Loading...
Plans ABBREVIATIONS ELECTRICAL NOTES JURISDICTION NOTES A AMPERE 1. THIS SYSTEM IS GRID—INTERTIED VIA A AC ALTERNATING CURRENT UL—LISTED POWER—CONDITIONING INVERTER. BLDG BUILDING 2. THIS SYSTEM HAS NO BATTERIES, NO UPS. CONC CONCRETE 3. A NATIONALLY—RECOGNIZED TESTING DQ DIRECT CURRENT LABORATORY SHALL LIST ALL EQUIPMENT IN CITY OF TIGARDRECEIVED EGC EQUIPMENT GROUNDING CONDUCTOR COMPLIANCE WITH ART. 110.3. REVIEWED FOR CO E COMPLIANCE (E) EXISTING 4. WHERE ALL TERMINALS OF THE DISCONNECTING EMT ELECTRICAL METALLIC TUBING MEANS MAY BE ENERGIZED IN THE OPEN POSITION, Approved: [ NOV 16 2015 FSB FIRE SET—BACK A SIGN WILL BE PROVIDED WARNING OF THE GALV GALVANIZED HAZARDS PER ART. 690.17. OTC: [ ] (;� r� TIGARD GEC GROUNDING ELECTRODE CONDUCTOR 5. EACH UNGROUNDED CONDUCTOR OF THE Permit#: LAA5TTZc '7-- ��(`---- BUILDING uIIN GND GROUND MULTIWIRE BRANCH CIRCUIT WILL BE IDENTIFIED BY HDG HOT DIPPED GALVANIZED PHASE AND SYSTEM PER ART. 210.5. Address: k.-- --7((-- . ,--6a it/kt-k,-( .._-__(-it- HDG CURRENT 6. CIRCUITS OVER 25OV TO GROUND SHALL Suite : ii ` Imp CURRENT AT MAX POWER COMPLY WITH ART. 250.97, 250.92(B). By: -- Date: l\ (2-3(l ---- Isc SHORT CIRCUIT CURRENT 7. DC CONDUCTORS EITHER DO NOT ENTER kVA KILOVOLT AMPERE BUILDING OR ARE RUN IN METALLIC RACEWAYS OR kW KILOWATT ENCLOSURES TO THE FIRST ACCESSIBLE DC LBW LOAD MIN MINIMUM 8. WALL DISCONNECTING PER ALL WIRES SHALL BE PROVIDED WITH STRAIN OFFICE COPY (N) NEW RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY NEUT NEUTRAL UL LISTING. NTS NOT TO SCALE 9. MODULE FRAMES SHALL BE GROUNDED AT THE OC ON CENTER UL—LISTED LOCATION PROVIDED BY THE PL PROPERTY LINE MANUFACTURER USING UL LISTED GROUNDING P01 POINT OF INTERCONNECTION HARDWARE. PV PHOTOVOLTAIC 10. MODULE FRAMES, RAIL, AND POSTS SHALL BE SCH SCHEDULE BONDED WITH EQUIPMENT GROUND CONDUCTORS. S STAINLESS STEEL STC STANDARD TESTING CONDITIONS TYP TYPICAL UPS UNINTERRUPTIBLE POWER SUPPLY V VOLT Vmp VOLTAGE AT MAX POWER VICINITY MAP INDEX Voc VOLTAGE AT OPEN CIRCUIT PV1 COVER SHEET 3R NEMA 3R, RAINTIGHT � �. t � � � : � - PV2 SITE PLAN ` � PV3 STRUCTURAL VIEWS PV4 UPLIFT CALCULATIONS LICENSE GENERAL NOTES �, `� PV5 THREE LINE DIAGRAM e PV6 ELECTRICAL CALCULATIONS OR # 180498 1. ALL WORK TO BE DONE TO THE 2014 OSSC ' �" - Cutsheets Attached AND 2012 IBC. '-, - ' 2. ALL ELECTRICAL WORK SHALL COMPLY WITH 3 THE CURRENT NATIONAL ELECTRIC CODE AS �� AMENDED BY THE OREGON ELECTRICAL SPECIALTY ': CODE. n MODULE GROUNDING METHOD: ZEP SOLAR ` AHJ: Tigards BY DATE COMMENTS s u� 9 .r , : ' v ` s ":111EREV ;��DATE COMMENTS .iii,1:: � ti.;„.. :1--- t. UTILITY: Portland General Electric I' : � � I ©©© Metro.. Po l ndOregon. t ° r ago � i0 i 1 Survey®©© . n. CONFIDENTIAL — THE INFORMATION HEREIN JOB NUMBER: PREMISE OWNER: DESCRIPTION: DESIGN: JB-9723066 00 tlSolarCity CONTAINED SHALL NOT BE USED FOR THEMOREJON, TARA MOREJON RESIDENCE Jim McLean ,;BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: I NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Com Mount Type C 13710 SW MARCIA DR 8.58 KW PV ARRAY PART TO OTHERS OUTSIDE THE RECIPIENTS MODULEP TIGARD OR 97223 3055 Clearview Way ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (33) REC # REC260PEZ SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET: REV DATE: San Mateo, CA 94402 PERMISSION OF SMENT, TY INC. INVERTER: (503) 524-8459 PV 1 11/7/2015 888 c650)636-1028 f:c850)638-102 ABB ; PVI-3.6—OUTD—S—US—Z—A COVER SHEETc )-soL-aTY c�s5-2aas)www.solarcity.com PITCH: 28 ARRAY PITCH:28 MP1 AZIMUTH: 180 ARRAY AZIMUTH: 180 13710 SW Marcia Dr „.4,.. „,_,..--ss..," E � s,, MATERIAL: Comp Shingle STORY: 2 Stories i� )1©� .NICHOLAS P.".....--<0. ii co : GO-DS : ,m7,0 (E) DRIVEWAY '�Exp: o t Front Of Houserlwoe �'`�,' ,a •!/ • o .'"71, "7--1/09/2015 1 y "- 11%09/2015 A tem.'nary permit to practice in Oregon has be granted to NICHOLAS GORDON valid only until official action is taken on 11/10/2015 for Oregon registration Digitally signed by Nick Gordon Date:2015.11.09 13:41:35-08'00' ..__ . --_ LEGEND Fence a a o a o 0 (E) UTILITY METER & WARNING LABEL LOAD BEARING WALLS ® INVERTER W/ INTEGRATED DC DISCO & WARNING LABELS DC DC DISCONNECT & WARNING LABELS ■ F AC DISCONNECT & WARNING LABELS . I- 12" FSB .f.;,,=, d Mph — 0 DC JUNCTION/COMBINER BOX & LABELS — — — -r, t — � — — — - - - - - - - - ----= y V I 0 DISTRIBUTION PANEL & LABELS Ica LG LOAD CENTER & WARNING LABELS o U _ a o 1"' c e 0 ,0 o ft'`' O DEDICATED PV SYSTEM METER i W o a I CONDDUIIT RUN CONIONS EXTERIOR _1 1 CONDUIT RUN ON INTERIOR L0 UnYock&d Gated 0 „ C „ 0/ — GATE/FENCE 0 HEAT PRODUCING VENTS ARE RED ik 'I INTERIOR EQUIPMENT IS DASHED A i...-2J SITE PLAN N TOTAL ARRAY AREA (SF): 598 Scale: 1/8" = 1' �+ _ TOTAL ROOF AREA (SF): 2302 w `+ E TOTAL ARRAY AREA IS a 25.99 0 1' 8' 16' PERCENT OF TOTAL ROOF AREA IMAM/1 /Z//��/11�7/1/17/1 t, //Y. S J 3-9723066 00 PREMISE OWNER: DESCRIPTION: DESIGN: CONFIDENTIAL- THE INFORMATION USED FORHTHE .BE MOREJON, TARA MOREJON RESIDENCE Jim McLean BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: NNOR ORTSHO OTHERS DISCOUTLOSED IN RECIPIENTS OOR IN Comp Mount Type C 13710 SW MARCIA DR 8.58 KW PV ARRAY ORGANIZATION, EXCEPT IN CONNECTION WInH MODULES TIGARD, OR 97223 THE SALE AND USE OF THE RESPECTIVE (33) U REC # REC260PEZ 3055 Clearview Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME SHEET: REV: DATE San Mateo, CA 94402 PERMISSION OF SMARMY INC. INVERTER: T:(650)638-1028 F:(650)638-1029 ABB # PVI-3.6-OUTD-S-US-Z-A (503) 524-8459 SITE PLAN PV 2 11/7/2015 (888)-SOL-QTY(765-2489)www.sdarcity.com I11Ilk I \ ii GNEER.Et%_ � *e�, 1.. , • i iii cfo NICHOLAS P. •: a+pit y : GO`DON s --(0.0 9:c • t i "T 0 \Iv f ....61., „ `sem.4j0yr '1/09/2015 —B.,In, 15,-8" A tern..rary permit to practice in Oregon has be granted to NICHOLAS GORDON (E) LBW valid only until official action is taken on 1/10/2015 for Oregon registration 0A SIDE VIEW OF MP1 NTS PV MODULE MP1 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES 5/16" BOLT WITH LOCK INSTALLATION ORDER LANDSCAPE 72" 24" STAGGERED & FENDER WASHERS LOCATE RAFTER, MARK HOLE PORTRAIT 48" 19" ZEP LEVELING FOOT (1) LOCATION, AND DRILL PILOT TOP CHORD 2x10 @ 24" OC ROOF AZI 180 PITCH 28 HOLE. STORIES: 2ARRAY AZI 180 PITCH 28 ZEP ARRAY SKIRT (6) BOT CHORD 2x8 @24" OC Comp Shingle 2\ SEAL PILOT HOLE WITH (4) ZEP COMP MOUNT C • --_ POLYURETHANE SEALANT. AWINI r?iima ZEP FLASHING C .4 `�tf� III/Law.... (�) INSERT FLASHING. r-z�jv_ �iiniei■ju— (E) COMP. SHINGLE !' (4) PLACE MOUNT. (E) ROOF DECKINGINSTALL LAG BOLT WITH VALMEI MIN ---- 5/16" DIA STAINLESS (5) (5) SEALING WASHER. STEEL LAG BOLT LOWEST MODULE SUBSEQUENT MODULES INSTALL LEVELING FOOT WITH WITH SEALING WASHER (6) BOLT & WASHERS. (2-1/2" EMBED, MIN) (E) RAFTER 1 STANDOFF . Scale: 1 1/2" = 1' J B-9723066 0 O PREMISE OWNER: DESCRIPTION: DESIGN: CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: -4 .1. CONTAINED � CONTAINED SHALL NOT BE USED FOR THE MOREJON, TARA MOREJON RESIDENCE Jim McLeanBEN :,;So�arCity, NOREFIT OF SHALL ITNBENE EXCEPT OISCLOSED N WHRCITY OLE ORCIN MOUNTING SYSTEM: 13710 SW MARCIA DR 8.58 KW PV ARRAY '••," Comp Mount Type C PART TO OTHERS OUTSIDE THE RECIPIENTSMODULES: TIGARD OR 97223 ORGANIZATION, EXCEPT IN CONNECTION WITH ' 3055 geardew Way THE SALE AND USE OF THE RESPECTIVE (33) REC # REC260PEZ PAGE NAME SHEET: REV: DATE: San Mateo,CA 94402 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: T:(650)638-1028 F:(650)638-1029 PERMISSION OF SOLARCITY INC. ABB # PVI-3.6—OUTD—S—US—Z—A (503) 524-8459 STRUCTURAL VIEWS PV 3 11/7/2015 (888)—SOL—CITY(765-2489) www.sola«Ity.com GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE BOND (N) #8 GEC TO (E) UFER AT PANEL Panel Number: G2040MB1200 Inv 1: DC Ungrounded INV 1 -(1)ABB I PVI-3.6-WTD-S-US-Z-AEL: A -(33)REC # REC26OPEZ OR # 180498 WITH IRREVERSIBLE CRIMP Meter Number:24 290 470 Inv 2: DC Ungrounded FCI Inverter, Zigbee 3600W, 240V, 96 PV Module; 260W, 236.6W PTC, MC4, 40mm, Black Frame, ZEP Enabled RGC, CGC1 Underground Service Entrance INV 2 -(1)ABB /PVI-3.6-WTD-S-US-Z-A LABEL: B FCI Inverter; Zigbee 3600W, 240V, 969. Voc: 37.8 Vpmax: 30.7 INV 3 Isc AND Imp ARE SHOWN IN THE DC STRINGS IDENTIFIER E 200A MAIN SERVICE PANEL E 200A/2P MAIN CIRCUIT BREAKER ADJUST MIN. ACTIVATION VOLTAGES! (E) WIRING BRYANT Inverter 1 IND CUTLER-HAMMER COOPER (N) 125A Load Center Q Vstart = 200V 200A/2P Disconnect Meter Socket u) O5 ABB //11 DC. PVI-3.6-OUTD-S-US-Z-A Dc- MP 1: 1x8 4 • (E) LOADS A / B C 20A/2P I EGC J A — �. n ■ •i• /A L1 I zaav (10 \ • • •—I ' "`• •-- L2 .� ,DC' I \ 40A/2P _ DC- I-- WC+ Vstart = 200V m GND - GND -- , EGC/ •� DC` T v ___-� �_�__ _ W E �__— DEC i0 •� DC- c- MP 1: 1x8 - 6 I 1 = I I GND I EGC -- �- =GC Cili ADJUST MIN. ACTIVATION VOLTAGES! `(1)Conduit Kit; 3/4" EMT NI Inverter2 IND 1 — 3 J EGC/GEC —i I © ABB i DCi Vstart = 200V z- i / PVI-3.6-OUTD-S-US-Z-A I- DG MP 1: 1x9 CD 20A/2P EGG M — z GEC ��• L, ! 290V I r -C L2 DC+ TO 120/240V I I ~ N �_ Dc I SINGLE PHASE i I �`r I� Vstart = 200V UTILITY SERVICE I L_�L • EGG 1 .� x- Da I DEC N -DG -- c- MP 1: 1x8 I GND I EGC __ __ _ GC m I (1)Conduit Kit; 3/4" EMT Voc* = MAX VOC AT MIN TEMP POI—(1)SIEMENS#0240 PV BACKFEED BREAKER A _(1)CUTLER-HAMMER #DG222URB /� D i Breaker, 40A/2P, 2 Spaces Disconnect; 60A, 240Vac, Non-Fusible, NEMA 3R /-� -(1)CUTLER-HAMMER I!DG100NB Ground/Neutral Kit; 60-100A, General Duty(DG) B (1)COOPER #B-Line Meter Socket 011 Meter Socket; 125A, 4-14AWG, Ring Type -(1)AW CAP; B-Line Meter Socket Accessory -(1)Milbank Y CL2000 /Itron CIS Solid-State Single-Phase Meter; Digital C (1)BRYANT#BR48L125RP Load Center; 125A, 120/240V, NEMA 3R -(2)CUTLER-HAMMER BR220 (1)AWG #8, THWN-2, Black -Breaker;20A 2P, 7Spaces � _ __ __ _-_. --___----. _..____ O 0�(1)AWG #8, THWN-2, Red (1)AWG#10, THWN-2, Black J II (2)AWG #10, PV Wire, 600V, Black Voc* =333.43 VDC Isc =9.01 ADC (1)AWG #8, THWN-2, White NEUTRAL Vmp =240 VAC Imp=32 MC O -(1)AWG#10, THWN-2, Red O 6 �(1)AWG #6, Stranded Bare Copper EGC Vmp =245.6 VDC Imp=8.5 ADC -(1 AWG , THWN-2, Green EGC GEC-(1)Conduit Kit; 3 4 EMT (1)AWG#10, THWN-2, White NEUTRAL Vmp =240 VAC Imp=16 MC 666 (1)Conduit , P.3/4 60 . ) #B / /'.EMT. . . . . . (2)AWG #10, PV Wire, t300V, Black Voc* =333.43VDC Isc =9.01 ADC . . . , . ,7.(1)04c. #8,.THWN-2, Green _ EGC/GEC-(1)Conduit.Kit;,3/4".EMT. . . , , , . . . . O M-(1)AWG (1)AW10, THA-2, Black I� ( ) #6, Stranded Bare Copper EGC Vmp =245.6 VDC Imp=8.5 ADC ©E ( ) # (1)Conduit Kit; 3/4" EMT 0 (1)AWG 10, THWN-2, Red (2)AWG #10, PV Wire, 600V, Black Voc* =375.1 VDC Isc =9.01 ADC (1)AWG#10, THWN-2, White NEUTRAL Vmp =240 VAC Imp=16 MC O M-(1)AWG #6, Stranded Bare Copper EGC Vmp =276.3 VDC Imp=8.5 ADC - -(1)AWG#8, THWN-2,_Green . . EGC/GEC.-(1)Conduit,Kit;.3/47 EMT. . . . . _ (1)Conduit Kit;.3/4...EMT ® (2) AWG #10, PV Wire, 600V, Black Voc* =333.43VDC Isc =9.01 ADC °-(1)AWG #6, Stranded Bare Copper EGC Vmp =245.6 VDC Imp=8.5 ADC (1)Conduit Kit• 3/4" FMT '- PREMISE OWNER: DESCRIPTION: DESIGN: CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: JB-9723066 0 0 ,SM BENEFIT SHALL NOT E USEDO FOR THE MOREJON, TARA MOREJON RESIDENCE Jim McLean �;,:So�arCity BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: �•,, NOR SHALL IT BE DISCLOSED IN WHOLE OR IN CompMount Type C 13710 SW MARCIA DR 8.58 KW PV ARRAY PART TO OTHERS OUTSIDE THE RECIPIENTS "us: TIGARD, OR 97223 3055 Clearvew Way ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (33) REC # REC260PEZ SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET: REV DATE: San Mateo, CA 94402 INVERTER: T:(650)638-1028 F:(650)638-1029 PERMISSION OF SOLARCITY INC. ABB # PVI-3.6-OUTD-S-US-Z-A (503) 524-8459 THREE LINE DIAGRAM PV 5 11/7/2015 (888)-SOL-aTY(765-2489)www.sdarcity.com ELECTRICAL CALCULATIONSModule: 16 REC 260PEZ 234.3 Inv Power WPIC Voltage Drop Calculations Version 5.8.0 Inverter 1: 1 ABB PVI 3.6 S AFCI 0.96 3840 3598.85 Vdrop= Imp) * (2*Length)*(Resistance) / Vmp) Module: 17 REC 260PEZ 234.3 lImp(A) Max.Length(ft) Wire i Inverter 2: 1 ABB PVI-3.6-S AFCI 0.96 3840 3823.78 String: 8.5 65 AWG#10 at Max Ave Hi:87 deg F Module: REC 260PEZ 234.3 Vdrop= (8.5 130 0.00124 Ohms) / 230.99 0.59 Inverter 3: Branch: 8.5 40 I AWG#10 at Max Ave Hi:87 deg F Module: REC 260PEZ 234.3 Vdrop= (8.5 80 0.00124 Ohms) / 276.3 0.37 Total voltage drop,in DC conductors= 0.96 Inverter 4: Inverter: 16 10 AWG#10 at 240V Vdrop= (16 20 0.00124 Ohms) / 240 V 0.08 Total: 33 Modules Total Inv Pwr: 7680 7422.62 PTC Combined: 25.6 20 AWG#8 at 240V Photovoltaic Module Electrical Specifications: Total STC: 8580 Vdrop= (25.6 40 0.00078 Ohms) / 240 V 0.22 Voc: 37.8 V deg F deg C Vmp:_ 30.7 V Record Low Temp: 8 -13 Total voltage drop in AC conductors= 0.31 Isc:_ 9.01 A Max Average Hi Temp: 87 31 Total voltage drop in AC and DC conductors= Imp: 8.5 A Record Hi Temp: Tvoc: -0.1 V/deg C Tisc: 2.16 mA/deg C String Type A and 2 Combined Strings Type A Voc Correction Method: Manuf TVoc Data Branch Circuit Type A 1 way wire length: N/A ABB PVI-3.6-S AFCI Voc Correction Factor: 1 strings per branch 1 1 strings per branch 2 Inverter Min Vdc Input: 139 9 REC 260PEZ Min Vmp at Max Temp: 230.99 9 modules per series string 8 modules per series string Voc= 340.2 Max Voc at Min Temp: 375.1 Voc= 340.2 V Voc=' 302.4 V Vmp= 276.3 Vmp= 276.3 V Vmp= 245.6 V Inverter Max Vdc Input: 600 Isc= 9.01 Isc= 9.01 A Isc= 9.01 A Imp= 8.5 Max String Size: 14 Imp= 8.5 A Imp= 8.5 A Icont= 11.26 Art 690.8(A)(1) 1-way wire length: 40 Icont= 11.26 A Icont= 11.26 A Art 690.8(A)(1) 1.a Conductor: AWG#10 PV Wire 2.a Conductor 1: N/A Conductor 2: N/A Icont*1.25=(Amps) 14.08 Conductor 1 Conductor 2 30 deg C ampacity= 40 Icont*1.25=(Amps) 14.08 14.08 1.b Icont=(Amps) 11.26 30 deg C ampacity= N/A N/A Start ampacity 40 2.b Icont=(Amps) 11.26 11.26 Temperature derate(%=F) 0.76 Start ampacity N/A N/A Conduit fill derate(%=#) 1 Temperature derate(%=F) N/A N/A Derated ampacity 30.4 Conduit fill derate(%_#) N/A N/A 1.c Derated ampacity N/A N/A Icont*1.25=(Amps) 14.08 2.c Term 1 Term 2 _ Ampacity 40 Temp table N/A N/A (cont*1.25=(Amps) 14.08 14.08 _ 1.d Icont*1.25=(Amps) 14.08 Ampacity N/A N/A OCP Size= 15 Inverter Type A Output 2.d OCP Size= 15 15 ABB PVI-3.6-S AFCI 1 way wire length: 10 ft Combined Inverter Output Icont= 16 A Art 690.8(A)(1) Service Voltage= 3.a Icont*1.25=(Amps) 20 Art 690.8(6)(1) Total Inverter Power= 1 way wire length= 20 OCP Size= 20 Art 240.6(A) lcont=#of inverters*max inverter current Art 690.8(A)(1) 3.b Conductor: AWG#10 THWN-2 at 90 deg C:Table 310.16 Icont=(Amps) Icont*1.25=(Amps) 20 4.a (cont*1.25=(Amps) 40 Art 690.8(B)(1) 30 deg C ampacity= 40 OCP size= 40 Art 240.6(A) 3.c Icont=(Amps) 16 4.b Conductor: AWG#8 THWN-2 at 90 deg C:Table 310.16 Start ampacity 40 Icont*1.25=(Amps) 40 - Temperature derate(%=F) 0.91 30 deg C ampacity= 55 Conduit fill derate(%=#) 1 4.c Icont=(Amps) 32 Derated ampacity 36.4 Start ampacity 55 3.d Icont*1.25=(Amps) 20 Temperature derate(%=F) 0.91 Ampacity 35 Conduit fill derate(%=#) 1 Derated ampacity 50.05 4.d Icont*1.25=(Amps) 40 Ampacity 50 J 8-9723066 O O PREMISE OWNER: DESCRIPTION: DESIGN: CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: ��.,. ■ CONTAINED SHALL NOT BE USED FOR THE MOREJON, TARA MOREJON RESIDENCE Jim McLean �:,;SO�arCit�/ BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: 0'" NOR SHALL IT BE DISCLOSED IN WHOLE OR IN CompMount Type C 13710 SW MARCIA DR 8.58 KW PV ARRAY PART TO OTHERS OUTSIDE THE RECIPIENTS MODULETIGARD, OR 97223 3055 Clearview Way ORGANIZATION, EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE (33) REC # REC260PEZ PAGE NAME SHEET: REV: DATE: San Mateo, CA 94402 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: T:(650)638-1028 F:(650)638-1029 PERMISSION OF SOLARCITY INC. ABB # PVI-3.6-OUTO-S-US-Z-A (503) 524-8459 ELECTRICAL CALCULATIONS PV 6 11/7/2015 (888)-SOL-CITY(765-2489)www.sdarcity.com .' ' Label Location: Label Location: Label Location: CAUTION:SOLAR CIRCUIT (C)(IC)(CB) MAXIMUM A '; (AC) (P01) (P01) E` WARNING Per Code: OPERATING CURRENT Per Code: Per Code: IFC 605.11.1.4 MAX MUM AC - v NEC 690.54 INVERTER OUTPUT NEC 690.64.6.7 OPERATING VOLTAGE CONNECTION . . - DO NOT RELOCATE Label Location: THIS OVERCURRENT - PHOTOVOLTAIC DC 3 (DC) (INV) DEVICE DISCONNECT : Per Code: NEC 690.14.C.2 Label Location: R � I G '. (AC) (P01) V Per Code: .� Label Location: EL.ECTR[ ,SHt�GK HAZpARD '' NEC 690.17(4) DC INV Label Location: ,, D®NOTTOUCH TERMINALS - W/�RN I N G ( ) (INV) TERMINALIS®N'B®TH UNE AND A Per Code: MAXIMUM POWER- (DC) (INV) € L®AD SIDES MAYBE ENERGIZED - ELECTRIC SHOCK HAZARD NEC 690.35(F) POINT-CURRENT(Imp) Per Per Code: 41i 1 iE OPEN POSITI®N� - �� THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE TO BE USED WHEN MAXIMUM POWER- v NEC 690.53 _ - � -" H UNGROUNDEDAEM POINT=VOLTAGE(Vmp) '" INVERTER IS MAY SYSTEMBE ENERGIZED. UNGROUNDED VOLTAGE(Voc) SH®RT-CIRCUIT A� CURRENT(Isc) Label Location:;�' � "�° �' IPU SYSTEM (AC) DISCONNECT FOR UTILITY OPERATION Label Location: WARNING (DC) (C6) ELECTRICAL SHOCK HAZARD Per Code: DO°NOTTOUCH TERMINALS NEC 690.17(4) ,`' Label Location: TERMINALS ON BOTH LINE AND PHOTOVOLTAIC POINT OF (P01) LOAD SIDES MAY BE ENERGIZED INTERCONNECTION IN THE OPEN POSITIONn: Per Code: WARNING:ELECTRIC SHOCK NEC 690.17.4; NEC 690.54 DC VOLTAGE IS HAZARDDO NOT TOUCH ALWAYS PRESENT WHEN 'y TERMINALS TERMINALS ON SOLAR MODULES ARE BOTH THE LINE AND LOAD SIDE EXPOSED TO SUNLIGHT ` MAY BE ENERGIZED IN THE OPEN . w. POSITION FOR SERVICE DE-ENERGIZE BOTH SOURCE AND MAIN BREAKER. PV POWER SOURCE MAXIMUM-AC Label Location: A. sOPERATING CURRENT, WARNING r k (DC) (INV) MAXIMUM AC V Per Code: OPERATING.VOL7AGE 1 ELECTRIC SHOCK HAZARD - NEC 690.5C IF A GROUND FAULT IS INDICATED_ - ( ) NORMALLY GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED Label Location: CAUTION (P01) DUAL POWER SOURCE Per Code: SECOND S®URCE IS NEC 690.64.8.4 1` •° Label Location: PHOTOVOLTAIC SYSTEM (AC): AC Disconnect PA TOVOLTAIG AC << (AC) (P01) DISCONNECT Per Code: (C):): Combiner NEC 690.14.C.2 (D): Distribution Panel Label Location: (DC): DC Disconnect CAUTION (D) (P01) (IC): Interior Run Conduit - PHOTO.. ,.IC`SYSTEM Per Code: (INV): Inverter With Integrated DC Disconnect CIRCUIT ISIBACKFED NEC 690.64.6.4 (LC): Load Center (M): Utility Meter (P01): Point of Interconnection CONFIDENTIAL- THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR `,id!j 3055 Clearview Way THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED a= ' e San Mateo,CA 91402 IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, Label Sett�►` T:(650)638-1028 F:(650)638-1029 EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE / SoIarIity (888)-SOL-Cm(765-2489)www.solarcity.com SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. { ZS Comp Edge Zone Calculations 1 of 4 ?. ZS Comp Edge Zone Calculations 2 of 4 3/26/15 ' 3/26/15 - Zep Solar Zep Sotar This set of calculations is intended to show that ZS Comp has sufficient strength to allow for attachment Down Force Spacing spacings of at least 48"in Edge Zones whether the modules are orientated in landscape or portrait.The Allowable Down Force Load calculations will vary the design variables to account for the worst case for each failure mode that is being down force spacing = module width x design load checked. Wind Down Calculations All variable the same as above except for roof pitch General Design Information: Roof Pitch Module Size: 39"x 65" Basic Wind Speed= 120 mph 14 30 45 System Weight= 3 psf Ground Snow Load= 30 psf GCN landscape= 0.5 0.9 0.9 GCN portrait= 0.4 0.9 0.9 Comp Mount Allowable Loads Load Duration Wind Snow +f design load landscape= 15.35 27.64 27.64 psf `,'. ► " design load portrait= 12.28 27.64 27.64 psf Uplift= 656 lbs N/A , . Lateral= 357 lbs 290 lbs a85818 Rc� note:use 10 psf minimum Down Force= 1074 lbs 771 lbs OREGON13 CI Snow Calculations 4� 4t i4 To account for unbalanced snow loads,ground snow loads will be used for roof pitches 30 degrees and lower. �Ca' 'D' t� Per section 7.6.1 of ASCE 7-10 unbalanced snow loads do not need to be considered for slopes above 30 Attachment Spacing Calculations r Rc degrees. Uplift Spacing ExPir+i:S: 12r'31l15 Allowable Uplift Load FOR PAGES 1-4 uplift spacing = Ground Snow Load= 30 psf module length or width x design load Roof Pitch Wind Uplift Calculations 14 30 2014 OSSC and ASCE 7-10 Method 2 Design Snow Load 29.11 25.98 psf p=qh GCN (snow load spread over the length of the rafter) qh=0.00256 Kt Kit Kd V2 I Down Force Load Roof Pitch Basic Wind Speed= 120 mph Combinations: 1 14 30 Exposure= C Roof Zone= Edge Zone D+S= 31.16 25.10 psf Importance Factor= 1.0 K,= 0.98 from Table 6-3 D+0.6*W= 12.91 19.18 psf Gable/Hip Roof Kit= 1.0 per 6.5.7.2 D+0.75*0.6*W+0.755 31.59 31.91 psf worst Case Roof Pitch= 14 degrees Kd= 0.85 from Table 6-4 Roof Height= 30 GCN landscape= -1.6 Allowable Spacing for Down Force Ascape effective area= 13.0 ft2 GCN portrait=-1.5 portrait effective area= 21.7 ft2 landscape down force spacing = 39"x 3L91psf x 144 Ft2 = 89" Piandscape= -49.13 psf qh= 30.71 psf Pportrait= -46.06 psf 7711bs in portrait down force spacing= x 144 = 53" 65"x 31.91ps f ft2 Uplift Load Combination:0.6D+0.6W(ASCE Section 2.4.1 equation 7) design load landscape= -27.73 psf design load portrait= -25.89 psf 656 lbs in landscape uplift spacing = 39"x 27.73 psf x 144f-t2 44 ft2 = 87" - 656 lbs in portrait uplift spacing = 65"x 25.89 psf x 144 ft2 = 56" l ZS Comp Edge Zone Calculations 3 of 4 .J,ji ZS Comp Edge Zone Calculations 4 of 4 3/26/15 3/26/15 Zep ioI.ar ZepSolar Lateral Spacing Module Deflection Spacing The lateral force on the system increases as the pitch of the roof increases,but the amount of snow on the landscape module spacing = -1.4545 x Maximum Uplift or Down Force Pressure+120.7273 roof decreases for slopes greater than 30 degrees.With this in mind,the lateral force will be checked at 30 degrees with ground snow load and 45 degrees with sloped roof snow. portrait module spacing = -0.8182 x Maximum Uplift or Down Force Pressure+79.909 Allowable Lateral Load Maximum Uplift Pressure Landscape= -27.73 lateral spacing = module width x design load Maximum Uplift Pressure Portrait= -25.89 Snow CalculationsMaximum Down Force Pressure= 31.91 psf Ground Snow Load= 30 psf p5=Cs pf Roof Pitch= 31 45 degrees landscape module spacing = -1.4545 x 31.91 psf+120.7273 = 74" pf=0.7CeC5Ipg Ce= 0.9 C5= 0.71 0.45 C5= 1.2 rig= 22.68 22.7 psf portrait module spacing= -0.8182 x 31.91 psf+79.909 = 54" I= 1.0 p5= 16.1 10.2 psf Calculation Summary Roof Pitch Calculated Edge Zone Spacing 27 30 31 45 Spacing Check Landscape Portrait Design Snow Load 26.73 25.98 13.80 7.22 psf Uplift 87" 56" (snow load spread over the length of the rafter) Down Force 89" 53" Lateral 30° 27° 30° Lateral Force Component 74" 48" , 44" Down Force Load Roof Pitch Module Deflection 74" 54" Combinations: 27 30 31 45 D+S= 13.50 14.49 8.65 7.22 psf As can be seen in the table above,for Design Wind Speeds up to 120 mph and Ground Snow Loads up to 30 D+0.75*0.6W+0.75S 10.46 11.24 6.88 5.95 psf psf with modules orientated in landscape,the system is strong enough to be installed at 72"on center in the Edge Zone.When modules are installed in portrait,the spacing for edge zone installations can be 48"on Allowable Spacing for Lateral Force center for most roof pitches.For roof pitches that are greater than 27 but less than 31°,the maximum 30 degree roof pitch attachment spacing is 44". 2901bs in landscape lateral spacing = 39"x 14.49 psf x 144 ft2 = 74" 290lbs in portrait lateral spacing = 65"x 14.49 psf x 144 ft2 =44" Portrait spacing is less than 48".Try roof pitch of 27 degrees 2901bs in portrait lateral spacing = 65"x 13.50 psf x 144 ft2 =48" "•SOiarCity ZepSolar Next-Level PV Mounting Technology "4SOiarCity Zep Solar Next-Level PV Mounting Technology Zep System Components for composition shingle roofs . . . .. .. v,.... i . w - . ..fi Lik w Up roof ® Zntedock .. t!r.ev sh7wos d ~� Leveling Foot I i"""; Zep compatible w Module , a - ..� ` Zep Greve •""`. Root Attachment Array Sk ! a� i ;3___ '?,----:".7-7 i: ��? 4F Description \I � 43 • PV mounting solution for composition shingle roofs o �o sii�s tnp ...q \��� `�1 comet Works with all Zep Compatible Modules t 111u \/U \lu� • Auto bonding UL-listed hardware creates structual and electrical bond • Zep System has a UL 1703 Class"A"Fire Rating when installed using IDmodules from any manufacturer certified as"Type 1"or"Type 2" Comp Mount Interlock Leveling Foot LISTED Part No.850-1382 Part No.850-1388 Part No.850-1397 Listed to UL 2582& Listed to UL 2703 Listed to UL 2703 Specifications Mounting Block to UL 2703 a • Designed for pitched roofs • Installs in portrait and landscape orientations • Zep System supports module wind uplift and snow load pressures to 50 psf per UL 1703 Ilk" . 11 • Wind tunnel report to ASCE 7-05 and 7-10 standards 1 `; ,. • Zep System grounding products are UL listed to UL 2703 and ETL listed to UL 4671. M `'" • Zep System bonding products are UL listed to UL 2703 r'i , 4 • Engineered for spans up to 72"and cantilevers up to 24" • Zep wire management products listed to UL 1565 for wire positioning devices Ground Zep Array Skirt,Grip,End Caps DC Wire Clip • Attachment method UL listed to UL 2582 for Wind Driven Rain Part No.850-1172 Part Nos.500-0113, Part No.850-1448 Listed to UL 2703 and 850-1421,850-1460, Listed UL 1565 ETL listed to UL 467 850-1467 zepsolar.com zepsolar.com Listed to UL 2703 This document does not create any express warranty by Zep Solar or about its products or services.Zep Solar's sole warranty is contained in the written product warranty for This document does not create any express warranty by Zep Solar or about its products or services.Zep Solar's sole warranty is contained in the written product warranty for each product.The end-user documentation shipped with Zep Solar's products constitutes the sole specifications referred to in the product warranty.The customer is solely each product.The end-user documentation shipped with Zep Solar's products constitutes the sole specifications referred to in the product warranty.The customer is solely responsible for verifying the suitability of Zep Solar's products for each use.Specifications are subject to change without notice.Patents and Apps.zspats.com. responsible for verifying the suitability of Zep Solar's products for each use.Specifications are subject to change without notice.Patents and Apps:zspats.com. 02 27 15 ZS for Comp Shingle Cutsheet Rev 04.pdf Page: 1 of 2 02 27 15 ZS for Comp Shingle Cutsheet Rev 04.pdf Page: 2 of 2 Solar inverters Additional highlights: . ABB + + — RS-485 communication interface string inverters (for connection to laptop or data logger). PVI-3.0+/3.6/3.8/4.2-TL-OUTD • - Integrated Arc Fault Detection and A ; gf 3'.OkW Lo 4.2kW Interruption(-A Version). -w 1 CS, Technical data and types ` - Type code PVI-3.0-OUTD-US PVI-3.6-OUTD-US PVI-3.8-OUTD-US PVI-4.2-OUTD-US $ Mechanical specifications 3300 AftL; ttr7F-M7740 Nominal output power 3000W 3600W 3800W 4200W ,.� •�,_ ����������� 3000 3300' 3300' 3600 4000' 4000' 3300 4200' 4200' 4200 4600' 4600' Maximum output power wattage � ..: W W W W W W W W W W W W r,4 -f 1i°"',i1a f `�: '""""'�•°,. «°� Rated grid AC voltage 208V240V 277V 208V 240V 277V 208V 240V277V 208V 240V 277V 33 Input side(DC) °,a -. 1,>: Number of independent MPPT channels 2 2 2 2 Maximum usable power for each channel 2000W3000W 3000W 3000W w..- Absolute maximum voltage(Vmax) 600V -. - 0 ��up voltage(Vstart) 200V(adi.120-350V) Stert- -°` Full ower MPPT voltage range 160-530V •• 120-530V : 140-530V 140-530V 1, rte, .. .. :..... - '# Operating MPPT voltage range 0.7 x Vstart-580V(>.----•90y).. h + Maximum current(Idcmax)for both MPPT in • 20A 32A 32A = 32A Parallel ..l .. ..... .. Maximum usable current per channel 10A 16A 16A 16A - .5 Maximum short circuit current limit per 12 5A 20 OA 20 OA 20.0A ,channel, _,,,,_,,,,, „, Number of wire landing terminals per channel 2 pairsmea+ Array wiring termination Terminal block,pressure clamp,AWG10-AWG4 Output side(AC) _. 10/ Split- 10/ 10/ Split- , 10/ 10/ Split- 10/ 10/ Split- 10/ Grid connection type ;;� ,- i ........ 2W 0/3W 2W,,,, 2W 0/3W..:._2W 2W 0/3W 2W 2W....,..0/3W ;...2W J Adjustable voltage range(Vmin-Vmax)(V) 183- • 211 - • 244- 183- 211 244- 183- 211- 244- 183- 211- 244- ""`" ,,.,,_ 228V 264V 304V 228V 264V 304V ,228V„ 2ov. 304V 228V 264V 304V . . • . Grid frequency 60Hz Adjustable grid frequency range 57-60.5Hz Maximum current(I,.°.) 14.5 14.5 12.0 17.2 16.0 16.0 16.0 16 0 . •16.0 20.0 20.0 20.0 .. A„es A„ea ANAS Anes Anes AWNS ' Ai-ie. '.A„e.F.• .Aaes. . An s. A„es A„es Power factor >0.995 Total harmonic distortion at rated power <2% This family of single-phase string The high-speed MPPT offers real- Highlights: Grid wiring termination type Terminal block,Pressure clamp,AWG10-AWG4 inverters complements the typical time power tracking and improved — Single phase and split phase output Input protection devices, ” , ,, Reverse polarity protection Yes number of rooftopsolarpanels energyharvestingrid connection. ' g• Over-voltage protection type Varistor,2 for each channel . enabling home-owners to get the most The flat efficiency curve ensures high — Wide input range for increased PV array ground fault detection Pre start-up Riso and Dynamic GFDI(requires floating arrays) efficient energy harvesting for the size efficiency at all output levels allowing stringing flexibility. Output protection devices ; of theproperty. a consistent and stableperformance — The high speed and precise MPPT bveevoitage protectprotecion Meets UL 1 stor,2(L L/47 i-G)rements 9 P Over-volta e .. 9 type Varistor,2(L�-Lz/L-G) across the entire input voltage and algorithm offers real time power Maximum AC OCPD Rating 20A,,,,° 20A„eC 15A„eS_25AfV„, 20A„„, 20A,s, 20A,,,u, 20A,,,a° 20ANeC 25A„,,,,,:25Aq,A,'25A,,s This inverter offers a dual input output power range. tracking and improved energy i Efficiency section that processes two strings The transformerless operation gives the harvesting. Maximum efficiency 96 9% 97% 97% 97% ...ax efficiency enc CEC efficiency 96% with independent Multiple Power Point highest efficiency of up to 97.0%. — Outdoor NEMA 4X rated enclosure i Operating performance Tracking(MPPT). The wide input voltage range makes for unrestricted use under any Night time consumption <0 6W,,,s This is especially useful for rooftop the inverter suitable to low power environmental conditions. Stand-by consumption <8W,,,,, Communication installations with two different installations with reduced string size. — Integrated DC disconnect switch User-interface16 characters x 2 lines LCD display orientations from two sub-arrays This rugged outdoor inverter has been in compliance with international •Remote monitoring(1xRS485 incl.) VSN700 Data Logger(opt.) Environmental oriented in different directions.(For designed to be a completely sealed Standards(-S Version). Ambient air operating temperature range -13°F to+140°F with derating above 122°F(50°C) example:East and West) unit able to withstand the harshest Ambient air storage temperature range -40°F to+176°F(-40°C to+80°C) • The dual input sections with environmental conditions. Relative humidity 0-100%RH condensing Hite pendent MPPT enable a more Acoustic noise emission level <50 db(A)@t m P 11 IR MO Maximum operating altitutde without derating 6560 ft(2000 m) optimal energy harvesting condition. Power and productivity 1 capability enabled at oommai AC voltage and with sufficient DC power available me• for a better world'”" ir 2 ABB Solar Inverters I Product flyer for PVI-3.0/3.6/3.8/4.2-TL-OUTD ' .:..:::„: -,,.,,,•_, . , .. N' - - - ENERGIZING LIFE TOGETHER �� RCC � 34 02 REE p - v ENERGY .EFFICIENCY HIGH PERFORMANCE : ----- Q ; YEAR FROCiUCT WARRANTY SOLAR PANELS ti % }©UTPUT( EARRAUNTYR a ' l. l �'` P A 1,1 �� 1 �/ A ;rq .. 41 r >w,v �- ,,. y*� ,i U5 IMPORT DUTY FREE ., 't I �U REQ �IERGY � 1 m - - -' 1 TEMPERATURE RATINGS Nominal0 erat!n CeliTem erature NOCt) 45.7°C s2°C ! Tem eratureCoefficientofP 0.40%/°C LU\K II(' r ( R . _,, _--. —__......_....._ TemperatureCoefficientofVbc 0.27%,°C , , . TemperatureCoefficientoflsc 0.024%/°C REC Peak Energy Z-Link Series solarli A I eteasnren ents,n oche= apply are the perfect choice for building. ELECTRICAIDATA @STC REC260PEZ GENERAL DATA a solarsystemsthatC©rrlbinelonglasting . . ! ' Nominal Power-PM,,,,(Wp) 260 CellType 60RECPEmulii-crystalline " 1 3 strin""s of20 cells w th bypass diodes � .... N,-pr©elur�t quality-with reliable power-output: < ,�,..m... _ wattaa55snrting-IWP) tJ-5 f � �;, .. .�.�.. . ._.v Glass ; 0125 insotarglasswlthanti-reflection i _ Nominal Power Voltage-VM,,,,(V) . a - � �`f� CCi1�lb1f125 high gUd�lty design and r � surface treatment Nominal Power Current-IM,,,,(A) 831505780 ,E ,= BackShee rhighlyresistoetpol ester 1 — ma> ufiact ''''' standards to produce high t Donblelaye y OpenCircwtVoltage-Voc(V 378 Framer �, Anodized aluminum(black) p C1rr11dn e so ar panels Wltii - 5hortCircwtCurrent-Is�(A) 9.01 ZepGroovecompatlble 1 �unfompromisingquality. Panel Efficiency(%) JunetlonBox T.- . IP67rated 0156A, in(12 AWG)solar cable,2 x 4724 in JThe electr cal cha,°cte,sou are w,thurv/10%uf the nd,�ated values of l,r,Va and PM,�at standard Test condrt,ons(STC) dd y Values at standard test cond,tmns STC(a,reruss AMI 5,r,ad,ance 1008 W/nr cell tempe,azure 77°F!25°CII Connectors ,p H4 Amphenol 0 f p� cot" PA r/ Al low,r,ad ante of 200W/0 (AM 15&refitemperanua 77.F 125°C11 at Ieas 197%nf the STC panaI ff:enc9 WI 1ffe a6hiev°d. t',=III !i r 1t.; Q Origin: MadeinSingapore I.i ( II' ! x'. �,� 1� � �, H 71. Fs as, !' • • �1' ELECTRICAL DATA@NOCT REC260PEZ MAXIMUM RATINGS I ` W/<{ t�`q v44 .. Nominal Power-PMi,i,(Wp) 197 Operational Temperature: -40...+185°F)40...+85°C) COMPP' Nominal Power Voltage-VMnr(VI 29.0 Max!mumSystemVoltage: 1000VUL m tt .,,. 't, .,.,�ign Y,,.c,Y� ..,. ,, a ` NominalPowerCurrent-IMn„(A) 681 DesignLoad 50tbs/ft (2400Pa)longside MORE POWER COMPATIBLE W ITH Open Circult Voltage- ac(V) 35 7 301bsJftz{1436 Pa)short side PER FT= ZEPGROOVEfRAME �r ! 0,, ,,, r. -;/, . Short Circuit Current Is, 724 Max Series FuseRatmg - 15A i �r� Nn ,nal pe,ac„g ecce,,,pe.an,ieNOCT(asses/n�',AMIS.wn,dspeedln/Sanu,e rcen,pe,att,eCeF120Cl ManReverseCurren i5A I ��" ��`""'� {{� _,� ,,. ' ;, ✓ CERTIFICATION_ WARRANTY.. MECHANICAL DATA. ,^�,t r I0 yearproductwarraety Dimensions, 5x39.02x1,57in(1665x991x40mm) f'' C I US 25 year linear power output warranty Area: `' 1775 ftz(1.65 m2) Wi USIMPORT EASY TO /. (max degressioninperformanceof0.7/op.a). z� .`, Ai r LISTED o g ,# pUTVFREE INSTALL ✓f -' r Weight: 43 lbs(19.S kg) v+ UL 1703,Poeranng Type 1,ClClassC .�.�� a Note! Allgtvenspecficationsaresubjecttochange " ° rf f t a F withoutnotiteatanytime. '",',;.':'%:- REC is a leading global provider of solar energy solutions. With more than years of experience,we offer sustainable,high performing ,?,:,:',''';',..-..'''-'6'.:-*.oVir[ ' ''''- '' '' r j;, '`rr'Ff;y��' '`a ✓rte`a :C.'..,,'''-.,'"..!;,::;:V �,rf fp"j .� 3/ producs,services and investments for the solar industry.Together with o1,111 partners,we create value by prowdmg soluLons that better R C C it !r'r Ff r' �` y ✓ ' Ir «` `'` ;r k ''f meet the world'sgrowingenergyneeds.RECisheadquarteredmNorwayandhstedontheOsloStockExchange(ticker:RECSOL) Our1,600 t� r,f, ,� .ffd {.¢ { r .!f r ' ` ' employees worldwide generated revenues ofU5D647millionm2013. °�?-,,,,,,,,,f,--,g ;.,1,..„,.-,„, .^✓" :f r.+ .f ,f I ,. r -l s r r ire ,-.--;.y.,-;.,-,,,,,,,,,,;-,. r f 1 ! www.recgroup.com r'r Y f_- '-*f. r. .i„,,--,..;`-:`-, --,:;',>-:;,-,/ t '-f::-.,,,'''':::''''-''':;.•;r,':';','.",� '''. ''''....t.",-''..'.,':.:;;' '✓ � /prr'� �� '•�` >,,,/,'...,, x �� y f f� r l { r` f , i r' lx f rt r 4''';',„'''.;:r.;'''':,'-',,,,rlr. --;','. .,•,-, r Y/' • xr f:',:;., ..� l . r << r f f , K ' ` r `fir13t:7‘ '':-,:,,%., :':,...%--',,,',;-.Z",,,'' f�,.p 'r > r �r l r ' 7 �,f:'-:':'.:;',--'':;''',. r'� .0 f. ,�lfr,'=�,/ rr " Si '✓,fi .?° }..r 7 V .F r `��:f a "^ j.. r __6� f ri .r d rrf r r`'..��` I� ,€ {p� � .'.:::°';',' "� ''",;;i",,, r' =�er�` "r'i`;s 3' / .e'`e a.r t rt ° nr fi �' ra J- t Jtf