Specifications pl , . September 13, 2004 CITY OF TIGARD Keith Johnson OREGON DULL OLSON WEEKES ARCHITECTS 319 SW Washington Street #200 Portland, OR 97204 RE: HVAC MODIFICATIONS Project Information Building Permit: MEC2004 -00281 Construction Type: II -1 HR Tenant Name: Tigard High School Occupancy Type: E -1 Address: 9000 SW Durham Road Occupant Load: NA The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99- 01) 1999 edition. The submitted plans are approved subject to the following. 1. Each appliance shall be provided with a shutoff valve separate from the appliance. The shutoff valve shall be located in the same room and within six feet of the appliance served. Access shall be provided to the shutoff valve. C409.5 OMSC 2. Equipment and appliances regulated by this code requiring electrical connections shall have a positive means of disconnect in accordance with the Electrical Code. 301.7 OMSC 3. Permanent equipment supported by the structure, 400 lbs and over, shall have their attachments designed in accordance with the Building Code. 301.16 OMSC 4. Appliances serving different areas of a building other than where they are installed shall be permanently marked in an approved manner that uniquely identifies the appliance and the area it serves. 304.10 OMSC 5. Appliances shall be accessible for inspection, service, repair or replacement without removal of permanent construction. 306.1 OMSC *r, 6. Manufacturer's installation instructions shall be available on the jobsite at the time of inspection. 304.1 OMSC 7. Condensate from cooling coils or evaporators shall be collected and discharged to an approved plumbing fixture or disposal area. 307.1 OMSC 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 8. Smoke detectors shall be installed in return air systems with a design capacity greater than 2000 cfm. Upon activation, the smoke detector shall shut down the air distribution system. Smoke detectors shall be connected to a fire alarm system and shall activate an audible and visible alarm at a constantly attended location. 606.2, 606.4 & 606.4.1 OMSC 9. Appliances installed on roofs or elevated structures exceeding 16 feet in height shall be provided with a permanent means of access grade or floor level. 306.5 OMSC 10. Ductwork shall be supported in accordance with Sheet Metal & Air Conditioning Contractors National Association, Inc. (SMACNA) Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC Premises Identification: Approved numbers or addresses shall be provided for all new buildings in such a position as to be plainly visible and legible from the street or road fronting the property. When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respect Ian tyt ock, Sen '.Plans Examiner I , • /�imu�ll�,� j August 18, 2004 =mss. 1 1 CITY OF TIGARD Keith Johnson OREGON DULL OLSON WEEKES ARCHITECTS 319 SW Washington Street #200 Portland, OR 97204 RE: HVAC MODIFICATIONS Project Information Building Permit: MEC2004 -00281 Construction Type: II -1 HR Tenant Name: Tigard High School Occupancy Type: E -1 Address: 9000 SW Durham Road Occupant Load: NA The plan review was performed under the State of Oregon Mechanical Specialty Code (OMSC) 2002 edition; the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The following information is required prior to approval of the submitted plans. 1. Provide details for the support of the ducts. The design of the structural support, materials, spacing and connection to structure of the duct supports is required prior to permit issuance. Detail 3, Sheet M6.2 indicates a seismic support system only (no indication of spacing or location). The duct supports shall be incorporated into the plans. 2. Fire AND Smoke Dampers are required at the penetrations of the Corridors, Area Separation Walls and Occupancy Separation Walls. The dampers require different ratings for each application. Please indicate on the plans the rating for the dampers. 3. Detail 4/M6.2 indicates a duct seismic brace. In several locations the duct is penetrating a corridor wall. Per Oregon Structural Specialty Code section 713.10 & 713.11, item 2, exception, a damper is not required if the duct is 26 gage and does not serve the corridor. Clarify material used in the "FLEX CONNECTION" as indicated on the detail. If the material is not 26 gage or better, a Fire /Smoke damper is required. 4. Additional Fire /Smoke dampers are required at the following location: • Grid 10 @ H, Sheet M2.22 • Grid 6 @ Room 118, Sheet M2.23 • Grid 10 @ H, Sheet M2.22 • Grid 10 @ J, Sheet M2.22 5. Clarify the hydronic system design pressure. The new piping is required to be tested at 1 %2 times the design pressure but not less than 100 PSI per section 1208 OMSC. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 Sent By: MFIA INC; 5032340677; Aug -23 -04 9:29; Page 2/4 August 20. 2004 M EI MEMO '10: Keith Johnson • I NC;. DOWA SI IFIJEC'C: Tigard HS- Phase 2 City of Tigard Plan Review Comments 0 in response to the IIVAC plan review comments from the City of l igard, we have the N following. 11 Provide details jar the support of ducts The support structure and installation instructions for ductwork are specified to 11 comply with SMACNA standards in section 15880- 3.03 -A of the construction L documents. The numerous duct sizes, orientations. and building construction types are addressed in chapter 4 ol'the SMACNA standard. The standard shows duct attachment, duct reinforcement and support intervals. .1 o replicate the tables and details on the construction documents would be redundant considering the specification requirement. The seismic details indicate the minimum acceptable requirements for support that we have selected from the vast array of options N allowed by the SMACNA standard for seismic bracing relative to the duct sizes listed on the detail. I'he SMACNA standard lists the interval liar support. The spacing for this support type is 40 'feet on center laterally and 80 feet longitudinally. However, since the mechanical contractor is required by section 15090- 3.03F3 to retain an engineer to design the seismic support system we would request that review of this item be completed through a deferred submittal. N 2) Fire AND Smoke Dampers are required.. This has been changed per the attached clarification to the contract documents. c; '1 he 1.5 hr rated dampers can be used in one or two hr rated construction. I here are no rated construction barriers higher than two hours. N ;) Detail 4/M6.2 indicates a duct seismic brace... This detail was changed after a conversation with Brian 13laylock. A copy of the changed details are attached. E 4) Additional i-`ire,i,Sinoke Dampers are required... a. Grid 10 (dd I1, Sheet M2.22: A new I-'SI) will be added, see revised drawing. tt b. Grid 6 (<i Room 118, Sheet M2.23: The design was changed during bidding to eliminate the wall penetration requireing the damper. A more recent change due to structure is attached showing the revised ductwork. 'Therefore the damper is not required. Sent By: MFIA INC; 5032340677; Aug -23 -04 9:29; Page 3/4 c. Grid I H . Sheet M2.31: A new FST) will he added, see revised drawing. The drawing referenced in the code review does not appear to be correct, we 1® L have listed what we believe is the correct drawing, please verify. -1 ][ d. Grid 10 (ii; J, Sheet M2.31: Ncw FSD will be added, see revised drawing. The drawing referenced in the code review does not appear to he correct, we have listed what we believe is the correct drawing,'please verify. INC. 5) The highest pressure of the hydronic system will be at the discharge of the pump. Per the pump schedule in phase 1 this will be 26 PSI plus about 12 -PST static pressure. So the total pressure will he about 40 PSI maximum. • C MPIA, Inc. Scott Miller U T. N Ci • N i; N E L tt Tigard High School - PhaSe II August 20, 2004 Addendum Items SPECIFICATIONS Section 15880 1) Article 2.02 C 1: Replace as follows. 1. Constructed and installed in accordance with NFPA No. 90A, UL labeled. Provide dampers with rating of not less than 1 /2 hours for use in 1 hour and 2 hour construction through fire - resistant rated construction per applicable codes. 2) Article 2.02 C 3: Replace as follows. 3. Each damper shall be classified by UL as a "corridor damper" for installation in tunnel corridors, shall be rated for 11/2 hours fire resistance under UL555, and shall have a minimum leakage rating of Class II under UL555S for use in smoke control systems. Each damper shall bear a UL label designating the damper as "corridor damper." MFIA, Inc. kRGED PLAN- LIFE SKILLS TAIL FIRE RATED SEAL A UN SULATED PIPE P ANCHOR, SEE 2 NEW ADDITION , 6. SIZE OF OPENING T• SIZE OF OPENING TO BE , DETERMINED BY STRUGT. DETERMINED BY STRUGT. LONG; i I lk ERIES :ELL FIG. Ail I�_ *_•_•_•_� a A AND = _ R 1r • AM , I rI;,I._.7�4,_•_❖:•:4I .I • 0 'i 3 ., im , , ^ l ip,3 INSULATED PIPE ,� � k . "44e4 (E) BUILDING SEISMIC, PIPE SUPF A + ^ RATED WALL SEE 6/M6.I FOR DI ti SEISMIC, PIPE SUPPORT; SEE 6/M6.1 FOR DETAIL " THIS DETAIL IS TYPICAL FOR ALL PIPE PENETRATIONS THRU CONNECTION WITH EXISTING BUILDING 4 PIPE CONNECTION AT BLDG JOINTS NOT TO SCALE BY:SWMICHK'D:SWMIDATE: 8.06.04 TI GA RD II. S. NO REVISION DATE 8.06.04 ADDITION /REMODEL REVISION MECHANICAL SCHEDULES /DETAILS A A MFIA INC. JOB NO. 02054 2007 S.B. ASH ST. SHEET NO A PORTUND OR. 97214 ph. 503- 234 -0548 RE V- REF: M6.2 a is. 41 411 41111 140.0•. SEISMIC, JOINT FIRE SEAL A NEW ADDITION 3/8" PIPE CLAMP 20" MIN. ` / / A , *% ,/ (E) BUILDING RATED WALL i 4* --.._ / , 2" X 2" X I/8" STEE IRON SUPPORT; ATI �—" WALL WITH (4) I /4 "x 1 ANCHOR BOLTS 1 Ak7 INSULATED PIPE 0 * TO BE USED ON EXISTING BUILDING SIDE ONLY; 5EE 6 FOR NEN ADDITION SIDE M6.1 1 2A SEISMIC PIPE SUPPORT \ e, 2 SCALE• DETAIL NOT TO SCALE BY:SWMICHK'D:SWM DATE: 8.06.04 TI GA RD �j T �+ S. NO REVISION DATE A REVISION 8.0b.04 ADDITION /REMODEL A MECHANICAL SCHEDULES /DETAILS A JOB NO. 02054 200 S.B. AS11 INC. SHEET NO A PORTLAND OR. 97214 ph. 503 -234 -0548 REV —REF: M6.2 b • NEW BUILDING (E) BUILDING A RATED WALL NING THRU WALL, SEE ZAL FOR EXACT SIZE ... 2 "X2 "XI /8" STEEL ANGLE IRON N SUPPORT ATTACH TO (E) WALL W/ (4) I/4 "X2" CONCRETE ANCHOR BOLTS o t0 a / 1 T M o ^ N. FIRE SEAL ez FLEX CONNECTION — EMD DUCT SEISMIC BRACE DETAIL SCALE DETAIL NOT TO SCALE BY :SWMICHK'D:SWMIDATE: 8.06.04 TI GA RD II. S. NO REVISION DATE 1 1 (y A REVISION 8.06.04 ADDITION /REMODEL A MECHANICAL SCHEDULES /DETAILS A MFIA JOB NO. 02054 2007 S.E. ASH I ■ SHEET NO A PORTLAND OR. 97214 ph. 503- 234 -0548 REV REF: M6. 2 c r x , 1 I �� `- I L 11 f - 18X12 RA y174 I I 2OXIS SA 1 d3 I 14 RA 111 X - ' I fV \\ 3 § II e u) I - T I BALL I.R. A v 3 8 " , . 1 - ,. T 3c F 3 ���� ' = 2 )12 TRAN�SF, R GRILLE C____IS dil" , 1 _ 1 q, 1 1 I CI= _ 1i i I II iI 1 1 1 NIAPJK AIWIII Nil : �� A I,I ��11•11E �1� -+ STAFF 11 1`40 V iiiit' " EXIT m ON ill i ilir TOILET i i 100 CF 53° MIN � w /\ L i 2000 J 200 CFM IMMI$ I6XI6 E , TLS U O BOYS 532 S "4 SA SSA IS C IS EXH UP THRU I 1< 50 CFM EL am■ /pia mil. lll� Ilr�� �, �.;�� �SROO� STAFF I!!' I I 323 LI R<RO0I11 ,_ f- it 5� CF 10X EXN _ gam' , 4e FM I \ I I4i• s r I ' 16)(12 LA l2 E )<H N IN CHAS\ - � � r.. - - i , I 2CX18 \ S,DN IN CHASE 11' A fly b f X A \\ �`+ NOT TO SCALE BY: RR ICHK'D: SM IDATE:5 -20 -04 TI GA RD l l u ►J - P - �j A ►J E .G NO REVISION DATE Z\ REVISION #6 8 -20 -04 CLASSROOM WAG PLAN A MECHANICAL REVISION A MFIA INC. JOB NO. 7104A 1 2007 S.E. ASH ST. SHEET NO. A PORTLAND OR. 97214 ph. 503- 234 -0548 RM6. 2 —REF: M2.3 1 - u U I ± _, LGOVL 222A SE I I I 6 I I--- - IO "(I) S ; SEE 12 TRANSFER GRILLE l y -- ,1 FOR G NT. 12.21 I I . I I 3 "c FLE DUCT II - I 1 .'GRILLE ` ►e''' �► _ I ■ 1._, * I 1 rw ,1 I , I I i 1 11110•03 - mi. STA"' 6 „ 0 , x I TOIL 0 _ r 100 , F . .. ' � .- - 7,- 1 11 - _ �a 1 T� > 1 1 10 co SA 10"4) SA 1' BOOM S" SA 200 CFM 200 CFM ) J _ I I — 4 150 CF B OYS 1 GIRLS B. awir * 1 254 I 235 16X10 EXH 10X10 E N 111, STAI*= 10X10 E N 400 CF 1 WORKROOM 400 CFM 232 �I I 4 SA " N X CFM 1 6 "4) EXI-I C) 1 IV OF 4) I \50 CFM L I - I LP - 2bXIb 5A > �i ISX1 EXH UP 1'4 LN- 11 - - — —T--- — — T Vi , 2CXISSA 0A. 24XI8 ■ 2 SA I 4 I I i��I- w. C J r _i_r I I Ai... NOT TO SCALE BY: RR I CHK'D: SM DATE: 8 -20 -04 T T GA R D l l U - �j S P - �r SE 2 NO REVISION DATE 1 1 lr A REVISION #6 8 -20 -04 CLASSROOM HVAC PLAN MECHANICAL REVISION A MFIA INC. JOB NO. 7104A1 A 2007 S.B. ASH ST. SHEET NO. A PORTLAND OR. 97214 ph. 503- 234 -0548 RM6. 1- REF: M2.22 Sent By: MFIA INC; 5032340677; Aug -23 -04 9:29; 'Page 4/4 � " 1 .Y� 12X12 RA - (V 11 . . E I — - - ---- 1 460 GFM ail_ .wIlu -1 ] T 1 ( E) 16X10 EXH UP O (E) EF -2; REBALANCE S NEW FSD IN (E) 10X8 EXH FAN 550 GFM � o ._ NEW 10X/3 EXH kl?� +CORMTOR�6F./ TO (E) IOXB EXH MUSIC L It�PAk r' (E) DIFFUSER1 ,vi. i 6 ° 0 5A / \ ► � . ° n , ` llci REBALANCE - A I® M ni 6•�+ e, EACH (TYPIG� 1 �� 'iT�i Fr-1 1 ,' A TR w. III NEW 24X16 RA TO -��� A N �� (FJ wNG -3 10x10 - • / / (E) 24X16 OPENING® • 111111 ABOVE I °� , OM • I. T.` W 2 •'XIO /5A 0 ,.,41.. r Cri ro tr ,.._ ro g ‘. pai . %Nu INII I . X10 R �� S f •`� ` 4��1� � _- - - - -- IG :IBM I II . ",,E1 10X1/.0 RA I Iigh,..w ._-___iv."-77.7.-. - I , ._.,�.r. �� ■ - .. 12X8 RA 3` >'. Prl +�91z am amer�J:�i»ICmm►j 3 DAN l 0 f�541 1P a 1 11- ( 10 ' M ' 8 ° 4' EMEI �`.,� 121 _ - 'V i 5 - 4 N05 � ' HALT 1 5 AI�/ - - -- -= - -- .2, . "/ —_____ - , ,, I .. Stil B - 5A NEV' 20X10 5A 8 I NEW 10X8 SA TO (E) \' 150 GFM w IOXIO SA TO (E) ® IQXIO 5A DIFFUSER; I 1 30X10 SA REBALANCE DIFFUSER • • PRAC 1 f ; TO 300 CFM • II EME01 I J a ( - Er. 5A N al A 15715"CFM i • 1 Isvir III t -loll 11y� - F .AND 6,'0 - 3 ! J f�C�c7M 100 C $m; I. I FA 0i% j ■ - - 1/8'01' -O' BY: RR 1CHK D: SM,bATE: 8 -19 -04 TGA T RD HS— PHASE 2 NO REVISION DATE l d V ! l -- MUSIC DEPARTMENT •HVAG PLAN A REVISION 3 *5 ; & -I9 -04 • MECHANICAL REVISION • MFIA INC. JOB NO. 7 1 0 1 — Q 2 007 Si. ASH ST. SHEET NO. • PORTLAND OR. mu ph. 503-134 -0548 RM5. > — R EF: M2.2 3