Loading...
Specifications • s PATRIOT FIRE PROTECTION, INC. 4708 NE MINNEHAHA STREET 3 VANCOUVER,WA 98661 00 J RECEI FEB 0 7 2005 HYDRAULIC CALCULATIONS CiTy o r1�AR 8U1CD1NG DI VISI O N FOR CROWN CARPET 12230 SW MAIN STREET TIGARD, OREGON FILE: CROWN CARPET.SDF DATE: 2/3/2005 - DESIGN DATA- ' OCCUPANCY CLASSIFICATION: GROUP A PLASTICS DENSITY: .6 GPM AREA OF APPLICATION: 2000 SQ. FT. COVERAGE PER SPRINKLER: 100 SQ. FT. MAXIMUM NUMBER OF SPRINKLERS CALCULATED: 21 SPRINKLERS TOTAL SPRINKLER WATER FLOW REQUIRED: 1305.3 GPM TOTAL WATER REQUIRED (including hose): 1805.3 GPM FLOW AND PRESSURE (@ BOR): 1305.3 GPM @ 69.5 PSI SPRINKLER ORIFICE SIZE: 3/4 INCH NAME OF CONTRACTOR: PATRIOT FIRE PROTECTION DESIGN /LAYOUT BY: JEFF COLLINS AUTHORITY HAVING JURISDICTION: CITY OF TIGARD CONTRACTOR CERTIFICATION NUMBER: 70822 CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 3808132120) HRS SYSTEMS, INC. ATLANTA, GA SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1 DATE: 2/3/2005 C: \PROGRAM FILES \HASS76 \CROWN CARPET.SDF JOB TITLE: Crown Carpet - .6/2000 sq. ft. - 14.0k WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS.- PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) CITY 98.0 86.0 2169.0 89.5 1805.3 80.0 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 1805.3 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 500.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 1305.3 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) CITY 0.0 SOURCE 80.0 1305.3 101 22.7 K =14.00 18.8 60.7 102 22.7 K =14.00 18.2 59.7 103 22.7 K =14.00 18.1 59.5 104 22.7 K =14.00 ' 18.1 59.6 105 22.7 K =14.00 18.6 60.4 106 22.7 K =14.00 20.0 62.6 107 23.2 K =14.00 18.7 60.6 108 23.2 K =14.00 18.1 59.6 109 23.2 K =14.00 18.0 59.4 110 23.2 K =14.00 18.1 59.5 111 23.2 K =14.00 18.6 60.3 112 23.2 K =14.00 19.9 62.5 113 23.7 K =14.00 19.0 61.1 114 23.7 K =14.00 18.4 60.0 115 23.7 K =14.00 18.3 59.8 116 23.7 K =14.00 18.3 59.9 117 23.7 K =14.00 18.8 60.7 118 23.7 K =14.00 20.1 62.8 119 24.2 K =14.00 26.4 71.9 120 24.2 K =14.00 26.5 72.0 121 24.2 K =14.00 27.1 72.9 Cl 22.0 - - - - 25.1 - - - C2 22.0 - - - - 25.4 - - - C3 22.0 - - - - 26.3 - - - C4 22.0 - - - - 28.3 - - - 05 22.0 - - - - 30.6 - - - - C6 22.0 - - - - 32.0 - - - C7 22.0 - - - - 32.6 - - - C8 22.0 - - - - 32.8 - - - C11 22.0 - - - - 56.0 - - - C12 22.0 - - - - 56.1 - - - C13 22.0 - - - - 56.1 - - - SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 2/3/2005 C: \PROGRAM FILES \HASS76 \CROWN CARPET.SDF JOB TITLE: Crown Carpet - .6/2000 sq. ft. - 14.0k NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) C14 22.0 - - - - 56.2 - - - C15 22.0 - - - - 56.4 - - - C16 22.0 - - - - 56.7 - - - C17 22.0 - - - - 57.0 - - - C18 22.0 - - - - 57.5 - - - R1 22.7 - - - - 21.7 - - - R2 23.2 - - - - 21.6 - - - R3 23.7 - - - - 22.0 - - - R4 24.2 - - - - 26.9 - - - R5 24.2 - - - - 32.2 - - - R6 23.7 - -. - - 33.6 - - - R7 23.2 - - - - 34.4 - - - R8 22.7 - - - - 34.8 - - - R11 22.7 - - - - 52.0 - - - R12 23.2 - - - - 51.7 - - - R13 23.7 - - - - 51.4 - - - R14 24.2 - - - - 52.5 - - - R15 24.2 - - - - 53.7 - - - R16 23.7 - - - - 54.3 - - - R17 23.2 - - - - 54.9 - - - R18 22.7 - - - - 55.6 - - - TR 22.7 - - - - 58.1 - - - BR 2.0 - - - - 69.5 - - - BF1 2.0 - - - - 69.5 - - - BF2 2.0 - - - - 79.5 - - - UG1 -3.0 - - - - 73.5 - - - • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 2/3/2005 C: \PROGRAM FILES \HASS76 \CROWN CARPET.SDF JOB TITLE: Crown Carpet - .6/2000 sq. ft. - 14.0k PIPE DATA PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 1 154.8 2.157 PL 16.83 PF 2.9 R1 22.7 0.0 21.7 0.0 13.6 120 FTG - - -- PE 0.0 101 22.7 14.0 18.8 60.7 0.171 TL 16.83 PV Pipe: 2 94.1 2.157 PL 9.00 PF 0.6 101 22.7 14.0 18.8 60.7 8.3 120 FTG - - -- PE 0.0 102 22.7 14.0 18.2 59.7 0.068 TL 9.00 PV Pipe: 3 34.4 2.157 PL 9.00 PF 0.1 102 22.7 14.0 18.2 59.7 3.0 120 FTG - - -- PE 0.0 103 22.7 14.0 18.1 59.5 0.011 TL 9.00 PV Pipe: 4 -25.1 2.157 PL 9.00 PF 0.1 ' 103 22.7 14.0 18.1 59.5 2.2 120 FTG - - -- PE 0.0 104 22.7 14.0 18.1 59.6 0.006 TL 9.00 PV Pipe: 5 -84.7 2.157 PL 9.00 PF 0.5 104 22.7 14.0 18.1 59.6 7.4 120 FTG - - -- PE 0.0 105 22.7 14.0 18.6 60.4 0.056 TL 9.00 PV Pipe: 6 -145.1 2.157 PL 9.00 PF 1.4 105 22.7 14.0 18.6 60.4 12.7 120 FTG - - -- PE 0.0 106 22.7 14.0 20.0 62.6 0.152 TL 9.00 PV Pipe: 7 -207.7 2.157 PL 102.50 PF 32.0 106 22.7 14.0 20.0 62.6 18.2 120 FTG E PE 0.0 R11 22.7 0.0 52.0 0.0 0.295 TL 108.50 PV Pipe: 8 -207.7 2.157 PL 0.67 PF 3.7 R11 22.7 0.0 52.0 0.0 18.2 120 FTG T PE 0.3 C11 22.0 0.0 56.0 0.0 0.295 TL 12.67 PV Pipe: 9 154.9 2.157 PL 16.83 PF 2.9 R2 23.2 0.0 21.6 0.0 13.6 120 FTG - - -- PE 0.0 107 23.2 14.0 18.7 60.6 0.172 TL 16.83 PV Pipe: 10 94.3 2.157 PL 9.00 PF 0.6 107 23.2 14.0 18.7 60.6 8.3 120 FTG - - -- PE 0.0 108 23.2 14.0 18.1 59.6 0.069 TL 9.00 PV Pipe: 11 34.8 2.157 PL 9.00 PF 0.1 108 23.2 14.0 18.1 59.6 3.1 120 FTG - - -- PE 0.0 109 23.2 14.0 18.0 59.4 0.011 TL 9.00 PV Pipe: 12 -24.6 2.157 PL 9.00 PF 0.1 109 23.2 14.0 18.0 59.4 2.2 120 FTG - - -- PE 0.0 ' 110 23.2 14.0 18.1 59.5 0.006 TL 9.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 2/3/2005 C: \PROGRAM FILES \HASS76 \CROWN CARPET.SDF JOB TITLE: Crown Carpet - .6/2000 sq. ft. - 14.0k PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. ' END. ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) ,,Pipe: 13 -84.1 2.157 PL 9.00 PF 0.5 110 23.2 14.0 18.1 59.5 7.4 120 FTG - - -- PE . 0.0 111 23.2 14.0 18.6 60.3 0.055 TL 9.00 PV Pipe: 14 -144.4 2.157 PL 9.00 PF ' 1.4 111 23.2 14.0 18.6 60.3 12.7 120 FTG - - -- PE 0.0 112 23.2 14.0 19.9 62.5 0.151 TL 9.00 PV Pipe: 15 -206.9 2.157 PL 102.50 PF 31.8 112 23.2 14.0 19.9 62.5 18.2 120 FTG E _PE. 0.0 R12 23.2 0.0 51.7 0.0 0.293 TL 108.50 PV Pipe: 16 -206.9 2.157 PL 1.17 PF 3.9 R12 23.2 0.0 51.7 0.0 18.2 120 FTG T PE 0.5 . C12 2 0.0 56.1 0. . 0.293 TL 13.17 PV Pipe: 17 158.8 2.157 PL 16.83 PF 3.0 R3 23.7 0.0 22.0 0.0 13.9 120 FTG - - -- PE 0.0 113 23.7 14.0 19.0 61.1 0.180 TL 16.83 PV Pipe: 18 97.8 2.157 PL 9.00 PF 0.7 113 23.7 14.0 19.0 61.1 8.6 120 FTG - - -- PE 0.0 114 23.7. 14.0 18.4 60.0 0.073 TL 9.0,0 PV Pipe: 19 37.8 2.157 PL 9.00 PF 0.1 114 23.7 14.0 18.4 60.0 3.3 120 FTG - - -- PE 0.0 115 23.7 14.0 18.3 59. 0.013 TL 9.00 PV Pipe: 20 -22.0 2.157 PL 9.00 PF 0.0 115 23.7 .14.0 18.3 59.8 1.9 120 FTG - - -- PE 0.0 116 23.7 14.0 18.3 59.9' 0.005 TL -9.00 PV Pipe: 21 -81.9 2.157 PL 9.00 PF 0.5 116 23.7 14.0 18.3 59.9 7.2 120 FTG - - -- PE 0.0 117 23.7 14.0 18.8 60.7 0.053 TL 9.00 PV Pipe: 22 -142.6 2.157 PL 9.00 PF 1.3 117 23.7 14.0 18.8 60.7 12.5 120 FTG - - -- PE 0.0 118 23.7 14.0 20.1 62.8 0.147 TL 9.00 PV Pipe: 23 -205.3 2.157 PL 102.50 PF 31.4 118 23.7 14.0 20.1 18.0 -- 120 FTG . E PE 0.0 R13 23.7 0.0 51.4 0.0 0.289 TL 108.50 PV Pipe: 24 -205.3 2.157 PL 1.67 PF 3.9 R13 23.7 0.0 51.4 0.0 18.0 120 FTG T PE 0.7 C13 22.0 0.0 56.1 0.0 0.289 TL 13.67 PV Pipe: 25 48.3 2.157 PL 25.83 PF 0.5 R4 24.2 0.0 26.9 0.0 4.2 120 FTG - - -- PE 0.0 119 ' 24.2 14.0 26.4 71.9 0.020 TL 25.83 PV • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 2/3/2005 C: \PROGRAM FILES \HASS76 \CROWN CARPET.SDF JOB TITLE: Crown Carpet - .6/2000 sq. ft. - 14.0k PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 26 -23.7 2.157 PL 9.00 PF 0.0 119 24.2 14.0 26.4 71.9 2.1 120 FTG - - -- PE 0.0 120 24.2 14.0 26.5 72.0 0.005 TL 9.00 PV Pipe: 27 -95.7 2.157 PL 9.00 PF 0.6 120 24.2 14.0 26.5 72.0 8.4 120 FTG - - -- PE 0.0 121 24.2 14.0 27.1 72.9 0.070 TL 9.00 PV Pipe: 28 -168.6 2.157 PL 120.50 PF 25.4 121 24.2 14.0 27.1 72.9 14.8 120 FTG E PE 0.0 R14 24.2 0.0 52.5 0.0 0.201 TL 126.50 PV Pipe: 29 -168.6 2.157 PL 2.17 PF 2.8 R14 24.2 0.0 52.5 0.0 14.8 120 FTG T PE 0.9 C14 22.0 0.0 56.2 0.0 0.201 TL 14.17 PV • Pipe: 30 -131.2 2.157 PL 164.33 PF 21.5 R5 24.2 0.0 32.2 0.0 11.5 120 FTG E PE 0.0 R15 24.2 0.0 53.7 0.0 0.126 TL 170.33 PV Pipe: 31 -131.2 2.157 PL 2.17 PF 1.8 R15 24.2 0.0 53.7 0.0 11.5 120 FTG T PE 0.9 C15 22.0 0.0 56.4 0.0 0.126 TL 14.17 PV Pipe: 32 -128.5 2.157 PL 164.33 PF 20.7 R6 23.7 0.0 33.6 0.0 11.3 120 FTG E PE 0.0 R16 23.7 0.0 54.3 0.0 0.121 TL 170.33 PV Pipe: 33 -128.5 2.157 PL 1.67 PF 1.7 R16 23.7 0.0 54.3 0.0 11.3 120 FTG T PE 0.7 C16 22.0 0.0 56.7 0.0 0.121 TL 13.67 PV Pipe: 34 -128.0 2.157 PL 164.33 PF 20.5 R7 23.2 0.0 34.4 0.0 11.2 120 FTG E PE 0.0 . R17 23.2 0.0 54.9 0.0 0.121 TL 170.33 PV Pipe: 35 -128.0 2.157 PL 1.17 PF 1.6 R17 23.2 0.0 54.9 0.0 11.2 120 FTG T PE 0.5 C17 22.0 0.0 57.0 0.0 0.121 TL 13.17 PV Pipe: 36 -129.0 2.157 PL 164.33 PF 20.8 R8 22.7 0.0 34.8 0.0 11.3 120 FTG E PE 0.0 R18 22.7 0.0 55.6 0.0 0.122 TL 170.33 PV Pipe: 37 -129.0 2.157 PL 0.67 PF 1.5 • R18 22.7 0.0 55.6 0.0 11.3 120 FTG T PE 0.3 C18 22.0 0.0 57.5 0.0 0.122 TL 12.67 PV Pipe: 38 -154.8 2.157 PL 0.67 PF 3.2 R1 22.7 0.0 21.7 0.0 13.6 120 FTG ET PE 0.3 Cl 22.0 0.0 25.1 0.0 0.171 TL 18.67 PV • SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 2/3/2005 C: \PROGRAM FILES \HASS76 \CROWN CARPET.SDF JOB TITLE: Crown Carpet - .6/2000 sq. ft. - 14.0k PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. . NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 39 -154.9 2.157 PL 1.17 PF 3.3 R2 23.2 0.0 21.6 0.0 13.6 120 FTG ET PE 0.5 C2 22.0 0.0 25.4 0.0 0.172 TL 19.17 PV Pipe: 40 -158.8 2.157 PL 1.67 PF 3.5 R3 23.7 0.0 22.0 0.0 13.9 120 FTG ET PE 0.7 C3 22.0 0.0 26.3 0.0 0.180 TL 19.67 PV Pipe: 41 -48.3 2.157 PL 2.17 PF 0.4 R4 24.2 0.0 26.9 0.0 4.2 120 FTG ET PE 0.9 C4 22.0 0.0 28.3 0.0 0.020 TL 20.17 PV Pipe: 42 131.2 2.157 PL 2.17 PF 2.5 R5 24.2 0.0 32.2 0.0 11.5 120 FTG ET PE 0.9 C5 22.0 0.0 30.6 0.0 0.126 TL 20.17 PV Pipe: 43 128.5 2.157 PL 1.67 PF 2.4 R6 23.7 0.0 33.6 0.0 11.3 120 FTG ET PE 0.7 C6 22.0 0.0 32.0 0.0 0.121 TL 19.67 PV Pipe: 44 128.0 2.157 PL 1.17 PF 2.3 R7 23.2 0.0 34.4 0.0 11.2 120 FTG ET PE 0.5 C7 22.0 0.0 32.6 0.0 0.121 TL 19.17 PV Pipe: 45 • 129.0 2.157 PL 0.67 PF 2.3 R8 22.7 0.0 34.8 0.0 11.3 120 FTG ET PE 0.3 C8 22.0 0.0 32.8 0.0 0.122 TL 18.67 PV Pipe: 46 -154.8 3.260 PL 11.00 PF 0.3 Cl 22.0 0.0 25.1 0.0 5.9 120 FTG - - -- PE 0.0 C2 22.0 0.0 25.4 0.0 0.023 TL 11.00 PV Pipe: 47 -309.7 3.260 PL 11.00 PF 0.9 C2 22.0 0.0 25.4 0.0 11.9 120 FTG - - -- PE 0.0 C3 22.0 0.0 26.3 0.0 0.083 TL 11.00 PV Pipe: 48 -468.5 3.260 PL 11.00 PF 2.0 C3 22.0 0.0 26.3 0.0 18.0 120 FTG - - -- PE 0.0 C4 22.0 0.0 28.3 0.0 0.178 TL 11.00 PV Pipe: 49 -516.8 3.260 PL 11.00 PF 2.3 C4 22.0 0.0 28.3 0.0 19.9 120 FTG - - -- PE 0.0 C5 22.0 0.0 30.6 0.0 0.213 TL 11.00 PV Pipe: 50 -385.5 3.260 PL 11.00 PF 1.4 C5 22.0 0.0 30.6 0.0 14.8 120 FTG - - -- PE 0.0 C6 22.0 0.0 32.0 0.0 0.124 TL 11.00 PV Pipe: 51 -257.0 3.260 PL 11.00 PF 0.6 C6 22.0 0.0 32.0 0.0 9.9 120 FTG - - -- PE 0.0 C7 22.0 0.0 32.6 0.0 0.059 TL 11.00 PV ' SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 2/3/2005 C: \PROGRAM FILES \HASS76 \CROWN CARPET.SDF JOB TITLE: Crown Carpet - .6/2000 sq. ft. - 14.0k PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 52 -129.0 3.260 PL 11.00 PF 0.2 C7 22.0 0.0 32.6 0.0 5.0 120 FTG - - -- PE 0.0 C8 22.0 0.0 32.8 0.0 0.016 TL 11.00 PV Pipe: 53 -207.7 6.357 PL 11.00 PF 0.0 C11 22.0 0.0 56.0 0.0 2.1 120 FTG - - -- PE 0.0 C12 22.0 0.0 56.1 0.0 0.002 TL 11.00 PV Pipe: 54 -414.6 6.357 PL 11.00 PF 0.1 C12 22.0 0.0 56.1 0.0 4.2 120 FTG - - -- PE 0.0 C13 22.0 0.0 56.1 0.0 0.005 TL 11.00 PV Pipe: 55 -619.9 6.357 PL 11.00 PF 0.1 C13 22.0 0.0 56.1 0.0 6.3 120 FTG - - -- PE 0.0 C14 22.0 0.0 56.2 0.0 0.012 TL 11.00 PV Pipe: 56 -788.5 6.357 PL 11.00 PF 0.2 C14 22.0 0.0 56.2 0.0 8.0 120 FTG - - -- PE 0.0 C15 22.0 0.0 56.4 0.0 0.018 TL 11.00 PV Pipe: 57 -919.7 6.357 PL 11.00 PF 0.3 C15 22.0 0.0 56.4 0.0 9.3 120 FTG - - -- PE 0.0 C16 22.0 0.0 56.7 0.0 0.024 TL 11.00 PV Pipe: 58 - 1048.2 6.357 PL 11.00 PF 0.3 C16 22.0 0.0 56.7 0.0 10.6 120 FTG - - -- PE 0.0 C17 22.0 0.0 57.0 0.0 0.031 TL 11.00 PV Pipe: 59 - 1176.2 6.357 PL 11.00 PF 0.4 C17 22.0 0.0 57.0 0.0 11.9 120 FTG - - -- PE 0.0 C18 22.0 0.0 57.5 0.0 0.038 TL 11.00 PV Pipe: 60 - 1305.2 6.357 PL 3.00 PF 1.0 018 22.0 0.0 57.5 0.0 13.2 120 FTG E PE -0.3 TR 22.7 0.0 58.1 0.0 0.046 TL 21.00 PV Pipe: 61 - 1305.2 6.357 PL 20.67 PF 2.4 TR 22.7 0.0 58.1 0.0 13.2 120 FTG EB PE 9.0 BR 2.0 0.0 69.5 0.0 0.046 TL 51.67 PV Pipe: 62 - 1305.2 6.357 PL 1.00 PF 0.0 BR 2.0 0.0 69.5 0.0 13.2 120 FTG - - -- PE 0.0 BF1 2.0 0.0 69.5 0.0 0.046 TL 1.00 PV Pipe: 63 FIXED PRESSURE LOSS DEVICE BF2 2.0 0.0 79.5 0.0 10.0 psi, 0.0 gpm BF1 2.0 0.0 69.5 0.0 Pipe: 64 - 1305.2 6.280 PL 5.00 PF 1.8 BF1 2.0 0.0 69.5 0.0 13.5 140 FTG 2E PE 2.2 UG1 -3.0 0.0 73.5 0.0 0.037 TL 49.00 PV SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 • DATE: 2/3/2005 C: \PROGRAM FILES \HASS76 \CROWN CARPET.SDF JOB TITLE: Crown Carpet - .6/2000 sq. ft. - 14.0k PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL /FT (PSI) Pipe: 65 - 1305.3 6.280 PL 120.00 PF 7.9 UG1 -3.0 0.0 73.5 0.0 13.5 140 FTG 2ETG PE -1.3 CITY 0.0 SRCE 80.0 (N /A) 0.037 TL 216.00 PV NOTES: (1) Calculations were performed by the HASS 7.6 computer program under license no. 3808132120 granted by HRS Systems, Inc. 4792 LaVista Road Tucker, GA 30084 (2) The system has been calculated to provide an average imbalance at each node of 0.002 gpm and a maximum imbalance at any node of 0.128 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 19.9 ft /sec at pipe 49. (4) PIPE FITTINGS TABLE Pipe Table Name: PATRIOT.PIP PAGE: B MATERIAL: Sch10 HWC: 120 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVly BfyVly GatVly AlmChk DPV1v NPTee F 45e11 2.157 6.00 12.00 3.00 14.00 8.00 1.00 12.00 12.00 12.00 2.00 3.260 10.00 20.00 7.00 22.00 14.00 1.00 18.00 18.00 20.00 4.00 6.357 18.00 38.00 11.00 40.00 13.00 4.00 35.00 35.00 38.00 6.00 PAGE: U MATERIAL: D -Iron HWC: 140 Diameter Equivalent Fitting Lengths in Feet (in) E T L C B G A D N Ell Tee LngEll ChkVa BFV GateVa NPTee 45e11 6.280 22.00 47.00 14.00 51.00 16.00 5.00 47.00 11.00 0.00 0.00 c t7 O Cu H c WATER SUPPLY ANALYSIS 1 3•• 120.0 Static: 98.00 psi Resid: 86.00 psi Flow: 2169.0 gpm 1 LEGEND m w .. Available pressure n c 1 0 89.46 psi @ 1805.3 gpm H 0 . Required pressure u' 100.0 __ 2 0 80.04 psi @ 1805.3 gpm 0 A. Source Supply Curve 0 . G System Demand Curve A j U 1 N m M ct 70 G . H I z E 80.0 __ 2 • r P N R o K E 0 to H S m 0 h] S 60.0 __ ▪ ro x U rt o 0 R • 0 E i i q ra H ( 40.0 _ ' "3 n H p • r 7y xLIz S cn Po ../.b i = W m H U Cn 20.0 _. ` m n 0 z 0.0 B z ro LI PO H a ,q m m -14.7 I I I I I i I PV 600 900 1200 1500 1800 2100 2400 2700 3000 FLOW (GPM) SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 DATE: 2/3/2005 C: \PROGRAM FILES \HASS76 \CROWN CARPET.SDF JOB TITLE: Crown Carpet - .6/2000 sq. ft. - 14.0k WATER SUPPLY CURVE 108+ I � I 1 99 * \ \\ I \ \\ \ \ \\ \ \\ 90+ \0 \\ I \ \\ 1 * < -86.0 psi @ 2169 gpm Flow Test Point 81+ X 1 1 1 P 72+ R I E I S I • S 63+ U 1 R 1 E 1 54+ P S 1 I 45+ ) I 1 1 36+ 1 1 1 27+ 1 18+ LEGEND " 1 I X = Required Water Supply I 80.04 psi @ 1805.3 gpm 9+ 1 0 = Available Water Supply " 1 89.46 psi @ 1805.3 gpm • 1 " 0 + + - +--- + - - - -+ + + + + + + 8001200 1600 2000 2400 2800 3200 3600 4000 FLOW (GPM) ATRI OT Fire Sprinklers Save Lives! Va 4708 NE er, WA 9866 Street ' FIRE;PROTECTION, INC. TEL (360) 699.4403 ��5 � `i3 N 7 PORTLAND 9.44 222.6001 1 3 FAX TLA D (503 85 R E EQUIPMENT - Si U `iITT:�� L C1 /VF FFe o D n;4 ll mo BN / 4 - � /N G r '4- .PATRIOT FIRE POT .C? Or1, 1 C ...I•'O 3 : ?1 L s /pN ' SPM KLERS " PENDENT RELIABLE VlE_ .7'" BP272. fi REc PENDENT RELIABLE Fl FP, i ' WHT I Wl'9T 15.: "a VALVE ,fay pCDA - -- -- ; ! S' , ^T F.. . C. 8" UGIFM TEST AN DPJ,iN AGF WiPF E SURE GAUGE i CHECK VALVE RELIABLE 1;.= , 1° ji.:;:11 • 4 ELECTRCAL DEVICES **4 • c ,F, . WEDGO i" _. �M . • _ • WATER FLOW INDICATOR Sys. . ='��.0 � ; �i, a ' HANGFP & WAV LAc1l1� , 7.._.� o • .n ;PIPE RING < FIG 65 0-CLAMP .(OLCO FIG 58 3/3' UL • • • TACOMA, WA OFFICE HANFORD, WA OFFICE SPOKANE, WA OFFICE TEL: (253) 926.2290 TEL (509) 373.8895 TEL: (509) 926.3428 FAX: (253) 922.6150 FAX (509) 373.8919 FAX: (509) 926.3708 PATRIFPO99CF Bulletin 146 Rev.0 w c ReIiabI m Model G VELD Pendent Very Extra Large Orifice Sprinkler c 0 Low Pressures for High Hazards 0.70" Orifice, 14.0 K, 7psi (0,5 bar) Minimum End - Head Pressure 1 , (SIN R4613) 1 R Features The Reliable Model G VELO pendent sprinkler ` ' ' offers opportunity for: # 1. Pipe size reduction. I 2. Fewer sprinklers. 3. Elimination of booster pumps. Model G VELD pendent utilizes a center strut solder in 4. The best choice for denies of 0.38 gpm/ft. compression fusible element (15 Umin /m or larger. It has been proven in UL and FM full-scale fire testing and 5. Simplifies future ESFR conversions. complies with all applicable mechanical and hydraulic 6. Also includes additional Specific Application listing: requirements Of the latest sprinkler standards. (See detailed "UL Specification Application listing" This product is intended for use as a standard spray sprinkler in hydraulically designed systems with a minimum described on the back page.) pressure of 7 psi (0,5 bar) in accordance with the US Patents: 5.890.657 and 5.915.479 area/density curves of NFPA 13* and for all area/density methods of design as referenced by Factory Mutual Loss Listing & Approvals Prevention Data Sheets. 1. Listed by Underwriters Laboratories, Inc. and Design Criteria Certified by UL for Canada (cULus). The following criteria apply when designing an automatic 2. Approved by Factory Mutual (FM) sprinkler system utilizing the Model G VELO sprinkler for 3. NYC MEA 258 -93-E NFPA 13* applications. UL Guide Number • Sprinkler spacing shall be a minimum of 6 ft. (1.8m). • Minimum design pressure 7 psi (0,5 bar). VNIV • Factory Mutual (FM) Approval for Modal G VELO sprinkler UL Listing Category allows installation into drops or branch line fittings. Sprinklers, Automatic & Open • Factory Mutual (FM) Loss Prevention Data Sheets c Application Sprinklers contain requirements which differ from NFPA. The Specific pri Model G VELO is Approved by Factory Mutual for all area/density methods of design as referenced by FM Technical Data Loss Prevention Data Sheets. Nominal Sprinkler K Factor Sprinkler Sprinkler Identification Note: The Model G VELO sprinkler is not a "Large Drop" TYPe US Metric Height Number (SIN) or "ESFR" sprinkler. Pendent 0.70 orifice PPT 14.0 200.0 (79mm) R4613 (R3 %) Temperature Ratings Note: This product has been tested and listed for storage Maximum Ceiling Classification Sprinkler Rating Temperature Frame applications to qualify its use in lieu of 5.6K or 8.0K Factor , , , oC Color sprinklers for the protection of high-pled storage Ordinary 165 74 100 38 Uncolored Intermediate 212 100 150 66 White Product Description High 286 141 225 _ 107 Blue . The Reliable Model G VELO sprinkler is a Very Extra Large Orifice pendent sprinkler that has been designed to control high challenge fires in both palletized and rack • For sprinkler standards prior to 1999 edition of NFPA 13 storage occupancies utilizing lower water pressures. The use NFPA standards 231, 231 C, 231 D & 231 F. The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552 • Finishes Maintenance Standard Fnilsflsa• Approvals Model G VELO Sprinkler should be inspected and the Natural Bronze sprinkler system maintained in accordance with NFPA 25. Bright Chrome Do not dean sprinklers with soap and water, ammonia or Satin Chrome Special Application Finishes* Approved for all any other cleaning fluids. Remove dust by using a soft brush Temperature Ratings or gentle vacuuming. Prior to installation, sprinklers should Lead be maintained in the original cartons and packaging until Wax /Lead used to minimize the potential for damage to sprinklers that *cULus lid only would cause improper operation or non - operation. Remove i listed anci FM approved any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of The UL Specific Application Listing is: damaged or operated sprinklers. The Model G VELO pendent sprinkler is intended for use in accordance with NFPA 13*. Standards when installed in accordance with the standard sprinkler positioning and area/density flow calculation requirements as specified in Model H the respective standards. The Model G VELO Pendent Sprinkler Wrench spy may be installed to protect single, double and Use only the Model H multiple row and portable rack storage of Class I-IV group A +! �, f,4�a sprinkler wrench for and B plastics, cartoned, expanded or unexpended, as well sprinkler removal and as exposed unexpanded with a maximum storage height of installation. Any other 20 ft. (6.5m), maximum ceiIng height of 25 ft. (82m) or 27** ft type of wrench may (8.8m) maximum ceiling height, 36 (914mm) minimum damage the sprinkler. deflector to top of storage clearance, design density of 0.60 gpm/ ft (24 L./min /m and design area of 2000 ft (186m for wet systems and 2600 ft (242m for dry systems. I **Note: Maximum 27ft ceiling height is allowed by NFPA 13*, without in -rack sprinklers in a protected area, provided • the ceiling sprinklers' discharge is increased to 0.6 gpm/ft in a 2000 ft design area A I� i I Note: Factory Mutual (FM) Standards also allow the same , 3 ro r>x74) 2000 ft. (186m2) remote design area when VELO sprinklers are used in this situation. AI Installation Reliable's Model G VELO Pendent sprinkler must be installed according to the NFPA Standards or the - appropriate Factory Mutual Loss Prevention Data Sheet ,- lit and the Authority Having Jurisdiction. MODEL G VELO PENDENT Installation Approvals Distance from Deflector to Top of Commodity Underwriters Laboratories, Inc. (cULus) 36 Factory Mutual Research (FM) * For sprinkler standards prior to 1999 edition of NFPA 13 use NFPA standards 231, 231C, 231D & 231F. The equipment presented In this bulletin is to be Installed in accordance with the latest published standards of the National Fire Protection Association. Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting fife and property for over 80 years. and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States. Canada and foreign countries. The Reliable Automatic Sprinkler Co.,lnc. ReliabId (800) 431 -1588 Sales Offices Recycled Paper (800) 848-6051 Sales Fax (914) 668-3470 Corporate Offices Revision Ines ledtate updated or new data. litplAwmferebespildEccom Internet Address Ea Aural in u.SA 602. PM 9939970738 Bulletin 148 Rev.B Model F1FR co -�. Model Fl FR Recessed Quick Response Extended Coverage Sprinklers i to A complete line of UL Listed and FM Approved quick response extended coverage _ sprinklers for light hazard applications. - . • Horizontal Sidewall Sprinklers are approved for installation 4" -12" (102mm - 305mm) '`" °` below the ceiling. 1 Model F1FR QREC Sprinkler Types Extended Coverage Pendent Extended Coverage Horizontal Sidewall Extended Coverage Recessed Extended • EC -8 Deflector Pendent Coverage Pendent • EC -9 Deflector Model Fl FR QREC Recessed Sprinkler Types w Recessed Extended Coverage Pendent v - - Recessed Extended Coverage Horizontal "',. —'- •s Sidewall: 4 t • EC -8 Deflector • EC -9 Deflector . -� Approval Organizations Extended Coverage Recessed Extended 1. Underwriters Laboratories, Inc. Horizontal Sidewall EC -8 Coverage H orizontal Sidewall 2. Underwriters' Laboratories of Canada EC-8 3. Factory Mutual Research Corporation 4. NYC MEA 258 -93 -E UL Listing Category , ' Sprinklers, Automatic & Open - Quick Response Extended Coverage Sprinkler UL Guide Number 't i VNIV Note: Consult appropriate FM Installation Standards regarding limitations of room size, ceiling height and minimum wall fire resistance rating. Extended Coverage Recessed Extended Horizontal Sidewall EC -9 Coverage Horizontal Sidewall Product Description EC -9 Reliable Models F1FR QREC and F1FR QREC The balance of parts are made of brass, copper and Recessed Sprinklers are quick response sprinklers which beryllium nickel. combine the durability for a standard sprinkler with the The temperature rating of the sprinkler is identified by attractive low profile of a decorative sprinkler. the color of the glass bulb. The Models F1FR QREC and F1FR QREC Recessed A Il Automatic Sprinklers utilize a 3.0mm frangible glass bulb. pp These sprinklers have demonstrated response times in Quick response sprinklers are used in fixed fire laboratory tests which are five times faster than standard protection systems: Wet, Dry, Deluge or Preaction. Care response sprinklers. This quick response enables these must be exercised that the orifice size, temperature sprinklers to apply water to a fire much faster than rating, deflector style and sprinkler type are in standard sprinklers of the same temperature rating. accordance with the latest published standards of the The glass bulb consists of an accurately controlled National Fire Protection Association or the approving amount of special fluid hermetically sealed inside a authority having jurisdiction. Quick response sprinklers precisely manufactured glass capsule. This glass bulb is are intended for installation as specified in NFPA 13. specially constructed to provide fast thermal response. The Reliable Automatic Sprinkler Co., Inc. • 525 North MacQuesten Parkway • Mount Vernon • New York •10552 Model Fl FR Quick Response Extended Coverage Pendent Sprinkler _ Deflector: EC . .: _ .• -"-. Installation Wrench: Model D Sprinkler Wrench Approval Type: Quick Response Extended Coverage -Light Hazard Occupancy t: ''' Data: G � "K" Factor Sprinkler Nominal Thread Sprinkler Temperature"' Approval Identification . .t Orifice Size US Metric Length Rating Organizations Number (SIN) "'/32" (20mm) 3 4" NPT (R 8.0 115 (56. 2. 1mm 2" ) 155 F 135°F (57(68°C) C) 12,3,4 R4842 ° ' /z" (15mm) ' /z" NPT (R' /2) 5.6 80 (53 1" 21" 13155°F 5°F (57(68°C) C) 12,4 R4845 ° ") FM Approval of pendent sprinkler - 135 °F (57 °C) only Model Fl FR Recessed Quick Response Extended Coverage Pendent Sprinkler Deflector: EC Installation Wrench: Model RC1 Sprinkler Wrench Approval Type: Quick Response Extended Coverage -Light Hazard Occupancy Installation Data: - "K" Factor Sprinkler Nominal Thread Sprinkler Temperature" Approver Identification , ,,,., Orifice Size US Metric Length ' Rating Organizations Number (SIN) _, ,. '' /3z 3 /< " NPr 8.0 115 22' 135°F (57°C) 1, 2, 3, 4 R4842 r — -I (21]rrn) (R (56.1mm) 155°F (68°C) - = -- non — /2 /2" NPT 5.6 80 2.1" 135°F (57°C) 1, 2 4 R4845 .401•67 N T a " (15mm) (R1) (53.4mm) 155°F (68°C) •°s ° — 1 (" FM Approval of recessed sprinkler — 135 °F (57 °C) 1 `21 Refer to escutcheon data table for approvals and dimensions. ,L -.1 L _ d„ _fie -� V iI i — row COVERAGE AREA T � .�� a.w Pressure, psi (bar) Maximum �� Flow Coverage Area - Rate Width x Length ) «s/n °+ IWO= gpm (1../min) K = 8.0 (115) K = 5.6 (80) ft x ft. (m x m) 26 (98.4) 10.6 (0,7) 21.6 (1,5) 16x16 (4.9x4.9) 33 (125.0) 17.0 (1,2) 34.7 (2,4) 18x 18 (5.5x5.5) 40 (151.4) 25.0 (1,7) 51.0 (3,5) 20x20 (6.0x6.0)" j3) 135 °F (57 °C) only for both Pendent and Recessed Pendent. Model Fl FR Quick Response Extended Coverage Horizontal Sidewall Sprinkler Deflector: EC -8 Installation Wrench: Model D Sprinkler Wrench Approval Type: Quick Response Extended Coverage -Light Hazard Occupancy Installation Data: "K" Factor Sprinkler Nominal Thread Sprinkler Approval Temperature Identification ,' -' Orifice Size US Metric Length Organizations Rating Number (SIN) - off ;::ms • /z' X. NPT 5.6 80 2.8" 1, 2, 3, 4 155°F (57°C) 84865 ( 15mm) (Rh) (71.1mm) 175 °F (79°C) 2. Model Fl FR Recessed Quick Response Extended Coverage Horizontal Sidewall Sprinkler Deflector: EC - , ;---\ ' Installation Wrench: Model GFR1 Sprinkler Wrench • Approval Type: Quick Response Extended Coverage -Light Hazard Occupancy Installation Data: . "K" Factor Sprinkler . • Nominal Thread - • Sprinkler Approval Temperature"' Identification \ \ \ \ \ \ \ \ \ \ \ \ \ \. Orifice Size US Metric Length Organizations Rating Number (SIN) / j NPf 135 °F (57°C) MCC a RIM m (1 5mm) ( R' /z) 5.6 - 80 (71 ) 1, a 3,4 155 °F (68°C) 84865 `a"° COMM \ r� 4• m 7 rr 175 °F WC) 11 . FM Approval of recessed sprinkler - 135 °F (57 °C) only _ .„\I „n°, j2) Refer to escutcheon data table for - approvals and dimensions. - r 47 . j COVERAGE AREA r rq „ 0 - IIII;II,I�IlI �- a Flow Rate Pressure Maximum Deflector to Ceiling I ii , I`��� � r II�I� I��IIII - n a gpm (Umin) psi (bar) Coverage Area Dimension Width x Length Min. - Max. ` L -- ' I UL FM UL FM ft x ft. (m x m) Inches (mm) �9 I " 26 (98.4) 26 (98.4) 21.4 (1,5) 21.4 (1,5) 16x16 (4.9x4.9) 4 -12 (102 -305) . .anur,an I -,. 29 (109.8) 30 (113.6) 26.6 (1,8) 28.5 (2,0) 16x18 (4.9 x 5.5) 4-12 (102-305) i L r` w I . 32 (121.1) 3 (125.0) 324 (2,2) 34.5 (2,4) 16x20 (4.9x6.0 4 -12 (102 -305) .I I . . i iw nivao r4scar • • .Model F1FR Quick Response Extended Coverage Horizontal Sidewall Sprinkler ' • Deflector: EC ' - installation Wrench: Model D Sprinkler Wrench - • Approval Type: Quick Response Extended Coverage -Light Hazard Occupancy Installation Data: - "K" Factor Sprinkler Nominal Thread - Sprinkler Approval Temperature .Identification • Orifice Size US Metric Length Organizations Rating Number (SIN) ' f n; - ' L • 3 135°F (57°C) s • "� '- � .•? „ NPl 285 a n o ,r= (20mm) (83/4) 8.0 115 (72.4mm) 1,2,3,4 175°F (78°C) 8°C) R4862 175°F (78°C) Model F1FR Recessed. Quick Response Exten Coverage Horizontal Sidewall Sprinkler Deflector: EC - 9. - • ' Installation Wrench: Model GFR1 Sprinkler Wrench . , Approval Type: Quick Res ponse Extended Coverage -Light Hazard Occupancy Installation Data: . "K" Factor . • Sprinkler ' Nominal Thread Sprinkler Approval Temperature Identification Orifice Size US Metric Length Organizations Rating"' Number (SIN) /3x" Ye NPl 8.0 115 2 a'" , , , 71 (20mm) (R (72.4mm) 175 °F (78°C) 1 2 3 4 155°F (68°C) R4862 °J Mr a' Arra e . 'm• • . , "' FM_ of recessed sprinkler - 135 ° F only. I 4 1D r: • 121 Refer to escutcheon, data table for approvals and dimensions. . Mil = ) - . 1 1 .v."v sr URN SPOSC . COVERAGE AREA { --- I 1 9°53 ' - Row Rata - Maximum ' , ter.- 1IIIIII .-1 ----- - n �a a. 9Pm (t / min) Pressure, psi (bar) Coverage Area Deflector to Ceiling IlllIijI �1' Width x Length Dimension loon. - Max. • ', UL FM UL FM ft. x ft (m x m) Inches (mm) l I t , .� .; - 26 (9 - 10.6 (0,7) - 16x 16 (4.9 x 4.9) 12 (305) . - "4J 1 29 (109.8) 32 (121.1) 13.1 (0,9) 16.0 (1,1) 16x16 (4.9x4.9) 4 -12 (102 -305) ' 29 (109.8) 36 (136.3) 13.1' (0,9) 202 (1,4) 16x18 (4.9x5.5) 4 -12 (102 -305) �rauoa � 32 (121.1) 40 (151.4) 16.0 (1,1) 25.0 (1;7) 16x20 (4 4 -12 (102 -305) r,;.-P" '"' ,a 4.°)- '36 (136.3) 44 (166.6) 202 (1,4) 30.2 (2,1) 16x22 (4.9x6.7) 4 - 12 (102 -305) I ,° „ar ; . 39 (147.6) 48 (181.7) 23.8 (1,6) 36.0. (2,5) 16x24 (4.9x7.3) 4 -12 (102 -305) . 3. Model F1 FR & Fl FR Recessed Quick Response Extended Coverage Sprinklers Finishes`° Quick response sprinkler are intended for installation Standard Finishes • as specified in NFPA 13. Quick response sprinklers and sprinae�' Escutcheon standard response sprinklers should not be intermixed. The Model, Fl FR Recessed QREC Sprinklers are to be Bronze Brass installed as shown. The Model Fl or F2 Escutcheons Chrome Plated Chrome Plated illustrated are the only recessed escutcheons to be used White Polyester Coated White Painted with the Model Fl FR Sprinklers. The use of any other Special Application Finishes recessed escutcheon will void all approvals and negate Sprinklef' Escutcheon all warranties. When installing Model F1FR QREC Sprinklers, use the Bright Brass Bright Brass Model D Sprinkler Wrench. When installing Model Fl FR Black Plating Black Plating QREC Recessed Sidewall Sprinklers, use the Model Black Paint Black Paint Sprinkler Wrench. Use the Model RC1 Wrench for Off n Chrome Off White GFR1 S Chr p Satin Chrome Satin Chrome installing F1FR QREC Recessed Pendent Sprinklers. Any other type of wrench may damage these sprinklers. "' Other colors and finishes are available on special order. Consult factory for details. Maintenance • «' FM Approval limited to bronze, bright and satin chrome plated, The Models F1FR QREC and F1FR QREC Recessed and polyester coated only. Sprinklers should be inspected quarterly and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ,. ammonia or any other cleaning fluids. Remove dust by , Escutcheon Data using a soft brush or gentle vacuuming. Remove any applied) which has been anpainted y. (other A stock of spare adlustmerit Dimension wtocei°llt�i„ Fitting ° sprinklers should, be maintained to allow quick „(19),,, ',6 ^() replacement of damaged or operated sprinklers. Prior to Fl 1 , 2 , 4 3;^ (19mm> installation, sprinklers should be maintained in the ly (35mmr % %B' (24mm) original cartons and packaging until used to minimize the 25mm • ^ () ", 3;6' (sue) potential for damage to sprinklers that would cause F2 1, 2,3,4 . y^ (13mm) 1 1 ( 5mn,Y >`� , y, (18mm improper operation or non -operation. (') EC Pendent ` EC HSW • Temperature Ratings "' NYC MEA 258 -93 -E, Pendent and Recessed Pendent Only. Sprinkler Maximum Rating Ambient Temp: Ordering Information Classification °F. °C °F °C Bulb Color Specify: Ordinary 135 57 100 38 Orange ' 1. . Sprin Type odel Ordinary 155 .68 100 38. Red 3. Orifice Size • Intermediate . 175 79 150 66 Yellow 4. Deflector Type . 5. Temperature Rating • B. Sprinkler Finish • Sprinkler Types 7. Escutcheon Type Extended Coverage Pendent 8. Escutcheon Finish (where applicable) • • Extended Coverage Sidewall Note: When Model F1FR Recessed sprinklers are • EC -8 HSW Deflector ordered, the sprinklers and escutcheons are . • EC -9 HSW Deflector packaged separately. Recessed Extended Coverage Pendent Recessed Extended Coverage Sidewall • • EC -8 HSW Deflector . • EC -9 HSW Deflector The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory - Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Reld The Reliable Automatic Sprinkler Co., Inc. L? Recycled 1 Paper (800) 431 -1588 Sales Offices (800) 848-6051 Sales Fax (914) 668 - 3470 Corporate Office Revision lines indicate updated or new data. immiim www.reliablesprinkler.com Internet Address E.G. Printed in U.S.A. 4/03 P/N 9999970142 • WILKINS Model 350ADABGVIC a MO. company Double Check Detector Assembly SPECIFICATION SUBMITTAL SHEET APPLICATION Designed for installation on potable water connections in • fire sprinkler systems to protect against both backsipho- 11 - . e4 -- r - - nage and backpressure of polluted water into the potable water supply. Model 350ADABGVIC shall provide protec- tion where a potential health hazard does not exist. Incor- i ' porates metered by -pass to detect leaks and unauthorized 1s i) I I ,r i r B water use. STANDARDS COMPLIANCE (horizontal and vertical orientations) • ASSE® Listed 1048 FEATURES • UL® Classified Sizes: ❑ 4" ❑ 6" ❑ 8" • C -UL® Classified Maximum working water pressure 175 PSI Maximum working water temperature 140 °F • FM ®Approved Hydrostatic test pressure 350 PSI • Approved by the Foundation for Cross Connection End connections (Grooved for steel) AWWA C606 Control and Hydraulic Research at the University of Southern California MATERIALS Victaulic grooved end butterfly valves (standard) Main valve body Ductile Iron ASTM A 536 Grade 4 Access covers Ductile Iron ASTM A536 Grade 4 OPTIONS Coatings FDAApproved electrostatic epoxy finish (Suffixes can be combined) Internals Stainless steel, 300 Series ❑ LM - less water meter NORYLTh, NSF Listed ❑ - with remote reading meter Fasteners & springs Stainless Steel, 300 Series ❑ - with gpm meter (standard) Elastomers EPDM (FDA approved) ❑ - with cu ft/min meter Buna Nitrite (FDA approved) Polymers NORYLTm, NSF Listed ACCESSORIES , c ❑ Repair kit (rubber only) ❑ Thermal expansion tank (Model WXTP) S. „ _.4 ■LL 1 —�, ;n ,ITIIMEz 11 1lC d 1 Illi 7 • A DIMENSIONS & WEIGHTS (do not include pkg.) MODEL 360ADABGVIC DIMENSION (approxirate) WEIGHT MODEL B LESS WITH WITHOUT SZE A BUTTERFLY BUTTERFLY BUTTERFLY VALVES VALVES in. mm in. mm in. mm in. mm in. rim h. mm in. mm in. mm be. Iv be. I® 4 100 33 3/8 848 19 7/8 505 341/4 870 9 229 103/4 273 6 152 51/4 133 91 41.3 129 59 6 150 401/8 1019 257/8 657 411/4 1048 1012 267 121/8 308 7 178 712 191 141 64 197 89 8 200 54 3/4 1391 38 12 978 55 1397 12 305 13 330 812 216 9 229 302 137 424 193 (Patent No. 5.913 e� 350 onsGVIC 6 041SION: Page 1 of 2 • • FLOW CHARACTE MODEL 350ADABGVIC 4" & 6" (STANDA RD S METRIC) FLOW RATES (Us) 25.2 50.5 - 75.7 101 • I 15 - I - 104 -- 4" (100mm) 10 69 0 + S _ 6" (150mm) - _ 1 5 35 Ct 1 ° 0 400 800 1200 t� 1600 E FLOW RATES (GPM) - MODEL 350ADABGVIC 8" (STANDARD & METRIC) FLOW RATES (us) 63.1 126.2 189.3 • 252:4 IT 15 _ ) - 104 8" (200mm) g J 10 69 0 - J - I 5 . 35 D i c i e s & 0 w a. 0 1000 2000 3 000 4000 a FLOW RATES (GPM) • • ORated Flow (Established by approval agendas) TYPICAL INSTALLATION - , Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted at a minimum of 12" ,_,�_ (305mm) and a maximum of 30" (762mm) ,,,„ -,_ wS c -. — ; : 0 — BLS above adequate drains with sufficient side clearance for ' _ _ I 7 testing and maintenance. The installation shall be made so :Ills VIII — d III) AIII' that no part of the unit can be submerged. e 1!_Cd �i $ • i f lil l lil" II - 7 _ Capacity thru Schedule • Cap y th Shdl 40 Pipe (GPM) 12 MIN. Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec U 30• x• 2 1/2" 75 V 112 149 224 ■ 3" 115 173 230 346 • d • • ° • • ' . • •• • - 4" 198 298 397 595 •• 6" 450 675 900 1351 8" 780 1169 1559 2339 ° . DIRECTION OF FLOW 10" 1229 1843 2458 3687 MODEL 350ADABGVIC INDOOR INSTALLATION SPECIFICATIONS - - The Double Check Detector BackflowPrevention Assembly shall be supplied with butterfly valves. The main body and access cover shall be epoxy coated ductile iron (ASTM A 536 Grade 4), the seat ring and checkvalveshall be NoryI (NSF Listed), the stem shall be stainless steel (ASTM A 276) and the seat disc elastomers shall be EPDM. The first and second check valves shall be accessible for maintenance without removing the device from the line. The Double Check Detector Backflow - Prevention Assembly shall be a WILKINS Model 350ADABGVIC. Page 2 of 2 WILKINS a Zum company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238 -7100 Fax:805/238 -5766 IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905 /405 -8272 Fax:905/405 -1292 Product Support Help Line: 1- 877 - BACKFLOW (1 -877- 222 -5356) • Website: http://www.zum.com ---- . i - - Bulletin' 807 Rev.E Model G 2y " ,3 " ,4 " &6" 3 zoir ._, HeiiabI (65mm, 80mm, xi 100mm 150mm Swing e vin C heck Valves m TM The Right -Check Features 1. Grooved end connections. 2. Compact, lightweight design. 1 '' • 3. Non - slamming, spring loaded clap- ` 1 per to minimize water hammer. 4. Approved for horizontal and vertical installation. 5. Streamlined body design provides Am- very low friction loss. Figure 1 6. Elastomer faced clapper provides 3. Friction loss, expressed in equivalent length of - leak -free, non - sticking sealing. Sch. 40 pipe with C = 120 (based on Hazen and Williams formula): General 21/2" - 7 ft. (65mm - 231 cm) Reliable Model G Swing Check Valves are multiple 3" - 7 ft. (80mm - 213cm) purpose valves performing regular check valve 4" - 10 ft. (100mm- 305cm) duties with very low friction loss. All four sizes are • 6" - 16 ft. (150mm - 488cm) approved for use in fire protection systems. Typical 4. Standard grooved end dimensions per ANSI /AWWA applications include connections between public ' C606. water supplies and private fire systems, at the measure Jrcp vs. 7Ik.w iota discharge from fire pumps, at gravity tank M. •. "J " "' ` " "y connections and at fire department pumper D ` re/ ' ' ' connections. - - = The 4" (80mm) Model G Check Valve is provided a with a' /2" NPT (R'/2) supply side connection (Item 12, o '•' ", • v � F F f F o`` Fig.2). This supply side connection is optional for all t .�' � �� r = ° . r other valve sizes and must be specified. ,, ;0.07 '' o a Grooved end connections provide fast and easy installation using listed or approved mechanical ° grooved couplings. Rigid style grooved couplings r:..:;.15.00 -r,, trr. Vr.t. :m- can be used for positive clamping to resist flexural ;37S; ,•`S''? - - ; ;'• "''r 1 .'``'' and torsional loads. flow `al°. 9p`" (` /`"'") Right- CheckTM valves and associated equipment Technical Data should periodically be given a thorough inspection Valve Size Face-to-Face Shipping weight and test. NFPA 25 provides minimum maintenance Dimensions requirements. Check valves should be inspected and 2'k" (65mm) 7.03' (178mm) 9 lbs. (4kg) operated at least annually. Parts should be replaced 3" (80mm) 7.62" (193mm) 11 lbs. (5kg) as required. 4" (100mm) 8.44 (214mm) 17 lbs. (7.7kg) When Model G Swing Check Valves are installed vertically, the direction of the flow arrow must point 6" (150mm) 10.25 (260mm) 38 lbs. (17.25kg) upward. For horizontal installations, the hinge pin Approvals must be located at the top. 1. Listed by Underwriters Laboratories, Inc. Valve Description 2. Underwriters Laboratories certified for Canada. 1. Rated working pressure 250 psi (17,25 bar). 3. Approved by Factory Mutual Research Corp.' 2. Factory hydrostatic test pressure 500 psi (34,5 bar). 4. NYC MEA 258 -93-E. . Note: 1 bar=100 kPa * FM Approved both a "Single" Aleck valve and "Anti -Water Hamer" check valve. The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, NewYork10552 Parts List - Refer to Figure 2 Part Name Material Quarttltp Part Number I No. 2)(" (65mm) 3" (80mm) 4" (100mm) 6" (150mm) f 1* Valve Body Gray Iron, ASTM -A48 Class 30A 1 91005022 91005023 91005024 91005026 2• Seat Bronze C83600 or C93200, ASTM-B505 1 96020200 96020300 96020400 96020600 3 Clapper Stainless Steel 304, ASTM -A240 1 91816112 91816113 91816114 91816116 4 Facing Seal" EPDM Rubber 1 95520200 95520300 95520400 95520600 5 Clamping Ring Stainless Steel 304, ASTM -A240 1 95290300 95290300 95290400 95290600 6 Gasket" EPDM Rubber 1 93720302 93720302 93720604 93720604 , 7 Spring Stainless Steel 302, ASTM -A313 1 96400300 96400300 96400400 96400600 8 Hinge Pin • Stainless Steel 303. ASTM -A582 1 95000280 95000300 95006824 95000600 9 Bolt . •Stainless Steel 304, ASTM -F593 1 91090300 91090300 91090400 91090600 . 10 Locknut " Stainless Steel 303, ASTM -F594 1 94911420 94911420 94913816 94913816 11 Plug, ) NPT Steel 1 95201800 95201800 95201800 95201800 12 Plug, y° NPT Steel • 1 Optional Optional 98604402 Optional ** Replacement Seal Kit 1 _ 6888040025 _ 6888040030 _ 6888040040 _ 6888040060 Not field replaceable. Valve Disassembly 1. Close the main water supply valve and drain the L 1 system. 2. Remove the check valve from the piping system. 0 O (V 0 0 3. Inspect the Seat (2) for any cuts, scrapes and - , • dents. Replace the valve if any damage is found. �. ��� , 4. To replace the Facing Seal (4), remove the Clapper - (3), unscrew the Locknut (10) and, remove the - r , �,- � � Retention (9): l s. .. ' .- Valve Reassembly 5 : :: 1. Thoroughly clean the Clapper (3). Insert the Alb ___ - _ Retention Bolt (9) with a new Gasket (6). M/ - ' Jk l i 2. Place the new Facing Seal (4) and the Clamping �1 , . ` Ring. (5) against the Clapper (3). Tighten the new r • Locknut (10) to 21 in: lbs. (2.37N.m) torque in 2 ` (63mm) and 3" (76mm) sizes and to 52 in. -lbs. 1 r ' ! ' • (5.87N•m) in 4" (101mm) and 6" (152mm) sizes. I ED 3. Insert the dapper assembly into the.valve,through the downstream opening. Reinsert the Hinge Pin (8) . 0 , e . while holding the coils of the properly oriented 0 0 0 Spring (7) in place. Install the hinge pin Plug (11). Figure 2 • 4. Reinstall the check valve in the system. • 5. Place the system back in service. . Ordering Information Specify: 1. Model G Right-Check Valve. 2. Size. 3. 1/2" NPT (R'h) optional supply side connection for valve sizes other than 4" (100mm). Contact the installing contractor or Reliable if any difficulties are experienced. Should replacement parts be needed, use only genuine Reliable parts. , The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fre Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. • Manufactured by ' . Th Reliable Automatic Sprinkler Co., Inc . Recycled Paper. tt� iIbI (800) 431 -1588 Sales Offices (800) 648 - 347 Sales Fax Revision tines indicate updated or new'data. (914) 668-3470 Corporate Offices www.reiiabbsprinWe.coa Internet Address EG. Printed in U.SA. 0501 W149999970071 A ;c 0 b S P R I N K L E R R S Y S T E M S M O N I T O R I N G • WF D Series `Th SYSTEM Waterflorw Detector �� SENSOR' UL ULC/Canadlan - , a � Models Models - ......4, rrh lY.i W FD20 W FD20A ' ,., ' : .. WFD25 WFD25A " -. .i Q*�l , r' a ^ - .E - W FD30.2 W FD30 -2A x Er !"': WFD35 W FD35A e "Y : '_ W FD40 W FD40A ` ` ' WFD50 WFD50A "` ' - t' ?' ` • i W FD60 W FD60A W FD80 W FD80A ta e.- ..- - Replacement Parts vi . . A3008-00 Retard Mechanism . a A77 -01 -02 Terminal Block : 546 -7000 Cover Tamper Switch Kit ?• :' F F .. WFDW Cover Wrench °!" w,- '- ' . • WFON4 Replacement gasket kit 1 Y n _ '3._... ` . +y .- M `? , , px. - cud . • ,',4P''''';' . Product Overview New WFD30 -2 models install In 2" System Sensor's WFD series Is compatible with schedule 10 through 40 steel pipe, hole sizes sizes 2" through 8'•, and can be mounted In a vertical or horizontal position. UL models are NEMA 4 rated Robust Construction. The WFD series consists of a rugged, NEMA 4 raced Sealed retard mechanism assures that enclosure. Designed for both indoor and outdoor use, the WFD series operates the retard is not contaminated by dust across a wide temperature range, from 32 °F to 120 °F. and dirt when the cover is removed Reliable Performance. UI. listed models are equipped with tamper resistant Visual switch activation permits cover screws to prevent unauthorized entry. Inside, two sets of SPDT (Form C) installer to accurately set retard under synchronized switches are enclosed in a durable terminal block to assure noisy conditions reliable performance. Rugged, dual SPDT switches are enclosed in a durable terminal block False Alarm Immunity. The WFD series incorporates a mechanical retard fea- ture, which minimizes the risk of false alarm due to pressure surges or air Accommodates up to 12 AWG wire trapped in the sprinkler system. In addition, the mechanical retard's unique 100% synchronization activates sealed design is immune to dust and other contaminants. both alarm panel and local bell Simplified Operation. The WFD series is designed to simplify installation. Two . simultaneously conduit openings permit easy attachment to the local alarm system. The retard mechanism and dual SPDT switches are field - replaceable. la ® MEA 415 ,� approved LISTED ll Engineering Specifications Vane -type waterflow detectors shall be installed on system piping as designated on the drawing and /or as specified herein. Detectors shall mount on any clear pipe span of the appropriate nominal size, either a vertical upflow or horizontal run, at least 6" from any fittings which may change water direction, flow rate, or pipe diameter or no closer than 24" from a valve or drain. • Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a static pressure rating of 450 psi* for 2" - 8" pipes. The detector shall respond to waterflow in the specified direction after a preset time delay which is field adjustable. The delay mechanism shall be a sealed mechanical pneumatic unit with visual indication of actuation. The actuation mechanism shall include a polyethylene vane inserted through a hole in the pipe and connected by a mechanical linkage to the delay mech- anism. Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit entrances for standard fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. Unless noted, enclosures shall be NEMA 4 listed by Underwriters Laboratories Inc. All detectors shall be listed by Underwriters Laboratories Inc. for indoor or out- door use. Standard Specifications Static Pressure Rating Conduit Entrances Service Use 450 PSI• Two openings for W conduit. One open, one Automatic Sprinkler: NFPA -13 knock -out type One or Two Family Dwelling: NFPA 130 Triggering Threshold Bandwidth (Flow Rate.) Residential Occupancies up to 4 Stories: NFPA 13R 4-10 GPM Operating Temperature Range National Fire Alarm Code: NFPA -72 32 °F to 120°F (0°C to 49 °C) Maximum Surge Warranty 18 Feet Per Second (FPS) Enclosure Rating• 3 Years NEMA 4 - suitable for Indoor /outdoor use Compatible Pipe: U.S. Patent Numbers Steel water pipe, schedule 10 through 40 Cover Tamper Switch 3,845.259 Standard with ULC models 4.782.333 Contact Ratings Optional for UL models, part no. 546 -7000 5.213.205 Two sets of SPOT (Form C) 10.0 A, 1/2 HP 0 125/250 VAC Shipping Weight 2.5 A 0 8/12/24 VDC WFD20: 4.2 lbs. WFD40: 5.2 lbs. WFD25: 4.3 lbs. W FD50: 6.3 lbs. Overall Dimensions Installed: WFD30.2: 4.5 lbs. WFD60: 6.8 lbs. a . , WFD35: 4.7 lbs. WFD80: 7.5 lbs. I '0 111. L i ■ uO.nut 1.r13 gig Pip saddle . Mehl Ira . Modal Meet Modal Width i t 'l l WF 4.5' WFe.Ot 6.e' 4. '� WFM 0 7 5.2'0 wV00 's WFD342 3. WF06 Se 0 9.1Y wr�rrrr WF035 5.71 WFD80, 109' Ordering Information UL Model Numbers ULC/Canadian Model Numbers , Pipe Size ' Hole Size PTrt Number Description WFD20 WFD20A ' 2' 1v.' A3008-00 Retard mechanism WFD25 WFD25A . 2 :6' • 1V4' A77.01 -02 Terminal block WFD30.2 i WFD30.2A 3' 2' 546 -7000 Tamper proof switch kit WFD35 WFD35A i 3+4 ' 114- WFDW Tamper proof wrench for cover WFD40 j WFD40A , 4' , 2' WFDN4 Gasket kit WFD50 WFD50A 5' 2' WFD6O• WFD60A 6' . 2' WFD8O• i WFD80A , 8' 2 •Maximum pressure rating 400 psi as approved by Factory Mutual. System Sensor Sales and Service System Sensor Headquarters System Sensor Canada System Sensor In China System Sensor - Far East System Sensor - India 3825 Ohio Avenue Ph: 905.812.0787 Ph: 88.29.524.6253 Ph: 85.22.191.9003 Ph: 91.124.637.1770 x.2700 • St. Charles, IL 60174 Fx: 905.812.0771 Fx: 86.29.524.6259 Fx: 85.22.736.6580 Fx: 91.124.637.3118 Ph: 800 /SENSOR2 System Sensor Europe System Sensor In Singapore System Sensor - Australia Fx: 630/377-6495 Ph: 44.1403.276500 Ph: 65.6273.2230 Ph: 613.54.281.142 Documents -on- Demand Fx: 44.1403.276501 Fx: 65.6273.2610 Fx: 613.54.281.172 . 800/736. 7672 x3 www.systemsensor.com 02002 System Sensor. The company reserves the right to change product specifications without notice. A05.0180008.04/02'4947 MODEL 101 1 . . 10 MODEL 101 1T F TESTANDRAIR ., MODEL 1011 WITH REUEF VALVE AND BYPASS PIPING MODEL 1011 T WITH RELIEF VALVE, BYPASS PIPING, AND PRESSURE GAUGE TAPPING TEST ORIFICES AVAILABLE— VC - 7 /16 " -' /_" - 11 hi 175 PSI REUEF VE NORMALLY PROVIDED FRONT VIEW-MODEL 101 1T FRONT VIEW-MODEL 1011 _ —_ O TEST Ohl.° 01 I iii ''. i L_9_ 15 4 -- \se i 111 410-).____ 1 li W -1110104.1dii1W1 _ o r • . _ l z I. „ _ai ImmilLiAlasi ____,.._._ . . alikstmazzai!illa siggisiz:ww.:K.--ei illa _ _ .... _ ....„........„... v..; From February 6, 1989 Edition of NFPA 13 and subsequent editions Paragraph 3 -4.1.1 states: A minimum size of 1" supply for the test connection Drain connections MAIN SIZE systems s SIZE OF DRAIN CONNECTIONsized as shown in Table 3 -6.2.2 upply risers and mains shall be RISER O Up to 2" 3 /4" or larger 2'/2 ", 3 ", 3' /2" 1'/4" or larger 4" and larger 2" only Paragraph 3 -9.3.3 states: A ' /2" relief valve set at 175 PSI shall be installed downstream of P.R.V. valve Paragraph 5 -1.3 states: A relief valve shall be provided set to operate at 175 PSI ORIFICE SIZE PROVIDED- 3 /8 - 7 /16 -'/z - "/32 MATERIAL LIST MATERIAL DIMENSIONS — INCHES HANDLE STEEL OVERALL LENGTH 101 1 AND 101 1T STEM ROD BRASS , loll 101 IT . BALL C.P. BRONZE SIZE A A E F G H , BODY BRONZE 3 /4 6 "/16 9 '/16 33/ 13/ 4 6 VALVE SEAT GLaSS INPREGNATED TEFLON INDICATOR PLATE STEEL 1 6 " /I 9'/1 3 1 /4 4 9 /I6 65/16 HANDLE LOCK SPRING STEEL 1 7 9'/16 3 I's /16 5'/2 7 SIGHT GLASS (2) FUSED TEMPERED GLASS RELIEF VALVE BRONZE 1 1 /z 7's /16 11 3 2 8'/16 101/16 BYPASS FITTINGS BRASS _--->- 2 1 715/ 1 1 s /16 3'/2 2 8'/16 10 BYPASS TUBING NYLOBRAID AGF MFG. CO. JOB NAME: Box 4437, 150 Mt. Bethel Rd. ARCHITECT: Warren, N.J. 07059- 043 ".5'` ENGINEER: Telephone (908) 604 -6471 Fax (908) 604 -6501 CONTRACTOR: 1011/10117 -1 Grinnell , pipe rings r i adjustable swivel ring fig. 70 SIZE RANGE: Fig. 69 '/2" - 8" tapped per NFPA standards Fig. 70 2t/2° - 8" fig. 69 MATERIAL: Carbon steel. FINISH: Plated. • SERVICE: Recommended for suspension of non - insulated, stationary pipe line. • �_ ,, 1A MAXIMUM TEMPERATURE 650 °F. on. /: APPROVALS: Fig. 69 Underwriters' Laboratories listed • ik and Factory Mutual approved' thru 8 ". Complies with -N Federal Specification WW -H -171 E (Type 10) and Manu- \ F facturers Standardization Society SP -69 (Type 10). e FEATURES: - : � c • Threads are countersunk so that they cannot become I • burred or damaged. • -_; — -�'\ • Knurled swivel nut provides vertical adjustment after t ; piping is in place. �.`, I . , • Captured socket will not fall out. �.: ORDERING: Specify size, figure number, name. iv V, ) • • . loads • weights • dimensions (inches) max weight recom (approx) pipe load, lb lbs each A e C F size Fig. 69 Fig. 70 Fig. 69, Fig. 70 Fig. 69 Fig. 70 Fig. 69 Fig. 70 Fig. 69 Fig. 70 Fig. 69 1 Fig. 70 'h 300 .09 3V 21 1% '/e 3 300 .09 36 2' /,a 1'•',e '/e 1 300 .10 36 2 1 "e 11/4 300 .10 $ 2% 13 '.'e 1 300 .10 36 23 1% 'e 2 300 _ .11 Ve 3'i. 2's - i -- 2'h 525 1000 .25 .33 % %i 4 3 's 15 2 2" •6 l' ,.. I' t ) 3 525 1000 .27 .36 . Sr 436 4 ",6 3'/e 3' ,,, 1'i 1' , 6 4 650 1100 .48 56 36 ?e 4" ,6 5 3" ,e 3�a t °'.6 i 1% 5 1000 1100 .53 .62 'h ye 5 59•■9 4% 41/2 1 it, 1'. 6 1000 1250 1.0 1.2 V2 '.S 6'1•6 6''e 51/2 51/2 2 ',a 2' ' 8 1000 1250 1.0 1.4 'h ?. 8 8". 7 7 . 2" ,.. 2" 'e ph -10 Grinnell hanger rods machine threaded rods continuous thread: 146 threaded both ends. I right -hand threads: fig. 140 F 8 -i right- and left -hand threads: fig. 253 I ae .....etnnrrnnmma -A • . • SIZE RANGE: 1 /4 through 11/2 inch diameter. i Stocked in six, ten and twelve foot lengths. Other even foot lengths can be furnished to order. , ............... L I MATERIAL: Carbon steel; rod threaded complete --D -I to {—D length. . FINISH: Black or electro- galvanized. • MAXIMUM TEMPERATURE: 750 °F. ORDERING: Specify rod diameter and length, figure number, name. • loads • weights max recom ht MATERIAL: Carbon steel. rod load, lb (ap weight MAXIMUM TEMPERATURE: 750 °F. A 650 °F { lbs tt ORDERING: Specify rod size, figure number, name, rod 1 /4 240 • .12 . length. Specify thread length if other than standard. % 610 .30 • '2 1130 . .53 FINISH: Black or electro- galvanized. % 1810 .84 4 • 3 4 2710 1.2 7 /° 3770 1.7 1 4960 2.3 loads • standard thread lengths 11/4 8000 I 3.6 1' /z 11630 l 5.1 maximum recommended rod load, lb standard rod size thread length A 650 °F I 750 °F D•, in coach screw rods ve 610 540 21/2 machine threaded on opposite end: '/2 1130 1010 21/2 fig. 142 ke 1810 1610 2 3 /4 2710 2420 3 , lie 3770 3360 3 �` 1 1 4960 4420 I ' /z 4 -- C A ' - D 11/4 I 7140 5 1V2 1 11630 10370 I 6 MATERIAL: Carbon steel. 13/4 15700 14000 7 ORDERING: Specify rod size, figure number, name, rod 2 20700 18460 8 length. 21/4 27200 24260 9 21/2 33500 29880 10 standard thread lengths • loads 23'4 41580 37066 11 I coach I 3 50580 45085 12 screw std max 3'/4• 60480 53906 13 rod standard thread rod the recom 31/2• 71280 63493 14 size rod lengths L. in I D, in load, lb 334• 82890 I 73855 15 % 31/2 2 3 4 390 3e 8 2 ; 21/2 I 390 - • %,'/2 and % inch fig. 140 rod in lengths of 24 inch or shorter will be '/z 3'/2 2 3 4 640 furnished as continuous thread rod unless order states that all thread 1/2 8 2 21/2 640 rod is not acceptable. % 4 2 ° +6 3: { 760 • Furnished with 8 UN threads. 3 /4 5 2 I 3 830 r ph-59 • TOLCO INCORPORATED ' CORONA CA 909 737 -5599 • Fig. 65 and Fig. 66 40. s Reversible C-Type Beam Clam .��� Y p 3/4 and 1 -1/4 Inch Throat Openings Size Range– (Fig. 65 and Fig. 66) 3/8, 1/2, AND 5/8 inch rod. Material – Carbon Steel with hardened cup point set screw and jam nut. - Function – Recommended for hanging from steel beam where flange thickness does not exceed 3/4 inch (Fig. 65).or 1-1/4" (Fig. 66) B Features – All steel construction eliminates structural deficiencies p associated with casting type beam clamps. May be used on top or , bottom flange of the beam. (Beveled lip allows hanging from top flange 4r k E where clearance is limited.) May be installed with set screw in up or • m/�a C • down position. Offset design permits unlimited rod adjustment by , %/ 1P allowing the rod to be threaded completely through the clamp. Open design permits inspection of thread engagement. F 4 � ,, Approvals– Underwriters' Laboratories Listed in the USA UL and Canada (cUL). Factory Mutual Engineering Approved. Conforms to • Federal Specification Society SP -69, type 19 and 23. Exceeds %II A requirements of the National Fire Protection Association (NFPA), Pamphlet #13, 3/8 inch rod will support 1/2 thru 4 inch pipe, 1/2 inch rod 1� vill support 1/2 thru 8 inch pipe. . Finish – Plain. . Note - Available in Electro- Galvanized and HDG finish. • Order By— Figure number, rod size, and finish. Fig. 65 Patent #4,570,885 B D • IjP E FIG. 65 TABLE ROD MAX. REC. APPROX 0 SIZE A B C D E F LOAD LBS.• WTJ100 F . 3/8 1 -3/16 3/4 1 7/16 ' 1 610 28 1/2 '- 1 -1/2 3/4 1 9/16 1 -1/4 1130 55 ) - 5/8 1-1/2 3/4 1 9/16 1-1/4 1130 55 *Max: loads for clamp with set screw in up or down position. W A . e • FIG. 66 TABLE ROD MAX. REC. APPROX . SIZE A ' B. . C D E F LOAD LBS.* WTJ100 3/8 1 -3/16 1 -1/4 1 7/16 1 610 28 . '1/2 1 -1/2 1 -1/4 1 9/16 1 -1/4 1130 55 5/8 1 -1/2 1 -1/4 1 9/16 1 -1/4 1130 55 ;tax. loads for clamp with set screw in up or down position. -61-