Correspondence September 21, 2005 CITY OF TIGARD
Jeffery Strockbine OREGON
Olympic Associates Company
701 Dexter Avenue North, Suite # 301
Seattle, WA 98109
Project Information
Building Permit: MEC2005 -00555 Occupancy Type: B
Tenant Name: Washignton Square Starbucks Construction Type: IIB
Address: 9359 SW Washington Square Road Occupant Load: 43
Area: 1,572 Sq Ft Stories: 1
The plan review was performed under the State of Oregon Mechanical Specialty Code
(OMSC) 2004 edition; and the State of Oregon Fire Code (OFC) 2004 edition. The submitted
plans are approved subject to the following.
1. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning
Contractors National Association, Inc. (SMACNA)
2. Equipment and appliances regulated by this code requiring electrical connections
shall have a positive means of disconnect in accordance with the Electrical Code.
301.7 OMSC
3. Appliances serving different areas of a building other than where they are installed
shall be permanently marked in an approved manner that uniquely identifies the
appliance and the area it serves. 304.11 OMSC
4. Appliances shall be accessible for inspection, service, repair or replacement without
removal of permanent construction. 306.1 OMSC
5. Manufacturer's installation instructions shall be available on the jobsite at the time of
inspection. 304.1 OMSC
6. Condensate from cooling coils or evaporators shall be collected and discharged to an
approved plumbing fixture or disposal area. 307.2 OMSC
7. Smoke detectors shall be installed in return air systems with a design capacity greater
than 2000 cfm. Upon activation, the smoke detector shall shut down the air
distribution system. Smoke detectors shall be connected to a fire alarm system and
shall activate an audible and visible alarm at a constantly attended location. 606.2,
606.4 & 606.4.1 OMSC
13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772
8. Appliances installed on roofs or elevated structures exceeding 16 feet in height shall
be provided with a permanent means of access grade or floor level. 306.5 OMSC
Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall
be maintained on the jobsite. The plans shall be available to the Building Division inspectors
throughout all phases of construction. 106.4.2 OSSC
Premises Identification: Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or road
fronting the property.
When submitting revised drawings or additional information, please attach a copy of the
enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of
Tigard in tracking and process'il, 1e documents.
R te"
:'. :alp
Senior Examiner
09- 21 -'05 10:53 FROM- T -101 P002/002 F -169
3 /" HILTI HDI DROP -IN ANCHOR
IN CONCRETE FLOOR DECK
TYPICAL EACH THREADED ROD
III SPRING ISOLATOR,EACH
THREADED ROD INSTALL
10 PER MFG. SPECIFICATIONS
3 / 8 " THREADED ROD HANGER (4)
PLACES BOLT TO AHU PER MFG.
SPECIFICATIONS
d 45 12 G:Wu IRE OF AS 45 SHOWN DEGREES 8
_ PLAS TO BE ATTACHED AT
M MIN.
45° MAX
OF (4) TIGHT TURNS IN 1Y2"
45 ' � 5 AT BOTH ENDS OF ALL BRACING
° WIRE
45° AHU SEE MECHANICAL FOR
DIMENSIONS
45° . 45°
its
1 AIR HANDLER UNIT SUPPORT
1 /2a = 1 , A a
- (,
r - -
DATE: 9/21/2005 PAGE; 1 OF 1 r r ,
DRAWN: C. TERAO SHEET SUPPL E MENTAL DETAILS
•
CHECKED: REFFRENCED . r17
STARBUCKS WASHINGTON SQUARE III oL►�P(S
REVISION • _ - A150(IATU
JOB NO. 2005086 NUMBER: c o 4 r A i r
,a Arieaoacermaq 4cm mount ar Doha mm°o owner „° Nc wor TO a •m « mom a. M ow incur mo m Wo:oB,mI o/ wins ,SIDZOCI �6YXI
•