Loading...
Plans[Page Too Large for OCR Processing] [Page Too Large for OCR Processing] c( - vc053 r � Z Lt i-t s ti/ Dui-kayo COMcheck Software Version 3.8.0 Mecha Comp Certificate Oregon Energy Efficiency Specialty Code Section 1: Project Information Project Type: New Construction Project Title • RSD Construction Site: Owner /Agent: Designer /Contractor. 7244 SW Durham RD Tigard, OR 97224 Section 2: General Information Building Location (for weather data): Portland, Oregon Climate Zone: 4c Section 3: Mechanical Systems List Quantity System Type & Description 1 HVAC System 1: Heating: Heating equipment (Other), Gas, Capacity 72 kBtu /h / Cooling. Cooling equipment (Rooftop Package Unit), Capacity 57 kBtu /h, Efficiency: 13.00 SEER, Air - Cooled Condenser / Single Zone Section 4: Requirements Checklist In the following requirements, the relevant code section reference is shown in [ ] ' +' denotes that more details exist in the specified code section. Requirements Specific To: HVAC System 1 : �1. [503.2.3 +] Equipment meets minimum efficiency Rooftop Package Unit: 13.0 SEER e2 [503.3 1 +] Supply air economizers shall be provided on each cooling system and are capable of providing 100 - percent outdoor air, even if additional mechanical cooling is required to meet the cooling load of the building. Systems provide a means to relieve excess outdoor air during economizer operation to prevent overpressurizing the building. o Exception Cooling equipment less than 54,000 Btu /hr total cooling capacity. The total capacity of all such units without economizers shall not exceed 240,000 Btu /hr per building area served by one utility meter or service, or 10 percent of its total installed cooling capacity, whichever is greater. That portion of the equipment serving dwelling units and guest rooms is not included in determining the total capacity of units without economizers. Location in plans/specs where compliance can be identified (enter NA if not applicable) 4 40 3. [503 3.2] Hydronic system controls. Hydronic systems of at least 300,000 Btu /h design output capacity supplying heated and chilled water to comfort conditioning systems include controls that meet the requirements of Section 503 4.3. Location in plans/specs where compliance can be identified (enter NA if not applicable) Generic Requirements: Must be met by all systems to which the requirement is applicable: 1. [503.2.1 +] Calculation of heating and cooling loads. Design loads are determined in accordance with the procedures described in the ASHRAE/ACCA Standard 183. Alternatively, design loads have been determined by an approved equivalent computation procedure. 2. [503.2.1.1 +] Packaged Electnc Equipment. Specified packaged electrical equipment has a heat pump as the primary heating source. o Exception: Unstaffed equipment shelters or cabinets used solely for personal wireless service facilities Location in plans/specs where compliance can be identified (enter NA if not applicable) -; 13. [503.2.2 +] Equipment and system sizing. Heating and cooling equipment and systems capacity do not exceed the loads calculated in T accordance with Section 503.2.1 Project Title: RSD Report date: 02/03/11 Data filename: C \Documents and Settings \bruce\My Documents \COMcheck \Untitled cckRSD.cck Page 1 of 10 O Exception Required standby equipment and systems provided with controls and devices that allow such systems or equipment to operate automatically only when the primary equipment is not operating D Exception Multiple units of the same equipment type with combined capacities exceeding the design load and provided with controls that have the capability to sequence the operation of each unit based on load. Location in plans/specs where compliance can be identified (enter NA it not applicable) pr 4 [503 2 3 +] HVAC Equipment Performance Requirements Reported efficiencies have been tested and rated in accordance with the applicable test procedure The efficiency has been verified through certification under an approved certification program or, if no certification program exists, the equipment efficiency ratings are supported by data furnished by the manufacturer. y 5 [503 2 4 1 +] Thermostatic Controls. The supply of heating and cooling energy to each zone is controlled by individual thermostatic controls that respond to temperature within the zone. Location in plans /specs where compliance can be identified (enter NA if not applicable) /tA 6 [503.2 4 1 1] Heat pump supplementary heat Heat pumps having supplementary electric resistance heat have controls that, except during defrost, prevent supplementary heat operation when the heat pump can meet the heating load. Location in plans /specs where compliance can be identified (enter NA if not applicable) 7 [503.2 4 2] Set point overlap restnction Where used to control both heating and cooling, zone thermostatic controls provide a temperature range or deadband of at least 5 °F (2 8 °C) within which the supply of heating and cooling energy to the zone is capable of being shut off or reduced to a minimum D Exception Thermostats requinng manual change over between heating and cooling modes Location in plans /specs where compliance can be identified (enter NA if not applicable) j /$ [503 2 4.3] Optimum Start Controls Each HVAC system has controls that vary the start-up time of the system to just meet the 77`` temperature set point at time of occupancy. Location in plans/specs where compliance can be identified (enter NA if not applicable) 7 9. [503 2 4.4 +] Off -hour controls. Each zone is provided with thermostatic setback controls that are controlled by either an automatic time clock or programmable control system LI Exception Zones that will be operated continuously D Exception Zones with a full HVAC load demand not exceeding 6,800 Btu /h (2 kW) and having a readily accessible manual shutoff switch Location in plans/specs where compliance can be identified (enter NA if not applicable) %10 [503.2.4.5 +] Shutoff damper controls Both outdoor air supply and exhaust are equipped with not less than Class I motonzed dampers Exception: Gravity dampers shall be permitted for outside air intake or exhaust airflows of 300 cfm or less. Location in plans/specs where compliance can be identified (enter NA If not applicable) 44111 [503.2.4.6 +] Freeze Protection and Snow melt system controls. Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self - regulating heat tracing, include automatic controls capable of shutting off the systems when outdoor air temperatures meet code criteria. Location in plans/specs where compliance can be identified (enter NA if not applicable) 12 [503.2.4 8] Separate air distribution systems. Zones with special process temperature requirements and /or humidity requirements are served by separate air distribution systems from those serving zones requiring only comfort conditions; or shall include supplementary control provisions so that the pnmary systems may be specifically controlled for comfort purposes only. D Exception [503.2 4.8 +] Zones requiring only comfort heating or comfort cooling that are served by a system primarily used for process temperature and humidity control. Location in plans /specs where compliance can be identified (enter NA If not applicable) � kio 13 [503.2 4 9] Humidity control If a system is equipped with a means to add or remove moisture to maintain specific humidity levels in a /_ � zone or zones, a humidity control device is provided Location in plans /specs where compliance can be identified (enter NA if not applicable) 14 [503.2 4 9 1] ] Humidity control Where a humidity control device exists it is set to prevent the use of fossil fuel or electncity to produce ai� relative humidity in excess of 30 percent Where a humidity control device is used for dehumidification, it is set to prevent the use of fossil fuel or electncity to reduce relative humidity below 60 percent • Exception: Hospitals, process needs, archives, museums, critical equipment, and other non - comfort situations with specific humidity requirements outside this range. Location in plans /specs where compliance can be identified (enter NA if not applicable) Project Title RSD Report date 02/03/11 Data filename C \Documents and Settings \bruce\My Documents \COMcheck \Untitled.cckRSD.cck Page 2 of 10 . y❑ 15 [503 2 4 9 2] Humidity control Where a humidity control device exists it is set to maintain a deadband of at least 10% relative humidity �` Q, where no active humidification or dehumidification takes place ❑ Exception Heating for dehumidification is provided with heat recovery or heat pumping and the mechanical cooling system efficiency is 10 percent higher than required in section 503 2 3, HVAC equipment performance requirements. Location in plans /specs where compliance can be identified (enter NA if not applicable) • 0, 16 [503 2 5] Ventilation Ventilation, either natural or mechanical, is provided in accordance with Chapter 4 of the International Mechanical Code. Where mechanical ventilation is provided, the system has the capability to reduce the outdoor air supply to the minimum required by Chapter 4 of the International Mechanical Code Location in plans /specs where compliance can be identified (enter NA if not applicable) A/4 ❑ 17. [503 2 5.1 +] Demand controlled ventilation (DCV) DCV is required for spaces larger than 500 ft2 for simple systems and spaces larger /�i than 150 ft2 for multiple zone systems. ❑ Exception Systems with energy recovery complying with Section 503 2.6 ❑ Exception Spaces less than 750 ft2 (69.7 m2) where an occupancy sensor turns the fan off, closes the ventilation damper, or closes the zone damper when the space is unoccupied Location in plans /specs where compliance can be identified (enter NA if not applicable) 'y li 18. [503.2 5.2 +] Kitchen hoods Kitchen makeup is provided as required by the Oregon Mechanical Specialty Code ❑ Exception Where hoods are used to exhaust ventilation air that would otherwise be exhausted by other fan systems ❑ Exception. Kitchen exhaust systems that include exhaust air energy recovery complying with section 503 2 6 Location in plans /specs where compliance can be identified (enter NA if not applicable) N/l4 ❑ 19 [503.2.5.3 +] Enclosed parking garage ventilation controls In Group S -2, enclosed parking garages used for stonng or handling automobiles employs automatic carbon monoxide sensing devices. Location in plans /specs where compliance can be identified (enter NA if not applicable) n ,4W 20 [503.2 6 +] Energy recovery ventilation systems. Individual fan systems that have both a design supply air capacity of 5,000 cfm or ," greater and a minimum outside air supply of 70 percent or greater of the design supply air quantity have an energy recovery system ❑ Exception Where energy recovery systems are prohibited by the International Mechanical Code ❑ Exception Systems serving spaces that are not cooled and are heated to less than 60 °F ❑ Exception Where more than 60 percent of the outdoor heating energy is provided from site- recovered or site solar energy ❑ Exception Type 1 kitchen exhaust hoods. ❑ Exception Cooling systems in climates with a 1- percent cooling design wet -bulb temperature less than 64 °F (18 °C). ❑ Exception Systems requinng dehumidification that employ senes -style energy recovery coils wrapped around the cooling coil when the evaporative coil is located upstream of the exhaust air stream ❑ Exception Systems exhausting toxic, flammable, paint exhaust, corrosive fumes, or dust ❑ Exception Laboratory fume hood systems that include qualifying features. Location in plans /specs where compliance can be identified (enter NA if not applicable) x21 [503.2 7 +] Duct and plenum insulation and sealing. All supply and return air ducts and plenums are insulated with the specified insulation When located within a building envelope assembly, the duct or plenum is separated from the building exterior or unconditioned or exempt spaces by a minimum of R -8 insulation All ducts, air handlers and filter boxes are sealed. Joints and seams comply with Section 603.9 of the International Mechanical Code ❑ Exception When located within equipment. Li Exception When the design temperature difference between the intenor and exterior of the duct or plenum does not exceed 15 °F (8 °C) • 1 "22. [503.2 7 1.1 +] Low - pressure duct systems All longitudinal and transverse joints, seams and connections of low- pressure supply and )'' return ducts are securely fastened and sealed with welds, gaskets. mastics (adhesives). mastic -plus- embedded - fabric systems or tapes installed in accordance with the manufacturer's installation instructions. ❑ Exception Continuously welded and locking -type longitudinal joints and seams on ducts operating at static pressures less than 2 inches w g pressure classification. Location in plans /specs where compliance can be identified (enter NA if not applicable) ❑ 23 [503 2 7.1.2 +] Medium - pressure duct systems All ducts and plenums designed to operate medium- pressure are insulated and sealed • in accordance with Section 503.2 7. Pressure classifications specific to the duct system are clearly indicated on the construction documents Project Title RSD Report date 02/03/11 Data filename C \Documents and Settings\bruce\My Documents \COMcheck \Untitled cckRSD.cck Page 3 of 10 Location in plans /specs where compliance can be identified (enter NA If not applicable) • 24 [503 2 7.1 3 +] High - pressure duct systems Ducts designed to operate at high- pressure are insulated and sealed in accordance with Section 503.2.7 In addition, ducts and plenums are leak- tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual Location in plans /specs where compliance can be identified (enter NA if not applicable) �� 25 [503.2 8 +] Piping Insulation All pipes serving space - conditioning systems (hot water piping for heat systems, chilled water, refrigerant, N !� and brine piping systems, and steam piping) are insulated as specified by this section O Exception. Pipe insulation is not required for factory- installed piping within HVAC equipment O Exception Pipe insulation is not required for piping that conveys fluids having a design operating temperature range between 60 °F and 105 °F O Exception Piping within room fan-coil (with AHRI440 rating) and unit ventilators (with AHRI840 rating). O Exception' Pipe insulation is not required for runout piping not exceeding 4 ft in length and 1 in in diameter between the control valve and HVAC coil [q� 26 [503.2.9 1 +] Air system balancing Each supply air outlet and zone terminal device is equipped with means for air balancing in T` accordance with the requirements of IMC 603 17. Discharge dampers intended to modulate airflow are prohibited on constant volume fans and variable volume fans with motors 10 horsepower. Location in plans /specs where compliance can be identified (enter NA if not applicable) A4q 0 27. [503.2.9.2] Hydronic system balancing Individual hydronic heating and cooling coils are equipped with means for balancing and pressure test connections Location in plans /specs where compliance can be identified (enter NA If not applicable) 71 28 [503.2 9 3 +] Manuals The construction documents require that an operating and maintenance manual be provided to the building owner by the mechanical contractor See long description for specifications. Location in plans /specs where compliance can be identified (enter NA if not applicable) /1/4 29. [503.2.10 +] Air System Design and Control Each HVAC system having a total fan system motor nameplate hp exceeding 5 hp meets the provisions of Sections 503.2.10.1 through 503 2 10 2 Location in plans /specs where compliance can be identified (enter NA if not applicable) /440 30 [503.2 10.1 +] Allowable fan floor horsepower Each HVAC system at fan system design conditions does not exceed the allowable fan system motor nameplate hp (Option 1) or fan system bhp (Option 2) as shown and calulated in requirement details. O Exception Hospital and laboratory systems that utilize flow control devices on exhaust and /or return to maintain space pressure relationships necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power limitation O Exception. Individual exhaust fans with motor nameplate horsepower of 1 hp or less Location in plans /specs where compliance can be identified (enter NA if not applicable) 4/Swo 31 [503 2 10 2 +] Motor nameplate horsepower For each fan, the selected fan motor is no larger than the first available motor size greater than the brake horsepower (bhp) O Exception For fans less than 6 bhp, where the first available motor larger than the brake horsepower has a nameplate rating within 50 percent of the bhp, selection of the next larger nameplate motor size is allowed O Exception For fans 6 bhp and larger, where the first available motor larger than the bhp has a nameplate rating within 30 percent of the bhp, selection of the next larger nameplate motor size is allowed. Location in plans /specs where compliance can be identified (enter NA if not applicable) ivMr0 32 [503.2 10 3 1] Large Volume Fan Systems Fan systems over 8,000 (7 m3 /s) cfm without direct expansion cooling coils that serve single zones reduce airflow based on space thermostat heating and cooling demand A two -speed motor or vanable frequency drive reduces airflow to a maximum 60 percent of peak airflow or minimum ventilation air requirement as required by Chapter 4 of the International Mechanical Code, whichever is greater. O Exception Systems where the function of the supply air is for purposes other than temperature control, such as maintaining specific humidity levels or supplying an exhaust system Location in plans /specs where compliance can be identified (enter NA If not applicable) O 33 [503 2.10 4] Series fan - powered terminal unit fan motors. Fan motors for series fan - powered terminal units are electronically- commutated motors and have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard MG 1 -2006 at full load rating conditions Location in plans /specs where compliance can be identified (enter NA If not applicable) O 34 [503 2 11] Heating outside a building. Systems installed to provide heat outside a building are radiant systems Such heating systems are controlled by an occupancy sensing device or a timer switch, so that the system is automatically deenergized when no occupants are present Project Title RSD Report date: 02/03/11 Data filename: C. \Documents and Settings \bruce\My Documents \COMcheck \Untitled cckRSD cck Page 4 of 10 • e. Location in plans /specs where compliance can be identified (enter NA It not applicable) • ,(/14, 35 [503.2.12] Hot Gas Bypass Limitation. For cooling systems <= 240 kBtu /h, maximum hot gas bypass capacity is no more than 50% ' total cooling capacity. Location in plans /specs where compliance can be identified (enter NA if not applicable) Section 5: Compliance Statement Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the Oregon Energy Efficiency Specialty Code requirements in COMcheck Version 3.8.0 and to comply with the mandatory requirements in the Requirements Checklist. f e/L/A! ( � — /N.0 =c :! • r/% 2 `—J // Name - Title Signature Date • • • Project Title RSD Report date: 02/03/11 Data filename: C: \Documents and Settings \bruce\My Documents \COMcheck \Untitled.cckRSD.cck Page 5 of 10 • /14 c -00053 STRUCTURAL CALCULATIONS FOR RSD 7244 SW DURHAM RD • - PORTLAND, OR 97224 -- ROOF MECHANICAL UNIT -- tt0 PROFF . � c it187 . OREGON I . . /y E NOR EXPIRES. 12 / 31 / ( III Contents Details A - B D1 - D2 Gravity Calculations G I - G2 Seismic Calculations S 1 Contact Person: John E Nordling, PE Enclosures El - E2 -- -- NORDLING Proj. No : 11 -023 RSD ' l ' STRUCTURAL ROOF MECH UNITS c7 4 Aggi • 4. 1-1: • ; ENGINEERS, LLC PAC TRUST - - Date: FEB 2011 By: JEN Sheet No.: COVER 6775 SW 1111h. tiunc 200 • ld�:.n•cnun Olt. 97008 , - . . la 0 1 ill 1 I i _ . . 77 ___ .., -4,6 1 . - ;i00 - - • - I _. . -,..-; .. Ka ---- 1 ___ ..... . _ 1 13:. • 1 " . • - ,, -._—.: 1 El 1 i 1 1 1111 Lea I _Kz ... _ . • ...-\ N: 0, 0 ,,,. '1, 74.,=.4. vt4 t.1" .,/ \ . . i I , . (...tiecUrta %Sit 5 or.mk) 1 A'l 'I 41:311CMA, Plc> 6 1 Fil ; 0 m El 1 [:4_ E17.1 4 11 1,1 ,, ....___.. . T , T. ALL PAILS 1 ti a i .., . i 1._ . t.,-1 , . - . _ _ _ _ _ _ i . :-- -11- 0 0 L i® - ---- rT1 ----1-1. - - .r. 2 - . - .,,D) <&.---p .... ' l'® L -' • . -- z G.) . 1 I -,. th-11 ..,.. 1 gi m ..5, ..1 . e Eh IR I Ur - 1 ., ® \ I. .1 ® L 01 , . . ... .11 !id I 1_ 3 --_ , ,--,----,-----L---, ..,_=.---,-_-.-i„ 12187 -_-_-=_J ,,. r; ,,. ( . _ A E C 1 CAA COI Nab PO.0 ' DO U.° MT/ a ?rr / . OREGON . N . 15 v ON) Cr. cl, );1<l›..- ? ko• AC)."/ , Y,/, \ • EXPIRES: 11131 / .1110° I 1 I -------- NORDLING Proj No.: 11-023 RSD STRUCTURAL 12.00F MEC1-I UNITS I ' i'; ' --';' •-v: PAC TRUST _. _ , e ..... ,:,... v Anne ' ENGINEERS LLC .._______ _._ .. Date' FEB 2011 : By JEN Sheet Nu.: 5775 SW 111.11. Stit'L. 200 - Beaverton Olt. 970011 .._ __ • 10-rTs • - . II CA•cLVEn- S. —, o� , (i) Qr o.c c.DA b (2 S -- I I J ((..4 I- tk►V4 d 0 t u A�tgN WE itte. a.stA. c1 2 lo ( �-O C.L. 6atzeo. A+f CaCIAO ( o 1 I " Vt - F -J v ? It 0NE Oyc ajdn, EIL Psru tsr a. cmrgrt wcwo ��o�Et ((.4% do. s r M A J S . 71 ./. _J ....... ■ % V CIO 4 4-tel. 7-Eo S (f.0.3rs1, '. — D'rC ‘tpu i_ M041L,M.rM. — 4 © (..r- G. Pt.- tw.soo �nr' t r 'Pz cc Wet -I1T (Q1,0 © 4 ulsocxt. ‘h-St1 r `� I I • .E06e- — 5„I4p » ..1 `L) — 0 ..'a • . ^ o I 2 ca 1,.." M CZ I til J I . . ��tD PROF \ .,IG 1 NF / 12,187 1 4 ' . 'EGON 'C/4 09 ' ii . a , '(` l r�cu -t cam. Vts t 'PG o y� Y 15 • � • E. NORO 6- , v , -- , 68)etc.v Ao la 1 — - - - -- -- -- -.._ _ °_ -- - -- i ( EXPIRES 12 / 31 / NORDLING 1'10,. No.: 11-023 RSD I. , + - �, I STRUCTURAL, ROOF MEC} I UNITS ENGINEERS LLC PAC TRUST 6776 SW 111th. Suite 200 • Beaverton Oh 97008 Date' FEB 2011 • By JEN Sheet No.. P2 0 ' . • . • . 1 I CI CD . . . . • . • ) ' C) • . . . 1 1 - k•L• c" . N. . ..L 1 I 1-C- -0 4 T1 ■"!' I. ' . 1 z..* a% ' ...3 0 -i es — 4:6 I • • , • 1 .:. . 0 1 , I . ., _____ I Ciki\-11.1Cao . +to ,c„›.., la . ,.),..._, 6(>6 0 - 1 I . • , 1 A r; i 1 7 1 i 1 4 . " l {D • 1 . .r • I I . . • , . A\ 0 13 Vf E -0 G1/43 S OX a @ ki N5 VI erY SO?P...T e (e Ct 'et 1.1 tS ktir.ir- ( ttg.c.)'r 4 4 k 50 %•-•° ' t ( -... A- v....4._ , lc c .-UNItT 1.2s ti9° 1 t.cr I 34 .. t r . (CoxactAa) 1. 1 A•t-Ei■ --- D TZ-- "" V - . 1 .b 1363 b(C° w.71.60) \ i is ': 3 ,14 1 4-Su c Mil te '9 ' • 650 1 0, D o (1 1/4 . c.‘c- — —,...__-- . • — ------- v..- - --.. NORDLING . Proj. No.: 11-021 ,RSD , STRUCTURAL ROOF MECH UNITS 0 rill Vs, . . ' 0 4 1 1 ',/mICIE tiP ! ENGINEERS, LLC - PAC TRUST -- ri775 SW I Iith. Suite 200- Ileavei !on OR, 97008 Date: FEB 2011 Ily: JEN Sheet No.: 6 k • • • Nordling Structural Engineers LLC 6775 SW 111th, Suite 200 Beaverton, OR 97008 • . Date: 02102111. Page: MULTI-SPAN TIMBER BEAM DESIGN _ ._ _ • . • • RSD - ROOF MECHANICAL UNIT • A -(TL) B -ITL) B -(TL) B -(TL) B -(TL) C- (EXIST) C- (WIMECH) • GENERAL DATA - 1 2 3 4 5 6 7 ' All Spans Simple Support ?? : YES ' Spans Length ft : 4.00 8.00 8.00 8.00 8.00 24.00 24.00 End Fixity: Pin:Pin Pin:Pin Pin:Pin Pin:Pin Pin:Pin Pin:Pin Pin:Pin Beam Width in : 3.500 3.500 3.500 3.500 3.500 2.500 2.500 Beam Depth in : 5.50 5.50 5.50 7.25 7.25 16.50 16.50 CALCULATED VALUES -OK- -OK- -OK- -OK- -OK- -OK- -OK- F'b- Modified Allow. psi : 1345.5 1345.5 1345.5 1345.5 1345.5 2664.0 2664.0 - fb - Actual. psi : 306.0 1088.1 1116.4 626.2 642.5. 2285.0 2356.9 F'v- Modified Allow. psi : 207.0 207.0 207.0 207.0 207.0' 218.5 218.5 Iv (actual) ` 1.5 psi : 27.1 54.9 58.4 40.4 43.5 115.2 129.5 . Moment @ Left k -in : 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Moment @ Right kin : 0.0 0.0 0.0 . 0.0 0.0 0.0 0.0 Max. Mom. @ Mid -Span k -in : 5.4 19.2 . 19.7 19.2 19.7 259.2 267.4 X -Dist ft : 2.00 4.00 5.12 4.00 • 5.12 12.00 12.16 Shears: Left k : 0.45 0.80 0.64 0.80 0.64 3.60 3.66 Right ,• k : -0.45 -0.80 -0.81 -0.80 -0.81 -3.60 -3.99 Reaction @ Left DL k : 0.15 0.30 0.25 0.30 0.25 1.20 1.20 LL k : 0.30 0.50 0.39 0.50 0.39 2.40 2.46 • Total k : 0.45 0.80' 0.64 0.80 0.64 3.60 3.66 • Reaction @ Right DL k : 0.15 0.30 0.30 0.30 0.30 1.20 1.20 LL k : 0.30 0.50 0.51 0.50 0.51 2.40 2.79 Total k : 0.45 0.80 0.81 0.80 0.81 3.60 3.99 Max. Dell. @ Mid Span in : -0.017 -0.237 -0.236 -0.104 -0.103 -1.329 -1.378 X -Dist ft : 2.00 4.00 4.16 4.00 4.16 12.00 12.00 DESIGN DATA V • Le: Unsupported Length ft : 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Fb:Basic Allowable psi : 1170.0 1170.0 1170.0 1170.0 1170.0 2400.0 2400.0 Fv:Basic Allowable psi : 180.0 180.0 180.0 180.0 180.0 190.0 190.0 Elastic Modulus ksi : • 1600 1600 • 1600 1600 1600 1800 1800. ' Load Duration Factor 1.15 1.15 1.15 1.15 1.15 1.15 1.15 APPLIED LOADS ' Use Live Load on This Span ? Yes . Yes Yes Yes Yes Yes Yes Uniform DL plf : 75.0 75.0 50.0 75.0 50.0 100.0 100.0 LL plf : 150.0 125.0 75.0 125.0 75.0 200.0 200.0 Point DL N : 150.00 150.00 . LL b : 300.00 300.00 450.00 X -Dist. ft : 5.50 , 5.50 21.00 QUERY VALUES Location ft : 0.00 0.00 0.00 0.00 0.00 0.00 0.00 Shear b : 0.45 0.80 0.64 0.80 .0.64 3.60 3.66 Moment kin : 0.00 0.00 0.00 0.00 0.00 .0.00 0.00 Deflection in`: 0.000 0.000 • 0.000 0.000 0.000 0.000 0.000 V4.4R2 1r1 MI AS FNFRI.AI C Bruce W. Kenny. KW060914SL -A USGS Earthquake Hazards Program 2005 ASCE 7 Standard Location 45" 24' 0.31" N Ss and SI -- Mapped Spectral Acceleration Values 122'45' .1.59" W 7244 ti \V Dui ham Rd, Portland. ( )R 97224 Ground Motion Ss (1.932 Si 0.335 Occupancy Category I I Site Coefficients F;, 1.13 Site Class D F,• 1.73 Importance Factor 1.0 Height of Structure 20.0 ft SMS F;, * Ss 1.051 SW Fv * Si 0.580 Design Category (SDC) D SDS (2/3) SMS 0.700 SDI (2/3) Snit 0.386 Mr Side FIVAC Eq = 0.270W + 0.2 SDS W a 2.50 R 6.00 = 0.2 W + 0.20 * 0.700 W .27 W +0.140 W 0.4 1 p • S • 1-' I1,, 1 +2•? -W W: ightofUnit P R ( h) '' ` 1.117 z= 20.011 ASD 4r F 31 " 4Q* = 23.0 (IC FP = 0.39 Wp -> * 0.7 0.270 / . FP MIN = 0.3 SDS II' WI' /' � • = 0.210 Wr -> * 0.7 0.147 '` �, '` 6 C 2? . ., i coo . I:1 MAX = 1.6 SDS IP WP = 1.12 WP -> * 0.7 0.784 16 C.44 l .: -- os t ` 1 156 1 0 . s' \ sf..` '.---.° '� ,c1' t...- G.00 O,�s) ( '.) J 3c. ' kl-Pyuk Nb.1uC "-/ 4 17- ''- IS AL, su s l a• PIC P • NORDLING Proj. No : 11 -023 RSD 1 t ‘ ' )1 ‘ 11 STRUCTURAL ROOF MECH UNITS ENGINEERS, LLC PAC TRUST 6775 SW I IIa,. S, ,c 200 I +,:.vc, n OH. 970013 Date: FEB 2011 By: JEN Sheet No.. S 1 • CURBS & WEIGHTS DIMENSIONS - CHASSIS I Corner A _ II:CI l li� /� ��l °\ i • Corner �� i/1 ,l o Corner *, 'O Corner / / C � 251/8 ". I . 7„ T61/8" ® 11 3 /� 101/2" '. '' A Z 1�6 1/4" 22" C08001 1 211/4» IS O . -, ��/ 191/2 1 z._ _. A 7 i �� �'� 6 5/8" 33 3/8" I u. 1 4 y � � � 4 S/8" 74 3/8" iii 008000 Table 9 — BASE UNIT DIMENSIONS - CHASSIS I OPERATING SHIPPING CORNER WEIGHTS (LB) _ I CENTER OF GRAVITY (IN) • UNIT WGT (LB) WGT (LB) K A B C D X Y HEIGHT 04 483 520 33 5/16" 18 5/8" 111 125 131 116 _ 39 _I 23 16 3/4 -1fr 05 07 537 575 33 5/16" 14 7/8" 124 13• _ 145 129 39 23 17 06 569 605 33 5/16" 14 7/8" 131 147 15 — 137 39 23 17 1/4 07 652 690 41 5/16" 14 7/8" 150 169 176 57 39 23 20 1/8 { NOTES: , 1. If one side has at least 36" (914mm) of clearance, the 4. Keep combustible material at 36" (914mm) away from opposite side can be reduced to 12" (305mm). Make the flue discharge. Accessory flue discharge deflector sure to plan for OA handler, if equipped. may allow smaller clearance. 2. Clearance of 0" requires use of an alternate drain con- 5. Units shown with optional economizer. nection. 6. Local codes and jurisdictions may prevail. 3. Maintain 36" (914mm) between control box and groun- 7. Height is measured from bottom of base rail. ded surface or 42" (1067mm) between control box and ungrounded surfaces (concrete or block wall). - . I 14 te 1 • ' GASKET / / (SUPPLIED WITH CURB) :% o• , •,, "- NAIL • el (FIELD SUPPLIED) al, COUNTER FLASHING = ,� ; ' ' a2• ` `, • • ` = ' ' (FIELD SUPPLED) - /CANT STRIP - ; r FIELD SUPPLIED) j " �� Iliji. 1 2-' \\ �\ ROOFING FELT 'Z -; r :/ - V (FIELD SUPPLIED) / /' I Required bottom condensate drain connection ' ` Otherwise, 36" for condensate connection. C07457 C07459 Fig. 1 - Curb Installation Detail ('1'pical) Fig. 2 - Service Clearance - \ _ /I U / / 4 i ` ` I i i I — Q,— 1 I / ; I I `, / // I : / 1 . 0' -3• - - - I 1761 1 I 1 4 1 1- I 1 1 1 1761 t RETURN AIR I 1 OPENING I 2' -7 5 /8 • 1 O 1 - I 1603) I SUPPLY AIR I I ' 1' -I 7/16• OPENING I I (3411 1 I 1 I I I 4 0 -0 7/16- I . 1111 1 -/ ( /1b I 11 1 /6• 0' - 7 /I6 (BOLT HEADS) 150 13341 111) 0' - 3 • (BOLT HEADS) 1761 , 0' -0 7/I6 3' -0 0' -0 7/16 III) 19141 ' (BOLL HEADS) (80L1 MEADS) C07456 Fig. 3 - Curb Dimensions r — 11-3/8 — -- 18481 [C0NOM12ER HOOD !OPTION/0.1 16 14061 IC •: II � "� 1i !65.16 — [ IO 7)d �/ 16621 12711 ON � • 1\ )� -�. % i " � � _ -�_ __ NrlAIR (11171 \� / D.NSA J 4 I • CONDENSATE • 29.318 /-.] GRAIN 06(x186 1 13/4 11411 1„46. 1 IM BA SPAN (4611 14.178 1 I J 26 -112 SUPPLY (4111 16731 AIR SEE 111841 THE--/ 18 (lb 14.1/4 12-1/4 BASE CHART. _ 14591 I (.1611 (1121 1 6 1/4 I 1 . 1 i _____ • • 1 is/1 . ----- -- S - 75 -- -- — 3 3/8 16361 - -- 12 -1 /8 -- 1851 4 13011 (8181 �QN .-- 18 1/2 -- 14701 - 007461 Fig. 4 - Basepan Detail - 15 e Z •