Loading...
Plans FPS 026 I o -cri s'y- 10 ©3I 5 Ca,aco,.dQ - Global Project Values: 10 SILENT Project Name:1ULTIMATE ELECTRONICS 1 Standby Hours: 24 1 KNIGHT Project ID:1 Alarm Mins: 5 • Prepared Bv:1ADAM SWEET 1 Derating Factor: 1.2 5808 Calculations Date:18 /3/2010 Voltage Drop Warning Threshold % : 19 Panel ID: 15808 Model: 5808 Add. Fire Alarm Control Panel Max NAC Current: 3.0 Amps Location: 1 Volts: 24 VDC Max Panel Current: 6.0 Amps Current Draw Wire AWG Ohms Per Length(ft) Actual Volts 0 %Drop Circuit Name Qty Standb Alarm & T •e 1000 Ft. One -Wa Ohms EOL kDrop 5808 5808 CTRL Panel 1 0 0 Module 5860 LCD Remote Annunc 1 0.020 0.025 5824 Serial/Parallel 000 0.000 Power p .- 0.000 0.000 5865 -4 LED Annunciator (4G) 0.000 0.000 5865 -3 LED Annunciator (3G) 0.000 0.000 5880 LED Driver Module 0.000 0.000 Other 0.000 0.000 Other 0.000 (D.I000 SD-Duct Duct . 0.000 0.000 5883 Relay Module 0.000 0.000 PGM -I /O #1 Notification Appl Circuit 0.000 1.762 #14 Solid 2.54 365 1.85 17.13 16.02% . PGM -I /O #2 Notification Appl Circuit 0.000 1.460 #14 Solid 2.54 305 1.55 18.14 11.09% PGM -I /O #3 Notification Appl Circuit 0.000 1.630 #14 Solid 2.54 450 2.29 16.67 18.27% PGM -I /O #4 Initiating Device Circuit 0.126 0.390 #14 Solid 2.54 0.00 20.40 N/A Aux Power *1 # of NAC's Used 0.000 0.000 Total Standby Current (Amps) 0.358 5.629 Total Alarm Current (Amps) Standby Time In Hours 24 0.083 Alarm Time In Minutes / 60 (5 Mins) Total Standby AH Required 8.580 0.469 Total Alarm AH Required Total Combined AH Required 9.05 Command Shortcuts Multiply By The Derating Factor 1.20 r ,- - \ Minimum Battery AmpHours Required 10.86 Configure Circuits Print Page J I #1 . Note: A value msut be entered if ou have selected an NAC circuits as AUX Power. RECEIVED AUG 0 6 2010 CITY OF TIGARD BUILDING DIVISION • 0 Sinn/ K NIGHT ' Circuit Configuration Project Information Project Name: ULTIMATE ELECTRONICS Project ID: 0 Prepared By: ADAM SWEET Date: 8/3/2010 Ckt. Number: PGM -I /O #1 Panel ID: 5808 Ckt. Name: Notification Appl Circuit I/O Use: Notification Appl Circuit ■ Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 8 System Sensor PC2R/P2RK 110 0.000 0.212 0.000 1.696 1 System Sensor SCR 15 0.000 0.066 0.000 0.066 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 1.762 Ckt. Number: PGM -I /O #2 Panel ID: 5808 Ckt. Name: Notification Appl Circuit I/O Use :l Notification Appl Circuit 1 • Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 6 System Sensor PC2R /P2RK 110 0.000 0.212 0.000 1.272 2 System Sensor SCR 30 0.000 0.094 0.000 0.188 Unused 0.000 0.000 0.000 0.000 Unused 0.000 0.000 0.000 0.000 0.000 0.000 Totals 0.000 1.460 Ckt. Number: PGM - /O #3 Panel ID: 5808 Ckt. Name: Notification Appl Circuit I/O Use: Notification Appi Circuit v Qty Device Current Draw Each Current Draw Total Standby Alarm Standby Alarm 4 System Sensor SCR 15 0.000 0.066 0.000 0.264 6 System Sensor PC2R /P2RK 110 0.000 0.212 0.000 1.272 1 System Sensor SCR 30 0.000 0.094 0.000 0.094 Unused 0.000 0.000 0.000 0.000 0.000 0.000 I • Totals 0.000 _ _ .630 _i l • INTELLIKNIGHT MODEL 5808 FIRE ALARM CONTROL PANEL IntelliKnight® Model 5808 T Single Loop Addressable Fire Alarm Control System Yw ,' r The convenience of an addressable fire �. •,_. alarm control panel in a cost effective easy to use package. ICJ Ira ry IntelliKnight Model 5808 is a 127 point class leading single loop addressable fire alarm control /communicator system that provides you with the revolutionary value and performance of addressable sensing technology combined with exclusive, built -in digital communication, distributed intelligent power, easy to use interface. Powerful features such as drift compensation and maintenance alert are delivered in this powerful FACP from Silent Knight. For more information about the IntelliKnight system, or to locate your nearest source, please call 1- 800 -446 -6444, or in Minnesota, call 763 -493 -6435. Description • Built -in RS -232 interface for The IntelliKnight 5808 performs drift programming via PC. compensation and calibration checks • Built -in Form C trouble relay rated at on each of the sensors in the system. 2.5 amps at 24 VDC. The basic IntelliKnight 5808 system • Two built -in Form C programmable can be enhanced by adding modules relays rated at 2.5 amps at 24 VDC. such as the Model 5860 Remote Approvals: Annunciator, the Model 5824 UL Listed / NFPA 72 Serial /Parallel Interface (for printing - Central Station system reports), and an Intelligent -DACT Power Module. The Model 5808 also -Local Protective features a powerful built -in dual line fire Signalling System communicator that allows for reporting -Water Deluge of all system activity to a remote Releasing Service monitoring location. Features Specifications • Up to 127 addressable points. Primary AC: 120 VRMS at 50 / 60 hz, • Uses standard wire —no shielded or 2.75A twisted pair required. Total Accessory Load: 6A at 24 VDC • Built -in digital communicator. 6 amps at 24 VDC of power - limited • Central station reporting by Point or notification power by Zone. Standby Current: 206 mA • Supports Class B (Style 4) and Class Alarm Current: 356 mA Model 5808 A (Style 6) configuration for SLC. Notification circuits: 3 amps of Telephone Requirements: • Distributed, intelligent power. power- limited power per circuit at 24 FCC Part 15 and Part 68 approved • Drift compensation. VDC. • 13 re ro rammed output Type of Jack: RJ31X (two required) P P 9 P Auxiliary power circuits: 3 amps of cadences, (including ANSI - 3.41), and power - limited power per circuit at 24 4 programmable outputs. VDC. • Notification circuits can be configured Mechanical Specifications: as 2 Class A (Style Z) or 4 Class B (Style Y), or auxiliary power for Flush Mount resettable, constant, or door holder Dimensions power. 14.5 "W x 24.75 "H x 3.5 "D - Built -in annunciator with 80- character (36.8W x 62.9H x 8.73D cm) LCD display. Overall • • RS-485 bus provides communication Dimensions: to system accessories. 16 "W x 26.4 "H x 4.65 "D SILENT • Up or Down load programming, (40.6 x 67 x 11.8 cm) KNIGHT' event history, or detector status via Weight: 28 lbs. (12.8 kg) remote or direct connection. Color: Red INTELLIKNIGHT FIRE ALARM CONTROL PANEL • SLC Sensor Devices Intelligent SLC Modules 5496 Intelligent Power Module Model SD505 -APS Model SD500 -AIM The Model 5496 is a 6 amp.notification power Addressable photoelectric smoke detector. Dry Contact Input Module. Designed to used expander that provides • Model SD505 -AIS with normally open dry contacts. Mounts in a four additional power - Addressable ionization smoke detector. 4 inch square electrical box. It features an limited notification indicator LED to show alarm status and a appliance circuit outputs. Model SD505 -AHS coverplate. Addressable heat sensor. Model SD500 -MIM 5865 -3 and 5865 -4 Model SD505 -6AB Mini Dry Contact Input Module. A miniature Remote LED Six inch base designed for use with detector version of the addressable input module Annunciator head models SD505 -APS, SD505 -AIS and which is designed to be used with pull Features 30 Programmable LEDs (15 red SD505 -AHS. stations and other normally open dry contact and 15 yellow) outputs and piezo sounder. Model SD505 -ADH inputs where a smaller size is desired. The 5865 -4 adds a silence and reset switch Model SD500 -ARM to the package. Duct Housing. Detects smoke in I-1VAC 5883 Relay Board ducts. Use with SD505 -APS or SD505 -AIS. Addressable Relay Module. Features 2 y SD505- ADHR /DTS Form C output relays, designed to mount on Features 10 General purpose Form C a 4 inch square electrical box. Provides relays. Used with 5880 module. Addressable Duct smoke detector with built- indicator LED to show output status and 5824 Serial /Parallel Gateway in relay module detects products of comes with a coverplate. combustion present in air moving through an Module HVAC system. Provides form C alarm Model SD500 -LED Has one parallel and one RS -232 serial port contact. The SD505 -ADHR is compatible An LED driver capable of driving 80 LEDs for connecting any standard IBM - compatible with the SD505 -DTS, which provides remote through the SLC loop. Up to 40 SD500- printer to the IntelliKnight system. Interfaces annunciation and testing capabilities for the LEDs can be used per system. with building control system. SD505 -ADHR. Use with SD505 -APS or S -BUS Accessories SKSS Silent Knight Software SD505 -AIS. The following items listed are devices that Suite Model SD500 -PS connected to the IntelliKnight's RS-485 Bus Addressable Pull Station with visible LED. 5860 Remote Fire Annunciator 5660 Up Down Load Software The 5860 features the same 80 character User - friendly, WindowsTM software for backlit LCD display keypad and firefighter's remote programming of the IntelliKnight keyswitch as the 5820. The system can be panel using a PC. fully programmed and operated from any 5670 Facility Management remote annunciator. Software 5880 LED/I0 Module Powerful end -user software allows viewing Features 40 LED outputs, 8 normally open of detector status and event history via dry contact inputs and one piezo output. modem or direct connection. M. I I I - lmEiL SDSM.OED 111 .. .. .. ÷1111: SYO IIIE SOSOO.ANY SOSOS. PS SDSOS.AlS SOS05.AHS I - • I g".12" kili A *A {t I "" I theft .MOlo oawdo. io . I_ I l.pRNIF.wYaMmub I la ♦ 10..FAO l pIM m MN/OF 1 fON..O. AI •■■••• _ Ynrrwr,wl I 4 R E 44 SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800 -446 -6444 or in Minnesota 763 -493 -6435 FORM# 350386, Rev. 9/01 FAX: 763 -493 -6475 World Wide Web: http: / /www.silentknight.com Copyright © 2001 Silent Knight n ' INTELLIKNIGHT ACCESSORY Model 5860 2 Remote Annunciator f Bring the power to control IntelliKnight® to every j ... i � `' ` area within your facility. ..- . r 2 , 1 Now you can operate and program your IntelliKnight system from up to 8 locations throughout your facility. The Model 5860 Remote Annunciator provides the same advanced, easy -to -use interface found on the IntelliKnight panel's built -in annunciator. The 80- character display and ergonomically designed keypad allow for simple and error -free system operation. All operations — including reset, silence, detector status checking, fire drill, and programming —are identical. Access to the system is through a firefighter's key or an access code. For security, a special installation code is needed for programming functions. The 5860 connects to the IntelliKnight panel via the RS -485 system bus. Wire runs can be up to 6000 feet from the panel. Model 5860 Users identify themselves to the Remote Annunciator panel by enterin a code on the annunciator or by turning the • .. Y , The 5860 is designed to look and firefighter's key. When a user operate exactly the same as the presses a button, the annunciator , a IntelliKnight built -in annunciator. piezo beeps and the LCD prompts Features include an 80- character the user to enter a code or other A backlit LCD providing easy -to- relevant information. understand system messages. The annunciator is ergonomically Multiple users can work at different 5860 Remote Annunciator designed with over -sized buttons annunciators simultaneously for the most frequently used without affecting each other. Specifications features, like Reset and Silence. Operating Voltage 24 VDC FNtVreS Standby Current: 20 mA In addition to status messages • 80- character display displayed on the LCD, there are Alarm Current: 25 mA • Tactile /audible feedback five LEDs for alarm, supervisory, Max. per system: 8 • trouble, silence, and AC power Accepts user codes or firefighter's key Ambient Temperature: 32 °F to 120 °F status. • RS -485 interface to panel (0°C to 49°C) The annunciator is available in gray Can be flush- or surface- Mounting: Surface or flush • to match virtually any decor and red mounted. Trim ring available for Wiring Distance from for applications where the IntelliKnight panel: Up to 6,000 feet annunciator must stand out. The surface - mounting. annunciator enclosure can be • Operation and appearance Dimensions: Height: 7 -3/8" surface or flush mounted. A trim identical to on -board annunciator De tn: 9-1/8" Depth: 1 -1/2" ring kit is available for surface • Supports simultaneous use by Colors: Lt. gray (5860) mounting. multiple users Red (5860R) Operation • UL listed, complies with NFPA 72 When the system is normal and • CSFM Approved receiving AC power, the power LED • MEA Listed is lit and all other LEDs are off. Other LEDs turn on as the SILENT conditions occur. KNIGHT INTELLIKNIGHT ACCESSORY Model 5860 Remote Annunciator ' Engineering Specifications The main control must have a built -in annunciator and must support up to eight remote annunciators. Remote annunciators shall have the same control and display layout so as to match the appearance of the built -in annunciator. Remote annunciators shall be available in two colors, red or light gray. Remote annunciators shall have identical functionality and operation as the built -in annunciator. All annunciators must have an 80- character LCD display and must feature five LEDs for: General Alarm, Supervisory, System Trouble, System Silence, and System Power. All controls and programming keys are silicone mechanical type with tactile and audible feedback. Keys have a travel of .040 inches. No membrane style buttons will be permissible. The annunciator must be able to silence and reset alarms through the use of a code entered on the annunciator keypad or by using a firefighter's key. The annunciator must have two levels of user codes that will limit the operating system programming to authorized individuals. The control panel must allow all annunciators to accommodate multiple user input simultaneously. 5860 Block Diagram w Up is 600L' feel from panel a a - �:::� ?• + D err `f 0= • Up 10 8 devices per system. • SILENT it KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800 - 446 -6444 or in Minnesota 612 - 493 -6435 FORM# 350224, Rev. 01 /00 FAX: 612- 493 -6475 World Wide Web: http: / /www.silentknight.com Copyright © 2000 Silent Knight INTELLIKNIGHT ACCESSORY SD500 -PS and SD500 -PSDA Addressable Pull- Station ilk ►- ,,.:t • .. . }f ..3iN n ht's addressable pull stations ,� ` N 9 p . ° _ ,, o combine fast response with pin -point o p location ID. The SD500 -PS and SD500 -PSDA are a single action or dual action addressable manual fire alarm pull station for use with Silent Knight's IntelliKnight fire control panel. Extremely easy to operate, the SD500 -PS /PSDA provides a fast and practical means of manually initiating a fire alarm signal. The IntelliKnight panel recognizes each manual pull station by its specific address saving precious seconds in determining the location of an alarm. The SD500 -PS /PSDA mounts to a single gang box and features a rugged metal construction that lasts and lasts. Combine all this with the features you've come to expect from Silent Knight - easy installation and stable operation - and it adds up to a flexible solution for all your fire protection needs. Model SD500 -PS & • Extremely easy to operate SD500 -PSDA • Corrosion - resistant gold - plated contacts. 4 PULL 4 Addressable Pull • Reflective label makes it easier Station to locate in low light The SD500 -PS is a single action Operation i addressable fire pull station, and The SD500 -PS /PSDA single action the SD500 - -PSDA is a dual action pull stations are operated by a pull " R' `'` addressable fire pull station. The on the front pull cover of the SD500 -PS /PSDA feature rugged station. A plunger switch, wired to metal construction A terminal strip a self contained addressable ���� on back of the pull station allows module, is released as the pull interconnection of the pull station to station opens to initiate the alarm. 1 the SLC of an IntelliKnight control Once operated, the cover hangs panel. The SD500 -PS /PSDA is down and can be seen up to 100 � LA �� designed for indoor use in non- feet away. The pull station is reset explosive environments. The by returning the front cover to the normally open initiating point normal upright position and contacts are gold - plated to avoid relocking the station with a reset , ,111 i risk of corrosion. The SD500- key. The reset keys are the same ,, htili -ii i PS /PSDA has been tested by UL keys used on Silent Knight for compliance to the requirements enclosures. of the Americans with Disabilities The SD500 -PS /PSDA includes a ACT (ADA). status LED which blinks, indicating SD500 -PS Features that the addressable module is Ambient Temperature: 32 °F to 120 °F • UL Listed communicating with the loop. The (0 °C to 49°C) • CSFM listed status LED lights continuously Mounting: Single gang • during an alarm. A dip switch on box - • ADA compliant the addressable module is used to Optional Red Surface Mount Box PS - SMBB • Key reset (Same key as Silent set the unique address. Knight enclosures) • Surface mount back box Specifications available Operating Voltage: 24VDC SILENT Standby Current: .55mA KNIGHT • Terminals - accept up to 14 Alarm Current: .55mA To gauge wire A li..,,rd Crew y, INTELLIKNIGHT ACCESSORY SD500 -PS and SD500 -PSDA Addressable Pull- Station 2 Engineering Specifications Manual pull station shall be addressable Module SD500- PS /SD500 -PSDA. Equipment shall be made of 14 gauge C.R.S.(Cold Rolled Steel), painted with a red enamel . The label shall contain the words Fire Alarm and be made of a reflective material embossed text 3/8 inches tall. Operating instruction shall be clearly visible on the same label. Manual station Shall contain a key operated test and reset lock using a lock plate actuator, the key shall match the control panel. Manual station shall contain four terminal blocks with two connected to the addressable module and two connect to the SLC loop. Manual station shall provide data to the control panel with an ID address programmed by dip switch settings . Manual stations shall be Underwriters Laboratories Inc. listed and installed within the limits defined in the American Disabilities Act. R F!i%P - ,, _ s \ i / • ' % , 4:k 10 ,,......... , A , ' .1 ,71. s ` 2 rs,— R Q N%,, \ ‘ Cr r* s imi i i i um Es \ I `• \ I II 111 ti I I ``� ``, i, SPS SAC •b -- SINWINCOPS SLC - ro ;AtoSAC - ■ % Illrilli Nib Wiring r 21: I I I I ) Mounting to Single Mounting to Optional * PV Gang Electrical Box Surface Mount Box I SD500 -PSDA 4 ii LIFT 1 1. Electrical Boa must be Installing SD500 -LK at NNW 1 - ti 7° 0..s'P Dimensions • SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800 -446 -6444 or in Minnesota 763 - 493 -6435 FORM# 350342, Rev. 09/03 FAX: 763 - 493 -6475 World Wide Web: http: / /www.silentknight.com Copyright © 2003 Silent Knight INTELLIKNIGHT ACCESSORY lia Addressable 2 ,,' Photoelectric Type '► Smoke Detector 3 r 1 1 Detect smoldering fires quickly and get help fast • with IntelliKnight- photoelectric smoke detectors. LI At IntelliKnight addressable photoelectric smoke detectors are the clear choice for commercial settings where smoldering fires are a threat. In addition to accurately detecting a smoldering fire, each SD505 -APS photoelectric detector has a unique address, which is recognized by the IntelliKnight panel. No precious seconds are wasted in determining location of an alarm. The SD505 -APS compensates automatically for contamination in the environment. And detector testing is simple —even from a remote site. Like other IntelliKnight detector models, the SD505 -APS offers a low profile for pleasing aesthetics. The IntelliKnight family of detectors has been designed to use a common base, Model SD505 -6AB, allowing complete application and placement flexibility. Combine all this with the features you've come to expect from Silent Knight smoke detectors —easy installation, stable operation, RF /transient protection, and vandal- resistant locking —and it adds up to a flexible solution for all your fire protection needs. Model SD505 -APS The light received is converted into Analog / an electronic signal. Under normal 9 conditions, the status LED blinks Photoelectric Type approximately every 15 seconds, � I indicating that the head is Smoke Detector communicating with the loop. The • • The SD505 -APS is particularly LED lights continuously during the suited to detecting dense smoke alarm period. typical of fires involving materials such as soft furnishings, plastic, Features foam or other similar materials • Low profile, 2 inches, including SD505 -APS Smoke Detector which tend to smolder and produce base large visible particles. • Simple and reliable addressing The detector features automatic without mechanical switches Specifications Operating Voltage: 17 -41 VDC compensation for contamination • Automatic compensation for and a simple detector calibration Current Consumption: p sensor contamination test procedure that can be run from Built-in fire test feature Standby: .55 mA the panel or remotely (using the Alarm: .55 mA WindowsTM based downloading • Simple detector calibration ° ° g testing through the control panel Ambient Temperature: 32°F to 100°F software). or remotely through a (0°C to 50 °C) tion WindowsTM based computer Mounting: 4" Square, 4" OCT, �� software. Single gang mud ware. The SD505 -APS units made up of ring an LED light source and a silicon • Vandal- resistance locking Relative Humidity: 85% photo diode receiving element. In a features noncondensing normal standby condition, the • Field cleanable Sensitivity: 0.88% - 3.57% FT receiving element receives no light • UL listed, meets NFPA 72 Ch 7 Air Velocity: 500 4000 FPM from the pulsing light source. In the requirements event or fire, smoke enters the • CSFM approved • detector and light is reflected from MEA approved • the smoke particles to the receiving SILENT element. likk KNIGHT INTELLIKNIGHT ACCESSORY Model SD505 -APS Addressable Photoelectric Type Smoke Detector Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable photoelectric smoke detector Silent Knight SD505 -APS. The combination detector head, and twist -lock base, shall be UL® listed compatible with Silent Knight's IntelliKnight 5820XL fire panel. The base shall permit direct interchange with Silent Knight SD505 -AIS Ionization Smoke Detector, or SD505- AHS Heat Detector. Base shall be the appropriate twist -lock base SD505 -6AB. The smoke detector shall have a flashing status LED for visual supervision. When the detector is actuated, the flashing LED will latch on steady. The detector may be reset by actuating the control panel reset switch. The calibration of the detector shall be capable of being selected and measured by the control panel without the need for external test apparatus. The vandal- resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable as required. The SD505 -APS shall automatically perform a functional test of the detector. The test method shall simulate effects of products of combustion in the chamber to ensure testing of detector circuits. N Diameter = 5- 15/16" M Diameter = 3- 15/16" 11 01 ( r- - Height = 2 inches, • including base `u B M:NIGHT Model SD505 -6AB Detector Base Model SD505 -APS Detector Head (front view) (front view) f t SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800 - 446 -6444 or in Minnesota 612493 -6435 FORM# 350225, Rev. 01 /00 FAX: 612 -493 -6475 World Wide Web: http: / /www.silentknight.com Copyright © 2000 Silent Knight INTELLIKNIGHT ACCESSORY Model SD500 -AIM Addressable Input Module A And Model SD500 -MIM i Miniature Input Module • I Y ' tea, IntelliKnight's addressable contact monitor modules combine fast response with pin -point location ID. A combination that saves lives and property. The SD500 -AIM and SD500 -MIM are addressable input modules for use with Silent Knight's IntelliKnight fire control panel. The SD500 -AIM and SD500 -MIM are designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm initiation devices. The SD500 -AIM addressable input module mounts to a 4 "- square box. The SD500 -MIM mini input module fits inside a single gang box. The modules are supervised, single input contact monitors. Using an EOL resister, they monitor for alarm contact closures and for open circuit wiring fault conditions. The SD500 -AIM and SD500 -MIM offer a compact design for adaptability and pleasing aesthetics as well as easy installation and stable operation —a flexible solution for all your fire protection needs. Model SD500 -AIM and SD500 -MIM Input Modules The addressable input modules expand the flexibility of the qi• IntelliKnight system by allowing the i,} use of contact type inputs. Typical applications include manual pull stations and water flow switches. ' r ' t Features • Operates on Class A (Style 6 & -. — - - Style 7) or Class B (Style 4)SLC Loop. 50500 -AIM 5050C' -MIM. • Single contact monitor. • Up to 127 modules per SLC Operation Specifications loop. Each addressable input module is Operating Voltage: 24 VDC • SD500-MIM mounts in a single programmed with a unique SLC Standby Current: 0.55 mA loop address. The module gang box. supervises the wiring to the contact Alarm Current: 0.55 mA • SD500 -AIM mounts in a with an End Of Line (EOL) resistor. Ambient Temperature: 32 °F to 120 °F 4 "- square or double gang If a fault occurs in the wiring, the (0 °C to 49°C) electrical box, and has an module alerts the FACP. Mounting: SD500 -AIM attractive ivory cover plate. double gang box or • SD500- AIM /MIM are DIP switch 4 "- square electrical programmable. box • Accepts up to 14 gauge wire. S sinngle gle gang g ng box • Both modules UL 864 listed; comply with NFPA 72 SILENT' • 2500 ft max. wiring distance from input module to contact. KNIGHT • CSFM listed. INTELLIKNIGHT ACCESSORY Model SD500 -AIM and SD500 -MIM • Addressable Input and Mini Input Modules Engineering Specifications The contractor shall furnish and install where indicated on the plans, addressable input modules Silent Knight SD500 -AIM or SD500 -MIM. The modules shall be UL listed and compatible with Silent Knight's IntelliKnight 5820XL fire panel. The SD500 -MIM shall fit inside a single gang electrical box. The SD500 -AIM shall be supplied with a plastic cover and shall be suitable for mounting to a 4 "- square or double gang electrical box. The SD500 -AIM addressable input module must provide a monitor LED that is visible from outside the cover plate. Model 5D500 -AIM FRONT VIEW BACK VIEW SIDE VIEW Qw. Illy. 1 1' Model SD500 -MIIM 3 -103 All # 4 ■ 1* SILENT KNIGHT 7550 Meridian Circle, Maple Grove, MN 55369 -4927 MADE IN AMERICA 800 - 446 -6444 or in Minnesota 612 -493 -6435 FORM# 350231, Rev. 01 /00 FAX: 612- 493 -6475 World Wide Web: http: / /www.silentknight.com Copyright © 2000 Silent Knight SYSTEM SENSOR Selectable Output ,.., Notification Devices R SpectrAlert' Advance selectable - output horns, strobes, and horn /strobes are rich with features guaranteed to IE cut installation times and maximize profits. SPECTRANert A- w V A N G E The SpectrAlert Advance series of notification appliances is Features designed to simplify your installations, with features such as: plug in Plug-in design designs, instant feedback messages to ensure correct installation of individual devices, and eleven field - selectable candela settings for • Same mounting plate for wall- and ceiling -mount units wall and ceiling strobes and horn /strobes. • Shorting spring on mounting plate for continuity check before installation More specifically, when installing Advance products, first attach a universal mounting plate to a four -inch square, four -inch octagon or •Captive mounting screw double -gang junction box. The two -wire mounting plate attaches to •Tamper resistance capability a single -gang junction box. • Field selectable candela settings on wall and ceiling units: 15, 15/75, Then, connect the notification appliance circuit wiring to the SEMS 30, 75, 95, 110, 115, 135, 150, 177, 185 terminals on the mounting plate. • Automatic selection of 12 or 24 volt operation at 15 and 15/75 candela Finally, attach the horn, strobe or horn /strobe to the mounting plate Outdoor wall and ceiling products by inserting the product's tabs in the mounting plate's grooves. The device will rotate into position, locking the product's pins into the • Outdoor products rated from -40° to 151°F mounting plate's terminals. The device will temporarily hold in place • Minimal intrusion into the back box with a catch until it is secured with a captured mounting screw. SpectrAlert Advance products allow you to choose: • Horn rated at 88+ dbA at 16 volts • 12 or 24 volts • Rotary switch for tone selection • At 24 volts, 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177 or 185 • candela by way of rear - mounted slide switch and front viewing 3 horn volume settings window • Electrically compatible with existing SpectrAlert products • Horn tones and volume by way of rotary switch • The SpectrAlert Advance series includes outdoor notification Agency Listings appliances. Outdoor strobes and horn/strobes (two wire and four wire) are available for wall or ceiling. Outdoor horns are available for SIGNALING wall only. All System Sensor outdoor products are rated between 0 ME T 7125-1653.186 (ndoor strobes) L 7125- 1653 strobes) minus 40 degrees Fahrenheit and 151 degrees Fahrenheit in wet or U a pp roved � � 7125 - 1 7125 - 1653: (barb) bes) LISTED APPROVED �1 189 (barb) dry applications. SpectrAlert Advance Specifications Architect /Engineer Specifications General SpectrAlert Advance horns, strobes and horn /strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4 -inch octagon back box or double -gang back box. Two -wire products shall also mount to a single -gang 2 x 4 x 1A -inch back box A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit' Module accessory, shall be powered from a non -coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12 -volt rated notification appliance circuit outputs shall operate between nine and 17.5 volts; 24 -volt rated notification appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC, or full -wave rectified, unfiltered power supply. Strobes and horn /strobes shall have field - selectable candela settings induding 15,15/75, 30, 75, 95,110,115, 135,150,177,185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service.The strobe shall be wired as a primary - signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Hom /Strobe Combination The horn /strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn /strobe shall be wired as a primary- signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1Hz over the strobe's entire operating voltage range.The strobe light shall consist of a xenon flash tube and associated lens/reflector system.The horn shall have three audibility options and an option to switch between a temporal three - pattern and a non- temporal (continuous) pattern.These options are set by a multiple position switch. On four -wire products, the strobe shall be powered independently of the sounder. The horn on horn/strobe models shall operate on a coded or non -coded power supply. Outdoor Products SpectrAlert Advance outdoor horns, strobes and horn/strobes shall be listed for outdoor use by UL and shall operate between minus 40 degrees and 151 degrees Fahrenheit. The products shall be listed for use with a System Sensor outdoor/weatherproof back box with half inch and three - fourths inch conduit entries. Synchronization Module The module shall be a System Sensor Sync-Circuit listed to UL 464 and shall be approved for fire protective service.The module shall synchronize SpectrAlert strobes at 1Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn /strobe models over a single pair of wires. The module shall mount to a 4916 x 41(6 x 2X -inch back box The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit.The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical /Electrical Specifications Standard Operating Temperature 32 °F to 120°F (0°C to 49°C) K Series Operating Temperature —40 °F to 151°F (-40 °C to 66 °C) Humidity Range 10 to 93% non-condensing (indoor products) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12DC/FWR or regulated 24DC/FWR Operating Voltage Range' 8 to 17.5 V (12V nominal) or 16 to 33 V (24 nominal) Input terminal wire gauge 12 to 18 AWG Ceiling mount dimensions (including lens) 6.8 diameter x 2.5 (173 mm diameter x 64 mm high) Wall mount dimensions (including lens) 5.61 x 4.7'W x 25D (142 mm L x 119 mm W x 64 mm D) Horn dimensions 5.61 x 4.71W x 13D (142 mm L x 119 mm Wx33 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non - regulated, time varying power source that is used on some power supply and panel outputs. 2. P, 5, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. A05 -0395-002 UL Current Draw Data UL Max. Strobe Current Draw (mA RMS) UL Max. Horn Current Draw (mA RMS) 8 - 17.5 Volts 16 - 33 Volts 8 - 17.5 Volts 16 - Volts Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR Standard 15 123 128 66 71 Temporal High 57 55 69 75 Candela Range 15/75 142 148 77 81 Temporal Medium 44 49 58 69 30 NA NA 94 96 Temporal Low 38 44 44 48 75 NA NA 158 153 Non - temporal High 57 56 69 75 95 NA NA 181 176 Non - temporal Medium 42 50 60 69 110 NA NA 202 195 Non - temporal Low 41 44 50 50 115 NA NA 210 205 Coded High 57 55 69 75 High 135 NA NA 228 207 Coded Medium 44 51 56 69 Candela Range 150 NA NA 246 220 Coded Low 40 46 52 50 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (mA RMS), 2 -wire Horn /Strobe, Standard Candela Range (15 -115 cd) 8 -17.5 Volts 16 -33 Volts DClnput 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non- temporal High 141 152 91 100 116 176 201 221 229 Non - temporal Medium 133 145 75 85 102 163 187 207 216 Non - temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non - temporal High 142 161 103 112 126 181 203 221 229 Non - temporal Medium 134 155 85 95 110 166 189 208 216 Non - temporal Low 132 154 80 90 105 161 184 202 211 UL Max. Current Draw (mA RMS), 2 -wire Horn /Strobe, High Candela Range (135 -185 cd) 16 -33 Volts 16 -33 Volts DClnput 135 150 177 185 FWR Input 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non - temporal High 255 270 303 309 Non - temporal High 233 248 275 281 Non - temporal Medium 242 259 293 299 Non - temporal Medium 219 232 262 267 Non - temporal Low 238 254 291 295 Non - temporal Low 214 229 256 262 Horn Tones and Sound Output Data Rotary Horn and Horn /Strobe Switch Settings Horn and Horn /Strobe Output (dBA) Setting Repetition Rate dB Level Switch 8 -17.5 Volts 16 -33 Volts 1 Temporal horn High Position Sound Pattern dB DC FWR DC FWR 2 Temporal horn Medium 1 Temporal High 78 78 84 84 3 Temporal horn Low 2 Temporal Medium 74 74 80 80 4 Normal horn High 3 Temporal Low 71 73 76 76 5 Normal horn Medium 4 Non - temporal High 82 82 88 88 6 Normal horn Low 5 Non - temporal Medium 78 78 85 85 7' Externally coded High 6 Non - temporal Low 75 75 81 81 8' Externally coded Medium 7• Coded High 82 82 88 88 9• Externally coded Low 8• Coded Medium 78 78 85 85 9" Coded Low 75 75 81 81 'Settings 7, 8, and 9 are not available on 2 -wire horn /strobe. A05 -0395-002 SpectrAlert Advance Dimensions „...„,- ., .c..........==.., I ll �.c "' I ,40"\ 2.5 Fc___„„, , (3 III 1 „ ,./) -.0 ) 1-2.5" SpectrAlert Advance Ordering Information Model Description Model Description Wall Horn /Strobes Ceiling Horn /Strobes (cont'd.) P2R *t 2 -wire Horn /Strobe, Standard cdt, Red PC2W *t 2 -wire Horn /Strobe, Standard cd, White P2RH* 2 -wire Horn /Strobe, High cd, Red PC2WH *t 2 -wire Horn /Strobe, High cd, White P2RK* 2 -wire Horn/Strobe, Standard cd, Red, Outdoor PC4R 4 -wire Horn /Strobe, Standard cd, Red P2RHK* 2 -wire Horn/Strobe, High cd, Red, Outdoor PC4RH 4 -wire Horn /Strobe, High cd, Red P2W* 2 -wire Horn /Strobe, Standard cd, White PC4RK 4 -wire Horn /Strobe, Standard cd, Red, Outdoor P2WH* 2 -wire Horn/Strobe, High cd, White PC4RHK 4 -wire Horn /Strobe, High cd, Red, Outdoor P4R* 4 -wire Horn /Strobe, Standard cd, Red PC4W 4 -wire Horn /Strobe, Standard cd, White P4RH* 4 -wire Horn /Strobe, High cd, Red PC4WH 4 -wire Horn /Strobe, High cd, White P4RK 4 -wire Horn /Strobe, Standard cd, Red, Outdoor Ceiling Strobes P4RHK 4 -wire Horn /Strobe, High cd, Red, Outdoor SCR* Strobe, Standard cd, Red P4W* 4 -wire Horn /Strobe, Standard cd, White SCRH* Strobe, High cd, Red P4WH* 4 -wire Horn /Strobe, High cd, White SCRK Strobe, Standard cd, Red, Outdoor Wall Strobes SCRHK Strobe, High cd, Red, Outdoor SR *t Strobe, Standard cd, Red SCW*t Strobe, Standard cd, White SRH *t Strobe, High cd, Red SCWH *f Strobe, High cd, White SRK Strobe, Standard cd, Red, Outdoor Horns SRHK Strobe, High cd, Red, Outdoor HR Horn, Red SW* Strobe, Standard cd, White HRK Horn, Red, Outdoor SWH* Strobe, High cd, White HW Horn, White Ceiling Horn /Strobes Accessories PC2R* 2 -wire Horn/Strobe, Standard cd, Red BBS -2 Back Box Skirt, Wall, Red PC2RH* 2 -wire Horn/Strobe, High cd, Red BBSW -2 Back Box Skirt, Wall, White PC2RK 2 -wire Horn/Strobe, Standard cd, Red, Outdoor BBSC -2 Back Box Skirt, Ceiling, Red PC2RHK 2 -wire Horn /Strobe, High cd, Red, Outdoor BBSCW -2 Back Box Skirt, Ceiling, White Notes: * Add "-P" to model number for plain housing (no 'FIRE' marking on cover), e.g., P2R -P t Add '-SP" to model number for "FUEGO" marking on cover, e.g., P2R -SP *'High cd' refers to strobes that include 135, 150, 177, and 185 candela settings.' Standard cd' refers to strobes that include 15,15/75, 30, 75, 95,110, and 115 candela settings. 1 SYSTEM 02006 System Sensor. �j SENSOR 3825 Ohio Avenue • St. Charles, IL 60174 Productspecr e<t ;o change mthan e�n cam fa Phone: 800-SENSOR2 • Fax: 630- 377-6495 current aci tinf orm aton• includingthelatestve rsionofthis datasheet. A05 -0395-002.7/06.01659 SYSTEM SENSOR P to 4 -Wire Photoelectric Duct Smoke Detector %.41A— ''""�'" The InnovairFlex'' Series are the only duct smoke . detectors flexible enough to fit configurations from InnOVOI square to rectangular and everything in between. Features The InnovairFlex D4120 4 -wire photoelectric duct smoke Photoelectric, integrated low flow technology detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. • Air velocity rating from 100 ft/min to 4,000 ft /min (0.5 m/s to 20.32 This unit senses smoke in the most challenging conditions, operating m /sec) in airflow speeds of 100 to 4,000 feet per minute, temperatures • Versatile mounting options: square or rectangular configuration of —4 °F to 158 °F, and a humidity range of 0 to 95 percent (non- • Plug -in sensor offers superb false alarm immunity and the latest condensing). A plug-in sensor head offers improved false alarm sensor technology immunity and simple installation, testing, and maintenance. An improved cover design isolates the sensor head from the low -flow • Broad ranges for operating temperature (-4 °F to 158 °F) and feature for simple maintenance. humidity (0% to 95% non - condensing) • Patented sampling tube installs from front or back of the detector The InnovairFlex housing provides ample wiring space, a 3 /4-inch with no tools required conduit knockout, and built -in short circuit protection to prevent damage to sensitive components during installation. High contrast • Increased wiring space with a newly added 3 4 -inch conduit terminal designations make wiring easy. With its 2:1 sensor -to -power knockout capability, the power board of the D4120 may be used to monitor • One easy- access Test/Reset button and improved LED status a second sensor, D4S, simultaneously (i.e., supply and return side). • Patented interconnect feature for multi -fan shutdown As many as 50 InnovairFlex detectors can be interconnected. When one unit senses smoke, all interconnected detectors will switch • New high contrast terminal designations their relays; only the detector sensing smoke will go into alarm, thus - Built -in short circuit protection from operator wiring errors pinpointing the fire source. • Field selectable settings for configuring the detector An easy- access Test/Reset button makes it possible to test the unit ▪ Two DPDT Form -C relay contacts with the cover on. Three DIP switches can be used to configure field • 24 VAC /DC or 120 VAC selectable settings: cover tamper delay, number of sensors to be controlled, and shut down on trouble option. Each power board • Backward compatibility with existing Innovair products, including has two LEDs that can be used to indicate the status of connected remote accessories sensors, and a quick reference imprinted on the cover explains the LED status indications (Standby, Maintenance, Trouble, and Alarm). The InnovairFlex duct smoke detector can be customized to meet local codes and specifications without additional wiring. The new InnovairFlex product line is compatible with all previous Innovair Agency Listings models, including remote test accessories. WARNING: Duct smoke detectors are NOT a substitute for open area smoke detectors; NOT a substitute for early warning detection; LISTED NOT a replacement for a building's regular fire detection system. Refer to NFPA 72 and 90A for additional information. InnovairFlex" Duct Smoke Detector Specifications Architectural /Engineering Specifications The air duct smoke detector shall be a System Sensor InnovairFlex` D4170 Photoelectric Duct Smoke Detector.The detector housing shall be UL listed per UL 268A specifically for use in air handling systems.The flexible housing of the duct smoke detector fits multiple footprints from square to rectangular.The detector shall operate at air velocities of 100 feet per minute to 4000 feet per minute (0.5 to 2032 meters/second).The unit shall be capable of controlling up to 50 air handling systems when interconnected with other detectors.The detector shall be capable of providing a trouble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch, test button on the cover, or remote testing using the SSK451 Multi- Signaling Accessory or the RTS451 KEY Remote Test Station.Terminal connections shall be of the strip and clamp method suitable for 12 -18 AWG wiring. Physical Specifications Size: (Rectangular Dimensions) 14.38 in (37 cm) Length; 5 in (12.74 cm) Width; 2.5 in (636 cm) Depth (Square Dimensions) 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth Weight: 2.5 lbs (1.14 kg) Operating Temperature Range: D4120 & D4S: -4° to 158°F ( -20° to 70 °C); D4P120: -40° to 158 °F ( -40° to 70 °C) Storage Temperature Range: D4120 & D4S: -22° to 158 °F ( -30° to 70 °C); D4P120: -40° to 158 °F (-40° to 70 °C) Operating Humidity Range: 0% to 95% relative humidity non - condensing Air Duct Velocity: 100 to 4000 ft/min (05 to 2032 m/sec) Electrical Ratings Power supply voltage: 20 -29VDC 24 VAC 50-60 Hz 120 VAC 50 -60 Hz Input capacitance: 270NFmax. 270pFmax. N/A Reset voltage: 3.0 VDC min. 2.0 VAC min. 10 VAC min. Reset time: (with RTS451) .03 to 03 sec. .03 to 03 sec. .03 to 0.3 sec. Reset time: (by power down) 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. Power up time: 35 sec. max. 35 sec. max. 35 sec. max. Alarm response time: 15 sec. 15 sec. 15 sec. Sensitivity Test: See detector label See detector label See detector label Current Requirements: (Using No Accessories) Max. standby current: 21 mA @ 24VDC 65 mA RMS @ 24VAC 60Hz 20 mA RMS @ 120VAC 60Hz Max. alarm current: 65 mA @ 24VDC 135 mA RMS @ 24VAC 60Hz 35 mA RMS @ 120VAC 60Hz Contact Ratings Alarm initiation contacts: (SPST) 2.0A @ 30 VDC (resistive) Alarm auxiliary contacts: (DPDT) 10A @ 30 VDC (resistive); 10A @ 250 VAC (resistive); V2 HP @ 240 VAC ; 1/4 HP @ 120 VAC Note: Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose. Supervisory contacts: (SPDT) 2.OA @ 30 VDC (resistive); 2.OA @ 125 VAC (resistive) Accessory Current Loads at 24 VDC Device Standby Trouble Alarm APA1 S 1 /APA451 12.5 mA n/a 30 mA Max. MHR/MHW 0 mA n/a 29 mA Max. RAl00Z 0 mA n/a 12 mA Max. RTS151/RTS151KEY O mA/12 mA n/a 12 mA Max. RTS2 /RTS2 -AOS 3.0mA max 16 mA Max. with strobe: 55 mA max; without strobe 30 mA max Note: Any combination of accessories may be used such that the given accessory loads are:110 mA or less at the Aux output, and 50 mA or less at the Alarm output Installing the InnovairFlex Sampling Tube The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing the front or rear locking tab (front locking tab shown below right). - th; A05- 0414001 Wiring for 4 -wire Duct Smoke Detector and Accessories POWER INPUTS (NOTE 1) POWER INPUTS (NOTE 1) 4VAC/1 FVAC� r"'L 0 9 10 9 10 OR OR AUXILIARY CONTACTS AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. (NOTE 2) FOR FAN SHUTDOWN, ETC. (NOTE 2) AUXA AUXB AUXA AUXB N NQ. N N N N N • . 16 6 17 8 18 7 16 6 1 8 18 7 '�— EOL RESISTOR SPECIFIED BY SUPERVISORY CONTACTS SUPERVISORY CONTACTS PANEL MANUFACTURER (NOTE 3) (NOTE 3) SU SUP .O. SU SUP o. UL/FM LISTED 3 14 3 14 4-WIRE CONTROL PANEL + I I I ALARM 4 0 ALARM C ALARM 4 0 ALARM C. ALARM INITIATION INITIATION INITIATION CONTACTS CONTACTS LOOP \ (NOTE 4) (NOTE 4) \ \\ 5 0 ALARM N.O. 5 ,, ALARM N.O. J I J — — FIRST DETECTOR IN THE LOOP LAST DETECTOR IN THE LOOP NOTE 1: 24V Power Inputs accept a non - polarized 24VDC or 24VAC 50 -60Hz. NOTE 3: Supervisory contacts shown in standby position. Open contacts 120VAC Power Inputs accept only 120VAC 50 -60Hz. Connect power indicate a trouble condition to the panel. See specifications for source to appropriate terminals of each detector. See specifications contact ratings. for additional power supply Information. NOTE 4: Alarm Initiation contacts shown in standby position. Closed NOTE 2: Auxiliary contacts shown in standby position. Contacts switch contacts indicate an alarm condition to the panel. See specifications during alarm as indicated by arrows. Auxiliary contacts are not to for contact ratings. be used for connection to the control panel. See specifications for contact ratings. 'Please refer to the corresponding installation manual for accessory wiring diagrams. Important Notes on 2:1 Sensor -to -Power Capability • 2:1 sensor -to -power capability is not available for all InnovairFlex models. The feature is only available on the D4120 4 -wire conventional models. • 2:1 sensor -to -power capability can be enabled using one D4120 and one D4S, or two D45 and one D4P120. Important Interconnect Notes • When using the interconnect feature, all interconnected units must be powered using the same independent supply. • Polarity must be maintained throughout the interconnect wiring. Connect the INT+ terminal on unit 1 to the INT+ terminal on unit 2 and so on. Similarly, connect the INT/AUX— terminal on unit 1 to the INT /AUX- terminal on unit 2 and so on. • Up to 50 D4120 units, 50 D4P120 units, or 50 units of combination may be interconnected. • Up to 10 DH100ACDC units may be interconnected. Please note that each of the 9 DH100ACDC units interconnected may be replaced by three D4P120 • units. Therefore, when using the interconnect feature a single DH100ACDC can drive either 9 OH100ACDCs or 27 D4120 units. • NOTE: Alarm can be reset only at the initiating device and not at the devices interconnected. A05- 0419.001 Accessories System Sensor provides system flexibility with a variety of accessories, including two remote test stations and several different means of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL listed. moomosamillommoim - wry- - RTS151 UL S4011 RTS151 KEY UL 52522 APA151 UL 54011 RTS2 -AOS UL 52522 • :•t: m RA100Z UL 52522 MHW UL 54011 MHR UL 54011 AOS Ordering Information Part No. Description D4120 4 -wire photoelectric low -flow duct smoke detector Accessories D4S 4 -wire photoelectric sensor component only MHR Mini Horn, Red D4P120 4 -wire photoelectric power board component only, MHW Mini Horn, White 24 VAC/DC, 120 VAC 2D51 4 -wire conventional photoelectric sensor head P48 -21 -00 End cap for metal sampling tubes DST1 Metal sampling tube duct width up to lft (03m) RAl00Z Remote annunciator alarm LED DST1.5 Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m) RTS151 Remote test station DST3 Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 12 m) RTS151 KEY Remote test station with key lock DST5 Metal sampling tube duct widths 4 ft to 8 ft (12 to 2.4 m) RTS2 - AOS Multi- signaling accessory DST10 Metal sampling tube duct widths 8 ft to 12 ft (2. to 3.7 m) APA151 Remote annunciator with piezo alarm DH400 OE -1 Weatherproof enclosure ETX Metal exhaust tube duct width lft (0.3m) MO2 -04 -00 Test magnet SYSTEM 3825 Ohio Avenue • St. Charles, IL 60174 ��� 01009 system Sensor SENSOR product wbJeamc t nonce i mw e Phone: 800-SENSOR2 •Fax: 630 377 6495 current 0cin 5- 0419 -001 hel 6/09• °"�rmsaata sheet e . A05 -Od19 -001 6/09 "f2177 1 [Page Too Large for OCR Processing] [Page Too Large for OCR Processing]