Plans FP5 02o lo -oral± 10 7(0 3.2 Skit/ w, - Global Project Values: • 41 0 SILEN'I' Project Name:IOPTUMHEALTH I Standby Hours: 24 KNIGHT Project ID:1 I Alarm Mins: _ 5 Prepared By:IADAM SWEET Derating Factor: 1.2 5495 Power Expander Calculations Date: 19 /22/2010 I Voltage Drop Warning Threshold % : 15. Panel ID: I5495(3) Model: Silent Knight 5495 Power Expander Max Circuit Current: 3 Amps Location: 13RD FLR MDF ROOM Volts: 24 VDC Max Panel Current: 6 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Drop Circuit Name /aDrop Standby Alarm & Type 1000 Ft. One -Way Ohms EOL 1 3.1.1 0.000 1.066 #14 Solid 3.109 175 1.09 19.24 5.69% 2 3.1.2 0.000 0.869 #14 Solid 3.19 170 1.08 19.46 4.62% 3 3.1.3 0.000 1.565 #14 Solid 3.19 260 1.66 17.80 12.73% 4 SPARE 0.000 0.000 #14 Solid 3.19 160 1.02 20.40 0.00% Aux 5495(1) Aux Power Out 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 5495 5495 Power Expander 0.075 0.205 3.500 (Amps) Total Output Power Required Total Standby Current (Amps) 0.075 3.705 Total Alarm Current (Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 1.800 0.309 Total Alarm AH Required Total Combined AH Required 2.11 Wire resistances are based upon an ambient temperature of 72 degrees F. Because of Multiply By The Derating Factor 1.20 the minimal difference between solid and stranded wire no differential was made. Minimum Battery AmpHours Required 2.53 Panel ID: 15495(2) Model: Silent Knight 5495 Power Expander Max Circuit Current: 3 Amps • Location: Volts: 24 VDC Max Panel Current: 6 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts @ %Drop Circuit Name Standby Alarm & Type 1000 Ft. One -Way Ohms EOL �oDrop 1 5495(2) Circuit 1 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 2 5495(2) Circuit 2 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 3 5495(2) Circuit 3 0.000 0.000 #14 Solid 1.59 0.00 20.40 0.00% 4 5495(2) Circuit 4 0.000 0.000 #14 Solid 1.59 0.00 20.40 0.00% Aux 5495(2) Aux Power Out 0.000 0.000 #12 Solid 1.59 0.00 20.40 0.00% 5495 5495 Power Expander 0.075 0.205 0.000 (Amps) Total Output Power Required Total Standby Current (Amps) 0.075 0.205 Total Alarm Current (Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 1.800 _ 0.017 Total Alarm AH Required Total Combined AH Required 1.82 Wire resistances are based upon an ambient temperature of 72 degrees F. Because of Multiply By The Derating Factor 1.20 the minimal difference between solid and stranded wire no differential was made. Minimum Battery AmpHours Required 2.18 RECEIVED SEP 232010 CITY OF T►'.^ c �' BUILDING Dtv>:Jiv • ® SILENT KNIG11T Circuit Configuration Project Information Project Name: OPTUMHEALTH Project ID: 0 Prepared By: ADAM SWEET Date: 9/22/2010 Ckt. Number: 1 • Panel ID: 5495(3) INI Ckt. Name: 4.1.1 Max Circuit Current: 3 Amps Qty Device Current Draw Each Current Draw Total ® Standby Alarm Standby Alarm 2 HS 15 0.000 0.082 0.000 0.164 2 ST 15 0.000 0.057 0.000 0.114 4 HS 110 0.000 0.197 0.000 0.788 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 1.066 Ckt. Number: 2 Panel ID: 5495(3) Ckt. Name: 4.1.2 Max Circuit Current: 3 Amps Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm - - 2 HS 15 0.000 0.082 0.000 0.164 3 HS 110 0.000 0.197 0.000 0.591 2 ST 15 0.000 0.057 0.000 0.114 Unused 0.000 0.000 0.000 0,000 0.000 0.000 Totals 0.000 0 869 Ckt. Number: 3 Panel ID: 5495(3) Ckt. Name: 3.1.3 Max Circuit Current: 3 Amps Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 4 HS 15 0.000 0.082 0.000 0.328 2 ST 110 0.000 0.182 0.000 0.364 3 HS 110 0.000 0.197 0.000 0.591 1 HS 185 0.000+ 0.282 0.000 0.282 0.000 0.000 Totals 0.000 1.565 Ckt. Number: 4 Panel ID: 5495(3) Ckt. Name: SPARE Max Circuit Current: 3 Amps Qty Device Current Draw Each Current Draw Total Standby Alarm Standby _ Alarm Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 Unused 0.000, 0.000 0.000 0.000 0.000 0.000 Totals 0.000 0 000 FIRE SYSTEM ACCESSO• Model 5495 Distributed Power Module ` d 4 foal In an emergency, you need maximum power. 0046 r Apar ci .21* The 5495 Distributed Power Module by Silent Knight is the most powerful and cost- effective power supply available today. It delivers 6 amps of notification appliance circuit power and built -in synchronization for appliances from System Sensor®,Gentex®, AMSECO ®, Wheelock and Faraday — what you need to drive power -hungry components like ADA notification appliances. The 5495's advanced microprocessor design is years ahead of the competition. Its switch mode power supply design is up to 50% more efficient than competitive linear mode power supplies. And, ADA retrofits are easier and less expensive with the 5495 because it integrates into current systems without the costly investment in new components. For the most sophisticated and cost - effective notification power supply available, you need the 5495. Call Silent Knight today for more information at 1- 800 - 446 -6444. Model 5495 • Independent trouble relay Distributed Power Module • AC loss delay option shuts off power The 5495 is a 6 amp notification power to non - essential high- current expander that provides its own AC accessories like magnetic door power connection, battery charging holders circuit, and backup battery for use with • Built -in synchronization for fire and security controls such as the appliances from System Silent Knight Model 5208 Fire Control Sensor®,Gentex®, AMSECO ®, /Communicator. The 5495 is the cost- Wheelock and Faraday effective solution for powering • notification appliances required by the Stand alone operation Americans with Disabilities Act (ADA). • Lightweight design adds to ease of The 5495 has built -in ANSI cadence installation and reduces shipping pattern, which can upgrade older costs control panels that lack cadence • Operates with most polarized, UL capability. Listed notification devices Features • UL 864 & 1481 listed �C • UL Listed for 6 amps of notification • CSFM approved power Model 5495 • ANSI Cadence pattern output • Power supply's advanced switch capability built -in Distributed Power Module mode design reduces damaging heat and manages power up to 50% Connection to Local Fire Control more efficiently than other systems The 5495 may be connected to a local 4.7k0 end -of -line resistors provided. • Dip switches allow for easy fire control which utilizes Class A or Since the 5495 draws very little power reconfiguration Class B type notification circuits from the control, it is possible to • 24 VDC filtered output voltage operating between 9 and 32 VDC. The connect one 5495 to each notification control panel's notification circuit is circuit on the control panel and still • Four power - limited notification provide full supervision of the outputs; 2 Class A or 4 Class B, or 1 connected to one of the inputs on the 5495. The control panel's notification notification circuits all the way back to Class A and 2 Class B the control anel. • Additional continuous auxiliary circuit end-of-line resistor is also p connected across two terminals on the output 5495, which provides supervision SILENT • 3 amps per output circuit between the 5495 and the fire control • 2 inputs; 2 Class B or 2 Class A panel. Polarized audible and /or visual ` KNIGHT • Ground fault detector /indicator notification devices are then connected to the 5495 signal circuits using the by Honeywell FIRE SYSTEM ACCESSORY Model 5495 Distributed Power Module 2 Supervision Current: Input The 5495 supervises a variety of Standby 75 mA voltage range: 9 - 32 VDC functions including: Alarm 175 mA Battery charging • Low AC power Auxiliary capacity: 33.0 AH • Low battery condition power circuit: 1 Ambient temp.: 32° to 120° F • Earth ground fault 0° to 49° C Notification • Auxiliary output power limit circuits: 4 Mechanical condition Output Dimensions: 12.25" W x 16" H x • EOL supervision trouble or configuration: 2 Class A (Style Z) 3" D (30.88 cm W power limited condition at an 4 Class B (Style Y) x 40.64 cm H x output (1 Class A & 7.62 D cm) When a trouble condition occurs, 2 Class B) Indicator Lights the 5495 creates a trouble Amps per AC power on : Green condition on the host control signal circuits to which it is connected. the output circuit: 3.0 (6.0 amps total) Battery trouble: Yellow 5495 still maintains the ability to be Notification Ground fault: Yellow activated by the host control. In circuit output: 20.4 to 27.3 VDC addition, the 5495 provides a Form @ 3.0 amps each, Aux trouble: Yellow C trouble relay output as an 4.7 kS2 EOL Output alternative to using the notification resistor required troubles (1 -4): Yellow circuit trouble. on each Class B Approvals: Electrical Specification circuit UL: 864 & 1481 No. of inputs 2 NFPA: 72 AC input: 120 VAC at 2 amps Input CSFM Output: 24 VDC at 6 amps configuration: 2 Class B or 2 Class A Model 5495 Block Diagram Signal Circuit Output Signal 1 Signal 1 Input Distributed Signal 2 Signal Circuit Output Signal 2 Power input Module 5495 Signal 3 (Optional) Signal 4 120 VAC Aux. Power I Trouble Output Local Fire Control (Alternative to notification circuit trouble.) its SILENT This document is not intended to be used for installation purposes. We try to MADE IN AMERICA KNIGHT keep our product information up -to -date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are FORM# 350395 Rev B, 12/05 subject to change without notice. For more information, contact Silent Knight by Honeywell 7550 Meridian Circle Suite 100, Maple Grove, Mn 55369 -4927. Copyright © 2005 Silent Knight Phone: (800) 328 -0103, Fax: (763) 493 -6475. Wheelock`' ExcederTM Series COOPER Notification ED Finally, Design and Safety Meet... LI1 - !A • FIRE , l lt 1 Ceiling Wall Description: The Wheelock® Exceder Series of notification appliances feature a sleek modern design that will please building owners with reduced - Save up to 48% in current draw* total cost of ownership. Installers will benefit from its comprehensive feature list, including the most candela options in one appliance, low current draw, no tools needed for setting changes, voltage test - Up to 9 models now in 1 appliance points, 12/24 VDC operation, universal mounting base and multiple mounting options for both new and retrofit construction. - Save up to 14% cost of installation ** The Wheelock® ExcederTM Series incorporates high reliability and high efficiency optics to minimize current draw allowing for a greater number of appliances on the notification appliance circuit. All strobe models feature an industry first of 8 candela settings on a single u Sleek Modern Aesthetics appliance. Models with an audible feature 3 sound settings (90, 95, • 99 dB). All switches to change settings, can be set without the use of a tool and are located behind the appliance to prevent tampering. Finger Slide Switches Wall models feature voltage test points to take readings with a voltage meter for troubleshooting and AHJ inspection. The Wheelock ExcederTM Series of wall and ceiling notification Voltage Test Points appliances feature a Universal Mounting Base (UMB) designed to simplify the installation and testing of horns, strobes, and combination horn strobes. The separate universal mounting 1 Multiple Voltages base can be pre -wired to allow full testing of circuit wiring before the appliance is installed and the surface is finished. It comes complete with a Contact Cover for protection against dirt, dust, paint 3 Audible Settings and damage to the contacts. The Contact Cover also acts as a 90, 95, 99 d6 shunting device to allow pre -wire testing for common wiring issues. The Contact Cover is polarized to prevent it from being installed incorrectly and prevents the appliance from being installed while 8 Candela Settings * ** it is on the UMB. When the Contact Cover is removed the circuit Wall - 15/1575/30/75/95 /110/135/185 will show an open until the appliance is installed. The UMB allows Ceiling - 15/30/60/75/95/115 /150/177 for consistent installation and easy replacement of appliances if required. Wall models provide an optional locking screw for extra WO Universal Mounting Base * ** secure installation, while the ceiling models provide a captivated Ceiling and Wall screw to prevent the screw from falling during installation. Mounts to 5 Backbox Types U Environmentally Friendly Low Current Draw Compatibility and Requirements - Synchronize using the Wheelock' Sync Modules or panels with built -in Wheelock Patented Sync Protocol - Compatible with UL "Regulated Voltage" using filtered VDC or unfiltered VRMS input voltage - Strobes produce 1 flash per second over the "Regulated Voltage" range Compared to competitive models "" Patented Compared to previous models NOTE: All CAUTIONS and WARNINGS are identified by the symbol d. All warnings are printed in bold capital letters. 4. IL WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND /OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND /OR OTHERS. General Notes: General Notes: • Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range ". • All candela ratings represent minimum effective strobe intensity based on UL Standard 1971. • Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32 °F to 120 °F (0 °C to 49 °C) and maximum humidity of 93% (± 2 %) UL 464 (85% UL 1971). • Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only). Low Current Draw = Fewer Power Supplies Strobe Ratings per UL Standard 1971 UL Max Current' 24 VDC / 24 FWR 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC ST 8.0 -33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140 • STC 8.0 -33.0 0.061 r j 0.085 0.103 0.135 0.163 ; 0.182 0.205 0.253 ; 0.110 Horn Strobe Ratings per UL 1971 & UL 464 at 24 VDC UL Max Current* at 99 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0 -33.0 0.082 0.095 0.102_ 0.148 0.176 0.197 0.242 0.282 0.125 0.159 HSC 8.0 -33.0 0.082 LJ 0.102 0.141 0.148 0.176 0.197 ; 0.242 0.282 0.125 UL Max Current' at 95 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0 -33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153 HSC 8.0 -33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122 UL Max Current' at 90 dBA 24 VDC 12 VDC Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC HS 8.0 -33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148 • HSC 8.0 -33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120 Horn Ratings per UL 464 • Regulated Voltage Model Range VDC 99 dB 95 dB 90 dB 44(Z-- HN 16 -33.0 0.064 0.044 0.022 HNC 16 -33.0 0.084 0.044 0.022 3 HN 8.0 -17.5 0.047 0.026 0.017 . HNC 8.017.5 0.047 0.026 0.017 * UL max current rating is the maximum RMS current within the listed voltage range (16 -33 VDC for 24 VDC units). For strobes the UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions. Specification & Ordering Information Strobe Sync wl SM, Mounting Model DSM or 12/24 VDC* Candela PS -6 & PS -8 y Options d • Horn Strobes o Jo HSR 15/1575/30/75/95 /110 /135/185 X X UMB ** o 15/1575/30/75/95 /110/135/185 X X C UMB ** V - • 15/30/60/75/95/115 /150/177 X X a UMB ** 0 HSWC 15/30/60/75/95/115 /150/177 X X °d UMB ** -o 0 o Strobes V u E STR .5 15/1575/30/75/95 /110/135/185 X X UMB "" u) STW 15/1575/30/75/95 /110/135/185 X X c'i UMB** E STRC 15/30/60/75/95/115 /150/177 X X 0 UMB "* STWC C 15/30/60/75/95/115 /150/177 X X 4 UMB ** E ti Horn Cl) CO c L f0 G HNR d ._ X X 0 UMB"" N HNW C X X UMB ** HNRC V X X rn UMB ** MI W HNWC CO X X r UMB ** *12 VDC models feature 15 815/75 settings * *UMB = Universal Mounting Base Wrq t Model Legend 4 r- 4 C 4,4' . Z 1 11 HN = Horn '� 4, ST = Strobe ' .r ` � HS = Horn Strobe . !. C = Ceiling Mount` //Pi , \ W = White ti ` R =Red Example 1: STRC = Strobe, Red, Ceiling Mount / Example 2: HSR = Horn Strobe, Red, Wall Mount Example 3: HSW = Horn Strobe, White, Wall Mount Example. Example: HSWC j .41'Ni 1 L 4 0 0 b �. s *UMB Co ntact Cove Voltage test points for quick 8 candela settings Common base for wall and ceiling with 5 troubleshooting and easy spot mounting options checking (wall models only) NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions. Architects and Engineers Specifications The notification appliances shall be Wheelock ExcederTM Series HS Audible Strobe appliances, Series ST Visual Strobe appliances and Series HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency Devices for the Hearing- Impaired) for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard • 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC. Indoor wall models shall incorporate voltage test points for easy voltage inspection. The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design. Where Multi - Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on -axis is required (e.g. ADA compliance). Appliances with candela settings shall show the candela selection in a visible location at all times when installed. The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow mounting to a single -gang, double -gang, 4 -inch square, 3.5 -inch octal, 4 -inch octal or 100mm European type back boxes. Two wire appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible. The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58" W x 2.19" D. Series HN wall shall measure 5.24" H x 4.58" W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series HNC ceiling shall have a diameter of 6.68" x 1.50" D. When synchronization is required, the appliance shall be compatible with Wheelock®'s SM, DSM Sync Modules, Wheelock® Power Supplies or other manufacturer's panels with built -in Wheelock® Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync protocol fails to operate, the strobe shall revert to a non- synchronized flash -rate and still maintain (1) flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock® synchronization protocol. Wall Appliances — UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC Ceiling Appliances — UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC NEM WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Exceder - Spec Sheet 11/09 NJ Location FL Location VA Location 273 Branchport Ave. 7565 Commerce Ct. 4401 Wilson Boulevard, Suite 220 Long Branch, NJ 07740 Sarasota, FL 34243 Arlington, VA 22203 P: 800 - 631 -2148 P: 941- 487 -2300 P: 877 - 459 -7726 F: 732 - 222 -8707 F: 941- 487 -2389 F: 703- 294 -6560 / www.coopernotification.com � , Cooper Notification is Wheelock' (MEDC SAFEPATH• WAVES, a t) COOPER Notification [Page Too Large for OCR Processing] [Page Too Large for OCR Processing]