Loading...
Plans (30) ABBREVIATIONS ELECTRICAL NOTES JURISDICTION NOTES A AMPERE 1. THIS SYSTEM IS GRID-INTERTIED VIA A AC ALTERNATING CURRENT UL-LISTED POWER-CONDITIONING INVERTER. litCEIVE1 BLDG BUILDING 2. THIS SYSTEM HAS NO BATTERIES, NO UPS. • CONC CONCRETE 3. A NATIONALLY-RECOGNIZED TESTING DC DIRECT CURRENT LABORATORY SHALL LIST ALL EQUIPMENT IN OCT 8 2014 EGC EQUIPMENT GROUNDING CONDUCTOR COMPLIANCE WITH ART. 110.3. . (E) EXISTING 4. WHERE ALL TERMINALS OF THE DISCONNECTING CITY OFTIGARD EMT ELECTRICAL METALLIC TUBING MEANS MAY BE ENERGIZED IN THE OPEN POSITION, FSB FIRE SET-BACK A SIGN WILL BE PROVIDED WARNING OF THE BUILDING DIVISION GALV GALVANIZED HAZARDS PER ART. 690.17. GEC GROUNDING ELECTRODE CONDUCTOR 5. EACH UNGROUNDED CONDUCTOR OF THE GND GROUND MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY CITY OF TIGARD HDG HOT DIPPED GALVANIZED PHASE AND SYSTEM PER ART. 210.5. I CURRENT 6. CIRCUITS OVER 250V TO GROUND SHALL REVIEWED FOR CODE COMPLIANCE Imp CURRENT AT MAX POWER COMPLY WITH ART. 250.97, 250.92(B). OTS Approved: I Isc SHORT CIRCUIT CURRENT 7. DC CONDUCTORS EITHER DO NOT ENTER kVA KILOVOLT AMPERE BUILDING OR ARE RUN IN METALLIC RACEWAYS OR I I A kW KILOWATT ENCLOSURES TO THE FIRST ACCESSIBLE DC Permit#: 144T2614--(Z)(7 LBW LOAD BEARING WALL DISCONNECTING MEANS PER ART. 690.31(E). MIN MINIMUM 8. ALL WIRES SHALL BE PROVIDED WITH STRAIN Address: I7 (11 f( s ._ ► I ,;,, (N) NEW RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY Suite NEUT NEUTRAL UL LISTING. NTS NOT TO SCALE 9. MODULE FRAMES SHALL BE GROUNDED AT THE B . ~ Data I .- OC ON CENTER UL-LISTED LOCATION PROVIDED BY THE PL PROPERTY LINE MANUFACTURER USING UL LISTED GROUNDING Approved plans P01 POINT OF INTERCONNECTION HARDWARE. pp PV PHOTOVOLTAIC 10. MODULE FRAMES, RAIL, AND POSTS SHALL BE shall be on job site. SCH SCHEDULE BONDED WITH EQUIPMENT GROUND CONDUCTORS. S STAINLESS STEEL STC STANDARD TESTING CONDITIONS OFFICE COPY TYP TYPICAL UPS UNINTERRUPTIBLE POWER SUPPLY I V VOLT V cVmp VOLTAGE AT OPENVOLTAGE AT MAX PCIRCUIT OWER VICINITY MAP INDEX W WATT 3R NEMA 3R, RAINTIGHT _ Sr �' - PV1 COVER SHEET ;.. w , _4. - PV2 SITE PLAN L,,,,,‘,01, ,.., ...1,:l.. .i,'-' -, , `%,..' , #.- ,4 i , -E.Twrir lirr°`� PV3 STRUCTURAL VIEWS `, ` '` PV4 UPLIFT CALCULATIONS �� �� „r ; ,sPV5 THREE LINE DIAGRAM LICENSE GENERAL NOTES f e",� PV6 ELECTRICAL CALCULATIONS 1. ALL WORK TO BE DONE TO THE 2010 OBC stcrIf x OR # 180498 k �- ��-.•. - "� " I. _ Cutsheets Attached BASED ON THE 2009 IBC. _' "Ret.set'Voir _ f - t= f a k 2. ALL ELECTRICAL WORK SHALL COMPLY WITH THE CURRENT NATIONAL ELECTRIC CODE AS ii :§ $ - .. •". rt I ' e, II' i . AMENDED BY THE OREGON ELECTRICAL SPECIALTY M► a"a CODE. •; " ` ". ` t.?,, ` ' !�► , . r MODULE GROUNDING METHOD: ZEP SOLAR - - Imo"` L`'ik`" 1 s AHJ: Tigard 0 SURIt?1e1 lake City Park , cn it, •„ :A, a_ A ' 1 REV BY DATE COMMENTS ° '�� � df «,„ '. . 1=111:11 DATE COMMENTS UTILITY: Portland General Electric its - '�, ©®® s .4tcrt ra r •rt end Oregon. aa{ . CONFIDENTIAL — THE INFORMATION HEREIN JOB NUMBER: J3-9722191 0 0 PREMISE OWNER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE KENYON, PAM KENYON RESIDENCE Aaron Banks ��!• • BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: ` SolarC�ty NOR SHALL IT BE DISCLOSED IN WHOLE OR IN 12207 SW MILLVIEW CT �•��° PART TO OTHERS OUTSIDE THE RECIPIENTS Comp Mount Type C 6.63 KW PV ARRAY �r ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES: TIGARD, OR 97223 THE SALE AND USE OF THE RESPECTIVE (26) TRINA SOLAR # TSM-255PA05.18 3055 Clearview Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET: REV: DATE: San Mateo, CA 94402 PERMISSION OF SOLARCITY INC. (503) 590-3113 T:(650)636-1028 F:(650)838-1029 ABB ; PVI-5000-OUTD-US-Z-ACOVER SHEET PV 1 10/2/2014 (BBB)—SOL—CITY(765-2489)www.solarcity.com I PITCH: 30 ARRAY PITCH:30 MP1 AZIMUTH: 180 ARRAY AZIMUTH: 180 MATERIAL: Comp Shingle STORY: 2 Stories PITCH: 30 ARRAY PITCH:30 MP2 AZIMUTH:90 ARRAY AZIMUTH: 90 MATERIAL: Comp Shingle STORY: 2 Stories PITCH: 30 ARRAY PITCH:30 MP3 AZIMUTH:90 ARRAY AZIMUTH:90 MATERIAL: Comp Shingle STORY: 2 Stories 12" FSB ° 0 0 0 - C) - 9 O ____ t o 0 0 o LEGEND co /--0 \D ,, ,�-,� 0 0- - 9 0 O (E) UTILITY METER & WARNING LABEL __ N YV a Q AC 'i o �\0 0 0 ;IA, 6 ® INVERTER W/ INTEGRATED DC DISCO H-H MP & WARNING LABELS 4s id B •1% DC 4111, , I . DC DISCONNECT & WARNING LABELS tPV3 Locked GatedAC I o Un-Locked 0 F.,..-{ AC DISCONNECT & WARNING LABELS lintocked Ca:ed — I \ t, 0 DC JUNCTION/COMBINER BOX & LABELS ': A ) PV3 OD DISTRIBUTION PANEL & LABELS ) C 1I I I I PV3 Front Of House LG LOAD CENTER & WARNING LABELS ODEDICATED PV SYSTEM METER O STANDOFF LOCATIONS CONDUIT RUN ON EXTERIOR (E) DRIVEWAY --- CONDUIT RUN ON INTERIOR — GATE/FENCE O HEAT PRODUCING VENTS ARE RED r-,---i ii `l INTERIOR EQUIPMENT IS DASHED 12207 SW Millview Ct SITE PLAN N TOTAL ARRAY AREA (SF): 468 Scale: 1/8" = 1' MI ROOF AREA (SF): 2104 w `+ E TOTAL ARRAY AREA IS N 22.22 0 1' 8' 16' PERCENT OF TOTAL ROOF AREA .. , s CONFIDENTIAL — THE INFORMATION HEREIN JOB NUMBER: J B-9722191 00 PREMISE OWNER: DESCRIPTION: DESIGN: CONTAINED SHALL NOT BE USED FOR THE KENYON, PAM KENYON RESIDENCE Aaron Banks ''V`, • BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: '.°„So�arCity NOR SHALL IT BE DISCLOSED IN WHOLE OR IN CompMount Type C 12207 SW MILLVIEW CT 6.63 KW PV ARRAY ,,, �,/� PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: TIGARD OR 97223 ORGANIZATION, EXCEPT IN CONNECTION wTHr THE SALE AND USE OF THE RESPECTIVE (26) TRINA SOLAR # TSM-255PA05.18 3055 Clearview Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET REV: DATE: San Mateo, CA 94402 PERMISSION OF SOLARCITY INC. (503) 590-3113 T:(650)638-1028 F:(650)638-1029 ABB # PVI-5000-OUTD-US-Z-ASITE PLAN PV 2 10/2/2014 (888)—SOL—olY(765-2489) www.sdarcity.com �� (E) 2x10 re , • � `0,••//,/,,i41 (E) LBW 7/0/.:110k STRUCTURE MEETS THE —7 PRESCRIPTIVE REQUIREMENTS M (E) LBW OF THE OSISC SECTION 305.4 SIDE VIEW OF MP2 NTS STRUCTURE MEETS THE ii 13'-8" :'_11" PRESCRIPTIVE REQUIREMENTS OF THE OSISC SECTION 305.4 (E) LBW MP2 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES O SIDE VIEW OF MP1 NTS LANDSCAPE 72" 24" STAGGERED PORTRAIT 48" 18" ROOF AZI 90 PITCH 30 MP1 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES RAFTER 2x8 @ 24" OCARRAY AZI 90 PITCH 30 STORIES: 2 LANDSCAPE 72" 24" STAGGERED C.J. 2x8 @24" OC Comp Shingle PORTRAIT 48" 18" RAFTER 2x10©a 24"OC ROOFAZI 180 PITCH 30 STORIES: 2 ARRRAYRAYAZI 180 PITCH 30 Comp Shingle 1*PV MODULE 5/16" BOLT WITH LOCK INSTALLATION ORDER 0 Aiiiiiii & FENDER WASHERS i LOCATE RAFTER, MARK HOLE ZEP LEVELING FOOT (1) LOCATION, AND DRILL PILOT ZEP ARRAY SKIRT (6) ,. HOLE. 0 , ) SEAL PILOT HOLE WITH (4) 2 POLYURETHANE SEALANT. ZEP COMP MOUNT CAVkWATAI 1?NB IININO \ ZEP FLASHING C ;I`j��1I� (3) INSERT FLASHING. 4" �jl STRUCTURE MEETS THE imL —8" �'I 10'-10' PRESCRIPTIVE REQUIREMENTS rZ�j:V— � L'z�� (E) COMP. SHINGLE vii i " (\) PLACE MOUNT. (E) LBW OF THE OSISC SECTION 305.4 (E) ROOF DECKINGVA= (MIIIIII 5) INSTALL LAG BOLT WITH SIDE VIEW OF MP3 NTS 5/16" DIA STAINLESS (5) SEALING WASHER. 0 STEEL LAG BOLT LOWEST MODULE SUBSEQUENT MODULES " INSTALL LEVELING FOOT WITH WITH SEALING WASHER (6) BOLT & WASHERS. MP3 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES (2-1/2" EMBED, MIN) LANDSCAPE 72" 24" STAGGERED . (E) RAFTER PORTRAIT 48" 18" 411) STANDOFF RAFTER 2X8 @ 24"OC ROOF AZI 90 PITCH 30 STORIES: 2 ARRAY AZI 90 PITCH 30 Scale: 1 1/2" = 1' C.]. 2x8 @24" OC Comp Shingle J B-9722191 O O PREMISE OWNER: DESCRIPTION: DESIGN: CONFIDENTIAL — THE INFORMATION HEREIN JOB NUMBER: ��4 CONTAINED SHALL NOT BE USED FOR THEKENYON, PAM KENYON RESIDENCE Aaron BanksSolarCity BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: ��"` NOR SHALL IT BE DISCLOSED IN WHOLE OR IN CompMount Type C 12207 SW MILLVIEW CT 6.63 KW PV ARRAY PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: �' TIGARD, OR 97223 ORGANIZATION, EXCEPT IN CONNECTION WITH 3055 Gearview Way THE SALE AND USE OF THE RESPECTIVE (26) TRINA SOLAR # TSM-255PA05.18 PAGE NAME: SHEET: REV DATE: San Mateo, CA 94402 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: T:(650)638-1028 F:(650)638-1029 PERMISSION OF SOLARCITY INC. ABB # PVI-5000—OUTD—US—Z—A (503) 590-3113 STRUCTURAL VIEWS PV 3 10/2/2014 (888)—SOL—CITY(765-2489)www.solaraityaom UPLIFT CALCULATIONS 10.02.2014 SolarCity SleekMountTM PV System Version#39.1 Structural Desian Software Project Information &Table Of Contents Risk Category: II PV System Type SolarCity SleekMount"' Comp Roof Comp Roof Layers of Comp Roofing 1 Roof Slope 30° Rafter Spacing 24"O.C. PV System Module Orientation Landscape and Portrait PV Module Area 458 sf PV Module Width 39" PV Module Length 65" Standoff(Attachment Hardware) Comp Mount Type C Reduced Ground/Roof Live/Snow Loads Ground Snow Load pg 25.0 psf ' ASCE Table 7-1 Surrounding Roof Snow 100% 25.0 psi 'ASCE Eq:7.4-1 Roof Snow Over PV Modules 100% 25.0 psf 'ASCE Eq:7.4-1 Wind Design Criteria Wind Design Code ASCE 7-05 Wind Design Method Partially/Fully Enclosed Method Basic Wind Speed V 95 mph Fig.6-1 Exposure Category C ' Section 6.5.6.3 Roof Style Gable/Hip Roof 'Fig.6-11BjUD-14AJB Mean Roof Height h 25 ft Section 6.2 Effective Wind Area(1 Module) A 17.6 sf IBC 1509.7.1 Wind Pressure Calculation Coefficients Wind Pressure Exposure Kz 0.95 Table 6-3 Topographic Factor Kzt 1.00 Section 6.5.7 Wind Directionality Factor Kd 0.85 Table 6-4 Importance Factor I 1.0 Table 6-1 Velocity Pressure qh qh =0.00256(Kz)(Kzt)(Kd)(V^2)(I) Equation 6-15 18.6 psi Ext.Pressure Coefficient(Up) GCp(Up) -0.95 Fig.6-118/CID-14A;B Ext.Pressure Coefficient(Down) GCp(Down) 0.88 Fig.6-11BJCfD-14A/8 Design Wind Pressure p p= qh(GCp) Equation 6-22 Wind Pressure Up p(up) -17.7 psf Wind Pressure Down p(down) 16.3 psi Allowable Standoff Spacings X-Direction Y-Direction Max Allowable Standoff Spacing Landscape 72" 39" Max Allowable Cantilever Landscape 24" NA Standoff Configuration Landscape Staggered Max Standoff Tributary Area Trib 20 sf PV Assembly Dead Load W-PV 3 psf Net Wind Uplift at Standoff T-actual -314 lbs Uplift Capacity of Standoff T-allow 500 lbs Standoff Demand/Capacity DCR 62.8% Max Allowable Standoff Spacing Portrait 48" 65" Max Allowable Cantilever Portrait 18" NA Standoff Configuration Portrait Staggered Max Standoff Tributary Area Trib 22 sf PV Assembly Dead Load W-PV 3 psf Net Wind Uplift at Standoff T-actual -348 lbs Uplift Capacity of Standoff T-allow 500 lbs Standoff Demand/Capacity DCR 69.7% PREMISE OWNER: DESCRIPTION: DESIGN: CONFIDENTIAL— THE INFORMATION HEREIN JOB NUMBER: JB-9722191 0 O \�� CONTAINEDEEFIT SHALL NOT BE USED FOR THE KENYON, PAM KENYON RESIDENCE Aaron Banks �� `SolarCity BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: �•.,,,• PARTNOR TO SHALL OIT BERS DISCLOSEDE IN RECIPIENTS ORGANIZATION, IN Comp Mount Type C 12207 SW MILLVIEW CT 6.63 KW PV ARRAY ►\N ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES: TIGARD, OR 97223 THE SALE AND USE OF THE RESPECTIVE (26) TRINA SOLAR # TSM-255PA05.18 3055 iew Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME SHEET: REV: DATE: San CA 94402 T:(650)638-1028teo, F:(650)638-1029 PERMISSION OF SOLARCITY INC. ABB # PVI-5000—OUTD—US—Z—A (503) 590-3113 UPLIFT CALCULATIONS PV 4 10/2/2014 (888)—SOL—CITY(765-2489)www.solarcity.com GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE BOND (N) #8 GEC TO TWO (N) GROUND Panel Number: G2030MB1150 Inv 1: DC Ungrounded INV 1 —(1)ABB # PVI-5000—OUTD—US—Z—A LABEL: A —(26)TRINA SOLAR # TSM-255PA05.18 OR # 180498 RODS AT PANEL WITH IRREVERSIBLE CRIMP Meter Number:24 145 613 FCI Inverter; Zigbee 5000W, 240V, 96.5% PV Module; 255W, 232.2W PTC, 40MM, Black Frame, MC4, ZEP Enabled RGC, CGC1 Underground Service Entrance INV 2 Voc: 37.7 Vpmax: 30.5 INV 3 Isc AND Imp ARE SHOWN IN THE DC STRINGS IDENTIFIER (E) 150A MAIN SERVICE PANEL E150A/2P MAIN CIRCUIT BREAKER Inverter 1 IND (E) WIRING COOPER CUTLER—HAMMER VstartPI=:DEFAULT113 150A/2P Meter Socket Disconnect ABB 1 r DC+ / PVI-5000—OUTD—US—Z—A DC- Mx :� (E) LOADS n A\ n B I 240VI __ EGC / / U Ll • I ■~■ I �- L2 • , DC+ I • N IR l� 30A/2P I \\_ GND 1-- GID — EGC/ Dc. I DG+ Vstart = DEFAULT — \ / -- n n • A � � �— GEC --—TO DC,- MEM c Dc- c7MP2 &MP3: 1x13 B I ® ----EGC--- ----f-- - - EGC / I • (1)Conduit Kit; 1" EMT N L _ U EGC/GEC i z—z CD GEC r 1 TO 120/240V I I SINGLE PHASE I I UTILITY SERVICE I I I I I II I I I I I I I I I Voc* = MAX VOC AT MIN TEMP POI—(1)SIEMENS #0230 PV BACKFEED BREAKER A —(1)COOPER #B-Line Meter Socket 011 p H DC^ Breaker, 30A/2P, 2 Spaces Meter Socket; 125A, 4-14AWG, Ring Type (v -(2)Ground Rod; 5/8' x 8', Copper -(1)AW CAP; B-Line Meter Socket Accessory -(1)Milbank #CL200D /Itron CIS Solid-State Single-Phase Meter; Digital B I-(1)CUTLER-HAMMER #DG221URB Disconnect; 30A, 240Vac, Non-Fusible, NEMA 3R -(1)CUTLER-HAMMER ,Y DGO3ONB Ground/Neutral it; 30A, General Duty(DG) 3 -(1)AwG#10, THWN-2, Black —(2)AWG#10, PV 1MRE, Black Voc* =549.7 VDC Isc =8.92 ADC • O o-(1)AWG #10, THWN-2, Red 1 ''°-(1)AWG (1)AWG#10, THWN-2, White NEUTRAL Vmp =240 VAC Imp=23 MC O. (1)Conduit Kit; 3/4W EMT, Stranded Bare Copper EGC Vmp =396.5 VDC Imp=8.36 ADC . . , , . , ,-70)AWG#8, THWN-2,Green , EGC/GEC (1)Conduit,Kit; 3/4" EMT (2)AWG #10, PV WIRE, Black Voc* =549.7 VDC Isc =8.92 ADC 'E°- )AWG #6, Stranded Bare Copper EGC Vmp =396.5 VDC Imp=8.36 ADC (1)Conduit Kit; 3/4' EMT I CONFIDENTIALTHE INFORMATION HEREIN PREMISE OWNER: DESCRIPTION: DESIGN:NUMBER: JB-9722191 00 KENYON, PAM KENYON RESIDENCE Aaron Banks �\�. CONTAINEDEEFIT SHALL NOT BE USED FOR THE SolarCity BENEFIT OF ANYONE EXCEPT SOLARCITYT INC., MOUNTING SYSTEM; �.,r NOR SHALL IT BE DISCLOSED IN WHOLE OR IN CompMount Type C 12207 SW MILLVIEW CT 6.63 KW PV ARRAY ��� PART TO OTHERS OUTSIDE THE RECIPIENTS MODULETIGARD OR 97223 ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (26) TRINA SOLAR # TSM-255PA05.18 3055 Clearvew Way SanSOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: PAGE NAME: SHEET: REV: DATE: T:(650)638-1028 F:(650)638-1029 PERMISSION OF SOLARCITY INC. ABB # PVI-5000—OUTD—US—Z—A (503) 590-3113 THREE LINE DIAGRAM PV 5 10/2/2014 (888)-SOL-CITY(765-2489)www.solarcity.cam ELECTRICAL CALCULATIONSModule 26 TRINA SOLAR#TSM255 ZEP 232.2 Inv Power WPIC Voltage Drop Calculations Version 5_8.0 Inverter 1: 1 ABB PVI 5000 S AFCI 0.965 5000 5825.9 Vdrop= Imp) (2*Length)`(Resistance) / (Vmp) Module: Imp(A) Max. Length(ft) Wire Inverter 2: String: 8.36 85 AWG_10 at Max Ave Hi:87 deg F Module: Vdrop= (8.36 * 170 *0.001240hms) / 326.59705 0.54 Inverter 3: Branch: 8.36 50 I AWG_10 at Max Ave Hi:87 deg F • Module: Vdrop= (8.36 * 100 *0.001240hms) / 326.59705 0.32 Total voltage drop in DC conductors= 0.86 Inverter 4: Inverter: 8.36 20 AWG_10 at 240V Vdrop= (8.36 *40 *0.0012 Ohms) / 240 V 0.1672 Total: 26 Modules Total Inv Pwr: 5000 5825.9 PTC Combined: 0 0 AWG_10 at 240V Photovoltaic Module Electrical Specifications: Total STC: 6630 Vdrop= (0 *0 0.0012 Ohms) / 240 V 0 Voc: 37.7 V deg F deg C Vmp: 30.5 V Record Low Temp: 8 -13 Total voltage drop in AC conductors= 0.17 Isc: 8.92 A Max Average Hi Temp: 87 31 Total voltage drop in AC and DC conductors= 1.02 Imp: 8.36 A Record Hi Temp: 96 36 Tvoc: -0.12064 V/deg C Tisc: 4.1924 mA/deg C String Type A and 2 Combined Strings Type A Voc Correction Method: Manuf Tvoc data Branch Circuit Type A 1 way wire length: 50 ABB PVI-5000-S AFCI Voc Correction Factor: 1 strings per branch 1 1 strings per branch 2 Inverter Min Vdc Input: 120 13 TRINA SOLAR#TSM-255 ZEP Min Vmp at Max Temp: 326.6 13 modules per series string 13 modules per series string Voc= 490.1 Voc= 490.1 V Voc= 490.1 V Max Voc at Min Temp: 549.7 Vmp= 396.5 Vmp= 396.5 V Vmp= 396.5 V Inverter Max Vdc Input: 600 Isc= 8.92 Isc= 8.92 A Isc= 8.92 A Imp= 8.36 Max String Size: 14 Imp= 8.36 A Imp= 8.36 A Icont= 11.15 Art 690.8(A)(1) 1-way wire length: 85 Icont= 11.15 A Icont= 11.15 A Art 690.8(A)(1) 1.a Conductor: AWG_10 I PV Wire 2.a Conductor 1: AWG_10 Conductor 2: AWG_10 Icont"1.25=(Amps) 13.94 Conductor 1 Conductor 2 30 deg C ampacity= 40 Icont"1.25=(Amps) 13.94 13.94 1.b Icont=(Amps) 11.15 30 deg C ampacity= 40 40 Start ampacity 40 2.b Icont=(Amps) 11.15 11.15 Temperature derate(%=F) 0.76 Start ampacity 40 40 Conduit fill derate(%=#) 1 Temperature derate(%=F) 0.76 0.76 Derated ampacity 30.4 Conduit fill derate(%=#) 0.8 0.8 1.c Derated ampacity I 24.32 24.32 Icont*1.25=(Amps) 13.94 2.c Term 1 Term 2 Ampacity 40 Temp table 75degC 75degC Icont"1.25=(Amps) 13.94 13.94 1.d Icont"1.25=(Amps) 13.94 Ampacity 35 35 OCP Size= 15 Inverter Type A Output 2.d OCP Size= 15 15 ABB PVI-5000-S AFCI 1 way wire length: 10 ft Combined Inverter Output Icont= 23 A Art 690.8(A)(1) Service Voltage= 3.a Icont"1.25=(Amps) 28.75 Art 690.8(8)(1) Total Inverter Power= 1 way wire length= 0 OCP Size= 30 Art 240.6(A) Icont=#of inverters*max inverter current Art 690.8(A)(1) 3.b Conductor: AWG_10 THWN-2 at 90 deg C:Table 310.16 Icont=(Amps) Icont*1.25=(Amps) 28.75 4.a Icont"1.25=(Amps) 28.75 Art 690.8(B)(1) 30 deg C ampacity= 40 OCP size= 30 Art 240.6(A) 3.c Icont=(Amps) 23 4.b Conductor: AWG_10 THWN-2 at 90 deg C:Table 310.16 Start ampacity 40 Icont"1.25=(Amps) 28.75 Temperature derate(%=F) 0.91 30 deg C ampacity= 40 Conduit fill derate(%=#) 1 4.c Icont=(Amps) 23 Derated ampacity 36.4 Start ampacityo - 40 3.d Icont"1.25=(Amps) 28.75 Temperature derate(/o=F) 0.91 Ampacity 35 Conduit fill derate(%=#) 1 Derated ampacity 36.4 4.d Icont*1.25=(Amps) 28.75 Ampacity 35 J B-97221 91 O O PREMISE OWNER: DESCRIPTION: DESIGN: CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: �.�?�CONTAINED SHALL NOT BE USED FOR THEKENYON, PAM KENYON RESIDENCE Aaron BanksSolarCity BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: I d4o 12207 SW MILLVIEW CT 6.63 KW PV ARRAY NOR SHALL IT BE DISCLOSED IN WHOLE OR IN CompMount Type C PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: TIGARD, OR 97223 ORGANIZATION, EXCEPT IN CONNECTION WITH 3055 Clearview Woy THE SALE AND USE OF THE RESPECTIVE (26) TRINA SOLAR # TSM-255PA05.18 PAGE NAME: SHEET: REV: DATE: San Mateo, CA 94402 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: (503) 590-3113 PV 6 10/2/2014 29 (888)T(SOL)g3Y(765-2 638-1028 F:(65w)w.68-10ity.com PERMISSION OF SOLARCITY INC. ABB # PVI-5000-OUTD-US-Z-A ELECTRICAL CALCULATIONS Label Location: Label Location: Label Location: _ CAUTION: SOLAR CIRCUIT (C)(IC)(CB) MAXIMUM AC _ A (AC) (P01) CAUTION (P01) Per Code: OPERATING CURRENT Per Code: DUAL POWER SOURCE Per Code: IFC 605.11.1.4 MAXIMUM AC - v NEC 690.54 SECOND SOURCE IS NEC 690.64.8.4 OPERATING VOLTAGE PHOTOVOLTAIC SYSTEM Label Location: PHOTOVOLTAIC DC (DC) (INV) DISCONNECT Per Code: NEC 690.14.C.2 Label Location: Label Location: PV SYSTEM (AC) WARNING (DC)(INV) DISCONNECT FOR Per Code: UTILITY OPERATION ELECTRIC SHOCK HAZARD NEC 690.35(F) Label Location: THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE TO BE USED WHEN MAXIMUM POWER- A (DC) (INV) ) UNGROUNDED AND INVERTER IS POINT CURRENT(Imp)_ Per Code: MAY BE ENERGIZED MAXIMUM POWER UNGROUNDED -v NEC 690.53 POINT VOLTAGE(Vmp) MAXIMUM SYSTEM Label Location: VOLTAGE(Voc)_v WARNING (AC) (P01) SHORT-CIRCUIT Per Code: CURRENT(Isc) A ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS NEC 690.17(4) TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION Label Location: WARNING (DC) (CB) Per Code: ELECTRICAL SHOCK HAZARD DO NOT TOUCH TERMINALS NEC 690.17(4) Label Location: TERMINALS ON BOTH LINE AND WARNING (POI) LOAD SIDES MAY BE ENERGIZED Per Code: IN THE OPEN POSITION INVERTER OUTPUT NEC 690.64.8.7 DC VOLTAGE IS CONNECTION ALWAYS PRESENT WHEN DO NOT RELOCATE SOLAR MODULES ARE THIS OVERCURRENT EXPOSED TO SUNLIGHT DEVICE Label Location: Label Location: WARNING (DC) (INV) PHOTOVOLTAIC POINT OF (P01) Per Code: INTERCONNECTION Per Code: ELECTRIC SHOCK HAZARD NEC 690.5(C) WARNING: ELECTRIC SHOCK NEC 690.17.4; NEC 690.54 IF A GROUND FAULT IS INDICATED HAZARD. DO NOT TOUCH NORMALLY GROUNDED TERMINALS.TERMINALS ON CONDUCTORS MAY BE BOTH THE LINE AND LOAD SIDE UNGROUNDED AND ENERGIZED MAY BE ENERGIZED IN THE OPEN POSITION. FOR SERVICE DE-ENERGIZE BOTH SOURCE AND MAIN BREAKER. PV POWER SOURCE Label Location: MAXIMUM AC A OPERATING CURRENT (AC): AC Disconnect PHOTOVOLTAIC AC (AC) (P01) MAXIMUM AC _ (C): Conduit - DISCONNECT Per Code: OPERATING VOLTAGE V (CB): Combiner Box NEC 690.14.C.2 (D): Distribution Panel (DC): DC Disconnect (IC): Interior Run Conduit Label Location: (INV): Inverter With Integrated DC Disconnect CAUTION (D) (P01) (LC): Load Center Per Code: (M): Utility Meter PHOTOVOLTAIC SYSTEM NEC 690.64.B.4 CIRCUIT IS BACKFED (P01): Point of Interconnection CONFIDENTIAL- THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR `014fr 3055 Cleaview Way THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED ..- ■ San Mateo,CA 94402 IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, SC - OR Label Set So Ia rCqT:(650)638-1028 F:(650)638-1029 EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE I' ty (888)-SOL-CITY(765-2489)www.solarcity.com SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. ZS Comp Edge Zone Calculations 1 of 4 ZS Comp Edge Zone Calculations 2 of 4 Zep Sa .a r 5/28/13 Zep So l a r 5/28/13 This set of calculations is intended to show that ZS Comp has sufficient strength to allow for attachment Down Force Spacing spacings of at least 48"in Edge Zones whether the modules are orientated in landscape or portrait.The Allowable Down Force Load down force spacing= calculations will vary the design variables to account for the worst case for each failure mode that is being module width x design load checked. ' Wind Down Calculations All variable the same as above except for roof pitch General Design Information: Roof Pitch Module Size: 39"x 65" Basic Wind Speed= 95 mph 14 30 45 System Weight= 3 psf Ground Snow Load= 30 psf GCN landscape= 0.5 0.9 0.9 GCN portrait= 0.4 0.9 0.9 Comp Mount Allowable Loads design load landscape= 9.62 17.32 17.32 psf Uplift= 656 lbs Lateral= 436 lbs design load portrait= 7.70 17.32 17.32 psf Down Force= 1147 lbs - -RC) .4►/ note:use 10 psf minimum te •.ilb► .ems Snow Calculations ifir Attachment Spacing Calculations 85818 IA To account for unbalanced snow loads,ground snow loads will be used for roof pitches 30 degrees and Uplift Spacing a OREGON o lower.Per section 7.6.1 of ASCE 7-10 unbalanced snow loads do not need to be considered for slopes 4ov. 10 \,,,'-''- vti above 30 degrees. Allowable Uplift Load �4'eMy RGGc uplift spacing= module length or width x design load EXPIRES: 12/31/14 Ground Snow Load= 30 psf Wind Uplift Calculations FOR PAGES 1-4 Roof Pitch ASCE 7-05 Method 2 14 30 Design Snow Load 29.11 25.98 psf p= qh GCN load spread over the length of the qh=0.00256 K,K,Kd V2 I (snowP g rafter) Basic Wind Speed= 95 mph Down Force Load Roof Pitch Exposure= C Roof Zone= Edge Zone Combinations: 14 30 Importance Factor= 1.0 K,= 0.98 from Table 6-3 D+S= 31.16 _ 25.10 psf Gable/Hip Roof K,= 1.0 per 6.5.7.2 D+W= 12.91 19.92 psf forst Case Roof Pitch= 14 degrees Kd= 0.85 from Table 6-4 D+0.75W+0.755 31.59 32.46 psf Roof Height= 30 GCN landscape= -1.6 Iscape effective area= 13.0 ft2 GCN portrait= -1.5 landscape down force spacing = 39"x132.46 s x 144 i = 130" ortrait effective area= 21.7 ft2 32.46psf f 2 Plandscape= -30.79 psf qh= 19.25 psf pportrait= 28.87 psf 1147/bs portrait down force spacing = 65"x 32.46psf x 144 in = 78" Uplift Load Combination:0.6D+W(ASCE Section 2.4.1 equation 7) design load landscape= -29.05 psf z design load portrait= -27.12 psf 656 lbs in landscape uplift spacing = 39"x 29.05 psf x 144-=83" t2 656 lbs in portrait uplift spacing = x 144 65"x 27.12 psf f= 54" t2 ZS Comp Edge Zone Calculations 3 of 4 ZS Comp Edge Zone Calculations 4 of 4 5/28/13 5/28/13 ZepSoar ZepSolar Lateral Spacing Module Deflection Spacing landscape module spacing= -1.4545 x Maximum Uplift or Down Force Pressure+120.7273 The lateral force on the system increases as the pitch of the roof increases,but the amount of snow on the roof decreases for slopes greater than 30 degrees.With this in mind,the lateral force will be checked at 30 degrees with ground snow load and 45 degrees with sloped roof snow. portrait module spacing=-1.7917 x Maximum Uplift or Down Force Pressure+118.58 Allowable Lateral Load lateral spacing= module width x design load Maximum Uplift of Down Force Pressure= 32.46 psf Snow Calculations Ground Snow Load= 30 psf landscape module spacing =-1.4545 x 32.46 psf+120.7273 = 73" P5=Cs Pf Roof Pitch= 31 45 degrees Pf=0.7 Ce Ct I pg Ce= 0.9 C5= 0.71 0.45 portrait module spacing =-1.7917 x 32.46 psf+118.58= 60" Ct= 1.2 pf= 22.68 22.7 psf I= 1.0 Ps= 16.1 10.2 psf Calculation Summary Calculated Edge Zone Spacing Roof Pitch Spacing Check Landscape Portrait 27 30 31 45 Uplift 83" 54" Design Snow Load 26.73 25.98 13.80 7.22 psf Down Force 130" 78" (snow load spread over the length of the rafter) 30° 27° 30° Lateral 74" 48" 45" Lateral Force Component Module Deflection 73" 60" Down Force Load Roof Pitch Combinations: 27 30 31 45 As can be seen in the table above,for Design Wind Speeds up to 95 mph and Ground Snow Loads up to 30 D+S= 13.50 14.49 8.65 7.22 psf psf with modules orientated in landscape,the system is strong enough to be installed at 72"on center in D+0.75W+0.755 10.46 11.24 6.88 5.95 psf the Edge Zone.When modules are installed in portrait,the spacing for edge zone installations can be 48" on center for most roof pitches.For roof pitches that are greater than 27°but less than 31°,the maximum 30 degree roof pitch attachment spacing is 45". 292lbs in landscape lateral spacing= 39"x 14.49 psf x 144 ft2 = 74" 292lbs in portrait lateral spacing = ft2 65"x 14.49 psf x 144 =45" Portrait spacing is less than 48".Try roof pitch of 27 degrees 292lbs in portrait lateral spacing = 65"x 13.50 psf x 144 ft2 =48" SolarCity SleekMountTM — Comp SolarCity SleekMountTM - Comp ' The SolarCity SleekMount hardware solution •Utilizes Zep Solar hardware and UL 1703 listedInstallation Instructions is optimized to achieve superior strength and Zep CompatibleTM modules , " aesthetics while minimizing roof disruption and • Drill Pilot Hole of Proper Diameter for labor.The elimination of visible rail ends and •Interlock and grounding devices in system UL Fastener Size Per NDS Section 1.1.3.2 listed to UL 2703 mounting clamps, combined with the addition of array trim and a lower profile all contribute •Interlock and Ground Zep ETL listed to UL 1703 Seal pilot hole with roofing sealant to a more visually appealing system.SleekMount as"Grounding and Bonding System" •• Insert Comp Mount flashing under upper utilizes Zep CompatibleTM modules with •Ground Zep UL and ETL listed to UL 467 as w $, \ layer of shingle strengthened frames that attach directly to grounding device • Place Comp Mount centered Zep Solar standoffs,effectively eliminating the need for rail and reducing the number of •Painted galvanized waterproof flashing - upon flashing standoffs required. In addition, composition • •Anodized components for corrosion resistance • Install lag pursuant to NDS Section 11.1.3 shingles are not required to be cut for this \� with sealing washer system, allowing for minimal roof disturbance. •Applicable for vent spanning functions • Secure Leveling Foot to the Comp Mount using machine Screw f. • Place module A Components B ►_ • 5/16"Machine Screw � • L:: ot • • Lrew C • Comp Mount • Comp Mount Flashing D �/1io ; 0 4-110) E 40 ,�:vq .veil Y. iiM B - �����it © January 2013 FA����� CO CO LISTED '" SolarCity, January 2013 1 TSM-PA05.18 TRINAMOUNT II WITH THE UNIVERSAL MODULE Mono Multi Solutions DIMENSIONS OF PV MODULE TSM-PA05.18 ELECTRICAL DATA @ STC TSM-240 TSM-245 TSM-250 TSM-255 TSM-260 PA05.18 PA05.18 PA05.18 PA05.18 PA05.18 941mm Peak Power Watts-Prinz(Wp) 240 245 250 255 260 Power Output Tolerance-Pon.(%) 0/+3 0/+3 0/+3 0/+3 0/+3 -� • 7- ,urxnorr w Maximum Power Voltage-Vie(V) 29.7 30.2 30.3 30.5 30.7 w. o Maximum Power Current-lore(A) 8.10 8.13 8.27 8.36 8.47 TSM pA05.18 "nrrrne 0 Open Circuit Voltage-Voc(V) 37.3 37.5 37.6 37.7 37.9 � INSTALLING Short Circuit Current-Isc(A) 8.62 8.68 8.85 8.92 9.00 Module Efficiency rink(%) 14.7 15.0 15.3 15.6 15.9 3 THE TRINAMOUNT MODULE 3 STC:Irradiance 1000 W/m2,Cell Temperature 25°C,Air Mass AM1.5 according to EN 60904-3. Average efficiency reduction of 4.5%a1200 W/m2 according to EN 60904-I. E is 0 0 ELECTRICAL DATA @ NOCT TSM-240 TSM-245 TSM-250 TSM-255 TSM-260 PA05.18 PA05.18 PA05.18 PA05.18 PA05.18 60 CELL Maximum Power-Pon.(Wp) 174 178 181 184 188 Maximum Power Voltage-Vie(V) 26.6 26.8 27.0 27.2 27.4 • se4s GROUNDING uorc • Maximum Power Current-lisp(A) 6.55 6.64 6.70 6.77 6.86 MULTICRYSTALLINE MODULE i A A• WITH TRINAMOUNT FRAME WITH ears Open Circuit Voltage(V)-Voc(V) 34.1 34.2 34.3 34.4 34.6 4644454414.144044,4444 n O Short Circuit Current(A)-Isc(A) 7.04 7.10 7.25 7.31 7.37 I 812mm I 180 I NOCT:Irradiance at 800 Wim',Ambient Temperature 20°C,Wind Speed I m/s. 240-260W Back View MECHANICAL DATA POWER OUTPUT RANGE Our most versitile product I 11 Solar cells Multicrystalline 156.156 mm(6 inches) • Compatible with at major BOS components and system designs Cell orientation 60 cells(6 x 10) 15.9%o o Module dimensions 1650 x 992.40 mm(64.95 x 39.05 x 1.57 inches) � a Weight 18.6 kg(41.0 Ibs) MAXIMUM EFFICIENCY LI Glass High transparency solar glass 3.2 mm(0.13 inches) Backsheet White •� One of the industry's most trusted modules Frame Black Anodized Aluminium Alloy with Trinamount Groove t'.�;l • Over 2 GW sold across all major global markets 0 +3% • Field proven performance I-V CURVES OF PV MODULE TSM-245 PA05.18 J-Box Cables IP 65 or IP 67 rated Photovoltaic Technology cable 4.0 mm'(0.006 inches'), 10.00 1100 mm(43.3 inches) POWER OUTPUT GUARANTEE 8.-40000/"' Connector Original MC4 ^700 800W/m2 Highly reliable due to stringent quality control 5m 600W/m` As a leading global manufacturer • Over 30 in-house tests(UV,TC,HF,and many more) u 4.0 400W/m. ` TEMPERATURE RATINGS MAXIMUM RATINGS of next generation photovoltaic • In-house testing goes well beyong certification requirements am 2oow/m2 Nominal Operating Cell 45°C(±2°C) Operational Temperature -40-+85°C products,we believe close m , Temperature(NOCT) Maximum System 1000V DC(IEC)/ cooperation with our partners o.m Temperature Coefficient of Pon. -0.43%/°C Voltage 600V DC(UL) is critical to success. With local op Io.°° 2a. 3o.nk 40.. presence around the globe,Trina isVoltage(V) Temperature Coefficient of Voc -0.32%/°C Max Series Fuse Rating 15A able to provide exceptional service Temperature Coefficient of Isc 0.047%/°C to each customer in each market Certified to withstand challenging environmental and supplement our innovative, reliable products with the backing conditions of Trina as a strong,bankable • 130 km/hr wind load (2400 Pa) WARRANTY partner. We are committed • 900 kg snow load per module(5400 Pa) 10 year Product Workmanship Warranty to building strategic,mutually - beneficial collaboration with 25 year Linear Power Warranty installers,developers,distributors (Please refer to product warranty for details) and other partners as the backbone of our shared success in CERTIFICATION o driving Smart Energy Together. LINEAR PERFORMANCE WARRANTYPACKAGING CONFIGURATION '10 Year Product Warranty•25 Year Linear Power Warranty 'rim -j $P s Modules per box:24 pieces Trona Solar Limited 4y 3 • dr►ro 6o na Modules per 40'contamer:672 pieces www.trinasolar.com oloo5c rid naf a So ISO +'✓� E USTeous pit e Valu m Trf ,-90% f fors pnear Warrant CAUTION:READ SAFETY AND INSTALLATION INSTRUCTIONS BEFORE USING THE PRODUCT. ceMPATj@ T• o y � 02013 Trina Solar Limited.All rights reserved.Specifications included in this datasheet are subject to 4"/ c,°, rinasolar 80% h Trinasolar change without notice. Smart Energy Together o 20 ss Smart Energy Together ACaMPptO Additional highlights: Solar inverters — RS-485 communication interface ABB string inverters i gr,ceo)nec on to laptop or data • PVI-5000/6000-TL-OUTD - Integrated Arc Fault Detection and Interruptior!(-A Version). 5kW to 6kW M I. ei Technical data and types Type code PVI-5000-OUTD-US PVI-6000-OUTD-US Mt Inputside .�:%s--- --_• Nominal output rower 5000W 6000W ....__r Maximum output power 5000W 6000W Rated grid AC voltage 208V 240V 277V 208V 240V 277V ) Input side(DC) . ,p Number of independent MPPT channels 2 • Maximum usable power for each channel 4000W ° Absolute maxirrtWR voltage(Vmax) 600V _,_--..— ° Start-up voltage(Vstart)............... 200V(adj.120-350) Full poter MPPT voltage range 200-530V } Operating MPPT voltage range 0.7 x Vstart-580V 1 II Maximum c nt(Idcmax)for both MPPT in parallel 36A Maximum,dsle current per channel 22A ) Number tf wife lan ng terminals per channel 2 Pairs Array wiring termination Terminal block,pressure clamp,AWG16-AWG6 Output side(AC) Grid connection type • 10/2W Split 0/3W 10/2W 10/2W Split-0/3W 10/2W Adju9fable voltage range(Vmin-Vmax) 183V 228V 221V-264V . 244V-304V 183V 228V 211V-264V 244V-304V Grid frequency 60Hz Adjustable grid frequency range 57-60.5Hz A Maximum current(I, )A 27ALa .....i 23 .te. 20AL. 30'1wa ..._ 28ALa 24AL. Designed for residential and small The wide input voltage range Highlights: Power factor >0.995 g Total harmonic distortion at rated power <2% makes the inverter suitable to low _ gsplitphaseContributory fault current' Pk Pk p Pk commercial PV installations,this Single phase and output36 25 A 36 5 A..../ 31.75 A.,/ 36.25 A k/ 36.5 A / 31.75 A k/ inverter fills a specific niche in the Power installations with reduced grid connection. 25 63Aa„� 25 81ALp 22 45 e% 25.63AL.. 25.81P 22.45ARMs P Grid wiring termination type Terminal block,pressure clamp,AWG14 AWG4 stria size. - ABB product line to cater for those 9 - Wide input range for increased Input The transformerless operation offers Reverse polarity protection Yes installations producing between p stringing flexibility. high performance efficiencies of up to The high speed and precise MPPT Over voltage protection type Varistor,2 for each channel 5kW and 20kW. - 9 P Pstart-up ure. arrays) o PV array ground fault detection Pre Riso and Dynamic GFDI(requires floating arrays) 97.1/o. algorithm offers real time power Output This inverter includes dual input Free remote monitoring capability tracking and improved energy Anti-islanding protection • Meets UL 1741/IEEE1547 requirements Meets UL 1741/IEEE1547 requirements available with everyinstallation.This Over voltage protection type Varistor,2(L-Lz/L, G) Varistor,2(L,-L2/L,-G) section to process two strings with harvesting. Mtimum AC OCPD Rating 35A 30A 25A 40A • 35A 30A enables homeowners to view their independent MPPT. — Outdoor NEMA 4X rated enclosure Efficiency The high speed and precise MPPT energy production and offers installers for unrestricted use under any Maximum efficierwy 97.1% algorithm offers real-time power a proactive and economic way of environmental conditions. CEC efficiency ... .., 96% 96.5% 96.5% 96% 96.5% 96.5% maintainingand troubleshooting the User interface Graphic display Graphic display tracking and energy harvesting. g - Integrated DC disconnect switch Operating performance • em. s st Flat efficiency curves ensure high y in compliance with international Stand-by consumption <BW.0. <sWRms efficiency at all output levels ensuring Standards(-S Version). Nigfit time coniimption <0.6W0,,n . <0.6W0sn Communicati . consistent and stable performance User-interface 16 characters x 2 lines LCD display across the entire input voltage and Retote monitoring(1xRs485 incl.) VSN700 Data Logger(opt) Output power range. Wired local monitoring(1xRS485 incl.) PVI-USB-RS485_232(opt.) Environmental! • This outdoor inverter has been -13°F to+140°F(-25°C to+60°C)with Antbie airoperating temperature range -13°F to+140°F(-25°C to+60°C) designed as a completely sealed unit to # # derating above 122°F(50°C) withstand the harshest environmental Ambie air storage temperature range -40°F to+176°F(-40°C to+80°C) -40°F to+176°F(-40°C to+80°C) Relativ humidity 0-100%RH condensing 0-100%RH condensing conditions. Ac6ustic rase emission level <50 db(A)elm <50 db(A)WI m Power and productivity „ II It Maximum operating altitutde without derating 2.Inverter can a 6560 ft(2000 m) 6560 ft(2000 m) p Y P111111111ppy that much current-Breaker will open • for a better world'" 2 ABB Solar Inverters I Product flyer for PVI-5000/6000-TL-oUTD