Report -p,s201L4- 00IaL( 52-3O w v(3- Ck FLEXHEAD INDUSTRIES ') c LISTED Ol us ® :LRCM WEIVED MAXIM Installation Of Flexhead Commercial Sprinkler System JUL 21 2014 1. Mounting Bracket Assembly M#: MP-24-BKT-2 TIGhRD 714U Remove one(1)3/8"bolt and one(1) %."bolt from hardware bag in box. Remove(1) unive , i..'•• t• • + (1)mounting bracket from box. Thread the 3/8"bolt through side of universal hub. Select', I I. (4)sprinkler port locations on mounting bracket. la .4111111111B A. Insert tab of universal hub into slot on mounting bracket as shown. (Photo 1 a) B. Flip bracket over and insert and tighten /"attachment bolt thru pre-punched hole in bracket until tight as shown. (Photo 1b) 2. Attach Mounting Bracket to T-bar Suspended Ceiling Grid. *Note: These products are designed for use with Intermediate or Heavy Duty ceiling grids manufactured to ASTM C 635 (Standard Specification for the Manufacture, Performance, and Testing of Metal Suspension 1 b Systems for Acoustical Tile and Lay-in Panel Ceilings)and ASTM C 636(Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels)Designation. A. From above the ceiling, position FlexHead Mounting Bracket ends on to T-bar grid so that the center hole , in support bracket aligns directly above the sprinkler hole prepared in ceiling tile. Be sure the center section of the bracket end is on the outside of grid and base section is on the inside. Position the ends of the support `" �./ bracket on the T-bar grid and push each of the two(2)ends of the bracket down to snap in place as shown. (Photo 2) 2 3. Anchor Bracket to T-bar Grid la A. Anchor bracket to t-bar grid with self tapping screw through bottom hole in bracket end into grid. Be sure to install self taping screw in lower hole of bracket end with attachment clip as shown. Repeat ,f— process on opposite end of bracket. Both ends of bracket should be anchored as shown.(Photo 3) 4. Connect FlexHead to Sprinkler Branch-line Apply teflon tape and pipe sealant to one inch (1") threaded end of FlexHead Sprinkler Drop per NFPA guidelines.Attach one inch(1")threaded end of FlexHead Sprinkler Drop to branch-line per NFPA, State and local code guidelines. The flexible hose with fitting is only intended to be installed with bends. 4 r" Do not use welded or braided hose section of FlexHead Sprinkler Drop for a wrenching surface. Attach FlexHead Sprinkler Drop using rigid pipe end of units as wrenching surface as shown.(Photo 4) 5. Secure FlexHead Sprinkler Drop to Mounting Bracket and install Sprinkler Head. _A. Bend the Flexhead to hold its desired position. Do not overbend the flexible hose. FlexHead has a 3" (75mm) minimum bend radius. Insert reducing coupling end of FlexHead Sprinkler Drop through center hole in previously installed support bracket and hole in ceiling tile. Make sure the hose is bent sufficiently so 5a • _ that the reducing coupling sits perfectly vertical in center hole of support bracket. Do not torque or twist FlexHead during installation process.(Photo 5a) B. Attach sprinkler head, properly prepared with teflon tape and sealant to FlexHead Sprinkler Drop according to NFPA and sprinkler head manufacturer's guidelines.(Photo 5b) C. Adjust FlexHead Sprinkler height to accommodate l p g type of sprinkler head. When sprinkler head is in desired location, tighten the fastening bolt on center hub of support bracket by turning clockwise hand tight Sb plus 1 turn (100 inch Ibs)with wrench as shown. After tightening the bolt, tighten the nut hand tight plus 1 turn(100 inch Ibs)with wrench. (Photo 5c) 6. Installation of the FlexHead Ceiling Sprinkler System is complete. "Test installation of sprinkler system for any leaks per NFPA Guidelines. 'Install sprinkler escutcheon from below ceiling per manufacturers guidelines. ti.m.2111d, _ 5c Flexhead Industries,Inc. 56 Lowland Street Tel 800-829-6975/508-893-9596 Holliston,MA 01746 Fax 508-893-60201 www.flexhead.com U.S and International Patent Pending: #6,123,154,#6.119,784,#6,752,218,#7.032,680,#6,488,097 FGG/BM System Compatible indicates this product has been tested and is monitored on an ongoing basis to assure chemical compatibility with FlowGuard Gold,Blazemaster,and Corzan pipe and fittings. The FlexHead name and logo are trademarks of FlexHead Industries. FGG/BM,FlowGuard Gold,Blazemaster,and Corzan are registered trademarks of Noveon IP Holding Corp. • FlexHead Friction Loss Data Flexhead Outlet Size Hose Maximum Rated Pressure Model# Assembly Maximum Maximum Length Equivalent Maximum K-factor& Length of Ambient Orifice of Maximum Number Schedule 40, Temperature Sprinkler of 90-Degree Nominal I in Rating K-factor/orifice Bends Diameter Pipe F(C) (3 in.Bending (C=120),ft H-Series in(cm) Ft(m) Radius) psi(kPa)/ psi(kPa) 2024,2024H 1/2(1.27) 2(0.6) 3 11 300° (148°) 175(1205)/300(2068) 5.62/1/2" 2036,2036H 1/2(1.27) 3(0.9) 3 16 300° (148°) 175(1205)/300(2068) 5.62/1/2" 2048,2048H 1/2(1.27) 4(1.2) 4 24 300° (148 0) 175(1205)/300(2068) 5.62/1/2" 2060,2060H 1/2(1.27) 5(1.5) 4 29 300° (148°) 175(1205)/300(2068) 5.62/1/2" 2072,2072H 1/2(1.27) 6(1.8) 4 35 300° (148°) 175(1205)/300(2068) 5.62/1/2" F �. 2024,2024H 3/4(1.90) 2(0.6) 3 1 2 300° (148°) 175(1205)1300(2068) 14.0/3/4" I' 2036,2036H 3/4(1.90) 3(0.9) 3 18 300° (148°) 175(1205)/300(2068) 14.0/3/4" I O 2048,2048H 3/4(1.90) 4(1.2) 4 23 300° (148°) 175(1205)/300(2068) 14.0/3/4" 2060,2060H 3/4(1.90) 5(1.5) 4 29 300° (148 0) 175(1205)/300(2068) 14.0/3/4" I. 2072,2072H 3/4(1.90) 6(1.8) 4 32 300° (148°) 175(1205)/300(2068) 14.0/3/4" 0 S s 2024E,2024HE 1/2(1.27) 2(0.6) 3 19 300° (148°) 175(1205)1300(2068) 5.62/1/2" 2036E,2036HE 1/2(1.27) 3(0.9) 3 23 300° (148°) 175(1205)/300(2068) 5.62/1/2" 2048E,2048HE 1/2(1.27) 4(1.2) 4 27 300° (148°) 175(1205)/300(2068) 5.62/1/2" 2060E,2060HE 1/2(1.27) 5(1.5) 4 32 300° (148°) 175(1205)/300(2068) 5.62/1/2" 2072E,2072HE 1/2(1.27) 6(1.8) 4 35 300° (148°) 175(1205)/300(2068) 5.62/1/2" 2024E,2024HE 3/4(1.90) 2(0.6) 3 18 300° (148°) 175(1205)/300(2068) 14.0/3/4" 2036E,2036HE 3/4(1.90) 3(0.9) 3 23 300° (148°) 175(1205)/300(2068) 14.0/3/4" 2048E,2048HE 3/4(1.90) 4(1.2) 4 23 300° (148°) 175(1205)/300(2068) 14.0/3/4" 2060E,2060HE 3/4(1.90) 5(1.5) 4 29 300° (148°) 175(1205)/300(2068) 14.0/3/4" 2072E,2072HE 3/4(1.90) 6(1.5) 4 32 300° (148°) 175(1205)/300(2068) 14.0/3/4" • FlexHead products are intended for use in hydraulically designed wet,pre-action,deluge or dry pipe sprinkler per NFPA 13, 13R,and I3D guidelines. • The hydraulic loss of FlexHead should be included in the hydraulic design calculations the same as a valve or fitting. • Each FlexHead Sprinkler Drop has a 3"minimum bend radius per UL guidelines. FlexHead products are listed to limited flexibility standards and are intended for direct connection to fire sprinklers. • Bracket System MP-24-BKT-2 has a minimum of 6 inch and a maximum of 24 inch spacing requirement for anchoring to the building component. y ,1 f■11,' stm;ig e 1�( txataltRta IVHI'1'11 flullfad ,(i•i.‘ s ankle A'[tj1 —' 1/kilts-pun coding wed mounting limb* . A4p.ptalstab 1 . . t .11 vi I t° np 06/11/2009 Sptmklt Nod um incsu s4) June 28, 2013 Sprinkler 11j STANDARD RESPONSE TECHNICAL DATA CONCEALED PENDENT SPRINKLERS (VK102&VK202) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 • Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION _ . Viking Standard Response Concealed Pendent Sprinklers are thermosensitive glass bulb spray sprinklers pre-assembled with a threaded adapter for installation with a domed cover that provides up to 1/2" (12.7 mm) of vertical adjustment. The cover plate is available with several decorative finishes to meet design requirements. The Electroless Nickel PTFE (ENT) finish has been investigated for installation in corrosive atmospheres and is listed/approved as corrosion resistant as indicated in _ the Approval Charts. (Note: FM Global approves the ENT coating as corrosion resistant.) The ENT finish is only available for the sprinkler assembly, the cover , plate is not plated ,i.: „. ; The two-piece design allows installation and testing of the sprinkler prior to instal- lation of the cover plate. The "push-on", "thread-off design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been ;�'� I,: .; �,'; ;•: tested and the ceiling finish has been applied.The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the ' sprinkler system out of service or removing the sprinkler. 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV cO„s FM Approved: Classes 2015 -(2> Refer to Approval Chart 1 and Design Criteria on page 11 m for cULus Listing requirements, and refer to Approval Chart 2 "'" and Design Criteria on page 11n for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Maximum Working Pressure: 175 psi(12 bar). Factory tested hydrostatically to 500 psi (34.5 bar). Thread Sizes: Sprinkler VK102: 1/2"(15 mm)NPT, Sprinkler VK202: 3/4"(20 mm) NPT Nominal K-Factors• Sprinkler VK102: 5.6 U.S. (80.6 metric`), Sprinkler VK202: 8.0 U.S. (115.2 metric`) Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to-65°F(-55 °C) Overall Length (sprinkler body): Sprinkler VK102: 2-1/4" (57 mm), Sprinkler VK202: 2-5/16" (59 mm) Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinkler VK102. Brass UNS-C84400 for Sprinkler VK202. Viking Technical Data may be found on Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 The Viking Corporation's Web site at Bulb: Glass, nominal 5 mm diameter http://www.vikinggroupinc.com. Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with The Web site may include a more recent Teflon Tape Compression Screw: Brass UNS-C36000 edition of this Technical Data Page. Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Cover Adapter Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating Cover Assembly Materials: Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800 Spring: Beryllium Nickel Solder Eutectic Ordering Information: (Also refer to the current Viking price list.) Viking Standard Response Concealed Pendent Sprinklers VK102 and VK202 and Cover Plate Assemblies must be ordered sepa- rately: Form No. F_070703 Replaces page 11j-o, dated June 5, 2013. (ENT finish is now approved as corrosion resistant.) Sprinkler 11k June 28, 2013 NIKIN6® STANDARD RESPONSE TECHNICAL DATA CONCEALED PENDENT SPRINKLERS (VK102 &VK202) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 ' Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Sprinkler: Base Part No. 12987A-X, 18020A-X or 10142A-X for brass finish, and 12987JN-X or 10142JN-X for ENT finish(includes sprinkler and adapter pre-assembled, with a protective plastic cap covering the unit) Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number: Temperature Suffix: 155 °F (68°C) = B, 175 °F (79°C) = D, 200°F(93 °C)= E For example, concealed sprinkler VK102 with a 155°F (68°C)temperature rating = 12987ABX. Note:When ordering this sprinkler using the SIN,add suffix-D. For example,concealed sprinkler VK102=VK102-D. Cover Plate Assembly: Base Part No. 12381 Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover temperature rating to the base part number: Finish Suffix: Polished Chrome=F, Painted White=M-/W, Painted Ivory =M-/l, Painted Black =M-/B Temperature Suffix: 135°F(57°C)=A (for use with 155°F(68°C)rated sprinklers only), 165°F(74°C)=C(for use with 175°F(79°C) or 200°F (93°C) rated sprinklers). For example, cover 12381 with a Polished Chrome finish and a 135 °F (57 °C)temperature rating = 12381 FA. Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the"Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrench: Part No. 13577W/B**(available since 2006) ratchet is required(not available from Viking). Sprinkler Cabinet: Part No 01731A(available since 1971) 4. INSTALLATION - Refer to appropriate NFPA Installation Standards. I WO 5. OPERATION Lam, or? • During fire conditions, when the temperature around the sprinkler approaches gl its operating temperature, the cover plate detaches. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand li and the bulb to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements -- 7. AVAILABILITY The Viking Standard Response Concealed Pendent Sprinklers are available � through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. Figure 1: 8. GUARANTEE Concealed Sprinkler VK102 and Cover 12381 For details of warranty, refer to Viking's current list price schedule or contact Viking directly. June 28, 2013 Sprinkler 111 ® STANDARD RESPONSE TECHNICAL DATA CONCEALED PENDENT SPRINKLERS (VK102 &VK202) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES •rinkler Temperature ,• Sprinkler Nomin-. ' Maxi ..urn Ambien, Ordinary 155 °F(68 °C) 100°F(38°C) Red Intermediate 175 °F(79 °C) 150 °F(65°C) Yellow Intermediate 200 °F(93 °C) 150 °F(65 °C) Green Cover Plate Finishes: Polished Chrome, Painted White. Painted Ivory, or Painted Black Sprinkler Finishes: Brass or ENT(See Ordering Information section page 33K) Corrosion-Resistant Coatings': ENT Footnotes 'The sprinkler temperature rating is stamped on the deflector. 'Based on NFPA-13.Other limits may apply.depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 'The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts.These tests cannot and do not represent all possible corrosive environments. Prior to installation,verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment.For automatic sprinklers,the ENT coating is applied to all exposed exterior surfaces,including the waterway. For ENT coated sprinklers the belleville spring is exposed. \0), cusroyA • ti diameter opening / o required in 6 4 the ceiling. NIKING Identification of Custom Paint Color: B All custom color painted cover plates will have an identifying label affixed to the inside of the cover that indicates custom Sprinkler and color and will have a representative sample Sprinkler - Adapter Assembly Ca paint dot) of the paint on the label, Wrench (Protective Shell Figure 3: Identification of Custom Paint Color Part No. Removed for for Concealed Covers 13577W/B** Installation.) x*A 1/2' ratchet is required (not available from Viking). • Figure 2: Sprinkler Installation and Correct Use of Wrench Sprinkler 11 m June 28, 2013 STANDARD RESPONSE TECHNICAL DATA CONCEALED PENDENT SPRINKLERS (VK102 &VK202) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 1 (UL) Sprinkler Temperature Rating Standard Response Concealed Pendent Sprinklers Covar Plats Temperature Rating AWtt Cover Plate Finish KEY Maximum 175 PSI(12 bar)WWP NPT Sprinkler Thread Size Nominal K-Factor Overall Length Listings and Approvals' Base Part SIN (Sprinkler Body) (Refer also to Design Criteria below.) Number Inch mm U.S. metric' Inches mm cULus° NYC VdS LPCB 12987A-X VK102 1/2" 15 5.6 80.6 2-1/4- 57 AW1, BX1 See Footnotes -- _- 12987JN-X• VK102 1/2" 15 5.6 80.6 2-1/4" 57 AW1, BX1 See Footnote 5 -- -- 18020A-X VK102 1/2" 15 5.6 80.6 2-1/4" 57 AW1, BX1 See Footnotes -- -- 10142A-X VK202 3/4" 20 8.0 115.2 2-5/16" 59 AW1, BX1 See Footnote 5 -- 10142JN-X" VK202 3/4" 20 8.0 115.2 2-5/16" 59 AW1, BX1 See Footnote 5 -- -- Sprinkler Temperature Ratings Cover Plate Assembly Temp. Ratings' Finishes of the Cover Plate Assembly' A- 155 °F(68°C) W- 135°F(57 °C)cover 12381' 1 -Polished Chrome. Painted White, Painted B- 175 °F(79°C) and 200 °F(93°C) X- 165 °F (74°C) cover 123811 Ivory, or Painted Black Footnotes ' Part number shown is the base part number.For complete part number, refer to current Viking price list schedule. 2 Metnc K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 3 This chart shows the listings and approvals available at the time of printing.Other approvals may be in process.Check with the manufacturer for any • additional approvals. 'Listed by Underwriter's Laboratories for use in the U.S. and Canada. 8 Meets New York City requirements,effective July 1,2008. 'The 135°F(57°C)cover has an orange label.The 165°F(74°C)cover has a white label. s cULus Listed as corrosion-resistant. 'Standard painted finishes consist of Polyester Baked Enamel.Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer.Contact Viking for additional information. NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3. DESIGN CRITERIA - UL aii:e.' v'•'ss. �+_i..••.awav� °A '(:.t- '. I.�tebf7E�.`..L.....s\ _ cULus Listing Reauirements; Viking Standard Response Concealed Pendent Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light, Ordinary,and Extra Hazard occupancies. • Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. • Minimum spacing allowed is 6 ft. (1.8 m)unless baffles are installed in accordance with NFPA 13. • Minimum distance from walls is 4 in. (102 mm). • Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall. • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. • DEFLECTOR POSITION: Install Concealed Pendent Sprinklers VK102 and VK202 with the deflector 3/8"(9.5 mm)to 7/8"(22.2 mm)below the ceiling. Refer to Figures 3 and 4. NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. June 28, 2013 Sprinkler 11n N1KING® STANDARD RESPONSE TECHNICAL DATA CONCEALED PENDENT SPRINKLERS (VK102&VK202) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 • Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 2 (FM) Spnnkler Temperature Rating Response Concealed Pendent Sprinklers Cover Plate Temperature Rating• Standard Res P P gVi/1t cover Plate Finish KEY Maximum 175 PSI (12 bar)WWP Sprinkler Overall Length NPT Thread Size Nominal K-Factor FM Approvals 3 Base Part SIN (Sprinkler Body) Number' Inch mm U.S. metric' Inches mm (Refer also to Design Criteria below.) 12987A-X VK102 1/2" 15 5.6 80.6 2-1/4" 57 AW1. BX1 12987JN-X` VK102 1/2" 15 5.6 80.6 2-1/4" 57 AW1. BX1 18020A-X VK102 1/2" 15 5.6 80.6 2-1/4" 57 AW1, BX1 10142A-X VK202 3/4" 20 8.0 115.2 2-5/16" 59 AW1, BX1 - 10142JN-X6 VK202 3/4" 20 8.0 115.2 2-5/16" 59 AW1, BX1 Sprinkler Temperature Ratings Cover Plate Assembly Temp. Ratings' Finishes of the Cover Plate Assemblys A- 155 °F (68 °C) W- 135 °F(57 °C)cover 12381' 1 - Polished Chrome, Painted White. B- 175°F (79°C)and 200 °F(93°C) X- 165 °F(74°C)cover 12381' Painted Ivory. or Painted Black Footnotes ' Part number shown is the base part number.For complete part number, refer to current Viking price list schedule. Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This chart shows the FM Approvals available at the time of printing.Other approvals may be in process.Check with the manufacturer for any additional approvals. °The 135°F(57°C)cover has an orange label.The 165°F(74°C)cover has a white label. 'Standard painted finishes consist of Polyester Baked Enamel.Other paint colors are available on request with the same listings as the standard paint colors.Approvals apply for any paint manufacturer.Contact Viking for additional information. 6 FM approved as corrosion resistant. NOTE:Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3. DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above.) FM Annroval Reouirements; The sprinklers indicated in Approval Chart 2 are FM Approved as standard response Non-Storage concealed pendent sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design,ceiling slope and obstructions,minimum and maximum allowable spacing, and deflector distance below the ceiling. • DEFLECTOR POSITION: Install Concealed Pendent Sprinklers VK102 and VK202 with the deflector 3/8"(9.5 mm)to 7/8"(22.2 mm)below the ceiling. Refer to Figures 3 and 4. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations,and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Sprinkler 110 June 28, 2013 NIKING. STANDARD RESPONSE TECHNICAL DATA CONCEALED PENDENT • SPRINKLERS(VK102&VK202) The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 • Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs©vikingcorp.com 1/2" NPI �� (15 mm)" / 11= 1 – / 2-1/4 (57.3 mm) 1-3/8" ��(35.1 mm)Minimum o (25.4 mm) L 3-1/a" c_a I (80 mm) ‘ / 1 / cr,--A 7/e- —I�� 1 / (22.2 mm) ` / 3/8" E Maximum A (9.5 mm) Minimum —� 1-7/8" (47.8 mm) o __ o Maximum Figure 4: Concealed Sprinkler VK102 Dimensions and Cover Installation (20" m (20 mm)) , ; _ Q 2-S/1s- 1-1-i=i-ir-.. - (55.2 mm) o 81 a Minimum- --_ - / (37 mm) A Minimum ° ° (25.4 mm) 4----? [ 3-1/9" (80 mm) E • (22.2 111%W \ / 3/8 s a . Maxim A (1.S mm) Minimum 1-15/18" (41.7 mm) 0 f --- o-- Maximum T o ° Figure 5: Concealed Sprinkler VK202 Dimensions and Cover Installation Form No. F_070703 Replaces page 11j-o, dated June 5, 2013. (ENT finish is now approved as corrosion resistant.) December 12, 2013 Sprinkler 14e NIKING® MICROMATIC®AND TECHNICAL DATA MICROMATICHP° STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION Viking Micromatic® and MicromaticHP®Standard Response Horizontal Sidewall _. Sprinklers are small thermosensitive glass bulb spray sprinklers available with I j•I_ `� various finishes and temperature ratings to meet design requirements. The Ili" special Polyester, PTFE, and Electroless Nickel PTFE (ENT) coatings can Imo—, in decorative applications where colors are desired. In n Z / be used deco pp s e e co s addition,o I I�;(�,��� these coatings have been investigated for installation in corrosive atmospheres and are listed/approved as corrosion resistant as indicated in the Approval Charts. (Note: FM Global approves the ENT coating as corrosion resistant. FM Global has no approval classification for PTFE and Polyester coatings as corrosion Sprinkler Base Part No.09849 resistant.) Viking standard response sprinklers may be ordered and/or used as open sprin- klers (glass bulb and pip cap assembly removed) on deluge systems. Refer to ; Ordering Instructions on page 14f. � erA1. II I 2. LISTINGS AND APPROVALS �'4-1=111 can cULus Listed: Category VNIV - �� FM Approved: Classes 2012 and 2015 LPC Approved: Ref. No. 096e/06 Sprinkler Base Part No. 10224 `PCB CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD- E 2001 and 0832-CPD-2003 Refer to Approval Chart 1 and Design Criteria on page 14h for cULus Listing requirements that must be followed. Refer to Approval Chart 2 and Design Criteria on page 14j for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 1996. — Minimum Operating Pressure: 7 psi (0.5 bar)' Viking Technical Data may be found on Maximum Working Pressure: Sprinklers VK116 and VK015 are rated for The Viking Corporation's Web site at use with water working pressures ranging from the minimum 7 psi http://www.vikinggroupinc.com. (0.5 bar)up to 250 psi (17 bar)for high-pressure systems. High-pres- The Web site may include a more recent sure (HP) sprinklers can be identified by locating "250" stamped on edition of this Technical Data Page. the deflector.All other Part Nos. not mentioned above are rated to a maximum 175 psi(12 bar)wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to-65 °F (-55 °C) Overall Length: Refer to the Approval Charts 'cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi(0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinkler 10224. Brass UNS-C84400 for all other sprinklers. Deflector Copper UNS-C19500 Bushing (for high pressure sprinkler 09997): Brass UNS-C36000 Bulb: Glass, nominal 5 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Pip Cap Attachment(for sprinkler 09997): Brass UNS-C36000 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Form No F_123096 Replaces page 14e-k, dated September 30, 2013. (Added E-3 Escutcheon.) Sprinkler 14f December 12, 2013 NIKING® MICROMATIC®AND TECHNICAL DATA MICROMATICHP® STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap-ENT plated. Ordering Information: (Also refer to the current Viking price list.) Order Standard Response Horizontal Sidewall Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass =A, Chrome = F, White Polyester = M-/W, Black Polyester= M-/B, and Black PTFE = N, Wax Coated = C. Wax Over Polyester=V-/W, and ENT=JN Temperature Suffix: 135 °F(68 °C) =A, 155°F (68°C) = B, 175 °F (79°C) = D, 200 °F (93 °C) = E, 212 °F (100 °C) = M, 286 °F (141 °C) = G, 360°F(182 °C) = H, OPEN =Z(PTFE only). For example, sprinkler VK104 with a 1/2"thread, Brass finish and a 155 °F (68 °C)temperature rating = Part No. 10224AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No 10896W/B (available since 2000). B. Wrench for recessed sprinklers with protective shields: Part No. 13655W/B"(available since 2003) C Wrench for wax coated sprinklers: Part No 13577W/B" (available since 2006) "A%"ratchet is required(not available from Viking). Sprinkler Cabinets: A. Six-head capacity: Part No 01724A(available since 1971) B. Twelve-head capacity: Part No 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection,Testing and Maintenance requirements. Wrench Protective 7. AVAILABILITY Flat Viking Standard Response Horizontal Sidewall Sprinklers are available ®Q° Sprinkler through a network of domestic and international distributors. See The fi ;al.u.,i Shield Viking Corporation web site for the closest distributor or contact The �� Viking Corporation. �I A�ll'b�l��� 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. 10896 Figure 1: Standard Sprinkler Wrench 10896W/B December 12, 2013 Sprinkler 14g NimaNGS MICROMATIC®AND TECHNICAL DATA MICROMATICHP° STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 • Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient - • Bulb Color• Classification Temperature Rating' Ceiling Tem.peraturez Ordinary 135°F(57 °C) 100 °F(38 °C) Orange Ordinary 155 °F(68°C) 100 °F(38 °C) Red Intermediate 175°F(79°C) 150 °F(65 °C) Yellow Intermediate 200°F(93°C) 150 °F(65 °C) Green High 286°F(141 °C) 225 °F(107 °C) Blue Extra High 360 °F(182 °C) 300 °F(149°C) Mauve Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT Corrosion-Resistant Coatings':White Polyester, Black Polyester, and Black PTFE in all temperature ratings. ENT in all temperature ratings except 135°F (57°C). Wax-Coated Brass and Wax over Polyester for sprinklers with the following temperature ratings 135 °F(57 °C)Off-White Wax 155 °F (68°C) Lt. Brown Wax 175°F (79 °C) Brown Wax 200 °F (93°C) Brown Wax 286 °F(141 °C) Dk. Brown Wax" Footnotes 'The sprinkler temperature rating is stamped on the deflector. Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 'The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart.These tests cannot and do not represent all possible corrosive environments. Prior to installation,verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment.For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only Note that the spring is exposed on sprinklers with Polyester,ENT,and PTFE coatings.For PTFE coated open sprinklers only,the waterway is coated. For all ENT coated sprinklers,the waterway is coated. °Wax melting point is 170°F(76°C)for 286 0F(141 °C)temperature rated sprinklers. Sprinkler Wrench Part No. 13655W/Bx For Recessed Horizontal Sidewall Sprinklers Protective Fit the wrench over the sprinkler Sprinkler and protective shield as shown. Shield I 1- 1 ' I 1, 9 E---1,�II�i ' //f/ \ 1 1�,III 1 11 11 1 11111 %Note: A 1/2' ratchet is required (not available from Viking). Figure 2: Wrench 13655W/B for Recessed Horizontal Sidewall Sprinklers Sprinkler 14h December 12, 2013 NIKINels MICROMATIC®AND TECHNICAL DATA MICROMATICHP® STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 • Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com .1111.11111111;111111°13rova l C hart 1 (UL) Tempeature KEY Finish ndard Response Horizontal Sidewall Sprinklers A1X.-Escutcheon Of applicable) Maximum 175 PSI(12 Bar)WWP (See Footnotes Below for Allowable Deflector Distance Below the Ceiling.) Base Part Maximum Thread Size Nominal K-Factor Overall Length Listings and Approvals' Number' SIN Pressure (Refer also to Design Criteria on pg 14i.) NPT BSP U.S. metric' Inches mm cULus"6 NYC' LPCB \E 10 I $" Standard Orifice 10224 VK104 175 psi 1/2" 15 mm 5.6 80.6 2-7/16 62.4 B3W,B1W, B3V, B1V, A2Y D2Y D2Y 10171 VK104 175 psi -- 15 mm -- 80.6 2-7/16 62.4 A1X A1X Small Orifice 09126 VK016 175 psi -- 10 mm 4.2 57 2-7/16 62.4 cULus NYC LPCB E E � Maximum 250 PSI(17 Bar)WWP Standard Orifice,for Installation 4"to 12"(102 mm to 305 mm)Below the Ceiling. cULus" NYC LPCB C E v 09849 VK116 250 psi 1/2` 15 mm 5.6 80.6 2-11/16 67.6 A1X,B1W, ESZ,D5Y See Footnote 7 -- -- -- Maximum 250 PSI(17 Bar)WWP Small Orifice',for Installation 4"to 6"(102 mm to 152 mm)Below the Ceiling. cULusa9 NYC LPCB C E .( 09997'2 VK015 250 psi 1/2" 15 mm 2.8 40.3 2-3/4 69 Al X.B1W See Footnote 7 -- -- Approved Escutcheons Approved Temperature Ratings Approved Finishes V- Installed with standard surface-mounted escutcheons or the 1 - Brass, Chrome, White Polyester"". Black Viking Microfast'' Model F-1 Adjustable Escutcheon, or re- A cessed with the Viking Micromatic° Model E-1, E-2, or E-3 °C),200°F(93°C), 286°F(141°C),and 360 Polyester'''',and Black PTFE' Recessed Escutcheon °F(182°C) 2 - Brass, Chrome, White Polyester, and Black W - Installed with standard surface-mounted escutcheons or Polyester B-135°F(57°C),155°F(68°C),175°F(79°C), the Viking Microfast' Model F-1 Adjustable Escutcheon, or and 200°F(93°C) 3-Wax-Coated Brass and Wax Over Polyester(cor- recessed with the Viking Micromatic'Model E-1, E-2,E-3,or rosion resistant) C-286°F(141°C) Model G-1 Recessed Escutcheon 4-High Temperature 200°F(93°C)Wax Coating(cor- D-155°F(68°C),175°F(79°C),200°F(93°C), X- Installed with standard surface-mounted escutcheons or the 286°F(141°C),and 360°F(182°C) llowe resistant); maximum ambient temperature Viking Microfast°Model F-1 Adjustable Escutcheon E-155°F(68°C),175°F(79°C),and allowed at ceiling=150°F(65°C) Y-Installed with standard surface-mounted escutcheons only 200°F(93°C) 5-ENT' Z-Standard surface-mounted escutcheons or recessed with the Viking Micromatic Model E-1 Recessed Escutcheon. Footnotes 'Base part number shown.For complete part number,refer to Viking's current price schedule Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing.Other approvals may be in process. 'Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada. 'cULus Listings limited to Light Hazard Occupancies where allowed by the installation standards being applied,with the deflector 4"to 12"(102 mm to 305 mm)below the ceiling. 'Approved by the New York City Board of Standards and Appeals under Calendar Number 219-76-SA Meets New York City requirements,effective July 1,2008 'cULus Listed for Light Hazard Occupancies where allowed by the installation standards being applied,and Ordinary Hazard Group I and II Occupancies. °cULus Listings limited to Light Hazard Occupancies where allowed by the installation standards being applied,with hydraulically calculated wet systems. 10((Certified.Standard EN 12259-1,EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. 0 MED Certified,Standard EN 12259-1.EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008. '=The sprinkler orifice is bushed. "cULus Listed as corrosion-resistant. "Other colors are available on request with the same Listings and Approvals as the standard colors December 12, 2013 Sprinkler 14i NIKIN68 MICROMATIC®AND TECHNICAL DATA MICROMATICHP° STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 • Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com DESIGN CRI (Also refer to Approval Chart 1 on page 14h.) cULus Listing Requirements; Standard Horizontal Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for sidewall standard spray sprinklers. • Designed for use in occupancy hazard classifications as indicated in the approval chart, below smooth.flat ceilings only • Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. • Minimum spacing allowed is 6 ft.(1.8 m). • Align the top of the deflector parallel with the ceiling. • Locate no less than 4"(102 mm)from end walls. • Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers.The distance shall be measured perpendicular to the wall. • The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Carefully press the wrench onto the sprinkler wrench flats. Wax Coated HSW Sprinkler 1 �� r ff wwA 1/2' ratchet is required (not available from Viking). Sprinkler Wrench 13577W/Box for installing wax coated sprinklers Figure 3: Wrench 13577W/B for Wax Coated Sprinklers Sprinkler 14j December 12, 2013 NIKINot MICROMATIC®AND TECHNICAL DATA MICROMATICHP® STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 2 (FM) Ternperalure KEY Micromatics'Standard Response Horizontal Sidewall Sprinklers ++ FI"Ish AIX•-Escutcheon Of apphcable) Maximum 175 PSI(12 Bar)WWP Base Part Maximum Thread Size Nominal K-Factor Overall Length FM Approvals' Number' SIN Pressure NPT BSP U.S. metric' Inches mm (Refer also to Design Criteria below.) 10224 VK104 175 psi 112 15 mm 5.6 80.6 2-7/16 62.4 A1X.B1W 10171 VK104 175 psi -- 15 mm -- 80.6 2-7/16 62.4 Approved Escutcheons Approved Temperature Ratings W- Installed with standard surface-mounted escutcheons or the A-135'F(57'C), 155'F(68'C), 175'F(79'C). Approved Finishes Viking Microfast" Model F-1 Adjustable Escutcheon, or re- 200°F(93°C), and 286°F(141 °C), 1 -Brass and Chrome cessed with the Viking Micromatic" Model E-1, E-2, E-3. or B-135°F(57°C), 155°F(68°C), 175'F(79"C), Model G-1 Recessed Escutcheon and 200°F(93°C) X - Installed with standard surface-mounted escutcheons or the Viking Microfast' Model F-1 Adjustable Escutcheon Footnotes Base part number shown. For complete part number,refer to Viking's current price schedule. 'Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10 0. 'This table shows the listings and approvals available at the time of printing. Other approvals may be in process. DESIGN CRIAIRIA - FM (Also refer to Approval Chart 2 above.) AIL FM Aooroval Reauirements; Sprinkler VK104 is FM Approved as a standard response Non-Storage sidewall sprinkler as indicated in the FM Approval Guide. For specific applica- tion and installation requirements,reference the latest applicable FM Loss Prevention Data Sheets(including 2-0)and Technical Advisory Bulletins. FM Global Loss Prevention Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply require- ments,hydraulic design,ceiling slope and obstructions,minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations,and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Sprinkler 14k December 12, 2013 NIKING. MICROMATIC®AND TECHNICAL DATA MICROMATICHP® STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 • Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Wall Opening Size: 2-5/16' (58.7 mm) minimum 2-1/2' (63.5 mm) maximum 2-7/16' 2 2-11/16' 1 (61.9 mm) (50.8 mm) <68.3 mm) Il Minimum 1— 31111 — 1 r.��►tee 1-1/4' �1(; 2-1/8' e�►�. 7).-- II I -Ili/,, (31.: mm) II I , (54 mm) i I Ilwr,�/ 1/2' _ , (15 mm) Sprinkler III 2-1/2' NPT HSW Sprr 09849 inkle) (63.5 mm) Installed with a standard Maximum 1/8' <3.1 mm) surface- mounted escutcheon Installed with a Microfast Model F-1 Adjustable Escutcheon Figure 4: Sidewall Sprinkler Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon Wall Opening Size with the 1-5/8' Model E-1 or E-2 Escutcheon 1-3/4' '(41.3 mm) 2-5/16' <58.7 mm) minimum 2-1/2' (63.5 mm) maximum (44.5 mm) Minimum I Minimum f-3!! iiiiiiii�.11-11 — 2-1/8' l m, ∎V- 2-1/8' ', I' ��:: I 0 2-1/4' IIIII 2-5/8' (57.2 mm) (67 mm) Maximum Maximum Installed with a Micromatic Installed with a Model E-2 Model E-1 Recessed Escutcheon Thread-on Recessed Escutcheon Figure 5: Sidewall Sprinkler Dimensions with the Model E-1 or E-2 Recessed Escutcheons Wall Opening Size with the Model G-1 Escutcheon: 1/8' 2-5/8' (66 mm) minimum —I (3.2 mm) 3-3/4' (95 mm) maximum Adjustable Ad justable Outer Cup I Adapter Ring ' 1 's j 10 I �' (66 mm) (102 mm) 11` /'sN Depth: • 1-1/16' (27 mm) 1-1/16'1 L Maximum Recess: (27 mm) I— 1/2' (12.7 mm) Figure 6: Sidewall Sprinkler Dimensions with the Model G-1 Recessed Escutcheons THIS PAGE INTENTIONALLY LEFT BLANK Form No. F_123096 Replaces page 14e-k, dated September 30,2013. (Added E-3 Escutcheon.) February 3, 2012 Sprinkler 41u NIKINGI® QUICK RESPONSE TECHNICAL DATA UPRIGHT AND PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com 1. DESCRIPTION Viking Quick Response Upright and Pendent Sprinklers are small thermosensi- ..�-„_��'�_�,,�_�_..y tive glass bulb spray sprinklers available with various finishes and tempera- �... lure ratings to meet design requirements. The special Polyester and Teflon i�loll.coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive at- mospheres and are cULus listed as corrosion resistant as indicated in Approval I Chart 1. (Note: FM Global has no approval classification for Teflon®and Polyester I coatings as corrosion resistant.) Ala 2. LISTINGS AND APPROVALS I4. 1.�I c0,s cULus Listed: Category VNIV --'0`�••° .,, FM Approved: Classes 2002 and 2020 Refer to Approval Chart 1 and Design Criteria on page 41x for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 41y for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Available since 2004. Minimum Operating Pressure: 7 psi (0.5 bar) Viking Technical Data may be found on Rated to 175 psi (12 bar)water working pressure The Viking Corporation's Web site at Factory tested hydrostatically to 500 psi (34.5 bar) http://www.vikinggroupinc.com. • Thread size: Refer to the Approval Charts The Web site may include a more recent Nominal K-Factor: Refer to the Approval Charts edition of this Technical Data Page. Glass-bulb fluid temperature rated to-65 °F (-55°C) Overall Length: 2-1/4" (58 mm) Material Standards: Frame Casting: Brass UNS-C84400 for Sprinkler 17508. Brass UNS-C84400 or QM Brass for all other Sprinklers. Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 12978 and 12984. Phosphor Bronze UNS-C51000 or Copper UNS-C19500 for Sprinklers 12979 and 17508. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 12981 and 12980): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 Pip Cap Attachment(for Sprinkler 12980): Brass UNS-C36000 For Teflon'Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon°Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.) Order Quick Response Upright and Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass=A, Chrome-Enloy®= F, White Polyester= M-AN, Black Polyester= M-/B, and Black Teflon®= N Temperature Suffix: 135 °F(68°C) =A, 155 °F (68°C) = B, 175 °F (79 °C) = D, 200°F (93 °C) = E, 286°F(141 °C) = G For example, sprinkler VK300 with a Brass finish and a 155 °F(68 °C)temperature rating = Part No 12978AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the Sprinkler Accessories" section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No 10896W/B(available since 2000). B. Wrench for Recessed Pendent Sprinklers: Part No 16036W/B**(available since 2011) C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No 15915 (available since 2010) *A'/' ratchet is required(not available from Viking). ***Allows use from the floor by attaching a length of 1"diameter CPVC tubing to the tool. Ideal for sprinkler cabinets.Refer to Bulletin F_051808. Form No. F_052204 Replaces page 41u-z, dated December 2, 2011. (New protective sprinkler cap.) Sprinkler 41v February 3, 2012 NIKING® QUICK RESPONSE TECHNICAL DATA UPRIGHT AND PENDENT SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Sprinkler Cabinets: A. Six-head capacity: Part No 01724A(available since 1971) B. Twelve-head capacity: Part No 01725A(available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Quick Response Upright and Pendent Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking's current list price schedule or contact Viking directly. Wrench nim Flat ; 1-1/2" '�i1r,i�' Protective ~38.1 mri) "leg Sprinkler 0"" Protective Cap _ _ Sprinkler Shield i I 11111 I 1f ii 2-1/4" (58 mri) 1 III■ 10896 1(:?) Figure 1: Standard Sprinkler Wrench 10896W/B Figure 2: Upright Sprinkler Dimensions • February 3, 2012 Sprinkler 41w ® QUICK RESPONSE TECHNICAL DATA UPRIGHT AND PENDENT • SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperatu Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature2 Ordinary 135°F(57 °C) 100°F(38 °C) Orange Ordinary 155 °F(68 °C) 100 °F(38°C) Red Intermediate 175 °F(79 °C) 150 °F(65 °C) Yellow Intermediate 200 °F(93 °C) 150 °F(65 °C) Green High 286 °F(141 °C) 225 °F(107 °C) Blue Sprinkler Finishes: Brass, Chrome-Enloy®,White Polyester, Black Polyester, and Black Teflon® Corrosion-Resistant Coatings': White Polyester, Black Polyester, and Black Teflon® Footnotes 'The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13.Other limits may apply,depending on fire loading,sprinkler location,and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts.These tests cannot and do not represent all possible corrosive environments. Prior to installation,verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment. For automatic sprinklers,the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and Teflon' coatings. 1 / 1 / '■I�':\I� I�� 11411! !!'41 'iL1111I tai Sprinkler Wrench I fan —A �;— 16036W/BA0K for 11.161 — installing recessed i I ELI I I I pendent sprinklers FII�I.Iei i ■*A 1/2' ratchet is required I I I i (not avnilnble fron Viking). _~ Carefully press the ,a= am. wrench upward and Lip'_ _ _ = _ ensure engagement with sprinkler wrench flats. Figure 3: Wrench 16036W/B for Recessed Pendent Sprinklers • Sprinkler 41x February 3, 2012 N1K1NG® QUICK RESPONSE TECHNICAL DATA UPRIGHT AND PENDENT • SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 1 (UL) II Temph,re KEY Quick Response Upright and Pendent Sprinklers 471- Fns�era Maximum 175 PSI(12 Bar) WP A Escutcheon(if applicable) W Base Part Sprinkler Thread Size Nominal K-Factor Overall Length Listings and Approvals' SIN (Refer also to Design Criteria below.) Number' Style - - NPT BSP U.S. metric' Inches mm cULus° NYC VdS LPCB EC3 Standard Orifice 12978 VK300 Upright 1/2" 15 mm 5.6 80.6 2-1/4 58 Al -- -- -- -- 12984 VK345 Upright -- 15 mm 5.6 80.6 2-1/4 58 -- -- -- -- -- -- 12979 VK302 Pendent 1/2" 15 mm 56 80.6 2-1/4 58 A1Z, B1Y -- -- -- -- -- Small Orifice6 12980' VK325 Upright 1/2" 15 mm 2.8 40.3 2-1/4 58 Al -- -- -- -- -- 12981' VK329 Pendent 1/2" 15 mm 2.8 40.3 2-1/4 58 A1Z, B1Y -- -- -- -- -- Approved Escutcheons Approved Temperature Ratings Y - Standard surface-mounted escutcheon or the Approved Finishes A-135 °F(57°C), 155°F(68°C), 175°F(79°C), 1 _ grass, Chrome-Enlo White Viking Microfast"Model F-1 Adjustable Escutcheon, or Y"'. 200°F(93°C),286°F(141 °C) Polyester, Black Polyester', recessed with the Viking Micromatic"Model E-1 or E-2 B-135 °F(57 °C), 155°F(68°C), 175°F(79°C), and Black Teflon' Recessed Escutcheon and 200°F(93°C) Z - Standard surface-mounted escutcheon or the Viking Microfast' Model F-1 Adjustable Escutcheon Footnotes Base part number shown. For complete part number,refer to Viking's current price schedule. Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 'This table shows the listings and approvals available at the time of printing.Other approvals may be in process. °Listed by Underwriters Laboratories Inc.for use in the U.S.and Canada. s The sprinkler orifice is bushed. 6 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied.with hydraulically calculated wet systems only. 'cULus Listed as corrosion-resistant. 'tJ ypl.:. (Also refer to Approval Chart 1 above.) • cULus Listing Reauirements; Standard Upright and Pendent Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light,Ordinary,and Extra Hazard occupancies(exception:small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). • The sprinkler installation rules contained in NFPA 13 for standard spray upright and pendent sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. February 3, 2012 Sprinkler 41y N1KING® QUICK RESPONSE TECHNICAL DATA UPRIGHT AND PENDENT • SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 • Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Approval Chart 2 (FM) --Temperature KEY Quick Response Upright and Pendent Sprinklers ��Finish Maximum 175 PSI(12 Bar)WWP A1Xf Esculd eon la applicable) Base Part I SIN Sprinkler Thread Size Nominal K-Factor Overall Length FM Approvals' Number' Style NPT BSP U.S. metric7 Inches mm (Refer also to Design Criteria below.) Standard Orifice 12978 VK300 Upright 1/2" 15 mm 5.6 80.6 2-1/4 58 Al 12984 VK345 Upright -- 15 mm 5.6 80.6 2-1/4 58 Al 12979 VK302 Pendent 1/2" 15 mm 5.6 80.6 2-1/4 58 _ A1Z, B1Y Large Orifice 17508 I VK352 Pendent 1/2" 1 15 mm I 8.0 115.2 2-1/4 58 I A2Z.B2Y Small Orifice' 12980' VK325 Upright 1/2" 15 mm 2.8 40.3 2-1/4 58 A2 12981' VK329 Pendent 1/2" 15 mm 2.8 40.3 2-1/4 58 A2Z Approved Escutcheons Approved Temperature Ratings Y - Standard surface-mounted escutcheon or the Approved Finishes A- 135°F(57°C),155°F(68°C), 175°F(79°C),200°F 1 _ grass. Chrome Enloy White Viking Microfast' Model F-1 Adjustable Escutcheon, (93 CC),286°F(141 °C) Polyester',and Black Polyesters or recessed with the Viking Micromatic` Model E-1 B- 135 °F(57 °C), 155°F (68°C), 175°F(79°C),and 2_grass and Chrome-Enlo l or E-2 Recessed Escutcheon 200°F(93°C) Z - Standard surface-mounted escutcheon or the Viking Microfast- Model F-1 Adjustable Escutcheon Footnotes ' Base part number shown. For complete part number, refer to Viking's current price schedule. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 'This table shows the FM Approvals available at the time of printing.Other approvals may be in process. FM Approved as quick response Non-storage upright and pendent sprinklers. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets(including Data Sheet 2-0). 'Other colors are available on request with the same Approvals as the standard colors. °The sprinkler orifice is bushed. ,DESIGN CRITERIA FNS DESI A- FM Aooroval Reauirements*, The sprinklers in Approval Chart 2 are FM Approved as quick response Non-storage upright and pendent sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing,and deflector distance below the ceiling. NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD,VdS or other similar organizations,and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Sprinkler 41z February 3, 2012 NIKINo. QUICK RESPONSE TECHNICAL DATA UPRIGHT AND PENDENT • SPRINKLERS The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 • Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com Ceiling Opening Size: 2-5/16' (58.7 mm) minimum 2-1/8' 2-1/2' (63.5 mm) maximum (54 mm) 2-1/4' Ill III - __ .. 1-3/4' lil I'� /ll Irlr� (44.5 mm) 2' 1-1/2' (38 mm) l I`j�l `; :%' (51 r'un) rI Miniu1 f \, ,/ 1k .............. Maximum - 1' 1 _L__® (25.4 mm) Installed with a standard 1/8' (3.2 rim) surface- Installed with a Microfast Pendent Sprinkler' mounted escutcheon Model F-1 Adjustable 12979 (VK302) Escutcheon Figure 4: Pendent Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon • Ceiling Opening Size: 2-1/8' 2-5/16' (58.7 mm) minimum 2-1/8' (54 mm) 2-1/2' (63.5 mm) maximum (54 mm) ll'a -1'L La II. :TINS Will • 1-3/4' l I r'il 1-1/8' (28.6 mm) 2' � 1-1/8' (28.6 mm) �, , Minimum (44.5 mm) .I Minimum (51 mm) �=l 1 Maximum Maximum _. ._... 1 1 Installed with a Micromatic Installed with a Model E-2 Model E-1 Recessed Thread-on Recessed Escutcheon Escutcheon Figure 5: Pendent Sprinkler VK302 Dimensions with the Model E-1 and E-2 Recessed Escutcheons Form No. F_052204 Replaces page 41u-z, dated December 2, 2011. (New protective sprinkler cap.)