Loading...
Report (24) +fS -O(S - OoocO 2.073 5& 4i4 RFc •.� •• ' M4R � � � • ***/ WYATT / ; 2015� FIRE PROTECTION, INC. Go/� Ao S/QN 9095 S.W. Burnham Tigard, OR 97223 SOUTHVIEW HEIGHTS LOT 19 12073 SW AUTU M NVI EW STREET TIGARD, OREGON 97223 FIRE PROTECTION EQUIPMENT SUBMITTAL tqccsWorldwide Fire Protection Contacts www.tyco-fire.com Products RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinklers, Flat Plate • Wet Pipe and Dry Pipe Systems General The Series LFII Residential Concealed Pendent Sprinklers(TY3596)has been Description designed with heat sensitivity and wa- ter distribution characteristics proven The TYCO RAPID RESPONSE Se- to help in the control of residential fires ries LFII Residential 4.9 K-factor Con- and to improve the chance for occu- cealed Pendent Sprinklers (TY3596) pants to escape or be evacuated. are decorative, fast response, fus- The Series LFII Residential Concealed ible solder sprinklers designed for use Pendent Sprinklers (TY3596) are s . in residential occupancies such as shipped with a Disposable Protective homes, apartments, dormitories, and Cap. The Protective Cap is temporar- gw hotels. ily removed for installation, and then The cover plate assembly conceals it can be replaced to help protect the the sprinkler operating components sprinkler while the ceiling is being in- NOTICE above the ceiling.The flat profile of the stalled or finished.The tip of the Pro- cover plate provides the optimum aes- tective Cap can also be used to mark The Series LFII Residential Con- thetically appealing sprinkler design. the center of the ceiling hole into plas- cealed Pendent Sprinklers (TY3596) In addition, the concealed design of ter board, ceiling tiles, etc. by gently described herein must be installed the Series LFII Residential Concealed pushing the ceiling product against and maintained in compliance with Pendent Sprinklers (TY3596) provides the Protective Cap. When the ceiling this document and with the applica- 1/2 inch(12,7 mm)vertical adjustment. installation is complete the Protective ble standards of the National Fire Pro- This adjustment provides a measure of Cap is removed and the Cover Plate tection Association, in addition to the flexibility when cutting fixed sprinkler Assembly installed. standards of any authorities having ju- drops. risdiction. Failure to do so may impair Dry Pipe System Application the performance of these devices. The Series LFII Residential Concealed The Series LFII Residential Concealed The owner is responsible for maintain- Sprinklers are intended for use in the Pendent Sprinklers offers a laboratory ing their fire protection system and de- following scenarios: approved option for designing drypipe p 9 9 vices in proper operating condition. residential sprinkler systems,whereas, • wet and dry pipe residential sprin- most residential sprinklers are labora- The installing contractor or sprinkler kler systems for one-and two-fam- tory approved for wet systems only. manufacturer should be contacted ily dwellings and mobile homes per with any questions. NFPA 13D Through extensive testing, it has been • wet and dry pipe residential sprin- determined that the number of design S rinkler kler systems for residential occu- sprinklers (hydraulic design area) for p pancies up to and including four the Series LFII Residential Concealed Identification stories in height per NFPA 13R Pendent Sprinklers(TY3596) need not be increased over the number of de- • wet and dry pipe sprinkler systems sign sprinklers (hydraulic design area) Number for the residential portions of any as specified for wet pipe sprinkler sys- occupancy per NFPA 13 tems, as is accustomed for density/ TY3596 area sprinkler systems designed per NFPA 13. Consequently,the Series LFII Residen- tial Concealed Pendent Sprinklers of- IMPORTANT fer the features of non-water filled pipe in Always refer to Technical Data the nu�mberto ofndes havingsprinklerse - h Sheet TFP700 for the "INSTALLERase design ( e- WARNING" that provides cautions draulic design area) for systems d - signed to NFPA 13, 13D,or 13R. with respect to handling and instal- lation of sprinkler systems and com- ponents.Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 FEBRUARY 2014 TFP442 TFP442 Page 2 of 6 BODY . p SEALING WRENCH (1/2" NPT) ASSEMBLY RECESS CAP 1 "'y —�� L. N SPRINKLER SI i ��=dmi /" WRENCHING REA SADDLE 1 r� _ t \/ SUPPORT 1 s COMPRESSION PUSH WRENCH IN TO ENSURE CUP WITH % I I I SCREW ENGAGEMENT ROLL FORMED i WITH SPRINKLER THREADS WRENCHING AREA LEVER FIGU 11_____11_____ W-TYPERE 128 GUIDE I I SPRINKLER WRENCH PIN �y a SOLDER LINK ELEMENT GUIDE PIN HOUSING DEFLECTOR c �_---- __� ] (OPERATED DEFLECTOR --;_i,-- r POSITION) SPRINKLER/SUPPORT CUP ASSEMBLY THREAD INTO I I RETAINER SUPPORT I i WITH THREAD CUP UNTIL ) I DIMPLES MOUNTING t, 0 O SURFACE IS J FLUSH WITH CEILING EJECTION SPRING SOLDER J COVER PLATE/RETAINER COVER TAB ASSEMBLY PLATE FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER(TY3596) 2-1/2" DIA. SPRINKLER- (63,5(Nm) ~ 1/2"(12,7 mm) FACE OF SUPPORT CUP 1/2" THREADED SPRINKLER ASSEMBLY NPTADJUSTMENT FITTING / OPERATED SPRINKLER �I R 1-7/8"±1/4" COVER _ 47'6 mm PLATE i 1/8"GAP ±6,4 mm) RETAINER � I (3,2 mm) -1-1111-1__1 . i ii COVER- SPRINKLER- I I 7/8"(22,2 mm) I RETAINER SUPPORT CUP MOUNTING 1-1/8"(28,6 mm) ASSEMBLY ASSEMBLY 3/16" SURFACE � � � (4,8 mm) II \ 3-3/16"DIA, DISPOSABLE DEFLECTOR IN (81,0 mm) - TIP PROTECTIVE CAP OPERATED POSITION FIGURE 3 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLER(TY3596) INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR TFP442 Page 3 of 6 Technical Design Criteria Dry Pipe System Water Delivery When using the Series LFII Residen- Data The TYCO RAPID RESPONSE Series tial Concealed Pendent Sprinklers LFII Residential Concealed Pendent (TY3596)in dry pipe sprinkler systems, Sprinklers (TY3596) are UL and C-UL the time for water delivery must not ex Approvals ceed 15 seconds for the most remote UL and C-UL Listed. NYC Approved Listed for installation in accordance operating sprinkler. under MEA 44-03-E-2NSF.Certified to with this section. NSF/ANSI 61. Note: When conditions exist that are Obstruction to Water Distribution The TYCO RAPID RESPONSE Series outside the scope of the provided cri- Sprinklers are to be located in accor- LFII Residential Concealed Pendent teria, refer to the Residential Sprinkler dance with the obstruction rules of Sprinklers are only listed with the Se- Design Guide TFP490 for the manu- NFPA 13D, 13R, and 13 as applicable ries LFII Concealed Cover Plates hav- facturer s recommendations that may for residential sprinklers as well as with ing a factory-applied finish. be acceptable to the authority having the obstruction criteria described with- jurisdiction. in the Technical Data Sheet TFP490. These Cover Plates and their part numbers can be found in the Ordering System Types Operational Sensitivity Procedure section at the end of this Per the UL Listing, wet pipe and dry The sprinklers are to be installed rela- data sheet. pipe systems may be utilized. Per the tive to the ceiling mounting surface as C-UL Listing, only wet pipe systems shown in Figure 3. Maximum Working Pressure may be utilized. 175 psi(12,1 bar) Refer to Technical Data Sheet TFP485 Sprinkler Spacing about the use of residential sprinklers The minimum spacing between sprin- Discharge Coefficient in residential dry pipe systems. klers is 8 feet (2,4 m). The maximum K=4.9 GPM/psi1/2(70,6 LPM/bar'/2) spacing between sprinklers cannot ex- Ceiling Types ceed the length of the coverage area Temperature Rating Smooth flat horizontal, or beamed, or (Ref. Table A or B) being hydraulically 160°F(71°C)Sprinkler with 139°F sloped, in accordance with the 2013 calculated(e.g.,maximum 12 feet for a (59°C)Cover Plate Edition of NFPA 13D, 13R, or 13 as 12 ft.x 12 ft.coverage area, or 20 feet applicable. for a 20 ft.x 20 ft.coverage area). Vertical Adjustment The Series LFII must not be used in 1/2 inch(12,7 mm) Hydraulic Design applications where the air pressure (NFPA 13D and 13R) above the ceiling is greater than that Finishes For systems designed to NFPA 13D below. Down drafts through the Sup- Refer to Ordering Procedure section or NFPA 13R, the minimum required port Cup could delay sprinkler opera- sprinkler flow rates are given in Ta- tion in a fire situation. Physical Characteristics bles A and B as a function of tem- Body Brass perature rating and the maximum Cap Bronze allowable coverage areas. The sprin- Saddle Brass kler flow rate is the minimum re- Sealing Assembly Beryllium quired discharge from each of the Nickel w/TEFLON total number of"design sprinklers" as Soldered Link Halves Nickel specified in NFPA 13D or NFPA 13R. Lever Bronze The number of "design sprinklers" Compression Screw Brass specified in NFPA 13D and 13R for wet Deflector Copper or Brass pipe systems is to be applied when Guide Pin Housing Bronze designing dry pipe systems. Guide Pins Stainless Steel or Bronze Support Cup Steel Hydraulic Design Cover Plate Copper (NFPA 13) Retainer Brass For systems designed to NFPA 13,the Cover Plate Ejection Spring Stainless Steel number of design sprinklers is to be Operation the four most hydraulically demanding sprinklers.The minimum required dis- Wexposed to heat from a fire, the charge from each of the four sprinklers When is to be the greater of the following: Cover Plate, which is normally sol- dered to the Support Cup at three • The flow rates given in Tables A points,falls away to expose the Sprin- and B as a function of temperature kler Assembly. At this point the De- rating and the maximum allowable flector supported by the Arms drops coverage area. • down to its operated position.The fus- • A minimum discharge of 0.1 gpm/ • ible link of the Sprinkler Assembly is ft2 over the"design area"comprised comprised of two link halves that are of the four most hydraulically soldered together with a thin layer of demanding sprinklers for actual solder. When the rated temperature is coverage areas protected by the reached, the solder melts and the two four sprinklers. link halves separate allowing the sprin- kler to activate and flow water. The number of "design sprinklers" specified in NFPA 13 for wet pipe sys- tems is to be applied when designing dry pipe systems. TFP442 Page 4 of 6 WET PIPE SYSTEM Maximum Minimum Flow and Residual Pressurejb.°0 ! Coverage Maximum Ordinary Temp.Rating Area iii Spacing 160°F(71°C) Minimum Ft.x Ft. Ft' Deflector to Installation Spacing (m x m) (m) Flow Pressure Ceiling Type Ft. GPM PSI (m) (L/min) (bar) 12 x 12 12 13 7.0 Smooth (3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to 1-1/8 14 x 14 14 13 7.0 inches (4,3 x 4,3) (4,3) (49,2) (0,48) Beamed 16 x 16 16 13 7.0 Ceilings per 8 (4,9 x 4,9) (4,9) (49,2) (0,48) NFPA 13D or Concealed (2 4) 13R,or 13. Installed in 18 x 18 18 17 12.0 beam (5,5 x 5,5) (5,5) (64,3) (0,83) 7/8 to 1-1/8 inches below 20 x 20 20 20 16.7 bottom of (6,1 x 6,1) (6,1) (75,7) (1,15) beam (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft'over the design area of the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT-PLATE CONCEALED PENDENT SPRINKLER(TY3596) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Minimum Flow and Residual Pressure(bc) Maximum Maximum Coverage Spacing Ordinary Temp.Rating Aream P g 160°F(71°C) Minimum Ft.x Ft. Ft' Deflector to Installation Spacing (m x m) (m) Flow Pressure Ceiling Type Ft. GPM PSI (m) (L/min) (bar) 12 x 12 12 13 7.0 Smooth (3,7 x 3,7) (3,7) (49,2) (0,48) Ceilings 7/8 to 1-1/8 14 x 14 14 14 8.2 inches (4,3 x 4,3) (4.3) (53,0) (0,57) Beamed 16 x 16 16 15 9,4 Ceilings per 8 (4,9 x 4,9) (4.9) (56,8) (0,65) NFPA 13D or Concealed (2 4) 13R,or 13. Installed in 18 x 18 18 18 13.5 beam (5,5 x 5,5) (5,5) (68,1) (0,93) 7/8 to 1-1/8 inches below 20 x 20 20 21 18.4 bottom of - (6,1 x 6,1) (6,1) (79,5) (1,27) beam (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. • (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications;the greater of 0.1 gpm/ft'over the design area of the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM RAPID RESPONSE SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT-PLATE CONCEALED PENDENT(TY3596) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP442 Page 5 of 6 Installation Step 6.Screw on the Cover Plate As- Care must be exercised to avoid dam- sembly until its flange comes in con- age-before, during, and after installa- The TYCO RAPID RESPONSE Series tact with the ceiling. tion.Sprinklers damaged by dropping, LFII Residential Concealed Pendent Do not continue to screw on the Cover striking, wrench twist/slippage, or the Sprinklers (TY3596) must be installed Plate Assembly such that it lifts a cell- like,must be replaced. in accordance with this section. ing panel out of its normal position. The owner is responsible for the in- General Instructions If the Cover Plate Assembly cannot in- spection testing, and maintenance of devic- Damage to the fusible Link Assembly be engaged with the Mounting Cup their fire protection system and during installation can be avoided by or the Cover Plate Assembly cannot des in compliance with this document, handling the sprinkler by the support be engaged sufficiently to contact the ar as dwell as with the applicable stan- cup only(i.e.,do not apply pressure to ceiling, the Sprinkler Fitting must be Association athe National 25),Fire Protection the fusible Link Assembly). repositioned. (e.g., NFPA in addition to the standards of any other authori- A 1/2 inch NPT sprinkler joint should ties having jurisdiction. The installing be obtained with a minimum to maxi- Care and contractor or sprinkler manufacturer mum torque of 7 to 14 ft.-lbs. (9,5 to should be contacted relative to any 19,0 Nm). Higher levels of torque may Maintenance questions. distort the sprinkler inlet with conse- The owner must assure that the sprin- quent leakage or impairment of the The TYCO RAPID RESPONSE Se- kiers are not used for hanging any ob- sprinkler. ries LFII Residential Concealed Pen- jests and that the sprinklers are only Do not attempt to compensate for in- dent Sprinklers (TY3596) must P pcleaned by means of gently dusting sufficient adjustment in the Cover be maintained and serviced in with a feather duster; otherwise, non- Plate/Retainer Assembly by under-or accordance with this section. operation in the event of a fire or inad- over-tightening the Sprinkler. Readjust Before closing a fire protection system vertent operation may result. the position of the sprinkler fitting to main control valve for maintenance Automatic sprinkler systems should be suit. work on the fire protection system inspected,tested,and maintained by a Step 1.The sprinkler must only be in- which it controls, permission to shut qualified Inspection Service in accor- stalled in the pendent position and down the affected fire protection sys- dance with local requirements and/or with the centerline of the sprinkler per- tern must be obtained from the prop- national national codes. pentular to the mounting surface. er authorities and all personnel who may be affected by this action must be Step 2.Remove the Protective Cap, notified. Step 3. With pipe thread sealant ap- Absence of a Cover Plate may de- plied to the pipe threads,and using the lay the sprinkler operation in a fire W-Type 18 Wrench shown in Figure 2, situation. install and tighten the Sprinkler/Sup- When properly installed, there is a port Cup Assembly into the fitting.The nominal 1/8 inch (3,2 mm) air gap be- W-Type 18 Wrench will accept a 1/2 tween the lip of the Cover Plate and inch ratchet drive. the ceiling, as shown in Figure 3.This Step 4.Replace the Protective Cap by air gap is necessary for proper op- pushing it upwards until it bottoms out eration of the sprinkler by allowing against the Support Cup.The Protec- heat flow from a fire to pass below tive Cap helps prevent damage to the and above the Cover Plate to help as- Deflector and Guide Pins during ceil- sure appropriate release of the Cover ing installation and/or during applica- Plate in a fire situation. If the ceiling is tion of the finish coating of the cell- to be repainted after the installation of ing. It may also be used to locate the the Sprinkler, care must be exercised center of the clearance hole by gen- to ensure that the new paint does not tly pushing the ceiling material against seal off any of the air gap. the center point of the Cap. Factory painted Cover Plates must Note: As long as the protective Cap not be repainted. They should be re- remains in place, the system is consid- placed, if necessary, by factory paint- ered to be"Out Of Service" ed units. Non-factory applied paint Step 5. After the ceiling has been may adversely delay or prevent sprin- completed with the 2-1/2 inch(63 mm) kler operation in the event of a fire. diameter clearance hole and in prep- Do not pull the Cover Plate relative to aration for installing the Cover Plate the Enclosure.Separation may result. • Assembly, remove and discard the Sprinklers which are found to be leak- Protective Cap,and verify that the De- ing or exhibiting visible signs of corro- flector moves up and down freely. sion must be replaced. If the Sprinkler has been damaged and Automatic sprinklers must never be the Deflector does not move up and painted, plated, coated, or otherwise down freely, replace the entire Sprin- altered after leaving the factory. Modi- kler assembly.Do not attempt to modi- fled or over heated sprinklers must be fy or repair a damaged sprinkler, replaced. TFP442 Page 6 of 6 Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure When placing an order, indicate the full product name. Contact your local distributor for availability. Sprinkler Assembly Specify: Series LFII (TY3596), K=4.9, Residential Concealed Pendent Sprin- kler without Cover Plate Assembly, P/N 51-112-1-160 Cover Plate Assembly Specify: Cover Plate Assembly hav- ing a (specify) finish for the Series LFII (TY3596), K = 4.9, Residential Concealed Pendent Sprinkler, P/N (specify): Ivory(RAL1015) P/N 56-202-0-135 Beige(RAL1001) P/N 56-202-2-135 Pure White(b)(RAL9010) P/N 56-202-3-135 Signal White(a)(RAL9003) P/N 56-202-4-135 Grey White(RAL9002) P/N 56-202-5-135 Brown(RAL8028) P/N 56-202-6-135 Black(RAL9005) P/N 56-202-7-135 Brushed Brass P/N 56-202-8-135 Brushed Chrome P/N 56-202-9-135 Custom Paint P/N 56-202-X-135 (a)Previously known as Bright White. (b)Eastern Hemisphere sales only. Note: All Custom Cover Plates are painted using Sherwin Williams Interior Latex Paint. Contact TYCO Customer Service with any questions related to custom orders. Sprinkler Wrench Specify: W-Type 18 Sprinkler Wrench, P/N 56-000-1-265 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright®2014 Tyco Fire Products,LP. All rights reserved. two TEFLON is trademark of The DuPont Corporation. Fire Protection Products Vico I Fire & Building Products rapid response HOME FIRE SPRINKLER SYSTEM Technical Services:Tel:(800)381-9312/Fax:(800)791-5500 BlazeMaster ® CPVC Fire Sprinkler Pipe & Fittings Submittal Sheet General TechnicalIit Description Data "? Tyco Fire& Building Products (TFBP) Sizes BlazeMaster CPVC Pipe and Fittings 3/4"to 3" are designed exclusively for use in wet ' pipe automatic fire sprinkler systems. Maximum Working Pressure They are made from a specially devel- oped thermoplastic compound corn- Approvals ¢ posed of post chlorinated polyvinyl UL, FM, CUL, NSF, Dade County, '. ' chloride(CPVC)resin and state of the LPCB,MEA,and the City of Los Ange 4 art additives. TFBP BlazeMaster les. (Refer to IH-1900, Rev. 0, Janu- CPVC products are easier to install ary 2005 "Installation Instruction & than traditional steel pipe systems, Technical Handbook" for exact list- and at the same time,provide superior ing/approval information.) s0'" ${`— heat resistance and strength as corn- Manufacture Source pared to traditional CPVC and PVC U.S.A. piping materials used in the plumbing trade. Various adapters are available Material to connect CPVC pipe to metallic pip- • pipe:ASTM F442, SDR 13.5 ing. All female pipe thread adapters have brass inserts for durability. • Fittings: ASTM F438 (Sch. 40) and Grooved adapters connect directly to ASTM F439(Sch.80),ASTM F1970 grooved end valves and metallic pipe, with flexible grooved end couplings. Color Color Orange WARNING Tyco Fire& Building Products(TFBP) BlazeMaster CPVC Pipe and Fittings described herein must be installed and maintained in compliance with this document, as well as with the applica- ble standards of the National Fire Pro- tection Association, in addition to the standards of any other authorities hav- ing jurisdiction. Failure to do so may impair the performance of these de- _ vices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. BlazeMaster®is a registered trademark of Noveon IP Holding Corp. Page 1 of 6 JANUARY, 2006 TFP1915 Page 2 of 6 TFP1915 WATER NOMINAL AVERAGE AVERAGE WEIGHT FILLED WEIGHT FT.OF PIPE WEIGHT PER LIFT SIZE O.D. I.D. lbs./ft. bsJft PER LIFT lbs. 3/4" 1.050" 0.874" 0.18 0.44 7875 1339 1" 1.315" 1.101' 0.26 0.67 5040 1320 1-1/4" 1.660" 1.394" 0.42 1.08 2835 1191 1-1/2" 1.900" 1.598" 0.54 1.41 2205 1213 2" 2.375" 2.003" 0.84 220 1260 1084 2-1/2" 2.875" 2.423" 1.26 326 1215 1531 3" 3.500" 2.952" 1.87 4.83 720 1344 FIGURE 1—PIPE DIMENSIONS Installation Care and Tyco Fire and Building Products Maintenance (TFBP) BlazeMaster CPVC Pipe and Fittings are to be installed in accord- The owner is responsible for the fin- ance with IH-1900, Rev. 0, January spection, testing, and maintenance of 2005"Installation Instruction&Techni- their fire protection system and de- cal Handbook". vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stalling contractor or product manufac- turer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. NOTES Before closing a fire protection system control valve for inspection or mainte- nance work on the fire protection sys- tem that it controls,permission to shut down the affected fire protection sys- tem must first be obtained from the proper authorities and all personnel • who may be affected by this action must be notified. After placing a fire protection system in service,notify the proper authorities and advise those responsible for moni- toring proprietary and/or central sta- tion alarms. TFP1915 Page 3 of 6 FITTING PART NOMINAL TAKE-OUT WEIGHT TYPE NUMBER NOMINAL SIZE (TM) SCHD. (lb.) TEE 80000 3/4" 5/8" 40 0.11 ► ► 1/0 80001 1" 11/16" 40 0.19 %.,j_ 80002 1-1/4" 7/8" 40 0.26 .ii. 80003 1-1/2" 1-1/16" 80 0.51 -mm. 80004 2" 1-3/8" 80 0.90 80005 2-1/2" 1-9/16" 80 1.59 T/0 ■■ T/0 80006 3" 1-13/16" 80 2.41 XxYx2 X Y Z 80132 3/4"x 3/4"x 1" 3/4" 3/4" 5/8" 40 0.14 80133 1"x 3/4"x 3/4" 9/16" 9/16" 3/4" 40 0.14 80134 1"x 3/4"x 1" 3/4" 11/16" 3/4" 40 0.17 80260 1"x 1"x 3/4" 5/8" 5/8" 13/16" 40 0.16 80135 1-1/4"x 1"x 3/4" 5/8" 5/8" 15/16" 40 0.21 80136 1-1/4"x 1"x 1" 3/4" 3/4" 15/16" 40 0.22 80137 1-1/4"x 1"x 1-1/4" 15/16" 15/16" 7/8" 40 0.26 REDUCING TEE 80261 1-1/4"x 1-1/4"x 3/4" 5/8" 5/8" 7/8" 40 0.23 80262 1-1/4"x 1-1/4"x 1" 3/4" 3/4" 7/8" 40 0.26 Z 80138 1-1/4"x 1-1/4"x 1-1/2" 1" 1" 1" 80 0.43 SMO T/O 80140 1-1/2"x 1-114"x 3/4" 9/16" 9/16" 1" 80 0.36 .. ...111.10,"A. 80141 1-1/2"x 1-1/4"x 1" 9/16" 9/16" 1-1/16" 80 0.38 - M 80263 1-1/2"x 1-1/2"x 3/4" 9/16" 9/16" 1" 80 0.36 X-...Y 80264 1-1/2"x 1-1/2"x 1" 9/16" 9/16" 1-1/16" 80 0.38 � ����'�- 80275 1-12"x 1-12"x 1-1/4" 7/8" 7/8" 1" 80 0.45 T!O ■• T/O 80265 2"x 2"x3!4" 3/4" 3/4" 1-3/8" 80 0.61 80266 2"x 2"x 1" 7/8" 7/8" 1-3/8" 80 0.66 80274 2"x 2"x 1-1/4" 1-1/16" 1-1/16" 1-3/8" 80 0.74 80267 2"x 2"x 1-1/2" 1-1/8" 1-1/8" 1-3/8" 80 0.78 80271 2-1/2"x 2-1/2"x 1" 1-9/16" 1-9/16" 1-9/16" 80 1.43 80272 2-1/2"x2-112"x 1-1/4" 1-9/16" 1-9/16" 1-9/16" 80 1.46 80273 2-1/2"x 2-12"x 1-1/2" 1-9/16" 1-9/16" 1-9/16" 80 1.48 80276 2-1/2"x 2-12"x 2" 1-9/16" 1-9/16" 1-9/16" 80 1.50 80270 3"x 3"x 1-1/2" 1-13/16" 1-13/16" 1-13/16" 80 2.28 80268 3"x 3"x 2" 1-13/16" 1-13/16" 1-3/4" 80 2.25 80269 3"x 3"x 2-12" 1-13/16" 1-13/16" 1-13/16" 80 2.44 CROSS&REDUCING CROSS 80009 3/4" 9/16" 40 0.13 80010 1" 11/16" 40 0.23 J..�__ T/O 80011 1-1/4" 15/16" 40 0.34 - - 80012 1-1/2" 1-1/16" 80 0.67 =MIME 80013 2" 1-5/16" 80 1.00 fIF- pi 80014 2-12" 1-9/16" 80 1.91 I.,II T/0 80008 3" 1-13/16" 80 2.89 T/0 ■■ T/O 80015 1"x 1"x3/4"x 314" 7/8" 40 0.28 • 80025 3/4" 5/8" 40 0.09 90°ELBOW& REDUCING ELBOW 80026 1" 3/4" 40 0.14 80027 1-1/4" 7/8" 40 0.21 X 80028 1-1/2" 1-1/16" 80 0.40 '.,i T/O 80029 2" 1-5/16" 80 0.79 IMM‘ 80030 2-12" 1-9/16" 80 1.14 Mild 80031 3" 1-13/16" 80 1.82 Y ••�� XxY X Y -T/0 80032 1"x 3/4" 11/16" 13/16" 40 0.16 FIGURE 2-FITTING DIMENSIONS(Part 1 of 4) Page 4 of 6 TFP1915 FITTING PART NOMINAL TAKE-OUT WEIGHT TYPE NUMBER NOMINAL SIZE (TIO) SCHD. (lb.) 45°ELBOW 80050 3/4" 3/8" 40 0.08 T/O- - 80051 1" 3/8" 40 0.11 �� 80052 1-1/4" 3/4" 40 0.20 ''�+' 80053 1-1/2" 1/2" 80 0.31 �s a- 80054 2" 3/4" 80 0.56 I/O swam 80055 2-1/2" 13/16" 80 0.89 80056 3" 1" 80 1.19 80075 3/4" 1/8" 40 0.07 - COUPLING& 80076 1" 1/8" 40 0.11 REDUCING COUPLING 80077 1-1/4" 3/16" 40 0.12 p„,. 80078 1-1/2" 3/16" 80 0.25 80079 2" 3/16" 80 0.38 r , 80080 2-1/2" 1/4" 80 0.67 -I-T/O 80081 3" 3/16" 80 0.91 80220 1"x 3/4" 1/8" 40 0.08 80200 1"x 3/4" 7/16" 40 0.04 80201 1-1/4"x 3/4" 1/2" 40 0.11 80202 1-1/4"x 1" 5/16" 40 0.12 80203 1-1/2"x 3/4" 5/8" 80 0.16 80204 1-1/2"x1" 1/2" 80 0.14 REDUCER BUSHING 80205 1-1/2"x 1-1/4" 3/8" 80 0.17 80206 2"x 3/4" 13/16" 80 0.27 -,-.7/7 80207 2"x 1" 11/16" 80 0.26 80208 2"x 1-1/4" 9/16" 80 0.24 'T ',z 80209 2"x 1-1/2" 7/16" 80 0.19 -I 1-T/0 80215 2-1/2"x 1" 15/16" 80 0.42 80214 2-1/2"x 1-1/4" 13/16" 80 0.45 80213 2-1/2"x 1-1/2" 11/16" 80 0.46 80211 2-1/2"x 2" 5/8" 80 0.29 80210 3"x 2" 3/4" 80 0.72 80212 3"x 2-1/2" 1/2" 80 0.47 CAP 80100 3/4" 5/16" 40 0.04 80101 1" 3/8" 40 0.06 80102 1-1/4" 7/16" 40 0.10 80103 1-1/2" 11/16" 80 0.20 80104 2" 5/8" 80 0.31 T/O - 80105 2-1/2" 7/8" 80 0.58 80106 3" 1" 80 0.88 GROOVED T10 PIPE O.D. COUPLING ADAPTER 80160 1-1/4"x 1-1/4"Groove 2-5/16" 1-1/4"(1.660") 40 0.78 I ��' '- 80161 1-1/2"x 1-1/2"Groove 2-5/16" 1-1/2"(1.900") 60 0.95 PIPE 80162 2"x 2"Groove 2-5/16" 2"(2.375") 80 1.42 O.D. 80163 2-1/2"x 2-1/2"Groove 2-5/16" 2-1/2"(2.875") 80 2.28 80164 3"x 3"Groove 2-1/4" 3"(3.500") 80 3.00 -T/0-I 80169 2-1/2"x 76,1 mm Groove 2-5/16" 76,1 mm(3.000") 80 2.28 FIGURE 2-FITTING DIMENSIONS(Part 2 of 4) TFP1915 Page 5 of 6 FITTING PART NOMINAL SIZE NOMINAL TAKE-OUT SCHD. WEIGHT TYPE NUMBER (T/O) (lb.) SPRINKLER HEAD ADAPTER 80175E 3/4"x 1/2"NPT 7/16" 80 0.20 80176E 1"x 1/2"NPT 7/16" 80 0.22 I 80175WL 3/4"x 1/2"NPT 7/16" 40 0.16 NM` ,, 80179 1"x 314"NPT 13/16" 40 0.43 T/O SPRINKLER HEAD ADAPTER 80175W 3/4"x 1/2"NPT 1/2" 40 0.19 80176W 1"x 1/2"NPT 1/2" 40 0.18 —I TIO SPRINKLER HEAD ADAPTER(SPIGOT) 7 G 80177E 3/4"x 1/2"NPT 1/2" 40 0.16 ` �'� 80178 1"x 1/2"NPT 9/16" 40 0.20 80180 1"x 3/4"NPT 7/8" 40 0.40 - —T/O FEMALE ADAPTER ,,,, 80142 3/4"x 3/4"NPT 13/16" 40 0.41 80145 1'x 1"NPT 7/8" 40 0.63 80146 1-1/4"x 1-1/4"NPT 1-1/8" 40 1.03 ��� 80147 1-1/2"x 1-1/2"NPT 1-3/8" 80 1.42 ,/, 80148 2"x 2"NPT 1-11/16" 80 2.66 —T/O MALE ADAPTER ,,i„ PT/0l.-- 80157 3/4"x 3/4"NPT 1-5/16" 40 0.33 80158 1'x 1"NPT 1-3/8" 40 0.56 iii, —I XxYxZ X Y Z SPRINKLER HEAD ADAPTER TEE 80250 3/4"x 3/4"x 1/2"NPT 9/16" 9/16" 1" 40 0.22 I Z 80251 1"x 1"x 1/2"NPT 11/16" 11/16" 1-3/16" 40 0.29 ;_=p T/O 80249 1"x 1"x 1"NPT 15/16" 15/16" 1-9/16" 40 0.73 �+C _— I 80256 1-1/4"x 1"x 1/2"NPT 7/16" 9/16" 1-5/16" 40 0.30 =illi- 80252 1-1/4"x 1-1/4"x 1/2"NPT 7/16" 7/16" 1-5/16" 40 0.31 X -11.-Y 1 80257 1-1/2"x 1-1/4"x 1/2"NPT 1/2" 11/16" 1-7/16" 80 0.43 ...►.gw. 80254 1-1/2"x 1-1/2"x 1/2"NPT 1/2" 1/2" 1-7/16" 80 0.46 T/O •• T/O 80258 2"x 1-1/2"x 112"NPT 1/2" 5/8" 1-11/16" 80 0.56 80253 2"x 2"x 1/2"NPT 1/2" 1/2" 1-11/16" 80 0.62 FIGURE 2—FITTING DIMENSIONS(Part 3 of 4) Page 6 of 6 TFP1915 FITTING PART NOMINAL TAKE-OUT WEIGHT TYPE NUMBER NOMINAL SIZE (T/0) SCHD. (lb.) BACK-TO-BACK TEE X x Y z Z X Y,Z X T/0 I Y' .4 d'"` 80459 1"x 1/2"NPT x 1/2"NPT 5/8" 1-5/16" 40 0.48 . al `` Z I 80460 1"x 1/2"NPT x 1/2"NPT 5/8" 1-3/16" 40 0.46 I/O T/O BACK-TO-BACK CROSS X x Y x 2 x W X,Y Z,W x ilk T/O z.:: ....c IIIIIIMMRiN1111 80462 1"x 1"x 1/2"NPT x 1/2"NPT 5/8" 1-3/16" 40 0.46 " INN=r0. 80463 1"x 1"x 1/2"NPT x 1/2"NPT 5/8" 1-5/16" 40 0.47 T/O IN I/O T/O SPRINKLER HEAD X x Y X Y ADAPTER 90°ELBOW Y � I T/O I 80199 3/4"x 1/2"NPT 9/16" 1" 40 020 01 II(jai 80198 1"x 1/2"NPT 3/4" 1-1/4" 40 0.26 •.4r-�--X 80196 1"x 3/4"NPT 1-1/16" 1-7/16" 40 026 T/O FIGURE 2—FITTING DIMENSIONS(Part 4 of 4) Limited by TFBP to be defective shall be either of merchantability and fitness for a par- repaired or replaced, at TFBP's sole ticular purpose. Warranty option. TFBP neither assumes, nor This limited warranty sets forth the ex- authorizes any person to assume for it, clusive remedy for claims based on any other obligation in connection with failure of or defect in products, materi- als manufactured by Tyco Fire& the sale of products or parts of prod- als or components,,wether the claim Building Products (TFBP) are war- ucts.TFBP shall not be responsible for is made in contract, tort, strict liability ranted solely to the original Buyer for sprinkler system design errors or inac- or anyother legal theory. ten(10)years against defects in mate- curate or incomplete information sup- g ry' rial and workmanship when paid for plied by Buyer or Buyer's repre- This warranty will apply to the full ex- and properly installed and maintained sentatives. tent permitted by law.The invalidity,in under normal use and service. This whole or part, of any portion of this warranty will expire ten (10) years In no event shall TFBP be liable, in warranty will not affect the remainder. from date of shipment by TFBP. No contract, tort, strict liability or under warranty is given for products or com- any other legal theory, for incidental, . ponents manufactured by companies indirect,special or consequential dam- not affiliated by ownership with TFBP ages,including but not limited to labor or for products and components which charges, regardless of whether TFBP have been subject to misuse,improper was informed about the possibility of • installation, corrosion, or which have such damages, and in no event shall not been installed, maintained, modi- TFBP's liability exceed an amount tied or repaired in accordance with ap- equal to the sales price. plicable Standards of the National Fire The foregoing warranty is made in lieu Protection Association, and/or the of any and all other warranties. ex- standards of any other Authorities press or implied including warranties. Having Jurisdiction. Materials found TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale,Pennsylvania 19446 Dyna-Thread® - M-COAT® Submittal Data Sheet 0 Full Line Sch-40 Replacement Dyna-Thread—M-COAT Specifications Dyna-Thread'—M-Coat= sprinkler pipe represents an engineering NPS Nominal LD. Wt. Wt.(H20 Filled) CRR CRR advancement for the sprinkler pipe industry.It combines the safety In;mm In;mm Lbs/Ft;kg/m Lbs/Ft;kg/m Unthreaded Threaded and longevity of traditional Sch-40 pipe with quality and superior 1" 1.080 1.330 1.75 11.39 1.00 hydraulic advantages. 25 27.4 2.0 2.60 — — 11/4" 1.408 1.870 2.54 9.50 1.00 O Comparison to Schedule 40 32 35.8 2.8 3.78 — — 1'k" 1.639 2.290 3.22 9.14 1.00 Dyna-Thread'—M-Coat''inside diameter is up to 3.6%larger than Sch-40 40 41.6 3.4 4.79 — — giving it superior hydraulics.Also, when used in combination with Dyna- 2" 2.104 3.050 4.57 8.41 1.00 Flow—M-Coat pipe,down sizing often occurs.Dyna-Thread is fully listed and 50 53.4 4.5 6.80 — — approved UL, ULC,and FM for fire sprinkler applications.The life expectancy of Dyna-Thread—M-Coat and Sch-40 are equal based on the calculated wall 0 c() 4:11111, thicknesses per UL.The consistent quality of steel used to make Dyna-Thread— M-Coat facilitates smooth threading and lower maintenance costs.The exterior of Dyna-Thread—M-Coat is protected by a clean,durable mill coating for O American Made extended shelf life and easy paint application.With its increased strength Manufactured at one of 3 U.S.Facilities and is available and lighter weight, Dyna-Thread—M-Coat reduces installation fatigue and through distributors in the USA,Canada, Mexico,and is ideal for retro-fit applications.Corrosion Resistance Ratio(CRR)is a UL Latin America. (Underwriters Laboratory)term for the estimated life expectancy of a pipe joint. This is based on the calculated wall thickness at the base of the first exposed Q Specifications & Approvals thread, assumed to be the weakest point of the pipe length.Dyna-Thread— M-Coat and Sch-40 have the same calculated wall thicknesses at this point Dyna-Thread—M-Coat pipe is manufactured to meet:ASTM A and are both assigned the same CRR of 1.00. 135,Type E Grade A,and is in compliance with NFPA-13.All sizes of Dyna-Thread—M-Coat are rated at 300 psi working O Comparison to L.W.T. Pipe pressure.Dyna-Thread—M-Coat is UL and ULC Listed for wet, More wall thickness at the thread(CRR=1.00)gives Dyna-Thread—M-Coat dry and pre action sprinkler systems and FM Approved for better life expectancy than lightwall threadable pipe joints.Dyna-Thread— use in wet systems. Dyna Thread—M-Coat is approved for all M-Coat is approved for standard hanger spacing(15 ft.D.C.),can be used as threaded couplings and welded outlets and is suitable for all earthquake sway bracing,and is safe to use as drops.Dyna-Thiead—M-Coat roll grooved,and plain end fittings.(See listing information). is safer to weld on than many zinc coated lightwall threadable pipe products. Dyna-Thread—M-Coat is more widely accepted than lightwall threadable where Sch-40 is specified. Project: Sprinkler Contractor: Date: Engineer: Specification Reference: System Type: - Locations: Comments: � . Customer Service:(800)882-5543 Fax:(800)659-7730 www.alliedtube-sprinkler.com -J alliecJ • 16100 S Lathrop Ave • 11350 Norcom Rd. • 2525 N 27th Ave. TUBE&CONDUIT" Harvey,IL 60426 Philadelphia,PA 19154 Phoenix,AZ 85009 a PAN"F ^atkore =`, ©2013 Atkore International,Inc.All Rights Reserved.STP-S3-4M-1301 ES-A-2000B Series 20008 A M E S Double Check Valve Assemblies FIRE&WATERWORKS Sizes: 1" —2" (15—50mm) 0 4 Features , ? _ �< • Ease of maintenance with only one cover 2"2000B HC • Top entry (50mm) • Replaceable seats and seat discs — • Modular construction • • Compact design • ' • W—2"(15—50mm)Cast bronze body construction i • Top mounted ball valve test cocks '/+"20006 (20mm) • Low pressure drop • No special tools required Series 2000B Double Check Valve Assemblies are designed to protect drinking water sup- • '/"—1" (15—25 mm)have plies for dangerous cross-connections in accordance with national plumbing codes and tee handles water authority requirements for non-health-hazard non-potable service applications such as irrigation,fire line,or industrial processing. Available Models These valves meet the requirements of ASSE Std. 1015 and AWWA Std.C510 and are Suffix: approved by the Foundation for Cross-Connection Control and Hydraulic Research at the B- Quarter turn ball valves University of Southern California. LBV- less ball valves Specifications SH- stainless steel ball valve handles A Double Check Valve Assembly shall be installed at each noted location.The assembly HC- 21/2" inlet/outlet fire hydrant fitting shall consist of two positive seating check modules with captured springs and rubber seat (2"valve) discs.The check module seats and seat discs shall be replaceable.Service of all internal components shall be through a single access cover secured with stainless steel bolts. Pressure —Temperature The assembly shall also include two resilient seated isolation valves and four top mounted, Temperature Range:33°F—140°F resilient seated test cocks.The assembly shall meet the requirements of ASSE Std. 1015 (0.5°C—60°C) and AWWA Std.C510.Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.Assembly shall be an Ames Maximum Working Pressure: 175psi Company Series 2000B. (12.1 bar) Approvals Standards s vsso,e AWWA Std.C510, IAPMO PS31 c S P® u `®C Us us 1015 8645 '/+"-2" A WARNING (LBV Models Only) It is illegal to use this product in any plumbing Approved by the Foundation for Cross-Connection Control and Hydraulic Research at system providing water for human consumption, the University of Southern California. such as drinking or dishwashing,in the United LBV models not listed. States.Before installing standard material prod- - Horizontal and vertical°flow up"approval on all sizes. uct,consult your local water authority,building and plumbing codes. Job Name Contractor Job Location Approval Engineer Contractor's P.O.No. Approval Representative Ames product specifications in U.S.customary units and metdc are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. amesfirewater.com Dimensions -Weights =ilk B �•� ® • �► ® _1 ��_■1,- r-rte■1■ illik �, I F Suffix HC- Fire Hydrant Fittings dimension"A"=231/2"(594mm) *H l-. G SIZE(DN) DIMENSIONS WEIGHT A B C F 6 H - I in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. 1/2 15 10 254 , 4% 117 2%6 62 5 127 3% 85 26/6 59 21/6 52 4.5 2 3/4 20 11% 282 4 102 31/2 79 . 63/16 157 37A6 87 21/6 54 16/6 33 5 2.3 1 25 131/4 337 5% 130 4 102 7' 191 3% 85 11'/6 43 _ 111/6 43 12 5.4 11/4 32 16% 416 _ 5 127 33/16 84 91/2 241 5 127 3 76 2 50 15 6.8 1' 40 163/4 425 4% 124 311 89 93/4 248 513/16 148 3% 79 2'1/16 68 1536 72 2 50 191/2 495 61/4 159 4 102 13% 340 61/8 156 3%/6 87 211/16 68 25.75 11.7 Strainer sold separately Capacities kPa psi A 11/4"(32mm) As compiled from documented Foundation for Cross-Connection Control 96 14 and Hydraulic Research at the University of Southern California lab tests. in 83 12 ATypical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.) 0 69 10 • 1/2" (15mm) ` 55 6 kPa psi 41 6 � 83 12 e 0 _, 0 69 10 11 28 4 '.. J 55 8 it14 2 r 0 DP 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm y 28 4 N 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm d 14 2 tt 0 0 5 7.5 10 15 fps 0 2 4 6 8 10 12 gpm 1.5 2.3 3.0 4.6 mps AP 0 7.6 15.2 22.8 30.4 38 45.6 Ipm Flow Rate 5 7.5 10 fps 1.5 2.3 3.0 Ps kPa psi 11/2"(40mm) Flow Rate 83 12 kPai Pa a 3/4" (20mm) a 69 10 a 152 22 055 8 J 124 18 ` 41 6 r _ 96 14 0 28 2 H 69 10 0 0 a APO 10 20 30 40 50 60 70 80 90 100 110 120 gpm 0. 41 6 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 14 2 ' ' 5 7.5 10 15 fps DP 0 5 10 15 26 25 30 35 40 45 50 gpm 1.5 2.3 3.0 4.6 mps 0 19 36 57 76 95 114 133 152 171 190 Ipm Flow Rate 7.5 15 fps 2.3 4.6 mps kPasl 2"(50mm P ) Flow RateN 83 12 e kPai N 110 16 A 1"(25mm) p 69 10 'S J 55 8 J 83 12 41 6 ,....---4. 069 w55 8 3 N I- 558 N 28 4 0 41 6 14 2 d 28 4 a o 0 0. 14 2 ' ��r� 0 25 50 75 100 125 150 175 200 gpm AP 0 95 190 285 380 475 570 665 760 pm eP 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm 5 7.5 10 15 fps 0 19 38 57 76 95 114 133 152 171 190 209 228 Ipm 1.5 2.3 3.0 4.6 mps 5 7.5 10 15 fps Flow Rate 1.5 2.3 3.0 4.6 mps FlowRate , A Rte AMES FIRE&WATERWORKS A Watts Water Technologies Company USA:Backflow Tel:(978)689-6066•Fax:(978)975-8350•AmesFireWater.com USA:Control Valves Tel:(713)943-0688•Fax:(713)944-9445•AmesFireWater.com Canada: Tel:(905)332-4090•Fax:(905)332-7068•AmesFireWater.ca Latin America: Tel:(52)81-1001-8600•Fax:(52)81-8000-7091 •AmesFireWater.com ES-A-2000B 1410 ©2014 Ames Fire&Waterworks Sprinkler Gauge F P P 1 Description 200 FPPI pressure gauges feature an impact and corrosion resistant case made from , \ ABS(plastic). Features phosphor bronze bourdon tube movement with white • enameled brass dial face with large numbers for easy reading. Dual scale to 300 0°° mos PSI/2000Kpa. UUULc Listed(Sprinkler Gauge Model 111.10SP, UL Listed file 6,1 EX5232) and FM Approved. .6„;'0' + °`a ti • T +fir Applications Standard Features Specifications • Fire sprinkler systems Design • Suitable for all media that will not EN 837-1 &ASME B40.100 Bourdon Tube Material:copper alloy C-type obstruct the pressure system or Sizes attack copper alloy parts 4" (100 mm) Pressure Connection Accuracy class Material:copper alloy /4"NPT lower mount(LM) Special Features ± 3%% of span • UL-listed (UL-393), United States (ASME B40.100 Grade B) Movement and Canada(Sprinkler Gauge Ranges Copper alloy Model 111.10SP, UL Listed file 0/80 psi, retard to 250 psi(air) Dial EX5232) 0/300 psi (air,water, air/water) White aluminum with stop pin; • Factory Mutual(FM)approved Working Pressure black and red lettering • Reliable and economical Steady: 3/4 of full scale value Pointer Fluctuating: %of full scale value Black aluminum Short time:full scale value Operating Temperature Case Black polycarbonate Ambient: -40°F to 140°F (-40°C to 60°C) Window Media: 140°F(+60°C) maximum Snap-in clear polycarbonate Temperature Error Additional error when temperature changes from reference temperature of 68°F(20°C)+0.4%for every 18°F (10°C) rising or falling. Percentage of span. 3198 LIONSHEAD AVE CARLSBAD, CA599 920100 +1 800 344-1822 FAX+1 800 344-3775 2012 Fire Pmteetion Products,Inc. - Model 1000 . imic TESTAN DRAIN® Sectional Floor Control Test and Drain Valve 03 us 34" 1" 1'/a" 11/2" 2" ;`T,y,'1 7.7,,,,,'%7,777.7. . srx' , N r x TEST 1 , @ .4 _:_,�_e,.__. v2"A: ICE. — PUSH 011110fi a ' TESTANDRAIN MCCEL MO N!I:. i LJ. N ., DRAIN FITTING•SPE6ML TYPE O+>��r' (a t t, 4. A, . AGF MII.IAC..Makete.PA y >' u _ � -! m ` F. :fir .{ .3 • stir ;r.&-. Sld .i� _ _ iir e •The AGF Manufacturing Inc.Model 1000 TESTANDRAIN® MODEL 1000- FRONT VIEW,VERTICAL INSTALLATION provides both the test function and the express drain function for a wet fire sprinkler system. •The Model 1000 complies with the requirements of I FROM BRANCH NFPA-13, NFPA-13R, and NFPA-13D. il •The Model 1000 TESTANDRAIN°is a compact single SYSTIEIM ACCESS PORT m. handle ball valve which includes a tamper resistant test ••11 orifice and integral tamper resistant sight glasses, and is 300 PSI rated. _� B •Available in a full range of sizes from 3/4"to 2' NPT and ��LI� " ' BSPT, with all specifiable orifice sizes 3/N" (2.8K), 7/i6" (4.2K), STREET EL ��� . 1/2" (5.6K), 17/32" (8.0K),5/e" (11.2K, ELO), 3/4" (14.0K, ESFR), 0�,�11 and K25 as required by NFPA 13, 2007 Edition(see reverse). 1.x.•l •The orifice size is noted on the indicator plate and the valve Iiht features a tapped and plugged port for system access. STREET E� III TO DRAIN •A locking kit is available and can be ordered with the valve OR PIPE I 1 to provide vandal resistance or prevent unintentional alarm � ' • TO DRAIN l activation. • Repair kits including (1) adapter gasket, (1)ball, (2)valve . seats, (1)stem packing, and (1) stem washer are available for all TESTANDRAIN®valves.Valve and orifice size must RIGHT HAND/STRAIGHT INSTALLATION be specified when ordering. Reliability, Versatility, Code Compatibility TESTANDRAIN is a registered trademark of AGF Manufacturing Inc. CS1000 10:09 Model 1000 . AG cOus ./�T,� AN D RAI No APPROVED 300 PSI Bronze Ball Valve MODEL 1000 - PLAN VIEW FRONT VIEW - HORIZONTAL INSTALL A . I E•I I O•- O I...I, 7/A ACCESS ESSYSTEM ACCESS PORT F 44 TO DRAIND _$1.11r 41100 • TO DRAIN H_1 .� _ ••■ le 1•111 ,, 1 ! I. 1 .. . 1El DIMENSIONS MATERIALS Orifice Size Available:3/8",7/16", 1/2",17/32",ELO(5/a")*, ESFR(3/4")*,&K25** Handle:Steel Stem: Rod Brass SIZE A B C D E F G H Ball:C.P.Brass 3/4.. 51/16" 11/2" 23/16" 35/8" 33/8" 113/16" 49/16° 63/8" Body: Bronze (128 mm) (37.5 mm) (57 mm) (93 mm) (86 mm) (46 mm) (117 mm) (162.5 mm) Valve Seat: Impregnated Teflon'' 51/1x" 11/2" 23/16" 35/8" 3y8" 113/is" 49/16" 63/8" Indicator Plate:Steel 1 ' (128 mm) (37.5 mm) (57 mm) (93 mm) (86 mm) (46 mm) (117 mm) (162.5 mm) Handle Stop:Steel ISI 11/4" 57A6" 111/16" 29A6" 41/4" 35/16" 115A6" 59/is" 51/2" APPROVALS (163 mm) (43 mm) (65 mm) (108 mm) (83 mm) (51 mm) (141 mm) (192 mm) UL and ULC Listed(EX4019) 11/2" 67/16" 113/46" 31/4" 51/16" 37/8" 25/8" 81/4" 107/8" FM Approved (163 mm) (45 mm) (81.5 mm) (127 mm) (99 mm) (67 mm) (207 mm) (274 mm) NYC-BSA No.720-87-SM 2" 67/1 s" 113/16" 31/4" 51/16" 37/8" 25/8" 81/4" 107/8" (163 mm) (45 mm) (81.5 mm) (127 mm) (99 mm) (67 mm) (207 mm) (274 mm) fra„* *Available on 11/4"to 2"size units only :744 **Available on 11 " and 2" size units only THE MODEL 1000 PROVIDES ALL OF THE FOLLOWING... MADE IN U.S.A. From the 2007 Edition of NFPA 13 Chapter 8.16.2.4.1* Provisions shall be made to properly drain all parts of the system. Chapter 8.16.2.4.2 Drain connections, interior sectional or floor control valve(s)-shall be provided with a drain &8.16.2.4.3 connection having a minimum size as shown in Table 8.16.2.4.2. Chapter 8.16.2.4.4 Drains shall discharge outside or to a drain capable of handling the flow of the drain. Chapter A.8.17.4.2 (Wet Pipe System)test connection is permitted to terminate into a drain capable of accepting full flow... using an approved sight test connection containing a smooth bore corrosion-resistant orifice giving a flow equivalent to one sprinkler... Chapter 8.17.4.2.2 The test connection valve shall be readily accessible. Chapter 8.17.4.2.4 shall be permitted to be installed in any location...downstream of the waterflow alarm. Chapter 8.17.4.3.1 (Dry Pipe System)a trip test connection not less than 1" in diameter,terminating in a smooth bore corrosion-resistant orifice,to provide a flow equivalent to one sprinkler... Chapter 8.17.4.3.2 The trip test connection...with a shutoff valve and plug not less than 1",at least one of which shall be brass. USA Patent # 4741361 and Other Patents Pending AGF Manufacturing Inc. Job Name: la 100 Quaker Lane,Malvern,PA 19355 Phone:610-240-4900 Architect: Fax:610-240-4906 Engineer: www.testandrain.com Contractor: p po'rr .i FOR SMALL PIPE `' SR—S VANE TYPE WATERFLOW The Symbol of Protection ALARM SWITCH WITH RETARD EL,ULC,CSFM Listed and NYMEAAccepted Service Pressure: Up to 300 PSI(20,7 BAR) Flow Sensitivity Range for Signal: 4-10 GPM(15-38 LPM)UL Maximum Surge: 18 FPS(5,5 m/s) Enclosure: Die-cast,red enamel finish Cover held in place with tamper resistant screws Contact Ratings: Two sets of SPDT(Form C) 10.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC Resistive l OmAmps min.at 24 VDC Conduit Entrances:Two openings provided for 1/2"conduit. Individual switch compartments suitable for dissimilar voltages. Usage: Listed plastic,copper and schedule 40 iron pipe. Fits pipe sizes-1"(25mm). 1 1/4"(32mm), 1 1/2"(38mm) and 2"(50mm) Stock No. 1144440 Note: 12 paddles are furnished with each unit,one for each pipe size of threaded and sweat TEE,one for 1"(25mm)CPVC, one for 1"(25mm)CPVC(Central),one for 1"threaded Nibco CPVC,and one for 1 1/2"(33mm)threaded(Japan). t �� Environmental Specifications: i `" •`"' " `: _" • NEMA-4/IP54 Rated enclosure suitable for indoor or outdoor Installation must be performed by qualified personnel and in use with factory installed gasket and die-cast housing when used accordance with all national and local codes and ordinances. with appropriate conduit fitting. Shock hazard. Disconnect power source before servicing. • Temperature range:40°F to 120°F,(4,5°C to 49°C)UL Serious injuly or death could result. Service Use: Risk of explosion. Not for use in hazardous locations. Serious Automatic Sprinkler NFPA-13 injury or death could result. One or two family dwelling NEPA-13D Residential occupancy up to four stories NEPA-13R National Fire Alarm Code NFPA-72 Optional:Cover Tamper Switch Kit.Stock No.0090148 (See Fig.7 for terminations) Replaceable Components:Retard/Switch Assembly.stock no. 1029030 The Model VSR-S is a vane type watertlow switch for use on wet Installation sprinkler systems that use 1"(25mm),11/4"(32mm),1'h"(38mm)or 2" These devices may be mounted in horizontal or vertical pipe. On (50mm)pipe size.The unit may also be used as a sectional waterfow horizontal pipe they should be installed on the top side of the pipe where detector on large systems. they will he accessible.The units should not be installed within 6"(15cm) The unit contains two single pole double throw snap action switches and of a valve,drain or fitting which changes the direction of the watertiow. an adjustable, instantly recycling pneumatic retard. The switches are Select the proper paddle for the pipe size and type of TEE used see Fig. actuated when a flow of 10 gallons per minute(38 LPM)or more occurs 1 for instructions on changing paddle.The unit has a 1" NPT bushing downstream of the device.The flow condition must exist for a period of for threading into a non-corrosive TEE.See Fig. for proper TEE size, time necessary to overcome the selected retard period. type and installation Use no more than three wraps of teflon tape. Enclosure Screw the device into the TEE fitting as shown in Fig.2.Care must be The VSR-S switches and retard device are enclosed in a general purpose_ taken to properly orient the device for the direction of waterflow. die-cast housing.The cover is held in place with two tamper resistant The vane must not rub the inside of the TEE or bind in any way.The screws which require a special key for removal.A field installable cover stem should move freely when operated by hand. tamper switch is available as an option which may he used to indicate The device can also be used in copper or plastic pipe installations with unauthorized removal of the cover. See bulletin number 5401103 for the proper adapters so that the specified TEE fitting may be installed installation instructions of this switch. on the pipe run. Note:Do not leave cover off for an extended period of time. Potter Electric Signal Company,LLC•2081 Craig Road,St.Louis,MO,63146-4161•Phone:800-325-3936 Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.tS4OI2Oo-REV G PAGE I OF 3 12/05 P POTTER FOR SMALL PIPE VSR-S VANE TYPE WATERFLOW ® The Symbol of Protection ALARM SWITCH WITH RETARD Fig. I Fig.2 Retard Adjustment DU Nut LEAVE COT-ERok Fr OR EXTENDED PERIL"I)/1F IDE FtlN —� ,','1n.,,PPP,, The time delay is factory set at 30±10 seconds. COVER TAMPER SWITCH ' The delay can be adjusted by rotating the retard _ .+ �� —h _,-- adjustment 40 ��j�,I,t Il ` nFPTa / I 90 seconds).The time delay should be set at the ,�I j.� minimum required to present false alarms. �-. ` 14, , ; ffi I !?•\�\"\ , Screw the device into the tee fitting as shown. �'\�,-I4111%........P- ..0.1,11110' Ic I Care must be taken to properly orient the DIREcr(oh UF :As' �I�,1/�• WATER FLUTE KRONT`O �, �` device for the direction of watetflow.On sweat vROTo ii# BLSHING POINTS j tees,no threaded bushings,inserts.or adapters l: �Di�IRriow ; � are permitted.unless they comply with the dimensions listed in the chart below. ~' FITTING MENDED Important-The depth to the inside bottom of pr1� �^•^^� ^"" ALL IZEs the tee should have the following dimensions: •�� !1 • - ` RUN OF 7HE TEE . MAY BE � Applovmate Depth Requirement A There are 12 paddles furnished with each unit. THREwAD-EAT PIPEEDf•R �\ Tee Sae Threaded Sweat CPUC S One for each size of threaded,swwtt or plastic 1 1"><1",.1" 21/16^ 134" 271.," DIRECTION DF `\` FEE as described in Fig.2.These paddles have uR.,TEritt wr g-. 1 1 4"r 1 1'3"<1" 2 7/16" 2 7/16" N A I raised letteringthat shows the pipesize and �Q DU us`J� . 1 1'^x l l^_"x 1" 2 11!16" 2 1/4" N/A of TEE that they are to be used with.The proper 2"n 2"x 1' 3 3,16" 2 3/4^ N/A pa&kllemustbeused.Thepaddlemustbepr'oper'ly Shown with optional Cover Tamper Switch Kit. attached(see drawing)and the screw that holds ' 'AWIVARNifi the paddle must be securely tightened. Do not use more than three lamps of teflon tape. Fig.3 Switch Terminal Connections Clamping Plate Terminal Fig.7 Cover Tamper Switch Wiring (Shown with cover in place) U , 'I' • An uninsulated section of a single conductor should not be looped Pe around the terminal and serve as two separate connections.The wire ,ro g;., must be severed,thereby providing supervision of the connection in o`'" the event that the wire become dislodged from under the terminal. C N.O. N.C. Failure to sever the wire may render the device inoperable risking (WHT) (RED) 031,10 severe property damage and loss of life. DwfrsIinoIS.: Fig.4 Typical Electrical Connections Fig.5 Fig.6 To remove knockouts: Break out thin sectionofcoverwhenwiring ligrilI' —1 N pili , UR Placescrewdriver switches n +. NEtrrRALAc at edge ofboth fro none conduit entrance. oco i.1.7-4 +; ' ® laT k uts,not in the center. 1_.l I POSITIVE DC€'R '_ t ___.� L±. . • • • HUT AC \ i • IIT. Ill_ —Irl I - — _.___I, c.)) ll_i I til "=_.-_-._._.' IIS•• 1 � int* II XI �maa INATFIRE PANEL LONE ON lic.k..1r� IG— III � FIRE PANEL ��0 • Notes: _,\ ��j '�r • 1. The Model VSR-S has two switches,one can be used to operate a -u—' • central station,proprietary or remote signaling unit,while the other 1 u is used to operate a local audible or visual annunciator. 2. For supervised circuits see"Switch Terminal Connections-drawing v and caution note(Fig.3). PRINTED IN USA MFG.A54(112U6-REV 0 PAGE 2 OF S 12 08 • ,„ , • FOR SMALL PIPE ��S -S ` , . . • . VANE TYPE WA`I'ERFLOW ® The Symbol of Protection ALARM SWITCH WITH RETARD Testing Removal The frequency of inspection and testing for the Model VSR-S and its • To prevent accidental water damage,all control valves should associated protective monitoring system should be in accordance with be shut tight and the system completely drained before waterflow applicable NFPA Codes and Standards and/or the authority having detectors are removed or replaced. jurisdiction(manufacturer recommends quarterly or more frequently.) • Turn off electrical power to the detector,then disconnect wiring. An inspector's test valve(usual lylocated atthe end ofthemost remote branch • Use a wrench on the flats of the bushing.Turn the switch line)should always be used for test purposes.If there are no provisions for counterclockwise to disengage the pipe threads. testing the operation of the flow detection device on the system,application • Gently lift with your fingers,roll the vane so it will tit through the of the VSR-S is not recommended or advisable. hole while continuing to lift the watertlow detector. A minimum flow of 10 gpm(38 Lpm)is required to activate this device. • Lift detector clear of pipe. NOTICE Please advise the person responsible for testing of the A CAUTION fire protection system that this system must be tested in accordance with the testing instructions. Waterfl ow switches that are monitoring wet pipe sprinkler systems Maintenance shall not be used as the sole initiating device to discharge AFFF, Inspect detectors monthly for leaks. If leaks are found, replace the deluge,or chemical suppression systems.Waterfl ow sw itches used for this application may result in unintended discharges caused • detector.The VSR-S waterflow switch should provide years of trouble- application by surges., trapped air,or short retard times. Gee service.The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock#1029030.There is no maintenance required,only periodic testing and inspection. Mounting Dimensions 3.50" 5.56" GROUND SCREWS (89.0 mm) (141.2 mm) �#o[g'1'.'1' (50 80mm)� 1115. II'� IIII 2.34" I M _.._ (59.4 mm) ji 111 il 1 ._ 489" _._. __... _. ., —6T(.82"401•11 - �i•r�lr III (52.3 mm) igii RF _�_ ►Q 1"-111/2 NPT DwG4 12206-5 • • • PRINTED IN USA MFG.454011206-REV G PAGE 3 OF 3 12/08 . 7v,Z 'g P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org 510 • CPVC - COPPER - STEEL HANGER 1O 510 Fastener 4 SIZE 3/4 2.12.12 5 0 1 2.312 1 1/4 3.170 1 1/2 3.400 2 4.010 2 1/2 4.320 3 5.320 SIZE-SYSTEM PIPE:3/4"thru 3" MATERIAL-Carbon Steel. FINISH-Mil. Galvanized. LISTING/APPROVAL- c®ca 203-EX 4231,EX 2551 unto FUNCTION-Support horizontal piping: CPVC,Copper or Steel. Size 3/4"-2"Prevents upward movement of pipe from pendent sprinkler discharge. Stabilize vertical piping. INSTALLATION- Per these instructions ' including NFPA 13, 13R, 13D and CPVC manufacturers instructions. MIN Install on horizontal or vertical mounting surface. FASTENERS- UL Listed per NFPA 13 in WOOD: 3/4"-3"CPVC pipe-#905 screw-no pre-drill. 3/4"-3"Steel and Copper pipe-#14 x 1 1/2" SMS or 1/4"x11/2"lag bolt-no pre-drill. Restraint in STEEL-train. 18 GA. 3/4"-3"CPVC,Copper and Steel pipe- 1/4"or#14 Tek Screw. • 1....41 FEATURES a *Offset edge eliminates abrasion. r%�✓ * Retainer dimples secure hanger to pipe during installation. Hanger* Required .4FCON#905 screw included-5/16"hex head. Han g wll amStabilize ORDERING-Part#and pipe size. � A III CAN ALSO BE USED TO REPLACE-#500 Pipe Strap #520 Tin Strap Specific.4FCO.Y products are exclusively designed to be compatible ONLY o ith other IFCO.Y products including parts and fasteners,resulting in a listed so as brace,restrainer or hanger assembly. Be advised the following warrants restriction will apply.DISCLAI\IER-.4FCOV will NOT warrant against the failure of its products when used in combination ssith other products.pans or systems not manufactured or sold by.4FCOA'.AFC0.1 shall NOT be liable under any circumstances uhatsoeser for any direct or indirect.incidental tar consequential damages of any kind,including but not limited to loss of business or profit,when non-AFCO_V products have been.or are used. 5/14 _�