Loading...
Correspondence • • :PRESSURE GAGES. -= Section 7.2.1 ; . �3. -, Listed pressure gages conforming with "8.16.3 shall be connected as follows: 1.' ',On ,the water side and air.side of dry pipe valve ._ the air pump :supplying the air receiver where one is provided 3. At the air receiver where one is provided 4. In each independent pipe from air supply to dry pipe system 5. At exhauster and accelerators • SPRINKLER SYSTEM MONITORING: OSSC 901.6. - NFPA 72 4. All valves; controlling the water supply for automatic sprinkler systems and water -flow switches on , all sprinkler systems shall be electrically monitored where the number of sprinklers are less than 20 HANGERS: _M „ 5. The maximum distance between hangers shall not exceed that specified in Table 9 -2.2. 6. The maximum distance 'between hangers for listed nonmetallic pipe shall be modified as specified in the individual product listings . _ SWAYBRACING: - Section 9.3.5 ' 9.3.5.8 7. The system piping shall be braced to resist both lateral and longitudinal horizontal seismic .loads and to prevent vertical motion resulting from seismic loads. The structural components to which bracing is attached shall be determined to be capable' of carrying the added applied seismic loads. Sway braces shall be designed to withstand forces in tension and compression. Bracing 'shall be attached directly to feed and cross mains. SPARE SPRINKLERS: - Section 6.2.9 8. The stock of spare sprinklers shall include all types and ratings installed and shall be as follows: a. For systems having less than 300 sprinklers, not fewer than six sprinklers Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be maintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.3.1 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. Respec Val He z•1, Senior Plans Examiner Bulletin 153 Rev. Reliable ® Model F3 co c Dry Sprinkle W x cp M Features 1. The Model F3 Sprinkler utilizes Belleville Spring ► \:� ?' '' , 'A Closure Technology : '� •, P .:�'- • 2. Styles available for Model F3 Dry Sprinklers: �`' .. • Pendent � k : , , g t - , • Recessed Pendent . it � � , - ,• i9 • Concealed w 7 'r '' • Horizontal Sidewall �` ° °: �,. • Recessed Horizontal Sidewall - ` � S dew I I =' : °'R 3. 11/2" (38mm) escutcheon adjustment on pendent:. 1,-�.. -':f - ::.. -::4 sprinkler. Concealed 4. 1 /2" (13mm) escutcheon adjustment on recessed �' - sprinkler with push -on /thread -off FP Model ,,;, - .1. : -+ escutcheon ring. _£: • ; ' .� 5. %" (9.5mm) cover plate adjustment on concealed , " sprinkler with push -on / thread -off CCP cover. �• ' � 6. Attractive appearance. Employs 5mm frangible -- , . s I., glass bulb and galvanized nipple. : - ., , • 7. Lengths available to accommodate installation �' dimensions from 2" - to - 48" (51mm - to "" " . • 1219mm), in 'A" (6mm) increments. 8. Available in avariety of plated and painted finishes. Recessed Pendent T 9. For use with wet pipe, dry pipe and all preaction sprinkler systems. • i l U.S. Patent Numbers 5,775,431 and 5,967,240. ; Approvals .,� _,ti.x��.�.. w�^.���..a:�. _ :�.,.,.�= r� �w�x SIN Sprinider Type Approvals ra Pendent R5314 Recessed Pendent 1 (1)(2) . 2 (1)(3) , 3(1)(2), 4(1) CCP Concealed Pendent Pendent R5334 Horizontal Sidewall 1 (1 (2) r.(1) 4 (1 (2, Recessed Horizontal Sidewall L ;. a Approval Organization e ' fp 1 Listed by Underwriters Laboratories Inc and UL d Certified for Canada (cULus) = 2 Certified by FM Approvals 7. ,, r^ = 3 LPCB EC Certificate of Conformity (CE) _ , ' 6832 -CPD -2006 (EN 12259 -1) tit 4 NYC MEA 258 -93-E : Note: (1) Light Hazard (2) Ordinary Hazard (3) Ordinary Hazard, Group 1 & 2 ! Horizontal Sidewall The Reliable Automatic Sprinlder Co., Inc., 525 North MacQuesten Parkway, Mount Vernon. New York10552 Model F3 Dry Pendent Sprinkler "A" Dim. 2" to 48" (51mm to 1219mm) in 1 /4" (6mm) rcrements Inlet Protrusion Elevated Finishes "' " Pipe Sprinkler Escutcheon _._ - 1t_ _ • Bronze Brass �___�- � r�-- I-- r � �i =__d Chrome Plated Chrome Plated White Painted" White ti System ree Lead Plated (3) Wax Coated (3(4) Wax Over Lead ( " 2 1 /8 U°. L. '• NPT ��� - A - Cm [53.98nm] Other finishes and colors are available on special order Consult Ad tn.en' ROn hots in Celing factory for details .1/4 [ +6.35mrn] a -1 1 /a' [ -31 75 „m] 1 43/64' Die. 1 /z' [39.1anm7 White painted sprinklers will have chrome plated can. [42470„„] 11111 101.1 nd]ement to 200 °F (93 °C) rating only c� � 1 1" 212 ° F (100 °C) brown wax may be used on 286 °F (141 °C) sprinklers ll""" " =;- when maximum ceiling temperatures do not exceed 150 °F (66 °C) Escutc "°° . - - - -- l 1/4 [635mm] Ceilmg i -c Escutcheon AdjuStment Standard Temperature Ratings 'mil ` Nommol Position Spinkier of Escutcheon I1v�v+ 1 5/e Temperature Max. Bub I a1 Tem semm 1 /4' [6.35.1.1] 1i0 Classification Rating Ambient Temp. Color Protrusion Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange y .1 3 [7620.1 Ordinary 155 °F (68 °C) 100 °F (38 °C) Red DM ] 15.7001 -C Intermediate 200 °F (93 °C) 150 °F (66 °C) Green High 286 °F (141 °C) 225 °F(107 °C) Blue Sprinkler can and escutcheon fabricated of brass for better weather resistance in exterior applications Note: The sprinkler can protrudes 1 /4" when escutcheon Sprinkler Guard: Model C -2 is in nominal position. Escutcheon adjustment provides + 1/4" ( +6mm) to -114" ( -32mm) "A" Sprinkler Installation Wrench: dimension adjustment range. Model G3 Sprinkler Wrench Sprinkler Identification Number (SIN): R5314 Model F3 Dry Pendent Recessed Sprinkler "A" Dim. 31/2" b 48" (89mm to 1219mm) in 1 /4" (6mm) naements - .1. - + Inlet Protruson Etevoted ___ - --- - - - - r J = -- d Finishes ' ' Above Inside P � —:--111- Dili- � Sprinkler Escutcheon t ; 4 =-- Air 3 r --j Bronze Brass r Chrome Plated Chrome Plated system ree White Painted White (1) Other finishes and colors are available on special order II 1 NPT Consult factory for details Cup remains unfinished Only the escutcheon will contain desired finish. 2 1/2 o °. - A' Dimension [63.50mm] In Adjustment Range Noie in Ceiing t1/4" Standard Temperature Ratings [t6.35mm] 2 19/64' D1a. Sprinkler Max- [saa4mm] Temperature Ambient Bub Nom,nol Positron Classification Sprinkler Rating Temp- Color of Escutcheon Cup Assembly Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Escutcheon Intermediate 200 °F (93 °C) 150 °F (66°C) Green eel6n I High" 286 °F (141°C) 225 °F (107°C) Blue MIlarlillik "c Sprinkler cup and FP Escutcheon fabricated of steel and 1 /4 [6.35.1.1] - - - - recommended for interior applications Escutcheon Adjustment 1/4' [6.35mm] 3 7/32" Mo. "Listed and Certified only by cULus Escutcheon Adjustment [81 78nm] l/2' [12.70mm) Sprinkler Installation Wrench: rota Adjustment 153eea2 -c Model G3 R/C Sprinkler Wrench Sprinkler Identification Number (SIN): R5314 Note: Do not install the Model F3 Dry Pendent Recessed Sprinkler in ceilings which have positive pressure I in space above. 2. • Model F3 Dry Horizontal Recessed Sidewall Sprinkler "A" Dim. 3' /2" to 48" (89rrun to 1219mm) in 1 /4" (6rrmm) ncrernents i Finishes E — cc___ Spriner Escutcheon L kl ' 3/u Bronze Brass Euut°hro^ (367:71c1. 7 Chrome Plated Chrome Plated ' anmg„ti System r« Cup 5 i a - [ 152 4mm]M°+ White Painted White I : ( "Other finishes and colors are available on special order Consult r Mar factory for details \ -- 1 - --- ,----, MI!. ; _.. _ _ fl�� _i "/� Sprinkler's can and FP Escutcheon are fabricated of steel and 4(_F..-21•‘1110111:11 a IIIIiIIIII �' w° recommended for interior applications. =:; '•`- -' -- y ' uo tat t -� -' � IlullllWllll 7 1(2 5 1 smm] Nil olA. I; "o . 2 19 /a4'[Sa.lmmPik [--..1 Standard Temperature Ratings ,/,2 he [,z.rmm, -A" rlmem,°n Eeweon Miuslmenl Sprinkler Max. Bulb $11/1707 • � /s -e Classification Temperature Rating Ambient Temp. Color [.12.7 -01 • Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Intermediate 200 °F (93 °C) 150 °F (66°C) Green High" 286 °F (141 °C) 225 °F (107 °C) Blue ' Listed and Certified only by cULus. Notes: Do not install the Model F3 Dry Horizontal Recessed Sidewall Sprinkler in walls which have positive pressure in their side space. • Recessed Horizontal Sidewall sprinklers are rl nkler Installation Wrench: listed by cULus for installation of min. 4" (100mm) Sprinkler le Installation t Sprinkler Wrench : - to - max. 6" (150mm) below ceiling, and FM p approved for installation of min. 4" (100mm) - to - Sprinkler Identification Number (SIN): R5334 max. 12" (306mm). Technical Data Ordering Information Orifice Size:'h" (15mm) Specify: Thread size: 1" NPT per ANSI B2.1 1. Sprinkler Type (select one): Working Pressure: 175 psi (12 bar) (a) Model F3 Dry Pendent Nominal K Factor - US / (Metric): 5.6 / (80) (b) Model F3 Dry Recessed Pendent Product Description (c) Model F3 Dry Concealed Pendent Reliable Model F3 Dry Sprinklers are standard (d) Model F3 Dry Horizontal sidewall response sprinklers utilizing a durable 5mm frangible (e) Model F3 Dry Recessed Horizontal Sidewall glass bulb. Model F3 Dry Sprinklers are intended for use 2. Sprinkler Temperature Rating. in dry and preaction systems and in areas subjected to freezing temperatures, such as freezers and unheated 3. Sprinkler Finish. portions of buildings. 4. Cover Plate/FP Escutcheon Finish. Environments wherein dry sprinklers are employed 5. Length: "A" Dimension (face of tee to face of ceiling can be corrosive. For this reason, Model F3 Sprinklers or wall) in 'A " (6.4mm) increments. have a special wax fillet placed in the gap between the cup that supports the bulb and the wrenching boss. This Note: wax will not interfere with the operation of the sprinkler, 1. The "A" dimension is based on a nominally gauged and it prevents contaminents from entering the internal pipe thread "make -up" of .600" (15mm) per ANSI portion of the drop nipple. The wax must not be B2.1 [7' /2 threads approximately]. removed. 2. All latin s and p g paintings are decorative and Operation intended for interior use. The glass bulb consists of an accurately controlled 3. Acceptable appearance in conditions such as amount of special fluid hermetically sealed inside a parking garages is generally provided with bronze precisely manufactured glass capsule. When the sprinkler, brass cup and escutcheon for the Model F3 temperature increases sufficiently due to a fire, the bulb Pendent only. shatters allowing operating parts to clear the waterway. This enables the inlet seal to release air or water and subsequently, cause water flow over the deflector in a uniform spray pattern, controlling or extinguishing the fire. 1 4. Model F3 Dry Pendent Concealed Sprinkler "A" Dim. 3%" to 48" (89mm to 1219mm) in 1 /4" (6mm) increments 1 CCP Cover PlatemFinishesm Inlet Protrusion Elevated 7-71:9 r - ` - T ---- T ---- r a: E�' : : :i1T� Above Ina;de ape 1'U , �= _Ai_ Standard Finishes Special Application Finishes Chrome Plated Bright Brass Plated °__ 4 r_'� _� �, 11L = = =' White Black Plated r == ti Black Paint ` = _— system Tee Off White / aj i � Satin Chrome i • NPT t't Utilizes the X" cover plate with %" total adjustment. (2) Other finishes and colors are available on special order '- (63 sam Consult facto for details. A Dimension 111 factory Hole in Ceiling Adjustment Range t 3/16" Standard Temperature Ratings [t4.76mm] 2 19/64' ail. [58.34mm] Sprinider Temperature Cover Plate Max. Ambient Nominal Positron • Classification Rating Temp. Rating Temp. of coverpla :e Cupp As Ordinary 135 °F (57 °C) 135 °F (57 °C) 100 °F (38 °C) 1= j Caverpate Ordinary 155 °F (68 °C) 135 °F (57 °C) 100 °F (38 °C) ced; "�� Assembly nq r� r — Intermediate 200 °F (93 °C) 165 °F (74 °C) 150 °F (66 °C) w o g g r - ccx_y l High' 286 °F (141 °C) 165 °F (74 °C) 150 °F (66 °C) 1 p / Sprinkler cup fabricated of steel and CCP Cover Plate fabricated of Co 3 // e 7 15' Adjustesb ment brass and recommended for interior applications. 3/16 [4.76mm] Coverplate Adjustment 3 * Listed and Certified only by cULus. S/16" 3 3 m ] ° y 3/8" [9.53mm] [ Total Adjustment 15FG03 - Sprinkler Installation Wrench Model G3 R/C Sprinkler Wrench Note: Do not install the Model F3 CCP Pendent Sprinkler Identification Number (SIN): R5314 Concealed Sprinkler in ceilings which have positive pressure in the space above. Model F3 Dry Horizontal Sidewall Sprinkler "A" Dim. 2" to 48" (51 mm to 1219mm) in 1 /4" (6mm) increments Finishes Sprinkler Escutcheon , ,/r [38.10 mm] Bronze Brass Total Adjustme,t - _- •_ - - -_. r 7 r --- - Cc2;n Chrome Plated Chrome Plated ________ __ _ White Painted White I - r - i Lead Plated 13 1_j 1..3_I 4' [101.60mm] Alin Wax Coated 131(4) , 1/4- [31.75mm] 12 1304.S0mmj 4oe Wax Over Lead 131" Fscutcheon Adjustment r h..— 1/4' [635mrr] (1) Other finishes and colors are available on special order. system le 1 NPT Escutch o Adjustment Consult factory for details. r '; ' 2 . [3 ,emm] } a White painted sprinklers will have chrome plated can. - 1 - -- r� l I " 155 °F (68 °C) to 200°F (93 °C) rating only. ' W _ (4) ° a -;: —�- 411 I till III I --- -- --- 1 ----- -- 3' D.a. 212 °F (100 °C) brown wax may be used on 286 F (141 °C) sprinklers IIIiI�III I 1 � [76.z when maximum ceiling temperatures do not exceed 150°F (66 °C). .'= }= _- -_-__ Standard Temperature Ratings r ~ 2 1/8' Dro. r L398j Sprinkl� m W m II 1/4 (6 -35mmj Temperature Max. Ambient t Spnnker con Protrusron Classification Rating Temp. Bulb Color ► A Dimension Adp.slment Norrencl Position Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange moor', Range + 1/4 1,635rnm] of Escutcheon Ordinary 155 °F (68 °C) 100 °F (38 °C) Red rv. a.-C - 1 1/4 [- 31.75mm] Intermediate 200 °F (93 °C) 150 °F (66 °C) Green High 286 °F (141 °C) 225 °F (107 °C) Blue Sprinkler can and escutcheon fabricated of brass for better weather resistance in exterior applications Note: The sprinkler can protrudes 1" when escutcheon Sprinkler Installation Wrench: is in nominal position. Escutcheon adjustment Model G3 Sprinkler Wrench. provides + 1 /4" ( +6mm) to - 1 ( -32mm) "A" dimension adjustment range. 1 Sprinkler Identification Number (SIN): R5334 3. General Installation Instructions Model F3 dry sprinklers must be installed only in -Hk�^ c aw . Y K. standard (ANSI B 16.3 class 150 and ANSI B 16.4 class M'„ i. ,4.a,*. 125) pipe tees even at branch line ends. For these and �` t f a- 7 other fittings including CPVC, the dry sprinkler should be c ", => , installed into a fitting to conform with protrusion into the fitting in accordance with the diagrams. Dry sprinklers z. should not be installed into elbows and into pipe g couplings located on drop nipples to the sprinklers. The P een , "A" dimension of a dry sprinkler, which extends into Ra°G freezers from wet pipe systems, should be selected to c d jeki provide at least 14" (356mm) between the freezer's ix outside wall or ceiling and the wet pipe line. 1. Cut the specified size hole (see illustrations) for the sprinkler in the ceiling directly in line with the tee. 4 2. Apply pipe joint compound to the 1" (25mm) pipe Fig. 1 - G3 R/C Wrench threads and install sprinkler using the Model G3 or • G3 R/C Sprinkler Wrench as specified. 3. Install the Model FP push -on /thread-off escutcheon or CCP cover plate if required. ‘7.4. Note: Installation of the Model F3 Sprinklers in : "" A copper pipe systems is not recommended, as this may reduce the life expectancy of the sprinklers. _ Model F3 Concealed and Recessed Installation Instructions • The Model G3 R/C Wrench (Fig. 1) is designed to ,"pduaua locate on the wrenching pads of the Recessed ' °ac{ ed " sprinkler while centering in the cup. A standard Y/" lC F d A f drive ratchet may be used to drive this wrench. Figures 1 and 2 show sequentially the insertion of the '" wrench. First, the wrench, with its jaws above the sprinkler deflector, is moved laterally until centered with the cup. Then raise the wrench inside the cup Fig. 2 - G3 R/C Wrench until its jaws engage the sprinkler's square wrenching 1 pads (Fig. 3). To remove the wrench, follow this procedure in reverse order. Care should be taken to - k ,,„- avoid striking the deflector with the wrench. _ ~ • Model G3 Wrench Fi 4) is used for installation of fn 4 , "'' " ` Pendent and Horizontal sidewall sprinklers. A , , Maintenance a r The Model F3 Dry Sprinklers should be inspected quarterly and the sprinkler system maintained in ' - accordance with NFPA 25. Do not remove the factory , . r.... " ,# .RL:aiv1 0 applied thermally sensitive wax fillet between the bulb t « ''..".,3.,,,,1 5 supporting cup and the wrenching boss. Do not replace : ,�� r^ „�, this wax with a substitute substance. An Alternate w substance may interfere with proper operation of the ” — sprinkler. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by Fig. 3 - G3 R/C Wrench using a soft brush or gently vacuuming. Remove any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare, sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior ''''' ''*C4-1131i f Filir : 11 : 4:444 , to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize` ' the potential for damage to spnnklers that would cause m ; ' ," . , improper operation or non - operation. " ` '' , Fig. 4 - G3 Wrench 5.