Loading...
Plans 6Gt Pao°% -D°®cos tqca I F/re & Building r1 CEVED Products ' .. MAR 1 0 2008 CITY ®F TIGAR® Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 BUILDIMGIDIVISIOs �� Series RFII — 5.6 K- factor "Royal Flush I1" Pendent Concealed Sprinklers Quick & Standard Response, Standard Coverage General Cap. The Protective Cap is temporarily removed for installation, and then it can be replaced to help protect the illik Description sprinkler while the ceiling is being in- stalled or finished. The tip of the Pro - The Series RFII Quick Response tective Cap can also be used to mark (3 mm bulb) & Standard Response (5 the center of the ceiling hole into plas- _ y mm bulb), 5.6 K- Factor, "Royal Flush ter board, ceiling tiles, etc. by gently II" Concealed Pendent Sprinklers are pushing the ceiling product against the ---- -- -....,,., decorative sprinklers featuring a flat Protective Cap. When the ceiling in- cover plate designed to conceal the stallation is complete the Protective sprinkler. It is the best choice for archi- Cap is removed and the Cover Plate tecturally sensitive areas such as hotel Assembly installed. lobbies, office buildings, churches, As an option, the Series RFII Standard - and restaurants. Response (5 mm bulb) "Royal Flush II" Each unit includes a Cover Plate As- Concealed Pendent Sprinklers may be sembly that conceals the sprinkler op- fitted with a silicone Air and Dust Seal UL, C -UL, and NYC. Maximum 175 erating components above the ceiling. (Ref. Fig. 5). The Air and Dust Seal is psi (12,1 bar) by FM. The separable two -piece design of the intended for sensitive areas where it is Cover Plate and Support Cup Assem- desirable to stop air and dust travel Technical blies allows installation of the sprin- through the cover plate from the area klers and pressure testing of the fire above the ceiling. Data protection system prior to installation WARNINGS of a suspended ceiling or application The Series RFII Concealed Pendent Approvals for Series RFII of the finish coating to a fixed ceiling. Sprinklers described herein must be UL and C -UL Listed. FM Approved. They also permit removal of sus- installed and maintained im li NYC under MEA 353 -01 -E. LPCB Ref. pended ceiling panels for access to building service equipment without ante with this d ne ocumentn compli- , as well as No. 094a/09 for TY3551 & 094a/10 for h g avin to first shut down the fire pro- with the applicable standards of the TY3531) Approved. hav system and remove sprinklers. National Fire Protection Association, The approvals apply only to the serv- design i addition to the standards of any ice conditions indicated in the Design Also, the separable two-piece desn f the the Sprinkler wo pi other authorities having jurisdiction. Criteria section and maximum pres- inch the th mm) of vertical provides for ign for adjustment, 2 Failure to do so may impair the per- sure ratings indicated in the to reduce the accuracy to which the formance of these devices. Model /Sprinkler Identification Num length of fixed pipe drops to the sprin The owner is responsible for maintain- bers section. klers must be cut. i ng their fire protection system and de- Approvals for Air & Dust Seal vices in proper operating condition. P #10908100 The Series RFII Sprinklers are The installing contractor or sprinkler ( ) g ikl p RFII and C-UL Listed for use with the shipped with a Disposable Protective manufacturer should be contacted RFII (TY3551 & TY3504) Standard Re- with any questions. sponse Concealed Sprinkler. IMPORTANT Temperature Ratings Always refer to Technical Data Model /Sprinkler 155F/68C Sprinkler - 135F/57C Plate Sheet TFP700 for the "INSTALLER 200F/93C Sprinkler - 165F/74C Plate WARNING" that provides cautions Identification Discharge Coeffi lent with respect to handling and instal- K = 5.6 GPM /psi' (80,6 LPM /bar lation of sprinkler systems and corn- Numbers Adjustment ponents. Improper handling and in- 1/2 inch (12,7 mm) stallation can permanently damage TY3551 (5mm bulb) & TY3531 (3 mm Finishes a sprinkler system or its compo- bulb): maximum 175 psi (12,1 bar) by Cover Plate: Chrome Plated, Brass nents and cause the sprinkler to fail UL, C -UL, FM, LPCB and NYC. Plated, or White Painted (Custom paint to operate in a fire situation or cause TY3504 (5 mm bulb) & TY3505 (3 mm matches and colors other than white it to operate prematurely. bulb): maximum 250 psi (17,3 bar) by are available on request.) Page 1 of 4 JULY, 2004 TFP181 Page 2 of 4 TFP181 Physical Characteristics 1/2" NPT SEALING Frame Bronze , ASSEMBLY Support Cup . Chrome Plated Steel Guide Pins Stainless Steel Deflector Bronze FRAM ,j/ ` ` Compression Screw Brass I nl � ' I CAP Bulb Glass �� � MO � � Cap Bronze or Copper SUPPORT 1 Sealing Assembly CUP WITH 1 BULB Beryllium Nickel w/Teflon' ROLL FORMED ; THREADS l, II Cover Plate Brass Retainer Brass \ li I 1 COMPRESSION Ejection Spring ....Stainless Steel �� f � I ' , , � 1 i IN SCREW Patents PINS (2) � p r r i U.S.A. 4,014,388 I DEFLECTOR I (DROPPED ra n Opetio DEFLECTOR i C ti i i ` r POSITION) Operation When exposed to heat from a fire, the I SPRINKLER/SUPPORT CUP Cover Plate, which is normally sol- ASSEMBLY dered to the Retainer at three points, falls, away to expose the Sprinkler As THREAD INT I RETAINER sembly. At this point the Deflector sup- SUPPORT CUP J O WITH THREAD Y P P UNTIL MOUNTING 0 l DIMPLES ported by the Guide Pins drops down SURFACE IS to its operational position. FLUSH WITH EJECTION The glass Bulb contains a fluid that CEILING SPRING expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter then �; glass Bulb, activating the sprinkler and allowing water to flow. SOLDER COVER TABS (3) COVER PLATE/RETAINER PLATE ASSEMBLY Design FIGURE 1 Criteria SERIES RFII CONCEALED SPRINKLER ASSEMBLY The RFII (TY3551 & TY3504), 5 mm Bulb Type, Concealed Pendent Sprin- Step 1. The sprinkler must only be klers are UL and C -UL Listed as stand- Installation installed in the pendent position and and response - standard spray sprin- with the centerline of the sprinkler per - klers for use in accordance with the The Series RFII must be installed in pendicular to the mounting surface. current NFPA standard. They are FM accordance with the following instruc- Step 2. Remove the Protective Cap. Approved as standard response - tions: Step 3. W ith pipe thread sealant a standard spray sprinklers for use in P p p p accordance with the current FM Loss NOTES plied to the pipe threads, hand tighten Prevention Data Sheets. Do not install any bulb type sprinkler if the sprinkler into the sprinkler fitting. the bulb is cracked or there is a loss of Step 4. W rench tighten the sprinkler The RFII (TY3531 & TY3505) 3 mm liquid from the bulb. With the sprinkler P g- p using only Bulb Type, (Ref. Fig ure Concealed Pendent Sprin- held horizontally, a small air bubble Figure 3). The Sprinkler Wrench he RFII Sprinkle- klers are UL and C -UL Listed as quick should be present. The diameter of the g a T applied Wrench response - standard spray sprinklers air bubble is approximately 1/16 inch F gu re 3. to the Sprin as shown i i n Figure for use in accordance with the current (1,6 mm) for the 155 °F /68 °C and 3/32 kler as NFPA standard. They are FM Ap- inch (2,4 mm) for the 200 °F /93 °C tem- Step 5. Replace the Protective Cap proved as standard response - stand- perature ratings. (Ref. Figure 4) by pushing it upwards and spray sprinklers for use in accord- until it bottoms out against the Support ante with the current FM Loss A leak tight 1/2 inch NPT sprinkler Cup. The Protective Cap helps prevent Prevention Data Sheets. should be obtained with a torque o 7 damage to the Deflector and Arms dur- The Series RFII Concealed Pendent to 14 ft.lbs. (9,5 to 19 Nm). A maxi- ing ceiling installation and /or during Sprinklers Seri are only listed and a mum of 21 ft.lbs. (28,5 Nm) of torque application of the finish coating of the Y p is to be used to install sprinklers. proved with the Series RFII Concealed Higher levels of torque may distort the ceiling. It may also be used to locate Cover Plates having a metallic or white sprinkler inlet with consequent leak- the center of the clearance hole by painted finish. gently pushing the ceiling material up • age or impairment of the sprinkler. against the center point of the Protec- The Series RFII must not be used in Do not attempt to compensate for in- tive Cap. applications where the air pressure sufficient adjustment in the Sprinkler above the ceiling is greater than that Assembly by under- or over- tightening NOTE below. Down drafts through the Sup- the Sprinkler /Support Cup Assembly. As long as the Protective Cap remains port Cup could delay sprinkler opera- Readjust the position of the sprinkler in place, the system is considered to tion in a fire situation. fitting to suit. be "Out of Service ". ' Registered Trademark of DuPont TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE F CLEARANCE SPRINKLER L - DIAMETER HOLE FITTING DIMENSION C lei. e SPRINKLER i SUPPORT CUP - ---- ASSEMBLY j ]i/ 1/2" (12,7 mm) ` t �� OIL �I�� r THREADED I u_ . D ADJUSTMENT FACE OF CEILING, RETAINING RING ' FIGURE 4 MOUNTING ' I DISPOSABLE PROTECTIVE CAP SURFACE i r :I \ Step 6. After the ceiling has been com- pleted with the 2 -1/2 inch (63,5 mm) �ll��� - 1 — diameter clearance hole and in prepa- V ration for installing the Cover Plate As- sembly, remove and discard the Pro- \ I T tective Cap, and verify that the 3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE Deflector moves up and down freely. If (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER the Sprinkler has been damaged and REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY the Deflector does not move up and down freely, replace the entire Sprin- COVER PLATE COVER PLATE kler assembly. Do not attempt to mod- - PROFILE DEPTH - DIAMETER ify or repair a damaged sprinkler. DIMENSION B DIMENSION A Step 7. When installing an Air and Dust Seal, refer to Figure 5, otherwise proceed to Step 8. To attach the Air and A: 3 -1/4" (82,6 mm) C: 2 -3/8" to 2 -5/8" (60,3 to 66,7 mm) Dust Seal, verify the angle of the out - B: 3/16" (4,8 mm) D: 1 -3/4" to 2 -1/4" (44,5 to 57,2 mm) side edge of the seal is oriented ac- cording to Figure 5. Start the edge of FlGURE the Retainer in the grooved slot of the SERIES RFII CONCEALED SPRINKLER Air and Dust Seal and continue around INSTALLATION DIMENSIONS the retainer until the entire Air and Dust Seal is engaged. NOTE - The Air and Dust Seal is only to be installed on the periphery of the Re- � tamer. – =lt _f� FRAME ;It =l'. ARM ;r� Step 8. Screw on the Cover Plate /Re '- . I�� �� tamer Assembly until the Retainer - I - III – I – \ Figure 2 (or Air and Dust Seal Figure SUPPORT ' / 5) contacts with the ceiling. Do not _ 1 continue to screw on the Cover CUP # i Plate /Retainer Assembly such that it ME ' '` 11M11 � lifts a, ceiling panel out of its normal '■I � position. If the Cover Plate /Retainer i ,�,�� % Assembly cannot be engaged with the O Support Cup or the Cover Plate /Re- 7/8" (23 mm) tamer Assembly cannot be engaged SQUARE sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. ALIGN J ARROWS WITH \ Care and FRAME ARMS a l Maintenance ACCEPT ' . �/ ACCEPTS The Series RFII must be maintained r 0 1/2" SOCKET - and serviced in accordance with the DRIVE following instructions: NOTES FIGURE 3 Absence of the Cover Plate Assembly RFII SPRINKLER WRENCH may delay sprinkler operation in a fire situation. Page 4 of 4 TFP181 When properly installed, there is a SUPPORT SPRINKLER FACE OF ORIENT nominal 3/32 inch (2,4 mm) air gap CUP CEILING SEAL between the lip of the Cover Plate and % BEVEL AS the ceiling,_as shown in Figure 2. This ��` COVER j, SHOWN air gap `is necessary for proper opera- PLATE All G j �G. tion of the sprinkler. If the ceiling is to I RETAINER be repainted after the installation of i) - ' - It, ASSEMBLY �� the Sprinkler, care must be exercised ' --•. r to ensure that the new paint does NOT . 14 I ',: seal off any of the air gap. j � r . iii* CLEAN OOM Factory painted Cover Plates MUST /� „■" .!__ SEAL NOT be repainted. They should be re- � r �= LIP OF COVER placed, if necessary, by factory RETAINER PLATE painted units. FIGURE 5 Do not pull the Cover Plate relative to OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504) the Enclosure. Separation may result. Before closinga fire protection system Inspection Service in accordance with DAMAGES, AND IN NO EVENT main control valve for maintenance local requirements and /or national SHALL TYCO FIRE PRODUCTS' LI- work on the fire protection system that codes. ABILITY EXCEED AN AMOUNT it controls, permission to shut down the EQUAL TO THE SALES PRICE. affected fire protection system must be obtained from the proper authorities Limited THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL. and all personnel who maybe affected by this action must be notified. W arrant OTHER WARRANTIES EXPRESS OR Y IMPLIED. INCLUDING WARRANTIES Sprinklers that are found to be leaking OF MERCHANTABILITY AND FIT - or exhibiting visible signs of corrosion Products manufactured by Tyco Fire NESS FOR A PARTICULAR PUR- must be replaced. Products are warranted solely to the POSE. tic sprinklers must never be original Buyer for ten (10) years Automa i n utoma otherwise against defects in material and work - altered painted, , plated, coated or for manship when paid for and properly Ordering after leaving ving the must be rep laced. factory. . Modi- installed and maintained under normal fied d sprinklers that have been exposed klr use and service. This warranty will ex- Procedure Sprinklers corrosive not operated, should be replaced pr products of combustion, but pire ten (10) years from date of ship - have ment by Tyco Fire Products. No war- When placing an order, indicate the full h if they cannot be completely cleaned ranty is given for products or product name. Contact your local dis- by wiping the sprinkler with a cloth or components manufactured by compa tributor for availability. Hies not affiliated by ownership with by brushing it with a soft bristle brush. Tyco Fire Products or for products and Sprinkler Assembly: Care must be exercised to avoid dam- components which have been subject rating) ng) Semi s ) (specify temperature Pen - age to the sprinklers - before, during, to misuse, improper installation, corro- and after installation. Sprinklers dam- sion, or which have not been installed, dent Sprinkler, P/N (specify). aged by dropping, striking, wrench maintained, modified or repaired in ac- or the like, must be re- cordance with applicable Standards of 17 - 1-1 27 - twist/slippage, 1-2 PP TY3551 51- 790 -1 -155 51-790-1-200 placed. Also, replace any sprinkler that the National Fire Protection Associa- TY3504 51- 796 -1 -155 51 -796 -1 -200 has a cracked bulb or that has lost tion, and /or the standards of any other TY3531 51- 792 -1 -155 51 -792 -1 -200 liquid from its bulb. (Ref. Installation Authorities Having Jurisdiction. Mate - TY3505 51- 797 -1 -155 51- 797 -1 -200 Section). rials found by Tyco Fire Products to be If a sprinkler must be removed, do not defective shall be either repaired or Separately Ordered Cover Plate: reinstall it or a replacement without replaced, at Tyco Fire Products' sole Specify: (specify temperature rating) reinstalling the Cover Plate Assembly. option. Tyco Fire Products neither as- Series RFII Concealed Cover Plate If a Cover Plate Assembly becomes sumes, nor authorizes any person to with (specify finish), P/N (specify). dislodged during service, replace it im- assume for it, any other obligation in mediately. connection with the sale of products or 135F/57C(a) 16 79 24C 1 65 parts of products. Tyco Fire Products Brass 56- 792 -1 -135 56- 792 -1 -165 P P Y Bright Brass 56- 792 -2 -135 56- 792 -2 -165 The owner is responsible for the in- shall not be responsible for sprinkler Chrome 56- 792 -9 -135 56- 792 -9 -165 spection, testing, and maintenance of system design errors or inaccurate or Brushed Chrome --- -- protection system and de- incomplete information supplied by White 56- 792 56- 792 -3 8 -135 135 56 792 792 -3 8 -165 165 their fire P Y P PP Y White (RAL9010)' 56- 792 -3 -135 56- 792 -3 -165 vices in compliance with this docu- Buyer or Buyer's representatives. Bright White 56- 792 -4 -135 56- 792 -4 -165 ment, as well as with the applicable IN NO EVENT SHALL TYCO FIRE Oft White 56- 792 -5 -135 56- 792 -5 -165 standards of the National Fire Protec- PRODUCTS BE LIABLE, IN CON- Clack 56- 792 -6 -135 56- 792 -6 -165 . tion Association (e.g., NFPA 25), in TRACT, TORT, STRICT LIABILITY OR Custom 56- 792 -X-135 Ss- 7sz -x -lss other (a) For use with 155F/68C sprinklers. addition to the standards of any UNDER ANY OTHER LEGAL THE- (b) For use with 200E /93C sprinklers. authorities having jurisdiction. The in- ORY, FOR INCIDENTAL, INDIRECT, • Eastern Hemisphere sales only. stalling contractor or sprinkler manu- SPECIAL OR CONSEQUENTIAL facturer should be contacted relative to DAMAGES, INCLUDING BUT NOT Sprinkler Wrench: any questions. LIMITED TO LABOR CHARGES, RE- Specify: RFII Sprinkler Wrench, It is recommended that automatic GARDLESS OF WHETHER TYCO P/N 56-000-1-075. sprinkler systems be inspected, FIRE PRODUCTS WAS INFORMED Air and Dust Seal: tested, and maintained by a qualified ABOUT THE POSSIBILITY OF SUCH Specify: Air and Dust Seal, P/N 56- 908 -1 -001. TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 tL 'Fire & Building Products Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Series TY -B — 2.8, 5.6, and 8.0 K- factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General cable approval agencies, the testing is not representative of all possible cor- rosive atmospheres. Consequently, it -. " Description is recommended that the end user be _ A ,R: consulted with respect to the suitability , _ • 14, _ The Series TY -B, 2.8, 5.6, and 8.0 of these coatings for any given corro- h� K- factor, Upright and Pendent Sprin- sive environment. The effects of ambi- rift I n klers described in this data sheet are ent temperature, concentration of 1 - w standard response - standard cover - P chemicals, and gas /chemical velocity, age, decorative 5 mm glass bulb type should be considered, as a minimum, spray sprinklers designed for use in along with the corrosive nature of the ` light, ordinary, or extra hazard, com- chemical to which the sprinklers will be t;.; , mercial occupancies such as banks, exposed. ` _ �__� hotels, shopping malls, factories, refin- eries, chemical plants, etc. An intermediate level version of the Series TY -B Pendent Sprinkler can be The recessed version of the Series obtained by utilizing the Series TY -B TY -B Pendent Sprinkler, where appli- Pendent Sprinkler in combination with cable, is intended for use in areas with the Model S2 Shield.``, a finished ceiling. It uses a two -piece -� Style 10 (1/2 inch NPT) or Style 40 (3/4 WARNINGS inch NPT) Recessed Escutcheon. The The Series TY -B Sprinklers described l Recessed Escutcheon provides 1/2 herein must be installed and main- ' inch (12,7 mm) of recessed adjust- tained in compliance with this docu 1 ment or up to 3/4 inch (19,1 mm) of ment, as well as with the applicable t ; total adjustment from the flush pen- standards of the National Fire Protec- dent position. The adjustment pro- tion Association, in addition to the: vided by the Recessed Escutcheon re- standards of any other authorities hay- ''''- - - �" duces the accuracy to which the fixed ing jurisdiction. Failure to do so may '^° ....e. pipe drops to the sprinklers must be impair the performance of these de- cut. vices. Corrosion resistant coatings, where The owner is responsible for maintain- applicable, are utilized_ to- extend _the ing their fire protection system and de- life of copper alloy sprinklers beyond vices in proper operating condition._ -- that which would otherwise be ob- The installing contractor or sprinkler tained when exposed to corrosive at- manufacturer should be contacted mospheres. Although corrosion resis- with any questions. tant coated sprinklers have passed the standard corrosion tests of the appli- Model /Sprinkler IMPORTANT Identification Y Always refer to Technical Data E Sheet TFP700 for the "INSTALLER Numbers N WARNING" that provides cautions m with respect to handling and instal - TY1151 - Upright 2.8K, 1/2"NPT F - lation of sprinkler systems and corn- TY1251 - Pendent 2.8K, 112 "NPT a ponents. Improper handling and in- TY3151 - Upright 5.6K, 1l2 "NPT a) stallation can permanently damage TY3251 - Pendent 5.6K, 1/2 "NPT c a sprinkler system or its compo- TY4151 - Upright 8.0K, 3/4 "NPT or nents and cause the sprinkler to fail TY4251 - Pendent 8.0K, 314 "NPT o to operate in a fire situation or cause TY4851 - Upright 8.0K, 112 "NPT a it to operate prematurely. TY4951 - Pendent 8.0K, 112 "NPT o i- Page 1 of 8 OCTOBER, 2005 TFP151 Page 2 of 8 TFP151 ESCUTCHEON 7/16" (11,1 mm) PLATE SEATING ** NOMINAL SSU SURFACE NP T MAKE -IN DEFLECTOR i f _ We ' 5 2 -1/4" } 2-3/16" 4 (57,2 mm) / = �I OR (55,6 mm) I I 1- 9/16" ' WRENCH �� ��', 3 (39,7 mm) FLATS - ` � \ \� 1 SSP 7 DEFLECTOR CROSS PENDENT UPRIGHT SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 STANDARD RESPONSE SERIES TY -B UPRIGHT (TY1151) AND PENDENT (TY1251) SPRINKLERS 2.8 K- FACTOR, 1/2 INCH NPT ESCUTCHEON 7/16" (11,1 mm) STYLE 10 - PLATE SEATING ** NOMINAL RECESSED * SURFACE 1/2" T T M A MAKE-IN ESCUTCHEON DEFLECTOR _ _ 7/16" 0 ' 5 2- 3/16" + UMW- (11,1 mm) (55,6 mm) I I NOMINAL 4 MAKE -IN I 1 -1 /2" � �� g. � ` � 2-3/16" � : , �� 2 (38,1 mm) , W I RENH (55,6 mm) 01 • 3 ' - — 1 � _. .- ��.11� -• FLATS 1 / f f 1 SSP DEFLECTOR -- • — • 2 -7/8' ^ (73,0 mm) DIA. — " -. 1 1/2" NPT ** • PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to - ---'- - 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 2 STANDARD RESPONSE SERIES TY -B UPRIGHT (TY3151) AND PENDENT (TY3251) SPRINKLERS 5.6 K- FACTOR, 1/2 INCH NPT TFP151 Page 3 of 8 ESCUTCHEON 1/2" (12,7 mm) STYLE 40 PLATE SEATING NOMINAL RECESSED SURFACE 3/4', MAKE -IN ESCUTCHEON SSU __ _ t V NPT 1 DEFLECTOR . 1/2 " °g 5 2- 5/16" } `1 I (12,7 mm) 1 (58,7 mm) lu u ��� 7 ilit N OMAKE -IN MINAL 4 1- 9/16" �� 2 -1/4" W � � (572 mmWRENCH . � FLATS ir ii 1 SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA. 3/4" NPT ** PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Ejection orifice seat on frame. Screw Spring ** Pipe thread connections per ISO 7/1 can be provided on • special request. FIGURE 3 STANDARD RESPONSE SERIES TY -B UPRIGHT (TY4151) AND PENDENT (TY4251) SPRINKLERS 8.0 K- FACTOR, 3/4 INCH NPT ESCUTCHEON 7/16" (11,1 mm) PLATE SEATING ** NOMINAL SSU SURFACE NPT MAKE -IN DEFLECTOR t w t 5 = s 2 -1/4" } 2- 3/16" (57,2 mm) /N _ A; ' ( 5 5,6 mm) I I t 4 •1- 9/16" WRENCH 11r■ � .; `i 2 (39,7 mm) Wt. FLATS 7 '� $ '- 0 3 SSP 7 1 DEFLECTOR CROSS PENDENT UPRIGHT SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw * * Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 4 STANDARD RESPONSE SERIES TY -B UPRIGHT (TY4851) AND PENDENT (TY4951) SPRINKLERS 8.0 K- FACTOR, 1/2 INCH NPT • Page 4 of 8 TFP151 SPRINKLER FINISH (See Note 8) K TYPE TEMP. BULB NATURAL CHROME WHITE*** LEAD WAX WAX OVER LIQUID BRASS PLATED POLYESTER COATED COATED LEAD COATED 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red 2.8 (TY1251) 1, 2, 3 N/A 1/2" and 175 °F /79 °C Yellow NPT UPRIGHT 200 °F /93 °C Green (TY1151) 286 °F /141 °C Blue 360 °F /182 °C Mauve 1, 2 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY3251) 1, 2, 3, 4, 5, 6, 7 1, 2, 3, 5 1, 2, 3, 5 1, 2, 3, 5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green 5.6 (TY3151) - 286 °F/141 °C Blue 1",2", 3" 5 ** 1 ** 2 ** 3 *' 5 ** 1/2" NPT 360 °F /182 °C Mauve N/A 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 1, 2, 4, 5 N/A (TY3251)* 175 °F /79 °C Yellow Figure 4 200 °F /93 °C Green 286 °F /141 °C Blue 1, 2 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY4251) 1,2,5 1, 2,3,5 1,2,5 and 175 °F /79 °C Yellow 1, 2, 3, 4, 5, 6, 7 8.0 UPRIGHT 200 °F /93 °C Green 3/40 (TY4151) - 286 °F/141 °C Blue 1",2**, 3 ** 5** I**, 2 ** 5 *' NPT 360 °F /182 °C Mauve N/A 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1, 2, 3, 4, 5 N/A (TY4251)* 175 °F /79 °C Yellow Figure 5 200 °F /93 °C Green 286 °F /141 °C Blue 1, 2 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red 8.0 (TY4951) 1/2" and 175 °F /79 °C Yellow 1, 2, 3, 5 N/A NPT UPRIGHT 200 °F /93 °C Green (TY4851) 286 °F /141 °C Blue 360 °F /182 °C Mauve NOTES: 1. Listed by Underwriters Laboratories, Inc. (UL). 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL). 3. Approved by Factory Mutual Research Corporation (FM). 4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/03). 5. Approved by the City of New York under MEA 354 -01 -E. 6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31 -53- 428- 4444/Fax 31 -53 -428- 3377). 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/05). 8. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be UL and C -UL Listed, the • sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers. * Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable. ** 150 °F /66 °C Maximum Ceiling Temperature. * ** Frame and deflector only. Listings and approvals apply to color (Special Order). N /A: Not Available TABLE A, LABORATORY LISTINGS AND APPROVALS TFP151 Page 5 of 8 2 -7/8" DIA. C., 5/8 ±1/4" (73,0 mm) 3/4" (19,1 mm) : ., w . (15,9 ±6,4 mm) - 2:1/4" DIA. ._1/4':4,4_mm) WRENCH ECESS_ "A" USED FOR FACE OF (57,2 mm) (END 1/2" NPT MODELS) MOUNTING SPRINKLER PLATE '..,/ FITTING 1/8" WRENCH RECESS i 1 -' ( 3,2 mm) (END "B" USED FOR G I 3/4" NPT MODELS) % , FIGURE 7 � � �� W -TYPE 6 SPRINKLER � WRENCH MOUNTING SURFACE - ' WRENCH CLOSURE SERIES 1 -1/4" (31,8 mm) RECESS TY-B 3/4" (19,1 mm) f FIGURE 5 SERIES TY -B RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT .. PUSH WRENCH INTO ENSURE 2 - 7/8" DIA. ENGAGEMENT (73,0 mm) 3/4" (19,1 mm) WITH SPRINKLER 5/8±1/4" WRENCHING AREA (15,9±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) (57,2 mm) FIGURE 8 FACE OF MOUNTING W -TYPE 7 RECESSED SPRINKLER PLATE SPRINKLER WRENCH FITTING 1/8" (3,2 mm) � MOUNTING . SURFACE • CLOSURE SERIES 1- 5/16" (33,3 mm) TY-B 13/16" (20,6 mm) FIGURE 6 SERIES TY -B RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT • Page 6 of 8 TFP151 ing the wax coating. Before wrench Technical Installation tightening the sprinkler, the jaws of the wrench are to be adjusted to just con - Data The Series TY -B Sprinklers must be tact the sprinkler wrench flats. After installed in accordance with the follow- wrench tightening the sprinkler, loosen Approvals ing instructions: the wrench jaws before removing the UL and C -UL Listed. wrench. FM, LPCB, VdS, and NYC Approved. NOTES (Refer to Table A for complete ap- Do not install any bulb type sprinkler if After installation, the sprinkler wrench proval information including corrosion the bulb is cracked or there is a loss of flats and frame arms must be in resistant status.) liquid from the bulb. With the sprinkler spected and the wax coating re- Maximum Working Pressure held horizontally a small air bubble touched (repaired) whenever the coat g should be present. The diameter of the ing has been damaged and bare metal 175 psi (12,1 bar) air bubble is approximately 1/16 inch is exposed. The wax coating on the Discharge Coefficient (1,6 mm) for the 135 °F /57 °C to 3/32 wrench flats can be retouched by gen- K = 2.8 GPM /psi (40,3 LPM /bar inch (2,4 mm) for the 360 °F /182 °C tly applying a heated 1/8 inch diameter K = 5.6 GPM /psi (80,6 LPM /bar temperature ratings. steel rod to the areas of wax that have K = 8.0 GPM /psi (115,2 LPM /bar1I2) been damaged, to smooth it back over A leak tight 1/2 inch NPT sprinkler joint areas where bare metal is exposed. Temperature Ratings should be obtained with a torque of 7 Refer to Table A to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi- NOTES Finishes mum of 21 ft. lbs. (28,5 Nm) of torque Only retouching of the wax coating ap- Sprinkler: Reessed Escutcheon: may be used to install sprinklers with plied to the wrench flats and frame White Coated, Chrome Plated, or 1/2 NPT connections. A ti h4, arms is permitted, and the retouching Brass Plated inch NPT sprinkler joint should be ob- is to be performed only at the time of tained with a torque of 10 to 20 ft.lbs. the initial sprinkler installation. Physical Characteristics (13,4 (40,7 26,8 ) ). A maximum of 30 The steel rod should be heated only to Frame Bronze ft.lbs. Nm oftor torque is to be used the point at which it can begin to melt Button Brass /Copper to install sprinklers with 3/4 NPT con - Sealing Assembly nections. Higher levels of torque may the wax, and appropriate precautions Beryllium Nickel w /Teflont distort the sprinkler inlet and cause need to be taken, when handling the Bulb Glass leakage or impairment of the sprinkler. heated rod, in order to prevent the Compression Screw Bronze installer from being burned. ffi Deflector Copper Do not attempt to make -u for insu- -- pp cient adjustment in the escutcheon If attempts to retouch the wax coating Bushing (K =2.8) Bronze plate by under- or over-tightening the with complete coverage are unsuc- sprinkler. Readjust the position of the cessful, additional wax can be ordered a. sprinkler fitting to suit. in the form of a wax stick (the end of Operation The Series TY -B Pendent and U which is color coded). Only the correct p- color coded wax is to be used, and right Sprinklers must be installed in retouching of wrench flats and frame The glass Bulb contains a fluid which accordance with the following instruc- arms is only permitted at the time of expands when exposed to heat. When tions. initial sprinkler installation. With the the rated temperature is reached, the steel rod heated as previously de- fluid expands sufficiently to shatter the Step 1. Pendent sprinklers are to be glass Bulb, allowing the sprinkler to installed in the pendent position, and scribed, touch the rod to the area re activate and water to flow. upright sprinklers are to be installed in quiring additional wax with the rod an the upright position. gled downward, and then touch the wax stick to the rod approximately Design Step 2. With pipe thread sealant ap- one -half inch away from the area re- plied to the pipe threads, hand tighten quiring retouching. The wax will melt C riteria the sprinkler into the sprinkler fitting. and run down onto the sprinkler. Step 3 Tighten " spinkler into the The Series TY -B Pendent and Upright sprinkler fitting using only the W -Type The Series TY -B Recessed Pendent Sprinklers are intended for fire protec- 6 Sprinkler Wrench (Ref. Figure 7), Sprinklers must be installed in ac- tion systems designed in accordance except that an 8 or 10 inch adjustable cordance with the following instruc- with the standard installation rules rec- Crescent wrench is to be used for wax tions. ognized by the applicable Listing or coated sprinklers. With reference to Step A. After installing the Style 10 or Approval agency (e.g., UL Listing is Figures 1, 2, 3, and 4 the W -Type 7 based on the requirements of NFPA Sprinkler Wrench or the adjustable 40 Mounting Plate, as applicable, over 13, and FM Approval is based on the Crescent wrench, as applicable is to the sprinkler threads and with pipe requirements of FM's Loss Prevention be applied to the wrench flats. thread sealant applied to the pipe Data Sheets). Only the Style 10 or 40 threads, hand tighten the sprinkler into Recessed Escutcheon, as applicable, When installing wax coated sprinklers the sprinkler fitting. is to be used for recessed pendent with the adjustable Crescent wrench, Step B. Tighten the s rinkler into the installations. additional care needs to be exercised p g p sprinkler to prevent damage to the wax coating fitting using only the W-Type on the sprinkler wrench flats or frame 7 Recessed Sprinkler Wrench (Ref. arms and, consequently, exposure of Figure 8). With reference to Figure 3 bare metal to the corrosive environ or 4, the W -Type 7 Recessed Sprinkler ment. The jaws of the wrench should Wrench is to be applied to the sprinkler be opened sufficiently wide to pass wrench flats. over the wrench flats without damag- Step C. After the ceiling has been in- TFP151 Page7of8 ._ __ ._ _. . stalled or the finish coat has been ap- The owner is responsible for the in- plied, slide on the Style 10 or 40 Clo- spection, testing, and maintenance of ___ united sure over the Series TY -B Sprinkler their fire protection system and de- ®,. and push the Closure over the Mount- vices in compliance with this docu- warranty ing Plate until its flange comes in con- ment, as well as with the applicable tact with the ceiling. standards of the National Fire Protec- Products manufactured by Tyco Fire & tion Association (e.g., NFPA 25), in Building Products are warranted solely are and addition to the standards of any other to the original Buyer for ten (10) years authorities having jurisdiction. The in- against defects in material and work - M ►�/� stalling contractor or sprinkler manu- manship when paid for and properly aintenance facturer should be contacted relative installed and maintained under normal The Series TY-B Sprinklers must be to any questions. use and service. This warranty will ex- p pire ten (10) years from date of ship - maintained and serviced in accord- It is recommended that automatic ment by Tyco Fire & Building Products. ance with the following instructions: sprinkler systems be inspected, No warranty is given for products or tested, and maintained by a qualified components manufactured by compa- NOTES Inspection Service in accordance with Hies not affiliated by ownership with Before closing a fire protection system local requirements and /or national Tyco Fire & Building Products or for main control valve for maintenance codes. products and components which have work on the fire protection system that been subject to misuse, improper in- it controls, permission to shut down the stallation, corrosion, or which have not affected fire protection system must be been installed, maintained, modified obtained from the proper authorities or repaired in accordance with applica- and all personnel who may be affected ble Standards of the National Fire Pro - by this action must be notified. tection Association, and /or the stand - Absence of an escutcheon, which is ards of any other Authorities Having used to cover a clearance hole, may Jurisdiction. Materials found by Tyco delay the time to sprinkler operation in Fire & Building Products to be defec- a fire situation. tive shall be either repaired or re- placed, at Tyco Fire & Building Prod - Sprinklers that are found to be leaking ucts' sole option. Tyco Fire & Building or exhibiting visible signs of corrosion Products neither assumes, nor author - must be replaced. izes any person to assume for it, any Automatic sprinklers must never be other obligation in connection with the painted, plated, coated or otherwise sale of products or parts of products. altered after leaving the factory. Modi- Tyco Fire & Building Products shall not fied sprinklers must be replaced. be responsible for sprinkler system de- Sprinklers that have been exposed to sign errors or inaccurate or incomplete corrosive products of combustion, but information supplied by Buyer or have not operated, should be replaced Buyer's representatives. if they cannot be completely cleaned IN NO EVENT SHALL TYCO FIRE & by wiping the sprinkler with a cloth or BUILDING PRODUCTS BE LIABLE, by brushing it with a soft bristle brush. IN CONTRACT, TORT, STRICT LI- Care must be exercised to avoid darn- ABILITY OR UNDER ANY OTHER age to the sprinklers - before, during, LEGAL THEORY, FOR INCIDENTAL, and after installation. Sprinklers darn- INDIRECT, SPECIAL OR CONSE- aged by dropping, striking, wrench QUENTIAL DAMAGES, INCLUDING twist/slippage, or the like, must be re- BUT NOT LIMITED TO LABOR -9;s emplaced ,Also;.replace.anysprinklerthat CHARGES, REGARDLESS OF has a cracked bulb or that has lost WHETHER TYCO FIRE & BUILDING liquid from its bulb. (Ref. Installation PRODUCTS WAS INFORMED Section). ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT Frequent visual inspections are rec- SHALL TYCO FIRE & BUILDING ommended to be initially performed for PRODUCTS' LIABILITY EXCEED AN corrosion resistant coated sprinklers, AMOUNT EQUAL TO THE SALES after the installation has been corn- PRICE. pleted, to verify the integrity of the cor- - - rosion resistant coating. Thereafter, THE FOREGOING WARRANTY IS annual inspections per NFPA 25 MADE IN LIEU OF ANY AND ALL, should suffice; however, instead of in- OTHER WARRANTIES EXPRESS specting from the floor level, a random OR IMPLIED. INCLUDING WARRAN- sampling of close -up visual inspec- TIES OF MERCHANTABILITY AND tions should be made, so as to better FITNESS FOR A PARTICULAR PUR- determine the exact sprinkler condi- POSE, tion and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions 717-2•-r present. "''''_.- Page 8 of 8 TFP151 P/N 57 - XXX - X - XXX • I I SPRINKLER TEMPERATURE MODEUSIN RATING 530 2.8K UPRIGHT (1/2 "NPT) TY1151 1 NATURAL BRASS 135 135 °F /57 °C 531 2.8K PENDENT (1/2 "NPT) TY1251 4 WHITE POLYESTER 155 155 °F /68 °C 570 5.6K UPRIGHT (1/2 "NPT) TY3151 3 WHITE (RAL9010)" 175 175 °F /79 °C 571 5.6K PENDENT (1/2 "NPT) TY3251 9 CHROME PLATED 200 200 °F /93 °C 590 8.0K UPRIGHT (3/4 "NPT) TY4151 7 LEAD COATED 286 286 °F /141 °C 591 8.0K PENDENT (3/4 "NPT) TY4251 6 WAX COATED 360 360 °F /182 °C 286 °F /141 °C MAX. 560 8.0K UPRIGHT (1/2 "NPT) TY4851 8 WAX OVER LEAD 561 8.0K PENDENT (1/2 "NPT) TY4951 286 °F /141 °C MAX. " Eastern Hemisphere sales only. TABLE B PART NUMBER SELECTION SERIES TY -B PENDENT AND UPRIGHT SPRINKLERS Recessed Escutcheon: Wax Sticks: Ordering Specify: Style (specify) Recessed Es- (for retouching wrench damaged Procedure (spec fy) with (specify finish), P/N wax coating) Specify: (Specify color) color coded When placing an order, indicate the full 1/2" (15 mm) Wax Stick for retouching (specify tern - product name. Refer to the Price List Style 10 perature rating) temperature rated Se- for complete listing of Part Numbers. Chrome Plated P/N 56- 701 -9 -010 ries TY -B Sprinklers, P/N (specify). 1/2" (15 mm) Contact your local distributor for avail Style 10 Black for 135 °F P/N 56- 065 -1 -135 ability. White Color Red for 155 °F P/N 56- 065 -1 -155 Coated P/N 56- 701 -4 -010 Yellow for 175 °F P/N 56- 065 -1 -175 1/2" (15 mm) Blue for 200 °F and Sprinkler Assemblies with NPT Style 10 Thread Connections: White RAL9010' P/N 56 -701 -3 -010 286 °F P/N 56- 065 -1 -286 Specify: (Specify Model /SIN), Stand- 1/2 0 NOTES ard Response, (specify K- factor), Brass Plated P/N 56- 701 -2 -010 Each wax stick is suitable for retouch - (specify temperature rating), Series 3/4" (20 mm) ing up to twenty -five sprinklers. TY -B (specify Pendent or Upright) Style 40 Sprinkler with (specify type of finish or Chrome Plated P/N 56- 700 -9 -010 The wax used for 286 °F sprinklers is coating), P/N (specify from Table B). 3/4" (20 mm) the same as for200°F sprinklers, and, Style 40 therefore, the 286 °F sprinkler is limited White Color Coated P/N 56- 700 -4 -010 to the same maximum ceiling tempera - 3/4" (20 mm) ture as the 200 °F sprinkler (i.e., Style 40 White RAL9010" P/N 56- 700 -3 -010 150 °F . 3/4" (20 mm) Style 40 Brass Plated P/N 56- 700 -2 -010 • Eastern Hemisphere sales only. Sprinkler Wrench: • Specify: W -Type 6 Sprinkler Wrench, P/N 56- 000 -6 -387. • Specify: W -Type 7 Sprinkler Wrench, P/N 56- 850 -4 -001. • TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446