Report (2) fivsa.vt3 -C) '2 10)-s sto U w7- RECEIVED FACP BATTERY CALCULATIONS AUG 2 1 2013 CAPITOL ELECTRIC CO., INC. (503)255-9488 Office, (503) 255-1966 Fax CITY OFTIGARD BUILDING DIVIS!O JOB NAME: St.Anthony Community Center JOB ADDRESS: 9905 SW McKenzie Street Tigard,OR 97223 DATE: 8/8/13 PANEL DESCRIPTION:SK 5808 FACP BY: Dan Wilson • DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE DESCRIPTION QUANTITY CURRENT CURRENT CURRENT CURRENT FACP INTERNAL COMPONENTS Silent Knight Model 5808 FACP 1 0.170 0.17000 0.325 0.325000 5860 Remote Annunciator 1 0.020 0.02000 0.025 0.025000 5496 Addressable Power Module 0.010 0.00000 0.010 0.000000 INITIATING DEVICES SK-Photo Photo Smoke Detector 1 0.000300 0.000000 0.006500 0.000000 Duct Smoke Detector,Photo 3 0.000300 0.000000 0.006500 0.000000 SK-Pull-SA Manual Station,Single Action 1 0.000400 0.000000 0.000400 0.000000 Spklr Flow Switch @ Riser w/SK-Minimon 1 0.000400 0.000000 0.000400 0.000000 Spklr Valve Switch @ Riser w/SK-Minimon 1 0.000550 0.00055 0.000550 0.000550 Spklr Valve Switch @ Vault w/SK-Minimon 1 0.000550 0.00055 0.000550 0.000550 OUTPUT DEVICES HVAC AHU Shut Down Relay Module SK-Relay 2 0.000300 0.000600 0.005500 0.011000 FSD Control Relay Module SK-Relay 1 0.000300 0.000300 0.005500 0.005500 OUTPUT 1 Outside Sprinkler Flow Alarm Wheelock ASWP-2475W-FW Outside H/S (H) 1 0.168 0.168 OUTPUT 1 Alarm Total 0.168 OUTPUT 2 NAC West Community Center 0.000 Whlk HSW 75 Cd H/S-Wall (H) 1 0.148 0.148 Whlk HSW 30 Cd H/S-Wall (H) 3 0.102 0.306 Whlk HSW 15 Cd H/S-Wall (H) 2 0.082 0.164 Whlk STW 15 Cd Strobe-Wall 1 0.057 0.057 0.000 0.000 0.000 0.000 0.000 OUTPUT 2 Alarm Total 0.675 NAC 1.0 Batt Calc, FACP 2013.0808.xls 5808 Batt Calc FACP BATTERY CALCULATIONS OUTPUT 3 NAC Center Community Center 0.000 Whlk HSWC 115 Cd H/S-Ceiling (H) 3 0.197 0.591 Whlk STWC 115 Cd Strobe-Ceiling 2 0.182 0.364 0.000 0.000 0.000 0.000 0.000 0.000 0.000 OUTPUT 3 Alarm Total 0.955 OUTPUT 4 NAC East Community Center _ 0.000 Whlk HSW 75 Cd H/S-Wall (H) 1 0.148 0.148 Whlk HSW 15 Cd H/S-Wall (H) 3 0.082 0.246 Whlk STW 75 Cd Strobe-Wall 0.135 0.000 Whlk STW 15 Cd Strobe-Wall 1 0.057 0.057 Whlk HSWC 75 Cd H/S-Ceiling (H) 1 0.148 0.148 Whlk STWC 75 Cd Strobe-Ceiling 1 0.135 0.135 0.000 0.000 0.000 OUTPUT 4 Alarm Total 0.734 STANDBY TOTAL CURRENT: 0.192000 STANDBY HOURS: 24 STANDBY AMP HOURS: 4.60800 ALARM TOTAL CURRENT: 0.536 ALARM MINUTES: 5 ALARM AMP HOURS: 0.0446 TOTAL CALCULATED AMP HOURS 4.653 NAC TOTAL CURRENT: 2.532 APPLIED SAFETY FACTOR 1.20 MINIMUM AMP HOURS REQURED 5.583 SELECTED BATTERY SIZE 12 EACH 12 VOLT, 7.0 AMP HOUR BATTERIES NAC 1.0 Batt Calc, FACP 2013.0808.xls 5808 Batt Calc NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: St. Anthony Community Center Job Address: 9905 SW McKenzie Street Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/8/2013 Cable Length In Feet (source to end of line) 300 Total Circuit Current 0.168 Nominal System Voltage 20.4 Panel Description: Silent Knight 5808 FACP Minimum Device Voltage 16 Panel No.: NAC 1.0 Output No.: 1 Point To Point Method EOLv 20.09 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv 20.09 Circuit Within Limits ? YES Load Centering Method EOLv 20.25 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) 1 Outside Waterflow Horn/Strobe ASWP-2475W-FR W/P H/S-H 75 Cd 0.168 300 20.09 2 20.09 3 20.09 4 20.09 5 20.09 6 20.09 7 20.09 8 20.09 9 20.09 10 20.09 11 20.09 12 20.09 13 20.09 14 20.09 15 20.09 16 20.09 17 20.09 18 20.09 19 20.09 20 20.09 NAC 1.0 EOLv Calc, FACP 2013.0808.xls OUTPUT 1 • NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: St.Anthony Community Center ,Job Address: 9905 SW McKenzie Street Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/8/2013 Cable Length In Feet(source to end of line) 457 Total Circuit Current 0.675 Nominal System Voltage 20.4 Panel Description: Silent Knight 5808 FACP Minimum Device Voltage 16 Panel No.: NAC 1.0 Output No.: 2 Point To Point Method EOLv 18.99 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv 18.51 Circuit Within Limits ? YES Load Centering Method EOLv 19.45 Circuit Within Limits ? s YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) 1 Community Center-West HSW(15) H/S-Wall, White, Hi 15 Cd 0.082 220 19.49 2 Community Center-West HSW (30) H/S-Wall, White, Hi 30 Cd 0.102 30 19.38 3 Community Center-West HSW (15) H/S-Wall, White, Hi 15 Cd 0.082 59 19.20 4 Community Center-West HSW (75) H/S-Wall, White, Hi 75 Cd 0.148 38 19.11 5 Community Center-West HSW (30) H/S-Wall, White, Hi 30 Cd 0.102 46 19.03 6 Community Center-West HSW (30) H/S-Wall, White, Hi 30 Cd 0.102 24 19.01 7 Community Center-West STW (15) Strobe-Wall, White 15 Cd 0.057 40 18.99 8 18.99 9 18.99 10 18.99 11 18.99 12 18.99 13 18.99 '14 18.99 15 18.99 16 18.99 17 18.99 18 18.99 19 18.99 20 - 18.99 NAC 1.0 EOLv Calc, FACP 2013.0808.xls OUTPUT 2 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: St.Anthony Community Center Job Address: 9905 SW McKenzie Street Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/8/2013 Cable Length In Feet (source to end of line) 356 Total Circuit Current 0.955 Nominal System Voltage 20.4 Panel Description: Silent Knight 5808 FACP Minimum Device Voltage 16 Panel No.: NAC 1.0 Output No.: 3 Point To Point Method EOLv 19.08 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv 18.31 Circuit Within Limits ? YES Load Centering Method EOLv 19.36 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) 1 Community Center-Center HSWC (115) H/S-Ceil, White, Hi 115 Cd 0.197 114 19.73 2 Community Center-Center STWC (115)Stb-Ceil, White 115 Cd 0.182 60 19.45 3 Community Center-Center HSWC (115) H/S-Ceil, White, Hi 115 Cd 0.197 38 19.32 4 Community Center-Center STWC (115)Stb-Ceil, White 115 Cd 0.182 60 19.18 5 Community Center-Center HSWC (115) H/S-Ceil, White, Hi 115 Cd 0.197 84 19.08 6 19.08 7 19.08 8 19.08 9 19.08 10 19.08 11 19.08 12 19.08 13 19.08 14 19.08 15 19.08 16 19.08 17 19.08 18 19.08 19 19.08 20 19.08 NAC 1.0 EOLv Calc, FACP 2013.0808.xls OUTPUT 3 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: St.Anthony Community Center Job Address: 9905 SW McKenzie Street Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/8/2013 Cable Length In Feet (source to end of line) 286 Total Circuit Current 0.734 Nominal System Voltage 20.4 Panel Description: Silent Knight 5808 FACP Minimum Device Voltage 16 Panel No.: NAC 1.0 Output No.: 4 Point To Point Method EOLv 19.58 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv 19.11 Circuit Within Limits ? YES Load Centering Method EOLv 19.76 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) 1 Community Center-East HSW (15) H/S-Wall, White, Hi 15 Cd 0.082 60 20.13 2 Community Center-East HSW (75) H/S-Wall, White, Hi 75 Cd 0.148 33 20.00 3 Community Center-East HSW (15) H/S-Wall, White, Hi 15 Cd 0.082 58 19.82 4 Community Center-East STW (15)Strobe-Wall, White 15 Cd 0.057 30 19.74 5 Community Center-East HSW (15) H/S-Wall, White, Hi 15 Cd 0.082 35 19.66 6 Community Center-East STWC (75) Stb-Ceil, White 75 Cd 0.135 28 19.61 7 Community Center-East HSWC (75) H/S-Ceil, White, Hi 75 Cd 0.148 42 19.58 8 19.58 9 19.58 10 19.58 11 19.58 12 19.58 13 19.58 14 19.58 15 19.58 .16 19.58 17 19.58 18 19.58 19 19.58 20 19.58 NAC 1.0 EOLv Calc, FACP 2013.0808.xls OUTPUT 4 INTELLIKNIGHT FIRE ALARM CONTROL PANEL IntelliKnight° 5808F ,� _ . .. Single Loop Addressable ;r ., 4 rI( Fire Alarm Control System 0 r 3 t:� e'; ' The convenience of an addressable fire .1- , ',a ./ 4. alarm control panel in a cost-effective 111. 4 -, easy to use package. iin ,r EJ ',•'. IntelliKnight Model 5808 is a 127 point class leading single loop addressable , .� r ` , fire alarm control/communicator system. 5808 provides you with the --, 0"j,'1 - revolutionary value and performance of addressable sensing technology combined with exclusive, built-in digital communication, distributed intelligent power, easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the IntelliKnight system, or to locate your nearest source, please call 1-800-328-0103, or in Connecticut, call 203-484-7161. Description „,-:'r =.2,- ,s '` The basic 5808 system can be enhanced by adding modules . - such as 5860 remote annunciator, 5824 serial/parallel printer "" � , interface module (for printing system reports), and 5496 lin ;'! intelligent power module. 5808 supports Hochiki or SK protocol ; !0'it:: ”' I --5 devices• . 5808 also features a powerful built-in dual line fire , ,h communicator that allows for reporting of all system activity to € a remote monitoring location. 5-..-..---...q +fF Features ,r4 -,,;:i5+444 • Built-in support for up to 127 Hochiki devices or 99 SK detectors and 99 SK modules *<: Y • Up to 125 zones and 125 output groups i.:' r, ,; ' ' , • Uses standard wire—no shielded or twisted pair required " •' " • Built-in digital communicator }� µ • Central station reporting by point or by zone _ • Supports Class B (Style 4) and Class A(Style 6 or 7) Model 5808 configuration for SLC • Integrated dead front panel protects operator • Distributed, intelligent power from exposure to electrical components • Drift compensation • The FACP enclosure features a Plexiglass® • 13 pre-programmed output cadences, (including ANSI-3.41), viewing window to protect annunciator and 4 programmable outputs • Notification circuits can be configured as 2 Class A(Style Z) • Acknowledge function allows operator to keep or 4 Class B (Style Y), or auxiliary power for resettable, track of event status constant, or door holder power • Built-in annunciator with 80-character LCD display Installation • RS-485 bus provides communication to system accessories The 5800 can be surface or flush mounted. • Built-in RS-232 and USB interface for programming via a PC • Upload or download programming, event history, or detector Compatibility status via remote or direct connection P y • Improvements in SKSS deliver five times faster The 5808 SLC supports multiple device types of the upload/downloads same protocol: • Built-in synchronization for appliances from AMSECO, • Hochiki Gentex®, Faraday, System Sensor®, and Wheelock® • SK • One Form C trouble relay rated at 2.5A at 27.4 VDC and two You cannot mix Hochiki and SK devices on a FACP. Form C programmable relays rated at 2.5A at 27.4 VDC However, any combination of addressable devices of • Programmable date setting for Daylight Saving Time the same protocol can be used on the 5808. • Plex-2 door option combines a dead front cabinet door with a clear window, limiting access to the panel while providing SILENT 1 single button operation of the reset and silence functions44 KNIGHT by Honeywell INTELLIKNIGHT FIRE ALARM CONTROL PANEL l I i i ....fil o NB s A 1 I 1 l; 4 I ❑. _- I ] 1_ l�^a 4 5496 h „v, . r 5808 Specifications Other Approvals: UL Listed; Miscellaneous Accessories Electrical CSFM 7170-0559: 142; 5660 Silent Knight Software Suite MEA 429-92-E Vol.XIV Primary AC: 120 VRMS at 50/60 Hz, PC-base software for FACP 2.75A programming. Upload and view panel Total Accessory Load: 6A @ 27.4 VDC S-BUS Accessories account information, event history, and Notification Power:6A @ 27.4 VDC, 5860/R Remote Fire Annunciator detector status. power-limited Features the same 80 character backlit Standby Current: 170 mA LCD display keypad and firefighter's 5670 Silent Knight Software Suite Alarm Current:325 mA key switch as the 5808. 5860 is gray End-user facility management software and 5860R is red. allows viewing of detector status and Notification&Auxiliary Circuits: event history via modem or direct 3A @ 27.4 VDC per circuit,power-limited 5496 Intelligent Power Module connection. Battery Charging Capacity: 7.0-35.0 AH A 6 amp notification power expander Battery Size: 18 AH max. allowed in that provides four additional power- Plex-2 Door FACP. Larger capacity batteries can be limited notification appliance circuit Dead front cabinet door with clear housed in an RBB accessory cabinet outputs. window to limit access to the FACP. Physical 5880 LED/IO Module RBB Flush Mount Dimensions: Features 40 LED outputs, 8 normally Remote Battery Box Accessory 14.5”W x 24.75"H x 3.5"D open dry contact inputs and one piezo Cabinet. Use if backup batteries are (36.8 W x 62.9 H x 8.73 D cm) output. too large to fit into FACP cabinet. Overall Dimensions: Dimensions: 516"W x 26.4"H x 4.65" D emot ande LED Annunciator x x R16"W 10" H 6" D(406 mm W x 254 Remot (40.6 W x 67 H x 11.8 D cm) Features 30 programmable LED (15 mm H x 152 mm D) Weight: 28 lbs. (12.8 kg) red and 15 yellow) outputs and a SD505-DTS-K Color: Red piezo sounder. The 5865-4 adds a Remote test switch that provides Telephone Requirements: silence and reset switch to the remote key operated test function and FCC Part 15 and Part 68 approved package. annunciation of detector alarm with Type of Jack: RJ31X(two required) 5824 Serial/Parallel Printer SD505-DUCTR. Approvals Interface Module Hochiki and SK Devices NFPA 13, NFPA 15, NFPA 16, NFPA 70, Provides one parallel and one RS-232 See the specification sheets listed below for & NFPA 72: Central Station; Remote serial port for connecting a printer to a complete listing of the Hochiki and SK Signalling; Local Protective Signalling 5808. Use to print a real-time log of devices. Systems;Auxiliary Protected Premises system events, detector status reports, 53624 Hochiki Devices Unit; &Water Deluge Releasing Service. and event history. Specification Sheet Suitable for automatic, manual,waterflow, 53623 SK Device Protocol sprinkler supervisory(DACT non-coded) 5883 Relay Board Devices Specification signalling services. Features 10 general purpose Form C Sheet - relays. Used with 5880 module. SILENT This document is not intended to be used for installation purposes.We try to keep our MADE IN AMERICA KNIGHT product information up-to-date and accurate.We cannot cover all specific applications or 350386 Rev.F anticipate all requirements.All specifications are subject to change without notice. For ECN 09-520 09/09 more information,contact Silent Knight 12 Clintonville Road,Northford,CT 06472-1610. ©2009 Honeywell International Inc. by Honeywell Phone:(800)328-0103,Fax:(203)484-7118.www.silentknight.com IntelliKnight&Jumpstart are Registered Trademarks of Silent Knight Flexput is a Trademark of Silent Knight INTELLIKNIGHT ACCESSORY 10SILENT 5860 Remote Annunciator 1 KNIGHT by Honeywell Bring the power to control an IntelliKnight fire alarm control panel to every area within your facility. Now you can operate and program your IntelliKnight system from up to eight locations throughout your facility. The 5860 remote annunciator provides the same advanced, easy-to-use interface found on the IntelliKnight panel's built-in annunciator. The 80-character display and ergonomically designed keypad allow for simple and error-free system operation.All operations—including reset, silence, detector status checking, fire drill, and programming—are identical. Access to the system is through a firefighter's key or an access code. For security, a special installation code is needed for programming functions.The 5860 connects to the IntelliKnight panel via the RS-485 system bus. Wire runs can be up to 6000 feet from the panel. For more information about the IntelliKnight system, or to locate your nearest source, please call 1-800-328-0103. Description multiple 5860s P P Features include an 80-character • RS-485 interface to panel backlit LCD providing easy-to- • Operation and appearance is understand system messages. The identical to 5860 built-in _ annunciator is ergonomically annunciator designed with over-sized buttons • On-board piezo sounder audibly u for the most frequently used indicates alarms, troubles, and t CZI u„u u features, like Reset and Silence. supervisories = u In addition to status messages • Five status LEDs for alarm, �►u t, supervisory, trouble, silence and displayed on the LCD, there are AC power conditions five LEDs for alarm, supervisory,p ry, • Wiring lengths up to 6000 ft. from trouble, silence, and AC power the FACP (depending on wire 5860 status. gauge and number of devices on SBUS) Environmental The annunciator is available in gray • UL listed, complies with NFPA 72 Operating Temperature: 32°F– to match virtually any decor and 120°F (0°C–49°C) red for applications where the • CSFM approved ° ° annunciator must stand out.The Electrical Specifications Humidity: 10/°–93/° non annunciator enclosure can be Operating Voltage: 24 VDC condensing surface or flush mounted.A trim Standby Current: 20 mA max Compatibility ring kit is available for surface The 5860 is compatible is the mounting. Alarm Current: 25 mA following FACP's: Features Wiring Distance: 6,000 max. from . IntelliKnight 5820XL FACP FACP (depending on wire gauge IntelliKnight 5808 FACP • 80-character backlit LCD display and number of devices on the • g (4 lines with 20 characters on SBUS) • IntelliKnight 5700 FACP each line) • Tactile and audible feedback Max Per System: 8 Approvals/Listings NFP• Accepts user codes or fire Mechanical Specifications CSFM 7 1 0-UL 5Li59: 1 fighter's key 7170-0559: 135; 9 Physical 9.1"W x 7.4" H x 1.5" D MEA 429-92-E Vol. IX; • Larger keypad buttons for system (23.1 W x 18.8 H x 3.8 D cm) FM Approved • reset and silence • Install up to eight 5860s per Shipping Weight: 2.8 lbs (1.3 kg) FACP Color • Available in red or light gray 5860R: Red 5860: Gray • Support for simultaneous use of INTELLIKNIGHT ACCESSORY 5860 Remote Annunciator Engineering Specifications J J N The main control must have a built-in annunciator and must support up to eight remote annunciators. Remote annunciators shall have the same control and display layout so as to match the appearance of the built-in annunciator. Remote annunciators shall be available in two colors, red or light gray. Remote annunciators shall have identical functionality and operation as the built-in annunciator.All annunciators must have an 80-character LCD display and must feature five LEDs for: General Alarm, Supervisory, System Trouble, System Silence, and System Power. All controls and programming keys are silicone mechanical type with tactile and audible feedback. Keys have a travel of.040 inches. No membrane style buttons will be permissible. The annunciator must be able to silence and reset alarms through the use of a code entered on the annunciator keypad or by using a firefighter's key.The annunciator must have two levels of user codes that will limit the operating system programming to authorized individuals. The control panel must allow all annunciators to accommodate multiple user input simultaneously. • Wire Runs Up to 6000 Feet From FACP MIN SBUS u u JQL 0 u u J^�L ;:au u «L =,1= u m =uuu =uau V m 5860 5860 5860 Up to Eight 5860s Per System Compatible IntelliKnight FACP Ordering Information 5860R Remote Annunicator four line LCD annunciator with 20 characters per line. Red. 5860 Remote Annunciator.Four line LCD annunciator with 20 characters per line. Gray. Accessories 5860TR Red Trim Ring for surface mounting. 5860TG Gray Trim Ring for surface mounting. SILENT This document is not intended to be used for installation purposes.We try MADE IN AMERICA to keep our product information up-to-date and accurate.We cannot cover • KNIGHT all specific applications or anticipate all requirements.All specifications are FORM#350224 Rev E subject to change without notice.For more information,contact Silent ©2010 Honeywell International Inc. by Honeywell Knight 12 Clintonville Road,Northford, CT 06472-1610. Phone: (800)328-0103, Fax:(203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY SK-Photo , .. of . and f/i .:' I ,j.. ,T: if 441 i SK-Photo-T - _ Intelligent Photoelectric Smoke Sensors ,.-,, t„4 - SK-Photo is a photoelectric smoke detector and the SK-Photo-T is a ;� .� -- _ The � '. ..1.10:14.1:0,',,t'-,--..' . photoelectric smoke detector with thermal. These plug in smoke detectors, with integral communication, provide features that surpass conventional detectors and are for use with Silent Knight IntelliKnight Fire Alarm Control Panels (FACPs). For more information about the IntelliKnight system, or to locate your nearest source, please call 800-328-0103 or in Connecticut, call (203)484-7161. Description • Plug-in mounting provides ease of SK-Photo and SK-Photo-T are plug-in installation type smoke sensors that combine a • Tamper-proof feature available on photoelectric sensing chamber with mounting bases ;, addressable analog communications. • Listed for use in duct applications Point ID capability allows each detector's address to be set with rotary • Rotary address switches for fast address switches, providing exact installation detector locations for selective • UL Listed maintenance when chamber • FM Approved contamination reaches unacceptable levels. Specifications SK-Photo and SK-Photo-T have a " unique optical sensing chamber that is Physical engineered to sense smoke produced Height:2.0"(5.0 cm) by a wide range of combustion Diameter:4.1"(10.4 cm) sources. In the SK-Photo-T, dual Shipping Weight: 5.2 oz. (147 g) SK-Photo (Base included) electronic thermistors add 135°F (57°C) Electrical thermal technology to maximize Operating Voltage: 15-32 VDC Compatibility detection. Standby Current: The SK-Photo and SK-Photo-T are compatible with the following Features 300 pA @ 24 VDC Maximum IntelliKnight FACPs: • Sleek, low-profile design Alarm Current: 6.5 mA @ 24 VDC max 5700 • Base included (with LED on) 5808 • Reliable analog communications for Environmental 5820XL trouble-free operation Operating Temperature SK-Photo and SK-Photo-T are SK-Photo: 32°— 120°F (0°C—49°C) compatible with the following detector • Age resistant polymer housing SK-Photo-T:32°—100°F(0°C—38°C) bases: • Dual electronic thermistor design on Humidity: 10%—93% non condensing B210LP (included)6"base the SK-Photo-T B501 2 wire base Other Ratings B501 BHT-2 Temporal base • Superior EMI resistance for reliability SK-Photo-T Thermal: Fixed B224RB Relay base • Simple field cleaning for code temperature set point 135°F(57°C) B224B1 Isolator base compliance Velocity:0—4000 fpm (0—20 m/sec) B501 BH-2 Sounder base • Variety of mounting options to meet SK-Photo Insect Screen Hole Size: any application 0.016"(0.41 mm) nominal • Dual LED indicators for 360°visibility SILENT • Detector transmits signal to indicate 110 KNIGHT maintenance is required • Optional remote LED annunciator by Honk;`ti 4 (System Sensor®PN RA100Z) INTELLIKNIGHT ACCESSORY Model SK-Photo and SK-Photo-T Intelligent Photoelectric Smoke • Sensors i �'. Engineering Specifications The contractor shall furnish and install where indicated on the plans, Intelligent photoelectric smoke sensors- Silent Knight SK-Photo or SK-Photo-T with thermal. The combination detector head, and twist-lock base, shall be UL listed and compatible with Silent Knight's IntelliKnight fire control panels. The base shall permit direct interchange with SK-Photo or SK-Photo-T. Base shall be the appropriate twist-lock base part number B210LP (included). The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady.The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SK-Photo shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. :LC ill OUT C e.-g1.-Inl�r. :1' 'Alit • i' /` _, f-• - f f .fry,, • • • ti 1- - I • _ • • SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA keep our product information up-to-date and accurate.We cannot cover all hN iC 1-I I specific applications or anticipate all requirements.All specifications are subject FORM#350118 Rev A, to change without notice.For more information,contact Silent Knight 12 ©2009 Honeywell International Inc. t4: Hong Clintonville Road, Northford,CT 06472-1610 Phone:(800)328-0103, Fax:(203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY SK-Pull-SA • and SK-PuII-DA . Intelligent Pull Stations �r s The SK-Pull-SA and SK-Pull-DA are a single action or dual action - • addressable fire alarm pull station for use with Silent Knight's IntelliKnight jr24 fire control panel. Extremely easy to operate, the SK-Pull-DA/SA provides ICI E' { a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes each manual pull station by its specific ,► I,�'. f address saving precious seconds in determining the location of an alarm. For more information about the IntelliKnight system, or to locate you nearest source, please call 1-800-328-0103 or in Connecticut, call (203)484-7161. Description eon The SK-Pull-SA is a single action pull station requiring only one motion to activate the station. The SK-Pull-DA is a dual Frij.I action pull station requiring two motions to active the station. • Both pull stations are designed to work with Silent Knight • ' �, DOWN 4, Intelliknight series fire alarm control panels (FACPs). Features • Installer can open station without causing an alarm condition YaLY7 ,, • Dual-color LED is visible through handle of station blinks green to indicate normal operation and remains steady red in an alarm condition SK-Pull-SA • Key operated test and reset lock using lock plate actuator • Key matches compatible FACP locks • Meets the Americans with Disabilities Act AccessibilityBUSH •IN Guidelines (ADAAG) controls and operating mechanisms fr PULL DOWN* guidelines (Section 4.1.3[13]) • Meets ADA requirement for 5 lbs maximum pull force to active labhccansEtvl 11;T • Shell, door, and handle molded from durable LEXAN® -. n • Reliable analog communications for trouble-free operation SK-Pull-DA • Braille text on station handle Compatibility • Handle latches in down position and the word Activated The SK-Beam and SK-Beam-T are compatible appears, clearly indicating the station has been pulled with the following IntelliKnight FACP's: • Rotary address switches for fast installation 5700 5808 • UL Listed, including UL 38, Standard of Manually Actuated 5820XL Signaling System 410SILENT 1 KNIGHT by Hone r•ell INTELLIKNIGHT ACCESSORY Model SK-Pull-Da and SK-Pull-SA 444 Engineering Specifications The contractor shall furnish and install where indicated on the plans,Addressable Pull Stations, Silent Knight model SK-Pull-SA single action pull station or SK-Pull-DA, dual action pull station. SK-Pull-DA or SK-Pull-SA meet the ADAAG controls and operating mechanisms guidelines, and the ADA requirements for a 5 lb. maximum pull force to activate the pull station. • sLc 0.11 • t • _ I r l I Lamite ;q.,„.,yR.„u: . c. ^.t r.,.k Specifications Electrical Physical Operating Voltage: 15-32 VDC Height: 5.5"(14 cm) Average Operating Current(LED flashing): 300 pA Width:4"(10.2 cm) Wire Gauge: Up to 12 AWG (3.1 mm2) Depth: 5.4 oz. (3.7 cm) Environmental Housing Material: LEXAN polycarbonate resin Operating Temperature 32°—120°F(0°C—49°C) Bi-Colored LED: Humidity: 10%—93% non-condensing Blinking Green: Normal Steady Red:Alarm Accessories Switch:Single pole, single throw(SPST)normally open (N/O) BG-TR Optional trim ring. switch which closes upon activation of the pull station SB-I/O Surface backbox This document is not intended to be used for installation purposes.We try to MADE IN AMERICA SILENT keep our product information up-to-date and accurate.We cannot cover all KNIGI IT specific applications or anticipate all requirements.All specifications are subject to change without notice.For more information,contact Silent Knight FORM#350135 Rev A 12 Clintonville Road,Northford,CT 06472-1610 Phone:(800)328-0103, ©2009 Honeywell International Inc. by Hon ,'well Fax:(203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY SK-DUCT n4 Y - I 4. NAL i NV ...4'bAiDetect smoke in air handling systems and ° air handling equipment with Silent Knight's addressable duct smoke detector r, Jtt The SK-Duct Intelligent Non-Relay air duct smoke detector is used with SK- • .: ;,; _ , Photo (included)for detecting smoke and products of combustion present in air moving through an HVAC air handling system. When smoke is detected in a duct, the unit communicates the condition to the IntelliKnight control panel. The panel, in turn, depending on programming and wiring, turns off fans, blowers, and other devices. Now there's even more power and flexibility available to the IntelliKnight family of products! Description The Model SK-Duct Air Duct Smoke Detector utilizes photoelectric technology for the detection of smoke. It provides early detection of smoke and products of combustion present 'gx �,'P lr ,•�- ; in air moving through HVAC ducts in Commercial and Industrial : 'Ei\ K applications. .. '. • The SK-Duct is in a heavy duty gray steel back box with a ad, clear cover. It features a pivoting housing that fits both square and rectangular footprints capable of mounting to a round or rectangular duct. It installs quickly and easily. SK-DUCT The unit senses smoke in the most challenging conditions, Specifications operating in airflow speeds of 100 to 4000 feet per minute, temperatures of-4°F to 158°F, and a humidity range of 0 to 95 Physical percent(non-condensing). (Rectangular): 14.38 in (37 cm) Length; 5in (12.7 cm)Width; 2.5 in (6..6 cm) Depth (Square): 7.75 in (19.7cm) Length; Features 9 in (22.9cm)Width ; 2.5 in (6.35cm) Depth • Versatile mounting options: square or rectangular Weight: 1.61b (0.73kg) configuration Environmental • New Cover tamper signal Operating Temperature: -4°F— 158°F • LED alarm indication and communication on sensor head (-20°C—70°C) • Detects and limits the spread of smoke • Rugged steel back box with clear plastic cover Humidity: 0%—95% (non-condensing) • Easy to clean Air Velocity • Large terminal connection screws 100 to 4000 ft/min (0.5—20.3 m/sec.) • Transparent cover for convenient visual inspection Electrical • Patented sampling tube installs from front or back of the Please see detector head installation manual detector with no tools required for electrical specifications. • Available space within housing to accommodate mounting of relay module • UL listeditsSl LENT KNIGHT by Honeywell • INTELLIKNIGHT ACCESSORY Model SK-DUCT Air Duct Smoke Detector • Engineering Specifications The air duct smoke detector shall be a SK-Duct non-relay photoelectric duct smoke detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4000 ft/min (0.5 m/sec to 20.32 m/sec). The unit shall be capable of providing a trouble signal in the event that the sensor cover is removed or improperly installed. It shall be capable of local testing via magnetic switch or remote testing using the RTS151KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12-18AWG wiring. Ordering Information • SK-Duct Intelligent non-relay duct smoke detector SK-Photo Addressable Photo Detector(included with SK-Duct) SK-Relay Addressable Relay Module,must be added if relay function is required, (fits in housing) Accessoriest DST1 Metal Sampling Tube Duct Width up to 1' DST1.5 Metal Sampling Tube Duct Widths 1'-2' DST3 Metal Sampling Tube Duct Widths 2'—4' DST5 Metal Sampling Tube Duct Widths 4'—8' DST10 Metal Sampling Tube Duct Widths 8'—12' DH4000E-1 Weatherproof Enclosure ETX Metal Exhaust Tube Duct width 1' RA100Z Remote LED Annunciator DCOIL Duct accessory coil,required on DNR if a remote test station is used RTS151 Magnetic Remote Test station RTS151KEY Key-Activated Remote Test station M02-04-00 Test Magnet P48-21-00 Replacement End Cap for Metal Sampling Tube APA151 Remote annunciator with piezo alarm Important Notes: •The use of either RTS151 or RTS151KEY requires the installation of an accessory coil, DCOIL, sold separately. Please refer to the SK-Duct installation instructions for more information •The RTS151/RTS151 KEY test coil circuit requires an external 24VDC power supply which must be UL listed • SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA keep our product information up-to-date and accurate.We cannot cover all To KNIGHT specific applications or anticipate all requirements.All specifications are subject to change without notice. For more information,contact Silent Knight FORM#350122 Rev A 12 Clintonville Road,Northford,CT 06472-1610 Phone:(800)328-0103, ©2009 Honeywell International Inc. by Honeywell Fax:(203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY SK-Minimon ;, -y 14.1A I :11 ' -0, ��� �. Intelligent Mini Monitor Module r t pi 11:3 _ ' ' F'rt ` The SK-Minimon addressable mini monitor modules for use with Silent i`;���� G p - •#S Knight IntelliKnight fire alarm control panels (FACP). The SK-Minimon is i designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm initiation devices. For more information about the IntelliKnight system, or to locate your nearest source, please call 800-328-0103 or in Connecticut, call (203)484-7161. Description The SK-Minimon is an addressable monitor modules for use with the - IntelliKnight fire alarm control panels (FACPs).The SK-Minimon acts as an interface to contact devices, such as waterfow switches and pull stations. - ` The SK-Minimon supports Class B f> supervised wiring to the load J device. Conventional 4-wire smoke +_ , detectors can be monitored for alarm and trouble conditions .?6 ., The SK-Minimon can be mounted in a single gang junction box = directly behind the monitored SK-Minimon device. Its small size and light weight allow it to be installed Specifications: Compatibility without rigid mountingElectrical The SK-Minimon is compatible with requirements. Standby Current: 400 uA max @ the following IntelliKnight FACP's: Features 24 VDC with comm. 5700 Voltage Range: 15- 32 VDC 5808 • Single contact monitor End of Line Resistance: 47 k Ohms 5820XL • SK-Minimon support for Class B (Style B) contact monitor wiring Physical • Small and lightweight size allows Dimensions: Approvals for flexible mounting options 2.75"W x 1.3" H x 0.5" D UL approved • Rotary address switches for fast Weight: 1.2 oz (37 g) CSFM installation Environmental FM Approved • UL listed Operating Temperature: 32°F— 120°F (0°C—49°C) Humidity: SILEN 1 10%—93% non-condensing 110 ! KNIGHT by Hone';kveZ INTELLIKNIGHT ACCESSORY SK-Minimon Intelligent • Monitor Module Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable monitor modules Silent Knight SK-Minimon. The modules shall be UL listed and compatible with Silent Knight's IntelliKnight FACPs. The device shall be capable of Styles A and B supervised wiring to the load device. The SK-Minimon shall be installed inside a single gang junction box directly behind the monitored unit. 1'1 - ;I cjUI r'n 0 •t 1. Z / 2 1 21 1 3 .l 1Z(. I 'TG Yi _ UIJtS I fr ...tilt rK-Mum, SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA keep our product information up-to-date and accurate.We cannot cover all KNIGHT specific applications or anticipate all requirements.All specifications are subject FORM#350133 Rev A to change without notice.For more information,contact Silent Knight 12 by Hon.,:y we:: Clintonville Road,Northford,CT 06472-1610 Phone:(800)328-0103, ©2009 Honeywell International Inc Fax:(203)484-7118. www.silentknight.com INTELLIKNIGHT ACCESSORY SK-Relay to a i :'ti � . Intelligent Relay Module *„ IRA .- ,A The SK-Relay Module is intended for use in intelligent, two-wire systems \` rag - .11 where the individual address of each module is selected using the built in ___. ..=„1-1.4.. - ice,,/ ' 1' rotary switches. ; gip- ' For more information about the Intelliknight system, or to locate you nearest source, please call 800-328-0103 or in Connecticut, call (203)484-7161. Description The SK-Relay is an addressable relay module for use with Ar--- 1 m„7.- Silent Knight IntelliKnight series fire alarm control panels �.' (FACPs). -- The SK-Relay allows a Silent Knight FACP to switch discrete - d ` - contacts by code command. The relay contains two isolated .... which operate as a DPDT switch. No --4:-:.„-y-,,, y: sets of Form C contacts, p . � supervision is provided for the notification appliance circuit. '- '4c- ti, The SK-Relay contacts can be used for virtually any normally -/ open or normally closed application. Each SK-Relay is _ 48:An programmed with a unique signaling line circuit(SLC) loop address. When an event occurs that controls the SK-Relay, the SK-Relay relay is triggered by the FACP. Installation The SK-Relay mounts directly into a 4" square Features electrical box. The box must have a minimum • Two sets of Form C contacts depth of 2-1/8".A surface mount electrical box • Rotary address switches for fast installation (System Sensor®PN SMB500) is available • Contacts are rated for a variety of amps (see Specifications) from Silent Knight • Panel controlled status LED that flashes green in normal state and is solid red in alarm Compatibility The SK-Relay is compatible with the following • Relay programming is completely flexible-can be mapped to IntelliKnight FACP's: zone conditions 5700 5808 • Polling LED visible through the cover plate 5820XL • Attractive ivory cover plate • SEMS screws for easy wiring SILENT • UL Listed 10 KNIGHT j by Honeywell 1 INTELLIKNIGHT ACCESSORY Model SK-Relay 3 �- } :: r�. } . i i , 1 - 4 If Any Wiring to Terminals 3-9 is Not Power To Next Device + 4 Limited,the CB5DD Barrier is Required. The CB500 Includes a Non-Power Limited Label, n n Which Must Be Placed Over the Power Limited Terminal Information on the Name Plate Label. Q ° C) 0 L__../ Relay Common 2 ®9 `,• 00. Normally Closed 2 Ea' •'y1 17^ Normally Open 2 Bir"„;� 2 3 ; From Compatible FACP Relay Common 1 ®° :':`''.. 3 ;= + or Previous Device Normally Closed 1 ®s =,:' 4 ;' o Normally Open 1 Module DoesNotSupervise Controlled Circuits U U Wiring the SK-Relay Module Specifications End-of-Line Resistance: not used Physical Standby Current: 300 pA max @ 24 VDC (one Height:4.65" communication every 5 sec with LED enabled) Width:4.25" LED Current: 5.5 mA(with LED latched on) Depth: 1.1" SLC Loop Resistance:4052 max. Shipping Weight: 6.3 oz(196 g) Relay Contact Ratings 3.0A @ 30 VDC resistive Electrical Operating Voltage: 15-32 VDC 0.9A @ 110 VDC resistive Current Draw: 6.5 mA max (LED on) 0.9A @ 125 VAC resistive Operating Current: 0.5A @ 125 VAC inductive(PF= .35) 230 pA(LED flashing)direct poll 0.7A @ 75 VAC inductive (PF= .35) 255 pA(LED flashing)group poll SILENT This document is not intended to be used for installation purposes.We try to MADE IN AMERICA keep our product information up-to-date and accurate.We cannot cover all N KNIGHT specific applications or anticipate all requirements.All specifications are subject to change without notice.For more information,contact Silent Knight FORM#350127 Rev A by Honeywell 12 Clintonville Road, Northford,CT 06472-1610 Phone:(800)328-0103, ©2009 Honeywell International Inc. Fax:(203)484-7118. www.silentknight.com • Wheelock° ExcederTM Series COOPER Notification ED Finally, Design and Safety Meet... t ,T FIRE . 010. Ceiling ' Wall Description: The Wheelock®ExcederTM Series of notification appliances feature a sleek modern design that will please building owners with reduced - Save up to 48% in current draw* total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw,no tools needed for setting changes,voltage test - Up to 9 models now in 1 appliance points,12/24 VDC operation,universal mounting base and multiple mounting options for both new and retrofit construction. up 14% installation** - Save to cost of The Wheelock®ExcederTM Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit.All strobe models feature an industry first of 8 candela settings on a single Sleek Modern Aesthetics appliance.Models with an audible feature 3 sound settings(90,95, 99 dB).All switches to change settings,can be set without the use of a tool and are located behind the appliance to prevent tampering. Finger Slide Switches Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock® ExcederTM Series of wall and ceiling notification Voltage Test Points appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting 1' Multiple Voltages base can be pre-wired to allow full testing of circuit wiring before VDC the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt,dust,paint 3 Audible Settings and damage to the contacts. The Contact Cover also acts as a Lig) 90,95,99 dB shunting device to allow pre-wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while u 8 Candela Settings""* it is on the UMB. When the Contact Cover is removed the circuit Wall-15/1575/30/75/95/110/135/185 will show an open until the appliance is installed.The UMB allows Ceiling-15/30/60/75/95/115/150/177 for consistent installation and easy replacement of appliances if **, required. Wall models provide an optional locking screw for extra 1.4 Universal Mounting Base secure installation, while the ceiling models provide a captivated Ceiling and Wall Mounts to 5 Backbox Types screw to prevent the screw from falling during installation. Environmentally Friendly Low Current Draw Compatibility and Requirements -Synchronize using the Wheelock®Sync Modules or panels with built-in Wheelock®Patented Sync Protocol -Compatible with UL"Regulated Voltage"using filtered VDC or unfiltered VRMS input voltage -Strobes produce 1 flash per second over the"Regulated Voltage"range Compared to competitive models "`Patented Compared to previous models NOTE:All CAUTIONS and WARNINGS are identified by the symbol I .All warnings are printed in bold capital letters. LL WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.000PERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: General Notes: •Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range". •All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. •Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32°F to 120°F(0°C to 49°C)and maximum humidity of 93%(±2%)UL 464(85%UL 1971). •Series Exceder horns are under UL Standard 464 for audible signal appliances(Indoor use only). Low Current Draw = Fewer Power Supplies Strobe per s UL Standard 1971 UL Max Current* 24 VDC/24 FWR 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140 STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110 Horn Strobe Ratings per UL 1971 &UL 464 at 24 VDC • UL Max Current*at 99 dBA 24 VDC 12 VDC Regulated e Voltag Model Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159 HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125 UL Max Current*at 95 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC . ±fb. "7 HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153 HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 - 0.230 0.272 0.122 t*"'', UL Max Current*at 90 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148 HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120 Horn Ratings per UL 464 .. °!' t.„ Model Regulated Voltage 99 dB 95 dB 90 dB - Range VDC HN 16-33.0 0.064 0.044 0.022 HNC 16-33.0 0.084 0.044 0.022 -• HN 8.0-17.5 0.047 0.026 0.017 HNC 8.0-17.5 0.047 0.026 0.017 1, *UL max current rating is the maximum RMS current within the listed voltage range(16-33 VDC for 24 VDC units).For strobes the UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage(33 VDC for 24 VDC units). For unfiltered ratings,see installation instructions. Oxy C 'a`Ta y �� ,Y rte.. LL • ' �I � r � �k.:7! � ti-'9 . pf-f11 DESCRIPTION: SERIES RSSWP, ASWP, AHWP, MTWP Wheelock's Weatherproof Strobe,Audible Strobe,Audible• and MT-12/24 Horn and Multitone Strobe appliances have an extended temperature range of-31°F to 150°F(-35°C to 66°C)that WEATHERPROOF STROBE will satisfy virtually all outdoor and severe environment WEATHERPROOF AUDIBLE STROBE applications. All strobes are Indoor/Outdoor UL Standard AND WEATHERPROOF AUDIBLES 1638 Listed and rated for 180 candela on axis @ 77°F (25°C) and 75 candela at -31°F (35°C) with low current draw. .,• The Wheelock Weatherproof Appliances are designed for i-_1 SERIES MTWP maximum performance, reliability, and cost effectiveness 1 � Mounted to IOB-R while meeting or exceeding the latest requirements of E NFPA 72 (National Fire Alarm Code), UL Standard 1638 (Standard for Visual Signaling Appliances), and UL - Standard 464(Standard for Audible Signaling Appliances). 1v,*IREf • Series RSSWP Strobes,Series ASWP Audible Strobes and SERIES RSSWP Series AHWP Audibles may be synchronized when used Mounted to WPSBB-R E in conjunction with the Wheelock SM and DSM Sync " FIR.: Modules or the PS-12/24-8CP and PS-12/24-8MP Power +. ti • Supplies with Patented Sync Protocol. The Series MTWP ("I is a true 4-wire appliance. The strobeportion can be ki,q{ PP t I tt SERIES AHWP synchronized as stated above. The multitone portion Jii Mounted to WBB-R cannot, but it can be connected to a coded fire alarm 3 t ; „f, system. 'qs t;"t�D Weatherproof Strobe Series RSSWP Is UL Standard 1638 approved for Indoor/Outdoor use. The appliances use a Xenon flashtube with solid state F circuitry enclosed in a rugged Lexan® lens to provide SERIES ASWP 1 maximum visibility and reliability for effective visual Mounted to WPBB-R E • signaling. The Series RSSWP mounts to a Series WPSBB Weatherproof Backbox. Features Weatherproof Audible Strobe and Audible Series • Approvals include: UL Standard 1971, California State ASWP and AHWP Fire Marshal (CSFM)and New York City(MEA),Factory Is UL Standard 1638 and UL Standard 464 approved for Mutual (FM)and Chicago(BFP) See approvals by model Indoor/Outdoor use and offer a field selectable choice of in Table 8 continuous horn or temporal pattern (Code 3) when • Designed to meet or exceed NFPA,/UFC/ANSI 117.1/ constant voltage from the Fire Alarm Control Panel(FACP) OSHA Part 29, 1910.165, and ADA requirements is applied. Additionally,the audible has three(3)selectable dBA settings of 99, 95, and 90 dBA in both tones and, • UL Standard 1638 and UL Standard 464 listed with extended temperature range of-31°to 150°F(-35°C to when synchronized, maybe silenced while maintainingP 9 Y strobe activation. The Series ASWP mounts to a WPBB 66°C) Weatherproof Backbox while the Series AH mounts to a • 24 VDC with new UL"Regulated"Voltage Range:of WBB Weatherproof Backbox. 16-33 VDC using filtered DC or unfiltered FWR voltage Weatherproof Multitone Strobe and Multitone Horn Note: The Series MT-12/24 voltage range is 10.5- 15.6 Series MTWP and MT-12/24 VDC (for 12V)and 20-31 VDC(for 24V) Is UL Standard 1638 and UL Standard 464 approved for • Sync/Non-Sync in each product. Note: The audible Indoor/Outdoor use and offers a field selectable choice portion of the Series MTWP and MT-12/24 is non sync of 8 nationally and internationally recognized alerting only signals. Additionally,the audible has 2 installer selectable • Synchronize with Series SM, DSM Sync Modules or PS- sound output levels: Standard and high covering a range 12/24-8CP and PS-12/24-8MP Power Supplies with (depending on selected signal)of 76-94 dBA reverberant. built-in patented sync protocol The Series MTWP is a true 4 wire appliance. The Strobe portion can be synchronized or non-synchronized. The • Selectable dBA settings multitone (audible) portion cannot be synchronized, but it • Selectable alert signals can be connected to a coded fire alarm system. The Series • IN and OUT wiring termination that accepts two#12-18 MTWP and the MT-12/24 mount to a series IOB Backbox. AWG wires at each terminal • Inputs are polarized for compatibility with Copyright 2004 Wheelock,Inc.All rights reservedindustry standard reverse polarity supervision i J • NOTE: All CAUTIONS and WARNINGS are identified by the symbol A All WARNINGS are printed in bold capital letters. ,WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS,OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION,AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: • Wheelock UL Standard 1638 Strobes are designed to produce 30-62 flashes per minute over the Regulated Voltage Range. If used in an indoor application, UL Standard 1638 strobes must be operated at a minimum of 20 VDC to meet the NFPA-72 flash rate of 1 to 2 flashes per second and ADA Guideline flash rate of 1 to 3 flashes per second. • Wheelock Weatherproof Appliances are designed to operate over an extended temperature range of-31'F to 1507(-35'C to 66°C)and all candela ratings represent minimum effective strobe intensity based on UL Standard 1638. Maximum humidity of 93%RH±2%. • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the terminology "Listed Voltage Range". ,WARNING: CONTACT WHEELOCK FOR THE CURRENT"INSTALLATION INSTRUCTIONS"AND"GENERAL INFORMATION"SHEET(P82380)ON THESE PRODUCTS. THE INSTALLATION INSTRUCTIONSAREAS FOLLOWS: P84135 FOR SERIES RSSWP,P83957 FOR SERIES ASWP,P83641 FOR SERIESAH-WP,P84150 FOR SERIES MTWPAND P824671 FOR SERIES MT-12/24-R.THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THATYOU HAVE CURRENT INFORMATION ON THESE PRODUCTS.THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS,INCLUDING: • Total current required by all appliances connected to system secondary power sources. • Fuse ratings on notification appliance circuits to handle peak currents from all appliances on those circuits. • Adding, replacing or changing appliances will effect current draw. Recalculate current draw to insure that the total average current and total peak required by all appliances does not exceed the rated capacity of the power source or fuses. • Composite flash rate from multiple strobes within a person's field of view. • The voltage applied to these products must be within their"REGULATED VOLTAGE RANGE". • Use strobe only on circuits with continuously applied operating voltage. Do not use strobes on coded or interrupted circuits in which the applied voltage is cycled on and off as the strobe may not flash. • Conductor size(AWG), length and ampacity should be taken into consideration prior to design and installation of these products, particu larly in retrofit installations. Table 1: Average Current*for Series RSSWP and Table 5: Average Current*(AMPS)for 24 V Series MTWP Strobe in MTWP -- - Audible Strobe Avg.Current* -_ -- - -- Strobe 75 cd @ Regulated 24.0 VDC UL Max* 24.0 UL -31°F(-35°C) Voltage Range 24.0 UL Tone VDC Max* VDC Max* Standard High Standard High RSSWP-2475W-FR 16.0-33.0 VDC 0.094 0.138 Horn 0.033 _0.074 0.044 0.108 Table 2: Average Current*(AMPS)For Series ASWP# Bell 0.018 0.040 0.024 0.053 March lime 0.033 0.067 0.038 0.104 High dBA Medium dBA Low dBA Voltage Setting Setting Setting Code 3 Horn 0.026 0.069 0.035 0.091 0.094 0.138 (99)dBA (95)dBA (90)dBA Code 3 Tone 0.026 0.061 0.035 0.075 24.0 VDC 0.128 0.105 0.098 UL Max* 0.168 0.155 0.150 Slow Whoop 0.028 0.069 0.037 0.098 #Audible and Visual combined. Siren 0.027 0.080 0.036 0.104 Table 3: Average Current*(AMPS)for Series AHWP Hi/Lo 0.020 0.044 0.026 0.057 Voltage AH-24WP Voltage AH-12WP AH-24WP Hi/Med/Low AH-12WP Hi/Med/Low Table 6: dBA Ratings for Series MTWP and MT-12/24 24.0 VDC 0.062/0.033/0.017 12.0 VDC 0.163/0.076/0.039 Tone Standard MTWP MT-12/24 i High1 16M 24.0 V 33.0 20.0 24.0 10.5 12.0 UL Max* 0.080/0.043/0.021 UL Max* 0.192/0.108/0.058 i Setting ! VDC DC 1 VDC VDC VDC VDC VDC Horn Standard 84 87 r 90 82 85 82 85 Table 4: dBA Ratings for Series ASWP & AHWP High Setting 89 92 ' 94 I 88 1 91 88 91 Reverberant dBA Anechoic dBA Bell Standard 1 76 80 83 75 79 75 79 Per UL464@10 ft. @10 ft. Description Volume High Setting I 83 86 i 88 82 85 82 85 24 VDC 24 VDC -_.__ _. __-__.__- -_ -.__-_- --..-- _--..---_--__i March lime Standard ' 80 84 87 1 79 82 79 82 High 91 99 Continuous High Setting 1 86 89 91 85 88 85 88 Med 88 95 HornStandard ' 79 83 86 . 75 79 75 i 79 I Low 82 90 Code 3 Horn -- • High Setting_- 85 88 90 85 85 85 85 High 85 99 Code 3 Med 82 95 Code 3 Tone Standard 76 80 82 75 75 75 75 Horn j High Setting 1 81 85 86 79 82 79 82 Low 75 90 - - 1 -- Slow Whoop 'Standard 81 85 { 87 82 82 82 82 *RMS current per are ratingsUL average RMS method. UL max current 9 g 'High Setting 87 90 I 92 i 88 i 88 88 88 rating is the maximum RMS current within the listed voltage range(16- 33v for 24v units). For strobes the UL max current is usually at the Siren 1 Standard j 81 84 j 87 82 1 82 82 82 minimum listed voltage(16v for 24v units). For audibles the max currentHigh Setting 86 89 92 85 88 85 j 88 is usually at the maximum listed voltage(33v for 24v units). For unfiltered Hi/Lo Standard 77 81 84 79 79 79 79 FWR ratings, see installation instructions. High Setting 83 86 89 j 82 1 85 82 85 - - ® • • P7-1212V, 7 OAh genesis e S N ,AAi G OA A • � � YEALEO PELNAPGFAlIE LE (L_____-- NP .-,Y -. ENENSYS . w4ni"n waw• �r�w•n' NP7- 12 -'&.,i7 '.'.. NP7- 12FR Sealed Rechargeable Lead-Acid Battery •NOMINAL VOLTAGE: 12V •CHARGE RETENTION(shelf life) 12V 7.0Ah at 687(20*C): •NOMINAL CAPACITY: 1 month 97% 20 hr.rate of 0.35A to 10.5V 7.OAh 3 months 91% 10 hr.rate of 0.65A to 10.5V 6.5Ah 6 months 85% Tern-Anal 5 hr.rate of 1.19A to 10.2V 5.95Ah 1 hr.rate of 4.20A to 9.60V 4.2Ah •LIFE EXPECTANCY: .185±.004 STANDBY USE 3 to 5 years •WEIGHT(approx.): 6.17 pounds CYCLE USE (approx.): .060 .020 (2.80 kgs.) 100%depth of discharge 250 cycles ill f'- A 50%depth of discharge 550 cycles IIAS e 5 •ENERGY DENSITY(20 hr.rate): 30%depth of discharge 1200 cycles $ 1111111 11 _ _ 1.49 WH/cubic inch(91.0 WH/liter) N •• •SEALED CONSTRUCTION: INCH= MM •SPECIFIC ENERGY(20 hr.rate): Can be operated in any position _ .250 6.35 13.6 WH/pound(30 WH/kg) without leakage. —I I .185.124 3.15 4.70 ifl -INTERNAL RESISTANCE OF CHARGED •STANDARD TERMINAL: .098 2.49 BATTERY: Quick Disconnect.187 .031 ±004 30 milliohms(approx.) or Optional.250 .060 1.52 .031 0.79 MAXIMUM DISCHARGE CURRENT •HOUSING MATERIAL: ABS Resin .020 0.51 WITH STANDARD TERMINALS: .004 0.10 40 amperes •OPTIONAL: Container and cover made from •MAXIMUM SHORT-DURATION Flame Retardant ABS DISCHARGE CURRENT: (UL94-VO/L.0.I.>28%) Dimensions 210 amperes •OPERATING TEMPERATURE RANGE: ®'' p CHARGE 5°F to 122°F I �/ (-15°C to 50°C) 65±1 p DISCHARGE -4°F to 140°F (2.56±0.00) �OF r♦/ (-20°C to 60°C) t _----- (5if1 0 8( 5.95±004) m R l �''��:t ,7k -+fi",.+L .k41G .p' A•'..--.W.- ":',7i',4 R._ DIMENSIONS:MM(INCHES) 6 +$A ,,,,,,,,,n i,s- UL listing pending-File No MH16464 , - . cnerSys . ._._ ..:.... _ .. ISO ...„.., t ,, . 9000 ,s,- Power/Full Solutions A- ; Publication No: US-NP7-12-02•July 2005 • DISCHARGE ClfAlt!_L I'ERIST€( TEMPERATURE EFFECTS IN RELATION CURVES AT 2500 (77 F) TO BATTERY CAPACITY M sv) (41 Battery Battery Battery NP Temperature 25•C(77•F) 120 14, ) 110 6.5-lJJ . 1.1.10.111.1011.11.11111111.1.10.111.1011.11.1111111.1.10.111.1011.11.1111111111111111.„mei.6� \ a� ��Mk�\� 100 zo • DoS� - \,! ,",,,1 „= 80 O, n.05.53.67 • • ..11'!IIkI1' ar.lA.00 >- ,. La /p2 G _ • 0513-3.33 F1, ..,1'. ICAO04CA BCA 1111 40 • 604 -J.0 ' 1111111 II i 111111111 c-a 20 1.111111.1 .Aa 1 2 4 68 10 20 40 60 2 4 6 610 20 -20 -10 0 10 20 30 40 50(°C) I°----min ' e- .i -24 14 32 50 68 86 104 122 (°F) Discharge Time Temperature 4'!. ' III €-1A 6 GE CI 1 AC r iC. OPEN CIiCUIT OLiAGE S ii[ty A IN IfsM CAPACI1 Y (y) M AT 25T(77F) too 14.0 a 13.0 • tat ▪ 75illhall F i ....•'” i ca EWE 50 5 12.0 s 40'c(104'F) 30'C(WE) c 25 ) 11.0 • L i „., 0 I 10.D ci 3 6 9 12 15 18 0 20 40 60 80 100 STORAGE TIME(MONTHS) REMAINING CAPACITY(%) W N U O C CVCA_I SERVICE LIFE IN iil_1..AT)(i.4 rLO LT SERVICE LIFE o TO DEPTH OF DISCHARGE a TESTING CONDITIONS:DISCHARGE CURRENT:0.17C AMP.(F.V.1.7V/CELL) po 5 S-' S^' CHARGING CURRENT:0.09C AMP. O TESTING CONDITIONS:FLOATING VOLTAGE 2.25 TO 2.30V/CELL t.. CHARGING VOLUME:125%OF DISCHARGED CAPACITY ¢ AMBIENT TEMPERATURE:20T TO 22T(64•F TO 7rF) a (AH%) AMBIENT TEMPERATURE 20'C TO 25'C(68'F TO T7'F) a (ANY.) • 120 120 C Vc 100 .E •T O i 100a •y U BO 0 BO o 60 .'.'.....,... CU c, c3 40 • 60 0 50%D.D.D. 30%DEPTH OF DISCHARGE 1- w 100%D.0.0. W 20 v i ttj 40 2 0 cc 1 2 3 4 5 5.5 0) i -O a 20 LIFE(YEARS) (i) 0 200 400 600 800 1000 1200 1400 NUMBER OF CYCLES o 0 N When the battery wit be used by current in excess of 3C,consult with EnerSys prior to use. CHARGING METHODS(At 20*C) Cycle use: Maximum charging current 1.75A N Charging voltage 14.4 to 15.0V o Standby use: Float charging voltage 13.50 to 13.80V CAUTION •Avoid short circuit a *Co not charge in a sealed container. Z e Z c 0 0 V_ • C EnerSys EnerSys EMEA Represented by: ' c P.O. Box 14145 Brussels,Belgium EnerSvs- Reading, PA 19612-4145 Tel:+32(0)2 247 94 47 USA EnerSys Asia --46,- •,zF sourro^a Tel:+1-610-208-1991 Guandong,China +1-800-538-3627 Tel:+86 755 689 9220 Printed in U.S.A. wwwenersys.com ©2005 EnerSys.All rights reserved. Trademarks are the property of EnerSys and its affiliates unless otherwise noted.