Plans U 20 9 0 0 1 13 _ „, 1 1 01 00 00 GENERAL DATA 7. AT ALL EXISTING WALLS,REMOVE ALL NAILS,SCREWS,FASTENERS,ETC.LEFT BY PREVIOUS TENANT AND PATCH 23 00 00 HVAC ,,,„`\HOLES READY FOR PAINT. ER REQUIREMENTS 8. HVAC �� GENERAL REQUI N $ . UPON REMOVAL OF ANY WALL BASE MATERIAL,CONTRACTOR TO PREP WALL TO PAINT READY CONDITION. VAC -BID PROCEDURE TENANT IMPROVEMENT for N 1. ALL CONSTRUCTION WORK SHALL BE DONE IN COMPLIANCE WITH THE LATEST EDITION OF THE WALL CONSTRUCTION MATERIALS 1. FOR BIDDING PURPOSES,THE HVAC CONTRACTOR WILL ASSUME THAT EXISTING HVAC EQUIPMENT IS IN PROPER M.RTIN W. HANSON INTERNATIONAL BUILDING CODE AS AMENDED BY THE STATE OF OREGON AND ALL OTHER STATE OR LOCAL WORKING ORDER, 20 G,4 3 5/D METAL STUD BRACING C� " 1. PROVIDE STUDS,TRACKS,BRACING,FASTENING AND OTHER ACCESSORIES NECESSARY FOR COMPLETE TO ROOF STRUCTURE AT 10 OG CODE REQUIREMENTS THAT APPLY. INSTALLATION. 2. INVENTORY EXISTING H.VA.C.ROOFTOP UNITS AND SUBMIT TO ARCHITECT A CONDITIONS REPORT OF EACH UNIT WHERE REQUIRED CLAC MAS, OREGON 2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS SHOWN ON DRAWINGS INGS AND AT THE EXISTING �- 3. LIST TONNAGE OF EACH UNIT. -EMTrR D OVER WALL ,/ BUILDING AND NOTIFY ARCHITECT OF ANY DISCREPANCIES PRIOR TO STARTING THE WORK. 2. FRAMING MEMBERS SHALL HAVE THE STRUCTURAL PROPERTIES INDICATED WHERE PHYSICAL STRUCTURAL �, � R-u BAT". INSUL.ATI�TL 4'�� PROPERTIES ARE NOT INDICATED,THEY SHALL BE AS NECESSARY TO WITHSTAND ALL IMPOSED LOADS. DESIGN HVAC -DESIGN PROCEDURE &44 & 'Ak��,���,�,O�+I CV 3. CONTRACTOR AND ALL SUBCONTRACTORS SHALL PERFORM DUE DILIGENCE INSPECTION OF ALL EXISTING FRAMING IN ACCORDANCE WITH AISI SG-673. 1 EXISTING SUSPENDED CEILING ��i CONDITIONS PRIOR TO SUBMITTAL OF A PROPOSAL.SUBMITTAL OF A PROPOSAL SHALL BE CONSIDERED USE EXISTING AND/OR NEW EQUIPMENT TO DESIGN MECHANICAL H.VA.C.SYSTEM PER DESIGN STANDARDS LISTED BELOW. ^ _4 OF 0 w 3. COW-FORMED FRAMING SHALL BE GALVANIZED METAL CONFORMING TO ASTM A446/A 446 M GRADE A(33000 PSI)G60. RAW RECESSED CONFIRMATION THAT SUCH INSPECTION HAS BEEN MADE AND NO FURTHER COMPENSATION SHALL BE DUE IZ D A ( ) • B RE E SED THE CONTRACTOR FOR CLAIMS ARISING AS A RESULT OF FAILURE TO PERFORM SUCH INSPECTION. PRIOR TO AWARD OF CONSTRUCTION CONTRACT,H.VA.C.CONTRACTOR SHALL SUBMIT TO ARCHITECT FOR REVIEW AND 14.14. C. REVEAL HEADER 4. PROVIDE THE LISTED GYPSUM BOARD PRODUCTS BY U.S.GYPSUM,GEORGIA PACIFIC,NATIONAL GYPSUM OR AN APPROVAL A FULL DESIGN SCHEMATIC FOR THE TENANT SPACE INCLUDING BOTH NEW/RENOVATED WORK AND SYSTEMS 4. BY SUBMITTING A PROPOSAL,CONTRACTOR AND ALL SUBCONTRACTORS CERTIFY THAT THEY HAVE APPROVED EQUAL. UNTOUCHED BY THE TENANT IMPROVEMENT AS APPLICABLE. INCLUDE THE FOLLOWING: �A PROJECT 09270 EXAMINED THE SITE AND INCLUDED IN THEIR PROPOSAL ALL WORK NECESSARY TO COMPLETE THE WORK R �• DESCRIBED OR REASONABLY IMPLIED IN THESE DOCUMENTS. THIS INCLUDES BUT MAY NOT BE LIMITED TO 5. STANDARD GYPSUM BOARD SHALL BE 5/8 THICK WITH TAPERED EDGES CONFORMING TO AS1M C-36. A. DUCTING AND SIZES �� 3-1/2" ATT INSUL �� � ALL MATERIALS AND INSTALLATION,DISPOSAL OF EXCESS MATERIALS(USEABLE FINISH MATERIALS SHALL BE 6. WATER RESISTANT GYPSUM BOARD SHALL BE 5/8"THICK WITH TAPERED EDGES. CONFORMING TO ASTM C-630. B. SUPPLY AND RETURN LOCATIONS AND CFM PROJECT NARRATIVE stag $ ' LEFT IN THE TENANT SPACE AS DIRECTED BY PACTRUST),CLEANING AND ALL PREPARATION OF SUBSTRATE 7. CEMENT BACKER BOARD SHALL BE A"THICK WITH SQUARE,REINFORCED,SMOOTH EDGES. PROVIDE DUROCK BRAND C. ROOF EQUIPMENT,SIZES AND LOCATIONS THE PROJECT CONSTIST OF REMODEL WORK TO 1,694 SF OF EXISTING OFFICE SPACE. 3-5/8"MIL.STUDS 24"O.C. JUN 0 SURFACES PRIOR TO INSTALLATION,AS WELL AS FINAL CLEAN UP. D. UNITS REQUIRING DUCTED SMOKE DETECTION CEMENT BOARD OR APPROVED EQUAL. WORK SHALL INCLUDE BUT NOT BE LIMITED TO DRYWALUMETAL STUDS, DOORS/FRAMES 5/8"GYP. BOTH SIDES E. THERMOSTAT LOCATIONS AND ZONE/UNITASSOCIATED THEREWITH ' - / CITY OF'TIGA ZD 5. IT IS THE INTENT OF THESE CONTRACT DOCUMENTS TO MATCH AND MAINTAIN THE EXISTING BUILDING 61 CENTER LINE OF STUD STANDARDS FOR ALL EXISTING PRODUCTS AND SYSTEMS. UPON DISCOVERY OF A DISCREPANCY TO THIS 8. TRIM ACCESSORIES SHALL COMPLY WITH ASTM C-1047. F. ANY SUPPLEMENTAL EXHAUST FANS OR SPECIAL SYSTEMS AND PAINTING. ALL WORK TO MEET ADA REQUIREMENTS. BUILDING DIVISION G. ZONE DIAGRAM INTENSION,THE CONTRACTOR SHA LL NOTIF Y THE ARCHITECT IMMEDIATELY. WALL CONSTRUCTION EXECUTION AT COMPLETION OF PROJECT THE HVAC CONTRACTOR IS TO PROVIDE LABEL ON GAS METER WITH TENANT ADDRESS AND Will 6. FURNISH ALL NEW MATERIALS EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. 1. FASTEN FRAMING MEMBERS TOGETHER BY WELDING OR BY USING SELF-DRILLING OR SELF-TAPPING SCREWS. SUITE NUMBER. r . 7. CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES. PROVIDE CARPET'WALK-OFF MATS"TO WELDING SHALL CONFORM TO AWS D13 WELDING PROCEDURE. ELECTRODES AND SCREW CONNECTIONS SHALL BE WORK INCLUDED BUT PERFORMED UNDER SEP. PERMIT Nil PROTECT EXISTING CARPETS. AS REQUIRED AND INDICATED IN THE DESIGN CALCULATIONS. DO NOT FIELD WELD MATERIALS LIGHTER THAN 18 GA. HVAC DESIGN STANDARDS . 2. PROVIDE ACCURATELY ALIGNED RUNNERS AT TOP AND BOTTOM OF PARTITIONS. ANCHOR TRACKS AS INDICATED IN THE FOLLOWING ARE MINIMUM DESIGN STANDARDS: FIRE PROTECTION SPRINKLERING `� 3-1/2" BAIT INSUL.IN SOUND ATTENUATION WALLS r j 8. ALL ROOF PENETRATIONS FROM ABANDONED EQUIPMENT TO BE REMOVED. PATCH AND REPAIR ROOF AS �/ NEEDED. THE DESIGN CALCULATIONS. BUTT WELD JOINTS IN TRACKS OR SPLICE WITH STUD INSERTS. FASTENERS SHALL BEAT 1. 350 SQUARE FOOT PER TON. HEATING,VENTILATION&AIR CONDITIONING WORK a 4" RUBBER BASE-PIP. LEAST 3 INCHES FROfv1 THE EDGE OF CONCRETE SLABS. ELECTRICAL WORK BOTH LINE VOLTAGE AND LOW VOLTAGE 41,2" ATTACH BOTTOM TRACK TO FLOOR WITH 9. ALL ROOF WORK TO BE PERFORMED BY PACTRUST APPROVED ROOFING COMPANIES. APPROVED COMPANIES `I INCLUDE: 3. CUT STUDS SQUARE AND SET WITH FIRM BEARING AGAINST WEBS OF TOP AND BOTTOM TRACKS. POSITION STUDS 2. ADDRESS LOADS BY SPECIFIC LOCATION AND USE AS WELL AS CRITERIA PROVIDED TO PACTRUST BY TENANT PRIOR TO '0�, POWDER DRIVEN ANCHORS AT 12" O.G. CONSTRUCTION: ��, � A. ANDERSON ROOFING, (503)294-0202 VERTICALLY IN TRACKS AND SPACE AS INDICATED IN DESIGN. DO NOT SPLICE STUDS. PROVIDE AT LEAST TWO FULL � FINISH FLOOR 4 M HEIGHT KING STUDS T N TUDS A DOORS AND OTHER OPENINGS 2 FEET WIDE OR LARGER. PROVIDE JACK STUDS OVER A. EXTERIOR EXPOSURE AREAS � ,, ., ,1.1"141, ., ,, ; B. PACIFIC ROOFING (503)640-3163 OPENINGS,AS NECESSARY,TO MAINTAIN INDICATED STUD SPACING. PROVIDE TRIPLE STUDS AT CORNERS, B. INTERIOR AREAS,SIZE AND USE ! C. GRIFFITH ROOFING (503)643-1596 4'(/8' POSITIONED TO RECEIVE INTERIOR AND EXTERIOR FINISHES. FASTEN STUDS AT TOP AND BOTTOM TRACKS BY C. CONFERENCE/TRAINING ROOMS WELDING OR SCREWING BOTH FLANGES TO THE TRACKS. D. COMPUTER/SERVER AND TELEPHONE ROOMS TO HAVE PROVISION FOR LOW AMBIENT OPERATION AND 24-HOUR AI WALL SECTION WI SOUND INSUL. 10. CONTRACTOR SHALL KEEP NE AREA OF WORK FREE OF GARBAGE AND DEBRIS ON A DAILY BASIS INCLUDING 4. INSTALL ALL INTERIOR AND EXTERIOR GYPSUM BOARD PRODUCTS AND ACCESSORIES AS REQUIRED FOR THE USE. BUILDING INFORMATION TENANT INFORMATION A-1 1"- n a N DOCK ACCESS AREAS AND COMMON AREA. FLOORS TO BE SWEPT OR VACUUMED DAILY. PROJECT. 3. PACTRUST PREFERENCE IS ZONES TYPICAL 3-5 TON BASED ON USE&EXPOSURE CRITERIA. ZONE LOADS GREATER OWNER: PACIFIC REALTY ASSOCIATES,L.P. TENANT: SCALE 1 - 1-0 N 11. THE CONTRACTOR SHALL PROVIDE ADEQUATE PROTECTION TO ALL EXISTING IMPROVEMENTS INCLUDING BUT THAN 5 TONS FOR PACKAGED OR SPLIT SYSTEM EQUIPMENT SHALL BE SPLIT INTO MULTIPLE ZONES. ZONE LOADS 15350 SW SEQUOIA PKWY#300 REFERENCE CAPITAL MANAGEMENT,L.L.C. 5. COMPLY WITH USG GYPSUM S UM CON TRUC7'lON HANDBOOK AND MANUFACTURER'S RECOMMENDATIONS. 0 NOT In LIMITED TO COMMON CORRIDORS AND STAIRS,BUILDING ENTRANCES,SUITE ENTRANCES,ETC. THE GREATER THAN 3 TONS FOR VAV OR H2O SOURCE HEAT PUMPS SHALL BE SPLIT INTO MULTIPLE ZONES. PORTLAND,ORE 97224 O in CONTRACTOR WILL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGES TO EXISTING IMPROVEMENTS DUE 6. FINISH QUALITY: 4. ALL ENCLOSED ROOMS OR OFFICES TO HAVE DUCTED SUPPLY&RETURN GRILLES. OCCUPANCY AREAS&LOADS: TO CONSTRUCTION ACTIVITIES. AREA PROCESS TRADE NOMENCLATURE (503)624-6300 (PHONE) AREA LOAD REQ. EXITS I, WAREHOUSE TAPE/FINISH COA7'� TIGHT DOUBLE 5. UNITS: LENNOX TRANE YORK OR CARRIER-7 1/2-TON MAXIMUM UNIT SIZE. ANY UNIT IN EXCESS OF 71/2 TONS SHALL 12. CONTRACTOR TO PROVIDE TEMPORARY SANITARY FACILITIES. CONSTRUCTION WORKERS SHALL NOT USE HAVE SPECIAL APPROVAL BY PACTRUST. (503)624-7755(FAX) 1,694 SF 17 OCC 1 EXIT C4 c4 cNi BUILDING RESTROOM FACILITIES. OFFICE/OTHER AREAS TAPE/2 FINISH COATS*/ SMOOTH FINISH TAPED 1/40 1/40 USG"FIRST COAT' *SAND AFTER TAPE/FINISH COAT(S) 6. HVAC UNITS WITH EQUAL TO OR GREATER THAN 5-TONS TO HAVE DUCTED SMOKE DETECTION AND BE CONNECTED TO A BLDG.#. BLDG. B ttc082 VI M M 1 13. STORAGE AND STAGING OF CONSTRUCTION MATERIALS SHALL BE LIMITED TO AREAS AS DESIGNATED AT PRE- ( ) cc r3 CONSTRUCTION MEETING. UNDER NO CIRCUMSTANCES SHALL BUILDING UTILITY AREAS OR ANY OTHER 7. FINISH EXPOSED INTERIOR GYPSUM BOARD WALLS AND CEILINGS SMOOTH STRAIGHT READY FOR TEXTURE AND/OR MONITORING STATION WITHIN THE BUILDING. COMMON BUILDING AREA BE USED FOR STORAGE. FINISH AS SHOWN ON PLANS. 7. SEISMICALLY ATTACH UNIT TO CURB IN CODE-APPROVED FASHION. CONST.TYPE.: I I-B M 0 Z k I 14. CONTRACTOR SHALL KEEP THE ROOF FREE OF DEBRIS(I.E.NAILS,SCREWS,BOTTLES,ETC.)AT ALL TIMES. 8. INSTALL WATER-RESISTANT GYPSUM BOARD AT WALLS WITH WAINSCOT PANELING(RESTROOMS,JANITOR CLOSETS). 8. ANY GAS PIPING SHALL BE STANDARD BLACK STEEL PIPE W/SUPPORTS PER CODE. PIPING SHALL BE RUN INSIDE OF EXISTING UIINDOW WALL 'I� Pr f BUILDING W/LEAD FLASHINGS AT ROOF PENETRATIONS. LEAD ROOF JACKS TO BE SEALED AND CLAMPED(S.S.WORM THIS BUILDING HOUSES MULTIPLE TENANTS INCLUDING THIS TENANT. THE EXISTING 15. ALL DIMENSIONS ARE TO FACE OF GYPSUM BOARD UNLESS OTHERWISE NOTED. 09 53 00 SUSPENDED ACOUSTICAL CEILING /// -.- - - - - ., GEAR). BUILDING IS A FOUR STORY BUILDING OF 87,890 SF AND IS FULLY SPRINKLERED. EACH I 16. CONFIRM SIZES OF ALL OPENINGS REQUIRED FOR THE INSTALLATION OF STRUCTURAL,MECHANICAL, 1. IN EXISTING SPACES REPLACE WATER STAINED OR DAMAGED TILES AS NEEDED. TUNE UP GRID SYSTEM AS NEEDED. 9. LOW VOLTAGE IN SEALTITE CONDUIT FROM BELOW ROOF LINE DIRECT TO UNIT. DO NOT EXCEED BEND RADIUS FLOOR IS LESS THAN 23,000 SF ALLOWING FOR NON SEPERATED USE. EXISTING GLAZING ELECTRICAL AND PLUMBING WORK PRIOR TO FRAMING OR CUTTING FOR INSTALLATION. 2. REPAIR HOLES IN GRID FROM REMOVED WALLS. USE OF ARMSTRONG"BP ES-4"EXPANSION SLEEVE ACCEPTABLE. MANUFACTURERS GUIDELINE. 17. LEAVE THE PROJECT CLEAN AND READY FOR OCCUPANCY. 09 91 23 PAINTING 10. ECONOMIZER TO MEET CODE AND AS FOLLOWS: 18. CONTRACTOR TO CLEAN ADJACENT EXTERIOR AREA,I.E.WALKS,EXTERIOR GLASS,ETC. A. 6 TONS AND ABOVE MUST HAVE ECONOMIZER. • II 19. CONTRACTOR TO FILL ALL PAPER AND SOAP DISPENSERS IN RESTROOMS AND BREAK AREAS. INTERIOR: B. BAROMETRIC RELIEF ON 5-7112 TON UNITS. �‘...`� I/2" SILICON BUTT GLAZE 0 III R " 1. WALLS: C. 8 TONS AND ABOVE MUST HAVE POWER EXHAUST. 20. PROVIDE AS-BUILT"DRAWINGS!Jr THE WORK AT THE CONCLUSION OF CONSTRUCTION. AS-BUILT" D. 1 112 THRU 4-TON OSA INTAKE WITH DAMPER. -+ PL ATE GLASS • I DRAWINGS MAY BE IN THE FORM OF TWO COPIES OF CONSTRUCTION DOCUMENTS MARKED-UP WITH RED a. PRIME NEW DRYWALL WITH MILLER'S HIGH-BUILD"SUPER SEAL"PRIMER. PROJECT LOCATION ALUMINUM GLAZING CHANNEL FASTENED TO tuuramal a PEN.DELIVER RECORD DRAWINGS TO NE ARCHITECT. COMPLETE OPERATION AND MAINTENANCE MANUALS b. NEW AND EXISTING DRYWALL TO BE FINISHED TO ACHIEVE UNIFORM COVERAGE WITH MILLER'S 6200 OR 4480 WITH 11. ALL UNITS TO MEET OR EXCEED CURRENT ENERGY EFFICIENCY CODE REQUIREMENTS. J S.W. HAMPTON STREET RACO WITH SCREWS. PAINT TO MATCH METAL 0 SHALL BE PROVIDED FOR ALL MECHANICAL,ELECTRICAL AND PLUMBING EQUIPMENT.PACTRUST MAY HOLD A TIGHT ROLLER STIPPLE FINISH. RESTROOM FINISHES TO BE MILLER'S SIG LATEX ENAMEL. 12. DISTRIBUTION DUCTWORK: �!� �- •__I)CONTRACTOR'S FINAL PAYMENT UNTIL"AS-BUILT'DRAWINGS AND 0&M MANUALS HAVE BEEN RECEIVED AND N APPROVED. 2. DOORS AND FRAMES: A. SPIRAL ONLY IF EXPOSED. : limmlll a. NEW HOLLOW METAL-PRIME,SAND,AND FINISH WITH TWO COATS OF SEMI-GLOSS OIL. B. 26 GAUGE OR TO SMACNA STANDARDS IF PIPE IS CONCEALED ABOVE DROP OR HARD CEILING. ..-w.,� _ A a 21. IT IS THE INTENT OF THE CONTRACT DOCUMENTS THAT THE CONTRACTOR PROVIDES A COMPLETE, ' C. IN NON-CONDITIONED AND SEMI CONDITIONED SPACES, d Ir RACO TRACK CENTER ON WINDOW MULLION n b. EXISTING HOLLOW METAL-SAND,FILL IMPERFECTIONS WITH BONDO,SAND AND PRIME PATCHES WIN ALKYD 1 - - FUNCTIONING PROJECT INCLUDING ALL GENERAL,MECHANICAL AND ELECTRICAL CONSTRUCTION REQUIRED .R.,;; UP D. WRAP CONCEALED SUPPLY DUCTWORK WITH MINIMUM R4.2 INSULATION WITH FSK BARRIER. H - SECURED Y PRIMER,AND FINISH WITH SEMI-GLOSS OIL ENAMEL. W Ai"' E RED B GYP BOARD FM TO FULFILL THAT INTENT. ALL ITEMS REQUIRED SHALL BE FURNISHED AND INSTALLED,REGARDLESS OF E. HANGERS 12 GAUGE WIRE OR 18-GAUGE 1"WIDE STRAP. EXPOSED DUCT MUST HAVE ALL THREAD HANGERS AND ,1 - W �, I ■4%YF44�4 - - 1 WHETHER OR NOT SHOWN ON THE DRAWINGS. c. NEW WOOD-PRIME WITH ALKYD OIL UNDER-GOOIER,SAND,FILL ALL FASTENING HOLES WITH PAINTERS PUTTY, FULL DIAMETER STRAP UP TO 18"B. LARGER THAN 18"MUST HAVE SADDLE TYPE CLAMP. i 1 • '' CAULK ALL CRACKS IN CASINGS AND BETWEEN JAMBS AND WALLS USING DAP LATEX CAULK,AND FINISH WITH S/G I (L • 1`U 22. ITEMS OR WORK NOT TO BE FURNISHED OR ACCOMPLISHED BY CONTRACTOR ARE NOTED"N.I.0". OIL ENAMEL. F. BRANCH DUCTS SHALL BE PLUMB AND SQUARE(NO OCTOPUS). TES SHALL BE MAXIMUM OF 45 DEGREES. u - EXISTING WINDOW SILL G. EACH BRANCH DUCT TO HAVE BALANCE DAMPER IN Y BRANCH. -- I raiii (.5 3 23. "ALIGN"AS USED IN THESE DOCUMENTS,MEANS TO ALIGN THE FINISHED FACES OF ELEMENTS IN THE SAME d. EXISTING WOOD-PREP,REPAIR IMPERFECTIONS,PRIME AS REQUIRED,AND REPAINT WITH SEMI-GLOSS OIL H. ALL DISTRIBUTION DUCT WORK TO BE INSTALLED MIN.24"ABOVE DROP CEILING. P ' :o `• - \ 4 fir PLANE,E111-ER IMMEDIATELY ADJACENT TO ONE ANOTHER OR ACROSS AN OPENING. ENAMEL. IF FINISH IS NOT PAINTED,TOUCH UP STAIN,SEAL AS REQUIRED,AND RE VARNISH WITH SATIN VARNISH. :11' 14? • WALL STUD FLUSH WI TI-I WINDOW SILL 13. FLEX DUCT WILL BE NO LONGER THAN 6'FROM RIGID DUCT DOWN TO DIFFUSER_ + �. 24. DO NOT DISASSEMBLE SETS OF CONSTRUCTION DRAWINGS.DRAWINGS ARE INTERRELATED. 3. CEILINGS: i - SMOOTH FIN.GYP BD.OVER METAL STUDS RE{N RRELA _ \ \ CI la 14. DIFFUSERS: • r- D H Li 1 25. SUBMIT SAMPLES OR DRAW DOWNS FOR ALL FINISHES REQUESTED TO THE ARCHITECT OF RECORD WITHIN a EXISTING PLASTER-SAND,SPACKLE ALL IMPERFECTIONS,SPOT PRIME AND FINISH TO ACHIEVE UNIFORM ■ 1 44 1 TWO WEEKS OF PROJECT AWARD.PRODUCTS INSTALLED WITHOUT APPROVED SAMPLES ARE SUBJECT TO COVERAGE WITH MILLER'S 6200 OR 4480. A. SUSPENDED CEILING SYSTEM(T BAR)-PERFORATED FACE ADJUS''ABLE CURVED BLADES-DESIGN TITUS PCS SUPPLY I tr ��,,,,,,,,�„���� ,,,,,,,■ �. 11 REPLACEMENT AT CONTRACTOR COST. b. NEW PLASTER-PRRIME WITH SUPER SEAL AND FINISH TO ACHIEVE UNIFORM COVERAGE WITH MILLER'S 6200 OR AND TITUS PAR RETURN OR APPROVED EQUAL. /-' \ gitl 4 ;,�r��,,��,,,,,,,,, I (---,4- , D0 CLC)S AT �YIND®W (.. 01. 4480. B. GYP.BD.CEILING;SUPPLY-CURVED BLADE W/OBD DESIGN TITUS 250;RETURN-BAR TYPE-DESIGN TITUS 350; w w .Rww- 26. CONTRACTOR SHALL SUBMIT COMPLETE SHOP DRAWINGS FOR MILLWORK,SPECIAL SYSTEMS,MECHANICAL, EXHAUST-METAL OR ALUMINUM-1/2 x 1/2 EGG CRATE DESIGN TITUS 50F. �, 4. GENERAL NOTES: �.1 1 �. A-� SCALE 3" = �r_�rr I II ELECTRICAL AND PLUMBING SYSTEMS(INCLUDING FIRE PROTECTION SYSTEMS). SUBMIT A MINIMUM OF TWO C. ALL SUPPLY REGISTERS TO HAVE MANUAL VOLUME DAMPERS LOCATED IN DUCT AT/OR NEAR CLOSEST WYE BRANCH. I I► ...MI am SCALE -' _ 1 COPIES OF ALL SHOP DRAWINGS FOR REVIEW AND APPROVAL TO THE ARCHITECT OF RECORD.ARCHITECT I WILL RETAIN ONE COPY AND ONE COPY WILL BE RETURNED TO THE CONTRACTOR, a. KEEP ALL HARDWARE,BINGES,AND DOOR KNOBS CLEAN OF ALL PAINT SPLATTERS,DRIPS,OR ROLLER SPRAY. D. CLEAN OR REPLACE ALL SUPPLY AND RETURN AIR GRILLS AND 11-L1R HOUSINGS AT PROJECT COMPLETION. • r. 1 b. ALL SURFACES TO BE SANDED BETWEEN COATS,PRIOR TO INSTALLATION OF NEXT COAT. ' I 27. THE DESIGN OF FIRE PROTECTION SYSTEMS IS NE RESPONSIBILITY OF THE FIRE PROTECTION SYSTEMS C. DURING PROGRESS OF WORK,KEEP JOB SITE CLEAN OF ALL PAINT MATERIALS,RUBBISH,CANS,AND RAGS AT THE 15. THERMOSTAT: ALL EXISTING MERCURY TYPE THERMOSTATS TO BE REPLACED. NEW THERMOSTATS TO BE HONEYWELL _ I U +(� I ! CONTRACTOR. END OF EACH DAY. COMMERCIAL GRADE V13IQNPR0$000 TOUCH SCREEN MODEL TB82 2¢U1003 WHERE POSSIBLE APPROVED SUBSTITUTE: CONTRACT R.ALL FIRE PROTECTION SYSTEMS SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER 0 I I HEAD LICENSED BY THE APPROPRIATE JURISDICTION FOR THE DESIGN OF THIS TYPE OF SYSTEM. COORDINATE d. UPON COMPLETION OF WORK,CLEAN ANY PAINT SPLATTER BY USING PROPER METHODS OF WASHING AND TOTAL- IGNA • M ;�!� .�_'+1,0 AT, •�1_ N•. ' Td- << -7 DAY PROGRAMMABLE WITH LOCKOUT = 1 -ir-L-4 RACO E D - INTERFACE WITH EXISTING BUILDING SYSTEMS AND WITH ARCHITECT. ALL SPRINKLER HEADS SHALL BE SCRAPING,USING CARE NOT TO SCRATCH OR DAMAGE FINISHED SURFACES. FUNCTION-AUTO CHANGEOVER ONLY. MOUNT AT ADA HEIGHT(MAY REQUIRE CHANGING HEIGHT AT"REPLACEMENT I _ - o n • e. PROTECT WORK OF OTHER TRADES. LOCATIONS). CONTRACTOR SHALL PROGRAM THERMOSTATS AND BALANCE SYSTEM. I I�� �� W CENTERED IN CEILING TILE(OR 2 x 2 MODULE OF A SECOND LOOK II TYPE OF CEILING TILE WHERE APPLICABLE). LOCATION OF NOSE IN GYPSUM BOARD CEILINGS SHALL BE PRE APPROVED IN WRITING BY f. PROVIDE'WET PAINT'SIGNS AS REQUIRED TO PROTECT NEWLY PAINTED FINISHES. I I L I I I I 1 L=7,- 00 16. THERMOSTAT LOCATIONS TO BE REVIEWED BY ARCHIII_CT PRIOR TO INSTALLATION. _ _ I 0 I THE ARCHITECT PRIOR TO INSTALLATION. O OO DO SPECIALTIES 17. HVAC TESTING. 1 +l !I I I 11'4 28. THE CONTRACTOR SHALL COORDINATE ALL CONSTRUCTION SEQUENCING WITH PACTRUST AND SCHEDULE I " 6" I'I ALL SERVICE INTERRUPTIONS OUTSIDE NORMAL BUSINESS HOURS TO MINIMIZE INCONVENIENCE TO CURRENT 10 2813 BREAK COUNTER A. CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THATCONTROL DEVICES,COMPONENTS,EQUIPMENT 2.-0" U ITE KIT WHERE SPECIFIED TENANTS. SYSTEMS ARE CALIBRATED,ADJUSTED AND OPERATE IN ACCORDANCE WITH APPROVED PLANS AND SPECIFICATIONS. - _ 1. PAPER TOWEL DISPENSERS,SURFACE MOUNTED(KITCHEN/BREAK ROOM)BOBRICK B-262 B. SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO ENSURE THEY OPERATE IN ACCORDANCE WITH d GENERAL APPROVED PLANS AND SPECIFICATIONS. 10 4416 FIRE EXTINGUISHERS C. A COMPLETE COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL BE PREPARED AND FILED WITH 1. REMOVE ALL EXISTING VCT,SHEET VINYL,ETC.IN AREAS WHERE NEW FLOOR COVERING IS SPECIFIED PRIOR TO INSTALLATION OF NEW FLOORING. 1. FIRE EXTINGUISHER 2'10 BC (WALL MOUNTED OR IN SEMI RECESSED CABINET AS INDICATED ON PLAN) PACTRUST. Al LOCATION MAP i = 18. PROJECT CLOSE OUT DOCUMENTS REQUIRED: z z T I e 08 10 00 DOORS AND WINDOWS 12 00 00 FURNISHINGS A. AutoCAD FILE SHOWING AS-BUILT INFORMATION. -1 NOT TO SCALE O -° �^ _ --.--- 1. RE-USE EXISTING DOORS AND FRAMES WHERE POSSIBLE 1. CONTRACTOR TO CLEAN/REFURBISH EXISTING BUILDING STANDARD BLINDS AT ALL EXTERIOR GLASS. B. ELECTRONIC PDF FILE OF THE AutoCAD FILE ABOVE. U Vi 0 - Car) 2. DOOR AND RELITE FRAMES SHALL BE TIMELY II,OR APPROVED. SUBMITTAL REQUIRED PRIOR TO ORDERING 2. CONTRACTOR TO INSTALL BUILDING STANDARD ADDRESS AND/OR SUITE NUMBER LABELS TO ALL EXTERIOR DOORS. C. HARD COPY OF AutoCAD FILE ABOVE. 0 C'• 0 ADDITIONAL SWITCH D. OPERATIONS MANUALS FOR ALL EQUIPMENT,INCLUDING T STATES. w GANG LOCATION MATERIAL.NEW FRAMES TO BE FACTORY FINISH CUSTOM COLOR. 12 23 16 CABINET SPECIFICATIONS E. COLORED ZONE MAP WITH THERMOSTAT LOCATIONS INDICATED. t - 1 3. FIELD VERIFY EXISTING FRAME FINISH PRIOR TO ORDERING NEW FRAMES. ALL NEW FRAMES TO MATCH U �j" EXISTING 1. ALL CABINETRY TO BE INSTALLED OVER FINISH FLOOR AT ALL RESILIENT FLOORING LOCATIONS. 26 00 00 ELECTRICAL I - W EX NG BUILDING STANDARD FRAMES. u; O 2. AWI CUSTOM GRADE STANDARDS FOR CASEWORK AND COUNTER TOPS U.N.O. (DEFAULT TO IF NO OTHER STANDARD o © © o o ® o e a ,� •-- 0 Cn 4. ALL DOORS SHALL BE SOLID CORE WOOD UNLESS NOTED OTHERWISE. GIVEN.) GENERAL __� _ _ _ W & W 5. DOOR HARDWARE SHALL BE SCHLAGE AL SATURN OR D RHODES SERIES U.N.O. 1. ALL ELECTRICAL FEEDS TO OUTLET SWITCHES ETC.MUST BE VERTICAL DROPS FROM CEILINGS U.N.O. EXCEPTION OF I - - ,y, \Oz V ? U M 3. HIGH PRESSURE LAMINATE(P-LAM HPL)ALL EXTERIOR SURFACES,INCLUDING 4"TOE KICK. EDGE BANDING(MATCHING I I I I OC z i _i N n I L I O HORIZONTAL RUNS UNDER WINDOWS AND FIXTURES ON THE SAME STUD ACCEPTED. ELECTRICAL 6. ALL HARDWARE SHALL BE INSTALLED WITH A 5 BACKSET. PVC ACCEPTABLE),FIN ENDS,DOORS,AND LIGHT VALENCE ETC. UPPER CABINET BOTTOMS OPTIONAL HPL FINISH, d ELE TR L U to 11.1 ,`�-+ I I I I I w t- 7. DOOR FINISH SUBMITTAL:CONTRACTOR TO PROVIDE SHOP DRAWINGS F R MES HARDWARE STANDARD MELAMINE FINISH. OPEN CABINETS OPTIONAL HPL FINISH,STANDARD MELAMINE FINISH. 2. PROVIDE LABEL FOR EACH CIRCUIT PANEL FOR IDENTIFICATION PURPOSES. I OUTLET - p V i�i ,p FOR DOOR FRAMES, RDW I 1 0 Z AND DOORS AS WELL AS A CONTROL SAMPLE OF THE FINISHED DOOR SKIN W/STAIN AND FINISH APPLIED(IF 4. TOE KICK PLYWOOD 4"H WITH P-LAM COVER 3. ELECTRICAL CONTRACTOR TO PROVIDE LABELS AT EACH ELECTRICAL RECEPTACLE IDENTIFYING CORRESPONDING ® I - ft '-- "' Z NEW DOORS ARE BEING PROVIDED). BEFORE FINISHING OF DOORS IS COMMENCED ARCHITECT SHALL I I I I �I . \ . � W � „ _ BREAKER SWITCH AND PANEL. I I © - _ 5. DOORS AND DRAWER FRONTS PLASTIC LAMINATE OVER 11116 PARTICLE WITH MATCHING P-LAM OR PVC O _ ~ • H •APPROVE CONTROL SAMPLE. FINISHED PRODUCT IS SUBJECT TO REJECTION BY ARCHITECT IF THIS PROCESS - '(�I� � I I '°_ ' "" -� - I UNDERCUT POOR • • n = a f� 00 EDGES. 4. CONTRACTOR TO VERIFY ELECTRICAL METER AND TAG METER WITH THE TENANTS ADDRESS OR SUITE NUMBER. METER { � -_ IS NOT FULLY ADHERED TO AND FIELD PRODUCT DOES NOT MATCH THE APPROVED CONTROL SAMPLE. �diiu 1 �� u -1 - Zia cA 0 vO 6. MELAMINE LOW PRESSURE LAMINATE!LPL)ALL INTERIOR AREAS DRAWER PARTS SHELVING ETC. IDENTIFICATION NUMBER AND TENANT ADDRESS INFORMATION SHALL BE GIVEN TO PACTRUST PRIOR TO TENANTS MOVE- Ilil►s' ��° A. �l 9 FFLL OOR FINISH CL�A-' 6' O a+ 8. ALL INTERIOR GLAZING SHALL BE TEMPERED. ( ) IN. it i, f� (� , �I 9. DEAD BOLT LOCKS AT NEW EXTERIOR DOORS TO BE INSTALLED WITH A SCHLAGE MORTISE DOUBLE CYLINDER 7. FLUSH OVERLAY/FRAMELESS STYLE CONSTRUCTION. 5. ELECTRICAL CONTRACTOR TO PROVIDE EMERGENCY LIGHTING IN PATH SHOWN ON PLAN EQUAL TO 1-FOOT CANDLE. I Li I I 1 "C' � H 20-013C C KEYWAY;SOLI BRASS;WITH ADAMS-RITE CAM AND COMPRESSION RING 1 1/8"LENGTH WITH - I O 8. HINGES BLUM#75M3580,110 DEG.SELF CLOSING CLIP ON(OR EQUAL). " n u �,) p 6. EXIT LIGHTS I EXPBURWH E HI US WITH °' FORE T LIGH USE RUUD LIGHTING PLASTIC LED EXIT SIGN MODEL BURWH RED L TIERS WHITE HOUSING,HARDENED CYLINDER GUARD RING KEEDEX K-24. FINISH TO MATCH BUILDING STANDARD. 5 MOUNTING HEIGHTS 9. DRAWER SLIDES-BLUM #230M SERIES EXTENSION(OR EQUAL)75 LBS.MIN.FOR STANDARD DRAWERS. ACCURIDE BATTERY BACKUP, I i ,,.., 10. PATCH AND REPAIR ALL HOLES OR DAMAGE TO EXISTING STORE FRONT WINDOWS AND DOORS.TOUCH UP #4032(OR EQUAL)HD/FULL EXT 150 LBS.MIN.FOR HD AND FILE DRAWERS. I I I A-1 SCALE 1/2" = 1.'-0" FINISH FOR AS NEW LOOK. 11 7. WHERE NEEDED,CONTRACTOR TO FURNISH AND INSTALL NEW DRY TYPE TRANSFORMERS TO PROVIDE 208V/120V POWER a 10. PULL-96 MM C-TO-C WIRE PULLS. FINISH TO MATCH DOOR HARDWARE. FROM THE 480V/277V SYSTEM. SIZE TO BE BIDDER DESIGN. e"---'" 11. TOUCH UP ALL EXISTING INTERIOR DOORS AND FRAMES FOR AS NEW LOOK. _ ___ _■-._ - REVISION 11. GENERAL CONTRACTOR TO PROVIDE CABINET MAKER WITH SINK TEMPLATE(SPEC SHEETS)FOR EACH SINK. SINK a. TRANSFORMERS TO BE ENERGY STAR LABELED. - AREA OF WOE 12. TUNE UP EXISTING OVERHEAD DOORS AS NEEDED. CUTOUT WILL BE DONE IN SHOP WHEN FEASIBLE AND BEFORE BACK SPLASH IS INSTALLED IN ALL CASES TO ALLOW b. CASE TO BE TOTALLY ENCLOSED WITH LOUVERS TO PREVENT FOREIGN OBJECTS INTO THE INTERIOR. CUT OUT TO BE POSITIONED PROPERLY. ALL RAW EDGES OF CUT OUT AND BACK SPLASH TO BE SEALED. MINIMIZE c. ENCLOSED AND VENTILATED AIR COOLED TYPE,CLASS H INSULATION,DESIGNED FOR 115 DEGREES C TEMPERATURE 0 0 FINISHES ' ' 1 9 0 00 S S SINK . COUNTERTOP BUILD UPS AT FRONT BACK OF SINK CUT OUT TO ACCOMMODATE PLUMBERS S NK CLAMPS RISE ABOVE 40 DEGREES C AMBIENT TEMPERATURE AT FULL LOAD CONTINUOUS OPERATION. EQUIP WITH 2-1/2 CLEARANCE. PERCENTANFC TAPS AND FOUR 2-1/2 PERCENT BNFC TAPS. MAXIMUM SOUND LEVEL SHALL BE NEMA STANDARD 2 BUILDING PLAN 2. GENERAL, WITH ISOLATION DAMPERS BETWEEN THE CORE AND COIL ASSEMBLY AND CASE. Gz n - ; O I A w 12. KITCHEN/BREAK ROOM CABINETS-BASE CABINET WITH P-LAM TOP ON PLYWOOD DECKING AND 4 BACK SPLASH. ALL "_ ' A-1 SCALE 1 -50 w w 1. I CLEAN,SEAL AND WAX ALL RESILIENT FLOORS PER MANUFACTURERS SPECIFICATIONS. - 3. CABINETS TO HAVE DOORS AND DRAWERS U.N.O. UPPERS 17 D X 36 H,COUNTER AND COUNTERTOPS 26 D. 8. FOR FLOOR POWER AND DATA ACCESS IN BUILDINGS WITH ACCESS BELOW FLOOR USE WIREMOLD RC7 FLUSH POKE- •.•#:. . ��a••e■■•■•••■,�a�.��•• MICROWAVE SHELF 18"D WITH 3"RADIUS OUTSIDE CORNERS. P-LAM AT TOE/BASE. ALL SFELVES ADJ.HOLES AND THRU SERIES OR EQUAL. FOR SLAB ON GRADE INSTALLATIONS USE RACO#55111 2 AT EACH LOCATION TO SEPARATE ~1 Conditionally ved • ..•••,�•.•.•� 2. SUBMIT SAMPLES OR DRAW DOWNS FOR THE FOLLOWING: POSTS(1 AT BASE,2 AT UPPERS). POWER AND DATA. PIS 4• a. FLOOR COVERINGS AND BASE . 9. TELECOMMUNICATION SYSTEM BY FUTURE TENANT. �+�41�'�l►.;�•••�s ■■••:■•R +..` �o� t��6�ete�i��te . b. PLASTIC LAMINATES 21 00 00 FIRE SUPPRESSION 5" c A (INCLUDING DOORS CASEWORK) * I r !!_LL NATURAL WOOD(INCLUD NG D AND EWO K) 10. LIGHTING ENERGY MANAGEMENT IS REQUIRED IN OFFICE AREAS 5,000 SF AND LARGER. �`` �Lt�'��.�. w��.. � �d. PAINT COLORS 1. ADJUST EXISTING SPRINKLERS BELOW SUSPENDED CEILING PER CODE PER NEW WALL LAYOUT SPRINKLER HEADS ' fj- SHALL BE CENTERED IN 2 X 2 CEILING TILE.LAYOUT OF SPRINKLERS BY CONTRACTOR. SPRINKLER LAYOUT IN ALL 11. OCCUPANCY CONTROL DEVICES SHALL BE LEVITON OR WATT STOP. "' 5 =� 1 e. TILE,MARBLE,GRANITE,STONE,AND GROUT •T HARD CEILING AREAS(GYPSUM BOARD/PLASTER)TO BE REVIEWED AND APPROVED BY ARCHITECT PRIOR TO fly:.,,, �':. *, . K,,ti_ t,. _, 7• f. TOILET PARTITIONS 12. CONTRACTOR SHALL TEST ALL LIGHTING CONTROL SYSTEMS TO ENSURE THAT CONTROL DEVICES,COMPONENTS, g. HARDWARE INSTALLATION. EQUIPMENT AND SYSTEMS ARE CALIBRATED,ADJUSTED AND OPERATE IN ACCORDANCE WITH APPROVED PLANS AND 3. FINISH FLOORING TO BE INSTALLED UNDER ALL NEW CASEWORK. 22 00 00 PLUMBING ACCORDANCE SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO ENSURE TRAY OPERATE IN S. ACCORDANCE WITH APPROVED PLANS AND SPECIFICATIONS. DEFERRED ' 09 2100 GYPSUM BOARD i GENERAL REQUIREMENTS 13. WHEN REQUIRED IN DIVISION 15,PROVIDE MONITORING OF HVAC EQUIPMENT PER CODE. ��S f�, �� - , � - - ,: GENERAL 1. POINT OF DEMAND WATER HEATER-BOSCH POWER STREAM PRO-MODEL RPOP 277V/18A. RESTRICT FLOW TO 1GPM 14. CONTRACTOR TO REMOVE ALL UNUSED DATA A POWER BOXES AND INFILL WITH GYP BOARD. EXCEPTION-UNUSED DATA ,�I �' DRAWN BY' R R R WITH A SPOUT AERATOR. BOXES UNDER WINDOW SILLS TO REMAIN. ALL BLANK COVER PLATES TO BE BUILDING STANDARD FINISH. Mechanical ; ,� -�. ; IP_ ' Ron Tesc 1. ALL GYPSUM BOARD TO BE A MINIMUM OF 5/8 THICK VERTICALLY ATTACHED TO METAL STUDS 24 O.C.WIN 1 TYPE S-12 SCREWS 12"O.C.UNLESS OTHERWISE NOTED. - OFFICE LIGHTING Numbing .- PLUMBING BREAK ROOM FIXTURES st T DATE: 6/16/09 2. ALL OFFICE GYPSUM BOARD TO RECEIVE ONE TAPE COAT AND TWO FINISH COATS WITH SANDING BETWEEN _ !` arc rar FINISH COATS. APPLY USG SHEETROCK BRAND FIRST COAT. PAINT AS INDICATED. 1. REUSE EXISTING FIXTURES WHERE POSSIBLE. 1. RE TAMP EXISTING FLUORESCENT LIGHTS AS NEEDED. °1' g #Engineering r�� _ Rated Corridor PERMIT SET 3. ALL OTHER GYPSUM BOARD TO RECEIVE ONE TAPE COAT AND ONE FINISH COAT WITH SANDING AFTER FINISH 2• BREAK ROOM SINK ELKAY CR-2522 2. OFFICE LIGHT FIXTURES-LIIHONIA 2PM3N G B 3 3218LD MVOLTADVANCE OR EQUAL.(NO SYLVANIA BALLASTS) Dr�tvlt }; tCOd COAT. PAINTAS INDICATED. 3. KITCHEN FAUCET DELTA 100-WF Accessibility 4. ALL ONE HOUR RATED WALLS WHERE APPLICABLE): ONE LAYER 5/8" TYP E X GYPS UM WALLBOARD,RD EITHER AT 4. INSTANT HOT W ATER D IS PENSER IN-SINK-ERATOR MO DEL#11770-22 H 77 0-2 2 RIGHT ANGLES OR PARALLEL TO FRAMING ON EACH SIDE OF METAL STUDS SPACED AT24"O.C. FASTEN WITH w R w . 5. 114 COPPER WATER LINE W/SHUT OFF VALVE FOR COFFEE MAKER AND REFRIGERATOR,SEPARATE LINES IF OVER CAE AND O.C.TO TOP OM RUNNERS AND 1 TYPE S DRYWALL SCREWS 8 O.C.TO VERTICAL EDGES N 12 0 TO AND BOTT R 1 INTERMEDIATE STUDS. STAGGER ALL VERTICAL AND HORIZONTAL JOINTS 24"O.C.(OR ONE STUD SPACING), REQUIRED. EACH SIDE AND OPPOSITE SIDES. 1 5. IN FINISHED SPACES FURR-OUT BUILDING COLUMNS AND EXTERIOR WALLS WITH 5/8"GYPSUM BOARD OVER METAL STUDS. OFFICE COPY 6. PROVIDE ACOUSTIC GASKETS WHERE WALL INTERSECTS MULLIONS OR GLAZING. BUILDING DEPARTMENT USE i I I ��� �� e- ® ARTIN W. HANSON C� H _ 1E:) � ,. - �'9" - - - - �r 333" 333�� 163�� III �G'"`j` e _ 36 8 8 _ 2 LA MAS, OREGON L__________._ ) x • 1 . . • ZAD/J/\.SHEL ,._.,,,, ,,_\ 1,7> (-\,Ct , 1 1 , _ : 1 rr(ji 4 .0: • ® ; ,` �:, < PROJECT #09270 CONFERENCE u 1.,...,:),: �.--p., 1,-,„/, ■RECEPTION QQ rfll'�' - � I402I / I1 _ - MICRO SHELF AT 18" 401 ` I DEEP IUIrN 2..- _ -- I" RAD I OUS CORNERS �/ i k - ___,_- �_- .___ - - T OPEN BACK PROVIDE PAPER 74WEL + 8 I-:.} ,; , ( - F-2, I DISPENSER 13'-3" ,� ' I a C: I PEI a X 2 T ANSUM _`a _? 338" PL-2 33- 16-" 2.. 7t:s 1 J . WINOW CENTER 12—:_ ,I r oN LL ' z!, [: i, <� I` _ _ I ill Er = .` BACK SPLASH I, r- -► III 1 ICI Csd I I IL' "J--1-Z" _ a X s TR4N5llM I OFFICE - �--- — _ — 4 r UIINDOU!CENTER 1 �. ;• --_ `\ E = = # '� L/ flN i I 66 MICRO. ' ON WALL g i 406 �: 9 !- °_� ,S\' t >51 ELEGL La -- - . _-- -- - _ 45"RED. PANI=L • r + -21 / \ ADA SINK �\ 0 < ADSHELF>N O ‘11 S.,.1 -.1) 1 (At 10) -1- -- wi —lc, <® `� OPEN OFFICE i® a--e. —;�- ___; �, n ® e: — \ /'. > A BREAK a03 `!-'' ``! - y� '�° I Cr) • / NZ 404 tRC. I 1 C _ 44.1 I 405 --. , v- P-LAM BA5E I OPEN BASE 1 N t ALIGN ..:.:._..•�f®_.:.:•:$•:.:...:� ___ çJI , _ V — N ".ill) LJ - _><OrCE OFFICE 4 .OFFICE ,.-;�- f O E"4 to ‘ ><I _ `II-D 1,,...-' . `_ter � � ' 11! n - - CC) 'y V n u n 1yi a c u ›. Em. .0 a , in,PARTITION AND POWER PLAN Z OREFLECTED CEILING PLAN z •A-2 SCALE 1/8"= 1'-0" SCALE 1/8"=1'-0" lalawall O. . , 0 ii...1 Soo es. 5 a Emig° H lam DOOR SCHEDULE Z gel 1110 (.., 3 DOOR DATA FRAME DATA HARDWARE 4 A Fire Rating Remarks l'illmi Mark Door Size Thk Core Veneer Finish Hand Type Frame Depth Hardware Manufacturer Finish Function El -- 402 3'-0" x 9'-0" I 3/4" SC SAPELE CHERRY Right TIMELY II 4 -(/S" LEVER LATCH SCHLAGE 605 POLISHED BRASS ALIOS 3090 SIDELITE . Clii, na 406 31-0" x 9 0 1 3/4 SC SAPELE CHERRY Left 0 TIMELY II 4 1/8 LEVER LATCH SCHLACE 605 POLISHED BRASS ALIOS -- 401 3'-0" x 9'-0" 1 3/4" SC SAPELE CHERRY LeFt TIMELY II 4 1/8" LEVER LATCH SCHLAGE X005 POLISHED BRASS ALTOS 309@ SIDELITE q - 408 3'-0" x S'-0" 1 3/4" SC SAPELE CHERRY LeFt TIMELY II 4 1/8" LEVER LATCH 6CHLACE X005 POLISHED BRASS AL105 3090 SIDELITE Z_....001 409 3'-0" x 9'-0" 1 3/4" SC 5APELE CHERRY Right TIMELY II 4 1/8" LEVER LATCH 6CHLAGE 605 POLISHED BRA55 AL105 -- IS SCHEDULE WALLS LL RM NAME FLR BASE CEILING CL - REMARKS NORTH EAST SOUTH WEST HT. - i► _ " _- 40l RECEPTION E-LP E-4" RF PC�WE PCWB E-PC�WB E-PCzU1E3 E SAT 91-0" E---4 . 1....4 402 CONFERENCE E-LP E-4" RF E-PGWB PC�WB PGWB E-PGWB E-SAT 9'-0" -- 403 OPEN OFFICE E-LP E-4" RF Pate PC�WB PGWB PGWB E-5AT 9'-0" -- 404 SPEAK VGT/E-L cE-4" RF PGWE PGWB E-PGWB PGWE E-SAT 91-0" -- 405 CIRC- E-LP E-4" RF E-PC�WB E PC�WE E PC�WB E PC�WE E-5AT 91-0" -- C.,„,) , 40�o OFFICE E-LP E-4" RF E-WW-PGWB E-PCWB PGWB E-PGWP E-SAT 9'-0" -- 401 OFFICE E-LP E-4" RF E-WW-PGWB E-WW-PGWB E-PGWB E-PGWB E-54T 9'-0" -- W 0 408 OFFICE E LP E-4" RF E-PCaWB E WW PC�WB PC�WB PCzWB E SAT 91-0" -- 0 c+1 409 OFFICE E-LP E-4" RF Pate E-WW-PGWE3 E-PCWS PGWt3 E-SAT 9'-0" -- V �,, ›"' ' N � aC FINISH MATERIALS (SABLE)-(TAN) x g y I ALL FINISHES MUST BE SUBMITTED TO PACTRUST PRIOR TO INSTALLATION. H 0 00 „,,,„1 CARPET LOOP PILE: P4.' pl,„1 LP PATCRAFT 10129-NIGHT MOVES, 29703 LIONS TIGERS BEARS, DIRECT GLUE r� FOR PACTRUST PRICING&ORDERING INFO:IVY O'BRIEN 503-754-6826 I I VI ,4 CONTACT R PAC R � � � E.-4 VINYL COMPOSITION TILE c) CD 04 VCT ARMSTRONG STANDARD EXCELON 51811 ANTIQUE WHITE, 12"x 12"x 1/8” VI a4 (1 0 SHEET VINYL SV ARMSTRONG MEDINTECH,88439 DESERT GOLD, WELDED SEAMS REVISION CONTACT FOR PACTRUST PRICING&ORDERING INFO: MARK JONES 503-201-3657 BASE RF BURKE MERCER 4"FLAT RUBBER BASE,597 MOCHA AT ALL CARPET AREAS. CONSTRUCTION LEGEND 1 RC BURKE MERCER 4"COVE RUBBER BASE, 597 MOCHA AT ALL HARD SURFACES. I 1 EXISTING TO REMAIN 2. PAINT: PT-1 MILLER 4480 PREMIUM SATIN 8721W CLAY BEIGE, SATIN LATEX. c D EXISTING TO BE REMOVED 3. CONTACT FOR PACTRUST PRICING&ORDERING INFO:AMY TACKE 503-348-3307 MY NEW STANDARD WALL WITH INS. 4. LAMINATE: 5• PL-1 WILSONART 1530-60 BEIGE,AT ALL FACES PL-2 WILSONART 4669-60 NATURAL TIGRIS COUNTER, B.S.AND SELF-EDGE. DUPLEX RECEPTACLE ELECTRICAL PANEL CONTACT TECH SERVICES: 800-433-3222 FOURPLEX RECEPTACLE POWER'J BOX 6. CAB PULLS 605 POLISEHD BRASS 7. Dg) DEDICATED OUTLET FLUSH MOUNT FLOOR MONUMENT W/POWER AND DATA DOORS, HARDWARE AND FRAMES HARDWARE 605 POLISHED 8. �'� EXISTING ELECTRICAL REMAIN Fit FIRE EXTINGUISHER IN RECESSED CAB. • FRAMES PAC RED J1 FLOOR MONUMENT W/SERVICES SHOWN Es FIRE EXTINGUISHER-SURFACE MOUNTED DRAWN BY: 2S SPECIAL OUTLET Q THERMOSTAT Ron Tesch 1 TEUDATA MUD RING WITH PULL STRING - DATE: 6/16/09 2 X 4 FLUOR.FIXTURE EXHAUST FAN PERMIT SET ><- PARABOLIC LENSE TILE • SPRINKLER HEAD ' •"IIIJIJ" 2 X 4 FLUOR.FIXTURE Rum PARABOLIC LENSE/STEADY BURN BALLIST 0 EXIT SIGN(LED RED) 2 x 4 FLUOR.FIXTURE Its HORN/STROBE FIRE ALARM(WALL MOUNT) 0 FOUR LAMP T5 FIXTURE . 0 HORN/STROBE FIRE ALARM(CEILING MOUNT) LIGHT P. RECESSED COMPACT FLUORESCENT G T 0 SMOKE DETECTOR XSUPPLY DIFFUSER ARETURN DUCT