Loading...
Plans &a20). Y)(47, hA„ August 22 2003 cm( OF TIGARD OR GON Cascade Fire Protection, Co 24023 NE Shea Lane #110 Wood Village, OR 97060 RE: CONTRACT FURNISHINGS, FIRE SPRINKLER SYSTEM Project Information Building Permit: BUP2003 -00476 Construction Type: VN Tenant Name: Contract Furnishings Occupancy Type: B Address: 14160 SW 72 Avenue Occupant Load: NA Area: NA Stories: 1 Hazard: Ordinary Group I The plan review was performed under the State of Oregon Structural Specialty Code (OSSC) 1998 edition; and the Tualatin Valley Fire & Rescue Ordinance 99 -01 (TVFR99 -01) 1999 edition. The submitted plans are approved subject to the following. 1. A supply of spare sprinklers (never less than 6) shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. These sprinklers shall correspond to the types and temperature ratings of the sprinklers in the property. Standard 9 -1, section 2 -2.7.1 OSSC 2. A special sprinkler wrench shall be provided and kept in the cabinet along with the spare sprinklers to be used in the removal and installation of sprinklers. Standard 9 -1, section 2 -2.7.2 OSSC 3. A minimum of 18 inches shall be maintained between top of storage and ceiling sprinkler deflectors. The distance shall be increased to 36 inches for large drop sprinkler heads. Standard 9 -1, section 4 -4.1.6 and 4 -4.3.2 OSSC 4. Clearances shall be provided around all piping extending through walls, floors, platforms and foundations. Minimum clearance for pipe sizes 1 inch through 3 1 /2 inches shall be not less than 1 inch. Minimum clearance for pipes 4 inches and larger shall be 2 inches. Standard 9 -1, section 4- 5.4.3.4 13125 SW Hall Blvd., Tigard, OR 97223 (503) 639 -4171 TDD (503) 684 -2772 5. Monitoring, Section 904.3.1 OSSC All valves controlling the water supply for automatic sprinkler systems and all water flow monitoring devices shall be electrically monitored where the number of sprinklers are; •. Twenty or more in group I, Divisions 1.1 and 1.2 Occupancies. • One hundred or more in all other occupancies. 6. An approved audible sprinkler flow alarm shall be provided on the exterior of the building in an approved location. An approved audible sprinkler flow alarm to alert the occupants shall be provided in the interior of the building in a normally occupied location. 904.3.2 OSSC Approved Plans: 1 set of approved plans, bearing the City of Tigard approval stamp, shall be inaintained on the jobsite. The plans shall be available to the Building Division inspectors throughout all phases of construction. 106.4.2 OSSC When submitting revised drawings or additional information, please attach a copy of the enclosed City of Tigard, Letter of Transmittal. The letter of transmittal assists the City of Tigard in tracking and processing the documents. • Respectfully, Brian Bla ock, Senior Plans Examiner t qco /Fire & Building Products (E3YTRAL- Customer Service/Sales: Technical Services: Tel: (800) 381 -9312 / Fax: (800) 791 -5500 Tel: (215) 362-0700 / (800) 523-6512 Fax: (215) 362 -5385 Series TY-B — 28, 5.6, and 8.0 ( -factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Qoverage 1 obtained by utilizing the SeriOS TY B ' General Pendent Sprinkler in combinatt with �o:? the Model S2 Shield. Description WARNINGS �i: . ; r ;). The Series TY-B, 2.8, 5.6, and 8.0 The Series TY-B Sprinklers described >: =-• r •R t . . K- factor, Upright and Pendent Sprin- herein must be Installed and main- A 'x ,: kiers described in this data sheet are tained in compliance with th1$ docu- ; x r standard response - standard cover- ment, as well as with the applicable ;,, age, decorative 5 mm glass bulb type standards of the National Flre�Proteo- spray sprinklers designed for use in tion Association, in additions to the tight, ordinary, or extra hazard, com- standards of any other authorities hay- ei , l_. mercial occupancies such as banks, Ing jurisdiction. Failure to do ao may -• - hotels, shopping malls, factories, refln- impair the integrity of these dev/ces. 'Nles, chemical plants, etc. The owner is responsible for maintain- /----. The recessed version of the Series ing their fire protection systemand de- TY-B Pendent Sprinkler; where appli- vices in proper operating cgnditon. w = cable, is Intended for use in areas with The installing contractor or sprinkler t , y� ^, v a finished ceiling. It uses a two-piece manufacturer should be co tacted ° ' '........):\ Style 1011/2 inch NPT) or Style 40 (3/4 relative to any questons. �. inch NPT) Recessed Escutcheon. The c u s' • Recessed Escutcheon provides 1/21'5 inch (12,7 of recessed au m or up to 3/4 l/5 prim ler ro �.. ent or up to 3/4 inch (19,1 mmm o ) of .. total adjustment from the flush pen- ldent /cat 4 � dent position. The adjustment provided by the Recessed Escutcheon reduces 4 the accuracy to which the fixed pipe Numbers drops to the sprinklers must be cut. Corrosion resistant coatings, where TY1151 - Upright 2.8K, 1P2 "NPT Discharge CoefflcieM applicable, are utilized to extend the TY1251 - Pendent 2.8K,1 R "NPT K = 2.8 GPM/psita (40,3 LPM/bar life of copper alloy sprinklers beyond TY3151 - Upright 6.6K,112 "NPT K = 5.6 GPM/psitn (80,6 LPM/bar'n that which would otherwise be ob- TY3251 - Pendent 5.6K,1 2 K = 8.0 GPM/ps1 (115,2 LPM/barrr�) tained when exposed to corrosive at- TY4151 - Upright 8.0K, " Temperature Ratings mospheres. Although corrosion resis- TY4251 - Pendent 8.0K, 4 "NPT er to Table A tant coated sprinklers have passed the TY4851 - Upright 8.0K, 1 "NPT standard corrosion tests of the appli- TY4951 - Pendent 8.0K,1I12 "NPT Finishes cable approval agencies, the testing Is i Sprinkler: Refer to Table A not representative of all possible cor- Technical i Recessed Escutcheon: White Coated,; rosive atmospheres. Consequently, It Chrome Plated, or Brass Plated Is recommended that the end user be Data Physical Characteristics consulted with respect to the suitability Frame Bronze e of these coatings for any given corro- Approvals Button Brass/Copper t sive environment. The effects of ambi- UL and C -UL Listed. Sealing Assembly . . • ent temperature, concentration of FM, LPCB, and NYC Approved. Beryllium Nickel w/Teflont i chemicals, and gas/chemical velocity, (Refer to Table A for complete approval Bulb Glass g should be considered, as a minimum, information including corrosion resis- Compression Screw Bronze along with the corrosive nature of the Pant status.) Deflector Copper chemical to which the sprinklers will be Bushing (K=2.8) Bronze k- exposed. Maximum Working Pressurel 175 psi (12,1 bar) An Intermediate level version of the - Series TY-B Pendent Sprinkler can be } Page 1 of 8 JANUARY, 2003 j TFP1S1 Pogo 2 of 8 TFP151 • /--, I . • ESCUTCHEON 7/16' (11,1 mm) PLATE SEATING ** NOMINAL SOU SURFACE N 2' MAKE -IN DEFLECTOR • 8 ; ',.T, -- A .• :',? 51, -, • 5 2-3/16' (57,2 mm) 1 L ■ (5513/1m6" ,6 mm) 4 . 1-9/16' ' WRENCH roliti ;:iiiiii:79// 3 FLATS (39.7 mm) -- j II _ - _ _ -__ ,■ DEFLECTOR I CROSS PENDENT . UPRIGHT • SECTION .1 - Frame 3 - Sealing s - Bulb e - Deflector • Te rating Is Indicated on deflector or adjacent to 2 - Sutton Assembly 5 - t p uM Ion 7 - B INI orIfio seat on frame. • •• Pi thread connections per ISO 7/1 can be provided on • apes i I request. • FIGURE 1 I STANDARD RESPONSE SERIES � - K ¢ HT '1�CH PE (TY1251) SPRINKLERS NPT 1 • ESCUTCHEON • 7/16' (11,1 mm) STYLE 10 • t PLATE SEATING • 1/2' ** NOMINAL RECESSED 1 • U* / SURFACE NPT MAKE -IN • ESCUTCHEON • i DEFLECTOR ■ 6• T1�7�Tt ■ �_ 7/18' = -� • ��� (11,1 mm) 2-3/18 -- /desk NOMINAL 4 (55,8 mm) } tl"-M- ■ ■ _ MAKE -IN i I .,.�∎ - -- g 2.3118' y•- - .,/ 2 • • (38,1 mm) ' _ - _ _ (55,8 mm) � � . 1 WRENCH . - _° I ..A_ ... -_ : FtAT i i G 1 . • 1 � 1/2' NPT ** SSP DEFLECTOR 2 -7/8' (73,0 mm) DIA. --0 1 PENDENT RECESSED PENDENT . UPRIGHT CROSS SECTION • 1 -Frame 3 - Sealing a - Bulb e - Deflector • Temperature rating is Indicated on deflector or ad)acent.to 2 .- Button Assembly • 5. o preseion • officio seat on frame. *'Pipe thread connections per ISO 7/1 can be provided on spefial request. . FIGURE 2 STANDARD RESPONSE SERIES � - K �UP A H r Y5� PENDENT (TY3251) SPRINKLERS • • • TFPISI Page 3 of 8 ESCUTCHEON 1/2' (12,7 mm) STYLE 40 PLATE SEATING . •* NOMINAL. RECESSED ! SSU" • SURFACE SEATING ,,,,„ MAKE -IN • ESCUTCHEON i DEFLECTOR • • �_ Y. Uri' _ 5 IN ii (12 mm) 2-6/18' 7rtttt e 4 (58,7 mm) 1 ■ = ■ 1 �/ �. 7 N MAKE IN illy / / 2 1 ■1/�■■ 2.1/4' i ' • 1-8/ ITV , I lam` (57,2 mm) (38,7 mm) WRENCH = °= =- % 3 1 . - . FLATS _ _:(_ = 1 //. SSP DEFLECTOR* ' 2-7/8' (73,0 mm) DIA..-� 1 13/4• NPT ** t PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION ! 1 - Frame 3. Sealing 4 - Bulb e - Deflector • Terhperature rating is indicated on deflector or adjacent to 2 - Button • Assem 5 -. Compression 7 - Election p Seat on frame. Screw SPrinli '"Pipe thread connections per ISO 7/1 can be provided on . speclsl request. . . FIGURE 3 1 STANDARD RESPONSE SERIES Y- K U 4�� PENDENT (TY4251) SPRINKLERS . -FACTOR, 314 8.0 ESCUTCHEON 7/16' (11,1 mm) 1 PLATE SEATING 1/2• r• NOMINAL SS* �—.. SURFACE NPT MAKE -IN DEFLECTOR 11 . 7 1 - — T ..'' . 6 � _ s 2-1/4' — 23/,8' (57,2 mm) I 111 j Ub (55,8 mm) 4 WRENCH . .E�■1 i� r , 2 • (39,7 _ = mm) FLATS - -_ I _ 7 i : 3 • 1 SSP DEFLECTOR 1 . CROSS PENDENT UPRIGHT SECTION 1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector • Temperature rating Is Indicated on deflector or adjacent to 2 - Button • Assembly • s - Compression orifgP seat on frame. per ISO 7/1 can be provlded.on . Screw Pi' thread connections pe special request. • FIGURE 4 • STANDARD RESPONSE SERIES TV-B UPRIGHT (TY4851) AND PENDENT (TY4051) SPRINKLERS 8.0 K- FACTOR, 1/2 INCH NPT • • n • . Page 4 of 8 - TFP1S1 n, SPRINKLER FINISH (Else Note 7) K TYPE TEMP. BULB NATURAL I CHROME WHIP" LEAD WAX WAX OVER UQUID BRASS PLATED POLYESTER COATED I COATED LEAD COATED 135 °F /57°C Orange PENDENT ) 2.8 155 °F /68°C Red (TY1251 1, 2, 3 WA 1/2' and 175Ft79°C Yellow NPT UPRIGHT 200°F/93°C Green (T/1151) 286 °F /141 °C Blue 380°F/182 Mauve 1, 2 135'F/57°C Orange t . PENDENT (T 1) 155°F/68°C Red 1,2,3,4,5,6 i 1,2,3,5 1,2,3,5 1, 2, 3, 5 and 175°F/79°C Yellow UPRIGHT 200°F/93°C Green 5.6 (TY3151) 266°F/141 °C Blue 1 ... (1 «. ». 5• • 1/2' I NPT 360 °F /182°C Mauve WA 135 °F /57°C Orange i RECESSED 155°F/68 °C Red N/A PENDENT 1,2,3,5 1,2,5 (TY3281Y 175 °F /79°C Yellow Allure 4 200°F/93 °C Green 135 °F /57°C Orange ! PENDENT 155 °F /68°C Red 1,2,5 1,2,3,5 1,2,5 g 1 ) 175 °F /79°C Yellow 1, 2, 3, 4, 5, 6 8.0 f 3/4' RY41b 286°F/ °C Blue • 1",2", 3", 5" 1", 2", 5" NPT N/A 360 °F/182 °C Mauve 135'F/57 Orange RECESSED 155 °F /68°C Red PENDENT 1, 2, 3, 5 N/A (TY4251) 175 °F /79 °C Yellow I i tagurs 5 200°F/93 Green 135°F/57°C Orange PENDENT 155'F/68°C Red ao 1 . �� 1) 175 °F/T9°C Yellow NIA 1,2,3,6 j NPT UPRIGHT 200°F/93 Green (n4851) 268 °F /141°C Blue 360°F/182°C Mauve NOTES: 1. Usted by Underwriters Laboratories, Inc. (UL). 2. Usted by Underwriters Laboratories, Inc. for use In Canada (C -UL). - 3. Approved by Factory Mutual Research Corporation (FM). 4. Approved by the Loss Prevention Certification Board (LPCB). 5. Approved by the City of New Ybrk under MEA 354-01 -E. 8. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, eriands, Tel. 31-53. 428- 4444/Fax 31- 53.428-3377). 7. Where Polyester Coated, Lead Coated, Wax Coated, and Wax over Lead Coat Sprinlders are noted to be UL and C-UL Usted, the sprinklers are UL and C - UL Usted as Corrosion Resistant Sprinklers. Where Lead Coated, Wax Coated, and Wax over Lead Coated Sprinklers are noted to be FM Approved, the sprinlders are FM Approved as Corrosion Resistant Sprinklers. • Installed with Style 10 (1/2' NPT) or Style 40 (3/4' NPT) 3/4' Total Adjustment Escutcheon, as applicable. " 150 °F /88 °C Maximum Ceuing Temperature. 77' •'• Frame and deflector only. listings and approvals apply to all colors (Special er). WA: Not Available TABLE A LABORATORY LISTINGS AND APPROVALS 1 i TFP161 Page 8 of.8 2 -7/8 DIA. • L 5/801/4" (73,0 mm) 3/4" 19,1 mm • (15,918,4 mm) 2 -1/4° DIA. 1/4° (6,4 mm) RECESS 'A• (END USED FOR FACE OF (57,2 mm) MOUNTING _ VWRENCH 1/2' NPT MODELS) • SPRINKLER PLATE • FITTING • 1/8■ WRENCH RECESS � •� (3,2 mm) (END'S' USED FOR _` 1��ii 3/4'NPTMODELS) • e i i FIGURE 7 ��� �� W -TYPE 8 SPRINKLER 6 J , WRENCH MOUNTING • , SURFACE - 44. . WRENCH SERIES 1 -1/4° (31,8 mm) � RECESS. • CLOSURE TY-B 314■ (19,1 mm) FIGURE 5 • SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBL)'I � q ' WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT / lJ • STYLE 10 RECESSED ESCUTCHEON ; `... 5.8 K- FACTOR, 1/2 INCH NPT i PUSH WRENCH • INTO ENSURE 2 -7/8" DIA. ENGAGEMENT • ! WITH SPRINKLER � (73,0 mm) � — 3/4° 19,1 m 5/8:1/4' WRENCHING AREA (15,908,4 mm) 2 -1/4 ° DIA 1/4' (8,4 mm) FIGURE 8 _. " FACE OF (572 mm) MOUNTING W n'PE 7 RECESSED • SPRINKLER PLATE SPRINKLER WRENCH FITTING 1/8° (3,2 mm) � _ •� / 1 Operation • • �� j �- Th lass Bulb Contains a fluid which • , expands when exposed to heat. When • MOUNTING the rated temperature is reached, the SURFACE fluid expands sufficiently to shatter the glass Bulb, allowing the sprinkler to CLOSURE SERIES 1 -5/18° (33,3 mm • activate and water to flow: • TY-B B . 13/18' (20,8 mm) FIGURE 8 Criteria • SERIES TY-8 RECESSED PENDENT SPRINKLER ASSEMBLY The S TY-B Pendent and Upright WITH TWO -PIECE 3/4 INCH TOTAL ADJUSTMENT Sprinklers e Series eri are intended for fire and p Upright STYLE 40 RECESSED ESCUTCHEON ? bon systems designed re accordance a0 K- FACTOR, 3/4 INCH NPT with the standard Installation rules rec- ognized by the applicable Listing or Approval agency (e.g., UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM's Loss Prevention • Data Sheets). Only the Style 10 or 40 Recessed Escutcheon, as applicable, i is to be used for recessed pendent installations. . • . • Page of 8 TFP151 Q ing the wax coating Before ]wrench stalled or the finish coat has been.ap- i��l��a�ll�h tightening the sprinkler, the jaws of the plied, slide on the Style 10 or 40 Coo- wrench are to be adjusted to just con- sure over the Series TY B Sprinkler The Series TY B Sprinklers must be • tact the sprinkler wrench fiats.' After and push the Closure over the Mount - installed in accordance with the follow- wrench tightening the sprinkler, loosen ing Plate until its flange comes in con- ing instructions: the wrench jaws before removing the tact with the ceiling. wrench. NOTES After Installation, the sprinkler Tarench Do not Install any bulb type sprinkler if (repaired) whenever (ra r t n re n- p arms must; be m and a frame i the bulb is cracked or there is a loss of flats a d fra the a wax coating I n- Squid from the bulb. With the sprinkler - held horizontally, a small alr bubble touched t o has been damaged and r t oat should b nt. The erof the 1e exposed. The wax coating Ion the air bubble le is /s approximately 1 1/18 Inch. (1,6 mm) for the 135 °F /57°C to 3/32 wrench flats can be retouched by gen- Inch (2,4 mm) for the 380 °F /182 °C tI applying a heated 1/8 inch d ameter temperature ratings. steel rod o the areas of wax th t have been damaged, to smooth it bayck over A leak tight 1/2 inch NPT sprinkler joint areas where bare metal Is exposed. should be obtained with a torque of 7 to 14 ftlbs. (9,5 to 19,0 Nm). A maxi- NOTES } mum of 21 ft lbs. (28,5 Nm) of torque Only retouching of the wax coiling ap- may be used to install sprinklers with plied to the wrench flats and frame 1/2 NPT connections. A. leak tight 3/4 arms Is permitted, and the retouching Inch NPT sprinkler joint should be ob- is to be performed only at thel time of talned with a torque of 10 to 20 ftlbs. the initial sprinkler installation. (13,4 to 28,8 Nm). A maximum of 30 The steel rod should be heated only to to Install tubs. (40 , sprinklers r with torque Ism be used the point at which it can begin] to melt distorts. a Higher le eve els et f t orrqq a con- ue may the wax, and appropriate precautions sprinkler l t torque need to be taken, when handling the leakage or impairment o of the spp rinkler. t and cause heated rod, In order to prevent the lea the p mef installer from being bumed. 1 Do not attempt !make -up for inset- if attempts to retouch the wax !coating clent adjustment in the escutcheon with complete coverage are unsuc- s prin by under- or over-tightening the cessful, additional wax can be prdered sprinkler. Readjust the position of the in the form of a wax stick (the end of sprinkler fitting to suit which is color coded). Only the correct The Series TY-B Pendent and Up- color coded wax is to be usd, and • right Sprinklere must be installed In retouching of wrench flats and frame accordance with the following Instruc- arms Is only permitted at the time of torts. initial sprinkler Installation. ith the • Step 1. Pendent sprinklers are to be steel rod heated as prevlo48ly de- installed in the pendent position. and scribed, touch the rod to the area re- upright sprinklers are to be installed in gulling additional wax with the rod an- the upright position. glad downward, and then torch the wax stick to the rod approximately Step 2. plied to the threads, hand tighten gulling irfng inch The wax area melt the sprinkler Into the sprinkler fitting. and run down onto the sprinkler. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W -type The Series TY-5 Recessed pendent 6 Sprinkler. Wrench (Ref. Figure 7), Sprinklers must be installs ' in ac- except that an 8 or 10 Inch adjustable cordance with the following instruc - Crescent wrench is to be used for lions. i I coated sprinklers. With reference to A. After installing the Stile 10 or Sprinkler Wrench 1, 2 n 3, and 4 ch or a t dj type e 40 Mounting Plate, as applicable, over Crescent wrench, as applicable Is e e enp the sprinkler threads and with pipe p adjustable to thread sealant applied to the pipe be applied to the wrench flats. threads, hand tighten the sprinkler Into When installing wax coated sprinklers the sprinkler fitting. with the adjustable Crescent wrench, p B. Tighten the sprinkler into the additional care needs to be exercised sprinkler fitting using only thel W -Type to prevent damage to the wax coating 7 Recessed Sprinkler Wrench (Ref. on the sprinkler wrench flats or frame Figure 8). With reference to Figure 3 or arms and, consequently, exposure of 4, the W -Type 7 Recessed Sprinkler bare metal to the corrosive erniron- Wrench is to be applied to the sprinkler ment. The jaws of the wrench should wrench flats. be opened sufficiently wide to pass l n in- over the wrench flats without damag- Step C. After the ceilin g has been . i ' TFP181 I Page T of 8 addition to the standards of arty' other p 3 Care and authorities having )urisdiction The in- L /fl stalling contractor or sprinkler menu- Warranty Maintenance facturer should be contacted relative to any questions. j The Series TY B Sprinklers must be Products manufactured by co Fire maintained and serviced in accord- it Is recommended that automatic . Products are warranted sole to the ance with the following instructions: sprinkler systems be Inspected, .original Buyer for ten (10 years tested, and maintained by a qualified against defects in material and work- NOTES Inspection Service. j manship when paid for and properly Before closing a fire protection system f installed and maintained under normal main control valve for maintenance use and service. This warranty will ex- work . on the fire protection system that I pire ten (10) years from date of ship - ft controls, permission to shutdown the ment by Tyco Fire Products. No war- affected fire protection system must be ranty is given for products or obtained from the proper authorities components manufactured by compa- ring all personnel who maybe affected nies not affiliated by ownership with by this action must be notified.. Tyco Fire Products or for roducts and Absence of an escutcheon, which is j components which have been subject to misuse, Improper installation, corro- used to cover a clearance hole, may the time to sprinkler ration in sion, or which have not been installed, delay sP operation maintained, modified or repaired in ac- a fire situation. cordance with applicable Standards of Sprinklers that are found to be leaking i the National Fire Protection Associa- or exhibiting visible signs of corrosion l tion, and/or the standards of any other must be replaced. Authorities Having Jurisdiction. Mate - rials found by Tyco Fire Products to. be Automatic sprinklers must never be , coated or otherwise.. defective shall be either repaired or painted, plated, replaced, at Tyco Fire Products' sole altered after leaving the factory. Modi- option. Tyco Are Products neither as- fled sprinklers must be replaced. i sumes, nor authorizes any person to Sprinklers that have been exposed to assume for it, any other obligation in corrosiv products of combustion, but connection with the sale of products or have not operated, should be replaced i parts of products. Tyco Fire Products If they cannot be completely cleaned shall not be responsible for sprinkler by wiping the sprinkler with a cloth or system design errors or inaccurate or by brushing It with a soft bristle brush. incomplete information supplied by Care must be exercised to avoid dam- Buyer or Buyer's representatives. age to the sprinklers - before, during, IN NO EVENT SHALL TYCO FIRE • and after installation. Sprinklers dam- PRODUCTS BE LIABLE, IN CON - aged by dropping, striking, wrench j TRACT, TORT, STRICT LIABILITY OR twist/slippage, or the like, must be re- UNDER ANY OTHER LEGAL THE - placed. Also, replace any sprinkler that ORY, FOR INCIDENTAL, INDIRECT, • has a cracked bulb or that has lost SPECIAL OR CONSEQUENTIAL liquid from its bulb. (Ref. Installation i DAMAGES, INCLUDING BUT NOT Section). UMITED TO LABOR CHARGES, RE- Frequent visual inspections are rec- i GARDLESS OF WHETHER TYCO ommended to be Initially performed for • FIRE PRODUCTS WAS INFORMED corrosion resistant coated sprinklers, ; ABOUT THE POSSIBIUTY OF SUCH after the installation has been com- i DAMAGES, AND IN NO EVENT ;Meted, to verify the Integrity of the cor- SHALL TYCO FIRE PRODUCTS' LI- rosion resistant coating. Thereafter, ABILITY EXCEED AN AMOUNT annual inspections per NFPA 25 EQUAL TO THE SALES PRICE. should suffice; however, instead of in- THE F_ ______ a WARRANTY L spading from the floor level, a random MADE IN LIEU OF ANY AND A(,L sampling of close -up visual inspec- ar1HER tES RESS Lions should be made, so as to better determine the exact sprinkler condl F MERCHANTABILITY AND ` FIT- tion and the long term integrity of the /NESS FOR 4 PARTICULAR PUR corrosion resistant coating, as it may NIEL be affected by the corrosive conditions present. The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), In