Loading...
Correspondence ... • City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 November 3, 2008 S • RE: FIRE SPRINKLER TI T I GARD Project Information Building Permit: BUP2008 -00358 Construction Type: 1 -B Tenant Name: Plaza West Occupancy Type: B Address: 9600 SW Oak St. Occupant Load: NA Area: NA Stories: 5 The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2007 edition; National Fire Protection Association, Standard 13 (NFPA 13)2002 edition and the State of Oregon Fire Code (OFC) 2007 edition. Please respond to the following conditions; 1) Please provide current hydrant flow test (within 5 years). 2) Show equivalent pipe length for FlexHead sprinkler connectors in hydraulic calculations. 3) Please provide hydraulic calculations for anticipated most remote area for sizing of standpipe. When responding, provide an itemized letter stating in what way each numbered issue has been addressed in the revision. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectf ly, I fk,4 Dan Nelson, Senior Plans Examiner (503)718 -2436 dann @tigard -or.gov Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772