Specifications Oregon Heating" & Air Conditioning fC( JUN 1 3 2012 Summerfield Retirement Kitchen,11205 SW Summerfield Dr, Tigard, Or � I � 6 IY OFTIG ARD DING DIVISION Scope of Work Oregon Heating and Air Conditioning will perform the following scope of work: 1. Replace existing rooftop HVAC 10 -ton unit on existing sleepers. Equipment Schedule RTU1- Carrier 48TCED12A2G6- 208/3/60. 43.7 MCA, 50 MOCP. 11.1 eer, 4000 cfm, 114,000 Btu cooling. 224,000 Btu gas input. 1015 #. Rei'sladiha 1210# Rheern RRGF -12. Ventilation Requirements- based on 2010 OMSC table 403.3 RTU1- single zone kitchen Provides MUA for existing exhaust fan, provide 50% OSA during occupied. SA = 4000 cfm RA = 2000 cfm OSA = 2000 cfm GAS Per OMSC Tabel C402.4(3) 2Psi inlet pressure @ 1.0 Psi pressure drop Existing, no change to input. Mechanical General Notes: 1. All roof steel ducting will be 24 ga minimum galvanized, 2" insulation (R8). 2. Heating and cooling ducting to be designed to not exceed 0.5 wc positive (supply) and 0.5 wc negative (return). 3. Provide programmable thermostat. 5 degree deadband minimum. 7 day. Microprocessor. Set program for night energy savings. 4. Seal ducting with UL listed mastic or mastic tape. 5. Max leakage rate of OSA or exhaust dampers to be 4 cfm /sft @ 1.0 sp. 6. Support duct every 8' max or within 2' of direction change. 7. Provide 0 and M to building owner. CITY OF TIGARD Approved . ff? '�fr:U.l{:: [ Conditionally Approved [ J See Letter to: Follow [ J Attached ....... F ,] Permit Number. "CC l ?- 2O 3 l Addr- s: ati• =;g_ - L t) By: .I's_ t&Vi' Date: BLS Approved plans shall be on job site. OFFICE COPY Page 1 of 1 Oregon Heating & A/C, Inc. Oregon Heating Ilk PHONE NUMBERS MAILING ADDRESS OPERATIONS CONTRACTOR LICENSE 503 - 691 -9699 PO Box 241 19300 SW 118`" Ave Oregon CCB 172126 503 -691 -8556 (Fax) Dundee, OR 97115 Tualatin, OR 97062 Washington OREGOHC900BN www.oregonheating.com Symmerfield Tiprd, Or - Google Maps Page 1 of 2 . itlatattl Z To see a!! the details that are visible on the - « _ - • -e the "Print" ', , n: • t 1 - • I, G 6 , 1 i e.... et ... ••■••-- . • 4 ,.i. A ,4,1•45 - • 14 ,114... M W X I a ` ' . .4611. f r , f i •. — •,� » 1151:111111 I•esk _, 4* 0 y w • ^ x r e. ,.�, it : _ , : .- 7.- ...... Pam a ir y . . i A inliih.._, _ „ ' I I! 1 Ai , Pi . _ • _ millhesp , f . - ....... i ., 0'04' *4' " 1"41111 / 11141 11 111n1 . t .4 „I ,--,..., _ ............_.... t j .......... _Am ItA. ■ � . http://maps.google.com/maps?h1=en&tab--vvl 6/7/2012 Ill')1/1/6------- ./r/IL' 20 r2 -- (1'16 H PHYSICAL DATA /lZo3-u r • MODEL RRCF- /RREF- /RRGF- COOLING DATA Nominal Cooling Capacity - (Tons) ns) [k 8.5 [29.9 10 (35.2] . Compressors - Hermetic (No.) 2 2 Capacity Stages -% 50/100 50/100 _ Refrigerant Charge /Circuit (Oz. R -22) _ 122 118 Condenser Fans (No.) _ 2 2 CFM [Us] Total 6000 [2832] 6000 [2832) Diameter -(In.) [mm]/Blades (No.) _ 22 [5591/3 22 (559]13 Motor HP [W]/RPM 1 /3 [248.61/1075 1 /3 [248.61/1075 Condenser Coils (No.) 1 1 Face Area-Sq. Ft. [mI -Total 24.0 [2.2] 24.0 [2.2] Rows/Fins Per In. -Total 2/14 2/22 Tube Dia. -In. [mm] .375 [9.5] .375 [9.5] Indoor Blower (No.) 1 1 CFM (Us] -Nom. 3400 [1605] 4000 [1888) Wheel-Dia./Width -(In.) [mm] 12/12 [305/305] 15/11 [381/279] Motor HP [W]-Std./Att. 1.5/2.0 [1118.5/1491.4] 2/3 [1491.4/2237.1] Motor RPM 1725 1725 Evaporator Coil (No.) 1 1 Face Area -Sq. Ft. (m'] -Total 11.8 [1.1] 11.8 [1.1] Rows/Fins Per In. 4/13 4/13 Tube Dia. -In. [mm] .3125 [7.9] .3125 [7.9] Filters-(Number) Size ea. -(in.) [mm] (2) 20 x 25 x 2 [508 x 635 x 51] (2) 20 x 25 x 2 [508 x 635 x 51] (2)20x 25 x 2[508 x 635 x51] (2)16 x 25x 2[406x 635x 51] Crated Unit Dimensions -(In.) [mm] 42 [1067] H x 86.25 [2191] W x 86.75 [2204] L 42 [1067] H x 86.25 [21911W x 86.75 [2204] L Shipping Weight (lbs.) [kg] RRCF Cool Only _ 1192 [540.7] 1234 [559.7] RRGF Gas Heat 1329 [602.8] 1388 (629.8] RRCF Cool Only 1014 [459.9] 1056 [479.0] Operating Weight (lbs.) [kW RRGF Gas Heat t' 1151 [522.1] 1210 [548.8] MODEL RRGF GAS HEATING DATA Heating Input -BTUH [kW] 200,000 [58.6) 200,000 [58.6] 250,000 [73.3] Heating Output -BTUH [kW] _ 162,000 [47.5] 162,000 (47.5) 202,500 [59.3 ] Heat Exchanger Tubes -(No.) 5 5 6 Capacity Stages -( %) 50/100 50/100 Thermal Effidency -( %) 81 81 MODEL RREF- ELECTRIC HEATING DATA Heater Size Designation 15K 20K(1' 30K:1 40K -`) "'60K 208V 10.8 15.0 21.6 30.0 43.2 KW Input @ 240V 14.4 20.0 28.8 40.0 57.6 480V 14.4 20.0 28.8 40.0 57.6 600V - 20.0 28.8 40.0 57.6 208V 36.9 51.2 73.7 102.3 147.4 Heating Capacity -MBH @ 240V 49.1 68.2 98.3 136.4 196.6 480V 49.1 68.2 98,3 136.4 196.6 600V - 68.3 98.3 136.5 196.6 Capacity Stages* 2 2 2 2 2 Nominal Cooling Capacity - (Tons) [kW] 8.5 10 8.5 10 8.5 10 8.5 10 10 _ [29.9] [35.2] [29.9] [35.2] [29.9] [35.2] [29.9] [35.2] [35.2] Shipping Weight (lbs.) [kg] 1202 1244 1212 1254 1222 1264 1232 1274 1284 [545.5] [564.3) [549.8] [568.8] [554.3] [573.3] [558.8] [577.9] [582.4] Operating Weight (lbs.) [kg] 1024 1076 1034 1086 1044 1086 1054 1096 1106 [464.5] [488.1] [469.0] [492.6] [473.6] [492.6] [478-11 ( [501.7] Element Material Helix Wound Nickel Chrome Wire ' First stage heating is 50% of total capacity. - "For RREF -10 ton [35.2 kW] model only. Ci) 600 volt model not available for RREF -10 ton [35.2 kW]. .2)600 volt model not available for RREF -8.5 ton [29.9 kW]. [ ] Designates Metric Conversions 4 • GP -5 -6 Project: Phagans REV -3 07/19/2010 Prepared By: 05:04PM GP-5-6 Tag Cover Sheet Unit Report Certified Drawing Performance Report Spec Sheet Unit Feature Sheet Packaged Rooftop Builder 1.21 Page 30 of 37 r Unit Report For GP -5 -6 Project: Phagans REV -3 07/19/2010 • Prepared By: 05:04PM Unit Parameters Dimensions (ft. in.) & Weight (lb.) "" Unit Model: 48TCED12A2G6 -0B0A0 Unit Length: 7' 4.125" Unit Size: 12 (10 Tons) Unit Width: 4' 11.5" Volts- Phase -Hertz 460 -3 -60 Unit Height: 4' 1.375" Heating Type: Gas Base Unit Weight 1015 lb Duct Cfg: Vertical Supply I Vertical Return ••• Weights and Dimensions are approximate. Weight does not include roof Heating Capacity: curbs, unit packaging, field installed accessories or factory Medium Heat installed options. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions and weights, refer to appropriate product data catalog. Unit Configuration Medium Static Option Al /AI - Al /Cu Electro- mechanical controls Temperature Economizer w/ Barometric Relief Standard Packaging Warranty Information No standard warranties. No optional warranties were selected. NOTE: Please see Warranty Catalog 500 -089 for explanation of policies and ordering methods. An uncoated Novation condenser coil was selected for this product. This is based on an installed location with postal code: 97201 and a non - corrosive localized environment. Ordering Information Part Number Description Quantity 48TCED12A2G6 -0B0A0 Rooftop Unit 2 Base Unit Medium Static Option Al/A1- Al/Cu Electro- mechanical controls Temperature Economizer w/ Barometric Relief Standard Packaging Accessories _ CRPWREXH023A01 Power Exhaust System 2 Packaged Rooftop Builder 1.21 Page 31 of 37 • A F I • Certified Drawing for GP -5 -6 . Project: Phagans REV -3 07/19/2010 Prepared By: 05:04PM NOTES: UNITED P.O. SW NM ISIS WNW IS 116 PN*PEAT1 6F WW1 49MNAT� UNIT OUTDOOR J 6 X TECNMOIWIIS S3NACWI Sl IM IS OELIWMD NP/N 1NI FWSIS4 COMITION (NAT fNF .0. OS TRH IMNI -i d 66ExrtS 1. DIMENSIONS ARE IN INCHES. DIMENSIONS COIL TTPE c -ARTS nu NOT 6I 61T0.CAI a N3[611TS? WIIU 6115 6DT "an" If 7 rt6E961NNI[ a CARRIER 13221 EOAPONATI01'S R[111N ISE COST. ICC[iut If COIRICT, IN 1 1 ORE IN MILLIMETERS. 48TC -A08 RTPF IT 171 33 15 778 2 S CENTER OF GRAVITY 110481 (6561 14031 4810 -AOl RIPE 4125/1 1/4 27 7/8 CONNECTION SIZES 3. y DIRECTION OF AIR FLOW 49 1/8 37 114 15 118 A 1 318' (351 DIA FIELD POKER SUPPLE NOTE ABTC -Al2 RTPF 40-3/8 (12531 19441 (4031 110261 8 2 112' (041 DIA POWER SUPPLY KNOCKOUT 41 1/4 33 15 718 48TC -008 RIPE r C 1 314 1511 019 GAUGE ACCESS PLUG 118181 (6381 14031 1 D 7/8' 1221 DIA FIELD CONTROL WIRING HOLE C125331 1 19461 UO31 37 171 15 7/8 4131C-809 RIPE 49 E 3/4'-14 NPT CONDENSATE DRAIN 20 -311 181C-D12 RIPE 15271 49 318 31 1/4 15 7/8 ECONOMIZER 11000 F 112' -14 NPT GAS CONNECTION E12531 E9461 14031 • (OPTIONAL) 3/4'-14 NPT GAS CONNECTION 48TC -D06 (CHI 41 1/4 33 23 (10167 16581 1564.21 G 2 • (511 DIA POWER SUPPLY KNOCK-OUT 461C-D12 MCHX 46 3/8 37 1/4 11 _ - -... _ - - - - (12531 (9461 1279.41 1 ' ' ' ' ' - _ THRU-THE -BASE CHART (FIELD INST) RTPF - POUND TUBE. PLATE FIN (COPPER /ALUM) THESE NOTES REQUIRED IR P0* USE 117M ACCT NITS: MCNR - 'OVATION (ALUM /ALUM/ —t CI1B1Mfl1002A01; GAS TURD CURB 36.378 12-5/8 • (3211 C8UTMP6ROOIA01: 6AS TNRU 045E PAM • 19251 RETURN AIR RETTURN INREAD(0 SIRE ROOD MOLE CONDUIT USE SIZES (MAX.7 . - . . . . } 6 1/2' ACC. I /8' (22.2) FILTER ACCESS PANEL - E AL7, I S 1/2' 240 7/8' 122.21 (1001 -LESS( • i '\ MAIN 7 H I 1 /4' 1002,004) POSER 1 3/1' 114.41 CONDENSER / ' IN BASEPAN 2731/1 COIL 17311 37-5/8 218 Z 10017 311' FPT GAS 1 371' ( 41. {1 .00 '� W SUPPLY 19551 (10 [1D2I1 YIN. 1 ' 5EE TARN AIR SUPPLY N (002) PROVIDES 3 /4' FPT TO CURB INDOOR COIL 1 I T THE BASF FLANGE 6 FITTING. HOLE SIIE: 2' (50,61 ACCESS PANEL 18 ��V / %'I 2 DART I AIR BACK l OON 14121 (3ss1 1) f A TNRU- THE-BASE CHART (FIOPI • l 12 711 I 1 FOR 'TNRU- THE-BASEPAN' FACT0R0 OPTION. / 6 • *e* FITTINGS FOR ONLY I. Y, 0 I ARE PROVIDED. .5 { FOR BROW LISTED MODELS, A FIELD L 6 -1/4 SUPPLIED 1/2' ADAPTER IS REWIRED ^— 20 --+ lUF �, 3 -1 /4 (159) •• 00160(1 BASE PAN 1(10(G AND GAS VALVE: 11511 11001 NOW 1831 /8HCD.S406 T. 13361 t[ TOP --_ 25-1/2 -.• [6471 1.111 H 11-1/8 1-3 /8 1321 [302) (1181 • - l LECiRIUI 0 _ —i CONTROL BON IL TER A I ii DISCgINECT AC PANEL C STD CONDENSER B . CON I33A1 ENSATE COIL 6 DRAIN OPTIONAL —� INDOOR Bt06E1 ? 1110 CONDENSER III FACTOR( ACCESS __ _ __ , FACTORY INSTALLED I I OUTSIDE III 21 -1/8 OI SCONNECT 21 - 3// INSTALLED ) (. (1091 F P "—HANDLE 13 -178 17 1 2 6 A[R CONVEOUTLET C-/ ,' _ 6� / -10 121/:131/ 011 AIR — • I I 16591 [ v XAMDIE Lam __ 11 6.5/8 ~� ` i__J • 1 1681 *1.1(5 _ 6 -t /8 E_ •�_ —�g o ("1 C� OO (1571 3 -311 2-518 6 -5/6 7 4 -378 (931 59 -1 /2 (671 w 8- /B (1677 11711 6 -128 (1131 3 37 12111 [96218 11551 (15101 TIP [9401 LEFT WIDTH •... 66.1/6 [1 BAROMETRIC 122361 SUPPLT RETURN RELIEF AI FRONT RIGHT A1R 1106 MP UPI TUPFKEOCS 48TC 08-12 SINGLE ZONE ELECTRICAL 48TM500985 Iff I OF 2 03 - 08 - 10 11 -24-08 COOLING WITH GAS HEAT F F Packaged Rooftop Builder 1.21 Page 32 of 37 • • Certified Drawing for GP -5 -6 Project: Phagans REV -3 07/19/2010 Prepared By: 05:04PM O UNITED P.O. 1OI an 601010[11 Ills( 1.0,1111 m (AnI11 CNA?•Tla W1NSSSSa 01 ncsc w9sns a uo<u991. STD. UNIT CORNER CORNER CORNER CORKER TECHNOL06I(7 amuse. 01 1003 IS 511•(51 0.09191 csn9ss COn1110A 151 7E 0as NO 10081:1671 nn SS S o 9 o, WTpOpR C.G. CARRIES 7 322+ ACCCPIA <� O IMAT 1093 RII�[� I CwR11 1 M 1 Wtlf9 IICE 10 CatuCT. WITT ° " NOWT 1•• /EIGHT 141 WEIGHT ID1 WEIGHT IC) WEIGHT 131 LBS. HG. LDS. NG. LBS. HG. LBS. KG. LBS. N6. X 1 2 18TC -418 RTPF 780 354 113 81 153 72 219 95 236 107 41 112 (1051) 33 1/8 06631 20 I/O 15211 446 STANDARD UNIT WEIGHT IS QTR LON GAS NEAT AND WITHOUT PACKAGING. 46TC -409 RIPE 920 413 212 96 183 83 243 110 232 128 40 7/8 (10381 34 18641 23 1/8 (5871 FOR OTHER OPTIONS AND ACCESSORIES, REM 70 THE PRODUCT DATA CATALOG. 46TC-412 RTPF 930 422 216 98 186 88 247 112 272 - 123.5 42 110671 33 1/8 16417 24 1/4 (6101 437[ -308 RTPF 835 379 161 14.5 170 77.2 255 115.8 246 111.7 44 7/8 01401 35 5/8 19051 19 3/8 (4921 46TC -0/9 ROOF 930 422 226 103.5 181 85 272 105.3 283 128,5 39 3/4 (10101 32 1/8 16351 18 5/6 14131 46TC -012 RTPF 940 421 231 104.3 103 85.3 234 706.2 284 '129.6 39 3/4 110101 33 18331 18 112 14101 43TC-308 4C40 805 365.5 160 12 -6 153 69.5 240 109 210 113 43 110921 34 3/6 13241 20 3/3 1511.11 48TC -912 NCNX 865 406.3 135 84 176 79.1 260 118 214 '124.4 42 1/0 (10897 35 1/2 19021 22 118 15811 CORNER A MONK - *OVATION MOD TUBE. IALNAIA`UN( (COPPER /ALUM CORNER B \■ik , 111�/-� 1. .01M I CORNER D L. 0 CORNER C TOP z • l 1 • • 1 . A 2 C ��ii = H o 1 [j00 0E� 4 s I : : 00 FRONT SMMET 101E 65410005 48TC 08-12 SINGLE ZONE ELECTRICAL HIS 2 07 2 03-08 -10 11 -24 -08 COOLING WITH GAS HEAT 48TM500985 F Packaged Rooftop Builder 1.21 Page 33 of 37 Performance Summary For GP -5 -6 Project: Phagans REV -3 07/19/2010 Prepared By: 05:04PM Outdoor Motor Qty:_.. _ .. - --- ...... - ...... _... ....... - .................................. ....- . ... . 2 0 Outdoor Fan FLA (ea): 0.8 Indoor Fan Motor Type' MED Indoor Fan Motor FLA _ 4.4 Combustion Fan Motor FLA (ea): 0.25 Pwr. Exhaust Fan Motor FLA: 1.8 Power Supply MCA 25.1 Power Supply MOCP (Fuse or HACR):..... - .._ 30 Min. Unit Disconnect FLA: 27 Min. Unit Disconnect LRA: 147 Electrical Convenience Outlet: None An uncoated Novation condenser coil was selected for this product. This is based on an installed location with postal code: 97201 and a non - corrosive localized environment. Acoustics Sound Power Levels, db re 10E -12 Watts Discharge Inlet Outdoor 63 Hz 97.9 94.7 88.6 125 Hz 94.1 87.5 85.0 250 Hz 80.8 72.4 81.6 500 Hz 74.7 67.8 79.5 1000 Hz 71.0 65.6 77.4 2000 Hz 68.4 61.3 74.1 4000 Hz 71.6 61.5 71.0 8000 Hz 73.2 59.8 66.3 A- Weighted 82.2 75.3 82.0 Packaged Rooftop Builder 1.21 Page 35 of 37 Performance Summary For GP-5-6 Project: Phagans REV-3 07Y19/2010 ' Prepared By: 05:04PM Part Num ber:48TCED12A2G6'0B0A0 AR|EER: 11J0 . |EER: 11.8 Base Unit Weight: — 1015 lb Base Unit Dimensions Unit Length: 88.1 in Unit Width: 59.5 in Unit Height: 49.4 in Unit 460-3-60 Air Discharge' Vertical Fan Drive Type Belt Actual Airflow 4000 CFM Site Altitude' 0 ft Cooling Performance Condenser Entering Air DB: 95.0 F Evaporator Entering Air DB: 80.0 F Evaporator Entering Air WB: 67.0 F Entering Air Enthalpy: 31.44 BTU/lb Evaporator Leaving AIrOB: 57.7 F Evaporator Leaving Air WB 57.3 F Evaporator Leaving Air Enthalpy 24.54 BTU/lb Gross Cooling Capacity: 134.10 MBH Gross Sensible Capacity 96.20 MBH Compressor Power Input 8.90 kW Coil Bypass Factor: 0.046 Heating Performance Heating Airflow 4000 CFM Entering Air Temp* 70.0 F Leaving Air Temp 112.5 F Gas Input Capacity' — 180.0/ 224.O MBH Gas Heating Capacity — 1B3.DD MBH Temperature Rise' 42.5 F NOTE _---_._ Second Stage Supply Fan External Static Pressure* 0.75 in wg Options / Accessories Static Pressure Economizer' 0.20 in wg Power Exhaust: (Fan Data Includes Drop) Total External Static* 0.85 in wg Fan RPM 980 Fan Power 2.60 BHP NOTE• Medium Static Fan Option Power Exhaust Return Duct Static: 0.20 in wg Max. Air To Exhaust: 3850 CFM Electrical Data Minimum Voltage: 414 Maximum Voltage: 506 Compressor #1 RLA: 7.7 Compressor #1 LRA' _ 52 Compressor #2RLA - 7.7 Compressor #2 LRA: 52 Packaged Rooftop Builder 1.21 Page 34 of 37 Performance Summary For GP -5 -6 Project: Phagans REV -3 07/19/2010 Prepared By: 05:04PM FanCirve 20 \ " 18 \\ \ . - \ \ 18 �; \ \ y 100f>RAA - \ N ' 7 - \ \ \ N 10 _ + N \ \ \ ,.\\\ a. co a3 NEE. „ 4,,, ,,, Ei N _ NM "111111k‘. _31013HP, Wirdi - a - • 1 “ : • - 1.50 -P CO - - -mo ► ► � \ CO C6 12 18 24 30 M 42 48 54 A lic w(CFM- 1t1ousands) RPM= 980BHP= 2.60Maxin unRPM= 1084MaximumHP =4.70 Note :Pleasecontactapplicationeti nigforselectionsoutsidethe 1egiion. SC- Systan C urve RP- RatedPoint Packaged Rooftop Builder 1.21 Page 36 of 37 - Unit Feature Sheet for GP -5 -6 Project: Phagans REV -3 07/19/2010 Prepared By: 05:04PM Carri Q WeatherMaker — 48TC PACKAGED ROOFTOP GAS HEATING /ELECTRIC COOLING UNITS 3, 4, 6, 6,7.5,8.5,10,12.6TONS STANDARD FEATURES INCLUDE: • Puron (R -41CA) HFC 'refrigerant celmegageewsw • ASHRAE 90.1 conplart and Energy Star quailed 1 • Scroll wmoressas wet internal line break and overload protection firgZe • Singe-stage cooling =peaty control on 04-12 moOeis Two -stage cooling capacity central on 08.14 models • SEER supto 13 .0.EER'supto 11.1 and IEER'supto t1.8 • *cursor'. • Exclusive non- corrosive composite condensate pia` in accordance with ASHQAE Standard 82. sloping design side a center drain • Standard coding operation up to 115•F WIC) and down to 40•F (4•C n I - down to 25• F jam• C) with MMr start kit • Pre-painted * em pawls and owner-coated +r4snor panels tested to era l • 500 loins son spray protect= �" wily insulated cabernet • Exclusive IOC sold -state control 10 or -board diagnostics with LED error code designation burner control logic and energy saving indoor • • ' fan motor delay Optional Louvered Had Guard Shown draft g � California Air 'Duality Management desgr` • Redundant gas valves with up to two stages of heating • Low pressure and high pressure switch protected. MAINTENANCE FEATURES: ASN RAE IN• Aco twi ess panels n easy pp handles v.. 5 i - / y � • lrrnovatve easy starting. no-strip sow unit s an u access t e panels ('M i \i V1A • - • Two-Inch disposable retail air taus and Tool-less liar access door C • Bab drove evaporator-Ian motor and plAsy combinations • New terminal board tadlitsMg simple sally *cut troubleshooting and simplified caramoi box arrangement WEATHERMAKER SERIES • Exclusive IOC solid-slate control for on-board diagnostics with LEO error code WeatherMaker (48TC) units e one - piece gas heating. electric fan boner cored logic and energy saving indoor motor delay coding units that we pre -wired and charged ged with Puron (R- 4101 refrigerant- They are factory tested in both heating and INSTALLATION FEATURES: cooling modes. and rated in accordance with ARI Standards • Thro.ts.Eoacrn power ray ospabikty 212 :04-06 sizes I and 360 (07 -14 sizes). WeathetMaker units • Single peed gas and a ectrio connections are designed in accordance with UL Standard 1995, and listed • Full permew base rail with buain rigging adapters and fork slots by the Underwriters' Laboratories • Conwrsbe from vertical to hcrizontal tee low for slab mowing STANDARD WARRANTY: • Azproved and csec b•,• 10 year hNRexchanger - 15-year stains steel colon • 5-Yex =impresser • 1-year pats • 3-year pals on N on ovadon Condenser coils - where evadable . ..� � i . • • Many optional upgrades also available C (11) it ter no l 14p1O •j „' t1 n r " ' OPTIONS INCLUDE BUT ARE NOT LIMITED TO: ... , .. • Prarte and d Direct Protocol Digital Contras (DOC Sees 04 Sizes 07 - • Supply and Return Air Smoke Detectors, high static motors • Lowered condenser coil guards • Economizer. disoomect and convenience outlet options • Stainless Steel heat exchanger caber • Corrosion resistant coil coaling Certified to ISO 9001:2000 • Exdusrw Hvnia-lizar adaptive for system available en al sizes - Motor Master I controller included For a compete kit of options and accessories refer to the Product Data Catalog ,for the unit. Packaged Rooftop Builder 1.21 Page 37 of 37 Eg A60_20 1Z -315 RECEIVED JUN 1 3 2012 CITY OF TIGARD BUILDING DIVISION STRUCTURAL CALCULATIONS FOR SUMMERFIELD 11205 SW SUMMERFIELD DRIVE TIGARD, OREGON -- ROOF MECHANICAL UNIT REPLACEMENT -- 0.o PROFF ��� 0 2,187 . t � OREGON il yN E NOR EXPIRES: 12 / 31 / LJ Contents Detail A D Gravity Calculations G1 Lateral Calculations Ll - L2 Contact Person: John E Nordling, PE Enclosures El - E5 NORDLING Pro;. No.: 12 -211 :11111, STRUCTURAL SUMMERFIELD ENGINEERS, LLC OREGON HEATING & AIR CONDITIONING 6775 SW 111th, Suite 200 • Beaverton OR, 97008 Date: JUN 2012 By: JEN Sheet No.: COVER uatT SQe Po.g 1 difigillikk 17 __ _______ , . ..... _. • , 4 i , 1 El vl 3. „ 1 I , N i h 141111 tni:14 V' —y� . I1 I • r , UJ r III Jr. 6 =9" 12'- b , ...,,,,,..... ,..., (i.... c „.„,,, T cz..., h.Aa 0 TIP.12.. c 8.640 t:r3 •17. : IJLw hJ TL14,ua 'r 7 Ir — ii � 661t...0". 4,,,1 VLI n t . J I 1 J i i to 4...rt\Nots lD6 �, t N.,,, �' i ` is r -- AvD c tam P . T. 4 � � SyL j icy i . 1��� 1tZ - SFea r��r y, 57443. ert 1 1 - }� - '` - ----- �- + 1 -- - - 4- - L+ uNt 1 a 41 T Sit% Cy 3 6) 187- � 1 - I - ( t._... t r l.. ` LIV'(oK1.4.. S«te#4s 11. efrsak I 2 I I I i... I© S,MPfo..,. Mkt AP EA.)tor .... 1 Nt; Ott I � CO* C41t o �-2ys T• RA 40* � _ fi Er . d 3 � ' 6 C41'�'to r-lt1c 1TK T 1 3 w ice u 3 , � r i . , PROFF g a a - E-- / .. �S , N G I N R /D 12,18 • . 14; O EG' tip l a 4 f b \ 0 t k 41NOJ C.1"L+ V If L'r -- l vE 1A•..em 04 l. 1g k r 6'4, . NOR \ EXPIRES: 12 / 31 / I NORDLING Prof. No.: 12 -211 ;11, STRUCTURAL SUMMERFIELD ENGINEERS, LLC OREGON HEATING & AIR CONDITIONING 6775 SW 111th. Suite 200 • Beaverton 09. 97008 Date: JUN 2012 By: JEN Sheet No.: b1 --W — — — II_ _ ___ , ,t4 , J • � �� ' , _ �' t 1 r, I C. LI , 1,121_1" 4 it...‘:_____,., 1 i. e.u.?.k..Arc,.:, t ..1 (111„. c. (...,$) • © TIP. I / 1 7 11.01C4 A-s C.-4- 26ts - re lit .IJt w Nlri.tt,ua iD { I "(Cc PIALttMS 944‘1"..:1 — 1 1 IC — —, fi t pM t ,.n,: i = l2i° --- j z ilia mmommommil im m om mimmen gsmi `h i i 4 I , i r l I + � . � --•• pvUU (3\ 1.40 CT. 44.6 -I ` S�'' , � �Icy,i `; !rl I 'tht.4Kt'rto1 R+r$, efs,t e?Itt. , � —� -., I C L" -- Arrrkc.A- ArS KdSUo h I I a 0 d i 0E) - It.. - -- J� - t StwArs- 1'itft .5 Pc' EA.L y I I I t I , 2 I I i I . 1 I © S1MPio.a' t.SAt EA,),o(PF I 'I I I � : I NG� 41 t, - (04.10 4 4'« pi i I , (..EiCii.e.i5 i I '�, TQJA W — -- Qvhv ti ot- kauktk134„1,t uts < cLatisizAawr tst,wr G n1 Lc OTO 16 a\4 •L)T► tiws t l`o`') t ,„ 14. — r NORDLING Proj. No.: 12-211 SUMMERFIELD j STRUCTURAL e ° • ENGINEERS, LLC OREGON HEATING & AIR CONDITIONING 6775 SW 111th, Suite 200 • Beaverton OR, 97008 Date: JUN 2012 By: JEN Sheet No.: 1 USGS Earthquake Hazards Program 2005 ASCE 7 Standard Location 45° 24' 19.17" N Ss and SI = Mapped Spectral Acceleration Values 122° 47' 35.14" W 11205 SW Summerfield Dr, Tigard, OR Ground Motion Ss 0.916 Si 0.333 Occupancy Category II Site Coefficients Fa 1.13 Site Class D Fv 1.73 Importance Factor 1.00 Height of Structure 20.0 ft SMS Fa * Ss 1.038 SMI Fy * Si 0.577 Design Category (SDC) D Sips (2/3) SMS 0.692 SDI (2/3) SMi 0.385 Air Side HVAC Eq= 0.275W +0.2 SDS W ap 2.50 Rp 6.00 W : Weight of Unit Fp_ 0.4 aRS • I�( R z= 20.0 ft ASD FP = 0.35 WP -> * 0.7 0.242 z = 24.0 ft FP = 0.39 WP -> * 0.7 0.275 FP MIN = 0.3 SDS IP WP = 0.208 Wp -> * 0.7 0.145 FP MAX = 1.6 SDS IP WP = 1.11 WP -> * 0.7 0.775 ti5c NORDLING Prof. No.: 12 -211 STRUCTURAL SUMMERFIELD E LLC OREGON HEATING & AIR CONDITIONING 6775 SW 111th, Suite 200 • Beaverton OR, 97008 Date: JUN 2012 By: JEN Sheet No.: 1 E 141 lbs to mss. 1,015 lbs ^r4y V EQ 219 lbs �Iv" C: 118 lbs Height 50" Weight 1,015 lbs P ►r Length 88" Width 60" VEQ = 0.275 * 1,015 lbs + 0.2 * 0.692 * 1,015 lbs = 279 lbs + 141 lbs T = 279 lbs * (50 "/2) / 60" + 141 lbs / 2 - 0.6 * 1,015 lbs / 2 = - 118lbs [O Net Uplift ] V= 279 lbs ATTAGN TO 4x6 SUPPORT CURBS WI SIMPSON 1N2.5A', (6) LOCATIONS. _pk_ NORDLING Proj. No.: 12 -211 STRUCTURAL SUMMERFIELD ENGINEERS, LLC OREGON HEATING & AIR CONDITIONING Date: JUN 2012 By: JEN Sheet No.: 6775 SW I l Ith, Suite 200 • Beaverton OR, 97008 LZ PHYSICAL DATA f ) (r5 )/ MODEL RRCF - /RREF- /RRGF- COOLING DATA Nominal Cooling Capacity - (Tons) [kW1 I 8.5 [29.91 10 [3 Compressors - Hermetic (No.) 2 Capacity Stages -% 50/100 50/100 Refrigerant Charge /Circuit (Oz. R -22) 122 118 Condenser Fans (No.) 2 2 CFM [Us] Total 6000 [2832] 6 [2832] Diameter -(In.) [mm] /Blades (No.) 22 [559]/3 22 [559]/3 Motor HP [W]/RPM 1 /3 [248.61/1075 1 /3 [248.6]/1075 Condenser Coils (No.) 1 1 Face Area -Sq. Ft. [ml-Total 24.0 [2.2] 24.0 [2.2] Rows/Fins Per In. -Total 2/14 2/22 Tube Dia. -In. [mm] .375 [9.5] .375 [9.5] Indoor Blower (No.) 1 1 CFM [Us] -Nom. 3400 [1605] 4000 [1888] Wheel- Dia./Width -(In.) [mm] 12/12 [305/305] 15/11 [381/279] Motor HP [W}- Std. /Alt. 1.5/2.0 [1118.5/1491.4] 2/3 [1491.4/2237.1] Motor RPM 1725 1725 Evaporator Coil (No.) 1 1 Face Area -Sq. Ft. [m'j -Total 11.8 [1.1] 11.8 [1.1] Rows/Fins Per In. 4/13 4/i3 Tube Dia: In. [mm] .3125 [7.9] .3125 [7.9] Filters- (Number) Size ea. -(In.) [mm] (2) 20 x 25 x 2 [508 x 635 x 51] (2) 20 x 25 x 2 [508 x 635 x 51] (2) 20 x 25 x 2 [508 x 635 x 51] (2)16 x 25 x 2[406 x 635 x 51] Crated Unit Dimensions -(In.) [mm] 42 [1067] H x 86.25 [2191] W x 86.75 [2204] L 42 [1067] H x 86.25 [2191] W x 86.75 [2204] L RRCF Cool Only 1192 [540.71 1234 [559.7] Shipping Weight (lbs.) [kg] RRGF Gas Heat 1329 [602.8] 1388 [629.6], RRCF Cool Only 1014 (459.91 11 . , • ' Operating Weight (tbs.) [kW RRGF Gas Heat 1151 [522.1] 1210 [548.8] MODEL RRGF- GAS HEATING DATA Heating Input -BTUH [kW] 200,000 [58.6] 200,000 [58.6] 250,000 [73.3] Heating Output -BTUH [kW] 162,000 [47.5] 162,000 [47.5] 202,500 [59.3] Heat Exchanger Tubes -(No.) 5 5 6 Capacity Stages -( %) 50/100 50/100 Thermal Efficiency-( %) 81 81 MODEL RREF- ELECTRIC HEATING DATA Heater Size Designation 15K 20K0 30K0 4OK0 " - 60K 208V 10.8 15.0 21.6 30.0 43.2 240V 14.4 20.0 28.8 40.0 57.6 KW Input @ 480V _ 14.4 20.0 28.8 40.0 57.6 600V _ - 20.0 28.8 40.0 57.6 208V 36.9 51.2 73.7 102.3 147.4 240V 49.1 68.2 98.3 136.4 196.6 Heating Capacity -MBH @ 480V 49.1 68.2 98.3 136.4 196.6 600V - 68.3 98.3 136.5 196.6 Capacity Stages' 2 2 2 2 _ 2 Nominal Cooling Capacity- (Tons) [kW] 8.5 10 8.5 10 8.5 10 8.5 10 10 [29.9] A [35.2] [29.9] [35.2] [29.9] [35.2] _ [29.9] , [35.2 ] [35.2 ] Shipping Weight (lbs.) [kg] 1202 1244 1212 1254 1222 1264 1232 1274 1284 [545.5] [564.3] [549.8] [568.8] [554.3] [573.3] [558.8] [577.9] [582.4] Operating Weight (lbs.) [kg] 1024 1076 1034 1086 1044 1086 1054 1096 1106 [464.5] [488.1] [469.0] [492.6] [473.6] [492.6] [478.1] [497.1] [501.7] Element Material Helix Wound Nickel Chrome Wire • First stage heating is 50% of total capacity. ** For RREF -10 ton [35.2 kW] model only. 0 600 volt model not available for RREF - 10 ton [35.2 kW]. \ '� (l ` V Lr CD 600 volt model not available for RREF -8.5 ton [29.9 kW]. (� Ai- [ ] Designates Metric Conversions 1 • 1 4 c./ ` GP -5 -6 Project: Phagans REV -3 07/19/2010 Prepared By: 05:04PM • /1V.41 GP -5 -6 Tag Cover Sheet Unit Report Certified Drawing Performance Report Spec Sheet Unit Feature Sheet Packaged Rooftop Builder 1.21 Page 30 of 37 Unit Feature Sheet for GP -5 -6 Project: Phagans REV -3 07/19/2010 Prepared By: 05:04PM • Carrier 6 0 %Veatherillaker' — 48TC PACKAGED ROOFTOP GAS HEATINGELECTRIC COOLING UNITS 3, 4, 5, 6, 7.5, 8.5, 10, 12.5 TONS STANDARD FEATURES INCLUDE: • Prron (R-41CA) 1-FC refrigerant l ,x aac . ,r1Ylyrr_ _ ` • A3iiPAE 30.1 corm:f.srt r d tt l d Energy Star qused T -:rail compressors' with .ntemat lire creak and 3...e -toad oro1- on " '''''. • 3vlg a -stage cooing w=mot aacry C on 04-12 models l e t'* ` ` � ° ' a • Tao -stage cooling ..apac'ty orerol on r. S models • SEER 's up to 13.0, EER's up to 11.1 ono IccR's .ip to 11.3 Fr „ I A • itrol'w refrgerant metering system • 'Exclusive non -C rtSive composte condensate pan In accordance with x ,.x� i t .? a rt �r ASHPAE Standard 82, siopirg design, side or enter drain ' ` *` 1,1r1:1 • Standard coaling operation up to 11. •F {-e •C 1 and oown to -0'F (4' Cl co q; x g ;4. i - down to 25' F (-4' C1 with Wrier rant kit • 1 ( l t '`.. i r . ? • Pre - painted exterior panels and primer-coated .nterCr pa tasted to •led i • r "'' ' :v 500 Mlis sat spray protection t • Foy insulated cabinet .ti k:7 F < y t • rduswe IGC solid-slate =it'd for or: -basal oragnosdcs with LED "` r , error coda desiglaoon burner control logic and energy saving irdcor ='r«: vc 'an motor delay • • Low 1•ox models that meet Ca•ionra Air Qua. dry Management Optional Louvered Hail Guard Shown • :ndticed draft as heat combusbon desgn • Redundant gas valves will up to two $11023 3f hexing • Low presstse and high pressure switch protected. ,i, 411 MAINTENANCE FEATURES: • Access panels with easy anp handles l r!;iyr,+ � .y�t�f • InfW 3dve easy starting. ICstiO screws on wild access panels Z \i1Vla • Tao-rich disposable return air F.lters and T :U -less f*er access door CON I It ' ..... _.. • Belt drive evaporator -fan motor and pt. key oambna'dons • New terminal board radiating simple safety clraat Toutlesheoting and simplified oo,11101 boa arrangement WEATHERMAKER SERIES • ?xctusive ICC solid -stare cartrol for o•-beard oagnostics LED WeatherMaker rMaker `4bTC 1 units are one gas heating, electric error 5ade designadcn. burner control logic rd energy saving odacr P 9 foal -noon delay cooling units that are pre -aired and charged with Peron l.R- 4101 refrigerant They are factory tested in both heating and INSTALLATION FEATURES: coofrng modes, and rated in accordance with A.RI Standards • Ttr.i d - e - tottonl cower en'tr'y cspabity 210 :04 -06 sizes) and 360 (07 -14 saes). 'Weatherlataker units • S•ngle port as and electric connectors are designed in accordance with ith IJL tandar , an Standard 1955d listed • -1A permeter base rail wan brat -in rigging adapters and fort slots S • Conueribe from t tic al to her ontal a meow for slab mo1e'eng by the Underwrters' Laboratories. STANDARD WARRANTY: Approved and certified by: • 10-year heat exchanger- 15-year starless steel oaccn S-year compressor • 1 -year oats ifirtil �� \� • 3-year parts on Novadon Condenser coils - wt'ere 3.43-Larne • Many optional upgrades also avail3b1-s C US > •r e s hit, yet (r of e' tl l4; OPTIONS INCLUDE BUT ARE NOT LIMITED TO: _, • Prerttiertslk'`• and %gall Protocol Direct Digital Cantos !D0C1 • .S. C4 - A Sizes 07 - • Supply and Rta.rn Air Smoke Cetectors, rsgh stale motors • Lcuvwed oorderser cal guards • ' Economizer. disconnect and co-rven. roe outlet (Oars • Stainless Steel heat exchanger oaton • Corrosion res oaf coating. Certified to ISO 9001 :2000 •' Exolusve Hisnia keZ•r adapive ceht.mioficstcn system avairab:e cn all sees - Motor Master [controller ird,ided For a complete list of cations and accessories refer to the Pr;dt.ct Data Catalog fd 1 urdt. Packaged Rooftop Builder 1.21 Page 37 of 37 e 3 a Unit Report For GP -5 -6 Project: Phagans REV -3 07/19/2010 Prepared By: 05:04PM Unit Parameters Dimensions (ft. In.) & Weight (lb.)'"" Unit Model' 48TCED12A2G6 -0B0A0 Unit Length. 7' 4.125" Unit Size 12 (10 Tons Unit Width. 4' 11.5" Volts- Phase - Hertz' 4 4$7 Unit Height' 4' 1 1 lb Heating Type:. Gas Base Unit Weight' Duct Cfg' Vertical Supply ! Vertical Return "-• Weights and Dimensions are approximate. Weight do Inc ude roof Heating Capacity: curbs, unit packaging, field installed accessories or factory installed options. Approximate dimensions are provided primarily for Medium Heat shipping purposes. For exact dimensions and weights, refer to appropriate product data catalog. Unit Configuration Medium Static Option Al/A1- Al /Cu Electro-mechanical controls Temperature Economizer w/ Barometric Relief Standard Packaging Warranty Information No standard warranties. No optional warranties were selected. NOTE: Please see Warranty Catalog 500 -089 for explanation of policies and ordering methods. An uncoated Novation condenser coil was selected for this product. This is based on an installed location with postal code: 97201 and a non - corrosive localized environment. Ordering Information Part Number Description Quantity 48TCED12A2G6 -0B0A0 Rooftop Unit 2 Base Unit Medium Static Option Al /AI - Al /Cu Electro - mechanical controls Temperature Economizer w/ Barometric Relief Standard Packaging Accessories CRPWREXH023A01 Power Exhaust System 2 C1� - UN!1 • • Packaged Rooftop Builder 1.21 Page 31 of 37 Edr • 1 • . Certified Drawing for GP -5 -6 Project: Phagans REV -3 07/19/2010 Prepared By: 05 :04PM c NOTES; OUTDOOR YX (TED P.D. Wr uu lrtl OOTHNPi I( lrE MOIRtr a turl[A tOg41141 • IYMIIIIOr r 1846 NIrIW a rrcH[ITf 1. DIMENSIONS ARC IN /7[715, DIMENSIONS WIT COIL TYPE 3 N N ;-K TECNXOLO6IES (11ACM(. n 4,r 1s KtirOND.Or „M (m413 TDINIr1r11A/r r1( /o4 ca111rra rut 8 10 315 M iillD�' CARRION rtttt carols nu NO II tatoa II (1111 mror( un7u MIMIC( a( 1011441. rucr. IN l 1 ARE IN MILLCMETERS, tDPrE.11 s en11A o caalr. r 4810 -006 RIPE 41 1/4 33 15 716 2. 1 19 CENTER OF GRAVITY 110481 16581 14131 46TC -SDI RTPF 41z /8 371/ PI 2 CONNECTION SAES 1. 1 (100(1101 OF AIR FLOW 49 1 30' 1351 DIA Fitly MITER SUPPLY HOLE 19 316 37 114 15 71 6 5 3 Ilt' 1611 DIA POKER SUPPLY KNOCKOUT 4RTC•Al2 IMF 40 -3 /8 .y 112571 19411 0031 110261 48TC•001 ATPF 41 1/4 31 IS 7/8 C 1 3 /4' 1511 DIA GAUGE ACCESS PLUG 111431 16381 14031 4830-DOS RIPE 45 3/5 31 114 15 116 1 0 7 /1' 1221 DIA FIELD CONTROL WIRING NOTE 112531 0761 14031 3/4' -14 NAT CONDENSATE DRAIN IeTt-Dti RIPE [5271 /9 3/S 31 1/4 15 7/0 ECONOMIZER 800* 20-3!4 E [12531 19161 14031 (OPTIONAL) • F 1 /2'•14 NPT GAS CONNECTION // 114 33 23 314' -14 NPT GAS CONNECTION 48TC -001 17:618 110431 16581 1564.21 6 2 ' 1571 DIA POWER SUPPLY NNOCN -W7 46TC -112 MCNI (12531 (711 (21L/1 ; ' " • - ' — '�� CURD RIFF - RODND TUNE. PLATE FIN (COPPER /ALUM) THRU-THE-BASE CHART (FIELD INST) MCNI NOYATION WAN/ALUM) CR8T / I 'NESE MOLES REWIRED FOR USE NITN ACCT NITS: 36.316 12-5/8 Mr1R002A01; GAS TNRU 17r \�1 16231 12-5/ CR8TMPNH004A01: GAS 1101.1 6ASEPAN 1 �o i i I, RETURN AIR + R �\ _ , / AIR CONDUIT SIZE 818E IE0'0 MOLE " COMWIT SIZE USE 211(1 (MALI \ i /2 e ,• • • 5 1' ACC. I /6' (22.2) PILFER ACCESS P11301 ♦ �� I I 1 /2' 244 1/6' (22.2) • 1TOOL•LES5I E ALT, CONDENSATE T 1 1 /4' 1002,0041 POKER 1 3/4' (14.41 0 0010(15(6 \ ' /AIM OPENING 28 -3/4 • • ,./.%-'17-'1:77,:-,.,:, .' � \ IN BASEPAN 1 S 175511 40 -316 I r 10011 371' FPT 6115 1 711' 111.11 COI( if SUPPLY 19351 (10211 I118001 COIL • EE TARO AIR SUPPLY • 10021 PROVIDES 3/4' OPT 110U CURB ACCESS PANEL 1! \ \. " / //I 2 (MARTASE AIR FLANGE I FITTING, xOIE SIZE: 2' 150.81 �_i 1 BACK 1l4u r 42] 'I f r - . - _I TNRU- THE -BASE CHART (FLOP) ` FOR 'TU68- TNE- BASEPAN' FACTORY OPTION. _f Ll 102 FITTINGS FOR ONLY I. Y. 0 I ARE PROVIDED. so FOR 6(105 LISTED MODELS. A FIELD L 6.1/4 SUPPLIED tit' ADAPTER 15 REWIRED •-•-- 25 -516 / LU -+ 3 -1/4 (1511 44 8(180(1 OA SF PAN FITTING AND GAS VALVE: (1511 [1001 NOW (631 IBNCD. 1.06 -+ lI TOP [3561 j: .-- 25-1/2 164 11 N 1 -1 // 11.1/8 4-5/8 1321 13021 11181 ISCCONNECT CONTROL 552 ISONNECT I IL TER I D 4 II LOCATION ACCESS PANEL C ST D. CONDENSE! 6. 1 t COND COIL 6 1 OPTIONAL — • INDOOR 6105(8 y OPTIONAL , 3 STALLED - ACCESS _ - - ______ r_ FACTOR( I INSTALLED 21-1/6 - - f I W /SIDE INSTALLED CONVENIENCE DISCONNECT :11:1.:':111 1111 11091 F ANDIE 11 -716 1 I� I I 26 AIt OUTLET 13341 C� / - SU 1 1591 fi MAMW[�b `(� .... 11 6 -5re -- — -- -` - - -' 8 = £E4 "ill t � 1 OO `C-1. .. 1 o o (1378 _ [551 55-1/2 [1718 -- �' 1.--- 8 -3/8 11371 11111 6-1/8 1117, TIP 19401 (2111 376216 11551 LEFT WIDT „ 110151 6ARONETP IC 12 -118 68.1 /6 (22301 SUPPLY RETURN RELIEF r FRONT RIGHT AIR FLOr V Nutt "" R 1120381 48TC 08 -12 SINGLE ZONE ELECTRICAL 48TM500985 (n 1 a 2 03 - 08 -10 11 - 24 - 08 COOLING WITH GAS HEAT F Packaged Rooftop Builder 1.21 Page 32 of 37 .44 EC;zo r 2_- o-0 3I , °� Z p c 4 -'-,- 5 vy,-- v-a t t� inA COMcheck Software Version 3.9.0 U Mecha Comp Certificate REC EIVED Oregon Energy Efficiency Specialty Code JUN 1 3 2012 Section 1: Project Information CITY OF TIGARD BJI! DINS' DIVISION Project Type: Alteration Project Title : Summerfield Kitchen Construction Site: Owner/Agent: Designer /Contractor: Section 2: General Information Building Location (for weather data): Tigard, Oregon Climate Zone: 4c Section 3: Mechanical Systems List Quantity System Type & Description 1 HVAC System 1 (Single Zone) : Heating: 1 each - Central Furnace, Gas, Capacity = 244 kBtu/h, Efficiency = 80.00% Ec Cooling: 1 each - Rooftop Package Unit. Capacity = 120 kBtu /h, Efficiency = 11.10 EER, Air - Cooled Condenser, Air Economizer Section 4: Requirements Checklist In the following requirements, the relevant code section reference is shown in [ J. ' +' denotes that more details exist in the specified code section. Checkboxes identify requirements that the applicant has not acknowledged as being met. Check marked requirements identify those the applicant acknowledges are met or excepted from compliance. 'Plans reference page /section' identifies where in the plans/specs the requirement can be verified as being satisfied. Requirements Specific To: HVAC System 1 : 1. [503.2.3 +] Equipment meets minimum efficiency: Central Furnace (Gas): 80.00 % Ec 2. [503.2.3 +] Equipment meets minimum efficiency: Rooftop Package Unit: 11.00 EER (11.2 IEER) ❑ 3. [503.2.6 +] Energy recovery ventilation systems. Individual fan systems that have both a design supply air capacity of 5,000 cfm or greater and a minimum outside air supply of 70 percent or greater of the design supply air quantity have an energy recovery system. A /4 / Exception(s): j Where energy recovery systems are prohibited by the International Mechanical Code. ❑ Systems serving spaces that are not cooled and are heated to less than 60 °F. ❑ Where more than 60 percent of the outdoor heating energy is provided from site - recovered or site solar energy. ❑ Type 1 kitchen exhaust hoods. ❑ Cooling systems in climates with a 1- percent cooling design wet -bulb temperature less than 64 °F (18'C). fJ Systems requiring dehumidification that employ series -style energy recovery coils wrapped around the cooling coil when the . evaporative coil is located upstream of the exhaust air stream. ❑ Systems exhausting toxic, flammable, paint exhaust, corrosive fumes, or dust. ❑ Laboratory fume hood systems that in lude qualifying features. Plans reference page /section: 0 4. [503.2.12] Hot Gas Bypass Limitation. Cooling systems does not use hot gas bypass or other evaporator pressure control unless the equipment is designed with multiple steps (or continuous) capacity modulation. Plans reference page /section: Al p-- Project Title: Summerfield Kitchen Report date: 06/11/12 Data filename: Untitled.cck Page 1 of 5 ' ' . [503.3.1 +] Supply air economizers shall be provided on each cooling system and are capable of providing 100- percent outdoor air, even if additional mechanical cooling is required to meet the cooling load of the building. Systems provide a means to relieve excess outdoor air during economizer operation to prevent overpressurizing the building. Exception(s): ❑ Cooling equipment less than 54,000 Btu/hr total cooling capacity. ❑ Economizer cooling is not required for new cooling systems serving an existing dedicated computer server room, electronic equipment room or telecom switch room in existing buildings up to a total of 600.000 Btu/hr of new cooling equipment. ❑ Economizer cooling is not required for new cooling systems serving a new dedicated computer server room, electronic equipment room or telecom switch room in existing buildings up to a total of 240,000 Btu /hr of new cooling equipment. • Plans reference page /section: Generic Requirements: Must be met by all systems to which the requirement is applicable: 1. [503.2.1 +] Calculation of heating and cooling loads. Design loads are determined in accordance with the procedures described in the ASHRAE /ACCA Standard 183. Alternatively, design loads have been determined by an approved equivalent computation procedure. ❑ 2. [503.2.1.1 +] Packaged Electric Equipment. Specified packaged electrical equipment has a heat pump as the primary heating source. Exception(s): ❑ Unstaffed equipment shelters or cabinets used solely for personal wireless service facilities. (] Requirement is not applicable. Plans reference page /section: 3. [503.2.2 +] Equipment and system sizing. Heating and cooling equipment and systems capacity do not exceed the loads calculated in accordance with Section 503.2.1. Exception(s): ❑ Required standby equipment and systems provided with controls and devices that allow such systems or equipment to operate automatically only when the primary equipment is not operating. ❑ Multiple units of the same equipment type with combined capacities exceeding the design load and provided with controls that have the capability to sequence the operation of each unit based on load. Plans reference page /section: ex , Y 1,f' 8' i(114,.(.e .)( 4. [503.2.3 +] HVAC Equipment Performance Requirements. Reported efficiencies have been tested and rated in accordance with the applicable test procedure. The efficiency has been verified through certification under an approved certification program or, if no certification program exists, the equipment efficiency ratings are supported by data furnished by the manufacturer. X 5. [503.2.4.1 +j Thermostatic Controls. The supply of heating and cooling energy to each zone is controlled by individual thermostatic controls that respond to temperature within the zone. Plans reference page /section: l a 1 tt [503.2.4.1.1] Heat pump supplementary heat. Heat pumps having supplementary electric resistance heat have controls that, except t. i during defrost, prevent supplementary heat operation when the heat pump can meet the heating load. Plans reference page /section: NV 7. [503.2.4.2] Set point overlap restriction. Where used to control both heating and cooling, zone thermostatic controls provide a / 1 � temperature range or deadband of at least 5'F (2.8 °C) within which the supply of heating and cooling energy to the zone is capable of being shut off or reduced to a minimum. Exception(s): ❑ Thermostats requiring manual change over between heating and cooling modes. Plans reference page /section: kW) 8. [503.2.4.3] Optimum Start Controls. Each HVAC system has controls that vary the start-up time of the system to just meet the temperature set point at time of occupancy. • Plans reference page /section: A . 9. [503.2.4.4 +] Off-hour controls. Each zone is provided with thermostatic setback controls that are controlled by either an automatic time clock or programmable control system. Exception(s): ❑ Zones that will be operated continuously. ❑ Zones with a full HVAC load demand not exceeding 6,800 Btu/h (2 kW) and having a readily accessible manual shutoff switch. Y Plans reference page /section: VII i 10. [503.2.4.5 +] Shutoff damper controls. Both outdoor air supply and exhaust are equipped with not less than Class I motorized dampers. Project Title: Summerfield Kitchen Report date: 06/11/12 flafa filpnamp- I Intitlpri rrk Panp 7 of 5 • . Exception D Gravity dampers shall be permitted for outside air intake or exhaust airflows of 300 cfm or less. "t Plans reference page /section: till I D 11. [503.2.4.6 +] Freeze Protection and Snow melt system controls. Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self - regulating heat tracing, include automatic controls capable of shutting off the systems when outdoor air temperatures meet code criteria. Plans reference page /section: 'V ? vi D 12. [503.2.4.8] Separate air distribution systems. Zones with special process temperature requirements and /or humidity requirements are served by separate air distribution systems from those serving zones requiring only comfort conditions; or shall include supplementary control provisions so that the primary systems may be specifically controlled for comfort purposes only. e Exception(s): IJ [503.2.4.8 +] Zones requiring only comfort heating or comfort cooling that are served by a system primarily used for process temperature and humidity control. Plans reference page /section: � /!V D 13. [503.2.4.9] Humidity control. If a system is equipped with a means to add or remove moisture to maintain specific humidity levels in a zone or zones, a humidity control devi�rovided. Plans reference page /section: D 14. [503.2.4.9.1] Humidity control. Where a humidity control device exists it is set to prevent the use of fossil fuel or electricity to produce relative humidity in excess of 30 percent. Where a humidity control device is used for dehumidification, it is set to prevent the use of fossil fuel or electricity to reduce relative humidity below 60 percent. Exception(s): j Hospitals, process needs, archives, museums, critical equipment, and other non - comfort situations with specific humidity requirements outside this range. Plans reference page /section: D 15. [503.2.4.9.2] Humidity control. Where a humidity control device exists it is set to maintain a deadband of at least 10% relative humidity where no active humidification or dehumidification takes place. Exception(s): iD Heating for dehumidification is provided with heat recovery or heat pumping and the mechanical cooling system efficiency is 10 percent higher than required in section 503.2.3, HVAC equipment performance requirements. Plans reference page /section: 16. [503.2.5] Ventilation. Ventilation, either natural or mechanical, is provided in accordance with Chapter 4 of the International Mechanical Code. Where mechanical ventilation is provided, the system has the capability to reduce the outdoor air supply to the minimum required by Chapter 4 of the International Mechanical Code. Plans reference page /section: 10 1 D 1 7. [503.2.5.1 +] Demand controlled ventilation (DCV). DCV is required for spaces larger than 500 ft2 for simple systems and spaces larger than 150 ft2 for multiple zone systems. Exception(s): D Systems with energy recovery complying with Section 503.2.6 D Spaces less than 750 ft2 (69.7 m2) where an occupancy sensor turns the fan off, closes the ventilation damper, or closes the zone damper when the space is unocc pied. Plans reference page/ section: (((///•[[[��Y' / / / /rJJ{� D 18. [503.2.5.2 +] Kitchen hoods. Kitchen makeup is provided as required by the Oregon Mechanical Specialty Code. Exception(s): it ❑ Where hoods are used to exhaust ventilation air that would otherwise be exhausted by other fan systems. . D Kitchen exhaust systems that include exhaust air energy recovery complying with section 503.2.6. . Plans reference page /section: N D 19. [503.2.5.3 +] Enclosed parking garage ventilation controls. In Group S -2, enclosed parking garages used for storing or handling automobiles employs automatic carbon monoxide sensing devices. Plans reference page /section: 20. [503.2.7 +] Duct and plenum insulation and sealing. All supply and return air ducts and plenums are insulated with the specified insulation. When located within a building envelope assembly, the duct or plenum is separated from the building exterior or Project Title: Summerfield Kitchen Report date: 06/11/12 Bata filpnamp• I Intitlpri rrk Panel R of S unconditioned or exempt spaces by a minimum of R -8 insulation, All ducts, air handlers and filter boxes are sealed. Joints and seams comply with Section 603.9 of the International Mechanical Code. Exception(s): D When located within equipment. Li When the design temperature difference between the interior and exterior of the duct or plenum does not exceed 15'F (8 °C). / 21. [503.2.7.1.1 +] Low - pressure duct systems. All longitudinal and transverse joints, seams and connections of low- pressure supply and return ducts are securely fastened and sealed with welds, gaskets, mastics (adhesives), mastic -plus- embedded - fabric systems or tapes installed in accordance with the manufacturer's installation instructions. • Exception(s): • ❑ Continuously welded and locking -type longitudinal joints and seams on ducts operating at static pressures less than 2 inches w.g. pressure classification. Plans reference page,'section: 1 U 22. [503.2.7.1.2 +] Medium - pressure duct systems. All ducts and plenums designed to operate medium - pressure are insulated and sealed in accordance with Section 503.2.7. Pressure classifications specific to the duct system are clearly indicated on the construction documents. Plans reference page /section: '4 O 23. [503.2.7.1.3 +] High - pressure duct systems. Ducts designed to operate at high - pressure are insulated and sealed in accordance with Section 503.2.7. In addition. ducts and plenums are leak- tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual. Plans reference page /section: /1/1°- " X2 4. [503.2.9.1 +] Air system balancing. Each supply air outlet and zone terminal device is equipped with means for air balancing in Jf accordance with the requirements of IMC 603.17. Discharge dampers intended to modulate airflow are prohibited on constant volume fans and variable volume fans with motors 10 horsepower. Plans reference page /section: 44 ) ‚ 1 1 L 1 ' " / /�4 25. [503.2.9.3 +] Manuals. The construction documents require that an operating and maintenance manual be provided to the building owner by the mechanical contractor. See long description for specifications. J.. Plans reference page /section: �"l I ❑ 26. [503.2.10 +] Air System Design and Control. Each HVAC system having a total fan system motor nameplate hp exceeding 5 hp meets the provisions of Sections 503.2.10.1 through 503.2.10.2. Plans reference page /section: Li 27. [503.2.10.1 +1 Allowable fan floor horsepower. Each HVAC system at fan system design conditions does not exceed the allowable fan system motor nameplate hp (Option 1) or fan system bhp (Option 2) as shown and calulated in requirement details. Exception(s): j Hospital and laboratory systems that utilize flow control devices on exhaust and/or return to maintain space pressure relationships necessary for occupant health and safety or environmental control shall be permitted to use variable volume fan power limitation. J Individual exhaust fans with motor nameplate horsepower of 1 hp or less. Plans reference page /section: /144) ❑ 28. [503.2.10.2 +] Motor nameplate horsepower. For each fan, the selected fan motor is no larger than the first available motor size greater than the brake horsepower (bhp). Exception(s): 0 For fans less than 6 bhp, where the first available motor larger than the brake horsepower has a nameplate rating within 50 percent of the bhp. selection of the next larger nameplate motor size is allowed. J For fans 6 bhp and larger. where the first available motor larger than the bhp has a nameplate rating within 30 percent of the bhp, selection of the next larger nameplate motor size is allowed. Plans reference page /section: i t A a 29. [503.2.10.3.11 Large Volume Fan Systems. Fan systems over 8,000 (7 m3 /s) cfm without direct expansion cooling coils that serve • single zones reduce airflow based on space thermostat heating and cooling demand. A two -speed motor or variable frequency drive reduces airflow to a maximum 60 percent of peak airflow or minimum ventilation air requirement as required by Chapter 4 of the International Mechanical Code, whichever is greater. Exception(s): J Systems where the function of the supply air is for purposes other than temperature control, such as maintaining specific humidity levels or supplying an exhaust syste Plans reference page /section: Project Title: Summerfield Kitchen Report date: 06/11/12 flats filpnamo I Intitlpri nnk Pan! 4 of 5 • 0 30. [503.2.10.3.2 +] All air- conditioning equipment and air - handling units with direct expansion cooling and a cooling capacity at ARI conditions greater than or equal to 110,000 Btu/h that serve single zones have their supply fan operation controlled according to code specific requirements. Exception(s): J Systems where the function of the supply air is for purposes other than temperature control, such as maintaining specific humidity levels or supplying an exhaust system. Plans reference page /section: u 31. [503.2.10.4] Series fan - powered terminal unit fan motors. Fan motors for series fan - powered terminal units are • electronically- commutated motors and have a minimum motor efficiency of 70 percent when rated in accordance with NEMA Standard MG 1 -2006 at full load rating conditions. Plans reference page /section: QP u 32. [503.2.12] Hot Gas Bypass Limitation. For cooling systems <= 240 kBtu /h, maximum hot gas bypass capacity is no more than 50% total cooling capacity. Plans reference page /section: /140C Section 5: Compliance Statement Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building plans, specifications and other calculations submitted with this permit application. The proposed mechanical alteration project has been designed to meet the Oregon Energy Efficie y Specialty Code, Chapter 8, requirements in COMcheck Version 3.9.0 and to comply with the mandatory requirements in the R irem is Ch cklist. /1477 ki4 Name Title Signature Date f D1/1 Section : Post Constructioompliance Statement • HVAC record drawings of the actual installation, system capacities. calibration information. and performance data for each equipment provided to the owner. HVAC O &M documents for all mechanical equipment and system provided to the owner by the mechanical contractor. CJ Written HVAC balancing and operations report provided to the owner. The above post construction requirements have been completed. Principal Mechanical Designer -Name Signature Date • Project Title: Summerfield Kitchen Report date: 06/11/12 flats filcnamp• I lntitlpri nnk Pane 5 of