Loading...
Specifications 0fi June 8, 2006 Revised June 13, 2006 • CITY OF `TIG;`'_, ' D OREGON Master Fire Control , = Ken Molinari 12125 SE Hwy 212 Clackamas, OR 97015 RE: FIRE SPRINKLER SYSTEM MODIFICATION - REVIEW Project Information Building Permit BUP2006 -00229 Construction Type: 5 -B Tenant Name: Tigard High School Occupancy Type: E Address: 9000 SW Durham Rd. Stories: • 1 • Hazard: - Light The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 2004 edition, Oregon Fire Code 2004 edition; and NFPA 13. The submitted revised plans are approved subject to the following. (Discard old plans) TESTING - Section 16.2.1 Hydrostatic testing of the system shall occur at sprinkler final. The contractor's material and test certificate required by NFPA 13,16.1 shall be completed and signed by both the installer and building owner. 1. Unless permitted by 16.2.1.2 through 16.2.1.6, all piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested at 200 psi (13.8 bar) and shall maintain that pressure without loss for 2 hours. Loss shall be determined by a drop in gauge pressure or visual leakage. The test pressure shall be read from a gauge located at the low elevation point of the system or portion being tested. WATERFLOWALAR&IS: - Section 6.9.1 2. Water flow alarm apparatus shall be listed for the service and so constructed and installed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler of the smallest orifice size installed on the system will result in an audible alarm on the premises within 5 minutes after such flow begins and until such flow stops. SPRINKLER SYSTEM MONITORING: OSSC 901.6. - NFPA 13 sec 8.16 3. All valves controlling the water supply for automatic sprinkler systems and water -flow switches on all sprinkler 4 systems shall be electrically monitored where the number of sprinklers are more than 20. 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 HANGERS:: . 4. The maximum distance between hangers shall not exceed that specified in Table 9 -2.2. 5. The maximum distance between hangers for listed nonmetallic pipe shall be modified as specified in the individual product listings. SWAY BRACING: - Section 9.3.5 - 9.3.5.8 6. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads and to prevent vertical motion resulting from seismic loads. The structural components to which bracing is attached shall be determined to be capable of carrying the added applied seismic loads. Sway braces shall be designed to withstand forces in tension and compression. Bracing shall be attached directly to feed and cross mains. RESTRAINT OF BRANCH LINES. - Section 9.3.6 7. Restraint is considered a lesser degree of resisting loads than bracing and shall be provided by use of one of the following (1) A listed sway brace assembly (2) A wraparound U -hook satisfying the requirements of 6- 4.53, Exception Number 3 (3) No. 12, 440-lb (200 -kg) wire installed at least 45 degrees from the vertical plane and anchored on both sides of the pipe (4) Other approved means Wire used for restraint shall be located within 2 ft (610 mm) of a hanger. The hanger closest to a wire restraint shall be of a type that resists upward movement of a branch line. The end sprinkler on a line shall be restrained against excessive vertical and lateral movement. Where upward or lateral movement would result in an impact against the building structure, equipment, or finish materials, branch lines shall be restrained at intervals not exceeding 30 ft (9 m) PIPING CLEARANCE: - Section 9.3.4 8. Where pipe passes through holes in platforms, foundations, walls, or floors, the holes shall be sized such that the diameter of the holes is 2 in. (50 mm) larger than the pipe for 1 in. (25 mm) nominal to 31/2 in. (89 mm) nominal and 4 in. (100 mm) larger than the pipe for pipe 4 in (100 mm) nominal and larger. Clearance from structural members not penetrated or used, collectively or independently, to support the piping shall be at least 2 in. SPARE SPRINKLERS: - Section 6.2.9 1. The stock of spare sprinklers shall include all types and ratings installed and shall be as follows: a. For systems having less than 300 sprinklers, not fewer than six sprinklers Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respec • al Henzel, Senior Plans Examiner ;w1 • ✓& Master Fire Control, Inc. f� 1.. 12125 SE Hwy 212, Clackamas, OR 97015 ° * s 503-655-6992 — fax 503- 656 -0782 , ` � � ken@masterfirecontrol.com Cl� 04 . 4 Product Data for Fire Protection S ' I Tigard High School Phase IV CE2 /Transition & Girls Locker Room 9000 SW Durham Rd, Tigard, OR 97224 Specification Section 15300 Item Description Manufacturer 1. Pendent Spkr Heads Tyco Recessed Chrome Ty -Frb ''/2" 2. Ext. Coverage Spkr Heads - Tyco Recessed Chrome EC-11 3 /4" 3. Pipe 1" — 2" — Dyna Thread Allied 4. Threaded Pipe Fittings Stockham 5. Wood Anchoring Textron EZG 600 & EZG 665 6. Pipe Ring Hangers Fig 200 Tolco 7. All Thread Rod Fig 100 Tolco _ tqCO/Fire & Builclir7g S j , ,. n Products _ Customer Service /Sales: Technical Services: Tel (800) 381 -9312: Fax (800) 791 -5500 Tel (414) 570 -5000; (800) 558 -5236 Fax. (41 570-50101 (800) 877 -1295 Series -FRB — Larit 9 Ave, 5.6, and' K- factor Upright, Pendent, and Recessed Pendent Sprinklers • Quick Response, chemical to which the sprinklers will be ' General exposed. - . _ -: Description An intermediate level versions of the ..:�° ._ _,;� >� Series TY -FRB Pendent Sprinklers are The Series Ti -FRB, 2.8, 4 2, 5.6, and detailed in Technical Data Sheet ^'3` A ` 8.0 K- factor, Upright and Pendent TFP356, and Sprinkler Guards are de `; Sprinklers described in this data sheet tailed in Technical Data Sheet TFP780 d are quick response - standard cover- r: age, decorative 3 mm class bulb type WARNINGS spray sprinklers designed for use in The Senes TY Sprinklers d _ - light or ordinary hazard, commercial scribed herein must be in and _ -- occupancies such as banks, hotels, maintained in compliance with this •v,'- shopping malls, etc document, as well as with the applica- ble standards of the National Fire Pro - The recessed version of the Series tection Association, in addition to the - TY-FRB Pendent Sprinkler, where ap- standards of any other authorities hay- plicable, is intended for use in areas ing jurisdiction. Failure to do so may with a finished ceiling It uses either a impair the inteariry of these devices ._: - two -piece Style 10 (1/2 inch NPT) or `" ` t f' :: << `* Style 40 (3/4 inch NP Recessed Es- The owner is responsible for maintain - cutcheon with 1/2 inch (12,7 mm) of ing their fire protection system and de- ... ,.: t, recessed adjustment or up to 3/4 inch vices In proper operating condition. ' `t: '`-' ' - (19,1 mm) of total adjustment from the p • Th installing contractor or s rinkler "a''I flush pendent position. or a two -piece manufacturer should be contacted � ' - Style 20 (1/2 inch NPT) or Style 30 (3/4 relative to any questions '4- ` . ,' inch NPT) Recessed Escutcheon with , ,; .,,,, 1/4 inch (6,4 mm) of recessed adjust- ment or up to 1/2 inch (12,7 mm) of Model /Sprinkler Maximum Working Pressure total adjustment from the flush pen- dent position. The adjustment provided Identification 175 psi (12,1 bar) by the Recessed Escutcheon reduces Discharge Coefficient the accuracy to which the fixed pipe Numbers K = 2 8 GPM /psi (40 3 LPM /bar drops to the sprinklers must be cut. K = 4.2 GPM /psi (60.5 LPM /bar Corrosion resistant coatings. where TY1131 - Upright 2.8K, 1/2 "NPT K = 5.6 GPM /psi (80,6 LPM /bar applicable, -are utilized to extend the TY1231 - Pendent 2.8K. 1/2 "NPT K = 8.0 GPM /psi (115,2 LPM /bar ) life of copper alloy sprinklers beyond TY2131 - Upright 4.2K, 1/2 "NPT Temperature Ratings that which would otherwise be ob- TY2231 - Pendent 4.2K, 1/2 "NPT Refer to Table A and B tained when exposed to corrosive at- TY3131 - Upright 5.6K. 1/2 "NPT . mospheres Although corrosion rests- TY3231 - Pendent 5.6K, 1/2 "NPT Finishes tant coated sprinklers have passed the TY4131 - Upright 8.0K, 3/4 "NPT Sprinkler Refer to Table A and B standard corrosion tests of the apple- TY4231 - Pendent 8.0K, 3/4 "NPT Recessed Escutcheon White Coated. = cable approval agencies the testing is Chrome Plated, or Brass Plated R. not representative of all possible cor- Technical rosive atmospheres Consequently, it Physical Characteristics is recommended that the end user be Data Frame . . Bronze r consulted with respect to the suitability Button . . . . • Brass /Copper °' of these coatinas for any given corro- Sealing Assembly S sive environment. The effects of ambi Approvals UL and C -UL Listed Beryllium Nickel wiTeflon s grit temperature, concentration of p Bulb . . • Glass c chemicals, and aaslchemical velocity, FM, L CB, and NYC Approved (Refer to Table A for complete approval Compression Screw Bronze o should be considered, as a minimum, information including corrosion rests Deflector Copper /Bronze c alone with the corrosive nature of the tent status ) Bushing 'K =2.8' 1 Bronze t Page 1 of 8 APRIL, 2003 TFP171 T Page 2 of 8 TFP171 ESCUTCHEON 7/16" (1 1 1 mm) STYLE 10 or 20 PLATE SEATING ** NOMINAL RECESSED SSU* SURFACE MAKE -IN ESCUTCHEON NPT DEFLECTOR 1 / . - 01"? 6 I 1 l - - 7/16" 5 2 -1/4" I ' (11,1 mm) I 4 (57.2 mm) ■ I I i mim NOMINAL I I gil _'_ItQ MAKE -IN I 2 II I 1- 9/16" _— 2 -3 %16 3 (39 7 mm) V WRENCH < (55.6 mm) tit FLATS t 1 `!/J� 1 t SSF DEFLECTOR * I -- 2 -7/8" (73.0 mm) DIA -,, 1/2 " NPT * " I PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulp 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame screw '* Pipe thread connections per ISO 7/1 can be provided on special request FIGURE 1 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY/ 131) AND PENDENT (TY1231) SPRINKLERS 2.8 K- FACTOR. 1/2 INCH NPT ESCUTCHEON 7/16" (11,1 mm) STYLE 10 or 20 PLATE SEATING 1/2 ** NOMINAL RECESSED SSU* SURFACE NPT MAKE -IN ESCUTCHEON DEFLECTOR I I 1 / 6 I _ _ / Gzr'i _��`w*" i ta��' f N& 1 / 7/16„ 5 2- 3/16" \ �— 11� „Jr.. (55,6 mm) 1 I 4 NOMINAL ' Q MAK -IN _ pr 1 -1/2" I I 2 -3/1 6" " TO 2 (38,1 mm) I WRENCH t (55,6 mm) 0 ( 3 FLATS -- 1 1 1 1 1 SSP DEFLECTOR - 2 -7/8" (73,0 mm) DIA 1/2" NPT ** I PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing z - Bulb 6 - Deflector * Temperature sating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame, Screw ** Pipe thread connections per ISO 7/1 can be provided on special request FIGURE 2 . QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS 4.2 K- FACTOR, 1/2 INCH NPT -. .r ' TFP1 71 Page 3 of 8 . ESCUTCHEON 7/16' (11,1 mm) STYLE 10 or 20 PLATE SEATING 1/2 * NOMINAL RECESSED SaU' SURFACE MAKE -IN ESCUTCHEON NPT DEFLECTOR t 1 T I' / 1 I 7/16' j x; 2 -3/16" �� "� (11,1 mm) (55.6 mm) ■ I I I ■ 1 = NOMINAL 1 , 4 I AIM MAKE -IN w r 1- 1/2 " - 2 2 3/16" -..., ' A (38,1 mm) j j WRENCH 1 (55.6 mm) 4 FLATS 1 1 / 2-7/8" (73,0 mm) -�, 1/2" NPT I SSP DEFLECTOR �— " ( ) DIA PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature retina is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame Screw ** Pipe thread connections per ISO 7/1 can be provided on special request FIGURE 3 . QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS 5.6 K- FACTOR. 1/2 INCH NPT ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40 PLATE SEATING .,.* NOMINAL RECESSED SURFACE 3/4 MAKE -IN ESCUTCHEON SSU* NPT DEFLECTOR I / ■ \ — ________ — / � � 1/2 I S 2 5/16" \ 1 - ' � l (12,7 mm) (58,7 mm) l I ■ I NOMINAL 4 MAKE -IN itt. , 1-9/16" 2 1/4" 2 I (39,7 mm) WRENCH (57,21 mm) 1 j kl [ FLATS — 3 y �,. / ) 1 SSP DEFLECTOR* 2-7/8" (73,0 mm) DIA, 3/4" NPT PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION 1 - Prame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature ratino is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame Screw ** Pipe thread connections per ISO 7/1 can be provided on special request FIGURE 4 QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS 8.0 K- FACTOR. 3/4 INCH NPT Listing is based on the requirements of Operation Design NFPA 13, and FM Approval is based on the requirements of FM's Loss Pre - The glass Bulb contains a fluid which Criteria vention Data Sheets ). Only the Style expands when exposed to heat When 10, 20, 30, or 40 Recessed Escutch- the rated temperature is reached, the Tne Series TY -FRB Pendent and Up- eon, as applicable. is to be used for fluid expands sufficiently to shatter the right Sprinklers are intended for fire recessed pendent installations class Bulb, allowing the sprinkler to protection systems designed in ac- activate and water to flow cordance with the standard installation rules recognized by the applicable Listing or Approval agency (e.g. UL Page 4 of 8 TFP171 - SPRINKLER FINISH (See Note 7) Installation K TYPE TEMP. BULB NATURAL CHROME WHITE'**` LIQUID BRASS PLATED POLYESTER The Series TY -FRB Sprinklers must be Installed in accordance with the follow- 135°F/57°C Orange ins instructions PENDENT 155 °F /68 °C Red (TY1231) 1 2, 3, 5 NOTES and 175Fi79°C Yellow Do not install any bulb type sprinkler if UPRIGHT 200 °F /93 °C Green the bulb is cracked or there is a loss of (TY1131) liquid from the bulb With the sprinkler 28 286 °F /141 °C Blue held horizontally. a small air bubble 1/2" should be present The diameter of the - NPT 135 °F /57 °C Orange air bubble is approximately 06 inch RECESSED 155 °F /68 °C Red (1,6 mm) for the 135 °P /57 °C to 3/32 PENDENT inch (2.4 mm) for the 286 °F /141 °C (TY2231)* 175 °F /79 °C Yellow temperature ratings. Figure 5 200°F /93 °C Green 1, 2 5 A leak tight 1/2 inch NPT sprinkler joint 135 °F /57 °C Orange should be obtained with a torque of 7 RECESSED _ 14 ft.lbs (9.5 to 19.0 Nm). A maxi - 15 °F /68 °C Red mum of 21 ft. lbs. (28.5 Nm) of torque TY2231 PENDENT may be used to install sprinklers with 7 � °F/79 °C Yellow ( ) ** 1 , 1/2 NPT connections. A leak tignt 3/4 Figure 6 200F/93°C Green inch NPT sprinkler joint should be ob- 135°F/57°C Orange tarried with a torque of 10 to 20 ft.lbs - PENDENT (13.4 to 26.8 Nm). A maximum of 30 (TY2231) 1 ° °F/68° Red ft.lbs. (40,7 Nm) of torque is to be used and - 175 °F /79 °C Yellow to install sprinklers with 3/4 NPT con- nections. Higher levels of torque may UPRIGHT 200 °F /93 °C Green distort the sprinkler inlet and cause 4 9 (TY3131) 286 °F /141 °C Blue leakage or impairment of the sprinkler. 1/2" 1 2" 9 NPT 135°F/57°C Orange Do not attempt to make -up for insuffi- RECESSED ' cient adjustment in the escutcheon 155 °F /68 °C Red (TY2231)* 175 °Fr7 o °C Yellow plate by under or over - tightening the PENDENT sprinkler. Readjust the position of the sprinkler fitting to suit. Figure 7 200.F/93°C Green The Series TY -FRB Pendent and Up- 135F/57°C Orange right Sprinklers must be installed in RECESSED 155FI68°C Red accordance with the following instruc- PENDENT tions. (TY2231) ** 175 °F 79 °C Yellow Step 1. Pendent sprinklers are to be Figure 8 200 °F /93 °C Green installed in the pendent position, and upright sprinklers are to be installed in NOTES: the upright position 1 Listed by Underwriters Laboratories Inc (UL) as Quick Response Sprinklers Step 2. With pipe thread sealant a 2 Listed by Underwriters Laboratories. Inc for use in Canada (C -UL) as Quick Response P P P P Sprinklers plied to the pipe threads, hand tighten 3 Approved by Factory Mutual Research Corporation (FM) as Quick Response Spnn the sprinkler into the sprinkler fitting. klers Step 3. Tighten the sprinkler into the 5 Approved by the City of New York under MEA 354 -01 -E sprinkler fitting using only the W - Type 7 Where Polyester Coated Sprinklers are noted to be DL and C -UL Listed the sprin sprinkler Sprinkler Wrench (Ref. Figure 13) klers are UL and C Listed as Corrosion Resistant Sprinklers Figures 1 i F reference t fer to g 2, 3. and Installed with Style 10 (112" NPT) or Style 40 (3 NPT) 3/4" Total Adjustment Re - 4, the With re e ft enc 6 o F i g urer Wrench is to cessed Escutcheon, as applicable " Installed with Style 20 (1/2" NPT) or Style 30 (314" NPT) 1/2" Total Adjustment Re- be applied to the sprinkler wrench cessed Escutcheon as applicable flats "" Frame and Deflector only Listings and approvals apply to all colors (Special Order) N/A• Not Available The Series TY -FRB Recessed Pen- -, dent Sprinklers must be installed in TABLE A accordance with the following instruc -' LABORATORY LISTINGS AND APPROVALS tions 2,8 AND 4.2 K- FACTOR SPRINKLERS Step A. After installing the Style 10 20. 30, or 40 Mounting Plate, as appli- - cable, over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand tighten the sprin- kler into the sprinkler fitting. Step B. Tighten the sprinkler into the 4 TFPI 71 Page 5 of 8 SPRINKLER FINISH (See Note 7) K TYPE TEMP BULB NATURAL CHROME WHITE *** LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange PENDENT 155 °F /68 °C Red (TY3231) 1. 2 3, 4, 5, 6 1 2 3, 5 and 175 °F /79 °C Yellow UPRIGHT 200 °F /93 °C Green (TY3131) 5 6 286 °F /141 °C Blue 112 NPT 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1 2, 4 5 N/A (TY3231)' 175 °F /79 °C Yellow Figure 9 200 °F /93 °C Green 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1 . 2, 3, 4 , 5 1 , 2. 4, 5 N/A (TY3231)* 175 °F /79 °C Yellow Figure 10 200 °F /93 °C Green 135 °F /57 °C Orange PENDENT 15Ef/68 °C Red (TY4231) 1, 2, 5 and 175 °F /79 °C Yellow 1 2, 3, 4, 5, 6 UPRIGHT 200 °F /93 °C Green 8 0 (TY4131) 286 °F /141 °C Blue 3/4" NPT 135 °F /57 °C Green RECESSED 155 °F /68 °C Orange PENDENT 1 , 2, 4, 5 N/A (TY4231)' 175 °F /79 °C Red Figure 11 200 °F /93 °C Yellow 135 °F /57 °C Orange RECESSED 155 °F /68 °C Red PENDENT 1 2, 3, 4. 5 N/A (TY4231)** 175 °F79 °C Yellow Figure 12 200 °F /93 °C Green NOTES: - 1 Listed by Underwriters Laboratories, Inc (UL) as Quick Response Sprinklers 2 Listed by Underwriters Laboratories Inc for use in Canada (C -UL) as Quick Response Sprinklers 3 Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers 4 Approved by the Loss Prevention Certification Board (LPCB) as Quick Response Sprinklers, however, the LPC does not rate the thermal sensitivity of recessed sprinklers 5 Approved by the City of New York under MEA 354 -01 -E 6 VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands. Tel 31 -53 -428 -4444 /Fax 31 -53- 428 -3377) 7 Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion Resistant Sprinklers Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 314" Total Adjustment Recessed Escutcheon, as applicable " Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2' Total Adjustment Recessed Escutcheon as applicable Frame and Deflector only Listings and approvals apply to all colors (Special Oroer) N/A Not Available TABLE B LABORATORY LISTINGS AND APPROVALS 5.6 AND 8.0 K- FACTOR SPRINKLERS sprinkler fitting using only the W -Type Step C. After the ceiling has been in- - 7 Recessed Sprinkler Wrench (Ref stalled or the finish coat has been ap- Figure 14). With reference to Figure 1, plied, slide on the Style 10, 20, 30, or 2, 3. and 4, the W -Type 7 Recessed 40 Closure over the Series TY -FRB Sprinkler Wrench is to be applied to Sprinkler and push the Closure over • the sprinkler wrench flats, the Mounting Plate until its flange comes in contact with the ceiling. , lI Page 6 of 8 TFP1 71 2 - /8" DIA _ , 2 -7/8" DIG , 4 73 0 mm) I (73.0 mm) 5/8 -1/ ( 3/" (191 mm) 112=1/E' 1/2" (12. mm) j (15Gx8 2-1/ DIA 1 / c ' . ) . 6,4 mm) [ )127_3.2 mm) 1 2-1/4” Dip, i 1 /"16 mm) 1 , FACE OF ( ) MOUNTING FACE OF -- 1 I MOUNTING SPRINKLER \ � PLATE SPRINKLER 1 \ PLATE FITTING -- FITTWG / F / 1/8" / 1/8" _ mm) I vim \ �� � 1 t 1 MOUNTING / \ MOUNTING SURFACE \ ' SURFACE/ /i ,may _ 1 / COT E \ ! CLOSURE SERIES 1-5/16" (33 3 mm), CLOSURE SERIES 1- 5/16" (33.3 mm)i TY -FRB 13/16" (206 mm) TY -FRB 1- 1/16" (27.0 mm) FIGURE 5 FIGURE 6 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 2.8 K- FACTOR, 1/2 INCH NPT 2.8 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA 2 -7/8" DIA 1 (73 0 mm) 5/8E1/4' (73,0 mm) 3/�" (19,1 mm) 1/26.1/8" 1 1/2" (12 7 mm) (1.6.9.±6, mm) _ 2 -1/4" DIA 1/4" (6 mm) (12,7±3.2 mm) �- 2 -1 /�" DIA i 1/ (6. mm) i FACE OF (57.2 mm) MOUNTING FACE OF (57,2 mm) 1 MOUNTING. SPRINKLER \ / ' PLATE SPRINKLER i PLATE FITTING TING FIT - 1 / 1/8" / I 1/8" / a, (3 2 mm) I l I (` 2 mm) T ! \ t , � t t MOUNTING MOUNTING 1 SURFACE li ) SURFACE /I SERIES 1 -1/4" (Si a mm) SERIES 1-1/4' (31 8 mm) CLOSURE CLOSURE TY-FRB TY -FRB 3/4" (19,1 mm) 1" (25 C mm) . FIGURE 7 FIGURE 8 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 4.2 K- FACTOR, 1/2 INCH NPT 4.2 K- FACTOR, 1/2 INCH NPT used to cover a clearance hole, may and after installation Sprinklers dam - C are and delay the time to spnnkler operation in aged by dropping, striking, wrench a fire situation, twist/slippage, or the like, must be re- Maintenance Sprinklers that are found to be leaking placed. as a replace e any sprinkler kler that The Series TY -FRB Sprinklers must be or exhibiting visible signs of corrosion liquid from its bulb (Ref installation - maintained and serviced in accord- must be replaced. Section), ance with the following instructions: Automatic sprinklers must never be Frequent visual inspections are roc painted, plated, coated or otherwise ommended to be initially performed for NOTES altered after leaving the factory Modi corrosion resistant coated sprinklers, Before closing a fire protection system fled sprinklers must be replaced. af the installation has been corn- er main control valve for maintenance Sprinklers that have beer, exposed to after ed , to verify the intearity of the cot work on the fire protection system that corrosive products of combustion, but platter resistant coating Thereafter, It controls, permission to shut down the have not operated, should be replaced annual Inspections per NFPA 25 • affected fire protection system must be if they cannot be completely cleaned should suffice, however, instead of in obtained from the proper authorities by wiping the sprinkler with a cloth or s h o uld g from the floor level, instead random and all personnel who maybe affected by brushing it with a soft bristle brush sampling of close -up visual inspec- by this action must be notified. Care must be exercised to avoid darn- tions should be made, so as to better Absence of an escutcheon, which is age to the sprinklers - before, during, determine the exact sprinkler condi- V. , TFP171 Page 7 of 8 2 -7/8" DI 2 -7/8' DIA (73 (7 mm) 5/8.1/2' I Omm) 3 �„ (i9,1 mm) 112.1/8" I 112» (12,7 mm) (159±6, mm) i 2 -1/2" DIA 1/t' (6,c mm) I (12 7.3.2 mm) , 2 -1 /L" DIA 1 1 /L" (6 2171 ■1 ∎ (572 mm) FACE OF —.- (07 2 mm) -� MOUNTING =ACE OF 1 —' MOUNTING SPRINKLER t / i PLAT SPRINKLER \ / PLATE Fi i ING E i ING ( � i / r / 1/6" 'I � ^ 1 1/8' 1 AMP i5 2 mm; I (3 2 mm) � � f 1 I l l MOUNTING MOUNTING SURFACE/ i ) SURFACE 1 / SERIES 4" (31 8 mm) CLOSURE SERIES 1 -1 / (31 8 mm) CLOSURE TY -FRE 3/4" (19.1 mm) TY-FRE (25,4 mm) FIGURE 9 FIGURE 10 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON STYLE 20 RECESSED ESCUTCHEON 5.6 K- FACTOR, 1/2 INCH NPT 5.6 K- FACTOR, 1/2 INCH NPT 2 -7/8" DIA i..._ 2 -7/8" DIA (73 0 mm) 3/ (19,1 mm) (73 0 mm) 1/2" (12 7 mm) 5/8.1/4" 1/2.1/8' (159±6 d mm) 2 - 1/ 2 " DIA 1/4" (6 mm) (12 7.3.2 mm) , 2 -1 /" DIA 1 1/ (6,4 mm) (57.2 mm) (672 mm) M OUNTING FACE OF M OUNTING FACE OF �i -- PLATE SPRINKLER ' ATE • SPRINKLER \ FITTING /' FITTING r I 8" II I 1 /8" 7 l ( �� I - ='� �� (3,2 mm) t 1 mm) �� (3,2 ' / ,, /, 1 I / / /- _I- I l I \ _ — l l MOUNTING / I SURFACE SURFACE 1 SURCE ! t / / CLOSURE SERIES 1-5/16" (33,3 mm)1, CLOSURE SERIES 1- 5/16" (33.3 mm) TY -FRB 13/16" (20 6 mm) TY-FRB 1-1/16' (27 0 mm) FIGURE 11 FIGURE 12 SERIES TY -FRB RECESSED PENDENT SERIES TY -FRB RECESSED PENDENT WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON STYLE 30 RECESSED ESCUTCHEON 8.0 K- FACTOR, 3/4 INCH NPT 8.0 K- FACTOR, 3/4 INCH NPT tion and the long term integrity of the corrosion resistant coating, as it may WRENCH be affected by the corrosive conditions ' RECESS present. \ , WRENCH RECESS The owner is responsible for the in- (E "A" USED FOR J-! �I spection, testing, and maintenance of tl2' NPT MODELS) � �� / their fire protection system and de- \ vices in compliance with this docu- % ment, as well as with the applicable standards of the National Fire Protec- WRENCH RECESS PUSH WRENCH tion Association (e g , NFPA 25), in (END "B" USED FOR INTO ENSURE addition to the standards of any other 3)2" NPT MODELS) ENGAGEMENT authorities having jurisdiction The in- WITH SPRINKLER stalling contractor or sprinkler manu- FIGURE 13 WRENCHING AREA facturer should be contacted relative to W -TYPE 6 SPRINKLER ' any questions WRENCH It is recommended that automatic FIGURE 14 sprinkler systems be inspected. W-TYPE 7 RECESSED . tested, and maintained by a qualified SPRINKLER WRENCH Inspection Service Page 8 of 8 TFP171 P/N 57 - XXX - X - XXX I I TEMPERATURE MODEL/SIN RATING SPRINKLER 330 2 8K UPRIGHT (1/2 "NPT) TY 1131 135 135 °F /57 °C 331 2 8K PENDENT (1/2 "NPT) TY1231 1 NATURAL BRASS 155 155 °F /68 °C 340 4.2K UPRIGHT (1/2 "NPT) TY213 i c WHITE POLYESTER 175 175 °F /79 °C . 341 C 2K PENDENT (1/2 "NPT) TY2231 9 CHROME PLATED 200 200 °F /93 °C 370 5 6K UPRIGHT (1/2 "NPT) TY3131 7 LEAD COATED 286 286 °F /141 °C 371 5 6K PENDENT (1/2 "NPT) TY3231 390 8 OK UPRIGHT (3/4 "NPT) TY4131 391 8 OK PENDENT (3/4 "NPT) TY4231 TABLE C PART NUMBER SELECTION SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS Limited ORY, FOR INCIDENTAL. INDIRECT, cutcheon with (specify finish), P/N SPECIAL OR CONSEQUENTIAL (specify). DAMAGES, INCLUDING BUT NOT Warranty LIMITED TO LABOR CHARGES, RE- 1/2' (15 mm) GARDLESS OF WHETHER TYCO style 10 Products manufactured by Tyco Fire FIRE Cnrome Plated P/N 56 -701 -9 -010 P c y y IRS PRODUCTS WAS INFORMED 1/2" (15 mm Products are warranted solely to the ABOUT THE POSSIBILITY OF SUCH Style 10 original Buyer for ten (10) years DAMAGES, AND IN NO EVENT Wnne Color • against defects in material and work- SHALL TYCO FIRE PRODUCTS LI- Coated P/N 56 -70 - -010 manship when paid for and properly ABILITY EXCEED AN AMOUNT 1/2" (15 mm) Style 10 installed and maintained under normal EQUAL TO THE SALES PRICE, Brass Plated P/N 56- 701 -2 -010 use and service. This warranty will ex THE FOREGOING WARRANTY IS v2 (15 mm) pire ten (10) years from date of ship- stye 20 ment by Tyco Fire Products. No war- MADE IN LIEU OF ANY AND ALL Chrome Plaice P/N 56 -705 -9 -010 ant s given for products or OTHER WARRANTIES EXPRESS OR 1/2' (15 y P IMPLIED. INCLUDING WARRANTIES Style 20 components manufactured by compa- Whne Color nies not affiliated by ownership with OF MERCHANTABILITY AND FIT- Coated P/N 56- 705 - -010 Tyco Fire Products or for products and NESS FOR A PARTICULAR PUP- 1/2" (15 mm) components which have been subject POSE Style 20 installation, corro- Brass Plated P/N 56-705-2-010 10 to misuse, improper 3/�" (20 mm) lion, or which have not been installed, Style 30 maintained, modified or repaired in ac- Ordering Chrome Plated P/N 55- 705 -9 -011 cordance with applicable Standards of Ordering 3/4" (20 mm) the National Fire Protection Associa- Procedure Style 30 Wnne Color Lion, and /or the standards of any other Coated P/N 56- 705 - -011 Authorities Having Jurisdiction Mate- When placing an order, indicate the full 3/2" (20 mm) rials found by Tyco Fire Products to be product name. Refer to the Price List style. 30 defective shall be either repaired or P Brass Plated P/N 56- 705 -2 -011 P for complete listing of Part Numbers. 3/ (20 mm) - replaced, at Tyco Fire Products' sole Style ao option Tyco Fire Products neither as- Contact your local distributor for avail- Cnrome 40 Plated P/N 56a00-9 -010 sumes, nor authorizes any person to ability. 3/4" (20 mm) assume for it, any other obligation in Style 40 connection with the sale of products or Sprinkler Assemblies with NPT Wnne Color parts of products, Tyco Fir., Products Thread Connections: Coated, P/N 55- 700 - -010 shall not be responsible for sprinkler Specfy (Specify Model/SIN), (20 mm) SIN), Quick Style 40 system design errors or inaccurate or Response, (specify K- factor), (specify Brass Plated P/N 56 -700 -2 -010 incomplete information supplied by temperature rating), Series TY -FRB Buyer or Buyer's representatives (specify Pendent or Upright) Sprinkler Sprinkler Wrench: with (specify type of finish or coating), Specify: W -Type 6 Sprinkler Wrench, IN NO EVENT SHALL TYCO FIRE P/N (specify from Table C) P/N 56 -000 -6 -387. PRODUCTS BE LIABLE. IN CON- TRACT, TORT, STRICT LIABILITY OR Recessed Escutcheon: Specify: W -Type 7 Sprinkler Wrench, - UNDER ANY OTHER LEGAL THE- Specify, Style (specify) Recessed E P/N 56- 850 - -001 TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 /\ /As7\ Fire tLJCO& Building Products Customer Service /Sales: Technical Services: Tel: (800) 381 -9312 / Fax' (800) 791 -5500 Tei• (414) 570 -5000 / (800) 558 -5236 Fax. (414) 570-5010/ (800) 877 -1295 Series EC-11 — 11.2 and K-factor Extended Coverage (Light andeenikimply Hazard) Upright, Pendent, and Rec® Pendent Sprinklers Corrosion resistant coatings. where - General applicable, are utilized to extend the life of copper alloy sprinklers beyond Description that which would otherwise be ob 0,...4„.,=.7..-:-:. - tamed when exposed to corrosive at . - The Series EC -11 and EC -14 Ex- mospheres, Although corrosion resis- 4 . T �`' tended Coverage Upright and Pendent tant coated sprinklers have passed the . r Sprinklers are decorative glass bulb standard corrosion tests of the apple t sprinklers designed for use in light or cable approval agencies, the testing is ,, ordinary Y hazard occupancies. They not representative of all possible cor r ._ are intended for use in automatic rosive atmospheres. Consequently it " s sprinkler systems designed in accord � P Y is recommended that the end user be ,-,, • ance with standard installation rules consulted with respect to the suitability " (e.g., NFPA 13) for a maximum cover- _ of these corrosion resistant coatings age area of 400 ft (37,2 m as corn- for any given corrosive environment, pared to the maximum coverage area The effects of ambient temperature, of 130 ft (12,1 m for standard cover- concentration of chemicals, and age sprinklers used in ordinary haz- gas /chemical velocity, should be con - and occupancies or 225 ft (20,6 m sidered, as a minimum, along with the .yOrtilM. for standard coverage sprinklers used corrosive nature of the chemical to k in light hazard occupancies. which the sprinklers will be exposed. °' ' ', The Series EC 11 and EC 14 Sprin ,= klers feature a UL and C UL Listing WARNIN , ,, , ,W: 1 4t* ,- 2 ,1, - , -;-‘4 , risl.:-. that permits their use with unob The Series EC -11 and EC -74 Ex - tended Coverage Sprinklers described '= S structed or non - combustible ob- g p herein must be installed and main- .� � structed ceiling construction as de- -. 1 , fined and permitted by NFPA 13, as tamed in compliance with this docu well as a specific application listing for merit as well as with the applicable R ' use under concrete tees. standards of the National Fire Prote .< , tion Association, in addition to the The Series EC -11 and EC -14 Ex- standards of any otherauthorities hay- tended Coverage Sprinklers have ing jurisdiction. Failure to do so may been fire tested to compare their per- impair the integrity of these devices. spray formance sp to that of standard coverage The owner is responsible for maintain Model/Sprinkler spray sprinklers. These tests have p shown that the protection provided is ing their fire protection system and de- equal to or more effective than stand- vices in proper operating condition. Identification and coverage spray sprinklers. The installing contractor or sprinkler manufacturer should be contacted Number relative to any questions. TY5137 - Upright, 11.2K IMPORTANT TY5237 - Pendent. 11.2K - Always refer to Technical Data TY6137 - Upright, 14.0K Sheet TFP700 for the `INSTALLER TY6237 - Pendent.14.0K WARNING" that provides cautions TY5137 is a redesignation for C5137, with respect to handling and instal- G1894, and redes S2510. 9 lation of sprinkler systems and com- ponents. Improper handling and in- TY5237 is a redesignation for C stallation can permanently damage G1893, and S2511. a sprinkler system or its compo- nents and cause the sprinkler to fail G1896, and redesignation to operate in a fire situation or cause it to operate prematurely. TY6237 is a redesignation for C6237, G1895. and 32611. Page 1 of 8 FEBRUARY, 2004 TFP220 Page 2 of 8 TFP220 WRENCH 3/4" ** ESCUTCHEON PLATE - FLAT NPT SEATING SURFACE i ' - Frame 1 2 - Button zpree - oF 1n i jir 3 - Sealing Assembly ' 9 4 - Bulb 5 - Compression Screw �-- 6 - Deflector` 2 1 %� At 3 • (61.9 mm) ' Temperature rating is I UPRIGHT & indicated on deflector I I PENDENT I 1 - 1.1/16" r 4 Pipe tnread { (42.7 mm) connections per ISO s. • 7/1 can be provided ��� on special request � - ._ .. , ..___ __.._� t _ • _ --_. i \ ` 6 * 1/2" (12.7 mm) _I NOMINAL MAKE -IN CROSS UPRIGHT PENDENT SECTION FIGURE 1 SERIES EC -11 AND EC -14 EXTENDED COVERAGE SPRINKLERS 11.2 K- FACTOR (TY5137) UPRIGHT AND (TY5237) PENDENT 14.0 K- FACTOR (TY6137) UPRIGHT AND (TY6237) PENDENT SPRINKLER FINISH (See Note 5) - HAZARD TYPE TEMP. BULB NATURAL CHROME WHITE* LEAD LIQUID BRASS PLATED POLYESTER COATED 135 °F /57 °C Orange UPRIGHT 155 Red 1, 2, 3 *', 4 L K =11.2 (TY5137) . PENDENT 175 °F /79 °C Yellow K =11.2 (TY5237) 200 °F /93 °C Green 1. 2, 4 1, 2, 4 Refer to Table B for K =14.0 (TY6237) UL and C -UL 286°F/141°C Blue Sensitivity Rating 135 °F /57 °C Orange and REC. PENDENT 155 °F /68 °C Red 1. 2, 3, 4 Refer to Table C for K =11.2 (TY5237) N/A FM K =14.0 (TY6237) 175 °F /79 °C Yellow Sensitivity Rating With Style 30 200 °F /93 °C Green 1, 2, 4 Escutcheon 286°F/141°C Blue UPRIGHT 135 °F /57 °C Orange K =11.2 (TY5137) 155 °F /68 °C Red 1, 2, 3, 4 ORDINARY K =14.0 (TY6137) 1 2 3 4 and 175 °F /79 °C Yellow Refer to Table B for PENDENT 200 °F /93 °C Green 1, 2, 4 UL and C -UL K =11.2 (TY5237) Sensitivity Rating K =14.0 (TY6237) 286°F/141°C Blue and REC. PENDENT 135 °F /57 °C Orange Refer to Table C for K =11.2 (TY5237) 155 °F /68 °C Red FM K =14.0 (TY6237) , Sensitivity Rating With Style 40 175 °F /79 °C Yellow 1, 2 4 N/A Escutcheon 200 Green NOTES: 1.Listed by Underwriters Laboratories. Inc. (UL) 2.Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL). 3 Approved by Factory Mutual Research Corporation (FM). 4 Approved by the City of New York under MEA 177 -03 -E 5 Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C -UL Listed the sprinklers are UL and C -UL Listed as Corrosion Resistant Sprinklers 'Frame and Deflector only Listings and approvals apply to color (Special Order) — Pendent Only. N /A: Not Available TABLE A, LABORATORY LISTINGS AND APPROVALS TFP220 Page 3 of 8 LIGHT HAZARD ORDINARY HAZARD 135 °F 155 °F 175 °F 200 °F 286 °F 135 °F 155 °F 175 °F 200 °F 286 °F AREA STYLE 14 x 14 Up or Pend — — — — — SR SR SR SR SR 14 x 14 Style 30 Recessed — — — — — SR SR SR SR N/A 14 x 14 Style 40 Recessed — — — — — SR SR SR SR N/A 16 x 16 Up. or Pend. OR' OR* OR' OR' OR' SR SR SR SR SR ' 16 x 16 Style 30 Recessed QR' OR' OR' OR' OR' SR SR SR SR N/A 16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR N/A 18 x 18 Up. or Pend OR' OR° OR' OR' OR' SR SR SR SR SR 18 x 18 Style 30 Recessed - OR' OR' OR" OR' OR' SR SR SR SR N/A 18 x 18 Style 40 Recessed N /A. N/A N/A N/A N/A SR SR SR SR N/A 20 x 20 Up. or Pend OR' OR' OR" SR' SR" SR SR SR SR SR 20 x 20 Style 30 Recessed OR' SR' QR' SR" SR' SR SR SR SR N/A 20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR N/A OR Quick Response SR Standard Response N /A. Not Applicable ' Does not apply to Upright K = 14.0 TABLE B SENSITIVITY RATING FOR UL AND C -UL LISTING OF SERIES EC -11 OR EC -14 SPRINKLERS (SEE TABLE D FOR PERMITTED K- FACTOR/AREA COMBINATIONS) LIGHT HAZARD ORDINARY HAZARD 135 °F 155 °F 175 °F 200 °F 286 °F 135 °F 155 °F 175 °F 200 °F 286 °F AREA STYLE 14 x 14 Up or Pend — — — — — SR SR SR SR SR 14 x 14 Style 30 Recessed — — — — — N/A N/A N/A N/A N/A 14 x 14 Style 40 Recessed — — — — — N/A N/A N/A N/A N/A 16 x 16 Up. or Pend QR' QR' N/A N /A. N/A SR SR SR SR SR 16 x 16 Style 30 Recessed OR OR N/A N/A N/A N/A N/A N/A N/A N/A 16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 18 x 18 Up or Pend OR' OR' N/A N/A N/A SR SR SR SR SR 18 x 18 Style 30 Recessed OR QR NIA N/A N/A N/A N/A N/A N/A N/A 18 x 18 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 20 x 20 Up. or Pend OR' OR' N/A N/A N/A SR SR SR SR SR 20 x 20 Style 30 Recessed QR OR N/A N/A N/A N/A N/A N/A N/A N/A 20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A QR. Quick Response SR: Standard Response N /A: Not Applicable ' Pendent Only TABLE C -, SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC 11 OR EC -14 SPRINKLERS (SEE FM LOSS PREVENTION DATA SHEET 2 -BN FOR PERMITTED K- FACTOR/AREA COMBINATIONS) Page 4 of 8 TFP220 ® recessed installation, as applicable does not exceed 32 feet (9,8 m) in • Technical (Ref Table A. B, and C). length D ata UL and C -UL Listing 2. The sprinkler deflectors are to be Requirements located in a horizontal plane at or Approvals above 1 inch (25,4 mm) below the UL and C -UL Listed. FM Approved 1. The Series EC -11 and EC -14 Spnn- bottom of the concrete tee stems. (Refer -to Table A for complete approval klers may be used for the coverage information including corrosion resis- areas shown in Table D, based on 3 When the sprinkler deflectors are tent status. The approvals apply to the maintaining the minimum specified located higher than a horizontal service conditions indicated in the De- flow rate as a function of coverage plane 1 inch (251,4 mm) beneath the sign Criteria section.) area and hazard group for all of the bottom of the concrete tee stems, sprinklers in the design area. the obstruction to sprinkler dis- Maximum Working Pressure charge criteria requirements of 175 psi (12,1 bar) 2. With respect to heat sensitivity, the NFPA 13 for extended coverage up Pipe Thread Connection Series EC-11 and EC 14 Sprinklers naht sprinklers applies. 3/4 inch NPT are permitted to be used with unob- structed or non - combustible ob- FM Approval Discharge Coefficients structed ceiling construction as de- Requirements K.= 11 .2 GPM /psi fined and permitted by NFPA 13. For The Series EC-11 and EC 14 Ex (161.3 LPM /bar example• K = 14.0 GPM /psi1i2 tended Coverage Sprinklers are to be (201 LPM /barli Unobstructed, combustible or non- installed in accordance with the appli- combustible, ceiling construction cable Factory Mutual Loss Prevention Temperature Ratings ° with a deflector to ceiling/roof deck Data Sheet for limited use in buildings 135 °F /57 °C to 286°F/141 °C distance of 1 to 12 inches (25 to 300 of specific roof construction and for the Finish mm) protection of certain specific ordinary Sprinkler Refer to Table A hazard (non- storage and /or non -flam- Recessed Escutcheon: White Coated, Obstructed, noncombustible, ceiling mable or combustible liquid) occupan Chrome Plated, and Brass Plated construction with a deflector location ties. Information provided in the FM below structural members of 1 to 6 Loss Prevention Data Sheets relate to, • Physical Characteristics inches (25 to 150 mm) and a maxi- but are not limited to, hydraulic design, Frame Bronze mum deflector to ceiling /roof deck ceiling slope and obstructions. mini - Button . . . . . . . . . Bronze distance of 22 inches (550 mm). mum and maximum allowable spat Sealing Assembly . . . . . , ing, and deflector -to ceiling distance Beryllium Nidkel w/Teflonf 3 . The minimum allowable spacing be- Bulb . . . . . . . Glass (3 mm dia.) tween the Series EC -11 and EC -14 Installation Compression Screw . . . . . . . Sprinklers, to prevent cold solder - Bronze ing, is 8 feet (2,4 m) for upright sprin- The Series EC-11 and EC -14 Sprin- Deflector . . . . . . . . . Brass klers and 9 feet (2,7 m) for pendent klers must be installed in accordance sprinklers. with the following instructions: Patents 4. The Series EC-11 and_EC- 14_Sprin- - NOTES U.S.A. Patent Numbers 5,366,022; klers are to be installed in accord 5.579, 846; 5.584.344; 5,609,21 1 ; Do not install any bulb type sprinkler if 5,862,994; and 5,865,256 are apple ante with all other requirements of the bulb is cracked or there is a loss of cable to the Series EC 11 and E014 NFPA 13 for extended coverage up- liquid from the bulb. With the sprinkler Sprinklers. Other patents are pending right and pendent sprinklers. held horizontally, a small air bubble with regard to other design features. should be present. The diameter of the UL and C -UL Specific Application air bubble is approximately 1/16 inch /� Listing Requirements For (1.6 mm) for the 135F/57°C to 3/32 Operation Installation Under Concrete Tees inch (2,4 mm) for the 286 °F /141 °C The Series EC -11 and EC -14 Ex- temoerature ratings. The glass bulb contains a fluid which tended Coverage Upright Sprinklers expands when exposed to heat When (TY5137 & TY6137) have a UL and A leak tight 3/4 inch NPT sprinkler joint the - rated temperature is reached, the C -UL Specific Application Listing for should be obtained with a torque of 10 . fluid expands sufficiently to shatter the use under concrete tees when in- to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi - glass bulb, which then allows the span- stalled as follows: mum of 30 ft.lbs. (40.7 Nm) of torque kler to activate and flow water. is to be used to install sprinklers. 1. The stems of the concrete tee con- Higher levels of torque may distort the . struction must spaced at less than sprinkler inlet with consequent leak - D esign 7.5 feet (2,3 m) on center but more age 'or impairment of the sprinkler. than 3 feet (0,9 m) on center The Do not attempt to compensate for in- Criteria depth of the concrete tees must not sufficient adjustment in an Escutcheon exceed 30 inches (762 mm). The Plate by under- or over - tightening the The Series EC -11 and EC -14 Ex- maximum permitted concrete tee Sprinkler. Read just the position of the tended Coverage Sprinklers must only length is 32 feet (9,8 m): however, sprinkler fitting to suit. be installed in accordance with the ap- where the concrete tee length ex- . plicable UL and C -UL Listing or FM ceeds 32 feet (9,8 m), non - combus- Step 1. The sprinkler must be installed Approval requirements as indicated tible baffles, equal in height to the with the deflector parallel to the mount - below. Only the Style 30 or 40 Re- depth of the tees. can be installed so ing surface. Pendent sprinklers must cessed Escutcheon is to be used for that the space between the tees be installed in the pendent position, . TFP220 Page 5 of 8 _ 2 -7/8' DIA. 1 "FITTING SIDE' 1/2 ±1/8" (73.0 mm) 1/2" (12.7 mm) TOWARDS SPRINKLER r (12,7=3.2 mm) 2 -1/4" DIA 1 1/4" (6,4 mm) FITTING • FACE OF (57.2 mm) SPRINKLER 1/8 FITTING (3.2 mm) / . -' Wriallti f WRENCH RECESS I. \ �— 1 —� 1 1 ..� (END 'A��) MOUNTING II 4 I SURFACE MOUNTING FIGURE 4 PLATE W - TYPE 3 SPRINKLER CLOSURE I WRENCH 1 -3/8" (34.9 mm) WRENCH 1-1/8" (28,6 mm) RECESS �`! FIGURE 2 _ I �► , SERIES EC -11 AND EC -14 RECESSED PENDENT SPRINKLER ASSEMBLY I WITH TWO -PIECE 1/2 INCH TOTAL ADJUSTMENT � � STYLE 30 RECESSED ESCUTCHEO 2 -7/8" DIA. ----. i I _ . . 5/8±1/4" (73,0 mm) 3/4" (19,1 mm) UM (15,9 ±6,4 mm) 2 -1/4" DIA. 1/4" (6,4 mm) WRENCH - LUGS FACE OF (57.2 mm) FIGURE 5 SPRINKLER 1/8 W 4 RECESSED FITTING (3,2 mm) SPRINKLER WRENCH and upright sprinklers must be in- _ I stalled in the upright position. 4 I Step 2. After installing the Style 30 or \ l 40 mounting plate (or other escutch MOUNTING �� MOUNTING eon, as applicable) over the sprinkler SURFACE PLATE pipe threads and with pipe thread sealant applied to the pipe threads, CLOSURE ._—.—. - _. hand tighten the sprinkler into the 1 -3/8" (34,9 mm) sprinkler fitting (22,2 mm) Step 3. Wrench tighten upright or pen- 7/8" ( ) dent sprinklers using only the W -Type FIGURE 3 3 (End A) Sprinkler Wrench. Wrench SERIES EC -11 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMB tighten the recessed pendent span WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT klers using only the W - Type 4 Sprinkler STYLE 40 RECESSED ESCUTCHEON Wrench The wrench recess of the plicable sprinkler wrench (Ref. Figure 4 and 5) is to be applied to the sprinkler wrench flats (Ref. Figure 1). Page 6 of 8 TFP220 • GROUPI GROUP II LIGHT HAZARD ORDINARY HAZARD ORDINARY HAZARD 0.10 GPM/FT 0.15 GPM /F/ 0.20 GPM/FT DESCRIPTION AREA GPM PSI GPM PSI GPM PSI TY5137 (K =11.2) UPRIGHT 14 x 14 - - 30 7.2 39 12.1 16 x 16 30 7.2 39 12.1 51 20.7 18 x 18 33 8.7 49 19.1 65 33.7 20 x 20 40 12.8 60 28.7 80 57.0 • TY5237 (K =11.2) PENDENT 14 x 14 - - 30 7.2 39 12 1 16 x 16 30 7.2 39 12.1 51 20.7 18 x 18 33 8.7 49 19.1 65 33.7 20 x 20 40 12.8 60 28.7 80 57.0 TY6137 (K =14.0) UPRIGHT 14 x 14 N/A N/A - - - - 16 x 16 N/A N/A 39 7.8 51 13.3 18 x 18 N/A N/A 49 12.3 65 21.6 20 x 20 N/A N/A 60 18.4 80 32.7 TY6237 (K =14.0) PENDENT 14 x 14 - - - - - - 16 x 16 37 7.0 39 7.8 51 13.3 - 18 x 18 37 7.0 49 12.3 65 21.6 20 x 20 40 8.2 60 18 4 80 32.7 1 ft = 0.3048 m 1 ff = 0.093 m 1 gpm = 3.785 fpm 1 psi = 0.06895 bar 1 gprn /ft = 40.74 mm /min TABLE D FLOW CRITERIA FOR UL AND C -UL LISTING OF SERIES EC-11 AND EC -14 SPRINKLERS Care and by brushing it with a soft bristle brush vices in compliance with this docu- Care must be exercised to avoid dam- ment, as well as with the applicable standards of the National Fire Protec- tvlaint- enance age to the sprinklers - before, during, tion Association (e.g., NFPA 25), in and after installation. Sprinklers dam addition to the standards of any other The Series EC -11 and EC -14 Sprin- aged by dropping, striking, wrench authorities having jurisdiction. The m klers must be maintained and serviced twist/slippage, or the like, must be re stalling contractor or sprinkler menu - in accordance with the following in- placed Also, replace any sprinkler that facturer should be contacted relative structions: has a cracked bulb or that has lost to any questions liquid from its bulb. (Ref installation NOTE Section). It is recommended that automatic Before closing a fire protection system sprinkler systems be inspected, 9 p Y Frequent visual inspections are rec- main control valve for maintenance ommended to be initially performed for Inspection Service. tested, and maintained b y a q ualified work on the fire protection system that corrosion resistant coated sprinkler's, p if controls, permission to shut down the after the installation has been corn- affected fire protection systems must pleted, to verify the integrity of the cor- be obtained from the proper author- rosion resistant coating. Thereafter, ties and all personnel who may be annual inspections per NFPA 25 affected by this action must be notified. should suffice; however, instead of in- Sprinklers that are found to be leaking specting from the floor level, a random or exhibiting visible signs of corrosion sampling of close -up visual inspec- must be replaced. tions should be made, so as to better determine the exact sprinkler condi- Automatic sprinklers must never be tion and the long term integrity of the painted, plated, coated, or otherwise corrosion resistant coating, as it may altered after leaving the factory. Modi- be affected by the corrosive conditions tied sprinklers must be replaced. present. Sprinklers that have been exposed to corrosive products of combustion, but The owner is responsible for the in- have not operated. should be replaces spection, resting, and maintenance of if they cannot be completely cleaned their fire protection system and de- by wiping the sprinkler with a cloth or TFP22O Page 7 of 8 Limited Ordering P/N 51 - AAA - B -CCC Warranty Procedure AAA = 893 (for TY5237 • Products manufactured by Tyco Fire When placing an order, indicate the full K11.2 Pendent) Products are warranted solely to the product name. Please specify the AAA = 894 (for TY5137 original Buyer for ten (10) years Sprinkler Identification Number (SIN), K11.2 Upright) against defects in material and work- quantity, and temperature rating. Refer AAA = 895 (for TY6237 manship when paid for and properly to the Price Llsi for complete listing of K14.0 Pendent) installed and maintained under normal Part Numbers. AAA = 896 (for TY6137 use and service. This warranty will ex Contact your local distributor for avail- n pire ten (10) years from date of ship- ability. K14.0 Upright g ht ) ment by Tyco Fire Products. No war- ranty is given for products or Sprinkler Assemblies with NPT B = 1 (for Natural Brass) components manufactured by compa Thread Connections: B = 3 (for White [RAL9010])` nies not affiliated by ownership with Specify. (specify SIN), (specify Tyco Fire Products or for products and p ( p y } (p e y K-Fac- B = 4 (for White Polyester) components which have been subject tor), (specify temperature rating), B = 7 (for Lead Coated to misuse, improper installation, corro (specify Pendent or Upright) Extended B = 9 (for Chrome Plated) sion, or which have not been installed, Coverage Sprinkler with (specify fin maintained, modified or repaired in ac ish), P/N (specify - from Table E, where cordance with applicable Standards of applicable). CCC = 135 (for 135 °F,57 °C) the - National Fire Protection Associa- CCC = 155 (for 155 °F /68 °C) tion, and /or the standards of any other Recessed Escutcheon: CCC = 175 (for 175 °F /79 °C) Authorities Having Jurisdiction. Mate- Specify: Style (specify 30 or 40) Re CCC = 200 (for 200 °F /93 °C) vials found by Tyco Fire Products to be cessed Escutcheon with (specify fin - defective shall be either repaired or ish), P/N (specify) replaced, at Tyco Fire Products' sole Style 30 Recessed Escutcheon `Eastern Hemisphere sales only. option. Tyco Fire Products neither as- Chrome Plated PSN 56- 705 -9 -011 TABLE E sumes, nor authorizes any person to White C olor Coatea PSN 56- 705 -4 -011 White (RAL9010)' . PSN 56 -705 -3 -011 PART NUMBERS FOR assume for it, any other obligation in Brass Plated . . PSN 56- 705 -2 -011 EC -11 AND EC -14 SPRINKLERS connection with the sale of products or parts of products. Tyco Fire Products Style 40 Recessed Escutcheon shall not be responsible for sprinkler Chrome Plated . PSN 56- 700 -9 -010 system design errors or inaccurate or White Color Coated PSN 56- 700 -4 -010 incomplete information supplied by White (RA_9010) . . . PSN 56 -700 -5 -010 Brass Plated PSN 56- 700 -2 -010 Buyer or Buyer's representatives IN NO EVENT SHALL TYCO FIRE 'Eastern Hemisphere sales only PRODUCTS BE LIABLE, IN CON- TRACT, TORT, STRICT LIABILITY OR Sprinkler Wrench: UNDER ANY OTHER LEGAL THE- Specify: W -Type 3 Sprinkler Wrench, ORY, FOR INCIDENTAL. INDIRECT, P/N 56- 895 -1 -001 SPECIAL OR CONSEQUENTIAL Specify: W -Type 4 Recessed Sprinkler DAMAGES, INCLUDING BUT NOT Wrench, P/N 56- 875 -4 -001 LIMITED TO LABOR CHARGES, RE- GARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCTS' LI- ABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS•OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FIT- NESS FOR A PARTICULAR PUR- POSE. Page 8 of 8 TFP220 TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvana 19446 - .; -Q.:..- •..",:‘,",';',;:r,'!'". ' ." '' ' " ... , -'' -,,, „ . + '' ' ' - - ' -, . •„ . -* , ,, .., „„ „ '. , :, . ., _ _ „ .... . . ... , . , . , . , . . . , . . .. .. - • • - -- ' . ... . . . . A . '..-gi, .. - .-- .- ' :-...:, : • - ,!„,,,,,, ..tf, . - ..- :' '7,,' . .,`' ..T '',‘ . ' ' ^. • + ' . ' ' .' ,' ' ° .' : ''' -'. • . ' a, C):,,A .., • - • , ,,;', . ^ '''',: '''.'.' ' .. ,rkill.ttl , 4 '' . ' ^... : , , ' . - • ;, ' ' ' • '.. ' . . - ' 61 (.,41),, :Qt. - ..-,.. • -,,' ,,,, :4. ','",,‘",§4 .. _.„. -!-.,/,,,,:,.-,..‘•.:-... - -.,.,•1-7.1,....r6";.-..,i,--:*:-:•.,: ::: . •:;.'!„. , ;:- 1.4,,.,• ,-- ..• . : • , „ , ' ' „. - . ' . '... ,;-,',:„.,"%. "' "-- ' '''..,.4')V' -- -- , •-i - .1, ,-.', , ...4 ,: ' -- ;',ei;,'• ...•-.,/ .."'... '.inr.,:. r,- i'' - . - r , '• ;3', ' ---. ' - .• -• ' - ,•'".; . •• .- ' ' ' ?-. - . . ' r ' . : .'"2"1; : . "•;* "...f -''";a'r..."''''' ''''''"Y"'" .ri:)`:::""','"q"-:- . : • ' ,--. . '...,,.."--:- - ' ' '- . , .- '-. ' •-.1 ' ' " ,..-, -..`• ,.-'(, ' , - . , ;;V;:.-;--;"..i . ,r,„, ;,...,.. , -:-.:4:V---.,r,:t,'-'..; '.', , .,7: , • --: 1ti,„..- , ‘,.... :. :; ,.: ' . .- :. : .., . , ' .,. 1. , ,.: ; I :I, . - , : . . . : ' — ' =',...-Xk!4.:'t' .!PS' .;' ,":- ' ' '.' ;; ''.. - ' f' . 1 r . . 4 ..,' ';•... j . Z"",.-4 '.'-'2, ir14,,::: ‘',.., ,.,."- n,,,,A,‘„'-,•1_41-tfowe-N,t7;*44,,,-:.,"1;-,:-..7.,,,:„,-,s'‘'-'--_. ,:,,,-,i,' ,. , t',E1,,i,i," ?..- • 1,:,.APW; •=1,".;;.'s.,, ,,,,34M":"'611 .2'.-,,,,.,,;,;: :5!;tl'i,'' ,,P,,,4',;„;,-":',F,'"14.."[',2,,,;:"1- ,-,,,- :,17,'.:',.''''':*"-,..*:';i: 1 , ' , . I all % 1 , ..'' , ...0. 1 ,;- , o':',..„..' .. '::::,,Agimin..i,,,?„.,.,--,,°::,:::4.54,:,,...'.,,,,,,,.,-,;,,,. ,,, - „ . -, , . :,,),,,,,,,,.' . r,,,-T.'f,4:;,Ac,:::?„L:,,,Nptt...-.;-,,,Y ii,,,i,*:,i,:"„,-;,,,,--'vtijka . , . .... „, .. - --,‘ :!f6,,pJ:4,1,,.41,t.-,,,:,,;:',,:i': ''''?-:: ''' :.....,: . .: ' . : ..,, .,-. . '7_ - - 0.,,.tig::=;,,M!!!!,',',.7::::,;;,:n,i°;:-Y7''-'777-.:,'''4„ l-' -:-ttfiM1::' -‘, ,,.,' ,:,.:, - '' . ., ,,.',5))if,..4f7:-'--''!':- toilACI,, ' .: 3 .,:.. , ", r• --f"-,i..--:'‘ -,...,....-::--it,s'X?7,"'.',,--'',4.;',:-,.. :,...-; ,,,.,;;:.v.!,,,-.. ii 7 . ;.-- .. ,., . .L - -, ,...,...., ,L,,- f,-..,:„,,-,,-,5„,,,,- 4..,,,,„..7,,,r4-4,1011,,,, k . .,.. :,..-:.,„, 5, li. .. , .,.. - -. . • .. ' .'...".1',, , , '';', 4 ,,,„,,,,::::4,?,44■`t!I ,,, ,r2,,,,, „;;74,,,,,,,,,,,,,,,,,,,‘„,,,,,,,,1/4,,,,,,,,,,,,; ,,,,,01,44„.,,,,,,, , ,,,7,,:„,-,,,,;,,e,1;:".;:,:ii' ..:/_,...),74:,,, J.:.,,,:; -,F :,-,,,,,, -- ,' ,, ,_ ,, _ - .- ' - ,:,,,:ef,,',.- "1,,,,,,, 4-1,- ...1,- , f , 1:-.t , - , .,..,,,, .,.."4"..,[,..%,„„,,,,,,, '%.2, .„, • ,i ''.,?, '•:' ''.. ■:;.‘,. \Tift,. -1,k,%, ',..,;.,, ' . , :„R., ,, Kt - ' . 6t4,,/, 'erer' ' ' ''':' ' -;' 44 r +.$ 41'.',>kr...""e4i.,, vei:., 4.; A",*;',-;k„-"'-S -,:',•-l'',-'?:a *,,,,,'";-.•;•(''"."'*,tr". ---'-- .,,ie„.„,,,,,,,,,,...,.g.,,,,- stiwitlia . . :. .---' ' ,,,,,L..047,4, 4 r .,' 11 4 . 5 'Lk ;.,?.;,,e1.,%„ ', ',:lor,,""-'; ;,,,,:', ''',,,,41,,ne' ' - . ;,44'--,,,',.-7 VIM^ . " - '''" ...- . . "ly:,,41,'"0,"•444',",)4K:!,41.i,„;,iZ -,,: ,l',*- .: - -a, ,-,1,-,...."',ii,W ''-<- . , ,, ... , ',„_ . • ,, •_ .:-. 14„'1'..,, $2t;V,...,,,A,IV.,,,C;;,?,:,4,,,,.. , °„-5,1„.„ ..e., ,R.,,`,‘;.,''",,,,,,&,,,,,'',,,,,L.,,Z,, ,',•• ,-,..?:-.., ',,, ' ,-, .:' , „, ,, '..,, 4,',,,,r-.1'',,,,,,.''. ''''''',WPt.;,.144A4 ....",',,,,,' ', -,,,,„" ' „,44.,,,,,,,k,., ,,, ,' , , - • . . • "f.,".;,eig, .,:„'•<,' );;;44,r'11.`5•.,,',,,vt,k,'*4 .7,:pAt,-0:,,,,4-tts.,,s4gsf#,,4 ?; ,',, ,,,,.."•;t"..•,,,. r ''' , '"•V;•• , ?" ' : ijitiAti• • - ' „ • . •„, , ' ' 9;4"i;Ithei;4.;,:ii!,;#,IP„:„.7;•;4:tiT4-4 ‘•',4'.',!:'7,,",0311!" ' •-7 „:110,!,41L'r". : ' -,., - -"' nr .. . • . ",,,,,...-: ,, , 4, . • ... , ,...,,„,,„,,,,,,,,,,i4A. ,:...,....., ,...,....„„„:„,,,,,_ .:,.,...,„:„.„„ici,„:„:,,,,,,;.:. ':.':' ,,,,,,:,,,,:,: <:,Z;,,,,LV'''''' : . ,.,.,- . If , , ,', ; 4.i.-;:e.,:2,:`7,".•i'.'"<, •,.;, " ""r`n• ; . . . . 11r,T5''.7f-.''-'•'' ;iiiVACI-r. ".-:::.:':•: ,:-- - 1,..' ' ,..,:,...-.-I.:2,„,,,,,',,,!,='it;<"'?;::''1,,,,;=4,4t`'''.':::', .".'..-,,`,2:;:.}'•.;;-..'''''-‘-';'''iiiiii .. ' \ • ' ' , "::"'"N" „,,, .• ',4.ii; 11 III ;:. • .,:.:::'-':-;,,1:':.::.•si't::-a.lif.,";,..;',..1127:,1I;;;‘,1,1:4-16' ,:"•i'.';.t":•:;;;;;;'...:':;,'!. 4::;-::::'-:2•:;::::1,11;;;, ,Iiiv:'-'-:''-: '.. ' .- • a '‘: ...... , .:: .. ,, .. . ,.,.: ..„.,,.;;,,,,-,. - ' .,,,,,.,:::!..,„„ ,-. -- • :, „....„.1,:;.,,,,,., ,,,,,,,.„;_.., ,,...,,..„,„,,,, t ill ‘4 -,,,,,,,,z, -,,:,,,,•,,vilq4.-..0_4,,,,,,i46,,,,',-,...,..--,._-_,,•)•',,;;:,,,,-klk,•,,,,,,,,:•!7.77j- .,34"24 Ain: ' ,**10 -- - ' ,4,- ',.. • , 4 ., Ai';',..,:4-' '... :7-176:'ir,r6G.,-.'s' ,.:..„Z,.::,k-Ir--.'. - - _VIVA ' . ” ' . ,,,,....,-.,.,...‘, 1 ,7,07";''7-$4.000,4,4,„AkV1A10.4.444V4-tqltr";75..Wir';'''''''r 64-;P''''''' ' • .i . ' . -• . ' ' - , ,. . ,,., „ 0-.`,4 !,:'";•,%......,•?0,04°.,;:•'''.' - AO :. . - - - • - ,,,,,,,--" ' .,,,,>;!', , , -_-. ...N,,,,,-1,-', ',i''.:'1,"`-",--, t44,P%14V-7441.'47'n , . - , ..Vil , ,. , .,,, , , ,, ,,p , , -;-Iitx„, „ „ „:';';it,:;%, .• ,. '','$1:',4\''-"is-514%-4-4,''','''!', IL; ',. -. . ' ,;., . ' . . .. -• ,,,,,,,,i_MIN,,,%; i- ',,lieVf . . .. . ., , ,,,'.44,...t..4......,,,!,-;.-i11.1,...4s1,4,,,,-.w,,,,,,;;,„,--„..---,!;,;,:.„7i-:4,:!‘t•.:-::::::.,....,,:‘,.--.-!.',-*a_tyrii-A.a.. - --,,.-.,..„..,,,-..,,,...-.,,,;,-,..1--;.i,;,---,:!-..,,,,',,":?,,I;4_,,„-'--,1---,,-,,,,--.k.,,,,,,':,.:-.„;ii_.;:i..... ' .,,-.. - i: -.- * , d-,',,, - . 4,70. ' .„-i;,', ' ' ,:t ■,`,,'' • ' r . .1 ' •-•:, 14 til$Axiat,,,,';',,,V,',1,7".4iii '::'...'• ::.„ , ,, , - '':rt- '', ,„„;1,,•44,,ii.,,,,,,.''';''.. .,,,'S;13.,,!kk , ,,,,,,1,,,4; ' i.,; ,t, (1,--,- , . -,.7.-:.:-"Itit7:,,C.-vs.",,Aq4,,.,.%;,',%:''''';':•'''';.;'",,7,)7','.,t,,,i,fi,,' ,..7,,i,.:lf''' '''''1'-' = , ,, ,.,,,,,,,,, , ,, • ,,,, ,, .., .. . ' avimAr ;;-„,,,,,,w..,,,.z,„-;-.41-Ail :.---.-:'-,,:,....,-:,,,vi,,hi,,,Agi',!7',....:-. ,:-:41., w '''' - - , t,,,,0)..4,..--.1f;s2q,?;1„,-,,,,,,, :-..!.:44;,;ii. 4,4,,-,,,d,Y-','' -, ,, ,',:,- ;-,.!:,-;'' ' ' ' ' 'ro'''''i'''''il:'''' e.#4tirrC, •Ii4 t' ',.71&,$;*'-h, Nriteig-44,Nk. ',Iir,,:f,',4.34 .-;;;4,''' 0.--.''''''' '1' -4;',3,..'"'' ' brmli Mal ' . ., .':- . '..- '' gPf.,2,,,,itb"li,Az.-.1.iiig4Tilt•F:;i:.:;,4ei';i:04444:-,22,1!;.*;:1,',(a '-:: „,...,,:„4;4,4,0:i.A.111,--- - : - ,,...7 ... . . ,,„,,, , , . ,I.,.-.,,,-..., --Nr.,.,,,,,--- :-. - - - '„ .,.,,..:54,44ok,,,e.valv,.. . - . . • ' '-' ...:„*.,:,,-.1,,,,,,.-: ...: ,.-‘...,.....,,,,,,i,;,„,,,.*PAI:,,,,,..-.... votokti: , . - -... . ,•,Ity,,,',,••'.40-. - .'..,,,, •-,';- ', ;5-.44,, `-' • - •''' • ' -:: '::. ' •,,•.:, ; ; • .,14'ir''-''45$.4-4i' ' . .,..,,,OViti7,-;'".:-: ' ' .. , ....,„,„.,---k.-.,::',..:".froll.. ' ' ' - • ;,....,'":"""---,‘” .:,"'"'"-7 ' " whiAtt '- . 4, .., :;‘,....,- -7":, .-.,--t'"';;;,i;,-1'7,';".,"imio‘: ' ''''irl',,,,,/'",,';-,,,,4-114?-k, ..,.tggito.- ...L..„,:.:,,..?::,,,,'-'.4,, ,r112-sbItk,:g...';4141041A , .-` rr ''''' *: -': '. ...:” ! ;' ''. , - . ,',.. •.•0,.•!'•-."7i;:;•''4.:;;'•',,,„:". t.4"1.•„, ..•,,;",!,;:"A.g ',,!if „',..".,...:4.1,,*,',!,,,tk;.,,,,,oi',•5.'"•, ,0...„..,,.:. ,--..... .i ..--itli --,': -,- r ':. _,,,-.„-:::.-..,,;.,,,44;#;.*:14-'_';',.,-,-,‘ii-F,,,tliipal;',,-zo'::-.,.:7tk;,,,c:'*,- .. .-, .,--;;244.4: -‘z.ie-(0,., . .. ' V l'1 ,:t,,,,•;: .;'•,-:;k:;;'q,'t'•iii',!''','.;r,,,;.F;'A":''r;;r1,.;,,•''Vd''"., tn,4,,::i;•,,iff,M.ft'''':-.,' ' , ,,,..,•.`44'rie., ,4:.0111k"'"- "k - ..-,-,.e' ''" -2-,;,".:,,11Q''' :0 1:..1&: '." s ..;- , 7;'''Q ., ,::*"'''' - , ' a .'f''' ''.(4,g'.-:',..";:/- . '--- ',,;•41)'i':',.;-,IP,Mii-%;:qt721,.:Zi; 'ikjti,!'"i;;ZIWiltli''. , ,,P,"'W44-. II; i'V'''''' '' . ' ' .,`;,0,41.i.tri , - , .;,*=,"-,.: ' • ' ..,:, , cl. ,,,,,..t. A.....,...,_ - RIS4V:44;,,,,'IlilatitrAiaili.tiaigkat2,„"„e4,,,Af ,';,.,']:011?ii:.::::iiltrAilr 0!;.'''''‘itr.r.*'ir,' ;''' ',.. -'- ' . '3,,itdAt.3. ' ' , ,,,i';'''''‘,,7."i', " " ' ,..'','i::::,•:- ' , qt,:tift4i,":47-2fitiOrlit4fitORI.,1§!,,,L4,4144st,!.;,4i,41,?,*-if,*:,7,!".':,;" "s,,J,:,',',v,;t4iti ' i -, ' ' ' : ., ,.. - , -',. , ',, ,,AN.,,-:..,-., . ,,.. .. , kitirt,tlii.6tatittittost7;i2?,,.Ei:i34414;14-,,,,;!..rt.,-t- , '' . 3 ,, N, , ,t.a: - .,r: ,,:,,,:,,.,-,,,tAx-....071„::,.L.,,•,,,,i3f,s.,::,::?,, e4-.,24., , , , ,,, I,„„,,,,„-,,,,,,,,,,.:, .,, .. .. ...:,,,,„„„,,„,,,,z-,,,,,,,,:,,:,,,,,,:-.„,;,,,,:,,,,,,,,ti,-,-_,,,„:-..,.:„ , Itto-fattiAq..tioloittt,i4=4..stitti$7.4.4ii 1 ,,',.. .,.. -: ,--vzl,..!,:ii.:l";1'kki:,,,,!.!',,..,,,:o.,--TA:t, FaRitiltitlitt7titkegittltgiiiitliir:4 ki'IP*::1--*11%14;1:': 40-,-,4'.-*TP,I,011y,4,.:,•', '), '','•,,'".A,"44„,)•,j.,••1',i,e,..zz,,,,l,',•:4•,,!..,'.•; , •,. -, . NtiellIkikittalkififi;144NtitRIVA.144;•;.•.`, :iii" '11 itt,11:474,k4- tE01111;1-141k*Ottr;IVif.t:'=""'"'- ,4114744R4441.4VVII.F=A0q4.4z,Aktr.Ailiti#•-4.,•.-1.4gtifig,'z'AT4:0.' ' ‘"''.,•*,'Y'';',A,`'-:Ifitr.,1'-2it,F-- I i EirkaIktilfrAiiiim44%,,n('Kr0411.:=0;:t.4,c444,4,.',10104.4.,„„#,A.,-,44.4.-,k4',.;qz,414,eig , .1,r. ,,`m- ' Lkin"4,41,V#IMakir°14.:4,e1,1111StliktitiRtial.:,A-tt,07,,,;,74„,r;,,,4,-:. '1,, ,4% 1 - 42,04.V.1‘140:;kkbitelais,; otofklaktitgi,V4*.Zighakil s-,.: ' ''"'- tiii .• ';,,IfitedttillOAtigilgiVtiriii474ite*Pinfir44' 4,14r."11041,41kriar,Z.V.1/40-4 IffilitirliiihrigighTilt;NAtiM,t;"-Z.•,%4' "'- 'r Fir'6" ' 4 ; 11 illtg.4111T1.,$- rAff10,!4'''''''''' . - ' Dyna-Thread® . Full Line Sch -40 Replacement . Dyna- Thread offers the life expectancy of Sch40 with superior hydraulics and greater value. Dyna- Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry It combines the safety and longevity of traditional Sch -40 pipe with quality and superior hydraulic advantages :; Com :arson to Schedule 40` " ' N' ',:..'';':,.•... P "' Compari to L:W T.';Pipes` • Dyne- Thread's inside diameter is up • With its increased strength and lighter • More wall thickness at the thread to 3.6% larger than Sch -40 giving it weight, Dyna - Thread reduces (CRR =1.00) gives Dyna - Thread superior hydraulics And, when used installation fatigue and is ideal for better life expectancy than hghtwall in combination with Dyne -Flow pipe, retro -fit applications threadable pipe joints down sizing often occurs Corrosion Resistance Ratio (CRR) is a • U nlike lightwall threadable pipe, • Dyna- Thread is fully listed and UL (Underwriters Laboratory) term for Dyna - Thread has no thread gauge approved by UL ULC, and FM for the estimated life expectancy of a pipe warning. fire sprinkler applications joint This is based on the calculated • wall thickness at the base of the first Dyna Thread is approved for • The life expectancy of Dyna - Thread standard hanger spacing (15 ft. and Sch -40 are equal based on the exposed thread, assumed to be the q weakest point of the pipe length. Dyne- O.C.); can be used as earthquake calculated wall thicknesses per UL sway bracing and is safe to use as Thread and Sch -40 have the same • The consistent quality of steel used to calculated wall thicknesses at this point drops make Dyna - Thread facilitates smooth and are both assigned the same CRR of • Dyna- Thread is safer to weld on - threading and lower maintenance 1 00. costs. • Dyna-Thread is more widely - accepted than lightwall threadable • The exterior of Dyna - Thread is The internal surface of all black Allied where Sch -40 is specified protected by a clean, durable mill Tube & Conduit Fire Sprinkler pipe coating for extended shelf life and products up to 4.5000" in diameter is easy paint application coated with our new Antibacterial Formula, "ABF" In scientific laboratory test, ABS proved to have superior Specif a ti on s ' .& Appro resistance to microbial colonization of ® ® 411) pipe walls, thereby delaying or possibly Super 40/Dyne-Thread pipe is preventing the onset of manufactured to meet. ASTM A -135 Microbiologically Influenced corrosion Grade A and is in compliance with Listed Approved Listed NFPA -13 All sizes of Super 40/0 a (MIC) when the First Sprinkler System p is first installed. Thread are rated at 300 psi working pressure Super 40/Dyna- Thread is UL and ULC Listed for wet dry deluge and SPeclfications:. . ,_ pre- action sprinkler systems and FM NPS Nominal I.D. Wt. Wt. (H2D Filled) Pis/ Wt/Lift (21') Wt/Lift (24') Wt/Lift (25') Approved for use in wet systems Super In mm In, mm Lbs /Ft, Kg /m Lbs /Ft, K_g /m Litt Lbs. Kg Lbs Kg Lbs, Kg 40/Dyne Thread can be "hot - dip" 1" 1 080 1 330 1.75 70 1955 2234 2327 galvanized to meet FM requirement for 25 27 4 2.0 2.60 70 887 1013 105; dry systems. Super 40/Dyne- Thread is 1 1 408 1.870 2 54 51 2002 2288 2384 approved for all threaded couplings and 32 35 8 2.8 3.78 51 908 1038 108 welded outlets and is suitable for all 1W 1.639 2.290 3 22 44 2115 2418 2519 roll- grooved, and plain -end fittings. 40 41.6 3 4 4.79 44 959 1097 114 (See listing information) 2' 2104 3.050 4 57 30 1921 2196 2287 50 53 4 4.5 6.80 30 871 996 103 C® /Flow Control � (/ allied 16100 S Lathrop • Harvey. IL 60426 Customer Service Norcom Rd • Philadelphia PA 19154 (800) 882 -5543 TUBE & CONDUIT 2525 N. 27th Ave. • Phoenix. AZ 85009 Fax 708 -339 -1806 S3 -3 CAST. IRON FITTINGS FITTINGS 4' MATERIALS The material used in the use of malleable fittings is suggested • manufacture of Stockham cast iron under these conditions. - fittings conforms to the American Society Accurately aligned chamfered threads • for Testing and Materials Specification enable Stockham fittings to make up Al26 Class B, Cast Gray Iron. It is fully easily with tight joints and straight lines. described in the "Material Specifications" Fittings are threaded with ANSI /ASME Section. Standard Taper Pipe Threads B1.20.1. DESIGN: CAST IRON DRAINAGE RATED WORKING PRESSURES FITTINGS Drainage fittings are designed Classes 125 and 250 Cast Iron Threaded Fittings to give unobstructed flow. This is (ANSI Standard 816.4) accomplished by making the inside of the TEMPERATURES WORKING PRESSURES, NONSHOCK PSIG DEGREES F CLASS 125 CLASS 250 fitting approximately the same as the -20 to 150 175 400 inside diameter of wrought pipe. When 200 165 370 the joint is made, the end of the pipe 250 150 340 practically meets the shoulder at the back 350 125 280 of the thread chamber,' forming a smooth 400 1 250 g passageway to prevent catching or Classes 125 and 250 Cast Iron Flanged Fittings (ANSI B16.1) clogging of foreign matter. TEMPERATURES WORKING PRESSURES, NONSHOCK PSIG Fittings that have openings at right DEGREES F 1 CLASS 125 1 CLASS 250 angles have pitched threads so that the A. SIZES SIZES SIZES SIZES SIZES 1 -12 14 -24 30 -48 1 -12 '1 14 -24 horizontal line will pitch 1/4" per foot, -20 to 150 200 150 150 500 300 assuring positive drainage. 200 190 135 115 460 280 - 225 ' 180 130 100 440 270 Stockham cast iron drainage fittings 250 175 125 85 415 260 275 170 120 65 395 250 are manufactured according to ANSI 300 165 110 50 375 240 Standard B16.12. Pressure-temperature 325 155 105 355 230 p 350 150 100 335 220 ratings do not apply to drainage fittings. 375 145 315 210 400 140 290 200 DESIGN: CAST IRON FLANGES AND 425 , 130 270 FLA NGED FITTINGS, CLASSES 125 1 "353°F (Max)" to reflect the temperature of saturated steam at 125 PSIG AND 250 Stockham manufactures 2- 4.06°F (Max)" to reflect the temperature of saturated steam at 250 PSIG Classes 125 and 250 cast iron flanged 3 W argre aup cable o l aetab0a an g es nlya risotto Class vnosm;" 14" fittings and flanges conforming to ANSI and he larger ed are aophcable to Class 25 0 flanges only and not to Class 250 fittings The temperature shown for corresponding rating is the temperature of the pressure Standard B16.1. containing snell of the component In general, this temperature is the same as that of the com orfla formation Internal ice Fittings pressures should be enough to burst ctea so that can mea medeveloped au The bolt holes are drilled in multiples of during the i o ice = rt should proteat cod ia noe not freeze four, enabling the fittings to be rotated in . DESIGN: CAST IRON THREADED any quadrant. Flanged joints are easily FITTINGS, CLASSES 125 AND 250 assembled and disassembled. Flanged Stockham cast iron threaded fittings fittings can be furnished with bosses and are manufactured according to ANSI tapped drains. The standard locations Standard B16.4. Materials used in cast are shown in the "Engineering Data" iron fittings meet the specifications of Section. Orders for special drilling and ASTM Al26 Class B. Since cast iron has tapping should be accompanied by a It little or no ductility, excessive hammering sketch indicating the special details or shock could cause fitting failure. The involved. STOCKHAM VALVES AND FITTINGS 3 Sprinkler lines, heating and air conditioning systems, and plumbing installations utilize cast iron fittings. A wide range of types and sizes of fittings is manufactured by • CAST IRON StocKharn Proven product performance accompanying this broad line has enabled PIPE StocKham to Gain its excellent reputation as the leading pipe fittings manufacturer. FITTINGS DESIGN: CAST IRON PLUGS, dipped galvanized fittings provide a • BUSHINGS, AND LOCKNUTS Plug smooth, bonded zinc coating for added designs offered are square head, protection against corrosion. countersunk and bar plugs. Face bushings and hexagon head bushings Plumbing codes may require drainage are available in a wide range of sizes and fittings to be black (plain or uncoated), generally are furnished in cast iron or galvanized, or tarred with a heavy malleable iron. Certain small sizes of asphaltum preservative. All three finishes plugs, bushings, and locknuts are are available. furnished in steel. Plugs and bushings Flanged fittings are normally black are threaded with taper pipe threads (uncoated) or galvanized. They may be conforming to ANSI /ASME B1.20.1, tarred or painted on special order. except sizes of outside hexagon bushings Rubber -lined fittings may also be where external thread lengths are shorter furnished. than required by this standard. These bushings are threaded slightly large in PACKAGING For convenience in accordance with ANSI B16.14 to prevent warehouse handling, Stockham cast iron interference of the bushing head when threaded fittings (including flanges) are making up the joint. Locknuts have loose regularly packed in wooden pallet boxes. fitting mechanical joint straight pipe These may be stacked and are suitable .'- threads in accordance with ANSI /ASME storage containers. Broken lots are B1.20.1. usually shipped in these containers. MARKING For identification, each Certain sizes of cast iron fittings are • fitting has the name "Stockham" or available in corrugated cardboard cartons registered trademark. and containers. Class 125 threaded fittings are generally Flanged fittings are generally shipped referred to as "standard" fittings and loose or may be palletized. have no pressure class markings. Class 250 fittings are marked "250." WEIGHTS AND DIMENSIONS Weights Each flange and flange fitting is marked (pounds) and dimensions (inches) are with the saturated steam pressure rating. listed on the following pages beside each item. Dimensions are for estimating SPECIALS In addition to catalog listings, purposes only and are subject to change numerous sizes and types of additional without notice. patterns are available and can be supplied on special order. UNDERWRITERS LISTED Stockham TESTING AND INSPECTION Strict Classes 125 and 250 threaded cast iron metallurgical control, sound foundry fittings are listed by Underwriters techniques, and accurate machining Laboratories, Incorporated and assure the best in material and Underwriters Laboratories of Canada. workmanship. Threads are constantly Elbows, tees, crosses and wyes are checked for proper alignment and depth. included in sizes 1/4" through 8" for sprinkler service listing. Also listed are FINISH Threaded fittings are furnished Classes 125 and 250 flanges and short black (uncoated) or galvanized. Hot- turn flanged fittings in sizes 1" through 8 ". 4 STOCKHAM VALVES AND FITTINGS • CLASS 125 CAST IRON FITTINGS CAST IRON FITTINGS SEE PAGE 3 FOR PRESSURE-TEMPERATURE RATINGS FIGS: . £ h —B--t 101 • .„ GIN 102 � 4 120 f; ; �; 1 - r 131 4. 0 ' � T 1 4 I J — A 90° ELBOWS. REDUCING • FiG. 102 SiZE I WGT. I A j B 1 G H 1 /2 X 3 /2 4 I 1 I 1 1 9 A 6 5 /s 3/4 X 1/2 5 1 1 3/4 1 1/16 90° ELBOWS 1 x 3 /4 9 1 11/46 1 1/46 3/4 FiG. 101, RIGHT HAND 1 x 1 /2 7 1 1 9 /i 1/2 • SIZE I WET. I A I 0 1 x 1 1 2 1 1 7 /2 1 11/4x 3 /4 1 2 1 1 5 /s 3/4 11 /15 1/4 2 /4 s 1/46 11/4 x 1 / 1 0 13/46 1 We 1 • 3 /6 3 ' 5 /16 9/16 1 1 9 1 13/4 11/2 13 /16 1/2 4 1 1/2 5 /s 11/2x 1 1 7 1 /s 1 / 5 15 /15 11/2 3/4 6 13/46 3 /a 1 1 9 11/2 13 /16 11/2 x 3 /4 1 4 1 1/ 1 1 13 /16 1 1 5 1 1 11/2 x 1 1 4 11/2 1 /i s 1 2 x 1 11/2 2 1 1 /i 6 11/4 1 / 2 6 2 2 s 1 1 /4 1 2 x 1 2 4 13/4 2 11/2 1716 2 3 3 2 11/2 2 x 1 2 3 1 2 1 1 2 5 3 2 1 3 7 7 3 21/46 2 x 3 /4 1 2 1 13/4 2 7 1/2 11/46 3 10 3 23/2 2 x 1 h 2 3 1 2 7 /a 1 4 13 3 211/16 2 x 2 4 6 2 2 /e 1 1 %/a 5 21 41 /2 31/4 2 x 1 3 9 2 6 2 1 1' 6 34 5 3 s 2 x i '/4 a 0 2 2 1 1 8 66 63/46 51/2 2 x 1 3 3 11/2 2 75 /, 6 1 3 x 2 6 5 2 3 1 2 - 3 x 2 5 4 2 21/2 11/2 2 • 3 x 1 4 7 2 2 13/46 2 3 x 1 4 7 23/46 2 s 13/46 2 31/2x3 8 0 1 3/16 3 212 2 /6 A * ' 4 x 3 ' 12 3 3 /s 2 23/4 4 x 2 10 3 31/2 1 2 G 4 1 4 x 2 8 2 3 1 /s 2 ,' 5 x 4 17 1 4 4 2 I 3 An G 6 x 5 28 4 5 33/46 3 --- - � 6 x 4 23 41 /2 4 2 3 I 6 x 3 25 4 4' 2 3 45° ELBOWS • FIG. 120 SIZE I WET. I A G A /4 2 3 /4 3/s , _ _ F q r G G 1 3 /s 3 13 /6 7/s 'a L - --i 1/2 4 7/2 I 3/2 _ T - -- - 3 5 1 7 /16 %P. - . G y x A I -- 1 9 1 7 /6 . i i' ,- Y — — — — — , j (-- ' 1 1 d 1 5 / 46 5 /2 7 1 1 /2 1 9 11/46 3 /4 2 2 9 1 15/16 TEES • FIG. 131 21/2 4 4 j 115/1 6 1 • 3 6 5 23/46 13/46 SIZE WET. I A 1 G I SIZE I WET. I A I G 3 1/2 8 1 I 2 15/16 1/ 2 3 A6 1 7 / s 2 I 6 5 2' '/16 13/4 4 12 23/4 1 A 4 1 5/45 -3/46 3 11 1 31/46 21/46 5 20 3 1 1 /2 5 1 /a 5/s 31/2 1 12 3 2 6 ' 28 3 2 % 9 1 3 /4 4 19 313/ 6 2' 8 58 I Q 5 /16 2' /s 1 1 4 1 13 / 6 5 32 a 1 h 31/4 11/4 12 0 1 1 1 6 42 5 3 1 2 8 1 11/4 8 83 6 5 2 4 6 I 21/4 1' , STOCKHAM VALVES AND FITTINGS 5 ., CLASS 125 CAST 1 FITTINGS STANDARD CAST IRON '� FITTINGS SEE PAGE 3 FOR PRESSURE- I EiviPERATURE RATiNGS. • FIG: C > 132 _ �- c-� 7 -- 1.117r—fill44, _ B - B H h B i ' ' ' � r . I l -iP `4 i� �- 7 = 1 r t---C-7 j171 I Straight run, reducing outlet. Reduced run: other end and outlet equal. Reduced on run and outlet. TEES. REDUCING • FiG. 132 SIZE I WGT A B I C G H I I SIZE WGT I A I B I C I G I H I I 1 /2 x 1 /2 x V4 5 I 11/26 1 16 11/26 3/46 9 1/46 I "As 13/4 x 1/2 X 1 1 8 1 1 1' 13/46 I 1 11/2 1 /2 x 3 /s x 1 /2 6 1 1 /s 1 1/46 11/2 5 /8 1- ' /A 6 5 /8 1 x 1 x 1 2 0 1 1 1 13 /16 1 1 /E 1 /a 11/4 15 /16 3 /4 X 3 /4 X 1 /2 8 1 1 1 5 /8 5 /8 3/4 2 x 2 X 1 1 3 7 2 2 2 1 1 I/4 1 1 /2 3 /4 X 3 /4 X 3 /8 7 1 1 1 9 /16 9 /16 3 /4 2 x 2 x 1 1 3 4 11/2 11/2 1 1/4 2 1 1/2 1 1/2 1 6 3 /4 x 3 /4 x 1/4 7 11/46 11/46 13/46 1 /2 1 12 11/16 2 X 2 X 1 3 1 1 1 2 1 1 1 . 3/4x 1/2x 3 /4 8 13/46 11/4 13/46 3 /4 3/4 3/4 2 x 2 x 3 /4 1 3 0 1 1 2 7 /8 1/2 1 3 /4 X 1 /2 X 1 /2 7 1 1 ' 1 5 1/2 5 /8 5 /8 2 x 2 x 1 /2 2 8 . 1 i 1 1/ 1 1/2 3 /4 3 /4 13/48 12 x 1/2 x 3 /4 7 11/4 11/4 1 / 1/4 % 2 X 11/2x 2 3.8 2 2 2 1 1 11/2 1 x 1 x 3 /4 1 2 1 1 3 /4 1 11A6 11A6 7/ 2 x 11 /2 x 1 3 3 2 1 2 1 1 1 11/2 1 x 1 x 1/ 1 1 1 11/2 11/2 1 9 /16 9 /16 1/2 2 x 1 x 11/4 3 3 11/2 1 21 ' i 1 7 ' r6 1/s Ira 1/s 1 x 1 x 3 /8 1 1 1 13/46 11/4 I 1/ 1/2 7 /8 2 x 1 X 1 2,6 13/4 1% 2 1 15 /16 1 1 1 X 1 x 1 /4 1 0 11/2 1 1 7 /16 7 /16 1 3/46 2 X 11/2x 3 /4 2 6 1 1 2 i 7 /8 13 /16 1 1 x 3 /4 x 1 1 2 11/2 1 11/2 1 3/46 7 /8 13 /16 2 x 11/2 X '/2 2 4 11/2 13/46 11/2 1 3 /4 3/4 13/4 X 3/4 y, 3 /4 1 1 1 13/48 316 17 /16 3/4 7 /9 2 X 11/4 X 2 3 8 2 2 21/4 1 11/2 13/46 1/2 1 x 3 /4 x 1 /2 1 0 1 13/46 13/4 9 116 3/4 1/2 2 X 11/4x 11/2 3.4 2 3 7 1 1 1/9 2116 1 3 1/4 1/16 112 1 x 1 /2 x 1 1 1 11/2 13/4 1 13 1/46 7 /8 ' 2 X 11/4x 1 2.9 11/2 1 21/2 11/2 1 1 1 x 1 /2 x 3 /4 1 0 13/4 11/4 1 11 /16 3 /4 1/2 2 X 11/4 X 1 2 5 1 1 2 1 ' 38 1 1 1 /2 1/ 9 /4 1 x Y x 1 /2 9 1 1 /a 1 9 /16 5 /6 7 / 2 x 1 x 2 3 4 2 3 /4 3/4 2 2 5 6 11/2 X X 1 0 1 7 /16 1 7/ a 1 3 /8 7 /9 7 /8 11 /16 2 X 1 X 1 1 /2 3 0 2 1 73 /16 2 6 13/4 11/2 1 /2 1 1 /2 1/2 x %z x 1 8 13/4 13/4 1 /a /s 9/15 2 x x 1 2.7 1 /a 1 21/ fl 11/2 1 1 1 x 1 1 /4 x 1 1 8 1 1 1 7 /a 7/8 1 1 2 x 1 x 1 2 4 1 11/2 2 1 1 J /16 1 1 X 1 x 3 /4 1 6 1 1 1 3 /4 3 /4 1 2 X 1 X 3 /4 2 3 1 13/a 11 3/46 346 ' 13/4 1 x 1 x 1/2 1 5 1 13/46 11/2 5 /8 5 /s 1 2 x% x 2 3 5 2 2 2 11/2 1 1 1 x 1 x 1 1 9 1 1 1 11/46 1 1 2 x 1/2 x 2 3 4 2 1 2 1 1 1 1 x 1 x 1 1 6 13/46 1 1 7 / 1 3/46 1 2 x 1/2x 1 3 1 2 1 % 2 1 1 /6 11 1 x 1 x 3 /4 I 1 4 1 1 1% 3 /4 1 1/46 1 1 /16 11/2x 1 1 /2 x 2 3 3 2 2 2 11/2 11/2 11/4 1 x 1 x 1 /2 1 4 1 1 1 3/4 3/46 1 1 x 11/4x 2 3 4 2 21/2 2 1 13/46 13/4 11/4x 3 /4 X 11/4 1 9 1 1 1 11/46 1 11/46 11/2x 1 x 2 3 0 2 2 2 11/2 13/46 11/4 11/4 x 3 /4 x 1 1 6 1 1 6 1 7 / 7 /a 1 13/4 x 11/4x 2 3 0 21/2 21/2 11/2 13/46 13/46 11/2 11/4 x 3 /4 x 3 /4 1 1 4 1 13/46 13/4 3 /4 3 /4 1 /16 1 X 1 X 2 I 2.9 12 2 11/2 I 13/46 13/46 I 11/2 11/4x 1/2x 11/4 1 7 1 11/2 13/4 1 1 /16 1 1 2 x 2 x 2 6 4 2 2 2 /a 13/4 6 1 7 /46 1 1 x 1 /2 x 1 1 5 13/46 13/4 1 1/2 7 /a 1 2 x 2 x 1 5 6 2 2 2 1 1 1 a 1 X 1 X 11/4 1 6 1 1/ 6 13/46 1 1 3a 2'1/2x 21/2x 11/4 5 1 23/46 23/46 2 11/2 11/2 13/4 3/4x 3/4 X 11/4 1 4 1 1 1 11/28 1 3 /4 1 1 VZ X 1 11 2 5 1 13/16 1 13 /16 7 /8 1 /8 1 1 /8 3 21 /2 X 2 x 1 4 / 1 1 1 7 /8 2% 15 /16 15 /16 1 11 /16 2 x 21/2x 3 /4 4 6 1 1 2 1 3/46 13 /16 1 1 1 1 /2 X 1 2 2 1° 13/4 1 15 116 15 /16 11/2 21/2x 21/2x 1 /2 4 6 1 1 23/46 3 116 13 1/46 1 1 1/ X 11/2 X 3 /4 2 0 11/2 11/2 13/4 13 1/46 13 1/46 1 212 x 2 X 2 6 9 2 2 /a 2 13/4 1 1 1 x 1 x 1 /2 1 9 13/46 13/46 1 3 /4 3 /4 13/46 2 x 2 x 2 5 4 12 3/4 2 23/4 1346 11/2 11/2 11/2x 13/4x 1 2 7 1 1 1 1 1 11/4 11/2X 1 1 /4 X 11/4 1 2 4 13 /16 1 3 /4 1 11/2 6 13/46 2 x 2 X 1 4 1 2 2 2 1 1 /4 1 V4 1 2 x 2 x 1 4 1 2 1 2 11/2 1 / 13/4 1 X 1 X 1 2 1 Ws 1 1 15 /16 7 /a 11/2 21/2 x 2 x 1 4 2 1 1 23/4 15 /16 1 1 1 X 11/4 X 3/4 1 8 11/2 1 1 13/4 13 /16 3 /4 13/46 21/2x 2 x 3 /4 4 2 1 13/4 2% 15 116 1 1 11/2x 1 1 /4 x 1 /2 1 7 1 15/a 1"A6 I 3 /4 5 /8 13/46 21/2x 2 x 1 /2 3 7 13/4 11/2 21/4 "1/46 3 /4 1 11/2x 1 x 11/2 2 4 ' 1 1 a 1 1 1 1 1 1 /2 X 1 x 1 1/4 2 3 13 /16 1 '/ 6 1 1 Ve 1 13/16 2 X 1 X 2'1/2 6 0 2 2'/2 2 1 1'3/46 I 1 21/2 X 1 X 2 J I 23/4 • 23/16 2 /E 1 6 1 1 /2 1 11/2 X 1 X 1 1 9 1 13/4 11 1 1 15 116 '3/46 11/2 21/2 X 11/2x 1 4 4 23/46 1 2 11/4 11/4 1 11/2 X 1 x 3 /4 2.0 1 11/2 1 15 1/46 1 3/46 11/4 21/2x 11/2x 1 1 /4 4 1 2 1 2 11/2 11/2 1 11/2 X 1 X 1 /2 1 6 1 11/4 1 3/4 3/1 6 1X16 2 X 11/4 X 2 5 9 2 23/46 2 / 6 11/4 1 13/4 �¢��'� 11/2 x 3 /4 x 11/2 2 3 1 1/ 1 11/4 1 6 1 ?7 I X 3 /4 X 1 2 0 1'3 1 /e 1 1 1 13/16 2 '/2 x 1 x 2 5 1 2 2 2 1 %/46 1 7 /16 1 2 x 11/4 x 1 4 2 23/46 11/2 23/4 11/4 1 1 1 11/2 X 34 X 3 /4 1 6 1/ 1 1 " 3/4 I 13/10 21/2 x 1 x 2 5 1 1 2 23/4 2"1/46 13/4 1 I 1 1'/x %2x1 23 1 1 1i5 /i6 13/4 1 11 22x1 x2 4 5 12 2 23/4 1 1 3/46 11/2 • 11/2 x 1/2 X 1 1/4 I 2 0 I 1 1 11/2 11 3a 1 1 I 21/2 x 3 /4 x 2 I 5 5 2 2 I 2 1 1 1 1 1 1 1 1 1/4 X 1 X 1 1 /2 2 4 /a 1 1 1 1 6 1 13/4x 1 X 1 2 3 1' /a 1'3/46 1 1 /1a I1/2 11/2 6 STOCKHAM VALVES AND FITTINGS Bk ro Aoplication Gulde gy m.: = y ° �• ew `R >: ;i: Fastening Systems _ ' _ :, ti .. ac e HangerMate® Threaded Rod :. n �e:: ;r€ N:"= 9 .� .� >' � ms`s "` �� �� _ �.; Anchoring System . p - =: EZG660 & EZG670 Anchors F , Y > >.r =e. , w .. , ,, .' s . i c c hon "i ` ': _ ,: :,�' ,�� : - -. ,;n"� P; " „,5,-;':t4: e /•l�b.e h,ecxteelsFiactk :cfc '' ° s r 4o n e tece ia ' „ " "L rc ; head drilled ".I1I h - b `` " ` ' ''' :. , .411& hreac s, ; T Y Pe 1177 pia,nt, e n d , - r� � ie -, to cep' twin lead threads $fteOd =t . ',2 _, - ,'' : T, / ct" C eept /8 :6 # °r m » ' < threaded rod 111k. z , : =- 'g -'; „ " \- � 'm „ : -a ,. , : tt li:, , ;.; components ■ l z ; i' .: Q ' ' .? ,' " - t 1 `, -- ii �._�:1s`hn a S"- ` , , , % .' . ���� �ot i "sly es cC1L s L iste cf fo P .-A p ' t ` '. EZG660 '�t 'a i1'd r e o Vee O , U; fi ,,�: , " / , , f i?P s " p Pen p ; 's r ., r:,y r/ ` 2-1/4'' len : s ::£ .: =« F` ';: - ' '; .° . " . „ . - °- 6 ` .� ' > ti `. irs = " - - � - ' ;':- ,Er -r?' '€' a' - ; : - . . t =: a E , : fir.. r :fi j �9 l� �„- ,. ;,, '" �, >`� d z �;�,, ° ,Ii .; 7- 6,: d1d%,met e h ead e dril1ec or (d i -tA `e -=y si t . , ,,i ,, i �, h' , ' fr lam .. :. 3Y'N =` 1 v, ." �-3.:t F - r' C „. �1�) t udce ` t < F3 8 S 6 t r " ec , ' ne tj , " _ ” ' z" t Sri length it `� - H , ;.R _ ~j'=� ;..1:1C, • -_ , - �ii t :. ;; fix? : : ' u " .Q - a: _ : Features & Benefits 9 5 q,� End drilled and tapped for attaching 3/8 16 _' Z 0 , 1 7* _ ' g threaded components to wood ��;-` =;: :"`` :,,,,,,„4., , : ' - , s ' • mss•, r ,; • Solid one piece cold formed art head cannot -, un - = ,'', sin off or unscrew from body ".�s to tk " ret,,I t , 3 '„ - - u'` "' <�t � �%�%d�,�":n" "'`� .! )1 u'- A '. ti� +: ..r`%i,Yi '',a-' - }`''''`, 1 ` - . : s- 6 : b`` `1 =4, it h tFtread°s -- dxec `.r ,, -, r ; l l� ,: ;,- .. • hype 17 point cuts threads into wood and wax � < �,,, 9 � .�;,, �s� {� � ] �� ; �� y coating reduces installation torque -' ``` " "'`' " "''_ °' "' a 9 " ",. : = r : • 314:`,, , . gip. $ ': - ti.,,, ; _;,._ : a 7- y : F : = » .•:, a, a.:. t T yp e 7 (, axeu}�wtfn shank slot,`' : ` . -� .„ r : :x . , � .` ^: �;°r• ,: ",.> ; .•,,. 7,,, -;. " -, fir Performance Values for EZG360 & EZG670 Anchors , -F' ' °�'» `- ' : :I.', l ° Y'' V5 , rw� =x.� ;s atrsal & =1?lea Trent =:•: "�,.< , _: _- ;;f "� �tincte ull- Out'Yalue l: -.': =' .,M °:�'�. i t'� r°. Mme, ^C x , r ";.:: , -:� ;�Ccsraar�sfe'el' A� {:�l'C�flB�21 . no 'eat "t' tv »`. _ �_�.. €`�< ��.��;i�:i = -� :��: �.. �;�, tea �, f ; : . - � '�`�r, `, ' x 2487 2162 1768 1RI 5 �i3 ` .t, :. ` - 'x f " ,: iy ; ' n .::'r':rvrc;; ; . i .c iateo' `er • ,A. Mi 5 . 6i3 3f`Ty _ e 11 =:C rtss 7 < ,, ; ,: ` : ;� � ;��" °;��:- m ;�_,;�,� ' °`; rya ' ;� `�v� `S z � - °\ ; I r � Y ; , .�= . a n g e r ; �" y� > ::. � � ` � �. t �,- �� �'' >� ^ °. ": ; ; K la a teedfi v e;,so c k e < . ZE 2 , 1. * wtth_,saf ��' sef -,,,,, tre• ` ° ' F : automatt ., % ,,� ,.in : -° % , -, cllyteng ancVot ts: >secte =,5,` "E � •�3 -'iY �:',;�.,,t ?� ,a« 'kt. "-t- ^_ ,.,,• t o .� -ems. ;,;� � �� �, - ± �; e of �,r en =ded o -to =Contractor rcide`- screvr4 . t<i t ': -`?,- '° 99 s :, ` -,,< ,,•• ;a^2" •.`a fir :c = ":<: `. " 11 G{3� S5 C3 r` , - ' '` )':Cl?1irr t <'..; > :,.s a �, ` t '- - , , ;v. , r _. ;;lt . ' is f;.� >s ;�ln'ri�s�Q � , ;FP d l €I 11 �: �. >�. e eeded:'in. , n- .. . , a ,:ex "' o q rd wow ' -`d i - " ' <., R P• '. it, Qe�inly;>te.rtiia`i _: ° Viz; we e `-. `-:. ,, =x .;55 4 h, .. ' .: .. ` . - ,_ 1 The loads mdicoted above are a verage ultimate values achieved ' ° -'r ` M£ ` '''`€' ed under laboraro � ?; -� "�^, ` . � �'z �",�,",�'`': , --'�, _ z" � �•;�:� , ^,'. __�� condnons and oo ropnate sa factors should be spoked ed for design ourooses `�, €'? ^�,' <' - > , ' i •Y.. ; ': " y ,�- ::„-+ u - s= -s a• - - 5i - v' "'° ter >s "' ;'<. - : • ��, . - 2 NrPA (Nahonal nre Protection Assoc J rein mum iasrening regmremenh are five times the .t;„ ` _:;;;;._, _ - . ,» -<m; 4 ` - - wet Er of a 15 it section of water -tilled pipe plus 25O Ibs This is 1475 Ibs for pipe ' .,'1,;i ,,e : ; *:j ,., , - W , _< ' ""� ' � "a -' „- " a All rest values were obtomed us no 3/8'16 rod Whe 1 /4 -2G rod ¢used, tie strength of • ` - � a - ” " ; ;: , ," - " r N •- , the may be less than the Dull -our; '' '�'` °�?- ` " y - <„ £ °5 �',' ..~ : °r o • ` rod values of the archon f _ _; Q i; „>,' ': �� J. '{raa f,ort s;,a :��.: � ,:� <. loads were derermmed by testing products in the onentahon for wh ich they were ? , Te xtro nFas < ie � rsm�` ° - ` $E'm ® ,� y s t -� ; ",' ' ° de swn o be used E nd drilled Dart were pulled m 6ne with me anchor's axis while ; c' k ;, %-; r•, r t , ; , -_ corn -, s ,, ^ ,; ,.; - > ,, , ' : .. ; a = "t ' ? _ ¢,, a.:, 3 cross- anlled ports were tested with the force perpendicular to fie ows > tE ;,FTiatl:'.tn ' rQ �7ES 1 XTr' -OII "" 4117 -•4•i _'� "Sw ` HanaerMatee is a registered trademark of Textron Inc Back to Application Guide Fastening mywr te e- ry r . _ TEXTRON Systems ��>;.: �: 9 sac -� :.. A���n ��. �� : :� -,,�.: Hanger Mate Thr eaded - : r.._ Anchoring System :y £ Q -41, F , P ,, - t z _ r EZH665 Anchors = ,..4 4.54' , 49 - .:.'',441,r ; , .,, „ ' .- / 1 - , .= , ! J1 q ea �sl ai k '-' , eter = E sc e `. e'a a:E p a nciorr =v twin lead threads s k .6 44 �! =lN i]X d l€At i<` -6 `' ,, � c x ; ;,. % - ., T7 cross= In d ° ' a..: t �� � >� � = rte. °� mss, ":.�, . `ieacic? a cc�p i J$ ^,;. 5ira sd: : r� -q -, 1 1 _. `` � ; _ portents' ' , , k , ?) , - '`o =ms`s irk ?.a:, i -. A 4 ? - , ; ..t,^ : ; . ":. � ., _:; ° .:� '*,, . 4. ,,, " - - =" "<' •�;' 'read -,, P . - > ';t •; �� - `.'. ° . - < "" `i"r �� >.; ; qtr `r cross-drilled / • it E TA F7 S- ;' �� ,9 � P v ts�ntJL• L # � _ , s c:. ��> � . to accept � � �. ;;:a , 1 1,, J;L LJS ,4,- a ;" s =„- > • >^ «y s � �P � fQr i e ;� b �',. � 2` d iameter : , � '�; threa rod <y � .' " d £`: • "s, s a "' :,,;<•<;` ';�z. components �.< �.. 3,8_16 t �`h g ,,,, 9/ T R =....1 teterQhe c: c , ,, , °and. " � : C • � a � x t1 ETlf Si ' :r „•• y .,- � �; " , •; - � ,: mss a � . ,,, �'`;^'..:i . Features & Benefits XSrae: ,� ;� . �: . �., .;_4� ,- : ,,; � ,� °, , � "' • Cross drilled and to ed for a ttachin 3 rtl�s {�` �" � < .�', -� `'�` '';`' '' PP /8 - 16 �� - ��y�acro ci # s� : < ` � � " ":� �. , >�� •�. threaded com onent to woo k a� =_: . ' a • Soli one piece cold formed art; head cannot s in t''.--. ,.:: :9ri _° ;; ; N . 9 i ':,k,"'--1* .,, off or unscrew from hod ,T ; lit,.,,,, °� "-`� -z.�. ,; '4.1:t : ;, • Type 17 pint cuts threads into wood and wax �_� > �� <' �” �'''`` "� ,' ° '� <� = ° �: '� > ; coating reduces installation torque ` ;�:� �"rti �� ,,z �; = ,; _ ° low: waxed �' -:.; ".r `:Jill ; ; :,v: • ,`, ' _ -..»s.. :tt ; , , % _ 3 ; . " ., �� f - t .,�. ` � �,� 17 a#d >vitt s s1or;, :^':,.:.: y:. y °,.; Performan V alues for EZH665 Anchor � �� ���''`;. �� . r'��: � �� ;;�� ., � , ,.�, � , 9 tn 1- ;a!tilue�l�is� >i ��:. .� ^. � �� � • �:� .; °•�. " = � . � . , . ., . . fi t] CI .. ^ t'�;., > , .�,", '; , .., _ .,. - mot- , , i h. , � , 1 me s i ^H @Rfi It ,a;7 `' ;r 3' 4; :` '"Yes • ".'. Yti -i «' ?. >t- , -t % �� �:_�:, ; � �rE?on;�t� eh,. AiSiC� ^ �flB 2 �� � ° � � �� ^ �'� �. 180 i 1460 ; > 1451 ,� " � �_ -, °� ,,;`�,;��,��.: ; , �. .,,� ,, � � � . 3 � >� `T yp��� J� h�CI'ass1`2� '�°� � � � �` ' fir � " � �`tIf3S�t9��t3�'15i(3 ��A ©�S: -���: , ;, r ^r: ; x : ,�:'; • ; .. ". l ]te <. �� `; -� v � � �..�Ye,so =5 =rti ; s afe • set "'� . ��. ��, .,^ � e t� n cFi�c�rass e atecl..: -�: ;: ^�.. z-'�� " °•, " .„�^' -:,: � °, ,,`= ; °,,," rte:.`: ^, " ,;" - ''`�„- a•s$r^:. wee ool : . Ct�nfirocfor sg rac�e �s cFew�gu ▪ �� ,.4Y,;, o t m rr ,-.v ar!?6fb' c , ,,] - < z, °- `-N. r < •, _,;R�. �\w�"{ del#' -t 6oi; • � is y '':.:.���; 1'P�n.:'. .-. , n` P: a ons r s e r e Ft ` ii11;e -- i o e is n d !,.*:,-1,,, • ' _ >: ? ' § - : e y har, ° ,i r ' '. , � �'- : - . ":a ; -•a � " ..ha�+r^on�l to'ria��aimumsrze ,�, ` '.� 4 ,'�^�r + � ` - . ; mss ;� , �;`?��' .�.. >;; _2 � �,: 7 ;a The loads indicated above are a �eraa e ultimate values ache eved under laboratory r = '•,,� cond o s and approo ate saie bet, should be applied +or design oumoses => , ", ` - ,,c, ^, „ �.,t -• -` :.., <., ; . . o ; , .: ;off - , , <, 2 NFPA (Nahonal Pore Prole Assoc mtromum ieste r ar e five times the - - � Y - g : - - :; - " ,': 4 ,- a, K. ,, .�+ -eF^' - a`' - „ " weight of a 15 ft section of wam - filled pine plus ti'k `' ; � "`' 2 Iues Thos is 147" Ibs for e e _� ? 0 ^ ' .. AU test values were obramed using 3/8-16 rod Wir i /a-ZG rod is u t he srrenaf}� o� : _.. : ,� ^ � „ ; .� , r , ; � s< -; , y .�` > �= �« `� -'` r�t :- the rod may an less than the pull -our values os th onc w• y M t : :: ' ` , ` ":' ,� �^ ;'_ "'. A s 6t }- i' ��9fU'r +af}. S�a9-. : J •:r , 4 v.� A, Z . : ,_, ;` - a ny , �GY` ;'� 1, - i., ^ l` �'�re `. \ ti s. . '<�'�•' •';`;�: z ., i` ^t�° 4 moods were a te rra ed b' tearen <. `�”. , , -.. ', `fit " " " "` '. ' ^ - 5 ` : <" r g Products In the oreentanon for which thry were = � e X ' f OT1 i iiQ 3 , ,i ,, =:: t@1 X1 "•`s ° `'O :i� .` L� �. �` • a S �' ° � . , ..: :' "-• " °: d esigned to b e used End - drilled 71, were pulled m lone wifi the an az+s while - „ "'- ; ; ,,,, „.� ; "t; > ; --„ : �` _t „ms s ., ;^ ,,," e . ,, a , , .�.” ' ” ` ross - dri urn, te wrth the in pe endicular re the axe ' -� ' . 6 ; , �.::, •t - '"' -� `'- p e ii s on co -- = -,�}",, " -, .:: ; • r,sw >- • . >vx x , , ,. .EW <s„ fs ,`S"✓,> -: "ro' > `:k; . ;,a'>`'si u+Y` -�`. . HangerMate`o is a registered trademark of Textron Inc ■ D� - C0 t t r w ww t o lco eo - - - : - RevisiOn:5 24/2001 Fig. 200 - "Trimline" Adjustable Band Hanger Size Range — 1/2" thru 8" pipe 0c0 Material — Carbon Steel Mil. Galvanized to G90� specifications sprinkler and other general -G Function — For fire s P 9 piping . purposes. Knurled swivel nut design permits hanger �' z; �_ . ; adjustment after installation. '. ' Features — iz • (1/2" thru 2 ') Flared edges ease installation for _ ,. all pipe types and protect CPVC plastic pipe from �., '' 3 abrasion Captured design keeps adjusting nut r y � , f rom separating with hanger Hanger is easily z t A, installed around pipe ", • (2 thru 8" Spring tension on nut holds it "' : t,, " securely in hanger before installation. Adjusting 1 nut is easily removed. Approvals — Underwriters' Laboratories listed (1/2" $ % ,-. thru 8 ") in the USA (UL) and Canada (cUL) for steel r =.77 :0tnr^ -< 5 • 1 8 tN01 i P9 and CPVC plastic pipe and Factory Mutual Engineering Approved (3/4" thru 8 "). Conforms to Federal Specifications WW -H -171 E, Type 10 and Manufacturers Standardization Society SP -69, Type 10 FA : -, ' Maximum Temperature — 650 °F wk Finish — Mil. Galvanized. For Stainless Steel materi- , ° „ als, order TOLCOT" Fig. 200WON. j ;_ Order By — Figure number and pipe size ,:^ ' _ -' :r Dimensions • Weights Pipe Rod Size A Max. Rec. Approx. Size Inch Metric B Load Lbs. Length 1/2 3/8 8mm or 10mm 37f 2 400 11 3/4 3/8 8mm or 10mm 3' /, 27 400 11 3/8 8mm or 10mm 3 2 /, 400 12 1'1, 3/8 8mm or 10mm 3 2'/P 400 13 1 Y2 3/8 8mm or 10mm 3 27 400 14 2 3/8 8mm or 10mm 4'4 3 400 15 2'/ 3/8 10mm 5 /, 476 600 27 3 3/8 10mm 5 4 600 29 3 % 3/8 10mm 7'/ 5'/4 600 34 4 3/8 10mm 7 5 1000 35 5 1/2 12mm 9 6 1250 66 . 6 1/2 12mm 107 6 1250 73 8 1/2 12mm 131 8 1250 136 • Office /Manufacturing Facility • 1 375 Sampson Ave • Corona, C7 92879 • Pn 951 737 5599 • Fax 951 737 0330 .9D Customer Service • 800 789 5265 www.tolco.com 4 ww folco corn` '' bandofNIBCQ ,'j� '' •>� " ' ' r' -' Revision 8 /15/2005 Component or State of California OSHPD A pprovec, c Seismic Restraints Size Range — Secures 3/8" thru 7/8" hanger rod ••"al — Carbon Steel . • Function -' channel to hanger rod for vertical seismic bracing . >= Approvals — Underwriter • ies Listed in the USA (UL) _ • , 1.: Canada (cUL). Included in our Seismic �" --� Catalo.� Moved by , �:� � : . the State of California Office of Statewide Health ..uu.c;r` Develo•ment (OSHPD ..For additional lo.. ..- - : ;_cin. and •lacemen - - -- "%�� in Seismic Restraint ye n S stern to O elines OSHPD r lease ref to the TOLCO � Ktl Finish — Electra _ ... nized w :` .' Note — : -.le in HDG finish or Stainless Steel materials. . Or.` - By — Figure number Size Range — Secures 3/. :' rod in �� • ns • Weights 1" increments .. Rod Max. Rec. Load Lbs. Material — Carbon Steel ( �� Size For Service Temps Maximum Temperature — 750 °F SC - r . - � 650 °F 750 °F Finish — Plain f 3/8 610 540 `` /(((�y _ 1 /2 1130 1010 Note — Available in Ele r: %:razed and ( �l / � ,;. /8 1810 1610 HDG finish .,.. ._ s Steel materials. • `1( � 3 710 2420 =y — Fi gure num rod diameter, r ( 7 /8 3360 • . - a.:..y - , length and finish Fig. 100 - All Thread Rod Full Lengths Size Range — Secures 3/8" thru 7/8" rod in 10' lengths Material — Carbon Steel , _ Maximum Temperature — 750°F Finish — Plain f Note — Available in Electro- Galvanized and ' � f` HDG finish or Stainless Steel materials Order By — Figure number, rod diameter i ' and finish t( ( Dimensions • Weights ,� • Max Rec. Load Lbs.; Rod For Service Temps Approx. t' �. Size 650 °F 750 °F Wt. /100 >✓ ' 1/4 240 215 12 3/8 610 540 29 - 1/2 1130 1010 53 5/8 1810 1610 84 3/4 2710 2420 123 7/8 3770 3360 169 1 4960 4420 222 1'h 8000 7140 360 1'/2 11630 10370 510 • OFFICE /MANUFACTURING FACILITY • 1375 SAMPSON AVE • CORONA. CA 92879 • PH 951 737 5599 • FAX 951 737 0330 70 CUSTOMER SERVICE • 800 786 5266 www.to/co.com HYDRAULIC CALCULATIONS for CI -IV Tigard High School C �4y 9000 SW Durham Rd 41, 00 Tigard, OR. 97224 (j -1/1, t • Contract No 3685dw Date May 23, 2006 C:1OmniCADD \Hcs \Tigard H.S. Phase IV Remodel.hcp Design Data: Remote Area Location Health Room 524 Occupancy Classification Light Hazard Density 0.10 gpm /sq.ft Remote Area Size 900.0 sq.ft Coverage per Sprinkler 256.0 sq.ft Sprinkler K- Factor varies No of Sprinkler Calculated 6 In -Rack Demand 0.0 gpm Source Hose Demand 100.0 gpm Total Water Including Hose 284.3 gpm Name of Contractor Master Fire Control Name of Designer Ken Molinari Address 12125 SE Hwy 212,Clackamas, OR. 97015 Authority Having Jurisdiction City of Tigard • Reduced remote area 900 sq ft Quick Response Sprinkler Heads OmniCADD Hydraulic Calculation Software v. 2.3 May 24, 2006 09:39 AM Tigard High School CE2/Transitions & Girls Locker Room Remodel Page• 2 Water Curves for Src s1 0 300 500 700 900 1000 1200 1300 1400 1500 1600 1700 90 g I 90 A 80 C; . 80 70 I � 70 G . • . . 60 . 50 ' l , 50 .PSI • ' 40 1 ` 40 1 30 30 , i I 20 I 20 10 I 10 , 0 0 0 300 500 700 900 1000 1200 1300 1400 1500 1600 1700 GPM Curve Values - X : psi @ gpm Supply Curve @ Src :s1 I A:88 @0 - B. 87.9 @ 184.3 - C : 80 @ 1694 1 Demand Curve @ Src : s1 1 7.8 @ 0 - G . 67.8 © 184.3 OmniCADD Hydraulic Calculation Software v 2.3 May 24, 2006 09:39 AM Tigard High School CE2/Transitions & Girls Locker Room Remodel Page 3 NODES # I Type I Value I Elevation I X I Y I Res. Pres j Discharge I I I ft I ft i ft I psi 1 qpm s1 Src I [...] 0.0 - - ' 67.8 100.0 h1 Head 11.20 13.0 - - 13.1 40.5 h2 Head 11.20 13.0 - - 10.9 37.0 - h3 Head 5.60 13.0 - - 17.2 23.2 - h4 Head 11.20 13.0 - - 11.2 37.5 h5 Head 11.20 13.0 - - 7.2 30.0 h6 Head 5.60 13.0 - - 8.3 161 n1 Node - 0.0 I - - 67.7 - n2 Node - 0.0 - - 61.6 - n3 Node - 0.0 - - 61.1 - n4 Node - 4.0 - - 58.3 - n5 Node - 14.0 - - 49.6 - , n6 Node - 18.0 - - 22.8 - n7 Node - 18.0 - - 21.8 - n8 Node - 18.0 - - 21.3 - n9 Node - 17.0 - - 18.0 - n10 Node - 16.0 - - 13.7 - n11 Node - 17.0 - - 21.6 - n12 Node - 16.0 - - 20 4 - n13 Node - 15.0 - - 17.9 - n14 Node - 17.0 - - 15.6 - n15 Node - 16.0 - - 8.9 - n16 Node - 15.0 - - 8.4 - • OmniCADD Hydraulic Calculation Software v 2.3 May 24, 2006 09:39 AM Tigard High School CE2/Transitions & Girls Locker Room Remodel Page• 4 PIPES Start/End Nodes Material Size Length Pres.Fr.Loss -- - HWC Nom.Diam. Eq.Length Fr.Loss Pres.Eiev.Loss Flow Velocity Type # Type Value Elevation I Res.Pres. Discharge Fittings Int.Dlam. Total Length Pres.Vel.Loss I I ft I psi I gpm I I I ft psi /ft I psi qpm i ft/s ! ',pp1 s1 Src [...j 0.0 67.8 100.0 Ductile 6 40.0 0.001 0.099 184.4 2.1 Pipe - n1 Node - 0.0 67.7 - 140 6.000 42.3 0.000 TG 6.020 82.3 0.029 pp2 n1 Node - 0.0 I 67.7 - Ductile 6 5000.0 0.001 6.007 184 4 2 1 Pipe _ n2 Node - 0.0 61.6 - 140 6.000 0.0 0.000 - 6.020 5000.0 0.029 pp3 n2 Node - 0.0 61.6 - Ductile 6 400.0 0.001 0.524 184.4 21 Pipe n3 Node - 0.0 61.1 - 140 6.000 35.9 0.000 2E 6.020 435.9 0.029 pp4 n3 Node - 0.0 61.1 - Sch 10 3 10.0 0.032 I 1.040 184.3 7 1 Pipe n4 Node - 4.0 58.3 - 120 3.000 22.8 1.732 EB 3.260 32.8 0.338 • pp5 n4 Node - 4.0 58.3 - Sch10 3 106.7 0.032 4.314 184.3 7.1 Pipe n5 Node - 14.0 49.6 - 120 3.000 29.6 4.330 ET 3.260 136.2 0.338 pp6 n5 Node - 14.0 49.6 - Super40 2 79.2 0.261 24.987 184.3 16.8 Pipe n6 Node - 18.0 22.8 - 120 2.000 16.8 1.732 ET 2.115 95.9 1.907 pp7 n6 Node - 18.0 22.8 - Super40 2 114 0.095 1.084 106.8 9.8 Pipe n7 Node - 18.0 21.8 - 120 2.000 0.0 0.000 - 2.115 11.4 0.640 pp8 n7 Node - 18.0 21.8 - Super40 2 7.4 0.061 0.448 83.6 7.6 Pipe n8 Node - 18.0 21.3 - 120 2.000 0.0 0.000 - 2.115 7 4 0.392 pp9 n6 Node - 18.0 22.8 - Super40 1 -1/4 4.2 0.365 5.296 77.5 15.7 Pipe n9 Node - 17.0 18 0 - 120 1.250 10.3 0.433 ET 1.420 14.5 1.659 pp10 n7 Node - 18.0 21.8 - Super40 1 -1/4 4.2 0.039 0.569 23.2 4.7 Pipe - n11 Node - 17.0 21.6 - 120 1.250 10.3 0.433 - ET 1.420 14.5 0.149 pp11 n8 Node - 18.0 21.3 - Super40 1 -1/4 4.2 0.421 6.094 83.6 16.9 Pipe . n14 Node - 17.0 15.6 - 120 1.250 10.3 0 433 ET 1.420 14.5 1.931 pp12 n9 Node - 17.0 18.0 - Super40 1 14.0 0.338 4.732 37.0 12.7 Pipe n10 Node - 16.0 13.7 - 120 1.000 0.0 0 433 - 1.089 14.0 1.091 pp13 n11 Node - 17.0 21.6 - Super40 1 11.4 0.143 1.630 23.2 8.0 Pipe n12 Node - 16.0 20.4 - 120 1.000 0.0 0.433 - 1.089 11.4 0.430 pp14 n14 Node - 17.0 15.6 - Super40 1 14.0 0.509 7.125 461 15.9 Pipe n15 Node - 16.0 8.9 - 120 1.000 0.0 0.433 - 1.089 14.0 1.699 pp15 n12 Node - 16.0 20.4 - Super40 1 16.0 0 143 2.970 23.2 8.0 Pipe n13 Node - 15.0 17.9 - 120 1.000 4.8 0.433 2E 1.089 20.8 0.430 pp16 n15 Node - 16.0 8.9 - Super40 1 8.0 0.073 0.933 16.1 5.6 Pipe n16 Node - 15.0 8.4 - 120 1.000 4.8 0.433 2E 1.089 12.8 0.208 pp17 n9 Node - 17.0 18.0 - Super40 1 5.7 0.401 6.610 40.5 14.0 ' Pipe h1 Head 11.20 13.0 13.1 40.5 120 1.000 10.8 1.732 2ET 1.089 16.5 1.312 pp18 n10 Node - 16.0 13.7 - Super40 1 3.7 0.338 4.078 37.0 12.7 Pipe h2 Head 11.20 13.0 10.9 37.0 120 1.000 8.4 1.299 ET 1.089 12.1 1.091 pp19 n13 Node - 15.0 17.9 - Super40 1 2.7 0 143 1.580 23.2 8.0 Pipe h3 Head 5.60 13.0 17.2 23.2 120 1.000 8.4 0.866 ET 1.089 111 0.430 pp20 n14 Node - 17.0 15.6 - Super40 1 7.0 0.347 6.171 37.5 12.9 Pipe h4 Head 11.20 13.0 11.2 37.5 120 1.000 10.8 1.732 2ET 1.089 17.8 1 122 OmniCADD Hydraulic Calculation Software v 2.3 May 24 2006 09.39 AM Tigard High School CE2/Transitions & Girls Locker Room Remodel Page: 5 PIPES Start/End Nodes Material Size Length 1 Pres.Fr.Loss HWC Nom.Diam. Eq.Length Fr.Loss I Pres.Eiev_Loss Flow Velocity I Type # Type I Value Elevation Res.Pres. Discharge Fittings Int.Diam Total Length Pres.VeLLoss I ft psi 1 gpm I ft psi /ft psi gpm Ws op21 n15 Node - 16.0 8.9 - Super40 1 5.0 0.230 3.075 30.0 10.3 Pipe h5 Head 11.20 13.0 7.2 30.0 120 1.000 8.4 1.299 ET 1.089 13 4 0.718 pp22 n16 Node - 15.0 8 4 - Super40 1 5 4 0.073 1.007 16.1 5.6 Pipe h6 Head 5.60 13.0 8.3 161 120 1.000 8.4 0.866 ET I 1.089 13.8 0.208 • . . OmniCADD Hydraulic Calculation Software v. 2.3 05/23/20 ©B 12: AO 5036849482 05/28;'98 15:04 X502 528 2536 TT FIRE MARSRAi PAGE D6 IgJ UUllUU1 ' HYL210 HYDRANT IFNtSPECTION HISTORY LIST MAY 28, 1998 15:05:38 Tualatin Valley Fire & Rescue P age 1 FMZ /Hyd#, range 1 628919 - 38 to 62898 - 38 District : all ' Street range : beginning of file to ending of file Hyd Owner : all Asgnt code : all FM$- , Hydrant # / Address 62898 - 38 Test Cycle; 2 9000 SW DURTiAll RD TI Out Serv, Date District TI TIGARD 4 1/2 Thread : NSA' Hyd Own TI TIGARD # Turns Opel, : 0 Hyd Make : PACST Main Size i 6" valve Lo ; 1 FT TO THE RIGHT Comment : 5 -28 -98 test by InterfaceEagr Location : 300' from street, past cafeteria & Swim center, under trees Date Eng F P C 0 Ste Res Pitot Flow Flow20 Time - - - -- -- ( (2) ( ( 07/23/85 R225A ;X :>; Q 0 0 0 0 0 0 0 0,25 06/06/86 R225A :: sX;X: 0 0 0 0 0 0 0 D 0,25 05/17/87 R225A x ; rX :X= 0 0 0 ❑ 0 0 0 0 0.25 05/28 /88 R225A ,; ;X;Xi 0 0 0 0 0 0 0 0 0,25 05/06/89 R225A IX; ;X :X: 86 81 48 0 0 0 1162 4680 0.25 0 13 - 0 R225A •X: :X .. 9. -_ -• 0 • 0 6393 0.50 05/28/98 D ;X• .X• 88 80 25 26 0 0 1694 5380 0, 0 ** Total records printed - 1 ** Post -lr Fast Not 7671 0 i ° S"— a rp ,m. M Pnan9 FeuN _Fa:, , 1