Plans i flECwp0 MA 21 2014 STRUCTURAL CALCULATIONS m! , DP`!ginf FOR HOME INSTEAD 12194 SW SCHOLLS FERRY RD BEAVERTON, OR -- ROOF MECH UNIT REPLACEMENT -- CITY OF TIGARD REVIEWED FOR CODE COMPLIANCE Approve& t►>r--- ,����D PROFe oTCs [ 1 ' ; 12,1: 1 ,emit#+t il'tEZ: -D 1A--0 )244- .&e8. X21 hd � y ite O'EGON Date: ( -f v0 ''G(Y 1 5, '99 w ��� .., ii., ,, 4,4, E. NOCC)- I EXPIRES:12/31/14 t OFFICE COPY Contents Summary S1 • Details A-C D1 -D3 Gravity Calculations G1 Lateral Calculations L1 -L2 • Contact Person: John E Nordling,PE Enclosures El -E3 NORDLING Pro;. No.: 14-172 STRUCTURAL ROOF M CHTUNIITT ;� ENGINEERS, LLC OREGON HEATING&AIR CONDITIONING 6775 SW 111th.Suite 200•Beaverton OR,97008 Date:MAY 2014 By:JEN Sheet No.: COVER • ......SUMMARY ROOF TOP MECHANICAL UNIT SEISMIC REVIEW • 2010.Oregon.-Struc.t.ura.L.Specia Ity Code :• • . . Occupancy.Catagar..y..11 ..._ . • Site Class: - D Catagory .. . . ... . • Ss - 0.935 Si i 0.338 . . . Svs 2 0.102 Soi := 0.388 • ..... .... ... . There is. one.new.roar.mounted.:3.5.-Ton`replacement mechanical. unit. ..... .Carrier..3.5-.T.dn............. ... . .. .... .weight 420 Ibs..230.Ibs.adapter .curb. ... .. . length . 48' . ... .. .. ... ... . ... ..... .... width 4.4' • height 40' ..... • • • NORDLING Pro]. No.: 14-172 irk HOME INSTEAD .•. STRUCTURAL ROOF MECH UNIT ENGINEERS, LLC OREGON HEATING&AIR CONDITIONING 6775 SW 111th,Suite 200•Beaverton OR,97008 Date:MAY 2014 By:JEN Sheet No.: S1 I I I i I l l l l l l l l l l I I I I I I I I I I I I I I I I I I I I I I I I I I• I I I I I • • $_ CI I I 1 __ __ _II_I __ � __I II I I I I I I I I I I I I I I I I I I I I I I I I \5�Ic.,0 PROFe % 11 12,11 r.... •REGON /I ROOF FRAMING ELAN -0 ''''''- ,5•NORM ,\-.. I EXPIRES: 12/31/14 r 1 I 1 NORDLING Proj. No.: 14-172 HOME INSTEAD STRUCTURAL ROOF MECH UNIT ENGINEERS, LLC OREGON HEATING&AIR CONDITIONING 6775 SW 111th,Suite 200•Beaverton OR.97008 Date:MAY 2014 By:JEN Sheet No.: D1 ri n ri ri . Ij jI II 11 - II II II II (E) GL GIRDER � � I I _ _ _.t__ _ - 11 I I REPLACEMENT MECH UNIT I II B II II ' Ei I � (E) CURB TO REMAIN Ij 11 II II I , , I 3 ' ' O y (E) 20' TJL �J Li 1i 11 O 4x60 DIRECTLY UNDER CURB, WITH SIMPSON "U46" EACH END. B 4x6 DIRECTLY UNDER CURB, WITH SIMPSON "U46." EACH END. © 2x8 LEDGER W/ "10 x 4° WOOD SCREWS 612" o/c TO (E) TJL TOP CORD 4 (2) 8*I0 x 4" WOOD SCREWS TO 2x4 VERT AT TRUSS PANEL POINT. �t��p PROFF \ //o p. •,187 I . OREGON ' 0 ENLARGED ��4" INC FL � -4,y 0 � -o 7 5. � N \\ F NoRp- EXPIRES: 12/31/14 Pe I I , , -1 NORDLING Proj. No.: 14-172 HOME INSTEAD STRUCTURAL ROOF MECH UNIT ,;.‘ i—;;p 4..., ilio, i ENGINEERS, LLC OREGON HEATING&AIR CONDITIONING 6775 SW 111th,Suite 200•Beaverton OR,97008 Date:MAY 2014 By:JEN Sheet No.: D2 (4) "111 -PRC-HOLD' 16 Ga GALVANIZED STEEL BRACKET W/ (4) $10 x 1/2' TEK SCREWS TO CURB (BY OTHERS) d (4) *10 x 1%' TEK SCREWS TO UNIT BASE RAIL 140 rrIECHANICAL UNIT UNIT BASE RAIL (4) *10 SCREWS sn (4) "10 SCREW - I STEEL BRACKET 71 r-' i ADAPTER CURB \ . *12 SCREWS fD12' o/c---' . ALL SIDES –(E) CURB I SIMPSON 'L50' ' ---- -- ------ ------- ----------------- �— -- —1 . H----------- ---.‘ ili, -T: r n. c L _ '-------------------- ---- _\ _ \ s ' VERT '// I— - _( ) 20' TJL 5��,0 PRace (E) PANEL POINT—'1J I �\ t 187E r p I A OR GON 0 ET4IL 15. ,9a"' C oyN E. NORM\\ [ EXPIRES: 12/31/14 _- NORDLING Pro;. No.: 14-172 HOME INSTEAD ,A STRUCTURAL ROOF MECH UNIT 0, k� ENGINEERS, LLC OREGON HEATING&AIR CONDITIONING 6775 SW 111th.Suite 200•Beaverton OR,97006 Date: MAY 2014 By:JEN Sheet No.: D3 • I I I I I I I I I I I I ft=FHTHHH* " :— • REPLACEMENT UNIT t 0 ADAPTER CURB = 650 lbs I I (E) 2x CURB - 100 lbs N • I I I I I I I I I I I I I I I I I CE) 20' TJL 032" o/c Pr 125 'bs 150 lbs / (3 joists 2 sides) 125 lbs IP d b v 29'-m' Span 29.0 ft The replacement unit, new adapter Spacing 32" curb, and (E) roof curb add an equivalent 1.8 psf to the roof truss. _ok- #purlins 1 M 492 ft-lbs W plf 4.7 plf W psf 1.8 psf NORDLING Proj. No.: 14-172 HOME INSTEAD STRUCTURAL ROOF MECH UNIT 1•• ENGINEERS, LLC OREGON HEATING&AIR CONDITIONING 6775 SW 111th,Suite 200•Beaverton OR,97008 Date:MAY 2014 By:JEN Sheet No.: GI USGS Earthquake Hazards Program 2005 ASCE 7 Standard Location 45°26'33.99"N Ss and S1=Mapped Spectral Acceleration Values 122°48'3.31"W 12194 SW Scholls Ferry Rd,Beaverton,OR 97008 Ground Motion Ss 0.935 Si 0.338 Occupancy Category II Site Coefficients Fa 1.13 Site Class D Fv 1.72 Importance Factor 1.00 Height of Structure 20.0 ft SMS Fa* Ss 1.053 SMI F„ * Si 0.583 Design Category(SDC) D SDS (2/3)SMS 0.702 SDI (2/3)SMI 0.388 Air Side HVAC Eq= 0.278W+ 0.2 SDS W aI, 2.50 Rp 6.00 W :Weight of Unit Fp= 0.4 apR Sns •I n (1+2. z I Wn n I z= 20.Oft ASD FP= 0.35 WP->* 0.7 0.246 z= 24.0 ft FP= 0.40 WP->* 0.7 0.278 FP MIN= 0.3 SDS IP WP = 0.211 WP->* 0.7 0.147 FP MAX= 1.6 SDS IP WP = 1.12 WP->* 0.7 0.786 NORDLING Proj. No.: 14-172 4 I‘ HOME INSTEAD STRUCTURAL ROOF MECH UNIT ENGINEERS, LLC OREGON HEATING&AIR CONDITIONING 6775 SW 111th,Suite 200•Beaverton OR,97008 Date: MAY 2014 By: JEN Sheet No.: L1 EQ 91 1 bar W: 650 lbs Height 40" Weight 650 lbs 'A\ Length 48" Width 44" • Curb 28" VEQ VEQ= 0.278* 650 lbs+0.2* 0.702* 650 lbs 181 lbs � = 181 lbs+91 lbs T= 181 lbs * (28"+40"/2)/44" T: 48 lbs + 91 lbs/2 - 0.6* 650 lbs/2 = 48 lbs Net Uplift V= 181 1bs (4) 'MN-PRC-HOLD' 16 Ga GALvANIZED STEEL BRACKET W/ (4) "10 x 1/2' TEK SCREWS TO ROOF CURB d (4) "Im x 1/2' TEK SCREWS TO UNIT BASE RAIL -ok- *12 612' o/c SCREWS TO EXISTING CURB BELOW -ok- NORDLING Proj. No.: 14-172 , 5( STRUCTURAL ROOF HOME MECH INSTEAD UNIT ENGINEERS, LLC OREGON HEATING&AIR CONDITIONING 6775 SW 111th,Suite 200•Beaverton OR,97008 Date: MAY 2014 By: JEN Sheet No.: L2 Certified Drawing for rtu-1 Project: -Untitled26 05/02/2014 Prepared By: 12:34PM UNITED P.O.101 41H TNII SO E INI If INE MAMA 6.1101 1101[01141[011411101011 .....,.,,c........ rECHOOIES 11NANN,NI AS 1rKWRT WON I I nd 101p 11171 5N[U[N 013 X Xg46OPY PN01.MK of CARRIER '1311 c0 SAT10x'1 1ILX COMM. i J-1 SI I6 IJ•15f 1i UNIT ELECTRICAL UNIT WI. UNIT HEIGHT 1N/MM CENTER OF GRAVITY IN/MM 1.15// 1354.01 15/1 CHARACTERISTICS LB KG 'A• S 1 2 18(5I-/X11421060/090113/510 208/230-1, 206/230.3.60 411 156.5 41-3/4 1137 22-13/16 511.4 18 451.2 11-1/6-435.0 7-1116-�' 17-9716 18E51-/41V421010/090110 460.3.60 425 612.1 44-3/4 1137 22.13/16 519.4 16 457.2 17-1/8 435.0 187.31 1311.51 ISESI-/N1A/81010/115/130113/510 208/270-1, 208/230-3-60 411 190.2 46-3/4 1187 22-13/16 511.4 18 457.1 17-3/8 441.7 18051-/NIA461090/11S/110160 460-3-60 433 196.S 46.3/1 1187 02-13/16 579.4 18 451.1 17-3/8 441.3 48ES1-/NDA601090/1151130113/5)0 208/230-1, 2081230-3-10 441 200.1 46-3/4 1161 22.13/16 571.4 18 457.2 17-518 447.7 2-11/16-7 1(1011 SUPPLY © 48051-/R)16010901115/130160 160•3•60 455 206.5 46-7f4 1101 22.17111 511.1 10 151,2 /1.513_111.7 171.41 --=-,=--------,c.,..111.. I ,� -- - URIT5 VOLTAGE CORNER WEIGIM L8/KG i OPTIONAL MI OPTIONA 48E5/-fN1A421060/010113/510 208 1170 fl.l 28.8 62.2 71.3 123.1 56.0 143.9 65.3 IS-15116 RETURN -�, SUPPLY 48ESI-1IIA4210f0/090160 460 61.1 18.0 62.2 31.3 112.4 60.1 140.9 61.6 1104.81 AIA ./ ik AIR 40(Sl-/M)A181090/115/1101111510 208/230 62.1 28.6 63.8 38.1 125.1 57.1 116.7 66.6 OPENING / ,; PFXING ISESI-/NIAIR1090/115/130140 460 62.9 21.4 61.6 38.1 134.6 11.2 151.1 60.1 S: 1 % 18051-IX IA6010901115/1J011)1510 208/230 66.2 70.6 06.2 10.1 132./60.1 154.4 70.1 %/� ^ �\� '�,. �=-aQ�• 16051-IN IA6010f01115f 1301{0 460 64.2 30.0 66.2 40.1 111.4 11.2 159.4 72.1 II(H!!!I fl(�i iii-aA11111111 l \��=!//'li 11711 RIMMED CLEARANCES TO WMIU67HE WTL I``11`111\\`` ''/� NOTE: ALL TABLE DATA ECONOMIZER FOR ALL FACTORY INSTALLED INCIT14 1351 II \`\\\\\\��`\\" �/ry7 OPTIONS CICCPI[60NON1IER DUCT OF UNIT 14 250.02 OUTDOOR COIL \� ` SIDE OPPC or UNIT 2 150.81 l' ii.1.01 E =�\�_ , BUTT OPPOSITE DUCTS 16 13551!1 7` ``�i TIlE PANEL OF UNIT 0 10.01 BOTTOM PAMFL li 1114.11 1 -. ; _ 'I IRS.MOWED �° 11111[5 IMN1 •1• !9�\ �I I��,� BETWEEN UNITS.POWER ENTRY SIDE 42 11066.81 �� iT= UNIT AND UNGROUNDED SIlENCCS,POWER ENTRY SIDE 36 1111.01 -6-13/16 UNIT AND BLOC'OR CONCRETE WALLS AND DINER 4 = © 1173.61 GROUNDED SURFACES,POWER ENTRY SIDE 11061.81 CLEARANCE FON�Alpl AM=NCNB 42 INCHES INN' INDOOR COIL TOP VIEW 10001 COIL EYAP.COIL ACCESS SIDE 36 1111.01 POWER ENTRY SIDE 42 11016.61 'EXCEPT f0R NEC R04116(MCNTSI UNIT TOP 48 11211.21 SIDE OPPOSITE DUCTS 36 1914.01 DUCT PANEL 12 1304.81• 42-15/16 •MIIINUN DISTANCES:IF UNIT IS PLACED LESS THAN 12 1301.81 TOOM WALL 11090.61 2 I IT 1 ...-4.1/2 STSTEM,THEN SYSTEM PERFORMANCE XATDE CONPRCOISED. 150.81 11193.81 1 1114.31 DIMENSIONS IN II ARE IN NM • 'I<'. .. . N r IiiimIIIIIuIIIIIiI 1-1/71•I23.61 ou. f.o. 1liiiHiiiioiiiHICI -�- • POWER ENTRY '1"11'1"1 J IIIIIII"IIIII . 718.122.21 DIA. x010 1I'I"' ------P •A• CONTROL EIDLE •® 1-i/0 1 1123.01 ■. ,1. .y SUPPLY ILJ! 15.17/8\--- DUCT RETURN ] I 21-7 I/8 III 1/07.11 OPEYIMC DUCT 1555.61 I IT I OPENING • 1.11/16 16.1/4 11.5!6 11 1 ill • 117.71 13611.31 •Z I1/7.111[)06 S ,, 1 • �� •O I '-/ ' aI r•O O � 1 0, f ■f:� _ i I O' 116631 !OO I I I I eel • DRAIN OUTLET 12-15/16 1-13/16 314.119.11 x.P.T. 1318.11 COMPRESSOR •!• LOWER LCCIRICAL 146.01 1/2'111.11N.P.T. 311::).i IRf ,F 7 T/6'E22.210CEP PANEL PANEL ACCESS PANEL 1.1116 GAS ENTRY 14.81 3-7/16 14-I/0 - 18-7/li 152.41 187.)1 .«1]-1/0+•.-13-5/0--+-^-13-118 1752.11 11 46.11 1752.11 11122.41 11225.51 5-1/16 1141.31 RIGHT SIDE VIEW REAR VIEW LEFT SIDE VIEW FRONT VIEW DATE WAKENS NIT 07/24/09 SINGLE ZONE ELECTRIC COOLING WITH GAS REHEAT (LG) 48E5500215 3.0 Packaged Rooftop Builder 1.39g Page 5 of 10 Performance Summary For rtu-1 Project: -Untitled26 0503/2014 Prepared By: 12:34PM Part Number:48ES-A420903 ARI SEER. 13.20 Base Unit Dimensions Unit Length* ----_----' 48.2 in UnitV@dbh. 44.1 in Unit Height 39.9 in Total Operating 420 lb Unit Unit Voltage—Phase—Hertz' 230-1-60 Air Discha o* Vertical Fan Drive Type. Direct Actual Airflow 1403 CFM Site Altitude* 0 ft Cooling Performance Condenser Entering Air DB• 95.0 F Evaporator EntehngAir DB.-'-----__----------'-_--'--_-_ ---_-�----'-__ 8V.V F Evaporator Entering Air VVB' --__---_—__'__-'__-----'_---_-------'_-'- 67.0 F Entering Air Enthalpy ___-'----_--_.—___---____'--_-___' — 31.44 BTU/|b Evaporator Leaving Air DB. _'----__---'-'---_'_-'-_,--------'__'-'---_-59 9 F Evaporator Leaving Air VV8• 58.0 F • EvapoxytnrLeovingAirEntho|py------- -_---_--'_---'-'__--_'---- 25.02 BTU/lb Net Cooli Capacity* ---- _ 40.51 MBH Net Sensible Capacity. 30.53 MBH Total Unit Power Input* 3.62 kW Coi|BypaoaFaotoc 0.040 Heating Performance Heating Airflow' 1403 CFM Entering Air Temp: 70.0 F Leaving Air Temp: -'—_.- 118.2 F Gas Input Capac �V.� MBH d��_---------_—_'----- ___.__-----_----'--' _—__.—. Gas Heating Capacity* ----'_-' ----. ----_ 73 00 MBH Temperature Rise. ----_-'___—_— -_-- -----_'--'-__'_-_'____--_--. 48.2 F Supply Fan External Static Pressure ---- --'-- _-__-- 0.50 in wg Options I Accessories Static Pressure Wet Coil* 0.07 inwg Total External Static. 0.57 in wg FanRPM• '---'--'--_--''----'_--_-_------'-----_- ' _-__-''_—._1075 Fan Power --'---- --'----_-- - 0 3 BHP Fan Motor Size, hp:--___--'---' • - 3/4 NOTE - Medium Motor Speed,Vert Electrical Data Minimum Voltage. —_-_--- -'—__---' _--__---.'_'_—.------- 187 Maximum Vo|toge:-'----_''�--_-,_----'—'__-_-'-_—_--_--'---'------'-'____ 253 • CompeaoorRLA. _ --'- 17.9 CompneaoorLRA*----'--._--_----'--'--'---- ---.--'-- -'-----_-'-----'112 Outdoor Fan FLA -'1.2 Indoor Fan Motor F 6 Power Supply MCA' 29.6 Power Supply MOCP(Fuse orHACR)* _----_—_-_--_--'--'--_---.--_-_—'------__--40 Control Panel SCCR:5kA RMS at Rated Symmetrical Voltage Acoustics Packaged Rooftop Builder 1.39g Page 6 of 10 ROOFCURB ADAPTER PART NUMBER: CA-CAR-SDCL-BRY-011 SUBMITTED TO: . SUBMITTAL NEW UNIT: COMPANY: M Aos MicroMetl EXISTING UNIT: PROJECT NAME: QUOTE NUMBER: DATE: 06/25/2010 ■ r 46.06 59.13 i O.D. O.D. r L 42.19 O.D I 1 / \ f IMPORTANT: THE CURB ADAPTER 18.00 SHOWN WAS AUTOMATICALLY GENERATED. THE ACTUAL CURB HEIGHT AND DESIGN COULD BE ALTERED FROM THIS SUBMITTAL TO -- PROVIDE THE MOST EFFICIENT 72 pp O p CURB ADAPTER POSSIBLE. SHEET 2 OF 2 THIS DOCUMENT IS THE PROPERTY OF MICROMETL CORPORATION AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE CONTENTS WILL NOT BE DISCLOSED OR USED WITHOUT MICROMETL'S WRITTEN CONSENT. MICROMETL CORP. • 3035 N.SHADELAND AVENUE,SUITE 30D • INDIANAPOLIS,IN 46226 • 1-800-662-4822 ••• MICROMETL SPARKS • 202 SOUTH 18th ST. • SPARKS,NV 89431 • 1-800-884-4662 Oregon Heating' & Air Conditioning RECBiq D Scope of Work-Greenway Center Bldg C,12180-12196(12188)Sw Scholls Ferry Rd,Tigard,Or MAC( L+ 1 7-u Oregon Heating and Air Conditioning will perform the following scope of work: ,- t p 1. RTU8-Provide and install new rooftop HVAC 3.5 ton unit on existing curb with transition.Includes economizerC '(Or' 1n� 2. Provide economizers for RTU4,9,10. UII.D n11.11 014 3. Demo RTU5. I�`? , 4. Ducting and air-distribution mods on RTU9 as drawn. 5. Gas modification RTU10. Equipment Schedule- RTU8-Carrier 48ES0A420603,230-1-60,29.6 MCA,40 MOCP. 13.2 Seer,40.51 Btu cooling,80%AFUE,60 Mbtu gas input.420#plus 225#curb adapter.Reset OSA requirements. RTU9-Carrier 48TFE006-501 GA.Existng 5-ton,relocate smoke detector as required.Reset OSA requirements. RTU4-Rheem#RKNL-A06OCK13E.Provide economizer. RTU10-York#D1 NA024N03606C.Provide economizer. Ventilation Requirements- based on 2010 OMSC table 403.3 RTU8-single zone office 1000 sft breathable zone Persons-5 cfm X 5p/1000sft=25 cfm Area-0.06 cfm/sft=60 cfm Vbz=85 cfm Ez=0.8(supply and return in ceiling) Voz=107 cfm SA= 1400 cfm RA=1280 cfm OSA= 120 cfm RTU9-single zone retail 1800 sft breathable zone Persons-7.5 cfm X 15p11000sft/2 = 102 cfm Area-.12 cfm/sft=216 cfm Vbz=318 cfm Ez=0.8(supply and return in ceiling) Voz=397 cfm SA=2000cfm RA=1600 cfm OSA=400 cfm Mechanical General Notes: 1. Cooling equipment does not exceed the load of the calculated requirement. 2. All steel ducting will be 26 ga minimum galvanized. 3. Heating and cooling ducting to be designed to not exceed 0.5 wc positive(supply)and 0.5 wc negative(return). 4. Provide programmable thermostat.5 degree deadband minimum.7 day. Microprocessor.Set program for night energy savings. 5. Seal ducting with UL listed mastic or mastic tape. 6. Max leakage rate of OSA or exhaust dampers to be 4 cfm/sft @ 1.0 sp. 7. Insulate all supply and return duct. 8. Support duct every 8' max or within 2'of direction change with minimum 24ga strap or 12ga wire. 9. Provide 0 and M to building owner. M0 . 0 Page 1 of 2 Oregon Heating & A/C, Inc. Oregon Hating �. PHONE NUMBERS MAILING ADDRESS OPERATIONS CONTRACTOR LICENSE an' c°� °°in0-iti - ~ 503-691-9699 PO Box 241 19300 SW 118th Ave Oregon CCB 172126 1-800-Furnace 503-691-8556(Fax) Dundee,OR 97115 Tualatin,OR 97062 Washington OREGOHC900BN A" www.oregonheating.corn Oregon Heating- . St Air Conditioning Greenway bldg.C,12188 SW Scholls Ferry Rd,Tigard,Or GAS- Per OMSC-Tabel C40214(2) Standard pressure @ 0.5 Psi pressure drop Load- RTU10 @ 36,000 Btu RTU8 @ 60,000 Btu Total = 96,000 Btu 100' developed length 1" pipe adequate for 195,000 Btu 3/4" pipe adequate for 104,000 Btu MO.2 Page 2 of 2 Oregon Heating &A/C, Inc. Oregon Heating Ilk PHONE NUMBERS MAILING ADDRESS OPERATIONS CONTRACTOR LICENSE ' ati.c0 ,n 503-691-9699 PO Box 241 19300 SW 118t Ave Oregon CCB 172126 1-800-Furnace _ 503-691-8556(Fax) Dundee,OR 97115 Tualatin,OR 97062 Washington OREGOHC900BN www.oregonheating.corn . --11 . , I — - - - - - - - - - - - - - - -n- - - - - - - - - - - - -{r- - - - - - -1]- - - - - - - - - . kg-100g) . 1 2M4 (1---, CL----J -- op 2 1 ==.----Li nr150) cRIJ ,,,i‘slot N x 1 ....„ ,,---j ' L_.7 , I 8‘31045)c. I -... ....., i 1 i / I 1 I: - add eemv ..„... ,-E -° rat/C, 601(24 El 15 k ri a 1 F// x 0 1 A i...., - GAME HAVEN t'\ ,1-4 =I v LI , 3 , , ...),, i (ft.-1 1 Ilib,114— ,L it_ L. 1 ) ''-• .,D n ;ri w L. .• ___7. _11.___.. .11____ .1 1-- • . _ . II 1 .' L. bi 0 "'4Z.•• LIN I 1 I ' t r z ,----,---r----.— c.=-....-:, 1 -----, 07, .. :1__________. .,. >4121 • • X i ( . '—' 0 ' . —._ I, : ---, . ..- o ) ":—.LL • '— .__. :.., . ri z ........ c„,, , ,, _..,,,,,,,„I or4 lie,- -kell4 le w/A-4,4A-1 Z- X /-EN_ z il c. i 40' - Noir :.i iiIIIiiitl.STEAD Ct o N -.,,... r r==i SHEET TITLE T .. ....:.:____( ::!__ . • , 0 L rt____ Q.‘ --z•--- -eiet.,0 =1 i -1- r .Qt • J-- X .S" I exProP 1 FKF (see e2_.) I/ • 011 ...0. ,-I — reff46 .--r- --.) . o=_._...........vj , . 17)-----1......... ..------,..--- ------11 ..... c . [a. 12 L _D L 0 RTU OVERLAY//Coo/4 ptif/J/Fiffp4e, RAW SHEET NUMBER Ai1 Scate:1/16"= l'-0" M 1 a 0 N team —t T . ,,x,,144) 1 A ?dh .) . / r 2-1 ,r// ItC J T --f - / ! 481 Mru L Q N , n1.Ya ' ,a-1 mr [\\ _ _ ._-1 i ] 1 I I i 1 .. . .. _ i.---1 -r- ,i 11 ...._ i.. _ J I . r '. i 1 _ IV 7., --_ - _ j 1 11-wN 1 -I 1 N A Unit Report For rtu-1 Project: —Untitled26 05/02/2014 Prepared By: 12:34PM Unit Parameters Dimensions(ft. in.)&Weight(lb.)*** Unit Model. 48ES-A420903 Unit Length. 4'0.1875" Unit Size. 42(3.5 Tons) Unit Width: 3'8.125" Volts-Phase-Hertz 230-1-60 Unit Height. 3'3.9375" Heating Type. Gas "' Weights and Dimensions are approximate.Weight does not include roof Duct Cfg• Vertical Supply/Vertical Return curbs,unit packaging,field installed accessories or factory 90 000 Btuh installed options. Approximate dimensions are provided primarily for shipping purposes.For exact dimensions and weights,refer to appropriate Standard Unit_ product data catalog. Total Operating Weight. 420 lb Warranty Information 1 year warranty on parts 5 year warranty on compressor 5 year warranty on heat exchanger No optional warranties were selected. NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods. Ordering Information Part Number Description Quantity 48ES-A420903 Rooftop Unit 1 Base Unit Accessories CPMANDPR008A00 Manual Outside Air Damper 1 Packaged Rooftop Builder 1.39g Page 4 of 10 . . • , . Certified Drawing for rtu-1 Project: -Untitled26 05/02/2014 Prepared By: 12:34PM 6 WIPED P.O.441 MN 1114 1ONW11 IS TIE P101(111 Of 10101(1 CONP10AI/l�I 0.....11 01 0141144$a/000011$ CARRIER 1U21 MAAME,NI CW/100114t101YNEA1�[Y�naf[Il1Ta(OZNI1IZZAMIP IDES 447AK[11400 Ni 001gM l 44 13-15!16 13-IS/ti UNIT ELECTRICAL UNII IT. UNIT KIM 111/101 CEITER OF GRAVITY MIL [351.07 (351,0] CHARACTERISTICS LB KG 'A• I 1 4EE51-/411,421069/000/13/5/0 200/233-1. 208/230-3-8D 411 186.5 44-3/4 1137 22-13/16 579.4 18 457.2 11-1/B 435.0 3.1116 13-9/10 48E01-/4/6421040/090160 460-3.60 425 192.9 44-3/4 1137 2213/18 570.4 18 457.2 11.1/4 435.0 187.31 3344.51 40E5/-14I3491099/115/130l13/510 204/230-1. 208/230-3-60 419_190.2 44.3/4 1187 22-13/16 575 4 18 457.2 11-3/8 441.3 48E01-/414481090/115/130160 480-3-60 433 196.5 41-3/4 1107 2213/16 515.4 18 451.2 11-3/8 441.3 41E51-/NIA601099/115/130113/510 200/230-5.-208/230-3-80 441 200.1 46-3/4 1101 22-13/16 570.4 10 457.2 11-5/8 447.1 2-13/10 El IEIUIN 5U11L7 © 48E31-/N/A601090/115/130160 460-3-60 455 206.5 41-3/4 1101 22-13/16 511.4 18 457.2 11-5/8 447.7 111.41 ''T ' UNITS VOLTAGE .1. CORNER 9(1041 2.3/lA .4. OPi ION AI OPTIONAL ,I 49101-/NIA421060/040113/51D 200'231 61.1 20.0 02.2 31.3 123.4 16.0 143.8 85.3 15-15/16 I RETURN -�, SUPPLT 44E01-/NIA42104D/090160 440 61.7 21.0 82.2 37.3 132.4 00.1 146.1 01,6 AIP j hIR 1801;1-/NIA48(090/115/130113/5/1 2001230 62.1 28.1 83.8 38-•'125.8 -7.1 146.1 11.8 [101.6] OPENIYO - PEN I 40E51-/N1A401091/115/1301f0 450 62.9 20.6 03.0 3l 134.3E1.2 151.7 60.1 ��.�/ �;; I ��//f A, /8C31-/NIA60109A/115/130113/5/1 208'230 66.2 30.0 88.2 10•"132.1 EMI 754.4 10.1 �,(I� 48E61-/6/410/000/115/130110 460 66.2 30.0 88.2 40.•`141.1 Ell 159.4 72.4 tartic:C),:g6i,„041).'l�i`II111NI1111 �� B ��NOTE: All IABLC DA IA RCLEVFNI 001 ALL FACTORS 1431801(0 BF INCHES [X441 OUTDOOI CJII II _` //,/ OPTIONS/ta/ICOW3X12E0 TOP OF UNIT 14 1355 II -•-, .�� \,`. y DUCT SIDE OF UNIT • [50.81 II�� ��� ��, 3-3/16 SIDE OPPOSITE DUCTS 14[355.13 =% 8077041 OF UNIT 0 IO.PI II \ y:i� [81.0] FLUE PANEL 36 [014.41 -1• l.) I I■, BETWEEN UNITS,41 YOMEA ENTRY SIDE INCHES 14111 42 11060.01 :Lm.=_-i UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE 36 [914.01 6-13/16 UNIT AND BLOCK OR CONCRETE.BALLS AND OTHEI © (113.01 GROUNDED SURFACES, /OVER EN161 SIDE 42 [1060.81 MOIL CIL•RA/Ci FOR OPEItATU0 A10 SEMIS INCHES[4101 100000 COIL TOP V YY 'TDOOA COIL [YAP. COIL ACCESS SIDE 38[914.01 it POWER 041717 SIDE 42[1001.8] (EXCEPT FOR NEC OEDUUEMEYT51 041E TOP 48 11219.21 510E OPPOSITE DUCTS 30 1914.01 DUCT PANEL 12 1304.01, 42-15/16 -7 /4141400 DISTA4CES:IF UNIT IS PLACED LESS THAN 12 1304.81 FOOM WALL 11090.61 [50,62 47 f 1 1/2 STSTEM.TXEM SYSTEM PERFORMANCE MAYBE COMPROMISED. (1103.81 1714.77 DIMENSIONS IN 17 ARE IN NM $ y It - . . C r l 1-138' [28.6]DIA. N.O. ` - ..- POKER ENTRY :. w ■ N• 9 • • • 4 118.122.21 DIA. HOLE • 0 \ a •A• CONTROL ENTRY •® /-710 ( X21} 1123.87 1 1' I • [ • 6 I I•®>a 15-ITile` SUPPLY�•• R(IURY• 21-1/9 1103.27 • DUCT • DIET [555.61 7 OP(NIMfi DPENING' 11/11 16-1/1 1T-5/8 !9l.11 _ _ 1367.31 •1 1117.1112.1/9 ,•. - • _ [301) 1 ., pp 6-5/B r� / /_g���j�, �,1, ( ) I ) O ! ! 1 .. C1 O• 6-5/8 ,0 0 I r I 0 0 DRAIN(22 1225(00-� " �/'11'�?� •O 1-13116 5 3/4.I19.11 M.P i [328.61 COMPRESSOR •K' LOWER LECTRICAL 146.0] 112' [12.71N.P.T. 3/10 I T/B' [2I.2)UE EP PAYfI PANEL ACCESS PANEL •-1116 6A5 041717 f4 81 J-7116+. f- 1/-1'B r (52,1] [1T.)] r 13-718�.F 13-5/8+.f 13.118±. [1122.17 48-7116 1330.41 [346.11 1352.41 11221.11 141.31 RIGHT SIDE VIEW 1141.31 REAR VIEW LEFT SIDE VIEW FRONT VIEW MR an- m 01/24/G9 SINGLE-ZONE ELECTRIC COILING WITH 3 ITH GAS REHEAT (LG1 46E55002I S- 3.0 Packaged Rooftop Builder 1.39g Page 5 of 10 Performance Summary For rtu-1 Project: -Untitled26 0502/2014 Prepared By: 12:34PM Part Number:48ES-A420903 ARI SEER: 13.20 Base Unit Dimensions UnitLongdh• -_—_- 48.2 in Unit Width. 44.1 in Unit Height' 39.9 in Total Operating --' --_ 420 lb Unit Unit Voltage-Phase-Hertz 230'1'60 Air Discharge. __--'—_--- Vertical Fan Drive Type - — - Direct Actual Airflow 1403 CFM Site Altitude' ---'--- _-''__-___---_—___---- —__ 0 ft Cooling Performance Condenser Entering Air DB' __-'--'-____-___—_--_—'-__--- --_____'_____-V5.o F Evaporator Entering Air DB' 80.0 F Evaporator Entering Air WB - --' 67.0 F Entering Air Enthalpy: ___'----- 31.44 BTU/|b Evaporator Leaving Air DB. 59.9 F Evaporator Leaving Air VVB. --'----__— 58.0 F Evaporator Leaving Air Enthalpy.......................................... _ 25.02 BTU/lb Net Cooling Capacity. 40.51 MBH Net Sensible Capacity* -_---- .30.53 MBH Total Unit Power Input.--_--'_----_— ___-'----_-------_-- 3.62 kW Coil Bypass Factor:. -- 0.040 Heating Performance Heating Airflow. - _ --_.--- -_-' __--_-___-_---_'14U3 CFM Entering Air Temp. _-_-_' -----_-_---_----'_--_.---_--_'__ _-.----_.-7O.0 F Leaving Air Temp. F Gas Input Capacity:. 9n.o MBH Gas Heating Capacity.__-___--___--'---_—_ _-__— _—_ _--'---_---73 00 MBH Temperature Rise. -__--.—_'_----'__—__---_____.---__.'---___-__--_--__.___'48.2 F Supply Fan. External Static Pressure- - 0.50 in wg Options/Accessories Static Pressure Wet Coil* -----'--'__--__—_---- 0.07 inwg Total External StaticS _-- 0.57 in wg Fan RPM: _1076 Fan Power 0.30 BHP Fan Motor Size, hp:._ ---_ � _ 3/4 NOTE: - - -- �edimmMotmr Speed;Vert Electrical Data Minimum Voltage. ____' - 187 Maximum Voltage. 253 Compressor RLA. 17.9 Compressor LRA 112 Outdoor FurFLA(ea): . 1'2 • Indoor Fan Motor FLA: - 6 Power Supply MCA* omm Power Supply MOCP(Fuse nrHACR)' _ _ 40 Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics Packaged Rooftop Builder 1.39g Page 6 of 10 ROOfCURB ADAPTER PART NUMBER: CA-CAR-SDCL-BRY-011 SUBMITTED TO: FORM NO. 12564-1 P SUBMITTAL NEW UNIT: COMPANY: IM MicroMetl EXISTING UNIT: PROJECT NAME: 0%," QUOTE NUMBER: DATE: 06/25/2010 Curb Adapter Information 1. Before ordering curb adapter, contractor must 4e* confirm that dimensions of existing curb on job site matches dimensions of existing curb on this drawing. 2. Before new HVAC unit is set in place, inspect structural stability of existing curb and building's roof load capability. Reinforce if required. 3. All curb adapters will increase the system's external static pressure and must be included when calculating unit requirements. Features 1. Fully assembled curb adapter. Adapter pans, if included, are shipped loose and field assembly is required. 2. Includes internal transitions. 3. Internally insulated with 1"- 70.50 O.D. 1.5 lb. insulation. Gasketing 57.63 O.D. package provided. SHEET 1 OF 2 THIS DOCUMENT IS THE PROPERTY OF MICROMETL CORPORATION AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE CONTENTS WILL NOT BE DISCLOSED OR USED WITHOUT MICROMETL'S WRITTEN CONSENT. MICROMETL CORP. • 3035 N.SHADELAND AVENUE,SUITE 300 • INDIANAPOLIS,IN 46226 • 1-800-662-4822 ••• MICROMETL SPARKS • 202 SOUTH 18th ST. • SPARKS,NV 89431 • 1-800-884-4662• • ROOFCURB ADAPTER PART NUMBER: CA-CAR-SDCL-BRY-011 SUBMITTED TO: SUBMITTAL NEW UNIT: COMPANY: ' EXISTING UNIT: PROJECT NAM : MicroMetl QUOTE NUMBER: DATE: 06/25/201E0 f IT 46.06 59.13 ---� O.D. O.D. 1 42.19 O.D. IMPORTANT: THE CURB ADAPTER 18.00 SHOWN WAS AUTOMATICALLY GENERATED. r THE ACTUAL CURB HEIGHT AND DESIGN COULD BE ALTERED FROM THIS SUBMITTAL TO PROVIDE THE MOST EFFICIENT - 72.00 0.0. i►, CURB ADAPTER POSSIBLE. SHEET 2 OF 2 THIS DOCUMENT IS THE PROPERTY OF MICROMETL CORPORATION AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE CONTENTS WILL NOT BE DISCLOSED OR USED WITHOUT MICROMETL'S WRITTEN CONSENT. MICROMETL CORP. • 3035 N.SHADELAND AVENUE,SUITE 300 • INDIANAPOLIS,IN 46226 • 1-800-662-4822 ••• MICROMETL SPARKS • 202 SOUTH 18th ST. • SPARKS,NV 89431 • 1-800-884-4662 • •