Correspondence 9/ (Do — 7 3 'HO / or Plc( 1'1 5 ' U 'W zvfaol�. av-o37 1 2. - 000 out 49.49 c rtro 31 h/1N Al 1'%O R cdRuJk p Mp°/ MILBRANDT ARCHITECTS November 12, 2012 City of Tigard Building Department 13125 SW Hall Blvd Tigard, OR 97223 Attn: Mark VanDomelen Re: Brownstone at the Crossing (Ashbrook /Longstaff) Mr. VanDomelen, GUARDRAILS As per the approved design documents, the design and installation of the handrails and guardrails for the above mentioned project was done through the deferred submittal process where railings are pre- engineered, fabricated and installed solely in accordance with the railing manufacturer's requirements. For this project, the railing manufacturer provided guardrails at all decks within private dwelling units that are +36" above the adjacent decking surface. This height is not sufficient under the 2010 Oregon Structural Specialty Code which requires +42 ", but IS acceptable under Exception 1 of Section AN110.23.1 of Appendix N. As this project could have been submitted under Appendix N, with this letter I am requesting on behalf of our client JT Smith Companies that you approve the installation of +36" guardrails within private dwelling units as allowed per Appendix N, Section A110.23.1, Exception 1. FIRE - RESISTANT EXTERIOR WALLS & DOORS With regard to the rating of exterior walls and doors between Buildings 4 and 5, again Appendix N provides us an alternate and more favorable way of determining fire - resistive requirements based on Fire Separation Distance. Section AN103.4 specifies fire - resistive requirements based on Fire Separation Distance. Field measuring indicates there is 13' - 8" between exterior faces of Building 4 and 5 when measured at doors of Utility /Sprinkler Closets. An imaginary line positioned centered means a distance of 6' - 10" occurs to each side of this imaginary line. Per 25 CENTRAL WAY SUITE 210: KIRKLAND, WA 98033 : 425.454.7130 : WWW.MILBRANDTARCH.COM MILBRANDT ARCHITECTS AN1O3.4.3.1 exterior walls 5' or more from property line do no need to be fire rated. Per AN1O3.4.3.2 openings are permitted in exterior walls greater than 5' from property line. So, as with the guardrail issue, I am requesting on behalf of our client JT Smith Companies that you approve non -rated exterior walls and doors at the Utility /Sprinkler closets between Buildings 4 & 5 since they are not required to be fire -rated under Appendix N, Sections AN1O3.4.3.1 and AN1O3.4.3.2. Please don't hesitate to contact me with any questions or comments. Sincerely, g ei C rae/#14043 Rick B. Tolleshaug, AIA, NCARB Principal 25 CENTRAL WAY SUITE 210 : KIRKLAND, WA 98033 : 425.454.7130: WWW.MILBRANDTARCH.COM