '.' (OptionaVSoldTest Ball Separately) ® I Q c,, 11 Alarm Valve ) `� 1 oDrlp Cup l ) • 12 Diaphragm-Charge-Line Pressure �y♦ I ill tae < ti To Drip Cup tootion Gauge(0-300 psi/0-2068kPa/0-20.7 Bar) �(1l �f N. location qIlk� 13 Series 749 Auto Drain ® �-JJ O 2:0;0,!40 0 14 Series 746-LPA Dry Accelerator C,_.. b �` 4111 T Assembly(Optional/Sold Separately) et. 15 Series 776 Low-Pressure Actuator To 16 Air Manifold Note 1 \,• System 1 17 Air Supervisory Pressure Switch \ \ t ® -/ �7 (OptionaVSold Separately-Comes y �' - Standard when VQR Assembly is Ordered) m \, �_I 18 (0-8System Pressure Gauge O� e—'` /♦! I \ e\ ` �,40$410,,,, � , (0-80 psi/0-552 kPa/0-5.5 Bar with Retard) (J` 19 Water Supply Main Drain Valve 49- Flow Test Ifl.� n ������I ��7►# 20 Water Supply Pressure Gauge r"' •. U'r t (0-3n Connection (Optional/Sold 20.7 Bar) .• - \ 0 J 21 Drain Connection Kit(O •• Separately-Comes Standard when VQR \ \ I Assembly is Ordered) \y 'k.,r 22 Gauge Valve I • i 23 System Main Drain Valve 0 i 10I 24 Series 748 Ball Check Valve �= I r te -- — 0 44t;r• r- larition Drlpfup � To g ' D / © 14,,-.1,-.;Wail AFt From Water Supply Exaggerated for clarity Optional devices include the Series 75D Water Column Device Kit and the Series 75B Supplemental Alarm Kit. NOTE 1:Connection point for the Series 75D Water Column Device Kit. For installation of the Series 75B Supplemental Alarm Device,refer to the instructions supplied with the product. 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. jctaU�iC� victaulic.com • victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 Exploded View Drawing— Trim Components: (European Trim: c 0 us FM LPCB (( VdS a.) 104f/01 0832 MEA:248-98-E Series 768 FireLock NXT Dry Valve (Optional Accessories Also Shown) Bill of Materials i 1 Series 768 FireLock NXT Dry Valve ' 2 FireLock Rigid Coupling(Optional/Sold O� Separately-Comes Standard when VQR v Assembly is Ordered) From System �� i m -/I 3 Water Supply Main Control Valve(Optional/ Air 1 ; / % Sold Separately-Comes Standard when VQR I / Assembly is Ordered) 4 Drain Swing Check Valve �J % 5 Drip Cup with Cap ' ....--- 6 Alarm Pressure Switch(OptionaVSold / Location Separately-Comes Standard when VQR " V Location0 Assembly is Ordered) 7 Series 729 Drip Check Valve 8 Diaphragm-Charge-Line Ball Valve '�ii,� t ":' (Normally Open) LII i 'O Oa, 9 3-in-1 Strainer/ChecWRestrictor 24 r til © % ,, Assembly m ® i ( I ®� °A J To Orly Cup 10 Series 760 Water Motor Alarm ?i ti� To Drip canon �, (OptionaVSold Separately) • •1<< a r 11 Alarm Test Ball Valve y 0 CrW M4- `-' J Location - '0 � 12 Diaphragm-Charge-Line Pressure -� b �, Q.: (�� Gauge(0-300 psi/0-2068 kPa/0-20.7 Bar) 0 A 13 Series 749 Auto Drain �� I 1�0 �' To ® srnem oI t 'i.;,., 14 Series 746-LPA Dry Accelerator Notes '\, / Assembly(Optional/Sold Separately) '- • 15 Series 776 Low-Pressure Actuator : I I�'\ �•,� A 16 Air Manifold I `►� - 17 Air Supervisory Pressure Switch(OptionaVSold i 7 �. �� Separately-Comes Standard when VQR ® 1� 0., I - , ' �' r# Assembly is Ordered) ATC tr.. n i���� I ,` 18 System Pressure Gauge `''• \. 40 / Imo' s (0-80 psi/0-552 kPa/0-5.5 Bar with Retard) _� -4 �I 0 rO' '' %` `• 19 Water Supply Main Drain Valve- i � Flow Test , I 25 0 20 Water Supply Pressure Gauge �� r (0_300 psi/0-2068 kPa/0-20.7 Bar) �� 21 Drain Connection Kit(Optional/Sold © i�� 0 i 110 Separately-Comes Standard when VQR 41 To Drlp EP Cop Assembly is Ordered) •� e 22 Gauge Valve ,..,(:) 6 23 System Main Drain Valve �( �1 24 Series 748 Ball Check Valve © -;�L� �. 25 Water Motor Alarm Shutoff Valve I�r.`�foLisk J (Normally Open)* i 4 0,1 'Item 25,water motor alarm shutoff valve,can be closed to prevent water from flowing into the Series 760 Water Motor alarm during conditions that are not favorable for the alarm to sound(i.e during a trip test). From Water Supply 30.80 4219 Rev G Updated 01/2015 ©2015 Victaulic Company.All rights reserved. victaulic.com 12 ✓ctauliC victaulic.com I NXT Dry Valve I Series 768 I Publication 30.80 • This product must be installed by an experienced,trained installer, in accordance with the instructions provided with each valve.These instructions contain important information. Failure to follow these instructions may result in serious personal injury, property damage,or valve leakage. If you need additional copies of this product literature or the valve installation instructions,or if you have any questions about the safe installation and use of this device,contact Victaulic Company, P.O. Box 31, Easton, PA 18044-0031 USA, Telephone:001-610-559-3300. Installation Note Reference should always be made to the appropriate Installation,Maintenance,and This product shall be manufactured by Victaulic or to Victaulic specifications.All products Testing Manual included with each shipment of Victaulic products.These manuals are also to be installed in accordance with current Victaulic installation/assembly instructions. available in PDF format on our website at victaulic.com Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. Warranty Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks Victaulic®and FireLock°are registered trademarks of Victaulic Company. 30.80 4219 Rev G Updated 01/2015 0 2015 Victaulic Company.All rights reserved. victaulic.com 13 ictauliC IPS CARBON STEEL PIPE-FIRE PROTECTION PRODUCTS 30 3C FireLock® Devices Air Maintenance Trim Assembly SERIES 757 PROPER AIR SUPPLIES FOR SERIES 1.When a riser or base mounted air compressor is being used to supply air to a dry valve or preac- 756/SERIES 758/SERIES 768/SERIES769 tion system it is not necessary to use the air maintenance trim assembly with the air regulator. In this ACTUATED VALVES: circumstance the air line of the compressor is connected to the valve trim at the fitting into which the Air Maintenance Trim is normally installed. When the valve is used with this setup it is the engineer/system designer's responsibility to size the compressor so that the compressor brings the entire system to the required pressure in 30 minutes. The compressor must not be oversized to provide more air flow as this will slow down or possibly prevent the operation of the valve.It must further be emphasized that the base mounted compressor does not provide any backup air to the system and that continuous service(24 hours per day,7 days per week)must be maintained in order to prevent the potential of false tripping of the valve due to loss of air pressure. Additionally,due to the large on/off differential available on pressure switches that control base mounted compressors,the compressor pressure switch must be adjusted so that the"ON"contact of the pressure switch is set a minimum of 5 psi higher than the set point of the regulator. 2.When shop air or a tank mounted air compressor is being used,the Air Maintenance Trim Assembly(AMTA)must be used.The AMTA is designed to provide the proper air regulation to the sprinkler system which will assure the proper operation of the Fire Safety Valve. In the event of a compressor becoming inoperative the tank mounted air compressor provides the greatest protection.With a properly sized tank,air can be continuously supplied to the sprinkler sys- tem for an extended period of time even with a loss of compressor. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications.All products to be installed in accordance with current Victaulic installation/assembly instructions.Victaulic reserves the right to change product specifications,designs and standard equipment without notice and without incurring obligations. 1111111111111111 111111111 11 WCAS-7MYM68 For complete contact information,visit www.victaulic.com 30.35 2515 REV D UPDATED 1/2009 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY.®2009 VICTAULIC COMPANY.ALL RIGHTS RESERVED. �CtaUI11Gr 30.35 I'm also available In a BASEPLATE UNIT R-..... ill, I ...„, ", ,,..,,,,:J. .. . ,,... PPR 'll,'ll�i f Ill ' .. - COMPRESSORS „ . , : S300 ...„, , ,,. . ,.,.. PRODUCT NUMBERING SYSTEM S300H - SD1 I-,1 1 5 ,, I 1.5 HP l Il l I 1J 1 I Ll (1 VOLTAGE ADDITIONAL OPTION 3.8 CFM M SYSTEM CAPACITY MOUNTING OPTIONS SERIES PHASE 115cwaaeaaassoo �,/ 1 HD SD B:Baseplate HD:Heavy Duty 1:Single Phase aaa:m.<n P.Prewired Power Cord 175 300 H:Horizontal Tank SD:Standard Duty 3:Three Phase 2301¢oerzaon S:Prewired Magnetic Starter 265 2000 V.Vertical Tank 460 U:30-40psi Pressure Switch 325 IGnly on S$9U aM larged Gim evailaeleln Pn and 5111 500 300 GAL. MAX CAP. I `Greyed aut oltions do and apply to this unit 27" a 'S300H-SD1-1.5 is a stacked it6rn x 12" x 22" a SPECIAL ORDER OPTIONS: SINGLE PHASE VOLTS AMPS S.F. 70-100 PSI 1 Phase:115v 200v 230v ®M 1.0 -3 Phase:200v/230v/460v los In 1.0 -Power Cord 230 las 1.0 -3 Phase Starter THREE PHASE 35 L -30-40 PSI Pressure Switch VOLTS AMPS S.F. -Horizontal or Baseplate Mount losEl® 230 EM® 112" M PT a DON'T FORGET YOUR INSTALLATION KIT! 460 ®® 'C' The Advantage 26549 Fallbrook Avenue,Wyoming,MN 55092//800.762.2247//651.462.3440//www.c-aireinc.com Spare Sprinkler Head Storage Cabinet Description Fire Protection Products, Inc. Spare Sprinkler Head Cabinets are designed to allow for spare sprinkler head storage as required by NFPA guidelines. The Spare Sprinkler Head Cabinets are available Specifications in six configurations. Three head, six head, six head ESFR, twelve head, twenty-four head and thirty-six head. All six styles are Material: manufactured with "knockouts" to accommodate the most common Painted plain steel size sprinklers. The shelf is located to allow for the storage of a typical sprinkler head wrench. Each cabinet is finished with a red Finish: enamel fi nish. Each spare head cabinet comes with a hinged Red enamel door which remains closed to protect the spare sprinklers from the Styles: elements and features two holes on the back panel to allow for 3 Spare sprinklers, attachment to most surfaces utilizing the appropriate fasteners. 1/2 or 3/4 Not intended for exposed or harsh environments. 6 Spare sprinklers, 1/2 or 3/4 Installation 6 Spare, ESFR, Select the correct Spare Once the correct Spare Sprinkler 1/2 , 3/4 or 1" Sprinkler Head Cabinet in Head Cabinet has been select- 12 Spare sprinklers accordance with the Automatic ed, installation is accomplished 1/2 or 3/4 Sprinkler Systems Handbook. by inserting the correct fastener 24 Spare sprinklers As per the 1989 Edition the in each of the two holes inside 36 Spare sprinklers correct number of spare the cabinet, securing the cabinet sprinkler is as follows: securely to the wall. The insert the correct number and type of "0-300 sprinklers, not less than 6 sprinklers in accordance with the 300-1000, not less than 12 "handbook". 1000 or more, not less than 24. *Final determination is subject to approval Stock of spare sprinklers shall include all types and ratings by the AHJ. installed."* FPPI` Fire Protection Products, Inc 6241 Yarrow Dr.,Suite A,Carlsbad,CA 92011-1541 ©2000-2007 Fire Protection Products,Inc(FPPI) For questions: 1 800 344-1822.1 800 344-3775 fax•www.fppi.com • BELLS The Symbol of Protection PBA-AC &MBA-DC UL,ULC,and FM Approved Sizes Available: 6"(150mm),8"(200mm)and 10"(250mm) Voltages Available: 24VAC tt 120VAC 12VDC(10.2 to 15.6)Polarized 24VDC(20.4 to 31.2)Polarized Service Use: Fire Alarm . General Signaling *• � rBurglar Alarm Environment: Indoor or outdoor use(See Note 1) -40°to 150°F(-40°to 66°C) (Outdoor use requires weatherproof backbox.) Termination: AC Bells-4 No. 18 AWG stranded wires 0 ti r. DC Bells-Terminal strip Finish: Red powder coating * dhe Optional: Model BBK-1 weatherproof backbox Model BBX-1 deep weatherproof backbox These vibrating type bells are designed for use as fire,burglar or general Notes: signaling devices. They have low power consumption and high decibel 1. Minimum dB ratings are calculated from integrated sound pressure ratings.The unit mounts on a standard 4"(101mm)square electrical box measurements made at Underwriters Laboratories as specified in UL for indoor use or on a model BBK-1 weatherproof backbox or BBX-1 Standard 464. UL temperature range is-30°to 150°F(-34°to 66°C). deep weatherproof backbox for outdoor applications. Weatherproof 2. Typical dB ratings are calculated from measurements made with a backbox model BBK-1,Stock No.1500001. conventional sound level meter and are indicative of output levels in an actual installation. 3. ULC only applies to MBA DC bells. Size inches Voltage Model Stock Current Typical dB at Minimum dB at (mm) Number Number (Max.) 10 ft.(3m)(2) 10 ft.(3m)(1) 6(150) 12VDC MBA-6-12 1750070 .12A 85 76 8(200) 12VDC MBA-8-12 1750080 .12A 90 77 10(250) 12VDC MBA-10-12 1750060 .12A 92 78 6(150) 24VDC MBA-6-24 1750100 .06A 87 77 8(200) 24VDC MBA-8-24 1750110 .06A 91 79 10(250) 24VDC MBA-10-24 1750090 .06A 94 80 6(150) 24VAC PBA246 1806024* .17A 91 78 8(200) 24VAC PBA248 1808024* .17A 94 77 10(250) 24VAC PBA2410 1810024* .17A 94 78 6(150) 120VAC PBA1206 1806120* .05A 92 83 8(200) 120VAC PBA1208 1808120* .05A 99 84 10(250) 120VAC PBA12010 1810120* .05A 99 86 All DC bells are polarized and have built-in transient protection. *Does not have ULC listing. In outdoor or wet installations,bell must be mounted with weatherproof backbox,BBK-1 or BBX-1.Standard electrical boxes will not provide a weatherproof enclosure.If the bell and/or assembly is exposed to moisture,it may fail or create an electrical hazard. Potter Electric Signal Company, LLC • St. Louis, MO, • Phone: 866-572-3005/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5400776-REV Y-1 PAGE 1 OF 2 01/13 ES-A-I n Bu i l d i ng Ri ser For Fire Protection Applications Job Name Contractor Job Location Approval Engineer Contractor's P.O. No. Approval Representative LEAD FREE* Series IBR In-Building Risers Customizable Sizes: 4"- 10"(100-250mm) Building Floor Building perimeter wall T CAS � -7.••4* � ,�, .�� �, � �--.. ) • 6'x6'standard length ,iamni:=3 (custom lengths from 3'-20'available) Flow Features Series IBR In-Building Risers are used to connect the main fire supply to the building overhead fire system.The fitting passes under the foundation without joints and ex- •Cost savings tends up through the floor. Provided with installation tabs,the unit has a CIPS(Cast •Corrosion resistant stainless steel Iron Pipe Size)coupler for easy connection to the underground supply(AWWA C900 construction,type 304 PVC and Ductile Iron Pipe)and industry standard grooved-end connection(AWWA •Ease of installation and light weight allows C606)on the building side for easy connection to the overhead fire sprinkler system. one person to position and handle the riser The IBR features Lead Free*construction to comply with Lead Free*installation •Minimal site preparation;joint restraint one- requirements. piece construction reduces time and labor; Ames In Building Risers are precision engineered and manufactured to provide no missing parts, no leaks; easily identifiable exceptional reliability and reduce installation time&labor costs associated with field for approvals assembly. In accordance with NFPA 24,the UUFM approved In-Building Risers •Includes Test Cap and Coupler replace numerous fittings,elbows&spools and reduces the possibility of leaks or failure in comparison to traditional installation methods and materials. Factory tested •UUFM approved integrity ensures the highest quality installation.The use of stainless steel significantly •Sizes:available in 4"-10" (100-250mm) increases the reliability and life of the riser. with various lengths to meet local require- ments *The wetted surface of this product contacted by consumable water contains less •Designed to meet NFPA 24 than 0.25%of lead by weight. •AWWA C900 Inlet/DIP •AWWA C606 Outlet Ames Fire&Waterworks product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measure- ments,please contact Ames Fire&Waterworks Technical Service.Ames Fre&Waterworks reserves the right to change or modify product design,construction, specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames Fre&Waterworks products A M E S previously or subsequently sold. FIRE&WATERWORKS~ Specifications Standards • In-Building Riser shall be installed as indicated on the plans. NFPA— Designed to allow the contractor to conform to NFPA Riser shall be composed of a single extended 90 degree fitting 24 of fabricated 304 stainless steel tubing, maximum working Where a riser is close to building foundations,underground pressure 200psi(14 bar).The fitting shall have a grooved-end fittings of proper design and type shall be used to avoid pipe joints connection on the outlet(building)side and a CIPS coupler on being located under the foundations. the inlet(underground)side.The grooved end shall include a coupler and cap to facilitate testing of the underground pip- End Connections ing.The In-Building Riser shall be an Ames Fire&Waterworks Series IBR. Horizontal End:Mates with Ductile Iron Pipe and AWWA 0900 Pipe(PVC Pipe with Ductile Iron Pipe Equivalent OD's) Utilizes Gasket conforming to UL 157 with"Lock in" gasket configuration Approvals Fittings FM class 1920 SIZE(DN) MATING PIPE OD UL HKQA(4"-10") in. mm in. mm ® ® 4 100 4.8 122 6 150 6.9 175 8 200 9.1 230 10 250 11.1 282 Dimensions—Weights A I I Vertical End: LIM Meets AWWA C-606 dimensions for roll grooved pipe �---- Grooved End Meets AWWA C-207 class D for flanges (Flange Optional) Ratings Meets AWWA C-900 pressure class 200,DR 14 Pipe B Testing Welds are 100%leak tested at the factory illi ----1 CIPS Coupling Tie Rod Bracket SIZE DESIGN PROOF PRESSURE in. mm psi bar I 4 100 1000 70 I 4 C .I 6 150 1000 70 I 8 200 800 56 10 250 800 56 SIZE(DN) WEIGHT A(OD) B C in. mm in. mm ft. cm ft cm lbs. kg NOTICE 4 100 41/2 114 6 183 6 183 71 32 Inquire with governing authorities for local installation 6 150 6% 168 6 183 6 183 98 44 requirements 8 200 85/8 219 6 183 6 183 129 59 10 250 103/4 273 6 183 6 183 202 92 '*Each B(vertical)and C(horizontal)leg is customizable from 3'to 20'with UUFM NOTICE approvals.Consult with your factory representative for details. The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer.You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product. A AMES FIRE&WATERWORKS~ A Watts Water Technologies Company USA:Backflow Tel:(978)689-6066•Fax:(978)975-8350•AmesFireWater.com USA:Control Valves Tel:(713)943-0688•Fax:(713)944-9445•AmesFireWater.com Canada: Tel:(905)332-4090•Fax:(905)332-7068•AmesFireWater.ca Latin America: Tel:(52)81-1001-8600•Fax:(52)81-8000-7091 •AmesFireWater.com ES-A-InBuildingRiser 1540 ©2015 Ames Fire&Waterworks • P BELLS ® The Symbol of Protection PBA-AC &MBA-DC Bells Dimensions Inches(mm) Wiring(rear view) Fig. 1 Fig.3 A.C.BELLS H. WHITE(r WHITE(OUT) (250) $„ l-—a.c�.—-1 (200) 6 FROM CONTROLPANE (150) l7 _ R PRECEDING BELL .11 � J r‘M'illei 1 iiii BLACK(IN) AIIIIIIMMA111111111111 BLACK(OUT) CAUTION: 211/I6" WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN. (68) NOTES: DWG#776-1 I.WHEN USING AC BELLS,TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL. 2.END-OF-LINE RESISTOR.IS NOT REQUIRED ON AC BELLS. DWGI 776-3 Weatherproof Backbox Dimensions Inches(mm) Fig.2 FACP Box has one threaded 1/2"conduit entrance L911-1 SI 5 3/4" O _ 3 3/8" 5" + To Next (146) (86) (127) Device or - End-of-Line I� ��% Resistor ___J 1 5/8" 3 3/8") (866) I (41) f_ 4 1/4" (108) Installation DWG#776-2 1. The bell shall be installed in accordance with NFPA 13,72,or local AHJ.The top of the device shall be no less than 90"AFF and not less than 6"below the ceiling. 2. Remove the gong. 3. Connect wiring(see Fig.3). li 0 4. Mount bell mechanism to backbox(bell mechanism must be Dmounted with the striker pointing down). 5. Reinstall the gong(be sure that the gong positioning pin,in the /� mechanism housing,is in the hole in the gong). Z. 6. Test all bells for proper operation and observe that they can BBx-1 ti be heard where required(bells must be heard in all areas as designated by the authority having jurisdiction). Failure to install striker down will prevent bell from operating. PRINTED IN USA MFG.#5400776-REV Y-1 PAGE 2 OF 2 01/13 Product Information FAIL. I FS-ONE High Performance Intumescent P. Firestop Sealant , :} Product description ■ Intumescent(expands when exposed to fire)firestop sealant that .. helps protect combustible and non-combustible penetrations for up to 4 hours fire ratingx r Product features • Smoke,gas and water resistant after material has cured ,. b4 • Contains no halogen,solvents or asbestos "s' L� , ■ High fire rating propertiesV'r .. t ;< ; • Water based,easy to clean ° ° • Protects most typical firestop penetration applications ■ Paintable '.'.'..n. . ©ata" "." 6! l;" ■ Single component systems available Chemical basis Water-based intumescent acrylic ■ Meets LEEDTm requirements for indoor environmental quality credit dispersion 4.1 Low Emitting Materials,Sealants and Adhesives and 4.2 Paints Color Red and Coatings Application temperature 40°F to 104°F(5°C to 40°C) Skin forming time Approx.20-30 min. Areas of application Curing time Approx.2 mm/3 days ■ Steel,copper and EMT pipes Movement capability Approx.5% • Insulated steel and copper pipes Expansion rate(unrestricted) Up to 3-5 times original volume ■ Cable bundles Temperature resistance(cured) -40°F to 212°F(-40°C to 100°C) • Closed or vented plastic pipes Surface burning characteristics Flame Spread:0 • HVAC penetrations (ASTM E 84-96) Smoke Development:5 Sound transmission classification 56(Relates to specific construction) For use with (ASTM E 90-99) • Concrete,masonry,drywall and wood floor assemblies Approvals • Wall and floor assemblies rated up to 4 hours •California State Fire Marshal- No.4485-1200:108 •City of New York-MEA 326-96-M Vol.IV Examples Tested in accordance with ■ Sealing around combustible pipe penetrations in fire rated •UL 1479 •ASTM E 814 •ASTM E 84 construction *At 73°F(23°C)and 50%relative humidity ■ Sealing around non-combustible penetrations in fire rated construction c,psO° FILL,EOID OR CAVITY MATERITL v FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS ® •Y ITsU COMPATIBLE C Us SEE UL FIRE RESISTANCE DIRECTORY 66Y7 APPROVED Installation instructions for FS-ONE Notice 4. Smoothing of firestop sealant:To complete the • On materials where oil,plasticizers or solvents may • Before handling,read Material Safety Data Sheet seal,tool immediately to give a smooth appearance. bleed i.e.impregnated wood,oil based seals,green and product label for safe usage and health Excess sealant,prior to curing,can be cleaned away or partially vulcanized rubber information. from adjacent surfaces and tools with water. • In any penetration other than those specifically • Instructions below are general guidelines—always 5. Leave completed seal undisturbed for 48 hours. described in this manual or the test reports refer to the applicable drawing in the UL Fire 6. For maintenance reasons,a penetration seal could storage Resistance Directory or Hilti Firestop Systems Guide be permanently marked with an identification plate. • for complete installation information Store toedly in fromthe original packagingt in a location p In such a case,mark the identification plate and protected moisture at temperatures between Opening fasten it in a visible position next to the seal. 40°F(5°C)and 86°F(30°C) 1. Clean the opening.Surfaces to which FS-ONE will Not for use • Observe expiration date on the packag be applied should be cleaned of loose debris,dirt, • High movement expansion joints oil,moisture,frost and wax.Structures supporting • Underwater penetrating items must be installed in compliance with local building and electrical standards. LIJ Application of firestop sealant m 10 ,. ~1Eh1Ek 0-- s .,ter, 2. Install the prescribed backfilling material type and Q depth to obtain the desired rating(if required).Leave v sufficient depth for applying FS-ONE. 3. Application of firestop sealant:Apply FS-ONE to the 1.Clean opening. 2.Pack mineral wool. 3.Apply FS-ONE. 4.Smooth 5.Leave completed 6.Fasten identification (If required) FS-ONE. seal undisturbed for plate)f required). required depth in order to obtain the desired fire rating. 48 hours. Make sure FS-ONE contacts all surfaces to provide maximum adhesion.For application of FS-ONE use a ��. A/ llik standard caulking gun,foil pack gun,bulk loader and W f' 1 A bulk gun.With FS-ONE buckets,Graco type sealant a � ' pumps may be used.(Contact pump manufacturer for a ! I -- proper selection). 1.Clean opening. 2.Pack mineral wool. 3.Apply FS-ONE. 4.Smooth 5.Leave completed 6.Fasten Identification (If required) FS-ONE. seal undisturbed for plate(if required). 48 hours. Hilti. Outperform. Outlast. Hilti,Inc.(U.S.)1-800-879-8000•www.us.hilti.com•en espanol 1-800-879-5000•Hilti Firestop Systems Guide . • f1/1,11-pri,i, S‘ih ty P it MSDS No.: 259 Revision No.: 010 Revision Date: 08/17/04 Page: 1 of 2 Product name: FS-ONE High Performance Intumescent Firestop Sealant Description: One-part acrylic-based sealant Supplier: Hilti,Inc. P.O.Box 21148,Tulsa,OK 74121 Emergency#(Chem-Trec.): 1 800 424 9300(USA,PR,Virgin Islands,Canada);001 703 527 3887(other countries) INGREDIENTS AND EXPOSURE LIMITS Ingredients: CAS Number: PEL: TLV: STEL: Polyacrylate dispersion Mixture NE NE NE Calcium carbonate 001317-65-3 5 mg/m,(1) 10 mg/m.3(T) NE Zinc borate 138265-88-0 NE NE NE Ammonium polyphosphate 068333-79-9 NE NE NE Talc 014807-96-6 20 mppcf 2 mg/m3 NE Expandable graphite 012777-87-6 5 mg/m3(1) 2 mg/m3 M NE Ethylene glycol 000107-21-1 NE C:100 mg/m,(A) NE Polybutene 009003-29-6 NE NE NE Iron oxide 001309-37-1 10 mg/rn" 5 mg/113 NE Glass filament 065997-17-3 NE 5 mg/m3(T) NE Silicon dioxide 014808-60-7 0.05 mg/m3(T) 0.1 mg/m'M NE Water 007732-18-5 NE NE NE Abbreviations: PEL=OSHA Permissible Exposure Limit. TLV=ACGIH Threshold Limit Value. 0=Ceiling. STEL=Short Term Exposure Limit. NE=None Established. NA=Not Applicable. (T) indicates"as total dust". (R)indicates"as respirable fraction". (A)indicates as an aerosol". mppcf=million particles per cubic foot. PHYSICAL DATA Appearance: Red paste. Odor: Odorless. Vapor Density: (air=1) Not determined. Vapor Pressure: 23mbar 0 20C/68F Boiling Point: Not applicable. VOC Content: 75.0 g/L. Evaporation Rate: Not applicable. Solubility in Water: Soluble. Specific Gravity: 1.5 pH: Not determined. FIRE AND EXPLOSION HAZARD DATA Flash Point: Non-flammable. Flammable Limits: Not applicable. Extinguishing Media: Not applicable. Use extinguishing media as appropriate for surrounding fire. Special Fire Fighting Procedures: None known.Use a self-contained breathing apparatus when fighting fires involving chemicals. Unusual Fire and Explosion Hazards: None known. Thermal decomposition products can be formed such as oxides of carbon, sulfur and phosphorous. REACTIVITY DATA Stability: Stable. Hazardous Polymerization: Will not occur. Incompatibility: Strong acids, peroxides,and oxidizing agents. Decomposition Products: Thermal decomposition can yield CO and CO2. Conditions to Avoid: None known. HEALTH HAZARD DATA Known Hazards: None known. Signs and Symptoms of Exposure: Possibly irritating upon contact with the eyes or upon repeated contact with the skin. Medical Conditions Eye and skin conditions. Aggravated by Exposure: Routes of Exposure: Dermal. p Hilti Firestop / I Saving Lives a through innovation I and education Haiti. Outperform. Outlast. H/ti, Inc.(U.S,)1-800-879-8000•www.whilti.com•en espanol 1-800-879-5000•Hatt(Canada)Corp.1-800-363-4458 viww.hilti.ca • Muter ial Safety I ata St,ttt MSDS No.: 259 Revision No.: 010 Revision Date: 08/17/04 Page: 2 of 2 Carcinogenicity: IARC classifies crystalline silica(quartz sand)as Group I based upon evidence among workers in industries where there has been long-term and chronic exposure(via inhalation)to silica dust;e.g.mining,quarry,stone crushing,refractory brick and pottery workers. This product does not pose a dust hazard;therefore,this classification is not relevant. Based upon the nature and intended use of this product,it does not pose an increased cancer risk to workers. EMERGENCY AND FIRST AID PROCEDURES Eyes: Immediately flush with plenty of water. Call a physician if symptoms occur. Skin: Immediately wipe off material and wash with soap and water. Material can adhere to the skin. if material has adhered to the skin,use an abrasive containing hand cleaner. If material does not come off,buff with a pumice stone. lydialation: Move victim to fresh air if discomfort develops. Call a physician if symptoms persist. Ingestion: Seek medical attention. Do not induce vomiting unless directed by a physician. If a large quantity was ingested,give 1 to 2 glasses of water to dilute. Never give anything by mouth to an unconscious person. Other: Referral to a physician is recommended if there is any question about the seriousness of the injury/exposure. CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT Ventilation: General(natural or mechanically induced fresh air movements). Eye Protection: Not required,however,safety glasses should be worn in most industrial settings. Skin Protection: Avoid skin contact.Cloth gloves are suitable for hand protection. n. _ Respiratory Protection: None normally required. Where ventilation is inadequate to control vapors,use a NIOSH- approved respirator with organic vapor cartridges. Never enter a confined space without an appropriate air-supplied respirator. PRECAUTIONS FOR SAFE HANDLING AND USE Handling and Storing Precautions: Store in a cool,dry area preferably between 40o and 77o F. Keep from freezing. Do not store in direct sunlight. Avoid contact with the eyes or skin. Practice good hygiene;i.e. always wash thoroughly after handling and before eating or smoking. For industrial use only. Keep out of reach of children. Follow labeVuse instructions. Spill Procedures: Immediately wipe away spilled material before it hardens. Place in a container for proper disposal in accordance with all applicable local,state,or federal requirements. REGULATORY INFORMATION Hazard Communication: This MSDS has been prepared in accordance with the federal OSHA Hazard Communication Standard 29 CFR 1910.1200. HMIS Codes: Health 1, Flammability 0, Reactivity 0, PPE B DOT Shipping Name: Not regulated. IATA/ICAO Shipping Name: Not regulated. TSCA Inventory Status: Chemical components listed on TSCA inventory.SARA Title Ill,Section 313:This product contains<3%ethylene glycol(CAS 107-21-1)and<15%zinc borate(re:zinc compounds)which are subject to reporting under Section 313 of SARA Title III(40 CFR Part 372). EPA Waste Code(s): Not regulated by EPA as a hazardous waste. Waste Disposal Methods: Consult with regulatory agencies or your corporate personnel for disposal methods that comply with local,state,and federal safety,health and environmental regulations. CONTACTS Customer Service: 1 800 879 8000 Technical Service:1 800 879 8000 Health/Safety: 1 800 879 6000 Jerry Metcalf(x6704) Emergency# (Chem-Tree): 1 800 424 9300(USA,PR,Virgin Islands,Canada); 001 703 527 3887(other countries) The information and recommendations contained herein are based upon data believed to be correct;however,no guarantee or warranty of any kind expressed or implied is made with respect to the information provided. PT51 . mil Hilti Firestop Saving Lives trough innovation and education Hilti. Outperform. Outlast. Nitta,Inc.(U:S.)1-800-879-8000•www.us.hJRt.com•en espanol 1-800-879-5000•Hitti(Canada)Corp.1-800-383-4458 www.hitti4a Crti#iia p of Gam lance Certificate Number 20100512-R13240 Report Reference 2010 May 12 Underwriters Page 1 of i Issue Date 2010 May 12 t Laboso r ori Issued to: Hilti, Inc 54 S 122ND East Ave Tulsa,OK 74I46 USA This is to certify that Fiji, Void or Cavity Materials representative samples oof FS-ONE Have been investigated by Underwriters Laboratories Inc.®(UL)or any authorized licensee of UL in accordance with the Standard(s)indicated on this Certificate. Standard(s)for Safety: ANSUUL 1479,ANSI/UL 2079,CAN/UI.,C-SI 15-05 Third Edition,revised March 1,201• Additional Information: FS-ONE Sealant for use in Joint Systems and FS-ONE for use in Through-Penetration Firestop Systems as currently described in the UL Fire Resistance Directory. Only those products bearing the UL Classification Mark should be considered as being covered by UL's Classification and Follow-Up Service. The UL Classification Mark includes:UL in a circle symbol 4�J with the word"CLASSffTED"(as shown);a control number . (may be alphanumeric)assigned by UL;a statement to indicate the extent of UL s evaluation of the product, and,the product category name(product idenhry)as indicated in the appropriate;UL Directory Look for the LJL Classification Mark on the product Reviewed IIssuedby: � o, .t.Ne��l -. Mr " ,• f .i s1.4 :* Certificate of Corn s fiance Certificate Number 20060214-RI3240E Page 1 of 1 Report Reference 2006 February 14 Issue Date 2006 February 14 Underwriters L Laboratories Issued to: Hilt!, Inc. 5400 S 122ND East Ave Tulsa,OK 74146 USA This is to certify that Fill, Void or Cavity Materials representative samples of FS-ONE Have been investigated by Underwriters Laboratories Inc.®in accordance with the Standard(s) indicated on this Certificate. Standard(s)for Safety: ANSI/UL 1479,ANSI/UL 2079,CAN/ULC-S115-05 Additional Information: FS-ONE Sealant for use in Joint Systems and FS-ONE for use in Through- Penetration Firestop Systems as currently described in the UL Fire Resistance Directory. Only those products bearing the UL Classification Mark should be considered as being covered by UL's Classification and Follow-Up Service. The UL Classification Mark includes: UL in a circle symbol: II with the word "CLASSIFIED" (as shown); a control number (may be alphanumeric) assigned by UL; a statement to indicate the extent of UL's evaluation of the product;and,the product category name(product identity)as indicated in the appropriate UL Directory. Look for the UL Classification Mark on the product Issued by: Reviewed by: na Colouto uChristopher =i n lo Underwriters Laboratories Inc. Underwriters .ratories Inc. MITI Hilti North America 5400 South 122nd East Avenue Tulsa,OK 74146 P.O.Box 21148 I Tulsa,OK 74121-1148 T 1-800-879-8000 I F 918-252-6742 www.hilti.com June 27, 2008 To Whom It May Concern: Re: Hilti FS-ONE Intumescent Firestop The Hilti FS-ONE Intumescent Firestop is manufactured in Kaufering, Germany. The FS-ONE pail is made of polyethylene and can be completely recycled. There is no post- consumer or post-industrial content in FS-ONE and it cannot be recycled. The VOC content for FS-ONE is 75 grams/liter. FS-ONE is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 252-6704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc (918) 252 6704 jerry.metcalf(a,hilti.com NOTES/DEFINITIONS: 1. Post-Consumer Recycled Content: Portion of material or product derived from discarded consumer waste that has been recovered for use as a raw material[e.g.,plastic bottles, newspaper] 2. Post-Industrial Recycled Content: Portion of material or product derived from recovered industrial and mfg.materials that are diverted from municipal solid waste for use in a different mfg.process,prior to use by a consumer[e.g.,fly-ash in concrete or synthetic gypsum board,both of which are by-products of coal-burning power plants].Spills and scraps from the original manufacturing process that are combined with other constituents after a minimal amount of reprocessing for use in further production of the same product do not qualify. 3. Manufactured: Final assembly of components into building product that is furnished and installed by trades[e.g.,if the hardware comes from Dallas,TX,the lumber from Keene, NH,and the joist is assembled in Kent,WA;then the location of final assembly is Kent,WA]. www.apsvisualizer.com/calculators can be used to calculate straight-line distance between project site/New York,NY and location of manufacture and raw material source. Note:location noted on material data sheets is often corporate location;need manufacturer to verify actual manufacture location. 4. Raw Materials: Virgin or recovered resources from which the product's components are made[i.e.,before processing or manufacturing]. 5. Rapidly Renewable: Materials and products made from raw materials that are harvested within a 10-year cycle[e.g.,bamboo,cork,linoleum,fast-growing poplar,wheatboard,wool carpet]. 6. FSC Certified: Wood-based products that are certified by the Forest Stewardship Council and carry a Chain-of-Custody certificate number from the vendor or manufacturer. 7. VOC Content: The quantity of volatile organic compounds contained in products such as adhesives,sealants and architectural coatings.VOC content is to be reported in grams/liter or lbs/gallon,less water and any exempt compounds/solvents. CONTRACTOR CERTIFICATION: I, a duly authorized representative of hereby certify that the information contained herein accurately represents the listed"green building"characteristics of the materialto be provided by our company as components of the building construction.Furthermore, I understand that any change in such"green building"material characteristics during the purchasing and/or installation period will require prior written approval from the Construction Manager and Owner. SIGNATURE OF AUTHORIZED REPRESENTATIVE: DATE: p. of • 11.41,11.11.1.1 I MSDS No.: 259 Revision No.: 010 Revision Date: 08/17/04 ® Page: 1 of 2 MA;. TERiAL SAFETY DATA SHEET .. Product name: FS-ONE High Performance Intumescent Firestop Sealant Description: One-part acrylic-based sealant Supplier: Hilti, Inc. P.O.Box 21148,Tulsa,OK 74121 Emergency#(Chem-Trec.): 1 800 424 9300(USA,PR,Virgin Islands,Canada);001 703 527 3887(other countries) INoREDIENTS AND EXPOSURE LIMITS ' u.. �� '� '^ ,"� (,�i a Polyacrylate dispersion Mixture NE NE NE Calcium carbonate 001317-65-3 5 mg/m3(T) 10 mg/m3(T) NE Zinc borate 138265-88-0 NE NE NE Ammonium polyphosphate 068333-79-9 NE NE NE Talc 014807-96-6 20 mppcf 2 mg/m3 NE Expandable graphite 012777-87-6 5 mg/m3(T) 2 mg/m3(T) NE Ethylene glycol 000107-21-1 NE C:100 mg/m3(A) NE Polybutene 009003-29-6 NE NE NE Iron oxide 001309-37-1 10 mg/m3 5 mg/m3 NE Glass filament 065997-17-3 NE 5 mg/m3(T) NE Silicon dioxide 014808-60-7 0.05 mg/m3(T) 0.1 mg/m3(T) NE Water 007732-18-5 NE NE NE Abbreviations: PEL=OSHA Permissible Exposure Limit. TLV=ACGIH Threshold Limit Value. C=Ceiling. STEL=Short Term Exposure Limit. NE=None Established. NA=Not Applicable. (T)indicates"as total dust". (R)indicates"as respirable fraction". (A) indicates"as an aerosol". mppcf=million particles per cubic foot. PHYSICAL DATA x Appearance Red paste. r' Odorless. g/L. Vapor Density: (air=1) Not determined. \/apor Pressure: ,. 23mbar @ 20C/68F Boding Pomt: Nota livable. pp IOC''Coratent 75.0 l Evaporation Rate; -" Not applicable. Solubility m Nater Soluble. Specific cavity, ." 1.5 ''' Not determined. r FIRE AND EXPLOSIC N HAZARD=DATA , w� u . , Flash point. Non-flammable. Flammable Ltmtts Not applicable. xtingurshingMfliedia r Not applicable. Use extinguishing media as appropriate for surrounding fire. Special Fare i=fighting£ :: None known. Use a self-contained breathing apparatus when fighting fires involving chemicals. Procedures ry ainusua Fire and Explosion'` None known. Thermal decomposition products can be formed such as oxides of carbon, sulfur Hazards: and phosphorous. REACTIVITY DATA Stability Stable. Hazardous Polymerization. Will not occur. incompatibility Strong acids,peroxides,and oxidizing agents. Dedomposition Products: .. Thermal decomposition can yield CO and CO2. Conditions to,Avoid; £` None known. HEALTH HAZARD DATA : , Known#1azards None known. Signs and Symptoms of' Possibly irritating upon contact with the eyes or upon repeated contact with the skin. Exposure.<. Medical Conditions, Eye and skin conditions. Aggravated by F_xposure:. Routes of Exposure Dermal. HILTI®is a registered trademark of Hilti Corp. • 7 Carcinogens sty IARC classifies crystalline silica(quartz sand)as Group I based upon evidence among workers in industries where there has been long term and chronic exposure (via inhalation) to silica dust; e.g. mining, quarry, stone crushing, refractorybrick and pottery workers. This product does not pose a dust hazard; therefore, this classification is not relevant. Based upon the nature and £; intended use of this product,it does not pose an increased cancer risk to workers EMERGENCY AND FIRST ID PROCEDURE Immediately flush with plenty of water. Call a physician if symptoms occur. 1,..1:Ski Eyes:. x , Immediately wipe off material and wash with soap and water. Material can adhere to the skin. If material has adhered to the skin, use an abrasive containing hand cleaner. If material does not #. come off,buff with a pumice stone. lnhaIatiti i n f; Move victim to fresh air if discomfort develops. Call a physician if symptoms persist. lntror Seek medical attention. Do not induce vomiting unless directed by.a physician. If a large quantity was ingested, give 1 to 2 glasses of water to dilute. Never give anything by mouth to an unconscious person. Referral to a physician is recommended if there is any question about the seriousness of the 'en'',er , injury/exposure f. CONTROL MEASURES;'ANO PERSONAL.PROTECTIVE EQUI('.MEI i ::%M Vent lath n: General(natural or mechanically induced fresh air movements). Eyerotection Not required,however,safety glasses should be worn in most industrial settings. kir[Pro ection n Avoid skin contact.Cloth gloves are suitable for hand protection. esplrat a►y Protection None normally required. Where ventilation is inadequate to control vapors, use a NIOSH approved respirator with organic vapor cartridges. Never enter a confined space without an r appropri•ate air supplied respirator. PRECAUTIONS FOR SAID"#HAND NG rAND USE 7 H ndIJng and$onng Store in a cool,dry area preferably between 40°and 77°F. Keep from freezing. Do not store in Preca roes: direct sunlight. Avoid contact with the eyes or skin. Practice good hygiene; i.e. always wash thoroughly after handling and before eating or smoking. For industrial use only. Keep out of reach of children. Follow label/use instructions. piWProcetlures Immediately wipe away spilled material before it hardens. Place in a container for proper disposal ,.. w.,.f in accordance with all applicable local,state or federal requirements. RE UL.AT4SR'Y.I FORMAiTII N Hazard Communication This MSDS has been prepared in accordance with the federal OSHA Hazard Communication ''''''''r r Standard 29 CFR 1910.1200. SMI,Codes Health 1, Flammability 0, Reactivity 0, PPE B DOT hipping Nadie Not regulated. r 1ATA I ICAO'Shipping Islame Not regulated. TSAf "ven# ry tatU . Chemical components listed on TSCA inventory. SARA�Ie`II,Sectio 313 This product contains < 3% ethylene glycol (CAS 107-21-1) and < 15% zinc borate (re: zinc ' compounds) which are subject to reporting under Section 313 of SARA Title III (40 CFR Part 372). w n;. SPA Waste Codes) Not regulated by EPA as a hazardous waste. 4 . `�PA r a ie 4,,,,itIlf hod''' Consult with regulatory agencies or your corporate personnel for disposal methods that comply _, ; with local,state,and federal safety,health and environmental regulations. CONTACTS Customer Service` 1 800 879 8000 Technical"Service . 1 800 879 8000 Health/Safety; 1 800 879 6000 Jerry Metcalf (x6704) Emergency#(Cheat-Trec) 1 800 424 9300(USA,PR,Virgin Islands,Canada); 001 703 527 3887(other countries) The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or warranty of any kind expressed or implied is made with respect to the information provided. MSDS 259, Page 2 of 2 4 4 CALIFORNIA DEPARTMENT OF FORESTRY&FIRE PROTECTION "°F '" OFFICE OF THE STATE FIRE MARSHAL CAL IRE FIRE ENGINEERING— BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE , ,, LISTING No. 4485-1200:108 Page 1 of 1 CATEGORY: Opening Protection (Firestopping) LISTEE: Hilti, Inc., 5400 S. 122nd East Ave, Tulsa, OK 74146 Contact: *Clay Hensley(918)252-6216 Fax(918)254-1679 DESIGN: Model FS-ONE Firestop Sealant. Refer to listee's printed data sheet and UL Fire Resistance Directory for additional detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes&ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name,type identification and UL label. APPROVAL: Listed as firestop devices for use in through-penetration firestop system up to 3 hour rating. For indoor use only. Approved under Through-Penetration Fire Stop Systems: CAJ1155, CAJ2091, CAJ2118, CAJ3095, CAJ5044, CAJ8041, F-C-2025, WL1085, WL1056, WL3047,WL5029, WL8004. Refer to UL Fire Resistance Directory for detailed constructions. eta .) *Rev.06-20-2006 [" ( This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: JUNE 10, 2008 Listing Expires June 30, 2009 Authorized By: BEN HO, Chief Fire Engineering Division Report of Materials and BUL $ Equipment Acceptance Division NYC Department of Buildings 280 Broadway, New York,NY 10007 Patricia Lancaster, FAIA, Commissioner (2l2)566-5o, TTY: (212)566-4769 Pursuant to Administrative Code Section 27-131, the following equipment or material has been found acceptable for use subject to the terms and conditions contained herein. MEA 326-96-M Vol. 5 Manufacturer: Hilti, Inc., 5400 S. 122 East Avenue, Tulsa, OK 74146 Trade Name(s): Hilti, Inc. Product: Fill,void or cavity material for fire protection Pertinent Code Section(s): 27-345 Prescribed Test(s): RS 5-19 (ASTM E814}, UL 2079 Laboratory: Underwriters Laboratories, Inc. Test Report(s): File R13240, dated July 16, 1993, July 21, 1993, July 13, 1993, July 22, 1993, April 1, 1993, March 25, 1994, March 3 and 6, 1995, September 4, 1996, September 27,1997; File R13644, dated April 12, 1993 and May 3, 1993; File R12232, dated August 2, 1993; UL-design listings. Description: Fill, void or cavity material for through-penetrations in firesrated wall and/or' floor/ceiling construction. The Hilti FS-ONE Firestop Sealant shall be applied in accordance with Underwriters Laboratorie's 'Inc:. system numbers, listed on following pages, in achieving the required fire-resistance ratings. MEA 326-96-M Vol. 5 Page 1 of 10