Loading...
Report (56) - C Atir SUMMIT ENGINEERING L.L.C. May 27, 2016 Project: New Apartments 9550 SW Greenburg Road Tigard, OR 97202 Subject: Plan check response - Application no. BUP2015-00330-335 To DAN NELSON, In response to the plan check for the above referenced project, 1) Provide footing calcs for all spread footings supporting point loads using 3000# psf as per soils report for long term loading and update plans. Response: See included calculations per designer. 2) Indicate post locations and sizes on plans. Response: A post schedule has been added to the plans to indicate post types for gravity load conditions. All posts required for lateral load conditions are either noted on plan or noted in the hold-down schedule for hold-down posts. 3) Show 3x members and staggered nailing for E type shear wall on shear wall details. Indicate top and bottom nailing forA and B shear walls. Response: Detail has been added to all sheets at the Shearwall schedule. 4) Provide Geo Tech inspection for footing prep and have onsite for footing inspection. Response: Owner to coordinate. Geotech inspection shall be completed prior to construction. 5) Show property line firewall protection for north/east corner. Response: Reference modified plans. 6) Shear wall at rear party walls does not match calcs. nl. Response: See revised plans. 7) Show all hold down locations on plans. Response: All Hold-downs are now shown on all plans, including the foundations. Reference modified plans. 8) Provide engineer calcs showing depth, length, and width of foundation at hold down locations. Response: All buildings were carefully reviewed and footing sizes were checked for all HD's for uplift. Buildings 1, 5 and 6 have been modified to include larger footings as needed. See included additional footing calculations and revised building foundation plans. 9) All ground floor units are required to be B type accessible units. Response: Reference modified plans. 10) Provide 60 inch clearance between appliances and counters on floor plans in u-shaped kitchen. Response: Reference modified plans. 11) Show option A or B for B type units. Response: Reference modified plans. 12) Show details of A type showers including controls, required grab bars. Response: Reference modified plans. 13) All general notes are to be upgraded to current code requirements. Response: Reference modified plans. 14) Provide calcs for 17ft 2x10s @ 16" oc joist on third floor framing. Response: See included calculations per designer. 15) Show connections for back span beam to cantilever beam at both ends. Response: Reference modified plans. 16) Detail#2 from calcs to be on main plans and type of hold down required. Response: Reference modified plans. 17) Detail#4 from calcs to be on main plans. Response: Reference modified plans. sn Gtl 4 65469PE OREGON tb Sincerely, , Julie Havelka, PE0 oI/ Summit Engineering, LLC , 971-251-0194 Julie@summitengineeringllc.com r' Plan Check Response for Greenburg Road Project 1. Pad footings were originally designed for 1,500 lbs, proposed footing sizes are sufficient with 3,000 soil bearing pressures.See updated foundation pages for additional footings that were added. 2. Added post sizes to all framing plans. 3. Added shearwall nailing detail number 30/DS.2 4. Contractor to coordinate with Geo-Tech for footing prep and inspection. Note added to all foundation plans showing Geo-Tech to be on site. 5. Added firewall protection at this location. 6. This has been revised 7. Plans now show all holdown locations specifically. 8. Engineering calcs updated to include this information. 9. Added note to all ground floor units 10. Note added to u-shaped kitchens 11. All type B units to be option B. Note added. 12. All units are to be Type B Units,except as noted.Shower detail added to Type A units. 13. General notes have been updated on cover sheets and on sheet WT. 14. Calcs added,joists revised to double 2X10's at 16"o.c.at 16'-10"span. 15. Added HUC610 hanger at this location 16. Added to building 2&3 shearwall plans 17. Added to building 2&3 shearwall plans t çJ1 c- i a )Ic) driii 0 11aa,s , e )\feisci _ 44111%- IP I � i - _, r �_ -- -7 -..... r Au, t-_ or / (z ` ilkI 19.....!Po:! „r■�: A i*' _ � — =�1 `f' 0' -- .....a.#1, '.Z (N?) qP3 ma __ _ (\------ , a h,imam. 411111110111111ft IIP Oh. .MIPA d ,C `k. a/__: -- - �'—�. Via=" – �1 % .4_�— U c.g .. 4.r •�A.� ' dm Mt C\���Iillk iOM �e1M_ -i imp !: .t'�3! M -".,;`.— — 1 1 MO* .r_ e.. ..r. ) -.4.= 1\1-41�XA _'"gam rt it . ,.z.- 1 i 1a., -.MO aMillipg jialkirgr Qs C7,ZtACYSI-49 _ _ — vt,_ „..•ill/... "g-k 1 N • Altril1111I--.?_.•Nrair na - -. 'im% k z.....7- tt1 Cr?) _...... , , di ." mit.-- !nom , i _ is! hair ` . , '77,0 )vp-:-------. 11-11 . 11ImmimumillmilimmilmillimlYzcz;7'8--3 C 'Acam -1-010,--14 9 -=>::::1--39., c:) - -Nl c-710 I g .41-2.1Y W --).- c'--_ 2CI. -- 1 J cy 10 _ _�`_ • 40111,1r —-4 I 4111% -ill? 1.-- -"\—\-- --i1 �J0C1, ........ a, 0 .... 1,) X11 "M fi'f r , A ivn,,,,,, -is, __. r-so...- ow.--,. - ■• err ' ) �' ai : Map ��.r.Mr.�. _ ��� .: to 4 f►� ► �'"" - *11 `� Ir tVA,Z a�.rte iw �ew.�.r. i .► \ /� ,� -� / .rim sem._ , air " _ 7 7 -- 3cr-'1114 X11 --- � -° - - I (;)- .0t - y + 099g, c309_3, c.24) ± go go) , --/F"r4- -i--z 11 ti Dan Nelson From: Dan Wilson <Dan@cepdx.com> Sent: Friday, February 19, 2016 4:22 PM To: Dan Nelson Subject: 2013 NFPA-72 23.6.1 Hi Dan, The apartment campus fire alarm design we discussed yesterday may be affected by 2013 NFPA-72 23.6.1 Performance of Signaling Line Circuits(SLCs).A single fault on a pathway connected to the addressable devices shall not cause the loss of more than 50 addressable devices. The way many designers make this work is with addressable isolation modules. When a short circuit on the SLC downstream of an isolation module occurs,the fault is isolated from the addressable devices upstream from the module. In a fire alarm system serving multiple buildings, we would install an isolation module on each SLC as it leaves the fire alarm control panel,on the way to another building.This would be true for single building having more than 50 devices too. Dan Wilson, SET Fire&Life Safety Division NICET Level IV,Fire Alarm Systems Capitol Electric Co.,Inc. 11401 NE Marx St,Portland,OR 97220 T:(503)255-9488 I C:(971)506-3072 I D:(503)262-0411 dan@cepdx.com I www.capitolelectricco.com Co itol Electric Co., Inc, "Celebrating 30 Years of Excellence and Innovation" The information contained in this electronic mail transmission is intended by Capitol Electric Co.,Inc.for the use of the named individual or entity to which it is directed and may contain information that is confidential or privileged.If you have received this mail transmission in error,please delete it from your system without copying or forwarding it,and notify the sender of the error by reply e-mail or calling(503)255-9488 so that the sender's records can be corrected.Thank you. 1 FOR OFFICE USE ONLY-SITE ADDRESS: This form is recognized by most building departments in the Tri-County area for transmitting information. Please complete this form when submitting information for plan review responses and revisions. This form and the information it provides helps the review process and response to your project. City of Tigard • COMMUNITY DEVELOPMENT DEPARTMENT n ' Tr a smittal Letter 13125 SW Hall Blvd. • Tigard, Oregon 97223 • 503.718.2439 •www.tigard-or.gov TO: 41/4l ti--35DAT ; : DEPT: BUILDING DIVISION AUG 1 S 2016 FROM: 1--,�.�2 ` �2 L,,l�fid '1' ` ( F i : .} COMPANY: q BUILDING DIVISION PHONE: 93 L S .c: Oc-t By: " RE: vS"b 3Uec., ew 1c-oo 3�3c) (Site Address) (Permit umber) got 5 — )J331 I 'roject name or sus ivision name an, of num,er /C - r A a 333 It tf 3 351 ATTACHED ARE THE FOLLOWING ITEMS: 11 tt 335" Additional set(s)of plans. a Revisions: Cross section(s)and details. Wall bracing and/or lateral analysis. Floor/roof framing. Basement and retaining walls. Beam calculations. Engineer's calculations. Other(explain): REMARKS: '4 Routed to Permit Technician:, Date: Fees Due: ■ Yes Fee Descri tion: Amo sl ►ue: Special Instructions: Re.rint Permit ser PE : ❑ Yes ❑No ❑ Done A. .licant Notified: Date: Initials: I:\Building\Forms\TransmittalLetter-Revisions.doc 05/25/2012 FOR OFFICE USE ONLY—SITE ADDRESS: This form is recognized by most building departments in the Tri-County area for transmitting information. Please complete this form when submitting information for plan review responses and revisions. This form and the information it provides helps the review process and response to your project. City of Tigard • COMMUNITY DEVELOPMENT DEPARTMENT Tr • �� Transmittal Letter 7 13125 SW Hall Blvd. • Tigard, Oregon 97223 • 503.718.2439 •www.tigard-or.gov TO: D C -e`S Or\ DATE RECEIVED: DEPT: BUILDING DIVISION RECEIVED FROM: L ' I_, f'le '2,, -F 14 APR 1 8 2016 COMPANY: 'AV elft rt—e -N Z7 L1 1 kdeA5 Ilk` UU Dl�l{fit N PHONE: o3— tOC6o '` 60 ,,�t11 �Ut�iLDINC�S By: RE: 4510 SSao q$30,95 70aSTai a5-/-0 (Site Alidress) s W &re jaoure ( (Permit Number) diApaols---ao 331 (Project ct me or sub ' ision'fame and lot number ��1r-�C�3 844,00 15_'-- 1-1 ATTACHED ARE THE FOLLOWING ITEMS: -`!'2�cs�-(->c)• 5 ; '); i 'l r `� ; Yc.;' Ps} t "per+ Additional set(s)of plans. Revisions: Cross section(s)and details. Wall bracing and/or lateral analysis. Floor/roof framing. Basement and retaining walls. Beam calculations. / Engineer's calculations. Other(explain): REMARKS: eta^ r!..= p`>°st �.. Routed to Permit Technician: Date: 6 liTINNIIIIMNIEMEWRii1111111 Fees Due: • Yes (iso Fee Descristion: $ $ Special Instructions: Re.rint Permit 'er PE : ❑ Yes ❑No • Done A I .licant Notified: Date: Initials: I:\Building\Forms\TransmittalLetter-Revisions.doc 05/25/2012