Loading...
Specifications I- RECEIVED t[rcD 6305 6 im SlexGrinn Rosewood ood St.STE A �+.AA Fire& Lake Oswego,OR 97035 Security Phone:503-683-9000 OCT 0 4 202 Fax:503-675-6521 Simplex Grinnell www.simplexgrinnell.com CITY OFTIGARD BUILDING D1V1SK N City of Tigard Suppression Alarm System Product Submittal Project Engineer: Albert Bryant,SET,WET Level R'#111681 Simple_xGrinnell Project#448 SUPPRESSION ALARM SYSTEM EQUIPMENT MODEL# DESCRIPTION PFC-4410RC POTTER SUPPRESSION CONTROL PANEL W/8AH BATTERY ARM-2 POTTER AUXILARY RELAY MODULE RCDS-1 POTTER RELEASING CRKT.DISABLE W/LAMP P32-IT-UP POTTER MANUAL PULL STATION ABT POTTER ABORT SWITCH PS-24 POTTER PHOTO SMOKE DETECTOR Al IS-24 POTTER ION SMOKE DETECTOR SB-46 DETECTOR BASE SL-1224R STROBE LIGHT RED SH-1224R HORNSTROBE RED G-500 AERO-K G-500 GENERATOR • 1 4 P POTTER PFC_441 oRC The Symbol of Protection RELEASING CONTROL PANEL •Multi-Hazard Operation •Four Class B Initiating Circuits •Two Class B Supervisory Circuits** •Four Class B Output Circuits •Programmable Cross Zoning •Supervised Microprocessor •32 Character Alpha-Numeric LCD Display IN •Custom Banner Message and Zone Description text ■ •Custom Zone Description Text •On Board Menu Driven Programming Controls •Releasing Circuits Protected From False Activation •Continuous or Timed Discharge •40 Event History Buffer •Walktest with Automatic Time-out •Alarm,Trouble Supervisory,and Waterfiow relays PFC Series •Optional Class A Initiating Zone and output module Tr, r," Re easing aaaW" •34 character LED supplemental display • 19 Standard Programs in Panel Memory •Password Protection for all Programming •24 Hour Clock •Suitable for agent or water-based extinguishing •Programmable pre-discharge timers* •One Class B Abort circuit*(Defaults to additional supervisory zone in water based mode.) Dimensions: 18 '/"x 14 1/4"x 4 3/4" •Three Abort modes* UL and ULC Listed, FM Approved.NYMEA Accepted.and *Available in Chemical mode only CSFM Approved **One zone programmable as abort in chemical mode. General Description The PotterModelPFC-441ORC isa flexible multi-hazard releasing control The panel is Ninth Edition UL listed, ULC listed. Factory Mutual, panel that is well suited for a number of applications.The PFC-441 ORC CalifomiaStateFire Marshal(CSFM)andNewYork Materials Equipment is listed for use with pre-action and deluge sprinkler suppression systems Acceptance(MEA)approved. and agent based fire suppression systems. The PFC-44I ORC is housed in a durable steel cabinet with removable The panel utilizes a microprocessor-based system that has 19 Standard door and key lock.The panel is available in either a red or white finish Programs,which covers a majority of installations.The simple to follow and an optional flush mount trim ring is available.The cabinet contains Menu Structure programs the entire system in a matter of minutes. In knockouts on the side,back and top of the cabinet to ease installation. addition to the Standard Programs.the panel allows custom programming In addition,the cabinet will house up to 18 amp-hour batteries that will to accommodate any installation. provide in excess of 90 hours of standby power. Ordering Information Model Number Description Stock Number PFC-44IORC 4 Zone Releasing Control(White Cabinet) 3006144 PFC-441 ORC 4 Zone Releasing Control(Red Cabinet) 3006142 PFC-1'W Bezel for Semi-Flush Mounting(White) 5090157 PFC-TR Bezel for Semi-Flush Mounting(Red) 5090155 BT-40 Battery, I2V 4AH for 24 hour standby(2 Req'd) 5130092 _. BT-80 Battery, I2V 8AH for 60 hour standby(2 Req'd) 5130084 BT-120 Battery, I 2V 12AH for 90 hour standby(2 Req'd) 5130090 BT-180 Battery, 12V, I8AH for 90 hour standby(2 Req'd) 5130086 CA2Z 2 Zone Class A Initiating Circuit Module 3006013 CAM Class A Indicating Circuit Module 3005300 ARM-44 Relay Module for PFC-4410RC 3006221 ARM-2 Auxiliary Relay Module 3004725 RA-441 ORC Remote Annunciator 3006400 BB-RA-44R Surface Mount Back Box for RA-44 10RC(Red) 3006401 Potter Electric Signal Co.,LLC•St Louis,MO•Cust Service:866-240-1870•Tech Support:866-956-12I I•Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG N5401250-REV A PAGE 1 OF 2 12/09 2 1 P POTTER PFC-4410RC e The Symbol of Protection RELEASING CONTROL PANEL Architects/Engineers Specifications The control panel for the extinguishing agent releasing system shall Waterllow,Linear Heat Detection(up to 10,000 feet per zone). be a microprocessor based control capable of protecting multiple Manual Release,Low Air Alarm.Supervisory,Tamper.Low Air or hazards in one control panel.It shall be Underwriters Laboratories High Air. Inc.listed under Standard 864 Ninth Edition and Underwriters Optional Class A modules.CA2Z,may be added for Class A Laboratories of Canada for Local Control Units for Releasing Service. operation.The panel shall have a Low Air Zone that creates a The control shall also be approved by Factory Mutual Research supervisory condition and map to an output.UL and ULC Listed,FM Corporation and be compliant with the requirements of NFPA-72 Approved,NYMEA Accepted.CSFM Approved (Local:A.M,SS service types;DAC and NC signaling type)and The control shall have two fully supervised Class B(Style B) NFPA12.NFPA12A.NFPA-13.NFPA-15,NFPA-16.NFPA-17. supervisory circuits.These circuits shall be selectable through the NFPA-17A,NFPA-750,and NFPA-2001. programming sequence to operate in one of the following modes: The control shall be housed in an 18 gauge steel cabinet that has a Supervisory.Tamper,Low Air or High Air. hinged,removable door with a key lock.The finish shall be baked The control shall have one fully supervised class B(style B)Abort enamel and available in red or off=-white with contrasting trim and circuit with 3 different operating modes.ULI,1R1.and NYC. logo.An optional matching bezel should be available for semi-flush mounting.The cabinet shall have adequate space to house 18 AB The control shall have four fully supervised Class B(Style Y)output standby batteries capable of operating the system for at least 90 hours. circuits.These circuits shall be selectable through the programming sequence to operate as one of the following:Alarm Notification The control shall include a fully supervised integral power Appliance.Supervisory Notification Appliance,Trouble Notification supply/battery charger capable of providing 200mA to the auxiliary Appliance or Releasing. The optional CAM module may be added to power circuit.It shall also he capable of providing 2.5 Amps to all convert the outputs to Class A. releasing and notification appliance circuits combined.All initiating, output and auxiliary power circuits shall be power limited. The panel shall have an RS-485 output and auxiliary power outputs for connection and supervision of up to 4 remote annunciators or an The control shall have a 32 character(16 characters,2 lines)backlit ARM-44 Relay Module and 3 annunciators. LCD display and a 34 LED supplemental display.All diagnostic and alarm event information shall be viewable in text form on this display. The releasing circuits shall he supervised for short circuit conditions A field programmable custom banner message with the current date and shall be programmable for cross zoning operation when required. and time shall be displayed when no current alarm or diagnostic The discharge tinter for these releasing circuits shall be programmable information exists. for times of 7.8.9. 10,20 minutes or continuous.All initiating and output circuits shall be capable of being individually disabled or All operational features of the control panel shall be field enabled.In addition.when in the agent extinguishing mode there shall programmable using menu driven selections on the alpha-numeric be a pre-discharge timer adjustable from 0-60 seconds front an alarm display and on board controls.No special programmer will be zone or 0-30 seconds from a manual release zone. required and junipers or switches to configure operational features shall not be permitted.Alarm and trouble indications shall resound The control shall have a test mode that will automatically disable when required. all releasing circuits.The test mode shall operate in such a manner as to automatically reset the initiating circuit and indicating circuits The control panel shall he equipped with 19 programs built into the after detecting each alarm condition initiated by the test.All testing panel memory, 13 for water based extinguishing and 6 for agent shall be recorded in the 40 event history buffer.The test mode will extinguishing.In addition-the panel shall have the ability to add custom automatically terminate after twenty minutes of inactivity. programs.All programming functions shall be password protected. The control shall have four integral relay contacts rated 3 Amps at 30 The control shall have four fully supervised Class B(Style B) VDC for connection to external auxiliary equipment.One relay shall initiating circuits capable of supporting the operation of 25 compatible operate when an alarm condition occurs,another when a trouble signal 2-wire smoke detectors on each circuit. occurs,the third when a supervisory condition occurs,and the fourth The individual circuits shall be selectable through the programming during a waterflow condition. sequence to operate in one of the following modes:Conventional, UI.and ULC Listed,FM Approved.NYMEA Accepted,CSFM Approved. ►- PRINTED IN USA MFG 45401250-REV A PAGE 2 OF 2 12/09 3 PARM-2 0 The Symbol of Protection AUXILIARY RELAY MODULE UL Listed: For use with the PFC-441 ORC Series Dimensions: 2 1/4"x 3 1/2"x 3" Weight: .315 lb. ;__, ,. Assembly: Socketed relay in plastic mounting track Power Requirements: 40mA at 24VDC Contact Ratings: Each relay has DPDT contacts, Rated at 10 amps resistive, 120/240VAC,0-30VDC Stock number:3004725 The ARM-2 Auxiliary Relay Module is a UL listed option when factory by 24VDC Indicating and/or Releasing,polarity reversing circuits. installed in the Potter PFC-441 ORC Series. The module can be used for fan shutdown,door release,elevator When the ARM-2 is used the additional power required for this relay recall,etc. module must be subtracted from the total circuit current available. Note. One to four ARM-2 modules in the PFC-441ORC series may See PFC-441 ORC Manual#5403550.The ARM-2 Auxiliary Relay he utilized to provide multiple auxiliary functions. Module is a non-supervised DPDT Relay designed to be activated Wiring Placement In PFC-4410RC Series Control Unit I8^WIRE LEADS FURNISHED FOR 1• •NUMBERS REFER TO RELAY COIL S. SOCKET TERMINALS RED 8 A 0 3. NOT RELAY PINS. �-Q 2• 6• MAIN PC BOARD MODULE BLACK o /' 4. 7 RELAY SHOWN DE-ENERGIZED IS n --- �� 0 18 p-9 �?' FOURTH RELAY FOR PFC-4410 � I I ARM-2 RELAYS DWG#977-1 —110- ARM-2/PFC-4410RC Installation Hook-Up Diagram All relays shown in non-activated condition CONNECT CIRCUIT ACIRC IT * n O 3• OUTPUT CIRCUIT � s• BLACK 6• p n 04. PFC-4110RC OUTPUT TERMINALS OW011911-2 Notes: 1. *Numbers refer to socket terminals not relay pins. 2. Auxiliary relay operation is determined by programming of the PFC-4410RC Series panel. Consult the appropriate manual for further information. Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161 •Phone: 800-325-3936/Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.#5400977-REV N PAGE I OF I 9/08 4 PRCDS - 1 POTTER RELEASING CIRCUIT • The Symbol of Protection DISABLE SWITCH "," UL,CUL Listed Dimensions: 2 3/4"W x 4-1/2"H x 2"D(Approximate) Mounts on single gang or handy box • Contact Rating: 1 AMP @ 40 VDC Power Requirements: 24 VDC, IOmA Environmental Specifications: Indoor use only.Temperature range-22°F to140°F(-30°C to 60°C) Stock number: 3001002 Description The device consists of a stainless steel faceplate,green LED,amber LED,and a switch assembly.It is designed to mount on a standard single gang electrical enclosure. Application The RCDS-1 complies with the requirements of NFPA 72: • Specifying a physical switch to disconnect the release circuit in place of a software controlled disconnect. • Creating a supervisory condition on the associated release panel. Installation I. Connect the red and black leads to the 24 VDC auxiliary power terminals on the release panel. Be certain to observe polarity. 2. Connect the yellow wires to the supervisory zone on the panel. NOTICE Operation The connection for the supervisory circuit has 4 wires:2 yellow and The green LED indicates the RCDS is in the Normal condition and the 2 gray.The 2 yellow wires are for connection to the supervisory release circuit is enabled*. circuit.The 2 gray wires are for connection to additional supervisory The amber LED indicates that the release circuit is disabled. devices or the EOLR for the supervisory zone. *If the release circuit has been disabled by some other means,the green LED may still be on. 24 VDC SUPERVISORY RELEASING ZONE CIRCUIT NV v •• •• •• •• O LED'S 0 YELLOW YELLOW O ek KEY �:. O SWITCH,\ ORANGE BLACK I,RED ill EOL RAY DIODE RELEASING RAY ASSY DWG#214-1 SOLENOID Potter Electric Signal Company,LLC•St.Louis,MO•Cust Service:866-572-3005•Tech Support:866-956-0988•Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MFG.145401214-REV D PAGE 1 OF I 3/10 5 PPULL STATION SERIES POT1IR DIE-CAST METAL • The Symbol of Protection MANUAL PULL STATIONS • UL and cUL Listed,FM Approved,CSFM Listed,MEA FIRE ALARM FIRE ALARM Approved,ADA Compliant • Single or Dual Action 11":1 FIRE :> P Terminal connectors ALARM 1 • 10 Amp Snap Action Switch • Gold plated SPST contacts LIFT • Optional auxiliary contacts 111110 • Mounts on standard single gangbox PULL • Surface backboxes available Iltiportat • High-gloss red enamel finish • Glass 411 • Made in the U.S.A.MOM. Wi Description Engineering Specifications The Potter Pull Station Series offers a complete line of die-cast pull The contractor shall furnish and install the Potter series of pull stations for a variety of applications focusing mainly on fire alarm stations as indicated.The pull station shall be die cast construction systems.The pull stations are available in single or dual action with a"T"type pull handle that is ADA compliant.Single action pull models.All of the pull stations have a 10-amp snap action switch and stations shall be a P32-1T.Dual action pull stations shall be the Potter a dedicated terminal block for the ease of wire connections.All of P32-1T-LP.Any manual pull station installed in an outdoor or wet the metal is completely coated to inhibit corrosion and provide for a location shall be a RMS-IT-WP weather proof unit.The contact shall uniform and quality finish. be a single pole,single throw switch rated at 1 amp 30V DC/125V The standard models have a hex key reset,however a key reset is also AC.The device shall have a terminal block for ease of wiring.Once available.The models are available with shallow and deep surface activated,the pull station shall be reset by opening the front cover. mount back boxes and as a weatherproof version. Opening of the cover in a normal state shall initiate an alarm. Operation Specifications The Potter single action series of pull stations operate by pulling Switch Rating: I Amp @ 30 VDC the white operating handle straight down and the handle will lock 1 Amp @ 125 VAC into place.The dual action stations require the lifting of the front Pull Station Dimensions: 4-3/4"H x 3-1/4"W x 7/8"D cover and then pulling the white operating handle straight down.The Color:Red with raised white letters,white pull bar with raised red letters stations are reset by opening the front and placing the handle in the normal position. For special application manual stations see bulletin#8910014. For explosion proof manual stations see bulletin#8880014. Ordering Information Type Model Number Stock Number Contact Type P32-1T 1000447 SPST RMS-2T 1000477 DPST Single Action RMS-6T 1000478 DPDT RMS-1 T-KL 1000451 SPST RMS-IT KO 1000450 SPST,key operated,no pull Weather Proof RMS-IT-WP 1000401 dj Dual Action P32-1T-LP 1000476 SPST Weather Proof Dual Action RMS-1T WP-LP 1000403 Accessories Notes Dual Action RMS-LP 1000480 Converts single action to dual action Back Box P32-BB 1000444 Surface mount back box Back Box P32-DBB 1000445 Deep surface mount back box Glass Rods RMS-GB 1000470 Replacement glass rods(10 per pkg) Potter Electric Signal Co.,LLC•St.Louis,MO•Cust Service:866-240-1870•Tech Support:866-956-1211• Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MKT.08900097-REV K PAGE 1 OF 1 5/10 6 P POTTER The Symbol of Protection ABORT SWITCH ; G UL and ca'L Listed,FM Approved Dimensions: 4-1/2"W 4-1/2"I-1 x 2"D(Approximate) Contact Rating: r_ One N.O.momentary contact rated. 2.5 Amps(n 24 VDC(5 mA minimum) t Environmental Specifications: ' Indoor use only •1. Stock number:3001000 Description The Potter Abort Switch is designed to be wired to the abort terminals of the Potter PFC-4410-RC.PFC-4410A-RC and PFC-4410RC(9th Edition)releasing panels.The device consists of a stainless steel faceplate and a modular switch assembly.It is designed to mount on a standard double gang electrical enclosure. ty �'1, EGLR YRGM LE r `� • RELEASING PANEL �, 1 ) DWG.#I136-1 Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada 888-882-1833 • www.pottersignal.com PRINTED IN USA MFG.#5401130-REV F PAGE I OF I 10/09 7 F) -÷ PS-24 POTTER PHOTOELECTRIC • The Symbol of Protection SMOKE DETECTOR UL,ULC,and CSFM Listed,FM Approved Light Source:GaAIAs Infrared Emitting Diode o r'' • Rated Voltage: 17.7-33.0 VDC 8 Working Voltage: 15.0-33.0 VDC Maximum Voltage:42 VDC Supervisory Current:45µA Max.at 24 VDC • .r" a Surge Current: 160µA Max.at 24 VDC Alarm Current: 150 mA Max.at 24 VDC Ambient Temperature:32°F to 120°F(0°C to 49°C) Sensitivity Test Feature: Automatic Sensitivity window verification test. ® Q Mounting: Refer to Potter SB Series Smoke Detector Base series, bulletin no.8840008. Stock number: 1430011 Standard Features Operation • Low profile, 1.8"high(with base) The PS-24 photoelectric smoke detector utilizes two bi-colored LED's • 2 or 4 wire base compatibility,relay bases available for indication of status.In a normal standby condition the LED's flash green every 3 seconds.When the detector senses that its sensitivity has • Highly stable operation,RF/fransient protection drifted outside the UL listed sensitivity window the LED's will flash red • Low standby current,45µA at 24 VDC every 3 seconds.When the detector senses smoke and goes into alarm • Two built-in power/sensitivity supervision/alarm LED's the status LED's will latch on red. • Non directional smoke chamber The detector utilizes an infrared LED light source and silicon photo diode receiving element in the smoke chamber.In a normal standby condition, • Vandal resistant security locking feature the receiving element receives no light from the pulsing LED light source. • Built-in magnetic go/no go detector test feature In the event of a fire,smoke enters the detector smoke chamber and light • Removable smoke labyrinth for cleaning or replacement is reflected from the smoke particles to the receiving element.The light received is converted into an electronic signal. • Automatic Sensitivity window verification function meets outlined requirements in NFPA 72, Chapter 7, Inspection, Testing and Signals are processed and compared to a reference level,and when two Maintenance. consecutive signals exceeding the reference level are received within a specified period of time,the time delay circuit triggers the SCR switch • Compatible with IS-24 ionization detectors to activate the alarm signal.The status LED's light continuously during • Backwards compatible with Potter PS and IS detectors. the alarm period. • Compatible with Potter releasing controls Application The PS-24 can be used in all areas where Photoelectric Smoke Detectors are required.The wide range smoke chamber makes the PS-24 well suited for fires ranging from smoldering to flaming fires. SB Series Style bases maybe used with the PS-24.Current interchangeable/ compatible devices are the IS-24 ionization detector. Potter Electric Signal Co.,LLC •St.Louis,MO•Cost Service:866-240-1870•Tech Support: 866-956-1211 •Canada 888-882-1833•www.pottersi_nal.com PRINTED IN USA MKT.48840007-REV G PAGE I OF 2 8/04 8 PS-24 P POTTER PHOTOELECTRIC The Symbol of Protection SMOKE DETECTOR Engineering Specifications The contractor shall furnish and install where indicated on the plans, The sensitivity of the detector shall be capable of being measured.It shall Potter Model PS-24 photoelectric smoke detectors. The combination be possible to perform a functional test of the detector without the need detector head and twist-lock base shall be UL listed compatible with a of generating smoke.The sensitivity of the detector shall be monitored UL listed fire alarm panel. automatically and continuously to verify that it is operating within the The base shall permit direct interchange with Potter,PS-24H,combination listed sensitivity range. photoelectric/heat detector and IS-24 ionization type smoke detector. To facilitate installation,the detector shall be non-polarized. Voltage The base shall be appropriate twist-lock base SB Series.In the event of and RF transient suppression techniques shall be employed to minimize partial or complete retrofit,the PS-24 may be used in conjunction with, false alarm potential.Auxiliary SPDT relays shall be installed where or as a replacement for,Potter detectors(PS-24,PS-24H and the IS-24) indicated. the SB base applications. The vandal-resistant, security locking feature shall be used in those The smoke detector shall have two flashing status LED's for visual areas as indicated on the drawing. The locking feature shall be field supervision.When the detector is in standby condition the LED's will removable when not required. flash green.When the detector is outside the UL listed sensitivity window Specifications subject to change without notice. the LED's will flash red. When the detector is actuated,the flashing LED's will latch on red. The detector may be reset by actuating the control panel reset switch. PS-24 Sensitivity Test Feature The PS-24 Photoelectric Smoke Detector has a built-in automatic sensitivity test feature. 1. In normal condition,both LED's flash green. 2. When the sensitivity drifts outside of its sensitivity limits,both LED's flash red. 3. In the alarm state both LED's are red continuously. 4. When the sensitivity drifts outside of its sensitivity limits and both LED's flash red,the device needs to be cleaned or returned to the factory for cleaning. PRINTED IN USA MKT.#8840007-REV G PAGE 2 OF 2 8/04 9 P POTTER -► IS-24 The Symbol of Protection IONIZATION SMOKE DETECTOR UL,ULC,CSFM Listed,FM Approved Radioactive Source: AM-241 0.5 pCi r► Rated Voltage: 17.7-30.0 VDC / Working Voltage: 15.0-33.0 VDC Maximum Voltage: 42 VDC `t Supervisory Current: 40 pA at 24 VDC Surge Current: 200 p.A at 24 VDC .w Alarm Current: 150 mA at 24 VDC Ambient Temperature: 32°F to 120°F(0°C to 49°C) Sensitivity Test: Magnetically activated dual reed switch test ® Mounting: Refer to Potter SB Series Smoke Detector Base Series, Q bulletin no.8840008 IS-24 Stock No. 1430010 Standard Features Operation • Low profile, 1.8"high(with base) The IS-24 ionization smoke detector utilizes two bi-colored LED's for • 2 or 4 wire base compatibility,relay bases available status indication purposes.In a normal standby condition the LED's flash green approximately once each second.When the detector senses smoke • Highly stable operation,RF/Transient protection and goes into alarm the status LED's will latch on red. • Low standby current,40 pA at 24 VDC A single radioactive source of Americium-241 ionizes two chambers • Two built-in power/alarm LED's for 360°viewing within the detector,a reference chamber and the smoke sensing chamber. • Non-directional smoke chamber The air is ionized by this source and a small DC current flows between the • Vandal resistant security locking feature electrodes of each chamber.Smoke can freely enter the sensing chamber, while the inner chamber is virtually sealed to smoke.Smoke entering the • Built-in magnetic detector sensitivity test feature. sensing chamber causes a reduction in the DC current flow,the voltage Meets NFPA 72, Chapter 7, Inspection, Testing and Maintenance imbalance between the two chambers is proportional to the smoke density. requirements When the voltage difference becomes great enough it causes the detector • Compatible with PS-24 photoelectric detectors to go into alarm.The two chamber design is utilized to compensate for • Backwards compatible with Potter PS and IS smoke detectors. changes in atmospheric and environmental conditions. • Compatible with Potter releasing controls Application The IS-24 can be used in all areas where Ionization Smoke Detectors are required.The responsive,yet highly stable operation allows the IS-24 to fit in a wide range of uses.The IS-24 can be used in areas where early warning of superheated or flaming combustibles is expected. SB Series style bases may be used with the IS-24. The only current compatible device is the PS-24 Photoelectric detector. Potter Electric Signal Co.,LLC•St.Louis,MO•Cust Service: 866-240-1870•Tech Support: 866-956-1211 • Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MKT.#8840006-REV G PAGE I OF 2 8104 10 IS-24 P POTTER • The Symbol of Protection IONIZATION SMOKE DETECTOR Engineering Specifications The contractor shall furnish and install where indicated on the plans, The sensitivity of the detector shall be capable of being measured.It shall Potter Model IS-24 ionization smoke detectors.The combination detector be possible to perform a functional test of the detector without the need of head and twist-lock base shall be UL listed compatible with a UL listed generating smoke.The test method shall simulate effects of products of fire alarm panel. combustion in the chamber to ensure testing of the detector electronics. The base shall permit direct interchange with Potter PS-24 photoelectric To facilitate installation,the detector shall be non-polarized.Voltage and RF type detector and PS-24H combination photoelectric/heat detector.The transient suppression techniques shall be employed to minimize false alarm base shall be appropriate twist-lock base SB Series.In the event of partial potential.Auxiliary SPDT relays shall be installed where indicated. or complete retrofit,the IS-24 may be used in conjunction with,or as The vandal-resistant,security locking feature shall be used in those areas a replacement for, Potter detectors(PS 24,PS-24H and the IS-24)on indicated on the drawing. The locking feature shall be field removable most SB base applications. when not required. The smoke detector shall have two flashing status LED's for visual Specifications subject to change without notice. supervision.When the detector is in standby condition the LED's will flash green.When the detector is actuated,the flashing LED's will latch on red. The detector may be reset by actuating the control panel reset switch. IS-24 Sensitivity Test Feature Test Procedure 1. With detector wired to appropriate initiating circuit or current 5. If detector does alarm when magnet is positioned as in Fig.I or does limited power source and with normal applied power,place magnet not produce an alarm when magnet is positioned as in Fig.2,detector as shown in Fig. I. is not within specified sensitivity limits and may require service. 2. Wait at least six seconds.Detector SHOULD NOT alarm and LED x should not light. ', 3. Place magnet on detector as shown in Fig.2(opposite side). Conduct testing only under Normal Standby conditions.Abnormal 4. Wait at least six seconds. Detector SHOULD alarm. or Low Power conditions may affect sensitivity.Always reset power prior to testing of next unit. tQoto 0 10,01 0 ao�� �s� o°+o 1 p p FIG.I LED'S FIG.2 DWG#884306-4 PRINTED IN USA MKT.#8840006-REV G PAGE 2 OF 2 8/04 11 P POTTER SB SERIES The Symbol of Protection SMOKE DETECTOR BASES UL and ULC Listed Electrical: 24VDC-Polarized Suitable for use with Potter PFC Series Controls Mounting: 3 l/4"or 4"outlet box Annunciator Output: 15mA at 24VDC ' Alarm Current: HSC-4R-43mA @ 24 VDC-4 WIRE BASE SB-46 -46mA @ 24 VDC SB-81R-81mA @ 24 VDC-RELAY BASE SB-93 -93mA @ 24 VDC Q �� HSB-21 -32mA @ 24 VDC Service Use: National Fire Alarm Code NFPA-72 Application S A CAUTION The e SSB Series is a 6"polarized base with annunciator output featuring a current limiting resistor,and a blocking diode to enhance annunciator These units must be installed and maintained in accordance with all function.The SB Series Smoke Detector base is designed specifically for applicable NFPA standards, local codes and any authority having use with the Potter Smoke Detector Models IS-24,PS-24 and PS 24H. jurisdiction.Please refer to NFPA-72 Standards for Automatic Fire r:rg ; r ri< ; Detectors for installation guidelines,and testing procedures. These detectors will not work without power. They must be € our, properly connected into the signal initiating device circuit of a fire control panel that is listed as being compatible by Underwriters /��-Sj Laboratories,Inc. 2 (kW OM- These detectors will not sense fires which start where smoke does not g Mer reach the detector. E (-) #� Fires on other building levels,within walls,on roofs,in chimneys,or on the other side of closed doors may not be detected. •�� Fires from explosions, improperly stored flammable liquids, escaping ""*"` gas, arson or fires resulting from inadequate fire protection practices may not be detected. Terminal# Designation Smoke detectors should be tested upon completion of installation and I Positive In at least semi-annually thereafter, in accordance with the section of 2 Positive Out "Inspections,Tests,and Maintenance"in NFPA-72. To Install the Detector: Insert the detector into the base,turn the detector 3 Negative Out clockwise until it locks, then tighten the vandal resistant allen screw. 4 Negative In 5 Annunciator Out 6 Annunciator Out Ordering Information Model# Stock# Description Compatibility —01" SB-46 1430014 Smoke Base-46mA draw @ 24vdc All Potter release panels;Not for use with PFC3000,5000,9000 Series panels; Check other panel manufacturer's compatibility listings. SB-93 1430016 Smoke Base-93mA draw @ 24vdc For use on all Potter PFC 3000,5000 Series panels. PFC9000 series with ZA9008 module added. Not for use on Potter release panels; Check other panel manufacturer's compatibility listings. SB-81R 1430015 Smoke Base W/Relay-81mA draw For use on Potter PFC 3000 and 5000 Series;Not for use on Potter release panels Check other panel manufacturer's compatibility listings. HSC-4R 1430013 Wire Smoke Base W/Relay-43mA draw For use with any panel that can provide 24VDC 4-wire resettable power. For additional 2-wire base compatibility,contact Potter Technical Support at 800-325-3936 or technapottersignal.com. • Potter Electric Signal Co.,LLC•St.Louis,MO•Cust Service:866-240-1870•Tech Support: 866-956-1211 •Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MKT.#8840008-REV K PAGE 1 OF I 9/07 12 SL-1224 SERIES P P011ER WALL MOUNT • The Symbol of Protection SELECT-A-STROBE* •UL and cUL listed • 12 VDC with 15,35 or 60 cd setting •24 VDC with 15,35,60,75,95 or 110 .f •6 distinct candela settings a •Candela selection view window - 4 • 15/75 ADA compliant on 60cd setting M... •Pre-wire back plate N.-. •Universal back plate mounting(single gang,double gang, - octagon,or 4"square) •Single screw mounting cae ® •Indoor only MU •Low current draw The SL-1224 Strobe Series provides a wide range of candela light The SL-1224 utilizes a universal mounting plate that will mount on output options in a single device.The candela settings include a 12 or a single gang,double gang,octagon and 4"square electrical boxes. 24 volt operation for the 15,35 and 60(75 on axis)candela settings The back plate allows the installer to mount the plate and terminate and 24 volt operation for the 15,35,60,75,95 and 110 candela the wire connections.The strobe attaches in a hinge fashion from the settings.The candela setting is displayed through the front window top and is secured by a single mounting screw.The strobe completely and is selectable using a drum wheel.The voltage input can be either covers the mounting back plate,therefore it can be mounted before regulated DC or full wave rectified(FWR) 12 volt or 24 volt with an other trades work is completed and not affect the final look. operating range from 8 to 33V DC.The strobes can be synchronized using a control panel with the Potter(Amseco)sync protocol or a SMD 10-3A sync module. Installation Note:Installation must comply in accordance with applicable standards. ft`rc--iii,- --I.. ,, (gap .r.:-.--.4c„.,)-(1111;p/44 ihali OPTIONAL SQUARE �` % .�, O OunEr eox k- . 5 e \ Op • rj , • `� \ �'` _O Cf Select A Swtt h 15 Clear Lens Ordering Information Stock Number Model Number Description Color 4560060 SL-1224R Selectable strobe only Red .. 4560061 SL-1224W Selectable strobe only White Potter Electric Signal Co.,LLC•St.Louis,MO•Cust Service:866-240-1870•Tech Support:866-956-1211• Canada 888-882-1833•www.pottersignal.com PRINTED IN USA MKT.#8910002-REV D PAGE 1 OF 2 7/10 13 SL-1224 SERIES P POTTER WALL MOUNT • The Symbol of Protection SELECT-A-STROBE Wiring Diagram Dimensions:inches(mm) Wiring Observe Polarity Use both terminals(or Lead)for connection.Break wire run to provide electrical supervision. / Strobe Only 4-111—■" 1 -kl- Control SL-1224 To Next Nate ^ Panel SL-1224W ar 7 �! + - CSL-1224W �' End-of eRe € _;// a/ `r0 i POWER I-- 1 0 0 0 0 r-' 3112„ DWGa 89100024 )a. e,+F:^:td f i rY%t x� 1F ,7%W, 4'',,Xitait8 ,..E-I— il S � : '£i K 'Sdeo4 High voltage may be present inside the light assembly even though power is not - connected.If access to the coponent board is required(removal or replacement),the capacitor must be discarged by touching a wire to both ends of the flashtube. DO NOT attempt to touch or move the assembly until the capacitor has been discharged. Specifications Light output in precentage when measured from the following Strobe Current directions per UL 1971. Light Max.RMS Operating Current(mA RMS) Wall and ceiling mount horizontal dispersion - Output - Ceiling mount vertical dispersion Degrees %of Raring Reg.12 VDC Reg.12 FWR Reg.24 VDC Reg.24 FWR tight Horizontal vertical ISed 115 151 61 99 9 9 0 100 100 6-25 90 90 35cd 208 265 101 151 30 75 90 35 75 85 60/75cd 253 256 131 189 4 Il&45 40 76 48 75cd NA NA 145 207 a 45 75 34 95cd NA NA 176 242 Wall mount verricaldlsper Ion 555 446 22 I10cd NA NA 196 267 �W6t ��[' 80 40 18 55 35 1e Note:All current draw shown is worst case. 70 36 15 76 30 13 90 i 30 12 85-90 1 Voltage I2/24V 26 12 Floor UL Designation Regulated 12 DC'FWR Regulated 24 DC/FWR Imo, Operating Voltage Range 8-17.5V 16-33V I a? Flash Rate 60 timesimin. gS� `� �? Sync Module(SMDIO-3A) NA I Available qty WU* Operating Temperature Range 32°F to 120°F(0°C to 49°C) s +Fria Engineering Specifications R� The installer shall provide and install the Potter SL-1224 selectable The strobe shall utilize a mounting plate that allows the installer to strobe.The strobe shall have six(6)candela settings.The candela pre-wire the mounting plate.The mounting plate shall be universal settings shall be selectable using a drum roller and shall display the and mount on a single gang,double gang,octagon or 4 inch square candela setting on the front of the device.The strobe shall operate box.The mounting plate shall be completely covered by the strobe at 12 or 24 VDC regulated or full wave rectified.The strobe shall and shall be secured by a single screw.The strobe shall be UL listed have an operating range between 8 and 33 VDC.The strobes can to standard 1638,General Signaling,and standard 1971,Signaling be synchronized using a control panel with the Potter(Amseco)sync Devices for the Hearing Impaired.In addition,the strobes shall be protocol or a SMD10-3A sync module. cUL listed to CAN-ULC S526. PRINTED IN USA MKT.#8910002-REV D PAGE 2 OF 2 7/10 14 P POTTER SH-1224 SERIES WALL MOUNT ® The Symbol of Protection SELECT-A-STROBE/HORN® •UL and cUL listed • 12 VDC with 15,35 or 60 cd setting •24 VDC with 15,35,60,75,95 or 110 cd settings f •6 distinct candela settings _ •Candela selection view window _ •• 15/75 ADA compliant on 60cd setting t •33 sound output settings 4, \ iii •Horn or chime sound output •Pre-wire back plate - •Universal back plate mounting(single gang,double gang, octagon,or 4"square) •Single screw mounting •Indoor only L AEl •Low current draw The SH-1224 Strobe/Horn Series provides a wide range of candela The voltage input can be either regulated DC or full wave rectified light output options in a single device.The candela settings include a (FWR) 12 volt or 24 volt operation with an operating range from 8 to 12 or 24 volt DC operation for the 15,35 and 60(75 on axis)candela 33 V DC.The strobes can be synchronized using a control panel with settings and 24 volt DC operation for the 15,35,60,75,95 and 110 the Potter(Amseco)sync protocol or a SMD10-3A sync module. candela settings.The candela setting is displayed through the front The SH-]224 utilizes a universal mounting plate that will mount on a window and is selectable using a drum wheel. single gang,double gang,octagon and 4"square electrical boxes.The The horn settings include Temporal,Non-Temporal,March Time back plate allows the installer to mount the plate and connect the wire and a Chime sound.The horn also has Low,Mid and High volume connections.The strobe attaches in a hinge fashion from the top and is settings for each pattern and tone.The tones include 2400 Hz,Electro- secured by a single mounting screw.The strobe completely covers the Mechanical,Broadband and Chime. mounting back plate,therefore it can be mounted before other trades work is completed and not affect the final look. - Installation ,_C —' Ai\ A CAUTION � �„ +ii A Atumper plug is provided to test for correct ��Ii �i wiring in the supervisory mode only.Do not �� / \� � pass alarm current through the jumper. OPTIONAL � � i.. `� oounEr sox \ ��� �' p v ` � 0,� . 110 ��0 � , \ ii 75 n l 35 Plate O Select-A-Switch Clear Lens Note:Installation must comply in accordance with applicable standards. Ordering Information Stock Number Model Number Description Color 4560070 ' SH-1224R Selectable strobe/horn/chime Red 4560071 SH-1224W Selectable strobe/horn/chime White • Potter Electric Signal Co.,LLC•St.Louis,MO•Cust Service:866-240-1870•Tech Support:866-956-1211•Canada 888-882-1833•www.pottersignal.com 1 PRINTED IN USA MKT.#8910004-REV F PAGE I OF 4 7/10 15 SH-1224 SERIES P POTTER WALL MOUNT The Symbol of Protection SELECT-A-STROBE/HORN® Dimensions:inches(mm) Light output in precentage when measured from the following directions per UL 1971. Wall and mount ceiling mount ision horizontal dispersion Calling nrount verlir�dispersion Degrees %of Rating Horizontal Vedic 90 90 0 100 100 ,I, 5-26 75 90 ea 90 75 90 45 40 76 46 e \I 45 75 34 0 50 55 27 1 Wall mount mortise,dispa�On 56 45 22 L 60 40 18 __�-r' 65 35 16 70 35 15 75 5(127) \ ea 30 13 80 30 12 85-90 26 , 12 -7:1: 9 Roo \ � - ¢ � i Iii yn AWARNING High voltage may be present inside the light assembly even though power is not connected.if access to teh coponent board is required(removal or replacement),the capacitor must be - discarged by touching a wire to both ends of the flashtube. DO NOT attempt to touch or move the assembly until the capacitor has been discharged. Specifications Horn Dipswitch ON Strobe Current Pattern 0 0 0 0 0 0 0 0 Light Max.RMS Operating Current ImA RMS) I ON-Non-temporal Output Reg.12 VDC Reg.12 FWR Reg.24 VDC Reg.24 FWR 1 2 3 4 5 6 7 8 g a g 1 OFF Temporal I Sod 116 152 62 99 Both 2=OFF 35cd 209 267 102 152 l and 2 ON=March Time 60/75cd 254 258 131 190 Tone 75cd NA NA 146 208 3 and 4 ON=2400Hz 95cd NA NA 177 243 3 ON and 4 OFF=Electromechanical I 10cd NA NA 196 268 3 and 4 OFF=Chime Voltage 12/24v 3 OFF and 4 ON=Broadband UL Designation Regulated 12 DC/FWR Regulated 24 DC/FWR Volume Operating Voltage Range 8-I7.5V 16-33V 5 and 6 ON=High Flash Rate 60 times/min. 5 ON and 6 OFF=Mid Sync Module(SMDIO-3A) NA I Available 5 and 6 OFF=Low Operating Temperature „ 7 and 8 ON=Horn/strobe on 2 wires Range Indoor model:3_ F to 120°F(0°C to 49°C) 7 and 8 OFF=Horn and strobe on 4 wires . Note:To determine total current draw,add desired strobe setting and horn selection.Refer to the installation instructions for further information. i PRINTED IN USA MKT.#8910004-REV F PAGE 2 OF 4 7/10 16 P POTTER SH-1224 SERIES WALL MOUNT • The Symbol of Protection SELECT-A-STROBE/HORN* Non-Temporal Horn Current Max.RMS Current dBA Reverberant Ratings per dBA Anechoic Ratings per Pattern Volume (mA RMS Current) UL464(dBA r 10 ft.) CAN/ULC S525(dBA a 10 ft.) Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC High 119 87 87 87 99 100 2400 Hz Mid 44 28 82 82 94 96 Low 30 18 79 80 92 92 Iligh 118 81 86 87 100 100 Electro-Mechanical Mid 43 26 82 84 96 97 Low 27 16 79 80 93 93 High 146 78 86 86 101 102 Broadband Mid 41 26 81 82 96 98 Low 28 16 77 79 94 95 High 27 21 70 70 86 86 Chime Mid 11 8 62 62 79 80 Low 9 7 58 57 75 75 Temporal Horn Current Max.RMS Current dBA Reverberant Ratings per dBA Anechoic Ratings per Pattern Volume (mA RMS Current) UL464(dBA(a r'10 R.) CAN/ULC S525(dBA(n 10 ft.) Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC High 124 87 82 82 100 100 2400 1Iz Mid 46 30 77 79 95 96 Low 30 18 74 75 92 92 - High 114 80 83 82 100 101 Elector-Mechanical Mid 42 27 78 80 95 96 Low 28 16 75 76 93 93 High 151 80 82 82 101 102 Broadband Mid 45 26 77 78 97 98 Low 30 16 75 76 94 95 High 29 21 68 70 86 86 Chime Mid 10 9 61 61 79 79 Low 9 8 55 55 75 76 March Time Horn Current Max.RMS Current dBA Reverberant Ratings per dBA Anechoic Ratings per Pattern Volume (mA RMS Current) UL464(dBA(ii)10 ft.) CAN/ULC S525(dBA(F 10 11.1 Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC Reg 12 VDC Reg 24 VDC High 121 92 83 84 99 100 2400 Hz Mid 47 31 79 81 95 96 Low 36 19 76 77 92 92 High 114 86 83 83 100 100 Electro-Mechanical Mid 42 27 80 81 95 96 Low 30 19 77 77 92 93 High 153 77 83 84 101 102 Broadband Mid 42 28 79 80 97 98 Low 29 16 76 77 94 95 PRINTED IN USA MKT.#8910004-REV F PAGE 3 OF 4 7/10 17 P 1-,0. TFER SH-1224 SERIES WALL MOUNT . e The Symbol of Protection SELECT-A-STROBE/HORN® Wiring Diagram Wiring Observe Polarity Use both terminals(or Lead)for connection.Break wire run to provide electrical supervision. Horn I Strobe Signal Operate Independently F.A.C.P. SH-1224 F.A.C.P. SH-1224WP - To Next Device Strobe Signal Horn Signal SH-24 a Circuit Circuit CSH-1224W op- - End-of-Line-Resistor + - + - 'DIP SW setting • sw7,sw8=OFF STROBE HORN To Next Device Of f + - �'- End-of Line Resistor E LL I , i Horn/Strobe Wiring Diagram for Audible Strobe Class`B` Circuit SH-1224 with Audible Silence Feature. (SH-1224,SH1224W) SH-1224WP F.A.C.P. F.A.C.P. Sync Module SMD1O-3A SH-24 To Next Device Strobe Signal Horn Signal `DIP SW setting or Circuit Circuit INPUT OUTPUT ' �.. sw7,sw8=oN End-of-Line Resistor + - + - H+ H + - + - i ! I ? i POWER + + - i 0 0 0 0 0 1 1 1 . i < Horn or Strobe Wiring Diagram for Audible Strobe Class `B` Circuit without Audible Silence Feature. . i i Sync Module SMD10 3A To Next Device F.A.C.P. INPUT or Signal Circuit End-of-Line-Resistor I OUTPUT toilitIlP , 1 POWER + + - [ 00000 Refer to the SMD 10-3A Sync Module instruction manual for Class'A`wiring or other application diagrams. DWGB 8910004-1 Engineering Specifications The installer shall provide and install the Potter SH-1224 selectable the Potter sync protocol or the SMD10-3A sync module.The strobe strobe/hom.The strobe shall have six(6)candela settings.The shall utilize a mounting plate that allows the installer to pre-wire the candela settings shall be selectable using a drum roller and shall mounting plate.The mounting plate shall be universal and mount on a display the candela setting on the front of the device.The horn shall single gang,double gang,octagon or 4 inch square box.The mounting have 33 selectable settings configurable by dip switches.The sounder plate shall be completely covered by the strobe and shall be secured shall be capable of ANSI Temporal Code 3,March Time and produce by a single screw.The strobe shall be UL listed to standard 1638, a chime output.The horn shall have three distinct volume levels. General Signaling,and standard 1971,Signaling Devices for the The strobe/hom shall operate at 12 or 24 VDC regulated or full wave Hearing Impaired.In addition,the strobes shall be cUL listed to CAN- - rectified.The strobe/horn shall have an operating range between 8 and ULC S526.The horn shall be UL listed to standard 464,Audible 33 VDC.the strobes an by synchronized using a control panel with Signaling Devices. PRINTED IN USA MKT.#8910004-REV F PAGE 4 OF 4 7/10 18 Aero- FIRE SUPPRESSION SYSTEMS • at PATENTED Features • Significantly more effective than alternative extinguishing agents • Environmentally friendly-Ozone depletion potential (ODP) = 0, No global warming potential • Ease of installation - no pressure vessels, piping, or expensive installation manpower • Very low maintenance • Provides reliable, cost effective protection for a wide range of fire hazards • Tested and Listed to UL Standard 2127 • Favorably reviewed by EPA for SNAP listing • Suitable for enclosed facilities and local applications • Safe for personnel - non-harmful to personnel at design application rates • Safe for valuable equipment-will not harm electronic equipment or magnetic media • Post fire cleanup is minimal-aerosol suspends in air for quick and easy venting after discharge • Compact - up to a 90% reduction in space and weight requirements Applications Due to their fast response time, low fire extinguishing concentration, and environmental safety, Aero4< fire suppression systems may be used in critical applications across a wide range of industries. Aerosol generators are currently protecting and are suitable for use in: -Telecommunications facilities - Flammable liquid storage areas - Process control rooms -Turbine and generator enclosures - PABX rooms - Marine engine rooms and machinery spaces - High value mobile equipment - Power plants - Cellular sites and relay towers - Small boats - Data processing facilities - General industrial hazards Operation/Description Upon detection of a fire, Aero-e generators can be activated either manually or automatically from a suitable listed releasing device. All auxiliary system components (release panel, detection, remote pull stations, etc.) are listed/approved by UL, ULC, FM, New York City MEA, and California State Fire Marshall. Upon activation, the generators produce an exceptionally effective, ultra-fine, potassium based aerosol. Unlike gaseous systems, Aero-K°aerosol generators are very cost effective to install and maintain - as they do not require the pressure vessels, piping or expensive installation costs associated with other extinguishing systems. Space and weight requirements are minimal. On an agent weight basis, Aero-K°aerosol is ten times more effective than gaseous agent alternatives. The Aero•K° generator's effectiveness is a function of its patented design, aerosol composition, and ultra-fine particle size. Fire suppression is rapidly achieved through interference between the ultra-fine aerosol particulate and the flame's free radicals - terminating propagation of the fire.Aero-K•aerosol generators are virtually maintenance free and have a shelf life of over 10 years. This, coupled to their very low installation cost, makes them an extremely cost effective fire protection solution. 19 Aero-IC - FIRE SUPPRESSION AEROSOL GENERATORS 1 - General Specifications: Parameter G-100 G250 6-500 6-1000 G1500 G2500 Aerosol Mass(kgj,llos) .10 .22 .25 .55 .50 1.10 1.00 2.20 1.50 3.3 2.50 5.50 Ship.Wt./unit packaging[kgb its] 1.44 .32 2.72 6.0 3.63 8.0 7.05 15.5 8.60 19.0 11.33 25.0 Length(rnm),(in) 121 4.8 150 5.9 180 71 170 6.7 203 8.0 267 10.5 Diameter[mm),lin) 76 3.0 127 5.0 127 5.0 _ 203 8.0 203 8.0 203 8.0 Discharge Time(sec) 12.0 12.0 23.0 16.0 23.0 36.0 Initiation Current lamp) Parallel 0.5 0.5 0.5 0.5 0.5 0.5 Series 1.0 1.0 1.0 1.0 1.0 1.0 Pulse Duration(miiisecond) 50 50 50 50 50 50 Max.Supervisory Current[Amp] s.005 s.005 s.005 <_.005 <_.005 s.005 Coverage Parameters: Model Part Maximum Maximum Area Coverage Maximum Mounting Number Volume Coverage B/C Height (ml (ft') (m) (ft) (m) [ft] 6-100 11740 1.62 5721 2.18 x 2.18 720 x 720 2.50 8.20 6-250 11710 4.04 142.7 2.44 x 4.88 8.00 x 16.0 4.50 14.7 -1110•G-500 11690 8.08 285.3 4.88 x 4.88 16.0 x 16.0 4.50 14.7 6-1000 11770 16.2 572.1 4.88 x 4.88 16.0 x 16.0 4.88 16.0 6-1500 11800 24.2 854.6 4.88 x 4.88 16.0 x 16.0 4.88 16.0 • 6-2500 11850 40.4 1426.7 4.88 x 4.88 16.0 x 16.0 4.88 16.0 For additional information on use of AeroK®systems,please contact your local Distributor or Sensor Electronics Corporation. Operation/Storage Parameters: Temperature -54°C to +54° C (-65° F to +130° F) Relative Humidity up to 98%at +35°C(+95° F) Transportation Classification: • Classification Code: 1.4S _ISTED • UN Identification #: UN 0432 • Packaging Group: PGII • Shipping Limitations: -Ground: None - Max. weight per unit packaging - Cargo Air 100 kgs [220 Ibs) - Max. weight per unit packaging- Passenger Air 25 kgs (55 Ibs) ■ Aero-eis a registered trademark.Manufactured in the USA and sold worldwide exclusively by Sensor Electronics Corporation under license from R-Amtech,International Sensor Electronics Corporation BE 5500 Lincoln Drive, Minneapolis, Minnesota 55436 USA Toll Free: 800.285.3651 • Tel: 952.938.9486 • Fax: 952.938.9617 SENSOR www.sensorelectronic.com ELECTRONICS Made in the USA. Sensor Electronics and its Fire Combat Division also specialize in a wide range of custom fire suppression and gas detection products to meet a wide range of unique and OEM requirements Call our Toll Free number to discuss your specific requirements with one of our professionals. 20