Loading...
Specifications EC20I -0 335 731 c? 5 L4/ Kedo ( L !a ©o COMcheck Software Version 3.8.0 Mechanical Compliance Certificate Oregon Energy Efficiency Specialty Code Section 1: Project Information Project Type: Alteration Project Title : Solestruck • Construction Site: Owner /Agent: Designer /Contractor: 7319 SW Kable Lane Tigard, OR 97224 Section 2: General Information Building Location (for weather data): Tigard, Oregon Climate Zone: 4c Section 3: Mechanical Systems List Quantity System Type & Description 1 HVAC System 1: Heating: Heating equipment (Other), Gas, Capacity 64 kBtu /h / Cooling: Cooling equipment (Rooftop Package Unit), Capacity 35 kBtu/h, Efficiency: 13.00 SEER, Air - Cooled Condenser / Single Zone 1 HVAC System 2: Heating: Heating equipment (Other), Gas, Capacity 90 kBtu/h / Cooling: Cooling equipment (Rooftop Package Unit), Capacity 56 kBtu/h, Efficiency: 13.00 SEER, Air - Cooled Condenser / Single Zone Section 4: Requirements Checklist In the following requirements, the relevant code section reference is shown in [ ]. ' +' denotes that more details exist in the specified code section. Requirements Specific To: HVAC System 1 : [503.2.3 +] Equipment meets minimum efficiency: Rooftop Package Unit: 13.0 SEER Lr 2. [503.3.1 +] Supply air economizers shall be provided on each cooling system and are capable of providing 100 - percent outdoor air, even if additional mechanical cooling is required to meet the cooling load of the building. Systems provide a means to relieve excess outdoor air during economizer operation to prevent overpressurizing the building. k Exception: Cooling equipment less than 54,000 Btu/hr total cooling capacity. The total capacity of all such units without economizers shall not exceed 240,000 Btu /hr per building area served by one utility meter or service, or 10 percent of its total installed cooling capacity, whichever is greater. That portion of the equipment serving dwelling units and guest rooms is not included in determining the total capacity of units without economizers. Location in plans/specs where compliance can be identified (enter NA if not applicable) Nci❑ 3. [503.3.2] Hydronic system controls. Hydrontc systems of at least 300,000 Btu /h design output capacity supplying heated and chilled • water to comfort conditioning systems include controls that meet the requirements of Section 503.4.3. Location in plans/specs where compliance can be identified (enter NA if not applicable). Requirements Specific To: HVAC System 2 : ,1. [503.2.3 +] Equipment meets minimum efficiency: Rooftop Package Unit: 13.0 SEER 2. [503.3.1 +] Supply air economizers shall be provided on each cooling system and are capable of providing 100 - percent outdoor air, even if additional mechanical cooling is required to meet the cooling load of the building. Systems provide a means to relieve excess outdoor air during economizer operation to prevent overpressurizing the building. ❑ Exception: Cooling equipment less than 54,000 Btu/hr total cooling capacity. The total capacity of all such units without economizers shall not exceed 240,000 Btu/hr per building area served by one utility meter or service, or 10 percent of its total installed cooling capacity, whichever is greater. That portion of the equipment serving dwelling units and guest rooms is not included in determining the total capacity of units without economizers. • Project Title: Solestruck Report date: 07/11/12 • Data filename: Untitled.cck Page 1 of 5 Location in plans/specs where compliance can be identified (enter NA if not applicable). UJ4 ❑ 3 [503.3.2] Hydronic system controls Hydronic systems of at least 300,000 Btu /h design output capacity supplying heated and chilled water to comfort conditioning systems include controls that meet the requirements of Section 503.4.3. Location in plans/specs where compliance can be identified (enter NA if not applicable) • Generic Requirements: Must be met by all systems to which the requirement is applicable: 1. [503.2.1 +] Calculation of heating and cooling loads. Design loads are determined in accordance with the procedures described in the ASHRAE/ACCA Standard 183. Alternatively, design loads have been determined by an approved equivalent computation procedure. pet ❑ 2. [503.2.1.1 +] Packaged Electric Equipment. Specified packaged electrical equipment has a heat pump as the primary heating source. • Exception: Unstaffed equipment shelters or cabinets used solely for personal wireless service facilities. Location in plans/specs where compliance can be identified (enter NA if not applicable): x 3. [503.2.2 +] Equipment and system sizing. Heating and cooling equipment and systems capacity do not exceed the loads calculated in accordance with Section 503.2.1. ❑ Exception: Required standby equipment and systems provided with controls and devices that allow such systems or equipment to operate automatically only when the primary equipment is not operating. ❑ Exception: Multiple units of the same equipment type with combined capacities exceeding the design load and provided with controls that have the capability to sequence the operation of each unit based on load. Location in plans/specs where compliance can be identified (enter NA if not applicable) p t 4. [503.2.3 +j HVAC Equipment Performance Requirements. Reported efficiencies have been tested and rated in accordance with the applicable test procedure. The efficiency has been verified through certification under an approved certification program or, if no certification program exists, the equipment efficiency ratings are supported by data furnished by the manufacturer. le- 5. [503.2.4.1 +] Thermostatic Controls. The supply of heating and cooling energy to each zone is controlled by individual thermostatic controls that respond to temperature within the zone. Location in plans/specs where compliance can be identified (enter NA if not applicable)* NAB 6. [503.2.4.1.1] Heat pump supplementary heat. Heat pumps having supplementary electric resistance heat have controls that, except during defrost, prevent supplementary heat operation when the heat pump can meet the heating load. Location in plans/specs where compliance can be identified (enter NA if not applicable): A r 7. [503.2.4.2] Set point overlap restriction. Where used to control both heating and cooling, zone thermostatic controls provide a temperature range or deadband of at least 5 °F (2.8 °C) within which the supply of heating and cooling energy to the zone is capable of being shut off or reduced to a minimum. ❑ Exception: Thermostats requiring manual change over between heating and cooling modes. Location in plans/specs where compliance can be identified (enter NA if not applicable) f3r8. [503.2.4.3] Optimum Start Controls. Each HVAC system has controls that vary the start-up time of the system to just meet the f" temperature set point at time of occupancy. Location in plans/specs where compliance can be identified (enter NA if not applicable)* W . [503.2.4.4 +] Off -hour controls. Each zone is provided with thermostatic setback controls that are controlled by either an automatic time clock or programmable control system. ❑ Exception: Zones that will be operated continuously. ❑ Exception: Zones with a full HVAC load demand not exceeding 6,800 Btu/h (2 kW) and having a readily accessible manual shutoff switch. Location in plans/specs where compliance can be identified (enter NA if not applicable)* "10. [503.2.4.5 +] Shutoff damper controls. Both outdoor air supply and exhaust are equipped with not less than Class I motorized dampers. ❑ Exception: Gravity dampers shall be permitted for outside air intake or exhaust airflows of 300 cfm or less. Location in plans/specs where compliance can be identified (enter NA if not applicable). AAA ❑ 11. [503.2.4.6 +] Freeze Protection and Snow melt system controls. Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self - regulating heat tracing, include automatic controls capable of shutting off the systems when outdoor air temperatures meet code criteria. Location in plans/specs where compliance can be identified (enter NA if not applicable) u ❑ 12. [503.2.4.8] Separate air distribution systems. Zones with special process temperature requirements and /or humidity requirements are served by separate air distribution systems from those serving zones requiring only comfort conditions; or shall include supplementary control provisions so that the primary systems may be specifically controlled for comfort purposes only. Project Title: Solestruck Report date: 07/11/12 Data filename: Untitled.cck Page 2 of 5 ❑ Exception: [503.2.4.8 +] Zones requiring only comfort heating or comfort cooling that are served by a system primarily used for process temperature and humidity control. Location in plans/specs where compliance can be identified (enter NA if not applicable) mi. ❑ 13. [503.2.4.9] Humidity control. If a system is equipped with a means to add or remove moisture to maintain specific humidity levels in a zone or zones, a humidity control device is provided. Location in plans/specs where compliance can be identified (enter NA if not applicable) • vs ❑ 14. [503.2.4.9.1] Humidity control. Where a humidity control device exists it is set to prevent the use of fossil fuel or electricity to produce relative humidity in excess of 30 percent. Where a humidity control device is used for dehumidification, it is set to prevent the use of fossil fuel or electricity to reduce relative humidity below 60 percent. ❑ Exception: Hospitals, process needs, archives, museums, critical equipment, and other non - comfort situations with specific humidity requirements outside this range. Location in plans/specs where compliance can be identified (enter NA if not applicable): o4 ❑ 15. [503.2.4.9.2] Humidity control. Where a humidity control device exists it is set to maintain a deadband of at least 10% relative humidity where no active humidification or dehumidification takes place. ❑ Exception: Heating for dehumidification is provided with heat recovery or heat pumping and the mechanical cooling system efficiency is 10 percent higher than required in section 503.2.3, HVAC equipment performance requirements. Location in plans/specs where compliance can be identified (enter NA if not applicable) I 6. [503.2.5] Ventilation. Ventilation, either natural or mechanical, is provided in accordance with Chapter 4 of the International Mechanical r Code. Where mechanical ventilation is provided, the system has the capability to reduce the outdoor air supply to the minimum required by Chapter 4 of the International Mechanical Code. Location in plans/specs where compliance can be identified (enter NA if not applicable). Ai, ❑ 17. [503.2.5.1 +] Demand controlled ventilation (DCV). DCV is required for spaces larger than 500 ft2 for simple systems and spaces larger than 150 ft2 for multiple zone systems. ❑ Exception: Systems with energy recovery complying with Section 503.2.6 ❑ Exception: Spaces less than 750 ft2 (69.7 m2) where an occupancy sensor turns the fan off, closes the ventilation damper, or closes the zone damper when the space is unoccupied. Location in plans/specs where compliance can be identified (enter NA if not applicable) NIN ❑ 18. [503.2.5.2 +] Kitchen hoods. Kitchen makeup is provided as required by the Oregon Mechanical Specialty Code. ❑ Exception: Where hoods are used to exhaust ventilation air that would otherwise be exhausted by other fan systems. ❑ Exception: Kitchen exhaust systems that include exhaust air energy recovery complying with section 503.2.6. Location in plans/specs where compliance can be identified (enter NA if not applicable) AA ❑ 19. [503.2.5.3 +] Enclosed parking garage ventilation controls. In Group S -2, enclosed parking garages used for storing or handling automobiles employs automatic carbon monoxide sensing devices. Location in plans/specs where compliance can be identified (enter NA if not applicable) A❑ 20. [503.2.6 +] Energy recovery ventilation systems. Individual fan systems that have both a design supply air capacity of 5,000 cfm or greater and a minimum outside air supply of 70 percent or greater of the design supply air quantity have an energy recovery system. ❑ Exception: Where energy recovery systems are prohibited by the International Mechanical Code. ❑ Exception: Systems serving spaces that are not cooled and are heated to less than 60 °F. ❑ Exception: Where more than 60 percent of the outdoor heating energy is provided from site - recovered or site solar energy. ❑ Exception: Type 1 kitchen exhaust hoods. ❑ Exception: Cooling systems in climates with a 1- percent cooling design wet -bulb temperature less than 64 °F (18 °C). ❑ Exception: Systems requiring dehumidification that employ series -style energy recovery coils wrapped around the cooling coil when the evaporative coil is located upstream of the exhaust air stream. ❑ Exception: Systems exhausting toxic, flammable, paint exhaust, corrosive fumes, or dust. ❑ Exception: Laboratory fume hood systems that include qualifying features. Location in plans/specs where compliance can be identified (enter NA if not applicable): y 1. [503.2.7 +] Duct and plenum insulation and sealing. All supply and return air ducts and plenums are insulated with the specified insulation. When located within a building envelope assembly, the duct or plenum is separated from the building exterior or unconditioned or exempt spaces by a minimum of R-8 insulation. All ducts, air handlers and filter boxes are sealed. Joints and seams comply with Section 603.9 of the International Mechanical Code. Project Title: Solestruck Report date: 07/11/12 Data filename: Untitled.cck Page 3 of 5 ❑ Exception: When located within equipment. ❑ Exception: When the design temperature difference between the interior and exterior of the duct or plenum does not exceed 15 °F (8 °C). 2. [503.2.7.1.1 +] Low - pressure duct systems. All longitudinal and transverse joints, seams and connections of low- pressure supply and return ducts are securely fastened and sealed with welds, gaskets, mastics (adhesives), mastic -plus- embedded -fabric systems or tapes installed in accordance with the manufacturer's installation instructions. ❑ Exception: Continuously welded and locking -type longitudinal joints and seams on ducts operating at static pressures less than 2 inches w.g. pressure classification. Location in plans/specs where compliance can be identified (enter NA if not applicable)- Nom] 23. [503.2.7.1.2 +] Medium - pressure duct systems. All ducts and plenums designed to operate medium - pressure are insulated and sealed in accordance with Section 503.2.7. Pressure classifications specific to the duct system are clearly indicated on the construction documents. Location in plans/specs where compliance can be identified (enter NA if not applicable). gyp❑ 24. [503.2.7.1.3 +] High - pressure duct systems. Ducts designed to operate at high - pressure are insulated and sealed in accordance with Section 503.2.7. In addition, ducts and plenums are leak- tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual. Location in plans/specs where compliance can be identified (enter NA if not applicable) N40 25. [503.2.8 +] Piping Insulation. All pipes serving space - conditioning systems (hot water piping for heat systems, chilled water, refrigerant, and brine piping systems, and steam piping) are insulated as specified by this section. ❑ Exception: Pipe insulation is not required for factory- installed piping within HVAC equipment. ❑ Exception: Pipe insulation is not required for piping that conveys fluids having a design operating temperature range between 60 °F and 105 °F. ❑ Exception: Piping within room fan -coil (with AHRI440 rating) and unit ventilators (with AHRI840 rating). ❑ Exception: Pipe insulation is not required for runout piping not exceeding 4 ft in length and 1 in. in diameter between the control valve and HVAC coil. Ax 26. [503.2.9.1 +] Air system balancing. Each supply air outlet and zone terminal device is equipped with means for air balancing in accordance with the requirements of IMC 603.17. Discharge dampers intended to modulate airflow are prohibited on constant volume fans and variable volume fans with motors 10 horsepower. Location in plans/specs where compliance can be identified (enter NA if not applicable). ,u ❑ 27. [503.2.9.2] Hydronic system balancing. Individual hydronic heating and cooling coils are equipped with means for balancing and pressure test connections. Location In plans/specs where compliance can be identified (enter NA if not applicable) ,'28. [503.2.9.3 +] Manuals. The construction documents require that an operating and maintenance manual be provided to the building owner by the mechanical contractor. See long description for specifications. Location in plans/specs where compliance can be identified (enter NA if not applicable). P 29. [503.2.10 +] Air System Design and Control. Each HVAC system having a total fan system motor nameplate hp exceeding 5 hp meets the provisions of Sections 503.2.10.1 through 503.2.10.2. Location in plans/specs where compliance can be identified (enter NA if not applicable) ,04 ❑ 30. [503.2.10.1 +] Allowable fan floor horsepower. Each HVAC system at fan system design conditions does not exceed the allowable fan system motor nameplate hp (Option 1) or fan system bhp (Option 2) as shown and calulated in requirement details. ❑ Exception: Hospital and laboratory systems that utilize flow control devices on exhaust and /or return to maintain space pressure relationships necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power limitation. ❑ Exception: Individual exhaust fans with motor nameplate horsepower of 1 hp or less. Location in plans/specs where compliance can be identified (enter NA if not applicable). a b,❑ 31. [503.2.10.2 +] Motor nameplate horsepower. For each fan, the selected fan motor is no larger than the first available motor size greater than the brake horsepower (bhp). ❑ Exception: For fans less than 6 bhp, where the first available motor larger than the brake horsepower has a nameplate rating within 50 percent of the bhp, selection of the next larger nameplate motor size is allowed. ❑ Exception: For fans 6 bhp and larger, where the first available motor larger than the bhp has a nameplate rating within 30 percent of the bhp, selection of the next larger nameplate motor size is allowed. Location in plans/specs where compliance can be identified (enter NA if not applicable). Np,❑ 32. [503.2.10.3.1] Large Volume Fan Systems. Fan systems over 8,000 (7 m3 /s) cfm without direct expansion cooling coils that serve single zones reduce airflow based on space thermostat heating and cooling demand. A two-speed motor or variable frequency drive Project Title: Solestruck Report date: 07/11/12 Data filename: Untitled.cck Page 4 of 5 reduces airflow to a maximum 60 percent of peak airflow or minimum ventilation air requirement as required by Chapter 4 of the International Mechanical Code, whichever is greater. 0 Exception: Systems where the function of the supply air is for purposes other than temperature control, such as maintaining specific humidity levels or supplying an exhaust system. Location in plans/specs where compliance can be identified (enter NA if not applicable): "/O 33. [503.2.10.3.2 +]All air - conditioning equipment and air - handling units with direct expansion cooling and a cooling capacity at ARI conditions greater than or equal to 110,000 Btu/h that serve single zones have their supply fan operation controlled according to code specific requirements. o Exception: Systems where the function of the supply air is for purposes other than temperature control, such as maintaining specific humidity levels or supplying an exhaust system. Location in plans/specs where compliance can be identified (enter NA if not applicable). 34. [503.2.10.4] Series fan - powered terminal unit fan motors. Fan motors for series fan - powered terminal units are electronically- commutated motors and have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard MG 1 -2006 at full load rating conditions. Location in plans/specs where compliance can be identified (enter NA if not applicable) A AA] 35. [503.2.11] Heating outside a building. Systems installed to provide heat outside a building are radiant systems. Such heating systems are controlled by an occupancy sensing device or a timer switch, so that the system is automatically deenergized when no occupants are present. Location in plans/specs where compliance can be identified (enter NA if not applicable). 36. [503.2.12] Hot Gas Bypass Limitation. For cooling systems <= 240 kBtu/h, maximum hot gas bypass capacity is no more than 50% total cooling capacity. Location in plans/specs where compliance can be identified (enter NA if not applicable)" Section 5: Compliance Statement Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building plans, specifications and other calculations submitted with this permit application. The proposed mechanical alteration project has been designed to meet the Oregon Energy Efficiency Specialty Code, Chapter 8, requirements in COMcheck Version 3.8.0 and to comply with the mandatory requirements in the Requirements Checklist. ate /— / 4 Ore r Name - Title Signature Date Project Title: Solestruck Report date: 07/11/12 Data filename: Untitled.cck Page 5 of 5 Jul 11 12 03:OOp Matthew Olson Constructio 5038920067 p.2 A4 ECa© r 2- o,o 357 ft"' (go.... v Wi t► ' r, M STRUCTURAL CALCULATIONS �f FOR SOLESTRUCK OREGON BUSINESS PARK III 7319 SW KABLE LANE, SUITE 600 TIGARD, OR 97224 -- ROOF MECHANICAL UNITS -- a 4. \ �,� ,a9 PROF / ,, 12.1: /' OREGON I v� , IS. ''t G N tiN E NO RO% . EXPIRES: 12131 ! 1 TO I Contents Summary S I Details A - C D 1 - D3 Plan P 1 Gravity Calculations GI Lateral Calculations LI - L2 Contact Person. John E Nordling. PE Enclosures E l - E3 • • . - " --- ! NORDLING Prod. No.: 12 -246 ' ;' STRUCTURAL SOLESTRUCT ito ROOF MECH UNIT ' :` i ENGINEERS, LLC PAC TRUST 5775S:v ti lilt S„i,c•200•licav rtm(1i<. Date' JUL 2012 Ily. JEN Sheet No' COVER Jul 11, 12 03:OOp Matthew Olson Constructio 5038920067 p.3 • • I SUMMARY • ROOF TOP MECHANICAL. UNIT SEISMIC REVIEW • 2010 Oregon Structural. Specialty Code. Seismic Occupancy. Ca tagory I I Site Class - D Seisimic Design Catagory - D • Ss L. 0.938 Si L. 0.331 5os = 0.103 Sol = 0.388 There are two new roof mounted mechanical units. '5 -Ton' unit: • '3 -Ton' unit: • • • weight . .125 lbs .weight . 650 lbs length 14' length 14' with 44' with 44' height 33' height 33' • • • NORDLING Pro;. No.: 12 -246 SOLESTRUCK t -, STRUCTURAL ROOF MECH UNIT ENGINEERS, LLC PAC TRUST fi775 SW :1 1 h. Sum; 200 ❑ca*crun in.mph Date: JUL 2012 By: JEN Sheet No.: SI Jul 11 12 03:OOp.. Matthew Olson Constructio 5038920067 p.4 ' I l l I III ! I I q_. __I__1__ I I_.1 I I I__I I _I_ ! !_ 1_ �_ 1 9 ` _ T! 1 1 1 1 1 1 1 :I I! 1 1 1!! 1 1 4' 1 I I I !I I; I _ _ ' — 1 1 1 i I ! I I. ill._ 1 1 I_ I�!�I. _I I _ ! _ I I I1 I I I I 1;1 III!: 7- 11I 1111i Hill' —'•• 1•-- 1._1__.11l l I I.1 1.11 I.1 I -1 1 I I•--I-.._ 1 1;1 1 1- :1 1. ' 1111:11111111 III': l!LTTIII I_ : 1 _I _ . _ _ I -I_ I M: I I I WI_ 1.11_ IM _' i 1 1 _ I i 1_! �! 1 1.1. _ 1 11,11, r I IIJI Ti11II I ! ! I ITi1ii Ki!!I I __i'I1WI 1I_LI_I11_1 IW!iI_II _Li Ii1-1H W i �_ 1i -11 I _ Ti111I1 IT I1 1`111111 i l . 1 1 1 -L:-- 1 _____ - I I lEJGL 71��x161h1 I � 1 11 __ 11 I_L 1 III I 1 ! 17 • 1 1 i i I I 1 1 I I 1 1 1 1 I I 1 Tull Ill i t 1 I I I i I I w 1 • • I. 1 � io _ 71-7 PP I 1 11 II I T 111171 r 1.J17 i11 :1111 _- - - - -ill. . -L _ -L _i -_I. L1_.III.41�_. . 1 I l i i h 1 1711 ; ' 1 1 i I I I I I I I . ! 1 1, 1 1 — __ 1 1 1 I I� I_ (E1GL , „.I _LI 1 _I 1 1 I_ 1 I _I 1 !! 111 !"!!1!!!!!!7!!!!!1!!!!!! I I II:: 1111 I 11'11111 1 111'11'1'• I ii! 11 T i - ; i -- - i ;1r 1• - I . TI� - IT! - !iii -!- i III � I I _ ILL I .I ! i i ' l 11 I_t!I_ 1 I ! I I _ I III T1 i 1 Ti 11 71 I �i , 1 1 I Ti IT 1 ' '__i , i ' i i i i l I, I i i I I I • I 1 1 1.1 ' _ I I ; --- � - - - 1I1.IIIiI - � � I7 I,�I1I - 17' I = — =_L _.i_ ,i_i__ ,LJ,JLJ = L;- i _L- -.11:J _LJ _LJ-i —= -L'- �J • , / skED PROpic 12.1 -7 f. y • id , OREGON / ROOF I='L AN O6 i NO9 E ' EXPIRES: 12131/ AIM NORDLING Proj. No.: !2 -246 '11 S TRUC T UR AL SOLCSTRUCK '11 " � " ROOF MECH UNIT ! ENGINEERS, LLC PAC TRUST 1177:5 SW 1111h, Saute 200 • Beavernnalt. Date: JUL 2012 By: JEN Sheet No.: D1 ,Jul 11 12 03:O1p Matthew Olson Constructio 5038920067 p.5 i ;I II I II li _ -L ! (E)GL 7'hxlb''2I_L ' (E)CsL 2V7x1(j '') . _ — `- r -- - — - - -- - i - I -- „ ,f -.- - - I . ROOF MECHANICAL UNIT II :I II I • I I . 13 © p 0 !- =I. I �I I VI • • IIE/ COLUI"IN IN H 1 ,I I x: a II II q II I _ , (E 7',7x1bv_i H 11_1 I (E) GL 2'k)x1o5 II I. l i I I II i I II I u 4x8 DIRECTLY UNDER EDGE OF MECHANICAL UNIT W/ SIMPSON 1146' EACH END. © 4x8 W/ SIMPSON "U46' EACH END. El RE- SUPPORT (E) 2x6 W/ SIMPSON 'LUS24', TYPICAL. v PROff ,,G.NE / O y 12,1: f, 'S' r // . EGO` •° e iwk , � ENLARGED PLAN o6, J .r� I lk (EXPIRES 12/ 31 t • 1 1 NORDLING Pro). No.: 12 -2461 SOLESTRUCK Ito STRUCTURAL ROOF MECH UNIT • 7,4143 ,__.-..z. C ENGINEERS, LLC PAC TRUST (7:: SW H ith, Su;:I. 200 I(4.:.lv —um Olt 07CO Date. JUL 2012 By: JEN Sheet No.: D2 ,lul 11 12 03:O1p Matthew Olson Constructio 5038920067 p.6 (4) STEEL BRACKETS W/ (4) "10 x 1 i7' TEK SCREWS TO CURB d (4) "10 x 1, 7' TEK SCREWS TO UNIT BASE RAIL q11111111111 .114° MECHANICAL UNIT UNIT BASE RAIL X � (4) "10 SCREWS ,�(4) "10 SCREWS "L STEEL BRACKET • _L "12 WOOD SCREWS 6 12' o/c CURBS FLASHING d ROOFING BY OTHERS LEVELING CURB (AS REQ'D) • iA • 1•__• - --(E) GL GIRDER \5 , x /0) PROFF /o tV 12.1: 1 `� 1 •RE •N ( c) SECTION tiN F NOW EXPIRES: 12 / 31 / LAN - - -- - I NORDLING Proj. No.: 12 -246 i STRUCTURAL SOLE H UNIT ;' '-'�"'� •;' ROOF MECH UNIT Asj ENGINEERS, LLC PAC TRUST (1775 SW 11IIII. Suite 200 - flu,tvcntm (III. 7:'001, Date JUL 2012 R)1: JEN Sheet No. • D3 Jul 11 12 03:01p Matthew Olson Constructio 5038920067 p.7 I! II I 11111111 111 1 111'111111 ' I IIII! I! I; I l I f _ • :;1! LI -! - } � • i- - Li ! a; . 1 1 I I i II �; I !!i!I� I III!! � j � II I.I�I +71- I_J. ! i4q I___ _ i j -17 III . L. 1 .1;! ' - 1 I i IiI� �� I _ L IL I I I_ I —� I I_ I !. I I I_ I II' I I_�-I_ I I I_L__!__I !1! II i! II I �IIIII I ! w it 1111 I ! • Illi!!;I.�i ,...,.. III!II I 'I I I III; II _II _I _ _ - L! _ HH +4 _I_ L I_ _ 11'111111 !I ��F2 I11;�1 111111I!,!jl e I I I I 71 I I , � _- ' + • „__ _ IIIJ_ 1 -1 ! 1 — I 1 1 1! I I ! I_ I i i ' ! is i .i i II!110 !II 0 ,!11 - ! I I i ��llllll�ll111 I 1 CE) COL UP1N, , I I I _I _ I_ _I , i _ I __ L: I I I_ _III _ I I I I _ I _ 11; 1' I_ ILL I 1I I I _ III- . 2'> - II11 Ti II 11111 •1.77! �I_ I I "11111 L � II . z 1.3 ' ! 'II i II ' ! � —I i , Iliilll! Il1111111 •11.1:: j I i= i -- � jii !�II�Ii - i: !' !Li • _ _I_ 1 _I_ I II ! I L I I I I ii l!1111!!I:Ij �i1111111 i TI!1111I 'I .1 i— I I !!ITj�! I_!!;1! !�I1 !— �� :j NORDLING Proj. N 12 -246 SOLESTRUCK ! STRUCTURAL ROOF MECH WIT ENGINEERS, LLC PAC TRUST 6775 SH' ;1 im. Flow loo • Him%elInn ou. 970:14 Date: JUL 2012 By: JEN Sheet No.: P1 ,Jul 11 12 03:O1p Matthew Olson Constructio 5038920067 p.8 A CURB SUPPORT 8 (E) GL 21/27(1(771/2 • P5F P5F P5F P5F P5F P5F . DL LL rtv DL LL TW DL ; LL TW 10 25 24' o/c 9 25 S' -0' o/c 8.5. 25 8' -0' o/c CORNER WT • CURB • DAMPER PM 125 Ibs RooFING 20 poi. F:7... r. 154 Ibs • 38 lbs SI1EATNING LB psr : 192 lbs Wm = 125 nos / (2 • 6.2') INSUL 7.0 psr 2x4 •2a' 0.1 psr 59 pH' MISC 2 psr 135 psr • SELF WT CORNER WT • CURB • DAMPER P = 131 lbs • 38 lbs : 169 lbs . PM3 W M W W W 1F1'.... 111111 II111 11111 Will A A A A A h LI '0 Jr 8' -0' ., ., 24' -6' l F 24' -6. • 1 EXISTING W/ MECN UNITS I 4118 DIr- I.No.2 C1.2' /,x16.5 DP24F GUY: x16.5 Dti.24F -- R1 R2 RI --- — — — _ RI _ R2 -- — I2 DL 1,002 1,002 Rot. 1,002 1,002 R DL It)a 104 ----- --- ------ • - - -- I.I. 420 339 u. 2,450 2,450 Li. 2,639 2,622 n. 524 - -- 443 n 3,452 3,452 o. 3,641 3,624 — brg L 11.24' 0.20" trg I. 2 12' 2 12" big L 2 24" 2 23" V MAX 524 lbs Self WI V MAX 3,452 Ihs Si if wt V MAX 3,641 lbs Self wi M MAX 1,025 11-lbs 6 03 p!! M MAX • 21,144 11-lbs 9 sO Or M MAX 21,721 • R - Ib, 9 110 p1! 1 V (d) 443 Ibs I I V (d) 3,065 lbs I I V (d) 3.254 lbs I fv 26 < 207 psi fv 111 <. 276 psi fv 118 < 276 psi lb 401 < 1.346 psi lb 2,237 < 2,675 psi lb 2,298 - 2,675 pst Si S1 _ _ Si - -- -- I A DI. -0 01 A DL -0.39 A oL -0.39 e u, -0.05 _ e u. -0.96 e u. -1.01 — L / +999 L/ 305 _•_ L/ 292 ok ok ok 0k - — A n. -0.07 a TL -1.36 e 2 -1.40 • L/ +999 L/217 L / 210 CR I00 1 Cl. 1 00 Qt I 00 CL 1.0 _ _0 _CA _ 100 CL I.(H) Co 1.15 CI 1.30 CD I 15 � l _ CL U 97{ l Co _ . ._ Cv_ 0.97 1 _ I NORDLING Prot. No.: 12 -246 SOLESTRUCK 7 ' STRUCTURAL ROOF MUCH UNIT . t 1 ENGINEERS, LLC PAC TRUST 11774 SW !I I :h. Suit, 200 • IieuTerlm, UI<. '170'18 Dote' JUL 2012 13y: J F . . N Sheet No.' G I _ 1 ,Jul 11 12 03:01p Matthew Olson Constructio 5038920067 p. 9 - �`Aj- 5 - - �J'Itl 1 1 1 fil I S 1 II '. , l ig , I - n lr 1 S i- I FI I . a I : 1 11 I ,l � f I 1, r : E Hazards( ° ' ; I • - 7 2005 ASCE 7 Standard Location 45' 24' 39.04" N Ss and SI = Mapped Spectral Acceleration Values I22'' 4S 4.26" 1V 7319 SW Kable Ln, Tigard, OR Ground Motion Ss 0.938 Sr 0.337 Occupancy Category II Site Coefficients Fa 1.12 Site Class D Fv 1.73 Importance Factor 1.00 Height ofStnlcture 20.0 ft SMS F * Ss 1.055 SMI Fv * Sr 0.5R2 Design Category (SDC) D SOS (2/3) Smis 0.703 Sol (2/3) SMI 0.388 Air Side HvAC Eq = 0.279W + 0.2 SDS W a 2 50 R 6.00 W : Weight of Unit F , n 0 . 4 • a l , ' S1) . I � 1 +2 ? ) YTr • R P h " z 20.011 ASD Fr= 0.35 WI - > *0.7 0 246 z = 24.0 ft Fi = 0.40 WI -> * 0.7 0.274 I Fr sups = 0.3 Sys le WI 0.211 W -> * 0.7 0.148 Fp him( = 1.6 SDS Ir WI' I . = 1.11 Wp - > *0.7 0.788 � .. NORDLING • Pro;. No.: 12 -246 SOLESTRUCK r I �;= ''' e STRUCTURAL R OOF MECH UNIT EN GINEERS, LLC . I k PAC TRUST I n775 SW : I Ph quite 21)0 Ik.w ruu, Olt. 9700A Date' JUL 2012 By TEN Sheet No.: 1_ I Jul 11 12 03:02p Matthew Olson Constructio 5038920067 p.10 /v EQ • � \ t102 lbs �p- • - \ W: 125 lbs ,',..., tt l ititta bisiti,... . ''''''''.':::::-.•' . 1 44 41 • r 202 lbs C: 26. lbs Height 33" Weight 725 lbs Height 33" Weight 650 lbs Length 74" Length 74" Width 44" Width 44" Curb 14" Curb 14" VFQ = 0 279 • 725 lbs + 0.2 * 0.703 " 725 lbs Vr0 = 0.279' 651) lbs + 0.2' 0.703 * 650 Ihs 2(12 lbs + 102 lbs = 181 Ibs + 91 Ibs 'f = 202 lbs * (14" + 33 " /2) / 41" T = 181 lbs * (14" + 33 "/2) / 44" + 102 lbs / 2 + 91 lbs / 2 - 0.6`725 lbs /2 - 0.6* 650 lbs / 2 = -2.6 lbs 10 Net Uplift ] _ -24 lbs ) ONet Uplift 1 V= 202 lbs V= 181 lbs (4) STEEL BRACKETS W/ (4) "1t0 x 1/2' TEK SCREWS TO ROOF CURB 4 (4) "I0 x 1 /2' TEK SCREWS TO UNIT BASE RAIL -ok- "12 012' o/c SCREWS FROM CURB TO FRAMING BELOW. __ 1 ••-- - 1 NORDLING Pro). No.: 12 -246 i 1>> STRUCTURAL SOLESTRUCK N' " 1. C ROOF MECH UNIT ENGINEERS LLC PAC TRUST f,775 SW 111,1,. S,,,:,; YGO Ibarvr nnOS. MOM Date. JUL 2012 By: JEN Sheet No : L2 • Jul 11 12 03:02p Matthew Olson Constructio 5038920067 p.11 CURBS & WEIGHTS DIMENSIONS — 48TC 04 -07 .otcs: 111--- ---- 33.1 /e 1 1518! 1. 01e(us101s 1/r I. 111025 011Eiswu 1■ 1 1 l0[ I1 R11L3M[iCjs. 7. clrre ar 6141111 ' ttaaltn NCO; .� _ n..._, 18 - -.� 1. y 011[CTI01 Cr All Fla 11 10711044, 11011 • 7 ' ----\'\--\ ,_ .,---- 251!/8 —., 104/1 ;.If f!!, /i ��-;�; 0211! Itll1 1{ y OCIOel 111 1111011 1,1111 .11... �. \ \ /. .. . - Alr I ( ALT. --I • I 011111 OCf0021 11.3+1 y UPI . _ ]: 1458110 SYrll 26.112 11111 sums 14118 1 An llSft 1 8711 V 14.1/8 11- 1/1 1)1231 � - I I t 1 11111 1111) 111!7 111 7144 SIT Yls [1118 ! co • i i 1 ... .. : . ■ cr — T. 12.111 1.316 L„ 1-1-\_„,.,, 130/1 1551 nut -w 11401 IOOe •-- 18.112 TOP loco. ,1.1/8 1 -111 (lull 1321 �� 4 1.3/! • F CID I 11.101 111 W1000 l[CIIICIL 01174 013C0N:IC1 23.1!6 _ _ `' -� I - I LOCATION 11.3 / 11111 i ' -• 001310[ [011(13(0 c �ijI! • 1 1{271 ' All UNIX / G011 =A. _ . .. i 11.310 fllh! 411 111 1 i 11171 71.1 // o 821!1 I OPTIONAL f -Ilt - -� 74!;87 -- , 11•,+2 = i 11911 CC41rE01111 Oe1llf I. ( 1171 11,21 + I - - -- 1 {1516 21.311 ER14 11611 11811 BAt041711C 31.114 . 11131 (111 1911 11.7/4 • 111611 Alt 1111081 UGH AIN LEFt flf - �•� • s CO11101 00[ 180020 010108 (111(1 ACC ISI fl ICCCf3 8411! • ACCESS ITOOL•lnSl fW • 412753 [0118781.1 ■ 11.1 ' • 741!3 ' g 110001 Cerl ' OST101At II_ ;, ACCESS PAUL 71[404: �1tpL1 016 G 1 100 ' —T mom. : 00i' 7.518 .1 11111111 5.1/8 BACK 1411 36.118 10131 17141 Cul • 81.114 2121 (11451 OHM FRONT INIU•IK. -essr CHAt, 0117 - J - 4 TR(II IOUs 110011(0 701 011E 11 318 II Ill [011([7101 014(3 cell . 007201 • 441[•.41 11113 (4121 A 1 315 1301 DIA {1(LD rPKR S0►111 IOL[ 141(10(2 fall ACO'0 21112 IItc.AOs 31 110 14 Ile e t• 1311 0(1 P0111 SUPPLY uX(OIJT COUNT $It[ 4SC 1171$ 1201.1 1441[ 13171 0 102 ACC. UO' 12t.21 31 311 11 118 401.804 C 1 328 1311 DIA 2106E 40[[33 PM - 1 ' Ur 241 118' 171.21 1818! 13111 D 1r• UZI PIA (0(15 00111107 121 1107 3 • 171• (161.0011 208[t 1 lap 128.41 {erc•AOl 11111 1A N8 110111 13111 [ 1/4 221 C010[4SAT[ 51411 1.1 10031 llr MT GAS , 3111. 130 11 ' 2 1/2'•14 in 003 (061(81101 701 '701•INC•4431pAP 742[4[ 011104. 6 t 1/2 • Ill) 011 701(4 S42111 11001.011 11111145 100 0111 I,1, 4 2 Al( region • 311(C) 111X[1 Ile 0e 112' 700 ['01(1. 0(21111110 O1 eill 7(7( • •• 1001) 1E0112(3 34• 111 1110 [016 FL116( l (111111. AI0484 Fig. 1 - Dimensions 48TC 04 -07 18 ieSTigUC . E\ Jul 11 12 03:02p Matthew Olson Constructio 5038920067 p.12 • CURBS & WEIGHTS DIMENSIONS - 48TC 04 -07 (cont.) • '510. UNIT CORNER CORNER CORNER CORNER C.G. HEIGHT UN11 WEIGHT WEIGHT (AT WEIGHT (8) WEIGH? (C1 WEIGHT ID) LBS. KG. LDS. KG. LBS. K6. LBS. KG. LBS. KG. K Y 2 • 3 --->. 487C•404 483 219 III 50 125 5? 131 59 116 _ 53 39 19911 23 (5841 16 378 (4161 481C-A05 531 244 124 55 139 63 145 66 129 59 39 19913 15841 17 (4321 rJ .�j 481C-406 569 258 131 59 147 61 154 10 137 62 39 19911 23 (5841 17 114 (4381 J 481C -407 652 296 150 68 _ 169 76 176 80 , 157 71 39 19911 23 15841 20 118 15111 'STANDARD UNIT WEIGHT IS WITH LOW NEAT 8 WITHOUT PACKAGING. FOR OPTIONS 8 ACCESSORIES. REFER TO THE PRODUCT DATA CATALOG. • CORNER A CORNER 8 ..Fro - r -- .1 �, '-:_ . `\ .. . , li: may , . (.., ,_ , .,...____„.....,,,.. 11 B I` }OO I I o "1` 00 _ __I CORNER 0 I j• CORNER C FROM; I 10P A10496A Fig. 2 - Dimensions 48TC 04 -07 • • , , 0 ,, ' 0,,,,-11 . 2,,r ' '''' ,, .'. - ' • • • C09337 Fig. 3 - Service Clearance • WC DIMENSION CONDITION 48 -in (1219 mm) Unit disconnect is mounted on panel A 16-In (457 mm) No disconnect, convenience outlet option 18 -In (457 mm) Recommended service dearance 12 -in (305 mm) Minimum clearance 42 -In (1067 mm) Surface behind servicer Is grounded (e.g., metal, masonry wall) B 36 -in (914 mm) Surface behind senricer is electrically non - conductive (e.g., wood, fiberglass) Special Check for sources of flue products within 10 -ft of unit fresh air intake hood C 36 -in (914 mm) Side condensate drain Is used 16 -In (457 mm) Minimum clearance 48 -in (1219 mm) No flue discharge accessory Installed, surface is combustible material D 42 -In (1067 mm) Surface behind servicer Is grounded (e.g., metal, masonry wall, another unit) 36 -in (914 mm) Surface behind servicer is electrically non - conductive (e.g., wood, fiberglass) Special Check for adjacent units or building fresh air Intakes within 10 -ft of this unit's flue outet • 19 �' ^ r`C C' l'' Jul 11 12 03:02p Matthew Olson Constructio 5038920067 p.13 OPTIO S & ACCESRY WEIGHTS PT 1ON 1 ACCESSORY WEIGHTS OPTION / ACCESSORY 04 05 06 07 I 08 09 12 14 18 lb kg lb kg lb. kg lb kg lb kg lb kg. lb kg Pb kg lb kg Humid'— MiZer 15 7 23 10 25: 11 29 13 38 17 47 21 '47 21 47 21 57 26 Power Exhaust — vertical 50 23 50 23 50' 23 50 23 75 34 75 34 75 34 75 34 85 39 Power Exhaust — horizontal 30 14 30 14 30 14 30 14 30 14 30 14 30 14 30 14 75 34 EoonoMiSer(IV or 2) 50 23 50 23 50 23 50 23 75 34 75 34 75 34 75 34 115 52 ..� Two Position damper 39 18 39 18 39 18 39 18 58 26 58 26 58 26 58 26 65 29 Manual Dampers 12 5 12 5 12 5 12 5 18 8 18 8 18 8 18 8 25 11 Medium Gas Heat 12 5 9 4 9 4 9 4 15 7 15 7 18 8 18 8 28 13 High Gas Heat — — 17 8 17 8 17 B 29 13 29 13i 35 16 35 16 50 23 Hag Guard (louvered) 16 7 16 7 16 7 16 7 34 15 34 15i 34 15 34 15 45 20 Cu /Cu Condenser Coil 6 3 13 6 13 6 15 7 12 5 23 10; 23 10 23 10 190 86 CulCu Condenser and Evaporator Coils 12 5 19 9 21 10 26 12 25 11 49 22' 49 22 49 22 280 127 v 1� Roof Curb (14 —in. curb) 115 52 115 52 115 52 115 52 143 65 143 65 143 65 143 65 180 82 ca Roof Curb (24 —In. curb) 197 89 197 89 197 89 197 89 245 111 245 111. 245 111 245 111 255 116 CO2 sensor 5 2 5 2 5 2 5 2 5 2 5 2. 5 2 5 2 5 2 Flue Discharge Deflector 7 3 7 3 7 3 7 3 7 3 7 3 7 3 7 3 7 3 Optional Indoor Motor /Drive 10 5 10 5 10 5 10 5 15 7 15 7 15 7 15 7 45 20 Motor Master Controller . 35 16 35 18 35 16 35 16 35 16 35 16 35 16 40 18 40 18 Return Smoke Detector 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 Supply Smoke Detector 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 Non —Fused Disoonnect 15 7 15 7 15 7 15 7 15 7 15 7 15 7 15 7 15 7 Powered Convenience outlet 35 16 35 16 35 18 35 16 35 16 35 16 35 16 35 16 35 16 Nom- Powered Convenience outlet 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 Enthalpy Sensor 2 1 2 1 2 1 2 1 2 1 2 1, 2 1 2 1 2 1 Differential Enthalpy Sensor 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 3 1 NOTE: Where multiple variations are eva0able, the heaviest combination Is listed. • 1 For Humid' —MiZer add MotorMaster Controller. 2 Where available. • • • • • • • • � 29 alCeSj �Q � ( C (� V 7 • [Page Too Large for OCR Processing] [Page Too Large for OCR Processing]