Loading...
Plans UA f .0 ?o o( - -vo-13 Form 4a Project Name: OCE IMAGISTICS Page: 1 SYSTEMS - GENERAL Applicability Plans /Specs ��� f, s r � L • Discussion of qualifying Show compliance by inclu r dray rn , isheet;�de ail exceptions on page 4 -25 specification section and subpa agraph. - 1. Applicablity (Section 1317) Is this form required? SEP !.` 2006 o Form Required. Complete form if a new HVAC system is being installed, or components of an existing HVAC system are being replaced (I.e., equipment, controls, ductworl ; "i# ialin u`rat nr,�, BillE ❑ Exception. The building or part of the building qualifies for an exception from HVAC code requirements. Applicable code exception is Section 1317.1. Portions of the building that qualify: Area: Exception ❑ -1 ❑ -2 ❑ -s Area: Exception ❑ -1 ❑ -2 ❑ -3 Area: Exception ❑ -1 ❑ -2 ❑ -s ❑ Form Not Required. This project does not contain work required to comply with code. 2. Simple or Complex Systems (Section 1317.9 or 1317.10) El Simple System. Building contains only Simple HVAC System(s). Complete this form (4a) and equipment efficiency worksheets as required. Form 4b is not required. ❑ Complex System. Project includes a Complex System. Complete this form (4a), form 4b and equipment efficiency worksheets as required. 3. Equipment Performance (Section 1317.5) ❑ No New HVAC Equipment. The building plans do not call for new electrical HVAC equipment, combustion heating equipment, or heat - operated cooling equipment. Complies. All new HVAC equipment have efficiencies not Tess than those required by code. The following equipment efficiency worksheets are attached: 0-4a 0 -4b 0 -4c 0 -4d 0 -4e ❑-4f 0 -49 0 -4h 0 -4i 0 -4 4. Duct Insulation and Sealing (Sections 1317.7 & 1317.8) ❑ No Ducts. The building plans and specifications do not call for new HVAC ducts or plenums. to Complies. The plans and specifications call for all air - handling ducts and plenums to be insulated and sealed as required by Sections 1317.7 &1317.8. 5. Distribution Transformers (Section 1316.1) ❑ No Distribution Transformers. The plans /specs do not call for new distribution transformers. El Complies. All new distribution transformers comply with efficiency, testing, and labeling requirements of Section 1316.1.1. ❑ Exception. The project qualifies for an exception per Section 1316.1.1, Exceptiion: 0 - 1 0 - 2 0 - 4 0 - 1 9 0 Attach relevant documentation for appropriate exception. The plans /specs show compliance in the A,,,14-1%., following locations: 4 -1 April 2005 Compliance with OSSC, effective 01/01/05 Form 4a Project Name: OCE IMAGISTICS Page: 2 SYSTEMS - GENERAL 6. HVAC Controls (Section 1317.4) 6.1 System Thermostat /Zone Controls (Section 1317.4.1) • Complies. All new HVAC systems include at least one temperature control device responding to temperatures within the zones. ❑ Exception. HVAC system qualifies for an exception from zone control requirements. The applicable code exception is Section 1317.4.2, Exception 0-1 0 Portions of the building that qualify: The plans /specs show compliance in the following locations: 6.2 Off - hour Controls - Auto Setback or Shutdown (Section 1317.4.3) O Complies. Systems must have at least one of the following features: ❑ Control Setback Complies. Each system is equipped with automatic control capable of reducing energy through control setback during periods of non -use or alternate use of spaces served. ❑ Equipment Shutdown Complies. Each system is equipped with controls capable of reducing energy use through automatic shutdown during periods of non -use or alternate use of spaces. HVAC systems with equipment shutdown are equipped with at least one of the following: O Programmable controls (1317.4.3.1 (1)) ❑ Occupant sensor (1317.4.3.1 (2)) ❑ Interlocked to a security system (1317.4.3.1 (3)) ❑ Manually activated timers with 2 -hour operation max (1317.4.3.1 (4)) ❑ Exception. The building qualifies for an exception to the requirement for automatic setback or shutdown controls. The applicable code exception is Section 1317.4.3 Exception 0-1 0-2 The plans /specs show compliance in the following locations: 6.3 Control Capabilities (Sec. 1317.4.2.1) • Complies. Zone thermostats are capable of being set to the temperatures described in Sec. 13174.2.1. Where used to control both heating and cooling, zone controls shall be capable of providing a temperature range or deadband of at least 5 degrees F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. ❑ Exception. The building qualifies for an exception to the deadband requirements. The applicable code exception is Section 1317.4.2.1 Exception ❑ -1 0-2 Portions of the building that qualify: The plans /specs show compliance in the following locations: 6.4 Optimum Start Controls (Section 1317.4.3.2) O Complies. Separate HVAC systems have controls capable of varying start-up time of system to just meet temperature set point at time of occupancy. ❑ Exception. HVAC systems have a design supply air capacity not exceeding 10,000 cfm. The plans /specs show compliance in the following locations: 6.5 Heat Pump Controls (Section 1317.4.4) ❑ No Heat Pump. The plans /specs do not call for a new heat pump ❑ Complies. All new heat pumps equipped with supplementary heaters are controlled to minimize the use of supplemental heat as defined in Section 1317.4.4. 74 V The plans /specs show compliance in the following locations: 4 -2 April 2005 Compliance with OSSC, effective 01/01/05 • Form 4a Project Name: OCE IMAGISTICS Page: 3 SYSTEMS - GENERAL 7. Economizer Cooling (Section 1317.3) ❑ No Cooling. The building plans do not call for a new fan system with mechanical cooling. El Complies. Each new fan system has an air economizer capable of modulating outside -air and return -air dampers to provide up to 100 percent of the design supply air as outside air. ❑ Exception At least one new fan system qualifies for an exception. The applicable code exception is Section 1317.3, Exception ❑ -1 ❑ -2 ❑ -3 ❑ -4 ❑ -5 ❑ -e If Exception 3 is selected complete the following: (a) Total cooling capacity of exempt units (Btu /hr) (b) Total installed building cooling capacity (Btu /hr) ❑ Complies. Sum of exempt units rated at less than 54,000 Btu /hr is <240,000 Btu /hr or a/b < 0.10 (10% of total building cooling capacity). Unit Identifier of exempt units: The plans /specs show compliance in the following locations: • 8. Economizer Pressure Relief & Integration (Section 1317.3.1 and 1317.3.2) ❑ No Economizers Required. Project does not contain a new fan system requiring economizers. ❑ Overpressurization Complies. The drawings specifically identify a pressure relief mechanism for each fan system that will relieve the extra air introduced by the economizer. Integration Complies. Economizer is capable of providing partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load. ❑ Exception. The applicable exception is Section 1317.3.2, Exception ❑ -1 ❑ -2 The plans /specs show compliance in the following locations: 9. Hot Gas Bypass (Section 1317.5) No Hot Gas Bypass ❑ Complies. See allowable amount of hot gas bypass as a percentage of total cooling capacity in table below. Unit ID Rated Cooling Capacity Hot Gas Bypass Capacity Allowable Hot Gas Bypass .. �ria�: f ol Rated Cooling Capacity Max Hot Gas Bypass .671 ' <240,000 Btu /hr 50% >240,000 Btu /hr 25% ❑ Exception. Unitary packaged system with cooling capacity no greater than 90,000 Btu /h 4 -3 April 2005 Compliance with OSSC, effective 01/01/05 Form 4a Project Name: OCE IMAGISTICS Page: 4 SYSTEMS - GENERAL 10. Shutoff Dampers (1317.4.3.3) El Not Required. Shutoff dampers are not required on this project. ❑ Complies. Each outdoor air supply & exhaust system shall be equipped with motorized dampers. ❑ Exception. The building qualifies for an exception to the motorized damper requirement. The applicable code exception is Section 1317.4.3.3 Exception ❑ -1 ❑ -2 ❑ -3 ❑ -4 ❑ -5 ❑ -6 The plans /specs show compliance in the following locations: 10.1. Shutoff Damper Controls (Section 1317.4.3.3.1) • Complies. Outdoor air supply and exhaust systems shall be provided dampers that automatically shut when systems or spaces served are not in use or during building warm -up, cooldown, or setback. ❑ Complies. Stair and shaft vents are capable of being automatically closed during normal building operation and interlocked to open as required by fire and smoke detection systems. The plans /specs show compliance in the following locations: 10.2. Motorized Damper Leakage (1317.4.3.3.2) • Complies. Motorized outdoor air supply and exhaust air dampers have a maximum leakage rate of 4 cfm /ft2 at 1.0 in w.g. when tested in accordance with AMCA Standard 500 -1998. ❑ Exception. Packaged HVAC equipment may have maximum leakage rate of 20 cfm /ft at 1.0 in w.g. when tested in accordance with AMCA Standard 500 -1998. The plans /specs show compliance in the following locations: 11. Piping Insulation (Section 1314) ❑ No New Piping. The building plans and specifications do not call for new piping serving a heating or cooling system or part of a circulating service water heating system. o Complies. All new piping serving a heating or cooling system or part of a circulating service water heating system complies with the requirements of the Code, Section 1314.1. O Exception. New piping qualifies for exception: Section 1314.1, Exception ❑ - ❑ - 12. Occupancy Ventilation • Complies. Mechanical ventilation systems provide the required amount of ventilation is indicated in plans /specifications as specified in Chapter 4 of the Oregon Mechanical Specialty Code. ❑ Complies. Natural ventilation systems provide required amount of ventilation as certified by a reg- istered architect or engineer as specified by Section1203.4.1, Exception. Attach worksheet 4m. The plans /specs show compliance in the following locations: The plans /specs show compliance �� on the following pages: tww •. ��Y. ,� 4 -4 April 2005 Compliance with OSSC, effective 01/01/05