Correspondence RECEIVED • C S D • JUL 151999 CORPORATE SPACE DESIGN, INC INTERIOR ARCHITECTURE • ARCIIITECTURE • FACILITIES CONSULTING COMMUNITY DEVELOPMENT PRINCIPALS SUSAN INGRIM SABINE O'I IALLORAN DANIEL INGRIM July 13, 1999 Mr Robert Poskin, CBO SENIOR PLANS EXAMINER City of Tigard 12125 SW Hall Blvd Tigard, OR. 97223 RE: BUILDING PLAN REVIEW SUBJ: COAST SERVICES, INC. 10505 SW Tigard Street PC #: 6 -36c BUP#: 1999 -00253 y Submittal documents for the above referenced project have been reviewed for conformance with the applicable 1998 Oregon Specialty Codes and other applicable codes and standards The following comments were noted from the original Robert Poskin letter dated June 23, 1999 Please find below _ original comment references with architectural response ' ACCESSIBLITIY: ' [City of Tigard Comment] C 1. Under the po,visions of OSSC, Section 1113, accessible parking is the first item required under the 0 1 2 vision. Provide a site plan showing accessible parking compliance Architectural Response! Please refer to newly developed site drmving AO• for parkrmation. Parking Requirements _ Office 1 space for ever, 50s f -- Waarehouse 1 space for every,2000 s f H'C Parking 1 space for every 25 required parking spaces lace Assessment Proposed ice Use Space 3129 s f ProposdaWarehouse Space. 2630 s f -�` Parking Calculations. i'— Office Space of 3129 s f divided by 250 s.f. = 12 5 or 13 spaces Warehouse Space of-2630 s f Divided by 2000 s f = l 3 or 2 spaces ..., .....--Total parking spaces required: 15 spaces Total existing parking spaces: 38 spaces Di et quired H.C. Parking space per section OSSC, Section 1113: Diet Coast Services Inc 07/14/99 City of Tigard Plan Review Comments + Response 15055 SW SEQUOIA PARKWAY SUITE 170 • PORTLAND, OREGON 97224 • (503) 624 -7796 • FAX (503) 624 -0635 • E -MAIL csd I @spryncl corn • C S D • Coast Services proposes to maintain the existing 38 site parking places, and to add one new handicapped parking space at the building entry. [City of Tigard Common] 2. Stair -ways shall comply with OSSC, Section 1109 8 Provide details [Architectural Response] The stairways indicated on the drawings r r, a existing stairways. Both stairways meet the requirements of Section 1006 and 509 and the provisions of 1109.8. Note stair 400 to be fully enclosed 1 hour. Refer to sheet A9 for stair 400 plan and sedional/eleva Lion. Note new fully compliant handrails installed pursuant ADAAG Figure / Stairway 204 is compliant. Per OSSC, Section 1109.8. Note: No new stainvat•s are proposed. Access to the occupieable mezzanine level is by way of pre- existing stairs. ENERGY COMPLIANCE: [City of Tigard ConmientJ 1 Provide lighting, to / adss on Forms 5a through 5c [Architectural Response] Please find under separate cover attached :ereto energy calculations prepared by R.C. Costello Electrical Contracting. Forms 5a throe 5c are prepared [City of Tigard Comment] 2. Glass shall comply with ie energy code Provide Details [Architectural Respons There is no new erior glass proposed within this renovation. The existing exterior glazing system is double paned lo v `e' glass set within an aluminum: frame system. FIRE AND LIFE SAFETY: [City of Tigard Comment] 1 Conference Room #200 exits through two intervening rooms The occupant load factor exceeds 10, therefore. OSSC. Section 1004 2 2 Exception 3 does not apply. Provide details. [Architectural Response] V Door 200B has been added to Conference Room #200. See reference on Sheet A3 Plan and Sheet AO for schedule values. Note door 200B is to be a rated assembly. Assembly to have 20- minute door rating, rated frame, smokes gasketing, and a closure. 2 Coast Services Inc 07/14/99 City of Tigard Plan Review Comments + Response 15055 SW SEQUOIA PARKWAY SUITE 170 • PORTLAND. OREGON 97224 • (503) 624 -7796 • FAX (503) 624 -0635 • E -MAIL csd I@sprynet con) 1 r • C S D • [City of Tigard Comment] 2 Storage under the exit stair enclosure in not allowed OSSC, Section 1005.3.3.6 Provide details [Architectural Response] Reference Sheet A3 — Note area below stair #400 has been fully enclosed with 1 - hour construction. 0 [City of Tigard Comment] 3. 20 minutes doors shall be rated in accordance with OSSC, Section 1004 3 4 3 2 1 Provide details [Architectural Response] Pursuant OSSC, Section 1104 4 3.4 2.1. All rated assembles comply. All such assemblies are protected by tight fitting smoke — and draft- controlled having a fire protection rating of not less than 20 minutes when tested in accordance with UBC Standard 7 -2, Part II. The doors and frame shall bear an approved label or other identification showing the rating thereof, followed by the letter "5", the name of the manufacturer and the identification of the service conduction the inspection of materials and workmanship at the factory during fabrication and assembly. Doors shall be maintained self-closing. Draft- control assemblies shall be provided with a gasket installed so as to provide a seal where the door meets the stop on both sides and across the top. [City of Tigard Comment] 4 It appears that the second level exceeds the 1/3 area for a mezzanine, therefore, the separation of the required 2 exits must be 'h the diagonal, which is 28 feet The exits as shown do not comply OSSC, Section 1004 2 5 [Architectural Response] Building Square Footage Summary: Total Main Floor Footage: Office 1925 s f Warehouse: 2630 s f Total: 4555 s.f. 4555 s.f. Divided by 1/3 = 1503 s.f. of code compliant mezzanine available Mezzanine Floor Footage Summary: 2 " Floor Occupied Mezzanine 1204 s.f Mezzanine Over Conference Room 250 s f Total Mezzanine Space Proposed: 1454 s.f. Allowable 1503 s f Per OSSC, Section 1004.2.5. Proposed 1454 s f The total proposed mezzanine space is within the allowable, therefore the existing stairwells are within code compliant parameters. 3 Coast Services Inc 07/14/99 City of Tigard Plan Review Comments + Response • 15055 SW SEQUOIA PARKWAY SUITE 170 • PORTLAND. OREGON •.(503) 624 -7796 • FAX (503) 624 -0635 • E -MAIL cod I @sprynct corn S t • • • C S D • MECHANICAL: [City of Tigard Comment] 1. Depending on the size of the proposed equipment additions, I would recommend you liaison with your contractor the requirements of OMSC, Section 304.2 (Architectural Response] The General Contractor and his HVAC sub - contractor have been informed of this suggestion. HVAC is bidder designed and will be submitted under separate cover, separate permit DEFERRED SUBMITTALS: [City of Tigard Comment] 1. Mechanical, plumbing and electrical require separate application, plan and permits (Architectural Response] Mechanical, plumbing and electrical trades will provide the City under separate cover, full and complete permit applications. ENVIRONMENTAL AIR: [City of Tigard Comment] 1 Provide details on how you will comply with OSSC, Chapter 12 [Architectural Response] Building occupants shall be provided with light and ventilation as set forth in OSSC, Chapter 12, or the principles of environmental technology specified in ASHRAE Standard 62 -1989 including ASHRAE Addendum 62a -1990, Ventilation for Acceptable Indoor Air Quality, for occupancy ventilation. HVAC bidder designed documentation will address mechanical air, air quality, and occupancy ventilation. HVAC design and plan documents will be submitted for permitting under deferred submission. Please find enclosed herein three copies of the revised submittal documents to include this letter indicating the architectural response to the above comments. It is felt that all conditions of permit have been met, and the applicant respectfully requests the issuance of a permit for construction at your earliest convenience. Should you have additional comments, questions, and or clarification to the above referenced comment responses please do not hesitate to notify me directly. Thank you for your time and consideration in this matt; Respectfully submitted, ' j i __ i � :1 'grim RA/IFMA ng Principal /CSD. Inc Cc Don Schaefer — Coast Services Inc a 639-9045 Roy Whitaker — Al Stearns Construction Co @ 257 -6366 4 Coast Services Inc 07/14/99 City of Tigard Plan Review Comments + Response 15055 SW SEQUOIA PARKWAY SUITE 170 • PORTLAND, OREGON 97224 • (503) 624 -7796 • FAX (503) 624 -0635 • E -MAIL csdI ©sprynet corn r 1 June 23, 1999 CITY OF T1 Corporate Space Design, Inc. OREG 15055 SW Sequoia Parkway Portland, OR 97224 RE: Coast Services, Inc. Building Plan Review 10505 SW Tigard PC #: 6 -36c BUP #: 1999 -00253 Submittal documents for the above referenced project have been reviewed for conformance with the applicable 1998 Oregon Specialty Codes and other applicable codes and standards. The following comments are noted: (:ACCESSIBILITY , :._ a , t �..' 1. Under the provisions of OSSC, Section 1113, accessible parking is the first item required under the 25% provision. Provide a site plan showing accessible parking compliance. 2. • Stairways shall comply with OSSC, Section 1109.8. Provide details. • ENERGY COMPLIANCE _ 1. Provide lighting loads on Forms 5a through 5c. 2. Glass shall comply with the energy code. Provide details. FIRE AND LIFE SAFETY .. ° 1. Conference Room #200 exits through two intervening rooms. The occupant load factor exceeds 10, therefore, OSSC, Section 1004.2.2 Exception 3 does not apply. Provide details. 2. Storage under the exit stair enclosure is not allowed. OSSC, Section 1005.3.3.6. Provide details. 3. 20 minutes doors shall be rated in accordance with OSSC, Section 1004.3.4.3.2.1. Provide details. 4. It appears the second level exceeds the 1/3 area for a mezzanine, therefore, the separation of the required 2 exits must be % the diagonal, which is 28 feet. The exits as shown do not comply. OSSC, Section 1004.2.5. (MECHANICAL' �;' :�� _ez. _ `) 1. Depending on the size of the proposed equipment additions, I would recommend you liason with your contractor the requirements of OMSC, Section 304.2 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 Coast Services, Inc. Building Plan Review PC #: 6 -36c BUP #: 1999 -00253 Page #2 (DEFERRED SUBMITTAL' Si `' 1. Mechanical, plumbing and electrical require separate applications, plans and permits. �ENV 1. Provide details on how you will comply with OSSC, Chapter 12. Please submit three copies of revised submittal documents and a letter indicating your response to the above comments for review. Please call me at (503) 639 -4171 if you have any questions. Sincerely, j w Ro ert Poskin, CBO SENIOR PLANS EXAMINER i \bldglprmsyskbup99253 doc