Loading...
Permit � s W CITY OF TIGARD ELECTRICAL PERMIT sE COMMUNITY DEVELOPMENT Permit#: ELC2015-00254 T IGARD 13125 SW Hall Blvd.,Tigard OR 97223 503.718.2439 Date Issued: 04/30/2015 Parcel: 25101 CA00200 Jurisdiction: Tigard Site address: 7904 SW HUNZIKER RD Project: Agilyx Subdivision: 1994-025 PARTITION PLAT Lot: 2 Project Description: Electrical service upgrade. Contractor: OREGON ELECTRIC GROUP Owner: WALL STREET INDUSTRIAL LLC 1709 SE 3RD AVE A RICHARD VIAL EXECUTIVE CENTER LLC PORTLAND, OR 97124 7000 SW VARNS ST PORTLAND, OR 97223 PHONE: 503-234-9900 PHONE: FAX: 503-234-1001 FEES Quantity Description Date Amount 1 ea Services or Feeders-601 to 04/30/2015 $301.04 Specifics: 1000 amps 20 crt Branch Circuits w/Purchase 04/30/2015 $148.40 Type of Use: COM Service or Feeder Class of Work: ALT 1 ea 12%State Surcharge- 04/30/2015 $53.93 Electrical Type of Const: 1 ea Plan Review Electricial 04/30/2015 $112.36 Occupancy Grp: Total $615.73 Required Items and Reports(Conditions) This permit is issued subject to the regulations contained in the Tigard Municipal Code. State of OR. Specialty Codes and all other applicable law. All work will be done in accordance with approved plans. This permit will expire if work is not started within 180 days of issuance, or if work is suspended for more the 180 days. ATTENTION: Oregon law requires you to follow the rules adopted by the Oregon Utility Notification Center. Those rules are set forth in OAR 952-001-0010 through OAR 952-001-0090. You may obtai of the rules or direct questions to OUNC by calling 503.232.1987 or 1.800.332.2344. Issued By: Permittee Signature: OWNER INSTALLATION ONLY The installation is being made on property I own which is not intended for sale,lease or rent. OWNER'S SIGNATURE Date: CONTRACTOR INSTALLATION ONLY SIGNATURE OF SUPR.ELEC' Date: LICENSE NO. Call 503.639.4175 by 7:00 a.m.for the next available inspection date. This permit card shall be kept in a conspicuous place on the job site until completion of the project. Approved plans are required on the job site at the time of each inspection. 1 Electrical Permit Applicatio aiNtV FOR OFFICE USE ONL\ 1 Received City of Tigard Date/B ti " 13125 SW Hall Blvd.,Tigard,OR 97223 APR 1 e Zp15 Plan Review /�� - i1i� Z Phone: 503.718,2439 Fax: 503.598.1960 1 Date/B : .2 —i'7 Other Permit: T 1 GAR D Inspection Line: 503.639.4175 (I A0 Date Ready/By: . 65 See Page 2 for Internet: www.tigard-or.gov 0 1"ktA Notified/Method: 7 Supplemental Information_ME TYPE OF W s e PLAN REVIEW ❑New construction ®Addition/alteration/replacement Pie enec all that apply(submit/sets of plans w/items checked below): ` ai Service or feeder 400 amps or more ❑Building over three stories. "s ❑Demolition ❑ Other: where the available fault current ❑Marinas and boatyards. I RY OF CONSTRUCTION exceeds 10,000 amps at 150 volts or ❑Floating buildings. less to ground,or exceeds 14,000 ❑Commercial-use agricultural ❑ 1-and 2-family dwelling ®Commercial/industrial ❑Accessory building amps for all other installations. buildings. ❑Multi-family ❑Master builder ❑Other: 0 Fire pump. 0 Installation of 150 KVA or larger separately derived system. JOB SITE INFORMATION AND LOCATION ❑Emergency system. ❑Addition of new motor load of ❑"A","E"."1-2","1-3", 1 Job no.:702848 I Job site address:7904 SW Hunziker St. IOOHP or more occupancy. ❑Six or more residential units. ❑Recreational vehicle parks. , City/State/ZIP:Tigard,OR 97223 ❑Health-care facilities. ❑Supply voltage for more than ❑Hazardous locations. 600 volts nominal. Suite/bldg./apt.no.: I Project name:Agilyx Corp ❑Service or feeder 600 amps or more. FEE SCHEDULE 1 Cross street/directions to job site: Description I Qty. I Fee. I Total I • t. New residential single-or multi-family dwelling unit. 4 Includes attached garage. 4• Subdivision: I Lot no.: 1,000 sq.ft.or less 168.54 4 Tax map/parcel no . Ea.add'l 500 sq.ft.or portion 33.92 1 Limited energy,residential 75.00 2 `DESCRIPTION OF WORK 'V (with above sq.ft.) Limited energy,multi-family 75.00 Power upgrade to electrical service. residential(with above sq.ft.) Renewable Energy ❑ See Page 2 Services or feeders installation,alteration,and/or relocation 0 PROPERTY OWNER I 0 TENANT 200 amps or less 100.70 2 201 amps to 400 amps 133.56 2 Name:Agilyx 401 amps to 600 amps 200.34 2 Address: 601 amps to 1,000 amps 1 301.04 301.04 2 Over 1,000 amps or volts 552.26 2 City/State/ZIP: Temporary services or feeders installation,alteration,and/or Phone:( ) Fax:( ) relocation 200 amps or less 59.36 1 Owner installation:This installation is being made on property that I own which is not 201 amps to 400 amps 125.08 2 intended for sale,lease,rent,or exchange,according to ORS 447,449,670,and 701. 401 amps to 599 amps 168.54 2 ' Owner signature: _ _ — _ Date:_ Branch circuits—new,alteration,or extension,per panel ❑ APPLICANT I ® CONTACT PERSON A.Fee for branch circuits with above service or feeder fee, 20 ,4' 148.40 2 i Business name: each branch circuit B.Fee for branch circuits without 1 Contact name:Brad Sisson service or feeder fee,first 56.18 2 branch circuit Address: Each add'l branch circuit 7.42 2 1 Miscellaneous(service or feeder not included) City/State/ZIP: Each manufactured or modular 44 Phone:(503)849-2252 I Fax::(503)234-1001 dwelling,service and/or feeder 67.84 2 IReconnect only 67.84 2 E-mail:brad.sisson®oregon-electric.com Pump or irrigation circle 67.84 2 CONTRACTOR Sign or outline lighting 67.84 2 Business name:Oregon Electric Construction,Inc Signal circuit(s)or limited-energy See panel,alteration,or extension. Page 2 2 Address: 1709 SE 3rd Ave Each additional inspection over allowable in any of the above Additional inspection(1 hr min) 66.25/hr City/State/ZIP:Portland,OR 97214 Investigation(1 hr min) 66.25/hr 1 Phone:(503)234-9900 Fax:(503)234-1001 Industrial plant(1 hr min) 78.18/hr Inspections for which no fee is 90.00/hr CCB Lie.: 203 I Electrical Lic.: 26-95c Suprv,Lie.: 4818s specifically listed(' hr min) , ELECTRICAL PERMIT FEES t;■ Suprv.Electrician signature,required:a Subtotal: 449.44 Print name: Mark Weinbender Date: 04/16/15 Plan review(25%of permit fee): 112.36 jf� State surcharge(12%of permit fee): 94' **g13 Authorized signahr a j/ TOTAL PERMIT FEE: 6/5-173 6 'A This permit application expires if a permit is not obtained within 180 Print name: U Date: days after it has been accepted as complete. ■ • Number of inspections allowed per permit. I:\Build ng\Permits\ELC_PetmitApp_ELR_ERE.doc Rev 05/21/2013 i •I5T(11/05/COM/WEB RECEIVED CR 16 2015 CITY OF 116AKU BUILDING DIVISION 1600 AMP PGE 4801277V 19,650AIC TRANSFORMER 500KVA 200A) 200A ) 400Ai) 600Ai) 600A ) 400A ) 0 0 0 0 o SPAR ET OFFICE COPY (OUTDOOR) (INCREASING FROM 400A TO SODA) 4"PVC (3)-350 ALUM PER PHASE TRANSFORMER (1)-4/0 GROUND CITY OF TIGARD EXISTING 600A REVIEWED FO ODE COMPLIANCE 75K(.E) PANEL#2 480V 30 �Fl Approved: I EjtG+e.'c" t I OTC: I ] Permit#: LC �0(S -0024.---K ATS (PANEL WAS SEED AT 400A) PANEL L1 Address: .290 cr 14,;r 2 t k e/ S r 200A Suite#' 208/120V gy; D 14/,771 CO PANEL#4 I U S 6 OREGON ii ELECTRIC GROUP •ITN SE.5d fl tSU[•P70Th Q.OREGON 17214• 3 •(SW)3]A-99W•rlJt(3Ql)3N-1001•....aK.^-M bl�mn• AGILYX CORP 1 9600 SW Nimbus Suite 260 Oregon c�,Inc. Beaverton, OR 97008 " z One Line Oregon supervisor ° Diagram Mark Weinbender,LIQ 48183 m PROJECT NO. oEG- ` / / DRAWN BY EH CHKD.BY DATE DATE EDITED: 15 April 2015 0 SCALE NTs s FILE: t l/6//` < K:\Cadtiles—new\0—No/�\15\Agilyx Corp\E5.00 One Line.dwg r J 0 Yx NUMBER E5.00 City of Tigard 13125 SW Hall Blvd. Tigard, OR 97223 Tel: 503.718.2439 Location: Inspection Date: 7904 SW HUNZIKER RD, TIGARD, OR, 97223 Record Type: Record ID: Commercial - Electrical ELC2015-00254 Inspection Type: Inspector: 199 Electrical final Jeff Grove Result: PASS - NoCofO Comments: Violation Summary: Inspector Contractor Location: Record Type: Inspection Type: Result: Comments: Inspection Date: Record ID: Inspector: City of Tigard 13125 SW Hall Blvd. Tigard, OR 97223 Tel: 503.718.2439 7904 SW HUNZIKER RD, TIGARD, OR, 97223 Commercial - Electrical 199 Electrical final PASS - No C of O ELC2015-00254 Jeff Grove Violation Summary: Inspector Contractor