Loading...
Correspondence City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 n December 21, 2006 TI GARD . Shepler Refrigeration, Inc John Makris 3961 N Williams Ave Portland, OR 97227 RE: ROOF -TOP CONDENSER AND GLYCOL COOLER Project Information Building Permit MEC2006 -00589 Construction Type: uk Tenant Name: Fanno Creek Brew Pub Occupancy Type: A2 Address: 12562 SW Main Occupant Load: na The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2004 edition. The submitted plans are approved subject to the following. 1. The building or structure shall not be weakened by the installation of mechanical systems. Where floors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with the Building Code. The cutting, notching and boring of framing members shall comply with OMSC 302 Sections 302.3.1 through 302.5.3 2. Every refrigerant system shall be tested and proved tight after complete installation, and before operation. Tests shall include both the high- and low- pressure sides of each system at not less than the lower of the design pressures or the setting of the pressure relief device(s). The design pressures for testing shall be those listed on the condensing unit, compressor or compressor unit name - plate, as required by ASHRAE 15. 1108.1 OMSC 3. Refrigeration Installer Certification All persons engaged in brazing or welding related to the installation, alteration or repair of refrigeration piping systems not regulated by the Oregon Boiler and Pressure Vessel Program under OAR Chapter 918, Division 225, shall be certified in accordance with the requirements of this rule. Oregon Administrative RuIe 91844o -oo1s 4. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer's installation instructions and this code. Manufacturer's installation instructions shall be available on the job site at the time of inspection. OMSC 304.1 5. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 6. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC - 7. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. 304.10 OMSC 8. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC 9. Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC Mercury Thermostats. The State of Oregon prohibits the installation of thermostats that contain mercury in commercial and residential buildings. "In accordance with ORS 455.355, the disposal of thermostats that contain mercury shall be in accordance with programs established by thermostat manufacturers, their representative or distributor, or by delivery to sites that will ensure that the mercury does not become part of the solid waste stream or wastewater." Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectful) Val Henzel, Senior Plans Examiner • City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 December 15, 2006 OFFICE COPY r TIGARD Cameron's Installations Scott Cameron 22170 SW Martinazzi Tualatin, OR 97062 RE: TYPE 1 HOOD /MAKEUP AIR Project Information Building Permit: MEC2006 -00589 Construction Type: 5B Tenant Name: Fanno Creek Brew Pub Occupancy Type: A2 Address: 12562 SW Main Occupant Load: Area: sq ft Stories: 2 The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2004 edition. The submitted plans are approved subject to the following. 1. Provide automatic fire suppression systems for to type 1 hood prior to final inspection. "Automatic fire suppression systems, including pre - engineered and engineered dry and wet chemical fire suppression systems shall be listed and labeled for specific use as protection for commercial cooking operations and shall be installed in accordance with Section 304.1." OMSC 509.2 2. Type I hoods shall be secured in place by non- combustible supports. All hood supports shall be adequate for the applied load of the hood, the unsupported ductwork, the effluent loading, and the possible weight of personnel working in or on the hood. 507.6 OMSC 3. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches. This clearance may be reduced to 3 inches, provided the combustible material is protected with materials as specified for one -hour fire- resistive construction on the hood side. Hoods less than 12 inches from the ceiling or wall shall be flashed solidly with materials of the thickness specified in Section 508.2 or materials conforming to one -hour fire- resistive construction. 507.9 OMSC 4. Makeup air shall be supplied during the operation of commercial kitchen exhaust systems. The amount of makeup air supplied shall be approximately equal to the amount of exhaust air. For mechanical makeup air systems. the exhaust and makeup air systems shall be electrically interlocked to insure that makeup air is provided whenever the exhaust system is in operation. Makeup air intake opening locations shall comply with Sections 401.5 and 401.5.1. 508.1 OMSC 5. The temperature differential between makeup air and the air in the conditioned space shall not exceed Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 I . 10oF (6oC). Exceptions: 1. Makeup air that is part of the air- conditioning system. 2. Makeup air that does not decrease the comfort conditions of the occupied space. 508.1.1 OMSC 6. Manufacturers of compensating hoods shall provide a label indicating minimum exhaust flow and /or maximum makeup airflow that provides capture and containment of the exhaust effluent. 508.2 OMSC 7. Duct- to- exhaust fan connections shall be flanged and gasketed at the base of the fan for vertical discharge fans. OMSC 506.3.2.3 8. Duct systems serving a Type I hood shall be constructed and installed so that grease cannot collect in any portion thereof, and the system shall slope not less than one - fourth unit vertical in 12 units horizontal (2- percent slope) toward the hood or toward an approved grease reservoir. OMSC 506.3.7 9. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer's installation instructions and this code. Manufacturer's installation instructions shall be available on the job site at the time of inspection. OMSC 304.1 10. The building or structure shall not be weakened by the installation of mechanical systems. Where floors, walls, ceilings or any other portion of the building or structure are required to be altered or replaced in the process of installing or repairing any system, the building or structure shall be left in a safe structural condition in accordance with the Building Code. The cutting, notching and boring of framing members shall comply with OMSC 302 Sections 302.3.1 through 302.5.3. 11. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC 12. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfull cp f 0" Val enzel, Senior Plans Examiner ti City of Tigard, Oregon • 13125 SW Hall Blvd. • Tigard, OR 97223 1, • December 11, 2006 TIGARD Cameron's Installations Scott Cameron 22170 SW Martinazzi Tualatin, OR 97062 RE: TYPE I HOOD /MAKEUP MR — REVIEW #1 Project Information Building Permit. MEC2006 -00589 Construction Type: Tenant Name: Fanno Creek Brew Pub Occupancy Type: Address: 12562 SW Main Occupant Load: Area sq ft Stories: The plan review is performed under the State of Oregon Mechanical Specialty Code (OMSC) 2004 edition. The following information is required in order to complete the review. 1. This permit can not be approved without a change of use permit issued per OMSC 110 CERTIFICATE OF OCCUPANCY No building or structure shall be used or occupied, and no change in the existing occupancy classification of a building or structure or portion thereof shall be made until the building official has issued a certificate of occupancy therefore as provided herein. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction. 2. Please provide equipment information per OMSC 106.3. 3. Please provide fire - restive rated material information per OMSC 507.9 4. A permit will be required for the fire suppression system for the type one hood prior to final inspection approval of the hood. 5. Please provide details showing equipment bracing information like straps, rods, screw sizes, etc. along with appliance installation information. OMSC 106.3.1 Please provide an item -by -item response Phone: 503.639.4171 • Fax: 503.684.7297 • www.tigard- or.gov • TTY Relay: 503.684.2772 When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respectfully, ( ‘.1//V7/ . Val Henzel, 'or Plans Eicaminer •