Specifications _ NAC EOL VOLTAGE CALCULATION FPS2o01- co070 CAPITOL ELECTRIC CO., INC. RECEIVED (503) 255-9488 Office 1 O,� 2009 (503) 255-1966 Fax A`�, Job Name: Lincoln Tower CM°FT1G�RD N Job Address: 10260 SW Greenberg Road Tigard, OR 97223 11_111500 Job Number: Conductor Wire Guage 14 Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/512009 Cable Length In Feet (source to end of line) 444 Total Circuit Current 1.308 Nominal System Voltage 20.4 Panel Description: Silent Knight 5495-7 Power Supply Minimum Device Voltage 16 Panel No.: NAC 8.1 Output No.: 1 Point To Point Method EOLv 18.67 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv 16.83 Circuit Within Limits ? YES Load Centering Method EOLv 18.62 • Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) 1 SUITE 830 E60-24MCC-FW(30) SPKR STB 30 Cd 0.105 33 20.13 2 SUITE 830 E60-24MCC-FW(30) SPKR STB 30 Cd 0.105 33 19.89 3 SUITE 830 E60-24MCC-FW(75) SPKR STB 75 Cd 0.189 42 19.61 4 SUITE 830 E60-24MCC-FW(30) SPKR STB 30 Cd 0.105 33 19.42 5 SUITE 830 E60-24MCC-FW(75) SPKR STB 75 Cd 0.189 45 19.20 6 SUITE 830 E60-24MCC-FW(30) SPKR STB 30 Cd 0.105 36 19.07 7 SUITE 830 E60-24MCC-FW(30) SPKR STB 30 Cd 0.105 31 18.97 8 SUITE 830 E60-24MCC-FW(15) SPKR STB 15 Cd 0.065 33 18.89 9 SUITE 830 E60-24MCC-FW(15) SPKR STB 15 Cd 0.065 43 18.80 10 SUITE 830 E60-24MCC-FW(30) SPKR STB 30 Cd 0.105 34 18.74 11 SUITE 830 E60-24MCC-FW(15) SPKR STB 15 Cd 0.065 48 18.69 12 SUITE 830 E60-24MCC-FW(30) SPKR STB 30 Cd 0.105 33 18.67 13 18.67 14 18.67 15 18.67 16 18.67 17 18.67 • 18 18.67 19 18.67 20 18.67 NAC 08.1 EOLv Calc OUTPUT 1 NAC EOL VOLTAGE CALCULATION CAPITOL ELECTRIC CO., INC. (503) 255-9488 Office (503) 255-1966 Fax Job Name: Lincoln Tower Job Address: 10260 SW Greenberg Road Tigard, OR 97223 Job Number: Conductor Wire Guage 14 Prepared By: Dan Wilson Ohms Per 1000 Ft @ 75 Deg C ( 167 Deg F ) 3.07 Date: 8/5/2009 Cable Length In Feet (source to end of line) 282 Total Circuit Current 1.117 Nominal System Voltage 20.4 Panel Description: Silent Knight 5495-7 Power Supply Minimum Device Voltage 16 Panel No.: NAC 8.1 Output No.: 2 Point To Point Method EOLv 19.19 Circuit Within Limits ? YES NAC Devices Mfg By: Wheelock End Of Line Method EOLv 18.47 Circuit Within Limits ? YES Load Centering Method EOLv 19.43 Circuit Within Limits ? YES Dev Device Location Device Model No. & Description Candella Alarm Distance From Voltage At No. Rating Current Previous Device Device ( Feet) 1 SUITE 830 E60-24MCC-FW(95) SPKR STB 95 Cd 0.249 64 19.96 2 SUITE 830 E60-24MCC-FW(15) SPKR STB 15 Cd 0.065 52 19.68 3 SUITE 830 E60-24MCCH-FW(115) SPKR STB 115 Cd 0.300 43 19.47 4 SUITE 830 E60-24MCC-FW(75) SPKR STB 75 Cd 0.189 52 19.31 5 SUITE 830 E60-24MCC-FW(15) SPKR STB 15 Cd 0.065 32 19.25 6 SUITE 830 E60-24MCC-FW(95) SPKR STB 95 Cd 0.249 39 19.19 7 19.19 8 19.19 9 19.19 10 19.19 11 19.19 12 19.19 13 19.19 14 19.19 15 19.19 16 19.19 17 19.19 18 19.19 19 19.19 20 19.19 NAC 08.1 EOLv Calc OUTPUT 2 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO., INC. • (503)255-9488 Office, (503)255-1966 Fax JOB NAME: Lincoln Tower ADDRESS: 10260 SW Greenberg Road Tigard,OR 97223 DATE: 8/5/09 PANEL DESCRIPTION: NAC 8.1 PREPARED BY: Dan Wilson DEVICE TOTAL DEVICE TOTAL STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT NAC EXTENDER Silent Knight 5495-7 NAC Panel 1 0.075 0.075 0.175 0.175 CIRCUIT#1 Suite 830 0.000 E60-24MCWH-FW 115 Cd SPKR STB,Ceiling 0.300 0.000 E60-24MCW-FW 95 Cd SPKR STB,Ceiling 0.249 0.000 E60-24MCW-FW 75 Cd SPKR STB,Ceiling 2 0.189 0.378 E60-24MCW-FW 30 Cd SPKR STB,Ceiling 7 0.105 0.735 E60-24MCW-FW 15 Cd SPKR STB,Ceiling 3 0.065 0.195 0.000 0.000 0.000 TOTAL 1.308 CIRCUIT#2 Suite 830 0.000 E60-24MCWH-FW 115 Cd SPKR STB,Ceiling 1 0.300 0.300 E60-24MCW-FW 95 Cd SPKR STB,Ceiling 2 0.249 0.498 E60-24MCW-FW 75 Cd SPKR STB,Ceiling 1 0.189 0.189 E60-24MCW-FW 30 Cd SPKR STB,Ceiling 0.105 0.000 E60-24MCW-FW 15 Cd SPKR STB,Ceiling 2 0.065 0.130 0.000 0.000 0.000 TOTAL 1.117 CIRCUIT#3 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 TOTAL 0.000 CIRCUIT#4 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 • TOTAL 0.000 NAC 08.1 Batt Calc Page 1 of 2 NAC EXTENDER BATTERY CALCULATIONS CAPITOL ELECTRIC CO•, INC. (503) 255-9488 Office, (503) 255-1966 Fax JOB NAME: Lincoln Tower ADDRESS: 10260 SW Greenberg Road Tigard,OR 97223 DATE: 8/5/09 PANEL DESCRIPTION: NAC 8.1 PREPARED BY: Dan Wilson DEVICE TOTAL DEVICE TOTAL 4 STANDBY STANDBY ALARM ALARM DEVICE QUANTITY CURRENT CURRENT CURRENT CURRENT AUXILIARY DEVICES 0.000 0.000 • 0.000 0.000 0.000 0.000 TOTAL 0.000 STANDBY TOTAL CURRENT: 0.075 STANDBY HOURS: 24 _ STANDBY AMP HOURS: 1.800 NAC DEVICE CURRENT 2.425 ALARM TOTAL CURRENT: [ 2.600 ALARM MINUTES: 5 ALARM AMP HOURS: 0.217 TOTAL CALCULATED AMP HOURS 2.017 APPLIED SAFETY FACTOR 1.15 MINIMUM AMP HOURS REQURED 2.319 SELECTED BATTERY SIZE II 2 EACH 12 VOLT, 7 AMP HOUR BATTERIES NAC 08.1 Batt Calc Page 2 of 2 • COOPER Notification Series E60 Speakers and Speaker Strobes Speaker Strobe Speaker Description Features The NEW Wheelock Series E60 Ceiling Speakers and Speaker • Approvals include: UL Standard 1971, UL Standard Strobes are designed for high efficiency sound output, with dual 1480, New York City(MEA),California State Fire Marshal voltage(25/70 VRMS)capability and field selectable taps from 1/8 (CSFM), Factory Mutual (FM) and Chicago (BFP) See to 2 watts. These E60 Multi-Candela ceiling appliances are part of approvals by model in Specifications and Ordering the new family of ceiling mount strobe appliances that will also be Information available on strobes, horns and horn/strobes. Optional Extender ADA/NFPA/ANSI compliant •(E60 Ext)is for mounting to 4"backboxes with no extension ring. • The Series E60 Speaker Strobe models incorporate the Low Current Complies with OSHA 29 Part 1910.165 draw Series RSS Strobes. These ceiling mount round models are • Ceiling mount strobe models are available with available in Wheelock patented MCC multi-candela ceiling strobe field selectable candela settings of 15/30/75/95cd or with field selectable intensities of 15/30/75/95cd or the high intensity 115/177cd (Multi-candela models) MCCH strobe with field selectable 115/177cd. • Strobes produce 1 flash per second over the regulated Series E60 Speakers and Speaker Strobes provide high audio voltage range output with clear audibility and are designed to meet the critical • 24 VDC with wide UL"Regulated Voltage" needs of the life safety industry for effective emergency voice communications, tone signaling and visible signaling to alert the using filtered DC or unfiltered VRMS input voltage hearing impaired. • Synchronize with Wheelock SM, DSM or Wheelock PS- The low profile design incorporates a speaker mounting plate for 24-8MC Power Supply with built-in sync protocol faster and easier installation.Each model has a built-in level adjust- • Field selectable taps for 25 or 70 VRMS operation from ment feature and snap-on cover with no visible mounting screws. 1/8 watt up to 2 watts The strobe portion of all Series E60 Speaker Strobes may be • High efficiency design for maximum output at minimum synchronized when used in conjunction with the Wheelock SM, wattage across a frequency range of 400 to 4000 HZ DSM Sync Modules or the Wheelock PS-24-8MC Power Supply with Patented Sync Protocol.Wheelock synchronized strobes offer • Fast installation with IN/OUT screw terminals using #12 an easy way to comply with ADA recommendations concerning to#18 AWG wires photosensitive epilepsy. • Optional Extender (E60 Ext) is for mounting to 4" Series E60 Speaker Strobes are UL Listed for indoor use under backboxes with no extension ring. Standard 1971 (Signaling Devices for the Hearing-Impaired) and Standard 1480(Speaker Appliances), and use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan® lens to provide maximum reliability for effective visual signaling. All inputs are supervised and employ IN/OUT wiring terminals for fast installation using#12 to#18 AWG wiring. Color options for the Series E60 Speakers and Speaker Strobes are red and white. MEA � APPROVED S5391 151-92-E NOTE:All CAUTIONS and WARNINGS are identified by the symbol 4A.All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING,SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE,AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their"Regulated Voltage Range". Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F(0°C to 49°C)and maximum humidity of 93%(±2%). • Series NH horns are listed under UL Standard 464 for audible signal appliances(Indoor use only). • "Regulated Voltage Range"is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology"Listed Voltage Range". Table 1: Average RMS Current E60 Strobe Current-Ceiling Mount E60 Speaker 24MCC 24MCCH Strobes 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.045 0.070 0.119 0.159 0.195 0.270 UL max* 0.065 0.105 0.189 0.249 0.300 0.420 Table 2: E60 UL Reverberant dBA @ 10 Feet** * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS • watts 1/8 1/4 1/2 1 2 current within the listed voltage range(16-33v for 24v E Speaker 77 79.5 82.5 85 88 units). For strobes the UL max current is usually at E Speaker Strobe 77 79.5 82.5 85 88 the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum •'dBA ratings are based on testing under UL Standard 1480. listed voltage(33v for 24v units). For unfiltered FWR ratings, see installation instructions. T FIRE SYSTEM ACCESSORY . Firepower 5495 •,•_, : , .. _ Distributed Power Module In an emergency, .- ` r you need maximum power. �sue` �-,�"�-,�: .} may , �. ,,' -Y.The Firepower 5495 Distributed Power Module by Silent Knight is the most- powerful and cost-effective power supply available today. It delivers 6 amps of .., notification appliance circuit power and built-in synchronization for appliances from System Sensore,Gentex®, Wheelock and Faraday—what you need to drive power-hungry components like ADA notification appliances. The 5495's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies. And,ADA retrofits are easier and less expensive with the 5495 because it integrates into current systems without the costly investment in new components. For the most sophisticated and cost-effective notification power supply available, you need Firepower 5495. Call Silent Knight today for more information at 1-800-446-6444. Firepower 5495 • Independent trouble relay resistors provided. Since the 5495 Distributed Power Module • AC loss delay option shuts off power draws very little power from the control, The firepower 5495 is a 6 amp to non-essential high-current it is possible to connect one Firepower notification power expander that accessories like magnetic door 5495 to each notification circuit on the provides its own AC power connection, holders control panel and still provide full • battery charging circuit, and backup • Built-in synchronization for supervision of the notification circuits all battery for use with fire and security appliances from System the way back to the control panel. controls such as the Silent Knight Sensore,Gentex®, Wheelock and Model 5208 Fire Control Faraday /Communicator.The 5495 is the cost- effective solution for powering Stand alone operation. notification appliances required by the • Lightweight design adds to ease of Americans with Disabilities Act(ADA). installation and reduces shipping The 5495 has built-in ANSI cadence costs pattern, which can upgrade older • Operates with most polarized, UL control panels that lack cadence Listed notification devices capability. • UL 864& 1481 listed Features • CSFM approved • UL Listed for 6 amps of notification " power • ANSI Cadence pattern output • Power supply's advanced switch capability built-in mode design reduces damaging Connection to Local Fire Control heat and manages power up to 50% Firepower 5495 may be connected to a " more efficiently than other systems local fire control which utilizes Class A • Dip switches allow for easy or Class B type notification circuits SFLGY reconfiguration operating between 9 and 32 VDC. The —� �HT r • 24 VDC filtered output voltage control panel's notification circuit is • Four power limited notification connected to one of the inputs on the outputs; 2 Class A or 4 Class B, or 1 5495.The control panel's notification Firepower 5495 • ClassA and 2 Class B circuit end-of-line resistor is also Distributed Power Module • Additional continuous auxiliary connected across two terminals on the Firepower 5495, which provides output supervision between the 5495 and the • 3 amps per output circuit fire control panel. Polarized audible SILENT • 2 inputs; 2 Class B or 2 Class A and/or visual notification devices are KNIGHT Liti • Ground fault detector/indicator then connected to the 5495 signal circuits using the 4.7k.2 end-of-line .v I +.,,' FIRE SYSTEM ACCESSORY • Firepower 5495 t Distributed Power Module '' Supervision Current: Input Firepower 5495 supervises a Standby 75 mA voltage range: 9 - 32 VDC variety of functions including: Alarm 175 mA Battery charging • Low AC power. Auxiliary capacity: 33.0 AH • Low battery condition. power circuit: 1 Ambient Temp.: 32° to 120° F • Earth ground fault. Notification 0° to 49° C • Auxiliary output power limit circuits: 4 Mechanical condition. Output Dimensions: 12.25" W x 16" H x • EOL supervision trouble or configuration: 2 Class A(Style Z) 3" D (30.88 cm W power limited condition at an 4 Class B (Style Y) x 40.64 cm H x output. (1 Class A& 7.62 D cm) When a trouble condition occurs, 2 Class B) Indicator Lights Firepower 5495 creates a trouble condition on the host control signal Amps per AC power on : Green circuits to which it is connected. output circuit: 3.0 (6.0 amps total) Battery trouble: Yellow Firepower 5495 still maintains the Notification Ground fault: Yellow ability to be activated by the host circuit output: 20.4 to 27.3 VDC amps each, Aux Trouble: Yellow 3.0 am control. In addition, the 5495 @ p - provides a Form C trouble relay 4.7 k52 EOL Output output as an alternative to using resistor required troubles (1-4): Yellow the notification circuit trouble. on each Class B Approvals: Electrical Specification circuit UL: 864 & 1481 AC Input: 120 VAC at 2 amps No. of inputs 2 NFPA: 72 Input CSFM Output: 24 VDC at 6 amps configuration: 2 Class B or 2 Class A Model 5495 Block Diagram Signal Circuit Output Signal 1 Signal 1 input Distributed Signal 2 Signal Circuit Output Signal 2 Power input Module 5495 Signal 3 (Optional) Signal 4 120 VAC Aux.Power Trouble Output Local Fire Control (Alternative to notification circuit trouble.) • tSILENT KNIGHT • • 7550 Meridian Circle, Maple Grove, MN 55369-4927 MADE IN AMERICA 800-446-6444 or in Minnesota 763-493-6435 FORM#350395, Rev. 04/02 FAX: 763-493-6475 World Wide Web: http://www.silentknight.com Copyright©2002 Silent Knight