Loading...
Specifications ' ;' Borders Books & Music #167 Tigard, OR 8/5/96 , _ 03q- �C Fire System Specifications Y P 1 Scope: Identify the Fire Alarm System Equipment, installation procedures, signal transmission, Central Station requirements, alarm control zoning, and all related wiring and connections of the Fire Alarm Systems installed. EQUIPMENT SPECIFICATIONS RADIONICS OMEGALARM D9112B ALARM CONTROL AND CENTRAL STATION TRANSMITTER The D9112B is UL listed for commercial fire, both local and central station, and as a commercial fire transmitter. The D91 12B control is approved for commercial fire by Factory Mutual, California Fire Marshal and New York Bureau of Standards and Appeals. RADIONICS D8132 POWER SUPPLY MODULE (If applicable) The UL listed D8132 increases the stand -by time and provides additional power to the 9112 control /communicator. 1 RADIONICS D1255 ALPHA COMMAND MODULE /ANNUNCIATION The command module operates as an arming station for the arming and disarming of the alarm control, as well as a 32 character alpha display annunciation. One annunciator is 1 located at the cash /wrap area and one at the delivery /sort area. WATERFLOW SENSORS AND GATE VALVES All waterflow switches are to be zoned separately for alarm transmission and all gate valve tamper switches are to be zoned separately for supervisory signal transmission. ' DS200 PHOTOELECTRIC SMOKE DETECTOR (If applicable) The DS200 is a low current photoelectric smoke detector that is UL listed for supervised fire - 1 alarm systems. DS200 EOL POWER SUPERVISION MODULE The DS200 EOL module is installed to supervise the smoke detector power at the end of each smoke detector circuit. ' FIRE POWER LIMITED PLENUM PROTECTIVE SIGNALING CIRCUIT CABLE (If applicable) The Champlain 18 -4 and Decoran 18 -4 plenum rated cables are UL listed and are used in ., accordance with NEC article 760 applications. NEC marking found on these cables is FPLP. D8125 POPEX The popex is a point of protection expander to be mounted in an 8109 UL fire approved enclosure. The popex allows for zone expansion of the 9112 up to 134 points of protection. 1 1 Borders Books & Music #167 Tigard, OR 8/5/96 D8127U POPITS (If applicable) The Radionics D8127 popit is a transponder that interfaces with the popex module to provide for individual annunciation of all alarm points. 8109 FIRE CONTROL ENCLOSUR ' FM #79 -03167 UL #S1871 -A BG -10 (If applicable) The BG -10 is a UL approved fire pull station. D928 DUAL PHONE LINE SWITCHER The D91 12 control communicator uses the model D928 dual phone line switcher to transmit over a secondary phone line when the primary phone is determined to be inoperative. The D928 periodically checks both the primary and secondary phone lines to determine that the phone lines are functioning. The D928 dual phone line switcher is mounted in a UL approved D8109 enclosure. GENTEX SHG24- 1575 -WR STROBE /SOUNDER AND GENTEX GXS -4- 1575 -WR STROBE (If applicable) UL approved strobe, horn /strobe or horn. RADIONICS D122 DUAL BATTERY HARNESS (If applicable) UL approved interface for use when using two batteries with D91 12 or D8132. ' RADIONICS D192C BELL CIRCUIT SUPERVISION MODULE (If applicable) UL listed module for use with D91 12 control to supervise wiring to remote signaling devices. CHEMETRONICS HEAT /RATE OF RISE DETECTOR The Chemetron 601 & 602 detectors are fixed temperature and rate of rise detectors. 1 1 1 • Borders Books Music #167, Tigard, OR alarm ' 09412 AMt CAL- WULATt01 TABLE _ AC Power ON , AC Pow @CUFF` _ • In Al . rm 1 T - NorFnai Ct irtsiit lllAi nimem Cu rrent Maximum Gcirr_er Motel •. - ' - Eac • • Each Each • Number : :._ Used : . :. _» • Unit . Total.- Unit i Total Umt : Total . _ D9112 • 1 , v2 x Quan. 250 25O X Quan r 250 •r -,500 xQuan 500 01258 - 20xQuan.= : '19x:Quan= 123'xzQuan I 0127 18 x Quan;= _ 14 x Quan 12 x Qua j 45 x Quan I 0 0129 928 1 14 x Q 25 x Quauan. 14 .. - 14 k 45 x-Quan _ 45 n.= 2 x Quan= .I26x Quan= D192Q _ 2 - 15 X Quan.= 30 µ _ _26 x Quan: 52 . 50 x Quart 100 • D1255 . 2 - =104 KQuan.= 208 ° 106 x Quan.= 212 ' =2 X Quan.= 412 D8125 . 1 {_ - - .48 rQuan 48 , 47 X:Quan:= 47 48 xQuan= 48 D8127. 12 - 3 x Quan.= 36 . „ 3 x Quan:= 36 r _4 x Quan.= 48 I 08129 ; 20'.x Quan. = . 2.0 x Q = : 20 x Quan;.+ 10')5 14irelal+s= - D8130 - , 1 5'x Quan.= 5 - 5 x Quan: = 5 '7 . 54 x,Quan. =; 54 139131y_ 24 x Quan _22 x, Quan = .: 36_5c Chan MOO i2 0 x Quan.= 0 x Quan: 60 x Quan= M805` . _ _0.x Quan:= _ 0 x Quan : = 100 x Quan:= Ratings of other devices in the system which are not shown above: V - DS_250 - 1 _ 3 •x Quan= 3 - 3 x Quan 3 25 x Quan 25 x Quan = x Quan 105x -Quan: . k Quan: x Quan x Qua X {,loan ua u • — x • x" Q an ', _ TOTAL,A,= 594 ; TOTAL 8 = 619 -TOTAL C 1232 m ill * If the column C total exceeds 1900 mA, a D8132 is required to provide an additional 1900 A. (16.2.2) NFPA 72A Local Systems require 24 hours of standby plus 5 minutes of alarm operation at the end of the 24 -hour period. Two batteries must be installed in the D9112 system to meet the basic I standby requirements for an NFPA 72A installation. You must use battery ampere hour (A.H.) calculations to verify compliance with NFPA 72A. The following formula includes the calculation for 5 minutes of alarm operation at the end of the 24 hour period, as well as a 10% contingency factor which I allows for depletion of battery capacity with age. FORMULA FOR NFPA 72A AMPERE HOUR CALCULATION: ( 619 x 24 ) + ( 1232 x 1/12 ) + or -10% = 16.455 Column Hours Column 5 min. Contingnecy Total A.H. ri: B Total C Total Factor Total A.H. requirements must not exceed A.H. capacity of batteries: Two D126 batteries = 14 A.H. (16.2.3) NFPA 72C Remote Station Systems require 60 hours of standby plus 5 minutes of alarm operation at the end of the 60 -hour period. A D8132 Battery Charger Module with additional batteries installed in a separate D8109 or D8108A enclosure may be required in the D9112 system to meet the basic standby requirements for an NFPA 72C installation. You must use battery ampere hour (A.H.) calculations to verify compliance with NFPA 72C. ® Add one D8132 module, bringing total panel power to 2800 mA and battery capacity to 28 A.H. 1 ❑ Add two D8132 module, bringing total panel power to 4200 mA and battery capacity to 42 A.H. II alarmex 1 L•9112 -030 -190 1 .Power Supply ...: . Primary Power Terminals O ' Primary (AC) Power Circuit A 16.5 VAC, 40 VA internally fused transformer (Radionics model D1640) is the primary ' power source for the D9112. The AC power circuit provides 1.9 Amps of rectified AC power. The panel reserves 500 mA of this power for intemal operations leaving 1.4 Amps for powered devices. 1 Transient suppressors and spark gaps protect the circuit from power surges. This protection relies on the ground connection at terminal 10. Make sure you connect terminal 10 to a proper ground. See Connecting Earth Ground in the Installation section. r AC Power Failure The D9112 indicates an AC power failure when the power at terminals 1 and 2 is missing. The AC FP!! Time program item sets the number of seconds that AC must be missing before the panel acicnowledges the failure and the number of seconds after the power returns before the panel acknowledges the restore] of power. You can program AC Fell 77ate from 1 to 90 seconds. The Radionics default sets AC Fell Time at 5 seconds. Installing the Transformer Do not short the terminals of the transformer. Shorting the terminals opens the intemal fuse causing permanent failure. Connect the transformer to terminals 1 and 2 of the panel before plugging it into the power source. ' Use 18 AWG (minimum) wire to connect the transformer to the panel. Wire length should be kept as short as possible. Maximum length is 50 feet. 1 Connect the battery and then plug In the transformer. Radionics recommends that you always connect the battery first and then plug in the transformer. Instructions for Installing the Battery appear on the next page. 1 Only plug the transformer into an unswitched, 120 VAC, 60 Hz power outlet. Secure the transformer to the outlet with the screw provided. Never share the transformer with other equipment Foreign grounds on the AC input damage the D9112 power circuit. AC wiring can induce both noise and low level voltage into adjacent wiring. Route phone • and sensor loop wiring away from any AC conductors, including the transformer wire. Route data wiring away from AC and phone wiring. 08004 Transformer Enclosure required for fire systems: Use the D8004 Transformer Enclosure for the D1640 transformer in fire and combined fire/burglary applications. 09112 Operation & Installation Manual 7406144 -OOaA 4/93 Page 19 O 1993 Radoracs 1 L -91 12 -030 -200 ' Secondary Power Terminals O U ' Secondary (DC) Power A 12V, 7 Ah sealed lead -acid rechargeable battery ( Radionics D126) supplies secondary power for auxiliary and alarm outputs, and powers the system during interruptions in primary (AC) power. Lead Acid Batteries ONLY: The D9112 charging circuit is only calibrated for lead -acid batteries. Do not use gel -cell or nicad batteries. ,- Extra Batteries Increase Back -up Time: To increase battery back -up time, connect a 1 second 12V. 7 Ah battery in parallel to the first battery to form a 12V, 14 Ah battery. Use a D122 Dual Battery Hamess to ensure proper and safe connection. You can use the D8132 Battery Charger Module to connect two additional batteries for a total of four. See the D9112 Standby Battery and Current Rating Chart in this manual for battery standby time calculations. Installing the Battery 1 Place the battery upright in the base of the enclosure. Locate the red and black leads - supplied in the literature pack. Connect the black battery lead to terminal 4. and then to the negative ( -) side of the battery. Connect the red battery lead to terminal 5, and then to the positive ( +) side of the battery. Warring, High Current Arcs Possible: The positive (red) battery lead and Terminal 5 can create high current arcs if shorted to other terminals or the enclosure. Use caution when working with the positive lead and terminal 5. Always disconnect the positive (red) lead from the-battery before removing it from terminal 5. Replacement Radionics recommends battery replacement every 3 to 5 years under normal use. Exceeding the maximum output ratings, or installing the transformer in an outlet that is routinely switched off. causes heavy discharges. Routine heavy discharges can lead to premature battery failure. 08132 boosts battey backup: Adding a D8132 Battery Charger Module supports additional batteries of up to 36 Ah capacity if required. Warning: The transformers for the D9112 and any D8132 modules connected to it must be powered from the same 120 VAC circuit. The D9112 supervises AC power by monitoring the power from the transformer connected to terminals 1 and 2. It cannot supervise the AC power for D8132 modules if their transformers are not plugged into the same AC circuit as the transformer for the panel. Battery Supervision When the battery voltage drops to 13.3 VDC, the yellow Charging Status LED lights. When the battery drops to 12.1 VDC the red Low Battery LED Tights and the panel, 11 programmed for power supervision. transmits a BATTERY LOW report in the Modem II transmission format. It transmits a TROUBLE ZN 9 report in the BFSK format If the battery is missing or shorted, the red Low Battery LED flashes at the same rate as the green Operation Monitor LED. If the panel is programmed for power supervision, it transmits a BATTERY MISSING report in the Modem II transmission format, or TROUBLE ZN 9 report in the BFSK format. D9112 Operation & Installation Manual 74-06144.000 -A 4193 Page 20 o 1993 Radionics 1 ' Battery Batte Supervision (Continued) L-9112-030-210 When battery voltage retums to 13.7 VDC the Low Battery LED goes out. If the panel is programmed for power supervision, it transmits a BATTERY RESTORAL report in the Modem II transmission format or RESTORAL ZN 9 report in the BFSK format. At 13.9 01 VDC the Charging Status LED goes out. Investigate low battery reports right away. If primary (AC) power is off and the discharge continues, the panel becomes inoperative when the battery voltage drops I below 102 VDC. Battery Charging Circuit Float Charge The float voltage for the battery charging circuit is 13.9 VDC at a maximum current of 1.4 Amps. Deduct any continuous Toad for devices connected to the panel from 1.4 Amps to I find the actual current available for charging. Load Shed Relay protects battery: During an AC power loss the battery supplies all power to the security system. If the battery voltage falls below 102 volts during an AC t power loss, a "load shed" relay isolates the battery from the panel and disables the panel. Load shed protects the battery from being damaged by deep discharge. When AC power restores, the load shed relay resets and battery voltage is again available. I Reset or power down required for shorted battery: If the D9112 determines the battery is shorted, it uses the load shed relay to disconnect the battery. You must reset or power down the panel after correcting the problem to reset the'load shed relay and reconnect the battery. I Reset the panel by momentarily placing the reset pin in the disable position. See Figure 3. The red Low Battery LED continues to flash until you reset the panel. A shorted battery condition is created either by a shorted cell inside the battery or by a short on terminals 4 and 5. A shorted battery may generate WATCHDOG RESET reports. Battery Discharge /Recharge Schedule (No AC Power) 0 Discharge Cycle AC OFF AC fail report when AC fails if panel is programmed to report AC failure at occurrence. 13.9 VDC Charging float level 13.8 VDC Charging Status LED on 12.1 VDC Low Battery & AC fail reports if programmed; Low Battery LED on 10.2 VDC Battery Toad shed (processing functions continue if AC is present) Recharge Cycle i AC ON Load shed relay resets, battery charging begins, battery trouble and AC restoral reports sent. 13.7 VDC Battery restoral reports sent, Low Battery LED off 1._. 13.9 VDC Charging Status LED off, battery float charged 1 74-06144 - 000 -A 4193 09112 Operation a Installation Manual Page 21 0 1993 Radionics L -9112- 030 -220 Charging Status and Low Battery LEDs C Charging Status LED (Yellow) The yellow LED shows the charging status r of the battery. Figure 4 shows its location. oft Moo lagnasi L • Yellow LED off e �*«•+� The yellow LED is off when the battery is a .e, sa••r fully charged. LED off when battery is missing, shorted, or reversed: The charging LED is off when the battery is missing. shorted, or reversed. but the red Low ' Battery LED is flashing. • Yellow LED on A steadily lit yellow LED indicates the Figure 4: Charging and Battery LEDs battery float voltage is below 13.8. If AC is present the battery is charging. The yellow LED also comes on when the combined current draw from all outputs exceeds 1.4 Amps. This is normal under alarm conditions for non -fire systems when sirens or bells draw more than 1.4 Amps. If the LED comes on regularly for extended periods or doesn't go out. check the current draw for devices connected to the power outputs. See the Power Outputs section in this manual for instructions. • Yellow LED flashing once per minute The yellow LED normally flashes once per minute as the D9112 checks the battery. • Yellow and red LEDs flashing once per minute The yellow and red LEDs flash on once every minute when current draw for devices connected to the power outputs exceeds 1.4 Amps and the battery is missing. Low Battery LED (Red) The red LED shows the condition of the battery. Figure 4 shows the location of the LED. • Red LED off The red LED is off when the battery is fully charged. When battery voltage drops below 12.1 VDC. the red LED comes on. It goes out when battery voltage reaches 13.7 VDC. • Red LED on A steadily lit red LED indicates battery voltage has fallen below 12.1 VDC. The LED goes out when battery voltage reaches 13.7 VDC. • Red LED flashing (same rate as green LED) The red LED flashes with the green Operation Monitor LED when the battery is missing or shorted. Reset required for shorted battery: If the D9112 detects a shorted battery, the battery remains disconnected and the red Low Battery LED continues to flash until you reset the panel. No missing battery with D192A Using a D192A with a D9112, prevents the D9112 from recognizing a missing battery condition. • Red and yellow LEDs flashing once per minute The yellow and red LEDs flash once every minute when current draw for devices connected to the power outputs exceeds 1.4 Amps and the battery is missing. 09112 Operation & Installation Manual 74-06144.000 -A 4/93 Page 22 0 1993 Radionics I SEP 14 '94 02:42PM DETECTION SYSTEM:= P.2/6 . c 1 - :P ° H 0 T • 0 E: L" ,E . C T •R : #- ..C.:. S:_ M . 0 K . E . ..D E . T. • E.. C T _ O "R -'.:.: Ill 111111 DS250 DS25O eries r.: Photoelectric • . ,v ,,: S moke Detector ,:.. 1 - 4;ii* :, c •:., . : I . FEATURING. -. - > Diagnostic/Sensitivity Test Features > Easy Disassembly for Cleaning > Sensitivity Voltage Output > Interchangeable 2- and 4 -Wire Bases > 12 or 24 VDC Operation 1 > 135 °F Heat Sensor Option _ Description different output configurations provide Th DS2S0 series are low profile, Photo- application flexibility. See Base Seiecti: :� - . -• _ , electric system type. smoke detectors. Guide on next page. S ::1,%':' i1,�• • h ; 1 1 1 } ,, ; : They a separate detector/ powe Requirements 1 " bye design thatpermits use �tiZth both 2 -wire: 8.5 to 33 VDC • :, 4-wire: 10 to 30 . . . 2 -wire and 4 -wire bases. A magnet ac- ,, t VDC ti aged test feature and a voltage output 10 to 30 °ADC, 80 :nitro -amps 12�'DC — provide the ability to confirm proper DS250 . OS75DTN P y p' p 90 micro -amps @.., 4t'DG. U factory calibration, after installation. A unit with a heat sensing thermistor is also available. Neat Sensor Temperature 135 °F (57 °C) Operation Alarm Output The detector has an Alarm reset with The Alarm /Test LED flashes briefly power interruption. of 1 second. Factory every seven seconds to indicate that t. calibrated for nominal 3.2 % /ft. gray detector has power and that the srnok smoke obscuration. sampling circuitry is functioning. The I Mounting LED latches ON in the event of an alar Compatible with 2 -wire cr 4-wire bases. Signal output is dependent on base _ Bases maybe mounted directly to 4- selection. See base selection. guide on 1 inch octagonal electrical boxes, single page 2. gang switch boxes, and wirernold sur- For 2 -wire installation, it is vital that(; face box #5738. Large diameter bases compatibility be verified by consultin I also allow 4" square box mounting. the MB Series installation instruction: Different diameter bases and several 425258 1 Detection Systems, Inc. 130 Perinton Parkway, Fairport, New 'Tbr i r: 144501 Fairport, NY: 8001289 -0096; 716!223.4060; FAX 716/223 -9180 I Hixson, TN: 8001727 -3002; 615/87 Sacramento, CA: 8a 0'444.3106: For Technical Service: 8001374-7454 SET 14 ''?4 v"_1E:43Pi•. DETECTION SYSTEMS P.3/5 =::: D. S 2 ;5 0 �. = S = E .R I E . S :S . P=° E C : I :: F:: /. G.: • A ..sT . / • p p -':::S* - '- ;' =: 1 Storage and Operating Temperature ' Ordering Information . :. :DS250.in. MB2W.Base. - •: +32° to 100°F (0' to 38 °C). 0 to 959 D5250 Detector only (requires a relative humidity (non - condensing). base) - • DS25_0_H __e_ad_. ^ ' �\ . ill High impact fire retardant ABS plastic D,.25� x Detector e' 35 F peat - - - ^ , sensing thermistor�Qgv�w = 'ti _�' 1 .. 73' enclosure and separate twist -lock bases. ,..,.._____ a base) 5.5. �- Test Features To meet the NFPA 72E Sect. 8-3.42 re- EOL200 End -of -Line Supervision DS250 in MB21d(1 Rase quires erts, the 05250 series feature a Module for use with 4-wire unique magnet operation/sensitivity systems test function and a direct voltage meas- it "T ' J:! urement test of the sensitivity. The de- TC2000 Test Cable -.. _ kg ,, d - -. ' , 1.75 • tcctor operation is tested by placing a Protected under one or more of the following ,patents: r ^ ^ - - -- side View — --- ----~• • i magnet to the unit I #339.079 1K. ' ..�a next it t;hich activates . 6.375' _�-� an internal reed switch. If the detector is Other patents pending. ; within its calibrated obscuration range. - - • _ . �� immediately listings r DS250in 1i9B4{�Base . . it ill ��: j ed iatel y si an alarm. if the i 9 Approvals • . - detector is outside of its calibrated ob- -1 DS250 & MB2 & MS4 y I scuration range, the alarm LED will flash i DS250TH Series ' l ' ' l �� ` 1 at different rates to indicate whether the ; f 1 D5250 Head �. I unit is above or below the proper cal- U.L. & �— ` — sin vier, _ – 9. 2.1j5" ' S3019 S3019 iteration. A voltage output is also avail- C -U.L ; y , able., which allows direct reading or the Acceptance# Acceptance# I I' — 6.375' sensitivity level using a standard DVM. NY C ity MEA274 -93 -E MEA274 -93 -E Radio Frequency Interference (RFI) MEA �� °' ll Vol. It I Immunity CSFM #727-1062:108 #7300 - 1062:107 NO alarm or set -up on critical fre- quencies in the range from 26 to 950 - megahertz using a 50 watt transmitter located 1 it (.3rn) from the unit or at- tached wiring. ' ..... . . . . BASE SELECTION GUIDE , • • • • . ..... . Mounts to: f Description Output 1 Diameter 4" octagon single gang wI j1d' 4° square i MB2W 2 -wire 2 -wire 5.5' • MB2WL 2 - wire with large diameter 2 -wire 6.375' • Normally open alarm contact. 1 MB4W 4 -wire Rated i 6 watts. 0.5 Amps a 6.375" 100V DC- Normally open alarm contact �^ I and Form "C'• (NO /C /NC) aux- MB4WA 4 -wire with aux relay iliary contact. 6.375" Contacts rated 62.5 VA. 0.5A @ I 125VAC, 30W, 1.0A @ 30VDC : rresistive loads. Normally open alarm contact — and normally open auxiliary I 4 -wire with N/O contact. MB4WE auxiliary relay and Contacts r.:.,::-. .5VA, 0.5A @ 6.375' • • • . power supervision ! 25V'AC, 30w, i .0A G 30VDC for resistive loads. Built - in N/C power supervision II relay opens on r - :e r loss. PIN 267900 , r (�.1 ^^fi�r�,j .} (^� Fax •612 -943 3SUJ Aug J '9 10 :55 1'. Ul • A D I 0 • I C S R D928 Dual Phone Line Switcher Operation and Installation Instructions Before You Begin The D928 module is used with D9112 and D7212 Control /Communicators. The Control' Communicator must be equipped with firmware revision 2.95 or higher. Use Command 59 to determine the revision currently in use. . Before you install the D928 you should be familiar with the operation and installation manual and the program entry guide for the panel you are installing. . Description The Radionics D9112 and D7212 Control/Communicator panels use the D928 Dual Line Switcher to transmit over a second phone line when the primary phone line is faulte �, The panel monitors the primary line and the D928 monitors the secondary line. If a signal is generated and the panel senses that the primary phone line is bad, then it will attempt to use the secondary phone line to send the message. For further explanation, see the Communication Failure section of the appropriate Operation and Installation manual. It trouble is detected, the panel keeps the faulty phone line in memory. If the primary line is found to be electrically faulty, the D928 switches to the secondary line and reports the fault. With the Modem II format, the panel sends a PHONE LINE FAI message to the D6500. The second line of the reportindicates which phone Ilne is in trouble When using BFSK, the panel sends a TROUBLE z1.1 B for trouble on the primary phone line and a TROUBLE zN C for trouble on the secondary phone line. The D928 uses the primary or secondary phone line to dial a primary, backup, or duplicat phone number. • Ground start systems: You cannot use the D928 on ground start systems for commercial fire applications. CPU Failure Annunciation • L. The 0928 module has a circuit that monitors the panel's CPU (Central Processing Unit) for L proper operation. If the CPU fails, a buzzer on the D928 sounds as does a sounder in 1h1 panel. You cannot reset this 'watchdog" sounder while the CPU is tailed. The D928 onl stops sounding when the panel's CPU returns to normal operation. Status LEDs Four LEDs mounted on the front edge of the 0928 module indicate primary phone lin ' failure, secondary phone line failure, failure to communicate, and AC power status (se Figure 1). When programmed and operating normally, only the green AC power status LE should be lit. D928 installation Manual 74.07040.000 -B 1194 Page 1 © 1994 Radioni Fax :612- 943 - 3809 Hug J,, i! ; . r . . Phone Line Failure LEDs Two yellow phone line status LEDs (one for the primary line, one for the secondary line) light up when phone line voltage drops below 4.5 -7.5 VDC without a corresponding 8 -13 mA increase in current. The panel monitors the faulty telephone line for the programmed interval belore indicating a trouble condition. For more information, see the description of Phone / $upv Time in the Program Entry Guide. I Failure to Communicate LED A yellow LED lights up when the panel goes into communications failure. The LED is cleared when communication restores. AC Power Status LED r The green AC power status LED lights up when the panel is running on AC power. When AC , power is not available, it is not lit. Installation Hardware /Software Compatibility Make sure that the control panel board hardware has part number 04- 05958 -004 printed in the lower right corner. The panel's operating software must be revision 2.95 or higher. . The D928 is not compatible with firmware revision 2.91 or lower or control panel board I hardware revision 04- 05958 -003 or lower. Mounting r The D928 Dual Phone Line Switcher mounts inside the D8103. D8108A and D8109 enclosures. Fasten the module to the inside of the enclosure with the screws provided. When using the D928 with a fire system, it must be mounted inside an enclosure that is UL listed for fire, such as the D8108A or 08109 Enclosure. Wiring 1. The D928 has two flying leads. Connect the green lead to Terminal 1 or 2 on the panel to monitor AC power. 2. Connect the black lead on the D928 to Terminal 10 on the panel. This provides surge protection for the two incoming phone lines. This is also ground reference for the AC LED. .. - Phone Connections - 1 t 1. Plug one end of the ribbon cable provided with the D928 into J4 on'the D928. Plug the .1— other end into J2 (ACCESSORY) on the panel. 2. Plug one end of the D162 (2') phone cord provided with the D928 Into J3 on the D128. Plug the other end into J3 (TELCO) on the panel. i 3. Plug one end of a D161 (8') or D162 (2') p hone cord into J1 on the D128. Plug the other /, J end into the RJ31 X for the primary phone line. 4. Plug one end of a D161 or D162 phone cord into J2 on the D928. Plug the other end into ' the RJ31 X for the secondary phone line. D928 Installation Manual ' 74 - 07040 - 000 - 1/94 Page 2 e 1994 Radionics !, _ , • r&x :!,1.'— J.4.J— :•� ` li .VLi n!,, _ _ • _ 1 . - .. s • - - Programming To use the D928, program Two Phone Lines and Phone Supv Time in the contrpl panel. See the Phone section in the appropriate Program Entry Guide for programming instructions. 1 . CONNECT TO ACCESSORY CONNECTOR (J2) WITH RIBBON CABLE mammal ����N�.IiTifilraiifal tai o II ..� GREEN•TO PHONE JACK TO PRIMARY : X : TERMINAL 1 PHONE LINE • RJ31X BLK - TO TERMINAL 10 �. >::wM�.,'''• � AC POWER PHONE JACK TO SECONDARY .:rr`. LED PHONE LINE • RJ31X w' (GREEN) Iiii;.:7,:7r:-.!.:::.. $ 1 N."--r- PRIMARY PHONE JACK TO FAIL LED Tc'LCO CONNECTOR — (YELLOW) SECONDARY �s GAIL LED (YELLOW) Bu2ZER O -�� • "'• ". `''; COMMUNICATIONS ,,,,,..v.;.... � FAILURE LED y 2- (YELLOW) . 0 1 Figure 1. Phone Cord and Wiring Connections 1 0928 Installation Manual 0 1994 Radiolics 74.07040.000•8 1/94 Page 3 1 r � u( J Specifications Current Required 18 mA • 13.8 VDC Id1e (average) 100 mA @ 13.8 VDC . Maximum (average): 10.2 • 13. VDC Operating Voltage: Status Indicators A sounder annunciates CPU failure. LEDs indicate: • AC power • Primary phone line failure • • Secondary phone line failure • Failure to communicate 1 Wiring Connections phone cords 3 Dual modular connector p 1 Ribbon cable black) 2 Flying leads (green, i'l I • • 1 I 1 1 1 1 . . . . 1 1 • 019g4 Radionic nics All CASU SA 1 I'm The Radionics logo is a registered trademark 111 Radionics, Inc., 1800 Abbott Street Radionics, 1 Park Gate Close, Bradbury '• Stockport, Cheshire, 6K) 4 94 085 ban Radion Customer Service: (800) 538 -5807 Technical Support: (061) 1