Loading...
Specifications RECEIVED - - APR 3O 13 a G System Power Requirements Fell iliST0.UM'ENT$ 7100 Fire Alarm Control Panel with Broadband CITY OFTIGA RD �M�•ri••• !�(Jff flmr f \J'SlON Protected Premises: FMC SCHOLLS FERRY Date: 4/25/2013 Address: 10300 SW NIMBUS AVE City: PORTLAND State: OR Zip: 97223 Prepared By: SCOTT SULLIVAN ADVANCED ALARM SYSTEMS Phone: 503 - 290 -4091 Address: 1030 NW CORPORATE DRIVE Email: City: TROUTDALE State: OR Zip: 97060 Secondary Load Requirements I 5.56 I Amp Hours Total Seconda Load from the calculation table below. Current Draw I I Time (hours) Total (AH) Secondary Standby Load Required Standby Time 0.188 A 24 hours 4.51 Secondary Alarm Load Required Alarm Time (hours) 1.473 A x 0.084 hours 0.12 Total Secondary Load 4.64 Derating factor x 1.2 Secondary Load Requirements 5.56 AH Battery Selection I 7.00 I Amp Hours Select batteries from the list below. 7.0 AH Battery (12 volt) 1 Battery Distribution Chart Shows amp -hour distribution of your selections. P .Spare Battery Capacity Secondary Alarm Load 2% ED Secondary Standby Load Spare Battery Capacity ❑ Secondary Alarm Load 21% WW Secondary Standby Load 77% Spare Battery y Standby 1.44 Amp Hours Secondary ry nda Stann L dby Load 5.42 Amp Hours Secondary Alarm Load 0.15 Amp Hours 2 D/ o0oC6 • Cliii:EO:Y-T;i°‘"1,4\9! Syste C urrent Draw 7100 Serie Control Panel with Br oadband by mmbeywaai I Total Standby I 0.188 A I Total Alarm 1.473 A I Standby Current I Alarm Current Device Qty Draw Standby Qty Draw Alarm 1. System (Please only select one) Basic System Module, 2 SLC 0 x 0.06500 0 x 0.08500 Basic System Module, 1 SLC with DACT 1 x 0.07500 0.07500 1 x 0.09500 0.09500 Basic System Module, 2 SLC with DACT 0 x 0.08500 0 x 0.10500 2. 7100 Optional Modules Optional Remote Serial Annunicator (LCD -7100) I 2 I x ! 0.05000 f 0.10000 I 2 I x I 0.07500 I 0.15000 6. Addressable devices Addressable Smoke Detector 39 x 0.00030 0.01170 39 x 0.00650 0.25350 Addressable Input Module 2 x 0.00038 0.00075 2 x 0.00060 0.00120 Addressable Relay 2 x 0.00030 0.00060 2 x 0.00030 0.00060 Addressable Pull Station 2 x 0.00000 0.00000 2 x 0.00000 0.00000 7. Notification Appliances CKT. 1 1 x 0.00000 0.00000 1 x 0.52400 0.52400 CKT. 2 1 x 0.00000 0.00000 1 x 0.44900 0.44900 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 Total Standby 0 A Total Alarm 1 .4 73 A Load: Load: This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name FMC Scholls Ferry CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date 3/21/2013 1 Circuit Number 1 Totals Voltage Totals Voltage Totals Voltage Area Covered Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.524 240 0.44 0.524 240 0.772 0.524 240 0.386 Minimum Device Voltage 16 End of Line Voltage 19.96 End of Line Voltage 19.63 End of Line Voltage 20.01 Total Circuit Current 0.524 Wire Ohm's Percent Drop 2.16% Percent Drop 3.79% Percent Drop 1.89% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st devic' 25 14 3.07 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit 14 3.07 18 =7.77 16 =4.89 14 =3.07 12 =1.98 10 =124 Enter current in amps. Distance 18-14 Awg = Solid Conductors 12-10 Awg = Stranded Conductors .150 = 150 ma from Voltage Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.060 25 20.32 0.080 0.39% the manufactures listed minimum operating voltage (IE: rated operating voltage 20 -32 VDC). Device 2 0.159 55 20.16 0.237 1.16% Device 3 0.0571 451 20.08 0.321 1.58% Device Manufacturer [Wheelock Device Manufacturer 'Wheelock Device 4 0.057 25 20.04 0.359 1.76% Current Current Device 5 0.022 35 20.00 0.401 1.96% Chime Strobe @Rated Strobe Only @Rated Device 6 0.109 30 19.97 0.432 2.12% Model # Candela Voltage Model # Candela Voltage Device 7 0.060 25 19.96 0.441 2.16% CH70 -24MCW 15 0.022 ST 15 0.057 END 19.96 0.441 2.16% 30 0.06 30 0.085 END 19.96 0.441 2.16% 75 0.109 75 0.135 END 19.96 0.441 2.16% 110 0.14 95 0.163 END 19.96 0.441 2.16% CH90 -24MCC 95 0.159 110 0.182 END 19.96 0.441 2.16% 135 0.205 END 19.96 0.441 2.16% 177 0.253 END 19.96 0.441 2.16% 185 0.253 END 19.96 0.441 2.16% END 19.96 0.441 2.16% END END 19.96 0.441 2.16% 19.96 0.441 2.16% END 19.96 0.441 2.16% END 19.96 0.441 2.16% Totals 0.524 240 End of Line Voltage 19.96 This calculator provided voltage drop calculations in three formats (Point to Point, End of Line, and Load Centering). Make sure that you know what method is accepted by, and the results do not exceed the limits set by the respective jurisdiction Point to Point Method End of Line Method Load Centering Method Project Name FMC Scholls Ferry CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS CIRCUIT IS WITHIN LIMITS Date 3/21/2013' Circuit Number 2 Totals Voltage Totals Voltage Totals Voltage Area Covered Current Distance Drop Current Distance Drop Current Distance Drop Nominal System Voltage 20.4 0.449 173 0.27 0.449 173 0.477 0.449 173 0.238 Minimum Device Voltage 16 End of Line Voltage 20.13 End of Line Voltage 19.92 End of Line Voltage 20.16 Total Circuit Current 0.449 Wire Ohm's Percent Drop 1.33% Percent Drop 2.34% Percent Drop 1.17% Gauge Per 1000 End of Line and Load Centering Methods use only the wire guage for the first device to source Distance from source to 1st devicl 3 14 3.07 Standard Wire Resistance in Ohms per 1000 feet. Wire Gauge for balance of circuit 14 3.07 18 =7.77 16 =4.89 14 =3.07 12 =1.98 10 =1.24 Enter current in amps. Distance 18 -14 Awg = Solid Conductors 12 -10 Awg = Stranded Conductors .150 = 150 ma from Voltage Notes: Device Device previous At Drop from Percent Wire resistance is doubled in the calculations for two wires (Positive and Negative) Number Current device Device source Drop The voltage calculated to the last device in any method must not be lower then Device 1 0.022 3 20.39 0.008 0.04% the manufactures listed minimum operating voltage (IE: rated operating voltage 20 -32 VDC). Device 2 0.060 40 20.29 0.113 0.55% Device 3 0.057) 101 20.26 0.136 0.67% Device Manufacturer 'Wheelock Device Manufacturer 'Wheelock Device 4 0.057 20 20.23 0.174 0.85% Current Current Device 5 0.022 5 20.22 0.182 0.89% Horn Strobes @Rated Strobe Only @Rated Device 6 0.057 20 20.19 0.210 1.03% Model # Candela Voltage Model # Candela Voltage Device 7 0.057 40 20.15 0.253 1.24% CH70 -24MCW 15 0.022 ST 15 0.057 Device 8 0.060 20 20.13 0.267 1.31% 30 0.06 30 0.085 Device 9 0.057 15 20.13 0.272 1.33% 75 0.109 75 0.135 END 20.13 0.272 1.33% 110 0.14 95 0.163 END 20.13 0.272 1.33% 110 0.182 END 20.13 0.272 1.33% 135 0.205 END 20.13 0.272 1.33% 177 0.253 END 20.13 0.272 1.33% 185 0.253 END 20.13 0.272 1.33% END 20.13 0.272 1.33% END 20.13 0.272 1.33% _ END 20.13 0.272 1.33% END 20.13 0.272 1.33% END 20.13 0.272 1.33% Totals 0.449 173 End of Line Voltage 20.13 • Gammen 7100 Series SO FIRE CONTROL INSTRUMENTS by Honeywell Compact Analog Addressable Description Fire Alarm Control Panel The Gamewell -FCI 7100 Series fire alarm control panel is a multi processor- based, analog addressable system. The control panel is a compact, yet expandable, platform. Intended for commercial, industrial and institutional instal- lations, the 7100 Series is ideal for life safety and property protection fire alarm applications. The basic 7100 Series control panel provides one (1) or two (2), analog addressable Signaling Line Circuits (SLCs). Each SLC supports up to ninety -eight (98) analog address- able sensors, as well as up to ninety -nine (99) addressable ". monitor modules and /or control points. With 197 addresses available on the 7100 -1 and 394 addresses available on the 7100 -2. The 7100 uses an advanced protocol that 7100 Series ensures an almost instant response to events while at the Features same time suppressing nuisance alarms. Listed per ANSI /UL 864 9th Edition • The system may be programmed with either the • 120 or 240 VAC (optional) input line voltage Windows -based Field Configuration Program (FCP -7100) • Front panel programming with day /night sensitivity or configured through a comprehensive set of intuitive, adjustments secure password protected front -panel programming • 80- character alpha- numeric display options. This important feature allows the system to quickly • adapt to any future requirements due to changes in occu- One or two Style 4 (Class "B ") signaling line circuits. pancies, building remodels, or other contingencies. Style 6 (Class "A ") with optional CAOM Module • Two Style Y (Class "B ") regulated notification appliance The sophisticated circuitry and powerful analog software enables the 7100 Series fire alarm control panel to read the circuits rated for 1.5 amp. each. Style Z (Class "A ") with specific sensitivity level of each sensor and compensate for optional CAOM Module changes due to age, dust accumulation or other environ- • Suitable for pre - action deluge applications with optional mental factors. The 7100 incorporates the Gamewell -FCI MCOM Module Listed Integrated Sensitivity Testing (LIST) which meets • Periodic trouble reminder NFPA 72 sensitivity testing and maintenance requirements. • Individual sensor drift compensation The LIST testing allows substantial savings in both mainte- nance and service while eliminating nuisance alarms. • Dual -stage maintenance alerts ( "dirty" and "very dirty ") • Multilevel sensor sensitivity adjustments (front panel The Model 7100-1D and 2D features an integral Digital programmable) Alarm Communicator Transmitter (DACT) with all popular continued on the next page transmission formats and a 16 -digit telephone number field. It is 8 -digit Carrier Information Code (CIC) compliant An ISO 9000 -2000 Company and also prevents "dialer- runaway" in the event of intermit- S"G'"'"G tent system faults. The 7100-1D and 2D are UL Listed for 0 FM IVEA LISTED APProved Microsoft Word is a registered trademark of Microsoft Corporation. 51969 3003549 30788.E l am; m 30789-E VOL u =:b, GAMEWELL -FCI 12 Clintonville Road, Northford, CT 06472 -1610 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell -FCI for their use. ©2008 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020 - 0466 Rev. E2 page 1 of 3 • Description (Continued) LDM -7100 The LED Driver Module (LDM -7100) is designed to mount Remote Station, Proprietary, and Central Station fire alarm in a UL Listed remote annunciator and provides outputs for systems. It allows ample space for wiring and room for bat- remote panel switches and thirty -three (33), remote LEDs. teries up to 7 A/H capacity. Three (3), LDM -7100 modules may be installed in a single Features (Continued) annunciator for a total of ninety -nine (99), LEDs per annun- ciator. This combination may be repeated up to five times • Alarm verification per individual sensor for a total of fifteen (15), LDM -7100 panels installed at up to • Positive alarm sequence for sensors or monitor five (5), different locations. Maximum distances of up to modules 4,000 feet (1,219 m) can be achieved using one pair of • Four levels of system access using six (6), digit pass - twisted, non - shielded wire for serial communication and words with up to five (5), user passwords per Level using another pair of straight -lay wire for operating voltage. • Duplicate and extra address indications (For additional information, refer to the LDM -7100 data sheet, Part Number: 9020 - 0519). • March time (60 or 120 BPM) /temporal pattern /coded fours /California Code /user- defined zone coding CAOM • Cross zoning The Class "A" Optional Module (CAOM) allows Style Y and • System configuration programming and 280 event log Z (Class "B" and "A ") operation for both Notification Appli- stored in non - volatile memory ance Circuits and allows Style 4 and 6 (Class "B" and "A ") • Fan restart with sequential restart delay for both Signaling Line Circuits. It also provides disconnect • Upload /download of panel configuration between panel switches for each signaling line circuit and a common dis connect switch for both notification appliance circuits. and FCP -7100 program (password protected feature) • Up to sixty -four (64), 7100 panels in the E3 Broadband MCOM network with an optional INI -7100 Module The Municipal Connection Option Module (MCOM) pro- vides three (3) choices of outputs. It can be configured as a Optional Accessories Municipal Circuit (City Box) output. It may also be set to serve as a Reverse Polarity output with a nominal voltage LCD - 7100 output of 24 VDC at 0.012 amp. maximum alarm and The LCD -7100 remote serial display offers an 80- character supervisory current. The MCOM's third option provides a alphanumeric readout for the remote display of all system releasing solenoid output rated at: events. It duplicates all the information on the 7100 Series • 24 VDC nominal voltage. panel display and provides key switch protected functions 0.005 amp. supervisory current. • such as System Reset, Alarm Acknowledge, Trouble • Acknowledge, Signal Silence, and Drill Test. 0.710 amp. maximum alarm current. • 2 ohms maximum line resistance. LEDs on the LCD -7100 indicate Alarm, Supervisory, Sys- tem Trouble, Power Fault, Systems Silenced, NAC #1, and PTRM NAC #2 Silenced conditions. The Printer Transient Module (PTRM) provides RS -232 Isolator/Transient protection for the 7100's RS -232 port The LCD -7100 can be surface or semi -flush mounted on a (BSM connector J2). It is used in conjunction with a serial standard four -gang electrical box. It can be installed up to printer applied to the RS -232 port for permanent record 4,000 feet (1,219 m) from the main control panel. The 7100 keeping. Series fire alarm control panel supports up to five (5), remote LCD -7100 annunciators using one pair of twisted, 1N1 - 7100 non - shielded 18 AWG min. wire or serial communication The Intelligent Network Interface Module allows the 7100 and uses another pair of 16 AWG min. for operating volt- Series fire alarm control panel to become the platform of a age. peer -to -peer, token ring, self- regenerative network com- (For additional information, refer to the LCD -7100 data prised of up to sixty -four (64), 7100 panels. sheet, Part Number: 9020 - 0486). GAMEWELL -FCI 12 Clintonville Road, Northford, CT 06472 -1610 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 9020 -0466 Rev. E2 page 2 of 3 www.gamewell - fci.com Specifications Ordering Information (Continued) Primary Input Power 120 VAC, 50/60 Hz @ 2.0 amps. Optional Modules or240 VAC, 50 /60Hz @1.0amp. LCD -7100 Remote Serial Annunciator, LCD Output Power 4 amps. @ 24 VDC (total) Display (80 character) Non - resettable Power: 1.0 amp. max. Dimensions: 4.25" H x 8.25" W x 1.90" 1.0 amp. max. from both circuits (43 H x 37 W x 7.7 D cm) Resettable Power: 1.0 amp. max. LDM -7100 Remote LED Driver Module Two (2) Notification Dimensions: 6" W x 4.50" (15.2 x 11.4 cm) Appliance Circuits: 1.5 amp. each @ 24 VDC CAOM Class A Option Combination Module Current: Supervisory Alarm with disconnect switches for both 7100 -1 (One SLC) 0.065 amp. 0.085 amp. signaling line circuits and notification 7100-1D 0.085 amp. 0.105 amp. appliance circuits (One SLC w /DACT) MCOM Municipal Connection Option Module 7100 -2 (Two SLC) 0.065 amp. 0.085 amp. for local energy city box reverse polar - 7100-2D ity signaling, or releasing solenoid (Two SLC w /DACT) 0.085 amp. 0.105 amp. PTRM Printer Transient Module LCD -7100 .012 amp. 023 amp. INI- 7100 -FO Intelligent Network Interface Module, LDM -7100 .012 amp. .023 amp. Fiber Optic (All LEDs lit) INI- 7100 -UTP Intelligent Network Interface Module, INI - 7100 - UTP, -FO 0.040 amp. 0.040 amp. Unshielded, Twisted Pair Operating Replacement Parts Temperature: 32° 120° F (0° 49° C) T -7100 Transformer, 120 VAC input (replace - Relative Humidity: 85 % (non- condensing) ment) Battery Charger T- 7100 -240 Transformer, 240 VAC input (replace- Capacity: 31 A/H (Cabinet accommodates ment) 12 A/H size batteries) BSM- 7100 -1 Replacement board for 7100 -1 Alarm & Trouble BSM- 7100 -1 D Replacement board for 7100-1D Relay Contacts: Form "C ", 2 amps. @ 24 VDC (resistive) Ordering Information Systems Model Description 7100 -1 7100 Addressable System, 1 SLC mounted in enclosure Dimensions: 19 3/8" x 19 3/8" (49 x49 cm) Enclosure 7100-1D 7100 Addressable FACP w /DACT, 1 SLC mounted in enclosure Dimensions: 19 3/8" x 19 3/8" (49 x 49 cm) Enclosure Basic Kits BK- 7100 -2 Basic System Kit, 2 SLC (BSM. Keypad Display, Transformer) BK- 7100 -2D Basic System Kit w /DACT, 2 SLC BK- 7100- 2 -240V Basic System Kit, 2 SLC, 240 VAC BK- 7100- 2D -240V Basic System Kit w /DACT, 2 SLC Cabinets EN -7100 Enclosure (replacement) CS -7100M Metal Door (replacement) 7100 - ENCL -M 7100 Enclosure Dimensions: 16.9" H x 14.4" W x 3" D I (43 H x 37 W x 7.7 D cm) NS -7100B Enclosure, E3 Series Broadband, NS -7100R black Enclosure, E3 Series Broadband, red Dimensions: 19 3/8" H x 19 3/8" W x 4" D (49 H x 49 W x 10 D cm) GAMEWELL -FCI 12 Clintonville Road, Northford, CT 0 64 72 -1 61 0 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 www.gamewell - fci.com 9020 -0466 Rev. E2 page 3 of 3 . . , . . . . , , Gamewell 1100 Series � FIRE C U U MENT U S L LCD -1100 by Honeywell Description Remote Serial LCD Display The LCD -7100 remote serial display provides superior flex- ibility to the 7100 or E3 Series installations. It features an 80- character display which duplicates all the information on the main display with the exception of menus. The LCD -7100 contains the following function keys: w • Alarm Acknowledge • System Reset/Lamp Test • Trouble Acknowledge • System Drill Test • Signal Silence LCD - 7100 A keylock must be placed in the "ON" position to enable the function keys with the exception of the "Trouble Acknowl- Features edge" key which is used to silence the trouble sounder on the LCD -7100. • Listed under UL Standard 864, 9th Edition LEDs on the LCD -7100 are: • Alarm • System Silenced • 80- character alphanumeric LCD display • Supervisory • NAC #1 Silenced • System Trouble • NAC #2 Silenced • Full complement of function keys and LEDs • Power Fault • Remote location up to 3,000 feet (914.4 m) away from the control panel Installation The LCD 7100 can be surface or flush mounted on a stan • • 7100 and E3 Series will accommodate up to five (5), annunciators dard four -gang electrical box and installed up to 3,000 feet (914.4 m) away from the main control. The 7100 or E3 • Surface or flush -mount on a standard four -gang, Series control panels can accommodate up to five (5), electrical box remote LCD -7100 annunciators. • Compact, attractive appearance Specifications Operating Voltage: 24 VDC (nominal) Ordering Information Supervisory Current: .012 amp. Alarm Current: .023 amp. Model Description Absolute Maximum LCD -7100 Remote Serial LCD Display Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 0 to 93% max., non - condensing at 90° F (32° C) An ISO 9000 -2000 Company Dimensions: 8 1/4" L x 4 1/2" H x 1 7/8" D City of (21 x 11 x 4.5 cm) SIGNALING ni Chic ag° C) O MEA ' `; A pp ro � city of . :� P"" . _..i- Class 1 DENVER LISTED APP93VED A S1869 3006578 255-02 -E 73000694231 Class 2 Approved E3 Series is a registered trademark of Honeywell International Inc. High Rse GAMEWELL - FC I 12 Clintonville Road, Northford, CT 06472 -1610 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell -FCI for their use. ©2007 by Honeywell International Inc. All rights reserved. www.gamewell fci.com 9020 -0486 Rev. h1 page 1 of 1 J . . . . . . . . 4.00-04s..... GameweH Velocit� TSeries FC I FIRE CONTROL INSTRUMENTS ASD -PL2F and by Honeywell ASD -PTL2F Description Analog, Addressable Photoelectronic Smoke Sensor The Gamewell -FCI VelocitirM Series, analog addres- sable plug -in smoke sensors with integral communi- .., cation provide features that surpass conventional sensors. Sensitivity can be programmed in the con- trol panel software, and is continuously monitored and reported to the panel. Point ID capability allows each sensor's address to be set, providing exact locations for selective maintenance when the cham- ber contamination reaches an unacceptable level. ASD-PL2F ASD -PTL2F The ASD -PL2F photoelectric sensor's unique optical sensing chamber is engineered to sense smoke pro- Features duced by a wide range of combustion sources. Dual electronic thermistors add 135 °F (57 °C) fixed -tem- perature thermal sensing on the ASD -PTL2F model. • Sleek, low profile design. The VelocitiTM Series use a communication protocol • Visual rotary, decimel switch addressing (01 - 159). that substantially increases the speed of communica- • Built - in functional test switch activated by an external tion between the sensors and certain Gamewell -FCI magnet. analog addressable fire alarm controls. These • Bicolor LEDs flash green whenever the sensor is devices operate in a grouped fashion. If one of the addressed, and light steady red on alarm*. devices in the group has a status change, the panel's • microprocessor stops the group poll and concen- relay, isolator, or sounder bases. trates on the single device. The net effect is a • Low standby current. response speed up to five times greater than earlier • Analog addressable communication. designs. • Stable communication technique with noise immunity. • Optional remote, single -gang LED Indicator (RA400Z). Ordering Information • Suitable for installation in ducts. • Compatible with Gamewell -FCI analog addressable Model Description ASD -PL2F Analog, addressable photoelectronic panels. smoke sensor Note: *Only the red LED is operative in panels that do not operate ASD -PTL2F Analog, addressable photoelectronic smoke in VelocitiTM mode. sensor with thermal sensing An ISO 9001 -2000 Company SIGNALING ®MEA LISTED APPROVED Approved 51913 3023594 219.02- EVo1.V1 07272.0694:263 GAMEWELL -FCI 12 Clintonville Road, Northford, CT 06472 -1653 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 S p ec ifications are for information only, are not intended for installation purposes and are su to ch without notice. No responsibility is assum b Gamew -FCI for their use. ©2006 Honey International Inc. All rights reserved. WWW.gamewell- fci.com 9020-0617 Rev. E page 1 of 2 J • Specifications Installation Size: 2.1" (5.1 cm) high x 4.1" (10.4 cm) diameter ASD -PL2F plug - sensors use a separate base to installed in 8501 base, 6.1" (15.5 cm) diameter installed in ADB -FL base. simplify installation, service, and maintenance. A Shipping weight: 5.2 oz. (147 g) special tool allows maintenance personnel to plug -in Operating and remove sensors without using a ladder. temperature: ASD - PL2F: 32° F to 120° F (0° C to 49° C) Mount the base on a box which is at least 1.5" (3.8 cm) ASD PTL2F: deep. Suitable mounting base boxes include: 32° F to 100° F (0° C to 38° C) UL- Listed • 4.0" (10.2 cm) square box. velocity range: 0 -4000 ft. /min. (1,219.2 m /min.), • 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box. suitable for installation in ducts. • Single -gang box (except relay or isolator bases). Relative • With 8501 BH or B501 BHT base, use a 4.0" (10.2 cm) humidity: 10 - 93% (non- condensing) Thermal ratings: Fixed - temperature setpoint square box. 135° F (57° C) • With B224RB or B224BI base, use a 3.5" (8.9 cm) octag- onal box, or a 4.0" (10.2 cm) octagonal or square box. Electrical Specifications NOTE: Because of the inherent supervision provided Voltage range: 15 - 32 volts DC peak by the SLC, end -of -line resistors are not required. Standby current: (max. avg.): 300 pA @ 24 VDC Wiring "T- taps" or branches are permitted for Style 4 (one communication every 5 (Class "B ") wiring. seconds with LED enabled) Maximum alarm Sensor Spacing current: 6.5 mA OP 24 VDC (LED) lit). Gamewell -FCI recommends spacing sensors in com- pliance with NFPA 72. In low airflow applications with Bases and Options smooth ceilings, space sensors 30 feet (9.1 m). For specific information regarding sensor spacing, place ADB - FL: 6.1" (15.5 cm) diameter ment and special applications, refer to NFPA 72. B501: 4.1" (10.4 cm) diameter B501 BH or Sounder base assembly (B501 BHT B501 BHT: produces a temporal pattern). Includes B501 base. B224RB Relay Base: Screw terminals: Up to 14 AWG (2.0 mm Relay type: Form -C Rating: 2.0A @ 30 VDC resistive; 0.3 A © 110 VDC inductive; 1.0 A ® 30 VDC inductive. Dimensions: 6.2 "x 1.2" (15.7 x 3.0 cm) Maximum: 25 devices between isolator bases. RA400Z Remote alarm indicator, LED. BCK -200 Black detector covers (box of 10). GAMEWELL -FCI 12 Clintonville Road, Northford, CT 06472 -1653 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 9020 -0617 Rev. E page 2 of 2 www.gamewell - fci.com • E . ,„ Velociti® Series Gamewell F CONTROL INIRE STRUMENTS ATD -L2F, ATD-H12F by Honeywell Description Addressable Thermal Sensor The Gamewell -FCI Velociti Series, addressable plug -in thermal sensors with integral communication provide fea- tures that surpass conventional sensors. Point ID capabil- ity allows each sensor's address to be set, providing exact locations for pinpointing alarm locations and for selective maintenance. ATD thermal sensors use an innovative ther- mistor sensing circuit to produce 135 °F /57 °C fixed- temper - ature (ATD -L2F). The ATD -RL2F provides a combination 15° /minute rate -of -rise with 135° fixed thermal detection that is included in a low - profile package. The ATD -HL2F provides fixed high- temperature detection at 190 °F /88 °C. These thermal sensors provide cost- effective, addressable property protection in a variety of applications. ATD - L2F The Velociti Series uses a communication protocol that substantially increases the speed of communication between the sensors and Gamewell -FCI analog address- Features able fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel's microprocessor stops the group poll and concentrates on the single device. The net effect • Sleek, low - profile design is response speed up to five times greater than earlier designs. • Visual rotary switch addressing • Built -in functional test switch activated by an external Installation magnet ATD plug -in sensors use a separate base to simplify instal- • Bicolor LEDs flash green whenever the sensor is lation, service, and maintenance. A special tool allows maintenance personnel to plug -in and remove sensors addressed, and light steadily red on alarm* without using a ladder. • Optional relay, isolator, or sounder bases • Mount the base on a box which is at least 1.5" (3.8 cm) Low standby current deep. Suitable mounting base boxes include: • Addressable communication • 4.0" (10.2 cm) square box. • Stable communication technique with noise immunity • 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box. • Optional remote, single -gang LED accessory • Single -gang box (except relay or isolator base). • With B501 BH or 8501 BHT base, use a 4.0" (10.2 cm) (RA-400Z) square box. • Suitable for installation in ducts • With B224RB or B224B1 base, use a 3.5" (8.9 cm) Note: "Only the red LED is operative in panels that do not operate octagonal box, or a 4.0" (10.2 cm) octagonal or square in Velociti mode. box. NOTE: Because of the inherent supervision provided by the SLC, end -of -line resistors are not required. Wiring "T- An ISO 9000 -2000 Company taps" or branches are permitted for Style 4 (Class "B ") P y wiring. SIGNALING Velociti and E3 Series are registered trademarks of Honeywell U u International Inc. ® ® MEA UL is a registered trademark of Underwriters Laboratories Inc. LISTED APPROVED Approved rim• 52332 3023594 21942•EVoLVI 07270-0694:256 GAMEWELL -FCI 12 Clintonville Road, Northford, CT 06472 -1610 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell -FCI for their use. ®2008 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020 - 0620 Rev. C3 page 1 of 2 • • • Specifications Specifications Size: 2.1" (5.3 cm) high x 4.1" (10.4 cm) Bases and Options diameter installed in B501 base, ADB -FLF 6.1" (15.5 cm) diameter standard base 6.1" (15.5 cm) diameter installed in B501 4.1" (10.4 cm) diameter flangeless base ADB -FLF base 8501 BH or Sounder base assembly (B501 BHT Shipping Weight: 4.8 oz. (137 g) B501BHT produces a Temporal Pattern) includes Operating B501 base Temperature: B224RB ATD -L2F or Relay Base Up to 14 AWG (2.0 mm2) ATD -RL2F —4° F to 100° F ( -20° C to 38 °C) Relay type: Form -C ATD -HL2 —4° F to 150 °F ( -20 C to 66 °C) Rating: Sensor Spacing: UL approved for 50 ft. (15.2 m) 2.0A @ 30 VDC resistive center to center 0.3 A @ 110 VDC inductive FM approved for 25 x 25 ft. 1.0 A @ 30 VDC inductive (7.6 x 7.6 m) spacing B224RB Relative Humidity: 10 — 93% (non - condensing) Relay Base ATD -L2F Fixed - temperature setpoint Dimensions: 6.2 ": (15.7 cm) x 1.2" (3.0 cm) 135 °F (57 °C) B224BI ATD -RL2F Combination 135° F fixed Isolator Base temperature and 15° (8.3 °c) per Dimensions: 6.2" (15.7 cm) x 1.2" (3.0 cm) minute rate -of -rise° Maximum 25 devices between isolator ATD -HL2F Fixed - temperature setpoint bases 190 °F (88 °C) RA -400Z Remote alarm indicator, LED BCK -200 Black detector covers (box of 10) Electrical Specifications Ordering Information Voltage Range: 15 - 32 volts DC peak Model Description Standby Current: 200 mA @ 24 VDC ATD -L2F Addressable thermal sensor, fixed, 135° F (without communication) ATD -RL2F Addressable thermal sensor, combination max. avg.) .0003 A @ 24 VDC fixed,135° F and 15° /minute rate -of -rise. (one communication every 5 seconds ATD -HL2F Addressable thermal sensor, fixed, 190° F with LED enabled) LED Current (max.) .0065 A @ 24 VDC (LED lit) Voltage Range 15 —32 volts DC peak GAMEWELL -FCI 12 Clintonville Road, Northford, CT 06472 -1610 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 9020 -0620 Rev. C3 page 2 of 2 www.gamewell fci.com ms_i ri Gamewell series FIRE CON INSTRUM L by Honeywell Description Non- Coded, Manual Fire Alarm Stations The Gamewell -FCI, MS -7 Series manual fire alarm sta- tions are available in a wide variety of configurations. The Stations comply with the Americans with Disabilities Act (ADA) 5 -lb. maximum pull force requirement. Operating F I R instructions and Braille text are engraved in the handle. All stations have a key lock/reset which is keyed alike with PUSH IN Gamewell -FCI fire alarm control panels and other manual I PULL. DOWN 1 fire alarm stations. MS - 7AF Velociti Addressable Station The MS -7AF Velociti Series addressable station is a dou- ble action station designed for installation in the signaling line circuit of Gamewell -FCI analog addressable control GamevoeM panels. Activation of the station causes its assigned address to register at the control panel. The door contains an LED which flashes green in normal condition and lights MS - steady red when the station has been activated.* The sta- tion features screw terminals. Features MS - 7ASF Velociti Addressable Station ® • Addressable stations compatible with all Gamewell -FCI The MS -7ASF Velociti Series addressable station is a single action station designed for installation in the signal- analog addressable fire alarm controls ing line circuit of Gamewell -FCI analog addressable con- trol panels. Activation of the station causes its assigned • Conventional stations suitable for use with any UL address to register at the control panel. The door contains Listed control panel an LED which flashes green in normal condition and lights steady red when the station has been activated.` The sta- • Both single and double action stations available tion features screw terminals. • Tumbler lock for test and reset keyed alike with The Velociti Series stations use a communication proto- Gamewell -FCI controls col that substantially increases the speed of communica- tion between the sensors and certain Gamewell -FCI • Surface or semi -flush mounting analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the Shock and vibration resistant • group has a status change, the panel's microprocessor stops the group poll and focuses on the single device. The net effect is response speed up to five times greater than • Stations (MS -7LOB) Listed for outdoor applications earlier designs. • Complies with ADA pull force requirements MS - Double Action Station `Only the red LED is operative in panels that do not oper- The MS -7 double action station is used with conventional ate in Velociti mode. fire alarm control panels. It features a set of single pole contacts and screw terminals for connection to an initiating circuit. An ISO 9001 -2000 Company Velociti is a registered trademark of Honeywell International Inc. scNnuxc UL is a registered trademark of Underwriter's Laboratories Inc. LEXAN is a registered trademark of GE Plastics, a subsidiary of General 0 0' MEA Electric Company. LISTED S12359 0715001114:261 GAMEWELL - FCI 12 Clintonville Road, Northford, CT 06472 -1610 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 Specifications are for information only, are not intended for installation purposes. and are subject to change without notice. No responsibility is assumed by Gamewell -FCI for their use. r ©2010 by Honeywell International In All rights reserved. www.gamewell- fci.com 9020 - 0616 Rev. D page 1 of 2 J MS -7S Single Action Station Specifications The MS -7S single action station is used with conventional fire alarm control panels. It features a set of single pole Material: Lexan® contacts and wire leads for connection to an initiating circuit. Contact Ratings: 0.25 amps. @ 30 VACNDC MS -7SP Double Action Station (resistive) The MS -7SP is a double action station similar to the MS -7 Dimensions: 5 5/8" H x 4 1/4" W x 1 1/4" D station, with the additional feature of both English and (14 x 10.1 x 3.2 cm) Spanish instructions molded into the unit. Operating Temperature MS -7LR Dual- action Agent Release Station (MS -7AF, MS- 7ASF): 32° to 120° F (0° to 49° C) The MS -7LR is designed for use with the Gamewell -FCI (MS- 7LOB): -30° to 150° F ( -35° to 66° C) fire alarm control panels with releasing capabilities and Relative Humidity Flex Series releasing systems. It features a set of single (MS -7AF, MS- 7ASF): 10 to 93% (non- condensing) pole contacts and screw terminals for connection to an ini- (MS- 7LOB): 85% ± 5% @ 86° ± 3.6° tiating circuit. (30° ± 2° C) Alarm Current: .0030 amp. 0.007 for LED MS -7LRA Agent Release Station with Abort Supervisory Current The MS -7LRA is designed for use with the Gamewell -FCI (MS -7AF, MS- 7ASF): .00030 amps. fire alarm control panels with releasing capabilities and Flex Series releasing systems where system abort capabil- ities are required. It consists of an MS -7LR mounted on a Ordering Information plate with an abort switch and LED indicators for system normal, and system activated status. Part Number Description MS -7LOB Double Action Station MS -7 Double action station (Listed for Outdoor Applications) MS -7AF ** Velociti addressable double action The MS -7LOB station must be mounted on a Model SB -I /O station backbox. In retrofit applications, the station is UL Listed for MS- 7ASF ** Velociti addressable single action station use with the WP -10 backbox. It is intended for use with MS -7S Single action station, wire leads conventional control panels and has a set of single pole MS -7SP Double action station, English and contacts and screw terminals. Spanish instructions MS -7LR Agent release station, dual- action Mounting MS -7LRA Agent release station with abort switch, The MS -7 interior stations may be surface mounted or LED indicators, dual- action semi -flush mounted on a standard double -gang, or 4 -inch MS -7LOB Double action station, outdoor use (10.2 cm) square electrical box. An optional trim ring (Includes SB -I /O - Indoor /outdoor use (BG12TR) may also be used for semi -flush mounting. backbox) NYC -Plate SB -I /O Indoor /outdoor use backbackbox The NYC -Plate provides the backplate for the manual pull SB -10 Surface backbox station. (See Figure 1). BG12TR Trim ring for semi -flush mount, plastic NY -PLATE NYC backplate for manual pull station * *For use with the Gamewell -FCI analog addressable control panels only. FIRE 11 'USH !N ♦HUII (PWN I Figure 1 NYC -Plate GAMEWELL - FCI 12 Clintonville Road, Northford, CT 06472 - 1610 USA • Tel: (203) 484 - 7161 • Fax: (203) 484 - 7118 9020 -0616 Rev. D page 2 of 2 www.gamewell- fci.com rei FI CONTROL Velocitr Series IN STRUMENTS by Honeywell AMM2F Addressable Description Monitor Module The FCI Velociti Series, addressable monitor module AMM -2F is a single Style B, Class B initiating device circuit (IDC) with a 47KW end -of -line resistor. This module provides an address for any device or group of devices connected to this circuit on the signaling line circuit (SLC) of the FCI addressable series fire alarm control panel. Any initiating device with normally open (N.O.) dry contacts may be made addressable when _ -�_��• " connected to the AMM -2F module. The Velociti Series use a communication protocol that AMM - 2F substantially increases the speed of communication between the sensors and certain FCI analog addressable fire alarm controls. These devices operate in a grouped Features fashion. If one of the devices in the group has a status change, the panel's microprocessor stops the group poll • Compact size allows easy installation. and concentrates on the single device. The net effect is • Class B, Style B, initiating circuit. response speed up to five times greater than earlier de- • 40 Ohm line resistance for each initiating device signs. circuit. • Connects to any normally open dry contact device. The AMM -2F module can be programmed to provide a • Bicolor LEDs flash green whenever the module wide variety of input functions to the FCI addressable is addressed, and light steady red on alarm.* series fire alarm control panels. It can be identified as a 'Note: Only the red LED is operative in panels that do not oper- ate in VelocitiTM mode. manual station, heat detector, plenum detector, waterflow switch, tamper switch, N.O. contact, smoke detector, projected beam smoke detector, sub loop, Specifications remote zone, etc. It can also serve as a remote system silence, system reset, system acknowledge or drill switch. It is even possible to customize its device type to Supervisory current: 375 pA Alarm current: 600 pA meet specific job requirements. Operating temperature: 32° to 120° F (0° to 49° C) The initiating device circuit of the AMM - can support a Relative humidity: 10 to 93% (non condensing) maximum line resistance of up to 40 ohms allowing the End-of-line Resistance: 47K ohms use of linear heat detection devices. The compact size Dimensions: 1.3" L x 2.5" W x 0.5" D facilitates the installation of the module inside manual (3.3 x 6.4 x 1.3 cm) stations, or mounting boxes of various types of alarm initiating devices. Ordering Information An ISO 9001 -2000 Company Model Description SIGNALING AMM -2F Addressable monitor module, single circuit, Style B, Class B ® MEA `� �" LISTED APPROVED Approved I' 3 Velocirm and E3 SeriesTM are trademarks of Fire Control Instruments. 51949 3023594 227.03.E VoLIV 07300.0694:178 GAMEWELL -FCI 12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484 -7161 - Fax: (203) 484 -7118 Specifications are for information only, are not intended for installafon purposes, and are subject to change without notice. No responsibility is assumed by Gamewell -FCI for their use. 02006 Gamewell -FCI. All rights reserved. www.gamewell.fci.com 9020 -0626 Rev. C page 1 of 1 • • f GameweO VelocitiTM Series © FI CONTROL Fe/ INSTRUMENTS AO M -2 R F by Honeywell Description Addressable Output Relay Control Module The Gamewell -FCI VelocitiTM Series, addressable output relay control module (AOM -2RF) allows an Gamewell -FCI analog addressable fire alarm control to switch discrete relay contacts by code command. The relay provides two (2), isolated sets of Form -C contacts which transfer simul • taneously. Circuit connections to the relay contacts are not supervised by the module. The VelocittTM Series use a communication protocol that substantially increases the speed of communication' between the sensors and certain Gamewell -FCI analog addressable fire alarm controls. These devices operate in a AOM -2RF grouped fashion. If one of the devices in the group has a status change, the panel's microprocessor stops the group Features poll and concentrates on the single device. The net effect is response speed up to five times greater than earlier • Two (2) sets of Form "C" contacts. designs. • Visual rotary, decimel switch addressing (01 -159). • The AOM -2RF Module is designed for installation in the Bicolor LEDs flash green whenever the sensor is signaling line circuit of any Gamewell -FCI analog address- addressed, and light steady red on alarm *. able fire control panel. The module contains a panel con- • Compact size allows easy installation. trolled LED. The AOM - 2RF is designed to mount in a 4" Note: Only the red LED is operative in panels that do not operate square junction box 2 1/8" deep. in VelocitiTM mode. Relay Contact Ratings Specifications Current Maximum Load Supervisory current: 300 pA Rating Voltage Description Application Alarm current: 300 pA 3A 30 VDC Resistive Non -Coded Operating temperature: 32° to 120° F (0° to 49° C) 2A 30 VDC Resistive Coded Relative humidity: 10 to 93% relative humidity 0.9A 110 VDC Resistive Non -Coded (non- condensing) 0.5A 125 VAC Resistive Non -Coded Dimensions: 4 1/2" H x 4" W x 1 1/4" 0.5A 30 VDC Inductive Coded (11.4x 10.2 x 3.2 cm) (UR =5ms) Ordering Information 1A 30 VDC Inductive Coded (UR =2ms) Model Description 0.5A 125 VAC Inductive Non -Coded AOM -2RF Addressable output relay control module (PF =.35) 0.7A 75 VAC Inductive Non -Coded An ISO 9001 - 2000 Company SIGNALING _...._ (") ® MEA I ' � ��: LISTED A PPROVED Approved . 51949 3023594 227 -03£ Vo4.IV 07300 -0694:179 GAMEWELL -FCI �1 12 Clintonville Road, Northford, CT 06472 -1653 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell -FCI for their use. ®2006 Honeywell Intematenal Inc. AO rights reserved. www.gamewell- fci.com 9020 - 0625 Rev. D page 1 of 1 • • Gamewell InnovairFletrm Series FIR CONTROL FCI INSE TRUMENTS DNR /DNRW Duct by Honeywell Smoke Housing Description Intelligent Non -Relay Photoelectric Duct Smoke Housing The InnovairFlex TM Series, DNR intelligent, non -relay pho- toelectric duct smoke detector, and the DNRW watertight, non -relay photoelectric duct smoke detector feature a piv- oting housing that fits both square and rectangular foot - ` - .> prints. These detectors are capable of mounting to a round or rectangular duct. The DNR /DNRW detectors can be used with the E3 Series and 7100 Systems. q Note: The InnovairFlexTM Series, DNR requires the Veloc- iti Series, ASD -PL2F Sensor and AOM -2RF, if relays are required for the fan control. InnovairFlex- DNRIDNRW The DNRW duct smoke detector, with its NEMA 4 rating, is Listed as a watertight enclosure providing protection against falling dirt, rain, and windblown dust, splashing and Features hose directed water. These features allow operators to use Photoelectric, integrated low -flow technology • the detector in the most extreme environments. • Air velocity rating from 100 ft/min to 4,000ft/ min The units sense smoke in the most challenging conditions, (0.5m /s to 20.32m /sec) operating in airflow speeds of 100 to 4,000 feet per minute, • Versatile mounting options: square or rectangular temperatures of -4 °F to 158 °F, and a humidity range of 0 to configuration 95 percent (non- condensing). • Broad ranges for operating temperature (-4 °F to 158 °F) and humidity (0% to 95% non - condensing) An improved cover design isolates the sensor head from • Patented sampling tube installs from front or back of the the low -flow feature for simple maintenance. A cover tamper feature was added to indicate a trouble signal for a detector with no tools required removed or improperly installed sensor cover. The • New Cover tamper signal InnovairFlex housing provides a 3/4 -inch conduit knockout • Increased wiring space with a newly added 3/4 -inch and ample space to facilitate easy wiring and mounting of conduit knockout the relay module. • Available space within housing to accommodate the mounting of the relay module The InnovairFlex duct smoke detector can be customized • Easily accessible code wheels on sensor head (sold to meet local codes and specifications without additional separately) wiring. The new InnovairFlex product line is compatible • with all previous Innovair models, including remote test Clear cover for convenient visual inspection • accessories. UL 268A Listed • Remote testing capability WARNING:Duct smoke detectors have specific limitations. • Requires SLC line power only DUCT SMOKE DETECTORS ARE: • NEMA Type 4 UL Listed for non - hazardous indoor and NOT a substitute for an open area smoke detector, outdoor applications (DNRW only) NOT a substitute for early warning detection, and NOT a • UV Resistant, UL Listed housing and cover material replacement for a building's regular fire detection system. (DNRW only) Refer to NFPA 72 and 90A for additional duct smoke detector 2911 application information. An ISO 9000 -2000 company SIGNALING E3 Series and Velotici ® are registered trademarks and InnovairFlex°° is a 0 trademark of Honeywell International, Inc. LISTED 2911 GAMEWELL -FCI 12 Clintonville Road, Northford, CT 064 72 -1 61 0 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 Specifications are for information only, are not intended for installation purposes. and are subject to change without notice. No responsibility is assumed by Gamewell -FCI for their use. 02009 by Honeywell International Inc. All rights reserved. www.gamewell- fCi.cOm 9021 - 60475 Rev. A page 1 of 4 Architectural /Engineering Specifications The air duct smoke detector shall be a System Sensor InnovairFlexnA DNR Intelligent Non -Relay Photoelectric Duct Smoke Detec- tor and DNRW Watertight NEMA4 Duct Smoke Detector. The detector housing shall be UL Listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits both square and rectangular footprints. The detector shall operate at air velocities of 100 ft/min to 4,000 ft/min (0.5 m /sec to 20.32 m /sec). The unit shall be capable of providing a trouble sig- nal in the event that the sensor cover is removed or improperly installed. It shall be capable of local testing via magnetic switch or remote testing using the RTS451KEY remote test station. Terminal connections shall be of the strip and clamp method suitable for 12 -18 AWG wiring. Physical Specifications Size: Rectangular Dimensions: 14.38 in (37 cm) Length; 5 in (12.7 cm) Width; 2.5 in (6.6 cm) Depth Square Dimensions: 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth Weight: 1.6 lb (0.73 kg) Environmental Rating: NEMA4 (DNRW only) Operating Temperature Range: —4° to 158 °F ( -20° to 70 °C) Storage Temperature Range: —22° to 158 °F ( -30° to 70 °C) Operating Humidity Range: 0% to 95% relative humidity non - condensing Air Duct Velocity: 100 to 4000 ft/min (0.5 to 20.32 m /sec) Electrical Ratings For information on electrical specifications, refer to the InnovairFlex DNR Duct Smoke Detector Installation Instructions, P/N 156-3051-001R. Accessory Current Loads at 24 VDC Device Standby Trouble RA400Z 0 mA 12 mA Max. RTS451 /RTS451 KEY 0 mA 12 mA Max. Installing the InnovairFlex Sampling Tube The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing the front or rear locking tab. (Figure 3 illustrates the front locking tab). • Figure 1 Figure 2 Figure 3 GAMEWELL - FCI 12 Clintonville Road, Northford, CT 06472 - 1610 USA • Tel: (203) 484 - 7161 • Fax: (203) 484 - 7118 9021 -60475 Rev. A page 2 of 4 www.gamewell- fci.com • Wiring for Intelligent Non -Relay Duct Smoke Detector I -- -- 1 - - - -- 1 COMM. 1 ' LINE ( +) T� COMM. LINE I I LINE (— I LINE ( —) — 1' �' 1 1 I 1 I I I I UUFM LISTED 1ST 2ND CONTROL DETECTOR DETECTOR PANEL IN LOOP IN LOOP Figure 4 System Wiring Diagram for DNR + RA 44 (-0 'V) RA400Z -RA,, () REMOTE ALARM LED OPTION 1 PER UNIT Figure 5 DNR to RA400Z TEST COIL + • E 4 (s * EXTERNAL J `� TEST COIL— -- c I - ) POWER (.0 SUPPLY COMM + P A i � ( Y / 3J OUT (CONV ONLY) + RTS451?RTS451 KEY — COMM — REMOTE TEST STATION RA/RTS — LED OPTION RA + e 1 PER UNIT FITS + TEST COIL OPTION 1 PER UNIT 95rnA CURRENT DRAW Figure 6 DNR to RTS451 /RTS451 Key Important Notes: • The use of either RTS451 or RTS451 KEY requires the installation of an accessory coil, DCOIL, sold separately. For additional information, refer to the DNR or DNRW Duct Smoke Detector Installation Instructions, P/N 156- 3051 -001 R and the Duct Application Smoke Detectors Application Guide. • The RTS451 /RTS451KEY test coil circuit requires an external 24 VDC power supply which must be UL Listed. GAMEWELL -FCI 12 Clintonville Road, Northford, CT 06472 -1610 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 www.gamewell - fci.com 9021 -60475 Rev. A page 3 of 4 J Accessories System Sensor provides system flexibility with a variety of accessories, including two remote test stations and different means of vis- ible and audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL Listed. 4 4 I a 'i 0 e Figure 7 RTS451 UL S2522 Figure 8 RTS451KEY UL S2522 Figure 9 RA400Z UL S2522 Ordering Information Part Number Description DNR Intelligent non -relay photoelectric low -flow duct smoke detector DNRW Watertight intelligent non -relay photoelectric low -flow duct smoke detector Accessories Part Number Description Part Number Description DCOIL Remove test coil required with RTS451 /RTS451 KEY ETX Metal exhaust tube duct width lft (0.3m) DST1 Metal sampling tube duct width up to 1 ft (0.3m) MO2 -04 -00 Test magnet DST1.5 Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m) P48 -21 -00 End cap for metal sampling tubes DST1.5 Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m) RA400Z Remote annunciator alarm LED DST3 Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m) RTS451 Remote test station DST5 Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m) RTS451 KEY Remote test station with key lock DST10 Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m) DH4000E -1 Weatherproof enclosure GAMEWELL -FCI 12 Clintonville Road, Northford, CT 06472 -1610 USA • Tel: (203) 484 -7161 • Fax: (203) 484 -7118 9021 -60475 Rev. A page 4 of 4 www.gamewell fci.com Wheelock ExcederTM Series 0 COOPER Notification E ,, Strobe, Horn Strobe, and Horn Notification Appliances FIRE • t f FIRE 1111% Ceiling - Wall Description: The Wheelock® Excederr' Series of notification appliances feature a sleek modern design that will please building owners with reduced - Save up to 48% in current draw* total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes, voltage test - Up to 9 models now in 1 appliance points, 12/24 VDC operation, universal mounting base and multiple mounting options for both new and retrofit construction. - Save up to 14% cost of installation ** The Wheelock® ExcederTM' Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit. All strobe models feature an industry first of 8 candela settings on a single 0 Sleek Modern Aesthetics appliance. Models with an audible feature 3 sound settings (90, 95, 99 dB). All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. Finger Slide Switches Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock® ExcederTM' Series of wall and ceiling notification Voltage Test Points appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting 12 4 Multiple Voltages base can be pre -wired to allow full testing of circuit wiring before VDC the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt, dust, p aint 1110 3 Audible Settings and damage to the contacts. The Contact Cover also acts as a so, ss, ss dB shunting device to allow pre -wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while li 8 Candela Settings ` *' it is on the UMB. When the Contact Cover is removed the circuit Wall - 15/1575/30/75/95 /110/135/185 will show an open until the appliance is installed. The UMB allows Ceiling - 15/30/60/75/95/115 /150/177 for consistent installation and easy replacement of appliances if *5* required. Wall models provide an optional locking screw for extra f� Universal Mounting Base secure installation, while the ceiling models provide a captivated Ceiling and Wall screw to prevent the screw from falling during installation. Mounts to 5 Backbox Types Environmentally Friendly Low Current Draw Compatibility and Requirements - Synchronize using the Wheelock' Sync Modules or panels with built -in Wheelock' Patented Sync Protocol - Compatible with UL "Regulated Voltage "using filtered VDC or unfiltered VRMS input voltage - Strobes produce 1 flash per second over the "Regulated Voltage" range *Compared to competitive models * ** Patented **Compared to previous models NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. General Notes: General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". • All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. • Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 93% (t 2 %) UL 464 (85% UL 1971). • Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only). Low Current Draw = Fewer Power Supplies Strobe Ratings per UL Standard 1971 UL Max Current* 24 VDC / 24 FWR 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 ST 8.0 - 33.0 0.057 0.070 0 085 r 0.135 0.163 0.182 0.205 0.253 0.110 0.140 STC 8.0 - 33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110 Horn Strobe Ratings per UL 1971 & Anechoic at 24 VDC UL Max Current* at Anechoic 99 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0 - 33.0 0.082 0.095 0.102 Mob 0.148 0.176 0.197 0242 0.282 0.125 0.159 HSC 8.0 -33.0 0.082 0.102 0.141 0.148 0.176 ° 0.197 0242 0.282 0.125 UL Max Current* at Anechoic 95 dBA 24 VDC 12 VDC Model Regulated VDC ulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 HS 8.0 -33.0 0.073 0.083 0.087 0.139 0.163 0.186 0230 0.272 0.122 0.153 HSC 8.0 -33.0 0.073 ' 0.087 0.128 0.139 0.163 0.186 0 230 0.272 4 0.122 d UL Max Current* at Anechoic 90 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC • HS 8.0 -33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148 HSC 8.0 -33.0 0.065 0.084 0.120 0.136 0.157;'; 0.184 0.226 0.267 0.120 Horn Ratings per UL Anechoic Model Regulated Voltage 99 d6 95 d6 90 dB Range VDC 44 Prs, HN 16 -33.0 0.064 0.044 0.022 ""+loakti' t `° HNC 16-33.0 0.084 0.044 0.022 HN 8.0 -17.5 0.047 0.026 0.017 HNC 8.0 -17.5 0.047 0.026 0.017 Ale * UL max current rating is the maximum RMS current within the listed voltage range (16 -33 VDC for 24 VDC units). For strobes the UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions. Specification & Ordering Information Sync w! Model Strobe DSM or 12/24 VDC* Mounting Candela Wheelock Power Options Supplies Horn Strobes N HSR 15/1575/30/75/95 /110/135/185 X X X UMB ** o — '^ HSW 15/1575/30/75/95 /110/135/185 X X ..o UMB ** CU HSRC 15/30/60175/95/115 /150/177 X X o UMB ** u HSWC 15/30/60/75/95/1151150/177 X X UMB ** CO 0a "O Strobes Y O O STR • ) 15/1575/30/75/95 /110/135/185 X X o UMB ** 5TW 15/1575/30/75!95!110 /135/185 X X M UMB ** p STRC 15/30/60/75/95/115 /150/177 X X It UMB ** STWC p 15/30/60/75/95/115 /150/177 X X 'r UMB ** N aJ H orn c c i 'o Tij O HNR X _ X ry UMB ** > HNW X X c' UMB ** W HNRC a ! X X 01 UMB ** HNWC /,- X X UMB ** *12 VDC models feature 15 & 15/75 settings * *UMB = Universal Mounting Base Model Legen ' n HN = Horn A =Agent Lettering ST = Strobe (Strobes only)�� a HS = Horn Strobe AL = Alert Lettering to" /I`" - ;: C = Ceiling Mount (Strobes only) I , e W =White N = No Lettering R = Red (Strobes only) r - / X ''' .. Example 1: STRC = Strobe, Red, Ceiling Mount N. a , Example 2: HSR =Horn Strobe, Red, Wall Mount Example 3: HSW = Horn Strobe, White, Wall Mount Example 4: STW -AL = Strobe, White, Wall Mount, Alert Lettering Example. Example: HSWC W IFF : A:, '141440W°4— " 'tj ti '411'4 2 ii ill 4 '? 0 0 0 ,, *UMB Contact Cover Voltage test points for quick 8 candela settings Common base for wall and ceiling with 5 troubleshooting and easy spot mounting options checking (wall models only) NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions. Architects and Engineers Specifications The notification appliances shall be Wheelock Exceder'' Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing - Impaired) for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design. Where Multi - Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on -axis is required (e.g. ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single -gang, double -gang, 4 -inch square, 3.5 -inch octal, 4 -inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58" W x 2.19" D. Series HN wall shall measure 5.24" H x 4.58" W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series HNC ceiling shall have a diameter of 6.68" x 1.50" D. When synchronization is required, the appliance shall be compatible with Wheelock's DSM Sync Modules, Wheelock Power Supplies or other manufacturer's panels with built -in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate, the strobe shall revert to a non - synchronized flash -rate and still maintain (1) flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock' synchronization protocol. Wall Appliances — UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM Ceiling Appliances — UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM NEM WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Exceder - Spec Sheet 6/11 NJ Location 273 Branchport Ave. Long Branch, NJ 07740 . P: 800 - 631 -2148 F: 732 - 222 -8707 www.coopernotification.com , cooper Notification is Wheelock (N0 SAFEPATH" WAV COOPER Notification COOPER N otification Series CH Chimes and Chime Strobes FIRE I' '- °.: rr 'v J SERIES CH70 CHIME STROBE SERIES CH70 SERIES CH90 SERIES CH90 CHIME CHIME STROBE CHIME Description Features The Wheelock Series CH Chimes and Chime Strobes • Approvals include: UL Standard 1971, UL Standard 464. minimize alarm system power supply requirements and New York City (MEA), and California State Fire Marshal wiring costs with a low current draw and a patented chime (CSFM) and Chicago (BFP) See approvals by model in mounting plate for fast, easy installation. Each model has Specifications and Ordering Information a built -in level adjustment feature and an aesthetic two (2) ADA /NFPA /UFC /ANSI compliant • screw grille cover. • These unique solid -state chime appliances provide field Complies with OSHA 29 Part 1910.165 selectable single- stroke or vibrating operation with Anechoic • Wall mount models are available with Field sound levels adjustable up to 83 dB and tone adjustable from Selectable Candela Settings of 15/30/75/110cd or 800 to 1200 Hz. 135/185cd (Multi - Candela models) or 1575cd (single Strobe options for wall mount models include 1575cd or candela model) Wheelock patented MCW multi - candela strobe with field Ceiling mount models are available with field selectable selectable candela settings of 15/30/75/110cd or the high candela settings of 15/30/75/95cd or intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models are available in Wheelock patented 115/177cd (Multi - candela models) MCC multi - candela ceiling strobe with field selectable • Low current draw with temperature compensation to intensities of 15/30/75/95cd or the high intensity MCCH strobe reduce power consumption and wiring costs with field selectable 115/177cd. Strobes produce 1 flash per second over the regulated The strobe portion of all Series CH Chime Strobes may be voltage range synchronized when used in conjunction with the Wheelock, 24 VDC with wide UL "Regulated Voltage" using filtered DSM Sync Modules, Wheelock Power Supplies or other DC or unfiltered VRMS input voltage manufacturers panels incorporating the Wheelock Patented Sync Protocol. Wheelock's synchronized strobes offer an • Synchronize using the Wheelock Sync Modules or panels easy way to comply with ADA recommendations concerning with built -in Wheelock Patented Sync Protocol photosensitive epilepsy as well as meeting the requirements • Adjustable Volume and Tone Control of NFPA 72 and UFC. • Single Stroke or Vibrating Operation The Series CH Chime Strobes are UL Listed for indoor. Fast Installation with IN /OUT screw terminals using wall or ceiling mount applications under Standard 1971 9 #12 to for Signaling Devices for the Hearing- Impaired and under #18 AWG wires Standard 464 for Private Mode Audible Signal Appliances. They are available in two attractive package styles for flush mounting to standard electrical boxes or convenient surface mounting. All models include IN /OUT wiring terminations that accept two #12 to #18 AWG wires at each terminal. Inputs are polarized for compatibility with industry standard reverse polarity supervision. A> '' '''': 4.-;__ A MEA r J! APPROVED S5391 151.92 -E 7125 - 0785:151 7135 - 0785:109 (Chime Only) • NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.000PERNOTIFICATION.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". Note that NFPA -72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. • All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. • "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range ". Table 1: Average RMS Current CH70 Strobe current - Wall Mount CH90 Strobe current - Ceiling Mount CH70/ Chime CH90 241575W 24MCW 24MCWH 24MCC 24MCCH Chimes current 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.022 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270 UL max' 0.022 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420 Table 2: Chime dBA ratings " RMS current ratings are per UL average RMS dBA @ 10 ft method. UL max current rating is the maximum RMS Peak dBA @ reverberant current within the listed voltage range (16 -33v for 24v CH70 /CH90 10 ft. anechoic units). For strobes the UL max current is usually at sound level Min Max the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum 83 52 58 listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. Application 1. The chimes are factory set in single stroke (SS) mode. They can be changed to vibrating (VIB) mode with jumper on PC Board. SINGLE STROKE OPERATION: The minimum input pulse duration must be at least 160 ms "on" time and 160 ma off time. The chime will only operate once each time it is pulsed. This mode is recommended for coded systems. VIBRATING OPERATION: Continuous input voltage applied to the chime will activate the chime at one - second intervals. 2. The volume and tone controls have been adjusted at the factory to insure maximum dBA output. However, once the mode is selected, the installer may want to fine -tune the signal to better suit the application. 3. Anechoic dBA is measured in an anechoic chamber with peak meter response. Reverberant dBA is rated per UL Standard 464. 4. Chime inrush current is 0.100 amps maximum with filtered DC input (0.140 amps with VRMS input voltage) with a time duration of 100 milliseconds. Wiring Diagram? SERIES CH CHIME & STROBE OPERATE INDEPEN- SERIES CH CHIME STROBES SYNCHRONIZED W/ DANTLY (NON -SYNC OR SYNC) MULTIPLE DSM MODULES FROM DSM el PRF.C'EI, + + TO NEXT SYNCH O D NCC OR Strobe NAC Cir. i'+` IM SYNC MCNILL OR EOL POWER SUPPLY C OR FACP r Note: Figure DSM e2 FROM _ — l ( — — — _ _ _ e shows intercon- PRECEDING TO NEXT r` ,. APPLIANCE. 11 + TOtt FOR Strobe NACCIr.' S y + DMZ nection to strobe SYNC MOSAIC. I I 1 r — — — — — - EOLR ■ � C POWER SUPPLY I through sync OR FACP ,, DSM e3 „ P sY�t module. Chime 0 ,, Strobe NAC Cm `? t t ]I t portion requires 2 STROBE CHIME separate conduc- DSM Interconnecting wiring shown. Maximum of tors to FACP. (OPTIONAL) twenty (20) SERIES CH CHIME STROBE APPLIANCES SERIES CH CHIME STROBE APPLIANCES & ST SYNCHRONIZED WITH DSM MODULE SINGLE STROBES SYNCHRONIZED WITH WHEELOCK "CLASS A" POWER SUPPLIES DSM Series PS Power Supplies ///��I 0. ". CH [' 01 R' NUS r • OUTPUTS v EOLF C F 1-4 OR 4-CLASS AP e A �J ° °T P I ___ •. r: Avnew.ce A.P.u.c. CH Mill CIRCUIT RETURN Series PS Power Supplies r For wiring information on the Wheelock Power Supplies, please refer to Data Sheet #9100. Specifications and Ordering Information Strobe Sync w/ DSM or Model Model Agency Approvals Model Number Order Wall Ceiling Wheelock Strobe 24 Color Color Mounting Code Mount Mount Power Sup- Candela VDC RED White Options UL MEA CSFM BFP plies CH70- 24MCW -FR 9018 X X 15/30/75/110 X X - L,O,P,Q,R,U,Y X X X X CH70- 24MCW -FW 9019 X - X 15/30/75/110 X - X L,O,P,Q,R,U,Y X X X X CH70- 24MCWH -FR 9083 X - X 135/185 X X - L,O,P,Q,R,U,Y X X X - CH70- 24MCWH -FW 9084 X - X 135/185 X - X L,O,P,Q,R,U,Y X X X - CH70- 241575W -FR 7830 X - X 15 (75 on Axis) X X - L,O,P,Q,R,U,Y X X X X CH90- 24MCC -FW 3168 - X X 15/30/75/95 X - X Q,U,V X X X - CH90- 24MCC -FR 3167 - X X 15/30/75/95 X X - Q,U,V X X X - CH90- 24MCCH -FW 3110 - X X 115/177 X - X Q,U,V X X X - CH70 -24 -R 7825 X X - - X X - L,O,P,Q,R,U,Y X X X X CH70 -24 -W 7827 X X - - X - X L,O,P,Q,R,U,Y X X X X CH90 -24 -W 7826 X X - - X - X Q,U,V X X X X CH90 -24 -R 7828 X X - - X X - Q,U,V X X X X Models are available in either Red or White. Call Customer Service for Order Code & Delivery. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Architects and Engineers Specifications The chime appliances shall be Wheelock Series CH Chimes and the chime strobe appliances shall be Wheelock Series CH Chime Strobes or approved equals. The chime shall be UL Listed under Standard 464 for Audible Signal Appliances and chimes equipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing- Impaired. In addition, the strobes shall be certified to meet the requirements of FCC Part 15, Class B and shall incorporate low temperature compensation to ensure the lowest possible current consumption. All chimes shall use solid state components and shall provide field selectable single stroke or vibrating operation with volume control and tone control. All models shall have a peak Anechoic sound output of 83 dB at 10 feet and an adjustable frequency range of 800 to 1200 Hz. All inputs shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The strobe shall be of low current design. Where Multi - Candela Chime Strobes are specified, the strobe intensity shall have a minimum of four (4) field selectable settings and shall be rated per UL Standard 1971 at: 15130175/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant and not accessible from the front of the appliance. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 listing with 75 candela on -axis is required (e.g. ADA compliance). When synchronization is required, the strobe portion of the appliance shall be compatible with Wheelock DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built -in Wheelock Patented Sync Protocol. The strobes shall not drift out of syn- chronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non - synchronized flash rate. The chime and the chime strobe appliances shall be designed for indoor surface or flush mounting. The chime and chime strobe shall incorporate a chime mounting plate with a grille cover which is secured with two screws for a level, aesthetic finish and shall mount to standard electrical hardware requiring no additional trimplate or adapter. All chime and chime strobe appliances shall be backward compatible. PJEMII WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY S0710 CH 06/11 NJ Location 273 Branchport Ave. Long Branch, NJ 07740 P: 800 -631 -2148 F: 732 - 222 -8707 www.coopernotification.com Cooper Notification is Wheelock' mix SAFEPATH wavED ZDEV COOPERNotification COOPER N otification Series SM and DSM Sync Modules Series SM or DSM Description Features The Wheelock Series SM and DSM Sync Modules are utilized • Approvals include: UL Standard 1971, ULC, New York City with the Series AS /AH, Series NS /NS4 /NH, Series RSS, Series (MEA), California State Fire Marshal (CSFM) and Chicago RSSP, Series SLM and selected strobe applications with other (BFP) Wheelock combination appliances. • When used with Series AS Audible Strobes and /or Series Uniquely designed to accept an independent strobe and audible input from the FACP and convert to a single output NS Horn Strobes. the SM and DSM Sync Modules provide that connects to Wheelock's Series AS or Series NS family of independent operation of synchronized temporal pattern (code audible strobes 3) horn and synchronized strobe flash, as well as the ability to silence the horn while maintaining the strobe flash. while using • Series SM and DSM Sync Modules can also be used to only a single pair of wires. The sync modules are available in synchronize Wheelock's Series RSS, RSSP and SLM Sync two versions; the SM -12/24 for control of a Class B NAC circuit; Strobes and a dual output version, the DSM -12/24 for control of either a • 3 ampere per circuit current handling at 12 or 24 VDC Class A or two (2) Class B NAC circuits. • Low operating current draw • Compatible with all standard fire alarm control panels • Meets the NFPA -72 requirement for Temporal Pattern when used with the Series AS /AH and /or Series NS /NS4 /NH • 3 year warranty POWERPATHCP AS /AH, NS, HS4 /HS FIRE ALARM POWERPATHMP NH, RSS, RSSP. CONTROL PANEL OR SM OR DSM E w /STB. ET w /STB. (FACP) OTHER POWER CH w /STB BOOSTERS APPLIANCES SM or DSM Connection Diagram with Power Booster ,T,;71 42110 ® MEA " APPROVED E5946 151 -92 -E 7300 - 0785.132 ' • • Table 1: Sync Module (SM) Current Requirements (AMPS) Tablet: Sync Module (DSM) Current Requirements (AMPS) UL ULC Rated Average Rated Peak Rated Inrush UL ULC Rated Average Rated Peak Rated Inrush Voltage Voltage Current Current Current Voltage Voltage Current Current Current In1 Audible In1 Audible In1 Audible In1/In2 Audible In1/In2 Audible In1/In2 Audible 8.0 VDC 10.5 VDC 0.017 0.004 0.055 0.004 0.140 0.016 8.0 VDC 10.5 VDC 0.019 0.004 0.055 0.004 0.150 0.016 12.0 VDC 12.0 VDC 0.017 0.004 0.060 0.004 0.160 0.019 12.0 VDC 12.0 VDC 0.020 0.004 0.064 0.004 0.170 0.019 24.0 VDC 24.0 VDC 0.028 0.008 0.070 0.008 0.320 0.030 24.0 VDC 24.0 VDC 0.035 0.008 0.080 0.008 0.342 0.030 33.0 VDC 33.0 VDC 0.038 0.010 0.080 0.010 0.440 0.040 33.0 VDC 33.0 VDC 0.045 0.010 0.090 0.010 0.470 0.040 8.0 VRMS 8.0 VRMS 0.026 0.006 0.085 0.008 0.210 0.016 8.0 VRMS 8.0 VRMS 0.028 0.005 0.107 0.008 0.210 0.016 12.0 VRMS 12.0 VRMS 0.028 0.006 0.090 0.009 0.225 0.019 12.0 VRMS 12.0 VRMS 0.030 0.006 0.103 0.009 0.240 0.019 24.0 VRMS 24.0 VRMS 0.040 0.010 0.120 0.015 0.446 0.033 24.0 VRMS 24.0 VRMS 0.048 0.010 0.145 0.015 0.480 0.033 33.0 VRMS 31.0 VRMS 0.055 0.012 0.150 0.022 0.645 0.056 33.0 VRMS 31.0 VRMS 0.062 0.012 0.175 0.022 0.685 0.056 NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. ,(Z WARNING: MAKE SURE THAT THE TOTAL CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO A SM OR DSM DOES NOT EXCEED 3.OA OR EXCEED THE RATING OF THE FIRE ALARM CONTROL PANELS PRIMARY AND SECONDARY POWER SOURCES AND NAC CIRCUITS. OVERLOADING THESE SOURCES COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. When calculating the total current, use Tables 1 & 2 to determine the highest value of "Rated Average Current" for the SM or DSM (across the listed volt- age range), then add this value to the total current for any other appliances powered by the same source and include any required safety factors. Refer to Instruction Sheet for addtional information. A WARNING: MAKE SURE THAT ALL FUSES USED ON NAC CIRCUITS ARE RATED TO HANDLE THE MAXIMUM INRUSH OR PEAK CURRENT FROM ALL APPLIANCES ON THOSE CIRCUITS. FAILURE TO DO THIS MAY RESULT IN LOSS OF POWER TO THE NAC CIRCUIT AND THE FAILURE OF ALL APPLIANCES ON THAT CIRCUIT TO OPERATE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. Table 3: Current Consumption of the SM and DSM Modules Outpurt Circuit Description of SM /DSM Module SM DSM Ref. Fig. Module Module Class "B" with Audible Silence (single circuit) Y 1 Class "B" with No Audible Silence (single circuit) Y 2 Class "B" with Audible Silence (dual circuit) Y 3 Class "B" with No Audible Silence (dual circuit) Y 4 Class "A" with Audible Silence (single circuit) Y 5 Class "A" with No Audible Silence (single circuit) Y 6 Note: SM Sync Modules are rated for 3.0 amperes at 12/24 VDC; DSM Dual Sync Modules are rated for 3.0 amperes per circuit. The maximum number of interconnected DSM modules is twenty (20). ACAUTION: Use SM or DSM Sync Modules only on NAC circuits with continuously applied voltage. Do not use SM or DSM Sync Modules on coded or interrupted NAC circuits in which the applied voltage is cycled on and off. ACAUTION: Power Boosters may be used in conjunction with the SM or DSM Sync Modules only in the order shown below. Only one SM or DSM Sync Module shall be allowed on a NAC circuit. Do not connect Power Booster to the NAC circuit after the one SM or DSM Sync Module. Exception: The Wheelock PS- 24 -8MC Power Booster can be connected either before or after the SM or DSM Sync Module. Refer to Power Booster instruction manual for proper application and installation. . . . SVC a EDaiLAE REMDR� R) IINC YD DYL{ '.. 9 e pan I JCE N Ii 64t ..Y<wwas Ii q aut+ I, Ii um., w Ili 'I I • G 4 ::: wi it f - s T . MNV • * I ail: Tg hEYlM9�7AtL r � .. +auaw +e.a.r * � OR Eplp Nhw..aa m aw ialN y .. FI(i. 1 SINGLE CLASS "B" C;IKC UI I WI I H FIG. 2 SINGLE CLASS "B" CIRCUIT WITH NO AUDIBLE AUDIBLE SILENCE FEATURE SILENCE FEATURE Nr + ew`»r ..Me PUAL• MODULO ra .uu. < nn lsua w. IL • ��,� C.Yw..\ T • . nw eoi a*A' J w ..« .111111111111--"I . 5, 9 .r I .Pr\YSN • t 7.7 111.111111.1111 UM li Lid FIG. 3 DUAL CLASS "B" CIRCUIT WITH AUDIBLE FIG. 4 DUAL CLASS "B" CIRCUIT W NO AUDIBLE SILENCE FEATURE SILENCE FEATURE ow., SYNC. MP44\w ..0 ...A ...u\N nth elNf 0..< ' '' . . . ' . §U111 Agit MI LgNAI Ihi „.. W ,.. .,......6.— II .., II., a h i FIG. 5 SINGLE CLASS "A" CIRCUIT WITH FIG. 6 SINGLE CLASS "A" CIRCUIT WITHOUT AUDIBLE AUDIBLE SILENCE FEATURE SILENCE FEATURE Notes 1. Non -Sync Appliances can be installed before or after a SM or DSM. If the Non -Sync appliance requires audible silence, four wire connection is necessary with the strobe circuit connected before the SM or DSM NAC circuit, and the audible leads connected to a silenceable NAC circuit from the FACP. 2. The audible appliance produces a momentary interruption (approximately 25ms) each time the strobes flash. 3. Circuit #2 may be omitted if only 1 circuit is required when using the DSM. 4. Non -Sync Audible Appliances can be installed on the audible NAC. Be aware of the current requirement for the SM or DSM module. See table 3. Specifications and Ordering Information R =Red Average Order Input Current UL Mounting * RMS current ratings are per UL average RMS method. UL max Model Code Voltage @ 12 or Max* Options*" current rating is the maximum RMS current within the listed volt - VDC 24 VDC age range (16 -33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For SM- 12/24 -R 6369 12 0.017 0.023 W audibles the max current is usually at the maximum listed voltage 24 0.028 0.038 W (33v for 24v units). For unfiltered FWR ratings, see installation DSM- 12/24 -R * ** 6374 12 0.020 0.026 W instructions. ** Refer to Data sheet # S7000 for Mounting Options. 24 0.035 0.055 W ***The maximum number of interconnected DSM modules is twenty (20). The total distance from the first to the last DSM shall not exceed 1,000 feet of #18 AWG wire. Use only #18 AWG wire. WARNING: THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 8 -33 VOLTS USING FILTERED DC OR UNFILTERED FULL -WAVE RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION. THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THESE PRODUCTS, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). WARNING: CONTACT WHEELOCK FOR "INSTALLATION INSTRUCTIONS" (P83123 -SM & P83177 -DSM) AND "GENERAL INFORMATION" SHEET ON THESE PRODUCTS. These documents do undergo periodic changes. It is important that you have current information on these products. These materials contain important information that should be read prior to specifying or installing these products including: • TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. • FUSE RATINGS ON NAC CIRCUITS TO HANDLE MAXIMUM INRUSH OR PEAK CURRENTS FROM ALLAPPLIANCES ON THOSE NAC CIRCUITS. • COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW. • THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED IN PUT VOLTAGE RANGE. • INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. • USE STROBES ONLY ON NAC CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBE ON CODED OR INTERRUPTED NAC CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY NOT FLASH. Architects and Engineers Specifications The sync modules shall be Wheelock Series SM or DSM Sync Modules. Series SM or DSM Sync Modules shall be the master control- lers for Wheelock Series AS /AH. NS /NS4 /NH. RSS, RSSP and appliances where a synchronized audible /visual audible or visual only appliance is specified. All modules shall be UL listed under Standard 464. Series SM and DSM modules shall be designed to interface with Series AS Audible Strobe Appliances and NS Horn Strobe Appliances to produce a syn- chronized temporal (Code 3) horn as well as synchronized strobe flash on a two -wire alarm circuit. Other synchronized products are the Wheelock Series RSS, RSSP, SLM visual only appliances and Series AH and NH Horn Appliances. SM Sync Module shall incorporate two input NAC circuits for power connection from the Fire Alarm Control Panel; one for the strobe NAC circuit and one for the audible NAC circuit. DSM modules shall provide an additional strobe circuit input/output for control of either two Class "B" NAC circuits or a single Class "A" NAC circuit. Upon activation of the audible silence function at the Fire Alarm Control Panel, the audible signal component of Series AS Audible Strobe and /or the Series NS Horn Stobe may be silenced while maintaining strobe activation. Series SM or DSM module shall be designed and available in two versions: the SM -12/24 for control of a single Class B NAC circuit and a dual output version, the DSM -12/24 for control of either Class A two (2) Class B NAC circuits. The DSM dual circuit version shall provide the additional capability of "daisy- chaining ", that is, the ability to interconnect multiple DSM's for synchronous horn and strobe operation on multiple NAC circuits. Interconnection capability shall be for a maximum of 40 NAC circuits. All modules shall operate on either 12 or 24 VDC. Rated average current requirement for the SM 12/24 shall be .017 amperes @ 12 VDC and .028 amperes © 24 VDC. The DSM 12/24 shall be .020 amperes @ 12 VDC and .035 amperes @ 24 VDC. A single circuit SM Sync Module shall be capable of handing a 3 ampere load at 12 or 24 VDC and the dual circuit DSM Sync Module shall be capable of handling a load of 3 amperes per NAC circuit at 12 or 24 VDC. All versions shall be polarized for DC supervision and shall incorporate screw terminals for in /out field wiring of #18 to #12 AWG wire size. The SM and DSM Sync modules shall mount to a 4- 11/16" x 2 -1/8" deep backbox. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. PZENIA WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S3000 SM /DSM 02/08 NJ Location FL Location VA Location 273 Branchport Ave. 7565 Commerce Ct. P: 877- 459 -7726 Long Branch, NJ 07740 Sarasota, FL 34243 F: 703- 294 -6560 P: 800-631-2148 P: 941-487-2300 F: 732 - 222 -8707 F: 941 - 487 -2389 www.coopernotification.com Cooper Notification is Wheelock lM�� SAFEPATH' WAVES, ` Wu COOPER Notification