Loading...
Plans ABBREVIATIONS ELECTRICAL NOTES JURISDICTION NOTES A AMPERE 1. THIS SYSTEM IS GRID—INTERTIED VIA A AC ALTERNATING CURRENT UL—LISTED POWER—CONDITIONING INVERTER. RECEIVED BLDG BUILDING 2. THIS SYSTEM HAS NO BATTERIES, NO UPS. CONC CONCRETE 3. A NATIONALLY—RECOGNIZED TESTING DC DIRECT CURRENT LABORATORY SHALL LIST ALL EQUIPMENT IN EGC EQUIPMENT GROUNDING CONDUCTOR COMPLIANCE WITH ART. 110.3. APR 2 9 2015 (E) EXISTING 4. WHERE ALL TERMINALS OF THE DISCONNECTING EMT ELECTRICAL METALLIC TUBING MEANS MAY BE ENERGIZED IN THE OPEN POSITION, CITY OF TIGARD FSB FIRE SET—BACK A SIGN WILL BE PROVIDED WARNING OF THE BUILDING DIVISION GALV GALVANIZED HAZARDS PER ART. 690.17. GEC GROUNDING ELECTRODE CONDUCTOR 5. EACH UNGROUNDED CONDUCTOR OF THE GROUND GND HDGG HOTDIPPED GALVANIZED PHASE AND CIRCUIT 21051DENTIFIED BY OFFICE COPY I CURRENT 6. CIRCUITS OVER 250V TO GROUND SHALL - Imp CURRENT AT MAX POWER COMPLY WITH ART. 250.97, 250.92(B). Isc SHORT CIRCUIT CURRENT 7. DC CONDUCTORS EITHER DO NOT ENTER CITY OF TIGARD kVA KILOVOLT AMPERE BUILDING OR ARE RUN IN METALLIC RACEWAYS OR REVIEWED FOR CODE COMPLIANCE kW KILOWATT ENCLOSURES TO THE FIRST ACCESSIBLE DC LBW LOAD BEARING WALL DISCONNECTING MEANS PER ART. 690.31(E). APPS [$ J MIN MINIMUM 8. ALL WIRES SHALL BE PROVIDED WITH STRAIN OTCs 1 3 (N) NEW RELIEF AT ALL ENTRY INTO BOXES AS REQUIRED BY NEUT NEUTRAL UL LISTING. Permit#Z fr1 TZ o 1'Z — c2( / NTS NOT TO SCALE 9. MODULE FRAMES SHALL BE GROUNDED AT THE Address j ,< c1,1" S 1, / ('-‘ 0 -4/04 Co!'v C r OC ON CENTER UL—LISTED LOCATION PROVIDED BY THE Suite#i PL PROPERTY LINE MANUFACTURER USING UL LISTED GROUNDING /� .� � P01 POINT OF INTERCONNECTION HARDWARE. By l Dates L JJ PV PHOTOVOLTAIC 10. MODULE FRAMES, RAIL, AND POSTS SHALL BE ' , SCH SCHEDULE BONDED WITH EQUIPMENT GROUND CONDUCTORS. S STAINLESS STEEL STC STANDARD TESTING CONDITIONS TYP TYPICAL UPS UNINTERRUPTIBLE POWER SUPPLY V VOLT Vmp VOLTAGE AT MAX POWER VICINITY MAP INDEX Voc VOLTAGE AT OPEN CIRCUIT W WATT �,__ .; 3R NEMA 3R, RAINTIGHT ,� w. i. / PV1 COVER SHEET _ � , - * ., PV2 SITE PLAN PV3 STRUCTURAL VIEWS SW Durham Rd SW Durham Rd PV5 THREE LINE DIAGRAM LICENSE GENERAL NOTES _ _ PV6 ELECTRICAL CALCULATIONS OR # 180498 1. ALL WORK TO BE DONE TO THE 2010 OBC ... : Cutsheets Attached RGC, CGC1 BASED ON THE 2009 IBC. ; - 2. ALL ELECTRICAL WORK SHALL COMPLY WITH THE CURRENT NATIONAL ELECTRIC CODE AS ! � �� r if AMENDED BY THE OREGON ELECTRICAL SPECIALTY — � t 1 ° a r CODE. MODULE GROUNDING METHOD: ZEP SOLAR �.> AHJ: Tigard REV BY DATE COMMENTS . " -Mel=DATE COMMENTS =MI * UTILITY: Portland General Electric IN ` ©®®tra k._-> nd Oregon, State of Oregon. U.S. Geological Survey CONFIDENTIAL — THE INFORMATION HEREIN JOB NUMBER: J B-9722123 00 PREMISE OWNER: DESCRIPTION: DESIGN: W. BETTS RESIDENCE Derrick Olds % SoIarCity MG SYSTEM: NOR SHALL IT BE DISCLOSED IN WWiOLE OR IN Comp ount T e C 16165 SW GRIMSON CT 4.08 KW PV ARRAY PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: TIGARD OR 97224 ORGANIZATION, EXCEPT IN CONNECTION Will Way THE SALE AND USE OF THE RESPECTIVE (16) TRINA SOLAR # TSM-255PA05.18 PAGE NAME: SHEET: REV: DATE: San Mateo, CA 3055 Clearvew 9 Wa02 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: 5037055656 T:(650) 638-1028 F:(650)638-1029 PERMISSION OF SOLARETTY INC. ABB; PVI-3.0—OUTD—S—US—Z—A COVER SHEET PV 1 11/5/2014 (888)—SOL—CITY(765-2489)www.solarcily.com I PITCH: 22 ARRAY PITCH:22 MP1 AZIMUTH: 180 ARRAY AZIMUTH: 180 • MATERIAL:Comp Shingle STORY: 1 Story PITCH: 22 ARRAY PITCH:22 • MP2 AZIMUTH:270 ARRAY AZIMUTH:270 3° MATERIAL:Comp Shingle STORY: 1 Story aAC ® HHO • • II '1 D 1I v, I% ,I L"J °' • cn — — — 0 0 12"" ps 0 0 0- (E)DRIVEWAY p • ° 0 o ■ 0 0 0 = LEGEND 0 -- 0 (E) UTILITY METER & WARNING LABEL O o a o 0 . ' ® INVERTER W/ INTEGRATED DC DISCO ► w MP1 ) 0 0 ° & WARNING LABELS R. N ® DC DISCONNECT & WARNING LABELS 0 AC . ii AC DISCONNECT & WARNING LABELS ''t`" O DC JUNC11ON/COMBINER BOX & LABELS 3 i Front Of House NJ Q° DISTRIBUTION PANEL & LABELS 11>i �C LOAD CENTER & WARNING LABELS L IV�II 0 DEDICATED PV SYSTEM METER 0 STANDOFF LOCATIONS I • CONDUIT RUN ON EXTERIOR CONDUIT RUN ON INTERIOR °C GATE/FENCE 0 HEAT PRODUCING VENTS ARE RED 1% ` INTERIOR EQUIPMENT IS DASHED °g o TOTAL ARRAY AREA (SF): 288 SITE PLAN N O TOTAL ROOF AREA (SF): 2742 Scale: 1/8" = 1' w `r E TOTAL ARRAY AREA IS a 10.49 0 1' 8' 16' PERCENT OF TOTAL ROOF AREA ■■m■omill S CONFIDENTIAL- THE INFORMATION HEREIN JOB NUMBER: J B-9722123 0 0 BET LLOYD W. BETTS RESIDENCE Derrick Olds �ZSoIarCity CONTAINED O SHALL NOT E BE USED FOR THE - BENEFlT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: � NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C 16165 SW CRIMSON CT 4.08 KW PV ARRAY PART TO OTHERS OUTSIDE THE RECIPIENTS P ORGANIZATION, EXCEPT IN CONNECTION WITH MODULES TIGARD, OR 97224 THE SALE AND USE OF THE RESPECIIYE (16) TRINA SOLAR # TSM-255PA05.18 3055 Ge°rvkw Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN IR PAGE NAME: SHEEP REY: DATE T:(650)638-1026, F:(650)638-1029 PERMISSION OF SOLARGTY INC. ABB# PVI-3.0—OUTD—S—US—Z—A 5037055656 SITE PLAN PV 2 11/5/2014 (ese)-sa-an(�65 269)www.�I�cHy. (E) 2x4 • PRE-MANUFACTURED TRUSS STRUCTURE MEETS THE /\ PRESCRIPTIVE REQUIREMENTS OF THE OSISC SECTION 305.4 2'-4" 0 6' / 6'-6" / I (E) LBW SIDE VIEW OF MP1 NTS A MP1 X-SPACING X-CANTILEVER Y-SPACING Y-CANTILEVER NOTES LANDSCAPE 72" 24" STAGGERED PORTRAIT 48" 20" TOP CHORD 2x4 @ 24 OC ROOF AZI 180 PITCH 22 STORIES: 1 ARRAY AZI 180 PITCH 22 BOT CHORD 2x4 @24" OC Comp Shingle PV MODULE 5/16" BOLT WITH LOCK INSTALLATION ORDER & FENDER WASHERS LOCATE RAFTER, MARK HOLE ZEP LEVELING FOOT (1) LOCATION, AND DRILL PILOT ZEP ARRAY SKIRT (6) HOLE. (4) 62 SEAL PILOT HOLE WITH POLYURETHANE SEALANT. ZEP COMP MOUNT C ZEP FLASHING C `��l4I ., (3) INSERT FLASHING. rs�ja :i— ra ■ (E) COMP. SHINGLE l (4) PLACE MOUNT. (E) ROOF DECKING MOE :: ( ) INSTALL LAG BOLT WITH 5/16', DIA STAINLESS (5) SEALING WASHER. STEEL LAG BOLT LOWEST MODULE SUBSEQUENT MODULES .----- INSTALL LEVELING FOOT WITH WITH SEALING WASHER (6) BOLT & WASHERS. (2-1/2" EMBED, MIN) (E) RAFTER 1 STANDOFF Si Scale: 1 1/2" = 1' CONFIDENTIAL PREMISE OWNER: DESCRIPTION: ' DESIGN: THE INFORMATION HEREIN JB-9722123 00 BETTS, LLOYD W. BETTS RESIDENCE Derrick Olds ��`.. CONTAINED OF SHALL NOT EXCEPT CE USED FOR THE SolarCity -- BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: �., �, NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C 16165 SW CRIMSON CT 4.08 KW PV ARRAY ►�� PART TO OTHERS OUTSIDE THE RECIPIENTS MODULEp ' TIGARD, OR 97224 ORGANIZATION, EXCEPT IN CONNECTION WITH , THE SALE AND USE OF THE RESPECTIVE (16) TRINA SOLAR # TSM-255PA05.18 3055 aearvew Way SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PAGE NAME: SHEET: REM. DATE: Si a Mateo, CA 94402 PERMISSION OF SOLARaTY INC. INVERTER: 5037055656 T:(650)638-1028 F:(650)638-1029 ABB# PVT-3.0—OUTD—S—US—Z—A STRUCTURAL VIEWS PV 3 11/5/2014 (888)—soL—aTY(765-2489) www.solarcity.cam UPLIFT CALCULATIONS 11.05.2014 S olarCity SleekMount'T PV System Version#39.5 7r Structural Design Software Project Information&Table Of Contents Risk Category: II PV System Type SolarCity SleekMount'" Comp Roof Comp Roof Layers of Comp Roofing 1 Roof Slope 22° Rafter Spacing 24"O.C. PV System Module Orientation Landscape and Portrait PV Module Area 282 sf PV Module Width 39" PV Module Length 65" Standoff(Attachment Hardwar e) Comp Mount Type C Reduced Ground/Roof Live/Snow Loads Ground Snow Load pg 25.0 psf • ASCE Table 7-1 Surrounding Roof Snow 100% 25.0 psf •ASCE Eq:7.4-1 Roof Snow Over PV Modules 100% 25.0 psf •ASCE Eq: 7.4-1 Wind Design Criteria Wind Design Code ASCE 7-05 Wind Design Method =- ,,, as Partially/Fully Enclosed Method Basic Wind Speed V 95 mph Fig.6-1 Exposure Category C ' Section 6.5.6.3 Roof Style Gable Roof 'Fig.a-11BIG'D-14Af8 Mean Roof Height h 15 ft Section 6.2 Effective Wind Area(1 Module) A 17.6 sf IBC 1509.7.1 Wind Pressure Calculation Coefficients Wind Pressure Exposure Kz 0.85 Table 6-3 Topographic Factor Kzt 1.00 Section 6.5.7 Wind Directionality Factor Kd 0.85 Table 6-4 Importance Factor I 1.0 Table 6-1 Velocity Pressure qh qh =0.00256(Kz)(Kzt)(Kd)(V^))(I) Equation 6-15 16.7 psf Ext.Pressure Coefficient(Up) GCp(Up) -0.88 Fig.6-11B/G'D-14A/8 Ext.Pressure Coefficient(Down) GCp(Down) 0.45 Fig.6-118/c/D-14a/13 Design Wind Pressure p p =qh(GCp) Equation 6-22 Wind Pressure Up p(up) -14.6 psf Wind Pressure Down p(down) 10.0 psf Allowable Standoff Spacings X-Direction V-Direction Max Allowable Standoff Spacing Landscape 72" n' Max Allowable Cantilever Landscape 24" NA Standoff Configuration Landscape Staggered Max Standoff Tributary Area Trib 20 sf PV Assembly Dead Load W-PV 3 psf Net Wind Uplift at Standoff T-actual -252 lbs Uplift Capacity of Standoff T-allow 500 lbs Standoff Demand/Capacity DCR _ 50.5% Max Allowable Standoff Spacing Portrait 48" 65" Max Allowable Cantilever Portrait 20" NA Standoff Configuration Portrait Staggered Max Standoff Tributary Area Trib ---71---r", 22 sf 3 ' if PV Assembly Dead Load W-PV 3 psf Net Wind Uplift at Standoff T-actual -280 lbs alaillan Uplift Capacity of Standoff T-allow 500 lbs Standoff Demand/Capacity DCR _ A 56.0% _ PREMISE OWNER: DESCRIPTION: DESIGN: CONFIDENTIAL - THE INFORMATION HEREIN NUMBER: JB-9722123 0o LLOYD W. BETTS RESIDENCE Derrick Olds t-1/4:',',SolarCity.CONTAINED SHALL NOT BE USED FDR THE BETTS,- BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: : NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C 16165 SW CRIMSON CT 4.08 KW PV ARRAY PART TO OTHERS OUTSIDE THE RECIPIENTS MODULES: TIGARD OR 97224 ORGANIZATION, EXCEPT IN CONNECTION WITH ' Way y W _ THE SALE AND USE OF THE RESPECTIVE (16) TRINA SOLAR # TSM-255PA05.18 PAGE NAME: SHEET REV: DATE: Sal Mateo,Cl5ateo,eorvle ae 9a SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN EVERTOR: T:(650) PERMISSION OF SOLARCITY INC. Aggg PVT-3.0-OUTD-S-US-Z A 5037055656 UPLIFT CALCULATIONS PV 4 11/5/2014 (888) SOLgTTYY(765 2 )�°�6 rcty.com GROUND SPECS MAIN PANEL SPECS GENERAL NOTES INVERTER SPECS MODULE SPECS LICENSE BOND (N) #8 GEC TO TWO (N) GROUND Panel Number: Inv 1: DC Ungrounded INV 1 -(1)ABB# PVT-3.0-OUTD-S-US-Z-A LABEL: A -(16)TRINA SOLAR # TSM-255PA05.18 OR # 180498 RODS AT PANEL WITH IRREVERSIBLE CRIMP Meter Number:24547826 FCI Inverter; Zigbee 3000W, 240V, 96% PV Module; 255W, 232.2W PTC, 40MM, Black Frame, MC4, ZEP Enabled RGC, CGC1 Underground Service Entrance INV 2 Voc: 37.7 Vpmax: 30.5 INV 3 Isc AND Imp ARE SHOWN IN THE DC STRINGS IDENTIFIER (E) 200A MAIN SERVICE PANEL Multiple Main Breakers (6 or fewer) Inverter 1 IND (E) WIRING CUTLER-HAMMER COOPER Disconnect Meter Socket ABB Vstart = DEFAULT Mli DC PV1-3.0-OUTD-S-US-Z-A DC- MP 1: 1x8 )‘, (E) LOADS A B � 240v 1 r _-- EGC f - Q —. • ---,.,. • — L2 DC. N DG I 2 I� I� 20A/2P I GND EGG I �� DC+ T DC. Vstart = DEFAULT --- - 14 14 ,-,L� _ r tT- ��-1f--- -I GND)- �f GEC ----TEl DG DC- MP 1: 1x8 B - —. . I I GND I---_EGC__- E__- EGC J I 1V 1 (1)Conduit Kit; 1" EMT N I V EGCIGEC -j o -- z-z CD — T GEC r 1 TO 120/240V I I SINGLE PHASE I I UTILITY SERVICE I { II I 1 I I I I I I I Voc* = MAX VOC AT MIN TEMP POI-(1)CUTLER-HAMMER #CH220 PV BACKFEED BREAKER A —(1)CUTLER-HAMMER I DG221URB AC DC Breaker; 20A 2P, 2 Spaces, Ton Handle Disconnect; 30A, 24OVac, Non-Fusible, NEMA 3R -(2)Ground Rod; 5/8" a 8., Copper -(1)CUTLER-HAMMER !DGO3ONB Ground/Neutral Kit; 30A, General Duty(DG) B (1)COOPER I B-Line Meter Socket 011 Meter Socket; 125A, 4-14AWG, Ring Type -(1)AW CAP; B-Line Meter Socket Accessory -(1)Milbank 4 CL200D /Itron C1 S Solid- ate Single-Phase Meter; Digital O M-(1)AWG 0, THWN-2, Block �7 2 MG/10, PV 1M RE, Block Voc* =338.27VDC Isc =8.92 ADC (1)AWG 10, 11 -2, Red O (1)AWG /6, Stranded Bare Copper EGC Vmp =244 VDC Imp=8.36 ADC (1)AWG #10, THWN-2, White NEUTRAL Vmp =240 VAC Imp=14.5 MC V(1)Conduit Kit; 3/4- EMT -(1)AWG #8, THWN-2, Green EGC/GEC,-(1)Conduit.Kit;.3/4'.EMT, , . . . . I (2)AWG #10, PV WRE, Black Voc* =338.27VDC Isc =8.92 ADC L O 61 (1)AWG /6, Stranded Bore Copper EGC Vmp =244 VDC Imp=8.36 ADC (1)Conduit Kit; 3/4" EMT CONFIDENTIAL - THE INFORMATION HEREIN JOB NUMBER: J B-9722123 0 0 PREMISE OWNER: DESCRIPTION: DESIGN: \‘� CONTAINED SHALL NOT BE USED FOR THE BETTS, LLOYD W. BETTS RESIDENCE Derrick Olds ';;;SolarCity �A A..� BENEFIT OF ANYONE EXCEPT IN WHOLE INC., MOUNTING SYSTEM: 16165 SW CRIMSON C T 4.08 K W P V ARRAY NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C PART TO OTHERS OUTSIDE THE RECIPIENTS MODULE4 TIGARD, OR 97224 WITH ORGANIZATION, EXCEPT IN CONNECTION W 3055 clearview Way THE SALE AND USE OF THE RESPECTIVE (16) TRINA SOLAR # TSM-255PA05.18 PAGE NAME: SHEET: REV DATE: Sa, Mateo, CA 94402 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: T:(650)638-1028 F:(650)638-1029 PERMISSION OF SOLARCITY INC. ABB# PVT-3.O—OUTD-S—US—Z—A 5037055656 THREE LINE DIAGRAM PV 5 11/5/2014 (888)-Sa-CITY(765-2489) www.solarcity.cam ELECTRICAL CALCULATIONS Module 16 TRINA SOLAR#TSM 255 ZEP 232.2 Inv Power WPTC Voltage Drop Calculations Version 5.8.0 Inverter 1: 1 ABB PVI 3.0 S AFCI 0.96 3300 3566.59 Vdrop= (Imp) * (2*Length)'(Resistance) / (Vmp) Module: Imp(A) Max. Length(ft) _ Wire . Inverter 2: String: 8.36 70 AWG_10 at Max Ave Hi:87 deg F Module: Vdrop= (8.36 * 140 *0.001240hms) / 200.9828 0.72 Inverter 3: - Branch: 1 8.36 l 50 I AWG_10 I at Max Ave Hi:87 deg F Module: Vdrop= ( 8.36 * 100 * 0.001240hms) / 200.9828 0.52 Inverter 4: Total voltage drop in DC conductors= 1.24 Inverter: 1 8.36 I 20 I AWG_10 I at 240V Vdrop= (8.36 *40 * 0.0012 Ohms) / 240 V 0.1672 Total: 16 Modules Total Inv Pwr: 3300 3566.59 PTC Combined:I 0 I 0 I AWG#10 at 240V Photovoltaic Module Electrical Specifications: Total STC: 4080 Vdrop= ( 0 *0 0.0012 Ohms) / 240 V 0 Voc: 37.7 V deg F deg C Vmp: 30.5 V Record Low Temp: 8 -13 Total voltage drop in AC conductors= 0.17 Isc: 8.92 A Max Average Hi Temp: 87 31 Total voltage drop in AC and DC conductors= 1.41 Imp: 8.36 A Record Hi Temp: 96 36 Tvoc: -0.12064 V/deg C Tisc: 4.1924 mA/deg C I String Type A and 2 Combined Strings Type A Voc Correction Method: Manuf Tvoc data Branch Circuit Type A 1 way wire length: 50 ABB PVI-3.0-S AFCI Voc Correction Factor: 1 strings per branch 1 1 strings per branch 2 Inverter Min Vdc Input: 120 8 TRINA SOLAR#TSM 255 ZEP 8 I modules per series string 8 modules per series string Voc= 301.6 Min Vmp at Max Temp: 200.98 Voc= 301.6 V Voc= 301.6 V Max Voc at Min Temp: 338.27 Vmp= 244 V Vmp= 244 V Inverter Max Vdc Input: 600 Vmp= 244 Isc= 8.92 Isc= 8.92 A Isc= 8.92 A Max String Size: 14 Imp= 8.36 1-way wire length: 70 Imp= 8.36 A Imp= 8.36_A Icont= 11.15 Art 690.8(A)(1) Icont= 11.15 A Icont= 11.15 A Art 690.8(A)(1) 1.a Conductor AWG#10 I PV Wire 2.a Conductor 1: AWG#10 Conductor 2: AWG#10 Icont'1.25=(Amps) 13.94 Conductor 1 Conductor 2 30 deg C ampacity= 25 r Icont*1.25=(Amps) 13.94 13.94 1 b Icont=(Amps) 11.15 30 deg C ampacity= 25 25 I Start ampacity 25 2.b Icont=(Amps) 11.15 11.15 Temperature derate(%=F) 0.76 Start ampacity 25 25 Conduit fill derate(%=#) 0.8 Temperature derate(%=F) 0.76 0.76 Derated ampacity 15.2 Conduit fill derate(%=#) 0.8 0.8 1 c Derated ampacity 15.2 15.2 Icont*1.25=(Amps) 0 2.c Term 1 Term 2 Ampacity 25 I I Temp table 90 1.d Icont*1.25=(Amps) I 0 I Icont*1.25=(Amps) 13.94 13.94 Ampacity 25 25 OCP Size= 15 Inverter Type A Output 2.d OCP Size= 15 I 15 ABB PVI-3.0-S AFCI I 1 way wire length: 10 ft Combined Inverter Output Icont= I 14.5 I A Art 690.8(A)(1) Service Voltage= 3.a Icont* 1.25=(Amps) 18.12 1 Art 690.8(B)(1) Total Inverter Power= 1 way wire length= 0 OCP Size= 20 Art 240.6(A) Icont=#of inverters*max inverter current Art 690.8(A)(1) 3.b Conductor:I AWG #10 THWN-2 at 90 deg C:Table 310.16 Icont=(Amps) Icont*1.25=(Amps) 18.12 4.a Icont*1.25=(Amps) 18.12 Art 690.8(B)(1) 30 deg C ampacity= 25 OCP size= 20 Art 240.6(A) 3.c Icont=(Amps) 14.5 4.b Conductor: I Wire Size: WGd VN1H at 90 deg C Table 310.16 Start ampacity 25 Icont*1.25=(Amps) 18.12 Temperature derate(%=F) 0.91 30 deg C ampacity= 25 Conduit fill derate(%=#) 1 4 c Icont=(Amps) 14.5 Derated ampacity 22.75 1 Start ampacity 25 3.d Icont*1.25=(Amps) 18.12 Temperature derate(%=F) 0.91 Ampacity 20 Conduit fill derate(%=#) 1 Derated ampacity 22.75 4.d Icont* 1.25=(Amps) 18.12 I Ampacity 20_ I CONFIDENTIAL THE INFORMATION HEREIN JOB NUMBER: J8-97221 23 O0 PREMISE OWNER: DESCRIPTION: DESIGN: � !, CONTAINED SHALL NOT BE USED FOR THE BETTS, LLOYD W. BETTS RESIDENCE Derrick Olds �;,`SolarCity - BENEFIT OF ANYONE EXCEPT SOLARCITY INC., MOUNTING SYSTEM: A'nvz NOR SHALL IT BE DISCLOSED IN WHOLE OR IN Comp Mount Type C 16165 SW CRIMSON CT 4.08 KW PV ARRAY PART TO OTHERS OUTSIDE THE RECIPIENTS MWULEP TIGARD, OR 97224 ORGANIZATION, EXCEPT IN CONNECTION 111TH 3055 Clearvew Way THE SALE AND USE OF THE RESPECTIVE (16) TRINA SOLAR # TSM-255PA05.18 PAGE NAME: SHEET: REV: DATE: San Mateo, CA 94402 SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN INVERTER: T:(650)638-1028 F:(650)638-1029 PERMISSION OF SOLARCITY INC. ABB# PVI-3.0 OUTD-S-US-Z-A 5037055656 ELECTRICAL CALCULATIONS PV 6 11/5/2014 (888)-SOL-OTT(765-2489) www.solorcity.com Label Location: Label Location: Label Location: CAUTION: SOLAR CIRCUIT (C)(IC)(CB) MAXIMUM AC - A (AC) (P01) CAUTION (P01) • Per Code: OPERATING CURRENT Per Code: DUAL POWER SOURCE Per Code: IFC 605.11.1.4 MAXIMUM AC - v NEC 690.54 SECOND SOURCE IS NEC 690.64.B.4 OPERATING VOLTAGE PHOTOVOLTAIC SYSTEM Label Location: PHOTOVOLTAIC DC (DC) (INV) DISCONNECT Per Code: NEC 690.14.C.2 Label Location: Label Location: PV SYSTEM (AC) WARNING (DC) (INV) DISCONNECT FOR Per Code: UTILITY OPERATION ELECTRIC SHOCK HAZARD NEC 690.35(F) Label Location: THE DC CONDUCTORS OF THIS PHOTOVOLTAIC SYSTEM ARE TO BE USED WHEN MAXIMUM POWER--A (DC) (INV) UNGROUNDED AND INVERTER IS POINT CURRENT(Imp) Per Code: MAY BE ENERGIZED UNGROUNDED MAXIMUM POWER _v NEC 690.53 POINT VOLTAGE(Vmp) Label Location: MAXIMUM SYSTEM v VOLTAGE(Voc) (AC) (P01) SHORT-CIRCUIT WARNING Per Code: CURRENT(Isc)-A ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS NEC 690.17(4) TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION Label Location: WARNING (DC) (CB) Per Code: ELECTRICAL SHOCK HAZARD DO NOT TOUCH TERMINALS NEC 690.17(4) Label Location: TERMINALS ON BOTH LINE AND WARNING (P01) LOAD SIDES MAY BE ENERGIZED Per Code: IN THE OPEN POSITION INVERTER OUTPUT NEC 690.64.B.7 DC VOLTAGE IS CONNECTION ALWAYS PRESENT WHEN DO NOT RELOCATE SOLAR MODULES ARE THIS OVERCURRENT EXPOSED TO SUNLIGHT DEVICE Label Location: Label Location: WARNING (DC) (INV) PHOTOVOLTAIC POINT OF (P01) Per Code: INTERCONNECTION Per Code: ELECTRIC SHOCK HAZARD NEC 690.5(C) WARNING: ELECTRIC SHOCK NEC 690.17.4; NEC 690.54 IF A GROUND FAULT IS INDICATED HAZARD. DO NOT TOUCH NORMALLY GROUNDED TERMINALS.TERMINALS ON CONDUCTORS MAY BE BOTH THE LINE AND LOAD SIDE UNGROUNDED AND ENERGIZED MAY BE ENERGIZED IN THE OPEN POSITION. FOR SERVICE DE-ENERGIZE BOTH SOURCE AND MAIN BREAKER. PV POWER SOURCE Label Location: MAXIMUM AC _ A OPERATING CURRENT (AC): AC Disconnect PHOTOVOLTAIC AC (AC) (P01) MAXIMUM AC _ V (C): Conduit DISCONNECT Per Code: OPERATING VOLTAGE (CB):CB : Combiner Box NEC 690.14.C.2 (D): Distribution Panel (DC): DC Disconnect (IC): Interior Run Conduit Label Location: (INV): Inverter With Integrated DC Disconnect CAUTION (D) (P01) (LC): Load Center PHOTOVOLTAIC SYSTEM Per Code: (M): Utility Meter CIRCUIT IS BACKFED NEC 690.64.6.4 (P01): Point of Interconnection CONFIDENTIAL - THE INFORMATION HEREIN CONTAINED SHALL NOT BE USED FOR .4■44 -=106ir 3055 Cleawew Way THE BENEFIT OF ANYONE EXCEPT SOLARCITY INC., NOR SHALL IT BE DISCLOSED ..- San Mateo,CA 94402 IN WHOLE OR IN PART TO OTHERS OUTSIDE THE RECIPIENTS ORGANIZATION, SC - OR Label Set lre T:(650)638-1028 F:(650)638-1029 EXCEPT IN CONNECTION WITH THE SALE AND USE OF THE RESPECTIVE I� SO I a Ity (888)SOL-CITY(765-2489)www.solarcfty.com SOLARCITY EQUIPMENT, WITHOUT THE WRITTEN PERMISSION OF SOLARCITY INC. ZS Comp Edge Zone Calculations 1 of 4 0 Z5 Comp Edge Zone Calculations 2 of 4 5/28/13 "•� 5/28/13 ZepSotor ZepSotar This set of calculations is intended to show that ZS Comp has sufficient strength to allow for attachment Down Force Spacing spacings of at least 48"in Edge Zones whether the modules are orientated in landscape or portrait.The Allowable Down Force Load calculations will vary the design variables to account for the worst case for each failure mode that is being down force spacing - module width x design load checked. Wind Down Calculations All variable the same as above except for roof pitch General Design Information: Roof Pitch Module Size: 39"x 65" Basic Wind Speed= 95 mph 14 30 45 System Weight= 3 psf Ground Snow Load= 30 psf GCN landscape= 0.5 0.9 0.9 GCN portrait= 0.4 0.9 0.9 Comp Mount Allowable Loads Uplift= 656 lbs design load landscape= 9.62 17.32 17.32 psf Lateral= 436 lbs design load portrait= 7.70 17.32 17.32 psf Down Force= 1147 lbs - Ro As/I note:use 10 psf minimum �� Snow Calculations Attachment Spacing Calculations 85818 To account for unbalanced snow loads,ground snow loads will be used for roof pitches 30 degrees and Uplift Spacing „ OREGON ° lower.Per section 7.6.1 of ASCE 7-10 unbalanced snow loads do not need to be considered for slopes "y, 19(1' y above 30 degrees. Allowable Uplift Load e- UY/C). s, uplift spacing= module length or width x design load EXPIRES: 12/31/14 Ground Snow Load= 30 psf Wind Uplift Calculations FOR PAGES 1-4 Roof Pitch ASCE 7-05 Method 2 14 30 p_qh GCN Design Snow Load 29.11 25.98 psf Kd V2 I (snow load spread over the length of the rafter) q =0.00256 K,K, Basic Wind Speed= 95 mph Down Force Load Roof Pitch Exposure= C Roof Zone= Edge Zone Combinations: 14 30 Importance Factor= 1.0 K,= 0.98 from Table 6-3 D+S= 31.16 25.10 psf Gable/Hip Roof Kzt= 1.0 per 6.5.7.2 -- D+W= 12.91 19.92 psf /orst Case Roof Pitch= 14 degrees Kd= 0.85 from Table 6-4 D+0.75W+0.755 31.59 32.46 psf Roof Height= 30 GCN landscape= -1.6 iscape effective area= 13.0 ft2 GCN portrait= -1.5 landscape down force spacing = 39"x132.46 s x 144 t z = 130" ortrait effective area= 21.7 ft2 p f f Plandscape= -30.79 psf qh= 19.25 psf Pp"rtralt= 28.87 psf 1 portrait down force spacing = 65"x32.46ps f x 144 in t = 78" Uplift Load Combination:0.6D+W(ASCE Section 2.4.1 equation 7) design load landscape= -29.05 psf design load portrait= -27.12 psf 656 lbs in landscape uplift spacing = 39"x 29.05 psf x 144 ftz =83" 656 lbs in portrait uplift spacing = 65"x 27.12 psf x 144 ft2 = 54" ZS Comp Edge Zone Calculations 3 of 4 ZS Comp Edge Zone Calculations 4 of 4 Zep Sola r 5/28/13 Zep So tar 5/28/13 Lateral Spacing Module Deflection Spacing The lateral force on the system increases as the pitch of the roof increases,but the amount of snow on landscape module spacing = -1.4545 x Maximum Uplift or Down Force Pressure+120.7273 the roof decreases for slopes greater than 30 degrees.With this in mind,the lateral force will be checked at 30 degrees with ground snow load and 45 degrees with sloped roof snow. portrait module spacing= -1.7917 x Maximum Uplift or Down Force Pressure+118.58 Allowable Lateral Load lateral spacing= module width x design load 9 Maximum Uplift of Down Force Pressure= 32.46 psf Snow Calculations Ground Snow Load= 30 psf landscape module spacing= -1.4545 x 32.46 psf+120.7273 =73" PS=C5 Pf Roof Pitch= 31 45 degrees Pf=0.7 Ce Ct I pg Ce= 0.9 C5= 0.71 0.45 Ct= 1.2 pt= 22.68 22.7 psf portrait module spacing = -1.7917 x 32.46 psf+118.58 =60" I= 1.0 ps= 16.1 10.2 psf Calculation Summary Calculated Edge Zone Spacing Roof Pitch Spacing Check Landscape Portrait 27 30 31 45 Uplift 83" 54" Design Snow Load 26.73 25.98 13.80 7.22 psf Down Force 130" 78" (snow load spread over the length of the rafter) Lateral 30° 27" 30° 74" 48" 45" Lateral Force Component Module Deflection 73" 60" Down Force Load Roof Pitch Combinations: 27 30 31 45 As can be seen in the table above,for Design Wind Speeds up to 95 mph and Ground Snow Loads up to 30 D+S= 13.50 14.49 8.65 7.22 psf psf with modules orientated in landscape,the system is strong enough to be installed at 72"on center in D+0.75W+0.75S 10.46 11.24 6.88 5.95 psf the Edge Zone.When modules are installed in portrait,the spacing for edge zone installations can be 48" on center for most roof pitches.For roof pitches that are greater than 27°but less than 31°,the maximum 30 degree roof pitch attachment spacing is 45". 292Ibs in landscape lateral spacing = 39"x 14.49 psf x 144 ft2 =74" 2921bs in portrait lateral spacing= 65"x 14.49 psf x 144 ft2 =45" Portrait spacing is less than 48".Try roof pitch of 27 degrees 2921bs in portrait lateral spacing = 65"x 13.50 psf x 144 ft2 =48" SolarCity SleekMountTM - Comp SolarCity SleekMountTM - Comp•The SolarCity SleekMount hardware solution •Utilizes Zep Solar hardware and UL 1703 listed r ..- \ Installation Instructions is optimized to achieve superior strength and Zep Compatible'"modules r \ , f! aesthetics while minimizing roof disruption and Drill Pilot Hole of Proper Diameter for labor.The elimination of visible rail ends and •Interlock and grounding devices in system UL Fastener Size Per NDS Section 1.1.3.2 listed to UL 2703 mounting clamps, combined with the addition • Seal pilot hole with roofing sealant of array trim and a lower profile all contribute •Interlock and Ground Zep ETL listed to UL 1703 L to a more visually appealing system. SleekMount as"Grounding and Bonding System" VA, Insert Comp Mount flashing under upper utilizes Zep CompatibleTM modules with •Ground Zep UL and ETL listed to UL 467 as ;f \ layer of shingle strengthened frames that attach directly to grounding device . Place Comp Mount centered Zep Solar standoffs, effectively eliminating the need for rail and reducing the number of •Painted galvanized waterproof flashing upon flashing standoffs required. In addition, composition .Anodized components for corrosion resistance • Install lag pursuant to NDS Section 11.1.3 shingles are not required to be cut for this ,,_._ with sealing washer. system, allowing for minimal roof disturbance. •Applicable for vent spanning functions , \ • Secure Leveling Foot to the Comp Mount using machine Screw • Place module ti) A Components ,� ri) i� A 5/16"Machine Screw B Leveling Foot „F„ ■of 4 C t_ag Screw �' D Comp Mount ; r.. C E Comp Mount Flashing 1 E ir:CII' m. ...��I� Y comPA�IB( ,q SolarCity January 2013 LISTED SOIar�I�y. January 2013 • • TSM-PA05.18 TRINAMOUNT II WITH THE UNIVERSAL MODULE Mono Multi Solutions DIMENSIONS OF PV MObULE TSM-PAp5,18 ELECTRICAL DATA @ STC TSM-240 TSM•245 TSM-250 TSM•255 TSM-260 PA05.18 PA05.18 PA05.18 PA05.18 PA05.18 941mm Peak Power Watts-PrAnx(Wp) 240 245 250 255 260 Power Output Tolerance-PMAx(%) 0/+3 0/+3 0/+3 0/+3 0/+3 cx, Maximum Power Voltage-V,AP(V) 29.7 30.2 30.3 30.5 30.7 i r 0 Maximum Power Current-IMP,(A) 8.10 8.13 8.27 8.36 8.47 T M - PAo5 .18 .S s. t .�O Open Circuit Voltage-Voc(VJ 37.3 37.5 37.6 37.7 37.9 e vxls Msuu•u Nea Short Circuit Current-Isc(A) 8.62 8.68 8.85 8.92 9.00 Module Efficiency q",(%) 14.7 15.0 15.3 15.6 15.9 THE TRINAMOUNT MODULE STC:Irradiance 1000 W/m'.Cell Temperature 25°C.Air Mass AMI.5 according to EN 60904-3. Average efficiency reduction of 4.5%a1200 WW according to EN 60904-I. E ,o E o ° 3 I 3 TSM-240 TSM-245 TSM-250 TSM-255 TSM-260 CELL ELECTRICAL DATA..NOCT PA05.18 PA05.18 PA05.18 PA05.18 PA05.18 60 Maximum Power-PMAx(Wp) 174 178 181 184 188 Maximum Power Voltage-VAw(V) 26.6 26.8 27.0 27.2 27.4• MULTICRYSTALLINE MODULE A.e3<<,.NIxNr.1N I A ' A Maximum Power Current-lerx(A) 6.55 6.64 6.70 6.77 6.86 WITH TRINAMOUNT FRAME /10AN"■01' Open Circuit Voltage(V)-Voc(V) 34.1 34.2 34.3 34.4 34.6 111 N. Short Circuit Current(A)-Isc(A) 7.04 7.10 7.25 7.31 7.37• 240-260W 812mm I 180 I NOCT Irradiance 800 W/m',Ambient temperature 20°C.Wind Speed I m/s. Back View , POWER OUTPUT RANGE MECHANICAL DATA Our most versitile product j11 Solar cells Multicrystalline 156=156 mm(6 inches) • Compatible with all major BOS components and system designs Cell orientation 60 cells(6 x 10) 1 o O e Module dimensions 1650 P 992=40 mm(64.95 x 39.05 x 1.57 inches) iyl� Weight 18.6 kg(41.0 Ibs) MAXIMUM EFFICIENCY 1 Gloss High transparency solar glass 3.2 mm(0.13 inches) Backsheet White One of the industry's most trusted modules Frame Black Anodized Aluminium Alloy with TrinamouniGroove ;(iii' • Over 2 GW sold across all major global markets 0 +3% • Field proven performance I-v CURVES OF PV MODULE TSM-245 PA05.18 J-Box IP 65 or IP 67 rated Cables Photovoltaic Technology cable 4.0 mm'(0.006 inches'). iT' -- 1100 mm(43.3 inches) POWER OUTPUT GUARANTEE 9.": 100ow/m - 80°1. Connector Original MC4 _7 m I 800w/m' Highly reliable due to stringent quality control 6° 600W/w' m 5m As a leading global manufacturer _ • Over 30 in-house tests(UV,T,HF,gand many more) u 2m' 400W/r& - - TEMPERATURE RATINGS MAXIMUM RATINGS of next generation photovoltaic 't`$ In-house testing goes well be on certification requirements products,we believe close 20aw/m Nominal Operating Cell 45°C(±2°C) Operational Temperature -40-+85°C p 1 Temperature(NOCT) cooperation with our partners 1 m, ---- - - Maximum System 1000V OC)IEC)/ is Critical to success. With local o o.o, - - 11 Temperature Coefficient of Pr4Ax -0.43%/°C Voltage 600V DC(UL) 0."0 10.00 10.10 30.m 40.00 presence around the globe,Irina is ---- --- Temperature Coefficient of Voc -0.32%/"C Max Series Fuse Rating 15A able to provide exceptional service Temperature Coefficient of Isc 0.047%/°C to each customer in each market and supplement our innovative, -v Certified to withstand challenging environmental reliable products with the backing S, * conditions of Trina as a strong,bankable • 130 km/hr wind load (2400 Pa) WARRANTY partner. We are committed • 900 kg snow load per module (5400 Pa) 10 year Product Workmanship Warranty to building strategic.mutually beneficial collaboration with 25 year Linear Power Warranty ca installers,developers,distributors (Please refer to product warranty for details) and other partners as the �' backbone of our shared success in CERTIFICATION ' r driving Smart Energy Together. LINEAR PERFORMANCE WARRANTY //�� (�`� �- !e PACKAGING CONFIGURATION 10 Year Product Warranty•25 Year Linear Power Warranty ''" - •ea ,,, C. JS Modules per box:24 pieces A Modules per 40'container:672 pieces Trina Solar Limited -" www.trinasolar.com `i,100% ISO t.1J (E c VL us PV'byttE 3 Addition .ra V 0 90% nal VaiUE lraM Trina Sotar'S/(near Warrant r, CAUTION:READ SAFETY AND INSTALLATION INSTRUCTIONS BEFORE USING THE PRODUCT. •caMPArA6 • a Y • .2013 Trina Solar Limited.All rights reserved.Specifications included in This datasheef ore subject to ti r Tr�nasolar Tr�nasolar than A O 80% change without notice. W Smart Energy Together Smart Energy Together c 4" Years 5 10 15 20 25 OMPA • ■Trina Solar I 1 Solar inverters Additional highlights: r, a — RS-485 communication interface ABB string inverters (for connection to laptop or data PVI-3.0/3.6/3.8/4.2-TL-OUTD logger). Integrated Arc Fault Detection and . 3.0kW to 4.2kW Interruption(-A Version). T__ Technical data and types Type code PVI-3.0-OUTD-US PVI-3.6-OUTD-US PVI-3.8-OUTD-US PVI-4.2-OUTD-US AU Mechanical specifications #, I,V#,,gag*R"' *# e4 Nominal output power 3000W 3600W 3300 3800W 4200W -<- W 3000 : 3300' 3300' 3600 4000' 4000' 3300 4200 4200' 4200 4600' 4606{• Maximum output power wattage : W : W W W w W W W W W W W grid voltage rid AC Volta a 208V 240V 277V 208V 240V ' 277V 208V 240V 277V 208V 240V 27N Input side(DC) Number of independent MPPT channels 2 2 2 2 Maximum usable power for each channel 2000W 3000W : 3000W 3000W Absolute maximum voltage(Vmax) 600V ' Start-up voltage(Vstart) 200V(adj.120-350V) Full power MPPT voltage range 160-530V 120-530V 140-530V 140-530V Operating MPPT voltage range 0.7 x Vstart-580V(>=90V) Maximum current(Idcmax)for both MPPT in 20A 32A 32A 32A parallel..._ Maximum usable current per channel 10A 16A 16A 16A Maximum short circuit current limit per 125A 20 OA 20.OA 20.OA channel Number of wire landing terminals per channel 2 pairs Array wiring termination Terminal block,pressure clamp,AWG1D-AWG4 1 Output side(AC) Grid connection type 0/ Split- 10/ 10/ Split- 10/ 10/ Split- 10/ 10/ Split- 10/ 2W 0/3W 2W ' 2W 0/3W 2W 2W 0/3W 2W 2W 0/3W 2W .. Adjustable voltage range(Vmin-Vmax)M 183- 211 - 244- 183- 211- 244- • 183- 211- 244- 183- -211- 244- 228V 1264V 304V 228V 264V 304V 228V 264V 304V 228V 264V 304V Grid frequency 60Hz Adjustable grid frequency range 57-60.5Hz Maximum current(Ir m„) 14.5 14.5 12.0 171 16.0 16.0 16.0 16.0 16.0 ! 20.0 200 20.0 .............. Aaus... ...Aare.. Aaas......Alw......._Anra......_Aaua ....A...........Ann-......Asus ....Aat.s '.__A_4 .....paws..... Power factor >0.995 Total harmonic distortion at rated power <2% This family of single-phase string The high-speed MPPT offers real- Highlights: Grid wiring termination type Terminal block,Pressure clamp,AWG10-AWG4 inverters complements the typical time power tracking and improved — Single phase and split phase output Input protection devices Reverse polarity protection Yes number of rooftop solar panels energy harvesting. grid connection. Over-voltage protection type Varistor,2 for each channel enabling home-owners to get the most The flat efficiency curve ensures high — Wide input range for increased PV array ground fault detection Pre start-up Riso and Dynamic GFDI(requires floating arrays) efficient energy harvesting for the size efficiency at all output levels allowing stringing flexibility. Output protection devices of the property. a consistent and stable performance — The high speed and precise MPPT Over-voltage protection Meets UL 1 Varistor,2EE154/requirements p 9 p Over voltage protection type Varistor,2(L,-1_2/L.-G) across the entire input voltage and algorithm offers real time power Maximum AC OCPD Rating 20A 20A 15A,,° 25A,,,,, 20A,,,,,, 20A,,,,° 20A,,,, 20Aw„` 20A4,,,, 25A,,,,° 25A,,,,° 25A,,,,° This inverter offers a dual input output power range. tracking and improved energy Efficiency Maximum efficiency 96 9% 97% 97% 97% section that processes two strings The transformerless operation gives the harvesting. CEC efficiency 96% with independent Multiple Power Point highest efficiency of up to 97.0%. — Outdoor NEMA 4X rated enclosure Operating performance Tracking(MPPT). The wide input voltage range makes for unrestricted use under any Night time consumption <0.6ww,,, This is especially useful for rooftop the inverter suitable to low power environmental conditions. Stand-by consumption <aWw •, Communication installations with two different installations with reduced string size. — Integrated DC disconnect switch User-interface 16 characters x 2 lines LCD display orientations from two sub-arrays This rugged outdoor inverter has been in compliance with international Remote monitoring(1 xRS485 incl.) VSN700 Data Logger(opt) oriented in different directions.(For designed to be a completely sealed Standards(-S Version). l bientrt air operating air operating temperature range -13°F to-4-140°F with derating above 122°F(50`C) example:East and West) unit able to withstand the harshest Ambient air storage temperature range -40°F to+176°F(-40°C to+80'C) The dual input sections with environmental conditions. Relative humidity 0-100%RH condensing independent MPPT enable a more Acoustic noise emission level <50 db(A)W1 m Maximum operating altitutde without derating 6560 ft(2000 m) optimal energy harvesting condition. Power and productivity 1.Capability enabiao at nominal AC voltage and with sufficient DC power available for a better work!'" 2 ABB Solar Inverters I Product flyer for PVI-3.0/3.6/3.8/4.2-TL-OUTD