Loading...
Report x 5,2_0/2 20O a 4i SPRINKLER SYSTEM HYDRAULIC ANALYSIS /04-1575- b'Page (ilk) ,°/4t DATE: 4/27/2012 ek JOB TITLE: Arlington Heights Lot #115 WATER SUPPLY DATA REECifilttED SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ' D NODE PRESS . PRESS . @ PRESS. @ DEMAND PRESS.R ' ® ` � TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) C ITYOFTiGARD 8 118 . 0 54 . 0 1230. 0 117 . 9 27. 0 87 . 3 AGGREGATE FLOW ANALYSIS : TOTAL FLOW AT SOURCE 27 . 0 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0 . 0 GPM OTHER HOSE STREAM ALLOWANCES 0 . 0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 27 . 0 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) 1 -1 . 0 K= 4 . 90 7 . 0 13. 0 2 -1 . 0 K= 4 . 90 8 . 2 14. 1 3 -0 . 5 - - - - 28. 8 - - - 4 19 . 0 - - - 56. 6 - - 5 8 . 0 - - - - 66. 6 - - - 6 1 . 0 - - - - --- -- 71-_-0 -- - __ --- -- --- 7-5. 0 -- 8 0 . 0 SOURCE 87 . 3 27. 0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 4/27/2012 C: \HASS74\ARLTNnTON1_ -SDF JOB TITLE: Arlington Heights Lot #115 PIPE DATA - PIPE TAG Q (GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL (FPS) HW (C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI) Pipe: 1 -13 . 0 0 . 874 PL 10.00 PF 1 . 2 1 -1 . 0 4 . 9 7 . 0 13 . 0 6. 9 150 FTG T PE 0 . 0 2 -1 . 0 4 . 9 8 . 2 14 . 1 0 . 094 TL 13.11 PV Pipe: 2 -27 . 0 0 . 874 PL 39. 00 PF 20 . 8 2 -1 . 0 4 . 9 8 . 2 14 . 1 14 . 4 150 FTG 2E5T PE -0 . 2 3 -0 . 5 0 . 0 28 . 8 0. 0 0 . 365 TL 57. 02 PV Pipe: 3 -27 . 0 0 . 874 PL 73.50 PF 36. 2 3 -0 . 5 0 . 0 28 . 8 0. 0 14 . 4 150 FTG 3E7T PE -8 . 4 4 19. 0 0 . 0 56. 6 0. 0 0 . 365 TL 98 . 97 PV Pipe: 4 -27. 0 0 . 874 PL 12. 00 PF 5 . 3 4 19 . 0 0 . 0 56. 6 0. 0 14 . 4 150 FTG 2E PE 4 . 8 5 8 . 0 0 . 0 66. 6 0. 0 0 . 365 TL 14. 49 PV Pipe: 5 -27 . 0 1 . 080 PL 7. 00 PF 1 . 4 5 8 . 0 0 . 0 66. 6 0. 0 9. 5 120 FTG ---- PE 3 . 0 6 1 . 0 0 . 0 71 . 0 0 . 0 0 . 197 TL 7 . 00 PV Pipe: 6 FIXED PRESSURE LOSS DEVICE 7 1 . 0 0 . 0 75 . 0 0. 0 4 . 0 psi, 27 . 0 gpm 6 - - -- 4. 0 0 . 0 = 71--.-0_ -= 0 . 1e- --_-_ -- Pipe: 7 -27 . 0 1 . 101 PL 100. 00 PF 11 . 8 7 1 . 0 0 . 0 75 . 0 0 . 0 9. 1 150 FTG ---- PE 0 . 4 8 0 . 0 SRCE 87 . 3 (N/A) 0. 118 TL 100. 00 PV NOTES: (1) Calculations were performed by the HASS 7 . 4 computer program under license no. 5010113212 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0. 013 gpm and a maximum imbalance at any node of 0 . 092 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 14 . 4 ft/sec at pipe 4 . (4) PIPE FITTINGS TABLE Pipe Table Name: STANDARD. PIP SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 4/27/2012 . JOB TITLE: Arlington Heights Lot #115 • PAGE: * MATERIAL: S40 HWC: 120 Diameter Equivalent Fitting Lengths in Feet ( in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee 0 . 874 0 . 82 2 . 06 0. 82 2 . 06 2 . 47 0 . 41 4 . 11 4 . 11 2 . 06 1 . 080 2 . 30 5 . 76 2. 30 5 . 76 6. 91 1 . 15 11 . 52 11. 52 5 . 76 1 .101 2 . 53 6. 33 2 . 53 6. 33 7 . 59 1 . 27 12 . 66 12 . 66 6. 33 y d O > W H WATER SUPPLY ANALYSIS m 140. 0 y '• Static: 118.00 psi Resid: 54. 00 psi Flow: 1230. 0 gpm y ..L. r --. LEGEND m N N 1 Available pressure H H 1 117. 95 psi @ 27.0 gpm ' N G112. 0 2 Required pressure Q A 87.31 psi @ 27.0 gpm o , U x b G I m E F'• H Lc) � �+ c P2 R 840. P' r+ E rt S y S H m U cn , R C d E 56. 0 ti ( • H p n n z s i .ter x1-c 28 .0 p ' :,ten H I :n to A 1 i II. to 1ill I E0.0 il Q -14 .7 co I I I I I f i I ',I ,r, 400 600 800 1000 1200 1400 1600 1800 2000 FLCW (GPM) tqco /Fire & Building Products trapi7r:sponse Technical Services:Tel: (800)381-9312/Fax: (800)791-5500 HOME FILER SYSTEM Series LFII Residential Horizontal Sidewall Sprinklers 4.2 K-factor General adjustment or up to 1/2 inch(12,7 mm) of total adjustment from the flush mounting surface position.The adjust- Description ment provided by the Recessed Es- cutcheon cutcheon reduces the accuracy to The Series LFII (TY1334) Residential which the pipe nipples to the sprinklers Horizontal Sidewall Sprinklers are must be cut. r> decorative, fast response, frangible bulb sprinklers designed for use in The Series LFII (TY1334) has been residential occupancies such as designed with heat sensitivity and3. homes, apartments, dormitories, andwater distribution characteristics hotels.When aesthetics and optimized proven to help in the control of residen- 3 es flow characteristics are the major con -_ improve the chance for sideration, the Series LFII (TY1334) occupants to escape or be evacuated. — tit�l tial firand to should be the first choice._ a The serifs LFji are lode cise�7n wef RNINUS pipe residential sprinkler systems for FII(TY1334 Y The Series LFII(TY1334)Residential one-and two-family dwellings and mo- Horizontal Sidewall Sprinklers de- bile homes per NFPA 13D; wet pipe scribed herein must be installed and - residential sprinkler systems for resi- maintained in compliance with this dential occupancies up to and includ- document, as well as with thea bca- ing four stories in height per NFPA ble standards of the National FirepPro- 13R;or, wet pipe sprinkler systems for tection Association, in addition to the � the residential portions of any occu- standards of any other authorities hav- pancy per NFPA 13. ing jurisdiction. Failure to do so mayAI° �� The Series LFII (TY1334) has a 4.2 � impair the performance of these de- � � , � :�E" � -t . . (60,5) K-factor that provides the re- vices, quired residential flow rates at reduced The owner is responsible for maintain- pressures,enabling smaller pipe sizes ing their fire protection system and de- and water supply requirements. vices in proper operating condition. , The recessed version of the Series The installing contractor or sprinkler LFII (TY1334) is intended for use in manufacturer should be contacted areas with finished walls. It employs a with any questions. two-piece Style 20 Recessed Escutch- eon. The Recessed Escutcheon pro- vides 1/4 inch (6,4 mm) of recessed Sprinkler/Model Identification IMPORTANT /�/umber Always refer to Technical Data /Y Sheet TFP700 for the "INSTALLER SIN TY1334 WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 JANUARY, 2006 TFP410 Page 2 of 8 TFP4IO Components: 5 3 2 1 1 - Frame WRENCH 2- Button Assembly gia►►�'� I 3- Sealing Assembly -� ��:;�� FLATS 4- Bulb Oo ���1�� IR 5- Compression Screw _ ` ��1,��► 6 Deflector* TOP-OF- 6* 4 7/16" 11,1 mm '? DEFLECTOR NOMINAL ) . 1111111111 2-7/8"DIA. *Temperature rating MAKE-IN t (73,0 mm) is indicated on top \ a�� ! �� of Deflector. Ni--- "� I n - CENTERLINE 7/16" ) /_ OF WATERWAY (11,1 mm) aNN_ STYLE 20 1/2"NPT RECESSED 1-5/8" ESCUTCHEON END-OF- (41,3 mm) ESCUTCHEON DEFLECTOR 2-1/4" I PLATE SEATING BOSS (57,2 mm) SURFACE RECESSED FIGURE 1 SERIES LFII(TY1334)RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS y7/16±1/8" cc..-.1 (11,1±3,2 mm) MOUNTING FACE OF WRENCH RECESS__— ___--_ SURFACE SPRINKLER (END"A"USED FITTING ^ FOR TY1334) CLOSURE R\ L1//,/ DEFLECTOR FIGURE 3 \ W--TYPETY1334 6 SPRINKLER WRENCH --1/- I 2-7/8"DIA. (73,0 mm) WRENCH !Int 2-1/4"DIA. RECESS 7/16" I a1P. (57,2 mm) (11,1 mm) I itfi k MOUNTING PLATE END-OF- C� DEFLECTOR L'• 1/8" BOSS (3,2 mm) PUSH WRENCH IN TO ENSURE 1-3/8"(34,9 mm) 1/2"(12,7 mm) ENGAGEMENT 1-1/8"(28,6 mm) 1/4"(6,4 mm) WITH SPRINKLER WRENCHING AREA FIGURE 2 FIGURE 4 STYLE 20 RECESSED ESCUTCHEON 7 RECESSED FOR USE WITH THE SERIES LFII(TY1334) SPRINKLER WRENCH RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER • , TFP410 Page 3 of 8 Technical total number of"design sprinklers"as Do not attempt to compensate for in- specified in NFPA 13D or NFPA 13R. sufficient adjustment in an Escutcheon Data For systems designed to NFPA 13,the Plate by under-or over-tightening the number of design sprinklers is to be Sprinkler. Readjust the position of the Approvals: the four most hydraulically demanding sprinkler fitting to suit. UL and C-UL Listed. NYC Approved sprinklers.The minimum required dis- The Series LFII Horizontal Sidewall under MEA 44-03-E. charge from each of the four sprinklers Sprinklers must be installed in ac- is to be the greater of the following: cordance with the following instruc- Maximum Working Pressure: tions. 175 psi (12,1 bar) • The flow rates given in Tables A, B, Discharge C, and D for NFPA 13D and 13R as Step 1. Horizontal sidewall sprinklers K=4.2 Ge Coefficient:( LPM/bar1�2) a function of temperature rating and are to be installed in the horizontal the maximum allowable coverage position with their centerline of water- Temperature Rating: area. way perpendicular to the back wall and 155°F/68°C or 175°F/79°C • A minimum discharge of 0.1 gpm/sq. onn the eDeflectol to the riis tto facet wards the Finishes: ft. over the"design area"comprised ceiling with the front edge of the De- White Polyester Coated, of the four most hydraulically de- flector parallel to the ceiling. Chrome Plated, or Natural Brass mantling sprinklers for the actual coverage areas being protected by Step 2. With pipe thread sealant ap- Physical Characteristics: the four sprinklers. plied to the pipe threads, hand tighten Frame Brass Obstruction To Water Distribution. the sprinkler into the sprinkler fitting. Button Bronze Locations of sprinklers are to be in Step3. Tighten the sprinkler into the Sealing Assembly p 9 P Beryllium Nickel w/Teflont accordance with the obstruction rules sprinkler fitting using only the W-Type Bulb 3 mm dia. Glass of NFPA 13 for residential sprinklers. 6 Sprinkler Wrench (Ref. Figure 3). Compression Screw Bronze Operational Sensitivity. The sprin- With reference to Figure 1,the W-Type Deflector Copper klers are to be installed with an end-of- 6 Sprinkler Wrench is to be applied to the wrench flats. deflector-boss to wall distance of 1- -1-Dupont Registered Trademark 3/8 to 6 inches or in the recessed po- The Series LFII Recessed Horizontal ---sition-using-only-the-Style-20 Re------Sidewah Sprinklers-musttiemstatled- Opin- Figure -- eration cessed Escutcheon as shown in in accordance with the following in- /" Figure 2. structions. The glass Bulb contains a fluid that In addition the top-of-deflector-to-ceil- Step A. Recessed horizontal sidewall expands when exposed to heat.When ing distance is to be within the range sprinklers are to be installed in the the rated temperature is reached, the (Ref. Table A, B, C, or.D)_being hy- horizontal position with their centerline fluid expands sufficiently to shatter the draulically calculated. of waterway perpendicular to the back glass Bulb allowing the sprinkler toSprinkler Spacing. The minimum wall and parallel to the ceiling. The activate and flow water, word"TOP"on the Deflector is to face spacing between sprinklers is 8 feet towards the ceiling. • (2,4 m). The maximum spacing be- Design tween sprinklers cannot exceed the Step B. After installing the Style 20 width of the coverage area(Ref.Table Mounting Plate over the sprinkler Criteria A)being hydraulically calculated(e.g., threads and with pipe thread sealant maximum 12 feet for a 12 ft. x 12 ft applied to the pipe threads, hand The Series LFII (TY1334) Residential coverage area,or 16 feet for a 16 ft.x tighten the sprinkler into the sprinkler Horizontal Sidewall Sprinklers are UL 20 ft. coverage area). fitting. and C-UL Listed for installation in ac- Step C. Tighten the sprinkler into the cordance with the following criteria. Installation sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. NOTE The Series LFII (TY1334) must be in Figure 4). With reference to Figure 1, When conditions exist that are outside stalled in accordance with the follow the W-Type 7 Recessed Sprinkler the scope of the provided criteria,refer ing instructions: Wrench is to be applied to the sprinkler to the Residential Sprinkler Design NOTES wrench flats. Guide TFP490 for the manufacturer's Do not install anybulbtype sprinkler if recommendations that may be accept- p Step C. After the wall has been in- able to the local Authority Having Ju- the bulb is cracked or there is a loss of stalled or the finish coat has been ap- isdiction. liquid from the bulb. With the sprinkler plied, slide on the Style 20 Closure held horizontally, a small air bubble- over the Series LFII Sprinkler and System Type. Only wet pipe systems should be present. The diameter of the push the Closure over the Mounting may be utilized, air bubble is approximately 1/16 inch Plate until its flange comes in contact Hydraulic Design. The minimum re (1,6 mm). with the wall. quired sprinkler flow rate for systems A leak tight 1/2 inch NPT sprinklerjoint designed to NFPA 13D or NFPA 13R should be obtained with a torque of 7 are given in Table A, B, C, and D as a to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- function of temperature rating and the mum of21 ft.lbs. (28,5 Nm) of torque maximum allowable coverage areas. is to be used to install sprinklers. The sprinkler flow rate is the minimum Higher levels of torque may distort the required discharge from each of the sprinkler inlet with consequent leak- age or impairment of the sprinkler. • (Continued on Page 8) i Page 4 of 8 TFP410 IN- ELEVATION Maximum Maximum Coverage Spacing Minimum flow-(c)and-Residual-Pressure Area(a) Ft. Width x Length(b) (m) Top-Of-Deflector-To-Ceiling: Top-Of-Deflector-To-Ceiling: Ft.x Ft. 4 to 6 Inches(100 to 150 mm) 6 to 12 Inches(150 to 300 mm) (mxm) 155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C 12 x 12 12 12 GPM(45,4 LPM) 12 GPM(45,4 LPM) 13 GPM(49,2 LPM) 13 GPM(49,2 LPM) a _: :_. -_ : psr.o = psi-( 66 • • • TFP410 Page5of8 12" 8" MAXIMUM ELEVATION Minimum-Flow(c)and Residual-Pressure (I)Two sprinkler design with the sprinklers at the high point of the slope and positioned to discharge down the slope. Maximum Maximum Coverage Spacing Area(a) Ft. - Width x Length(b) (m) Ft.x Ft. Top-Of-Deflector-To-Ceiling: Top-Of-Deflector-To-Ceiling: - __ _._( m=----- 4 to 6 Inches-(nn to-15¢mm�-- a+^+ lt}ches 54Lta39D.nun). ._155 F/68°C 175 F/79°C _155 F/68'C 175 F17 °__,._ 12 x 12 12 I 12 GPM(45,4 LPM) I 12 GPM(45,4 LPM) I 13 GPM(49,2 LPM) I 13 GPM(49,2 LPM) (3,7 x 3,7) (3,7) 8.2 psi(0,57 bar) 8.2 psi(0,57 bar) 9.6 psi(0,66 bar) 9.6 psi(0,66 bar) 14 x 14 14 I 14 GPM(53,0 LPM) I 14 GPM(53,0 LPM) I 17 GPM(64.3 LPM) I 17 GPM(64.3 LPM) (4,3 x 4,3) (4,3) 11.1 psi(0,77 bar) 11.1 psi(0,77 bar) 16.4 psi(1,13 bar) 16.4 psi(1,13 bar) 16 x 16 16 I 16 GPM(60,6 LPM) I 16 GPM(60,6 LPM) I 18 GPM(68,1 LPM) I 18 GPM(68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 16 x 18 16 I 19 GPM(71,9 LPM) I 19 GPM(71,9 LPM) I 21 GPM(79,5 LPM) I 21 GPM(79,5 LPM) (4,9 x 5,5) (4,9) 20.5 psi(1,41 bar) 20.5 psi(1,41 bar) 25.0 psi(1,72 bar) 25.0 psi(1,72 bar) 16 x 20 16 I 24 GPM(90,8 LPM) I 24 GPM(90,8 LPM) I 26 GPM(98,4 LPM) I 26 GPM(98,4 LPM) (4,9 x 6,1) (4,9) 32.7 psi(2,25 bar) 32.7 psi(2,25 bar) 38.3 psi(2,64 bar) 38.3 psi(2,64 bar) (a) For coverage area dimensions less than or between those indicated,it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)Width(backwall where sprinkler is located)x Length(horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.. TABLE B NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII(TY1334) RESIDENT/AL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR SPRINKLERS AT THE HIGH POINT OF THE SLOPE AND DISCHARGING DOWN THE SLOPE • (Greater Than 2 Inch Rise for 12 Inch Run Up To 8 Inch Rise for 12 Inch Run) Page 6 of 8 TFP410 .. 12" 4" MAXIMUM , AO- AD- ELEVATION Minimum-Flow-(c)and-Residual-Pressure (II)Two sprinkler design with the sprinklers located along the slope and positioned to discharge across the slope. Maximum Maximum (III)Three sprinkler design when there are more than two sprinklers in a compartment and Coverage Spacing with the sprinklers located along the slope,and positioned to discharge across the slope. Area(a) Ft. Width x Length(b) (m) Ft.x Ft. Top-Of-Deflector-To-Ceiling: Top-Of-Deflector-To-Ceiling: (m x m) 4 to 6 Inches(100 to 150 mm) 6 to 12 Inches(150 to 300 mm) 155°F/68°C 175°F/79°C 155°F/68°C 175°F/79°C 12 x 12 12 II 16 GPM(60,6 LPM) II 16 GPM(60,6 LPM) II 18 GPM(68,1 LPM) II 18 GPM(68,1 LPM) (3,7 x 3,7) (3,7) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 14 x 14 14 II 16 GPM(60,6 LPM) II 16 GPM(60,6 LPM) II 18 GPM(68,1 LPM) II 18 GPM(68,1 LPM) (4,3 x 4,3) (4,3) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 16 x 16 16 II 16 GPM(60,6 LPM) II 16 GPM(60,6 LPM) II 18 GPM(68,1 LPM) II 18 GPM(68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 18.4 psi(1,27 bar) 18.4 psi(1,27 bar) 16 x 18 16 II 22 GPM(83,3 LPM) II 22 GPM(83,3 LPM) II 22 GPM(83,3 LPM) II 22 GPM(83,3 LPM) (4,9 x 5,5) (4,9) 27.4 psi(1,89 bar) 27.4 psi(1,89 bar) 27.4 psi(1,89 bar) 27.4 psi(1,89 bar) 16 x 20 16 III 23 GPM(87,1 LPM) III 23 GPM(87,1 LPM) III 26 GPM(98,4 LPM) III 26 GPM(98,4 LPM) (4,9 x 6,1) (4,9) 30.0 psi(2,07 bar) 30.0 psi(2,07 bar) 38.3 psi(2,64 bar) 38.3 psi(2,64 bar) (a)For coverage area dimensions less than or between those indicated,it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)Width (backwall where sprinkler is located)x Length(horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.. TABLE C NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR SPRINKLERS LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE (Greater Than 2 Inch Rise for 12 Inch Run Up To 4 Inch Rise for 12 Inch Run) • TFP41O Page 7 of 8 12" 8" MAXIMUM ELEVATION Minimum-Flow-(c)and-Residual-Pressure (III)Three sprinkler design when there are more than two sprinklers in a compartment and with the sprinklers located along the slope.and positioned to discharge across the slope. Maximum Maximum Coverage Spacing Area(a) Ft. Width x Length(b) (m) Ft.x Ft. Top-Of-Deflector-To-Ceiling: (m xIn) 4 to 6 Inches(100 to 150 mm) 155°F/68°C 175°F/79°C 12 x 12 12 III 16 GPM(60,6 LPM) III 16 GPM(60,6 LPM) (3,7 x 3,7) (3,7) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 14 x 14 14 III 16 GPM(60,6 LPM) III 16 GPM(60,6 LPM) (4,3 x 4,3) (4,3) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 16 x 16 16 III 16 GPM(60,6 LPM) III 16 GPM(60,6 LPM) (4,9 x 4,9) (4,9) 14.5 psi(1,00 bar) 14.5 psi(1,00 bar) 16 x 18 16 N/A N/A (4,9 x 5,5) (4,9) 16 x 20 16 N/A N/A (4,9 x 6,1) (4,9) (a) For coverage area dimensions less than or between those indicated,it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b)Width(backwall where sprinkler is located)x Length(horizontal throw of sprinkler). (c) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design Criteria Section for details.. TABLE D NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII(TY1334) RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS FOR SPRINKLERS LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE (Greater Than 4 Inch Rise for 12 Inch Run Up To 8 Inch Rise for 12 Inch Run) . Page 8 of 8 TFP410 + Care and Limited Ordering Maintenance Warranty Procedure The Series LFII (TY1334) must be Products manufactured by Tyco Fire& When placing an order, indicate the maintained and serviced in accord- Building Products (TFBP) are war- full product name. Contact your local ance with the following instructions: ranted solely to the original Buyer for distributor for availability.. NOTES ten(10)years against defects in mate Sprinkler Assembly: Absence of an Escutcheon Plate may rial and workmanship when paid for delay the sprinkler operation in a fire and properly installed and maintained Series LFII(TY1334),K=4.2,Residen- situation. under normal use and service. This tial Horizontal Sidewall Sprinkler with warranty will expire ten (10) years (specify) temperature rating and Before closinga fire protection system from date of shipment by TFBP. No (specify)finish, P/N (specify). main control valve for maintenance warranty is given for products or corn- work on the fire protection system ponents manufactured by companies 155°F/68°C or which it controls, permission to shut not affiliated by ownership with TFBP Chrome Plated P/N 51-211-9-155 d wn the m must be obtained from thre e proon per s- or for products and components which 155°F/68°C s White Polyester P/N 51-211-4-155 have been subject to misuse,improper 155°F/68°c authorities and all personnel who may installation, be affected_by this_action must be no- corrosion, or which have White tified. not been installed,maintained,modi- (RALso1o)' P/N 51-211-3-155 fled or r_epaired_in accordance-with_ap- 155°F/68al Sprinklers which are found to be leak- plicable Standards of the National Fire 175Natural Brass P/N 51-211-1-155 °Fr/9°C or ing or exhibiting visible signs of corro- Protection Association, and/or the Chrome Plated P/N 51-211-9-175 sion must be replaced. standards of any other Authorities 175°F/79°C Automatic sprinklers must never be Having Jurisdiction. Materials found White Polyester P/N 51-211-4-175 byTFBP to be defective shall be either 17s°Erre°c painted, plated, coated, or otherwise White altered after leaving the factory. Modi- repaired or replaced, at TFBP's sole (RAL9010)' P/N 51-211-3-175 fied sprinklers must be replaced. option. TFBP neither assumes, nor 175°F/79°C Sprinklers that have been exposed to authorizes any person to assume for it, Natural Brass P/N 51-211-1-175 corrosive products of combustion, but any other obligation in connection with have not operated,should be replaced the sale of products or parts of prod- Eastern Hemisphere sales only. if they cannot be completely cleaned ucts.TFBP shall not be responsible for Recessed Escutcheon* - - --t1 y wiping the sprinkler with a cloth or sprinkler system design errors or Inas by brushing it with a soft bristle brush. curate or incomplete information sup- Specify: Style 20 Recessed Escutch- Care must be exercised to avoid dam- plied by Buyer or Buyer's repre- eon with (specify*) finish, P/N (spec- age to the sprinklers- before, during, sentatives. ify*), and after installation. Sprinklers dam- In no event shall TFBP be liable, in *Refer to Technical Data Sheet TFP770. aged by dropping, striking, wrench contract, tort, strict liability or under twist/slippage, or the like, must be re- any other legal theory, for incidental, placed.Also,replace any sprinkler that indirect,special or consequential dam- Sprinkler Wrench: has a cracked bulb or that has lost ages, including but not limited to labor Specify: W-Type 6 Sprinkler Wrench, liquid from its bulb. (Ref. Installation charges, regardless of whether TFBP P/N 56-000-6-387. Section). was informed about the possibility of Specify: W-Type 7 Sprinkler Wrench, The owner is responsible for the in- such damages, and in no event shall P/N 56-850-4-001. spection, testing, and maintenance of TFBP's liability exceed an amount their fire protection system and de- equal to the sales price. vices in compliance with this docu- The foregoing warranty is made in lieu ment, as well as with the applicable of any and all other warranties. ex- standards of the National Fire Protec Dress or implied. including warranties tion Association (e.g., NEPA 25), in of merchantability and fitness fora par- addition to the standards of any other authorities having jurisdiction. The in- titular purpose. stalling contractor or sprinkler manu- This limited warranty sets forth the ex- facturer should be contacted relative clusive remedy for claims based on to any questions. failure of or defect in products,materi- NOTE als or components,whether the claim The owner must assure that the sprin- is made in contract, tort, strict liability kiers are not used for hanging of any or any other legal theory. objects and that the sprinklers are only This warranty will apply to the full ex- cleaned by means of gently dusting tent permitted by law.The invalidity,in with a feather duster,•otherwise, non- whole or part, of any portion of this operation in the event of a fire orinad- warranty will not affect the remainder. vertent operation may result. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 a 'NCO Fire Suppression & Building Products 'a rapid response® Technical Services 800-381-93121+1-401-781-8220 HOME FIRE SPRINKLER SYSTEM www.tyco-fire.com Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General The Series LFII Residential Flat-Plate Concealed Pendent Sprinkler has a 4.9 Description (60,5)K-factor that provides the required residential flow rates at reduced pres- The TYCO RAPID RESPONSE Series sures,enabling smaller pipe sizes and LFII Residential Flat-Plate Concealed water supply requirements. Pendent Sprinklers(TY2524)are decora- This sprinkler has been designed with , tive,fast response,fusible solder sprin- • "" T klers designed for use in residential oc- heat sensitivityand water distribution "- ' cupancies such as homes,apartments, characteristics proven to help in the con- ;-, dormitories, and hotels. trot of residential fires and to improve � the chance for occupants to escape or The Cover Plate/Retainer Assembly con- be evacuated. . c ,4' ceals the sprinkler operating -,, ,4w,,compo- The Series LFII Residential Flat-Plate ,taN `,a nents above the ceiling.The flat profile Concealed Pendent Sprinklers are of the Cover Plate provides the optimum shipped with a Disposable Protective aes#hetically appealing sprinkler design. -Cap.The Protective Cap protects the Additionally,the concealed design of the sprinkler during ceiling installation or Series LFII_Residential Flat=Plate-Con ==finish.After ceiling installation-is com =_ -Technical-ed Pendent Sprinklers provides 1/2 ee /�/cal inch(12,8 mm)vertical adjustment.This plete, the Protective Cap is removed adjustment provides a measure of flex- and the Cover Plate/Retainer Assem- Data y when cutting i a pipe drops. bly is installed. Removing the Protec- tive Cap is required for proper sprinkler Approvals The Series LFII Residential Flat-Plate performance. UL and C-UL Listed Concealed Pendent Sprinklers are in- NSF-61 Certified tended for use in the following systems: NOTICE The Series LFII Residential • per NFPA 13D, wet pipe residential The Series LFII Residential Flat-Plate Concealed P ndent Sprinkle stat-Plate are only sprinkler systems for one-and two- Concealed Pendent Sprinklers(TY2524) listed with the Series LFII Concealed family dwellings and mobile homes; described herein must be installed and Cover Plates having a factory-applied • per NFPA 13R, wet pipe residential maintained in compliance with this doc- finish. sprinkler systems for residential oc- ument and with the applicable standards cupancies up to and including four of the National Fire Protection Associa- Maximum Working Pressure stories in height;and tion,in addition to the standards of any 175 psi(12,1 bar) urisd •per NFPA 13,wet pipe sprinkler sys to do soy es mayaviimnpa'r the pe/rforma�nce lure Discharge Coefficient tems for the residential portions of of these devices. K=4.9 GPM/psi'" (70,6 LPM/bar's) any occupancy. Owners are responsible for maintaining Temperature Rating their fire protection system and devices Sprinkler: 160°F(71°C). in proper operating condition. The in Cover Plate: 139°F(59°C) IMPORTANT stalling contractor or sprinkler manu- Always refer to Technical Data facturer should be contacted with any Vertical Adjustment Sheet TFP700 for the "INSTALLER questions. 1/2 inch (12,7 mm) WARNING" that provides cautions / p Finishes with respect to handling and instal- Model/S rinkler Refer to the Ordering Procedure lation of sprinkler systems and corn- section. ponents. Improper handling and in- Identification • stallation can permanently damage Physical Characteristics a sprinkler system or its components Number (SIN) •• Cover Plate/Retainer Assembly: and cause the sprinkler to fail to Cover Plate Copper operate in a fire situation or cause it TY2524 Ejection Spring . . . . Stainless Steel to operate prematurely. Retainer Brass Page 1 of 6 OCTOBER 2010 TFP443 - i . TFP443 __•- . • Horizontal Ceiling Sloped Ceiling Sloped Ceiling Minimum Fiow(bland Minimum FiowS'and Minimum Flow(bjand Residual Pressure Residual Pressure Residual Pressure " Maximum Maximum (Maximum 2-inch rise Coverage (Greater than 2-inch rise (Greater than 4-inch rise Area 9 Spacing for 12-inch run) up to maximum 4-inch up to maximum 8-inch rise for 12-inch run) rise for 12-inch run) 160°F(71°C) 160°F(71°C) 160°F 71°C) Sprinkler (kler Sprinkler Sprinkler 12'x 12' 12' 13 GPM(49,2 LPM) 17 GPM64,3 LPM (3,7 m x 3,7 m) (3,7 m) 7.0 psi(0,48 bar) ( ) 17 GPM(64,3 LPM) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 14'x 14' 14' 13 GPM(49,2 LPM) 17 GPM( LPM) (4,3 m x 4,3 m) (4,3 m) 7.0 psi(0,48 bar) 12,0 ( 17 GPM(64,3(0,8LPM) psi(0,83 bar) 12.0 psi(0,83 bar) 16'x 16' 16' 13 GPM(49,2 LPM) 17 GPM (4,9 m x 4,9 m) (4,9 m) (64,3 LPM) 17 GPM(64,3 LPM) 7.0 psi(0,48 bar) 12.0 psi(0,83 bar) 12.0 psi(0,83 bar) 18 x 18' 18' 17 GPM(64,3 LPM) 22 GPM( LPM) (5,5 m x 5,5 m) (5,5 m) 12.0 psi(0,83 bar) 20,2 ( 22 GPM((1, 3 LPM) psi(1,39 bar) 20.2 psi(1,39 bar) 20'x20' 20' 20 GPM(75,7 LPM) 24 GPM90,8 LPM) (6,1 m x 6,1 m) (6,1 m) 16.7 psi(1,15 bar) 24.0psi( 24 GPM(90,8 LPM) (1,65 bar) 24.0 psi((11,,665 bar) (a)For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated. (b)The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to"Hydraulic Design"in the Design Criteria section for details. TABLE A SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) NFPA 13DAND NFPA 13R HYDRAULIC DESIGN CRITERIA WET PIPE SYSTEMS •Sprinkler/Support Cup Assembly: Body Brass Design For systems designed to NFPA 13,the _number of design sprinklers_is_to be __-Cap -_ :. .-Bronze �/' _ the four most hydraulically-demanding-- Saddle Brass /fel/a Sealing Assembly Ber Ilium sprinklers.The minimum required dis- Nickel w/TefloThe TYCO RAPID RESPONSE Series charge from each of the four sprinklers Soldered Link Halves Nickel LFII Residential Flat Plate Concealed is to be the greater of the following: Lever Bronze Pendent Sprinklers (TY2524) are UL •flow rates given in Table A for NFPA • and C-UL Listed for installation in ac- Compression Screw Brass Deflector cordance with the following criteria. 13D and 13R as a function of tem- Bronze perature rating and the maximum al- Guide Pin Housing Bronze towable coverage area Guide Pins Bronze NOTICE Support Cup Steel When conditions exist that are outside • minimum discharge of 0.1 GPM/sq. corn- the scope of the provided criteria,re- of thever re "design ydra fer to the Residential Sprinkler Desi n priseddemaof four most hydraulically Operation Guide TFP490 for the manufacturer's erage areasprrotectedklers or actualhecour recommendations that may be accept- pareas protected by the four When exposed to heat from a fire, the able to the Authority Having Jurisdiction. sprinklers Cover Plate,which is normally soldered to the Retainer at three points,falls away The Series LFII Residential Flat P/ate Obstruction To Water Distribution to expose the Sprinkler/Support Cup As- obstruction Pendent Sprinklers must Locate sprinklers in accordance with the sembly.At thispoint,the Deflector,sup- sprinklers not be used in applications where the obstruction rules of NFPA for residential y air pressure above the ceilingsprinklers as well as obstruction criteria ported by the Guide Pins, drops downisgreater to its operated position. . Down drafts through described within TYCO technical data than that below the Support Cup can delay sprinkler op- sheet TFP490. The Solder Link Element of the Sprinkler/ eration in a fire situation. Operational Sensitivity Support Cup Assembly is comprised of two link halves that are soldered togeth- System Type Install sprinklers relative to the ceiling er with a thin layer of solder. When the Only wet pipe systems may be utilized. mounting surface as shown in Figure 3. rated temperature is reached,the sol- der melts and the two link halves sera Hydraulic Design Sprinkler Spacing Table A provides the minimum required rate, allowing the sprinkler to activate The minimum spacing between sprin and flow water. sprinkler flow rate for systems designed klers is 8 feet(2,4 m). to NFPA 13D or NFPA 13R as a function The maximum spacing between sprin- of temperature rating and the maximum klers cannot exceed the length of the allowable coverage areas.The sprinkler coverage area(Table A)being hydrau- flow rate is the minimum required dis- lically calculated; for example, a maxi- charge from each of the total number of mum of 12 feet for a 12 ft.x 12 ft. cov- "design sprinklers"as specified in NFPA erage area or 20 feet for a 20 ft.x 20 ft. 1 Registered trademark of Dupont 13D or NFPA 13R. coverage area. TFP443 Page 3 of 6 BODY irSEALING . (1/2"NPT) ASSEMBLY CAPD/1 �-�tl� ��� SPRINKLER ���r llir \`�; I WRENCHING SADDLE I 4` ��` it 1 AREA i �-q 1 SUPPORT , Jr, -441:11*,), COMPRESSION CUP WITH 1 t Ili�ROLL FORMED all THREADS1ll 11111111- 11/111!)IN ( LEVER WRENCH GUIDE RECESS I PIN a■/_.L�— _.. I i i SOLDER LINKS ""�\ I ELEMENT �`�� GUIDE PIN I i i H HOUSING 1 i 1 i � I -- _ i i I DEFLECTOR DEFLECTOR 1t- --....----,______,----,=3� (OPERATED PUSH WRENCH iPOSITION) IN TO ENSURE ' I SPRINKLER/SUPPORT CUP ENGAGEMENT ASSEMBLY I WITH SPRINKLER THREAD INTO ' WRENCHING AREA SUPPORT CUP i I RETAINER UNTIL MOUNTING )1 • WITH DIMPLES THREAD FIGURE2 SURFACE IS • FLUSH WITH i O W-TYPE 18 CEILING-_____-___I J EJECTION SPRINKLER WRENCH - - - --- - _.- ILING- _ - _ --- -- -- -- -- 1- _ . _ _SPRING-- . - - I - — r-iI ' SOLDER COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE • FIGURE 1 FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY2524) • ASSEMBLY f6-.31 " A. SPRINKLER- (63,51/2mDIm) 1/2"(12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPT ADJUSTMENT FITTING lib..._ / OPERATED 1 ag.....7. 11111.111.°M- SPRINKLER 41II1-7/8"t1/g" COVER 176.1......_...' (47,6 mm PLATE 1/B'GAP ±3,2 aim) RETAINEREon 1 111 II ` (3,2 mm] womminimmionw . , �I7 L--- \ ( L— COVER- SPRINKLER- 1 i 7/8" 22,2 mm) I I RETAINER SUPPORT CUP (4,8 mm) MOUNTING 1-1/B"(29,6 mm) ASSEMBLY ASSEMBLY 3/16" SURFACE '_-�' 3-3/16"DIA. DISPOSABLE (81,0 mm) DEFLECTOR IN " TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 PROTECTIVE CAP AND ACTIVATED DEFLECTOR INSTALLATION DIMENSIONS • r TFP443 Pdge4of6 Installation 6. Screw on the Cover Plate/Retainer Replace sprinklers that: Assembly until its flange contacts The TYCO RAPID RESPONSE Series the ceiling. •were damaged by dropping,striking, LFII Residential Flat Plate Concealed wrench twisting, wrench slippage,or DoPendent Sprinklers must be installed Cover not continue/Ritor screw ly the the like. in accordance with the following Plate/Retainer Assembly such instructions. that it lifts a ceiling panel out of its •were modified or over heated. normal position. • are leaking or exhibiting visible signs NOTICE If the Cover Plate/Retainer Assembly of corrosion. to the Solder Link Element dui cannot be engaged with the Mounting Responsibility lies with owners for the Damageing can avoidedbyhan- Cup or the Cover Plate/Retainer As- inspection,testing,and maintenance of ding installationthe sprinkler be y the ided by a sembly cannot be engaged sufficiently their fire protection system and devices only;that , do nea / Support to thep to contact the ceiling,the Sprinkler in compliance with this document, as applyFitting must be repositioned. well as with the applicable standards of Solder Link Element(Figure 1). Obtain a leak tight 1/2 inch NPT sprinkler ^ the National Fire Protection Association joint applying a minimum-to-maxi-NPT sprinkle Care and (for example,NFPA 25),in addition to torque ape lyof 7 to 14 i imu. (9,5-to axi- the standards of any other authorities mum orq ee levels.1 torque can distort Maintenance having jurisdiction. Contact the install- ing contractor or sprinkler manufacturer the sprinkler inlet with consequent leak- The TYCO RAPID RESPONSE Series regarding any questions. age or impairment of the sprinkler. LFII Residential Flat-Plate Concealed Do not attempt to compensate for in- Pendent Sprinkler(TY2524) must be Automatic sprinkler systems are rec- sufficientadjustmentin the Cover Plate/ maintained and serviced in accordance andommaintaineded to be inspected, tested, sufficient e t adjustment by under-r orover- with the following instructions. by a qualified with local- tightening the sprinkler. Re-adjust the tionrequirementsSernin d or nationaldancls. position of the sprinkler fitting to suit. NOTICE and/or codes. 1. Install pendent sprinklers in the Before closing a fire protection system pendent position, with the center- main control valve for maintenance work on the fireprotection system that it con- line of the sprinkler perpendicular to the mounting surface. trols,obtain permission to shut down the affected fire protection system from the 2. Remove the Protective Cap. proper authorities and notify all person- 3. With pipe-thread sealant applied nel who maybe affected by this action. W Pte the pipe threads,_and using_the__ When_properly_installed,there-is-a nomi--_ ._ ___---_._______--._ _ _ ____ __ Vv-Type 18 Wrench shown in Figure nal 7/8 inch (3,2 mm)air gap between 2, install and tighten the Sprinkler/ the lip of the Cover Plate and the cell- Support Cup Assembly into the fit- ing,as shown in Figure 3.This air gap ting. The W-Type 18 Wrench ac- is necessary for proper operation of the cepts a 1/2 inch ratchet drive. sprinkler by allowing heat flow from a 4. Replace the Protective Cap by fire to pass below and above the Cover pushing it upwards until it bottoms Plate to help assure appropriate release out against the Support Cup. The of the Cover Plate in a fire situation.If the Protective Cap helps prevent dam- ceiling needs repainting after sprinkler age to the Deflector and Guide installation, exercise care to ensure that Pins during ceiling installation and/ the new paint does NOT seal off any of or during application of the finish the air gap. Failure to do so may impair coating of the ceiling. sprinkler operation. Absence of a Cover Plate can delay the VIM sprinkler operation in a fire situation. As long as the protective Cap re- Do not pull the Cover Plate relative to mains in place, the system is con- the Enclosure. Separation may result. sidered"Out Of Service': Exercise care to avoid damage to sprin- 5. After the ceiling has been com- . klers before, during,and after installa- pleted with the 2-1/2 inch (63 mm) tion.Never paint, plate, coat, or other- diameter clearance hole and in wise alter automatic sprinklers after they preparation for installing the Cover leave the factory. Plate/Retainer Assembly, remove Never repaint factory-painted Cover and discard the Protective Cap, Plates.When necessary,replace cover and verify that the Deflector moves plates with factory-painted units. Non- up and down freely. factory applied paint can adversely de- If the Sprinkler has been damaged lay or prevent sprinkler operation in the and the Deflector does not move up event of a fire. and down freely, replace the entire Sprinkler assembly.Do not attempt to modify or repair a damaged sprinkler. • • TFP443 Page 5 of 6 Limited Ordering • Warranty Procedure Products manufactured by Tyco Fire Contact your local distributor for avail- Suppression & Building Products ability.When placing an order, indicate (TFSBP)are warranted solely to the orig- the full product description and Part inal Buyer for ten(10)years against de- Number(P/N). fects in material and workmanship when paid for and properly installed and main- Sprinkler/Support Cup Assembly tained under normal use and service. Specify: Series LFII Residential Flat This warranty will expire ten (10)years Plate Concealed Pendent Sprinkler (TY2524), K=4.9,without Cover Plate/ from date of shipment by TFSBP. No warranty is given for products or corn- Retainer Assembly,P/N 51-114-1-160. ponents manufactured by companies Cover Plate/Retainer Assembly not affiliated by ownership with TFSBP Specify:Cover Plate/Retainer Assem- or for products and components which bly with finish (below) for the Series have been subject to misuse, improper LFII Residential Flat-Plate Concealed installation,corrosion,or which have not Pendent Sprinkler(TY2524), K=4.9, P/N been installed,maintained, modified or (below): repaired in accordance with applicable Standards of the National Fire Protection Chrome P/N 56-201-9-135 Association,and/or the standards of any Custom P/N 56-201-X-135 other Authorities Having Jurisdiction. Off White Materials found by TFSBP to be defec- P/N 56-201-0-135 tive shall be either repaired or replaced, Pure White* at TFSBP's sole option.TFSBP neither (RAL 9010) P/N 56-201-3-135 assumes,nor authorizes any person to Signal White** assume for it, any other obligation in • (RAL P/N 56-201-4-135 connection with the sale of products or Standard White(Grey White) parts of products.TFSBP shall not be (RAL9002) P/N 56-201-5-135 responsible for sprinkler system design errors or inaccurate or incomplete in- *Eastern Hemisphere sales only. formation supplied by Buyer or Buyer's " Previously known as Bright White. representatives Note: All Custom Cover Plates are pafntea=using Sherwin Williams Interior - . In no event shall TFSBP be liable,in con- Latex Paint. Contact TYCO Customer tract,tort,strict liability or under any oth- Service with any questions related to er legal theory,for incidental, indirect, custom orders. special or consequential damages,in- cluding but not limited to labor charg- Sprinkler Wrench es, regardless of whether TFSBP was Specify W-Type 18 Sprinkler Wrench, informed about the possibility of such P/N 56-000-1-265. damages,and in no event shall TFSBP's liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, express or implied.including warranties of mer- chantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on fail- ure of or defect in products,materials or components,whether the claim is made in contract,tort,strict liability or any oth- er legal theory. This warranty will apply to the full extent permitted by law.The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. . .. , DynaThyead Full Line Sch-40 Replacement Dyne-Thread'offers the life expectancy of Sch4O with superior hydraulics and greater value, Dyna-Thread sprinkler pipe represents an engineering advancement for the s and longevity of traditional Sch-40 pipe with quality and superior hydraulic advanr agespipe�dustry,It combines the safety • Comparison to Schedule 40• - • Coinparistin:to LULT. Pipes' ' Dyna-Thread's inside diameter 15 up • With its increased strength and lighter • More wall thickness at the thread to 3.6/0 larger than Soh-40 giving it to LG% hydraulics.And,when used weigh;Dyna-Thread reduces (CRR=Lo0)gives Dyne-Thread installation fatigue and is ideal for better life expectancy than li in combination with Dyne-Flow pipe, retro-fit a lications. ghtwall down sizing often occurs, tbreadablc pipe joints. Corrosion Resistance Ratio(CRR)is a • Unlike lightwall threadable pipe, • Dina-Thread is fully listed and t71,(Underwriters Laboratory)term for Dyna-Thread approved by UL,ULC,and FM ibr arni has no thread gauge the estimated life expectancy of a pipe warning, fire sprinkler applications. joint.This is based on the calculated •• The life expectancy of Dyna-Thread wall thickness at the base of the first star Dyne-Thread is approved for and Sch-40 are equal based on the exposed thread.assumed to be the standard hoe used spacing as earthquake it. calculated wall thicknesses per UL. vs eekeat Point of'the pipe length,Dyna- C`C,)b can be as Thread and Sch-40 have the same sway bracing, and is safe to use as • The consistent quality of steel used to calculated wall thiclatesses at this point ' make Dyna-Thread facilitates smooth and are both assigned the same CRR of threading and lower maintenance 1,00. Dyna-Thread is safer to weld on, cote, • Dyna-Thread is more widely • The exterior of Dyna-Thread is The Internal surflioe of all black Allied accepted than lightwall ihreadalnle protected by a clean,durable mill Tuba&Conduit Fire Sprinkler pipe where 9°h-40 specified. • coating for extended shelf life and products up to 45000"in diameter is easy paint application. coated with our new Antibacterial -- — — — —— - - ==Form—u7a;°,ABF'L ry Ire scientific-laboratory — —- test;ABS proved to have superior Specifications & Appi.pvals resistance to microbial colonization of GO ilell11' 010 pipe walls,thereby delaying or possibly super 40IDyn$-Thread pipe is preventing the onset of manufactured to meet:ASTIVIA-135, Listed Approved Listed Microbiologically Influenced corrosion Grade A and is in compliance with (WC)when the First Sprinkler System NFPA-13.All sizes of Super 40/Dyna- is&et installed. Thread are rated at 300 psi working pressure.Super 40/Dyna-Thread is UL 5Nectfi"cations and ULC Listed for wet,dry deluge and NPS MamfRa►IX, Nit, Wt.(1120 t711a4) Pa/ W1,4.111(21`) �"80�sprinkler systems and FM M: In;mm Lbs/Ft Ktv1r1 Lbs/ft KrUIs Lilt i Kg WE/l ilt(24') Wt/LIit(25' Approved for use in wet systems.Super t' 1,060 1.930 1,76 eg Kg Lbs;Kg 40/Dyna-Thread can bo"hot-dip" 7D 1955 2234 2327 galvanized to meet FM requirement for 25 274 2.0 2.20 70 857 7013 105: dry systems,Super 40/Dyna-Thread is 1W 1,408 1,$70 2.54 51 2002 2288 2384 approved for all threaded couplings and 32 358 2.8 3,78 51 908 7088 i08 welded outlets and is suitable for all 1 1.688 2.290 3.22 44 2113 2418 251' roll-grooved,and plain-end fittings. •10 41.ff 3.4 4.79 44 859 7097 774' (See list infermatian). 2" 2.104 3.050 4.57 30 1921 2193 2287 50 53.4 4,5 8.80 30 877 996 ' 105 ' 'lIC121 FI°w cw7tr°I61;-) allied 16100 S. Lathrop•Harvoy,IL 60426 Customer Service: LJ 11350 Norcom Rd.•Philadelphia,PA 19154 (B00)882-5543 TUBE 6 OQNOUIT 2525 N,27th Ave.-Phoenix,AZ 85009 Fax 708-339-1806 83-3 Submittal Data Sheet Dyna-Thr - Full Line Sch-40 Replacement Dyna-Thread aprinklea pine reeceaemts an engine-nue' advanoetnent for the sprinkler pipe Industry.It combines the safety and longevity of traditional Soh-40 pipe with quality and supezior hydraulic edvanrages. Comparison to Schedule 40 Dyna-Thready inside diameter is up to 3.6%larger than Sch-40 giving it superior hydraulics.Also,whet used in combination with Dyna-Flow pine, dawn sinus often occurs.Dyna-Thread is fully listed mad approved UL, ULC, _ --;_ and FM for fire sprinkler applications.The life expectancy of Dyna•T read and Sch-40 ..-.::-.,- '- are equal based en the calculated wall thicknesses per UL.,The consistent quality of - i ;-. i_:"_ - steel used to make Dyna-Thread facilitates smooth threading and lower maintenance - _ •'= !: tt: _```_-. costs. The exterior ofDyna-Thread is protected by a clean,durable mill coating ` :.t --` extended shelf life and easy paint application.With its increased strength and lighter Weight,Dyne-Thread reduces installation fatigue tad is ideal for rens-fit applications. Can-mien Resiztaace Ratio(CRR)is a UL(Underwriters - ._ Laboratory)term for the - estnnated life expectancy of s pipe joist This is bland c - _ 't - ,}` - the calculated wall thickness ' ,c:: at the base of the first exposed thread,assumed to be the weakestpaint of the pipe r.>_:.' length.Dyna-Thread and Soh-40 have the same calculated wall thicknesses at this ;i point and are both assigned the same CRR of 1.00. - `ill."''1 Comparison More wall( , o q `: Pipe thickness at the thread(CRR=1.00)gives • r . " - Dyna-Thread better life expectancy than liglttwelt threadable pipe joints. Unlike S:;-. . -, k T` hghtwall ti readable pipe Dyne-Thread has no thread " 'ere.. .FP ` ,! . -."I' •`.s,4: approved forstaadart! s gaugeused as earthquake Dyne-Thread ix €Acid t'" • 1 r per' (15 ft.QC.),can be as sway '" tti 't �. •r r braoing,•and is tate to use as drops.Dyna-Thread is safer to weld on than many ping d,, '°''� " ' > M :::i:; coated lightwail thrcadabfe pipe produ "" z }tel:::'•;::'El.:e....: lightwall tbreadable where Sah-40 is specified,�Dyna•ZTuead is more widely accepted than T�. :; � , �l a.;:al .. �- .`., _ �`'f 1, Specifications&ApprovaIs Super 40/ Dyne-Thread pipe is manufactured to Specifications meet:ASTM A 135,Grade A and is in HP8 MINIUM!U), Wt. Wt.(H20 Filled) Pal WI4.11t(21') Warn(2/') WI/Llll(2d' compliance With NFPA-I3.All s1zca at he mm he mm tbvee Kart Lbs/Fr K-An Lit Ldrt.' as;Kg L. K• Super 40/Dyea-Thread tie rated at 30019 psi working pressure.Super 40/Dyne 1' t M 1.330 1.750 70 f 8 887 1073074 232 105 25 27:4 2.0 Z60 li7 103% _ _. -ThreadaUL andW-CListed for lust, __-- dry s ri —--— =f1/i== 1:408 =.__1 870=-— _ Pro-action primkler lyatams tad _2.54„ --61 2402 2288 '-- 238: FM Approved far use in wet systems. 8 2.8 378 31 908 1098 108 Super 40/Dyna-Thread can be"hot-dip" 1/' 1,639 2.290 3,22 44 2115 2418 251: galvanized to meet FM requirement for 40 41,6 3.4 4.79 44 959 1097 11• dry systems.Super 40/Dyna-Thread is 2' . 2.104 3.050 4,57 30 1921 2186 228 - approved for all threaded couplings and 60 53.4 45 5.80 30 871 998 103 welded outlets and is mutable for all roll- lisgmaved,and ppllam' -end fittings.(Seo Mrerican Tube and Pipe was acquired byAllied Tube and Conduit to February 1, ting infonnce), 1997.The engineered ligbtwall and standard wall family of products.(though they The Ines/eel surface of all black ��di rnt names arc the same in all respects with regard to strength,weight, Sprinkler pipe up W 4.5000"is diameter bundle count,listings end approvals.For example, shall be coated with Allied Tube& Dyna-Flow and Super Flo arc the same product as 420 .41). is) Conduit Antibacterial Formula"ABF', area Thread tad Super 40.XL is manufactured with Exterior galvanized coating.BLT is manufactured with Blacklacquer seating Listed Approved Listed Project: sprinkler Contractor: name enginear: Specification Reference: System Type: eocetions: comments: S3-4 • s . . tLjcQ Flo w Tyco Fire Con tro/ Products BlazeMaster ° FIRE SPRINKLER PIPE & FITTINGS SUBMITTAL SHEET • .._.-.___vacs. c..... T SCO FIRE PRODUCTS 451 North Cannon Avenue Lansdale, Pennsylvania 19446 www.tyco-fire.com TECHNICAL SERVICES TEL' (800) 381-9312 • FAX." (800) 791-5500 E-MAIL techserv@tycofp.com C a tom. p d.nSW'. {, _ r'w11%1 e 57 feZ fe ~nzzazsz41 fF�"�1 -,� i .K"' Y .ff ft¢%c r nr�a h Y ♦'frit MINIM No. 19-1.5 TD915 4-1.1.20 9/2001 I O - introduction tyco Fire Products (TFP) BlazeMaster®CPVC pipe and the same time, they provide superior heat resistance and fittings are designed exclusively for use in wet pipe strength as compared to traditional CPVC and PVC piping automatic fire sprinkler systems. They are made from a materials used in the plumbing trade. Various adapters are specially developed thermoplastic compound composed of available to connect CPVC pipe to metallic piping.All female post chlorinated polyvinyl chloride (CPVC) resin and state of pipe thread adapters have brass inserts for durability. the art additives. TFP BlazeMaster2 CPVC products are Grooved adapters connect directly to grooved end valves easier to install than traditional steel pipe systems, and at and metallic pipe, with flexible grooved end couplings. Technical Data Sizes: 1/4"-3" Manufacture Source: U.S.A. Maximum Working Pressure: 175 psi Material: Approvals: UL, FM, CUL, NSF, Dade County, LPCB, Pipe: ASTM F442, SDR 13.5 MEA, and the City of Los Angeles Fittings: ASTM F438 (Sch. 40) and Note: See current TFP BlazeMaster Installation Instructions and Technical Manual,for exact listing/approval information ASTM F439 (Sch. 80) Color: Orange Pipe Nom.Pipe Size Avg. O.D.Inches Avg.ID. Inches Wt. Lbs./Ft. Wt.N:0 filled Pipe Lbs./Ft. Ft.of Pipe per Lift Wt.per Lift Lbs. 3/4" 1.050 0.874 0.17 0.43 1" 1.315 7875 1413 1.101 0.26 0.67 5040 1320 174" 1.660 1.394 0.42 1.07 1'/2" 1.900' 2835 1191 1.598 0.55 1.40 2205 1136 2" 2.375 2.003 0.86 2.20 1260 1063 2 1/2" 2.875 2.423 1.26 3.22 1215 1531 3" 3.500 2.952 • 1.87 4.79 720 1344 - Fittings T,° . T/o' T/0 • 45° Elbow _. �► T/° -�' :k1%__ �P� Reducing 90° Elbow11111 T�_ 90 Elbow- ____ �� T/o� -- --- ° iII! Partze T/O Wt. . e ' 80050No. Si3/ Sch.<" 40 3/T/O" 0.08Wt.Ib. Part No. Size Sch. 1 2 lb 80025PartNo3/Siz," 40Sch. "/T/O,6" , 0.09 Wt.Ib. 80051 1" 40 3/6„ 0.11 lb. 80032 1"x /, 40 "/,6" 13/,6" 0.16 80026 1" 40 3/," 0.14 lb. 80052 1'/4" 40 3/, 0.20 lb. 80027 1'/," 40 '/a" 0.21 lb. 80053 172" 80 '/16" 0.31 lb. 80028 1'/2" 80 1'/16" 0.40 lb. 80054 2" 80 3/," 0.56 lb. 80055 272" 80 3/," 80029 2" 80 174" 0.79 lb. 0.89 lb. 80030 21/2" 80 172" 1.14 lb. 80056 3" 80 1" 1.19 lb. 80031 3" 80 113/,6" 1.82 lb. I i i r . T/O' I ', T/O I = sr_ . int �Tee - _ T/O Reducing "mg_ Cross .--- Tee T/O I I T/O T/D° I T/O ; T/O' I T/O' T/O Rai T/O Part80000 No. Size Sch.40 T/O5/6" 0.11 Wt.Ib. PartNo. T/O Wt. PartNo. Size Sch. T/O Wt. ," 80001 1" 40 3/," 0.19 lb. 80015 1"x,/Q„ Size Sch. 1 2 Ib. 80009 3/," 40 9/16" 0.13 Ib. 40 "/16" "/16" 0.28 80010 1" 40 15/16" 0.23 lb. . 80002 174" 40 7/6" 0.26 lb. 80003 172" 80011 1'/," 40 75/,6" 0.34 Ib. 80 1" 0.51 Ib. 80012 1'/2" 80 1'/,6" 80004 2" 80 13/6" 0.671b. 0.90 lb. 80013 2" 80 13/6" 80005 272" 80 19/,6" 1.59 lb. 1.00 lb. 80014 2'/2" 80 19/,e" 1.91 Ib. 80006 3" 80 111/,6" 2.41 lb. 80008 3" 80 113/,6" 2.89 lb. sa 8002 AL_ rc T/0 • 1111-II '-"-{ T/0 .....„........ P ._____ Coupling _, ,_._. 1 _. Cap _ Reducer _t..,, ,. " Bushing /IIPart No. Size Sch. T/0 Wt. Part No. Size Sch. T/O Wt. Part No. Size Sch. T/O Wt. 80200 1"X'/4" 40 '/,6"80075 '/," 40 /e" 0.071b. 3 6 0.041b. 80100 /4" 40 /,s" 0.04 Ib. 80201 1'/4"X 3/4" 40 '/,s" 0.11 Ib. 80076 1" 40 1/8" 0.11 Ib. 80101 1 40 3/8" 0.06 Ib. 80202 1'/4"x 1" 40 5/,6" 0.12 Ib. 80077 1'/4" 40 3/16" 0.12 Ib. 80102 1'/4" 40 '/z" 0.10 Ib. 80203 1'/z"x 3/4" 680078 1'/z" 80 3/,6" 0.251b. 5 80 /e" 0.161b. 80103 1 /z" 80 /e" 0.20 Ib. 80204 1'/z"x 1" 80 i/z" 0.14 Ib. 80079 2" 80 3/,6" 0.38 Ib. 80104 2" 80 5/8" 0.31 Ib. 80205 1'/z"x i'/," 80 '/e" 0.17 Ib. 80080 2'/z" 80 3/,6" 0.67 Ib. 80105 21/2" 80 '/8" 0.58 Ib. 80206 2"x 3/4" 80 3/4" 0.27 Ib. 80081 3" 80 3/,6" 0.91 Ib. 80106 3" 80 1" 0.88 Ib. 80207 2"x 1" 80 "/is" 0.26 Ib. 80208 2"x 1'/4" 80 9/I6" 0.24 Ib. I T/0 Gr00Ved80209 2"x 11/2" 80 '/,6" 0.19 Ib. 80215 21/2"x 1" 80 115/16" 0.42 Ib. Coupling _ P 80214 21/2"x 11/4" 80 13/4" 0.45 lb. Adapter __� 80213 21/2"X 1'/z" 80 15/6" 0.46 lb. Part No. Size Sch. T/O Wt. Pipe OD 80211 2'/2"x 2" 80 19/19" 0.29 lb. 80160 11/4"x 1'/4"Grooved 40 2 5/,e" 0.78 lb. 11/4"(1.660") 80210 3"x 2" 80 2 3/,6" 0.72 lb. 80161 1'/2"x 1'/2" Grooved 80 2 5/I8" 0.95 lb: 1'/z"(1.900") 80212 3"x 2'/z" 80 115/,6" 0.471b. 80162 2"x 2" Grooved 80 2 5/16" 1.42 lb. 2"(2.375") 80163 2W'x 2'/2" Grooved 80 25/16" 2.28 lb. 2'/z"(2.875") 80164 3"x 3" Grooved 80 2'/4" 3.00 lb. 3"(3.500") Reducing iJyx�111r 80168 3"x 76.1mm Grooved 80 2'/4" 2.72 lb. 76.1mm(3.000") Tee TTro' sJo___ -- rro' 'e T/02----part_-`-_z_-- =_-_ _ ::-.--2--:_.-__ /0----__ VI/ Female - '`'�'� No. Size Sch. T - 1 2 3 lb. Adapter Sri 80132 3/4"X'/4"x 1" 40 3/4" 3/4" 5/90 0.14 -• �, 80133 1"x 3/4"x 3/4" 40 1/2" 11/,e" 3/4" 0.14• 80134 1"X 3/4"X 1" 40 %" 3/4" 3/4" 0.17 Part No. Size Sch. T/0 Wt. 80260 1"x 1"x 3/4" 40 80142 3/,"x 3/4"NPT 40 5/8" 0.41 lb. , 3 " 3/4" 3/4" 18/160 0.16 80145 1"x 1" NPT 40 3/," 80135 1 /,"x 1"x /4 40 '/18" 3/4" '3/49" 0.21 80146 174"x 1'/4" NPT 40 '/8" 1.030lb. 80136 1'/4"x 1"x 1" 40 "/,e" 3/4n 'S/16" 0.22 80137 1 /4 x 1"x 1'/4" 40 13/9" 13/48" 13/19" 0.26 80147 1'/2"x 1'/2" NPT 80 1" 1.42 lb. 80261 17+"X 11/4"X 314" 40 /e 80148 2"x 2" NPT 80 13/8" 2.66 lb. , " 5 5/e" '/e" 0.23 80262 1 /4 X 174"X 1" 40 3/4" 3/4" '/e" 0.26 80138 1'/4"x 1'/4"x 172" 80 1" 1" 1" 0.43 C T/0 80140 1...._ '/z"x 1'/4"x 3/4" 80 '/z" 5/e" 1" 0.36 Male 80141 11/2"X 1'/4"X 1" 80 '/z" 5/8" 1'/8" 0.38 - -- -- 80263 1'/z"x 11/2"x 3/4" 80 VI e" 9/76" 1" 0.36 Adapter _ 80264 1'/2"x 1'/2"X 1" 80 9/18" 3/48" 1" 0.38 Part No. Size Sch80275 1'/z"X 1'/z"X 1'/4" 80 '/e" '/e" 1" 0.45 . T/0 Wt. 80265 2"x 2"x 3/," 80 314" 3/4" 13/6" 0.61 80157 3/4"x 3/4" NPT 40 15/ 0.33 lb. 80158 1"x 1"NPT 40 13/8"8" 0.56 lb. 80266 2"x 2"x 1" 80 '/e" 7/8" 13/8" 0.66 80274 2"x 2"x 1'/4" 80 1" 1" 13/6" 0.74 80267 2"x 2"x 1'/2" 80 1'/e" 1'/e" 13/9" 0.78 --j T/O 80271 21/2"X 2'/2"X 1" 80 111/16" 1"/1600 19/19" 1.43 1 80272 21/2"x 2'/z"x 11/4" 80 171/16" 1"/16" -18/16" 1.46 Reducing _. _._ ._ _ 80273 2'/2"X 2'/z"X 1'/2" 80 1"/,6" 1"/,s" 19/16" 1.48 Coupling 80276 2'/2"x 2'/2"x 2" 80 1"1/28" 1"/19" 19/19" 1.50 80270 3"x 3"x 11/2" 80 13/4" 13/4" 173/18" 2.28 Part No. Size I Sch. T/0 Wt. 80268 3"x 3"x 2" 80 111311111111 3/4" 80220 I 1"x 3/4" 40 � '/8" ( 0.08 lb. Mg 802693 •. 3" x3"x2/z 80 1 /, 13/4" 115/,9" 2.44 gym.. IT!0 Sprinkler Head Adapter ��I _ Sprinkler Head Adapter with Brass Threaded Insert �. with Brass Threaded Insert ���— Part No. Size 1 Sch. T/O 1 Wt. Part No. Size Sch. T/O 1 Wt. 80175E 3/4"x '/2" NPT 80 7/1e" 0.20 lb. 80175W 3/4"x 1/2" NPT 40 7/16" 0.19 lb. 80176E 1"x '/2" NPT 80 716" 0.22 lb. 80176W 1"x'/2" NPT 40 7/16" 0.18 lb. 80177WL 3/4"x '/2" NPT 40 9/16" 0.16 lb. 80179 1 x 3/4" NPT 40 3/4" 0.43 lb. T/0' iiT/0 ' Back-to-Back Cross i i Sprinkler Head Adapterakm ��_ _�� - (Spigot with Brass Threaded Insert �- = + 111 T!O �. with Brass Threaded Insert 1 Part No. Size Sch. T/O Wt. T/0 rro' 80177E 3/4"x 1/2" NPT 40 1/2" 0.16 lb. No. Size Sch. 1 2 lb. 80178 1"x 1/2"NPT 40 '/2" 0.20 lb. Part 80462 1"x 1"x'/2"NPT x '/2"NPT 40 5/e"TIO Wt.11/6" 0.46 80463 1"x 1"x1/2"NPT x1/2"NPT 40 5/e" 15/,6" 0.47 ism rro' � Sprinkler Head Adapter ,' 1 90° Elbowsti, I R 11 with Brass Threaded Insert �� T!°' Back-to-Back Tee r7ro "" ` I '"'' iniwith Brass Threaded Insert I �C ' ,! i rro: Tr0' Part T/O Wt. Part Size No Size Sch Sch. T/O Wt. _ - -- 1 2 _lb, _ _ ._._ No. -— - — -1 - —2- --lb.--- ( 80199 3/i'x '/2" NPT 40 5/6" 15/+6" 0.20 80459 1"x'/2"NPT x 1/2"NPT 40 "/s' 5 80189 1"x 1/2" NPT 40 13/,6" 13/16" 0.261 /,6" 0.48 80460 1"x'/2"NPTx'/2"NPT 40 "/,e" 11/6" 0.46 • • Part T/O Wt. No. Size Sch. 1 2 3 lb. 80250 3/4"x 3/4"x'/2"NPT 40 5/6" 5/6" 1" 0.22 80251 1"x 1"x1/2"NPT 40 "/,6" "/,6" 13/,6" 0.29 ' 80249 1"x 1 x 1"NPT 40 15/,6" 1 " 5 7 ^ Sprinkler Head Adapter 4U3/ I /,6' 1 /,6 0.73 rio' 80256 1'/4"x 1"x'/2"NPT 40 7/,6" ,6" 1'/6" 0.30 Tee — - --1 80252 11/4"X 11/4"X'/2"NPT 40 71,6" 7 ' with Brass Threaded Insert r 80257 1'/2"x 1'/4"x1/2"NPT 80 9/,6" 5'/6n 11a" 0.314 / 0.43 no' rio' 80254 172"X 11/2"x 72"NPT 80 '/+6" 9/16" 17/is" 0.46 80258 2"x 11/2"x '/2"NPT 80 72" 5/6" 15/6" 0.56 80253 2"x 2"x1/2"NPT 80 '/2" 1/2" 15/6" 0.62 Limited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten(10)years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten(10)years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse,improper installation.corrosion,or which have not been installed,maintained,modified or repaired in accordance with applicable Standards of the National Fire Protection Association(NFPA),and/or the standards of any other Authorities Having Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced.at Tyco Fire Products sole option. Tyco Fire Products neither assumes,nor authorizes any person to assume for it,any other obligation in connection with the ` sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer's representatives. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE.IN CONTRACT,TORT,STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY,FOR INCIDENTAL INDIRECT.SPECIAL OR CONSEQUENTIAL DAMAGES,INCLUDING BUT NOT LIMITED TO LABOR CHARGES,REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCT'S LIABILITY EXCI:1:.7)AN AMOUNT EQUAL TO THE SALES PRICE.THE FOREGOING fi WARRANTIES OF MERCHANTABILITY Y ANDIS MADE IN MFITUNE S FOR A PARTF ANY AND ICULAR�LAR PUURPPHER OSE��S EXPRESS OR IMPLIED,INCLUDING tLICO/Flow Control/ 0 Fire Products 0 ; : = * -. ler WI 111. ® VANE TYPE WATERFLOW :- ENINIENb- APPROVED SWITCH WITH RETARC Poffier Electric Signal Company 2081 Craig Rd., / St. Louis, MO 63146 / (800)325-3936 / (314)878-432' SERVICE PRESSURE UP TO 450 PSI FOR 2" TO S" PIPE SIZES CHARACTERISTICS 250 PSI FOR 10" PIPE SIZE U.L. LISTED AND F.M. APPROVED MINIMUM FLOW RATE FOR ALARM-10 GPM DIMENSIONS & WEIGHTS: See Fig. 2 ENCLOSURE: Cast Aluminum Finished: Red Enamel CONTACT RATINGS:Two sets of S.P.D.T. (Form C) 15.00 Amp. @ 125/250V. AC 0.50 Amp. 0 125V. DC 0.25 Amp. @ 250V. DC 2.50 Amp. 0 0-30V. DC • Resistive ENVIRONMENTAL LIMITATIONS: 40°F/120°F 4.5°C/49°C � _�_ General Purpose for Indoor Use . CAUTION: This device is not intended for ce... ." applications outdoors or in explosive environments. •.. ��_ SIZES AVAILABLE: U.L. - For Schedule 40 Pipe:2" thru 10" _- For Schedule:30 Pipe: 8" -F.M.---For Schedule-40 Pipe:2"thou 6" For Schedule 30 Pipe: 8" and 10" {` Ai SERVICE USE: Automatic Sprinkler NFPA-13 One or Two Family Dwelling NFPA-13D Central Station NFPA-71 Local NFPA-72A Auxiliary NFPA-72B Remote Station NFPA-72C U.S. Pat. Nos. Proprietary NFPA-72D 3,921,989 12,247 OPTIONAL: Cover Tamper Switch Order Stk. No. 5420220 The Model VSR-D is a vane type waterflow switch for The flow condition must exist for a period of time necessary use on wet sprinkler systems. It is UL Listed for use on steel pipe;schedule 40 sizes 2"thru 10"and schedule to overcome the selected retard period. 30 size B"and has FM approvals for schedule 40 steel ENCLOSURE:The unit is enclosed in a general purpose, indoor use, cast aluminum housing. The cover is held in pipe in sizes 2" thru 6" and schedule 30 pipe in sizes B" and 10", place with two tamper resistant screws which require a spe- cial key for removal.A field installable cover tamper switch The unit may also be used as a sectional waterflow is available as an option which may be used to indicate detector on large systems. unauthorized removal of the cover. See Bulletin 751 for installation instructions of this switch. The unit contains two single pole, double throw, snap RETARD ADJUSTMENT: The unit has an adjustable action switches and an adjustable pneumatic retard. pneumatic retard to prevent false alarms due to water The switches are actuated when a flow of 10 gallons surges.The retard is adjustable from 0 to approximately 75 per minute or more occurs downstream of the device. seconds. 2-88 1 CAT.#A010 PAGE 1 __ _ .. R.D ,. Potter Electric Signal Company 2081 Craig Rd., / P.O.Box 28480 / St. Louis,MO 63146 / FAX: 314 878 7264 * VSR-D INSTALLATION �(�` 1 FACTORY ADJUSTED SENSITIVITY SPRING. RETARD ADJUSTMENT DO NOT ADJUST TO CHANGE TIME TURN KNOB (EITHER DIRECTION)FOR I' DESIRED TIME DELAY. II,� USE THE MINIMUM AMOUNT ♦ / ALTERNATELY OF RETARD NECESSARY TO �� TO AN PREVENT FALSE ALARMS. -;:414011).1 '�' • EVENTUAL 50 FT.-LBS. A'S'SETTING IS USUALLY 471 �` OF TORQUE. ADEQUATE FOR THIS. / y �.�IMOUNT ON PIPE SO .� ARROW ON SADDLE POINTS IN DIRECTION OF WATERFLOW. TO INSTALL � d ROLL PADDLE IN FOR 2"AND 2 V2"SIZES OPPOSITE DIRECTION DRILL I (/4"HOLE. 4P OF WATERFLOW, 1101 FOR ALL OTHER SIZES ..10 DRILL 2-HOLE a 4I APPROX. RETARD SETTING ON SEC.) o A e c 1-370 E 0 10-25 20-40 35-66 60-70 $0-f0 -,, I, r �w- OPTIONAL: Cow,Tamper thwttch 4111 4101 Order Stk. No.5420220 DIRECTION OF WATERFLAW� It DWG.5400710-306 SWITCH TERMINAL CONNECTIONS • CLAMPING PLATE TERMINAL CAUTION: AN UNINSULATED SECTION OF A SINGLE CONDUCTOR IS NOT PERMIT _ I TED TO BE LOOPED AROUND THE TERMINAL AND SERVE AS TWO -_-_ _ SEPARATE CONNECTIONS.THE WIRE MUST BE SEVERED TO SERVE ‘) ::=1....__INCOMING AS TWO SEPARATE CONNECTIONS,THEREBY PROVIDING SUPERVI- SION OF THE CONNECTION IN THE EVENT THAT THE WIRE BECOMES oUTGorN6�� DISLODGED FROM UNDER TERMINAL. DWG.5400710-31 INSTALLATION INSTRUCTIONS: These devices may Clean the inside of the pipe of all growth or other mate- be mounted in a horizontal or vertical pipe. On horizon- rial for a distance equal to the pipe diameter on either tal pipe they should be installed on the topside of the sideial for a the hole. equal to the pipe diameter on either of hole. pipe where they will be accessible.The units should not be installed within 6 inches of a fitting which changes the Roll the vane so that it maybe inserted into the hole;do direction of the waterflow or within 24 inches of a valve not bend or crease it. Insert the vane so that the arrow or drain. on the saddle points in the direction of the waterflow. Install the saddle strap and tighten nuts alternately to an Drain the system and drill a hole in the pipe using a cir- eventual 50 FT-LBS. of torque. See Fig. 1 above. cular saw in a slow speed drill.The 2"and 21/2"devices require a 11/4" hole; all other sizes require a 2" hole. The vane must not rub the inside of the pipe or bind in any way. TESTING The frequency of testing for the model VSR-D and its associated protective monitoring system should be in accordance with applicable NFPA Standards and/or the authority having jurisdiction,but under no circumstances less than bi-monthly. zr CAT.itA010 PAGE 2 2-88 • t • • 44 TEs TA NDRA _ .) � P y s d � ��r r �.� r �R ry zre r t N ��� ry �'1 ' 11t �,,., vr ri ;J, }� k #" ;t P .- r tl3xar� j4 1�1 Ka u'a 4 t `b fa i� �r � � xt� �'i '�11ysr ( , o E �`' r.9..['. �0 as„, � P t�t �r4�,$ it n�-irk j F 1j�- rl€e� ci L.P,LT/dlO.d7.1 ,SVS^F ty { Pl 1 �.' "'Jb T1J jf VIr ( �S'�,�h� ? Ir '[-� ' a(v • ■ The AGF Manufacturing Co., Inc. Model 1000 has been designed to provide both the Test Function and the Express Drain Function in a multi story installation. • Complies with all requirements of NFPA-13, and NFPA-13R ■ Complies with all requirements of NFPA-13D (HOUSING) • Positive Shut Off = Single Locking Handle • Tapped '/z” for Pressure Gauge • Tamper Resistant Orifice permanently installed • Available with all required Orifices • Orifice size noted on Indicator Plate • Lightweight and compact (1 '/4" weighs 5 lbs.) • 300 PSI Rating • Fused, tempered, tamper resistant Sight Glasses /roll A, • Ij • • • • . •0IS: Ar-_ TEsTANDRAin 3/4 ,1 a 1 " a 1 1/4t1 ' 1 1/2 " 2 ►, - - -— - - * T FM APPROVED PLAN VIEW FRONT VIEW A 1 [ FROM 0 BRANCH si GAUGE OUTLET e \/0111. 0.7riptim �� - PROVIDED al TO DRAIN D 414111111 �' itp(in V1,11: DRAIN STREET EL CD 1 FRONT VIEW/HORIZONTAL INSTALLATION, ���� STREET EL IIll 70 DRAIN Wel_ OR PIPE �,� ; i '��., i 1 F �' TO DRAIN il In -i :T !Im, TFOR RIGHT HAND/STRAIGHT/NSTALTION TO DRAIN NI 1 ®-..._____ __..._ __...__. i...._ IIII III ild MI APPROVALS .M. ....r! • UL and ULC Listed 3/4 ■ FM Approved except " n • NYC BD. of S&A CAL. NO. 720-87-SM ■ CA. State Fire Marshall ORIFICE SIZE PROVIDED--3/8-7/16 -1/2- 77/32-5/8**-3/4** DIMENSIONS—INCHES SIZE A B C D E F G 5 H MATERIAL LIST PART MATERIAL 3/4 5'/16 13/4 23/R 4'/R 33/s 13/4 49/j6 6 /16 HANDLE STEEL STEM ROD BRASS I 5'/16 13/4 23/8 4'/e 33/R 13/4 49/16 65/16 BALL C.P. BRONZE 1 '/a 57/6 13/4 2'/8 45/e 35/,6 115/1e 5'/2 77/16 BODY BRONZE 1 '/2 67/16 13/4 3"116 5'/16 3'/z 23/R 81/16 10'/Ib VALVE SEAT INDICATOR PLATE STEEL GLASS INPREGNATED TEFLON 2 67A6 13/4 3"A6 57/16 3'/z 23/s 8'A6 I07/16 HANDLE LOCK SPRING STEEL SIGHT GLASS (2) FUSED TEMPERED GLASS ** Available on 1'A"to 2"size units only. AGF MFG. CO. JOB NAME: (" • Box 4437, 150 Mt. Bethel Rd. '-� _ Warren, N.J. 07059-0437 ARCHITECT: Telephone (908) 604-6471 MADE IN ll SA. ENGINEER: Fax (908) 604-6501 CONTRACTOR: 1000 8/94 V • 4 CO n ILILCO INCORPORATED CORONA, CA (909)737-5599 0c 6 Fig. 27 & 27A "Stand-Off" Hanger/Restrainer for CPVC Plastic Pipe Size Range- 3/4" & 1" CPVC Plastic Pipe*. Material- Carbon Steel, Pre-Galvanized. "' Function-Designed to be used as a hanger/restrainer**for CPVC piping -'� where the "stand-off" design will ease installation by eliminating the need for `• wood blocking. �, Features: Flared edge design protects CPVC from any rough or abrasive surfaces. / •• Snap-in retainers hold pipe firmly in place during installation. I ,t • The "Stand-Off" design eliminates the need for wood block extension. • Can be installed on horizontal or vertical piping regardless of mounting Fig. 27 surface orientation. • Attaches easily to wood structure with 2 hex head self-threading screws furnished with product. • Installs easily using rechargeable electrical driver with 5/16"sockets, eliminating impact tool damage to pipe 0 Approvals- Underwriters Laboratories Listed in the U.S. (UL) and Canada ° (cUL) to support automatic fire sprinkler systems. Meets and exceeds the ' requirements of NFPA 13, 13R, and 13D. Fig. 27A ' **Important Note When installed in slot opening on Fig.27, Fi 9 :g27A _ _ - provides additional stability and satisfies the Ur.-vertical restraint requirement where needed. o , Order By-Fig. 27: By figure number and CPVC pipe size. \' \\. Fig. 27A: By figure number and CPVC pipe size. �i U.S. and International Patent application in process. if' '4.Jb *for other sizes consult factory. Fig. 27 and Fig. 27/27A have also been tested by U.L. mounted on 3/8" ' composite wood web material (such as TJI Series/Trus Joist MacMillan) Fig. 27/Fig.27A without the use of back up wood blocking. When using Fig.27 &27A in Combination combination on 3/8"web to satisfy the UL requirement for vertical restraint, install 2 reinforcing speed nuts (Fig. 27B). Fig.27B is UL Listed only. when. W/Fic 27A used with Tolco products. EMS FIG.27B w jI — FIG.27 nka W/FIG.27A ■O A III Purl I FIG.27 IE FIG.27 FIG.27 FIG.27 W/FIG.27A FIG.27 El illiV IF...-. (� '1) Typical Applications Itll ��■• :- . • .: :-. ` .. f A . - - ES A 20008 A. • Series 2000 AMES Double Check-Valve Assemblies : FIRE B:WATERWORKST" Sizes: 1/z"-2" (15 60mm) t r W: - "ma�,cc, =_ , tr ... - F sFeatures w1 • Ease of maintenance with only one:;: - cover : 2"200• • 013 HC • Top entry - _ (50mm) • Replaceable:seats and seat:discs • Modular construction .:',.f','.68"6. • t design ' I4 /ai::.,.,:, n 1/22" (15 J.50mm)-Cast bronze' s"'n x M body construction • Top mounted`bal(valve test cocks f"20008 ,. Low pressure drop_, • -- . -- -., • No special tools required Series 20008 Double Check Valve Assemblies shall be• ,.:1 installed at referenced cross con • 1/2"-1 ' (15-25 mm)have nections to prevent the backflow of polluted water into the potable water supply.Only tee handles • those cross-connections identified by local inspection authorities as non-health hazard shall be allowed the use of an approved double check valve assembly. Check with local authority having jurisdiction regarding vertical orientation, frequency of Available Models testing or other installation requirements. Suffix: These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are _B_Quarter turn_ball valves approved by_the Eoundatior_for Cross_Connection_Control and.Hydraulic.Research_at the LBV- less ball valves -University-Of Stilt-hem-California.- LH- locking handle ball valves(open • position) • ' Specifications SH- stainless steel ball valve handles A Double Check Valve Assembly shall be installed at each noted location.The assembly • HC- 2W inlet/outlet fire hydrant fitting shall consist of two positive seating check modules with captured springs and rubber seat • (2"valve) discs.The check module seats and seat discs shall be replaceable.Service of all internal Prefix: components shall be through a single access cover secured with stainless steel bolts.The U .union connections assembly shall also include two resilient seated isolation valves and four top mounted, re- silient seated test cocks.The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std.C510.Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.Assembly shall be an Ames Pressure — Temperature Temperature Range:33°F-140°F Company Series 20008 (5°C-60°C) Approvals . Maximum Working Pressure: 175psi (12 bars) t ASSE, IAPMO,CSA,UPC A Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Standards • Model LBV is not listed. ASSE Std. 1015,AWWA Std. C510 u UL Classified(LBV models only)3/4"-2"(19-50mm) ID e IAPMO PS31, CSA 864.5 * Horizontal and vertical"flow up"approval on all sizes. `� Ij® &o PP Job Name Contractor Job Location Approval Engineer Contractor's P.O.No. Approval Representative Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.com a Dimensions -. Weic-itc iiiik I. A �� .._ �r.�..► • "annul MINIIIII1-4 IL���- 4 ,M*Qlj F - H _►<- i G Suffix HC-Fire Hydrant Fittings dimension"A"=231/(594mm) Size(DN) A B Dimensions Model in. mm in. mm in. mm in. C mm in. F mm in. G H I Weight 20008 �/ 15 10 254 4% 117 27,116 62 3% 85 mm in. mm in.59 / mm lbs. kgs. 20008 M3 % 20 1111A 282 4 102 31 79 6/16 157 3%6 87 2% 54 1/16 33 4 5 2.3 20008 1 25 13' 337 51/6 130 4 102 71% 191 3% 85 171/6 43 111/16 43 12 4 20008 111 32 16% 416 5 127 36/16 84 9%z 241 5 127 3 5.4 50 15 6.8 20008 11 40 16% 425 4% 124 31% 89 9% 248 513/6 148 31/6 79 21A6 68 15.86 7.2 20008 2 50 19% 495 6% 159 4 102 13% 340 6% 156 376 87 211/6 68 25.75 11.7 Strainer sold separately Capacities As compiled from documented Foundation for Cross-Connection Control ba 1 psis 4 ��� (32mm) and Hydraulic Research at the University of Southern California lab tests. y .8 12 "Typical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.) .7o 5 10 8 d .5 8 a�,. bars psi %"(15mm) ` _ J .7 10 I= a.- .3 4 ���I����1♦����� .1 2 i 0 .4 6 MEl� a 0 6 Cl) .3 4 eP 0 10 20 30 40 50 CO .1 2; 0 38 76 114 152 10 28 266 304 342 380 418 456 ippm x 5_ 7.5-_ 10 __-_15 0 2 fps -' 4 610 12 1:5 2 3 3.0 4.6 mps • AP 0 7.6 15.2 22.8 30.4 38 45.61ppm m Flow Rate 5 7.5 10 fps bars psi 11.h"(40mm) 1.5 2.3 3.0 p W .8 12 bars psi %"(20mm) Flow Rate m s y • m 1.5 22 * o .7 10 J o� 1.2' 18 ., .4 6 es I. ____.5 8 -... N .96 14 m .3 4 a .69 10 'i .1 2 a) n`. .41 6 ep0 10 20 30 40 50 60 70 80 90 700 110 120 gpm . 4 2 0 38 76 114 152 190 228 266 304 342 300 418 456 1pm 0 5 10 .15 20 25 30 35 40 45 50 gpm 5 7.5 10 15 fps AP 0 19 38 57 76 95 114 133 152 171 1901pm 1.5 2.3 3.0 4.6 mps 7.5 15 fps Flow Rate 2.3 4,6 mps bars psi 2"(50mm) bars psi 7"(25mm) * Flow Rate co8 12 y 1.1 16 p 7 10 ■ 8 12 IIIIl_ J5 8d.46 ==== m 3 2 illumine I .3 4 ���lm 1 Z D 1 2 ���=���r o- 0 0 AP 0 95 190 285 380 475 570 665 760 m p0 25 50 75 100 125 150 175 200 pm e 0 5 10 15 20 25 30 35 40 P 0 19 38 57 76 95 114 133 152 171 190 550 228 1pmp 5 7.5 10 15 fps 5 7.5 10 15 1.5 2.3 3.0 4.6 mps 1.5 2.3 3.0 4.6 Ips mps Flow Rate Flow Rate i. IMPORTANT Inquire with governing authorities for local installation requirements. t AMES I 'FIRE&WATERWORKS A Division of Watts Industries _ A. il 9001 I www.amesfirewater.com CERTIFIED 875 National Drive • Suite #107 . Sacramento, CA 95834 • Phone: 916-928-0123 • Fax: 916-928-9333 L� ES-A-2000B 0313 ©Ames Co.2003 Printed in U.S.A.