Report (56) 0602_1 �3 7'1 s�> G��s4 S� . RECEIVED • •� Ea 1 o zois �; A( vA1 R'�, �OFTIGARD FIRE PROTECTION, i " ��NGDIVISION 9095 S.W. Burnham Tigard, OR 97223 • VERIZON WASH SQ 9355 SW WASHINGTON SQ RD #R05-07 TIGARD, OR 97223 FIRE PROTECTION EQUIPMENT SUBMITTAL tico Worldwide Contacts www.tyco-fire.com Series RFII — 5.6 K-factor "Royal Flush II" Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General stallation or finish. The tip of the Pro- tective Cap can be used to mark the Description center of the ceiling hole into plaster p board or ceiling tiles by gently push- q The TYCO Series RFII 5.6 K-factor, ing the ceiling product against the Pro- "Royal Flush II" Concealed Pendent tective Cap. When ceiling installation Sprinklers Quick Response (3-mm is complete, the Protective Cap is re bulb) and Standard Response (5-mm moved and the Cover Plate/Retainer w Assemblyis installed. bulb), are decorative sprinklers featur- ing a flat cover plate designed to con- As an option,the Series RFII Standard ceal the sprinkler.These sprinklers are Response(5-mm bulb)"Royal Flush II" optimal for architecturally sensitive ar- Concealed Pendent Sprinklers can be eas such as hotel lobbies,office build- fitted with a silicone Air and Dust Seal. ings,churches,and restaurants. (Refer to Figure 5.) The Air and Dust ' TY3531 (3 mm Bulb) is UL Listed, includes a Cover Plate/ Seal is intended for sensitive areas Each sprinklerCUL Listed, VdS Approved (Certif where it is desirable toprevent air and icate No. G4090007), and NYC Ap Retainer Assembly and a Sprinkler/ proved (MEA 353-01-E as Quick Support Assembly. separa- dust from the area above the ceiling to ) pp Cup Y p through the late. Response. ble, two-piece assembly design pro- passg cover p vides the following benefits: • TY3531 (3-mm Bulb) is FM and NOTICE LPCB Approved (Ref. No. 094a/10) • Allows installation of the sprinklers The Series RFII Concealed Pendent Approved as Standard Response. and pressure testing of the fire pro- Factory Mutual and LPCB do not tection system prior to installation Sprinklers described herein must be approve any concealed sprinklers of a suspended ceilingor lica installed and maintained in compli- • P pP for quick response. tion of the finish coating to a fixed ante with this document and with the ceiling. applicable standards of the National • TY3551 (5-mm Bulb) is UL Listed, Fire Protection Association, in addi- C-UL Listed, FM Approved, LPCB • Permits the removal of suspended tion to the standards of any authori- Approved (Ref. No. 094a/9), and ceiling panels for access to building ties having jurisdiction.Failure to do so NYC Approved (MEA 353-01-E) as service equipment without having may impair the performance of these Standard Response. to first shut down the fire protection devices. system and remove sprinklers. Approvals for Air and Dust Seal The owner is responsible for maintain- UL and C-UL Listed for use with the • Provides for 1/2 inch (12,7 mm) of ing their fire protection system and de- RFII Standard Response Concealed vertical adjustment to allow a mea- vices in proper operating condition. Sprinkler(TY3551). sure of flexibility in determining the The installing contractor or sprinkler length of fixed piping to cut for the manufacturer should be contacted Maximum Working Pressure sprinkler drops. with any questions. Maximum 250 psi (17,3 bar) by UL, The Series RFII Sprinklers are shipped C-UL,and NYC with a Disposable Protective Cap.The Sprinkler Protective Cap is temporarily removed p Maximum 175 psi (12,1 bar) by FM, during installation and replaced to help Identification VdS,and LPCB protect the sprinkler during ceiling in- Temperature Rating Number (SIN) 155°F(68°C)Sprinkler with IMPORTANT TY3531 3 mm bulb 139°F(59°C)Plate — Always refer to Technical Data 200°F(93°C)Sprinkler with Sheet TFP700 for the "INSTALLER TY3551 — 5 mm bulb 0°16F (74°C)Srinkl Plate WARNING" that provides cautions with respect to handling and instal- Technical Discharge Coefficient lation of sprinkler systems and corn- K=5.6 GPM/psiv2(80,6 LPM/bar1/2) ponents. Improper handling and in- Data stallation can permanently damage Adjustment a sprinkler system or its components Sprinkler Approvals 1/2 inch(12,7 mm) and cause the sprinkler to fail to Approvals apply only to the service - operate in a fire situation or cause it conditions indicated in the Design Cri- Finishes to operate prematurely. teria section. See the Ordering Procedure section. Page 1 of 4 MARCH 2013 TFP181 TFP181 Page 2 of 4 Physical Characteristics 1/2" NPT Jr rSEALING Frame Bronze ASSEMBLY Support Cup Chrome Plated Steel Guide Pins Stainless Steel FRAME I, \ , ' Deflector Bronze j Compression Screw Brass 1 1 . • /,, \. ` ` CAP Bulb Glass %� I • Cap Bronze or Copper SUPPORT Sealing Assembly Beryllium CUP WITH I BULB Nickel w/TEFLON ROLL FORMED Cover Plate Brass THREADS Retainer Brass Ejection Spring Stainless Steelr 7 1 COMPRESSION Design _ SCREW GUIDE i r $ Criteria PINS(2) - The TYCO Series RFII 5.6 K-factor, DEFLECTOR "Royal Flush II" Concealed Pendent , (DROPPED Sprinklers are intended for fire protec- DEFLECTOR �- 1� I --�% POSITION) tion systems designed in accordance I - r ti-�- with the standard installation rules rec- ognized by the applicable Listing or I SPRINKLER/SUPPORT CUP Approval agency;for example, UL List- ASSEMBLY ing is based on NFPA 13 and VdS Ap- proval is based on the CEA 4001. THREAD INTO P I RETAINER For more information on LPCB and SUPPORT I I WITH THREAD Approvals, CUP contact Tyco Fire Pro- MOUNTING Y , O O DIMPLES VdS tection Products at the following office: SURFACE IS EJECTION Enschede,Netherlands FLUSH WITH SPRING Telephone:31-53-428-4444 CEILING Fax:31-53-428-3377 The Series RFII Concealed Pendent J L ---- Sprinklers are only listed and approved !ter with the Series RFII Concealed Cover / Plates having a factory applied finish. SOLDER J COVER TABS(3) COVER PLATE/RETAINER PLATE NOTICE ASSEMBLY Do not use the Series RFII in applica- FIGURE 1 tions where the air pressure above MODEL RFII CONCEALED SPRINKLER the ceiling is greater than that be- ASSEMBLY low. Down drafts through the Sprin- kler/Support Cup Assembly can delay Installation Do not attempt to compensate for in- sprinkler operation in a fire situation. sufficient adjustment in the Sprinkler The TYCO Series RFII 5.6 K-factor, by under-or over-tightening the Sprin- Operation "Royal Flush II" Concealed Pendent kler/Support Cup Assembly. Re-adjust p Sprinklers must be installed in accor- the position of the sprinkler fitting to When exposed to heat from a fire, the dance with this section. suit. Cover Plate, normally soldered to the General Instructions Step 1. Install the sprinkler only in the Retainer at three points, falls ppoat away Do not install any bulb-type sprinkler if of thenst pr nklernperlpend perpendicular th the center-line the expose the Sprinkler/Support the bulb is cracked or there is a loss Assembly. Cup mounting surface. of liquid from the bulb. With the sprin- Step 2. Remove the Protective Cap. The Deflector — supported by the kler held horizontally, a small air bub- Guide Pins — then drops down to its ble should be present. The diameter Step 3. With pipe thread sealant ap- operational position. of the air bubble is approximately 1/16 plied to the pipe threads, hand-tighten The glass bulb contains a fluid that ex- inch (1,6 mm)for the 155°F(68°C)and the sprinkler into the sprinkler fitting. pands when exposed to heat. When 3/32 inch(2,4 mm)for the 200°F(93°C) Step 4. Wrench-tighten the sprinkler temperature ratings. using only the RFII Sprinkler Wrench. the rated temperature is reached, the (Refer to Figure 3.) Apply the RFII fluid expands sufficiently to shatter the A leak-tight 1/2 inch NPT sprinkler joint Sprinkler Wrench to the Sprinkler as glass bulb, activating the sprinkler and should be obtained by applying a min- shown in Figure 3. allowing water to flow. imum to maximum torque of 7 to 14 Step 5. Replace the Protective Cap ft.-lbs. (9,5 to 19,0 Nm). Higher levels by pushing it upwards until it bottoms of torque can distort the sprinkler In- out against the Support Cup. (Refer let with consequent leakage or impair- to Figure 4.)The Protective Cap helps ment of the sprinkler. prevent damage to the Deflector and TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE CLEARANCE SPRINKLER DIAMETER ._ f HOLE FITTING DIMENSION C > SPRINKLER ��MMUM SUPPORT CUP ASSEMBLY I �, 1 t , 1/2"(12,7 mm) I THREADED D ADJUSTMENT A I IFililli��� � FACE OF CEILING, i, RETAINING RING •�/ MOUNTING 4 /j SURFACE / A \ I I FIGURE 4 � DISPOSABLE PROTECTIVE CAP I ‘.\-- ' .. .111.__JI Z—. I I 1 Arms during ceiling installation and/or finish.You can also use the Protective I - T -`-� Cap to locate the center of the clear- 3/16"to 11/16" MANUFACTURER DEFLECTOR COVER PLATE ance hole by gently pushing the ceiling (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER material up against the center point of REFERENCE 3/32"(2,4 mm) POSITION ASSEMBLY the Protective Cap. COVER PLATE COVER PLATE NOTICE -PROFILE DEPTH DIAMETER As long as the Protective Cap remains DIMENSION B DIMENSION A in place, the system is considered A:3-1/4 inches(82,6 mm) C:2-3/8 to 2-5/8 inches(60,3 to 66,7 mm) "Out of Service': Step 6.After the ceiling has been com- B:3/16 inches(4,8 mm) D:1-3/4 to 2-1/4 inches(44,5 to 57,2 mm) pleted with the 2-1/2 inch(63,5 mm)di- ameter clearance hole and in prepa- FIGURE 2 ration for installing the Cover Plate/ SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Retainer Assembly, remove and dis- card the Protective Cap.Verify that the Deflector moves up and down freely. If the Sprinkler is damaged and the lel__ FRAME f►tea Deflector does not move up and down freely, replace the entire Sprinkler. ARM \/ �' Do not attempt to modify or repair a ► damaged sprinkler. SUPPORT [a_n_ _ II Step 7. When installing an Air and CUP Dust Seal, refer to Figure 5; otherwise, _ _ Ii proceed to Step 8. To attach the Air IIWI 1.', i and Dust Seal, verify the angle of the r = outside edge of the seal is oriented I■I ac- cording to Figure 5. Start the edge of -- — —- 0 the Retainer in the grooved slot of the 7/8"(23 mm) Air and Dust Seal and continue around SQUARE the retainer until the entire Air and Dust Seal is engaged. Step 8. Screw on the Cover Plate/ ALIGN /...:.<-7,--1-1-1:� Retainer Assembly until the Retainer ARROWS WITH \ (shown in Figure 2)or the Air and Dust FRAME ARMS - 1.1L Seal (shown in Figure 5) contacts the i1 ai ceiling. Do not continue to screw on i i / the Cover Plate/Retainer Assembly ACCEPTS \,-r-- so that it lifts a ceiling panel out of its DRIVE the Cover Plate/Retainer Assembly FIGURE 3 with the Support Cup or you cannot SPRINKLER WRENCH engage the Cover Plate/Retainer As- RFIIsembly sufficiently to contact the ceil- ing, you must reposition the Sprinkler Fitting. TFP181 Page 4 of 4 Care and SUPPORT SPRINKLER FACE OF ORIENT Maintenance CUP CEILING `BEVEL AS �l ___ 'T SHOWN The TYCO Series RFII 5.6 K-fac- PLATE j� ' tor, "Royal Flush II" Concealed Pen- )) RETAINER — dent Sprinklers must be maintainedASSEMBLY ' and serviced in accordance with this :141,1111.11-111111 section. Before closing a fire protection system ` .main control valve for maintenancei ':' !j��� AIR work on the fire protection system that /` ����i / AND DUST I.. i__ .... SEAL it controls, obtain permission to shut �•—-----— �� LIP OF COVER down the affected fire protection sys- RETAINER PLATE tern from the proper authorities and FIGURE 5 notify all personnel who may be affect- OPTIONAL AIR AND DUST SEAL FOR SERIES RFII(TY3551) ed by this action. Absence of the Cover Plate/Retainer If you must remove a sprinkler, do not Ordering Assembly can delay sprinkler opera- reinstall it or a replacement without re- tion in a fire situation. installing the Cover Plate/Retainer As- Procedure When properly installed, there is a sembly. If a Cover Plate/Retainer As- nominal 3/32 inch(2,4 mm)air gap be- sembly becomes dislodged during Contact your local distributor for tween the lip of the Cover Plate and the service,replace it immediately. availability. When placing an order, ceiling,as shown in Figure 2. The owner is responsible for the in- indicate the full product name. specThis air gap is necessary for proper their ire testing, and maintenance of Sprinkler/Support Cup Assembly operation the If the ceil- their fire protection system and devic- op requires of the sprinkler.after If sprinkler es in compliance with this document, Specify: Series RFII (specify SIN), ing thatng atha new paint as well as with the applicable stan- K=5.6, "Royal Flush II" Pendent Sprin- installation,does noseal ensureff any othe air gap. dards of the National Fire Protection klers (specify) temperature rating and Association(e.g.,NFPA 25), in addition (specify)finish, P/N(specify). Do not pull the Cover Plate relative to to the standards of any other authori- the Enclosure.Separation may result. ties having jurisdiction.Contact the in- 155°F(68°C) 200°F(93°C) Sprinklers which are found to be leak- stalling contractor or sprinkler manu- TY3531 51-792-1-155 51-792-1-200 pfacturer regarding any questions. TY3551 51-I90-1-155 51-790-1-200 ing or exhibiting visible signs of corro- sion must be replaced. Automatic sprinkler systems should be Separately Ordered Cover Plate/ inspected,tested,and maintained by a Retainer Assembly: Automatic sprinklers must never be qualified Inspection Service in accor- painted, plated, coated, or other- dance with local requirements and/or Specify: (temperature rating from be- wise altered after leaving the factory. national code. low) Series RFII Concealed Cover Modified sprinklers must be replaced. Plate with(finish),P/N(specify). Sprinklers that have been exposed to 139°F(59°C)(a) 165°F(74°C)(b) corrosive products of combustion, but Grey White have not operated,should be replaced (RAL9002) 56-792-0-135 56-792-0-165 if they cannot be completely cleaned Brass 56-792-1-135 56-792-1-165 by wiping the sprinkler with a cloth or Pure White(c) by brushing it with a soft bristle brush. (RAL9010) 56-792-3-135 56-792-3-165 Signal White Care must be exercised to avoid darn- (RAL9003) 56-792-4-135 56-792-4-165 age to the sprinklers - before, during, Jet Black and after installation. Sprinklers dam- (RAL9005) 56-792-6-135 59-792-6-165 aged by dropping, striking, wrench Brushed twist/slippage, or the like, must be re- Chrome 56-792-8-135 56-792-8-165 placed.Also,replace any sprinkler that Chrome ss-792-s-135 56-792-9-165 has a cracked bulb or that has lost Custom 56-792-x-13 56-792-x-165 liquid from its bulb. (Ref. Installation (a) For use with 155°F(68°C)sprinklers. Section.) (b) For use with 200°F(93°C)sprinklers. Exercise care to avoid damage to (c) Eastern Hemisphere sales only. sprinklers before, during, and after in- Sprinkler Wrench stallation. Replace sprinklers damaged Specify: RFII Sprinkler Wrench, by dropping, striking,wrench twisting, P/N 56-000-1-075. wrench slipping, or the like. Also, re- place any sprinkler that has a cracked Air and Dust Seal bulb or that has lost liquid from its Specify:Air and Dust Seal, bulb.(Refer to the Installation section.) p P/N 56-908-1-001. GLOBAL HEADQUARTERS 1 1400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright 0 2013 Tyco Fire Products,LP. All rights reserved. t `co TEFLON is trademark of The DuPont Corporation. 'f Eddythread4O A Lightweight Schedule 40 Replacement Pipe That Has a Corrosion Resistance Ratio of 1.0 Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our customers have an option to buy a carefully designed replacement for Schedule 40 that: • Has a Corrosion Resistance Ratio of 1.0 • Has a Pressure Rating of 300 psi • Is Lighter Weight Than Schedule 40 • Is Approved by Factory Mutual and Listed by Underwriters Laboratories • Is Produced in Accordance to ASTM A-135 and A-795 • Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves • Is Produced From Steel With Excellent Properties of Strength and Threadability • Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems* • Offers Lower Freight Costs EDDYTHREAD 40 SPECIFICATIONS NOMINAL PIPE SIZE(in) WEIGHT Ms/ft) I.D. (in) BUNDLE SIZE 1, 1.461 1.083 1 1/4 2.070 1.418 51 1 1/2 2.547 1.654 44 2 3.308 2.123 30 CORROSION RESISTANCE RATIOS NOMINAL PIPE SIZE(in) SCHEDULE 40 EDDYTHREAD EAD 40 1 1.00 1.00 1 1/4 1.00 1.00 1 1/2 1.00 1.00 2 1.00 1.00 *Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems . ..::4. -a'AR;*ms,:.,... rrkKK, xm v m;..s..rr.:a-..uifla„+=-+w..4.e ..«..-:...... ..va--.»-..,...<.v-.-+»n-.'m^c...eexr-+fc•mz?:s. -w,.,., w ea im ...qc, Fnr w •� 1819 Clarkson Road For additional information, 1F•+►`-�-�) Chesterfield,MO 63017 contact your salesperson today at C u� aS LW, IIc Nv (800)325-4467 (800)325-4467 or(636)537-2600 USTED BUJ-IVIOOSE TUBEFAX:(636)537-2645 in the USA,or from Canada www.bullmoosetube.com call(800)882-4666 411> A OP�company e-mail:sales@bullmoosetube.com APPROVED All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 .$Ci . Ductile Iron Fittings - Class 300 UL/FM Q > ._ cooS APPROVED LISTED Fig. 35E 3-90°Elbow Size A Packing Weight �,..,� Part Number ` in in Inner Master lb 111___+`i 1/2 35E 3004 1.13 100 200 0.2 3/4 35E 3006 1.31 70 140 0.3 A 1 35E 3010 1.50 40 80 0.5 1-1/4 35E 3012 1.75 25 ,50 0.8 1-1/2 35E 3014 1.94 18 36 1.1 2 35E 3020 2.25 10 = 20 1.8 2-1/2 35E 3024 2.70 4 8 3.2 Fig. 35RE3-90°Reducing Elbow 11111 . B Size A B Packing Weight Part Number w in 3/4 x 1/2 35RE300600 �n in Inner Master lb 4 1.22 80 I� 1 x 1/2 - 35RE3010004 1.20 1.26 1.36 70 160 0.3 140 0.4 1 x 3/4 35RE3010006 1.38 1.45 50 100 0.4 a' A 1-1/4 x 1/2 35RE3012004 1.34 1.53 35 70 0.5 1-1/4 x 3/4 35RE3012006 1.45 1.63 35 70 0.6 1-1/4 x 1 , „,35RE3012010 1.58„ 1.67 30 4;60 =,,; _0.7 1-1/2x 1/2 35RE3014004 1.52 1.75 30 60 0.6 ,;1-1/2,x 3/4 .,35RE3014006 x,1.52. 1.75 . m 25 • 50 5,.7 1-1/2 x 1 35RE3014010 1.65 1.80 20 40 0.8 1-1/2 x 1-1/4 - 15_9Q014/012 ', 1.82 1.88.A; , 18 , 74.36 s 4.0 2 x 1/2 35RE3020004 1.60 1.97 18 36 1.0 2$:3/4 35RE5020006 1.60 '4.97.',,,,I 18 ' :36 .,. 4.0 2 x 1 35RE3020010 1.73 2.02 16 32 1.2 2 x 1-1/4 w35RE302O012 1.90 r II 2.10 - 12* 24 , t3 2 x 1-1/2 35RE3020014 2.02 2.16 10 20 1.5 2-1/2 x 1-1/2 3513E3024014 2.16' III 251 7312. 6M 12 2.2 a, 2-1/2 x 2 35RE3024020 2.39 2.60 6 12 2.5 a^ ""1 Fig. 35F 3-45°Elbow Size 4: l A A. ' ' Packing Height A in Part Number in :,Inner Master lb a�~' , 1/2 35F 3004 0.88 150 300 0.2 . 3/4 35�3006 998 80 160 0 o, 0,„416 1 35F 3010 1.13 40 80 0 5 1-1/4 35F 3912 1.29* ,. 25 ,i t. Q. 0.7~a hint �A 1-1/2 35F3014 1.44 20 40 10 35F 3020~ 1,,1.6,4 ! 410 44. 0 1 1 2-1/2 35F 3024 1.95 4 8 2.7 Fig. 35T 3- Tee Size n A Packing lit u Weight Part Number 1 in in _- Inner x- Master =, lb 1/2 35T 3004 1.13 80 160 0.3 I 3/4 3513006 1.31 .30 , .,<. .60 0.5 ---- I-- - 1 35T 3010 1.50 25 50 0.7 1-1/4 357 3012 1,75, 10 1h gp 1.1 li a , A I A 1-1/2 35T3014 1.94 10 20 1.5 2 35I,430-1, £. .4....„2.25 ,- 6 12 z 2.4 2-1/2 35T 3024 2.70 4 8 4.3 111 SMITH-COOPER INTERNATIONAL`S • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • www.smithcooper.com .S,Ut.. Ductile Iron Fittings - Class 300 UL/FM muff PUS c ® us 11> APPROVED A Fig. 35CP3 -Straight Coupling with Ribs LISTED --_,----may Size Part Number A Packing Weight in in Inner Master lb 1/2 35CP3004 1.38 200 400 0.1 3/4 35CP3006 1,63 10Q 200« , x:0.2 1 35CP3010 1.75 60 120 0.4 1-1/4 35CP3012 2.00 35 70 _ 0.5 1-1/2 35CP3014 2.19 25 50 0.7 2 35CP3020 2.62 15 30 1.2 2-1/2 35CP3024 3.00 9 18 2.2 Fig. 35RC3 -Hex Reducing Coupling it Size A Part Number Packing Weight N = in in Inner' Master lb ® IA 1 x 1/2 35R03010004 1.69 80 160 0.3 1x3/4 35RC3010006 1.69 60 120 0.4 1-1/4 x 3/4 35RC3012006 2.06 40 80 0.6 2 x 1(not hex) 35RC3020010 2.81 20 40 1.0 Fig. 35HB3 -Hex Bushing Size - part Number Ate...: Packing Weight B in in Inner. Master lb 1 x 1/2 35HB3010004 1.06 180 360 0.2 i' 1 1 JA 1 x 3/4 35HB3010006 " 106 180 360,, 0.1 iili 1-1/4 x 1 35HB3012010 1.19 90 180 0.2 1-1/2 x 1 35H63014010 125 w 7 , 150 , 0.4 1-1/2 x 1 1/4 35H93014012 1.25 75 150 0.3 I 2 x 1 3511133020010 1.38_ 40 80 ' 0.6 2 x 1-1/4 35HB3020012 1.38 40 80 0.6 2 x 1-112 35H63020014 ' .1.38 40 80 - 0.6 1`l:::� ri Fig. 355P3 -Square Head Plug Size A Packing Weight Part Number in. .: '_; in Inner Master' lb .. p 1/2 35SP3004 0.94 600 1200 0.07 IN' Hsi i A 3(4 35SP'3006 1.12 350 700,~ 0.1 I 1 35SP3010 1.25 200 400 0.1 I 1-1/4 35SP3012 1.37 100 200 0.3 1-1/2 35SP3014 1.44 80 160 0.4 2 35S03020 '1.50 . 45 ; 90 °-: .:; 0.6 Fig. 35U 3-Union with Brass Seat A Size A Packing k°: Weight Part Number = in in Inner Master ' lb 1 35U 3010 2.19 20 40 1.0 �� 111) 1-1/4 ., 35U3012 " k�, 2,50 15 30 -' x:-1.2 "'"' 1-1/2 35U 3014 2.62 10 20 1.7 '‘kNciE'°a 2 35U 3020 3.12 6 12,x 2.4 issw • 113 SMITH-COOPER INTERNATIONAL' • TOLL FREE 1-800-766-0076 • FAX(323)890-4456 • wwaw.smithcooper.com Pipe Hangers Fig. 200- "Trimline"Adjustable Band Hanger (B-Line Fig.B317ONF) ®TOLCO- Fig. 200F- "Trimline"Adjustable Band Hanger with Felt Lining (B-Line Fig.B3170NFF) Fig. 200C- "Trimline"Adjustable Band Hanger with Plastic Coated (B-Line Fig.B317ONFC) USTED - Fig. 200S - "Trimline"Adjustable Band Hanger with Non-Captured Nut Size Range: Fig. 200 - 1/2" (15mm)thru 8" (200mm)pipe Material: Steel, Pre-Galvanized to G90 specifications Function: For fire sprinkler and other general piping purposes. Knurled -- _ swivel nut design permits hanger adjustment after installation. Features: , ® ;_ • (1/2" (15mm)thru 2" (5omm))Flared edges ease installation for all pipe �`�'► types and protect CPVC plastic pipe from abrasion. Captured design - "' '' keeps adjusting nut from separating with hanger. Hanger is easily n s installed around pipe. A \ For hanger with non-captured nut order Fig. 200S. • (21/2" (65mm)thru 8" (20omm)) Spring tension on nut holds it securely in � - :, - hanger before installation.Adjusting nut is easily removed. Approvals: Underwriters Laboratories listed(1/2" (15mm)thru 8" (2oomm)) Fig 200+h 200-3/4 in the USA(UL)and Canada(cUL)for steel and CPVC plastic pipe and Factory Mutual Engineering Approved(FM)(3/4" (20mm)thru 8" (200mm)). Fig.200-1 to 200-2 Fig.200-21/2 to 200-8 Conforms to Federal Specifications WW-H-171 E&A-A-1192A,Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69&SP-58, ...,- Type 10. Maximum Temperature: 650°F 1343°C) mew Finish: Pre-Galvanized. Stainless Steel 41 materials will be supplied with (2) hex nuts - °x' in place of a knurl nut. °' Order By: Figure number and pipe size , , I I Designed to meet or exceed requirements of r .3 : FMDS2-0. Fig.200 ', Fig.200C Fig.200F Pipe Size Rod Size A B Approx.Wt./100 Part No. in. (mm) in. (mm) in. (nun) lbs. (kg) i. . " 200-1/2 1/2' (15) 3/8' 16 31/8" (79.4) 25/8 1 •11 11 (5.0) 't 200-3/4 3/4" (201 3/a"-16 31/8" (79.41 21/2" (63.51 11 (5.0) 200-1 1" (25) 3/e"-16 33/e (85.7) 25/e (66.7) 12 (5.51 # 200-11/4 11/4" (321 3/8-16 33/4" (94.01 27/a" (73.01 13 (5.91 r' 200-14/2 11/2' (40) 3/e-16 37/8 (98.4) 27/e" (73.0) 14 (6.4) 1 i. J 200-2 2 1501 3/8-16 41/2" (114.3) 3" (76.3) 15 16.91 4,., 200-2'h 21/2" (65) 3/8"-16 55/8" (142.9) 41/8" (104.7) 27 (12.3) 200-3 3" 175) 3/8"-16 51/8" (149.11 4" (101.61 29 (13.31 Fig.200S 200-31/2 31/2" (901 W-16 73/8" (187.3) 51/4" (133.3) 34 (15.6) 200-4 4" (1001 3/8-16 73/8" 1187.31 5" 1127.01 35 (16.01 200-5 5' (125) W-13 91/9 (231.8) 61/4" (158.7) 66 (30.2) 200-6 6" (1501 1/2"-13 101/8" (257.2) 63/4" (171.41 73 133.41 200-8 8" (200) 1/2"-13 131/8" (333.4) 83/4" (222.2) 136 (62.3) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. ■ • B-Line Fire Protection Solutions 21 by E:T•N Threaded Accessories B3205 - Threaded Rod (right-hand threads-both ends) (TOLCO Fig.103) B3205L-Threaded Rod (right&left hand threads) TI. Size Range: 3/8"-16 thru 3"-4 rod Specify Leath Material: Steel TL n: Recommend for use as a haner support in hanger es. Rod is threaded on bothends with right hand threads of the length shown.Also 1l A available with left and right hand threads-specify Fig. B3205L when ordering. mead size Maximum Temperature: 750°F(399°C) Finish: Plain.Contact B-Line for alternative finishes and materials. Order By: Part number,rod size,length and finish Standard Design Load Thread Size Thread Length TL 650°F(343°C) 750°F(399°C) Part No. A in. (mm) Lbs. (kN) Lbs. (kN) B3205-3h X'L' 3/8"-16 21/2" (63.5) 730 (3.25) 572 (2.54) 83205-1/2 x'L' 1/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) 83205-5/8x11.' 5/8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52) 83205-3/4 x'L' 3/4"-10 3" (76.2) 3230 (14.37) 2530 (11.25) B3205-7hx'L' 7/8"-9 31/2" (88.9) 4480 (19.93) 3508 (15.60) B3205-1 x'L' 1"-8 4" (101.6) 5900 (26.24) 4620 (20.55) 83205-11/8 x'L' - 11/8"-7 41/2" (114.3) 7450 (33.14) 5830 (25.93) 83205-11/4 x'L' 11/4"-7 5" (127.0) 9500 (42.25) 7440 (33.09) B3205-11/2 x'L' . 11/2"-6 6" (152.4) 13800 (61.38) 10807 (48.07) 83205-13/4 x'L' 13/4"-5 7" (177.8) 18600 (82.73) 14566 (64.79) 83205-2 x'L', . :, 2"-41/2 8" (203.2) 24600 (109.42) 19625 (87.29) B3205-21/4 x'L' 21/4"-41/2 9" (228.6) 32300 (143.67) 25295 (112.51) B3205-21/2 x11.' 21/2"-4 10" (254.0) 39800 (177.03) 31169 (138.64) 83205-23/4x'L' 23/4"-4 11" (279.4) 49400 (219.73) 38687 (172.08) B3205-3 x'L'; 3"-4 12" (304.8) 60100 (267.32) 47066 (209.35) ATR -All Threaded Rod 120" (3.05m)Lengths (TOLCO Fig.100) Fig. 99 -All Threaded Rod Cut To Length �I') lllli1`l G11�\ Size Range: 3/8"-16 thru 11/2"-6 rod in 120"(3.05m)lengths or cut to length ���4����1�1111)�'i''' Material: Steel ��� Maximum Temperature: 750°F(399°C) % &K- Finish: Plain.Contact B-Line for alternative finishes and materials. r. � U. Order By: Part number,rod diameter and finish &.. Part No.-Size x Length Threads Recommended Load Approx.Wt./100 Ft. ATR Fig.99 Per Inch Lbs. (kN) Lbs. (kg) "ATR 1/4".x 120 ' ;';,99-1/4"X length 20 240 (1.07) 12 (5.44) ATR 3h'x 120 99-3/"x length 16 730 (3.24) 29 (13.15) ATR 1h",C 120 . . /2"x length 13 1350 (6.00) 53 (24.04) AIR 5h"x 120 ,99.5/8"x length 11 2160 (9.60) 89 (40.37) ATV/4'114120. , x/4"x length 10 3230 (14.37) 123 (55.79) ATR 7/87,4120 ' .'?h"x length 9 4480 (19.93) 170 (77.11) ATR 1'x 120 99-1"x length 8 5900 (26.24) 225 (102.06) All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified. Pipe Hangers&Supports Revised 4/28/2014 Line 236 by E:T•N SAMMY X-PRESS® SAMMYS �R I. Sammy X Presse sProduct Features 4 111 •The Sammy X-Press expands to provide •Installs in seconds,saving time& ` (XP) direct vertical attachment in: installation costs. v.. Patent No Metal Deck(22-16 gauge) t: ;s r --- 6,935,821 —, '-•s - -Z-Purlin(18-16 gauge) •Use in applications where access >> i to the back of the installed fastener is •The SammyX-Press Swivel allows you prohibited.ie.metal roof deck,tubular I . to hang plumb in extreme roof pitches: steel,or vapor barrier fabric. (SWXP) -89°in Z-Purlin -45°in metal deck for 12/12 pitch •Less jobsite material needed. Patent Pending for •The Sammy X-Press Sidewinder expands •No retaining nut required. to provide horizontal attachment in: 0, "' (SXP) QXt r e -16 ga-3/16"steel-purlin,tubular •Provides design flexibility. °r steel. Patent Pending Variant roof Pitches Rod Part,' . . Ukimate UL Ted- ° .Fr&Test Mtn Max Box -Case .x :, Approvals She member klodet De cn On Load(lbs) Load(lbs), 'Thick Thies City Qty 1/4' 8181922 XP 200 X-Press 200 1146(22 ga) 185(Luminaire) 027" ,125' 25 125 Metal Deck 250(Luminaire) .056• 850(7/:'Pipe) 940(7 Pipe) .027' 185(Lttmilaire) 318' 8150922. XP 20 X-Press ZO 1146(22 ga) 250(Lunitase} , 1475 Pipe) .02T .125' 25 125 M�Deck 283(Conduit&Cable) N(4' .056' e '1500(4 Pipe) .060" •`f 0 3/8' 8153922 XP 35 X-Press 35 1783(16 ga) 85(Luminaire) 940 (2'Pipe) .105" 125' 25 125 Pudin 250(Luminaire) 1475(4'POO .027• `- 416(Conduit&Cable) .056' 750(2'Pipe) .� - 170 vertical(Lumi ialre le' 318' 8294922 SXP 20 Swivel X-Press 20 1061(22 ya Veficaq 80 @ 45'(Lumhake) 635(7 Pipe) 02T .125' 25 125 efal Deck �5,. �'� 829(45'08 Vertices 283 (Corduk&Cable) e .. 233,01.5'(Conduit&Cable) ,,, t, 1500(4'Pipe) 1675(16 ga Vetticl) 250 vertical(Luminaire) Q..• 3/8' 8295922 SXP 35 Swivel X-Press 35 1558(89°OU Vertical) 80 @ 90'(Luminaire) 635(2'Pipe) .060' 125' 25 125 Purlin 500 vertical(Conduit&Cable) 333 @ 89°(Conduit&Cable) — Pre-Pour StructuraiConcrete0 300o psi — i•. 3/8' x 8150922 XP 20 Sammy X-Press 20 1146(22 ga) 850(214 Pipe) 125 25 Metal Deck y„y ''_ Post-Pour(tangs 01WCs ,)'CF(1bs1A')4,- Post-Po 1250(3%”Pipe) E' 3/8' 8293957 SWXP 35 Sidewinder X-Press 35 1798(16 ga) 80(Luminaire) .060' .125' 25 125 Pudin 416(Conduk&Cable) Pre•Pour Structural Concrete 4$3000 psi Poet-Pour Range II LWCS 35 PCF(Ibsr ft') '. ': ' —/-A--/-A.- -.FAii.rA-- el" ---- •, 15A' Er‘.. —r\_'. '- - . -. er! Vrr-W. ti Sammy X Press It° INSTALLATION TOOL UXPIT l , . 4er - :P:S.2,,`:ri:',..:,; Zil i Patent Pending '1.1% -. s'. - -, �x ' i Part _. ' It,--',..'e, ,!„,, .,.‘j,::- ' ..-. N umber Model Description Each Qty 8194910 UXPir UniversaiX-Press it Tod 1 r t • ; 8195910 RXPIT Retro Socket for 8151910 1 " 8152910 XPDB 25f64'Drill Bit 1 To watch a video demonstration of the Sammy X Press,visithttplhvwwsammysuperscrew.com/sammyxpress.htm ' , "Tool Includes Sleeve,Bit Receiver,Hex Wrench,and 2584'Drill Bit. For the most up to date information visit www sammysupetscrew corn 8 1 t--j W t� HS