Loading...
Plans[Page Too Large for OCR Processing] FPS 20 12. — 00 15 I q .c55 1/liaA Vl ate( .415 .., _ ,. 800- 381 -9312 Technical Services +1 401 781 - 8220 2 Q�L www.tyco- fire.com S` P a 4 66 Series RFII — 5.6 . , :1 , "Royal Flush II" Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage General tective Cap can be used to mark the center of the ceiling hole into plaster Description board or ceiling tiles by gently push- ing the ceiling product against the Pro - The TYCO Series RFII Quick Response tective Cap. When ceiling installation (3 -mm bulb) and Standard Response is complete, the Protective Cap is re- 4; ... (5 -mm bulb), 5.6 K- Factor, "Royal moved and the Cover Plate /Retainer G Flush II" Concealed Pendent Sprin- Assembly is installed. kiers are decorative sprinklers featur- As an option, the Series RFII Standard • ing a flat cover plate designed to con- Response (5 -mm bulb) "Royal Flush II" _ ceal the sprinkler. These sprinklers are Concealed Pendent Sprinklers can be - - optimal for architecturally sensitive ar- fitted with a silicone Air and Dust Seal. eas such as hotel lobbies, office build- (Refer to Figure 5.) The Air and Dust ings, churches, and restaurants. Seal is intended for sensitive areas Each sprinkler includes a Cover Plate/ where it is desirable to prevent air and Sprinkler Retainer Assembly and a Sprinkler! dust from the area above the ceiling to Support Cup Assembly. The separa- pass through the cover plate. Identification ble, two -piece assembly design pro- N OTICE Number (SIN) • the following benefits: SIN ) • Allows installation of the sprinklers The Series RFII Concealed Penden TY3531 — 3 mm bulb and pressure testing of the fire pro- Sprinklers described herein must be tection system prior to installation of installed and maintained in compli- TY3551 — 5 mm bulb • a suspended ceiling or application of ance with this document and with the the finish coating to a fixed ceiling. applicable standards of the National Fire Protection Association, in addi- • Permits the removal of suspended tion to the standards of any authori- ceiling panels for access to building ties having jurisdiction. Failure to do so service equipment without having may impair the performance of these to first shut down the fire protection devices. system and remove sprinklers. The owner is responsible for maintain- • Provides for 1/2 inch (12,7 mm) of ing their fire protection system and de- vertical adjustment to allow a mea vices in proper operating condition. sure of flexibility in determining the The installing contractor or sprinkler length of fixed piping to cut.for the manufacturer should be contacted sprinkler drops. with any questions. The Series RFII Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap is temporarily removed during installation and replaced to help protect the sprinkler during ceiling in- stallation or finish. The tip of the Pro - IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 SEPTEMBER 2011 TFP181 • • TFP181 . Page 2 of 6 ' _ Technical 1/2" NPT . I Data /' ' ASSEMBLY Sprinkler Approvals = ` Approvals apply only to the service FRAME �j ' " j 1 a L M -- conditions indicated in the Design -� - -� ► �' , / , CAP Criteria section. 1'44 � TY3531 (3 -mm Bulb) is UL Listed, SUPPORT 1 C - Listed, VdS Approved (Certif- CUP WITH ( BULB icate No. G4090007), and NYC Ap- ROLL FORMED proved (MEA 353 -01 -E) as Quick THREADS Response. _ aill • TY3531 (3 -mm Bulb) is FM and COMPRESSION LPCB Approved (Ref. No. 094a/10) Aril ,lSCREW Appro� d as. Standard Res PINS (2) %�� Ilia . Factory Mutual and LPCB do not �I �� approve any concealed sprinklers for quick response. ' ._ ___. DEFLECTOR ' (DROPPED I • TY3551 (5 -mm Bulb) is UL Listed, DEFLECTOR I ; i 'POSITION) C -UL Listed, FM• Approved, LPCB I ,= ' I Approved (Ref:" No. 094a/9), and , . NYC Approved (MEA 353-01-E) .as I SPRINKLER/SUPPORT CUP Standard Response. I • ASSEMBLY • Approvals for Air and Dust Seal THREAD INTO . RETAINER UL and C -UL Listed for use with the SUPPORT CUP ) . I WITH THREAD RFII Standard Response Concealed UNTIL MOUNTING \ 0 0 Is. ,-- DIMPLES Sprinkler (TY3551). SURFACE IS J FLUSH WITH Maximum Working Pressure • CEILING EJECTION Maximum 250 psi (17,3 bar) by UL, . SPRING • C -UL, and NYC Maximum 175 psi (12,1 bar) by FM, VdS, and LPCB 'rte„ Temperature Rating 155 °F (68 °C) Sprinkler with SOLDER COVER • . 139 °F (59 °C) Plate TABS (3) COVER PLATE /RETAINER - PLATE 200 °F (93 °C) Sprinkler with ASSEMBLY 165 °F (74 °C) Plate - . Discharge Coefficient • • FIGURE 1 K= 5.6 GPM /psis / (80,6 LPM /bar / MODEL RFII CONCEALED SPRINKLER Adjustment • . ASSEMBLY 1/2 inch (12,7 mm) . Finishes . See the Ordering Procedure section. Physical Characteristics Frame Bronze Support Cup Chrome Plated Steel Guide Pins Stainless Steel Deflector Bronze Compression Screw Brass Bulb Glass Cap Bronze or Copper Sealing Assembly Beryllium Nickel w/ TEFLON Cover Plate Brass Retainer • Brass Ejection Spring Stainless Steel TFP181 Page 3 of 6 • FACE -OF CLEARANCE.HOLE Design -- • SPRINKLER DIAMETER C FITTING DIMENSION C J The TYCO Series RFII Concealed Pen- SPRINKLER ` � dent Sprinklers are intended for fire SUPPORT CUP . ,- - --- - protection systems designed in ac- ASSEMBLY 'I I ■ cordance with the standard instal- lation rules recognized by the appli- 1/2" (12,7 mm) cable Listing or Approval agency; for THREADED example, UL Listing is based on NFPA D ADJUSTMENT � i 13 and VdS Approval is based on the `( CEA 4001. FACE OF CEILING, o For more information on LPCB and fi) RETAINING MOUNTING RING VdS.Approvals, contact Tyco Fire Sup - SURFACE �' i pression & Building Products at the j / r / following office: , = I - r Enschede, Netherlands • Telephone: 31 53 -428 4444 �� ' - - -- -' Z Fax:31 -53- 428 -3377 Y ` r --- j z r -' The Sprinklers Series are RFII only listed Concealed and approved Pendent 3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE with the Series 'RFII Concealed Cover (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER - Plates having a factory applied finish. . REFERENCE • 3/32" (2,4 mm) POSITION ASSEMBLY , - . NOTICE COVER PLATE COVER PLATE Do not use Series RFII in applica- — PROFILE DEPTH DIAMETER tions . where the air. pressure above DIMENSION B DIMENSION A the ceiling is greater than that be- low. Down drafts through the Sprin- A: 3 inches (82,6 mm) C: 2 to 2 inches (60,3 to 66,7 mm) kler /Support Cup Assembly can delay sprinkler operation in a fire situation. B: 3/16 inches (4,8 mm) D: 1 -3/4 to 2 -1/4 inches (44,5 to 57,2 mm) Operation When exposed to heat from a fire, the FIGURE.2 • Cover Plate, normally soldered to the SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS Retainer at three points, 'falls away to expose the Sprinkler /Support Cup • Assembly. • The Deflector— supported by the • Guide Pins —then drops down to its • operational position. • The. glass Bulb contains a fluid that ex- pands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass Bulb, activating the sprinkler and allowing water to flow. • TFP181 Page4of6 - - -- - - — - CLEARANCE -- — . ° --- HOLE __MEW FRAME �` =II___ ARM 4 I S IL ■ SUPPORT __ i ia. 4 __ ICI! - 7/8" (23 mm) SQUARE AUGN J L ARROWS WITH / i i \ ` FIGURE4 FRAME ARMS \L DISPOSABLE PROTECTIVE CAP 1 III r • • ACCEPTS `� �/ . _ - 1/2° SOCKET •- - --i-r. DRIVE . • FIGURE 3 • RFII SPRINKLER WRENCH • • SUPPORT SPRINKLER FACE OF O RIENT CUP • CEILING SEAL • - BEVEL AS I `= t.__�_ 1 % • SHOWN PLATE . . ` + ) RETAINER lit ` ®i ; ' t' lJ I( . ASSEMBLY = - I. • . I : • / ma 1 j1 4 AND • DUST 1 -1- L� SEAL �_ �_ — —• LIP OF COVER RETAINER PLATE FIGURE 5 OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551) • TFP181 Page 5 of 6 Installation .-NOTICE Absence of the Cover Plate /Retainer Assembly _can _delay _sprinkler _opera- The TYCO Series RFII must be in- As-long-as-the-Protect/ye-Cap-remains lion in a fire situation. • stalled in accordance with the follow- in place, the system is considered "Out of Service ". When properly installed, there is a ing instructions. nominal 3/32 inch (2,4 mm) air gap be- Step 6. After the ceiling has been com- tween the lip of the Cover Plate and the MO.TICE pleted with the 2 -1/2 inch (63,5 mm) di- ceiling, as shown in Figure 2. Do not install any bulb -type sprinkler if am ration clearance hole and in prepa the bulb is cracked or there is a loss ration for installing the Cover Plate/ t This air gap is necessary for proper t h liquid the Retainer Assembly, remove and dis- operation of the sprinkler. If the ceil- f li liquid d from om the bulb. With the a l sprin- air bun- card the Protective Cap. Verify that the ing requires repainting after sprinkler o held be present. The diameter Deflector moves up and down freely installation, ensure that the new paint ble should of the air bubble is approximately 1/16 If the Sprinkler is damaged and the does not seal off any of the air gap. inch (1,6 mm) for the 155 °F /68 °C and Deflector does not move up and down Do not pull the Cover Plate relative to 3/32 inch (2,4 mm) for the 200 °F /93 °C freely, replace the entire Sprinkler. the Enclosure. Separation may result. temperature ratings. Do not attempt to modify or repair a Replace sprinklers that: damaged sprinkler. Obtain a 1/2 inch NPT sprinkler joint • are leaking or exhibiting visible signs by applying a minimum to maximum Step 7. When installing an Air and Dust of corrosion. torque of 7 to 14 ft. -lbs. (9,5 to 19,0 Seal, refer to Figure 5; otherwise, pro - Nm). Higher levels of torque can dis- ceed to Step 8. To attach the Air and • were modified or over - heated. tort the sprinkler Inlet with consequent Dust Seal, verify the angle of the out- Never paint, plate, coat, or otherwise leakage or impairment of the sprinkler. side edge of the seal is oriented ac- alter automatic sprinklers after they cording to Figure 5. Start the edge of leave the factory . Never repaint facto - Do not attempt to compensate for in- the Retainer in the grooved slot of the r - painted Cover Plates. If necessary, sufficient adjustment in the Sprinkler Air and Dust Seal and continue around y p ry by under- or over - tightening the Sprin- the retainer until the entire Air and Dust replace them with factory - painted kler /Support Cup Assembly. Re- adjust Seal is engaged. units. Non - factory applied paint can adversely delay or prevent sprinkler the position of the sprinkler fitting to suit: Step 8. Screw on the Cover Plate/ operation in the event of a fire. Retainer Assembly. until the Retainer Exercise care to avoid. damage to Step 1. Install the sprinkler only in the (shown in Figure 2) or the Air and Dust sprinklers before, during, and after in- pendent position with the center -line Seal (shown in Figure 5) contacts the stallation. Replace sprinklers damaged . of the sprinkler perpendicular to the ceiling. Do not continue to screw on by dropping, striking, wrench twisting, mounting surface. the Cover Plate /Retainer Assembly wrench slipping, or the like. Also, re- Step 2. Remove the Protective Cap. so that it lifts a ceiling panel out of its place any sprinkler that has a cracked Ste 3 . With p i p e thread sealant ap- normal position. If you cannot engage bulb or that has lost liquid from its plied to the pipe threads, hand - tighten the Cover Plate /Retainer Assembly bulb. (Refer to the Installation section.) the sprinkler into the sprinkler fitting. with the Support Cup or you cannot engage the Cover Plate /Retainer As- If you must remove a sprinkler, do not Step 4. Wrench- tighten the sprinkler sembly sufficiently to contact the cell- reinstall it or a replacement without re- using only the RFII Sprinkler Wrench. ing, you must reposition the Sprinkler installing the Cover Plate /Retainer As- • (Refer to Figure. 3.) Apply. the • RFII . Fitting. sembly. If a Cover Plate /Retainer As- Sprinkler Wrench to the Sprinkler as . • • sembly becomes dislodged during shown in Figure 3. • service, replace it immediately. Step 5. Replace the • Protective Cap Care and Responsibility lies with sprinkler own - by pushing it upwards until it bottoms Main era for the inspection, testing, and. out against the Support Cup. (R efer i7F�� ®�t �J�S���'v� maintenance of their fire protection to Figure 4.) The Protective Cap helps The TYCO Series RFII must be system and devices in compliance prevent damage to the Deflector and maintained and'serviced in accordance with this document, as well as with the Arms during ceiling installation and /or with the following instructions. applicable standards of the National finish. You can also use the Protective Fire Protection Association (for exam - Cap to locate the center of the clear- ance hole by gently pushing the ceiling 'NOTICE ple NFPA 25), in addition to the n- dards of any other authorities having material up against the center point of Before closing a fire protection sys- jurisdiction. Contact the installing con - the Protective Cap. tem main control valve for maintenance tractor or sprinkler manufacturer re- work on the fire protection system that garding any questions. it controls, obtain permission to shut down the affected fire protection sys- Automatic sprinkler systems should be tem from the proper authorities and no- inspected, tested, and maintained by a tify all personnel who may be affected qualified Inspection Service in accor- by this action. dance with local requirements and /or national code. TFP181 Page 6 of 6 Limited Orde ring • - - Warranty Procedure -- - Products manufactured by Tyco Fire Contact your local distributor for Protection Products (TFPP) are war- availability. When placing an order, ranted solely to the original Buyer for indicate the full product name. ten (10) years against defects in ma- terial and workmanship when paid for Sprinkler /Support Cup Assembly and properly installed and maintained Specify: (SIN), (temperature rating under normal use and service. This from below) Series RFII Concealed warranty will expire ten (10) years from Pendent Sprinkler, P/N (specify). date of shipment by TFPP. No warran- ty is given for products or components 155 °F /68 °C . 200°F /93 °C manufactured by companies not af- TY3531 51- 792 -1 -155 51 -792 -1 -200 filiated by ownership with TFPP or for TY3551 51- 790 -1 -155 51 -790 -1 -200 products and components which have been subject to misuse, improper in- Separately Ordered Cover Plate/ stallation, corrosion, or which have not • Retainer Assembly: been installed, maintained, modified or Specify: (temperature rating from be- repaired in accordance with applicable low) Series RFII Concealed Cover Standards of the National. Fire Protec- - Plate with (finish), P/N (specify). tion Association, and /or the standards . . of any other Authorities Having Juris- • 139°F /59°C(a) :165 °F /74 °c(b) diction. Materials found by TFPP to be Brass . 56- 792 -1 -135 56- 792 -1 -165 defective shall be either repaired or re- Chrome 56- 792 -9-135 56-792,9-165 placed, at TFPP's sole option.' TFPP . Cn om 56- 792 -8 -135 56- 792 -8 -165 neither assumes, nor authorizes any s ignal White - • person to assume for it, any other ob- (RAL 9003) 56- 792 -4 -135 56- 792 -4 -165 ligation in connection with the sale of Grey White products. or parts of products. TFPP (RAL 9002) 56 -792 -0 -135 56- 792 -0 -165 shall not be responsible for sprinkler Pure White (c) system design errors or inaccurate or (RAL 9010) 56- 792 -3 -135 56- 792 -3 -165 incomplete information supplied by Custom 56- 792 -X -135 56- 792 -X -165 Buyer or Buyer's representatives. •(a) For use with 155 °F /68`C sprinklers. • In no event shall TFPP be liable, in (b) For use with 200F/93°C sprinklers. • contract, tort, strict liability or under (c) Eastern Hemisphere sales only. any other legal theory, for inciden- Sprinkler Wrench tal, indirect, special or consequential Specify: RFII Sprinkler Wrench, - damages, including but not limited to P/N 56- 000 -1 =075: • • labor charges, regardless of whether • TFPP was informed about the possibil- Air and Du Seal ity of such damages, and in no event Specify: Air and Dust Seal, shall TFPP's liability exceed an amount P/N 56- 908 -1 -001. • - equal to the sales price. • • • The foregoing warranty is made in lieu of any and all other warranties, ex- press or implied, including warranties of merchantability and fitness for a particular purpose. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex- tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. • • Copyright © 2008, 2011 Tyco Fire Protection Products. All rights reserved. t• O®C® TEFLON is trademark of The DuPont Corporation. '�f C® Fire Suppression & Building Products Technical Services 800 - 381 -9312 I +1- 401 - 781 -8220 www.tyco - fire.com Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K- Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage G eneral Corrosion- resistant coatings, where applicable, are utilized to extend the - Description life of copper alloy sprinklers beyond �d>a : 4 ,Y X17 3^ that which would otherwise be obtained _ !�' - • The TYCO Series TY -FRB, 2.8, 4.2, 5.6, when exposed to corrosive atmo- — Y,. � ✓ ,, and 8.0 K- factor, Upright and Pendent spheres. Although corrosion- resistant , 4+rn . 1 1 i Sprinklers described in this data sheet coated sprinklers have passed the it f � , 1 t_:;; J i are quick response, standard coverage, standard corrosion tests of the appli- decorative 3 mm glass bulb -type spray cable approval agencies, the testing is t ;� _ , l sprinklers designed for use in light or not representative of all possible tor- `;� °% ` - rosive atmospheres. Consequently, • . :,-'-4"-- �� ordinary hazard, commercial occupan- P 4 Y, • ;-••••-•.- • • it is recommended that the end user = =.== ties such as banks, hotels, and shop- -• ping malls. be consulted with respect to the suit- ability of these coatings for any given The recessed version of the Series TY- corrosive environment. The effects of FRB Pendent Sprinkler, where applica- ambient temperature, concentration of ble, is intended for use in areas with a chemicals, and gas /chemical velocity, finished ceiling. This recessed pendent should be considered, as a minimum, �go.. sprinkler uses one of the following, along with the corrosive nature of the -- • A two -piece Style 10 (1/2 inch NPT) chemical to which the sprinklers will be , exposed. �, •; ` —��, LA or Style 40 (3/4 inch NPT) Recessed P Escutcheon with 1/2 inch (12,7 mm) of An intermediate level of the Series TY- _, recessed adjustment or up to 3/4 inch FRB Pendent Sprinklers is detailed (19,1 mm) of total adjustment from the in Technical Data Sheet TFP356, and ' ' =': , flush pendent position, or a Sprinkler Guards are detailed in Tech- _ -:� - • A two -piece Style 20 (1/2 inch NPT) nical Data Sheet TFP780. or Style 30 (3/4 inch NPT) Recessed Escutcheon with 1/4 inch (6,4 mm) of NOTICE Model /Sprinkler recessed adjustment or up to 1/2 inch The Series TY-FRB Concealed Pendent (12,7 mm) of total adjustment from the Sprinklers described herein must be flush pendent position. installed and maintained in compliance Identification The adjustment provided by the with this document and with the appli- Number (SIN) Escutcheon reduces the cable standards of the National Fire accuracy to which the fixed pipe drops Protection Association, in addition to to the sprinklers must be cut. the standards of any authorities having TY1131: Upright 2.8K, 1/2" NPT jurisdiction. Failure to do so may impair TY1231: Pendent 2.8K,1/2" NPT the performance of these devices. TY2131: Upright 4.2K, 1/2 " NPT Owners are responsible for maintaining TY2231: Pendent 4.2K, 1/2" NPT their fire protection system and devices TY3131: Upright 5.6K,1/2" NPT IMPORTANT in proper operating condition. The TY3231: Pendent 5.6K, 1/2 "NPT installing contractor or sprinkler manu- TY4131: Upright 8.0K, 3/4" NPT Always refer to Technical Data facturer should be contacted with any TY4231: Pendent 8.0K, 3/4" NPT Sheet TFP700 for the "INSTALLER questions. TY4831: Upright' 8.0K, 1/2" NPT WARNING" that provides cautions TY4931: Pendent* 8.0K, 1/2" NPT with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. 'Eastern Hemisphere Sales Only Page 1 of 10 JULY 2010 TFP171 • TFP171 Page 2 of 10 7/16" - (11;1 mrn) ESCUTCHEON STYLE 10 or 20 • * NOMINAL PLATE SEATING RECESSED SSU 1/2 MAKE -IN SURFACE ESCUTCHEON DEFLECTOR NPT • 5 4 S.1 � 7/16" I ': ili f 2 -1/4" �-- (11,1 mm) NOMINAL di (57,2 mm) �m��- 2 11 F MAKE -IN t/ iyil I r 1 9 /16" - 3 2- 3/16" + � (55,6 mm) '�� WRENCH (39,7 mm) f � FLATS I 1 k ----- l 7 1/2 NPT SSP DEFLECTOR — 2 -7/8" (73,0 mm) DIA. CROSS SECTION • UPRIGHT PENDENT RECESSED PENDENT • 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector • Temperature rating is indicated on deflector or adjacent to • 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. l • Screw • . FIGURE 1 • • QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS • 2.8 K- FACTOR, 1/2 INCH NPT • • • 7/16" (11,1 mm) ESCUTCHEON STYLE 10 or 20 • * NOMINAL • PLATE SEATING - .RECESSED SSU MAKE -IN 1/2" SURFACE ESCUTCHEON DEFLECTOR NPT • • .._.-.....,_ —/ -.,,- c I . �� 5 �' 7/16" rr 2 -3/16" uur 4 li■ NOMINAL I OA�i (55,6 mm) —�p`� • MAKE -IN - .. 2 5. 2- 3/16" r \r 1 -1/2" y T , r , (55,6 mm) I WRENCH I (38, mm) kli 3 � FLATS 1/2" NPT SSP DEFLECTOR �— 2 -7/8" (73,0 mm) DIA. CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT • 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector • Temperature rating is indicated on deflector or adjacent to Assembly 5 - ress Com ion 2 - Button p orifice seat on frame. Screw FIGURE 2 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT • • TFP171 Page 3 of 10 • — -- • 7/16 " - (11;1 - mm) ESCUTCHEON STYLE - 10 or 20 ' * NOMINAL PLATE SEATING RECESSED SSU 1/2 MAKE -IN SURFACE ESCUTCHEON • DEFLECTOR NPT 6* � . / r „Trig *ii 4:,. , �_ _,_ , } I �_— 5 ear 7/16 " rr 2 -3/16° ,,�li' o 4 ; I (11,1 mm) NOMINAL liFiliMili l A (55,6 mm) �.1L MAKE -IN i • 2 — I • i 2- 3/16" r I 1-1/2” illif 3 i � (55,6 mm) �_ WRENCH (38,1 mm) 0 i I FLATS —Tr. .�, 1 - .7.--...:—.—r- 1 1/2" NPT SSP DEFLECTOR * • 2 -7/8" (73,0 mm) DIA. CROSS SECTION • UPRIGHT PENDENT RECESSED PENDENT 1 -Frame 3 - Sealing 4 - Bulb 6 - Deflector • Temperature rating is indicated on deflector or adjacent to • Assembly 5 - Compression orifice seat on fra 1 2 - Button Screw • FIGURE 3 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND•PENDENT (TY3231) SPRINKLERS . 5.6 K- FACTOR, 1/2 INCH NPT • 1/2" (12,7 mm) ESCUTCHEON STYLE 30 or 40 SSU * NOMINAL 3/4" PLATE SEATING RECESSED MAKE -IN SURFACE ESCUTCHEON DEFLECTOR I NPT 1/2" 1 — c • lir (12,7 mm) } 2 -5/16" Illikill 4 NOMINAL I III! AA (58,7 mm) • MAKE -IN �`�� 2 P;;;' ti ,fie 2-1/4" I I I 1 9/16" . _ . . . .. (57,2 mm) + � • (39,7 mm) ._ __,... 1 I 3/4" NPT SSP DEFLECTOR * - - 2 -7/8" (73,0 mm) DIA. - CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector • Temperature rating is indicated on deflector or ad to Assembly 5 - Compression orifice seat on frame. f 2 - Button Screw FIGURE 4 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT TFP171 . Page 4 of 10 7/16" (11,1 mm) - -`- -- - -- — SSU * NOMINAL - 1/2 DEFLECTOR MAKE -IN NPT 1 f 5 0 �` 7/16° I I (11,1 mm) I 1 2 -1/4" 4 ' NOMINAL /M = A 1 (57,2 mm) MAKE -IN — 2 I r — I 1 -9/16" 2 3/16" ry i ( mm) WRENCH (39,7 mm) - FLATS . SSP* i 0 1 1 CROSS 1/2" NPT DEFLECTOR SECTION UPRIGHT PENDENT 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector ' Temperature rating is indicated on deflector or adjacent to . • Assembly 5 - Com ression 2 - Button p orifice seat on frame. Screw FIGURE 5 QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS 8.0 K- FACTOR, 1/2 INCH NPT Technical Operation inch (1,6 mm) for the 135 °F /57 °C and 3/32 inch (2,4 mm) for the 286 °F /141 °C D ata The glass Bulb contains a fluid that temperature ratings. expands when exposed to heat. When Obtain a leak -tight 1/2 inch NPT sprin- Approvals the rated temperature is reached, the kler joint by applying a minimum to • UL and C -UL Listed . fluid expands sufficiently to shatter the maximum torque of 7 to 14 ft.lbs. (9,5 ' FM, LPCB, and NYC Approved glass Bulb, allowing the sprinkler to to 19,0 Nm). Higher levels of torque Refer to Table A and B for complete activate and water to flow. can distort the sprinkler Inlet with con - approval information including • • • sequent leakage or impairment of the corrosion- resistant status. sprinkler. Maximum Working Pressure Do not attempt to compensate for Maximum to Table Working C. Criteria • insufficient adjustment in the Escutch- The TYCO Series • TY-FRB eon Plate by under- e-ad or over-tightening h posiion TY FRB Pendent o Discharge Coefficient the sprinkler. Re- adjust the position of K =2.8 GPM /psi (40,3 LPM /bars / 2) and Upright Sprinklers are intended the sprinkler fitting to suit. K =4.2 GPM /psi (60,5 LPM /bar1/2) for fire protection systems designed in The • Series TY -FRB Pendent and accordance with the standard installa- K=5.6 GPM /psit/ (80,6 LPM /bar1/2) tion rules recognized by the applicable Upright Sprinklers must be installed K =8.0 GPM /psis / (115,2 LPM /bar1/2) Listing or Approval agency (such as, UL in accordance with the following Listing is based on the requirements of instructions. Temperature Rating NFPA 13, and FM Approval is based on 1. Install Pendent sprinklers in the Refer to Table A and B. the requirements of FM's Loss Preven- pendent position. Install upright Finishes tion Data Sheets). Only the Style 10, sprinklers in the upright position. Sprinkler: Refer to Table A and B. 20, 30, or 40 Recessed Escutcheon, as 2. With pipe- thread sealant applied to Recessed Escutcheon: White Coated, applicable, is to be used for recessed pendent installations. the pipe threads, hand - tighten the Chrome Plated, or Brass Plated. P sprinkler into the sprinkler fitting. Physical Characteristics Installation 3. Tighten the sprinkler into the sprin- Frame Bronze kler fitting using only the W-Type 6 Button Brass /Copper The TYCO Series TY -FRB Sprinklers Sprinkler Wrench (Figure 14). With Sealing Assembly Beryllium must be installed in accordance with reference to Figures 1 through Nickel w/Teflont the following instructions. 5, apply the W-Type 6 Sprinkler Bulb Glass Wrench to the sprinkler wrench Compression Screw Bronze 3tNO.TICEt flats. Deflector Copper /Bronze Bushing (K =2.8) Bronze Do not install any bulb -type sprinkler if • the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bub- ble should be present. The diameter • t Registered Trademark of Dupont of the air bubble is approximately 1/16 TFP171 Page 5 of 10 SPRINKLER FINISH (See Note 5) K BULB LIQUID NATURAL CHROME WHITE * ** FACTOR TYPE TEMPERATURE COLOR BRASS PLATED POLYESTER 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY1231) and 175 °F /79 °C Yellow 1, 2, 3, 4 UPRIGHT (TY1131) 200 °F /93 °C Green 286 °F /141 °C Blue • • 135 °F /57 °C Orange 2.8 RECESSED 155 °F /68 °C Red 1/2 "NPT PENDENT • (TY1231)* 175 °F /79 °C Yellow Figure 6 200 °F /93 Green 124 • 135 °F /57 °C • Orange RECESSED 1 55 F /68 C Red • ° PENDENT ° • (TY1231) ** 175 °F /79 °C • Yellow Figure 7 • 200 °F /93 °C Green • • . • 135FJ57°C Orange • • PENDENT 155F/68°C . Red . (TY2231) and . 175 °F /79 °C Yellow . • UPRIGHT • (TY2131) 200 °F /93 °C Green • 286 °F /141 °C Blue • 135 °F /57 °C Orange • 4.2 RECESSED 1/2" NPT PENDENT • 155 °F /68 °C Red 1, 2 • (TY2231)* 175 °F /79 °C Yellow • . Figure 8 • 200 °F /93 °C Green . 135 °F /57 °C Orange RECESSED PENDENT 155'F/68 °C Red • (TY2231) ** 175 °F /79 °C Yellow - Figure 9 ' • 200 °F /93 °C • • . Green NOTES:. . • • 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. • 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. ' Approved by the City of New York under MEA 354 -01 -E. 5. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers aro UL and C -UL Listed as Corrosion- Resistant Sprinklers. Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. ** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. "' Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS FOR 2.8 AND 4.2 K- FACTOR SPRINKLERS • • • • TFP171 Page 6 of 10 SPRINKLER FINISH (See Note 8) K TYPE TEMPERATURE BULB LIQUID NATURAL CHROME WHITE * ** LEAD FACTOR COLOR BRASS PLATED POLYESTER COATED 135F/57°C Orange PENDENT 155 °F /68 °C Red (TY3231) . and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 UPRIGHT 200 °F /93 °C Green • (TY3131) 286 °F /141 °C Blue 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red • 5.6 PENDENT 175F/79°C Yellow 1, 2, 4, 5 N/A 1/2" NPT (TY3231)* Figure 10 200 °F /93 °C Green 286 °F /141 °C • Blue 135 °F /57 °C Orange • RECESSED 155 °F /68 °C Red . • PENDENT • 175 °F /79 °C Yellow 1, 2, 3, 4, 5 N/A • (TY3231) ** • - Figure 11 200 °F /93 °C Green • . 286F/141°C Blue • 135 °F /57 °C Orange PENDENT (TY4231) 155'F/68 °C Red and 175 °F /79 °C • Yellow 1, 2, 3, 4, 5, 6, 7 1, 2, 5 UPRIGHT 200 °F /93 °C Green (TY4131) 286 °F /141 °C Blue • 135F/57°C Orange • RECESSED 155 °F /68 °C Red 8.0 PENDENT 175 °F /79 °C Yellow 1, 2, 5 N/A . 3/4" NPT (TY4231)* Figure 12 20OF/93°C Green • 286F/141°C Blue 135 °F /57 °C Orange • • • RECESSED 155 °F /68 °C . Red • PENDENT • 175F/79°C Yellow - 1, 2, 3, 5 N/A (TY4231) ** Figure 13 200F/93°C . • Green • . • . 286 °F /141 °C Blue • • 135 °F /57 °C Orange - PENDENT 155 °F /68 °C Red • (TY4931) 1/2 /2$ NPT and 175 °F /79 °C Yellow 1, 2, 4, 5, 6 1,2,5 • • UPRIGHT 2O0F/93°C Green • (TY4831) 286 °F /141 °C Blue • NOTES: 1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers. 2. Listed by Underwriters Laboratories, Inc., for use in Canada (C -UL) as Quick Response Sprinklers. 3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers. 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed sprinklers. 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details, contact Tyco Fire Suppression & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53- 428 - 3377.) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers. 8. Where Polyester Coated and Lead - Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion- Resistant Sprinklers. Where Lead - Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion- Resistant Sprinklers. * Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable. Frame and Deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE B LABORATORY LISTINGS AND APPROVALS FOR 5.6 AND 8.0 K- FACTOR SPRINKLERS • TFP171 • Page 7 of 10 -- -. - ______ - --- - -- - -- SPRINKLER FINISH - -- — K NATURAL CHROME WHITE LEAD FACTOR TYPE BRASS PLATED POLYESTER COATED PENDENT (TY1231) and 2.8 UPRIGHT (TY1131) 1/2" NPT 175 PSI (12,1 BAR) N/A RECESSED PENDENT (TY1231) PENDENT (TY2231) • and 4 2 UPRIGHT (TY2131) 175 PSI (12,1 BAR) N/A 1/2" NPT RECESSED PENDENT (TY2231) PENDENT (TY3231) 175 PSI and (12,1 BAR) 5.6 UPRIGHT (TY3131) 250 PSI (17,2 BAR) 1/2" NPT OR 175 PSI (12,1 BAR) RECESSED (SEE NOTE 1) N/A PENDENT (TY3231) PENDENT (TY4231) 175 PSI • and (12,1 BAR) UPRIGHT (TY4131) • 8.0 – 3/4 ".NPT • 175 PSI (12,1 BAR) - RECESSED N/A . PENDENT (TY4231) 8 U PENDENT (TY4931) 175 PSI • • 1/2" NPT UPRIGHT and (TY4831) 175 PSI (12,1 BAR) (12,1 BAR) NOTES: 1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in Canada (C -UL); and, the Approval by the City of New York. TABLE,C MAXIMUM WORKING PRESSURE The Series TY -FRB Recessed Pendent Care and Exercise care to avoid damage to Sprinklers must be installed in accor- sprinklers before, during, and after dance with the following instructions. Maintenance installation. Never paint, plate, coat, 1. After installing the Style 10, 20, 30, or otherwise alter automatic sprinklers or 40 Mounting Plate, as applica- The TYCO Series TY -FRB must be after they leave the factory. ble, over the sprinkler threads and maintained and serviced in accordance Replace sprinklers that: with pipe- thread sealant applied to with the following instructions. • were modified or over - heated. the pipe threads, hand - tighten the sprinkler Into the sprinkler fitting. • were damaged by dropping, striking, • NOTICE wrench twisting, wrench slippage, or 2. Tighten the sprinkler into the sprin- Before closing a fire protection system the like. kler fitting using only the W -Type 7 main control valve for maintenance . are leaking or exhibiting visible signs Recessed Sprinkler Wrench (Fig - work on the fire protection system of corrosi g ns g ure 15). With reference to Figures 1 that it controls, obtain permission to to 4, apply the W-Type 7 Recessed shut down the affected fire protection • were exposed to corrosive products Sprinkler Wrench to the sprinkler systems from the proper authorities of combustion but have not oper- wrench flats. and notify all personnel who may be ated, if you cannot easily remove 3. After ceiling installation and finish- affected by this action. combustion by- products with a cloth. ing, slide on the Style 10, 20, 30, or Absence of the outer piece of an • have a cracked bulb or have lost liq- 40 Closure over the Series TY -FRB escutcheon, which is used to cover uid from the bulb. Refer to the Instal- . Sprinkler and push the Closure over a clearance hole, can delay sprinkler lation section in this data sheet. the Mounting Plate until its flange operation in a fire situation. comes in contact with the ceiling. TFP171 Page 8 of 10 2 -7/8" DIA. 2 -7/8" DIA. _ _ - 5/8±1/4" 3/4" (19,1 mm) 1/2±1/8" __ _n3;0'mm)- 1/2 -,:-- mm) -- - -- (15,9±6,4 mm) 2 -1/4" DIA. 1/4° (6,4 mm) (12,7 ±3,2 mm 2 -1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) 1 (57,2 mm) SPRINKLER MOUNTING FACE OF MOUNTING • PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8° •�' (3,2 mm) .. (3 mm) iim d „A 1 MOUNTING 11' t 1 . • MOUNTING , SURFACE . SURFACE 7 •T I .0 SERIES 1- 5/16" (33,3 mm) CLOSURE 1 -5/16 (33,3 mrn CLOSURE SERIES ° ( mm) TY-FRB 13/16° (20,6 mm) TY-FRB 1 -1/16° (27,0 mm) • 'FIGURE 6 FIGURE 7 SERIES TY-FRB RECESSED. PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT : 2.8 K- FACTOR, 1/2 INCH NPT .. i:';j•�� }::'`.:. ; ....;i_ ° _.. .,.. :��•:: -.., ....� . 2 -7/8" DIA. 2 -7/8" DIA. 5/8 ±1/4" (73,0 mm) - 3/4" (19,1 mm) (73,0 mm) 1/2 ±1/8° 1/2° (12,7 mm) (15,9 ±6,4 mm) 2_1/4" DIA. 1/4"(6,4 mm) (12,7±3,2 mm) 2-1/4" DIA. 1/4° (6,4 mm) • FACE OF (57,2 mm ) �I ) MOUNTING FACE OF (57,2 mm MOUNTING SPRINKLER PLATE SPRINKLER • PLATE FITTING FITTING 1/8" 1/8" il' (3,2 mm) .. (3,2 mm) • G�l1fli' i ����i ��� _ i iI 4 . • _ \ MOUNTING vi' t MOUNTING , SURFACE SURFACE _ •____. 1 CLOSURE SERIES 1 -1/4° (31,8 mm) CLOSURE SERIES 1 -1/4" (31,8 mm) TY-FRB 3/4" (19,1 mm) ' TY -FRB 1" (25,4 mm) . FIGURE 8 . FIGURE 9 SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT Initial and frequent visual inspections of Responsibility lies with the owner for Care must be exercised to avoid dam - random samples are recommended for the inspection, testing, and mainte- age to the sprinklers - before, during, corrosion - resistant sprinklers to verify nance of their fire protection system and after installation. Sprinklers dam - the integrity of the corrosion - resistant and devices in compliance with this aged by dropping, striking, wrench material of construction. Thereafter, document, as well as with the appli- twist /slippage, or the like, must be annual inspections per NFPA 25 should cable standards of the National Fire replaced. Also, replace any sprinkler suffice. Protection Association (for example, that has a cracked bulb or that has lost Inspections of corrosion- resistant NFPA 25), in addition to the standards liquid from its bulb. (Ref. Installation sprinklers are recommended at close of any other authorities having jurisdic- Section). tion. Contact the installing contractor or range, instead of from the floor level sprinkler manufacturer regarding any Initial and frequent visual inspections of per NFPA. Inspection at close range random samples are recommended for can better determine the exact sprin- questions. corrosion- resistant sprinklers to verify kler condition and the long -term integ- Automatic sprinkler systems are rec- the integrity of the corrosion- resistant - rity of the corrosion - resistant material, ommended to be inspected, tested, material of construction. Thereafter, • which can be affected by the corrosive and maintained by a qualified lnspec- annual inspections per NFPA 25 should conditions present. tion Service in accordance with local suffice. requirements and /or national codes. TFP171 • Page 9 of 10 2 -7/8" DIA. _ 2 -7/8" DIA. " 5/8 ±1/4" ( mm)- 3/4° (19,1 mm) 1/2±1/8" (73,0 mm) 1/2° (12,7 mm) (15,9 ±6,4 mm) 2 -1/4" DIA. 1/4° (6,4 mm) (12,7 ±3,2 mm) 2 -1/4" DIA. 1/4 "(6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8" 1/8° ... (3,2 mm) •. (3,2 mm) -- ;l�q� x:1,/11,1 %� of - 1 I ■ t _ �� , ,, f , MOUNTING IIP MOUNTING SURFAC - - ∎ -- SURFACE - I CLOSURE SERIES 1 -1/4° (31,8 mm) CLOSURE SERIES 1 -1/4° (31,8 mm) TY -FRB 3/4° (19,1 mm) TY-FRB 1" (25,4 mm) FIGURE 10 FIGURE 11 • SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT • WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR; 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA. _ 2 -7/8' DIA. 5/8±1/4 (73,0 mm) 3/4 °(19,1 mm) 1/211/8" (73,0 mm) 1/2 "(12,7 mm) (15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (12,7 ±3,2 mm) 2 -1/4" DIA. 1/4° (6,4 mm) FACE OF (57,2 mm) MOUNTING FACE OF f- (57,2 mm) MOUNTING • SPRINKLER PLATE SPRINKLER PLATE FITTING FITTING 1/8° I 1/8' n (3,2 mm) n (3,2 mm) AN I IM .I.II W.' i ''. � , MOUNTING 1I MOUNTING IR - } . SURFACE SURFACE i j • • CLOSURE SERIES . 1 -5/16" (33,3 mm) CLOSURE SERIES .1- 5/16" (33,3 mm) ' TY-FRB 13/16" (20,6 mm) TY -FRB 1- 1/16" (27,0 mm) • FIGURE 1 FIGURE 13 . SERIES TY-FRB RECESSED PENDENT SERIES TY-FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT • • STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT Inspections of corrosion - resistant sprinklers are recommended at close el . WRENCH range, instead of from the floor level RECESS per NFPA. Inspection at close range WRENCH RECESS can better determine the exact sprin- (END "A" USED FOR / � 1 1 kler condition and the long -term integ- 1/2" NPT MODELS) rity of the corrosion - resistant material, which can be affected by the corrosive -,...0 conditions present. WRENCH RECESS (END "B" USED FOR %,„..• 3/4" NPT MODELS) PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH FIGURE 14 SPRINKLER WRENCHING AREA W -TYPE 6 SPRINKLER FIGURE 15 WRENCH W -TYPE 7 RECESSED • SPRINKLER WRENCH • TFP171 Page 10 of 10 _ P/N 57 - XXX - X - XXX _ _ __ 1 I MODEL/SIN SPRINKLER TEMPERATURE FINISH RATINGS • 330 2.8K UPRIGHT (1 /2 "NPT) TY1131 1 NATURAL BRASS 135 135 °F (57 °C) 331 2.8K PENDENT (1 /2 "NPT) TY1231 4 WHITE POLYESTER 155 155 °F (68 °C) 340 4.2K UPRIGHT (1 /2 "NPT) TY2131 3 WHITE (RAL9010)' 175 175 °F (79 °C) 341 4.2K PENDENT (1 /2 "NPT) TY2231 9 CHROME PLATED 200 200 °F (93 °C) 370 5.6K UPRIGHT (1 /2 "NPT) TY3131 7 LEAD COATED 286 286 °F (141 °C) 371 5.6K PENDENT (1 /2 "NPT) TY3231 • 390 ' 8.0K UPRIGHT (3 /4 "NPT) TY4131 391 8.0K PENDENT (3 /4 "NPT) TY4231 360 8.0K UPRIGHT (1 /2 "NPT) TY4831' • Eastern Hemisphere sales only. 361 8.0K PENDENT (1 /2 "NPT) TY4931' TABLE D PART NUMBER SELECTION • SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS Limited responsible for sprinkler system design r rderin errors or inaccurate or incomplete infor- mation supplied by Buyer or Buyer's Pro Warranty . representatives. Procedure . Products manufactured by Tyco Fire In no event shall TFSBP be liable, in Contact your local distributor for Suppression & Building Products contract, tort, strict liability or under availability. When placing an order, (TFSBP) are warranted solely to the any other legal theory, for incidental, indicate the full product name and Part • original Buyer for ten (10) years against indirect, special or consequential dam- Number (P /N). defects in material and workmanship ages, including but not limited to labor when paid for and properly installed charges, regardless of whether TFSBP Sprinkler Assemblies with NPT and maintained under normal use and was informed about the possibility of Thread Connections service. This warranty will expire ten such damages, and in no event shall Specify: (Specify Model /SIN), Quick (10) years from date of shipment by TFSBP's liability exceed an amount Response, (specify K- factor), (specify TFSBP. No warranty is given for prod- equal to the sales price. temperature ucts or components manufactured by P rature rating), Series TY-FRB companies not affiliated by ownership The foregoing warranty is made in lieu (specify Pendent or Upright) Sprinkler with TFSBP or for products and corn- of any and all other warranties, express with (specify type of finish or coating), • ponents which have been subject to or implied, including warranties of mer- P/N (specify from Table D). misuse, improper installation, corro- chantability and fitness for a particular Recessed Escutcheon: sion, or which have not been installed, purpose. Specify: Style (10, 20, 30, or 40) maintained, modified or repaired in This limited warranty sets forth the Recessed Escutcheon with (specify`) accordance with applicable Standards exclusive remedy for claims based on finish, P/N (specify'). of the National Fire Protection Associa- failure of or defect in products, materi- tion, and /or the standards of any other als or components, whether the claim is Sprinkler Wrench Authorities Having Jurisdiction. Mate- made in contract, tort, strict liability or Specify: W -Type 6 Sp Wrench, rials found by TFSBP to be defective any other legal theory. P/N 56- 000 -6 -387. shall be either repaired or replaced, at TFSBP's sole option. TFSBP neither This warranty will apply to the full Specify: W -Type 7 Sprinkler Wrench, assumes, nor authorizes any person extent permitted by law. The invalidity, P/N 56- 850 -4 -001. to assume for it, any other obligation in in whole or part, of any portion of this - Refer to Technical Data Sheet TFP770. connection with the sale of products or warranty will not affect the remainder. parts of products. TFSBP shall not be Copyright © 2007 -2010 Tyco Fire Suppression & Building Products. All rights reserved.