Loading...
Correspondence #ILtO City of Tigard, Oregon O 13125 SW Hall Blvd. • Tigard, OR 97223 November 10, 2008 11 RE: MECHANICAL Project Information Building Permit: MEC2008 -00550 Construction Type: 2B Tenant Name: Geo Engineers Occupancy Type: S -1 Address: 15055 SW Sequoia Pkwy. Occupant Load: NA Area: NA Stories: 1 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2007 edition; and the State of Oregon Fire Code (OFC) 2007 edition. The submitted plans are approved subject to the following. 1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) 2. Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room and within six feet of the appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC 3. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC 4. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC 5. Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC 6. Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC 7. Inspector may require additional sway bracing at the final installation inspection. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City S of Tigard in tracking and processing the documents. Respectful , I I P II an Nelson, Senior Plans Examiner (503)718 -2436 dann @tigard- or.com • • • h '