Loading...
Permit CITY OF TIGARD MECHANICAL PERMIT a COMMUNITY DEVELOPMENT Permit#: MEC2014 00278 13125 SW Hall Blvd.,Tigard OR 97223 503.718.2439 Date Issued: 06/11/2014 T tt"\RD g Parcel: 2S102CC01900 Jurisdiction: Tigard Site address: 10225 SW HILLVIEW ST Project: UPHOFF Subdivision: FRELEON HEIGHTS NO.2 Lot: 22 Project Description: Installing(1)above ground oil storage tank. Contractor: DANA THOMPSON TANKS&SOIL Owner: UPHOFF FAMILY TRUST PO BOX 82285 BY RICHARD C/ELNOR A UPHOFF TRS PORTLAND, OR 97282 10225 SW HILL VIEW ST TIGARD,OR 97223 PHONE: 503-244-7002 PHONE: 503-639-5755 FAX: FEES Specifics: Description Date Amount Permit Fee 06/11/2014 $148.88 Type of Use: SF Plan Review 06/11/2014 $37.22 Class of Work: ALT Type of Const: VB 12%State Surcharge-Mechanical 06/11/2014 $17.87 Occupancy Grp: R-3 Info Process/Archiving-Sm$0.50(up to 06/11/2014 $0.50 Stories: 11x17) Fuel Fuel Types: Oil Gas Pressure: Total $204.47 Required Items and Reports(Conditions) This permit is issued subject to the regulations contained in the Tigard Municipal Code, State of OR. Specialty Codes and all other applicable law. All work will be done in accordance with approved plans. This permit will expire if work is not started within 180 days of issuance, or if work is suspended for more the 180 days. ATTENTION: Oregon law requires you to follow the rules adopted by the Oregon Utility No - •-• Center. Those rules are set forth in OAR 952-001-0010 through OAR 952-001-0090. You may obtain a copy of the rules or di - questions to e UNC b .,ing 503.232.1987 or 1.800.332.2344. - t Is-ued By: _ �� Permittee Signature:/ _ ,{ Y Call 503.639.4175 by 7:00 a.m.for the next available inspection date. This permit card shall be kept in a conspicuous place on the job site until completion of the project. Approved plans are required on the job site at the time of each inspection. Mechanical Permit Application FOR OFFICE USE ONLY City of Tigard ik, Received Permit No.: 13125 SW Hall Blvd.,Tigard,OR 972 DateBy: �-� m r? ,,I `y / a 7 .11,1 • Plan' Phone: 503.718.2439 Fax: 503.598.1 Q1N Date/B )�i la ar Other Permit: T 1G. A It D Inspection Line: 503.639.4175 . Date Rea.y orris: y: /�/ la See Page 2 for Internet: www.tigard-or.gov iL QI� Notified/Method: if /O//Ii ' ` Supplemental Information it-1 ` `' % • - 40471M TYPE OF WOR it . _ ,, OMMERCIAL FEE* SCHEDULE — USE CHECKLIST i. Mechanical permit fees*are based on the value of the work ,rNew construction ❑Addition/alteration/replacement performed.Indicate the value(rounded to the nearest dollar)of all ❑ Demolition .Other: mechanical materials,equipment,labor,overhead,and profit. CATEGORY OF CONSTRUCTION Value:$3,/00.tit) RESIDENTIAL EQUIPMENT/SYSTEMS FEES* Jam'"-and 2-family dwelling ❑Commercial/industrial ❑Accessory building For special information use checklist. ❑Multi-family ❑ Master builder ❑Other: Description Qty. Ea. Total JOB SITE INFORMATION AND LOCATION Heating cooling: h ,,11 ,, Air conditioning 46.75 Job site address: V 224 111���W Furnace 100,000 BTU(ducts/vents) 46.75 City/State/ZIP: �%5 6e- 0 l 22 Furnace 100,000+BTU(ducts/vents) 54.91 Suite/bldg./apt.no.: J I Project name: u{H0 r pc -it- Heat pump 61.06 Duct work 23.32 Cross street/directions to job site: L(0 1 O v% Ave. Hydronic hot water system 23.32 J Resid tial boiler(radiator or h nic) 23.32 ll ,1 I \ r, theaters(fuel-type,not electric), v'. ` �� n-wall,in-duct,suspended,etc. 46.75 -to 5 ‘1 0(4%V . lue/vent for an of above 23.32 Subdivision: Lot no.: )ir Other:AS /)clsTAi-1- 23.32 Other fuel appliances: Tax map/parcel no.: O ( 1 00 15 Water heater 23.32 DESCRIPTION OF WORK f Gas fireplace/insert 33.39 ` Flue vent for water heater or gas Ci M&` ` am CO tic-Q&J A tO fireplace 23.32 �J Log lighter(gas) 23.32 k!, O Wood/pellet stove 33.39 Wood fireplace/insert 23.32 Chimney/liner/flue/vent 23.32 Other: 23.32 ROPERTY OWNER i AA TENANT Environmental exhaust and ventilation: Name: / t AK k i• v perk: Range hood/other kitchen 01- S. ' 1 1U fie" 1 41 • equipment 33.39 Address: h W �`ll W Clothes dryer exhaust 33.39 City/State/ZIP: I.N A S(� e + -23 Single-duct exhaust(bathrooms, 631- 47 1 toilet compartments,utility rooms) 23.32 Phone: ) Fax:( ) Attic/crawls ace fans 23.32 XAPPLICANT CONTAC P RSON Other: 23.32 Business name: �A1I1/L (}, Fuel piping: !WW^���` $14.15 for first four;$4.03 for each additional Contact name: \/ �Oh Furnace,etc. i' .) YYY ��� / Gas heat pump Address: b� Wall/suspended/unit heater City/State/ZIP: D 2„ Water heater Phone:60-5) . loot._ Fax: :( ) Fireplace . E-mail: 0 . 0 A .4& 4 a•/.. Range Barbecue CONTRACTOR Clothes dryer(gas) Business name: �i/ ( 0,..5 all;c- Other: MECHANICAL PERMIT FEES* Address: Subtotal City/State/ZIP: Minimum permit fee($90.00) Plan review(25%of permit fee) Phone:( ) Fax:( ) State surcharge(12%of permit fee) CCB lic.: 14/4 7 ff, ibepht TOTAL PERMIT FEE I, I This permit application expires if a permit is not obtained within 180 days after it has been accepted as complete. Authorized signature: i l t / * Fee methodology set by Tri-County Building Industry Service Board,ii Print name: 't t '% - Date: $ 1:\Building\Permits\MEC_PermitApp_040113.doc 440-4617T(11/02/COM/WEB) ,,� .. I RECEIVED yr : `, 1 __x . JUN -5 2014 4 - CITY OF TIGARD BUILDING DIVISION r. . ' N,.. ,.4e: ' ,,,„„..4. - ,,,....: :444....4:1- ..' ' -''-€ ..- ''7; illioNt. a ' A CITY OP TIGARD REVIEWED FOR CODE COMPLIANCE ;/ Approved: [ j, OTCs [ I Permit#s ttteG 2014-()0`LF Suite#S r_ By: 414.1126., Data (:::. 9 * ., it _. OFFICE COPY -!*i...41:',/:' 1,. Ana° , ;> , . , ; z , - ,. .. _ .. .. .... • ___ r„,c,F.407.- 1,,, .. cow , • it cEte P q " PAD WIDTH �F �—~rESv PAD WIDTH ��y G)N�c��,0 , T - /1 :/ R I• 1 t of t' i;'/,±7 ' f • '-y/' 44Ep 1 1! • f JUN -5 ?014 TANK STAND Xn 3 . 1 I 40 "" I A I CITY IIGARD ,, , i BUILDING D:VLSI 1 .°v 4 + + + ., I TANK x x 1- O 0 = _ _ TANK, STAND J W J LONGITUDINAL REBAR ON TOP t k PAD o o a le AT 12" OC EACH WAY I i (2" CLR TOP) -+ + + —I- 1 • TAHK STAND ANCHOR BOLT 4 TYP (--g. I +1—J TANK FOUNDATION PAD • I • FL T AT �'illy of � i� �PAD A U p W O ! E D •FOUNDATION PLAN GENERAL LAYOUT PLAN I TANK, STAND & PAD OCT 1 6 2001 r 1 A \ TANK 1/2" DIA A307 ,�,..� \_ HEX HEAD BOLT I ,--i- !l TANK NUT kWASHER / TANK STAND . 4 TYP 1 1 / 143-mi 'Murnb .. "H" (72" MAX) TANK STAND l - NING WALL OR z BASEMENT WALL-\\ FINISHED I �CONC PAD REBAR FINISHED GRADE • GRADE W Sm I - /. / '14l `l DETAIL "A" .. M W Y.- FOUNDATION DIMENSIONS• (OVAL TANK SIZES (GALLONS) I !` UNIT 135 220 275 330 I 6" MIN J (DS VIEW 3" MIN .1_1 WIDTHH INCH 42 60 72 84 ANCHOR BOLT 4 TTF DEPTH IINCH I 6 6 6 6 TOLERANCES STRUCTURAL NOTES 5. DESIGN CRITERIA.: OW n STAND 1. TANK & FOUNDATION SHALL BE SITED A MIN OF if CLEAR FROM f A. WIND 80 MPH. EXPOSURE 'B" 1=1.0 b- SLOPES IN FINISH GRADE CONTOURS AND SHALL BE SITED A MIN DIMENSION 'H" B. SEISMIC ZONE 3, 1=1.0 OVERALL LEER= -1/414-1/e FROM RETAINING WALLS AND BASEMENT WALLS PER DETAIL A . 6. FOUNDATION MATERIALS: OVAL TANK ) mom,.wmi -11''/+1/4- FINISH GRADE SHALL BE ESSENTIALLY FLAT AT LOCATION OF TANK. A. CONCRETE rc = 2,500 PSI MINIMUM 0tm mu1J-Hal6-1/47+1/c• 3. ALL FOOTINGS PRESSURE BEAR HS FIRM, UNDISTURBED SOIL OR APPROVED COMPACTED FILL.7. ALL STEEL FOR TANK STAND SHALL BE ASTM A36 MINIMUM INSTALLATION sNfET 1-Zoo-2a1-sago A REGISTERED GEOTECHN1CAL ENGINEER SHALL BE RETAINED BY OWNER TO PROVIDE 8. ANCHOR BOLTS ARE 1/2' DIA HILT! KWIK BOLT 11 OR OWNER ,aR0T RECOMENDATIONS IF ANY UNUSUAL CONDITIONS ARE ENCOUNTERED IN THE FOOTING APPROVED EQUAL ACMISC rQTY: 1�i �j�¶+�- EXCAVATIHS OR IF COMPACTED FILL IS REQUIRED. Y l�R4W J.LL ,roe n.r I K,e C nru T : w OF 4. ALL WORT: SHALL BE Ik STRICT COMPLIANCE WITN THE UNIFORM BUILDING CODE AS -� �/ GE01lEl�BaT AS AMENDED OY THE STATE OF OREGON k ALL OTHER STATE & LOCAL CODES t L cornsc Te e:sa wK s rawr OI Rr BUILDING REQUIREMENTS THAT APPLY. _ 01-01-01 SUPCEots .� 1 .* a r r BILL OF MATERIAL ITEMS QTY NAME IDESCRIPT'ION MAIL PART No. NOTES 1 _ 2 TANK STAND 10 GAUGE X 13 9/16" H X 30 1/4" LONG (BEND & WELD AS SHOWN) A36 — MOUNT, COAT 2 4 TANK LEG STAND 1/4 PLATE X 3" W X 9 1/8" LONG (BEND & WELD AS SHOWN) A36 — MOUNT, COAT Ch, of Portland 9 1/B �� GGq,' 1 Pt0 P R O FA,.'Y..9 2 3/8' Aa n n (1 V S U `4 l ��� �G�N�F� .Op I 1 5/8 BEND DOWN 90• w*� i• ■ I I OCT 1. & 2001 4/1 �E5517'�� tiR lb'1,'/ 1. N I a�R" cp � r. �Nn 9 LsLOT 9/16' x 1 1/2• LONG ' PO 1J N V 47:;(15'.. I 30 1/4- 'El j---;iiijI\ I!!I 3• 3- 9 1/8' 9 I/8- • 3' i 2 4,,,, ,i2„ 11ry 3/19: TR 'le 0 1111 iri ��; \ BEND OOWN 90' BEND DOWN 90'� + V m BEND DOWN 90' \ -.- a .n n o to I TYP r 3/18 3/6" ., o 24 1/2' OA WIDTH 1 � / 1 I/2' 9/16" CIA HOLE. `D �1 1/2" ■ FOP. " VIARBOLT 2 TTP TOLERANCES STEEL: ASTM A36 C AT7NG: SPECIAL INSTRUCTIONS APPROXIMATE SHIPPING WEIGHT: STAND "P" EXTERIOR COATING. ACE 7E LBS. w ovo04c mom -1/,c•/+1/10' GRAY SHOP COAT 1-3 MILS GRIND SMOOTH ALL CORNERS 1 oyexru 1^um -1/16/+1/18 "R" EXTERIOR COATING ACE 1A TANIC VENT CAPACITY OVERSLIWT -1/107+1/1r RED SHOP COAT 1-3 MILS 01191.WNENSONS -1/1e•/+1/TS PRIMARY O` 1-200-701-5000 OVAL STAND A' EXTERIOR COATING, ACE 3A COLOR WHITE (WHO1) OR LT GRAY (INOI) 2 ( SP-6 GRIT BLAST �m n .ou�Mrm..lu� T ,,,a n„.T. 1 CT TN-161 EPDXY: —5 MIL 8EC7J8BIT ACMISC QTY: 1 1CT TN-74 URETHANE: 2-3 MIL — — — m,,,.2,,,..,.=w..,no.m.,_(Fl1\ICUSrI rRn;.LUJIV1\\\z-onrN. 1) . TD T: 5-8 MIL • P-21-97 SUPERCEDES 00-00-00, • CHAPTER 22 r SPECIAL PIPING AND STORAGE SYSTEMS SECTION M2201 SECTION M2202 OIL TANKS OIL PIPING,FITTING AND CONNECTIONS M2202.1 Materials.Piping shall consist of steel pipe,copper M2201.1 Materials.Supply tanks shall be listed and labeled tubing or steel tubing conforming to ASTM A 539.Aluminum and shall conform to UL 58 for underground tanks and UL 80 tubing shall not be used between the fuel-oil tank and the for indoor tanks. burner units. M2201.2 Above-ground tanks.The maximum amount of fuel M2202.2 Joints and fittings.Piping shall be connected with oil stored above ground or inside of a building shall be 660 gal- standard fittings compatible with the piping material.Cast iron Ions (2498 L). The supply tank shall be supported on rigid fittings shall not be used for oil piping.Unions requiring gas- noncombustible supports to prevent settling or shifting. kets or packings, right or left couplings, and sweat fittings Exception:The storage of fuel oil,used for space or water employing solder having a melting point less than 1,000°F heating, above ground or inside buildings in quantities (538°C)shall not be used for oil piping. Threaded joints and exceeding 660 gallons (2498 L) shall comply with NFPA connections shall be made tight with a lubricant or pipe thread 31. compound. M2201.2.1 Tanks within buildings.Supply tanks for use M2202.3 Flexible connectors.Flexible metallic hoses shall be inside of buildings shall be of such size and shape to permit listed and labeled in accordance with UL 536 and shall be installation and removal from dwellings as whole units. installed in accordance with their listing and labeling and the Supply tanks larger than 10 gallons(38 L)shall be placed manufacturer's installation instructions. Connectors made not less than 5 feet(1524 mm)from any fire or flame either from combustible materials shall not be used inside of build- within or external to any fuel-burning appliance. ings or above ground outside of buildings. M2201.2.2 Outside above-ground tanks.Tanks installed outside above ground shall be a minimum of 5 feet(1524 M2203 SECTION mm)from an adjoining property line. Such tanks shall be INSTALLATION suitably protected from the weather and from physical dam- INSTALLATION age. M2203.1 General. Piping shall be installed in a manner to M2201.3 Underground tanks.Excavations for underground avoid placing stresses on the piping, and to accommodate tanks shall not undermine the foundations of existing struc- expansion and contraction of the piping system. tures.The clearance from the tank to the nearest wall of a base- M2203.2 Supply piping.Supply piping used in the installation ment,pit or property line shall not be less than 1 foot(305 mm). of oil burners and appliances shall be not smaller than 3/8-inch Tanks shall be set on and surrounded with noncorrosive inert (9 mm)pipe or3/8-inch(9 mm)outside diameter tubing.Copper materials such as clean earth, sand or gravel well tamped in tubing and fittings shall be a minimum of Type L. place. Tanks shall be covered with not less than 1 foot (305 mm)of earth.Corrosion protection shall be provided in accor- M2203.3 Fill piping. Fill piping shall terminate outside of dance with Section M2203.7. buildings at a point at least 2 feet(610 mm)from any building opening at the same or lower level. Fill openings shall be M2201.4 Multiple tanks. Cross connection of two supply tanks shall be permitted in accordance with Section M2203.6. equipped with a tight metal cover. M2201.5 Oil gauges. Inside tanks shall be provided with a M2203.4 Vent piping.Vent piping shall be not smaller than device to indicate when the oil in the tank has reached a prede- 1 /4-inch (32 mm) pipe. Vent piping shall be laid to drain termined safe level.Glass gauges or a gauge subject to break- toward the tank without sags or traps in which the liquid can age that could result in the escape of oil from the tank shall not collect.Vent pipes shall not be cross connected with fill pipes, be used. lines from burners or overflow lines from auxiliary tanks.The lower end of a vent pipe shall enter the tank through the top and M2201.6 Flood-resistant installation. In areas prone to shall extend into the tank not more than 1 inch(25 mm). I I flooding as established by the local jurisdictions,tanks shall be piping Vent termination.Vent i shall terminate out- installed at or above the elevation required in Section R322.2.1 p p g or R322.3.2 or shall be anchored to prevent flotation,collapse side of buildings at a point not less than 2 feet(610 mm),mea- and lateral movement under conditions of the design flood. sated vertically or horizontally, from any building opening. Outer ends of vent piping shall terminate in a weather-proof M2201.7 Tanks abandoned or removed. Exterior above- cap or fitting having an unobstructed area at least equal to the grade fill piping shall be removed when tanks are abandoned or cross-sectional area of the vent pipe,and shall be located suffi- removed.Tank abandonment and removal shall be in accordance ciently above the ground to avoid being obstructed by snow and with the Fire Code. ice. 2011 OREGON RESIDENTIAL SPECIALTY CODE 22-1 SPECIAL PIPING AND STORAGE SYSTEMS M2203.6 Cross connection of tanks.Cross connection of two supply tanks, not exceeding 660 gallons (2498 L) aggregate capacity, with gravity flow from one tank to another, shall be acceptable providing that the two tanks are on the same hori- r zontal plane. M2203.7 Corrosion protection.Underground tanks and bur- ied piping shall be protected by corrosion-resistant coatings or special alloys or fiberglass-reinforced plastic. SECTION M2204 OIL PUMPS AND VALVES M2204.1 Pumps. Oil pumps shall be positive displacement types that automatically shut off the oil supply when stopped. Automatic pumps shall be listed and labeled in accordance with UL 343 and shall be installed in accordance with their list- ing. M2204.2 Shutoff valves.A readily accessible manual shutoff valve shall be installed between the oil supply tank and the burner.Where the shutoff valve is installed in the discharge line of an oil pump,a pressure-relief valve shall be incorporated to bypass or return surplus oil. M2204.3 Maximum pressure.Pressure at the oil supply inlet to an appliance shall be not greater than 3 pounds per square inch(20.7 kPa). M2204.4 Relief valves. Fuel-oil lines incorporating heaters shall be provided with relief valves that will discharge to a return line when excess pressure exists. 22-2 2011 OREGON RESIDENTIAL SPECIALTY CODE Location: Record Type: Inspection Type: Result: Comments: Inspection Date: Record ID: Inspector: City of Tigard 13125 SW Hall Blvd. Tigard, OR 97223 Tel: 503.718.2439 10225 SW HILLVIEW ST, TIGARD, OR, 97223 Residential - Mechanical 699 Mechanical final FAIL MEC2014-00278 George Heimos 1. Seal galvanized pipe tank vent penetration on outside siding. 2.'recall when completed. Violation Summary: Inspector Contractor