Report f/SOI(- (Ito-70 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page kei1 DATE: 6/8/2011 C: \HASS /4\ARLINGTON57 . SDF JOB TITLE: Arlington Heights Lot #57 WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS . PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) 8 118 . 0 54 . 0 1230 . 0 117 . 9 26. 1 55 . 0 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 26. 1 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0. 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26. 1 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) ---- --- --- 1 -1 . 0 K= 4 . 90 7 . 2 13 . 1 - . i = . . zi i . i 3 -1 . 0 - - - - 8 . 3 - - - 4 19. 5 - - - - 17 . 6 - - - 5 8 . 0 - - - - 41 . 1 - - - 6 1 . 0 - - - - 45 . 6 - - - 7 1 . 0 - - - - 49. 6 - - 8 0 . 0 SOURCE 55 . 0 26. 1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 6/8/2011 c:: \HASS /4\ARLINGTON57 . SDF JOB TITLE: Arlington Heights Lot #57 PIPE DATA PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS . END ELEV. NOZ. PT DISC. VEL (FPS) HW (C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -13 . 1 0 . 874 PL 9 . 00 PF 1 .2 1 -1 . 0 4 . 9 7 . 2 13 . 1 7 . 0 150 FTG T PE 0. 0 3 -1 . 0 0 . 0 8 . 3 0. 0 0 . 096 TL 12 . 11 PV Pipe: 2 13. 0 0 . 874 PL 11 . 00 PF 1 . 3 3 -1 . 0 0 . 0 8 . 3 0 . 0 6. 9 150 FTG T PE 0. 0 2 -1 . 0 4 . 9 7 . 0 13 . 0 0. 094 TL 14 . 11 PV Pipe: 3 -26. 1 0 . 874 PL 43 . 00 PF 18 . 1 3 -1 . 0 0 . 0 8 .3 0. 0 13 . 9 150 FTG 3E2T PE -8 . 9 4 19 . 5 0 . 0 17 . 6 0 . 0 0 . 342 TL 52 . 94 PV Pipe: 4 -26. 1 0. 874 PL 38 . 00 PF 18 . 5 4 19. 5 0. 0 17 . 6 0 . 0 13 . 9 150 FTG 3E4T PE 5 . 0 5 8 . 0 0 . 0 41 . 1 0. 0 0 . 342 TL 54 . 15 PV Pipe: 5 - -26. 1 1 . 049 PL 7 . 00 PF 1. 5 5 8 . i • . i i . . 9. - - i 6 1 . 0 0 . 0 45 . 6 0 . 0 0 .213 TL 7 . 00 PV Pipe: 6 FIXED PRESSURE LOSS DEVICE 7 1 . 0 0 . 0 49. 6 0 . 0 4 . 0 psi, 26. 1 gpm 6 1 . 0 0. 0 45 . 6 0 . 0 Pipe: 7 -26. 1 1 .101 PL 45 .00 PF 5 . 0 . 7 . 1 . 0 0 . 0 49. 6 0 . 0 8 . 8 150 FTG ---- PE 0. 4 8 0 . 0 SRCE 55 . 0 (N/A) 0 . 111 TL 45 . 00 PV NOTES: (1) Calculations were performed by the HASS 7 . 4 computer program under license no. 5010113212 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0 . 015 gpm and a maximum imbalance at any node of 0 . 106 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 13 . 9 ft/sec at pipe 4 . (4) PIPE FITTINGS TABLE Pipe Table Name: STANDARD. PIP Y SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 6/8/2011 C: \HASS-74\ARLINGTON57 . SDF JOB TITLE: Arlington Heights Lot #57 PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee 0 . 874 0. 82 2 . 06 0 . 82 2 . 06 2 . 47 0 . 41 4 . 11 4 . 11 2 . 06 1 . 101 2 . 53 6. 33 2 . 53 6. 33 7 . 59 1 . 27 12 . 66 12 . 66 6. 33 PAGE: A MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkV1v BfyVly GatVly AlmChk DPV1v NPTee 1 . 049 2 . 00 5 . 00 2 . 00 5 . 00 6. 00 1 . 00 10. 00 10 . 00 5 . 00 0 bJ H WATER SUPPLY ANALYSI I '' R — 140. 0 Static: 118. 0 p.L ' Resid: 54 .00 psi Flow: 1230.0 gpm LEGEND 0 1 A' : iable pressure H 1 1P . 95 psi @ 26. 1 gpm G112. 0 2 R-° uired pressure �+ A 5104 psi @ 26. 1 gpm U U' x b G o H H E z � x m R 84.0 o to E rr ,-< S 4# H cn m S x U x R F-C d E 56. 02 • ( H p z s z 1 n x H 28. 0 v: to U. z 0. 0 y 0 z Cn rC7 S:11 • cnm -14 . 7 I 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM) tFire Suppression tico & Building ProductsIt/ rapid response® Technical Services 800-381-93121+1-401-781-8220 HOME FIRE SPRINKLER SYSTEM www.tyco-fire.com Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4-9 K-Factor The Series LFII Residential Flat-Plate Genera/ Concealed Pendent Sprinkler has a 4.9 Description (60,5)K factor that provides the required residential flow rates at reduced pres- The TYCO RAPID RESPONSE Series sures, enabling smaller pipe sizes and "° LFII Residential Flat-Plate Concealed water supply requirements. � {_. PPY , IL- Pendent Sprinklers(TY2524)are decora- tive,fast response,fusible solder sprin- _ This sprinkler hasp been designed with ;_ " Px riga#-`59rzui7ilat:7in .a..i..w m iromisi"7 --- - —"_ tri-: ••" I • , ' trol of residential fires and to improve == dormitories,and hotels. the-chance-foroccupants to escape or The Cover Plate/RetainerAssembl con- be evacuated. r ' ivi " r .4i.,•-• LJ � * f ceals the sprinkler operating compo- The Series LFII Residential Flat-Plate ' ` nents above the ceiling.The flat profile Concealed Pendent Sprinklers are of the Cover Plate provides the optimum shipped with a Disposable Protective aesthetically appealing sprinkler design. Cap. The Protective Cap protects the Additionally,the concealed design of the sprinkler during ceiling installation or Series LFII Residential Flat-Plate Con -finish.After-ceiling installation is com------- Technical cealed Pendent Sprinklers provides 1/2 inch(12,8 mm)vertical adjustment.This plete, the Protective Cap is removed provides a measure of flex- and the Cover Plate/Retainer Assem- Data adjustmenty when provedutting pfrovides a pipe drops. bly is installed. Removing the Protec- tive Cap is required for proper sprinkler Approvals The Series LFII Residential Flat-Plate performance. UL and C-UL Listed Concealed Pendent Sprinklers are in- NSF-61 Certified tended for use in the following systems: NOTICE The Series LFII Residential Flat-Plate • per NFPA 13D, wet pipe residential The Series LF//Residential Flat-Plate Concealed Pendent Sprinklers are only sprinkler systems for one- and two- Concealed Pendent Sprinklers(TY2524) listed with the Series LFII Concealed family dwellings and mobile homes; described herein must be installed and Cover Plates having a factory-applied • per NFPA 13R, wet pipe residential maintained in compliance with this doc- finish. sprinkler systems for residential oc- ument and with the applicable standards cupnklers up to and including four of the National Fire Protection Associa Maximum Working Pressure stories in height;and tion,in addition to the standards of any 175 psi(12,1 bar) authorities having jurisdiction. Failure • per NFPA 13, wet pipe sprinkler sys- to do so may impair the performance Discharge Coefficient tems for the residential portions of of these devices. K=4.9 GPM/psi'" (70,6 LPM/bar'n) any occupancy. Owners are responsible for maintaining Temperature Rating their fire protection system and devices Sprinkler: 160°F(71°C) in proper operating condition. The in- Cover Plate: 139°F(59°C) IMPORTANT stalling contractor or sprinklermanu Vertical Adjustment Always refer to Technical Data for the "lmanu- facturer should be contacted with any questi1/2 inch (12,7 mm) Sheet TFP700 that provides cautions Finishes with respect to handling and instal- Model/SI"rinkler Refer to the Ordering Procedure lation of sprinkler systems and corn- section. ponents. Improper handling and in- Identification Ph stallation can permanently damage ysical Characteristics a sprinkler system or its components Number (SIN) • Cover Plate/Retainer Assembly: and cause the sprinkler to fail to Cover Plate Copper operate in a fire situation or cause it TY2524 Ejection Spring . . . . Stainless Steel to operate prematurely. Retainer Brass Page 1 of 6 OCTOBER 2010 TFP443 • • TFP443 Page 2 of 6 Horizontal Ceiling Sloped Ceiling Sloped Ceiling Minimum Flowibiand Minimum Flow(b)and Minimum Flowib)and Residual Pressure Residual Pressure Residual Pressure • Maximum Maximum (Maximum 2-inch rise Covera e S acin (Greater than 2-inch rise (Greater than 4-inch rise Area i9 p g for 12-inch run) up to maximum 4-inch up to maximum 8-inch rise for 12-inch run) rise for 12-inch run) 160°F(71°C) 160°F(71°C) 160°F(71°C) Sprinkler Sprinkler Sprinkler 12'x 12' 12' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (3,7 m x 3,7 m) (3,7 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 14'x 14' 14' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (4,3 m x 4,3 m) (4,3 m) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 16'x 16' 16' 13 GPM(49,2 LPM) 17 GPM(64,3 LPM) 17 GPM(64,3 LPM) (4,9 m x 4,9 m) (4,9 m) 7.0 psi(0,48 bar) 12.0 si(0,83 bar) 12.0 psi(0,83 bar) 18'x 18' 18' 17 GPM(64,3 LPM) 22 GPM(83,3 LPM) 22 GPM(83,3 LPM) (5,5 m x 5,5 m) (5,5 m) 12.0 psi(0,83 bar) 20.2 psi(1,39 bar) 20.2 psi(1,39 bar) 20'x 20' 20' 20 GPM(75,7 LPM) 24 GPM(90,8 LPM) 24 GPM(90,8 LPM) (6,1 m x 6,1 m) (6,1 m) 16.7 psi(1,15 bar) 24.0si(1,65 bar) 24.0 psi(1,65 bar) (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b)The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures- - ...................................................., -- �"-`- - - -- --- . . •-�:cr.��s� fma aizaar��xiarrmr�aarz� - _TABLEA SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) NFPA 13D AND NFPA 13R HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS • pnkler/Support Cup Assembly: Design For systems designed to NFPA 13, the BodyCodBronzess /� - number of design sprinklers is to be Saddle Brass Cr/ter/a the four most hydraulically demanding Assembly Beryllium sprinklers.The minimum required dis- Sealingickel w/Teflon'Nickel The TYCO RAPID RESPONSE Series charge from each of the four sprinklers N Soldered Link HalveLFII Residential Flat-Plate Concealed is to be the greater of the following: Sold Bronze Pendent Sprinklers (TY2524) are UL •flow rates given in Table A for NFPA Cempression Screw Brasand C-UL Listed for installation in ac- 13D and 13R as a function of tem- Deflector Bronze cordance with the following criteria. perature rating and the maximum al- Guide Pin Housing Bronze towable coverage area Guide Pins Bronze NOTICE Support Cup Steel When conditions exist that are outside ' minimum discharge"design of 0.1a corn- theGPM scope of the provided criteria, re- prisedpft, over thefthydra fer to the Residential Sprinkler Desi n demandingof rinr e mostfor actualicoy- 0 eration Guide TFP490 for the manufactures eraeasprrote tedactual dour recommendations that may be accept- erage areas protected by the four When exposed to heat from a fire,the able to the Authority Having Jurisdiction. sprinklers Cover Plate,which is normally soldered Obstruction To Water Distribution to the Retainer at three points,falls away The Series LFII Residentia/Flat Flat-Plate Locate sprinklers in accordance with the to expose the Sprinkler/Support Cup As- Concealed Pendent Sprinklers must sembly.At this point,the Deflector,sup- not be used in applications where the obstruction rules of NFPA for residential air pressure above the ceiling is greater sprinklers as well as obstruction criteria ported by the Guide Pins, drops down than that below. Down drafts through described within TYCO technical data to its operated position. the Support Cup can delay sprinkler op- sheet TFP490. The Solder Link Element of the Sprinkler/ eration in a fire situation. Support Cup Assembly is comprised of Operational Sensitivity two link halves that are soldered togeth- System Type Install sprinklers relative to the ceiling er with a thin layer of solder. When the Only wet pipe systems may be utilized. mounting surface as shown in Figure 3. rated temperature is reached, the sol- der melts and the two link halves sopa- Hydraulic Design Sprinkler Spacing rate, allowing the sprinkler to activate Table A provides the minimum required The minimum spacing between sprin klers is 8 feet(2,4 m). and flow water. sprinkler flow rate for systems designed to NFPA 13D or NFPA 13R as a function The maximum spacing between sprin- of temperature rating and the maximum klers cannot exceed the length of the allowable coverage areas.The sprinkler coverage area(Table A) being hydrau- flow rate is the minimum required dis- lically calculated;for example, a maxi- charge from each of the total number of mum of 12 feet for a 12 ft.x 12 ft cov- "design sprinklers"as specified in NFPA erage area or 20 feet for a 20 ft.x 20 ft. 1 Registered trademark of Dupont 13D or NFPA 13R. coverage area. TFP443 Page 3 of 6 BODY z SEALING (1/2"NPT) /! ASSEMBLY 1 CAP 4.1.1M4...- ' �'/���1'_____, SPRINKLER Ii `����``!� j WRENCHING SADDLE 1 111. VL. 4) 1 AREA �• t SUPPORT 1 ,• ,I, COMPRESSION CUP WITH t ;�� 1 � � SCREW ROLL FORMED THREADS 1 � It 1 i �', — 1 ( LEVER WRENCH 1 L\i12 bi'i.� ' RECESS GUIDE I PIN ::.m_.�---..i.:1 I ' SOLDER LINK � \ I I ELEMENT kfill GUIDE PIN Mr HOUSING I DEFLECTOR OPERATED e w _ __-----,-- _ . , =p4 = _ -Ni. ,-6_ -- I SPRINKLER/SUPPORT CUP ENGAGEMENT - - —ASSEMBLY I WITFiSP_RINKLER_ I I WRENCHING AREA THREAD INTO t SUPPORT CUP I j RETAINER UNTIL MOUNTING )1 WITH DIMPLES THREAD FIGURE 2 SURFACE IS ts 0 I FLUSH WITH ) EJECTION SPRINKLER WRENCH CEILINGSPRING —, SOLDER COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE FIGURE 1 FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) ASSEMBLY 2-1/2"DIA. SPRINKLER- (63,5 mm) 1/2"(12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING \ / OPERATED • �r�t 1111111.mill- SPRINKLER t= 1-7/8"±1/8" COVER , _' I — ti_ ���al_ 1/8"GAP ±3,2 mm) RETAINER , 4 . I h I ..,.. l (3,2Imm) ________ I INI MB 11 11 COVER- SPRINKLER 7/8"(22,2 mm) RETAINER SUPPORT CUP MOUNTING 1-1/8"(28,6 mm) ASSEMBLY ASSEMBLY 3/16" SURFACE '.Ma J (4,8 mm) _._.__... 3-3/16"DIA. DISPOSABLE DEFLECTOR IN (81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION • FIGURE 3 PROTECTIVE CAP AND ACTIVATED DEFLECTOR INSTALLATION DIMENSIONS TFP443 Page 4 of 6 Installation 6. Screw on the Cover Plate/Retainer Replace sprinklers that: Assembly until its flange contacts The TYCO RAPID RESPONSE Series the ceiling. •were damaged by dropping, striking, LFII Residential Flat Plate Concealed Dowrench twisting,wrench slippage, or Pendent Sprinklers must be installed Cover not a e/Rinai to screw ly uchhe the like. in accordance with the following Plate/Retainer Assembly such • that it lifts a ceiling panel out of its •were modified or over-heated. instructions. normal position. • are leaking or exhibiting visible signs NOTICE If the Cover Plate/Retainer Assembly of corrosion. cannot be engaged with the Mounting Responsibility lies with owners for the Damage to the Solder Link Element dur- Cup or the Cover Plate/Retainer As- inspection,testing,and maintenance of ing installation can be avoided by han- sembly cannot be engaged sufficiently their fire protection system and devices I dling the sprinkler by the Support Cup to contact the ceiling,the Sprinkler in compliance with this document, as only;that is, do not apply pressure to the Fitting must be repositioned. Solder Link Element(Figure 1). well as with the applicable standards of the National Fire Protection Association Obtain a leak-tight 1/2 inch NPT sprinkler Care and (for example, NFPA 25), in addition to joint by applying a minimum-to-maxi- the standards of any other authorities mum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Maintenance having jurisdiction.Contact the install- Nm). Higher levels of torque can distort ing contractor or sprinkler manufacturer the sprinkler inlet with consequent leak- The TYCO RAPID RESPONSE Series regarding any questions. age or impairment of the sprinkler. LFII Residential Flat-Plate Concealed Pendent Sprinkler (TY2524) must be Automatic sprinkler systems are rec- Pendent not attempt to compensate for in- ommended to be inspected, tested, sufficient adjustment in the Cover Plate/ maintained and serviced in accordance and maintained by a qualified Inspec- Retainer Assembly by under-or over- with the following instructions. tion Service in accordance with local r... w . w — e.m e s• t 1. Install pendent sprinklers in the _ Before closing a fire protection system pendent position, with the center- main control valve for maintenance work on the fire protection system that it cos- line of the sprinkler perpendicular to the mounting surface, trols,obtain permission to shut down the affected fire protection system from the 2. Remove the Protective Cap. proper authorities and notify all person- 3. With pipe-thread sealant applied ne/who may be affected by this action. _ to the pipe threads, and using the When properly installed,there is a nomi-_ _ _ _ W-Type 18 Wrench shown in Figure nal 1/8 inch (3,2 mm)air gap between 2, install and tighten the Sprinkler/ the lip of the Cover Plate and the cell- ` Support Cup Assembly into the fit- ing,as shown in Figure 3.This air gap ting. The W-Type 18 Wrench ac- is necessary for proper operation of the cepts a 1/2 inch ratchet drive. sprinkler by allowing heat flow from a 4. Replace the Protective Cap by fire to pass below and above the Cover pushing it upwards until it bottoms Plate to help assure appropriate release out against the Support Cup. The of the Cover Plate in a fire situation.If the ceiling needs repainting after sprinkler Protective Cap helps prevent dam- age to the Deflector and Guide installation,exercise care to ensure that Pins during ceiling installation and/ the new paint does NOT seal off any of or during application of the finish the air gap.Failure to do so may impair coating of the ceiling. sprinkler operation. Absence of a Cover Plate can delay the NOTICE sprinkler operation in a fire situation. As long as the protective Cap re- Do not pull the Cover Plate relative to mains in place, the system is con- the Enclosure.Separation may result. sidered"Out Of Service". Exercise care to avoid damage to sprin- 5. After the ceiling has been corn- klers before, during, and after installa- pleted with the 2-1/2 inch (63 mm) tion.Never paint, plate, coat, or other- diameter clearance hole and in wise alter automatic sprinklers after they preparation for installing the Cover leave the factory. Plate/Retainer Assembly, remove Never repaint factory-painted Cover and discard the Protective Cap, Plates.When necessary,replace cover and verify that the Deflector moves plates with factory-painted units.Non- up and down freely. factory applied paint can adversely de- If the Sprinkler has been damaged lay or prevent sprinkler operation in the and the Deflector does not move up event of a fire. and down freely, replace the entire Sprinkler assembly.Do not attempt to modify or repair a damaged sprinkler. TFP443 Page 5 of 6 Limited Ordering Warranty Procedure • Products manufactured by Tyco Fire Contact your local distributor for avail- Suppression & Building Products ability. When placing an order,indicate (TFSBP)are warranted solely to the orig- the full product description and Part final Buyer for ten(10)years against de- Number(P/N). fects in material and workmanship when paid for and properly installed and main- Sprinkler/Support Cup Assembly Specify: Series LFII Residential Flat tained under normal use and service. This warranty will expire ten (10)years Plate Concealed Pendent Sprinkler from date of shipment by TFSBP. No (TY2524), K=4.9, without Cover Plate/ warranty is given for products or corn- Retainer Assembly, P/N 51-114-1-160. ponents manufactured by companies Cover Plate/Retainer Assembly not affiliated by ownership with TFSBP Specify:Cover Plate/Retainer Assem- or for products and components which bly with finish (below) for the Series have been subject to misuse, improper LFII Residential Flat-Plate Concealed installation,corrosion, or which have not Pendent Sprinkler(TY2524),K=4.9, P/N been installed,maintained, modified or (below): repaired in accordance with applicable Standards of the National Fire Protection Chrome P/N 56-201-9-135 Association,and/or the standards of any Custom P/N 56-201-X-135 other Authorities Having Jurisdiction. on White Materials found by TFSBP_to be_defec P/N 56-20i-0-135 T r'/N'.G-201-3=135 - _ at TFaBPs sole option. I}-SBP neither ,Rn�_o1a assumes,nor authorizes any person to Signal White** assume for it, any other obligation in (RAL 9003) P/N 56-201-4-135 connection with the sale of products or Standard White(Grey White) parts of products.TFSBP shall not be (RAL9002) P/N 56-201-5-135 responsible for sprinkler system design errors or inaccurate or incomplete in- ' Eastery Hemisphere sales only. " formation supplied by Buyer or Buyer's Previously known as Bright White. representatives. Note: All Custom Cover Plates are - -painted using Sherwin Williams Interior In no event shall TFSBP be liable,in con- tract,tort,strict liability or under anyoth- ServicLatex Paint. Contact TYCO Customer er legal theory, for incidental, indiect, custom rwdh any questions related to special or consequential damages, in- cluding custom orders. but not limited to labor charg- Sprinkler Wrench es, regardless of whether TFSBP was Specify W-Type 18 Sprinkler Wrench, informed about the possibility of such P/N 56-000-1-265. damages,and in no event shall TFSBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties,express or implied,including warranties of mer- chantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on fail- ure of or defect in products,materials or components,whether the claim is made in contract,tort,strict liability or any oth- er legal theory. This warranty will apply to the full extent permitted by law.The invalidity,in whole or part, of any portion of this warranty will not affect the remainder. . . tLJCQ /Fire11& Building Products rapid response HOME FIRE SPRINKLER SYSTEM Technical Services:Tel:(800)381-9312/Fax:(800)791-5500 Series LFII Residential Horizontal Sidewall Sprinklers 4.2 K-factor General adjustment or up to 1/2 inch(12,7 mm) of total adjustment from the flush mounting surface position.The adjust- Description ment provided by the Recessed Es- l" i cutcheon reduces the accuracy to The Series LFII (TY1334) Residential which the pipe nipples to the sprinklers C.? Horizontal Sidewall Sprinklers are must be cut. < � decorative, fast response, frangible — ii 9. Vi The Series LFII TY13341 as haan r n, '. -- homes, apartments, dormitories and water distribution characteristics .. , , . ° hotels.When aesthetics and optimized proven to help in the control of residen- ti,,,,,,,. ai flow characteristics are the major con- tial fires and to improve the chance for illl$ sideration, the Series LFII (TY1334) occupants to escape or be evacuated. , should be the first choice. The Series LFII are to be used in wet WARNINGS pipe residential sprinkler systems for The Series LFII(TY1334) Residential one-and two-family dwellings and mo- Horizontal Sidewall Sprinklers de- bile homes per NFPA 13D; wet pipe scribed herein must be installed and residential sprinkler systems for resi- maintained in compliance with this dential occupancies up to and includ- document,as well as with the applica- ing four stories in height per NFPA ble standards of the National Fire Pro- 13R;or, wet pipe sprinkler systems for tection Association, in addition to the *- , ,;� EZ the residential portions of any occu- standards of any other authorities hav- ,,, pancy per NFPA 13. ing jurisdiction. Failure to do so may , � " � The Series LFII (TY1334) has a 4.2 impair the performance of these de- ss € (60,5) K-factor that provides the re vices. ,,t quired residential flow rates at reduced The owner is responsible for maintain- 7 ii pressures,enabling smaller pipe sizes ing their fire protection system and de . and water supply requirements. vices in proper operating condition. The recessed version of the Series 71.4Ftire The installing contractor or sprinkler r w_ manufacturer should be contacted LFII (TY1334) is intended for use in areas with finished walls. It employs a with any questions. two-piece Style 20 Recessed Escutch- eon. The Recessed Escutcheon pro- vides 1/4 inch (6,4 mm) of recessed Sprinkler/Model Identification IMPORTANT Number Always refer to Technical Data Sheet TFP700 for the "INSTALLER SIN TY1334 WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail • to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 JANUARY, 2006 TFP410 Page 2 of 8 TFP410 Components: 5 3 2 1 1 - Frame WRENCH 2- Button Assembly alOka FLATS I 3- Sealing Assembly o nin 4- Bulb 5 Compression Screw _ `a,��►��►` Ill 6- Deflector* TOP-OF- 6* 4 7/16" 11,1 mm jiiIIll * DEFLECTOR ) ti 2-7/8"DIA. Temperature rating (73,0 is indicated on top MAKE-IN I mm) of Deflector. _ AO ' . _ CENTERLINE 7/16" OF WATERWAY (11,1 mm) – w`^^^""� STYLE 20 r� 1/2"NPT RECESSED 1-5/8" ESCUTCHEON END-OF- (41,3 mm)—�\I ESCUTCHEON DEFLECTOR 2-1/4" _I PLATE SEATING BOSS (57,2 mm) 1 SURFACE RECESSED FIGURE 1 SERIES LFII(TY1334)RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS 7/16±1/8" IIE-„,, (11,1±3,2 mm) MOUNTING FACE OF WRENCH RECESS SURFACE SPRINKLER (END"A"USED FITTING FOR TY1334) TOP-OF- CLOSURE FIGURE 3 DEFLECTOR IR W--TYPE 6 SPRINKLER WRENCH \ TY1334 2-7/8"DIA. . (73,0 mm) WRENCH 9 2-1/4"DIA. RECESS 7/16" a�►l (57,2 mm) /I (11,1 mm) Ij. 1 �, MOUNTING 11( . T ' _i PLATE END-OF- _ DEFLECTORy 1/8" PUSH WRENCH BOSS I (3,2 mm) IN TO ENSURE 1-3/8"(34,9 mm) l I 1/2"(12,7 mm) ENGAGEMENT F WITH SPRINKLER 1-1/8"(28,6 mm) 1/4"(6,4 mm) WRENCHING AREA FIGURE 4 FIGURE 2 W-TYPE 7 RECESSED STYLE 20 RECESSED ESCUTCHEON SPRINKLER WRENCH FOR USE WITH THE SERIES LFII(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER TFP47O Page 3 of 8 Technical total number of"design sprinklers" as Do not attempt to compensate for in- specified in NFPA 13D or NFPA 13R. sufficient adjustment in an Escutcheon Data For systems designed to NFPA 13,the Plate by under-or over-tightening the number of design sprinklers is to be Sprinkler. Readjust the position of the Approvals: the four most hydraulically demanding sprinkler fitting to suit. UL and C-UL Listed. NYC Approved sprinklers. The minimum required dis- The Series LFII Horizontal Sidewall under MEA 44-03-E. charge from each of the four sprinklers Sprinklers must be installed in ac- is to be the greater of the following: cordance with the following instruc- Maximum Working Pressure: tions. 175 psi (12,1 bar) • The flow rates given in Tables A, B, Discharge Coefficient: C, and D for NFPA 13D and 13R as Step 1. Horizontal sidewall sprinklers K=4.2 Ge Coefficient: iz (60,5nt: LPM/bar��z) a function of temperature rating and are to be installed in the horizontal the maximum allowable coverage position with their centerline of water- Temperature Rating: area. way perpendicular to the back wall and 155°F/68°C or 175°F/79°C . A minimum discharge of 0.1 gpm/sq. parallel to the ceiling.The word"TOP" Finishes: ft. over the"design area" comprised on the Deflector is to face towards the ceiling De- White Polyester Coated, of the four most hydraulically de- with the front edge . the Chrome Plated, or Natural Brass manding sprinklers for the actual Hector parallel to the ceiling. coverage areas being protected by Step 2. With pipe thread sealant ap- Physical Characteristics: the four sprinklers. plied to the pipe threads,hand tighten Frame Brass Obstruction To Water Distribution. the sprinkler into-the sprinkler fitting. Button Bronze Locations of sprinklers are to be in Step3. Tighten the sprinkler into the Sealing Assembly - P 9 P Beryllium Nickel w/Teflont accordance with the obstruction rules sprinkler fitting using only the W-Type -- -- -- .„,„-,.„,, ,- ,....,, --_-of NEPA 13 for-residential-sprinklers._._ 6 Sprinkler Wrench (Ref. Figure 3). . . ,. .e€erzenFato-Ftgure-t-=g..�_R5PP Deflector Copper klers are to be installed with an end-of- • . � ” the wrench flats. deflector-boss to wall distance of 1- tDupont Registered Trademark 3/8 to 6 inches or in the recessed po- The Series LFII Recessed Horizontal sition using only the Style 20 Re- Sidewall Sprinklers must be installed Operation cessed Escutcheon as shown in in accordance with the following in- Figure 2. structions. The glass Bulb contains a fluid that In addition the top-of-deflector-to-ceil- Step A. Recessed horizontal sidewall expands when exposed to heat.When ing distance is to be within the range sprinklers are to be installed in the the rated temperature is reached, the (Ref. Table A, B, C, or D) being by horizontal position with their centerline fluid expands sufficiently to shatter the draulically calculated. of waterway perpendicular to the back glass Bulb allowing the sprinkler to Sprinkler Spacing. The minimum wall and parallel to the ceiling. The activate and flow water. spacing between sprinklers is 8 feet word"TOP"on the Deflector is to face towards the ceiling. (2,4 m). The maximum spacing be Design tween sprinklers cannot exceed the Step B. After installing the Style 20 width of the coverage area(Ref.Table Mounting Plate over the sprinkler Criteria A)being hydraulically calculated(e.g., threads and with pipe thread sealant maximum 12 feet for a 12 ft. x 12 ft. applied to the pipe threads, hand The Series LFII (TY1334) Residential coverage area, or 16 feet for a 16 ft.x tighten the sprinkler into the sprinkler Horizontal Sidewall Sprinklers are UL 20 ft. coverage area). fitting. and C-UL Listed for installation in ac- Step C. Tighten the sprinkler into the cordance with the following criteria. Installation sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. NOTE The Series LFII (TY1334) must be in- Figure 4). With reference to Figure 1, When conditions exist that are outside stalled in accordance with the follow- the W-Type 7 Recessed Sprinkler the scope of the provided criteria,refering instructions: Wrench is to be applied to the sprinkler to the Residential Sprinkler Design NOTES wrench flats. Guide TFP490 for the manufacturer's Do not install any bulb type sprinkler if Step C. After the wall has been in- re ome the ndationlocalAthat ft aHe aving accept-J - the bulb is cracked or there is a loss of stalled or the finish coat has been ap- liquid from the bulb. With the sprinkler lied, slide on the Style 20 Closure risdiction. held horizontally, a small air bubble- P y over the Series LFII Sprinkler and System Type. Only wet pipe systems should be present. The diameter of the push the Closure over the Mounting may be utilized. air bubble is approximately 1/16 inch Plate until its flange comes in contact Hydraulic Design. The minimum re- (1,6 mm). with the wall. quired sprinkler flow rate for systems A leak tight 1/2 inch NPT sprinkler joint designed to NFPA 13D or NFPA 13R should be obtained with a torque of 7 are given in Table A, B, C,and D as a to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- function of temperature rating and the mum of 21 ft.lbs. (28,5 Nm) of torque maximum allowable coverage areas. is to be used to install sprinklers. The sprinkler flow rate is the minimum Higher levels of torque may distort the required discharge from each of the sprinkler inlet with consequent leak- age or impairment of the sprinkler. (Continued on Page 8) • Page 4 of 8 TFP4IO ELEVATION Maximum Maximum Coverage Spacing Minimum Flow lc/and Residual-Pressure Area(a) Ft. Width x Length(b) (m) Top-Of-Deflector-To-Ceiling: Top-Of-Deflector-To-Ceiling: Ft.x Ft. 4 to 6 Inches(100 to 150 mm) 6 to 12 Inches(150 to 300 mm) 12 x 12 12 12 GPM(45,4 LPM) 12 GPM(45,4 LPM) 13 GPM(49,2 LPM) 13 GPM(49,2 LPM) (3,7 x 3,7) (3,7) 8.2 psi(0,57 bar) 8.2 psi(0,57 bar) 9.6 psi(0,66 bar) 9.6 psi(0,66 bar) 14 x 14 14 14 GPM(53,0 LPM) 16 GPM(60,6 LPM) 17 GPM(64,3 LPM) 18 GPM(68,1 LPM) (4,3 x 4,3) (4,3) 11.1 psi(0,77 bar) 14.5 psi(1,00 bar) 16.4 psi(1,13 bar) 18.4 psi(1,27 bar) 16 x 16 16 16 GPM(60,6 LPM) 16 GPM(60,6 LPM) 18 GPM(68,1 LPM) 18 GPM(68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 16 x 18 -- 16 19 GPM(71,9 LPM) 19 GPM(71,9 LPM)- 21 GPM(79,5 LPM) 21 GPM(79,5 LPM) (4,9 x 5,5) (4,9) 20.5 psi(1,41 bar) 20.5 psi(1,41 bar) 25.0 psi(1,72 bar) 25.0 psi(1,72 bar) 16 x 20 16 23 GPM(87,1 LPM) 23 GPM(87,1 LPM) 26 GPM(98,4 LPM) 26 GPM(98,4 LPM) (4,9 x 6,1) (4,9) 30.0 psi(2,07 bar) 30.0 psi(2,07 bar) 38.3 psi(2,64 bar) 38.3 psi(2,64 bar) (a) For coverage area dimensions less than or between those indicated,it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)Width(backwall where sprinkler is located)x Length(horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details. (d)Sidewall sprinklers,where installed under a ceiling with a slope greater than 0 inch rise for a 12 inch run to a slope up to 2 inch rise for 12 inch run,must be located per one of the following: - • Locate the sprinklers at the high point of the slope and positioned to discharge down the slope. • Locate the sprinklers along the slope and positioned to discharge across the slope. TABLE A NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR HORIZONTAL CEILING(Maximum 2 Inch Rise for 12 Inch Run) TFP41O Page 5 of 8 12" 8" MAXIMUM ELEVATION Minimum-Flow lc)and-Residual-Pressure (I)Two-sprinkler design with the sprinklers-at the high point of the slope and positioned to discharge down the slope. Maximum Maximum Cever.7.71imm ., • ArPa��- -- Ft. Width x Length(b) (m) Top-Of-Deflector-To-Ceiling: - Top-Of-Deflector-To-Ceiling: Ft.xFt. (m x m) 4 to 6 Inches(100 to 150 mm) 6 to 12 Inches(150 to 300 mm) 155°F/68°C 175°F/79°C 155F/68°C 175°F/79°C 12 x 12 12 I 12 GPM(45,4 LPM) I 12 GPM(45,4 LPM) I 13 GPM(49,2 LPM) I 13 GPM(49,2 LPM) (3,7 x 3,7) (3,7) 8.2 psi(0,57 bar) 8.2 psi(0,57 bar) 9.6 psi(0,66 bar) 9.6 psi(0,66 bar) 14 x 14 14 I 14 GPM(53,0 LPM) I 14 GPM(53,0 LPM) I 17 GPM(64.3 LPM) I 17 GPM(64.3 LPM) (4,3 x 4,3) (4,3) 11.1 psi(0,77 bar) 11.1 psi(0,77 bar) 16.4 psi(1,13 bar) 16.4 psi(1,13 bar) 16 x 16 16 I 16 GPM(60,6 LPM) I 16 GPM(60,6 LPM) I 18 GPM(68,1 LPM) I 18 GPM(68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 16 x 18 16 I 19 GPM(71,9 LPM) I 19 GPM(71,9 LPM) I 21 GPM(79,5 LPM) I 21 GPM(79,5 LPM) (4,9 x 5,5) (4,9) 20.5 psi(1,41 bar) 20.5 psi(1,41 bar) 25.0 psi(1,72 bar) 25.0 psi(1,72 bar) 16 x 20 16 I 24 GPM(90,8 LPM) I 24 GPM(90,8 LPM) I 26 GPM(98,4 LPM) I 26 GPM(98,4 LPM) (4,9 x 6,1) (4,9) 32.7 psi(2,25 bar) 32.7 psi(2,25 bar) 38.3 psi(2,64 bar) 38.3 psi(2,64 bar) (a) For coverage area dimensions less than or between those indicated,it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)Width(backwall where sprinkler is located)x Length(horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.. TABLE B NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR SPRINKLERS AT THE HIGH POINT OF THE SLOPE AND DISCHARGING DOWN THE SLOPE (Greater Than 2 Inch Rise for 12 Inch Run Up To 8 Inch Rise for 12 Inch Run) Page 6 of 8 TFP470 • -1 4" MAXIMUM AI- ELEVATION Minimum-Flow lc)and Residual-Pressure (11)Two-sprinkler design with the sprinklers located along the slope and positioned to Maximum Maximum i design morthan two sprinklers in a compartment and - MOM•2".1.4111. ...1:w. Width x Length(b) (m) Ft,x Ft. Top-Of-Deflector-To-Ceiling: Top-Of-Deflector-To-Ceiling: (m x m) 4 to 6 Inches(100 to 150 mm) 6 to 12 Inche 50 to 300 mm) 155°F/68°C 175°F/79°C 155°F/68°C 175°FR9°C 12 x 12 12 II 16 GPM(60,6 LPM) II 16 GPM(60,6 LPM) II 18 GPM(68,1 LPM) II 18 GPM(68,1 LPM) (3,7 x 3,7) (3,7) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 14 x 14 14 II 16 GPM(60,6 LPM) II 16 GPM(60,6 LPM) II 18 GPM(68,1 LPM) II 18 GPM(68,1 LPM) (4,3 x 4,3) (4,3) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 16 x 16 16 II 16 GPM(60,6 LPM) II 16 GPM(60,6 LPM) II 18 GPM(68,1 LPM) II 18 GPM(68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 16 x 18 16 II 22 GPM(83,3 LPM) II 22 GPM(83,3 LPM) II 22 GPM(83,3 LPM) II 22 GPM(83,3 LPM) (4,9 x 5,5) (4,9) 27.4 psi(1,89 bar) 27.4 psi(1,89 bar) 27.4 psi(1,89 bar) 27.4 psi(1,89 bar) 16 x 20 16 III 23 GPM(87,1 LPM) III 23 GPM(87,1 LPM) III 26 GPM(98,4 LPM) III 26 GPM(98,4 LPM) (4,9 x 6,1) (4,9) 30.0 psi(2,07 bar) 30.0 psi(2,07 bar) 38.3 psi(2,64 bar) 38.3 psi(2,64 bar) (a)For coverage area dimensions less than or between those indicated,it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)Width (backwall where sprinkler is located)x Length(horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design Criteria Section for details.. TABLE C NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR SPRINKLERS LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE (Greater Than 2 Inch Rise for 12 Inch Run Up To 4 Inch Rise for 12 Inch Run) TFP410 Page 7 of 8 12" • 8" MAXIMUM ELEVATION Minimum-Flow(0 and-Residual-Pressure (III)Three-sprinkler design-when there are-more-than-two sprinklers in a compartment and with the sprinklers located along the slope.and positioned to discharge across the slope. Maximum Maximum Width x Length(b) (m) Ft.x Ft. Top-Of-Deflector-To-Ceiling: (m x m) 4 to 6 Inches(100 to 150 mm) 155°F/68°C 175°F/79°C 12 x 12 12 III 16 GPM(60,6 LPM) III 16 GPM(60,6 LPM) (3,7 x 3,7) (3,7) 14.5 psi(1,00 bar) - 14.5 psi(1,00 bar) 14 x 14 14 III 16 GPM(60,6 LPM) III 16 GPM(60,6 LPM) (4,3 x 4,3) (4,3) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 16 x 16 16 III 16 GPM(60,6 LPM) III 16 GPM(60,6 LPM) (4,9 x 4,9) (4,9) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 16 x 18 16 N/A N/A (4,9 x 5,5) (4,9) 16 x 20 16 N/A N/A (4,9 x 6,1) (4,9) (a) For coverage area dimensions less than or between those indicated,it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)Width(backwall where sprinkler is located)x Length(horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.. TABLE D NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR SPRINKLERS LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE (Greater Than 4 Inch Rise for 12 Inch Run Up To 8 Inch Rise for 12 Inch Run) Page 8 of 8 TFP41O Care and Limited Ordering Maintenance Warranty Procedure The Series LFII (TY1334) must be Products manufactured by Tyco Fire& When placing an order, indicate the maintained and serviced in accord- Building Products (TFBP) are war- full product name. Contact your local ance with the following instructions: ranted solely to the original Buyer for distributor for availability.. NOTES ten(10)years against defects in mate- Sprinkler Assembly: Absence of an Escutcheon Plate may rial and workmanship when paid for delay the sprinkler operation in a fire and properly installed and maintained Series LFII(TY1334),K=4.2,Residen- situation. under normal use and service. This tial Horizontal Sidewall Sprinkler with warranty will expire ten (10) years (specify) temperature rating and Before closing a fire protection system from date of shipment by TFBP. No (specify)finish, P/N (specify). main control valve for maintenance warranty is given for products or corn- work on the fire protection system ponents manufactured by companies 155°F/68°C or which it controls, permission to shut not affiliated by ownership with TFBP Chrome Plated P/N 51-211-9-155 terndown mthe affected fire ust be obtained from the pn roper ropgs-er or for products and components which 15 Nrhse Polyester P/N 51-211-4-155 p have been subject to misuse,improper 155°F/68°c authorities and all personnel who may installation. corrosion, or which have White be affectedbythis_action must be no- not been installed; maintained, modi (RAL9O1o)' P/N 51-211-3-155 tified. 155°F/68°C fied or repairedinaccordance-with.ap- Sprinklers which are found to be leak- plicable Standards of the National Fire 175Natural Brass P/N 51-211-1-155 °Fns°Cor ing or exhibiting visible signs of corro- Protection Association, and/or the Chrome Plated P/N 51-211-9-175 ------------- sion must be replaced. standards of any_other Authorities 175°F/79°C pain e., p a e., coa e.,Yor o erwise ., . .- e- - '. •_-_ ' Amami altered after leavingthe factory. Modi- repaired or replaced, at TFBP's sole White option. TFBP neither assumes, nor 175°F/79°C o). P/N 51-211-3-175 fled sprinklers must be replaced. P Sprinklers that have been exposed to authorizes any person to assume for it, Natural Brass P/N 51-211-1-175 corrosive products of combustion, but any other obligation in connection with have not operated,should be replaced the sale of products or parts of prod- Eastern Hemisphere sales only. if they cannot be completely cleaned ucts.TFBP shall not be responsible for Recessed Escutcheon: - by wiping the sprinkler with a cloth or sprinkler system design errors or inac- by brushing it with a soft bristle brush. curate or incomplete information sup- Specify: Style 20 Recessed Escutch- Care must be exercised to avoid dam- plied by Buyer or Buyer's repre- eon with (specify') finish, P/N (spec- age to the sprinklers- before, during, sentatives. ify*). and after installation. Sprinklers dam- In no event shall TFBP be liable, in *Refer to Technical Data Sheet TFP770. aged by dropping, striking, wrench contract, tort, strict liability or under twist/slippage, or the like, must be re- any other legal theory, for incidental, placed.Also,replace any sprinkler that indirect,special or consequential dam- Sprinkler Wrench: has a cracked bulb or that has lost ages, including but not limited to labor Specify: W-Type 6 Sprinkler Wrench, liquid from its bulb. (Ref. Installation charges, regardless of whether TFBP P/N 56-000-6-387. Section). was informed about the possibility of Specify: W-Type 7 Sprinkler Wrench, The owner is responsible for the in- such damages, and in no event shall P/N 56-850-4-001. spection, testing, and maintenance of TFBP's liability exceed an amount their fire protection system and de- equal to the sales price. vices in compliance with this docu- The foregoing warranty is made in lieu ment, as well as with the applicable of any and all other warranties. ex- standards of the National Fire Protec press or implied. including warranties tion Association (e.g., NFPA 25), in of merchantability and fitness for a par- addition to the standards of any other authorities having jurisdiction. The in- ticular purpose. stalling contractor or sprinkler manu- This limited warranty sets forth the ex- facturer should be contacted relative clusive remedy for claims based on to any questions. failure of or defect in products, materi- NOTE als or components, whether the claim The owner must assure that the sprin- is made in contract, tort, strict liability kiers are not used for hanging of any or any other legal theory. objects and that the sprinklers are only This warranty will apply to the full ex- cleaned by means of gently dusting tent permitted by law.The invalidity,in with a feather duster;otherwise, non- whole or part, of any portion of this operation in the event of a fire or road- warranty will not affect the remainder. vertent operation may result. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 DynaxTftrepd Replacement Dyna-Thread' offers the life expectancy of Sch4O with superior hydraulics and greater value. Dyne-Thread sprinkler pipe represents an engineering advancement for the sprinkler and longevity of traditional Sch-40 pipe withhydraulic pipe industry,It combines the safety qualitysuperior and ydraulic advantagges. Comparison to Schedule 40 � �Co>tnpdrisnl #o !W T Pipes'. • Dyna-Thread's inside diameter is up • With its increased strength and lighter • More wall thickness at the thread to 3.6%larger than Soli-40 giving it weight,Dyna-Tread reduces (CRR,1.00)gives D superior hydraulics.And,when used Dyna-Thread n tirwith Dyna-Flow pipe, installation fatigue and is ideal for better life expectancy than lightwall �' p p , retro-fit applications. threadable pipe joints.down sizing often occurs. Cosrosicm Resistance Ratio(CRR)is a • Unlike lightwall threadable pipe, • Dyna-Thread is fully listed and UL(Underwriters Laboratory)term for D approved by UL,ULC,and FM for Y�-Thread has no thread gauge tho estimated life expectancy of a pipe warning, fire sprinkler applications. joint.This is based on the calculated • The life expectancy of Dyna-Thread veal thickness at the base of the Brat Dyne-Thread is approved for and Sch-40 are equal based on the• exposed thread,assumed to be the standard hanger spacing(15 S. calculated wall thicknesses per UL. weakext point of the pipe length.Dyna- 0.C.),can be used as earthquake — - sway bra .,_ sod is safe to use as ..M.-"r......", ., .pnk7�it•Fif+33f{TI'Ff• Miiiirir4n=UM)VIM of ;., .R. ..., make Dyna-Thread facilitates smooth and are bath assigned the same CRR of • threading and lower maintenance 1,00. Dyna-Thread is safer to weld on, costs, • Dyne-Thread is more widely • The exterior of Dyna-Thread is The internal surface of all black Allied accepted than lightwall threadable wb protected by a clean,durable mill Tube&Conduit Fire Sprinkler pipe Soh-40 is specified. coating for extended shelf life and products up to 4.5000"in diameter is easy paint application, coated with our now Antibacterial _ . _-- ---- Formula,`ABB".In scientific laboratory tet;ABS proved to have superior Specifications & Approvals resistance to microbial CDlcnizatinn of (DI 4;it*- 0119 pipe walla,thereby delaying or possibly Super 40/Dyne-Thread pipe is preventing the onset of manufactured to meet:ATM A-135, Listed Approved Listed Microbiologioaisy Influenced corrosion Grade A.and is in compliance with (MK when the First Sprinkler System NFPA-13.All sizes of Super 40/Dyna- is$rat installed Thread are rated at 300 psi working pressure.Super 40/Dyna-Thread is UI. SyecifiCations and ULC Listed for wet,dry deluge and NPS Mantles/I.A. Wt. WI,(1120 Mad) Pett W (21') • pre-notion sprinkler systems and FM In;Plnl mm Lb Wt Kgmr ( �1n WI/Lltt(24') WL!Llft(25' Approved fur use In wet systems.Super b&?1'Kg/m Lilt Lk Kg Lbs;Kg Lbs;Kg 401Dyna-Thread can be"hot-dip" 1' 1,080 1.330 1,75 70 1865 2234 2327 galvanized to moot FM requirement for 25 27.4 20 2.80 70 857 7073 705: dty systems, Super 40/Dyne-Thread is 1W 1,408 1,870 2.54 51 2002 2288 2384 approved for all threaded couplings and 32 35.8 2.8 9,78 57 808 703e 108 welded outlets end is suitable for all 1W 1.699 2.290 3,22 44 2115 2418 261• roll-grooved,and plain-end fittings. 40 41.ff 3.4 4.79 44 858 7087 774. (See listinginfbrmarion). 2" 2.104 3.080 4.67 30 1921 2195 2287 50 53.4 4.5 8.80 30 877 996 103 tile°/ law control allied 16100 S. Lathrop•Harvey, IL 50425 Customer Service: 1..,i` ci 11350 Norcom Rd.•Philadelphia, PA 19154 (800)882.5543 TUEIE b CONDUIT 2528 N,27 th Ave, -Phoenix,AZ 85009 Fax 708-339-1808 33-3 Submittal Data Sheet Dyne-Thread° SvmP Here Full Line Sch-40 Replacement Dyna-T'arred sprinkler pipe represents an engineering advancement for the sprinkler pipe industry.It combines the safety and longevity uftraditional Soh-40 pipe with • quality and superior hydraulic advantages. Comparison to Schedule 40 Dyna-Threada inside diameter is up to 3.6%larger than Sch-40 giving it superior hydraulics.Also,when used in combination with Dyna-Flaw pipe, don sing often occurs.Dyna-Thread is fully listed and approved UL, UI..C, - : _ _ _- and FM for fire sprinkles applications.The life expectancy of Dyna-Thread and Sch-40 t= - ---- are equal based on the calculated wall thicknesses per UL.The consistent quality of �- steel used to make Dyne-Thread facilitates smooth threading and lower maintenance ` '':,' - " costs. The exterior of Dyna-Thread is protected bye clean,Mashie mill coating for oxtcnded shelf life and easy paint application.With its increased strength and Jtg'f'r weight,Dyna-Thread reduces installation fatigue and is ideal for retro-fit applications. <' '' ` ' • Corrosion Resistance Ratio(CRR)is a UL(Underwriters Laboratory)term far the 1 •=c.,:r :< . estimated life ezepectanoy of a pipe joint.This is based;n+_the calculated wall thickness --;; ?.'•',. <Y; . at the base of the first exposed thread,assumed to be the weakest point of the pipe - • --.: ��::_:: length.Dyna-Thread and Soh-40 have the game calculated wall thicknesses at this : i point and are both assigned the seine CRR of 1.00. '. ': /iii tE ' 1 € -r= • Comparison to L.W.T.Pipe More wall thickness at the thread(CRR=1.00)gives '.> tea. "'-_' Dyne-Thread better life expectancy than lightwall threadablc pipe joints.Unlike - `,ur. . ?` lightwnll threadablc Dyne-Thread - s pipe yna has no thread gauge warning.Dyna-Thread is 'i`1t: .. -ti approved for standard hanger spacing(15 fL O.C.),C112 baused as earthquake sway Pd.d•4� :. Y:4 ASF" brawng,•and is safe to use as drops.Dyna-Thread is safer to weld on than ;� . h 0. natty zinc,- sy °, '' • Specifications&ApprovaIs Super 40/ Dyne-Thread pipe is manufactured to Specifications meet:ASTM A 135,Grade A and is in NPS Nsmloal 1.0. WI. Wt.(H2O Filled) Per/ WWI(211 W$.if(2/) VII/L111(25' compliance with NFPA-13.All sizes of ln:on hr min theft Kahn Lhaift Kglit Lia' Lbs:Kp Lbs;Kg Lbs; • Super 40/Dyna-Thread are rated at 300 1' 1.080 1.330 1.75 70 1855 2234 232 • psi working pressure.Super 40/Dyna- 25 244 A0 260 70 887 1013 105% Thread is UL and ULC Listed far wet, , - ---— 1l/4. 1.405 1.870-------2.54-----51 -2002 -- 2288 238 -----—-- -------- y end pre-action sprinkler systema and 32 FM Approved for use in wet systems. 36.8 2.8 3.7 51 9% 1038 108 Super 40/Dyna-Thread can be"hot-dip" 1W 1,639 2.290 3,22 44 2115 2418 251 galvanized to meet FM requirement for 40 41.8 24 4.79 44 959 1087 11- dry systems. Super 40/Dyna-Thread is 2' . 2.104 3.050 4.57 30 1921 2198 228 approved for all threaded couplings and 50 53.4 4,5 8.80 30 871 998 103 welded outlets and is suitable for all roll- grooved,and plain-end fittings.(Soo American Tube and Pipe was enquired by Allied Tube and Conduit on February I, Bating information), 1997.Tho engineered lightwall and leaadard wall family of products although they The internal surface of all black Fire have tit$i reset names arc the same in all respects with regard to strength,weight, • Sprfnkier pipe tip to 4.5000"in diameter bundler count,listings and approvals.For example, shall be coated with Allied Tube& Dyna-Flow and Super Flo arc the same product as fp) ...i. 41) Conduit Antibacterial Formula"ADP", are Dyne Thread and Super 40.XL is manufactured with Exterior galvanized coating.HLT is manufactured with Black lacquer coatingListed Approved Usted Protect; Sprinkler Contractor: Data: Enginaar: Specification Reference: System'Ripa: Locations: comments: • S3-4 ttjcotqcol F/o wTyco Fire Control Products • BlazeMaster © • FIRE SPRINKLER PIPE & FITTINGS SUBMITTAL SHEET TYCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale, Pennsylvania 19446 www,tyco-fire.com TECHNICAL SERVICES TEL: (800) 381-9312 • Fax: (800) 791-5500 E-MAIL:techserv@tycofp.com 9� 1 t4 141 104 No. 19-1.5 TD915 4-1.1.20 9/2001 . IO Introduction Tyco Fire Products (TFP) BlazeMaster°CPVC pipe and the same time, they provide superior heat resistance and fittings are designed exclusively for use in wet pipe strength as compared to traditional CPVC and PVC piping automatic fire sprinkler systems. They are made from a materials used in the plumbing trade. Various adapters are • specially developed thermoplastic compound composed of available to connect CPVC pipe to metallic piping.All female post chlorinated polyvinyl chloride (CPVC) resin and state of pipe thread adapters have brass inserts for durability. the art additives. TFP BlazeMaster CPVC products are Grooved adapters connect directly to grooved end valves . easier to install than traditional steel pipe systems, and at and metallic pipe, with flexible grooved end couplings. Technical Data Sizes: 1/4"-3" Manufacture Source: U.S.A. Maximum Working Pressure: 175 psi Material: Approvals: UL, FM, CUL, NSF, Dade County, LPCB, Pipe: ASTM F442, SDR 13.5 MEA, and the City of Los Angeles Fittings: ASTM F438 (Sch. 40) and Note: See current TFP BlazeMaster Installation Instructions and ASTM F439 (Sch. 80) Technical Manual,for exact listing/approval information Color: Orange Pi ' e Nom.Pipe Size Avg. O.D.Inches Avg.LI. Inches Wt.Lbs./Ft. Wt.IIz0 filled Pipe Lbs./Ft. Ft. of Pipe per Lift Wt.per Lift Lbs. 3/4" 1.050 0.874 0.17 0.43 7875 1413 1" 11111E0111 1.101 0.26 0.67 5040 1320 IMUSIMI 1.660 1.394 0.42 1.07 2835 1191 1'/2" 1.900 1.598 0.55 1.40 2205 1136 2" IMEgall. 2.003 0.86 - __- _ 2.20__ 1260 - -- ___ __1063 _-_-_-- =:- - 3" 3.500 2.952 1.87 4.79 720 1344 Fittings T,° T/O' . T/O 45° Elbow _. 4,�, T�° Reducing 2 90° Elbow 90°_Elbow _ _ . T�o2 - = 1011_ ----TM ' 1 ' I I i t Part No. Size Sch. T/O Wt. Part T/O Wt. Part No. Size Sch. T/O Wt. 80050 '/," 40 '/6" 0.08 lb. 80051 1" 40 3/6" 0.11 lb. No. Size Sch. 1 2 lb. 80025 '/." 40 9/16" 0.09 lb. 80032 1"x'/<" 40 "/,6" '"/,6" 0.16 80026 1" 40 '/ 0.14 lb. 80052 174" 40 3/," 0.20 lb. 80053 172" 80 '/16" 0.31 lb. 80027 1'/4" 40 '/6" 0.21 lb. 80028 1'/z" 80 1'/,6" 0.40 lb. 80054 2" 80 3/," 0.56 lb. 80029 2" 80 11/4" 0.79 lb. 80055 2'/2" 80 '/," 0.89 lb. 80030 2'/2" 80 1'/2" 1.14 lb. 80056 3" 80 1" 1.19 lb. 80031 3" 80 113/76" 1.82 lb. t t i T/O' T/D ii IILINII_ Teehial T'° Reducing mss. Cross Cross T/O 1 I T/O Tro? - T/O si T/O' I T/O' T/O 111111 T/O rt e T/O Wt. Part T/O Wt. Part No. Size Sch. T/O Wt. Pa 80000No. Size'/ Sch.," 40 6/" 0.11 Ib. No. Size Sch. 1 2 lb. 80009 3/4 40 9/16" 0.13 lb. 80001 1" 40 3/4" 0.19 lb. 80015 1"x 3/4" 40 "/16" "/16" 0.28 80010 1" 40 15/,6" 0.23 lb. • 80002 11/4" 40 7/6" 0.26 lb. 80011 174" 40 t5/,6" 0.34 lb. 80003 1'/2" 80 1" 0.51 lb. 80012 11/2" 80 11/,6" 0.67 lb. ' - 80004 2" 80 1'/6" 0.90 lb. 80013 2" 80 13/6" 1.00 lb. 80005 2'/2" 80 19/,6" 1.59 lb. 80014 2'/2" 80 19/,6" 1.91 lb. 80006 3" 80 1"/,6" 2.41 lb. 80008 3" 80 113/,6" 2.89 lb. H� • Iso 9902 T/O T/O -•-•-I T/0 �- • ---- Reducer _. Coupling _, _, Cap • I .r._._. .- Bushing :. . ---- Part No. Size ® T/0 Wt. PartNo. Size Sch. T/O Wt. Part No. Size Sch. T/O Wt. 80200 1"X 3/4" 40 '/,6" 0.04 Ib. 80075 3/4" 40 '/6" 0.07 lb. 80100 3/4" 40 5/,6" 0.04 lb. 80201 1'/4"x 3/4" 40 '/16" 0.11 Ib. 80076 1" 40 1/6" 0.11 lb. 80101 1" 40 3/6" 0.06 lb. 80202 11/4"x 1" 40 5/16" 0.12 lb. 80077 11/4" 40 3/,6" 0.12 lb. 80102 174" 40 '/2" 0.10 lb. 80203 11/2"x 3/4" 80 5/6" 0.16 lb. 80078 11/2" 80 3/16" 0.25 lb. 80103 11/2" 80 5/6" 0.20 lb. 80204 ® 80 '/2" 0.14 lb. 80079 2" 80 3/16" 0.38 lb. 80104 2" 80 5/6" 0.31 lb. 80205 MEE 80 3/6" 0.17 lb. 80080 21/2" 80 3/16" 0.67 lb. 80105 21/2" 80 7/6" 0.58 lb. 80206 2"x 3/4" 80 3/4" 0.27 lb. 80081 3" 80 3/16" 0.91 lb. 80106 3" 80 1" 0.88 lb. 80207 2" x 1" 80 "/,6" 0.26 lb. 80208 2"x 11/4" 80 9/,6" 0.24 lb. I rio 80209 2"x 1'/2" 80 7,6" 0.19 lb. Grooved 80215 2'/2"x 1" 80 115/16" 0.42 lb. Coupling P g I nj 0.0. 80214 21/2"x 11/4" 80 13/4" 0.45 lb. Adapter -1 80213 21/2"x 11/2"Ej 15/a 0.46 lb. 80211 21/2"x 2" 80 19/16" 0.29 lb. I Part No. mirmignimm T/O Wt. Pipe OD 80210 3"x 2" 80 2 3/16" 0.72 lb. ouppopmmi Ia_ was .. -. _1_ I 2 .•1501 80162 2"x 2" Grooved 80 2 5/16" 1.42 lb. 2" (2.375") 1 80163 21/2"x 272" Grooved 80 2 2/16" 2.28 lb. 21/2"(2.875") «! )--• 80164 3"x 3" Grooved 80 21/4" 3.00 lb. 3" (3.500") Reducing TT/0'80168 3"x 76.1mm Grooved 80 21/4" 2.72 Ib. 76.1mm (3.000") Tee iiii._Nill 7 T10' 1111 Tro2 - -.. -Part - _ -;- - _ - - _ T/O'_ - - -Wt. T/O --�ridili g No. Size Sch. 1 2 3 Ib. Female _. 1111111 80132 3/4"X 3/4"x 1" 40 3/4" 3/4" 5/6" 0.14 Adapter 80133 1"x 3/4"x 3/4" 40 '/z" "/,6" 3/4" 0.14 80134 1"x 3/4"x 1" 40 5/6" 3/4" 3/4' 0.17 Part No. Size Sch. T/0 Wt. 80260 1"x 1"x 3/+" 40 3/," 3/," "/,6" 0.16 80142 3/4"x 3/4" NPT 40 5/6" 0.41 lb. 80135 1'/+"x 1"x 3/4" 40 '/,6" 3/," 5/,6" 0.21 80145 1"x 1" NPT 40 3/4" 0.63 lb. 80136 1'/+"x 1"x 1" 40 "/16" 3/+" 15/,6" 0.22 80146 1'/4"x 11/4" NPT 40 7/6" 1.03 lb. 80147 1'/2"x 1'/z" NPT 80 1" 1.42 lb. 80137 1'/+"x 1"x 11/+" 40 13/6" 15/,6" 13/,6" 0.26 80261 11/4"x 11/4"x 3/4" 40 5/6" 5/6" _ 7/6" 0.23 80148 2"x 2" NPT 80 13/6" 2.66 lb. 80262 1'/4"x 1'/4"x 1" 40 3/4" 3/4 '/6" 0.26_ 80138 1'/4"x 174"x 172" 80 1" 1" 1" 0.43 IT/0 80140 172"x 11/4"x 3/4" 80 1/2" 5/6" 1" 0.36 80141 11/2"x 11/4"x 1" 80 1/2" 5/6" 1'/6" 0.38 Male ___________ 80263 11/2"x 172"x 3/ 80 9/16" 9/,6" 1" 0.36 Adapter - _� r--„ 80264 1'/2"x 1'/2"x 1" 80 9/16" 9/,6" - 1" 0.38 80275 11/2"x 11/2"x 1 74" 80 3/4" 3/4" 1" 0.45 Part No. Size Sch. T/O Wt. 80265 2"x 2"x3/4" • 80 3/." _ 3/4" _ 13/6" 0.61 80157 3/4" x 3/4" NPT 40 15/,6" 0.33 lb. 80266 2"x 2"x 1" 80 7/6" 7/6" 13/6" 0.66 80158 1" x 1" NPT 40 13/6" 0-56 lb. 80274 2"x 2"x 1'/4" 80 1" 1" 13/6" 0.74 80267 2"x 2"x 11/2" 80 1'/6" 11/6" 13/6" 0.78 -1-T/O 80271 2'/2"X 2'/2"x 1" 80 111/18" 111/18"" 19/,6" 1.43 80272 21/2"X 272"x 174" 80 111/18" 1"h6" 19/,6" 1.46 Reducing _._ __ 80273 21/2"x 21/2"x 1'/2" 80 111/,6" 1"/,6" 19/,6" 1.48 Coupling ---. 80276 2'/2"x 21/2"x 2" 80 1"/,6" 1"/,6" 19/,6" 1.50 /___ 80270 3"x 3"x 1 72" 80 13/4" 13/4" 173/16" 2.28 Part No. Size Sch. T/0 Wt. 80268 3"x 3"x 2" 80 13/4" 13/ 13/4" 2.25 80220 1" x 3/4" 40 '/6" 0.08 lb. 80269 3"x 3"x 2'/2" 80 13/4" 13/4" 115/,6" 2.44 II T/O T/O Sprinkler Head Adapter _ j"'' Sprinkler Head Adapter with Brass Threaded Insert ��� with Brass Threaded Insert bil Part No. Size 1 Sch. T/O 1 Wt. 1 Part No. Size I.Sch. TIO I Wt. 80175E 3/4"x'/2" NPT 80 716" 0.20 lb. 80175W 1/4'x1/2" NPT 40 718" 0.19 lb. 80176E 1"x '/2" NPT 80 '/,6" 0.22 lb. 80176W 1"x '/2" NPT 40 7/16" 0.18 lb. 80177WL 1/4"x 1/2" NPT 40 9/18" 0.16 lb. 80179 1 x 3/4" NPT 40 3/4" 0.43 lb. T/O' T/O , , Back-to-Back Cross CIiI C ._ Sprinkler Head Adapter with Bras770. s Threaded Insert -: with Brass Threaded Insert III ' T/O' T/O' Part No. Size Sch.i I/O i Wt. Part T/O Wt. 80177L 3/4"x 1/2"NPT 40 '/2" 0.16 Ib. No. Size Sch. 1 2 lb. 80178 1"x '/2' NPT 40 '/z" 0.20 lb. 80462 1"x 1"x '/2"NPT x 72"NPT 40 5/e" 1'/e" 0.46 80463 1"x 1"x1/2" NPT x '/2"NPT 40 5/e" 15/16" 0.47 ------ T/O' iiriiiii1 r 90 Elbow amit with Brass Threaded Insert Back-to-Back Tee Tro' :1 ti AM� _ I h' h� rm with Brass Threaded Insert i —""^► _=I-�• 'rte;a,1 _.- Tro' Tro' Part I T/O I Wt. Part Size Sch. T/O Wt. if No. Size Sch. 1 2 lb. No. 1 2 lb. E` 80199 3/4"x 1/2"NPT 40 5/e" 75/16" 0.20 80459 1"x'/2"NPT x'!2"NPT 40 11/16" 15/16" 0.48 k 80189 1"x 72" NPT 40 13/16" 13/16" 0.26 80460 1"x'/2"NPT x1/2"NPT 40 "/16" 11/9" 0.46 Part T/O Wt. No. Size Sch. 2 Ib. 80250 3/4"x1/4"x 1/2"NPT 40 5/18" 5/6" 13" 0.22 80251 1"X 1"X'/2"NPT 40 11/1e" "/,5" 13/16" 0.29 80249 1"x 1"x 1"NPT 40 15/,6" 15/,6" 17 /,s" 0.73 Sprinkler Head Adapter !! Trc' 80256 11/4"x 1"x'/2"NPT 40 7/,e" 9I,s" 1'/e" 0.30 Tee ----t 80252 11/4"x 11/4"X '/2" NPT 40 7/,e" 7/16" 1'/e" 0.31 with Brass Threaded Insert - - 80257 172"X 11/4"X 1/2" NPT 80 9/16" 5/6" 17/16" 0.43 T/o' I T/O' 80254 11/2"x 1'/2"X '/2" NPT 80 9/,e" 9/,6" 1'h6" 0.46 80258 2"x 11/2"X'/2"NPT 80 '/2" 5/e" 15/6" 0.56 80253 2"x 2"x 72"NPT 80 72" '/2" 15/s" 0.62 Limited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten(10)years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten(10)years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse,improper installation,corrosion,or which have not been installed,maintained,modified or repaired in accordance with applicable Standards of the National Fire Protection Association(NFPA),and/or the standards of any other Authorities Having Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced.at Tyco Fire Products sole option. Tyco Fire Products neither assumes,nor authorizes any person to assume for it,any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or - incomplete information supplied by Buyer or Buyer's representatives. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE,IN CONTRACT,TORT,STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY,FOR INCIDENTAL,INDIRECT,SPECIAL OR CONSEQUENTIAL DAMAGES,INCLUDING BUT NOT LIMITED TO LABOR , CHARGES,REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCT'S LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. s% THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES}DRESS OR IMPLIED,INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, tLlCO/Flo�v Control IP Tyco Fire roducts k • 0® vs R.D = ® VANE TYPE WATERFLOW APPROVED SWITCH WITH RETARD Potter Electric Signal Company 2081 Craig Rd., / St. Louis, MO 63146 / (800)325-3936 / (314)878-4321 SERVICE PRESSURE UP TO 450 PSI CHARACTERISTICS FOR 2" TO 8" PIPE SIZES 250 PSI FOR 10" PIPE SIZE U.L. LISTED AND F.M. APPROVED MINIMUM FLOW RATE FOR ALARM-10 GPM DIMENSIONS & WEIGHTS: See Fig. 2 ENCLOSURE: Cast Aluminum Finished: Red Enamel CONTACT RATINGS: Two sets of S.P.D.T. (Form C) 15.00 Amp. @ 125/250V. AC 0.50 Amp. @ 125V. DC 0.25 Amp. @ 250V. DC 2.50 Amp. @ 0-30V. DC Resistive ENVIRONMENTAL LIMITATIONS: 40°F/120°F 4.5°C/49°C f -Carceral-Purpose-forIndoor-Use " -. CAUTION: This device is not intended for applications outdoors or in explosive environments. SIZES AVAILABLE: U.L. - For Schedule 40 Pipe: 2" thru 10" For Schedule 30 Pipe: 8" _ F.M.-- For Schedule 40 Pipe:2" thru 6" For Schedule 30 Pipe: 8" and 10" SERVICE USE: Automatic Sprinkler NFPA-13 One or Two Family Dwelling NFPA-13D Central Station NFPA-71 Local NFPA-72A Auxiliary NFPA-72B Remote Station NFPA-72C Proprietary NFPA-72D U.S. Pit. Nos. 3,612,247 OPTIONAL: Cover Tamper Switch 4,062,371 Order Stk. No. 5420220 The Model VSR-D is a vane type waterflow switch for The flow condition must exist for a period of time necessary use on wet sprinkler systems.It is UL Listed for use on to overcome the selected retard period. steel pipe;schedule 40 sizes 2"thru 10"and schedule 30 size 8"and has FM approvals for schedule 40 steel ENCLOSURE:The unit is enclosed in a general purpose, indoor use, cast aluminum housing. The cover is held in pipe in sizes 2" thru 6" and schedule 30 pipe in sizes 8" and 10". place with two tamper resistant screws which require a spe- cial key for removal.A field installable cover tamper switch is available as an option which may be used to indicate The unit may also be used as a sectional waterflow detector on large systems. unauthorized removal of the cover. See Bulletin 751 for installation instructions of this switch. The unit contains two single pole, double throw, snap RETARD ADJUSTMENT: The unit has an adjustable action switches and an adjustable pneumatic retard. pneumatic retard The switches are actuated when a flow of 10 gallons surges.The retard soalarms adjustableto from 0 due to water per minute or more occurs downstream of the device. seconds. approximately 75 2-88 CAT.#A010 PAGE 1 , P - POTTER VS Rot Potter Electric Signal Company 2081 Craig Rd., / P.O.Box 28480 / St. Louis, MO 63146 / FAX:314 878 7264 VSR-D INSTALLATION FACTORY ADJUSTED FIG. 1 SENSITIVITY SPRING. DO NOT ADJUST RETARD ADJUSTMENT TO CHANGE TIME TURN KNOB ' (EITHER DIRECTION)FOR I DESIRED TIME DELAY. TIGHTEN NUTS USE THE MINIMUM AMOUNT ' / ALTERNATELY TO AN OF RETARD NECESSARY TO �.` 'I EVENTUAL PREVENT FALSE ALARMS, 50 FTTOR.—ii LRS.PIPE 50 OF A 'B'SETTING IS USUALLY ADEQUATE FOR THIS. �� I MOUNT ON ARROW ON SADDLE POINTS IN DIRECTION OF WATERFLOW, ROLL PADDLE IN TO INSTALL. , / OPPOSITE DIRECTION FOR 2.AND 2 V2"SIZES O OF WATER FLOW, DRILL I I/4-HOLE. FOR ALLHOL SIZES DRILL 2--HOLE APPROX. RETARD SETTING ON SEC.) ll�ll�lllf OPTIONAL: Cores Tainper Swheh Ondtr Stk. No.54201220 u� DIRECTION OF � � WATERFLO� DWG.5400710-30B SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL CAUTION: AN UNINSULATED SECTION OF A SINGLE CONDUCTOR IS NOT PERMIT- TED ERMITTED TO BE LOOPED AROUND THE TERMINAL AND SERVE AS TWO SEPARATE CONNECTIONS.THE WIRE MUST BE SEVERED TO SERVE /NC°MjNG AS TWO SEPARATE CONNECTIONS,THEREBY PROVIDING SUPERVI- SION OF THE CONNECTION IN THE EVENT THAT THE WIRE BECOMES DISLODGED FROM UNDER TERMINAL. /NGi' DWG.5400710-31 OUTGO INSTALLATION INSTRUCTIONS: These devices may Clean the inside of the pipe of all growth or other mate- be mounted in a horizontal or vertical pipe. On horizon- rial for a distance equal to the pipe diameter on either tal pipe they should be installed on the top side of the side of the hole. pipe where they will be accessible.The units should not Roll the vane so that it may be inserted into the hole;do be installed within 6 inches of a fitting which changes the not bend or crease it. Insert the vane so that the arrow direction of the waterflow or within 24 inches of a valve on the saddle points in the direction of the waterflow. or drain. Install the saddle strap and tighten nuts alternately to an _Drain the system and drill a hole in the pipe using a cir- eventual 50 FT-LBS. of torque. See Fig. 1 above. cular saw in a slow speed drill.The 2"and 21/2"devices The vane must not rub the inside of the pipe or bind in require a 11/4" hole; all other sizes require a 2" hole. any way. TESTING The frequency of testing for the model VSR-D and its associated protective monitoring system should be in accordance with applicable NFPA Standards and/or the authority having jurisdiction,but under no circumstances less than bi-monthly. . CAT. #A010 PAGE 2 2-8B TESTANDRAI y „,- alu it 'd �s 1� �2 4i n xri7 , 'Muw§P a ui Jud Ff fil m7 � i k + f'21't*^r 75'ii�`It+1;ra rr arw,, c A �� Cit R�['v "R h Ill i r ,t� frt ��1,fjtlj !{tr..b`� �tttr5�� r—• Y�Iy �511'a �, I"��u 1fSI 4i's5j, fr r�a, c Fea���(a a� tz }o �a�2 �� z off- k A fir, � A 4wry fn lrir� q _ l ' J a�41ir �IN, rT �, Of ifE c, fF 32 eu[=.- et � �t��S�ifBt P Ca 3 �> a i i'��4� ig S,�i a 1 1 d,,44,,,,V” d J.L.d�.Prt llo.4.l a.:�Vi,97z at � Pn4 'l rt j.t 2 ,,,,�4 .J I r tS�i of ,7 ll� . , l ' rt ' =i I f ■ The AGF Manufacturing Co., Inc. Model 1000 has been designed to provide both the Test Function and the Express Drain Function in amulti story installation. • Complies with all requirements of NFPA-T 3, and NFPA-13R • Complies with all requirements of NFPA-13D (HOUSING) • Positive Shut Off 2 Single Locking Handle • Tapped '/z" for Pressure Gauge • Tamper Resistant Orifice permanently installed • Available with all required Orifices __ • Orifice size noted on Indicator Plate • Lightweight and compact (11/4" weighs 5 lbs.) • 300 PSI Rating • Fused, tempered, tamper resistant Sight Glasses MODEL 1000 300 PSI AF_ TEsTANDRAIR *'h"NOT FM APPROVED PLAN VIEW FRONT VIEW A I 1 FROM BRANCH GAUGE OUTLET , riga) PROVIDED .! � Ina �� TO DRAIN D EI 1 ..,�� �� . OFF 1 i CD . 40 IDRAIN Nom STREET EL ) ] _.... i.ea ` _.._.T_ -• �i 7x1.r. 41. ..,_ • _. 1 I1. • - ®' .erg -. -ET-E _. TO--DRAIN. OR PIPE I E I r is=s1 TO DRAIN --70,1Willailliiii���� � IIII ® _ _ _ FOR RIGHT HAND/STRAIGHT INSTALLATION _. - I o o - �i III■TO DgAIN IIII o o MI APPROVALS D \ II • UL and ULC Listed fl' ■ FM Approved except 3/4" U • NYC BD. of S&A CAL. NO. 720-87-SM • CA. State Fire Marshall ORIFICE SIZE PROVIDED—3/3-7,/,6—1h—t 732_508*'E—3/4** DIMENSIONS—INCHES MATERIAL LIST SIZE A BCDEFGH PART MATERIAL 3/4 5I/16 13/4 23/e 4'/e 33/a 13/4 49/16 65/16 HANDLE STEEL STEM ROD BRASS I 5'/16 13/4 23/e 4'/s 33/8 13/4 49/16 65/16 BALL C.P. BRONZE I1/4 "57/16 I3/4 27/e 45/e 35/16 115/16 51/2 77/16 BODY BRONZE VALVE SEAT GLASS INPREGNATED TEFLON 1 '/2 67/16 13/4 3"/16 57/16 31/2 23/e 81/I6 107/6 INDICATOR PLATE STEEL 2 67/16 13/4 3"/16 57/16 3'/2 23/e 18I/,6 107/16 HANDLE LOCK SPRING STEEL SIGHT GLASS (2) FUSED TEMPERED GLASS ** Available on 11/4"to 2"size units only. AGF MFG. CO. JOB NAME: 1 Box 4437, 150 Mt. Bethel Rd. ARCHITECT: Warren, N.J. 07059-0437 MADE IN U.Sli. Telephone (908) 604-6471 ENGINEER: Fax (908) 604-6501 CONTRACTOR: 1000 8/94 10 . ( TOLCO INCORPORATED CORONA,CA (909)737-5599 1 0 C ® Fig. 27 & 27A "Stand-Off" Hanger/Restrainer for CPVC Plastic Pipe Size Range—3/4" & 1" CPVC Plastic Pipe*. Material— Carbon Steel, Pre-Galvanized. _ Function—Designed to be used as a hanger/restrainer**for CPVC piping where the "stand-off'design will ease installation by eliminating the need for .',. wood blocking. i Features: /• ` • Flared edge design protects CPVC from any rough or abrasive surfaces. • Snap-in retainers hold pipe firmly in place during installation. ( '' • The "Stand-Off' design eliminates the need for wood block extension. • Can be installed on horizontal or vertical piping regardless of mounting Fig. 27 surface orientation. --..., furnls es with product. • Installs easily using rechargeable electrical driver with 5/16" sockets, o eliminating impact tool damage to pipe Approvals- Underwriters Laboratories Listed in the U.S. (UL) and Canada 0 .-- „ (cUL) to support automatic fire sprinkler systems. Meets and exceeds the ( ::;requirements of NFPA 13, 13R, and 13D. Fig. 27A **Important Note—When installed in slot openingon Fig. 27, Fig 27A ` A - provides - q i G �\ i additional stabilityand satisfies the UL vertical restraint requirement • where needed. \' Order By—Fig. 27: By figure number and CPVC pipe size. Fig. 27A: By figure number and CPVC pipe size. �� ) U.S. and International Patent application in process. � � *for other sizes consult factory. Fig. 27 and Fig. 27/27A have also been tested by U.L. mounted on 3/8" Fig. 27/Fig. 27A composite wood web material (such as TJI Series/Trus Joist MacMillan) Combination without the use of back up wood blocking. When using Fig. 27 &27A in combination on 3/8"web to satisfy the UL requirement for vertical restraint, FIG.27 install 2 reinforcing speed nuts (Fig. 27B). Fig. 276 is UL Listed on/v when. f W/FIG.27A used with Tolco products. FIG.27B FIG.27 1 Oft W/FIG.27A MO -1 ��u i � 4eIF FIG.27I FIG.27 FIG.27 FIG.27 W/FIG.27A FIG.27 40 IIII: :■ irP :.. : fill Typical Applications 2 CSA 20006 r.. - . .. .. . . .. .. . . • '. : . .. . . .. . . . : . Series 2000E l (� 1 7y� - :.- _ .. AME S Double Check Valve Assemblies FIRE&WATERWORKS Sizes: 1i`z" —2" (15—60mm) i . 4 3' F Features - 15 • Ease of maintenance with only one cover 2"20008 HC • Top entry (50mm) • Replaceable seats and seat discs ,� • Modular construction • Compact design , m. •--'/2 21' (15 50mm)Cast bronze body construction /a,: 20008 Top mounted ball valve test cocks (2Qmm) • Low pressure.drop - No special tools rcquircd __________Sen 20011H I)rnihlP Lbeck..VaLve.AssembUesshall be installed at referenced-crosscon-- • 1/z"-1" (15-25 mm)have nections to prevent the backflow of polluted water into the potable water supply. Only tee handles those cross-connections identified by local inspection authorities as non-health hazard shall be allowed the use of an approved double check valve assembly. Check with local authority having jurisdiction regarding vertical orientation,frequency of Available Models testing or other installation requirements. '' Suffix: These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are B—Quarter_turn.ball_valves_— _approv_ed by_the_Foufdation for Cross_Connection_Control and_Hydraulic_Researcb_at the LBV- less ball valves -University of Southern California. LH- locking handle ball valves(open S ecifieations position) p SH- stainless steel ball valve handles A Double Check Valve Assembly shall be installed at each noted location.The assembly HC- 21/2"inlet/outlet fire hydrant fitting shall consist of two positive seating check modules with captured springs and rubber seat (2" valve) discs.The check module seats and seat discs shall be replaceable.Service of all internal Prefix: components shall be through a single access cover secured with stainless steel bolts.The U union connections assembly shall also include two resilient seated isolation valves and four top mounted, re- silient seated test cocks.The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std.C510.Approved by the Foundation for Cross-Connection Control and Pressure — TemTemperature Hydraulic Research at the University of Southern California.Assembly shall be an Ames p Company Series 2000B Temperature Range:33°F-140°F (5°C-60°C) Approvals Maximum Working Pressure: 175psi t ASSE, IAPMO,CSA,UPC (12 bars) 4. Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Standards • Model LBV is not listed. ASSE Std. 1015,AWWA Std. C510 u UL Classified(LBV models only)3/4"-2"(19-50mm) ® �+ . „ I ‘,„, , IAPMO PS31, CSA B64.5 * Horizontal and vertical "flow up"approval on all sizes. SP o tli7 i Job Name Contractor Job Location Approval Engineer Contractor's P.O. No. _ Approval Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.com Dimensions - Weights bilk .... IX* .... 7Df lel='_ lk ■_ 1 _ III �. B ���,1 • ®wi r� 1_®,11 F - H -� 4--I G Suffix HC-Fire Hydrant Fittings dimension "A"=231/2"(594mm) Dimensions Size(DN) A B C F 9 H I Weight Model in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm ibs. kgs. 2000B 1/2 15 10 254 4% 117 Ns 62 5 127 33/a 85 25/s 59 2'/s 52 4.5 2 2000B M3 3/a 20 111/ 282 4 102 3% 79 63A6 157 3%s 87 21/2 54 1%6 33 5 2.3 20008 1 25 131/2 337 51s 130 4 102 71 191 33/s 85 1t1A6 43 171/26 43 12 5A 2000B 11/2 32 16% 416 5 127 3%s 84 912 241 5 127 3 76 2 50 15 6.8 20006 11 40 16% 425 41/2 124 31 89 9% 248 513/s 148 3% 79 271A6 68 15.86 7.2 20008 2 50 191/2 495 61/2 159 4 102 13%s 340 61/2 156 37A6 87 21%6 68 25.75 11.7 Strainer sold separately Capacities bars psi 11/4"(32mm) ----- -- -- - --- c rnm rlPd frorrrdor maant®r-F inclitrojfirj',ri3s•Cen��e�ti,n-GLi iG ui -- 1 14 and_I-Lydrauhc..Besearch.at-the University-of-Southern Galifornia-lab-tests. y 8--12 Mme.=®®: = - � o .7 10 IM11•1 1111•11•11•111111111111•11�1111 *Typical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.) '� .5 8 ■■■"�.■�.� d barspsi /A"( ) a) .4 6 _.-__.., , '4 .8 2 15mm * d .3 4 ���� o .7 10 � .1 2 .5 8.4 6 n 0 0 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm -r-.,,t • y .3 4 0 38 76 114 152 190 228 266 304 342 380 418 456 Im ! 1w+ a °� p 5 7.5 _1015 t1c,;, - fps ---- -= �P 0 2 4 6 8 10 12 gpm -1.5-2.3.--31)---4.s - mps , 0 7.6 15.2 22.8 30.4 38 45.6 1pm Flow Rate 5 7.5 10 fps bars psi 11/2"(40mm) 34" 1.5 2.3 3.0 mps H .8 12 bars psi (20mm) Flow Rate o .7 10 w f '.........----b............... 1.5 22 * J m .5 B 3 1.2 18 w .4 6 12 .96 14 .3 4 y .69 10 1117 .1 2 . .41 6 SPO 38 76 114 152 190 228 266 304 342 380 418 456 pm n10 20 30 40 50 60 70 80 90 100 110 120 .14 2 5 7.5 10 15 fps OP 0 5 10 15 20 25 30 35 40 45 50 gpm 1.5 2.3 3.0 4.6 mps 0 19 38 57 76 95 114 133 152 111 190 fpm Flow Rate 7.5 15 2.3 4.6 mps bars psi 2"(50mm) bars psi 1" 25mm * Flow Rate N 6 12 N 1.1 16 ( ) c 7 10 J .8 12 ami 5 8 0 .7 10 0 .4 6 ��� § .5 8 f y .3 4 eem .4 6 j ,_ ,1 2 .3 4 _J a` 0 0 D. .1 2 0 25 50 75 100 125 150 175 200 gpm AP 0 95 190 285 380 475 570 665 760 1pm AP 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm 5 7.5 10 15 fps 0 19 38 57 76 95 114 133 152 171 190 209 228 fpm 1.5 2.3 3.0 4.6 mps 5 7.5 10 15 fps Flow Rate 1.5 2.3 3.0 4.6 mps Flow Rate . IMPORTANT Inquire with governing authorities for .A. local installation requirements. A M E S ISO 9001 FIRE&WATERWORKS A Division of Watts Industries www.amesfirewater.com CERTIFIED 875 National Drive • Suite #107 • Sacramento, CA 95834 • Phone: 916-928-0123 • Fax: 916-928-9333 ES-A-2000B 0313 ©Ames Co.2003 Printed in U.S.A.