Loading...
Correspondence September 29, 2006 CITY OF TIGARD OREGON T&L Communication Ross Brshaw PO Box 87378 Vancouver, WA 98661 RE: FIRE ALARM SYSTEM HORN STROBES— ADDITION Project Information Building Permit BUP2006 -00459 Construction Type: 3-B Tenant Name: Oregon Human Development Occupancy Type: B Address: 9600 SW Oak St Hazard: LIGHT Sprinklers: YES The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition the Oregon Fire Code 2004 edition and NFPA 72. The submitted plans are approved subject to the following. General requirements A key box for building access may be required. Please contact the local Fire Marshal's Office for an order form and instructions regarding installation and placement. (OFC 506) TESTING — NFPA 72 Chapter 10, OFC 901.5, 903.5 1. Upon completion of the installation, a satisfactory test of the entire system shall be made in the presence of the building code official. All functions of the system or alteration shall be tested. 2. The permittee shall provide written certification to the building code official that the system has been installed in accordance with the approved plans and specifications. A copy of the completed form shall be maintained on the premises and made available to the Fire Chief. POWER- NFPA 72 section 4.4.1.2, 4.4.1.4.2, 4.4.7.3, OFC 907.5 4. Connections to the light and power service shall be on a dedicated branch circuit. The circuit and connections shall be mechanically protected. The circuit disconnecting means shall have a red mares, shall be accessible only to authorized personnel and shall be clearly and permanently marked "FIRE ALARM CIRCUIT" . 5. All power supplies shall be installed in conformity with NFPA 70. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 6. All primary and secondary power supplies shall be monitored for the presence of voltage at the point of connection to the system. Failure of either supply shall result in a trouble signal in accordance with 4.4.3.5. The trouble signal also shall be visually and audibly indicated at the protected premises. VISUAL ALARMS — NFPA 72 - 5.14.5, 7.5.4 7. When required; Visual alarms shall be located not less than 80 inches and not more than 96 inches above floor level. When a low ceiling exists, the visual alarm shall be mounted within the dimensions stated above and at least 6 inches below the ceiling. No place in a room shall be more than 50 feet from a visual signal. MANUAL ALARM - 1109.2.3.5, 1109.23.6 OSSC 8. Manual Fire Alarm activation devices when installed shall be mounted in the following reach ranges: • Forward Reach - 15 inches to 48 inches above the floor. • Side Reach — 9 inches to 54 inches above the floor. ALARM SIGNALS — OFC 903.4 9. Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote supervising station or proprietary supervising station as defined in NFPA 72 or, when approved by the fire code official, shall sound an audible signal at a constantly attended location. Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfu Val Henzel, Senior Plans Examiner